Appendix 3 Graphic

HIMAP - BCG
HYUNDAI HEAVY INDUSTRIES CO. LTD

BAY CONTROLLER
Appendix A3
Graphics

HEAVY INDUSTRIES CO., LTD.

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

1/42

Appendix 3 Graphic

Version:
File:

31.07.2007 (MO)
HIMAP - BCG_A3_Graphic_E.doc

Firmware:
-

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

CU:
MU:
RU:

1.10 / 31.07.2007
1.10 / 29.06.2005
1.10 / 07.04.2006

2/42

Appendix 3 Graphic
Table of content

A3

Graphic selection .........................................................................................................4

A3.1
A3.1.1
A3.1.2
A3.1.3
A3.1.4
A3.1.5

Graphic groups ..............................................................................................................6


Two bus bar sections .................................................................................................... 6
One bus bar sections with a disconnector and circuit breaker.................................... 10
One bus bar sections with a circuit breaker ................................................................ 13
One bus bar sections with separated earthing switch ................................................. 17
Special graphics .......................................................................................................... 21

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

3/42

Appendix 3 Graphic
A3

Graphic selection

On the right side of the LC Display a application graphic is shown. This graphic shows the
single line diagram of the feeder application and the state of the breakers which are in use. The
user has the possibility to select a graphic of switching devices according to the switchboard
design. The device provides a library of graphics. Via parameter [0107] the graphic for the LC
display will be selected (MENU: SETTING > SYSTEM > GENERAL PARAMETER >
[0107] GRAPHIC TYPE SELECT). The graphic library is separated into five graphic groups.
Graphics with:

Two bus bar sections


One bus bar and disconnecting switch
One bus bar without disconnecting switch
One bus bar section with separated earthing switch
Special graphics

The state of the breakers within the graphic will be controlled by their feedback signals. This
feedback signals (or auxiliary contacts of the breaker) can be assigned to the function inputs
via the general parameters [0113] to [0151] (MENU: SETTING > SYSTEM > GENERAL
PARAMETER > [0113] to [0151] BREAKER1-3).
At maximum three breakers can be displayed. For a breaker a additional earthing position can
be display. Thus at maximum six breaker elements can be managed.
Table A3-1 shows the selection of graphics which can be used. The first column shows the
graphic group, the second the parameter text of parameter [0107].

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

4/42

Appendix 3 Graphic
Table A3-1

Group
2 Bus bars

1 Bus bar
With a circuit breaker
and a disconnecting
switch.

1 Bus bar
With a circuit breaker

1 Bus bar
With a separate earth
switch (ES)

Special
graphics

Graphic selection

Name
2B Feed-O
2B Feed-I
2B Genera.
2B Motor
2B Transf.
2B Tie 1-2
2B Sect(2)
2B GPT
2B G+2Traf
2B GenTraf
1B DS F-O
1B DS F-I
1B DS Gen
1B DS Mot
1B DS Traf
1B DS GTie
1B DS GTfo
1B DS res1
1B DS res2
1B DS res3
1B Feed.-O
1B Feed.-I
1B Genera.
1B Motor
1B Transf.
1B Measure
1B Tie
1B G.no M.
1B Tfo+Gen
1B G+3Traf
1B ES F-O
1B ES F-I
1B ES Gen
1B ES Mot
1B ES Traf
1B ES two
1B ES 2/1E
1B ES D FO
1B ES D IO
1B ES res.
1B IO+2Gen
1B G+2T+BT
none
Proj.GC100
1B T,Bt,G
1B G,2T,Bt
1B Bt,TGT
1B G,T,I,O
Mehrgeb.11
Mehrgeb.12
Mehrgeb.21
Mehrgeb.22
1B G+BTie
1B TO,Bt,G
1B T,G,FO
1B FO,G,T
1B 2FO,T,G
1B T,G,Bt
Bt,G,T,F-I
1B G.n.M.2
Mehrgeb.13
1B 2T,FO,G
1B Bt,G
1B 2T,Bt,G
1 B 3Break.

