Jobsheet 1 AP 922 Firstly , enter value PB = 125 , TI = 38 and TD = 0 that given and wait for a minute. For SV = 6.

= 6.2 there no undershoot and overshoot at the settling time for 2 minute. SV = 12.5 , also no undershoot and overshoot , but have a rise time at settling time for another 2 minute. SV = 18.7 ,there are only have overshoot at the settling and rise time for 2 minute. For SV = 25 , there have overshoot and undershoot at the settling and rise time for 2 minute.

WLF 922 Firstly , enter value PB = 90 , TI = 40 and TD = 0 that given and wait for a minute and there have overshoot. For SV = 200, there have overshoot at the settling time and rise time for 3 minute. SV = 400, no undershoot and overshoot , at settling time and rise time for another 3 minute. SV = 600 ,there are also no overshoot and undershoot at the settling and rise time for 3 minute. For SV = 800 , there no overshoot and undershoot at the settling and rise time for 3 minute.

WF 922 firstly , enter value PB = 130 , TI = 36 and TD = 0 that given and wait for a minute and there have overshoot and also undershoot. For SV = 1.5, there have a little overshoot and undershoot at the settling time and rise time for 2 minute. SV = 3.0 there have a little undershoot and overshoot , at settling time and rise time for another 2 minute. SV = 4.5 ,there are also have a little overshoot and undershoot at the settling and rise time for 2 minute. For SV =6.0 , there no overshoot and undershoot at the settling and rise time for 3 minute.

WT 922 Firstly enter value PB , TI and TD that given and wait for a minute and there no overshoot and undershoot. For 0% , the value of PV=27.1, SV=27.1, MV=94.9 and wait for a minute. For 25% , the value of PV=27.1, SV=28.6, MV=100, and there have overshoot at the settling time for a 3 minute. For 50%, the value of PV=26.9, SV=30.1, MV=74.4, and there are also have overshoot at the settling time for a 3 minute. For 75% , the value of PV=27.6, SV=31.6 , MV=69.2, and there are have overshoot at the settling time for a 3 minute. Lastly, for 100% , the value of PV=28.1, SV=31.6, MV=61.5, there are no undershoot and overshoot.

Jobsheet 2 (open loop)

AP 922 Firstly , select Set point = 12.5 , MV= - 6.3 and wait for a minute. After that , up the MV to 70% = 63.7 for a 3 minute for settling time, and there are overshoot and undershoot , there are also have rise time = 2 minute and decrease the MV= - 6.3 and wait for a minute. Do the same step twice with the different Set point = 15.5 and 18.5, and the result will be same with the first one. For WLF 922 Same with the AP 922 plant Except set point = 400, MV = - 6.3 and wait for a minute. After that, up the value of MV to 70% = 63.7 , and there no undershoot and overshoot for the 3 minute of settling time and rise time. Do the same step twice for the different set point = 500 and 600, and the result also same with the first one.

WF 922 Enter the value of PB = 2%, TI = 9999 sec , TD = 0 sec and the set point = 2.4, and there are no undershoot and overshoot for a settling time and rise time at the 3 minute. Second and third, do the same thing, but for the second set point = 2.70, and third set point = 3.0 and the result also no undershoot and overshoot for a settling time and rise time at the 3 minute. After that change the value of PB = 100%, TI = 9999 sec , TD = 0 sec and the set point also = 2.4 , and the result no undershoot and overshoot for a settling time and rise time at the 3 minute. For the second and third , use the same step , but for the second set point = 2.7 , and third = 3.0 and the result also same. For WT 922 plant, there no undershoot and overshoot at the 3 minute for the settling time and rise time for the value of PV = 26.8 , SV = 44 , MV = -6.3. For the PV = 28.8 , SV = 44 , MV = -6.3 , there are have undershoot at the 3 minute for the settling time and rise time. There are also undershoot for the settling time and rise time at 3 minute of the settling time and rise time.

Jobsheet 2 (closed loop)

AP 922 Enter the value of PB = 20% , TI = max , TD = 0 and the set point = 12.5 and there are no undershoot , overshoot and also rise time at the 2 minute of settling time. Do the same step with the different value of PB = 30 % , TI = 6000 , TD = 0 , and the same set point = 12.5 , there are also no response. Third , enter the value of PB = 70% , TI = 2500 , TD = 0 and the value of set point = 12.5 , and there also no response. For WLF 922 plant , there are also need to enter the value of PB = 15% , TI = 9999 , TD = 0 sec , and there have overshoot , for the settling time and the rise time = 0.5 sec. After that , enter the different value of PB = 15%, TI = 20 , TD = 20 , and the result will undershoot and overshoot continuously. Do the same thing , with the different PB = 30% , TI = 40 , TD = 20 , and the result stability at the 4 minute for the settling time.

