System pro M compact S ystem


2
Miniature circuit breakers 00 S pro

Miniature circuit breakers


e M
S200, S200P, S200U, S200UP ries

Description Features
The S2 Series of miniature circuit breakers • Current limiting
offer a compact solution to protection • Fast breaking time (2.5 – 3.5 msec)
requirements. The S2 devices are current
limiting, DIN rail mounted and can offer a • Unique bus connection system
good equivalent to fused systems. • Wide range of accessories
The S2 is available with application-specific • Available with variable depth handle
trip characteristics to provide maximum mechanism
circuit protection. The breakers offer • Optional Z curve for SCR protection
thermal-magnetic trip protection according
to B, C, D, K and Z characteristics. • CE certified and marked
For the worldwide market, the breakers • DIN rail or front panel mounting 14
carry UL, CSA, IEC, CE and many other • Finger safe terminals
agency approvals and certifications.
• Multi-function terminals
• Suitable for reverse feed
• 480Y/277VAC and 500VDC versions
• UL489 Listed - branch circuit protective
device. UL file # E212323
• UL1077 Recognized - supplemental
protective device. UL file # E76126

d
lde
e Mo
i a tur and
M in ers rs
k o
v ed Brea tect
S200

o
p pro cuit l Pr
A ir ta
UL se C men
Ca pple
Su

Low Voltage Products & Systems 14.1


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M General information
pr ies
em er
y st 0 S
S 20
S

General information Applications


Miniature circuit breakers (MCBs) are used throughout the world in all MCBs can be used for equipment protection, in commercial appliances,
types of electrical installations. ABB MCBs are approved for use by protection of control circuits against overcurrent faults, computer
Underwriters Laboratories in systems rated up to 600VAC/VDC. Devices equipment and other computer peripheral devices.
are also certified per CSA. UL 489
MCBs are approved per IEC-898 and VDE 0641, and certified under S200U and S200UP MCBs are listed as molded case circuit breakers
IEC-947 and VDE 0660 standards for use in systems rated up to for use as branch circuit protective devices. Miniature MCCBs and
690VAC. accessories are listed under UL file E212323.
MCBs can be applied to 16 2/3Hz – 400Hz and DC power systems.
UL 1077
Special direct current version MCBs include a permanent magnet for DC
S200 and S200P MCBs are recognized as supplementary protectors
fault current interruption. These "UC" versions are rated 250/500VDC
and are intended for use as overcurrent protection within an appliance
under UL1077/CSA 22.2 No. 235.
or other electrical equipment where branch circuit overcurrent
Continuous current ratings are as low as 0.2 amperes and up to 125 protection is already provided or not required. MCBs and accessories
amperes maximum. are recognized under UL File E76126.
MCBs are of compact size and can be quickly mounted on standard CSA C22.2
35mm DIN rail or can be front mounted by use of a front mounting kit.
MCBs and accessories are certified under CSA C22.2 No. 235 per File
MCBs include line and load side terminals for conductors from 18 LR98793.
through 4AWG (0.75 – 25mm2) for 63 amperes.
MCBs can also be connected via busbar conductors which can be Tripping characteristics
either upper or lower mounted for top feed or bottom feed. Dual Time-current curves
function terminals allow busbars to be connected with main incoming
line conductors without separate lugs. ABB miniature circuit breakers are available with different trip
characteristics, allowing for maximum system protection.
Accessories B Characteristic
Auxiliary devices can be added to the, S200 series MCBs:
Available with the S200 and S500 series has rated currents of 6 through
• Shunt trips
63 amperes in 10 steps. The "B" time-current curve is designed
• Auxiliary contacts
primarily for use in cable protection applications. Instantaneous tripping
• Bell alarm contacts
occurs between approximately 3 to 5 times rated current in 50/60Hz
• Aux/bell alarm contacts
systems. This quick trip curve maximizes protection of control circuits
• Undervoltage release
under low short circuit fault levels that could damage control wiring.
Accessory device modules can be field mounted to all above listed ABB
C Characteristic
MCBs. Auxiliary contacts are also available for the S500 series MCB.
Available in the S200 and S500 series with rated currents up through 63
amperes and the S290 series with rated currents of 80, 100 and 125
amperes. The "C" time-current curve is designed for medium magnetic
start-up currents. Instantaneous tripping occurs between 5 and 10
14 times rated current in 50/60 Hz systems.
D Characteristic
The new magnetic trip action has an instantaneous trip between 10 and
20 times the breaker rating. Thus, the S200 and S500-D can be a good
protective solution for applications involving high in-rush transformers,
motors and other high inductive systems. It is also suitable for any
application where a high instantaneous trip point is desired.
K Characteristic
The "K" time-current characteristic considers high magnetic start-up
currents from motors, transformers and other equipment. Instantaneous
tripping occurs between 8 and 12 times rated current in 50/60Hz
systems. The "K" characteristic is available up through 63 amperes.
The "K" curve offers the best protection for the broadest range of
electrical systems. The higher magnetic trip settings maximizes
protection while allowing for higher in-rush currents during system start-
up. Available in S200P, S200U, S200UP and S500.
Z Characteristic
Also available up through 63 amperes, the "Z" characteristic offers
instantaneous tripping between 2 and 3 times rated current in 50/60Hz
systems. This trip characteristic is available in the S200P, S200U and
S200UP series with both the 480Y/277VAC and 250/500VDC ratings.
Many applications require a very low short circuit trip setting in order
to protect semiconductor or other sensitive devices and the "Z" trip
characteristic may provide maximum protection and service in these
applications.

14.2 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
General information S2 tem
00 p
Interruption ratings Se ro M
rie
Trip characteristics overview s

Interruption ratings Trip characteristics overview


Voltage Rated interrupting Rated MCB Curve Magnetic Thermal
Comment Series
capacity current type characteristic 1 characteristic
120 VAC 10kA 0.5 - 63A S200-B,C,D B 3 - 5X 1.13 1.45X S200, S500
0.5 - 63A S200-K C 5 - 10X 1.13 1.45X S200, S290, S500
0.2 - 63A S200P-K, Z D 10 - 20X 1.13 1.45X S200, S500
0.2 - 63A S200U-K, Z K 8 - 12X 1.05 1.20X S200, S500
0.2 - 25A S200UP-K, Z Z 2 - 3X 1.05 1.20X S200
18kA 32 - 63A S500-B,C,D 1 All values are relative to MCB's ampere rating.
26 - 45A S500-K
30kA 6 - 25A S500-B,C,D
0.15 - 25A S500-K
240 VAC 6kA 0.5 - 63A S200-B,C,D Single pole
0.5 - 63A S200-K Single pole
10kA 0.5 - 63A S200-B,C,D Multi pole
0.5 - 63A S200-K Multi pole
0.2 - 63A S200P-K,Z Single pole
0.2 - 63A S200P-K,Z Multi pole
0.2 - 63A S200U-K,Z Single pole
0.2 - 63A S200U-K,Z Multi pole
0.2 - 25A S200UP-K,Z Single pole
0.2 - 25A S200UP-K,Z Multi pole
18kA 32 - 63A S500-B,C,D
26 - 45A S500-K
30kA 6 - 25A S500-B,C,D
0.15 - 25A S500-K
277 VAC 6kA 0.5 - 63A S200-B,C,D
0.5 - 63A S200-K
10KA 0.2 - 63A S200P-K,Z
0.2 - 25A S200UP-K,Z
480Y/277 VAC 6kA 0.5 - 63A S200-B,C,D
0.5 - 63A S200-K
10KA 0.2 - 63A S200P-K,Z
0.2 - 25A S200UP-K,Z
60 VDC

10kA 0.5 - 63A
0.5 - 63A
S200-B,C,D
S200-K
Single pole
Single pole
14
125 VDC 10kA 0.5 - 63A S200-B,C,D Multi pole
0.5 - 63A S200-K Multi pole
0.2 - 63A S280UC-K,Z Single pole
250 VDC 4.5kA 0.2 - 63A S280UC-K,Z Single pole
500 VDC 4.5kA 0.2 - 63A S280UC-K,Z Multi pole

Low Voltage Products & Systems 14.3


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M General information
pr ies
em er Tripping curves
y st 0 S
S 20
S

B C D
10,000 10,000 10,000
5000 5000 5000

1000 1000 1000


500 500 500

100 100 100


50 50 50

10 10 10
5 5 5

1 1 1
0.5 0.5 0.5
seconds

seconds

seconds
AC AC AC
0.1 0.1 0.1
0.05 0.05 0.05
DC DC DC

0.01 0.01 0.01


1 2 3 5 7 10 20 30 1 2 3 5 10 18 20 30 1 2 3 5 10 20 30
multiple of rated current multiple of rated current multiple of rated current

K UC-K
10,000 10,000
5000 5000

1000 1000
500 500

100 100
50 50

10 10
5 5

14 1 1
0.5 0.5
seconds

seconds

AC
0.1 0.1
0.05 0.05
DC DC

0.01 0.01
1 2 3 5 8 10 12 20 30 1 2 3 5 10 20 30
multiple of rated current multiple of rated current

Z UC-Z
10,000 10,000
5000 5000

1000 1000
500 500

100 100
50 50

10 10
5 5

1 1
0.5 0.5
seconds
seconds

AC
0.1 0.1
0.05 0.05
DC DC

0.01 0.01

1 2 3 5 10 20 30 1 2 3 5 10 20 30
multiple of rated current multiple of rated current

14.4 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
General information S2 tem
00 p
Construction details Se ro M
rie
s

Electro-magnetic protection

Tripping lever Upper terminal

Operating Thermal protection-bimetal


mechanism

Operator

14
Arc chamber

Space for
identification marker Fixed contact

Moving contact

DIN rail holder

Lower terminal

Low Voltage Products & Systems 14.5


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S200
pr ies
em er 480Y/277 VAC
y st 0 S
S 20
S Supplemental protectors

B UL 1077 CSA C22.2 No. 235


VDE 0641 IEC-898
Cable protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class
current number price (1 pc.) order
current number price (1 pc.)
qty qty
1 pole 3 pole
6 S201-B6 $ 36 6 S203-B6 $ 118
10 S201-B10 36 10 S203-B10 118
13 S201-B13 36 13 S203-B13 118
16 S201-B16 36 16 S203-B16 118
20 S201-B20 38 20 S203-B20 130
A 10 4.5 A 1 13.5
25 S201-B25 38 25 S203-B25 132
32 S201-B32 40 32 S203-B32 142
S201-B, 1 pole 40 S201-B40 42 40 S203-B40 148
50 S201-B50 48 50 S203-B50 170
63 S201-B63 56 63 S203-B63 194
1 pole + neutral 3 pole + neutral
6 S201-B6NA 62 6 S203-B6NA 142
10 S201-B10NA 62 10 S203-B10NA 142
13 S201-B13NA 62 13 S203-B13NA 142
16 S201-B16NA 62 16 S203-B16NA 142
20 S201-B20NA 68 B 5 9.0 20 S203-B20NA 162 B 1 18.0
25 S201-B25NA 72 25 S203-B25NA 168
32 S201-B32NA 74 32 S203-B32NA 176
40 S201-B40NA 76 40 S203-B40NA 184
S202-B, 2 pole 50 S201-B50NA 90 50 S203-B50NA 212
S201-BNA, 1 P+N 63 S201-B63NA 102 63 S203-B63NA 240
2 pole 4 pole
6 S202-B6 78 6 S204-B6 156
10 S202-B10 78 10 S204-B10 156
13 S202-B13 78 13 S204-B13 156
16 S202-B16 78 16 S204-B16 156
20 S202-B20 86 20 S204-B20 172
A 5 9.0 B 1 18.0
25 S202-B25 88 25 S204-B25 176
32 S202-B32 94 32 S204-B32 188
40 S202-B40 98 40 S204-B40 196
50 S202-B50 112 50 S204-B50 224
63 S202-B63 128 63 S204-B63 256
14 S203-B, 3 pole
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

S204-B, 4 pole
S203-BNA, 3P+N

B
10,000
5000

1000
500

100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 7 10 20 30
multiple of rated current

14.6 Discount schedule CB5 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S200 S2 tem
00 p
480Y/277 VAC Se ro M
rie
Supplemental protectors s

C UL 1077 CSA C22.2 - NO. 235


VDE 0641 IEC-898
Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class
current number price (1 pc.) order
current number price (1 pc.)
qty qty
1 pole 3 pole
0.5 S201-C0.5 $ 42 0.5 S203-C0.5 $ 138
1 S201-C1 42 1 S203-C1 138
1.6 S201-C1.6 42 1.6 S203-C1.6 138
2 S201-C2 42 2 S203-C2 138
3 S201-C3 42 3 S203-C3 138
4 S201-C4 42 4 S203-C4 138
6 S201-C6 42 6 S203-C6 138
S201-C, 1 pole 8 S201-C8 42 8 S203-C8 138
10 S201-C10 42 A 10 4.5 10 S203-C10 138 A 1 13.5
13 S201-C13 42 13 S203-C13 138
16 S201-C16 42 16 S203-C16 138
20 S201-C20 42 20 S203-C20 138
25 S201-C25 46 25 S203-C25 156
32 S201-C32 48 32 S203-C32 158
40 S201-C40 52 40 S203-C40 174
50 S201-C50 60 50 S203-C50 200
63 S201-C63 68 63 S203-C63 228
1 pole + neutral 3 pole + neutral
0.5 S201-C0.5NA 84 0.5 S203-C0.5NA 200
1 S201-C1NA 84 1 S203-C1NA 200
S202-C, 2 pole
S201-CNA, 1P+N 1.6 S201-C1.6NA 84 1.6 S203-C1.6NA 200
2 S201-C2NA 84 2 S203-C2NA 200
3 S201-C3NA 84 3 S203-C3NA 200
4 S201-C4NA 84 4 S203-C4NA 200
6 S201-C6NA 84 6 S203-C6NA 200
8 S201-C8NA 84 B 5 9.0 8 S203-C8NA 200 B 1 18.0
10 S201-C10NA 84 10 S203-C10NA 200
13 S201-C13NA 84 13 S203-C13NA 200
16 S201-C16NA 84 16 S203-C16NA 200
20 S201-C20NA 84 20 S203-C20NA 200
25 S201-C25NA 88 25 S203-C25NA 206
32 S201-C32NA 90 32 S203-C32NA 212
40 S201-C40NA 96 40 S203-C40NA 224
S203-C, 3 pole 50 S201-C50NA 112 50 S203-C50NA 204 14
63 S201-C63NA 130 63 S203-C63NA 304
2 pole 4 pole
0.5 S202-C0.5 96 0.5 S204-C0.5 218
1 S202-C1 96 1 S204-C1 218
1.6 S202-C1.6 96 1.6 S204-C1.6 218
2 S202-C2 96 2 S204-C2 218
3 S202-C3 96 3 S204-C3 218
4 S202-C4 96 4 S204-C4 218
6 S202-C6 96 6 S204-C6 218
8 S202-C8 96 8 S204-C8 218
A 5 9.0 B 1 18.0
10 S202-C10 96 10 S204-C10 218
S204-C, 4 pole
13 S202-C13 96 13 S204-C13 218
S203-CNA, 3P+N 16 S202-C16 96 16 S204-C16 218
20 S202-C20 96 20 S204-C20 218
C 25 S202-C25 106 25 S204-C25 234
10,000 32 S202-C32 106 32 S204-C32 238
5000 40 S202-C40 116 40 S204-C40 260
50 S202-C50 136 50 S204-C50 300
1000 63 S202-C63 152 63 S204-C63 338
500

100 Delivery Class


50
A - Standard item, stock to 2 weeks lead time
10
5
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 10 18 20 30
multiple of rated current

Low Voltage Products & Systems Discount schedule CB5 14.7


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S200
pr ies
em er 480Y/277 VAC
y st 0 S
S 20
S Supplemental protectors

D UL 1077 CSA C22.2


VDE 0641 IEC-898
Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class order current number price (1 pc.)
current number price (1 pc.)
qty qty

1 pole 3 pole
0.5 S201-D0.5 $ 42 0.5 S203-D0.5 $ 138
1 S201-D1  42 1 S203-D1   138
1.6 S201-D1.6 42 1.6 S203-D1.6 138
2 S201-D2 42 2 S203-D2 138
3 S201-D3 42 3 S203-D3 138
4 S201-D4 42 4 S203-D4 138
6 S201-D6 42 6 S203-D6 138
8 S201-D8 42 8 S203-D8 138 A 1 13.5
10 S201-D10 42 A 10 4.5 10 S203-D10 138
S201-D, 1 pole
13 S201-D13 42 13 S203-D13 138
16 S201-D16 42 16 S203-D16 138
20 S201-D20 42 20 S203-D20 138
25 S201-D25 46 25 S203-D25 156
32 S201-D32 48 32 S203-D32 158
40 S201-D40 52 40 S203-D40 174
50 S201-D50 60 50 S203-D50 200
63 S201-D63 68 63 S203-D63 228
2 pole
0.5 S202-D0.5 96
1 S202-D1  96
1.6 S202-D1.6 96
2 S202-D2 96
S202-D, 2 pole 3 S202-D3 96
4 S202-D4 96
6 S202-D6 96
8 S202-D8 96 A 5 9.0
10 S202-D10 96
13 S202-D13 96
16 S202-D16 96
20 S202-D20 96
25 S202-D25 106
32 S202-D32 106
40 S202-D40 116
14 50 S202-D50 136
63 S202-D63 152

S203-D, 3 pole

D
10,000
5000

1000
500

100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 10 20 30
multiple of rated current

14.8 Discount schedule CB5 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S200 S2 tem
00 p
480Y/277 VAC Se ro M
rie
Supplemental protectors s

