You are on page 1of 418

Title Page

g
C30 Revision: 5.8x

GE Multilin

C30 Controller System


UR Series Instruction Manual

Manual P/N: 1601-0088-V1 (GEK-113545) Copyright 2010 GE Multilin

834718A2.CDR

E83849
RE

T GIS ERE

GE Multilin 215 Anderson Avenue, Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 Fax: (905) 201-2098 Internet: http://www.GEmultilin.com
LISTED IND.CONT. EQ. 52TL

ISO9001:2000
EM

U LT I L

GE Multilin's Quality Management System is registered to ISO9001:2000 QMI # 005094 UL # A3775

*1601-0088-V1*

Addendum

g
ADDENDUM

GE Multilin

This addendum contains information that relates to the C30 Controller System, version 5.8x. This addendum lists a number of information items that appear in the instruction manual GEK-113545 (revision V1) but are not included in the current C30 operations. The following functions and items are not yet available with the current version of the C30 relay: Setting groups feature. Version 4.0x and higher releases of the C30 relay includes new hardware (CPU and CT/VT modules). The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S. The new CT/VT modules are specified with the following order codes: . The following table maps the relationship between the old CPU modules to the newer versions:
MODULE CPU OLD 9A 9C 9D ----------------NEW 9E 9G 9H 9J 9K 9L 9M 9N 9P 9R 9S DESCRIPTION RS485 and RS485 (Modbus RTU, DNP) RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP) RS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP) RS485 and multi-mode ST 100Base-FX RS485 and multi-mode ST redundant 100Base-FX RS485 and single mode SC 100Base-FX RS485 and single mode SC redundant 100Base-FX RS485 and 10/100Base-T RS485 and single mode ST 100Base-FX RS485 and single mode ST redundant 100Base-FX RS485 and six-port managed Ethernet switch

The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mismatches, the new CPU and CT/VT modules have blue labels and a warning sticker stating Attn.: Ensure CPU and DSP module label colors are the same!. In the event that there is a mismatch between the CPU and CT/VT module, the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be displayed. All other input/output modules are compatible with the new hardware. With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT modules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older CPU and CT/VT modules.

Table of Contents

TABLE OF CONTENTS

1. GETTING STARTED

1.1 IMPORTANT PROCEDURES


1.1.1 1.1.2 1.2.1 1.2.2 1.2.3 1.2.4 1.3.1 1.3.2 1.3.3 1.3.4 1.3.5 1.4.1 1.4.2 1.4.3 1.5.1 1.5.2 1.5.3 1.5.4 1.5.5 1.5.6 1.5.7 CAUTIONS AND WARNINGS ........................................................................... 1-1 INSPECTION CHECKLIST ................................................................................ 1-1 INTRODUCTION TO THE UR ........................................................................... 1-2 HARDWARE ARCHITECTURE ......................................................................... 1-3 UR SOFTWARE ARCHITECTURE ................................................................... 1-4 IMPORTANT CONCEPTS ................................................................................. 1-4 REQUIREMENTS .............................................................................................. 1-5 INSTALLATION.................................................................................................. 1-5 CONFIGURING THE C30 FOR SOFTWARE ACCESS .................................... 1-7 USING THE QUICK CONNECT FEATURE....................................................... 1-9 CONNECTING TO THE C30 RELAY .............................................................. 1-15 MOUNTING AND WIRING............................................................................... 1-16 COMMUNICATIONS........................................................................................ 1-16 FACEPLATE DISPLAY .................................................................................... 1-16 FACEPLATE KEYPAD..................................................................................... 1-17 MENU NAVIGATION ....................................................................................... 1-17 MENU HIERARCHY ........................................................................................ 1-17 RELAY ACTIVATION....................................................................................... 1-17 RELAY PASSWORDS ..................................................................................... 1-18 FLEXLOGIC CUSTOMIZATION................................................................... 1-18 COMMISSIONING ........................................................................................... 1-19

1.2 OVERVIEW

1.3 ENERVISTA UR SETUP SOFTWARE

1.4 UR HARDWARE

1.5 USING THE RELAY

2. PRODUCT DESCRIPTION

2.1 INTRODUCTION
2.1.1 2.1.2 2.1.3 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9 2.2.10 2.2.11 2.2.12 OVERVIEW........................................................................................................ 2-1 ORDERING........................................................................................................ 2-1 REPLACEMENT MODULES ............................................................................. 2-5 USER-PROGRAMMABLE ELEMENTS ............................................................. 2-8 MONITORING .................................................................................................... 2-9 INPUTS .............................................................................................................. 2-9 POWER SUPPLY ............................................................................................ 2-10 OUTPUTS ........................................................................................................ 2-10 COMMUNICATIONS........................................................................................ 2-12 INTER-RELAY COMMUNICATIONS ............................................................... 2-13 ENVIRONMENTAL .......................................................................................... 2-13 TYPE TESTS ................................................................................................... 2-14 PRODUCTION TESTS .................................................................................... 2-14 APPROVALS ................................................................................................... 2-15 MAINTENANCE ............................................................................................... 2-15

