Lista de Cargas del Sistema POTENCIA TOTAL
Datos generales Alimentación Consumo unitario T. Uso Factor
N° TAG Descripción Ubicación Cant. Tipo Voltios Sist. Valor Unidad FP Eff % Horas Oper. VA W VAR
1 Bomba del SCI SCI 1 AC 480 3 Fases 100 HP 0.95 98 8 1.00 76091.84 72287.24 23759.67
2 Bomba Jockey SCI 1 AC 480 3 Fases 10 HP 0.95 98 8 1.00 7609.18 7228.72 2375.97
3 AC 240 1 Fase 0.2 A 0.00 0.00 0.00 0.00
4 AC 240 1 Fase 333 VA 0.00 0.00 0.00 0.00
5 110 0.00 0.00 0.00 0.00
6 110 0.00 0.00 0.00 0.00
7 110 0.00 0.00 0.00 0.00
8 110 0.00 0.00 0.00 0.00
9 110 0.00 0.00 0.00 0.00
10 110 0.00 0.00 0.00 0.00
11 110 0.00 0.00 0.00 0.00
12 110 0.00 0.00 0.00 0.00
13 110 0.00 0.00 0.00 0.00
14 110 0.00 0.00 0.00 0.00
15 110 0.00 0.00 0.00 0.00
16 110 0.00 0.00 0.00 0.00
17 110 0.00 0.00 0.00 0.00
18 110 0.00 0.00 0.00 0.00
19 110 0.00 0.00 0.00 0.00
20 110 0.00 0.00 0.00 0.00
21 110 0.00 0.00 0.00 0.00
22 110 0.00 0.00 0.00 0.00
23 110 0.00 0.00 0.00 0.00
24 110 0.00 0.00 0.00 0.00
25 110 0.00 0.00 0.00 0.00
26 110 0.00 0.00 0.00 0.00
27 110 0.00 0.00 0.00 0.00
28 110 0.00 0.00 0.00 0.00
29 110 0.00 0.00 0.00 0.00
30 110 0.00 0.00 0.00 0.00
Sub Total 79515.97 26135.64
Proyecto: TOMOPORO TOTAL [VA] 83701.02
Instalación: SCI kVA 83.70
Fecha: 3/20/2009 Reserva 10.00%

Carga Total de Diseño 92.07 kVA


Observaciones / Comentarios
Cálculos Eléctricos Para Motor

Nombre del Proyecto: Fecha


Código: 12/8/2021
Nombre del motor:

Datos del Motor

Tipo de Motor: MOTOR DE INDUCCION


Tipo de alimentación: Trifasico
Clase NEMA: B De propósito general
Tipo de aislamiento NEMA: F 155°C MAX (operación)
Codigo letra rotor bloqueado NEMA:
Potencia:
G 5.6 - 6.29 kVA/HP
100 HP
M
Potencia Activa salida: 74.57 kW (Rotor)
Potencia Activa entrada: 80.18 kW (Alimentación)
Potencia Aparente entrada: 94.33 kVA
Voltaje nominal: 460 V
Frecuencia de alimentación: 60 Hz
Corriente nominal: 118.40 A
Corriente de arranque: 746.16 A (6.3 In)
FP: 0.85
Eff.: 93 %
Factor de Servicio: 1.15
N° de Polos: 4 Cerramiento: TEFC
Velocidad de sincronismo: 1800 RPM
Deslizamiento aprox: 1.27 % Totalmente Cerrado con
Velocidad de operación aprox: 1777 RPM ventilación externa
Frame NEMA: 404T

Corriente a plena carga en base a un motor de: 100 HP con un voltaje de operación de: 460 V la
corriente a plena carga es: 124 A, según CEN 2004

Datos de Alimentador

Factor mult. de corriente: 125 % (CEN 2004 430.22)


Corriente de diseño: 124A X 125% = 155A
Tabla aplicada: 310-16 CEN 2004
Material: COBRE
Voltaje de Operación: 0 - 2000 V 0
Temp. Op.: 90°C
Fact. Temp: 36-40 °C 91% de la capacidad nominal del cable
Calibre: 2/0 AWG/MCM
Capacidad del cable: 177.45 A
Conductores por fase: 1
Cap. Total por fase: 177.45 A
% carga en el cable: 87.35% @155A
% Reserva: 12.65%
Material del ducto: PVC
Resistencia: 0.330 Ohm/kM CEN 2004 Tabla 9 0.00033 Ohm/M
Reactancia: 0.141 Ohm/kM CEN 2004 Tabla 9 0.000141 Ohm/M
Longitud del cable: 180.0 M
Caída de tensión: 2.85 % a corriente nominal
Máxima caída permitida: 5%
Caída durante el arranque: 9.76 % 6 X In (FP=0,2 IEEE Std 399-1997)
Max caída al arranque: 15 %

4/113
Datos de Canalización
Aislante: TTU 90 (XLPE-PVC) 600 V 4
Diametro: 15.68 mm X Conductor 9
Area Total: 579.30 mm2
Diametro de Ducto: 4 Pulgadas 11
Tipo: Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD 10
Diametro: 101.5 mm
Area Total: 8091.37 mm2

Ocupacion: 7.16%

Protección y Arranque

Protección contra cortocircuitos


Tipo: Interruptor automatico de disparo instantaneo
Característica de motor: Polifasico todo proteccion
Ajuste máximo del dispositivo: 800 % la corriente de diseño (CEN 2004 430-152)
Cap. de corriente del dispositivo: 15 A Amperios Frame
Máxima corriente de ajuste: 992.00 A Amperios de disparo
Marca: Cualquiera
Polos: 3
Voltaje Max: 600 V

Contactor Arrancador / Protección contra sobrecarga


Tipo de Arranque: Arranque directo.
Tipo de contactor: No Reversible
Característica: Motores con un factor de servicio no menor a 1,15
Ajuste de corriente según CEN: Articulo 430-32
Factor para ajuste de protección: 125 % In
Máxima corriente de ajuste: 155.00 A Tipo de Contactor
Tamaño del contactor: 3 NEMA AC-3
Voltaje de operación: 460/575 V Cant.
Cap. Del contactor hasta: 50 HP Contactos auxiliares NA 2
Amper-Frame: 90 A Contactos auxiliares NC 2

Sistema de puesta a tierra


Tipo de conductor: Desnudo
Cantidad de conexiones: 2 Puntos
Calibre mínimo: 2 AWG CEN 2004 tabla 250-122

5/113
Gabinete de control / potencia

Área de instalación
Clase: No Clasificada
División: N/A

Gabinete o Tablero
Ubicación: Exterior
Cerramiento: 1 NEMA
Tipo de protección: Para propósitos generales

Capacidad de las barras: 400 A


Instalación: Auto soportado

Otras caracteristicas

✘ Botón de START Comunicación con PLC ✘ TX auxiliar para control

✘ Botón de STOP Comunicación con RTU ✘ Fusibles para sist. control

✘ Selector de operación Calentador interno

Voltímetro Botón paro de emergencia

Amperímetro ✘ Luz indicadora 1 Verde

Pantalla digital ✘ Luz indicadora 2 Roja

Ventilación interna ✘ Luz indicadora 3 Ambar

Notas

V3.14 fm

6/113
460 V
Barra

3(1 X 2/0 AWG/MCM)

Interruptor 15A (AF) / 992A (AT)

460 V

NEMA 3
AC-3
Arrancador 120 V

155A (AT)

Circuito de Control

100 HP
Cálculos Eléctricos Para Transformador

Nombre del Proyecto:


Código: Fecha
Nombre del transformador: 12/8/2021

Datos Eléctricos

Potencia: 75 kVA Clase del transformador :


Tipo de alimentación: Trifasico Transformadores Monofásicos de Distribución Tipo Intemperie/Po
Impedancia base: 3.07 mΩ Enfriamiento: (IEEE C57.93)
Frecuencia: 60 Hz TIPO OA Sumergido en aceite, con enfriamiento
Relación de Trans.: 1:1 natural.

Primario Secundario
Tipo de conexión: Delta Tipo de conexión: Estrella
Hilos: 2 Hilos: 3
Voltaje de línea: 0.48 kV L-L Voltaje de línea: 0.48 kV L-L (480 V)
Voltaje de fase: 0.48 kV Voltaje(s) de fase: 0.277128129 kV
Corriente de línea: 90.21 A kV L-N (0 V)
Corriente de Fase: 52.08 A Corriente de línea: 90.21 A
Conexión del neutro: No tiene Corriente de Fase: 90.21 A
Conexión del neutro: solidamente a tierra

Alimentadores

Primario Secundario
Factor mult. de corriente 125 % Factor mult. de corriente 125 %
Corriente de diseño: 112.76 A Corriente de diseño: 112.76 A
Material: COBRE Material: COBRE
Voltaje de Operación Cable: 5001-35000 V Voltaje de Operación Cable: 0 - 2000 V
Tabla aplicada: Tabla 310.73 CEN 2004 Tabla aplicada: Tabla 310.16 CEN 2004
Calibre 2 AWG / MCM Calibre 1/0 AWG / MCM
Temp. Op. 90°C 0 Temp. Op. 90°C
Fact. Temp 36-40 °C Fact. Temp 36-40 °C
Corriente nominal cable 150 A Corriente nominal cable 154.7 A
Conductores por fase 1 Conductores por fase 1
Cap. Total por fase 150 A Cap. Total por fase 154.7 A
% carga en el cable 75.18% % carga en el cable 72.89%
% Reserva 24.82% % Reserva 27.11%
Calibre del neutro: 4 AWG / MCM Calibre del neutro: 4/0 AWG / MCM 0
Conductores por neutro: 1 Conductores del neutro: 2 0

Datos de canalización

Primario Secundario

Calibre de conductores 2 AWG / MCM Calibre de conductores 1/0 AWG / MCM


Aislante THW Aislante THW
Tabla 5 CEN 2004 Tabla 5 CEN 2004
Área del cable 86.14 mm2 Área del cable 143.70 mm2
Cantidad de cables 3 (Fases + Neutro igual calibre) Cantidad de cables 8 (Fases + Neutro igual calibre)
Área Total 258.42 mm2 Área Total 1149.58 mm2
Tamaño tubería 4" Tamaño tubería 4 "
Tipo : Tubo de PVC, Tipo A Tipo : Tubo de PVC Rigido, Sch. 40 y tubo de PE
Tabla 4 CEN 2004 Tabla 4 CEN 2004
Área Total 8946.53 mm2 Área Total 8110.96 mm2
% de Ocupación 2.89% % de Ocupación 14.17%

8/113
Protecciones

Primario Secundario
Limitaciones sobre el lugar: Cualquiera
% Impedancia del TX: Mas de 6% pero menos de 10%
Tipo de protección: Fusible Tipo de protección: Interruptor automático
Tabla 450.3(B) CEN 2004 Tabla 450.3(B) CEN 2004
Ajuste max. del dispositivo: 250 % I de diseño Ajuste max. del dispositivo: 125 % I de diseño
Cap. de corriente del dispositivo: 15 A AF Cap. de corriente del dispositivo: 200 A AF
Max corriente de ajuste: 281.91 A AD Max corriente de ajuste: 140.95 A AD

Sistema de puesta a tierra


Tipo de conductor: Desnudo
Cantidad de conexiones: 2 CEN 2004 tabla 250-122
Calibre mínimo: 2/0 0 AF: AMPERIOS FRAME
AD: AMPERIOS DE DISPARO
Otras características

Indicador de temperatura Descargador de sobre voltajes

Indicador de presión
Instalado en
Indicador de nivel de liquido ● Interior

Indicador de sobrecarga Exterior


Color de pintura: Gris

V3.14 fm

9/113
Proyecto: TX:
0

Cargas del Transformador


N° Descripción Carga Unidad FP Ef. VA W VAR
1 carga 1 5 HP 0.99 100 3766.111111 3728.45 531.2753511
2 0 0 0
3 0 0 0
5% 4 0 0 0
5 VA 0.707 0 0 0
6 VA 0 0 0
7 HP 90 0 0 0
8 HP 0 0 0
9 HP 0 0 0
10 HP 0 0 0

Voltaje del sistema 480 V Sub Total 3728.45 531.28

95% S= √ P 2 +Q2 Total 3766.11 VA


Nota: todas las cargas se consideran trifásicas para fines del calculo, a menos que se
exprese directamente en VA

Uso Reserva Capacidad del Transformador 5.02% Uso


75 kVA 94.98% Reserva
71.23 kVA Reserva
Cálculos Eléctricos Banco de Baterias
Según norma IEEE 1115-2000
Nombre del Proyecto:
Código: Fecha
Identificador : 12/8/2021

Tension terminal de celda: 1.1 V


Cap. Inicial del Banco: 369 A-H
Temp. electrolito: 25 °C
Margen de diseño: 1.10 FD
Factor de envejecimiento 1.25 FE

Tabla de carga
Tiempo Inicio Tiempo Fin Duracion Corriente Capacidad
Carga Descripcion
(min) (min) (min) (A) (A-H)
1 L1 0 30 30.00 37.18 18.59
2 L2 0 0 0.00 0 0.00
3 L3 0 0 0.00 0 0.00
4 L4 0 0 0.00 0 0.00
5 L5 0 0 0.00 0 0.00
6 L6 0 0 0.00 0 0.00

Aleatoria LA 0 0 0.00 0 0.00


TOTAL 18.59 A-H
Capacidad Preliminar

Curva de carga

Corriente (A)
40

35

30

25

20

15

10

0 Tiempo (min)
0 5 10 15 20 25 30 35

Tabla de comportamiento general de carga


Capacidad
SEC Desde (min) Hasta (min) Duracion(min) Total A
(A-H)
1 0 30 30.00 37.18 18.59
2 N/A N/A N/A N/A N/A
3 N/A N/A N/A N/A N/A
4 N/A N/A N/A N/A N/A
5 N/A N/A N/A N/A N/A
6 N/A N/A N/A N/A N/A
7 N/A N/A N/A N/A N/A
8 N/A N/A N/A N/A N/A
9 N/A N/A N/A N/A N/A
10 N/A N/A N/A N/A N/A