HIMAP - BCG

Description
Two bus bar sections and one outgoing feeder
Two bus bar sections and one incoming feeder
Two bus bar sections and one generator
Two bus bar sections and one motor
Two bus bar sections and one transformer
Two bus bar sections and one interconnector
Two bus bar sections and one sectionalizer
Two bus bar sections and two transformer feeder
Two bus bars, one gen. and two transformers
Two bus bars, one gen. and a transformer
One bus bar, one disconnecting switch and one outgoing feeder
One bus bar, one disconnecting switch and one incoming feeder
One bus bar, one disconnecting switch and one generator
One bus bar, one disconnecting switch and one motor
One bus bar, one disconnecting switch and one transformer
One bus, disconnector, circuit breaker, generator, and bustie
One bus, disconnector, circuit breaker, generator, and transformer
Reserved
Reserved
Reserved
One bus bar section and one outgoing feeder
One bus bar section and one incoming feeder
One bus bar section and one generator
One bus bar section and one motor
One bus bar section and one transformer
One bus bar section, one transformer (with fuse) and outgoing feeders, and one bus grounder
One bus bar section and one tie breaker
One bus bar section and one generator (without measure symbols)
One bus bar section, one transformer and one generator
One bus bar section, three transformers and one generator
One bus bar section, one outgoing feeder and separate ES
One bus bar section, one incoming feeder and separate ES
One bus bar section, one generator and separate ES
One bus bar section, one motor and separate ES
One bus bar section, one transformer and separate ES
One bus bar, one incoming feeder and separate ES and a mirrored bus bar
One bus bar, one incoming feeder and a mirrored bus bar with a separate ES
One bus bar, one disconnector, one circuit breaker, one outgoing feeder and a separate ES
Outgoing feeder with trafo, disconnector, earthing switch, circuit breaker, separate ES
Reserved
One bus bar, one outgoing feeder, one incoming feeder and two generators
One bus bar, two transformers, one bustie and one generator
No graphic display (the right LCD side is empty)
One bus bar, 2 separate ES, 3 Breaker, one trafo
One bus bar, 1 trafo, 1 gen, 1 bustie
One bus bar, 2 trafo, 1 gen, 1 bustie
One bus bar, 1 bustie, 2 trafo, 1 gen
One bus bar, one incoming feeder, one outgoing feeder, 1 trafo, 1 gen
3 outgoing feeder, 1 gen
3 incoming feeder, 3 trafos
4 outgoing feeder, 1 gen
4 incoming feeder, 4 trafos
One bus, gen, bustie, and 2 breaker
One Bus, Trafo, Feeder out, Bustie, Gen
One Bus, Trafo, Gen, Feeder out
One Bus, Feeder out, Gen, Trafo
One Bus, 2 Feeder out, Trafo, Gen
One Bus, Trafo, Gen, Bustie
Bustie, Gen, Trafo, Feeder Input
One bus bar section and one generator (without measure symbols)
3 incoming feeder, 3 trafos, 3 circuit breaker, 2 busties
One bus bar, two trafos, one feeder out and one generator
One bus bar, one bustie, one generator
One bus bar, two trafos, one bustie, one generator
One bus and 3 breaker

HIMAP_A3_Graphic_E.doc

5/42

Appendix 3 Graphic
A3.1

Graphic groups

In the following the five graphic groups will be explained. For each graphic group an overview
picture is shown which contains the explanation of all possible graphic elements.
A3.1.1

Two bus bar sections

This graphic group contains graphics with two bus bar sections. All possible graphic elements
of this group will be explained. The overview picture shows the breakers and the
corresponding feedback parameters. The earthing switches can be activated with their
corresponding feedback parameters.

Busbar 1.

1.Breaker
Breaker position:
- open/closed

Busbar 2

B1
B2

0 V
10 kV

2.Breaker .
Breaker position:
- open/closed

Feedback:

Feedback:

- Parameters [0113] & [0114]

- Parameters [0126] & [0127]

1.Breaker
Earthing switch:

2.Breaker .
Earthing switch:

- open/closed/none

- open/closed/none

Feedback:

Feedback:

- Parameters [0121] & [0122]

- Parameters [0134] & [0135]

3.Breaker .
Breaker position:

Operation Mode .

- open/closed

Feedback:

Autom.
Manuall

- Parameters [0139] & [0140]

Localll
Remote

3.Breaker
Earthing switch:
- open/closed/none

Feedback:
- Parameters [0147] & [0148]

This box appears with


device Type BCG & XG
only
Parameter [0086]

Operation Control .
This box appears, if
parameter is set to
Local/Remote
Parameter [0078]

Application Symbol
in use: Feeder

Figure:A3-1

Graphic overview/double bus bar

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

6/42

Appendix 3 Graphic
Figures A3-2 to A3-7 show the possible graphics which can be selected with parameter
[0107].The title of an graphic is the corresponding text of parameter [0107].

Feedback Parameter

1
2
3
4
5

Breaker

Graphic names: 2B Feed.-O,


2B Feed.-I, 2B Genera.,
2B Motor, 2B Transf.
B1
389 V
B2
403 V

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

Control Events

Localj
Remote

1
2
3
4
5

Breaker

Autom.
Manual

Counter Parameter

[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-2

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

Every EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

2B Feed.-O, 2B Feed.-I, 2B Genera., 2B Motor and 2B Transf.

Graphic name: 2B Tie 1-2

Feedback Parameter

389 V
403 V

Breaker

B1
B2

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

Control Events

Breaker

3
Autom.
Manual
Localj
Remote

Figure A3-3

Every Breaker
can be disabled
by setting the
corresponding
ON and OFF
feedback
parameters to
zero.

