Please fill the information correctly to analyse the system and find out the problem Product code : __________ 1) Please write the supply voltage and phase: R _______ V. S_________ V. T _________ V.
KRK
REACTIVE POWER CONTROLLER STANDARD TYPE
2) Please write the current transformer ratio: k : _______ 3) Current value from 3 phase : R _______ A. S ________ A. T ________ A.
Note : For this test, device should be in manual mode and all capacitors should be out 4) Please write the current transformer phase : R S T
5) In automatic mode, when you push the - button the current value that you see: _____ A. 6) Cos value that you adjust on device:__________ 7) The capacitor values that you connect to device : 1.step : ________ 2.step :________ 3.step : ________ 4.step : ________ 5.step : ________ 6.step : ________ 7.step : ________ 8.step : ________ 9.step : ________ 10.step : ________ 11.step : ________ 12.step : ________ 8) In manual mode, The Cos value that are seen after pressing + and - buttons step by step : (1). switched :_______________________ (1+2 ). switched : _______________________ (1+2+3). switched : _______________________ (1+2+3+4). switched : _______________________ (1+2+3+4+5). switched : _______________________ (1+2+3+4+5+6). switched : _______________________ (1+2+3+4+5+6+7). switched : _______________________ (1+2+3+4+5+6+7+8). switched : _______________________ (1+2+3+4+5+6+7+8+9). switched : _______________________ (1+2+3+4+5+6+7+8+9+10). switched : _______________________ (1+2+3+4+5+6+7+8+9+10+11). switched : _______________________ (1+2+3+4+5+6+7+8+9+10+11+12). switched : _______________________ 9) In automatic mode when the capacitors were connected (when the compensation was succesful ) the Cos value that are seen Capacitors value : ________________ Cos : _______________
YEARS GUARANTEE
10) In automatic mode , before the capacitors were connected, when you push - button the current value that you see : __________ A. For tecnical support: Fax No: +90 216 612 36 40 Web: www.krk.com.tr E-MAIL: info@krk.com.tr
User Guide
KRK
KRK
2L#=Xr
_,?#0n:M q
2p=Q
#>X
xEcu
REASON OF MISTAKE
A)After the cos and c/k adjustment user
should wait 5 sec. to save the values.
A)The capacitors may be connected the input of M, QV)coT!`-m?K~ current transformer. lxW#udPi{N_ B)The capacitors are insufficient that are
connected to RPC
Kg9y&frW#R$6I zF~ A) C/k value is entered is too low B) The first capacitor value is too low Kg9~K/I[(f9K]0 A) C/k value is entered is too high B) The current is too low C) The current transformer ratio is too high A) Supply phase is different from the current transformers phase
s?OjS Z&`~K*h4
Compensation Components are selected according the Harmonic distorsion . System with(Gh/Sn)<%15 has the standard compensation equipments; CALCULATION OF THE REACTIVE POWER THAT WILL NEEDED Needed reactive power is calculated according to bellow criteries * Reactive power value on the electricymeter * Current tg and targated tg values
Sn:Power of Transformer Gh:Power of load with Harmonic Content SOME LOADS THAT CREATE REACTIVE POWER * Speed control equipments * AC-DC converters * Electronic motor starters *Welding machine * Ovens .* UPS.
MR^0 |U"Zmyd0t The current transformer is on the phase A) P(5 that has the low current, so that the difference between phases is too high. G*n;z'g4F~K[-=w$c0B|N_1 l|Xj=}I |Za A) The current transformer is on the phase that has the high current so that the difference between phases is too high.
}JVi;yn;{GT ^1o A) The CT ratio is too low so that there is high current (> 5A) on the output of CT ,xR_1 yd _,l8r~K\hQ]*i6nA#5uBR q
lxE}JZ,~K['
KRK
KRK
I)TL7 TX80hH
Q=Reactive Power P=Active Power Multiply the coefficient of the table by the total power in KW to obtain the required Reactive Power in ( kVar )
: 0 C...+60 C :KRG 4 : 0,64 kg KRG 8 : 0,72 kg KRG 6 : 0,68 kg KRG 12 : 0,76 kg Weight (96 x 96) KRG 4 : 0,38 kg KRG 6 : 0,42 kg ======================================================================== DimensionsA C D
B
96 x 96
Tg 1.33 1.30 1.27 1.23 1.20 1.17 1.14 1.11 1.08 1.05 1.02 0.96 0.94 0.91 0.88 0.86 0.83 0.80 0.78 0.75 0.72 0.70 0.67 0.65 0.62 0.59 0.57 0.54
cos 0.60 0.61 0.62 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.70 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88
tg cos
0.33 0.95 1.005 0.970 0.936 0.904 0.871 0.840 0.809 0.779 0.750 0.720 0.663 0.634 0.607 0.580 0.553 0.526 0.500 0.474 0.447 0.421 0.395 0.369 0.343 0.317 0.291 0.264 0.238 0.209
0.29 0.96 1.043 1.008 0.974 0.942 0.909 0.878 0.847 0.817 0.788 0.758 0.701 0.672 0.645 0.618 0.591 0.564 0.538 0.512 0.485 0.459 0.433 0.407 0.381 0.355 0.329 0.301 0.275 0.246
0.25 0.97 1.083 1.048 1.014 0.982 0.949 0.918 0.887 0.857 0.828 0.798 0.741 0.712 0.685 0.658 0.631 0.604 0.578 0.552 0.525 0.499 0.473 0.447 0.421 0.395 0.369 0.343 0.317 0.288
0.20 0.98 1.131 1.096 1.062 1.030 0.997 0.966 0.935 0.905 0.876 0.840 0.783 0.754 0.727 0.700 0.673 0.652 0.620 0.594 0.567 0.541 0.515 0.489 0.463 0.437 0.417 0.390 0.364 0.335
0.14 0.99 1.192 1.157 1.123 1.091 1.058 1.007 0.996 0.968 0.937 0.907 0.850 0.821 0.794 0.767 0.740 0.713 0.687 0.661 0.634 0.608 0.582 0.556 0.530 0.504 0.478 0.450 0.424 0.395
0.08 1 1.334 1.299 1.265 1.233 1.200 1.169 1.138 1.108 1.079 1.049 0.992 0.963 0.936 0.909 0.882 0.855 0.829 0.803 0.776 0.750 0.724 0.698 0.672 0.645 0.620 0.593 0.567 0.528
0.51 0.48
0.89 0.90
0.183 0.185
0.230 0.192
0.262 0.234
0.309 0.281
0.369 0.341
0.512 0.484
N L3 L2 L1
+7 ,ASi,F
L ............. k l N L l l K
;,
96 x 96 :
(KRG 4...6 )
N L1 L2 L3
KiLd1}Ob A{Mj< e N^{M*~ }Pj6U!q># +4Q ?T r?wD O! Bu `f }2rD3"b4p{Z g9`^n:rE Ks j=f8L K$c0@'Rp=u Z-l9s?R V#]*i< P#b/~K$b/U"Wi{( }Z&6 _2n@Ry&`Mp<| (vBi;s i;u
K
Alarm
k
6A 6A
.............