11/113
Demanda Maxima: 37.18 A
Demanda Minima: 37.18 A
Demanda Promedio: 37.18 A

Calculo del factor de capacidad


n° T (MIN) T1 T2 A para T1 A para T2 Factor K1 Factor K2 Factor Kt
1 30.000 30 - 266 0 1.387 - 1.387
2 - - - - 0 - - -
3 - - - - 0 - - -
4 - - - - 0 - - -
5 - - - - 0 - - -
6 - - - - 0 - - -
7 - - - - 0 - - -
8 - - - - 0 - - -
9 - - - - 0 - - -
10 - - - - 0 - - -
11 - - - - 0 - - -
12 - - - - 0 - - -
13 - - - - 0 - - -
14 - - - - 0 - - -
15 - - - - 0 - - -
16 - - - - 0 - - -
17 - - - - 0 - - -
18 - - - - 0 - - -
19 - - - - 0 - - -
20 - - - - 0 - - -

Curva del factor de corrección por temperatura de electrolito


3

2.5

2
Factor Tt

1s - 10 min
1.5
30 min
60 min
1 3H
5-8H
0.5

0
-29 -20 -10 0 10 20 25
°C

12/113
Hoja de selección de capacidad
Carga Cambio de carga Duracion Tiempo final de Factor de Factor de Valor positivo
Periodo Valor negativo (AH)
(A) (A) (min) seccion (min) capacidad (Kt) temperatura (Tt) (AH)

1 37 37 30.000 30.000 1.387 1.000 52 0


Sub total 51.58 0.00
Total 51.58

1 37.18 37 30.000 30.000 1.387 1.000 51.58 0.00


2 0.00 -37 0.000 0.000 #N/A #N/A 0.00 #N/A
Sub total 0.00 0.00
Total 0.00

1 37 37 30.000 30.000 1.387 1.000 52 0


2 0 -37 0.000 0.000 #N/A #N/A 0 #N/A
3 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00
Total 0.00

1 37 37 30.000 30.000 1.387 1.000 52 0


2 0 -37 0.000 0.000 #N/A #N/A 0 #N/A
3 0 0 0.000 0.000 #N/A #N/A 0 0
4 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00
Total 0.00

1 37 37 30.000 30.000 1.387 1.000 52 0


2 0 -37 0.000 0.000 #N/A #N/A 0 #N/A
3 0 0 0.000 0.000 #N/A #N/A 0 0
4 0 0 0.000 0.000 #N/A #N/A 0 0
5 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00
Total 0.00

1 37 37 30.000 30.000 1.387 1.000 52 0


2 0 -37 0.000 0.000 #N/A #N/A 0 #N/A
3 0 0 0.000 0.000 #N/A #N/A 0 0
4 0 0 0.000 0.000 #N/A #N/A 0 0
5 0 0 0.000 0.000 #N/A #N/A 0 0
6 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00
Total 0.00

1 37 37 30.000 30.000 1.387 1.000 52 0


2 0 -37 0.000 0.000 #N/A #N/A 0 #N/A
3 0 0 0.000 0.000 #N/A #N/A 0 0
4 0 0 0.000 0.000 #N/A #N/A 0 0
5 0 0 0.000 0.000 #N/A #N/A 0 0
6 0 0 0.000 0.000 #N/A #N/A 0 0
7 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00
Total 0.00

Aleatoria 0 0 0.000 0.000 #N/A #N/A 0.000 0.000


Total 0.00

Tamaño de la sección mayor 51.57 AH + Sección aleatoria 0AH = Tamaño sin corrección: 51.57 AH
Capacidad final :TSC X FD X FE = 70.91 AH
V3.14 fm

13/113
TABLA DE REFERENCIA CRUZADA
Circular
AWG AWG (en notación "X/0" ) MCM o kcmil
MILS

41 41 8
40 40 10
39 39 12
38 38 16
37 37 20
36 36 25
35 35 32
34 34 40
33 33 50
32 32 63
31 31 80
30 30 100
29 29 127
28 28 160
27 27 201
26 26 254
25 25 320
24 24 404
23 23 509
22 22 642
21 21 810
20 20 1021
19 19 1288
18 18 1624
17 17 2048
16 16 2582
15 15 3256
14 14 4106
13 13 5178
12 12 6529
11 11 8233
10 10 10 10382
9 9 13 13091
8 8 17 16507
7 7 21 20815
6 6 26 26248
5 5 33 33098
4 4 42 41735
3 3 53 52627
2 2 66 66361
1 1 84 83680
0 1 /0 106 105518
-1 2 /0 133 133056
-2 3 /0 168 167780
-3 4 /0 212 211566
-3.7 4.7 /0 250 250000
-4.5 5.5 /0 300 300000
-5.2 6.2 /0 350 350000
-5.7 6.7 /0 400 400000
-6.3 7.3 /0 450 450000
-6.7 7.7 /0 500 500000
-7.5 8.5 /0 600 600000
-8.2 9.2 /0 700 700000
-8.5 9.5 /0 750 750000
-8.7 9.7 /0 800 800000
-9.2 10.2 /0 900 900000
-9.7 10.7 /0 1000 1000000
-10.7 11.7 /0 1250 1250000
-11.4 12.4 /0 1500 1500000
-12.1 13.1 /0 1750 1750000
-12.7 13.7 /0 2000 2000000

MCM significa 1000's (M) of (C)ircular (M)ils


kcmil significa 1000's (K) of (C)ircular (M)ils
Mil significa 1/1000 inch
Circular Mil means the area of a circle 1/1000 inch in diameter
AWG = -4.3125 LN (mm2) + 17.16 (approx interpolated)
AWG = -4.3125 LN (inch2) - 10.74 (approx interpolated)
Logical AWG numbers are based on continuing the series in a logarithmic 
relationship to the cross sectional area of the wire.
Fuente:
http://lugsdirect.com/AWG%20wire%20sizes.htm
RUZADA
Sección
Transversal
en mm2

0.00397
0.00501
0.00632
0.00797
0.01005
0.01267
0.01597
0.02014
0.0254
0.03203
0.04039
0.05093
0.06422
0.08097
0.10211
0.12875
0.16235
0.20473
0.25815
0.32552
0.41048
0.5176
0.65268
0.82301
1.0378
1.30864
1.65016
2.0808
2.62384
3.30859
4.17204
5.26084
6.63377
8.36501
10.5481
13.3008
16.772
21.149
26.6684
33.6281
42.4042
53.4705
67.4249
85.021
107.209
126.677
152.012
177.348
202.683
228.018
253.354
304.025
354.695
380.031
405.366
456.037
506.708
633.384
760.061
886.738
1013.415

eter

in a logarithmic 
TABLA DE SELECCIÓN DE AISLANTES PARA CONDUC
Mecánica PVC Polietileno
Resistencia a la Abrasión Buena Excelente
Resistencia a la Tracción Excelente Excelente
Elongación Buena Excelente
Resistencia a la Compresión Buena Excelente
Flexibilidad Buena Normal

Ambiental

Llama Buena Pobre


Humedad
Agua Dulce o Salada Buena Excepcional
Aceites de Petróleo
Aceite de Motor Excelente
Fuel-oil Buena (Se deforma levemente por
Petróleo Crudo encima de los 60ºC)
La Creosota Pobre Buena
Hidrocarburos parafínicos
Gasolina Excelente
Buena (Se deforma levemente a altas
Queroseno
temperaturas)
Alcoholes
Isopropílico
Wood Normal Buena
Grain
Ácidos minerales
Sulfúrico
Nítrico Excelente Excelente
Clorhídrico
Preparados Álcalis de hidróxido de sodio (lejía)
Hidróxido de potasio (potasa)
Buena Excelente
Hidróxido de calcio (cal)
Cetonas
Acetona
Pobre Buena
Metil Etil Cetona (MEK)
Esteres
Acetato de Etilo
Pobre Buena
Diluyentes para lacas
Hidrocarburos halogenados
Cloroformo
Tetracloruro de carbono Pobre Pobre
Cloruro de Metilo

General

Deja residuos después de la combustión SI No


Índice de Oxigeno (ASTM D-2863) 23-30% 17-18%
Contenido Halógeno - % Peso 26 0
Temperatura Minima de instalación 14°F (-10°C) -40°F (-40°C)
Dimensional stability under hear Normal Normal
Temperatura Máxima de Operación 75°C (167°F) 75°C (167°F)
Nota: Si los cables se van a instalar en frío, deben ser calentados en el almacenamiento durante al menos 24 hrs. Antes de la instalación.
ES PARA CONDUCTORES ELÉCTRICOS
Polietileno Cloro
Neopreno CPE Termoplástico
sulfonado
Buena Buena Excelente
Excelente Excelente Buena
Excelente Excelente Buena
Excelente Excelente Buena
Excelente Excelente Normal

Excelente Excelente Buena

Buena Excelente Excelente

Buena
Buena Buena
(Pobre por encima de 110°C)

Normal Normal Buena

Excelente
Pobre Pobre (Se deforma levemente a altas
temperaturas)

Normal Buena Buena

Excelente Excelente Excelente

Buena Excelente Excelente

Pobre Normal Buena

Pobre Normal Buena

Pobre Pobre Pobre

SI SI SI
31-39% 30-36% 30-34%
18 14 18-20
-4°F (-20°C) -4°F (-20°C) -40°F (-40°C)
Excelente Excelente Normal
90°C (194°F) 90°C (194°F) 75°C (167°F)
. Antes de la instalación.
¿Cómo Ayudar?
Si te gusta mi trabajo y quieres ayudar tienes 3 formas para poder hacerlo:

Envia tus comentarios o reportes de error a mi correo.


1 fidelsmc@gmail.com

Entra a mi blog y pulsa sobre alguno de los anuncios de adsgoogle


2 http://fidelsmc.blogspot.com/

Entra en mi blog y pulsa sobre "DONAR" en paypal


3 http://fidelsmc.blogspot.com/
Caída de tensión sistemas Trifasico (Conductor de Cobre)
Carga: 11150 VA 11.15 kVA
Longitud del circuito: 180 m (r×cos θ + x×se
Tensión del sistema 480 V
k= 2
105×kV
FP: 0.85
Calibre del Cable: 8 1 Cond. por fase
Material de la tubería: PVC
R: 2.56 OHM/kM
X: 0.171 OHM/kM
ΔV (%)=(kVA×m

Caída de tensión: ∆V(%) = 1.97


Voltaje Final: 470.52 V
de Cobre)
(r×cosθ + x×senθ )
k= 2
105×kV

k=0.0009

ΔV (%)=(kVA×m)×k
Regulación Max.
Caída de tensión sistemas Monofasicos (Conducto
Carga: 1500 VA 1.5 kVA
3%
Longitud del circuito: 140 m
Tensión del sistema 480 V
5% FP: 0.8
Calibre del Cable: 12 1
Material de la tubería: PVC
R: 6.6 OHM/kM
X: 0.177 OHM/kM

Caída de tensión: ∆V(%) = 0.98


Voltaje Final: 475.28 V

V3.14
ofasicos (Conductor de cobre) Distancia
0
(r×cos θ + x×senθ ) 0.64350111
k= 0.6
5×kV 2
0.00467552
Cond. por fase
k=0.0046

ΔV (%)=(kVA×m)×k 0.98185938

%) = 0.98 3

1000 22 10 220
Caida de tension en sistemas DC
2
Resistividad del cobre [ρ]: 0.018
Ω×mm
m
Distancia del tramo [L]: 180 m

Tipo de carga
● Vatios
15 A

Amperio

Voltaje del sistema [Vf]: 24 VDC

Calibre del cable: 14

Diámetro del cable: 1.63 mm

Area de cable [A]: 2.09 mm2

Resistencia del cable 3.11 Ω

Corriente del sistema [In]: 15 A

Resistencia de carga 1.6 Ω

Voltaje en terminales [Vl] 8.16 VDC

Regulación [ΔV%]: 66.00 %


Dimensiones de Bancada Bancada Referencial Distancia Centro a Centro
(No representa la cantidad de Tubos reales)
Profundidad [H1]: 120 cm Nivel del Suelo

Cantidad de Filas: 1
H1 120 cm
Cantidad de Columnas: 2
19cm
Espacio entre Ductos [V]: 8.84 cm H2
158
D
Espacio entre Ductos [H]: 8.84 cm cm

Distancia Centro a Paredes


Diámetro de Ductos [D]: 10.16 cm H H 38 cm

Distancia H2: 13.92 cm

Distancia H3: 13.92 cm H3 V


V
Distancia V1: 13.92 cm V1 V2
19 cm
Distancia V2: 13.92 cm 57 cm

Total de Ductos: 2 19 cm

Profundidad Total: 158.0 cm


Ancho Total: 57.0 cm Dibujo sin escala

Convertir Descripción Final


4 in 10.16 cm Bancada de 2 ductos de 10.16 cm de ancho c/u, en arreglo de 1 filas por 2 columnas a 120 cm bajo tierra, con una profundidad total de
19 cm 7.41 in 158 cm y 57 cm de ancho
Calculo de corriente de corto circuito
Tension del sistema: 0.48 kV
Lugar: Barra 480

Impedancias del sistema


Equipo R X
Red 0.194 0.788
Cable 0.374 0.270

Total
Rt = 0.5680 Ω
Xt = 1.0582 Ω
Zt = 1.2010 Ω

Icc = 0.23 kA sim


R/X = 0.54
Factor K = 1.18 IEC60909
Icc asimetrica = 0.39 kA asim
Calculo de corriente de corto circuito

Motor Trifásico

Potencia: 30 HP Análisis
Voltaje nominal: 0.46 kV en el lado de la falla Sub Transitorio
Eficiencia: 93 %
FP: 0.9 Transitorio
Tipo: Motor de alta velocidad

Xd" Xd´ Xd
Motor de alta velocidad 15 25 80
Motor de Baja velocidad 35 50 100
Compensador 25 40 160
T1. Reactancias en % de motores y compensadores

Se tiene que: P
S n=
FP×η
Sn = 26.73 kW

Luego: X V 2
X m  
100 S n

X= 25

Xm = 1979.25 mOhm 1.979254114

Ralignl¿ m ¿¿=0,2 X m¿
Rm = 395.85 mOhm

Rm 0.20
=
Xm
2.01845107
Zt= 2018.45 mOhm
Zt= √ R 2t + X 2t
2
Vn
I cc , sim=
√ 3×Z t
Por lo tanto: Icc, sim = 60.53 kA simétricos

Luego tenemos que: K= 1.54 , para


Rt
= 0.20 ( IEC 60909 )
Xt

I cc=√ 2×K×I cc , sim


Finalmente: Icc = 131.90 kA asimétricos
Basado en la norma UTE C 15-105 y IEC 60 909. 1.540952
Calculo de corriente de corto circuito

