You are on page 1of 15

Eurocodes Background and Applications

Eurocode example:
Actions on a six storey building

18-20 February 2008

Prepared by:
Kirstine Bak-Kristensen
Svend Ole Hansen

TABLE OF CONTENTS
1.

Introduction .................................................................................................................... 3

2.

Characteristic permanent actions (G) ............................................................................. 4

3.

Characteristic imposed loads (I)..................................................................................... 5

4.

Characteristic wind actions (W) ..................................................................................... 8

5.

Characteristic snow loads (S) ....................................................................................... 11

6.

Combination of actions ................................................................................................ 12

7.

Dimensioning combination of actions - STR ............................................................... 14

8.

Loss of static equilibrium - EQU ................................................................................. 15

Eurocode example actions on a six storey building

18-20 February 2008

1.

Introduction

The present example illustrates the Eurocode actions on a six storey building.
The characteristic actions and design actions on a six storey building are determined. The
support reactions are calculated for the actions considered. These cover permanent actions,
imposed loads, wind actions and snow loads.
The building is indefinitely long and supported per 10 m along the building in the points A
and B. The points A and B shown in figure 1.1 illustrate two points, for which the support
reactions are calculated.
The building includes residential and office areas as shown in figure 1.1. This indicates
that medium Consequence Class CC2 may be assumed, see B3.1 in EN 1990:2002.
The following recommended partial safety factors for permanent actions are applied, see
table A1.2(A) and A.1.2(B) in EN 1990:2002.

EQU: Gj ,sup =1,10 and Gj ,inf =0,90.

STR 6.10a: Gj ,sup =1,35 and Gj ,inf =1,00. Permanent actions only in 6.10a.

STR 6.10b: Gj ,sup =1,15 and Gj ,inf =1,00.

The recommended partial safety factor of 1.5 is applied for all variable actions, see table
A1.2(A) and A.1.2(B) in EN 1990:2002.
The reliability class RC3 with K FI =1,1 is assumed, see B3.3 in EN 1990:2002. The K FI
factor of 1,1 is applied to the partial safety factors of the unfavourable actions.

Figure 1.1 - Six storey building

Eurocode example actions on a six storey building

18-20 February 2008

2.

Characteristic permanent actions (G)

The characteristic permanent actions are assumed as follows:


Distributed loads:

g roof = 1,6 kN/m2


g floor = 2,4 kN/m2

G facade = 2,4 kN/m and 8,0 kN/m

Line loads:

Gwall = 2,4 kN/m

Figure 2.1 - Characteristic permanent action


The above-mentioned permanent actions give the characteristic permanent support
reactions specified in table 2.1.
Table 2.1 - Support reactions from characteristic permanent actions
Vertical support reactions

[kN]

RA [kN]

652

RB [kN]

2356

Eurocode example actions on a six storey building

18-20 February 2008

3.

Characteristic imposed loads (I)

The characteristic imposed uniformly distributed loads q and the load combination factors
0 for residential areas and office areas are as follows:
qres = 2,0 kN/m2

0, res = 0,7
qoff = 3,0 kN/m2

0, off = 0,7
The recommended floor reduction factor A is calculated by:
5
7

A = 0 +

A0
1,0
A

in which 0 is the above-mentioned load combination factor, the area A0 =10,0 m, and A
is the loaded area. For the three cases shown below, the reduced imposed loads are given
in table 3.1 below.
Table 3.1 Reduced imposed loads
Case no.

A qres

A qoff

0,571

1,14

1,71

0,625

1,25

1,88

0,667

1,33

2,00

The recommended multi storey reduction factor n is calculated by:

n =

2 + ( n 2 ) 0
n

in which n is the number of storeys. Inserting the number of storeys gives:

4 ,res =

2 + ( 4 2) 0,7
= 0,85
4

2 ,off =

2 + ( 2 2) 0,7
= 1,0
2

Eurocode example actions on a six storey building

18-20 February 2008

The imposed loads shall be classified as variable free actions, see 2.2 (1)P in EN 1991-11:2002. This gives the relevant load cases shown in figure 3.1, and the support reactions
are given in tables 3.2 and 3.3.
6.2.2 (1) in EN 1991-1-1:2002 specifies: For the design of columns or walls, loaded from
several storeys, the total imposed loads on the floor of each storey should be assumed to
be distributed uniformly. This specification has not been applied in the present example.

Figure 3.1 Distribution of imposed loads


Table 3.2 - Support reactions from reduced imposed loads for residential areas, see table
3.1
Support reactions

Case 1

Case 2

Case 3

RA [kN]

80

200

-120

RB [kN]

560

200

440

Table 3.3 - Support reactions from reduced imposed loads for office areas, see table 3.1
Support reactions

Case 1

Case 2

Case 3

RA [kN]

60

150

-90

RB [kN]

420

150

330

Figure 3.2 illustrates the reduction for multi storey in case 1. The load on the two middle
storeys are reduced by 0, res . The loads on the rest of the storey are unchanged. The
average reduction of the loads are expressed by n .