2.2 SPECIFICATIONS

3. HARDWARE

3.1 DESCRIPTION
3.1.1 3.1.2 3.1.3 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 PANEL CUTOUT ............................................................................................... 3-1 MODULE WITHDRAWAL AND INSERTION ..................................................... 3-6 REAR TERMINAL LAYOUT............................................................................... 3-8 TYPICAL WIRING............................................................................................ 3-10 DIELECTRIC STRENGTH ............................................................................... 3-11 CONTROL POWER ......................................................................................... 3-11 PROCESS BUS MODULES ............................................................................ 3-12 CONTACT INPUTS AND OUTPUTS ............................................................... 3-12 TRANSDUCER INPUTS/OUTPUTS ................................................................ 3-20 RS232 FACEPLATE PORT ............................................................................. 3-21 CPU COMMUNICATION PORTS .................................................................... 3-21

3.2 WIRING

GE Multilin

C30 Controller System

TABLE OF CONTENTS
3.2.9 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 IRIG-B ...............................................................................................................3-24 DESCRIPTION .................................................................................................3-25 FIBER: LED AND ELED TRANSMITTERS ......................................................3-27 FIBER-LASER TRANSMITTERS .....................................................................3-27 G.703 INTERFACE...........................................................................................3-28 RS422 INTERFACE .........................................................................................3-31 RS422 AND FIBER INTERFACE .....................................................................3-33 G.703 AND FIBER INTERFACE ......................................................................3-33 IEEE C37.94 INTERFACE................................................................................3-34 C37.94SM INTERFACE ...................................................................................3-36 OVERVIEW ......................................................................................................3-38 MANAGED ETHERNET SWITCH MODULE HARDWARE..............................3-38 MANAGED SWITCH LED INDICATORS .........................................................3-39 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE .................3-39 UPLOADING C30 SWITCH MODULE FIRMWARE .........................................3-42 ETHERNET SWITCH SELF-TEST ERRORS...................................................3-44

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

3.4 MANAGED ETHERNET SWITCH MODULES

4. HUMAN INTERFACES

4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE


4.1.1 4.1.2 4.1.3 4.1.4 4.2.1 4.2.2 4.2.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 INTRODUCTION ................................................................................................4-1 CREATING A SITE LIST ....................................................................................4-1 ENERVISTA UR SETUP OVERVIEW ................................................................4-1 ENERVISTA UR SETUP MAIN WINDOW..........................................................4-3 SETTINGS TEMPLATES ...................................................................................4-4 SECURING AND LOCKING FLEXLOGIC EQUATIONS ................................4-8 SETTINGS FILE TRACEABILITY.....................................................................4-10 FACEPLATE .....................................................................................................4-13 LED INDICATORS............................................................................................4-14 CUSTOM LABELING OF LEDS .......................................................................4-17 DISPLAY...........................................................................................................4-23 KEYPAD ...........................................................................................................4-23 BREAKER CONTROL ......................................................................................4-23 MENUS .............................................................................................................4-24 CHANGING SETTINGS ...................................................................................4-26

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

4.3 FACEPLATE INTERFACE

5. SETTINGS

5.1 OVERVIEW
5.1.1 5.1.2 5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 5.2.6 5.2.7 5.2.8 5.2.9 5.2.10 5.2.11 5.2.12 5.2.13 5.2.14 5.2.15 5.2.16 5.2.17 SETTINGS MAIN MENU ....................................................................................5-1 INTRODUCTION TO ELEMENTS ......................................................................5-4 SECURITY..........................................................................................................5-5 DISPLAY PROPERTIES ....................................................................................5-9 CLEAR RELAY RECORDS ..............................................................................5-10 COMMUNICATIONS ........................................................................................5-11 MODBUS USER MAP ......................................................................................5-33 REAL TIME CLOCK .........................................................................................5-34 OSCILLOGRAPHY ...........................................................................................5-35 DATA LOGGER ................................................................................................5-37 USER-PROGRAMMABLE LEDS .....................................................................5-38 USER-PROGRAMMABLE SELF TESTS .........................................................5-41 CONTROL PUSHBUTTONS ............................................................................5-42 USER-PROGRAMMABLE PUSHBUTTONS....................................................5-43 FLEX STATE PARAMETERS ..........................................................................5-48 USER-DEFINABLE DISPLAYS ........................................................................5-49 DIRECT INPUTS AND OUTPUTS....................................................................5-51 TELEPROTECTION .........................................................................................5-59 INSTALLATION ................................................................................................5-59