Transformador trifásico

Potencia: 75 kVA
Voltaje en lado de falla (V2): 0.48 kV V1: 13.8 kV
Voltaje de corto circuito %: 4 Tabla T1
Ra: 0.568032196 Ohm Rr 0.000687222 Ohm reflejada
Xa: 1.058234384 Ohm Xr 0.001280284 Ohm reflejada
T1. Tensión de cortocircuito Vcc normalizada para los transformadores MT/BT de distribución pública.
kVA 630 800 1000 1250 1600 2000
Vcc (%) 4 4.5 5 5.5 6 7

2
Vn
Se tiene que: Z t =V cc × Z del transformador
Sn

Por lo tanto: Zt = 122.88 mΩ 0.12288

Se tiene que: X t ≈Z t X del transformador

Por lo tanto: Xt = 122.88 mΩ Xr =1.28mΩ

Se tiene que: Rt ≈0 , 20× X t R del transformador

Por lo tanto: Rt = 24.576 mΩ Rr =0.687mΩ

Rtotal
Luego: = 0.20 0.126704406
X total

Z total =√( Rt +Rr )2 +( X t + X r )2 Zt = 126.70 mΩ

2
Vn
Se tiene que: I cc , sim=
√ 3× Z t
Por lo tanto: Icc, sim = 1049.86 kA simetricos

Rt
Luego tenemos que: K = 1.54 , para = 0.20 ( IEC 60909 )
Xt

I cc=√ 2×K×I cc , sim


Finalmente: Icc = 2279.13 kA asimetricos
Basado en la norma UTE C 15-105 y IEC 60 909. 1.535052081
Calculo de corriente de corto circuito
Aporte de corriente de la red electrica

Tension Nominal: 13.8 kV


Icc: 17 kA sim
Scc: 234.6 MVA
Icc Asimetrica: 35.27 kA asim

Ra/Za: 0.239
Za: 0.812 Ω
Xa: 0.788 Ω
Ra: 0.194 Ω
Ra/Xa: 0.246
Factor K: 1.467 (IEC 60909)

Red electrica

13.8kV 17kA sim


PDVSA 90619.1.089
Caída de tensión método amperios pie
Potencia de lámparas: 1600 W
Voltaje de operación: 277 V
Distancia entre lámparas: 30 M
Tramo inicial: 20.00 M
Cantidad de Luminarias: 30
Distancia entre lámpara: 98.424 FT
Distancia
N Amperios Distancia (FT) A-pie
(M)
0 65.6 20.00 --
1 5.78 65.6 20.00 378.9
2 5.78 131.2 40.00 757.8
3 5.78 196.8 60.00 1136.8
4 5.78 262.4 80.00 1515.7
5 5.78 328.0 100.00 1894.6
6 5.78 393.6 120.00 2273.5
7 5.78 459.2 140.00 2652.4
8 5.78 524.8 160.00 3031.3
9 5.78 590.4 180.00 3410.3
10 5.78 656.0 200.00 3789.2
11 5.78 721.6 220.00 4168.1
12 5.78 787.2 240.00 4547.0
13 5.78 852.8 260.00 4925.9
14 5.78 918.4 280.00 5304.8
15 5.78 984.0 300.00 5683.8
16 5.78 1049.6 320.00 6062.7
17 5.78 1115.2 340.00 6441.6
18 5.78 1180.8 360.00 6820.5
19 5.78 1246.4 380.00 7199.4
20 5.78 1312.0 400.00 7578.3
21 5.78 1377.6 420.00 7957.3

Total 87529.8 A-P

Calibre del conductor: 4/0


Factor K: 10.7
Area: 211600 Mil Circular

Caida de tension: 4.43 V


% de Caida de tension: 1.60%
Calculo de caída de tensión para circuitos monofásicos de iluminación

Tensión del sistema 0.12 kV Calibre del cable:


Factor de potencia 0.95 Canalizacion:
Cantidad de Postes 29 Resistencia:
P. Poste 100 VA Reactancia:
D0 114 m
DEP 5 m

Potencia Paso de Distancia


kVA x m
Nº [VA] Distancia [m] [m]
1 100 114 114 11.4 ( r×cos θ + x×senθ )
2 100 5 119 11.9 k=
3 100 5 124 12.4
5×kV 2
4 100 5 129 12.9
5 100 5 134 13.4 k = 0.005
6 100 5 139 13.9
7 100 5 144 14.4
8 100 5 149 14.9 ΔV (% )=(kVA×m)×k
9 100 5 154 15.4
10 100 5 159 15.9
11 100 5 164 16.4 ∆V(%) = 3.07
12 100 5 169 16.9
13 100 5 174 17.4
14 100 5 179 17.9 Voltaje Final:
15 100 5 184 18.4
16 100 5 189 18.9
17 100 5 194 19.4
18 100 5 199 19.9
19 100 5 204 20.4
20 100 5 209 20.9
21 100 5 214 21.4
22 100 5 219 21.9
23 100 5 224 22.4
24 100 5 229 22.9
25 100 5 234 23.4
26 100 5 239 23.9
27 100 5 244 24.4
28 100 5 249 24.9
29 100 5 254 25.4
30 0 5 0 0

Total 533.6 kVA x m


2
ofásicos de iluminación

1/0

PVC
0.39 Ω/km
0.144 Ω/km

( r×cos θ + x×senθ )
=
5×kV 2 3.07904976
0.005770333
0.317560429
0.3122499

V (% )=(kVA ×m)×k

116.31 V
Calibre
Alimentación Tipo de Carga Calculo de Alimentador Temperatura del cable
● W Datos de la Carga ● 60 °C 75 °C 90 °C
Monofasica Carga nominal: 150000 VA
HP Tension del sistema: 220 V
Fp: 0.9 Temperatura ambiente
Trifásica
A Eff: 95 %
31-35 °C
Factor de diseño: 125 %
VA Corriente: 393.65 A Conductores por fase

Datos del Conductor


Calibre: 1000 AWG/MCM
Capacidad nominal: 545 A
Factor correcion Temp: 0.94
Conductores por fase: 1
Capacidad Total: 512.30 A
Tabla 310,16
Lista de Cables Monopolares

Cant. Act.X
Distancia

Calibre

Calibre
Neutro
Fases

Fase
Tension Tension
COVENIN 398

(M)
TAG
Oper (V) Max (V)
Tipo Aislante Desdes Hasta

P-001 (#)
P-002 (#)
P-003 (#)
P-004 (#)
P-005 (#)
P-006 (#)
P-007 (#)
P-008 (#)
P-009 (#)
P-010 (#)
P-011 (#)
P-012 (#)
P-013 (#)
P-014 (#)
P-015 (#)
P-016 (#)
P-017 (#)
P-018 (#)
P-019 (#)
P-020 (#)
P-021 (#)
P-022 (#)
P-023 (#)
P-024 (#)
P-025 (#)
P-026 (#)
P-027 (#)
P-028 (#)
P-029 (#)
P-030 (#)
Proyecto: Nomenclatura COVENIN
X ( n×Y )+ mN ¿ Y ' + pT ¿ Y '' ¿
Indicación de X fases de n conductores monopolares por fase, calibre Y, mas m conductores de neutro (N) calibre
Links
Aralven (Cables)
Cant. Neutro

Cond. Tierra
Cant. Tierra

Neutro (M)
Activo (M)
Cond Act.

Cantidad
Cantidad

Cantidad
Calibre

Cond.
Cond.
Tierra
X GF

X GF

(M)
Observaciones

0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0

e Y, mas m conductores de neutro (N) calibre Y’, mas p conductores de tierra (T) calibre Y’’.
AISLANTES DE CONDUCTORES
Tipo Descripcion

DESNUDO Sin recubrimiento


FXT TFF TWF Los conductores flexibles de cobre tipo FXT, TFF y TW-F son utilizados para alambrado de aparatos, c
eléctricos de control, baterías de vehículos, instalaciones generales industriales y comerciales donde s
flexibilidad debido a las dificultades de trabajo y en general como cables sometidos a continuo movimie
especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y h
temperatura máxima de operación es 60 ºC y su tensión de servicio para todas las aplicaciones es 600

RHHN AISLANTE DE MATERIAL TERMOPLASTICO, XLPE 600 V. - 90 ºC, ANTILLAMA.

THHN Los conductores de cobre tipo THHN o THWN-2 son utilizados para circuitos de fuerza y alumbrado en
industriales, comerciales y residenciales, son especialmente aptos para instalaciones especiales por d
usarse en zonas abrasivas o contaminadas con aceites, grasas, gasolinas, etc. y otras sustancias quím
como pinturas, solventes, etc., tal como se especifica en el National Electrical Code. Este tipo de cond
utilizado como THHN puede ser usado en lugares secos con temperatura máxima de operación de 90
utilizado como THWN-2 puede ser usado en lugares secos y húmedos con temperatura máxima de op
así mismo cuando están expuestos a aceites, grasas, pinturas, solventes químicos, etc., su temperatur
operación es 75 ºC. En cuanto a su tensión de servicio, para todas las aplicaciones, es de 600 V.

THW Los conductores de cobre tipo THW son utilizados para circuitos de fuerza y alumbrado en edificacione
comerciales y residenciales donde se requiera de mayor seguridad, tal como se especifica en el Nation
Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de oper
su tensión de servicio para todas las aplicaciones es 600 V.

TTU Los conductores de cobre tipo TTU-0.6 KV. son utilizados para circuitos de fuerza y alumbrado en edif
industriales y comerciales, son especialmente aptos para instalaciones a la intemperie o directamente
se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos
temperatura máxima de operación es 75 ºC y su tensión de servicio para todas las aplicaciones es 600

TW Los conductores de cobre tipo TW son utilizados para circuitos de fuerza y alumbrado en edificaciones
comerciales y residenciales, tal como se especifica en el National Electrical Code. Este tipo de conduc
en lugares secos y húmedos, su temperatura máxima de operación es 60 ºC y su tensión de servicio p
aplicaciones es 600 V

XHHW Los conductores de cobre tipo XHHW son utilizados para circuitos de fuerza y alumbrado en edificacio
comerciales, son especialmente aptos para instalaciones a la intemperie, tal como se especifica en el N
Code. Este tipo de conductor puede ser utilizados en lugares secos y húmedos, su temperatura máxim
90 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
ORES

o
os para alambrado de aparatos, cableado de tableros
dustriales y comerciales donde se requiera de gran
es sometidos a continuo movimiento, tal como se
e ser usado en lugares secos y húmedos, su
ara todas las aplicaciones es 600 V.

ANTILLAMA.

rcuitos de fuerza y alumbrado en edificaciones


ra instalaciones especiales por ductos difíciles y
inas, etc. y otras sustancias químicas corrosivas
lectrical Code. Este tipo de conductor cuando es
ura máxima de operación de 90 ºC, pero si es
s con temperatura máxima de operación de 90 ºC,
tes químicos, etc., su temperatura máxima de
aplicaciones, es de 600 V.

erza y alumbrado en edificaciones industriales,


l como se especifica en el National Electrical Code.
su temperatura máxima de operación es de 75 ºC y

os de fuerza y alumbrado en edificaciones


s a la intemperie o directamente enterrados, tal como
ede ser usado en lugares secos y húmedos, su
ara todas las aplicaciones es 600 V.

rza y alumbrado en edificaciones industriales,


ctrical Code. Este tipo de conductor puede ser usado
s 60 ºC y su tensión de servicio para todas las

fuerza y alumbrado en edificaciones industriales y


rie, tal como se especifica en el National Electrical
húmedos, su temperatura máxima de operación es
Metros de cable por nivel de tension (TOTAL)

Calibr
e 600 5000 15000 3500
/
V

18 AWG 0 0 0 0
16 AWG 0 0 0 0
14 AWG 0 0 0 0
12 AWG 0 0 0 0
10 AWG 0 0 0 0
8 AWG 0 0 0 0
6 AWG 0 0 0 0
4 AWG 0 0 0 0
3 AWG 0 0 0 0
2 AWG 0 0 0 0
1 AWG 0 0 0 0
1/0 AWG 0 0 0 0
2/0 AWG 0 0 0 0
3/0 AWG 0 0 0 0
4/0 AWG 0 0 0 0
250 MCM 0 0 0 0
300 MCM 0 0 0 0
350 MCM 0 0 0 0
400 MCM 0 0 0 0
500 MCM 0 0 0 0
600 MCM 0 0 0 0
700 MCM 0 0 0 0
750 MCM 0 0 0 0
800 MCM 0 0 0 0
900 MCM 0 0 0 0
1000 MCM 0 0 0 0
1250 MCM 0 0 0 0
1500 MCM 0 0 0 0
1750 MCM 0 0 0 0
2000 MCM 0 0 0 0
Ocupacion de ductos
Cable Monopolar
Diametro* Area por cable Total Grupo
N° Calibre Aislante Cantidad mm mm2 mm2
1 2 TTU 90 (XLPE-PVC) 600 V 3 11.52 104.23 312.69
2 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
3 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
4 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00
5 12 TTU 90 (XLPE-PVC) 600 V 0 4.60 16.62 0.00

Area Total 312.69 mm2

Tipo de Ducto:
Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD

Diametro:
2 Pulgadas
Diametro** 52 mm
Diámetro mínimo recomendado Area Total 2123.72 mm2
1 1/4 "

Max. Ocupacion 40.00% Ocupación 14.72%


*Fabricante del cable: Aralven
** Según tabla del CEN 2004
Potencia Factor de Potencia

Potencia: 18600
Aparente [VA] FP (%): 41
Cos(θ): 0.41
Sen(θ): 0.91

● Activa [W]

S 45365.85 VA
P 18600.00 W
Reactiva [VAR] Q 41377.54 VAR
2
S P Q
VA 18600 7626 16964.79071
W 45365.85366 18600 41377.53833
VAR 20392.82452 8361.058052 18600

x y
p 0 0
18600.00 0
Q 18600.00 0
18600.00 41377.54
S 0 0
18600.00 41377.54

eje 0 18600.00
41377.54 0
Triangulo de potencia
45000
40000
35000
30000
25000
(VAR)

20000
15000
10000
5000
0
0 5000 10000 15000 20000 25000 30000 35000 40000 45000
(W )
TABLERO ELECTRICO
Tipo de Tablero: Instalacion: C. Interrupción [kA]: Fases: Proyecto:
NLAB Auto soportado 22 3 ejemplo
Polos: Cerramiento NEMA: Color: Alimentador Principal: Instalacion:
18 3R GRIS INDUSTRIAL Calibre Aislante Cnd X fase Conduit Entrada ejemplo
Voltaje del Tablero [V]: Corriente de Barras [A]: Interruptor principal 3P [A]: Nombre del Tablero:
250 MCM THHN 1 4 Superior
240 100 400 ejemplo