1
2
3
4
5

The EARTH
switches can
be disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

2B Tie 1-2

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

7/42

Appendix 3 Graphic
Graphic name: 2B Sect(2)
389 V
403 V

B1
B2

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

Control Events
1

Autom.
Manual

Breaker

Localj
Remote

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-4

The EARTH
switches can
be disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

2B Sect (2)

Graphic name: 2B GPT


389 V
403 V

B1
B2

1
2
3
4
5

Notes

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

[0121]
[0134]

[0122]
[0135]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

[0123]
[0136]

[0124]
[0137]

Control Events

Autom.
Manual
Localj
Remote

Breaker

Breaker

Feedback Parameter
ON

1
2
3
4
5

The EARTH
switches can
be disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-5

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

2B GPT

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

8/42

Appendix 3 Graphic

Graphic name: 2B G+2Traf


Breaker

Feedback Parameter

398 V
51.2 Hz
Bus1

Figure A3-6

402 V
50.7 Hz
Bus2

1879 A
Gen.
401 V
49.7 Hz

OFF

[0113]
[0126]
[0139]
[0143]
[0130]

[0114]
[0127]
[0140]
[0144]
[0131]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]
[0133]

116
129
142
145
132

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Control Events

1
2
3
4
5

Autom.
Manual

OUT

IN
-

IN

OUT
-

Every Breaker
can be disabled
by setting the
corresponding
ON and OFF
feedback
parameters to
zero.
PM
(BCG/XG):
CB CLOSED
if Breaker 5
ON.

Counter Parameter
Counts Breaker 1 OFF ON movement
Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

[0158]
[0159]
[0160]
[0161]
[0162]

2B G+2Traf

Graphic name: 2B GenTraf

Feedback Parameter
Breaker

1
2
3
4
5

Localj
Remote

Breaker

Autom.
Manual

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

Control Events

Figure A3-7

IN
-

Breaker

1
2
3
4
5

ON

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

Every Breaker
can be disabled
by setting the
corresponding
ON and OFF
feedback
parameters to
zero.
Every EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

2B GenTraf

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

9/42

Appendix 3 Graphic
A3.1.2

One bus bar sections with a disconnector and circuit breaker

This graphic group contains all one bus bar section graphics with one additional disconnector
switch. All possible graphic elements of this group will be explained. The Figure A3-8 shows
the breakers and the corresponding feedback parameters. The earthing switches can be
activated with their corresponding feedback parameters.

Busbar 1.

1.Breaker
Breaker position:

412 V

- open/closed

Feedback:
- Parameters [0113] & [0114]

1.Breaker
Earthing switch:
- open/closed/none

Feedback:
- Parameters [0121] & [0122]

2.Breaker.
Breaker position:

Operation Mode.

- open/closed

Feedback:

Autom.
Manuall

- Parameters [0126] & [0127]

Localll
Remote

2.Breaker
Earthing switch:
- open/closed/none

Feedback:
- Parameters [0134] & [0135]

This box appears with


device Type BCG & XG
only
Parameter [0086]

Operation Control .
This box appears, if
parameter is set to
Local/Remote
Parameter [0078]

Application Symbol.
in use: Feeder

Figure:A3.8

Single bus bar, two breaker

The figures A3-9 to A3-11 show the possible graphics which can be selected with parameter
[0107]. The title of an graphic is the corresponding text of parameter [0107].

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

10/42

Appendix 3 Graphic

Graphic names: 1B DS F-O,


1B DS F-I, 1B DS Gen,
1B DS Mot, 1B DS Traf

Feedback Parameter

Breaker

389 V
Bus1

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

[0121]
[0134]

[0122]
[0135]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

[0123]
[0136]

[0124]
[0137]

Autom.
Manual
Localj
Remote

Breaker

Control Events

1
2
3
4
5

Every EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.
PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Counter Parameter

[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-9

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

1B DS F-O, 1B DS F-I, 1B DS Gen, 1B DS Mot and 1B DS Traf

Graphic name: 1B DS GTie


389 V
50.7 Hz

Bus2

Breaker

Bus1 402 V
51.2 Hz

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

Control Events
1

1078 A
402 V
51.2 Hz
Gen.

Figure A3-10

Autom.
Manual
Localj
Remote

Breaker

2
1
2
3
4
5

The Breaker
(and EARTH
switches) can
be disabled by
setting the
corresponding
feedback
parameters to
zero.
PM
(BCG/XG):
CB CLOSED
if Breaker 1
and 3 ON.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

1B DS GTie

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

11/42

Appendix 3 Graphic
Graphic name: 1B DS GTfo
389 V
50.7 Hz
Bus1
1

Breaker

Feedback Parameter
1
2
3
4
5

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

1078 A
402 V
51.2 Hz
Gen.

Figure A3-11

402 V
51.2 Hz
Bus2

Breaker

Control Events

Autom.
Manual

Notes

ON

1
2
3
4
5

The Breaker
(and EARTH
switches) can
be disabled by
setting the
corresponding
feedback
parameters to
zero.
PM
(BCG/XG):
CB CLOSED
if Breaker 1
and 3 ON.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

1B DS G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

12/42

Appendix 3 Graphic
A3.1.3

One bus bar sections with a circuit breaker

This graphic group contains all graphics with one bus bar section. All possible graphic
elements of this group will be explained. The figure A3-12 shows the breakers and the
corresponding feedback parameters. The earthing switches can be activated with their
corresponding feedback parameters.

Busbar 1
1.Breaker
Breaker position:

378 V

- open/closed

Feedback:
- Parameters [0113] & [0114]

1.Breaker.
Earthing switch:
- open/closed/none

Feedback:
- Parameters [0121] & [0122]

Operation Mode

Autom.
Manuall
Localll
Remote

This box appears with


device Type BCG & XG
only
Parameter [0086]

Operation Control .
This box appears, if
parameter is set to
Local/Remote
Parameter [0078]

Application Symbol .
in use: Feeder

Figure:A3-12

Single bus bar, one breaker with earth position

Figures A3-13 to A3-18 show the possible graphics which can be selected with parameter
[0107]. The title of an graphic is the corresponding text of parameter [0107].