K UL 1077 CSA C22.2 - NO. 235


VDE 0641 IEC-898
Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class order current number price (1 pc.)
current number price (1 pc.)
qty qty
1 pole 3 pole
0.5 S201-K0.5 $ 42 0.5 S203-K0.5 $ 138
1 S201-K1 42 1 S203-K1 138
1.6 S201-K1.6 42 1.6 S203-K1.6 138
2 S201-K2 42 2 S203-K2 138
3 S201-K3 42 3 S203-K3 138
4 S201-K4 42 4 S203-K4 138
5 S201-K5 42 5 S203-K5 138
S201-K, 1 pole 6 S201-K6 42 6 S203-K6 138
8 S201-K8 42 8 S203-K8 138
10 S201-K10 42 10 S203-K10 138
13 S201-K13 42 A 10 4.5 13 S203-K13 138 A 1 13.5
15 S201-K15 42 15 S203-K15 138
16 S201-K16 42 16 S203-K16 138
20 S201-K20 42 20 S203-K20 138
25 S201-K25 46 25 S203-K25 156
30 S201-K30 48 30 S203-K30 158
32 S201-K32 48 32 S203-K32 158
40 S201-K40 52 40 S203-K40 174
50 S201-K50 60 50 S203-K50 200
60 S201-K60 68 60 S203-K60 228
S202-K, 2 pole 63 S201-K63 68 63 S203-K63 228
S201-KNA, 1P+N
1 pole + neutral 3 pole + neutral
0.5 S201-K0.5NA 84 0.5 S203-K0.5NA 200
1 S201-K1NA 84 1 S203-K1NA 200
1.6 S201-K1.6NA 84 1.6 S203-K1.6NA 200
2 S201-K2NA 84 2 S203-K2NA 200
3 S201-K3NA 84 3 S203-K3NA 200
4 S201-K4NA 84 4 S203-K4NA 200
6 S201-K6NA 84 6 S203-K6NA 200
8 S201-K8NA 84 8 S203-K8NA 200
10 S201-K10NA 84 B 5 9.0 10 S203-K10NA 200 B 1 18.0
13 S201-K13NA 84 13 S203-K13NA 200
16 S201-K16NA 84 16 S203-K16NA 200
S203-K, 3 pole 20 S201-K20NA 84 20 S203-K20NA 200 14
25 S201-K25NA 88 25 S203-K25NA 206
32 S201-K32NA 90 32 S203-K32NA 212
40 S201-K40NA 96 40 S203-K40NA 224
50 S201-K50NA 112 50 S203-K50NA 264
63 S201-K63NA 130 63 S203-K63NA 304
2 pole 4 pole
0.5 S202-K0.5 96 0.5 S204-K0.5 218
1 S202-K1 96 1 S204-K1 218
1.6 S202-K1.6 96 1.6 S204-K1.6 218
2 S202-K2 96 2 S204-K2 218
3 S202-K3 96 3 S204-K3 218
S204-K, 4 pole 4 S202-K4 96 4 S204-K4 218
S203-KNA, 3P+N 5 S202-K5 96 6 S204-K6 218
6 S202-K6 96 8 S204-K8 218 B 1 18.0
K 8 S202-K8 96 10 S204-K10 218
10,000 10 S202-K10 96 A 5 9.0 13 S204-K13 218
5000 13 S202-K13 96 16 S204-K16 218
15 S202-K15 96 20 S204-K20 218
1000 16 S202-K16 96 25 S204-K25 234
500
20 S202-K20 96 32 S204-K32 238
25 S202-K25 106 40 S204-K40 260
100
50 30 S202-K30 106 50 S204-K50 300
32 S202-K32 106 63 S204-K63 338
10 40 S202-K40 116
5 50 S202-K50 136
60 S202-K60 152
Delivery Class
1 63 S202-K63 152 A - Standard item, stock to 2 weeks lead time
0.5
B - Stock to 4 weeks lead time
seconds

AC
0.1 C - 6 to 8 week lead time
0.05
DC

0.01
1 2 3 5 8 10 12 20 30
multiple of rated current

Low Voltage Products & Systems Discount schedule CB5 14.9


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S200P
pr ies
em er 480Y/277 VAC
y st 0 S
S 20
S Supplemental protectors

K UL 1077
VDE 0660
CSA C22.2 - NO. 235

Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order class order
current number price (1 pc.) current number price (1 pc.)
qty qty
1 pole 3 pole
0.2 S201P-K0.2 $ 54 0.2 S203P-K0.2 $ 194
0.3 S201P-K0.3 54 0.3 S203P-K0.3 194
0.5 S201P-K0.5 54 0.5 S203P-K0.5 194
0.75 S201P-K0.75 54 0.75 S203P-K0.75 194
1 S201P-K1 54 1 S203P-K1 194
1.6 S201P-K1.6 54 1.6 S203P-K1.6 194
2 S201P-K2 54 2 S203P-K2 194
3 S201P-K3 54 3 S203P-K3 194
S201P-K, 1 pole
4 S201P-K4 54 4 S203P-K4 194
6 S201P-K6 54 6 S203P-K6 194 A 1 13.9
8 S201P-K8 54 A 10 4.6 8 S203P-K8 194
10 S201P-K10 54 10 S203P-K10 194
13 S201P-K13 54 13 S203P-K13 194
16 S201P-K16 54 16 S203P-K16 194
20 S201P-K20 54 20 S203P-K20 194
25 S201P-K25 56 25 S203P-K25 196
32 S201P-K32 58 32 S203P-K32 200
40 S201P-K40 64 40 S203P-K40 214
50 S201P-K50 70 50 S203P-K50 246
63 S201P-K63 80 63 S203P-K63 280
2 pole
S202P-K, 2 pole 0.2 S202P-K0.2 128 Delivery Class
0.3 S202P-K0.3 128
0.5 S202P-K0.5 128 A - Standard item, stock to 2 weeks lead time
0.75 S202P-K0.75 128 B - Stock to 4 weeks lead time
1 S202P-K1 128 C - 6 to 8 week lead time
1.6 S202P-K1.6 128
2 S202P-K2 128
3 S202P-K3 128
4 S202P-K4 128
6 S202P-K6 128 A 5 9.2
8 S202P-K8 128
10 S202P-K10 128
14 13 S202P-K13 128
16 S202P-K16 128
S203P-K, 3 pole 20 S202P-K20 128
25 S202P-K25 130
32 S202P-K32 134
40 S202P-K40 134
50 S202P-K50 162
63 S202P-K63 182

K
10,000
5000

1000
500

100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 8 10 12 20 30
multiple of rated current

14.10 Discount schedule CB7 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S280 (W) S2 tem
00 p
480Y/277 VAC Se ro M
rie
Supplemental protectors s

K UL 1077
VDE 0660
CSA C22.2 - NO. 235

Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class
current number price (1 pc.) order
current number price (1 pc.)
qty qty
1 pole 3 pole
0.2 S281-K0.2W $ 54 0.2 S283-K0.2W $ 194
0.3 S281-K0.3W 54 0.3 S283-K0.3W 194
0.5 S281-K0.5W 54 0.5 S283-K0.5W 194
0.75 S281-K0.75W 54 0.75 S283-K0.75W 194
1 S281-K1W 54 1 S283-K1W 194
1.6 S281-K1.6W 54 1.6 S283-K1.6W 194
2 S281-K2W 54 2 S283-K2W 194
S281-KW, 1 pole 3 S281-K3W 54 3 S283-K3W 194
4 S281-K4W 54 4 S283-K4W 194
6 S281-K6W 54 6 S283-K6W 194 B 3 13.9
8 S281-K8W 54 B 10 4.6 8 S283-K8W 194
10 S281-K10W 54 10 S283-K10W 194
13 S281-K13W 54 13 S283-K13W 194
16 S281-K16W 54 16 S283-K16W 194
20 S281-K20W 54 20 S283-K20W 194
25 S281-K25W 56 25 S283-K25W 196
32 S281-K32W 58 32 S283-K32W 200
40 S281-K40W 64 40 S283-K40W 214
50 S281-K50W 70 50 S283-K50W 246
63 S281-K63W 80 63 S283-K63W 280
S282-KW, 2 pole 2 pole
0.2 S282-K0.2W 128 Delivery Class
0.3 S282-K0.3W 128
0.5 S282-K0.5W 128 A - Standard item, stock to 2 weeks lead time
0.75 S282-K0.75W 128 B - Stock to 4 weeks lead time
1 S282-K1W 128 C - 6 to 8 week lead time
1.6 S282-K1.6W 128
2 S282-K2W 128
3 S282-K3W 128
4 S282-K4W 128
6 S282-K6W 128 B 5 9.2
8 S282-K8W 128
10 S282-K10W 128
13 S282-K13W 128 14
16 S282-K16W 128
S283-KW, 3 pole 20 S282-K20W 128
25 S282-K25W 130
32 S282-K32W 134
40 S282-K40W 134
50 S282-K50W 162
63 S282-K63W 182

K
g ue
10,000
t on
ing tors
5000

r
ith nec
1000

w
500

100
u se l con
r a
Fo min
50

ter
10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 8 10 12 20 30
multiple of rated current

Low Voltage Products & Systems Discount schedule CB7 14.11


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S280UC
pr ies
em er 500 VDC
y st 0 S
S 20
S Supplemental protectors

K UL 1077 VDE 0660


CSA 22.2 No. 235
Cable and Equipment Protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class order current number price (1 pc.)
current number price (1 pc.)
qty qty
1 pole 3 pole
0.2 S281UC-K0.2 $ 104 0.2 S283UC-K0.2 $ 370
0.3 S281UC-K0.3 104 0.3 S283UC-K0.3 370
0.5 S281UC-K0.5 104 0.5 S283UC-K0.5 370
0.75 S281UC-K0.75 104 0.75 S283UC-K0.75 370
1 S281UC-K1 104 1 S283UC-K1 370
1.6 S281UC-K1.6 104 1.6 S283UC-K1.6 370
2 S281UC-K2 104 2 S283UC-K2 370
3 S281UC-K3 104 3 S283UC-K3 370
S281UC-K, 1 pole 4 S281UC-K4 104 4 S283UC-K4 370 B 3 13.9
6 S281UC-K6 104 B 10 4.6 6 S283UC-K6 370
8 S281UC-K8 104 8 S283UC-K8 370
10 S281UC-K10 104 10 S283UC-K10 370
16 S281UC-K16 104 16 S283UC-K16 370
20 S281UC-K20 104 20 S283UC-K20 370
25 S281UC-K25 108 25 S283UC-K25 382
32 S281UC-K32 110 32 S283UC-K32 408
40 S281UC-K40 116 40 S283UC-K40 448
50 S281UC-K50 136 50 S283UC-K50 472
63 S281UC-K63 152 63 S283UC-K63 534
2 pole
0.2 S282UC-K0.2 242 Delivery Class
S282UC-K, 2 pole
0.3 S282UC-K0.3 242 A - Standard item, stock to 2 weeks lead time
0.5 S282UC-K0.5 242
0.75 S282UC-K0.75 242 B - Stock to 4 weeks lead time
1 S282UC-K1 242 C - 6 to 8 week lead time
1.6 S282UC-K1.6 242
2 S282UC-K2 242
3 S282UC-K3 242
4 S282UC-K4 242 B 5 9.2
6 S282UC-K6 242
8 S282UC-K8 242
10 S282UC-K10 242
16 S282UC-K16 242
14

20
25
S282UC-K20
S282UC-K25
242
248
32 S282UC-K32 256
S283UC-K, 3 pole
40 S282UC-K40 266
50 S282UC-K50 312
63 S282UC-K63 348

Direct current applications


The S280UC differs from standard miniature circuit breakers in that the UC versions include a permanent
magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to
observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct
connection are shown below.
Maximum voltage between leads
250VDC 500VDC
UC-K
10,000
Single Pole Two Pole
5000 L- L+
S281UC S282UC
1000
500 L- L+ L- L+
100
-1 3+
50

10 -1 -1 +2 3+ 4-
5

1 +2 +2 4-
0.5 LOAD
seconds

- +
0.1
0.05 LOAD LOAD
DC
- + - +
0.01
1 2 3 5 10 20 30 Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two
multiple of rated current (2) and three (3) are positive. Four pole breakers are also available for voltage reversal applications.

14.12 Discount schedule CB7 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S200P & S280UC S2 tem
00 p
480Y/277 VAC & 500 VDC Se ro M
rie
Supplemental protectors s

Z
UL 1077 VDE 0660
CSA 22.2 No. 235
Fast trip characteristic 480Y/277 VAC 500 VDC
Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order
class order current number price (1 pc.)
current number price (1 pc.)
qty qty
1 pole 1 pole
0.5 S201P-Z0.5 $ 70 0.5 S281UC-Z0.5 $ 168
1 S201P-Z1 70 1 S281UC-Z1 168
1.6 S201P-Z1.6 70 1.6 S281UC-Z1.6 168
2 S201P-Z2 70 2 S281UC-Z2 168
3 S201P-Z3 70 3 S281UC-Z3 168
4 S201P-Z4 70 4 S281UC-Z4 168
6 S201P-Z6 70 6 S281UC-Z6 168
8 S201P-Z8 70 B 10 4.5 8 S281UC-Z8 168
10 S201P-Z10 70 10 S281UC-Z10 168 B 10 4.6
S201P-Z, 1 pole
16 S201P-Z16 70 16 S281UC-Z16 168
20 S201P-Z20 70 20 S281UC-Z20 168
25 S201P-Z25 70 25 S281UC-Z25 170
32 S201P-Z32 74 32 S281UC-Z32 176
40 S201P-Z40 78 40 S281UC-Z40 188
50 S201P-Z50 88 50 S281UC-Z50 216
63 S201P-Z63 100 63 S281UC-Z63 242
2 pole 2 pole
0.5 S202P-Z0.5 162 0.5 S282UC-Z0.5 390
1 S202P-Z1 162 1 S282UC-Z1 390
1.6 S202P-Z1.6 162 1.6 S282UC-Z1.6 390
2 S202P-Z2 162 2 S282UC-Z2 390
3 S202P-Z3 162 3 S282UC-Z3 390
S202P-Z, 2 pole 4 S202P-Z4 162 4 S282UC-Z4 390
6 S202P-Z6 162 6 S282UC-Z6 390
8 S202P-Z8 162 B 5 9.2 8 S282UC-Z8 390 B 5 9.2
10 S202P-Z10 162 10 S282UC-Z10 390
16 S202P-Z16 162 16 S282UC-Z16 390
20 S202P-Z20 162 20 S282UC-Z20 390
25 S202P-Z25 170 25 S282UC-Z25 398
32 S202P-Z32 170 32 S282UC-Z32 410
40 S202P-Z40 176 40 S282UC-Z40 426
50 S202P-Z50 206 50 S282UC-Z50 498
63 S202P-Z63 232 63 S282UC-Z63 558
3 pole 3 pole
0.5 S203P-Z0.5 244 0.5 S283UC-Z0.5 594
14
1 S203P-Z1 244 1 S283UC-Z1 594
1.6 S203P-Z1.6 244 1.6 S283UC-Z1.6 594
S203P-Z, 3 pole 2 S203P-Z2 244 2 S283UC-Z2 594
3 S203P-Z3 244 3 S283UC-Z3 594
4 S203P-Z4 244 4 S283UC-Z4 594
6 S203P-Z6 244 6 S283UC-Z6 594
8 S203P-Z8 244 B 1 13.9 8 S283UC-Z8 594 B 3 13.9
10 S203P-Z10 244 10 S283UC-Z10 594
16 S203P-Z16 244 16 S283UC-Z16 594
20 S203P-Z20 244 20 S283UC-Z20 594
25 S203P-Z25 248 25 S283UC-Z25 603
32 S203P-Z32 254 32 S283UC-Z32 612
40 S203P-Z40 266 40 S283UC-Z40 657
50 S203P-Z50 306 50 S283UC-Z50 756
63 S203P-Z63 344 63 S283UC-Z63 855
Z UC-Z
10,000
5000
10,000 Delivery Class
5000
A - Standard item, stock to 2 weeks lead time
1000
500
1000 B - Stock to 4 weeks lead time
500
C - 6 to 8 week lead time
100 100
50 50

10 10
5 5

1 1
0.5 0.5
seconds

seconds

AC
0.1 0.1
0.05 0.05
DC DC
0.01 0.01
1 2 3 5 10 20 30 1 2 3 5 10 20 30
multiple of rated current multiple of rated current

Low Voltage Products & Systems Discount schedule CB7 14.13


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S200U
pr ies
em er 240 VAC
y st 0 S
S 20
S Miniature MCCBs

K UL 489
VDE 0660
CSA C22.2 - NO. 5

Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order class order
current number price (1 pc.) current number price (1 pc.)
qty qty
1 pole 3 pole
0.2 S201U-K0.2 $ 54 0.2 S203U-K0.2 $ 194
0.3 S201U-K0.3 54 0.3 S203U-K0.3 194
0.5 S201U-K0.5 54 0.5 S203U-K0.5 194
0.75 S201U-K0.75 54 0.75 S203U-K0.75 194
1 S201U-K1 54 1 S203U-K1 194
1.6 S201U-K1.6 54 1.6 S203U-K1.6 194
2 S201U-K2 54 2 S203U-K2 194
S201U-K, 1 pole 3 S201U-K3 54 3 S203U-K3 194
4 S201U-K4 54 4 S203U-K4 194
5 S201U-K5 54 5 S203U-K5 194
6 S201U-K6 54 6 S203U-K6 194
8 S201U-K8 54 8 S203U-K8 194
10 S201U-K10 54 A 10 4.6 10 S203U-K10 194 A 1 13.9
13 S201U-K13 54 13 S203U-K13 194
15 S201U-K15 54 15 S203U-K15 194
16 S201U-K16 54 16 S203U-K16 194
20 S201U-K20 54 20 S203U-K20 194
25 S201U-K25 56 25 S203U-K25 196
30 S201U-K30 58 30 S203U-K30 200
32 S201U-K32 58 32 S203U-K32 200
S202U-K, 2 pole 40 S201U-K40 64 40 S203U-K40 214
50 S201U-K50 70 50 S203U-K50 246
60 S201U-K60 80 60 S203U-K60 280
63 S201U-K63 80 63 S203U-K63 280
2 pole 4 pole
0.2 S202U-K0.2 128 0.2 S204U-K0.2 265
0.3 S202U-K0.3 128 0.3 S204U-K0.3 265
0.5 S202U-K0.5 128 0.5 S204U-K0.5 265
0.75 S202U-K0.75 128 0.75 S204U-K0.75 265
1 S202U-K1 128 1 S204U-K1 265
1.6 S202U-K1.6 128 1.6 S204U-K1.6 265
2 S202U-K2 128 2 S204U-K2 265
3 S202U-K3 128 3 S204U-K3 265
14 S203U-K, 3 pole 4 S202U-K4 128 4 S204U-K4 265
5 S202U-K5 128 5 S204U-K5 265
6 S202U-K6 128 6 S204U-K6 265
8 S202U-K8 128 A 5 9.2 8 S204U-K8 265
10 S202U-K10 128 10 S204U-K10 265 B 1 18.0
13 S202U-K13 128 13 S204U-K13 265
15 S202U-K15 128 15 S204U-K15 265
16 S202U-K16 128 16 S204U-K16 265
20 S202U-K20 128 20 S204U-K20 265
25 S202U-K25 130 25 S204U-K25 275
30 S202U-K30 134 30 S204U-K30 285
32 S202U-K32 134 32 S204U-K32 285
40 S202U-K40 134 40 S204U-K40 314
50 S202U-K50 162 50 S204U-K50 343
S204U-K, 4 pole
60 S202U-K60 182 60 S204U-K60 392
K 63 S202U-K63 182 63 S204U-K63 392
10,000
5000
Delivery Class
1000
A - Standard item, stock to 2 weeks lead time
ch
500
B - Stock to 4 weeks lead time
a n
100
50
s br evice C - 6 to 8 week lead time

t e d a ive d
t
10

is
9 l rotec
5

4 8 p
UL cuit
1
0.5
seconds

r
AC
0.1
0.05
DC
ci
0.01
1 2 3 5 8 10 12 20 30
multiple of rated current

14.14 Discount schedule CB12 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S200U S2 tem
00 p
240 VAC Se ro M
rie
Miniature MCCBs s

