DADO CORRENTE ALTERNADA


PROCURADO MONOFÁSICO
I x E x cos Ø
KW
1 000
IxE
KVA
1 000
I x E x cos Ø x ef.
CV
746

AMPERES HP x 746
SABENDO HP E x ef. x cos Ø

AMPERES KW x 1 000
SABENDO KW E x cos Ø

AMPERES KVA x 1 000


SABENDO KVA E

QUEDA DE 2 x I x L x cos Ø
TENSÃO KxS

FATOR DE W
POTÊNCIA 2xExI

WATTS
BTU x 0,293071
SABENDO BTU

BTU SABENDO
Watts x 3,14214
WATTS
FÓRMULAS PARA CÁLCULO de CIRCUITOS ELÉTRICOS

DADO CORRENTE ALTERNADA


PROCURADO TRIFÁSICO
1,73 x I x E x cos Ø
KW
1 000
1,73 x I x E
KVA
1 000
1,73 x I x E x cos Ø x ef.
CV
746

AMPERES HP x 746
SABENDO HP 1,73 x E x cos Ø x ef.

AMPERES KW x 1 000
SABENDO KW 1,73 x E x cos Ø

AMPERES KVA x 1 000


SABENDO KVA 1,73 x E

QUEDA DE 1,73 x I x L x cos Ø


TENSÃO KxS
FATOR DE W
POTÊNCIA 1,73 x E x I

DADO CORRENTE
PROCURADO CONTÍNUA

IxE
KW
1 000
IxE
KVA
1 000
I x E x ef.
CV
746

AMPERES HP x 746
SABENDO HP E x ef.

AMPERES KW x 1 000
SABENDO KW E

AMPERES KVA x 1 000


SABENDO KVA E

QUEDA DE
RxI
TENSÃO

FATOR DE
UNITÁRIO
POTÊNCIA

LUX SABENDO
Lum/Pés² x 10,7639
LUMENS

E = Voltagem
I = Amperagem
ef. = % eficiência
cos Ø = fator de potência
S = seção do condutor em mm²
K = coeficiente de condutibilidade
Para o cobre = 56
Para o alumínio = 33
L = comprimento do cabo em metro
R = resistência do cabo em Ohms (W)

Tel.: (11) 3748.1900


DDG: 0800.161333
www.ps.com.br