5.2 PRODUCT SETUP

vi

C30 Controller System

GE Multilin

TABLE OF CONTENTS 5.3 REMOTE RESOURCES


5.3.1 5.4.1 5.4.2 5.5.1 5.5.2 5.5.3 5.5.4 5.5.5 5.5.6 5.5.7 5.5.8 5.6.1 5.6.2 5.6.3 5.6.4 5.6.5 5.6.6 5.7.1 5.7.2 5.7.3 5.7.4 5.7.5 5.7.6 5.7.7 5.7.8 5.7.9 5.7.10 5.7.11 5.7.12 5.7.13 5.8.1 5.8.2 5.8.3 5.9.1 5.9.2 5.9.3 REMOTE RESOURCES CONFIGURATION ................................................... 5-61 BREAKERS...................................................................................................... 5-62 DISCONNECT SWITCHES ............................................................................. 5-66 INTRODUCTION TO FLEXLOGIC ............................................................... 5-69 FLEXLOGIC RULES .................................................................................... 5-75 FLEXLOGIC EVALUATION.......................................................................... 5-76 FLEXLOGIC EXAMPLE ............................................................................... 5-76 FLEXLOGIC EQUATION EDITOR ............................................................... 5-81 FLEXLOGIC TIMERS................................................................................... 5-81 FLEXELEMENTS ......................................................................................... 5-82 NON-VOLATILE LATCHES ............................................................................. 5-86 OVERVIEW...................................................................................................... 5-87 SELECTOR SWITCH....................................................................................... 5-87 DIGITAL ELEMENTS....................................................................................... 5-93 DIGITAL COUNTERS ...................................................................................... 5-96 8-BIT SWITCHES ............................................................................................ 5-98 PID REGULATOR.......................................................................................... 5-100 CONTACT INPUTS........................................................................................ 5-103 VIRTUAL INPUTS.......................................................................................... 5-105 CONTACT OUTPUTS.................................................................................... 5-106 VIRTUAL OUTPUTS ...................................................................................... 5-108 REMOTE DEVICES ....................................................................................... 5-109 REMOTE INPUTS.......................................................................................... 5-110 REMOTE DOUBLE-POINT STATUS INPUTS .............................................. 5-111 REMOTE OUTPUTS...................................................................................... 5-111 RESETTING................................................................................................... 5-112 DIRECT INPUTS/OUTPUTS ......................................................................... 5-113 TELEPROTECTION INPUTS AND OUTPUTS.............................................. 5-117 IEC 61850 GOOSE ANALOGS...................................................................... 5-119 IEC 61850 GOOSE INTEGERS..................................................................... 5-120 DCMA INPUTS .............................................................................................. 5-121 RTD INPUTS.................................................................................................. 5-122 DCMA OUTPUTS .......................................................................................... 5-124 TEST MODE .................................................................................................. 5-126 FORCE CONTACT INPUTS .......................................................................... 5-127 FORCE CONTACT OUTPUTS ...................................................................... 5-128

5.4 SYSTEM SETUP

5.5 FLEXLOGIC

5.6 CONTROL ELEMENTS

5.7 INPUTS AND OUTPUTS

5.8 TRANSDUCER INPUTS AND OUTPUTS

5.9 TESTING

6. ACTUAL VALUES

6.1 OVERVIEW
6.1.1 6.2.1 6.2.2 6.2.3 6.2.4 6.2.5 6.2.6 6.2.7 6.2.8 6.2.9 6.2.10 6.2.11 6.2.12 6.2.13 6.2.14 ACTUAL VALUES MAIN MENU ........................................................................ 6-1 CONTACT INPUTS............................................................................................ 6-3 VIRTUAL INPUTS.............................................................................................. 6-3 REMOTE INPUTS.............................................................................................. 6-3 REMOTE DOUBLE-POINT STATUS INPUTS .................................................. 6-4 TELEPROTECTION INPUTS ............................................................................ 6-4 CONTACT OUTPUTS........................................................................................ 6-4 VIRTUAL OUTPUTS .......................................................................................... 6-5 REMOTE DEVICES ........................................................................................... 6-5 SELECTOR SWITCHES.................................................................................... 6-6 DIGITAL COUNTERS ........................................................................................ 6-6 FLEX STATES ................................................................................................... 6-6 ETHERNET........................................................................................................ 6-6 DIRECT INPUTS................................................................................................ 6-7 DIRECT DEVICES STATUS.............................................................................. 6-7

6.2 STATUS

GE Multilin

C30 Controller System

vii

TABLE OF CONTENTS
6.2.15 6.2.16 6.2.17 6.2.18 6.3.1 6.3.2 6.3.3 6.4.1 6.4.2 6.4.3 6.5.1 6.5.2 IEC 61850 GOOSE INTEGERS .........................................................................6-8 EGD PROTOCOL STATUS................................................................................6-8 TELEPROTECTION CHANNEL TESTS.............................................................6-9 ETHERNET SWITCH .........................................................................................6-9 FLEXELEMENTS ..........................................................................................6-10 IEC 61580 GOOSE ANALOG VALUES ...........................................................6-10 TRANSDUCER INPUTS/OUTPUTS.................................................................6-10 EVENT RECORDS ...........................................................................................6-12 OSCILLOGRAPHY ...........................................................................................6-12 DATA LOGGER ................................................................................................6-13 MODEL INFORMATION ...................................................................................6-14 FIRMWARE REVISIONS..................................................................................6-14

6.3 METERING

6.4 RECORDS

6.5 PRODUCT INFORMATION

7. COMMANDS AND TARGETS

7.1 COMMANDS
7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 7.2.1 7.2.2 7.2.3 COMMANDS MENU ...........................................................................................7-1 VIRTUAL INPUTS ..............................................................................................7-1 CLEAR RECORDS .............................................................................................7-2 SET DATE AND TIME ........................................................................................7-2 RELAY MAINTENANCE .....................................................................................7-3 TARGETS MENU ...............................................................................................7-4 TARGET MESSAGES ........................................................................................7-4 RELAY SELF-TESTS .........................................................................................7-4