Z UL 489
VDE 0660
CSA C22.2 - NO. 5

Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order class order
current number price (1 pc.) current number price (1 pc.)
qty qty
1 pole 3 pole
0.5 S201U-Z0.5 70 0.5 S203U-Z0.5 244
0.75 S201U-Z0.75 70 0.75 S203U-Z0.75 244
1 S201U-Z1 70 1 S203U-Z1 244
1.6 S201U-Z1.6 70 1.6 S203U-Z1.6 244
2 S201U-Z2 70 2 S203U-Z2 244
3 S201U-Z3 70 3 S203U-Z3 244
4 S201U-Z4 70 4 S203U-Z4 244
S201U-Z, 1 pole 5 S201U-Z5 70 5 S203U-Z5 244
6 S201U-Z6 70 6 S203U-Z6 244
8 S201U-Z8 70 8 S203U-Z8 244
10 S201U-Z10 70 A 10 4.6 10 S203U-Z10 244 A 1 13.9
15 S201U-Z15 70 15 S203U-Z15 244
16 S201U-Z16 70 16 S203U-Z16 244
20 S201U-Z20 70 20 S203U-Z20 244
25 S201U-Z25 70 25 S203U-Z25 248
30 S201U-Z30 74 30 S203U-Z30 254
32 S201U-Z32 74 32 S203U-Z32 254
40 S201U-Z40 78 40 S203U-Z40 266
50 S201U-Z50 88 50 S203U-Z50 306
60 S201U-Z60 100 60 S203U-Z60 344
S202U-Z, 2 pole 63 S201U-Z63 100 63 S203U-Z63 344
2 pole 4 pole
0.5 S202U-Z0.5 162 0.5 S204U-Z0.5 343
0.75 S202U-Z0.75 162 0.75 S204U-Z0.75 343
1 S202U-Z1 162 1 S204U-Z1 343
1.6 S202U-Z1.6 162 1.6 S204U-Z1.6 343
2 S202U-Z2 162 2 S204U-Z2 343
3 S202U-Z3 162 3 S204U-Z3 343
4 S202U-Z4 162 4 S204U-Z4 343
5 S202U-Z5 162 5 S204U-Z5 343
6 S202U-Z6 162 6 S204U-Z6 343
8 S202U-Z8 162 8 S204U-Z8 343
10 S202U-Z10 162 A 5 9.2 10 S204U-Z10 343 B 1 18.0
S203U-Z, 3 pole 15 S202U-Z15 162 15 S204U-Z15 343 14
16 S202U-Z16 162 16 S204U-Z16 343
20 S202U-Z20 162 20 S204U-Z20 343
25 S202U-Z25 170 25 S204U-Z25 343
30 S202U-Z30 170 30 S204U-Z30 363
32 S202U-Z32 170 32 S204U-Z32 363
40 S202U-Z40 176 40 S204U-Z40 382
50 S202U-Z50 206 50 S204U-Z50 431
60 S202U-Z60 232 60 S204U-Z60 490
63 S202U-Z63 232 63 S204U-Z63 490

Delivery Class
S204U-Z, 4 pole A - Standard item, stock to 2 weeks lead time
Z
n ch B - Stock to 4 weeks lead time
10,000
5000
a
br evice
C - 6 to 8 week lead time

s
1000

t e d a ive d
lis tect
500

9
48 pro
100

UL cuit
50

cir
10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 10 20 30
multiple of rated current

Low Voltage Products & Systems Discount schedule CB12 14.15


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S200UP
pr ies
em er 480Y/277 VAC
y st 0 S
S 20
S Miniature MCCBs

K UL 489
VDE 0660
CSA C22.2 - NO. 5

Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order class order
current number price (1 pc.) current number price (1 pc.)
qty qty
1 pole 3 pole
0.2 S201UP-K0.2 $ 90 0.2 S203UP-K0.2 $ 320
0.3 S201UP-K0.3 90 0.3 S203UP-K0.3 320
0.5 S201UP-K0.5 90 0.5 S203UP-K0.5 320
0.75 S201UP-K0.75 90 0.75 S203UP-K0.75 320
1 S201UP-K1 90 1 S203UP-K1 320
1.6 S201UP-K1.6 90 1.6 S203UP-K1.6 320
2 S201UP-K2 90 2 S203UP-K2 320
S201UP-K, 1 pole
3 S201UP-K3 90 3 S203UP-K3 320
4 S201UP-K4 90 4 S203UP-K4 320
5 S201UP-K5 90 5 S203UP-K5 320
6 S201UP-K6 90 6 S203UP-K6 320 A 1 13.9
8 S201UP-K8 90 A 10 4.6 8 S203UP-K8 320
10 S201UP-K10 90 10 S203UP-K10 320
13 S201UP-K13 90 13 S203UP-K13 320
15 S201UP-K15 90 15 S203UP-K15 320
16 S201UP-K16 90 16 S203UP-K16 320
20 S201UP-K20 90 20 S203UP-K20 320
25 S201UP-K25 90 25 S203UP-K25 320
2 pole 4 pole
0.2 S202UP-K0.2 210 0.2 S204UP-K0.2 440
S202UP-K, 2 pole 0.3 S202UP-K0.3 210 0.3 S204UP-K0.3 440
0.5 S202UP-K0.5 210 0.5 S204UP-K0.5 440
0.75 S202UP-K0.75 210 0.75 S204UP-K0.75 440
1 S202UP-K1 210 1 S204UP-K1 440
1.6 S202UP-K1.6 210 1.6 S204UP-K1.6 440
2 S202UP-K2 210 2 S204UP-K2 440
3 S202UP-K3 210 3 S204UP-K3 440
4 S202UP-K4 210 4 S204UP-K4 440
5 S202UP-K5 210 5 S204UP-K5 440
6 S202UP-K6 210 A 5 9.2 6 S204UP-K6 440 B 1 18.0
8 S202UP-K8 210 8 S204UP-K8 440
10 S202UP-K10 210 10 S204UP-K10 440
13 S202UP-K13 210 13 S204UP-K13 440
14 S203UP-K, 3 pole 15 S202UP-K15 210 15 S204UP-K15 440
16 S202UP-K16 210 16 S204UP-K16 440
20 S202UP-K20 210 20 S204UP-K20 440
25 S202UP-K25 210 25 S204UP-K25 440

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time
h
r a nc e
c
S204UP-K, 4 pole
a s b devi
ed e
K
l ist tectiv
9
48 t pro
10,000

L
5000

U cui
cir
1000
500

100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 8 10 12 20 30
multiple of rated current

14.16 Discount schedule CB17 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
S200UP S2 tem
00 p
480Y/277 VAC Se ro M
rie
Miniature MCCBs s

Z UL 489
VDE 0660
CSA C22.2 - NO. 5

Cable & equipment protection

Rated Catalog List Delivery Sugg. Wgt. oz. Rated Catalog List Delivery Sugg. Wgt. oz.
class order class order
current number price (1 pc.) current number price (1 pc.)
qty qty
1 pole 3 pole
0.5 S201UP-Z0.5 115 0.5 S203UP-Z0.5 400
0.75 S201UP-Z0.75 115 0.75 S203UP-Z0.75 400
1 S201UP-Z1 115 1 S203UP-Z1 400
1.6 S201UP-Z1.6 115 1.6 S203UP-Z1.6 400
2 S201UP-Z2 115 2 S203UP-Z2 400
3 S201UP-Z3 115 3 S203UP-Z3 400
4 S201UP-Z4 115 4 S203UP-Z4 400
S201UP-Z, 1 pole 5 S201UP-Z5 115 5 S203UP-Z5 400
6 S201UP-Z6 115 6 S203UP-Z6 400 A 1 13.9
8 S201UP-Z8 115 A 10 4.6 8 S203UP-Z8 400
10 S201UP-Z10 115 10 S203UP-Z10 400
15 S201UP-Z15 115 15 S203UP-Z15 400
16 S201UP-Z16 115 16 S203UP-Z16 400
20 S201UP-Z20 115 20 S203UP-Z20 400
25 S201UP-Z25 115 25 S203UP-Z25 400
2 pole 4 pole
0.5 S202UP-Z0.5 270 0.5 S204UP-Z0.5 564
0.75 S202UP-Z0.75 270 0.75 S204UP-Z0.75 564
1 S202UP-Z1 270 1 S204UP-Z1 564
1.6 S202UP-Z1.6 270 1.6 S204UP-Z1.6 564
S202UP-Z, 2 pole
2 S202UP-Z2 270 2 S204UP-Z2 564
3 S202UP-Z3 270 3 S204UP-Z3 564
4 S202UP-Z4 270 4 S204UP-Z4 564
5 S202UP-Z5 270 5 S204UP-Z5 564
6 S202UP-Z6 270 A 5 9.2 6 S204UP-Z6 564 B 1 18.0
8 S202UP-Z8 270 8 S204UP-Z8 564
10 S202UP-Z10 270 10 S204UP-Z10 564
15 S202UP-Z15 270 15 S204UP-Z15 564
16 S202UP-Z16 270 16 S204UP-Z16 564
20 S202UP-Z20 270 20 S204UP-Z20 564
25 S202UP-Z25 270 25 S204UP-Z25 564

S203UP-Z, 3 pole
Delivery Class 14
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

h
r a nc e
c
a s b devi
ed e
S204UP-Z, 4 pole
l ist tectiv
9
48 t pro
Z
10,000
5000
L
U cui
1000
500
cir
100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 10 20 30
multiple of rated current

Low Voltage Products & Systems Discount schedule CB17 14.17


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S290
pr ies
em er 480Y/277 VAC
y st 0 S
S 20
S

C
VDE 0660
Cable and equipment protection
480 VAC
Rated Catalog List Delivery Sugg. Wgt. oz.
class order
current number price (1 pc.)
qty
1 pole
80 S291-C80 $ 138
100 S291-C100 144 B 6 9.2
125 S291-C125 192
2 pole
80 S292-C80 340
100 S292-C100 364 B 3 18.4
125 S292-C125 568
S291-C80
3 pole
80 S293-C80 536
100 S293-C100 548 B 2 27.6
125 S293-C125 732
4 pole
80 S294-C80 740
100 S294-C100 756 B 1 36.8
125 S294-C125 948

Auxiliary contact
S290-H11 S290-H11 72 B 1 1.75

Bell alarm
S290-S 112 B 1 1.75

Shunt trip
S290-A1 144 B 1 6.2
For field mounting, left side, 110V – 415VAC
S290-A2 144 B 1 6.2
For field mounting, left side, 24 – 48VDC

14
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

C
10,000
5000

1000
500

100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 10 18 20 30
multiple of rated current

14.18 Discount schedule CB12 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Accessories S2 tem
00 p
Busbars Se ro M
rie
s

0HASE
Amp Number Busbar End cap List Delivery Suggested Weight
For Catalog
rating of length catalog class order qty. (ozs)
use on: number price
poles (mm) number quantity

S200 & 63 60 988 PS-END0 PS1/60 $ 36 A 1 9


S200P 1 80 60 988 PS-END0 PS1/60/16 46 14

S200U & 6 108 – PS1/6/16BP 30 1.4
, S200UP 80 12 216 – PS1/12/16BP 60 B 1 2.9
23 18 324 – PS1/18/16BP 90 4.3
,

0HASE
Amp Number Busbar End cap Delivery Suggested Weight
For Catalog List
rating of length catalog class order qty.
use on: number price (ozs)
poles (mm) number quantity

S200 & 63 58 1035 PS-ENDSP PS2/58SP $ 122 11


S200P 1 80 58 1035 PS-ENDSP PS2/58/16SP 152 A 1 18
S200U & 6 108 – PS2/6/16BP 40 1.8
, S200UP 80 12 216 – PS2/12/16BP 80 B 1 3.7
, 23 18 324 – PS2/18/16BP 120 5.5

, , , ,

0HASE
Amp Number Busbar End cap Delivery Suggested
For Catalog List Weight
rating of length catalog class order qty.
use on: number price (ozs)
poles (mm) number quantity

S200 & 63 60 1065 PS-ENDSP PS3/60SP $ 130 12


A 1
S200P 1 80 60 1065 PS-ENDSP PS3/60/16SP 176 20

S200U & 6 108 – PS3/6/16BP 44 2
, S200UP 80 12 216 – PS3/12/16BP 88 B 1 4
, 23 18 324 – PS3/18/16BP 132 6
,
14
, , , , , ,

0HASE
Amp Number Busbar End cap Delivery Suggested
For Catalog List Weight
rating of length catalog class order qty.
number price (ozs)
use on: poles (mm) number quantity

S200 &
80 60 1056 PS-END1SP PS4/60/16SP $ 236 22
B 1
S200P

,
, Delivery Class
,
, A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
, , , , , , , , C - 6 to 8 week lead time

NOTE
All bus bars may be center fed in
order to double the ampacity rating

NOTE
BUS BARS MAY BE USED ON LINE OR LOAD
SIDE OF MCBS

1 UL Approved for use on UL1077 miniature circuit breakers. UL File #E76126


2 UL approved for use on UL 489 miniature circuit breakers. UL File # E250145
3 UL 489 bus bars may not be cut.

Low Voltage Products & Systems Discount schedule CB8 14.19


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Accessories
pr ies
em er Busbars
y st 0 S
S 20
S

1 Phase with 1 auxiliary


Amp Number Busbar End cap Delivery Suggested Weight
For Catalog List
rating of length catalog class order qty.
use on: number price (ozs)
poles (mm) number quantity

S200 & 63 38 1044 PS-END0 PS1/38H $ 50


B 1 7.4
S200P 80 38 1044 PS-END0 PS1/38/16H 56 10.1

L1

L1 L1 L1....

2 Phase with 1 auxillary


0HASE Amp Number Busbar End cap Catalog List Delivery Suggested Weight
For rating of length catalog class order qty.
, , , , , , use on: number price (ozs)
poles (mm) number quantity

S200 & 80 48 1065 PS-ENDSP PS2/48/16SP $ 174 B 1 23.3


,
, S200P
,

L1
L2

L1 L2 L1 L2 L1 L2....

3 Phase with 1 auxillary


0HASE Amp Number Busbar End cap Catalog List Delivery Suggested Weight
For rating of length catalog class
, order qty.
number price (ozs)
use on: poles (mm) number quantity

200 &
S 80 39 980 PS-ENDSP PS3/39/16SP $ 158 B 1 22.6
,
S200P

L1
L2
L3
14
L1 L2 L3 L1 L2 L3....

0HASE . FORUSEWITHPOLE-#"gS
ONPHASE7SYSTEM
Amp Number Busbar End cap Delivery Suggested Weight
Catalog List
For rating of length catalog class order qty.
number price (ozs)
use on: poles (mm) number quantity

200 &
S 80 58 1048 PS-END1SP PS4/58/16NSP $ 238 B 1 30.8
S200P
Insulated busbar assembly contains 4 separate circuits for use with 1+N or 2 pole MCBs.
.
,
,
,
Delivery Class
, . , . , . , . , A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

-#""USBARACCESSORIES
"USBARMOUNTED NOTE
TERMINALBLOCK "USTOOTHCOVERS
All bus bars may bePN3: "3+ POLES
PN3: %3+ POLE center fed in
order to double the ampacity rating

NOTE
BUS BARS MAY BE USED ON LINE OR LOAD
SIDE OF MCBS"USBAR%ND#APS

14.20 Discount schedule CB8 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Accessories S2 tem
00 p
Se ro M
rie
s

Electrical For Catalog List Delivery Suggested Wgt. oz.


accessories use on: number price class order quantities (1 pc.)

Auxiliary contacts
For field mounting: right side S200 &
S2C-H6R
Form C 1 NO / 1 NC S200P
$ 36 A 1 1.4
S200U
S200UP S2C-H6RU

The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC.
S2C-H6R Minimum operating voltage is 24 VAC/VDC.
Wire size: 18 AWG to 16 AWG.

Bell alarm
S200 &
S200P S2C-S/H6R
For field mounting, right side 48 A 1 1.4
S200U
S2C-S6RU
S200UP
The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm
or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without
opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC.
S2C-S/H6R
* Combination bell alarm/auxiliary contact

Shunt trip
S200 & S2C-A1
For field mounting, right side S200P S2C-A2
A1: 12-60 VAC (12-60VDC) 138 A 1 5.2
A2: 110-415 VAC (110-250 VDC) S200U & S2C-A1U
S200UP S2C-A2U
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is
applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC).

S2C-A_ Undervoltage release


For field mounting, right side
12 VDC S2C-UA12
24 VAC S2C-UA24
48 VAC S200 & S2C-UA48
110 VAC S200P
216
S2C-UA110
A 1 5.2 14
220 VAC S2C-UA230
415 VAC S2C-UA400
When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless
proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory.

S2C-UA_ Delivery Class


A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

Low Voltage Products & Systems Discount schedule CB8 14.21


9/6/07 Rev.
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Accessories
pr ies
em er S200
y st 0 S
S 20
S

Electrical Catalog List Delivery Suggested Wgt. oz.


accessories number price class order quantities (1 pc.)

Front mounting kit


For 2 poles S500-ME1 $ 60 2.1
For 2 – 5 poles S500-ME2 70 1 2.9
A
For 2 – 10 poles S500-ME3 80 3.6
Optional rear terminals S500-K1 16 1.5
Includes flange, mounting rail and hardware.
S500-ME2

Front mounting clip


For 1 – 4 poles MB-CL 35 A 1 2
Simple mounting clip for up to four module mounting.

Front mounting bracket


For 1 – 3 poles MB-3PD 35 A 1 2.5
For flush mounting of three pole MCBs: includes hardware.
MB-CL
Locking device
Adaptor only SA1 9 10 0.7
A
Padlock only w/ 2 keys SA2 19 0.1
Allows breaker to be locked in ON or OFF position.

Labeling accessory
MB-3PD 1 sheet = 40 blank labels BS 74 A 1 —
1 sheet = 40 numbered labels BS1/40 74
Adhesive labels mount on front face of components.