A B C

Tuberia Conductor Interruptor Interruptor Conductor Tuberia


Diametro Cond. por In [A] In [A] Cond. por Diametro
Carga Conectada VA Material Aislante Calibre Tipo Nº Nº Tipo Calibre Aislante Material VA Carga Conectada
[pul] fase 3P 3P fase [pul]

1500 1 2 1000

Carga Nº 1 1500 PVC 2 1 THHN 6 AWG QC 20 3 4 30 THQC 250 MCM TTU 1 4 PVC 1000 Carga Nº 2

1500 5 6 1000

500 7 8 1250

CARGA 4 500 PVC 2 1 THHN 14 AWG QC 20 9 10 90 THQC 14 AWG TTU 1 2 PVC 1250 CARGA 3

500 11 12 1250

13 14

15 16

17 18

19 20

21 22

23 24

25 26

27 28

29 30

31 32

33 34

35 36

VA A % POT. RESERVA ✘ BARRA DE TIERRA


A 4250 10.22 0.33 0.00 VA ✘ BARRA DE NEUTRO
B 4250 10.22 0.33 0.00%
C 4250 10.22 0.33

V3.14 TOTAL 12750


TABLERO ELECTRICO
Tipo de Tablero: Instalacion: C. Interrupción [kA]: Fases: Proyecto:
NLAB Auto soportado 22 2 ejemplo
Polos: Cerramiento NEMA: Color: Alimentador Principal: Instalacion:
36 3R GRIS INDUSTRIAL Calibre Aislante Cnd X fase Conduit Entrada ejemplo
Voltaje del Tablero [V]: Corriente de Barras [A]: Interruptor principal 3P [A]: Nombre del Tablero:
1/0 AWG THHN 2 4 Superior
240 100 400 ejemplo

A B

Tuberia Conductor Interruptor Interruptor Conductor Tuberia


Diametro Cond. por In [A] In [A] Cond. por Diametro
Carga Conectada VA Material Aislante Calibre Tipo Nº Nº Tipo Calibre Aislante Material VA Carga Conectada
[pul] fase 3P 3P fase [pul]

carga 1 1500 PVC 2 1 THW 12 AWG QC 20 1 2 PVC 2 1 THW 12 AWG QC 20 1500 carga 2

carga 4 1500 PVC 2 1 THW 12 AWG QC 20 3 4 PVC 2 1 THW 12 AWG QC 20 1500 reserva

✘ 5 6

✘ 7 8

✘ 9 10

✘ 11 12

✘ 13 14

✘ 15 16

✘ 17 18

✘ 19 20

✘ 21 22

✘ 23 24

✘ 25 26

✘ 27 28

✘ 29 30

✘ 31 32

✘ 33 34

✘ 35 36

VA A % POT. RESERVA ✘ BARRA DE TIERRA


A 3000 7.22 50.00 1500.00 VA ✘ BARRA DE NEUTRO
B 3000 7.22 50.00 25.00%

V3.14 TOTAL 6000


SEPARACIÓN MINIMA RECOMENDADA ENTRE DUCTOS Y BANDEJAS

NIVELES

1.- APLICACIONES ALTAMENTE SUSCEPTIBLES A RUIDOS.


SEÑALES DE INSTRUMENTOS DE 4-20 mA 24Vdc, OTRAS SEÑALES ANÁLOGAS < 50Vdc Y TRASMISORES DIGITALES
SEÑALES DISCRETAS DE 24 Vdc
BUSES DE COMUNICACIONES DE INSTRUMENTOS ANALÓGICOS +- 50Vdc
BUSES DE COMUNICACIONES DE INSTRUMENTOS DIGITALES +- 24Vdc
CIRCUITOS DE TERMOCUPLA Y RTD
CIRCUITOS TELEFÓNICOS
2.- APLICACIONES MEDIANAMENTE SUSCEPTIBLES A RUIDOS
ILUMINACION E INTERRUPTORES DE 24Vdc O MENOS
SEÑALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO
3.- APLICACIONES BAJAMENTE SUSCEPTIBLES A RUIDOS
ALIMENTADORES EN 120/240 Vac DE MENOS DE 20 A
ILUMINACION E INTERRUPTORES DE 24Vdc O MAS
SEÑALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO
4.- APLICACIONES DE POTENCIA INTERMEDIA
PRIMARIOS Y SECUNDARIOS DE TRANSFORMADORES < 5kVA
BARRAS AC O DC 0-800 V CON CORRIENTES MAYORES A 20 A
5.- APLICACIONES DE ALTA POTENCIA
BARRAS AC O DC> 1kW Y/O CORRIENTES MAYORES A 800 A

CASO DE ESTUDIO

CASO: NIVEL A: NIVEL B:


DUCTO METÁLICO A DUCTO METÁLICO 2 5

SEPARACIÓN MINIMA RECOMENDADA:

12 IN 30.48 CM

NOTAS

1 Esta hoja no aplica para ductos no metálicos


2 La distancia definida aquí, indica el espacio mínimo entre el tope y el fondo de las bandejas o el espacio lateral entre ellas.
3 Estas distancias también aplican como el espacio entre bandejas y equipos de potencia menores a 100kVA

4 Las distancia mínimas de los ductos se indican en referencia al exterior de los mismos

5 Cuando señales de distintos niveles deban cruzarse, deben hacer en un ángulo de 90º. Cuando no sea posible mantener las distancias de separación
se debe interponer una barrera metálica aterrada.

6 Los niveles 3 y 4 pueden ser canalizados en la misma bandeja siempre que se coloque una barrea entre ellos
7 Cuando sea impractico separarlos, los niveles 1 y 2 pueden ser usados en la misma bandeja, siempre que tenga una barrera metálica aterrada entre
ellos.

8 Las bandejas de todos los niveles deben ser metálicas solidamente aterradas.
9 Bandejas y ductos de los niveles 1 y 2 no podrán ser llevadas en paralelo con equipos de alta potencia cerrados mayores a 100kVA a 150 cm de las
bandejas y 80 cm de los ductos.

10 Cunado no se posible mantener el espacio indicado arriba, se debe minimizar el recorrido en paralelo de las rutas, en tal caso, el recorrido no podrá
superar los 150 cm de longitud.

Fuentes:
PIP PCCEL001
IEEE 518
BANDEJAS PORTACABLES

Caso de Estudio
Lista de Cables

Tipo de Bandeja: Perforado ranurado CABLES MONOPOLARES

Material: Acero Inoxidable Cables 1000kCMIL o mayores

Carga de Trabajo: 100 Lbs/ft. Cables 250kCMIL a 1000kCMIL

Espacio entre soportes: 8 ft. Cables Mayores a 1000kCMIL con menores a 1000 kCMIL

Clase NEMA: 8C Con algun cable instalado entre 1/0 y 4/0

Calculado: 33.75 cm CABLES MULTICONDUCTORES

Ancho Seleccionado: 22.5 cm Calibres 4/0 o Mayores

Bandeja de ancho menor a la requerida Calibres menores a 4/0

Cables 4/0 o mayores con cables menores a 4/0

Cables control / alumbrado / señalizacion


2 3 1 2 Selección
Tipo de bandeja Carga de Trabaj Distancia entre soportes Material Altura 3
Escalera 50 8 Aluminio 3
Perforado ranurado 75 12 Acero Inoxida 4
100 16 Acero Galvan 5
20 Fibra de Vidri 6
ancho de bandejas
15
22.5
30
45
60 Bandejas
75 ###
90 22.30
33.75
11.09
68.60
24.15
49.81
7.26
Lista de Cables
Selección

Bandejas
CABLE MONOPOLAR
Bandejas de fondo escalera o ventilado

Cables 1000 kCMIL o mayores


Area Total Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
(mm2) Requerido (cm)

5 1000 25.40 506.71 2533.54 12.7

10 1250 28.40 633.47 6334.71 28.4

10 1500 31.11 760.13 7601.34 31.11

36 1750 33.60 886.68 31920.59 120.96

36 2000 35.92 1013.36 36480.86 129.312

392-10(a) (1) NEC 2008 Ancho de conductores 322.48

Fuente: lugsdirect.com 20% Reserva: 64.50

Ancho total de Bandeja (cm) 386.98

Cables 250kCMIL a 1000kCMIL


Area Total Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
(mm2) Requerido (cm)

5 THW 600 V 250 13.51 143.35 716.75 2.58

8 TW 600 V 250 13.51 143.35 1146.81 4.13

5 THW 600 V 1000 19.42 296.20 1481.01 5.33

2 THW 600 V 300 14.66 168.79 337.59 1.22

5 THW 600 V 1000 19.42 296.20 1481.01 5.33

392-10(a) (2) NEC 2008 Ancho Minimo (cm) 18.59

Fuente: Aralven 20% Reserva: 3.72

Ancho total de Bandeja (cm) 22.30


Cables mayores a 1000kCMIL con menores a 1000kCMIL
Cables Mayores o iguales a 1000kCMIL
Area Total Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
(mm2) Requerido (cm)

6 1000 25.40 506.71 3040.24 15.24

1 1500 31.11 760.13 760.13 3.11

Cables menores a 1000kCMIL


Area Total Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
(mm2) Requerido (cm)

5 TW 600 V 500 25.52 511.51 2557.53 9.21

2 THW 600 V 10 4.47 15.69 31.39 0.11

2 THW 600 V 4 8.93 62.63 125.26 0.45

392-10(a) (3) NEC 2008 Ancho Minimo (cm) 28.12

Fuente: Aralven 20% Reserva: 5.62

Ancho total de Bandeja (cm) 33.75

Con algun cable instalado entre 1/0 y 4/0


Area Total Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
(mm2) Requerido (cm)

5 TTU 90 (XLPE-PVC) 600 V 4/0 18.48 268.22 1341.11 9.24

0 TW 600 V 1/0 13.51 143.35 0.00 0

0 TW 600 V 4/0 17.46 239.43 0.00 0

0 TW 600 V 4/0 17.46 239.43 0.00 0

0 THW 600 V 4/0 17.46 239.43 0.00 0

392-10(a) (4) NEC 2008 Ancho de conductores 9.24

Fuente: Aralven 20% Reserva: 1.85

Ancho total de Bandeja (cm) 11.09


CABLE MULTICONDUCTOR
Bandejas de fondo escalera o ventilado

CALIBRES 4/0 O MAYORES


Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2)
Requerido (cm)

2 THW 600 V 1000 34.88 955.53 1911.05 6.98

5 THW 600 V 500 25.52 511.51 2557.53 12.76

3 4 C, TIPO MC 600 VAC CON CONDUCTORES XHHW DE COBRE


350 54.86 2364.09 7092.28 16.46

1 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 500 55.90 2454.22 2454.22 5.59

2 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1000 76.90 4644.54 9289.08 15.38

NEC 2008 392.9 (a) (1) Ancho de conductores 57.17

Los cables deben ser instalados en una sola capa 20% Reserva: 11.43

Fuente: Manual de gedisa Ancho total de Bandeja (cm) 68.60

CABLES MENORES A 4/0


Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2)
Requerido (cm)

10 THW 600 V 1/0 13.51 143.35 1433.51 4.73

5 THW 600 V 3/0 15.96 200.06 1000.29 3.30

2 4 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 8 18.90 280.55 561.10 1.85

3 4 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 2/0 36.30 1034.91 3104.73 10.25

0 4 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 2/0 36.30 1034.91 0.00 0.00

NEC 2008 392.9 (a) (2) Ancho Minimo (cm) 20.13

Fuente: Manual de gedisa 20% Reserva: 4.03

Ancho total de Bandeja (cm) 24.15


CABLES 4/0 O MAYORES CON CABLES MENORES
Cables Mayores a 4/0
Ancho
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2)
Requerido (cm)

6 TW 600 V 1000 34.88 955.53 5733.16 20.93

1 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1000 76.90 4644.54 4644.54 7.69

Cables menores a 4/0

2 THW 600 V 1/0 13.51 143.35 286.70 0.95

5 THW 600 V 1/0 13.51 143.35 716.75 2.37

2 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1/0 30.40 725.83 1451.67 4.79

2 3 C,TC 600 VAC CON CONDUCTORES XHHW DE COBRE 1/0 30.40 725.83 1451.67 4.79

NEC 2008 392.9 (a) (3) Ancho Minimo (cm) 41.51

Todos los cables mayores a 4/0 se deben instalar en una sola capa 20% Reserva: 8.30

Fuente: Manual de gedisa Ancho total de Bandeja (cm) 49.81

CABLES CONTROL / ALUMBRADO / SEÑALIZACION


Diam. Area Area Total Ancho
Nº Conductores Tipo de Aislante Calibre
(mm) (mm2) (mm2) Requerido (cm)

4 Cables de Control EPR-PVC 90° 14 11.10 96.77 2419.22 6.05


10 Cables de Control PVC-PVC 75° 12 23.20 422.73 0.00 0.00
4 Cables de Control PVC-PVC 75° 10 16.30 208.67 0.00 0.00
4 Cables de Control PVC-PVC 75° 10 16.30 208.67 0.00 0.00
4 Cables de Control EPR-PVC 90° 10 14.40 162.86 0.00 0.00

NEC 2008 392.9 (b) Ancho de conductores 6.05

Se considera la altura de la bandeja como 10cm 20% Reserva: 1.21

Fuente: Manual de gedisa Ancho total de Bandeja (cm) 7.26


Calculo del Factor K para transformad

I Base = 1 A

Armónicos Forma de Onda

1 3 5 7 9 11 13

0 0.2 0.4 0.6 0.8 1 1.2

% de Ib ### 50 0 72 0 33 69 324

Espectro
100
90
80
70
60
50
40
30
20
10
0
1 3 5 7
Armónico
Corriente In
Armónico RMS
In I1
1 1 1
3 0.5 0.5
5 0 0
7 0.72 0.72
9 0 0
11 0.33 0.33
13 0.69 0.69

