Disadvantages of Absorption Refrigeration over Vapor

Compression Refrigeration Cycle


1) Initial capital cost: Though the running cost of the absorption refrigeration system is
much lesser than the vapor compression system, its initial capital cost is much higher.

2) Corrosive nature of lithium bromide: In the lithium bromide absorption refrigeration


system, lithium bromide is corrosive in nature, which reduces the overall life of the
system. In case of the ammonia system, ammonia is corrosive to copper. In the vapor
compression system copper is used with the halocarbon refrigerants and they are quite
safe thus ensuring long life of the refrigeration system. As such the vapor compression
system with reciprocating or centrifugal compressor has longer life than the lithium
bromide absorption refrigeration system.

3) Low working pressures: The working pressures of the absorption refrigeration cycle
are very low. In case of the lithium bromide system these pressures are so low that even
the expansion valve is not required since the drop in pressure of the refrigerant due to its
flow is good enough to produce its expansion. Due to this the refrigeration system should
be sealed thoroughly so that no atmospheric gases would enter the refrigeration system.
As such the system of the compression refrigeration should also be packed tightly, but
this is to prevent the leakage of the refrigerant to the atmosphere.

4) Coefficient of Performance (COP): The coefficient of performance of the absorption


refrigeration systems is very low compared to the vapor compression systems. For
instance, the COP of the two stage lithium bromide system is about 1.1, while that of the
vapor compression system used for the air conditioning applications it is about 4 to 5.
Thus the absorption refrigeration system becomes competitive only if the ratio of the
electricity to fuel (oil, gas or coal used to generate the steam in the boiler) becomes more
than four. If this ratio is lesser there are chances that excess fuel would be required to
generate the steam. However, if there is excess steam in the industry, this ratio may not
be given importance.

5) Higher heat rejection: In the absorption refrigeration heat has to be rejected from
number of parts like condenser, absorber, analyzer, rectifier etc. thus heat rejection factor
for absorption refrigeration system is high and it can be around 2.5. In the compression
refrigeration system the heat is given up only from the condenser, so it heat rejection
factor is small, which is about 1.2. Thus the cooling tower and pump capacities for
pumping the cooling water have to be higher in case of the absorption refrigeration
system, which leads to increase in the running cost of the system.