You are on page 1of 33

HVAC 101

The Basics of Heating, Ventilation and Air Conditioning


Presented by: Mike Barcik and Jeff Ross-Bain, PE Southface Energy Institute

Southface Energy Institute


Sensible Solutions for Environmental Living

Energy Code Workshops Greenprints


Commercial Systems

EarthCraft House
www.southface.org

HVAC
Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions.

Comfort
Comfort is primary intent of HVAC systems.
Productivity Building Durability Health

Mold

Load Calculations
Heating and Cooling Accuracy important! Design conditions Building shell load R, U value Internal load Ventilation load Infiltration Occupancy schedules

Heat Transfer
Conduction
Convection Radiation Resistance (R-Value) U=1/R Q = U x A x T
U-Value is the rate of heat flow in Btu/h through a one ft2 area when one side is 1oF warmer

Solar Heat Gain Coefficient

The

amount of solar heat energy allowed to pass through a window


Example:

SHGC = 0.40 Allows 40% through and turns 60% away

Psychrometrics
Dry bulb temp. Wet bulb temp. Humidity Dew point Moisture content Heating Cooling Humidify De-Humidify
Psychrometric Chart

Basic Refrigeration Cycle


Condenser
Compressor Expansion Valve Evaporator

Basic HVAC Equipment


Fans / Blowers Furnace / Heating unit Filters Compressor Condensing units Evaporator (cooling coil) Control System Air Distribution System

System Types and Common Terms


Packaged Rooftop Unit Split System Heat Pump Geothermal Air to Air Hydronic (water) PTAC / PTHP Constant Volume Variable Volume Indoor Air Quality Direct Expansion

Packaged Rooftop Units

Split System
Ductwork

Heating and Cooling Equipment


FURNACE A/C UNIT

Temperature & Humidity Controls

Heat Pump
Operate on simple refrigeration cycle

Reversing the cycle provides heating Temperature limitations Air to air Water source Geothermal Lake coupled

Geothermal Heat Pump Systems

Variable Air Volume


Variable Speed Supply Fan Supply Ducts

Filters

Cool Coil w/Temp Reset

Heat Coil w/Temp Reset

VAV Box Reheat Coil


T T

Return Air

Zone Thermostat

Variable Speed Return Fan

Return Ducts

HVAC-17

Terminal Units
Variable volume: Parallel Constant volume: Series

Hydronic systems
Pumps Piping Valves

Control Devices
Thermostats

Manual Programmable

Optimum Start DDC Systems Variable Speed Drives

Automatic Valves and Dampers


Outdoor Sensors

Major Equipment
Chillers Boilers Cooling Towers

Economizers

Air Side

Water Side

Economizers
Free cooling source: When available, use cool outdoor air instead of mechanically cooled air.
Minimum supply of outside air 55 oF 55 oF and up

85% outside air


85% exhaust 80 oF

80

oF

Normal Operation Outside air dampers are positioned to provide the minimum outside air

Economizer Operation Outside air dampers are fully open. Maximum outside air is provided
HVAC-23

Zoning and Economizers


Economizers provide free cooling when outdoor conditions are optimal Proper orientation & zoning yields comfort & efficiency N W Core S E

HVAC-24

Air Distribution
Ductwork

Metal Flexible Ductboard

Grilles, Louvers, & Registers Dampers


Shut off Fire Smoke

Sealants Supports

Return Plenum Problems

HVAC-26

Additional Equipment
Energy Recovery Units
Desiccant Systems

Additional Equipment
Heat Exchangers Humidifiers Silencers

Mechanical Dehumidification
Return air is mixed with ventilation air
Cold coil condenses moisture Heat is added back (electric or gas) so that room air is not over cooled- Reheat

Filter

Historical Minimum Ventilation Rates (cfm/person)


70
Smoking 62-89

60 50 40 30 20 10 0
35 42 49 56 63 70 77 84 91 98 05 12 19 26 33 40 47 54 61 68 75 82 89 19 18 18 18 18 18 18 18 18 18 18 19 19 19 19 19 19 19 19 19 19 19 19 19 96
Tredgold 1836 Yaglou 1938 Nightengale 1865 Flugge 1905 Smoking 62-81 ASHRAE 62-89

Billings 1895

ASHRAE 62-73

ASHRAE 62-81

Improved Ventilation Effectiveness


Mechanically provide filtered and dehumidified outdoor air to the breathing space Vary ventilation based on the number of occupants and process loads - changes in occupancy can be measured by CO2 sensors Consider designs that separate ventilation and space conditioning Utilize heat recovery systems to reduce system size and ventilation energy costs

Improved Ventilation Effectiveness


Effective mixing of ventilation air within space Net positive pressure in the southeast; exhaust from appropriate spaces Provide clean outdoor air, avoid:

loading docks exhaust vents plumbing stacks waste collection stagnant water

Additional Information / Resources


ASHRAE The American Society of Heating, Refrigerating and Air-Conditioning Engineers www.ashrae.org Southface Energy Institute www.southface.org Geothermal heat pump consortium www.geoexchange.org www.buildingscience.com www.energycodes.gov

You might also like