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

13/42

Appendix 3 Graphic
Graphic names: 1B Feed.-O,
1B Feed.-I, 1B Genera.,
1B Motor, 1B Transf.
389 V
Bus1

Breaker

Feedback Parameter

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

[0121]

[0122]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]

[0116]

[0119]

[0120]

[0123]

[0124]

Control Events

Autom.
Manual
Localj
Remote

Breaker

1
1
2
3
4
5

The EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter

Figure A3-13

[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
-

1B Feed.-O, 1B Feed.-I, 1B Genera., 1B Motor and 1B Transf.

Graphic name: 1B Measure


389 V
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

[0121]

[0122]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]

[0116]

[0119]

[0120]

[0123]

[0124]

Control Events

Autom.
Manual
Localj
Remote

Breaker

1
1
2
3
4
5

The EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
-

Figure A3-14 1B Measure

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

14/42

Appendix 3 Graphic
Graphic name: 1B Tie
389 V
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

[0121]

[0122]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]

[0116]

[0119]

[0120]

[0123]

[0124]

Control Events

Autom.
Manual
Localj
Remote

Breaker

1
1
2
3
4
5

The EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-15

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
-

1B Tie

Graphic name: 1B G.no M.


389 V
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

[0121]

[0122]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]

[0116]

[0119]

[0120]

[0123]

[0124]

Control Events

Autom.
Manual
Localj
Remote

Breaker

1
1
2
3
4
5

The EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter

Figure A3-16

[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
-

1B G.no.M.

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

15/42

Appendix 3 Graphic
Graphic name: 1B Tfo+Gen
389 V
50.7 Hz
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

[0121]
[0134]

[0122]
[0135]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

[0123]
[0136]

[0124]
[0137]

Control Events
1

738 A
402 V
51.2 Hz

402 V
51.2 Hz
Bus2

Gen.

1
2
3
4
5

Counter Parameter

Instead of the Bus2 Frequency a Power display can be


activated with any analog input (type: %).
The actual value is calculated relative to parameter
[0202].

Figure A3-17

Breaker

Autom.
Manual

[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

1B Tfo+Gen

Graphic name: 2B G+3Traf

Feedback Parameter
Breaker

Bus1

398 V/51.2 Hz

1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Control Events
2

G
Bus2

0
0.0

402
49.6

0
0.0

405 U
50.8 f Gen.
1155 I

Autom.
Manual

Figure A3-18

Breaker

The Breaker
(and EARTH
switches) can
be disabled by
setting the
corresponding
feedback
parameters to
zero.
PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

1
2
3
4
5

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

OUT

IN
-

IN

OUT
-

PM
(BCG/XG):
CB CLOSED
if Breaker 4
ON.
The Trafo
measure
(Bus2) displays
can be
activated with
the timer
events
[0887], [0888]
and [0889].

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

2B G+3Traf

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

16/42

Appendix 3 Graphic
A3.1.4

One bus bar sections with separated earthing switch

This graphic group contains all graphics with one bus bar section and one additional earthing
switch. All possible graphic elements of this group will be explained. Figure A3-19 shows the
breakers and the corresponding feedback parameters. For the earthing switch only the ON
feedback is available.

Busbar 1

0 V

1.Breaker
Breaker position:
- open/closed

Feedback:
- Parameters [0113] & [0114]

Operation Mode .
2.Breaker.
Earthing switch:

Autom.
Manual

- open/closed

Local
Remote

Feedback (EARTH ON):


- Parameter [0134]

This box appears with


device Type BCG & XG
only
Parameter [0086]

Operation Control .
This box appears if
parameter is set to
Local/Remote
Parameter [0078]

Application Symbol .
in use: Feeder

Figure:A3-19

Single bus bar, main breaker and earth breaker

The figures A3-20 to A3-24 show the possible graphics which can be selected with parameter
[0107]. The title of an graphic is the corresponding text of parameter [0107].

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

17/42

Appendix 3 Graphic
Graphic names: 1B ES F-O,
1B ES F-I, 1B ES Gen,
1B ES Mot, 1B ES Traf
389 V
Breaker

Bus1

Feedback Parameter

1
2
3
4
5

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0134]

[0114]

[0117]

[0118]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]

[0116]

[0119]

[0120]

E.

OFF
-

OFF

E.
-

Control Events

Localj
Remote

Breaker

Autom.
Manual

Notes

1
2
3
4
5

Counter Parameter

Figure A3-20

[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


-

1B ES F-O,1B ES F-I, 1B ES Gen,1B ES Mot, 1B ES Traf

Graphic name: 1B ES two

Feedback Parameter

Bus1

Breaker

398 V

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0134]
[0139]
[0147]

[0114]

[0117]

[0118]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]

[0116]

[0119]

[0120]

E.