%TDH-F

Algunos Valore
0 50 ### 28 ### 67 31
0 0 0 0 0 0 0 0 0
0.01 0 0.1 0.1 0.1 0.2 0.2 0.3 0.418
0.01 0 0.1 0.2 0.3 0.4 0.4 1 0.817
0.02 0.1 0.2 0.3 0.4 1 1 1 1.176
0.03 0.1 0.2 0.4 1 1 1 1 1.481
0.03 0.1 0.3 0.5 1 1 1 1 1.717
0.04 0.1 0.4 1 1 1 1 1 1.877
0.05 0.1 0.4 1 1 1 1 1 1.956
0.05 0.2 0.5 1 1 1 1 1 1.956
0.06 0.2 1 1 1 1 1 1 1.882
0.07 0.2 1 1 1 1 1 0.4 1.744
0.07 0.2 1 1 1 1 1 0.1 1.556
0.08 0.2 1 1 1 1 0.4 0 1.333
0.09 0.3 1 1 1 1 0.1 0 1.094
0.09 0.3 1 1 1 0.5 0 -1 0.856
0.1 0.3 1 1 1 0.3 0 -1 0.636
0.11 0.3 1 1 1 0.1 -1 -1 0.448
0.11 0.3 1 1 1 0 -1 -1 0.304
0.12 0.4 1 1 0.5 0 -1 -1 0.211
0.13 0.4 1 1 0.3 0 -1 -1 0.174
0.13 0.4 1 1 0.2 -1 -1 -1 0.191
0.14 0.4 1 1 0.1 -1 -1 -1 0.258
0.15 0.4 1 1 0 -1 -1 0 0.367
0.15 0.5 1 1 0 -1 -1 0 0.506
0.16 0.5 1 1 0 -1 -1 0.2 0.661
0.17 0.5 1 1 0 -1 -1 0.5 0.82
0.17 1 1 0.4 -1 -1 0 1 0.967
0.18 1 1 0.3 -1 -1 0 1 1.091
0.19 1 1 0.2 -1 -1 0.2 1 1.18
0.19 1 1 0.1 -1 -1 0.4 1 1.227
0.2 1 1 ### -1 -1 1 1 1.229
0.21 1 1 0 -1 0 1 1 1.184
0.21 1 1 0 -1 0 1 1 1.097
0.22 1 1 0 -1 0 1 0.4 0.975
0.23 1 1 0 -1 0.1 1 0.2 0.827
0.23 1 1 0 -1 0.3 1 0 0.667
0.24 1 1 -1 -1 0.5 1 0 0.506
0.25 1 1 -1 -1 1 1 -1 0.361
0.25 1 1 -1 -1 1 1 -1 0.242
0.26 1 1 -1 -1 1 0.4 -1 0.161
0.27 1 1 -1 0 1 0.2 -1 0.127
0.27 1 1 -1 0 1 0 -1 0.144
0.28 1 0.5 -1 0 1 0 -1 0.215
0.29 1 0.4 -1 0 1 0 -1 0.336
0.29 1 0.4 -1 0.2 1 -1 -1 0.503
0.3 1 0.3 -1 0.3 1 -1 0 0.706
0.31 1 0.2 -1 0.4 1 -1 0 0.933
0.31 1 0.2 -1 1 1 -1 0.2 1.17
0.32 1 0.1 -1 1 0.4 -1 0.5 1.403
0.33 1 0.1 -1 1 0.2 -1 1 1.618
0.33 1 ### -1 1 ### -1 1 1.801
0.34 1 0 -1 1 0 -1 1 1.942
0.35 1 0 -1 1 0 -1 1 2.032
0.35 1 0 -1 1 -1 0 1 2.065
0.36 1 0 -1 1 -1 0 1 2.04
0.37 1 0 -1 1 -1 0.1 1 1.959
0.37 1 0 0 1 -1 0.3 0.4 1.828
0.38 1 0 0 1 -1 1 0.2 1.654
0.39 1 0 0 1 -1 1 0 1.448
0.39 1 -1 0 1 -1 1 0 1.222
0.4 1 -1 ### 1 -1 1 -1 0.989
0.41 1 -1 0.1 0.5 -1 1 -1 0.76
0.41 1 -1 0.2 0.3 -1 1 -1 0.548
0.42 1 -1 0.3 0.2 -1 1 -1 0.361
0.43 1 -1 0.4 0 0 1 -1 0.207
0.43 1 -1 0.5 0 0 1 -1 0.089
0.44 1 -1 1 0 0 0.5 -1 0.008
0.45 1 -1 1 0 0.1 0.3 -1 -0.04
0.45 1 -1 1 -1 0.2 0 0 -0.05
0.46 1 -1 1 -1 0.4 0 0 -0.04
0.47 1 -1 1 -1 1 0 0.2 -0.01
0.47 1 -1 1 -1 1 -1 0.5 0.033
0.48 1 -1 1 -1 1 -1 1 0.073
0.49 1 -1 1 -1 1 -1 1 0.108
0.49 1 -1 1 -1 1 -1 1 0.132
0.5 1 -1 1 -1 1 -1 1 0.14
0.51 1 -1 1 -1 1 -1 1 0.132
0.51 1 -1 1 -1 1 -1 1 0.108
0.52 1 -1 1 -1 1 -1 1 0.073
0.53 1 -1 1 -1 1 -1 0.5 0.033
0.53 1 -1 1 -1 1 0 0.2 -0.01
0.54 1 -1 1 -1 0.4 0 0 -0.04
0.55 1 -1 1 -1 0.2 0 0 -0.05
0.55 1 -1 1 0 0.1 0.3 -1 -0.04
0.56 1 -1 1 0 0 0.5 -1 0.008
0.57 1 -1 1 0 0 1 -1 0.089
0.57 1 -1 0.4 0 0 1 -1 0.207
0.58 1 -1 0.3 0.2 -1 1 -1 0.361
0.59 1 -1 0.2 0.3 -1 1 -1 0.548
0.59 1 -1 0.1 0.5 -1 1 -1 0.76
0.6 1 -1 ### 1 -1 1 -1 0.989
0.61 1 -1 0 1 -1 1 0 1.222
0.61 1 0 0 1 -1 1 0 1.448
0.62 1 0 0 1 -1 1 0.2 1.654
0.63 1 0 0 1 -1 0.3 0.4 1.828
0.63 1 0 -1 1 -1 0.1 1 1.959
0.64 1 0 -1 1 -1 0 1 2.04
0.65 1 0 -1 1 -1 0 1 2.065
0.65 1 0 -1 1 0 -1 1 2.032
0.66 1 0 -1 1 0 -1 1 1.942
0.67 1 ### -1 1 ### -1 1 1.801
0.67 1 0.1 -1 1 0.2 -1 1 1.618
0.68 1 0.1 -1 1 0.4 -1 0.5 1.403
0.69 1 0.2 -1 1 1 -1 0.2 1.17
0.69 1 0.2 -1 0.4 1 -1 0 0.933
0.7 1 0.3 -1 0.3 1 -1 0 0.706
0.71 1 0.4 -1 0.2 1 -1 -1 0.503
0.71 1 0.4 -1 0 1 0 -1 0.336
0.72 1 0.5 -1 0 1 0 -1 0.215
0.73 1 1 -1 0 1 0 -1 0.144
0.73 1 1 -1 0 1 0.2 -1 0.127
0.74 1 1 -1 -1 1 0.4 -1 0.161
0.75 1 1 -1 -1 1 1 -1 0.242
0.75 1 1 -1 -1 1 1 -1 0.361
0.76 1 1 -1 -1 0.5 1 0 0.506
0.77 1 1 0 -1 0.3 1 0 0.667
0.77 1 1 0 -1 0.1 1 0.2 0.827
0.78 1 1 0 -1 0 1 0.4 0.975
0.79 1 1 0 -1 0 1 1 1.097
0.79 1 1 0 -1 0 1 1 1.184
0.8 1 1 ### -1 -1 1 1 1.229
0.81 1 1 0.1 -1 -1 0.4 1 1.227
0.81 1 1 0.2 -1 -1 0.2 1 1.18
0.82 1 1 0.3 -1 -1 0 1 1.091
0.83 1 1 0.4 -1 -1 0 1 0.967
0.83 0.5 1 1 0 -1 -1 0.5 0.82
0.84 0.5 1 1 0 -1 -1 0.2 0.661
0.85 0.5 1 1 0 -1 -1 0 0.506
0.85 0.4 1 1 0 -1 -1 0 0.367
0.86 0.4 1 1 0.1 -1 -1 -1 0.258
0.87 0.4 1 1 0.2 -1 -1 -1 0.191
0.87 0.4 1 1 0.3 0 -1 -1 0.174
0.88 0.4 1 1 0.5 0 -1 -1 0.211
0.89 0.3 1 1 1 0 -1 -1 0.304
0.89 0.3 1 1 1 0.1 -1 -1 0.448
0.9 0.3 1 1 1 0.3 0 -1 0.636
0.91 0.3 1 1 1 0.5 0 -1 0.856
0.91 0.3 1 1 1 1 0.1 0 1.094
0.92 0.2 1 1 1 1 0.4 0 1.333
0.93 0.2 1 1 1 1 1 0.1 1.556
0.93 0.2 1 1 1 1 1 0.4 1.744
0.94 0.2 1 1 1 1 1 1 1.882
0.95 0.2 0.5 1 1 1 1 1 1.956
1 0.1 0.4 1 1 1 1 1 1.956
1 0.1 0.4 1 1 1 1 1 1.877
1 0.1 0.3 0.5 1 1 1 1 1.717
1 0.1 0.2 0.4 1 1 1 1 1.481
1 0.1 0.2 0.3 0.4 1 1 1 1.176
1 0 0.1 0.2 0.3 0.4 0.4 1 0.817
1 0 0.1 0.1 0.1 0.2 0.2 0.3 0.418
1 ### ### ### ### ### ### ### ###
1 0 0 0 0 0 0 0 -0.42
1 0 0 0 0 0 0 -1 -0.82
1.02 0 0 0 0 -1 -1 -1 -1.18
1 0 0 0 -1 -1 -1 -1 -1.48
1 0 0 -1 -1 -1 -1 -1 -1.72
1.04 0 0 -1 -1 -1 -1 -1 -1.88
1 0 0 -1 -1 -1 -1 -1 -2
1.05 0 0 -1 -1 -1 -1 -1 -2
1.06 0 -1 -1 -1 -1 -1 -1 -1.88
1.07 0 -1 -1 -1 -1 -1 0 -1.74
1.07 0 -1 -1 -1 -1 -1 0 -1.56
1.08 0 -1 -1 -1 -1 0 0.1 -1.33
1.09 0 -1 -1 -1 -1 0 0.4 -1.09
1.09 0 -1 -1 -1 0 0.1 1 -0.86
1.1 0 -1 -1 -1 0 0.3 1 -0.64
1.11 0 -1 -1 -1 0 1 1 -0.45
1.11 0 -1 -1 -1 0.1 1 1 -0.3
1.12 0 -1 -1 0 0.2 1 1 -0.21
1.13 0 -1 -1 0 0.4 1 1 -0.17
1.13 0 -1 -1 0 1 1 1 -0.19
1.14 0 -1 -1 0 1 1 1 -0.26
1.15 0 -1 -1 0.1 1 1 0.3 -0.37
1.15 0 -1 -1 0.2 1 1 0 -0.51
1.16 0 -1 -1 0.4 1 1 0 -0.66
1.17 -1 -1 0 1 1 0.5 -1 -0.82
1.17 -1 -1 0 1 1 0.3 -1 -1
1.18 -1 -1 0 1 1 0.1 -1 -1.09
1.19 -1 -1 0 1 1 0 -1 -1.18
1.19 -1 -1 0 1 1 0 -1 -1.23
1.2 -1 -1 ### 1 1 -1 -1 -1.23
1.21 -1 -1 0.1 1 0.4 -1 -1 -1.18
1.21 -1 -1 0.2 1 0.2 -1 -1 -1.1
1.22 -1 -1 0.3 1 0.1 -1 0 -1
1.23 -1 -1 0.4 1 0 -1 0 -0.83
1.23 -1 -1 0.5 1 0 -1 0.1 -0.67
1.24 -1 -1 1 1 0 -1 0.4 -0.51
1.25 -1 -1 1 1 -1 -1 1 -0.36
1.25 -1 -1 1 1 -1 -1 1 -0.24
1.26 -1 -1 1 1 -1 0 1 -0.16
1.27 -1 -1 1 0.4 -1 0 1 -0.13
1.27 -1 -1 1 0.3 -1 0 1 -0.14
1.28 -1 0 1 0.1 -1 0.2 1 -0.21
1.29 -1 0 1 0 -1 0.5 1 -0.34
1.29 -1 0 1 0 -1 1 1 -0.5
1.3 -1 0 1 0 -1 1 0.3 -0.71
1.31 -1 0 1 0 -1 1 0 -0.93
1.31 -1 0 1 -1 -1 1 0 -1.17
1.32 -1 0 1 -1 0 1 0 -1.4
1.33 -1 0 1 -1 0 1 -1 -1.62
1.33 -1 ### 1 -1 ### 1 -1 -1.8
1.34 -1 0.1 1 -1 0.2 1 -1 -1.94
1.35 -1 0.1 1 -1 0.4 1 -1 -2
1.35 -1 0.2 1 -1 1 0.3 -1 -2.07
1.36 -1 0.2 1 -1 1 0.1 -1 -2
1.37 -1 0.3 1 -1 1 0 -1 -2
1.37 -1 0.4 0.4 -1 1 0 0 -1.83
1.38 -1 0.4 0.3 -1 1 -1 0 -1.65
1.39 -1 0.5 0.2 -1 1 -1 0.1 -1.45
1.39 -1 1 0.1 -1 1 -1 0.3 -1.22
1.4 -1 1 ### -1 1 -1 1 -1
1.41 -1 1 0 0 1 -1 1 -0.76
1.41 -1 1 0 0 1 -1 1 -0.55
1.42 -1 1 0 0 1 -1 1 -0.36
1.43 -1 1 0 0 0.5 -1 1 -0.21
1.43 -1 1 0 0.1 0.3 -1 1 -0.09
1.44 -1 1 -1 0.2 0.1 0 1 -0.01
1.45 -1 1 -1 0.4 0 0 1 0.036
1.45 -1 1 -1 1 0 0 0.3 0.049
1.46 -1 1 -1 1 0 0.2 0.1 0.037
1.47 -1 1 -1 1 -1 0.4 0 0.007
1.47 -1 1 -1 1 -1 1 0 -0.03
1.48 -1 1 -1 1 -1 1 -1 -0.07
1.49 -1 1 -1 1 -1 1 -1 -0.11
1.49 -1 1 -1 1 -1 1 -1 -0.13
1.5 -1 1 -1 1 -1 1 -1 -0.14
1.51 -1 1 -1 1 -1 1 -1 -0.13
1.51 -1 1 -1 1 -1 1 -1 -0.11
1.52 -1 1 -1 1 -1 1 -1 -0.07
1.53 -1 1 -1 1 -1 1 0 -0.03
1.53 -1 1 -1 1 -1 0.4 0 0.007
1.54 -1 1 -1 1 0 0.2 0.1 0.037
1.55 -1 1 -1 1 0 0 0.3 0.049
1.55 -1 1 -1 0.4 0 0 1 0.036
1.56 -1 1 -1 0.2 0.1 0 1 -0.01
1.57 -1 1 -1 0.1 0.3 -1 1 -0.09
1.57 -1 1 0 0 0.5 -1 1 -0.21
1.58 -1 1 0 0 1 -1 1 -0.36
1.59 -1 1 0 0 1 -1 1 -0.55
1.59 -1 1 0 0 1 -1 1 -0.76
1.6 -1 1 ### -1 1 -1 1 -1
1.61 -1 1 0.1 -1 1 -1 0.3 -1.22
1.61 -1 0.5 0.2 -1 1 -1 0.1 -1.45
1.62 -1 0.4 0.3 -1 1 -1 0 -1.65
1.63 -1 0.4 0.4 -1 1 0 0 -1.83
1.63 -1 0.3 0.5 -1 1 0 -1 -2
1.64 -1 0.2 1 -1 1 0.1 -1 -2
1.65 -1 0.2 1 -1 1 0.3 -1 -2.07
1.65 -1 0.1 1 -1 0.4 1 -1 -2
1.66 -1 0.1 1 -1 0.2 1 -1 -1.94
1.67 -1 ### 1 -1 ### 1 -1 -1.8
1.67 -1 0 1 -1 0 1 -1 -1.62
1.68 -1 0 1 -1 0 1 0 -1.4
1.69 -1 0 1 -1 -1 1 0 -1.17
1.69 -1 0 1 0 -1 1 0 -0.93
1.7 -1 0 1 0 -1 1 0.3 -0.71
1.71 -1 0 1 0 -1 1 1 -0.5
1.71 -1 0 1 0 -1 0.5 1 -0.34
1.72 -1 0 1 0.1 -1 0.2 1 -0.21
1.73 -1 -1 1 0.3 -1 0 1 -0.14
1.73 -1 -1 1 0.4 -1 0 1 -0.13
1.74 -1 -1 1 1 -1 0 1 -0.16
1.75 -1 -1 1 1 -1 -1 1 -0.24
1.75 -1 -1 1 1 -1 -1 1 -0.36
1.76 -1 -1 1 1 0 -1 0.4 -0.51
1.77 -1 -1 1 1 0 -1 0.1 -0.67
1.77 -1 -1 0.4 1 0 -1 0 -0.83
1.78 -1 -1 0.3 1 0.1 -1 0 -1
1.79 -1 -1 0.2 1 0.2 -1 -1 -1.1
1.79 -1 -1 0.1 1 0.4 -1 -1 -1.18
1.8 -1 -1 ### 1 1 -1 -1 -1.23
1.81 -1 -1 0 1 1 0 -1 -1.23
1.81 -1 -1 0 1 1 0 -1 -1.18
1.82 -1 -1 0 1 1 0.1 -1 -1.09
1.83 -1 -1 0 1 1 0.3 -1 -1
1.83 -1 -1 0 1 1 0.5 -1 -0.82
1.84 0 -1 -1 0.4 1 1 0 -0.66
1.85 0 -1 -1 0.2 1 1 0 -0.51
1.85 0 -1 -1 0.1 1 1 0.3 -0.37
1.86 0 -1 -1 0 1 1 1 -0.26
1.87 0 -1 -1 0 1 1 1 -0.19
1.87 0 -1 -1 0 0.4 1 1 -0.17
1.88 0 -1 -1 0 0.2 1 1 -0.21
1.89 0 -1 -1 -1 0.1 1 1 -0.3
1.89 0 -1 -1 -1 0 1 1 -0.45
1.9 0 -1 -1 -1 0 0.3 1 -0.64
1.91 0 -1 -1 -1 0 0.1 1 -0.86
1.91 0 -1 -1 -1 -1 0 0.4 -1.09
1.92 0 -1 -1 -1 -1 0 0.1 -1.33
1.93 0 -1 -1 -1 -1 -1 0 -1.56
1.93 0 -1 -1 -1 -1 -1 0 -1.74
1.94 0 -1 -1 -1 -1 -1 -1 -1.88
1.95 0 0 -1 -1 -1 -1 -1 -2
2 0 0 -1 -1 -1 -1 -1 -2
2 0 0 -1 -1 -1 -1 -1 -1.88
2 0 0 -1 -1 -1 -1 -1 -1.72
2 0 0 0 -1 -1 -1 -1 -1.48
2 0 0 0 0 -1 -1 -1 -1.18
2 0 0 0 0 0 0 -1 -0.82
2 0 0 0 0 0 0 0 -0.42
2 ### ### ### ### ### ### ### ###
a transformadores