Enclosure, IP40
For 2 modules 12402 32 2.0
For 4 modules 12404 45 1 2.8
SA1
B
For 6 modules 12406 56 3.4
For 8 modules 12408 66 4.1
For additional protection against accidental contact. Includes integrated mounting rail.

Enclosure, IP55
14 SA2 For 4 modules 12644 84 8.1
For 6 modules 12646 98 1 10.8
A
For 10 modules 12650 126 20.4
For 20 modules 12652 210 41.0
Molded plastic complete with mounting rail and knock-outs for cable entries.

Blanking plates
Single pole (set of 10) BP-1P 6 A 1 —
Twelve pole (snap-off, set of 1) BP-12P 7 — — —
12404

Handle mechanism
S2C-DH 76 A 1 9.2
For use with 2, 3 and 4 pole S2 MCBs and disconnect switch handles with 5mm shaft.

DIN rail
Universal mounting SMR-39 21 A 1 8
35mm DIN rails are available in 39-inch strips (1 meter).

S2C-DH
Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

SMR-39

14.22 Discount schedule CB8 Low Voltage Products & Systems


1SXU000023C0201 Discount schedule H6 – Handles & shafts ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Accessories S2 tem
00 p
S200 Se ro M
rie
s

Busbar accessories
Catalog List Delivery Suggested Weight
Description number price class order qty. ounce
qty. (2 pc.)

Busbar end caps 2 & 3 phase PS-ENDSP $ 2 A 10 —


4 phase PS-END1SP
Busbar tooth covers SZ-BSK 4 A 10 —
(shrouds unused portion of busbar)
Busbar mounted terminal block,
1 pole, for use on all busbars. SZ-ESK2 10 A 1 1.0
SZ-BSK Wire size: 14 AWG to 2 AWG

Electrical accessories
Catalog List Delivery Suggested Wgt. oz.
Item
number price class order quantities (1 pc.)

Posidrive tools
Screwdriver, #1 SD-PZ1 $ 40 A 1 4
Screwdriver, #2 SD-PZ2 40 A 1 4
Bit, #1 BIT-PZ1 4 A 1 4
Bit, #2 BIT-PZ2 4 A 1 4
SZ-ESK2

Connection terminals
Cross section For Catalog List Delivery Suggested Wgt. oz.
AWG/mm2 use on: number price class order quantities (1 pc.)
1/0 (50mm2) Straight SZ-AST55I $ 15 10 0.5
S200 & S200P B
1/0 (50mm ) 90°
2
SZ-AST50I 15 10 0.5
1/0 (50mm2) Straight SZ-AST55U 15 10 0.5
SZ-AST55_ S200U & S200UP B
1/0 (50mm2) 90° SZ-AST50U 15 10 0.5

Ring tongue accessories


Catalog List Delivery Suggested Weight
Description For use on number price class order qty. ounce
qty. (2 pc.)

Ring tongue terminal S200 & S200P


SZ-AST55UPRT $ 5 A 10 0.5
S200U & S200UP
Plug S2C-P N/C A 10 —
14
SZ-AST50_

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

Low Voltage Products & Systems Discount schedule CB8 14.23


9/6/07 Rev.
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Technical data
pr ies
em er Mounting and operating instructions
y st 0 S
S 20
S

Mounting Operation
Universal mounting position using snap-on MCBs are switched on by moving the handle to the
mounting to standard 35x7.5mm DIN rail. upper position. Stamped onto the handle switch, a
“I” is visible confirming that the breaker is closed.
Miniature circuit breakers (MCBs) can also be
mounted to front of door using a panel cut-out with The MCBs are “trip-free,” if the handle is being
breaker handle protruding through panel opening forced to the “ON” position, the breaker will still trip
for external operation. Special front mounting kit under fault conditions.
page 23.
The “O” marking indicates that the breaker is in the
Mounting MCB Connection “OFF” position. The MCB is now open and the load
Terminals are suitable for solid or flexible is disconnected from line power.
conductors from 18 to 4 AWG (0.75 to 25mm2) with When a breaker has tripped, the MCB handle should
no busbar connected. When maximum busbar size first be set to the full “OFF” position to make certain
of 36 mm2 is used, maximum cable is 6 AWG (16 the trip mechanism has been reset. Once the fault
mm2).
has been determined and cleared the MCB can
Maximum tightening torque of 17.5 in-lb (2 Nm) again be switched “ON”.
for line/load terminals and 4.5 in-lb (0.5Nm) for
accessory device terminals. Maintenance
ABB miniature circuit breakers require no special
maintenance; only normal electrical system
maintenance procedures are required.

Removing MCB

Possible mounting arrangements of MCB accessories

Legend
Auxiliary contact H
+S/H+S/H (H)+S/H (H)
S 200
Bell alarm/Auxiliary contact S/H
Bell alarm/Auxiliary contact
+H+H+H used as auxiliary contact S/H (H)
14 Shunt trip ST
Undervoltage release UR

+ST+H+H+H

+ST+S/H+S/H (H)+S/H (H)

+UR+H+H+H

+UR+S/H+S/H (H)+S/H (H)

14.24 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Technical data S2 tem
00 p
Busbars & connectors Se ro M
rie
Connection methods s

Top and bottom dual function terminals Terminals allow for connection of cable Two slots per terminal offer the ability to
provided in open position for connection to 18-4 AWG [top row] and 18-8 AWG [bottom connect, independently, two conductors.
busbars or cable. row]. This may be cables or bus bar.

Top and bottom terminals may be bussed Easy removal of devices from an assembly Conductors may only be inserted into open
together with single phase or multi-phase when using bus bar in the bottom, load side terminals, preventing mis-wiring and potential
busbars as shown. Both line and load side terminals. problems.
terminals can be bus bar connected.
14

Low Voltage Products & Systems 14.25


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Technical data
pr ies
em er
y st 0 S
S 20
S

Item S200-B S200-C, -D S200-K S200P-K


Approvals:
UL 1077 1077 1077 1077
CSA C22.2 — No.235 C22.2 — No. 235 C22.2 — No. 235 —
VDE 0641, 0660 0660 0660 0660
IEC 898, 947 898, 947 898, 947 898, 947

No. of poles: 1,2,3,4 1+N,3+N 1,2,3, 1+N,3+N 1,2,3,4, 1+N,3+N 1,2,3,4,1+N,3+N

Tripping characteristic: B C,D K K

Rated currents: 6 to 63A 0.5 to 63A 0.5 to 63A 0.2 to 63A

Minimum operating voltage: 12V 12V 12V 12V

UL/CSA rated voltage & Single pole Multi pole Single pole Multi pole Single pole Multi pole Single pole Multi pole
interrupting capacity
120VAC — 10kA
10kA — 10kA — 10kA —

10kA 10kA 10kA


240VAC 6kA 10kA 6kA 10kA 6kA

— 10kA
277VAC 6kA — 6kA — 6kA —
277/480 VAC — 6kA — 6kA — 6kA — 10kA

60VDC 10kA 10kA 10kA 10kA 10kA 10kA — —
125VDC — 10kA — 10kA — 10kA — —

Frequency: 50/60Hz (See below) 50/60Hz (see below) 50/60Hz (see below) 50/60Hz (see below)

Rated voltage
IEC single pole 240/415VAC 240/415VAC 240/415VAC 240/415VAC
60VDC 60VDC 60VDC 60VDC
IEC multi-pole 415VAC 415VAC 415VAC 415VAC
110VDC 110VDC 110VDC 110VDC

Protection category: IP20 IP20 IP20 IP20

Depth of unit per DIN 43880: 68mm 68mm 68mm 68mm

Mounting position: optional optional optional optional

Standard mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail

Main and shunt trip terminals:


Wire size 18‑4 AWG [top] 18-4 AWG [top] 18-4 AWG [top] 18-4 AWG [top]
18-8 [bottom] 18-8 [bottom] 18-8 [bottom] 18-8 [bottom]
14 Torque 17.5 in-lbs. 17.5 in-lbs. 17.5 in-lbs. 17.5 in-lbs.
Tool #2 Posidrive #2 Posidrive #2 Posidrive #2 Posidrive

Accessory terminals
Wire size 18-16 AWG 18-16 AWG 18-16 AWG 18-16 AWG
Torque 4.5 in-lbs. 4.5 in-lbs. 4.5 in-lbs. 4.5 in-lbs.
Tool #1 Posidrive #1 Posidrive #1 Posidrive #1 Posidrive

Service life at rated load: In < 32 A, 20,000 operations In < 32 A, 20,000 operations In < 32 A, 20,000 operations In < 32 A, 20,000 operations
In > 32 A, 10,000 operations In > 32 A, 10,000 operations In > 32 A, 10,000 operations In > 32 A, 10,000 operations

Ambient temperatures: -25°C to +70°C -25°C to +70°C -25°C to +70°C -25°C to +70°C
Storage temperatures -40°C to + 70°C -40°C to + 70°C -40°C to + 70°C -40°C to + 70°C

Shock resistance: 30g minimum of 2 impacts, 30g minimum of 2 impacts, 30g minimum of 2 impacts, 30g minimum of 2 impacts,
shock duration of 13ms shock duration of 13ms shock duration of 13ms shock duration of 13ms

Vibration resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In @ 0.8 ~ In @ 0.8 ~ In @ 0.8 ~ In

Disconnecting neutral rating: 6kA switching 6kA switching 6kA switching —

Influence of frequency on electro-magnetic trips


Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:

16 2/3 - 60Hz 100Hz 200Hz 400Hz DC


Approx. factor 1 1.1 1.2 1.5 1.5

Thermal tripping is independent of frequency.

14.26 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Technical data S2 tem
00 p
Se ro M
rie
s

Item S280UC-K S200P-Z S280UC-Z S290-C


Approvals:
UL 1077 1077 1077 —
CSA — — — —
VDE 0660 0660 0660 0660
IEC 898,947 898, 947 898, 947 898

No. of poles: 1,2,3 1,2,3,4 1,2,3 1,2,3,4

Tripping characteristic: K Z Z C

Rated currents: 0.2 to 63A 0.5 to 63A 0.5 to 63A 80 to 125A

Minimum operating voltage: 12V 12V 12V 12V

UL/CSA rated voltage & Single pole Multi pole Single pole Multi pole Single pole Multi pole
interrupting capacity
120VAC 10kA — 10kA — 10kA — —

240VAC 10kA 10kA 10kA 10kA 10kA 10kA —

277VAC 10kA 10kA 10kA
— — — —

277/480 VAC — 4.5kA for 0.2-40A — 10kA — 4.5kA for 0.2-40A —
5kA for 50-63A 5kA for 50-63A

60VDC 10kA 10kA — — 10kA 10kA —
125VDC 10kA 10kA — — 10kA 10kA —
250VDC 4.5kA 4.5kA — — 4.5kA 4.5kA —
500VDC — 4.5kA — — — 4.5kA —

Frequency: 50/60Hz (see below) 50/60 Hz (see below) 50/60Hz (see below) 50/60Hz (see below)
Rated voltage
IEC single pole 240/415VAC 240/415VAC 240/415VAC 230/440VAC
220VDC 60VDC 220VDC 60VDC
IEC multi-pole 415VAC 415VAC 415VAC 440VAC
440VDC 110VDC 440VDC 110VDC

Protection category: IP20 IP20 IP20 IP20

Depth of unit per DIN 43880: 68mm 68mm 68mm 70mm

Mounting position: optional optional optional optional

Standard mounting: 35mm DIN rail 35mm DIN rail 35mm DIN-rail 35mm DIN-rail

Main and shunt trip terminals: 14


Wire size 0.2-40A 18‑4 AWG 18-4 AWG [top] 0.5-40A 18-4 AWG 80-125A 14-1/0 AWG
50A & above 18-2 AWG 18-8 AWG [bottom] 18-2 AWG
Torque 17.5 in-lbs. 17.5 in-lbs. 17.5 in-lbs. 17.5 in-lbs.
Tool #2 Posidrive #2 Posidrive #2 Posidrive #2 Posidrive

Accessory terminals
Wire size 18-16 AWG 18-16 AWG 18-16 AWG 18-16 AWG
Torque 4.5 in-lbs. 4.5 in-lbs. 4.5 in-lbs. 4.5 in-lbs.
Tool #1 Posidrive #1 Posidrive #1 Posidrive #1 Posidrive

Service life at rated load: In < 32 A, 20,000 operations In < 32 A, 20,000 operations In < 32 A, 20,000 operations 10,000 operations
In > 32 A, 10,000 operations In > 32 A, 10,000 operations In > 32 A, 10,000 operations ––

Ambient temperatures: -25°C to +55°C -25°C to +70°C -25°C to +55°C -5°C to +45°C
Storage temperatures -40°C to + 70°C -40°C to + 70°C -40°C to + 70°C -40°C to + 70°C

Shock resistance: 30g minimum of 2 impacts, 30g minimum of 2 impacts, 30g minimum of 2 impacts, 30g minimum of 2 impacts,
shock duration of 13ms shock duration of 13ms shock duration of 13ms shock duration of 13ms

Vibration resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 60m/s2, at 10 – 150 Hz
@ 0.8 ~ In @ 0.8 ~ In @ 0.8 ~ In

Influence of frequency on electro-magnetic trips


Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:

16 2/3 - 60Hz 100Hz 200Hz 400Hz DC


Approx. factor 1 1.1 1.2 1.5 1.5

Thermal tripping is independent of frequency.

Low Voltage Products & Systems 14.27


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Technical data
pr ies
em er
y st 0 S
S 20
S

Item S200U-K S200U-Z S200UP-K S200UP-Z


Approvals:
UL 489 489 489 489
CSA C22.2 No.5 C22.2 No.5 C22.2 No.5 C22.2 No.5
VDE 0660 0660 0660 0660
IEC 898,947 898, 947 898, 947 898

No. of poles: 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4

Tripping characteristic: K Z K Z

Rated currents: 0.2 to 63A 0.2 to 63A 0.2 to 25A 0.2 to 25A

Minimum operating voltage: 12V 12V 12V 12V

UL/CSA rated voltage &


interrupting capacity
120VAC 10kA 10kA 10kA 10kA

240VAC 10kA 10kA 10kA 10kA

277VAC 10kA 10kA

480/277 VAC — — 10kA 10kA

Frequency: 50/60Hz (see below) 50/60 Hz (see below) 50/60Hz (see below) 50/60Hz (see below)
Rated voltage
IEC single pole 240/415VAC 240/415VAC 240/415VAC 240/415VAC
220VDC 60VDC 220VDC 220VDC
IEC multi-pole 415VAC 415VAC 415VAC 415VAC
440VDC 110VDC 440VDC 440VDC

Protection category: IP20 IP20 IP20 IP20

Depth of unit per DIN 43880: 68mm 68mm 68mm 68mm

Mounting position: optional optional optional optional

Standard mounting: 35mm DIN rail 35mm DIN rail 35mm DIN-rail 35mm DIN-rail

Main and shunt trip terminals:


Wire size 18-4 AWG [top] 18-4 AWG [top] 18-4 AWG [top] 18-4 AWG [top]
18-8 AWG [bottom] 18-8 AWG [bottom] 18-8 AWG [bottom] 18-8 AWG [bottom]
Torque 17.5 in-lbs. 17.5 in-lbs. 17.5 in-lbs. 17.5 in-lbs.
Tool #2 Posidrive #2 Posidrive #2 Posidrive #2 Posidrive

Accessory terminals
14 Wire size 18-16 AWG 18-16 AWG 18-16 AWG 18-16 AWG
Torque 4.5 in-lbs. 4.5 in-lbs. 4.5 in-lbs. 4.5 in-lbs.
Tool #1 Posidrive #1 Posidrive #1 Posidrive #1 Posidrive

Service life at rated load: In < 32 A, 20,000 operations In < 32 A, 20,000 operations In < 32 A, 20,000 operations In < 32 A, 20,000 operations
In > 32 A, 10,000 operations In > 32 A, 10,000 operations In > 32 A, 10,000 operations In > 32 A, 10,000 operations

Ambient temperatures: -25°C to +70°C -25°C to +70°C -25°C to +70°C -25°C to +70°C
Storage temperatures -40°C to + 70°C -40°C to + 70°C -40°C to + 70°C -40°C to + 70°C

Shock resistance: 30g minimum of 2 impacts, 30g minimum of 2 impacts, 30g minimum of 2 impacts, 30g minimum of 2 impacts,
shock duration of 13ms shock duration of 13ms shock duration of 13ms shock duration of 13ms

Vibration resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz
@ 0.8 ~ In @ 0.8 ~ In @ 0.8 ~ In @ 0.8 ~ In

Influence of frequency on electro-magnetic trips


Magnetic trip values shown on trip curves are valid for 50/60Hz applications.
For frequencies other than 50/60Hz, the magnetic (instantaneous) trip values are
increased by the factor given below:

16 2/3 - 60Hz 100Hz 200Hz 400Hz DC


Approx. factor 1 1.1 1.2 1.5 1.5

Thermal tripping is independent of frequency.

14.28 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Technical data S2 tem
00 p
Wire size comparison Se ro M
rie
s

Comparison of IEC and AWG wire sizes

mm AWG (mm ) Amps / UL Amps / IEC


1.0 — — 8
— 16 (1.3) 10 —
1.5 — — 12
— 14 (2.1) 15 —
2.5 — — 20
— 12 (3.3) 20 —
4 — — 25
— 10 (5.3) 30 —
6 — — 32
— 8 (8.4) 50 —
10 — — 50
— 6 (13.3) 65 —
16 — — 65
— 4 (21.2) 85 —
25 — — 85
— 3 (26.7) 100 —
— 2 (33.6) 115 —
35 — — 115

Ampacities for AWG wire are based on copper cable rated 75° C, except for 16AWG which is based on 60° C wire. Taken from UL508 Table 52.2.

Consult applicable standards for futher detail and information.

14

Low Voltage Products & Systems 14.29


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Approximate dimensions
pr ies
em er S200, S200P, S200U, S200UP
y st 0 S
S 20 00.00 Inches
S 00.00 [Millimeters]

S200 & S200P

S200U S200UP

14

S290
Accessories mount to right side
of MCB only

1.77
45

1.97 1.03 1.06


50 26 27
0.69 0.35 0.35
2.13 54 17.5 9 9
3.19 81
-A1, -A2 -H -S
Shunt Auxiliary Bell
trip switch alarm

S290

14.30 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Approximate dimensions S2 tem
00 p
Accessories Se ro M
rie
00.00 Inches s
00.00 [Millimeters]

Accessories
mm
S 2C-H...
S 2C-A... S 2C-S...
S 2C-UA... S 2C-S/H...