Eurocode example actions on a six storey building

18-20 February 2008

Figure 3.2 Distribution of imposed loads with reduction for multi storey, case 1

Eurocode example actions on a six storey building

18-20 February 2008

4.

Characteristic wind actions (W)

The indefinitely long facades of the building are assumed to be orientated north-south.

Basic values, see 4.2 in EN 1991-1-4:2005


The fundamental value of the basic wind velocity is assumed to be vb,0 =24 m/s. For
westerly and easterly winds perpendicular to the long facades, the directional factor
2
2
squared has been assumed to be c dir
=1,0 and c dir
=0,8, respectively,

Terrain roughness, see 4.3.2 in EN 1991-1-4:2005


For westerly and easterly winds the upstream terrains are assumed to be a suburban terrain
with a roughness length of z 0 =0,30 m and a lake with a roughness length of z 0 =0,01 m,
respectively.

Wind turbulence and peak velocity pressure, see 4.4-4.5 in EN 1991-1-4:2005


The characteristic peak velocity pressures at building height 22,0 m above terrain are
given in table 4.1 assuming flat terrain. The recommended turbulence factor of k I =1,0 has
been applied.

Table 4.1 The characteristic peak velocity pressure qp.


Wind direction

Directional factor
2
squared c dir

Terrain
category

z0 [m]

Wind from west

1,0

III

0,30

0,2154

0,810

Wind from east

0,8

0,01

0,1698

0,939

kr

qp
[kN/m2]

Pressure coefficients, see 7.2.2 and 7.2.5 in EN 1991-1-4:2005


The pressure coefficients for the wind action are given in figure 4.1.The lack of correlation
of wind pressures between the windward and leeward side has been taken into account by
the recommended procedure, see the note of 7.2.2 (3), giving a reduction factor of 0,87.
Thus, the pressure coefficients for wind loads on the facades become 0,87 0,80 = 0,70
and 0,87 ( 0,53) = 0,46 , respectively.

Eurocode example actions on a six storey building

18-20 February 2008

Figure 4.1 Pressure coefficients for wind actions. Westerly winds.

Eurocode example actions on a six storey building

18-20 February 2008

10

Figure 4.2 Pressure coefficients for wind actions. Easterly winds.


The reactions from characteristic wind actions in table 4.2 are determined for a structural
factor of 1. Thus, it is assumed that the load reducing effect of lack of correlation, in
extension of the above-mentioned correction factor of 0,87, is balanced out by the load
increasing effect from inertial forces originating from structural vibrations.

Table 4.2 Support reactions from characteristic wind loads


Westerly winds

Easterly winds

Reactions

Vertical RA [kN]

-217

-244

-174

-201

261

285

195

219

Vertical RB [kN]

250

252

152

154

-222

-275

-220

-273

Horizontal RV [kN]

-188

-202

-157

-171

218

235

182

198

The recommended reduction factor of 0,w =0,6 is applied, see table A1.1 in EN
1990:2002.

Eurocode example actions on a six storey building

18-20 February 2008

11

5.

Characteristic snow loads (S)

The characteristic value of snow load on the ground is assumed to be sk = 0.9 kN/m.
The shape coefficient for the snow load are given in figure 5 and the reactions for the
characteristic snow load are given in table 5.1.

Figure 5.1 - Snow load shape coefficients


The recommended load combination factor for remainder of CEN Member States, for
sites located at altitude H 1000 m a.s.l. is assumed, i.e. 0 ,S =0,50.

Table 5.1 - Support reactions from characteristic snow loads


Support reactions

Case 1

Case 2

Case 3

RA [kN]

13

-2

20

RB [kN]

88

77

55

Eurocode example actions on a six storey building

18-20 February 2008

12

6.

Combination of actions

Examples of possible load combinations are listed in table 6.1. The following comments
may clarify some of the load combinations:

When the imposed load is an accompanying action, the load combination factor 0 is
applied and not the multi storey reduction factor n , see 3.3.2 (2)P in EN 1991-11:2002.

When the imposed loads act simultaneously with the other variable actions due to
wind and / or snow, the total imposed loads considered in the load case shall be
considered as a single action, see 3.3.1 (2)P in EN 1991-1-1: 2002.

When the imposed loads are the only variable action present, one of the imposed load
categories is dominating and the other is accompanying, see the load combinations
STR (6.10b)-4 and STR (6.10b)-5.