OFF
-

OFF

E.
-

Control Events

Autom.
Manual
4
3

Localj
Remote

Breaker

2
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-21

Counts Breaker 1 OFF ON movement


-

1B ES two

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

18/42

Appendix 3 Graphic

Graphic name: 1B ES 2/1E


398 V
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0139]
[0147]

[0114]

[0117]

[0118]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]

[0116]

[0119]

[0120]

E.

OFF
-

OFF

E.
-

Control Events

Autom.
Manual
3
2

Breaker

Localj
Remote

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-22

Notes

ON

Counts Breaker 1 OFF ON movement


-

1B ES 2/1E

Graphic name: 1B ES D FO
378 V
Bus1
1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0147]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

[0121]
[0134]

[0122]
[0135]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

[0123]
[0136]

[0124]
[0137]

Control Events

Autom.
Manual
Localj
Remote

Breaker

2
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-23

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

1B ES D FO

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

19/42

Appendix 3 Graphic

Graphic name: 1B ES D IO
Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]
[0121]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

Control Events
1

Autom.
Manual
Localj
Remote
3
13.7 kV
Bus1

Figure A3-24

Breaker

2
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

1B ES D IO

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

20/42

Appendix 3 Graphic
A3.1.5

Special graphics

This group contains graphics for special, unusual applications. The figures A3-25 to A3-56
show the graphics which can be selected with parameter [0107].

Graphic name: 1B IO+2Gen


Bus1

417 V/49.7 Hz

Breaker

Feedback Parameter
1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Control Events
2

G
Bus2 378 V
49.6 Hz
Autom.
Manual

Figure A3-25

G
378 V
49.6 Hz
1237 A
Gen.

Breaker

1
2
3
4
5

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Position of
gen. meters:
Breaker 3 if
event [0889]
inactive,
Breaker 4 if
event [0889]
active.

1B IO+2Gen

Breaker

Feedback Parameter

T1

1
2
3
4
5

Autom.
Manual

1237 A
373 V
49.8 Hz
Gen.

Breaker

0 V
0.0 Hz
Bus2

ON

OFF

[0113]
[0126]
[0139]
[0143]
[0130]

[0114]
[0127]
[0140]
[0144]
[0131]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]
[0133]

[0116]
[0129]
[0142]
[0145]
[0132]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Control Events
T2

378 V
49.6 Hz

Figure A3- 26

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Graphic name: 1B G+2T+Bt

OUT

IN
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON and event
[0888] inactive
or Breaker 4
ON and event
[0888] active.

1
2
3
4
5

OUT

IN
-

IN

OUT
-

The Trafo
measure
(Bus2) displays
can be
activated with
the timer
events
[0888] and
[0889].
PM
(BCG/XG):
CB CLOSED
if Breaker 5
ON.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

1B G+2T+Bt

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

21/42

Appendix 3 Graphic
Graphic name: Proj.GC100

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]
[0121]
[0134]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events
4

Autom.
Manual
Localj
Remote

Breaker

5
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-27

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Proj.GC100

Graphic name: 1B T,Bt,G

Feedback Parameter
Bus1

Breaker

377 V

736 kW
427 V
49.7 Hz

1237 A
373 V
49.8 Hz

Gen.

Bus2

Localj Autom.
Remote Manual

1
2
3
4
5

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

E.

OFF
-

OFF

E.
-

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-28

OFF

Control Events

Breaker

1
2
3
4
5

Notes

ON

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.
The Power
display (at
Bus2) can be
activated with
any analog
input (type: %,
the actual
value is
calculated
relative to
parameter
[0202].

1B T,Bt,G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

22/42

Appendix 3 Graphic
Graphic name: 1B G,2T,Bt

Feedback Parameter
Breaker

1
2
3
4
5

5
T1

1
2
3
4
5

Breaker

Autom.
Manual
Localj
Remote

[0113]
[0126]
[0139]
[0143]
[0130]

[0114]
[0127]
[0140]
[0144]
[0131]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]
[0133]

[0116]
[0129]
[0142]
[0145]
[0132]

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 5
ON.

OUT

IN
-

IN

OUT
-

1B G,2T,Bt

Breaker

Feedback Parameter

U: 437
F:50.2
Bus1
Localj
Remote

375
396
50.1 49.8
1237 A
Bus2
Gen.
Autom.
Manual

1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events

Breaker

Figure A3-30

OUT
-

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

raphic name: 1B Bt,TGT

IN
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-29

OFF

Control Events

T2

1237 A
373 V
49.8 Hz

ON

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B.Bt,TGT

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

23/42

Appendix 3 Graphic
Graphic name: 1B G,T,I,O
Breaker

Feedback Parameter

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

Autom.
Manual
Localj
Remote

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 4
ON.

Control Events

Breaker

1
2
3
4
5

ON

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-31

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B G,T,I,O

Graphic name: Mehrgeb.11

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker
1 or 2 or 3 ON.

Autom.
Manual
1237 A
373 V
49.8 Hz

Figure A3-32

Localj
Remote

Breaker

Control Events

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Mehrgeb.11

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

24/42

Appendix 3 Graphic

Graphic name: Mehrgeb.12


Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker
1 or 2 or 3 ON.