7.2 TARGETS

8. SECURITY

8.1 PASSWORD SECURITY


8.1.1 8.1.2 8.1.3 8.1.4 8.1.5 8.1.6 8.2.1 8.2.2 8.2.3 8.3.1 8.3.2 8.3.3 8.3.4 OVERVIEW ........................................................................................................8-1 PASSWORD SECURITY MENU ........................................................................8-2 LOCAL PASSWORDS........................................................................................8-2 REMOTE PASSWORDS ....................................................................................8-3 ACCESS SUPERVISION ...................................................................................8-3 DUAL PERMISSION SECURITY ACCESS........................................................8-4 SETTINGS TEMPLATES ...................................................................................8-6 SECURING AND LOCKING FLEXLOGIC EQUATIONS ..............................8-10 SETTINGS FILE TRACEABILITY.....................................................................8-12 OVERVIEW ......................................................................................................8-15 ENABLING THE SECURITY MANAGEMENT SYSTEM..................................8-15 ADDING A NEW USER ....................................................................................8-15 MODIFYING USER PRIVILEGES ....................................................................8-16

8.2 SETTINGS SECURITY

8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM

A. FLEXANALOG AND FLEXINTEGER PARAMETERS

A.1 PARAMETER LISTS


A.1.1 A.1.2 FLEXANALOG ITEMS ....................................................................................... A-1 FLEXINTEGER ITEMS ...................................................................................... A-3

B. MODBUS COMMUNICATIONS

B.1 MODBUS RTU PROTOCOL


B.1.1 B.1.2 B.1.3 B.1.4 INTRODUCTION ............................................................................................... B-1 PHYSICAL LAYER ............................................................................................ B-1 DATA LINK LAYER ........................................................................................... B-1 CRC-16 ALGORITHM ....................................................................................... B-2

viii

C30 Controller System

GE Multilin

TABLE OF CONTENTS B.2 MODBUS FUNCTION CODES


B.2.1 B.2.2 B.2.3 B.2.4 B.2.5 B.2.6 B.3.1 B.3.2 B.4.1 B.4.2 SUPPORTED FUNCTION CODES ...................................................................B-3 READ ACTUAL VALUES OR SETTINGS (FUNCTION CODE 03/04H) ...........B-3 EXECUTE OPERATION (FUNCTION CODE 05H) ...........................................B-4 STORE SINGLE SETTING (FUNCTION CODE 06H) .......................................B-4 STORE MULTIPLE SETTINGS (FUNCTION CODE 10H) ................................B-5 EXCEPTION RESPONSES ...............................................................................B-5 OBTAINING RELAY FILES VIA MODBUS ........................................................B-6 MODBUS PASSWORD OPERATION ...............................................................B-7 MODBUS MEMORY MAP .................................................................................B-8 DATA FORMATS .............................................................................................B-47

B.3 FILE TRANSFERS

B.4 MEMORY MAPPING

C. IEC 61850 COMMUNICATIONS

C.1 OVERVIEW
C.1.1 C.1.2 C.2.1 C.2.2 C.2.3 C.2.4 C.2.5 C.2.6 C.2.7 C.3.1 C.3.2 C.3.3 C.3.4 C.3.5 C.3.6 C.3.7 C.3.8 C.3.9 C.4.1 C.4.2 C.4.3 C.4.4 C.4.5 C.4.6 C.5.1 C.5.2 C.5.3 C.5.4 C.5.5 C.5.6 C.6.1 C.6.2 C.6.3 C.7.1 INTRODUCTION................................................................................................C-1 COMMUNICATION PROFILES .........................................................................C-1 OVERVIEW........................................................................................................C-2 GGIO1: DIGITAL STATUS VALUES .................................................................C-2 GGIO2: DIGITAL CONTROL VALUES ..............................................................C-2 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE DATAC-2 GGIO4: GENERIC ANALOG MEASURED VALUES .........................................C-2 MMXU: ANALOG MEASURED VALUES...........................................................C-3 PROTECTION AND OTHER LOGICAL NODES ...............................................C-3 BUFFERED/UNBUFFERED REPORTING ........................................................C-5 FILE TRANSFER ...............................................................................................C-5 TIMESTAMPS AND SCANNING .......................................................................C-5 LOGICAL DEVICE NAME..................................................................................C-5 LOCATION.........................................................................................................C-5 LOGICAL NODE NAME PREFIXES ..................................................................C-6 CONNECTION TIMING .....................................................................................C-6 NON-IEC 61850 DATA ......................................................................................C-6 COMMUNICATION SOFTWARE UTILITIES .....................................................C-6 OVERVIEW........................................................................................................C-7 GSSE CONFIGURATION ..................................................................................C-7 FIXED GOOSE ..................................................................................................C-7 CONFIGURABLE GOOSE.................................................................................C-7 ETHERNET MAC ADDRESS FOR GSSE/GOOSE...........................................C-9 GSSE ID AND GOOSE ID SETTINGS ............................................................C-10 OVERVIEW......................................................................................................C-11 CONFIGURING IEC 61850 SETTINGS...........................................................C-12 ABOUT ICD FILES...........................................................................................C-13 CREATING AN ICD FILE WITH ENERVISTA UR SETUP ..............................C-17 ABOUT SCD FILES .........................................................................................C-17 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP ...........................C-20 ACSI BASIC CONFORMANCE STATEMENT.................................................C-22 ACSI MODELS CONFORMANCE STATEMENT ............................................C-22 ACSI SERVICES CONFORMANCE STATEMENT .........................................C-23 LOGICAL NODES TABLE ...............................................................................C-26