17.5 69 8.8 69
85

45

85

45
6.8 6.8

44 44

MB-CL mm
Front mounting clip
C.L.
1.77
45 D

2.26 1.77 C.L.


57.5 45

0.69
17.5
1.38
35
2.07
52.5
MB-3PD
Front mounting bracket 14
MB-CL 3.25
2.12 ( 3P )
in
1.43 ( 2P )

1.87
CL

C
L
BREAKER CUT OUT

0.74 ( 1P )

BKT. MT. HOLES


0.25 DIA. TYP 2
S2C-DH
CL CL
Handle mechanism 0.63
MB-3PD16

2.07 52.5 0.83


1.38 35 21

1.77 4.36
45 110.4
3.54
90
3.26
82.5

0.27 6.9

Low Voltage Products & Systems 14.31


ABB Inc. • 888-385-1221 • www.abb-control.com RHS2-M 1SXU000023C0201
o
M Approximate dimensions
pr ies
em er Accessories
y st 0 S
S 20
S 00.00
00.00
Inches
[Millimeters]

12402-12408

12644 12650
4.92 4.92
125 125
4.92 230
4.13 125 4.13 9.06
105 105

7.09 7.09
180 180

14

12646 12644 12652 12650


6.09
155
9.84
4.92
125 5.32 250
6.30 135
4.13 160
105

7.09
180
12.60
320

12646

12652

14.32 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
s
Cross-reference S2 tem
00 p
Se ro M
rie
s

Older Suggested Physical Electrical


version replacement comparison comparison
series

S260-B S200-B Same pole spacing Same trip characteristic


S260-C S200-C Same pole spacing Same trip characteristic
S260-D S200-D Same pole spacing Same trip characteristic
S270-K S200-K Same pole spacing Same trip characteristic
S280-K S200P-K Same pole spacing Same trip characteristic
S280-Z S200P-Z Same pole spacing Same trip characteristic
S280U-K S200U-K Same pole spacing Same trip characteristic
S280UX-K S200U-K Smaller pole spacing Same trip characteristic

Many older styles of ABB miniature circuit breakers have been replaced by new and improved versions. Many of these newer styles can be directly interchanged, both
electrically and physically, with the older version. There are also many international styles of ABB circuit breakers which are not normal stock items and may be inter-
changed with stocked ABB versions.

14

Low Voltage Products & Systems 14.33


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
ys S
System pro M compact S5 tem
Miniature Circuit Breakers 00 Se pro

Miniature circuit breakers


rie M
S500 Series s

Description Features
Increasing energy requirements result in • High breaking capacity
larger short-circuit currents which place • Energy-limiting
heavy demands on protective switchgear • Current-limiting
regarding safety, reliability and switching
capacities. • Extremely fast breaking time
The S500 heavy-duty circuit breaker fulfills • Optimal selectivity
these requirements by virtue of its technical • Various versions for special applications 14
features. It is equipped with a thermal and/ • Compact dimensions, DIN cap size
or electromagnetic release to protect circuits,
motors, switchgear and systems from the • Easy and quick to install
effects of overload and short-circuit currents. • Easy to connect; finger safe terminals
For the worldwide market, the S500 breakers • Wide range of accessories
carry UL, CSA, IEC, CE and many other • UL 1077 recognized 600VAC and
agency approvals. 500VDC versions

UL File # E167556
S500

Low Voltage Products & Systems 14.35


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S500
pr ies
em er 600Y/277 VAC
y st 0 S
S 50
S

B UL 1077
VDE 0641
CSA C22.2
IEC 947-2
C UL 1077
VDE 0641
CSA C22.2
IEC 947-2

Rated Catalog List Delivery Weight Rated Catalog List Delivery Weight
current number price class (oz.) 1 pc current number price class (oz.) 1 pc
1 pole 1 pole
6 S501-B6 $ 168 6 S501-C6 $ 168
10 S501-B10 168 10 S501-C10 168
13 S501-B13 168 13 S501-C13 168
16 S501-B16 168 16 S501-C16 168
S501-C16 20 S501-B20 168 20 S501-C20 168
B 8.90 B 8.90
25 S501-B25 168 25 S501-C25 168
32 S501-B32 168 32 S501-C32 168
40 S501-B40 168 40 S501-C40 168
50 S501-B50 186 50 S501-C50 184
63 S501-B63 202 63 S501-C63 202
2 pole 2 pole
6 S502-B6 328 6 S502-C6 328
10 S502-B10 328 10 S502-C10 328
13 S502-B13 328 13 S502-C13 328
16 S502-B16 328 16 S502-C16 328
20 S502-B20 328 20 S502-C20 328
B 17.85 B 17.85
S502-C6 25 S502-B25 328 25 S502-C25 328
32 S502-B32 328 32 S502-C32 328
40 S502-B40 328 40 S502-C40 328
50 S502-B50 362 50 S502-C50 362
63 S502-B63 392 63 S502-C63 392
3 pole 3 pole
6 S503-B6 478 6 S503-C6 478
10 S503-B10 478 10 S503-C10 478
13 S503-B13 478 13 S503-C13 478
16 S503-B16 478 16 S503-C16 478
20 S503-B20 478 20 S503-C20 478
B 25.36 B 25.36
25 S503-B25 478 25 S503-C25 478
S503-C10
32 S503-B32 478 32 S503-C32 478
B 40 S503-B40 478 40 S503-C40 478
10,000 50 S503-B50 526 50 S503-C50 526
5000 63 S503-B63 574 63 S503-C63 574

1000

14
D
500
UL 1077 CSA C22.2
VDE 0641 IEC 947-1
Delivery Class
100
50
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
Rated Catalog List Delivery Wgt. oz.
10
current number price class (1 Pc.)
C - 6 to 8 week lead time
5

1 pole
1 D
0.5 13 S501-D13 $ 190 10,000
seconds

AC 16 S501-D16 190 5000


0.1 20 S501-D20 190
0.05 25 S501-D25 190 1000
DC B 8.90
32 S501-D32 190 500
0.01 40 S501-D40 190
1 2 3 5 7 10 20 30 50 S501-D50 210 100
50
multiple of rated current 63 S501-D63 226
C 2 pole 10
5
10,000 13 S502-D13 372
5000
16 S502-D16 372 1
20 S502-D20 372 0.5
1000
seconds

25 S502-D25 372
500 B 17.85 AC
32 S502-D32 372 0.1

100
40 S502-D40 372 0.05
DC
50 50 S502-D50 408
63 S502-D63 442 0.01
10 1 2 3 5 10 20 30
5
3 pole
multiple of rated current
13 S503-D13 544
1 16 S503-D16 544
0.5 20 S503-D20 544
seconds

AC 25 S503-D25 544
0.1 B 25.36
32 S503-D32 544
0.05
DC 40 S503-D40 544
50 S503-D50 600
0.01
63 S503-D63 646
1 2 3 5 10 18 20 30
multiple of rated current

14.36 Discount schedule CB10 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
S500 s
S5 tem
00 p
600Y/277 VAC Se ro M
rie
s

K UL 1077
VDE 0641
CSA C22.2
IEC-898 Delivery Class
A - Standard item, stock to 2 weeks lead time
Rated Catalog List Delivery Wgt. oz. B - Stock to 4 weeks lead time
current number price class (1 Pc.) C - 6 to 8 week lead time
1 pole
0.1 – 0.15 S501-K0.15 $ 182
0.14 – 0.21 S501-K0.21 182
0.2 – 0.3 S501-K0.3 182
0.28 – 0.42 S501-K0.42 182
S501-D20 0.38 – 0.58 S501-K0.58 182
0.53 – 0.8 S501-K0.8 182
0.73 – 1.1 S501-K1.1 182
1 – 1.5 S501-K1.5 182
1.4 – 2.1 S501-K2.1 182
2 – 3 S501-K3 182
2.8 – 4.2 S501-K4.2 182 B 8.90
3.8 – 5.8 S501-K5.8 182
5.3 – 8 S501-K8 182
7.3 – 11 S501-K11 182
10 – 15 S501-K15 182
14 – 20 S501-K20 182
18 – 26 S501-K26 182
S502-D13 23 – 32 S501-K32 202
29 – 37 S501-K37 202
34 – 41 S501-K41 226
38 – 45 S501-K45 226
2 pole
0.1 – 0.15 S502-K0.15 356
0.14 – 0.21 S502-K0.21 356
0.2 – 0.3 S502-K0.3 356
0.28 – 0.42 S502-K0.42 356
0.38 – 0.58 S502-K0.58 356
0.53 – 0.8 S502-K0.8 356
0.73 – 1.1 S502-K1.1 356
1 – 1.5 S502-K1.5 356
S503-K6 1.4 – 2.1 S502-K2.1 356
2 – 3 S502-K3 356 B 17.85
2.8 – 4.2 S502-K4.2 356
3.8 – 5.8 S502-K5.8 356
5.3 – 8 S502-K8 356
7.3 – 11 S502-K11 356 14
10 – 15 S502-K15 356
14 – 20 S502-K20 356
18 – 26 S502-K26 356
23 – 32 S502-K32 392
K 29 – 37 S502-K37 392
10,000 34 – 41 S502-K41 442
5000 38 – 45 S502-K45 442
3 pole
1000
500 0.1 – 0.15 S503-K0.15 518
0.14 – 0.21 S503-K0.21 518
100 0.2 – 0.3 S503-K0.3 518
50
0.28 – 0.42 S503-K0.42 518
0.38 – 0.58 S503-K0.58 518
10
5
0.53 – 0.8 S503-K0.8 518
0.73 – 1.1 S503-K1.1 518
1 1 – 1.5 S503-K1.5 518
0.5 1.4 – 2.1 S503-K2.1 518
seconds

AC 2 – 3 S503-K3 518 B 25.36


0.1 2.8 – 4.2 S503-K4.2 518
0.05
DC
3.8 – 5.8 S503-K5.8 518
5.3 – 8 S503-K8 518
0.01 7.3 – 11 S503-K11 518
1 2 3 5 8 10 12 20 30 10 – 15 S503-K15 518
multiple of rated current 14 – 20 S503-K20 518
18 – 26 S503-K26 518
23 – 32 S503-K32 574
29 – 37 S503-K37 574
34 – 41 S503-K41 644
38 – 45 S503-K45 828

Low Voltage Products & Systems Discount schedule CB10 14.37


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M S500UC
pr ies
em er 600Y/277 VAC
y st 0 S
S 50
S
600 VDC

B UL 1077
VDE 0660
CSA C22.2

Rated Catalog List Delivery Weight Rated Catalog List Delivery Weight
current number price class (oz.) 1 pc current number price class (oz.) 1 pc
1 pole 3 pole
6 S501UC-B6 $ 226 6 S503UC-B6 $ 646
10 S501UC-B10 226 10 S503UC-B10 646
13 S501UC-B13 226 13 S503UC-B13 646
16 S501UC-B16 226 16 S503UC-B16 646
20 S501UC-B20 226 20 S503UC-B20 646
S501UC-B40
C 8.90 C 25.36
25 S501UC-B25 226 25 S503UC-B25 646
32 S501UC-B32 226 32 S503UC-B32 646
40 S501UC-B40 226 40 S503UC-B40 646
50 S501UC-B50 258 50 S503UC-B50 734
63 S501UC-B63 292 63 S503UC-B63 832
2 pole 4 pole
6 S502UC-B6 442 6 S504UC-B6 908
10 S502UC-B10 442 10 S504UC-B10 908
13 S502UC-B13 442 13 S504UC-B13 908
16 S502UC-B16 442 16 S504UC-B16 908
20 S502UC-B20 442 20 S504UC-B20 908 C 35.75
C 17.85
25 S502UC-B25 442 25 S504UC-B25 908
32 S502UC-B32 442 32 S504UC-B32 908
S502UC-B16
40 S502UC-B40 442 40 S504UC-B40 908
50 S502UC-B50 502 50 S504UC-B50 1030
63 S502UC-B63 568 63 S504UC-B63 1164

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

S503UC-B50

14

B
10,000
5000

1000
500

100
50

10
5

1
0.5
seconds

AC
0.1
0.05
DC

0.01
1 2 3 5 7 10 20 30
multiple of rated current

14.38 Discount schedule CB10 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
S500 UC s
S5 tem
600Y/277 VAC 00 p
Se ro M
rie
600 VDC s

K UL 1077
VDE 0660
CSA C22.2

Rated Catalog List Delivery Weight Rated Catalog List Delivery Weight
current number price class (oz.) 1 pc current number price class (oz.) 1 pc
1 pole 3 pole
0.1 – 0.15 S501UC-K0.15 $ 250 0.1 – 0.15 S503UC-K0.15 $ 712
0.14 – 0.21 S501UC-K0.21 250 0.14 – 0.21 S503UC-K0.21 712
0.2 – 0.3 S501UC-K0.3 250 0.2 – 0.3 S503UC-K0.3 712
0.28 – 0.42 S501UC-K0.42 250 0.28 – 0.42 S503UC-K0.42 712
0.38 – 0.58 S501UC-K0.58 250 0.38 – 0.58 S503UC-K0.58 712
S501UC-K0.15 0.53 – 0.8 S501UC-K0.8 250 0.53 – 0.8 S503UC-K0.8 712
0.73 – 1.1 S501UC-K1.1 250 0.73 – 1.1 S503UC-K1.1 712
1 – 1.5 S501UC-K1.5 250 1 – 1.5 S503UC-K1.5 712
1.4 – 2.1 S501UC-K2.1 250 1.4 – 2.1 S503UC-K2.1 712
2 – 3 S501UC-K3 250 2 – 3 S503UC-K3 712
2.8 – 4.2 S501UC-K4.2 250 C 8.90 2.8 – 4.2 S503UC-K4.2 712 C 25.36
3.8 – 5.8 S501UC-K5.8 250 3.8 – 5.8 S503UC-K5.8 712
5.3 – 8 S501UC-K8 250 5.3 – 8 S503UC-K8 712
7.3 – 11 S501UC-K11 250 7.3 – 11 S503UC-K11 712
10 – 15 S501UC-K15 250 10 – 15 S503UC-K15 712
14 – 20 S501UC-K20 250 14 – 20 S503UC-K20 712
18 – 26 S501UC-K26 250 18 – 26 S503UC-K26 712
23 – 32 S501UC-K32 286 23 – 32 S503UC-K32 814
S502UC-K0.15 29 – 37 S501UC-K37 286 29 – 37 S503UC-K37 814
34 – 41 S501UC-K41 320 34 – 41 S503UC-K41 910
38 – 45 S501UC-K45 320 38 – 45 S503UC-K45 910
2 pole 4 pole
0.1 – 0.15 S502UC-K0.15 488 0.1 – 0.15 S504UC-K0.15 996
0.14 – 0.21 S502UC-K0.21 488 0.14 – 0.21 S504UC-K0.21 996
0.2 – 0.3 S502UC-K0.3 488 0.2 – 0.3 S504UC-K0.3 996
0.28 – 0.42 S502UC-K0.42 488 0.28 – 0.42 S504UC-K0.42 996
0.38 – 0.58 S502UC-K0.58 488 0.38 – 0.58 S504UC-K0.58 996
0.53 – 0.8 S502UC-K0.8 488 0.53 – 0.8 S504UC-K0.8 996
0.73 – 1.1 S502UC-K1.1 488 0.73 – 1.1 S504UC-K1.1 996
1 – 1.5 S502UC-K1.5 488 1 – 1.5 S504UC-K1.5 996
1.4 – 2.1 S502UC-K2.1 488 1.4 – 2.1 S504UC-K2.1 996
C 17.85
S503UC-K0.15 2 – 3 S502UC-K3 488 2 – 3 S504UC-K3 996 C 35.75
2.8 – 4.2 S502UC-K4.2 488 2.8 – 4.2 S504UC-K4.2 996
3.8 – 5.8 S502UC-K5.8 488 3.8 – 5.8 S504UC-K5.8 996
5.3 – 8 S502UC-K8 488 5.3 – 8 S504UC-K8 996
7.3 – 11 S502UC-K11 488 7.3 – 11 S504UC-K11 996 14
10 – 15 S502UC-K15 488 10 – 15 S504UC-K15 996
14 – 20 S502UC-K20 488 14 – 20 S504UC-K20 996
18 – 26 S502UC-K26 488 18 – 26 S504UC-K26 996
23 – 32 S502UC-K32 558 23 – 32 S504UC-K32 1142
29 – 37 S502UC-K37 558 29 – 37 S504UC-K37 1142
34 – 41 S502UC-K41 622 34 – 41 S504UC-K41 1276
38 – 45 S502UC-K45 622 38 – 45 S504UC-K45 1276

S504UC-K0.15 Delivery Class


A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

UC-K
10,000
5000

1000
500

100
50

10
5

1
0.5
seconds

0.1
0.05
DC

0.01
1 2 3 5 10 20 30
multiple of rated current

Low Voltage Products & Systems Discount schedule CB10 14.39


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Accessories
pr ies
em er
y st 0 S
S 50
S

Electrical Catalog List Delivery Wgt. oz. Electrical Catalog List Delivery Wgt. oz.
accessories number price class (1pc.) accessories number suffix price class (1pc.)

Auxiliary contacts Undervoltage release


1 N.O./1 N.C. S500-H11 12 V UA12
2 N.O. S500-H20 $ 84 B 2.14 24 V UA24
2 N.C. S500-H02 48 V UA48 $ 266 B 5.71
For field mounting left side 110 V UA110
230 V UA230
500 V UA500
Bell alarm with auxiliary contacts Factory mount only.
S500-H11 1 N.O./1 N.C. S500-S11
Auxiliary contacts 2 N.O. S500-S20 92 B 2.14
2 N.C. S500-S02 Shunt trip
For field mounting left side 12 V AL12
24 V AL24
48 V AL48 224 B 5.71
Handle mechanism 110 V AL110
S500-RD3 100 B 6.5 230 V AL230
500 V AL500
For use with 1-4 pole S500 MCBs and disconnect switch selector
handles with 5mm shafts Factory mount only.

Front mounting kit


For 1 pole S500-ME1 60 2.1
S500-RD3
1 to 3 poles S500-ME2 70 A 2.9
1 to 7 poles S500-ME3 80 3.6

Power feed terminal – Accepts into 2/0 AWG


S500-K2 25 A 2
Suggested order quantity is 5.

Busbars – 3 phase L1, L2, L3


Amp Number Busbar End cap Delivery
S500-K2 Suggested
Catalog List Weight
rating of length catalog class order qty.
number price (ozs)
poles (mm) number quantity

3 x 8 650 — S500-BB38 $ 182


150 4 x 4 435 — S500-BB44 142 A 1 1
3 x 13 1055 — S500-BB313 274
14
S500-BB38
Busbar end caps
Electrical Catalog List Delivery Wgt. oz.
accessories number price class (1pc.)