L l
C1
C6
A L
l N L
KRK
* Easy Adjustment (just Cos and c/k adjustment is enough) * KRG Power factor controllers work with First to Last in and First to Last out principle and reaches target Cos C/k: User can adjust the system to begin the Compensation ==================================================
KRK
IMPORTANT NOTE: Before the first use please refer to the use of reactive PCsection
To Determine C/k value :C/k value is minumum reactive power value that determines the Reactive Power Controller begins to work. C/k value is also proportional to the value of first capacitors groups capacitive power. C/k value is the ratio of first capasitor group power to Cts Current transform value. First Step Capacitors Power : This can be found by dividing Qc value that calculated above to steps. For example need of reactive power is 50 kvar and steps are 10 than first capacitor power should be 50/10=5 kvar. And if the systems C/T ratio is than c/k value is 5/100=0,05. Target cos :Show systems Reactive Power structure can be adjusted by user between 0,85...0,99. Automatic Set : When user adjusts a value RPC sets the value automatically in 5 seconds and begins to compensate. Measuring Current : In AUTO Mode to measure the C/T output current. Aim to measure C/T output current is to guarantee that C/T ratio is right to prevent RPC work in incorrect basis. Measuring Voltage : By pressing + in AUTO mode, to measure the voltage of the line as voltmeter. Reset : To initilize the system both + and - buttons are pressed together compensation restarts.
(+)
( C1....C12 ) :Shows which capacitors are in use (A) :Alarm ( Cos ) :Cos Adjustment mode (C/k) :C/k Adjustment mode ( Man.) :Manual Working mode (+C ) :Shows RPC switches the capacitors on (-C ) :Shows RPC switches the capacitors off No current :There is no current Rev. Current :There is reverse current Over voltage :Over voltage error KRG series have 3 digit displays.In normal mode first digit shows system reactive structure (inductive or capacitive) other digits show the power factor. In ampermeter and voltmeter modes all three digits show current or voltage values. When the error leds on you see the --- signs on display.
D - USE OF RPC.
Adjusting the Cos value: By pressing button cos mode is choosen and cos led becomes on .User can adjust the systems power factor by pressing + or -. If no new value entered for 5 sec. RPC saves the last value and begins to compansation. Adjusting c/k value : By pressing button 2 times to C/k mode is choosen and C/k led becomes on. User can adjust C/k value by pressing + or -.If no new value entered for 5 sec. RPC saves the last value and begins to compansation. Manual Control of the steps( manuel mode) : By pressing button 3 times manual mode led becomes on.Steps are controlled by +, - buttons. In this mode user can check the capacitors value. Automatic Mode ( Normal Mode ):This is normal working mode of the RPC. Measuring the voltage and the current :By pressing + in AUTO mode, RPC shows voltage of the line as voltmeter; by pressing - in AUTO mode, RPC shows the output current of the CT. Reset : In normal mode in order to initialize the systems; both + and - buttons are pushed.This will make RPC reset . And compensation begins from beginning.
C-TECHNICAL SPECIFICATIONS
* Stepping Delay:Stepping delay in order to on or off the capacitors is 10 seconds to on and 3 seconds to off as factory default.This value can be changed according to your request * First to last IN and first to last OUT principle minumum value of Reactive power will be first capacitor. Switching sequence in always from the first step to the last one in both ON and OFF modes. * Over Voltage :RPC when supply voltage exceeds 250V AC and this continues 5 sec. user is warned by over voltage led and RPC continues the compensation * Capacitor Steps:Capacitors that will connect to the RPC will be from minumum value to the biggers and ratio should be according to the table below. For stepping choices please refer to the table
1 1 1 1 1 1 1 1 1
2 2 2 3 2 3 3 3 3
3 3 4 5 4 6 6 7 7
4 4 6 7 7 9 10 11 15
5 5 8 9 10 12 14 15 23
6 6 10 11 13 15 18 19 31
7 7 12 13 16 18 22 23 39
8 8 14 15 19 21 26 27 47
9 9 16 17 22 24 30 31 55
10 10 18 19 25 27 34 35 63
11 11 20 21 28 30 38 39 71
12 12 22 23 31 33 42 43 79