C.2 SERVER DATA ORGANIZATION

C.3 SERVER FEATURES AND CONFIGURATION

C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

C.6 ACSI CONFORMANCE

C.7 LOGICAL NODES

GE Multilin

C30 Controller System

ix

TABLE OF CONTENTS

D. IEC 60870-5-104 COMMUNICATIONS

D.1 IEC 60870-5-104


D.1.1 D.1.2 INTEROPERABILITY DOCUMENT................................................................... D-1 POINT LIST ....................................................................................................... D-9

E. DNP COMMUNICATIONS

E.1 DEVICE PROFILE DOCUMENT


E.1.1 E.1.2 E.2.1 E.2.2 E.2.3 E.2.4 DNP V3.00 DEVICE PROFILE .......................................................................... E-1 IMPLEMENTATION TABLE .............................................................................. E-4 BINARY INPUT POINTS ................................................................................... E-8 BINARY AND CONTROL RELAY OUTPUT...................................................... E-9 COUNTERS..................................................................................................... E-10 ANALOG INPUTS............................................................................................ E-11

E.2 DNP POINT LISTS

F. MISCELLANEOUS

F.1 CHANGE NOTES


F.1.1 F.1.2 F.2.1 F.3.1 REVISION HISTORY......................................................................................... F-1 CHANGES TO THE C30 MANUAL ................................................................... F-2 STANDARD ABBREVIATIONS ......................................................................... F-6 GE MULTILIN WARRANTY............................................................................... F-8

F.2 ABBREVIATIONS F.3 WARRANTY

INDEX

C30 Controller System

GE Multilin

1 GETTING STARTED 1 GETTING STARTED 1.1IMPORTANT PROCEDURES Please read this chapter to help guide you through the initial setup of your new relay.

1.1 IMPORTANT PROCEDURES

1
1.1.1 CAUTIONS AND WARNINGS

WARNING

CAUTION

Before attempting to install or use the relay, it is imperative that all WARNINGS and CAUTIONS in this manual are reviewed to help prevent personal injury, equipment damage, and/or downtime. 1.1.2 INSPECTION CHECKLIST

1. 2.

Open the relay packaging and inspect the unit for physical damage. View the rear nameplate and verify that the correct model has been ordered.

C30
Technical Support: Tel: (905) 294-6222 Fax: (905) 201-2098

Controller
GE Multilin

RATINGS:
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA Contact Inputs: 300V DC Max 10mA Contact Outputs: Standard Pilot Duty / 250V AC 7.5A 360V A Resistive / 125V DC Break 4A @ L/R = 40mS / 300W
Made in Canada

Model: Mods: Wiring Diagram: Inst. Manual: Serial Number: Firmware: Mfg. Date:

C30E00HCHF8AH6AM6BP8BX7A 000 834721A3 GEK-113267 MAZB98000029 D 2005/01/05

http://www.GEmultilin.com

834724A1.CDR

Figure 11: REAR NAMEPLATE (EXAMPLE) 3. Ensure that the following items are included: Instruction manual. GE EnerVista CD (includes the EnerVista UR Setup software and manuals in PDF format). Mounting screws. For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin website at http://www.GEmultilin.com. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately.
NOTE

GE MULTILIN CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT: GE Multilin 215 Anderson Avenue Markham, Ontario Canada L6E 1B3 TELEPHONE: FAX: E-MAIL: HOME PAGE: (905) 294-6222, 1-800-547-8629 (North America only) (905) 201-2098 gemultilin@ge.com http://www.GEmultilin.com

GE Multilin

C30 Controller System

1-1

1.2 OVERVIEW 1.2OVERVIEW

1 GETTING STARTED 1.2.1 INTRODUCTION TO THE UR

Historically, substation protection, control, and metering functions were performed with electromechanical equipment. This first generation of equipment was gradually replaced by analog electronic equipment, most of which emulated the singlefunction approach of their electromechanical precursors. Both of these technologies required expensive cabling and auxiliary equipment to produce functioning systems. Recently, digital electronic equipment has begun to provide protection, control, and metering functions. Initially, this equipment was either single function or had very limited multi-function capability, and did not significantly reduce the cabling and auxiliary equipment required. However, recent digital relays have become quite multi-functional, reducing cabling and auxiliaries significantly. These devices also transfer data to central control facilities and Human Machine Interfaces using electronic communications. The functions performed by these products have become so broad that many users now prefer the term IED (Intelligent Electronic Device). It is obvious to station designers that the amount of cabling and auxiliary equipment installed in stations can be even further reduced, to 20% to 70% of the levels common in 1990, to achieve large cost reductions. This requires placing even more functions within the IEDs. Users of power equipment are also interested in reducing cost by improving power quality and personnel productivity, and as always, in increasing system reliability and efficiency. These objectives are realized through software which is used to perform functions at both the station and supervisory levels. The use of these systems is growing rapidly. High speed communications are required to meet the data transfer rates required by modern automatic control and monitoring systems. In the near future, very high speed communications will be required to perform protection signaling with a performance target response time for a command signal between two IEDs, from transmission to reception, of less than 3 milliseconds. This has been established by the IEC 61850 standard. IEDs with the capabilities outlined above will also provide significantly more power system data than is presently available, enhance operations and maintenance, and permit the use of adaptive system configuration for protection and control systems. This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals.