STR load combinations for largest RA and largest RB


STR 6.10b-1: 1,1 1,15 G + 1,1 1,5 res I res + 1,1 1,5 off I off + 1,1 1,5 0, wW + 1,1 1,5 0, s S
STR 6.10b-2: 1,1 1,15 G + 1,1 1,5 W + 1,1 1,5 0, res I res + 1,1 1,5 0, off I off + 1,1 1,5 0, S S
STR 6.10b-3: 1,1 1,15 G + 1,1 1,5 S + 1,1 1,5 0, res I res + 1,1 1,5 0, off I off + 1,1 1,5 0,W W
STR 6.10b-4: 1,1 1,15 G + 1,1 1,5 res I res + 1,1 1,5 0, off I off
STR 6.10b-5: 1,1 1,15 G + 1,1 1,5 off I off + 1,1 1,5 0, res I res
STR 6.10a:

1,1 1,35 G

STR load combinations for smallest RA (permanent action favourable)


STR 6.10b-6: 1,0 G + 1,1 1,5 res I res + 1,1 1,5 off I off + 1,1 1,5 0,W W + 1,1 1,5 0, S S
STR 6.10b-7: 1,0 G + 1,1 1,5 W + 1,1 1,5 0, res I res + 1,1 1,5 0, off I off + 1,1 1,5 0, S S
STR 6.10b-8: 1,0 G + 1,1 1,5 S + 1,1 1,5 0, res I res + 1,1 1,5 0, off I off + 1,1 1,5 0,W W
STR 6.10b-9: 1,0 G + 1,1 1,5 W
STR load combinations for smallest RB (permanent action favourable)
STR 6.10b-10: 1,0 G + 1,1 1,5 W

Eurocode example actions on a six storey building

18-20 February 2008

13

Table 6.1 Design combination factors


G

I res

I off

Dominating
variable
action

STR (6.10b)-1

1,1 1,15

1,1 1,5 0,85

1,1 1,5 1,0

1,1 1,5 0,6

1,1 1,5 0,5

STR (6.10b)-2

1,1 1,15

1,1 1,5 0,7

1,1 1,5 0,7

1,1 1,5

1,1 1,5 0,5

STR (6.10b)-3

1,1 1,15

1,1 1,5 0,7

1,1 1,5 0,7

1,1 1,5 0,6

1,1 1,5

STR (6.10b)-4

1,1 1,15

1,1 1,5 0,85

1,1 1,5 0,7

I res

STR (6.10b)-5

1,1 1,15

1,1 1,5 0,7

1,1 1,5 1,0

I off

STR (6.10b)-6

1,0

1,1 1,5 0,85

1,1 1,5 1,0

1,1 1,5 0,6

1,1 1,5 0,5

STR (6.10b)-7

1,0

1,1 1,5 0,7

1,1 1,5 0,7

1,1 1,5

1,1 1,5 0,5

STR (6.10b)-8

1,0

1,1 1,5 0,7

1,1 1,5 0,7

1,1 1,5 0,6

1,1 1,5

STR (6.10b)-9

1,0

1,1 1,5

1,1 1,35

STR (6.10a)

The design support reactions are given in table 6.2. The largest upward pointing reactions
in points A and B occur for STR (6.10b) - 2 and STR (6.10b) 1, respectively. STR
(6.10b) - 7 gives the smallest reaction in point A of 6 kN. Thus, an anchor in point A is not
needed according to STR.
The dimensioning support reactions are shown bold in table 6.2.

Table 6.2 Design support reactions - STR


RA [kN]

RB [kN]

STR (6.10b)-1

1652

4780

STR (6.10b)-2

1716

4600

STR (6.10b)-3

1545

4507

STR (6.10b)-4

1279

4250

STR (6.10b)-5

1303

4319

STR (6.10b)-6

92

STR (6.10b)-7

STR (6.10b)-8

165

STR (6.10b)-9

250

1902

STR (6.10a)

968

3499

Eurocode example actions on a six storey building

18-20 February 2008

14

7.

Dimensioning combination of actions - STR

Largest RB: (STR (6.10b)-1)

1,1 1,15 G

"+"

1,1 1,5 n I

"+" 1,1 1,5 0, s S

"+"

1,1 1,5 0, w W

Largest RA: (STR (6.10b)-2)

1,1 1,15 G

"+"

1,1 1,5 W

"+"

1,1 1,5 0 , I I "+"

1,1 1,5 0, s S

1,1 1,5 0 , I I "+"

1,1 1,5 0, s S

Smallest RA: (STR (6.10b)-7)

1,0 G

"+"

1,1 1,5 W

Eurocode example actions on a six storey building

"+"

18-20 February 2008

15

8.

Loss of static equilibrium - EQU

The design support reaction in EQU is given in table 8.1.


Table 8.1 Design support reaction - EQU

EQU

RA [kN]

RB [kN]

-153

1,10 Gsup + 0,9 Ginf "+"

1,1 1,5 W

"+"

1,1 1,5 0,i I "+"

1,1 1,5 0, s S

6.4.1 (1)P in EN 1990:2002 specifies:


EQU : Loss of static equilibrium of the structure or any part of it considered as a rigid
body, where:

minor variations in the value or the spatial distribution of actions from a single source
are significant, and

the strengths of construction materials or ground are generally not governing

Is EQU relevant in the present example?


If yes, how should the anchor be designed?
Give STR alone sufficient safety if an anchor is chosen in the first place?

Eurocode example actions on a six storey building

18-20 February 2008

You might also like