Control Events

Localj
Remote

Breaker

Autom.
Manual

Figure A3-33

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Mehrgeb.12

Graphic name: Mehrgeb.21

Breaker

Feedback Parameter
1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]
[0130]

[0114]
[0127]
[0140]
[0144]
[0131]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]
[0133]

[0116]
[0129]
[0142]
[0145]
[0132]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Autom.
Manual
1237 A
373 V
49.8 Hz

Localj
Remote

Breaker

Control Events

1
2
3
4
5

IN

OUT
-

Breaker 5 can
be disabled by
setting the
corresponding
ON and OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-34

OUT

IN
-

PM
(BCG/XG):
CB CLOSED
if Breaker
1 or 2 or 3 or 4
ON.

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

Mehrgeb.21

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

25/42

Appendix 3 Graphic
Graphic name: Mehrgeb.22
Breaker

Feedback Parameter
1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker
1 or 2 or 3 or 4
ON.

Localj
Remote

Figure A3-35

Autom.
Manual

Breaker

Control Events

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Mehrgeb.22

Graphic name: 1B G+BTie


389 V
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

[0121]
[0134]

[0122]
[0135]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

[0123]
[0136]

[0124]
[0137]

Control Events

Breaker

MB

Autom.
Manual

1
2
3
4
5

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-36

The EARTH
switches can
be enabled by
setting the
corresponding
feedback
parameters.

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

1B G+BTie

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

26/42

Appendix 3 Graphic

Graphic name: 1B TO,Bt,G


Bus1

377 V

1
2
3
4
5

Gen.

Localj Autom.
Remote Manual

Breaker

Notes

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events

1237 A
373 V
49.8 Hz

Figure A3-37

Breaker

Feedback Parameter
ON

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B TO,Bt,G

Graphic name: 1B T,G,FO


Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events
2

G
375 V
50.1 Hz
1237 A

437 V
50.2 Hz
Bus2

Gen.

Figure A3-38

Localj
Remote

Breaker

1
2
3
4
5

Counter Parameter
Autom.
Manual

[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B T,G,FO

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

27/42

Appendix 3 Graphic
Graphic name: 1B FO,G,T
Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events
3

G
Localj
Remote

375 V
50.1 Hz
1237 A

437 V
50.2 Hz

Gen.

Autom.
Manual

Figure A3-39

Bus2

Breaker

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B FO,G,T

Graphic name: 1B 2FO,T,G


Breaker

Feedback Parameter

G
U: 405
F:50.1
Bus2

389 Autom.
49.8 Manual
1237 A
Gen.

Figure A3-40

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events

Breaker

1
2
3
4
5

ON

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B 2FO,T,G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

28/42

Appendix 3 Graphic
Graphic name: 1B T,G,Bt
Breaker

Feedback Parameter

Autom.
Manual
Localj
Remote

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events

Breaker

1
2
3
4
5

Notes

ON

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-41

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B T,G,Bt

Graphic name: Bt,G,T,F-I


Breaker

Feedback Parameter

Localj
Remote

G
Autom.
Manual

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-42

OFF

Breaker

1
2
3
4
5

ON

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Bt,G,T,F-I

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

29/42

Appendix 3 Graphic
Graphic name: 1B G.n.M.2
Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

[0121]

[0122]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]

[0116]

[0119]

[0120]

[0123]

[0124]

Control Events

Breaker

1
Autom.
Manual
Localj
Remote

833 A
402 V
50.3 Hz G

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Gen.

Figure A3-43

1
2
3
4
5

The EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
-

1B G.n.M.2

Graphic name: Mehrgeb.13


Breaker

Feedback Parameter

OFF

[0113]
[0126]
[0139]
[0143]
[0130]

[0114]
[0127]
[0140]
[0144]
[0131]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]
[0133]

[0116]
[0129]
[0142]
[0145]
[0132]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Control Events

Breaker

1
2
3
4
5

ON

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
Localj
Remote

Figure A3-44

Autom.
Manual

[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

Mehrgeb.13

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

30/42

Appendix 3 Graphic
Graphic name: 1B 2T,FO,G
Breaker

Feedback Parameter

5
373
49.8

403 V
50.3 Hz

Bus1

Bus2

373 V
49.8 Hz
1237 A
Gen .

Autom.
Manual

Figure A3-45

OFF

[0113]
[0126]
[0139]
[0143]
[0130]

[0114]
[0127]
[0140]
[0144]
[0131]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Control Events

Breaker

1
2
3
4
5

ON

1
2
3
4
5

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]
[0133]

[0116]
[0129]
[0142]
[0145]
[0132]

OUT

IN
-

IN

OUT
-

PM
(BCG/XG):
CB CLOSED
if Breaker 4
ON.
Breaker 3 and
5 can be
disabled by
setting the
corresponding
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

1B 2T,FO,G

Graphic name: 1B Bt,G


Breaker

Feedback Parameter

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]

[0114]
[0127]

[0117]
[0130]

[0118}
[0131]

[0121]
[0134]

[0122]
[0135]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

[0123]
[0136]

[0124]
[0137]

Control Events

Autom.
Manual

Breaker

1
2
3
4
5

The EARTH
switches can
be enabled by
setting the
corresponding
feedback
parameters.
PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-46

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
-

1B Bt,G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

31/42

Appendix 3 Graphic
Graphic name: 1B 2T,Bt,G

Breaker

Feedback Parameter

1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

Control Events

G
373 403 V
49.8 50.3 Hz
Bus1

Figure A3-47

1237 A
373 V
49.8 Hz

Bus2

Gen.