Forma de Onda

0.8 1 1.2 1.4 1.6 1.8 2

Espectro

5 7 9 11 13
Armónico

2
 In 
  n
2

 I 
2
 In 
2
In  In 
2
 In 
  n
2
   I 
 I1  I    I 
1 1 1 1
0.25 0.5 0.25 2.25
0 0 0 0
0.5184 0.72 0.5184 25.4016
0 0 0 0
0.1089 0.33 0.1089 13.1769
0.4761 0.69 0.4761 80.4609

116.34 Factor K 122.2894

Basado en la norma IEEE 519

Algunos Valores Tipicos de K

Fuente:
Nota tecnica 2
Ing. Mauricio Ardón.
FASOR, S.A. de C.V.
Transformadores en Delta Abierta

Voltaje de línea Primario:


13.8 kV

Voltaje de línea Secundario:


480 V

Potencia de cada TX monofasico:


25 kVA

Potencia Trifasica nominal:


43.28 kVA

Corriente Nominal Primario:


1.81 A

Corriente Nominal Secundario:


52.08 A
Ampacidad de Cables
Basado en IEEE 339-1997

1.- Factor de corrección por temperatura del ambiente y del conductor

Parametros Base:
En base a Tc=90 y Ta=20

Temperatura del Cable (TC): Temperatura Ambiente (TA):


A 90 ºC 30 ºC

Ft = 0.93

2.- Factor de corrección por resistividad térmica

Tipo de Instalación:
Cable hasta 1000V en ducto subterráneo

Tamaño del Conductor


B #12 – #1 AWG / MCM

Cantidad de Circuitos
1

Resistividad térmica del Suelo


140
º C  cm
W

Fth = 0.96

3.- Factor de Agrupamiento


Configuracion:
Cables de 0 a 5000 V 3/C, o Triples en bancada de ductos de 5" de diámetro y separación de 7.5" centro a centro.

Calibre del Cable:


B #8 AWG / MCM

Numero de Filas (Capas):


2

Numero de Columnas:
2

Fth = 0.84

Cable a emplear

Según Tabla 310.16 CEN 2004


B 12

Temperatura de Operación Normal

A 90°C

Capacidad Nominal: Capacidad Final de C

30 A

A: Verifique que las temperaturas sean similares


B: Verifique que los calibres sean iguales
3

o
separación de 7.5" centro a centro.

Factor de corrección
F  Ft  Fth  Fg
F = 0.93 X 0.96 X 0.84

F= 0.749952

Capacidad Final de Conductor

22.499 A
Calculo de Corriente máxima de Corto Circuito

Calibre del Cable: 250mcm

Área: 250000 CMIL

Frecuencia: 60 Hz

Duración del Corto C: 100 Ciclos


1.67 Seg

Temp. De Operación: 90 ºC

Temp. Max Corto C: 250 ºC

Corriente de CC: 13.93 kA


Formula Aplicada

 T  234 
0, 0297 log  2
 T1  234 
Icc  A
t
Donde:

Icc: Corriente de Corto Circuito


A: Área del Conductor en MCM
t: Tiempo de Corto Circuito en seg.
T1: Temperatura de operación del cable
T2: Temperatura Max. De Corto Circuito

Fuente: Okonite
Canalizacion
Tamaño 4"
Tuberia No Metalica Electrica

Diametro 0 mm
Area total 0.00 mm2

Area 31% 0.00 mm2


Area 40% 0.00 mm2
Area 53% 0.00 mm2

Tuberia Metalica Tuberia No Tubo Metalico Tubo Metalico


Tamaño
Electrica Metalica Electrica Flexible Intermedio IMC

3/8 0 0 9.7 0
1/2 15.8 14.2 16.1 16.8
3/4 20.9 19.3 20.9 21.9
1 26.6 25.4 25.9 28.1
1 1/4 35 34 32.4 36.8
1 1/2 40.9 39.8 39 42.7
2 52.5 51.3 51.8 54.6
2 1/2 69.4 0 63.5 64.9
3 85.2 0 76.2 80.7
3 1/2 97.4 0 88.9 93.2
4 110 0 101.6 105.8
5 0 0 0 0
6 0 0 0 0
Tubo No Flexible Tubo No Flexible
Tubo No Flexible
hermetico a los hermetico a los Tubo Metalico Tubo de PVC
hermetico a los
liquidos (Tipo liquidos (Tipo Rigido Rigido, Sch. 80
liquidos
FNMC-B) FNMCA-A*)

12.5 12.6 12.5 0 0


16 16 16 16 13.4
21.1 21 21.1 21.2 18.3
26.8 26.5 26.8 27 23.8
35.4 35.1 35.4 35.4 31.9
40.3 40.7 40.3 41.2 37.5
51.6 52.4 51.6 52.9 48.6
0 0 63.3 63.2 58.2
0 0 78.3 78.5 72.7
0 0 89.4 90.7 84.5
0 0 102.1 102.9 96.2
0 0 0 128.8 121.1
0 0 0 154.8 145
Tubo de PVC
Tubo de PVC, Tubo de PVC,
Rigido, Sch. 40 y
Tipo A Tipo EB
tubo de PE-AD

0 0 0
15.2 17.8 0
20.4 23.1 0
26.1 29.8 0
34.5 38.1 0
40.4 43.7 0
52 54.7 56.4
62.1 66.9 0
77.3 82 84.8
89.4 93.7 96.6
101.5 106.6 108.9
127.4 0 135
153.2 0 160.9
CALIBRE AISLANTE Cant Cables
14 THW 1

Diametro 4.14 mm
Area 13.49 mm2
Area Total 13.49 mm2

CEN 1999 Tabla 5


THW TW THHN
Calibre Diametro Seccion mm2 Diametro Seccion mm2 Diametro
18 0 0.00
16 0 0.00
14 4.14 13.49 3.38 8.99 2.82
12 4.62 16.80 3.86 11.73 3.3
10 5.23 21.53 4.47 15.73 4.16
8 6.76 35.98 5.99 28.25 5.48
6 7.72 46.92 6.45
4 8.94 62.92 8.23
3 9.65 73.32 8.94
2 10.46 86.14 9.75
1 12.5 123.02 11.33
1/0 13.51 143.70 12.34
2/0 14.68 169.67 13.51
3/0 16 201.55 14.83
4/0 17.47 240.28 16.3
250 19.43 297.23 18.06
300 20.83 341.60 19.45
350 22.12 385.22 20.75
400 23.31 427.78 21.94
500 25.47 510.74 24.1
600 28.27 629.20 26.69
700 30.07 711.88 28.5
750 30.93 753.18 29.36
800 31.75 793.65 30.17
900 33.37 876.70 31.8
1000 34.85 956.19 33.27
1250 39.09 1203.02
1500 42.21 1402.72
1750 45.11 1602.09
2000 47.8 1798.85
Resistencia y reactancia de conductores
Calibre: 250 Conductore por fase 1
Mat. de la tuberia: Aluminio
Distancia: 2000 M
Resistencia 0.187 Ohm/kM R: 0.374
Reactancia 0.135 Ohm/kM X: 0.270
CALIBRE TEMP. MATERIAL COR. Temp.
8 75°C COBRE 36-40

Cap. Nominal 50 A
Factor Correc. 0.88

Capacidad 44 A
Tabla 310.16 CEN 1999

Ampacidades admisibles de los conductores aislados para tensiones nominales de 0 a 2000 V y


60°c a 90°c con no mas de tres conductores portadores de corriente en una canalización, cable
o directamente enterrados, basadas en una temperatura ambiente de 30°c

Calibre COBRE ALUMINIO


60°C 75°C 90°C 60°C 75°C 90°C
TBS, SA,
SIS, FEP*, TBS, SA,
FEPB*, MI, SIS, THHN*,
RHH*, THHW*,
FEPW*,
RHW-2, RH*, RHW*, THW-2,
RH*, RHW*,
THHN*, THHW*, THWN-2,
THHW*,
THHW*, THW*, RHH*,
AWG/kcmil TW*, UF* THW*, TW*, UF*
THW-2*, THWN*, RHW-2,
THWN*,
THWN-2*, XHHW*, USE-2,
XHHW*,
USE-2, USE* XHH,
USE*, ZW*
XHH, XHHW,
XHHW*, XHHW-2,
XHHW-2, ZW-2
ZW-2
18 0 0 14 0 0 0
16 0 0 18 0 0 0
14 20 20 25 0 0 0
12 25 25 30 0 20 25
10 30 35 40 25 30 35
8 40 50 55 30 40 45
6 55 65 75 40 50 60
4 70 85 95 55 65 75
3 85 100 110 65 75 85
2 95 115 130 75 90 100
1 110 130 150 85 100 115
1/0 125 150 170 100 120 135
2/0 145 175 195 115 135 150
3/0 165 200 225 130 155 175
4/0 195 230 260 150 180 205
250 215 255 290 170 205 230
300 240 285 320 190 230 255
350 260 310 350 210 250 280
400 280 335 380 225 270 305
500 320 380 430 260 310 350
600 355 420 475 285 340 385
700 385 460 520 310 375 420
750 400 475 535 320 385 435
800 410 490 555 330 395 450
900 435 520 585 355 425 480
1000 455 545 615 375 445 500
1250 495 590 665 405 485 545
1500 520 625 705 435 520 585
1750 545 650 735 455 545 615
2000 560 665 750 470 560 630

TEMP AMB.
21-25 1.08 1.05 1.04 1.08 1.05 1.04
26-30 1 1 1 1 1 1
31-35 0.91 0.94 0.96 0.91 0.94 0.96
36-40 0.82 0.88 0.91 0.82 0.88 0.91
41-45 0.71 0.82 0.87 0.71 0.82 0.87
46-50 0.58 0.75 0.82 0.58 0.75 0.82
51-55 0.41 0.67 0.76 0.41 0.67 0.76
56-60 0.58 0.71 0.58 0.71
61-70 0.33 0.58 0.33 0.58
71-80 0.41 0.41
CALIBRE TEMP. Tension
2 90°C 2001-5000 V