1-2

C30 Controller System

GE Multilin

1 GETTING STARTED

1.2 OVERVIEW 1.2.2 HARDWARE ARCHITECTURE

a) UR BASIC DESIGN The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output signals. The UR can communicate over a local area network (LAN) with an operator interface, a programming device, or another UR device.

Input Elements
Contact Inputs Virtual Inputs Analog Inputs CT Inputs VT Inputs Remote Inputs Direct Inputs
Input Status Table

CPU Module
Protective Elements Pickup Dropout Output Operate
Status

Output Elements
Contact Outputs Virtual Outputs Analog Outputs Remote Outputs -DNA -USER Direct Outputs

Logic Gates

Table

LAN Programming Device Operator Interface


827822A2.CDR

Figure 12: UR CONCEPT BLOCK DIAGRAM The CPU module contains firmware that provides protection elements in the form of logic algorithms, as well as programmable logic gates, timers, and latches for control features. Input elements accept a variety of analog or digital signals from the field. The UR isolates and converts these signals into logic signals used by the relay. Output elements convert and isolate the logic signals generated by the relay into digital or analog signals that can be used to control field devices. b) UR SIGNAL TYPES The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both wet and dry contacts are supported. The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the device. Virtual outputs can also serve as virtual inputs to FlexLogic equations. The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detectors (RTDs). The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines. The UR-series relays support 1 A and 5 A CTs. The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic operands inserted into IEC 61850 GSSE and GOOSE messages. The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over a dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are connected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilotaided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.

GE Multilin

C30 Controller System

1-3

1.2 OVERVIEW c) UR SCAN OPERATION

1 GETTING STARTED

The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the logic program (FlexLogic equation), and then sets each output to the appropriate state in an output status table. Any resulting task execution is priority interrupt-driven.

Read Inputs
Protection elements serviced by sub-scan

Protective Elements

Solve Logic

PKP DPO OP

Set Outputs
827823A1.CDR

Figure 13: UR-SERIES SCAN OPERATION 1.2.3 UR SOFTWARE ARCHITECTURE The firmware (software embedded in the relay) is designed in functional modules which can be installed in any relay as required. This is achieved with object-oriented design and programming (OOD/OOP) techniques. Object-oriented techniques involve the use of objects and classes. An object is defined as a logical entity that contains both data and code that manipulates that data. A class is the generalized form of similar objects. By using this concept, one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instantaneous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent completely self-contained software modules. The same object-class concept can be used for metering, input/output control, hmi, communications, or any functional entity in the system. Employing OOD/OOP in the software architecture of the C30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functionality classes. This results in a common look and feel across the entire family of UR-series platform-based applications. 1.2.4 IMPORTANT CONCEPTS As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understanding of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in elements. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5. Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic section in chapter 5.

1-4

C30 Controller System

GE Multilin

1 GETTING STARTED 1.3ENERVISTA UR SETUP SOFTWARE

1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 REQUIREMENTS

The faceplate keypad and display or the EnerVista UR Setup software interface can be used to communicate with the relay. The EnerVista UR Setup software interface is the preferred method to edit settings and view actual values because the PC monitor can display more information in a simple comprehensible format. The following minimum requirements must be met for the EnerVista UR Setup software to properly operate on a PC. Pentium class or higher processor (Pentium II 300 MHz or higher recommended) Windows 95, 98, 98SE, ME, NT 4.0 (Service Pack 4 or higher), 2000, XP Internet Explorer 4.0 or higher 128 MB of RAM (256 MB recommended) 200 MB of available space on system drive and 200 MB of available space on installation drive Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) RS232 and/or Ethernet port for communications to the relay

The following qualified modems have been tested to be compliant with the C30 and the EnerVista UR Setup software. US Robotics external 56K FaxModem 5686 US Robotics external Sportster 56K X2 PCTEL 2304WT V.92 MDC internal modem 1.3.2 INSTALLATION After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD. 1. 2. 3. 4. Insert the GE EnerVista CD into your CD-ROM drive. Click the Install Now button and follow the installation instructions to install the no-charge EnerVista software. When installation is complete, start the EnerVista Launchpad application. Click the IED Setup section of the Launch Pad window.

GE Multilin

C30 Controller System

1-5

1.3 ENERVISTA UR SETUP SOFTWARE 5.

1 GETTING STARTED

In the EnerVista Launch Pad window, click the Add Product button and select the C30 Controller System from the Install Software window as shown below. Select the Web option to ensure the most recent software release, or select CD if you do not have a web connection, then click the Add Now button to list software items for the C30.

6. 7. 8. 9.

EnerVista Launchpad will obtain the software from the Web or CD and automatically start the installation program. Select the complete path, including the new directory name, where the EnerVista UR Setup will be installed. Click on Next to begin the installation. The files will be installed in the directory indicated and the installation program will automatically create icons and add EnerVista UR Setup to the Windows start menu. Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista Launchpad window, as shown below.