Breaker

Autom.
Manual
1
2
3
4
5

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

OUT

IN
-

IN

OUT
-

PM
(BCG/XG):
CB CLOSED
if Breaker 4
ON.
Breaker 3 can
be disabled by
setting the
corresponding
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B 2T,Bt,G

Graphic name: 1B 3Break.


Breaker

Feedback Parameter

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

[0121]
[0134]
[0147]

[0122]
[0135]
[0148]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

[0123]
[0136]
[0149]

[0124]
[0137]
[0150]

Autom.
Manual
Localj
Remote

Breaker

Control Events

1
2
3
4
5

The EARTH
switches can
be disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-48

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
Counts Breaker 2 OFF ON movement
Counts Breaker 2 OFF EARTH movement
Counts Breaker 3 OFF ON movement

1B 3Break.

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

32/42

Appendix 3 Graphic
Graphic name: 4Br,FI,2FO
Breaker

Feedback Parameter

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

Autom.
Manual

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events

Breaker

1
2
3
4
5

ON

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-49

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

4Br,FI,2FO

Graphic name: 3Br,Bt,G


Breaker

Feedback Parameter

1
2
3
4
5

Breaker

1
2
3
4
5

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-50

OFF

Control Events

Autom.
Manual

ON

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

3Br,Bt,G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

33/42

Appendix 3 Graphic
Graphic name: 2T,G,SV,AV
Breaker

Feedback Parameter

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

G
SV
401
50.1

AV
402
50.2

Bus1

Bus2

Figure A3-51

MOBIL
403 V Gen.
50.3 Hz
Autom.
Manual

Breaker

Control Events

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

2T,G,SV,AV

Graphic name: 2T,G,AV,SV


Breaker

Feedback Parameter

SV
402
50.2

Bus2

Bus1

Figure A3-52

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events

G
AV
401
50.1

OFF

MOBIL
403 V Gen.
50.3 Hz
Autom.
Manual

Breaker

1
2
3
4
5

Notes

ON

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

2T,G,AV,SV

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

34/42

Appendix 3 Graphic
Graphic name: SAB 5173-I

Feedback Parameter

Breaker

Beh.Geb.

1
2
3
4
5

ON

OFF

[0113]

[0114]

[0126]

[0127]

[0139]

[0140]

[0143]

[0144]

[0130]

[0131]

ON

OFF

OFF

ON

[0115]

[0116]

[0128]

[0129]

[0141]

[0142]

[0146]

[0145]

[0133]

[0132]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 5
ON.

Control Events
WW
402 V
50.7 Hz

1879 A
401 V
Gen.
49.7 Hz

Bus2

Autom.
Manual

Breaker

398 V
51.2 Hz
Bus1

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-53

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 5 OFF ON movement
Counts Breaker 3 OFF ON movement

SAB 5173-I

Graphic name: 3Br,Btie,G


Breaker

Feedback Parameter

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Autom.
Manual
Localj
Remote

Breaker

Control Events

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-54

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

3Br,Btie,G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

35/42

Appendix 3 Graphic
Graphic name: 1B G.n.M.E

Feedback Parameter

Bus1
Sa

Breaker

389 V

1
2
3
4
5

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

121

122

ON

OFF

OFF

ON

OUT

IN

IN

OUT

E.

OFF

OFF

E.

[0115]

[0116]

[0119]

[0120]

[0123]

[0124]

Control Events

Sb

Localj
Remote

Sa: the symbol disappears if the Test (OUT) position is reached.


Sb: the symbol appears if the Test (OUT) position is reached, and the E-ON (P121) Feedback
is active.

Breaker

Autom.
Manual

Figure A3-55

1
2
3
4
5

The EARTH
switch can be
disabled by
setting the
corresponding
E-ON and
E-OFF
feedback
parameters to
zero.

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 1 OFF EARTH movement
-

1B G.n.M.E

Graphic name: 1B G,T,FO


Breaker

Feedback Parameter

Notes

ON

1
2
3
4
5

ON

OFF

[0113]

[0114]

[0126]

[0127]

[0139]

[0140]

[0143]

[0144]

[0147]

ON

OFF

OFF

ON

[0115]

[0116]

[0128]

[0129]

[0141]

[0142]

[0146]

[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Control Events

437 V
50.2 Hz
4

1237 A
375 V
50.1 Hz
Gen.

Figure A3-56

Bus1
Autom.
Manual

Breaker

5
1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B G,T,FO

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

36/42

Appendix 3 Graphic

Graphic name: 1B 2Br,2E


Breaker

Feedback Parameter

1
2
3
4
5

ON
113
126
121
134
-

OFF
114
127
-

1
2
3
4
5

ON

OFF
115
128
-

OFF

ON
116
129
-

Breaker

158
159
160
161
162

E-OFF

E.

OFF
-

OFF

E.
-

PM(BCG/XG):
CB CLOSED
if Breaker 1
ON.