Cap. Nominal 130 A

Capacidad 130 A
Tabla 310.73 CEN 1999
Ampacidades de cables triples aislados o de tres conductores de
cobre sencillos, en un conducto físicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90°C en una temperatura
ambiente de 40°C
Calibre 2001-5000 V 5001-35000 V
AWG/kcmil 90°C 105°C 90°C 105°C
8 55 61
6 75 84 83 93
4 97 110 110 120
2 130 145 150 165
1 155 175 170 190
1/0 180 200 195 215
2/0 205 225 225 255
3/0 240 270 260 290
4/0 280 305 295 330
250 315 355 330 365
350 385 430 395 440
500 475 530 480 535
750 600 665 585 655
1000 690 770 675 755
CALIBRE TEMP. Tension
4/0 90°C 5001-35000 V

Cap. Nominal 230 A

Capacidad 230 A
Tabla 310.74 CEN 1999
Ampacidades de cables triples aislados o de tres conductores de
aluminio sencillos, en un conducto físicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90°C en una temperatura
ambiente de 40°C
Calibre 2001-5000 V 5001-35000 V
AWG/kcmil 90°C 105°C 90°C 105°C
8 43 48
6 58 65 65 72
4 76 85 84 94
2 100 115 115 130
1 120 135 130 150
1/0 140 155 150 170
2/0 160 175 175 200
3/0 190 210 200 225
4/0 215 240 230 260
250 250 280 255 290
350 305 340 310 350
500 380 425 385 430
750 490 545 485 540
1000 580 645 565 640
A
AAC
AACS
AC
ACSR
ACSR-AG AL
ACSR-AW
AF

Al
Alta frecuencia
AM
Amplitud
Ancho de
banda
Apertura
numérica
Armadura

Atenuación

ATM

AW

AWG

AWM
Baja Frecuencia

Bel
BIL
Bit
Blindaje

C
c.a.

c.c.
c.d.
Capacitador

Capacitancia

Capacitancia
mutua
Capacitor

CATV

CCS
CCTV
Circuito en serie

Circuito paralelo

CL2
CL3
CM
Conductividad

Constante
dieléctrica
CP
CPE
CSA

Cu
CuSn
CV
CW
CXC
DCS
DGN
Diafonía
Dieléctrico
Dispersión
Dispersión
cromática

Dispersión
modal
DIT
DRS
DS

Efecto piel

EIA/TIA
Electromagnétic
o
EP(R)

EPDM
f

FA
Fan-out

Fase
FCC
FDDI
FEP

FM
FOA
FOW
FTP

G
G-GC

Glosario de términos relacionados con conductores eléctricos y cables para telecomunicaciones


H

HDPE
Higroscópico

Hilo dren
HMWP
HP
HPN

HPOF

Hz
I
I2R
IACS

ICEA

IEC

IEEE

Iexc
Impedancia

Indice de
refracción
Inductancia

ISO
ITU
Jumper
kCM

kV
l
LAN
LDPE
Línea
balanceada
Línea de
transmisión
Longitud de
onda de Malla
lpi Longitudinal

lpof
m.s.n.m
Malla
Mc
Mi

MIC

mp

mp-gc
MTW
Multimodo

Multiplexar
MV
mw
NEC
Neopreno
NFPA

NM

NM-B o NMC-B

NMC
NMX
NOM

Non break out

NZ

OA
Ohm

OTDR

OW
Pantalla
PCC
PCG

PCM
PE
Pérdidas por
doblez
PFA

PFAH
PG

Pig-tail
PILC
Plástico
Plastificante
Plenum
PMD

Polietileno
celular
Polilam

Polímero

POT
psi
PVC
PVDF

RDI
REA (RUS)

Reactancia

Resistencia a la
abrasión
RG/U
RH/RW

RHH
RHW

RHW-2
SA
SBR
SDH
SE
SF

SFF
SH

SHD

SHD-GC SHD.

SIC

SIS

SJ
SJO
SJT SJ

SMT
SNM

SO

SONET
SPT

ST

STP

SU
SV

SVT
SVTO
TA

TAGA

TAGT
TC

TEFLON*
TF

TFE
TFF
TFFN
TFN
THHN

THHW

THW1

THW-21
THWN

TP

TPT TP
TTU
TW

UD
UF

UHF
UL

Unimodo

URD

USE

USG
UTP
V
VA
Velocidad de la
luz
Velocidad de
propagación
VHF
Volt

VW-1
W

WDM

XHHW

XHHW-2
XLP

XT
Ampere: Unidad utilizada para denominar la intensidad de corriente eléctrica.
All Aluminum Conductor: conductor o cable de hilos de aluminio.
Aluminum Alloy Standed Conductor: cable de aleación de aluminio.
Armored Cable: cables provistos de una armadura metálica flexible.
Aluminum Conductor Steel Reinforced: conductor de aluminio con centro de acero galvanizado.
ACSR con aleación de aluminio para alta temperatura (150°C) y acero de alta resistencia. Símbolo del al
ACSR con centro de acero recubierto con aluminio (Alumo-Weld). También conocido como ACSR-AS.
Audio Frecuencia: Rango de frecuencias que caen dentro del rango perceptible del oído humano: aproxim
20 a 20, 000 Hz
Símbolo del aluminio.
La banda de 3 MHz a 1 GHz.
Amplitud Modulada.
El valor máximo de variación de una onda.
Es la diferencia entre los valores superior e inferior de una banda de frecuencias dada. Se expresa en He

Es la medida de aceptación angular de una fibra óptica, que es aproximadamente el seno de la mitad del
cono de aceptación de la fibra.
Cinta corrugada de acero que tiene la función de proteger el cable contra maltrato mecánico y ataque de
aplicaciones especiales se llegan a usar armaduras de cinta engargolada o de alambres de acero.

Es el decremento en magnitud de una onda mientras esta viaja en medio transmisor, sea un cable o un c
atenuación se mide como una razón o como logartimo de la razón (decibel).
Siglas en inglés para la técnica de codificación y conmutación en bloques llamada Asynchronous Transfe
permite multiplexar señales de velocidades distintas en un mismo canal digital.
American Wire Gauge: escala de calibres americanos para alambres y cables, también conocida como b
and Sharpe) Wire Gauge.
American Wire Gauge: Escala de calibres americanos para alambres y cables, también conocida como B
and Sharpe) Wire Gauge.
Appliance Wiring Material: Conductores destinados al alambrado interno de aparatos electrodomésticos.
La banda de 30-300 KHz.

Es una unidad que representa el logaritmo de la razón de dos niveles.


Basic Impulse Insulation Level: nivel básico de aislamiento al impulso.
Es un dígito binario.
Capa conductiva en un cable que tiene la función de reducir la interferencia electomagnética. Puede ser u
alambres, una cinta metálica o una cinta plástica metalizada.
Símbolo de capacitancia y grados centígrados.
Corriente alterna: Es una corriente que períodicamente revierte la dirección del flujo de electrones. La raz
un ciclo completo ocurre por unidad de tiempo (normalmente un segundo) se le denomina frecuencia de

Corriente continua (ver c.d.)


Corriente directa: Es la corriente eléctrica donde los electrones fluyen en una sola dirección.
Dos superficies conductoras separadas por un material dieléctrico. La capacitación es determinada por e
superficies, tipo de dieléctrico y el espaciamiento entre los conductores.
Es la propiedad que tiene un material dieléctrico situado en medio de dos conductores de almacenar elec
cuando existe una diferencia de potencial entre los conductores. La unidad de medida es el Farad, que e
capacitancia que almacenará una carga de un Cuolomb cuando exista una diferencia de potencial de un
conductores.
Es la capacitancia que existe entre dos concluctores cuando los demás conductores están conectados en

Dos superficies conductoras separadas por un material dieléctrico. La capacitancia es determinada por e
superficies, tipo de dieléctrico y el espaciamiento entre los conductores.
Community Antena TeleVision: término empleado para los cables coaxiales destinados a los sistemas de
comunitaria.
Siglas en lnglés para conductores de acero cubierto cle cobre (Copper Cladded Steel).
Circuito Cerrado cle TeleVisión.
Es un circuito cuyos componentes distribuidos a lo largo de camino común.

Es un circuito en el cual un mismo voltaje se presenta en todos los componentes, con corriente dividida e
acuerdo a su resistencia o impedancias.
Cables para circuitos Clase 2, según NEC-725, bajo voltaje y potencia.
Idem a CL2, para 300 volts máximo, bajo potencia.
Circular Mil: área de un circuito con un diámetro de 1/1000 de pulgada.
La capacidad de un material para permitir el flujo de electrones, medido por la corriente por unidad de vo
Es el recíproco de la resistividad.
También se llama permitividad. Es aquella propiedad del dieléctrico que determina la cantidad de energía
electróstatica que puede almacenarse cuando es aplicado un voltaje.
Caballos de Potencia: también conocido como HP.
Chlorinated PolyEthylene: polietileno clorado.
Canadian Standard Association: Institución canadiense para la certificación de equipo eléctrico y electrón
las normas que ellos mismos publican.
Símbolo del cobre.
Símbolo que denota cobre estañado.
Continuous Vulcanization: proceso de vulcanización en línea con la extrusión.
CopperWeld: varilla de acero, con recubrimiento de cobre.
Designación de cable coaxial por CSA (Canadian Standars Association).
Cables para Distribución Comercial Subterránea.
Dirección General de Normas de la Secretaría de Comercio y Fomento Industrial.
Transferencia no deseada de señal entre distintos canales de un equipo a cable.
Es un medio aislante (no-conductivo).
Fenómeno por el cual componentes de la luz transmitida por la fibra sufren retrasos distintos. Es la suma
efectos, principalmente dispersión modal y dispersión cromática. Puede limitar la velocidad de transmisió
Es el retraso diferente que sufren las distintas longitudes de onda que componen a luz portadora, por ten
velocidades distintas en la fibra. En fibras con diseño estándar la dispersión cromática tiene un valor mín
la ventana de 1310 nm.
Es el retraso diferente que presentan los modos de propagación en una fibra multimodo por viajar en áng
distintos, no existe en las fibras unimodo en las que se transmite un modo de propagación.
Dispositivo de Interconexión Terminal: es el límite entre la red pública y la que es responsabilidad del usu
Cables para Distribución Residencial Subterránea (tipo URD).
Siglas en inglés para dispersión corrida, son las fibras unimodo con dispersión mínima enla ventana de 1

Es la tendencia que tiene la corriente alterna de viajar en el perímetro del conductor con el incremento de
frecuencia.
Asociación de las industrias electrónica y de comunicaciones en EUA.
Se reflere a la combinación de campos eléctricos y magnéticos originado por el movimiento de los electro
conductor.
Fluorinated Ethylene Propylene: aislamiento de etileno-propileno fluorado.Ethylene Propylene (Rubber): a
base de etileno-propileno.
Ethylene Propylene Dionomer: etileno-propileno dieno monómero.
Frecuencia: El número de veces que una acción periódica ocurre en un lapso de tiempo: Es el número de
que una corriente eléctrica completa 1 seg.
Forced Air: enfriamiento con aire forzado.
Cable óptlco para conectorizar, que permite separar las fibras individuales sin necesidad de darles protec
adicional.
Es la relación angular entre ondas.
Flexible Control Cable: cable control, flexible.
Fiber Distribution Digital Interface: especificación para la red de datos 100% óptica a 100 Mb/s.
Nombre abreviado para tetrafluoruroetileno-exafluoruropropileno, material aislante con excelentes propie
eléctricas y químicas que se usan en cables categoría plenum.
Frecuencia modulada.
Forced Oil and Air: enfriamiento con aceite forzado y aire.
Forced Oil and Water: enfriamiento con aceite forzado y agua.
Foiled Twisted Pair: cables multipares para datos blindados por medio de una cinta plástica aluminizada

Ground: cable flexible para minas con conductores para conexión a tierra, 600 ó 2000 volts.
Ground-Ground Check: cable flexible para minas, con conductores para conexión a tierra y un conductor
verificar la continuidad de los conductores de tierra, 600 ó 2000 volts.
rio de términos relacionados con conductores eléctricos y cables para telecomunicaciones
Henry: Es la unidad práctica de inductancia que producirá un incremento de voltaje de 1 Volt cuando la c
cambie a razón de un ampere/seg.
High Density PolyEthylene (PE): polietileno de alto densidad.
Propiedad de algunos materiales de absorber agua del ambiente. Las cintas e hilos usados en cables no
hacerlo.
Es un alambre desnudo que está en contacto con el blindaje del cable a lo largo de toda su longitud.
High Molecular Weight Polyethylene: polietileno de alto peso molecualr.
Horse Power: caballo de potencia.
Heater Cord Parallel Neoprene: cordón paralelo de dos conductores flexibles con aislamiento elastoméric
aparatos electrodomésticos resistentes al calor, 90 °C, 600 volts.
High Pressure Oil Filled: cables tipo Pipe (tubo) de alta tensión con aislamiento de papel impregnado inst
de un tubo de acero con aceite a alta presión.
Hertz: Es la unidad de medida de frecuencia: 1 ciclo por segundo.
Símbolo utilizado para designar corriente.
Fórmula de potencia en Watts, donde I=corriente en amperes, R=resistencia en Ohms.
International Annealed Copper Standard: patrón internacional para la conductividad del cobre (igual al 10
cobre electrolítico recocido).
Insulated Cable Engineers Association: nombre actual de IPCEA (Power), asociación norteamericana par
normalización de conductores eléctricos.
International Electrotechnical Commission: organización internacional encargada de la normalización de p
eléctricos.
Institute of Electrical and Electronic Engineers: principal asociación a nivel mundial de ingenieros en elect
electrónica y materias afines.
Corriente de excitación.
Es la oposición total de un circuito, cable, o algún componente al paso de la corriente alterna. Esta incluy
resistencia y a la reactancia. La unidad de medida es el Ohm y su símbolo es la Z.
Es un promedio del índice de refracción para las longitudes de onda en la ventana de transmisión; es un
necesario que se debe conocer para medir la distancia de un enlace en un OTDR.
Es la propiedad de un conductor o un circuito que se resiste al cambio de corriente. Su unidad de medida
y su símbolo es L.
International Standards Organization: organización internacional de normalización.
International Telecomunication Union: organización para normalización internacional en
Cable para conexiones en un distribuidor, puede ser un par de cobre o una fibra Monotel con conectores.
kiloCircularMil:unidad de área del sistema norteamericano de calibres de conductores eléctricos, igual a 1
mils (CM). Anteriormente conocida como MCM.
kiloVolt: unidad de medida de tensión eléctrica igual a 1000 volts.
Símbolo utilizado para designar corriente.
Local Area Network: red de datos de corta longitud en un edificio o conjunto de edificios.
Low Density PolyEthylene (PE): polietileno de bajo densidad,
Es un cable que tiene 2 conductores idénticos con las mismas características electromagnéticas en relac
demás conductores y tierra.
Es el arreglo de dos o más conductores o una guía de onda que se utiliza para transferir señales de un lu

Es la distancia entre picos o nodos sucesivos de una onda.

