INTRODUCTION
 LAND REQUIREMENT:- 1267.3 acres
 CAPACITY :- 3300 MW
 WATER REQUIREMENT :- 9200 cum/hr
 COAL REQUIREMENT:-10 millions/yr
 COAL TRANSPORTATION:- Larger -437 kms

Shorter- 250 kms


THERMAL POWER PLANT
 
Advantages
 The fuel used is quite cheap.
 Less initial cost as compared to other generating plants.
 It can be installed at any place irrespective of the existence of coal.
The coal can be transported to the site of the plant by rail or road.
 It requires less space as compared to Hydro power plants.
 Cost of generation is less than that of diesel power plants.
Disadvantages
 It pollutes the atmosphere due to production of large amount of
smoke and fumes.
 It is costlier in running cost as compared to Hydro electric plants.
 
Detailed process of power generation in a thermal power plant:

 Water intake :- Pond or River


 Boiler heating:- Coal, Oil or Natural gas
 Steam Turbine :- Rotate turbine
 Boiler furnace and steam drum
660 MW TURBINE SPECIFICATIONS :-

 
Rated Turbine Load - 660 MW
 
Number of Turbine Cylinders :-
 HP Turbine – 1
 LP Turbine – 2
 IP Turbine – 1

 
Number of Stages in the Cylinders:-
(a) HPC - 17
(b) LPC - 11x2
(c) IPC - (5x2)x2
Total Number of Stages - 59
 
Heat Rate - 1889 kCal/kWh
CONSTRUCTION POWER (33/11 kV)

 
BRIEF DESCRIPTION OF SWITCHYARD
EQUIPMENTS :-
 
Circuit breakers
Isolators
Surge arrestor
Shunt Reactor
Post Insulators
Earthing
CIRCUIT BREAKER
ISOLATOR
CONTROL & RELAY PANELS
 Bus – Coupler
 Incomer Panel
 Outgoing Panel
 Chargers and Batteries
 AC Distribution Board
 DC Distribution Board
Incomer & Outgoing Panel

 It has the following switches and their readings are as


follows:-
 DC Selector Switch (to select the mode)
 Voltmeter switch (to control voltmeter) 11kV (approx.)
 Ammeter Switch (to control ammeter) 50 A
 Emergency Trip switch (to trip off supply manually)

 It has three relays which are as follows:-


 Definite Time Over Current Relay (for phase over-current
indication)
 Definite Time Over Current Relay (for earth fault indication)
 Master Relay (it supervises all the relays).
 
INCOMER & OUTCOMER READING
Purpose Protection & Metering

Rated Voltage 11 kV

Rated Current 630 A

Phase 3 phase

Insulation Level 12kV/28kV/75kVP

Frequency 50 Hz.

Ratio 300/1 A
Chargers and Batteries

 The charger has 3 meters and 2 isolator switches which are as


follows:-
 
 Meters :-
 
 AC Input Voltmeter 415 volts
 DC Output Voltage 2.75 volts/cell
 DC Output Current 2 A

 Isolator Switches :-

 AC Input Isolator Switch


 Dc Output Isolator Switch.
 
TRANSFORMERS
(33/11 kV & 4 MVA) Transformer
Rated kVA 4000 kVA
Rated kV 33,000 kV (HV)
11,500 kV ()
Rated Line Current 70.0 A (HV)
200.8 A ()
Phase & Connection 3 φ , Dyn ( Primary – Delta )
(Secondary – Star ),(Neutral - Grnd)

Frequency 50 Hz.
Type of cooling ONAN

Ambient Temperature Top Oil = 50 degrees Centigrate


Avg. Winding Temperature = 55 degrees
Centigrate

% Impedance (HV-LV) 7.25


Volume of Oil 2220 litres
WEIGHT
Mass of Oil 5020 kg

Core & Oil 1950 kg

Tank & Fittings 2950 kg

Total Mass 9900 kg

Transportable Mass 8250 kg


COMPONENTS OF A TRANSFORMER :-
 
 Main Tank

 Conservator Tank

 Buchholz Relay

 Breather

 Valves

 Tap Changer

 Drain Valve