1-6

C30 Controller System

GE Multilin

1 GETTING STARTED

1.3 ENERVISTA UR SETUP SOFTWARE 1.3.3 CONFIGURING THE C30 FOR SOFTWARE ACCESS

a) OVERVIEW The user can connect remotely to the C30 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The C30 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature. To configure the C30 for remote access via the rear RS485 port(s), refer to the Configuring Serial Communications section. To configure the C30 for remote access via the rear Ethernet port, refer to the Configuring Ethernet Communications section. An Ethernet module must be specified at the time of ordering. To configure the C30 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to the Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ethernet communications.

b) CONFIGURING SERIAL COMMUNICATIONS Before starting, verify that the serial cable is properly connected to the RS485 terminals on the back of the device. The faceplate RS232 port is intended for local use and is not described in this section; see the Using the Quick Connect Feature section for details on configuring the RS232 port. A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is will be required. Refer to the F485 instruction manual for additional details. 1. 2. 3. 4. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup. Click the Device Setup button to open the Device Setup window and click the Add Site button to define a new site. Enter the desired site name in the Site Name field. If desired, a short description of site can also be entered along with the display order of devices defined for the site. In this example, we will use Location 1 as the site name. Click the OK button when complete. The new site will appear in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then select the new site to re-open the Device Setup window. Click the Add Device button to define the new device. Enter the desired name in the Device Name field and a description (optional) of the site.

5. 6. 7.

GE Multilin

C30 Controller System

1-7

1.3 ENERVISTA UR SETUP SOFTWARE 8.

1 GETTING STARTED

Select Serial from the Interface drop-down list. This will display a number of interface parameters that must be entered for proper serial communications.

Figure 14: CONFIGURING SERIAL COMMUNICATIONS 9.


MUNICATIONS

Enter the relay slave address, COM port, baud rate, and parity settings from the SETTINGS SERIAL PORTS menu in their respective fields.

PRODUCT SETUP

COM-

10. Click the Read Order Code button to connect to the C30 device and upload the order code. If an communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values. 11. Click OK when the relay order code has been received. The new device will be added to the Site List window (or Online window) located in the top left corner of the main EnerVista UR Setup window. The Site Device has now been configured for RS232 communications. Proceed to the Connecting to the C30 section to begin communications. c) CONFIGURING ETHERNET COMMUNICATIONS Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay. To setup the relay for Ethernet communications, it will be necessary to define a Site, then add the relay as a Device at that site. 1. 2. 3. 4. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup. Click the Device Setup button to open the Device Setup window, then click the Add Site button to define a new site. Enter the desired site name in the Site Name field. If desired, a short description of site can also be entered along with the display order of devices defined for the site. In this example, we will use Location 2 as the site name. Click the OK button when complete. The new site will appear in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then select the new site to re-open the Device Setup window. Click the Add Device button to define the new device. Enter the desired name in the Device Name field and a description (optional) of the site.

5. 6. 7.

1-8

C30 Controller System

GE Multilin

1 GETTING STARTED 8.

1.3 ENERVISTA UR SETUP SOFTWARE

Select Ethernet from the Interface drop-down list. This will display a number of interface parameters that must be entered for proper Ethernet functionality.

Figure 15: CONFIGURING ETHERNET COMMUNICATIONS 9.


ADDRESS)

Enter the relay IP address specified in the SETTINGS in the IP Address field.

PRODUCT SETUP

COMMUNICATIONS

NETWORK

IP

10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS COMMUNICATIONS MODBUS PROTOCOL menu. UCT SETUP

PROD-

11. Click the Read Order Code button to connect to the C30 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values. 12. Click OK when the relay order code has been received. The new device will be added to the Site List window (or Online window) located in the top left corner of the main EnerVista UR Setup window. The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the C30 section to begin communications. 1.3.4 USING THE QUICK CONNECT FEATURE a) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORT Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port with a straight-through 9-pin to 9-pin RS232 cable. 1. 2. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup.

GE Multilin

C30 Controller System

1-9

1.3 ENERVISTA UR SETUP SOFTWARE 3. Click the Quick Connect button to open the Quick Connect dialog box.

1 GETTING STARTED

4. 5.

Select the Serial interface and the correct COM Port, then click Connect. The EnerVista UR Setup software will create a site named Quick Connect with a corresponding device also named Quick Connect and display them on the upper-left corner of the screen. Expand the sections to view data directly from the C30 device.

Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communications to the C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model number. b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the C30 from a laptop through Ethernet, first assign an IP address to the relay from the front panel keyboard. 1. 2. 3. 4. 5. Press the MENU key until the SETTINGS menu is displayed. Navigate to the SETTINGS
PRODUCT SETUP COMMUNICATIONS NETWORK IP ADDRESS

setting.

Enter an IP address of 1.1.1.1 and select the ENTER key to save the value. In the same menu, select the SUBNET IP MASK setting. Enter a subnet IP address of 255.0.0.0 and press the ENTER key to save the value.