S500-EK $ 25 A 10

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

14.40 Discount schedule CB8 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Sy
Technical data s
S5 tem
00 p
Se ro M
rie
s

Item S500-B, C, D S500-K


Approvals:
UL 1077 1077
CSA C22.2 - No.235 C22.2 - No. 235
VDE 0641/6.78­ 0641/6.78­
IEC 947-2 —

No. of poles: 1,2,3, +N, +NA 1,2,3, +N, +NA

Tripping characteristic: B.C.D. K

Rated currents: 6 to 63A 0.1 to 45A

Rated voltage:
UL/CSA single pole 277VAC 277VAC
UL/CSA multi pole 600YVAC 600YVAC
IEC single pole 690VAC 690VAC

Rated interrupting capacity:


Single pole 6-25A – 30KA/240VAC 0.15-25A – 30KA/240VAC
14KA/277VAC 14KA/277VAC
32-63A – 18KA/240VAC 26-45A – 18KA/240VAC
14KA/277VAC 14KA/277VAC
Multi-pole 6-63A – 14KA/480VAC 0.15-45A – 14KA/480VAC
6KA/600VAC 6KA/600VAC

Frequency: 50/60 Hz 50/60Hz

Mounting position: optional optional

Standard mounting: 35mm DIN rail 35mm DIN rail

Terminals: Conductors from 16-4AWG Conductors from 16-4AWG


(1-25sq mm) (1-25sq mm)

Service life at rated load: 20,000 operations 20,000 operations

Calibration temperature: 40°C 40°C

Item S500UC-B, K

Approvals:
UL 1077
CSA C22.2
VDE 0660

No. of poles:

1,2,3, 4
14
Tripping characteristic: B, K

Rated currents: B: 6 to 63A


K: 0.15 to 45A
Rated voltage:
UL single pole 277VAC/250VDC
UL multi pole 600VAC/600VDC

IEC multi pole 690VAC/750VDC

B single pole:
Rated interrupting capacity:
6 – 25A 18KA/240VAC 14KA/277VAC 30KA/250VDC
32 – 63A 30KA/240VAC 14KA/277VAC 30KA/250VDC

B two-pole:
6 – 63A 14KA/480VAC 6KA/600VAC 30KA/500VDC

B three-pole:

6 – 63A 14KA/480VAC 6KA/600VAC 30KA/600VDC

K single pole:
0.15 – 25A 30KA/240VAC 14KA/277VAC 30KA/250VDC
32 – 45A 18KA/240VAC 14KA/277VAC 30KA/250VDC

K two-pole:
0.15 – 45A 14KA/480VAC 6KA/600VAC 30KA/500VDC

K three-pole:
0.5 – 45A 14KA/480VAC 6KA/600VAC 30KA/600VDC

Frequency: 50/60Hz

Mounting position: optional

Standard mounting: 35mm DIN-rail

Terminals: Conductors from 16 to 4AWG


(1-25sq mm)

Service life at rated load: 20,000 operations

Low Voltage Products & Systems 14.41


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
o
M Approximate dimensions
pr ies
em er
y st 0 S
S 50
S 00.00
00.00
Inches
[Millimeters]

S500

2.95
75

1.97
50
0.98
25
3.64 92.5
1.73 44

3.15 3.62
80 1.77 45 92
CL
2.22
56.5 2.95 75

1.14
29

0.24 6

S500
S500-RD3 Handle mechanism

14

3.15 80 1.60 40.7

S500 handle mechanism

S500 Front mounting kit

CL

0.24 D
2.91 4.41
2.00 CUT-OUT 6D
51
74 112
CL
1.81
46
"L"

L + 0.51 13

L
L + 1.02 26
3.31 84 0.31 8

S500 FRONT MOUNT

14.42 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
cir G
Galaxie circuit breakers cu ala
it
br xie
GD, GH, GN & GV ea
ke
rs

Circuit breakers
Series GD, GH, GN & GV

Description Features
Galaxie circuit breakers are door mounted • Convenient actuators: Switch type,
for AC and DC applications. The breakers rocker switch & pushbutton
offer thermal-magnetic and magnetic-only • Various termination mountings
trip protection.
• Tropicalization protection
For the worldwide market, the Galaxie
breakers carry UL, CSA, IEC, CE and many • 480Y/277 VAC
other agency approvals and certifications. • UL 1077 Recognized – supplemental
protective device. UL File # E75741.
14

Low Voltage Products & Systems 14.43


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
ie ers Catalog number explanation
a lax eak
G br
uit
GD, GH, GN & GV Series circuit breakers
c irc Fitted, unpluggable or projecting type

Catalog number explanation

Circuit Breakers OPTIONS

SERIES RATING ENGRAVED


GD Standard Galaxie AC 240/415 V 50/60 Hz J On resetting button
can be used at 48 V DC max.
GH High rupturing capacity Galaxie METAL THREADED BUSHING
AC 240/415 V 50/60 Hz
W For fastening and operations 6-7-8.
GN Special Galaxie 100 V DC max. Tightening torque : 3 Nm max.
GV Special Galaxie 150 V DC max. (compulsory with option K)
GA Severe environment Galaxie
(i.e. military use) consult us CIRCUIT BREAKER SERIES GD MODEL D 2
R With adjustable thermal protection
VERSIONS (Not possible with option K)
U One-pole (1 protected pole)
B Two-pole (2 protected poles) MECHANICAL IMPACT
T Three-pole (3 protected poles) V 50 g
Q Four-pole (4 protected poles) E 100 G
1+N Two-pole (1 protected pole + neutral)
14 3+N Four-pole (3 protected poles + neutral) TROPICALIZATION
T (Compulsory with option E 100)
RATING (In : Amps)
0.1 - 0.2 - 0.3 - 0.5 - 1 - 1.5 - 2 - 2.5 - 3 - 4 - 5
6 - 8 - 10 - 12 - 13 - 16 - 20 - 25 - 30 - 32 THERMAL PROTECTION
Heavy duty types : ratings according to
NF EN60 898 Other ratings, consult us. C Temperature compensated from + 20°C to + 60°C
K Temperature compensated from - 40°C to + 85°C
series GD, GH and GA (Compulsory with Option W)
MODELS
L Thermal-magnetic - Curve B
according to NF EN60 898
AUXILIARY CONTACT FOR POSITION SIGNALLING O/F
U Thermal-magnetic - Curve C
according to NF EN60 898 P1 on 1 pole
D Thermal-magnetic - Curve D P2 on 2 poles
according to NF EN60 898 P3 on 3 poles
Ratings 6 to 32 A P4 on 4 poles
S Thermal-magnetic (series GN and GV only)
according to NF F 62001
1 See next page
T Thermal (except series GH)
2 Series GD, Model D only

FASTENINGS AND OPERATIONS 1


00 - 01 - 02 - 03 - 04 - 05 - 06 - 07 - 08 - 09

Terminations 1
00 - 01 - 02 - 03 - 07 - 08 - 09 - 33 - 43

EXAMPLE :
1 Circuit breaker Series : Galaxie standard AC - Version : 2 protected poles - Rating : 10 A - Model : magnetic-thermal, curve C - Fastenings and operations :
Threaded bushing flush type 2 buttons - Terminations : Screws and back connectors - With Options Auxiliary for position signalling O/F : on 2 poles - Tropicalization
has reference GDB10U0703 P2T
GD B 10 U 07 03 P2 - T - - - -

14.44 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
cir G
Technical data cu ala
it
br xie
ea
ke
r s

UL, CSA : For list of certified products : consult us Circuit breakers NF F62 001 : consult us

Characteristics SERIES GD SERIES GH SERIES GN SERIES GV


Rated voltage
1 + neutral version 240 V AC (50/60 Hz)
One pole version 240/415 V AC (50/60 Hz) 240/415 V AC (50/60 Hz)
Multipole version 415 V AC (50/60 Hz) 415 V AC (50/60 Hz)
One pole and two pole version 48 V DC max. 100 V DC max. 150 V DC max.
Interrupting capacity
According to standard IEC 898 3 000 A 4 500 A (models U and D: rating ≥ 5 A)
4 500 A (model L: rating ≥ 10 A)
According to standard NF F62 001 1 000 A (48 V DC max.) 500 A 1 000 A (48 V DC max.)
10 In cal. < 5 A ; 20 In cal > 5 A 10 In cal. < 5 A ; 20 In cal > 5 A 10 In cal. < 5 A ; 20 In cal > 5 A
Other characteristics
Life, number of cycles (On+Off) 4 000 4 000 4 000 4 000
Dielectric withstanding voltage 2 000 V rms 2 000 V rms 2 000 V rms 2 000 V rms

Tripping curves (1) (2) S Curve B : 3 In < S < 5 In - Curve C : 5 In < S < 10 In - Curve D : 10 In < S < 20 In Nominal current 0.1 to 2 A : 5 In < S < 10 In - 3 to 32 A : 7 In < S
< 14 In

Mechanical shock
30 g. 30 g. 30 g. 30 g.
Ambient temperature
-5° C to 40° C -5° C to 40° C -25° C to + 70° C -25° C to + 70° C

14

Low Voltage Products & Systems 14.45


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
ie ers Approximate dimensions
a lax eak
G br
uit
circ
 -ILLIMETERS

Fastenings and operations N 00 - 01 - 02 - 03 - 04 - 06 - 07 - 08


o

Fastenings / Operations 00 01 02 03 04 05 06 07 08 09
Size A 8 8 8 8 8 17,5 15 15 21 28
Size C 32 32 32 32 32 37 32 32 32 32

Terminations 00 01 02 03 33 43 07 08 09
Size B 15 4 4 12 4 4 4 4 11
Pole Pole Pole Pole Pole
N° 1 N° 2 N° 1 N° 2 N° 3

1 Width 2 Widths 3 Widths

Fastenings and operations No 05 - 09

Four-pole circuit breaker : NOTE :


Neutral on pole N° 1
Fastening and operation N 05 only
o
any
Fastenings and operations

Pole Pole Pole Pole Pole Pole Pole Pole Pole


N° 2 N° 1 N° 3 N° 2 N° 1 N° 4 N° 3 N° 2 N° 1

1 Width 2 Widths 3 Widths = 1 handle 4 Widths = 2 handles

Fastenings and operations (3 poles max. except 02 : 2 poles and 05 : 4 poles)


P R O J E C T I O N M O U N T I N G SCREW FLUSH MOUNTING Maximum thickness of mounting panel :
3 mm. 3 mm. 3 mm. 6 mm. 6 mm. 6 mm. 6 mm.

00 01 02 03 04 05 06 07 08 09
Tightening torque :
1,8 Nm max. 1,8 Nm max. 1,8 Nm max. 3 Nm max.

Terminations

14

00 01 02 03 33 43 07 08 09
16 A max. 240 A max. 16 A max. 16 A max. 16 A max.
Except Fastening 08 2 poles max. 2 poles max. 2 poles max.

14.46 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
S
Re yste
System pro M compact sid m
u p
Residual current devices de al c ro M
vic urr
F200, F670 series es en

Residual current devices


t

2 Pole 4 Pole

Description
RCDs provide ground fault equipment The F200 and F670 series are UL1053
protection by monitoring the leakage of recognized for use in 480Y/277VAC
current to ground. The F200 and F670 series applications.
will trip when ground faults are detected in The F202 and F672 is for use in single phase/
excess of the GF trip rating of the device. two wire or two wire systems. The F204
These devices provide GF protection only and and F674 is for use in three phase/four wire
are used in series with standard MCBs which systems.
provide overload and short circuit protection.
The F200 and F670 series can be used as The F200 and F670 series RCDs replace the
a main device providing GF protection for F360, F370 and F660 series with no change in 14
several MCB branch devices. fit, form or function.
The F200 and F670 have a profile similar to
the S2 MCBs and can be used with the MCB
busbars.
F200 – F670

Low Voltage Products & Systems 14.47


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
M t
o
pr rren F200 & F670
em cu
y st ual es
S sid vic
Re de

Residual current devices


Breaker GF trip Rated Catalog List Delivery Suggested Wgt. oz
level current number price class order qty (1 Pc.)

F202 Two pole 10mA 16 F202AC-16/0.01 $ 500


F672 480Y/277VAC 30mA 25 F202AC-25/0.03 300
40 F202AC-40/0.03 400
63 F202AC-63/0.03 550
80 F672-80/0.03 1600
100 F672-100/0.03 2200
100mA 25 F202AC-25/0.1 300
40 F202AC-40/0.1 400 B 1 13.8
63 F202AC-63/0.1 550
F202, F672 80 F672-80/0.1 1600
100 F672-100/0.1 2200
300mA 25 F202AC-25/0.3 300
40 F202AC-40/0.3 400
63 F202AC-63/0.3 550
80 F672-80/0.3 1300
100 F672-100/0.3 1800
F204 Four pole 30mA 25 F204AC-25/0.03 350
F674 480Y/277VAC 40 F204AC-40/0.03 450
63 F204AC-63/0.03 600
80 F674-80/0.03 1300
100 F674-100/0.03 1800
125 F674-125/0.03 1800
100mA 25 F204AC-25/0.1 350
F204, F674 40 F204AC-40/0.1 450
63 F204AC-63/0.1 600
80 F674-80/0.1 1300
100 F674-100/0.1 1800 B 1 19.0
125 F674-125/0.1 1800
300mA 25 F204AC-25/0.3 350
40 F204AC-40/0.3 450
63 F204AC-63/0.3 600
80 F674-80/0.3 1200
100 F674-100/0.3 1600
125 F674-125/0.3 1600
500mA 25 F204AC-25/0.5 450
40 F204AC-40/0.5 600
63 F204AC-63/0.5 650
14 Above devices are UL 1053 recognized and IEC 1008 approved.

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

14.48 Discount schedule CB14 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
S
Re yste
Accessories sid m
u p
F200 1 de al c ro M
vic urr
es en
t

Electrical For Catalog List Delivery Suggested Wgt. oz.


accessories use on: number price class order quantities (1 pc.)

Auxiliary contacts
For field mounting: right side F200 S2C-H6R $ 36 A 1 1.4
Form C 1 NO/ 1 NC

The auxiliary contacts will signal whether the breaker is in the ON or OFF position. The contacts are rated 2A/277 VAC and 1.5A/125 VDC.
Minimum operating voltage is 24 VAC/VDC.
Wire size: 18 AWG to 16 AWG.

S2C-H6R Bell alarm


For field mounting, right side F200 S2C-S/H6R 48 A 1 1.4

The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm
or bell to signal the operator that an overcurrent trip has occured. The bell alarm also includes a test button for testing the alarm contacts without
opening the breaker. The contact is rated 2A/277 VAC and 1.5A/125 VDC. Minimum operating voltage is 24 VAC/VDC.
* Combination bell alarm/auxiliary contact

Shunt trip
For field mounting, right side F200 S2C-A1
138 A 1 5.2
A1: 12-60 VAC (12-60VDC) S2C-A2
S2C-S/H6R
A2: 110-415 VAC (110-250 VDC)
For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is
applied. Shunt trips are available for on control system voltage (12-415 VAC/VDC).

Undervoltage release
For field mounting, right side
12 VDC S2C-UA12
24 VAC S2C-UA24
48 VAC F200 S2C-UA48 216 A 1 5.2
110 VAC S2C-UA110
220 VAC S2C-UA230
380 VAC S2C-UA400
S2C-A_ When control voltage drops below approximately 50% of rated voltage, the UVR opens the breaker. The breaker can not be operated unless
proper control voltage is first applied to the UVR coil. Similar in size and mounting to the shunt trip accessory.

Factory mounting
All accessories can be easily mounted in the field. For factory mounting of any accessory devices, add $30 list to total price
per breaker. To create complete catalog number, take suffix of accessory device following “S2C-” and add suffix to end of
14
breaker part number. Multiple suffixes must be added in alphabetical order.

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
S2C-UA_ C - 6 to 8 week lead time

1 Please consult factory for F670 accessories.

Low Voltage Products & Systems Discount schedule CB8 14.49


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
M t
o
pr rren Technical data
em cu F200, F670
y st ual es
S sid vic
Re de

F200AC F670
Electrical features
Standards UL 1053 & IEC 61008 UL1053 & IEC 61008
Poles 2P, 4P 2P, 4P
Rated current In 16,25,40,63 AMPS 2P- 80,100 4P- 80,100,125
Rated Voltage Ui 480Y/277 VAC 480Y/277 VAC
Max operating voltage of curcuit test 254 (440 for F200 left neutral) 254 (440 for left neutral)
Min operating voltage of circuit test 110 ( 195 for F200 left neutral) 110 ( 195 for left neutral)
Rated Frequency 50…60 Hz 50…60 Hz
Rated conditional 50…60 Hz 50…60 Hz
Short-circuit current 10 KA 10 KA
Rated residual breaking capacity 1 KA 2 KA
Rated impulse withstand voltage (1.2/50) Uimp 6 KV 6 KV
Power- frequency voltage dielectric strength 2.5 KV 2.5 KV
Surge current resistance acc. To VDE 0432 Part 2 250 AMPS 250 AMPS
(wave 8/20)

Mechanical features
Toggle Blue sealable in ON-OFF position Blue sealable in ON-OFF position
Contact position indicator yes yes
Electrical Life 10000 10000
Mechanical life 20000 20000
Ambient temperature -25°C… +55°C -25°C… +55°C
Storage temp. -40°C… +70°C -40°C… +70°C

Installation
failsafe bidirectional cylinder-lift terminal at top and
Terminal Type
bottom (shock protected)
Terminal size top/bottom per cable 6 AWG Max. 6 AWG Max.
Tightening torque 17.5 in-lb max. 17.5 in-lb max.
mounting 35mm din rail by means of fast clip 35mm din rail by means of fast clip
Connection From top & bottom From top & bottom
Withdraw from busbar Possible without the use of tools Possible without the use of tools

Approximate dimensions
2 Pole mm 85x69x35 MM 85x69x35 MM
4 Pole mm 85x69x70 MM 85x69x70 MM

Weight
2 Pole g 200g 200g
4 Pole g 350g 350g

Combination with auxiliary elements


14 Auxiliary contact yes yes
signal contact/ auxiliary switch yes yes
shunt trip yes yes
undervoltage release yes yes

14.50 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
S
Approximate dimensions Re yste
sid m
u p
Circuit diagrams de al c ro M
vic urr
00.00 Inches F200, F670 es en
t
00.00 [Millimeters]

Approximate dimensions


  
 



 
 

Circuit diagrams

POLE
& &
POLE
     .