WF 922 Start with PB = 200%, TI = Max , TD = 0,and there are overshoot at the 3 minute of the settling time and the rise time = 30 sec. Second , decrease the value PB to 100 % , TI = Max , TD = 0 , the result no undershoot , overshoot and also rise time , the settling time is 3 minute. After that decrease the value of PB = 50% , TI = Max , TD = 0 , and it give the same response. Then , PB = 40 , TI = 50 , TD = 0 , and the result also same. When PB = 30% , TI = Max , TD = 0 , and the results is stable. For WT 922 plant , PB = 10% , TI = 40 sec , TD = 0 , there no undershoot , overshoot and also rise time. After that use PB = 20% , TI = 40 sec , TD = 0 , the result no response. Then change the value of PB = 30% , TI = 40 sec , TD = 0 , there also no undershoot and overshoot.

Jobsheet 3

AP 922 Enter the PB = 30 , TI = 15 sec , TD = 0 , and wait for the 3 minute. And there are no undershoot and overshoot , and also the rise time. After that enter the value of PB = 15 , TI = 15 , TD = 0 for the 3 minute , and there have undershoot n overshoot . Repeat with PB = 30 , TI = 30 , TD = 0 , and wait also for 3 minute ,the result become stable, and there are no undershoot and overshoot.

WLF 922 Set the PID , where PB = 30 , TI = 25 sec , TD = 0 , there are no undershoot and overshoot , but have rise time = 3 minute at the settling time for the 3 minute. Change the PID , where PB = 15 , TI = 20 sec , TD = 0 sec , the result , no undershoot and overshoot , but have rise time = 3 minute at the settling time for the 3 minute.

WF 922 Set PB = 200%, TI = 6secs, TD = 0, then set SV = 1.8, PV = 1.8, MV = 43.1, there have undershoot n overshoot for 1 minutes and settling time 2 minutes. Then change the PID, where PB = 100%, TI = 6secs, TD = 0 sec, set SV = 2.5, the value of PV = 2.5 and MV = 50.0, there are no overshoot and undershoot while the rise time is 30 second and settling time is in 3 minutes. Set SV = 3.00, value of PV = 3.00 and MV = 52.6 which has no overshoot and undershoot while the rise time is 0 and settling time is in 3 minutes. Then set SV = 4.00, the value of PV = 4.00 and MV = 59.6, the result has no undershoot and overshoot with rise time is 0 and settling time is 2 minutes. After that, change the PB = 200% with the same TD and TI. Set SV = 2.40,value of PV = 2.41 and MV = 49.4 which has no overshoot and undershoot while the rise time is 0 and settling time is in 2 minutes. Set SV = 3.00, value of PV = 3.00 and MV = 51.7 which no undershoot and overshoot with rise time is 0 and settling time is 2 minutes. Then set SV = 3.60, value of PV = 3.60 and MV = 56.0 and there are no undershoot and overshoot with rise time is 0 and settling time is 2 minutes. Lastly, change the PB to 300% with same TI and TD, set SV 2.40, value of PV = 2.40 and MV = 49.3 which has no undershoot and overshoot with rise time is 0 and settling time is 2 minutes. Then set SV = 3.00, value of PV = 3.00 and MV = 51.8, there has no undershoot and overshoot with rise time is 0 and settling time is 2 minutes. Lastly, set SV = 3.60, the value of PV = 3.60 and MV = 56.6 which has no undershoot and overshoot with rise time is 0 and settling time is 2 minutes.

WT 922 Set value of PB = 10%, TI = 40secs, TD1 = 10secs, there are no undershoot and overshoot and also rise time is 0 and 3 minute of settling time. Do the same step with the different value of PB = 30%, TI = 60, TD = 20, there are also no response.

Third, enter PB = 104.4%, TI = 50, TD = 30 and there also no response. Then set PB = 300.9%, TI = 20, TD = 20, there are no undershoot and overshoot and also rise time is 0 and 3 minute of settling time and there are also no response.