Paper Insulated: proceso para la fabricación de cables telefónicos con aislamiento de papel aplicado
longitudinalmente.
Low Pressure Oil Filled: cables con aislamiento de papel impregnado tipo Autocontenidos para alta tensió
. Metros sobre el nivel del mar.
Es un grupo de filamentos metálicos entretejidos para formar una esfructura tubular la
Metal Clad: cable armado con una cubierta metálica del tipo interlock o tubo corrugado.
Mineral Insulated: cable con aislamiento mineral de óxido de magnesio y cubierta de tubo de cobre o ace
temperatura y resistencia al fuego, 90 a 250 °C.
Técnica de modulación en que la amplitud de una señal analógica en cierto momento se expresa con un
binario de 8 cifras.
Mine Power Feeder Cable: cable alimentador para minas con tres conductores de fase y tres conductores
conexión a tierra.
MP-Ground Check: MP con un conductor aislado para verificar la continuidad de los conductores de tierra
Machine Tool Wire: conductor con aislamiento termoplástico para alambrado de máquinas herramientas.
Fibras que tienen un núcleo relativamente grande (50 micras o más), que permiten transmitir varios hace
llamados modos de propagación.
Combinación de varias señales para enviarlas por un solo canal de transmisión.
Medium Voltage Cable: cables cona aislamiento sólido para tensiones de 2001 a 35,000 volts.
Micro m Wave: microonda.
Natinal Electrical Code: Norma general sobre productos e instalaciones
Policloropreno, hule sintético empleado como aislamiento y cubierta de cables flexibles.
National Fire Protection Association: asociación americana para la protección contra incendios responsab
publicación del NEC.
Non-Metallic Sheathed Cable: conductores aislados y con cubierta no metálica resistente a la humedad, r
la flama; sugerido para ambientes secos.
NM o NMC con aislamiento de THHN.

NM con cubierta elastomérica resistente a la corrosión; para ambientes secos o húmedos.


Norma Mexicana; documentos publicados por organismos privados autorizados. Son de uso voluntario.
Norma Oficial Mexicana: documentos publicados por la DGN para la normalización y especificación de pr

Cable óptico para distribución en edificios en el que las fibras no tienen protección individual para separa

Fibras ópticas de baja dispersión cromática, pero nunca igual a una de 1530 a 1560 mm, permite transmi
varios portadores (ver WDM).
Oil and Air: enfriamiento natural aire-aceite.
Es la unidad eléctrica de resistencia. Es el valor de resistencia a través del cual una diferencia de potenc
mantendrá una corriente de un ampere.
Reflectómetro óptico en dominio de tiempo, es un equipo que inyecta un pulso de luz a la fibra y detecta
reflexiones, permite medir atenuación y longitud de un enlace.
Oil and Water: enfriamiento con aceite-agua.
Vea blindaje.
Designación de CSA para los cables de uso interior (Premises Comunication Cable).
Portable Cable Control and Ground conductors: cable flexible para minas con conductores de control y pa
a tierra, 600 ó 2000 volts.
Siglas en inglés para la técnica de modulación llamada en español MIC (Modulación por Impulsos Codific
Polietileno, puede ser de los tipos HMWP,HDPE y LDPE.
Es la forma que toma la curva de atenuación que es causada por: a)Una fibra óptica curveada alrededor
de curvatura cerrado, o b) Microdobleces causados por esfuerzo mecánico de la fibra.
PerFluoro-Alkoxy: cables para alta temperatura; ambiente seco, con aislamiento de Perfluoro-Alkoxy, has

PerFluoro-Alkoxy Heat: PFA con temperaturas mayores de hasta 250 °C.


Portable Cable Ground Conductor: cable flexible para minas con conductores de fase y para conexión a t
2000 volts.
Fibra óptica Monotel con conector en una punta.
Papel Insulated Lead Cover: cable para media tensión aislado con papel impregnado y con cubierta de p
Sustancia poliméricas que incluyen tanto materiales naturales como sintéticos.
Es un químico que se agrega al plástico pare hacerlo más suave y flexible.
Cables que cumplen con las normas de seguridad parta poder instalarse sin tubo conduit sobre el falso p
Siglas en inglés para el fenómeno de dispersión por polarización de modos, en el que existe una diferenc
velocidad entre los componentes de campo eléctrico y magnético de un mismo modo de propagación.
Técnica de introducir burbujas en el plástico del aislamiento pare bajar la capacitancia del cable.

Cinta de aluminio ó de acero con espesor entre 0. 15 y 0.2 mm que tiene un recubrimiento plástico en un
caras, lo que permite que se adhiera a la cubierta de polietileno de un cable formando una barrera contra

Es una substancia hecha de muchas unidades químicas moleculares. El término polímero es regularmen
vez de plástico, hule o elastómero.
Cordón paralelo con aislamiento termoplástico para 300 volts, 60 °C.
pounds per square inch: libras por pulgada cuadrada.
PolyVinyl Chloride: cloruro cle poli-vinilo, compuesto ampliamente usado como aislamiento y cubierta.
PolyVinyliDene Fluoride: compuesto termoplástico a base de fluor usado generalmente como cubierta en
construcción.
Red Digital Integrada; servicio de alta velocidad para grandes usuarios a través de la red pública.
Rural Electrification Administracion: oficina norteamericana del Departamento de Agricultura encargada d
normalización de equipos ofrecidos por las compañías telefónicas independientes.
Es una medida de los efectos combinados de capacitancia e inductancia en corriente alterna. Es la variac
dicha oposición tiene con la frecuencia de la corriente. Su símbolo es X.
Capacidad de resistir desgaste superficial.

Radio Frecuency Guide, Universal: designación para cables coaxiales para radiofrecuencias.
Rubber Heat, Rubber Moisture (Water): cables con aislamiento y cubierta de hules sintéticos para 75 °C e
seco y 60 °C en húmedo, 600 volts.
Rubber High Heat: cables con aislamiento y cubierta de hule sintético, para 90 °C, 600 V.
Rubber Heat Moisture (Water): cables con aislamiento y cubierta de hules sintéticos para75 °C en ambien
húmedo.
Igual a RHW pero con aislamiento de 90 °C en ambiente seco y húmedo.
Silicone Asbestos: cables aislados con hule silicón y malla de asbesto o fibra de vidrio.
Styrene Butadiene Rubber: elastómero sintético a base de Estireno y Butadieno, empleado para aislamie
de cordones flexibles, se conocía como GRS (Government Rubber Standard).
Siglas en inglés pare el sistema de transmisión óptica sincrono (Synchronous Digital Hierarchy).
Service Entrance: uno o más conductores con o sin cubierta exterior usados para alimentación de servici
Silicone Rubber Fiber Glass: alambre o cable de 7 hilos aislados con hule silicón y malla de fibra de vidrio

Silicone Rubber Fiber Glass Flexible: SF con conductor más flexible, 150 °C.
Shielded Mining Cable Single Conductor: cable monopolar flexible para minas con pantalla y cubierta par
pesado.
Shielded mining Cable with Ground Conductors: cable trifásico flexible para minas con pantalla. "D" signif
conductor de fase lleva pantalla y que el cable tres conductores para conexión a tierra.
Ground Check: SHD con un conductor aislado para el circuito de comprobación de continuidad de conexi
dos conductores de tierra.
Specific Inductive Capacity: inductancia capacitiva específica, constante dieléctrica de un material que es
que existe entre un condensador con el material como dieléctrico y el mismo condensador con aire como

Synthetic Insulated Switchboard Cable: cable para tableros con aislamiento elastomérico sintético, 90 °C,

Hard Service Cord Junior: cordón uso rudo para servicio ligero con aislamiento elastomérico, 300 volts.
SJ Oil Resistant: SJ con aislamiento resistente al aceite.
Thermoplastic: SJ con aislamiento y cubierta termoplástica, 60 °C, 300 volts (90 y105 °C con aislamiento

Construcción igual al SPT pero con conductores clase M.


Shielded Non-Metallic-Sheathed Cable: dos o más conductores aislados con un núcleo de material resist
humedad y retardante de la llama; sobre el conjunto lleva una pantalla a base de hilos y cintas; cubierta e
material no metálico resis
Service Cord Oil Resistant: cordón uso rudo para servicio pesado; aislamiento y cubierta elastomérica; la
resistente al aceite, hasta 90 °C, 600 volts.
Siglas en inglés para el sistema de transmisión óptica sincrono de EUA (Synchronous Optical NETwork)
Service Parallel Thermoplastic: cordón paralelo con aislamiento de PVC para servicio ligero, 60 °C, 300 v
105 °C con aislamiento de PVC).
Hard Service Cord Thermoplastic: cable o cordón uso rudo para servicio pesado con aislamiento y cubier
termoplástica, 60 a 105 °C, 600 volts.
Shielded Twisted Pair: cables multipares para datos, blindados con una cinta plástica aluminizada y una m
de cobre estañado.
Término empleado para denominar la tubería de PVC Subterránea.
Service Cord Vacuum Cleaner: cordón tipo uso rudo flexible para conexión de aspiradoras con aislamien
elastomérica, 60 °C, 300 volts.SV con cubierta de neopreno.
SV con aislamiento y cubierta Termoplástica, 60 a 90 °C, 300 volts.
SVT Oil Resistant: SVT con cubierta resistente al aceite, 60 °C.
Thermoplastic Asbestos: cable para alambrado de tableros con aislamiento termoplástico; carda de asbe
de algodón retardante a la llama, 90 °C, 600 volts (En desuso).
Teflón*-Asbestos-G lass-Asbestos: conductor con aislamiento de Teflón trenza de asbesto, trenza de fibr
malla de eabesto para circuitos de fuerza y control, 250 °C, 600 volts.
TAGA sustituyendo la cubierta final de asbesto por una cinta de Teflón*.
Power and Control Tray Cable: dos o más conductores aislados con o sin conductor de tierra y con una c
exterior de material no metálico, y aprobado para usarse en instalaciones en charolas, canalizaciones o s
un hilo mensajero.
Marca registrada de DuPont para el poli-tetraflouretileno, también denominado PTFE.
Thermoplastic Fixture: alambre o cable de 7 hilos para alambrado de aparatos eléctricos , aislamiento de
600 volts.
Cable para alta temperatura aislado con Teflón*, 250 °C.
TF Flexible: TF pero con conductor flexible.
Thermoplastic Fixture Flexible Nylon: TFN con conductor flexible.
TF Nylon: TF con aislamiento de PVC y cubierta de nylon, 90 °C, 600 volts.
Thermoplastic High Heat Nylon: alambre o cable con aislamiento de PVC y cubierta de nylon, 90 °C en a
600 volts.
Thermoplastic High Heat Moisture (Water) Resistant: cable aislado con PVC para 90 °C en ambientes se
en húmedos, 600 volts.
Thermoplastic Heat and Moisture (Water) Resistant: alambre o cable con aislamiento de PVC par a75 °C
ambientes secos o húmedos, 600 volts.
THW para 90 °C en ambientes secos y húmedos
THW con cubierta de nylon, resistente a la humedad, aceites e hidrocarburos, 75 °C en ambientes húmed
volts.
Tinsel Cord Parallel: dos conductores paralelos extraflexibles con aislamiento y cubierta elastomérica par
en dispositivos de hasta 50 watts.
Thermoplastic: TP pero con aislamiento y cubierta termoplásticos, 125 volts.
Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground
Thermoplastic Building Wire Moisture (Water) Resistant: alambre o cable aislado con PVC resistente a la
°C, 600 volts.
Underground Distribution: cables para distribución subterránea, también conocidos como cables DS.
Underground Feeder: cable de uno o varios conductores con aislamiento y cubierta termoplástica para ac
subterráneas en baja tensión.
Ultra High Frequency: ultra alto frecuencia. Es la banda de 300 a 3000 MHz.
Underwrites Laboratories, Inc.: institución (privada) dedicada al reconocimiento y aprobación de producto
electrónicos, acorde a sus propias normas.
Fibras que tienen un núcleo pequeño que permite transmitir un solo haz luminoso llamado modo de propa

Underground Residential Distribution: cables de distribución residencial subterránea, también conocidos c

Underground Service Entrance: cable para acometidas subterráneas en baja tensión, aislamiento y cubie
elastoméricas.
United States Standard Gauge: escala para calibres de lámina de acero.
Unshielded Twisted Pair: cables multipares para datos, sin blindaje.
Volt: unidad utilizada para denominar tensión eléctrica.
Volt Ampere: unidad de potencia aparente para transformadores.
2.998x108 m/seg.
La velocidad de transmisión de la energía eléctrica en una longitud de cable comparado con la velocidad
en el aire. Se estima generalmente en porcentaje.
Very High Frecuency: extra alta frecuencia, 30 a 300 MHz.
Es la unidad de tensión eléctrica: 1 Volt será la tensión eléctrica que causará que 1 ampere de corriente f
de una resistencia de 1 Ohm.
Vertical Wire Flame Test: prueba de resistencia a la flama colocando el especimen en posición vertical.
Cables flexibles para minas: redondos o planos de uno o varios conductores con aislamiento y cubiertas
para servicio extrapesado.
Siglas en inglés para la multiplexación por división de longitud de onda. En estos sistemas se transmiten
simultánea varias longitudes de onda independientes.
Cross (X)-Linked Polyethylene High Heat and Moisture (Water) Resistant: cable con aislamiento de poliet
cadena cruzada, 90 °C ambiente seco y 75 °C en ambiente húmedo, 600 volts.
XHHW para 90 °C en ambientes secos y húmedos.
Cross (X)-Linked Polyethylene: polietileno de cadena cruzada, también conocida como polietileno vulcan
XLPE.
Xmas Tree Cord: cordón paralelo, dos conductores aislados con PVC para series de árboles de navidad.
CÁLCULOS ELÉCTRICOS

Ing. FIDEL MORENO


fidelsmc@gmail.com
Maracaibo - Venezuela

Version

Dedicado a Jessica
LÉCTRICOS

Ing. FIDEL MORENO


fidelsmc@gmail.com
Maracaibo - Venezuela
2008
3.14

Dedicado a Jessica

You might also like