42)0 42)0
4%34 5.)4 4%34 5.)4

#4 #4

     .

14
& &

1 To use on 3p/3w systems, add jumper between 4 and 8N for operation of test button.

Low Voltage Products & Systems 14.51


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
Modular DIN rail components
S
System pro M compact Mo yste
d m
Modular DIN rail components co ular pro
mp D
on IN r M
E220 - E270 Series en ail
ts

Description
• Safe connection by box terminals • DIN rail mounted with 45mm front opening
• Captive screws with Pozidrive slotted head, • For use in auxiliary and logic devices
Pozidrive system, Gr. 1 • Provide additional user functions for system
• Snap-on labels available control and operation
• Quick mounting with snap-on clip, easily • Include pushbuttons, indicating lights and
accessible and detachable at the bottom selector switches
• Protection against unintentional direct touch • ABB System Pro M compatibility
• System approach for control and circuit • Most devices are both UL 508 recognized 14
protection and are IEC compliant
• Compact size that dimensionally matches • Labeled with the CE Mark
the S2 MCB series
• Control and pilot functions can be along
side protective devices
E220 – E270

Low Voltage Products & Systems 14.53


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
M l
o i E221 & E222 Switches, 240VAC
pr ra
e m DIN ts
st r n 16 & 25A
Sy dula one
o p
M om
c

Type Rated Catalog List Delivery Suggested Weight (Oz.)


current number price schedule order qtys 1 piece

Switches
1 N.O. + 1 N.C. 16 E221-11 $ 90
2 N.O. + 2 N.C. 16 E221-22 177 B 10 2.46
3 N.O. + 1 N.C. 16 E221-31 177
1 N.O. 16 E221-10 59 1.94
2 N.O. 16 E221-20 110 10 2.12
B
3 N.O. 16 E221-30 120 2.29
4 N.O. 16 E221-40 159 2.47
E221-10 1 N.O. + 1 N.C. 25 E222-11 140 2.47
1 N.O. 25 E222-10 107 1.94
2 N.O. 25 E222-20 141 B 10 2.12
3 N.O. 25 E222-30 159 2.29
4 N.O. 25 E222-40 239 2.47

Form “C” switches


1 Change-over contact 16 E221-6 69 B 10 2.12
2 Change-over contacts 16 E221-6/2 125 2.47
1 Change-over contact 25 E222-6 128 B 10 2.12

Form “C” switches (I-O-II, Hand-OFF-Automatic)


1 Pole 16 E221-4 99 B 10 2.12
2 Pole 16 E221-4/2 147 2.47
1 Pole 25 E222-4 150 B 10 2.12
Note: Above devices are UL 508 recognized and IEC certified.
A300 pilot duty UL file # E171252

Delivery Class
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

14

14.54 Discount schedule CB20 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
S
Mo yste
E225 - E229, E10 Pilot devices d m
co ular pro
mp D
on IN r M
en ail
ts

Type Catalog List Delivery Pack Weight (Oz.)


number price schedule units pcs. 1 piece

Pushbutton, 1 N.O. + 1 N.C. contact


Grey E225-11B
Red E225-11C  
Green E225-11D $ 75 A 10 1.94
Yellow E225-11E
Black E225-11F
Blue E225-11G

Illuminated pushbutton, 1 N.O. contact with lamp, 120 VAC


E225-11F
Clear E227-10B/110
Red E227-10C/110
Green E227-10D/110 100 A 10 1.94
Yellow E227-10E/110
Blue E227-10G/110

Pilot light with lamp, 120 VAC


Clear E229-B/110
Red E229-C/110
Green E229-D/110 93 A 10 1.59
Yellow E229-E/110
Blue E229-G/110

E227-10E Lamps
24 VAC/DC E10/24
120 VAC/DC E10/110 24 A 1 0.14
220 VAC/DC E10/220
Note: Above devices are UL 508 recognized and IEC certified. UL file # E171252

Special features
• Safe connection via box terminals
• Captive screws with Phillips/Slotted head, Posidriv system, Gr. 1
• Snap-on labels available
• Protection against unintentional touch acc. to DIN VDE 0106 Part 100
• Lenses and pushbuttons in six colors
14
Elapsed time meter
E233-120/60
Type Catalog List Delivery Pack Weight (KG)
number price schedule units pcs. 1 piece
24 VAC, 60 Hz E233-24/60 B
120 VAC, 60 Hz E233-120/60 $ 130 A 1 0.045
240 VAC, 60 Hz E233-240/60 B

• Non-resettable
• 100,000 hours (99999.99)
UL file #171252

Sockets
Type Catalog List Delivery Pack Weight (KG)
number price schedule units pcs. 1 piece

E1175
Socket, 250 VAC, 50/60 Hz E1173 $ 57 B 1 0.2
Italian standard
Socket, 250 VAC, 50/60 Hz E1174 $ 57 B 1 0.2
French standard
Socket, 250 VAC, 50/60 Hz E1175 $ 57 B 1 0.2
Schuko standard
Socket w/cover, 250 VAC, 50/60 Hz E1175-C $ 57 B 1 0.2
Schuko standard

Delivery Class
E1175-C
A - Standard item, stock to 2 weeks lead time
B - Stock to 4 weeks lead time
C - 6 to 8 week lead time

Low Voltage Products & Systems Discount schedule CB20 14.55


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
M l
o i Digital meters
pr ra
e m DIN ts
st r n
Sy dula one
o p
M om
c

Measuring instruments
Type Catalog List Delivery Pack Weight (KG)
number price schedule units pcs. 1 piece

Digital timer, 230 VAC, 50/60 Hz DTS7/1 $ 422 B 1 0.3


Voltmeter 600 VAC, 50-400 Hz VLMD-1-2 510 B 1 0.3

Ammeter 15-20-25-40-60A, AMTD-1 510 B 1 0.3


250-400-600A, 50-400 Hz

Transformer, 230 VAC, 50/60 Hz TM15/12 135 B 1 0.3


4-8-12 VAC sec
DTS7/1

VLMD-1-2

14
TM15/12

14.56 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
S
Mo yste
Technical data d m
co ular pro
mp D
on IN r M
en ail
ts

Components for quick mounting onto DIN rails (35mm)


Mounting depth: 68mm
Mounting width: 1, 2, 3 and 4 pole switches = 17.5mm (= 1 module)

E220 Switches, 16 & 25A


Switching capacity: 1.25 In, 1.1Un, cos j = 0.6
Short-circuit withstanding capacity: 3 kA, 380V, cos j = 0.9
Toggle sealable: In ON and OFF positions
Connection cross-sections: Up to 1 x 6mm2 or 2 x 2.5mm2
Rated AC voltage: 240 VAC UL/CSA (E171252)
250/440 VAC IEC

E240/270 Disconnect switches, 45, 63, 80, & 100A


Switching capacity: 1.25 In, 1.1Un, cos j = 0.3
Short-circuit withstanding capacity: E240 = 10kA, E270 = 25kA RMS
Connection cross-sections: E240 up to 25mm2

E270 up to 50mm2
Rated AC voltage: 240/400/415 VAC

E Series components for quick mounting onto DIN rails (35mm)


Mounting depth 68mm
Mounting width: 17.5mm (=1 module)
Color: RAL 7035, grey
Connection cross sections: Up to 1 X 6mm2 or 2 X 2.5mm2
Rated current: 16A
Rated voltage: 250 VAC IEC
Rated voltage: 240 VAC UL/CSA (E171252)

Terminal markings

5 7
1 3 5 7 1 3 5 7 1 3 1 1 3 1 3 5 1 3 5 7
1 3

2 4 6 8 2 4 6 8 2 4 2 2 4 2 4 6 2 4 6 8
2 NO & 2 NC 3 NO & 1 NC 2 NO 1 NO 2 NO 3 NO 4 NO
2 4
6 8 Switches Disconnect switches
14
1 3 1 3 7 1 3 5 7 1 3 1 3 7 5 1 3 1 3 7 5
0 0
I II I II

2 2 8 2 6 8 2 2 8 2 2 8
1 NO 2 NO 3 NO 1 Pole 2 Pole 1 Pole 2 Pole

Illuminated pushbutton Form "C" switches Form "C" switches


(Hand - OFF- Auto)

MCB terminal markings


Terminal assignments for pushbuttons and indicator lights

5 7
1 3 1

1 7 5 1 1

MAX MAX
2W 2W
2 4 2
6 8 2 8 6 2 2
1 NO
1 NO & 1 NC 1 NO
Illuminated

Pushbutton Pilot light

MCB pushbtn term mkgs

Low Voltage Products & Systems 14.57


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
M l
o i Approximate dimensions
pr ra
e m DIN ts
st lar en
Sy 00.00
du pon Inches
Mo00.00om [Millimeters]
c
E220

1.77 3.35 3.35


45.0 85.0 85.0

1.99 50.5

2.52 64.0 0.69 0.69


17.5 17.5

Pilot light Pushbutton

E220, 16 & 25A

1.77 3.35
45.0 85.0

1.99 50.5

2.52 64.0 0.69


17.5

16 & 25A SWITCHES

E233 1.97
50.0

14
1
2
3
4
1.77 3.35
85.0 5
45.0
9
9

2.52
64.0
0.69
17.5

E240/270
E233

1.77 3.52
45.0 89.5

1.99 50.5 1.38 35.0


0.69 1.38 52.5
17.5
2.52 64.0
2.76 70.0

E270
14.58 Low Voltage Products & Systems
1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
S
Mo yste
Approximate dimensions d m
co ular pro
mp D
on IN r M
en ail
ts

E1173 - E1175 DTS

VLMD, AMTD TMS

14

Low Voltage Products & Systems 14.59


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
Tr
su ans
Transient voltage surge supressors

Transient voltage surge suppressors


rg ien
es t
TVSS, OVR range up vol
p t re age
ss
or
s

Description
• Compact
• DIN rail mounting
• Broad range
• 1, 2, 3, & 4 pole versions
• Replaceable plug cartridges
• Finger safe
• 15, 40, 65 & 100 kA versions
• Three position visual status indication
• Auxiliary contact for remote signalling
• UL 1449, File # E238957 & E22406
14
TVSS

Low Voltage Products & Systems 14.61


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
ag rs
l t
vo so General points on lightning and its risks
nt pres
i
ns up
e Causes of transient overvoltages
Tra ge s
r
su
The most serious consequences of lightning are the death of people and farm animals, and the destruction of equipment: telephone lines, transformers connected
to the electrical distribution network, electrical meters, household appliances, etc.
At the same time, the growing amount of equipment incorporating very sensitive electronic devices increases the number of incidences linked to lightning.

Within companies, if office automation equipment or machines (in factories) are put out of action, it nearly always leads to operating losses, the cost of
which is much more than that of the damaged equipment.

For example, if a bank’s computers are no longer operational, it suffers large operating losses. For the general public, the damage is mainly material: computer,
household appliances, home cinema, etc.

ROBUSTNESS OF EQUIPMENT

1950 1970 2000

Causes of transient overvoltages PROPAGATION OF DISTURBANCES

A transient overvoltage is a voltage peak with a


maximum duration of less than one millisecond. There 1950 1970 2000
are two possible causes of overvoltages on electrical
networks:
14 • natural causes (lightning),
• other causes due to equipment or switching devices.

Natural overvoltages on low voltage networks are


caused by direct lightning strikes. The high level
of energy contained in a direct lightning strike on a
lightning conductor or an overhead low voltage line
leads to considerable damage of the installation. The
overvoltage can be over 20 times the nominal voltage.

Operating or switching overvoltages linked to a


network’s equipment create overvoltages of a lower
level (3 to 5 times the nominal voltage) but occur much
more frequently, thus causing premature ageing of the
equipment.

Three categories of overvoltage propagate


on low voltage networks:
• direct lightning strikes,
• indirect effects of lightning strikes,
• operating or switching overvoltages.

Propagation of overvoltages by electrical networks


(power and low current)

14.62 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
General points on lightning and its risks rg ien
es t
Causes of transient overvoltages up vol
pr tag
es
so e
rs

Overvoltages due to direct lightning strikes


These can take two forms:
• When lightning strikes a lightning conductor or the roof of a building which is earthed, the lightning current is dissipated into the ground. The impedance of the
ground and the current flowing through it create large difference of potential: this is the overvoltage. This overvoltage then propagates throughout the building via
the cables, damaging equipment along the way.

• When lightning strikes an overhead low voltage line, the latter conducts high currents which penetrate into the building creating large overvoltages. The damage
caused by this type of overvoltage is usually spectacular (e.g. fire in the electrical switchboard causing the destruction of buildings and industrial equipment) and
results in explosions.

Direct lightning strike on a lightning conductor or the roof of a Direct lightning strike on an overhead line
building

Overvoltages due to the indirect effects of lightning strikes


The overvoltages previously mentioned are also found when lightning strikes in the vicinity of a building, due to the increase in potential of the ground at the point of
impact. The electromagnetic fields created by the lightning current generate inductive and capacitive coupling, leading to other overvoltages.

Within a radius up to several kilometres, the electromagnetic field caused by lightning in clouds can also create sudden increases in voltage.
Although less spectacular than in the previous case, irreparable damage is also caused to so called sensitive equipment such as fax machines, computer power
supplies and safety and communication systems.

14

Increase in ground potential Magnetic field

Electrostatic field

Low Voltage Products & Systems 14.63


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
ag rs
l t
vo so Different types of surges
i e nt pres
ns up
Tra ge s
r
su
Equipment containing electronic switching components is also likely to generate electrical disturbances comparable to overvoltages.
The consequences of which on sensitive equipment, albeit not visible, are no less detrimental: premature ageing and unpredictable or fleeting breakdowns.

Operating overvoltages are produced when reactive or capacitive equipment is switched on and off.
Furthermore, interrupting factory production, lighting or transformers can generate overvoltages which will themselves cause greater damage to nearby electrical
equipment.

Direct lightning strikes

Indirect lightning strikes

Operating
overvoltages

14
Harmonics Micro breaks

Temporary phenomenon Duration > 200ms Transient phenomenon Duration < 1ms

➪ ➪
Too long for TVSS TVSS needed

Representation of the various disturbances on electrical networks

Different type of power supply disturbances Main effects


• Atmospheric discharges • Destruction of the equipment
• Industrial interferences • Premature aging
• Switching operations on the power distribution system • Incorrect operations

14.64 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
OVR Range rg ien
es t
Main features up vol
pr tag
es
so e
rs

TVSSs protect installations by limiting


transient overvoltages and run-off
lightning currents for electric and
electronic equipment.
They are divided into three families:

• Type 2 TVSSs provide protection for


equipment against transient overvolt-
age and they are installed in the Main
Switch Board (MSB), or in the Sub-
Distribution Board (SDB).

In addition to the standard TVSSs,


two options are available: the
Safety reserve system and the remote
indication (TS), in order to ensure
a preventive maintenance of the
installation.

ABB TVSS (OVR range) offer the


same “plus” advantages of the other
ABB safety reserve system Contact for alarm connection
System pro M compact devices,
in order to get a perfect compat-
ibility with all the modular range of
products.

All these TVSS products comply


with the international standard IEC
61643-1 and the European standard
EN 61643-11.

They also comply with UL 1449 and


CSA C22.2.

14

Pluggable unit / replacement modules

DIN rail unit, easy installation and wiring

Low Voltage Products & Systems 14.65


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
ag rs
l t
vo so Technical data
nt pres
i
ns up
e OVR range
Tra ge s
r
su

Technical Features Type 2


Standards IEC 61643-1 / EN 61643-11 / UL1499 / CSA
Type / test class T2 / II
Poles 1P / 1P+N / 3P / 3P+N / 4P
Types of networks TNS - TT - TNC - IT / Wye / Delta
Type of current A.C.
Nominal voltage Un V All US network voltages
Max. cont. operating voltage Uc (L-N / L-PE / N-PE) V 150 / 275 / 320 / 440 / 550 / 660
Voltage protection level Up at In (L-N / L-PE / N-PE) kV 0.6 / 1.2 / 1.4 / 1.8 / 2.5 / 2.9
Electrical features Nominal discharge current In (8/20) kA 5 / 15 / 20 / 30
Maximal discharge current Imax (8/20) kA 15 / 40 / 65 / 100
Impulse current Iimp (10/350) kA /
Follow current Ifi kA None
Operating current Ic mA <1
Short circuit withstand Icc kA 50
Disconnector
gG - gL fuse A 16 - 25
curve C circuit breaker A 10 - 40
curve K circuit breaker
Stocking temperature °C -40 to +80
Operating temperature °C -40 to +80
Degree of protection IP 20
Fire resistance according to UL 94 V2
Material of Housing PC grey RAL 7035
Mechanical features Maximal altitude m 2000
Integrated thermal disconnector Yes
14 State indicator Yes
Compatibility with OVR Sign Yes
Safety reserve Option
TS remote indicator Option
Wire range L/N
solid wire mm2 2.5 ... 25
stranded wire mm2 2.5 ... 16
Stripping length L/N mm 12.5
Tightening torque L/N Nm 2
Installation
Wire range PE
solid wire mm2 2.5 ... 25
stranded wire mm2 2.5 ... 16
Stripping length PE mm 12.5
Tightening torque PE Nm 2
Pole dimensions (H x D x W) mm 85 x 58 x 17.5
Dimensions and weight Pole weight g 120
Technical Features of the integrated auxiliary contact
Electrical features Contact complement 1NO (1 make contact),
1NC (1 normally closed contact)
Min. load 12V D.C. - 10 mA
Max. load 250V A.C. - 1A
Installation Connection cross-section mm2 1.5

14.66 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
OVR Range rg ien
es t
Single pole up vol
pr tag
es
so e
rs

Transient voltage surge suppressor


Function: TVSS provides protection for equipment against transient overvoltage (indirect lightning strike) that occur on the electri-
cal network (mains); the maximum discharge current (Imax) ranges from 15 to 100 kA per pole, based on MOV technology.