OUT

IN
119
132
-

IN

OUT
120
133
-

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
-

1B 2Br,2E

Graphic name: 1B T,Bt

Feedback Parameter
Breaker

Notes

E-ON

Counter Parameter

Localj
Remote

Figure A3-57

OUT
118
131
-

Control Events

IN
117
130
-

1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
-

[0114]
[0127]
-

[0117]
[0130]
-

[0118]
[0131]
-

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Autom.
Manual
Localj
Remote

Breaker

Control Events

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-58

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
-

1B T,Bt

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

37/42

Appendix 3 Graphic

Graphic name: 1B Bt,T


Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Control Events
1

Breaker

Autom.
Manual
Localj
Remote

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-59

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
-

1B Bt,T

Graphic name: 1B Bustie


Bus1
401V

Breaker

Gen.
400V

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]

[0114]

[0117]

[0118]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]

[0116]

[0119]

[0120]

E.

OFF
-

OFF

E.
-

Control Events

Autom.
Manual
Localj
Remote

Breaker

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-60

Counts Breaker 1 OFF ON movement


-

1B Bustie

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

38/42

Appendix 3 Graphic
Graphic name: Bt,FO,G

Feedback Parameter
Breaker

Bus1
402V

1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
-

[0114]
[0127]
[0140]
-

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
-

[0116]
[0129]
[0142]
-

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events
2

Breaker

Autom.
Manual

G
401V
Gen. 50.3Hz
997A

Figure A3-61

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Bt,FO,G

Graphic name: 2*FO,G,Bt


Bus1
402V

Breaker

Feedback Parameter
1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events
2

Autom.
Manual

G
401V
50.3Hz
997A
Gen.

Figure A3-62

Breaker

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

2*FO,G,Bt

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

39/42

Appendix 3 Graphic
Graphic name: Bt,2*FO,G
Breaker

Feedback Parameter

Bus1
402V

1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0143]

[0114]
[0127]
[0140]
[0144]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]
[0146]

[0116]
[0129]
[0142]
[0145]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 4
ON.

Control Events
2

Breaker

Autom.
Manual

G
401V
50.3Hz
997A

Gen.

Figure A3-63

1
2
3
4
5

OUT

IN
-

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 4 OFF ON movement
Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

Bt,2*FO,G

Graphic name: F-I,Btie,G


Breaker

Feedback Parameter

1
2
3
4
5

ON

OFF

[0113]
[0126]
[0139]
[0121]
[0147]

[0114]
[0127]
[0140]

ON

OFF

OFF

ON

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

IN
-

OUT
-

Notes

E-ON

E-OFF

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 3
ON.

Control Events
4
5
1237A
373V
49.8Hz

Autom.
Manual

Breaker

3
1
2
3
4
5

IN

OUT
-

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-64

OUT

IN
-

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

F-I,Btie,G

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

40/42

Appendix 3 Graphic

Graphic name: 1B FO,G,FO


437V / 50.2Hz Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0139]
[0134]

[0114]
[0127]
[0140]

[0117]
[0130]
[0143]

[0118]
[0131]
[0144]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]
[0141]

[0116]
[0129]
[0142]

[0119]
[0132]
[0145]

[0120]
[0133]
[0146]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events
1

Breaker

Autom.
Manual

Figure A3-65

375 V
50.1 Hz Gen.
1237 A

1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
Counts Breaker 3 OFF ON movement

1B FO,G,FO

Graphic name: 1B T+G+2ES


389 V
50.7 Hz
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0121]
[0134]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events
1

402 V 4
51.2 Hz
Bus2

738 A
402 V Gen.
51.2 Hz

Autom.
Manual

Breaker

2
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Figure A3-66

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
-

1B T+G+2ES

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

41/42

Appendix 3 Graphic

Graphic name: 1B G+FI+ES


389 V
50.7 Hz
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0121]
[0134]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 1
ON.

Control Events
1

Autom.
Manual

738 A 4
402 V
51.2 Hz

Figure A3-67

401 V
50.1 Hz
Bus2

Gen.

Breaker

2
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
-

1B G+FI+ES

Graphic name: 1B FI+G+ES


389 V
50.7 Hz
Bus1

Breaker

Feedback Parameter
1
2
3
4
5

Notes

ON

OFF

IN

OUT

E-ON

E-OFF

[0113]
[0126]
[0121]
[0134]

[0114]
[0127]

[0117]
[0130]

[0118]
[0131]

ON

OFF

OFF

ON

OUT

IN

IN

OUT

[0115]
[0128]

[0116]
[0129]

[0119]
[0132]

[0120]
[0133]

E.

OFF
-

OFF

E.
-

PM
(BCG/XG):
CB CLOSED
if Breaker 2
ON.

Control Events
1

Gen.
738 A
402 V
51.2 Hz

3
401 V
50.1 Hz
Bus2

Figure A3-68

Autom.
Manual

Breaker

2
1
2
3
4
5

Counter Parameter
[0158]
[0159]
[0160]
[0161]
[0162]

Counts Breaker 1 OFF ON movement


Counts Breaker 2 OFF ON movement
-

1B FI+G+ES

HIMAP - BCG

HIMAP_A3_Graphic_E.doc

42/42