Application: residential, commercial, industrial
Standard: CEI 61643-1 / EN 61643-11 / UL 1449 / CSA
8/20 current wave

Type 2 - Surge Protection Devices – Single pole


Max Discharge Voltage Protection Catalog
Nominal Voltage (V) MOV Voltage (V)
Current (KA) Level Up (KV) number
OVR 15 150
120 150 .06
OVR 15 150 s P
OVR 15 275
230 275 1.2 OVR 15 275 P TS
15 277 320 1.4 OVR 15 320
OVR 15 440
400 440 1.8
OVR 15 440 P
480 550 2.5 OVR 15 550
600 660 2.9 OVR 15 660
OVR 40 150 s P
120 150 0.6 OVR 40 150 s P TS
OVR 40 275 P
230 275 1.2 OVR 40 275 s P
OVR 40 275 s P TS
OVR 40 320 P
277 320 1.4 OVR 40 320 s P
40
OVR 40 320 s P TS
OVR 40 440
400 440 1.8 OVR 40 440 s P
OVR 40 440 s P TS
OVR 40 550
480 550 2.5
OVR 40 550 s
600 660 2.9 OVR 40 660 s
120 150 0.6 OVR 65 150 s P
OVR 65 275 s P
230 275 1.2 OVR 65 275 s P TS

65
277 320 1.4
OVR 65 320 s P
OVR 65 320 s P TS
14
OVR 65 440 s P
400 440 1.8
OVR 65 440 s P TS
480 550 2.5 OVR 65 550 s
600 660 2.9 OVR 65 660 s
OVR 100 275 s P
230 275 1.2 OVR 100 275 s P TS
OVR 100 320 s P
277 320 1.4
100 OVR 100 320 s P TS
OVR 100 440 s
400 440 1.8 OVR 100 440 s P
OVR 100 440 s P TS

OVR 1N  65 275 s P TS 1


Network TS Integrated remote indication
1N Single phase (left), neutral (right)
3N Three phase (left), neutral (right) P Pluggable unit
N1 Neutral (left), single phase (right) Nothing: Single block
N3 Neutral (left), three phases (right)
3L Three poles s with safety reserve
4L Four poles
Nothing Single pole Max. continuous operating
voltage
Max. discharge current 8/20 Uc (V) 660
Imax (kA) 15 550
40 440
65 385
100 320
275
1 This part number breakdown only explains our part numbering system; it is not to be used to build a 150
part number for ordering purposes. 75
Low Voltage Products & Systems 14.67
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
ag rs
l t
vo so OVR TVSS
nt pres
i
ns up
e Multi-pole
Tra ge s
r
su
Transient voltage surge suppressor
Function: TVSS provides protection for equipment against transient overvoltage (indirect lightning strike) that occur on the electri-
cal network (mains); the maximum discharge current (Imax) ranges from 15 to 100 kA per pole, based on MOV technology.

Application: residential, commercial, industrial
Standard: CEI 61643-1 / EN 61643-11 / UL 1449 / CSA
8/20 current wave

Max Discharge Voltage Protection Catalog


Nominal Voltage (V) MOV Voltage (V)
Current (KA) Level Up (KV) number
OVR 1N 15 150
120 150 0.6 OVR 1N 15 150 s P TS
OVR 3N 15 150
15
230 275 1.2 OVR 3L 15 275 P
OVR 3N 15 275
277 320 1.4 OVR 3N 15 320
OVR 1N 40 150 s P
120 150 0.6 OVR 1N 40 150 s P TS
OVR 3N 40 150 s P TS
OVR 3N 40 275 s P
230 275 1.2 OVR 3L 40 275 s P
40
OVR 3N 40 320 P
277 320 1.4 OVR 3N 40 320 s P
OVR 3N 40 320 s P TS
400 440 1.8 OVR 3N 40 440 s P
OVR 1N 65 150 s P
120 150 0.6 OVR 3N 65 150 s P
OVR 3N 65 150 s P TS
OVR 3L 65 275 s P
230 275 1.2 OVR 3N 65 275 s P
65
OVR 3N 65 320 s P
277 320 1.4 OVR 3N 65 320 s P TS
OVR 3N 65 440 s P
400 440 1.8 OVR 4L 65 440 s
OVR 3N 100 320 s P
100 277 320 1.4
OVR 3N 100 320 s P TS

14

OVR 1N  65 275 s P TS 1


Network TS Integrated remote indication
1N Single phase (left), neutral (right)
3N Three phase (left), neutral (right) P Pluggable unit
N1 Neutral (left), single phase (right) Nothing: Single block
N3 Neutral (left), three phases (right)
3L Three poles s with safety reserve
4L Four poles
Nothing Single pole Max. continuous operating
voltage
Max. discharge current 8/20 Uc (V) 660
Imax (kA) 15 550
40 440
65 385
100 320
275
150
75

1 This part number breakdown only explains our part numbering system; it is not to be used to build a part number for ordering purposes.

14.68 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
OVR Range rg ien
es t
Very low voltage transmission lines protection up vol
pr tag
es
so e
rs

Transmission line surge arresters (OVR TC) provide protection against transient overvoltages for equipment connected to
telephone lines (digital or analog) & current loops.

Standards Info:
Modular low current surge arresters comply with IEC 61643-21 / UL 1449.

Schematic diagrams

L1 L1 l1

L2
L2 l2

OVR TC 200 V in parallel OVR TC / xx V / 200 FR in series


OVR TC 06 V

Dimensions
Dimensions (mm) W H D
OVR TC (all models) 17.5 85 63

Connection
L1
L1 L2
L2

OVR TC 200 FR
OVR TC 48 V
OVR TC 200 FR OVR TC 200 V OVR TC 24 V
OVR TC 12 V
OVR TC 06 V

14
l1 l2
OVR TC 200 V in parallel OVR TC / xx V / 200 FR in series

Fixing

Simply clips onto DIN rail.

Pratical info:
Telecom and dataline protection surge arresters are installed in electrical
switchboards or enclosures using DIN rail.

Low Voltage Products & Systems 14.69


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
t ag rs
l
vo so Technical data
i e nt pres
ns up
Tra ge s
r
su
6V 12 V 24 V 48 V 200 V 200 V
Electrical characteristics
OVR TC 06 V OVR TC 12 V OVR TC 24 V OVR TC 48 V OVR TC 200 V OVR TC 200 FR
Types of network Communication Communication Communication Communication Communication Communication
Number of pairs 1 1 1 1 1 1
Type of protection Series Series Series Series Parallel Series
Type of current Low currents Low currents Low currents Low currents Low currents Low currents
Nominal voltage: Un 6V 12 V 24 V 48 V 200 V 200 V
Max cont operating voltage: Uc 7V 14 V 27 V 53 V 220 V 220 V
Voltage protection level: Up at In 15 V 20 V 35 V 70 V 700 V 300 V
Nominal discharge current: In (8/20) 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA
Maximum discharge current: Imax (8/20) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
Bandwidth 10 MHz 2 MHz 4 MHz 6 MHz 100 MHz 3 MHz
Operating current: Ic 20 mA 20 mA 20 mA 20 mA - 20 mA
Degree of protection IP 203 IP 203 IP 203 IP 203 IP 203 IP 203
50 Hz withstand (15 mn) 10 A 10 A 10 A 10 A - 10 A
Mechanical characteristics
L/N connection terminals:
– solid wire 0.5 ... 2.5 mm2
– stranded wire 0.5 ... 2.5 mm2
PE connection terminal:
– solid wire 0.5 ... 2.5 mm2
– stranded wire 0.5 ... 2.5 mm2
Integrated thermal disconnector Yes No Yes
End of life indicator Yes No Yes
Compatibility with OVR Sign Yes No Yes
Miscellaneous characteristics
Storage temperature -40 °C to +80 °C
Operating temperature -40 °C to +80 °C
Maximum altitude 2000 m
Case material PC grey RAL 7032
Insulating material UL94 V0 classification
Reference standard IEC 61643-21 / UL 1449
Weight 150 g

14

14.70 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
Installation rules rg ien
es t
Principles of coordination for TVSS up vol
pr tag
es
so e
rs

The first surge arrester does not provide effective protection for the whole installation by itself.
Certain electrical phenomena can double the protection’s residual voltage if cable lengths exceed 10m.
Surge arresters must be coordinated when they are installed refer to the tables below.

Coordination required if:


The first surge arrester does not reach the protection voltage (Up ) by itself.
The first surge arrester is more than 10m away from the equipment to be protected.

The first surge arrester diverts most of the current to the ground and the remaining surge current is diverted to
the ground by the second surge arrester.

The value of this remaining surge current gets lower as the distance between both surge arresters gets longer.
The lower is the current going through the last surge arrester, the lower is the voltage protection level applied
to the downstream equipment.

Coordination between Type 2 TVSS units

TVSS L>1m
TVSS
65 kA ➤ 15 kA

(1 m minimum between the two devices)
8/20 8/20

14

Low Voltage Products & Systems 14.71


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
t ag rs
l
vo so Approximate dimensions
nt pres
i
ns up
e OVR range
Tra ge s
r
su

Transient voltage surge suppressor

TVSS without TS TVSS with TS


63 63

87.3
87.3

95.6

97
45
45

40 40

1 pole 3 poles
17,6 52,8

OVR 15 275 P OVR 3L 15 275 P


OVR 15 440 P OVR 3L 40 275 P
OVR 40 275 P OVR 3L 40 275 s P TS
OVR 40 275 s P TS OVR 3L 65 275 s P TS
OVR 40 440 P
14

OVR 40 440 s P TS
OVR 65 275 s P TS
OVR 65 440 s P TS

4 poles 3 poles + Neutral


 70,4

OVR 4L 15 275 P OVR 3N 15 275 P


OVR 4L 40 275 P OVR 3N 40 275 P
OVR 4L 40 275 s P TS OVR 3N 40 275 s P TS
OVR 4L 65 275 s P TS OVR 3N 65 275 s P TS

14.72 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
Technical details rg ien
es t
up vol
Installation rules for TVSS choice of associated pr tag
es
breaking devices (fuse/circuit breaker) so e
rs

Choice of disconnector
Surge arresters must be associated with upstream short-circuit protection and residual current protection against indirect contact (usually already present in the installation)
Function Application

The breaking device associated with the surge arrester can


Protection against be either a circuit breaker or a fuse.
fault currents Its rating should take into consideration the surge arrester’s
characteristics and the short-circuit current of the installation.

Thermal protection Thermal protection is integrated into the surge arrester.

Maximum circuit-breaker or fuse protection rating depending


on Imax and Iimp of the surge arrester.

TVSS surge arresters Circuit-breaker (curve K) Fuse (gG)


100 kA (8/20)
• Icc = 300 A to 1 kA 40 A 25 A
• Icc = 1 kA to 7 kA 40 A 25 A 14
• Icc = 7 kA and above 40 A 25 A
TVSS surge arresters Circuit-breaker (curve C) Fuse (gG)
65 kA (8/20)
• Icc = 300 A to 1 kA 30 A 20 A
• Icc = 1 kA to 7 kA 32 A to 40 A 40 A
• Icc = 7 kA and above 32 A to 63 A 63 A
40 kA (8/20)
• Icc = 300 A to 1 kA 25 A 16 A
• Icc = 1 kA to 7 kA 25 A 25 A
• Icc = 7 kA and above 25 A to 50 A 50 A
15 kA (8/20)
• Icc = 300 A to 1 kA 10 A to 25 A 16 A
• Icc = 1 kA to 7 kA 10 A to 32 A 16 A
• Icc = 7 kA and above 10 A to 40 A 25 A to 40 A

Low Voltage Products & Systems 14.73


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
t ag rs
l
vo so Technical details
e nt pres
i
ns up Cabling and installation of Surge Protection Devices
Tra ge s in an electrical panel
r
su
50 cm rule
Remember that a 10 kA lightning current passing through a 1 m length of cable generates 1000 Volts. Equipment
protected by a surge arrester is subjected to a voltage equal to the sum of the Up voltage of the surge arrester,



Ud of its disconnector and the sum of the inductive voltages of connecting cables (U1+U2+U3).
It is therefore essential that the total length (L = L1+L2+L3) of the connecting cables is as short as possible U1 L1
(0.50 m).


If this length (L = L1 + L2+L3) exceeds 0.50m, it is necessary to carry out one of the following: UD
• Reduce this length by moving the connection terminals.


• Choose a surge arrester with a lower Up value. U2 L2 L
• Install a second, coordinated surge arrester near the device to be protected so as to adapt the combined


Up value to the impulse withstand of the equipment to be protected.

Wiring ring surfaces UP


The wires must be arranged in such a way that they are as close to each other as possible (see adjacent diagram)
to avoid overvoltages induced by a ring surface between phases, the neutral and the PE conductor.


U3 L3


Routing of clean cables and polluted cables
During installation, lay clean cables (protected) and polluted cables as shown in the adjacent diagrams.
To avoid magnetic coupling between the different cable types (clean and polluted), it is strongly advised that
they are kept apart (> 30 cm) and if a crossing cannot be avoided, it should be at right angles (90°).

Crossing
Polluted cables ➤ D > 30 cm ➤ Clean cables at 90°
Polluted
cable

Clean Main
cable circuit-
breaker

Ring
surface
Surge
arrester
Terminal / MCB circuit-
14 breaker

Clean Polluted
Feeder 1 cable cable

D > 30 cm
➤ ➤

MCB / TVSS
D < 30 cm
➤ ➤

Feeder 2

TVSS / Earth terminal Note:


The cross-section of the connecting cables is calculated according to
Equipotential grounding: the local short-circuit current level (where the surge arrester is installed).
It must be equal to the cross-section of the installation’s upstream
It is critical to check the earth equipotentiality of the various items of equipment.
cables.
The minimum cross-section for the earth conductor is 4 mm2 if there is
not a lightning conductor and 10 mm2 if there is a lightning conductor.

14.74 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
Application sheets rg ien
es t
up vol
OVR Surge Protection Devices pr tag
es
so e
rs

Operating principle Example of installation

The Surge Protection Devices (TVSS), suitable for


As shown in the diagrams, one of the possible
residential, commercial and industrial applications,
applications is to protect the equipment (TV,
are designed to limit transient overvoltage and
computer, ...) against overvoltage thanks to a
run-off lightning currents.
Surge Protection Device (TVSS) which ensures
the protection in common mode (Ph-PE / N-PE) and
differential mode (Ph-N).
Application environments

The Surge Protection Devices (TVSS) are


necessary in any environment where the lightning
risk exists (direct lightning strike / overvoltage).

, , , .

%QUIPMENT
PROTECTED

14

Type 2 TVSS

Low Voltage Products & Systems 14.75


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
t ag rs
l
vo so General points on lightning and its risks
e nt pres
i
ns up Diagram of an installation protected against lightning and its
Tra ge s indirect effects
r
su

The 100KA or 65KA surge arrester (depending on the lightning risk) fitted in the installation’s main incoming electrical switchboard, is capable of deviating the energy
of a direct lightning strike. This is the first stage of the electrical network’s protection.
The behavior of the cables, subjected to a transient signal, limits the effectiveness of a surge arrester to 10 m of cable. It is therefore necessary to use one or more
surge arresters in the installation in order to obtain the required level of protection for the equipment.
Here, a 40KA or 15KA surge arrester (depending on the lightning risk) should be used in coordination with the incoming surge arrester. This is the second stage of
the protection.
Finally, if there is a risk of overvoltage on the electrical network, this risk also exists for the auxiliary wiring network. The appropriate protection is a surge arrester
designed to protect telephone or data transmission lines (OVR TC). This is fitted in series on the network.

Protects the building

Protects the telephone


network

Telephone Line
Surge Arrester
OVR TC 200 FR

14

Sub-distribution
switchboard

Incoming power PABX Incoming


cable telephone line

Main
electrical
switchboard

Protects the machines Protects computer feeders

OVR 3N 65 275s PTS OVR 3N 15 275 s P TS

14.76 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Tr
su ans
Selection rg ien
es t
up vol
Example of a protected industrial installation pr tag
es
so e
rs

GE Transformer Transformer
(Generator set) T1 T2

OVR 3N 65 440s PTS OVR 3N 65 440s PTS OVR 3N 65 440s PTS

(1) (1) (1)

MSB 10 MSB 11 MSB 12

Type 2 Surge Arrester Type 2 Surge Arrester Surge Arrester Type 2


OVR 3N 40 440 s P TS OVR 3N 40 440 s P TS OVR 3N 40 440 s P TS

SDB 20 (Sub-distribution board) SDB 21 (Sub-distribution board) SDB 22 (Sub-distribution board)

Type 2 Surge Arrester Type 2 Surge Arrester Surge Arrester Type 2 14


OVR 3N 15 440 s P TS OVR 3N 15 440 s P TS OVR 3N 15 440 s P TS

(1) (1) (1)


SDB 23 (Sub-distribution board) SDB 24 (Sub-distribution board) SDB 25 (Sub-distribution board)

The above diagram is an example of an industrial application located in an area where the lightning strike density (Ng) is 1.2 lightning strikes per km2 and per year:
• the building is protected by a lightning conductor.
• the lightning conductor's earthing strip is connected to the installation's earth network.
• the earthing system is IT (with distributed neutral) and then TNS for the sub-distribution boards.
• main switch boards (MSB) 10, 11 and 12 are fitted with Type 2 surge arresters OVR 3N 65 440 s PTS.
• sub-distribution boards (SDB) 20, 21 and 22 are fitted with Type 2 surge arresters OVR 3N 40 440 s P TS.
• sub-distribution boards (SDB) 23, 24 and 25 are fitted with Type 2 surge arresters OVR 3N 15 440 s P TS.

Low Voltage Products & Systems 14.77


ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU000023C0201
e
t ag rs
l
vo so Terminology of electrical characteristics
i e nt pres
ns up
Tra ge s
r
su

Surge arrester:
Device designed to limit transient overvoltages and run-off lightning
currents. It consists of at least one non-linear component. It must comply
with European standard EN 61643-11.

1.2/50 wave:
Standardized overvoltage waveform created on networks and which
adds to the network’s voltage.

8/20 wave:
Current waveform which passes through equipment when subjected
to an overvoltage.

Type 2 surge arrester:


Surge arrester designed to run-off energy caused by an overvoltage
comparable to that of an indirect lightning strike or an operating
overvoltage. It has successfully passed testing to the standard with the
8/20 wave (class II test).

Up: 8/20
Voltage protection level / Let through voltage
Parameter characterising surge arrester operation by the level of voltage
limitation between its terminals and which is selected from the list of
preferred values in the standard. This value is greater than the highest
value obtained during voltage limitation measurements (at In).

In:
Nominal discharge current.
Peak current value of an 8/20 waveform (15 times) flowing in the surge
arrester. It is used to determine the Up value of the surge arrester. µs
Type 2 Surge Arresters
Imax: Imax: current wave
Maximum discharge current for class II testing.
Peak current value of an 8/20 waveform flowing in the surge arrester
with an amplitude complying with the class II operating test sequence.
14 Imax is greater than In.
Un:
Nominal AC voltage of the network : nominal voltage between phase
and neutral (AC rms value).

14.78 Low Voltage Products & Systems


1SXU000023C0201 ABB Inc. • 888-385-1221 • www.abb-control.com