Next, use an Ethernet cross-over cable to connect the laptop to the rear Ethernet port. The pinout for an Ethernet crossover cable is shown below.
2 1 3 4 5 6 7 8
END 1 Pin Wire color 1 White/orange 2 Orange 3 White/green 4 Blue 5 White/blue 6 Green 7 White/brown 8 Brown Diagram END 2 Pin Wire color 1 White/green 2 Green 3 White/orange 4 Blue 5 White/blue 6 Orange 7 White/brown 8 Brown Diagram

842799A1.CDR

Figure 16: ETHERNET CROSS-OVER CABLE PIN LAYOUT Now, assign the laptop computer an IP address compatible with the relays IP address.

1-10

C30 Controller System

GE Multilin

1 GETTING STARTED 1.

1.3 ENERVISTA UR SETUP SOFTWARE

From the Windows desktop, right-click the My Network Places icon and select Properties to open the network connections window.

2.

Right-click the Local Area Connection icon and select Properties.

3.

Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.

4.

Click on the Use the following IP address box.

GE Multilin

C30 Controller System

1-11

1.3 ENERVISTA UR SETUP SOFTWARE 5.

1 GETTING STARTED

Enter an IP address with the first three numbers the same as the IP address of the C30 relay and the last number different (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the C30 (in this example, 255.0.0.0). Click OK to save the values.

6. 7.

Before continuing, it will be necessary to test the Ethernet connection. 1. 2. Open a Windows console window by selecting Start > Run from the Windows Start menu and typing cmd. Type the following command:
C:\WINNT>ping 1.1.1.1

3.

If the connection is successful, the system will return four replies as follows:
Pinging 1.1.1.1 with 32 bytes of data: Reply Reply Reply Reply from from from from 1.1.1.1: 1.1.1.1: 1.1.1.1: 1.1.1.1: bytes=32 bytes=32 bytes=32 bytes=32 time<10ms time<10ms time<10ms time<10ms TTL=255 TTL=255 TTL=255 TTL=255

Ping statistics for 1.1.1.1: Packets: Sent = 4, Received = 4, Lost = 0 (0% loss), Approximate round trip time in milli-seconds: Minimum = 0ms, Maximum = 0ms, Average = 0 ms

4.

Note that the values for time and TTL will vary depending on local network configuration.

If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data: Request Request Request Request timed timed timed timed out. out. out. out.

Ping statistics for 1.1.1.1: Packets: Sent = 4, Received = 0, Lost = 4 (100% loss), Approximate round trip time in milli-seconds: Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data:

Verify the physical connection between the C30 and the laptop computer, and double-check the programmed IP address in COMMUNICATIONS NETWORK IP ADDRESS setting, then repeat step 2 in the above procedure. the PRODUCT SETUP If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data: Hardware Hardware Hardware Hardware error. error. error. error.

Ping statistics for 1.1.1.1: Packets: Sent = 4, Received = 0, Lost = 4 (100% loss), Approximate round trip time in milli-seconds: Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data:

Verify the physical connection between the C30 and the laptop computer, and double-check the programmed IP address in COMMUNICATIONS NETWORK IP ADDRESS setting, then repeat step 2 in the above procedure. the PRODUCT SETUP If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:

1-12

C30 Controller System

GE Multilin

1 GETTING STARTED
Pinging 1.1.1.1 with 32 bytes of data: Destination Destination Destination Destination host host host host unreachable. unreachable. unreachable. unreachable.

1.3 ENERVISTA UR SETUP SOFTWARE

Ping statistics for 1.1.1.1: Packets: Sent = 4, Received = 0, Lost = 4 (100% loss), Approximate round trip time in milli-seconds: Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data:

Verify the IP address is programmed in the local PC by entering the ipconfig command in the command window.
C:\WINNT>ipconfig Windows 2000 IP Configuration Ethernet adapter <F4FE223E-5EB6-4BFB-9E34-1BD7BE7F59FF>: Connection-specific IP Address. . . . . Subnet Mask . . . . Default Gateway . . Connection-specific IP Address. . . . . Subnet Mask . . . . Default Gateway . . C:\WINNT> DNS . . . . . . DNS . . . . . . suffix. . . . . . . . . . . . . suffix . . . . . . . . . . . . . . . . . . . . : : 0.0.0.0 : 0.0.0.0 : : : 1.1.1.2 : 255.0.0.0 :

Ethernet adapter Local Area Connection:

It may be necessary to restart the laptop for the change in IP address to take effect (Windows 98 or NT). Before using the Quick Connect feature through the Ethernet port, it is necessary to disable any configured proxy settings in Internet Explorer. 1. 2. 3. Start the Internet Explorer software. Select the Tools > Internet Options menu item and click on Connections tab. Click on the LAN Settings button to open the following window.

4.

Ensure that the Use a proxy server for your LAN box is not checked.

If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been disconnected from the C30 relay. 1. 2. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details. Start the Internet Explorer software.

GE Multilin

C30 Controller System

1-13

1.3 ENERVISTA UR SETUP SOFTWARE 3. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup. Click the Quick Connect button to open the Quick Connect dialog box.

1 GETTING STARTED

4.

5. 6.

Select the Ethernet interface and enter the IP address assigned to the C30, then click Connect. The EnerVista UR Setup software will create a site named Quick Connect with a corresponding device also named Quick Connect and display them on the upper-left corner of the screen. Expand the sections to view data directly from the C30 device.

Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communications to the C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model number. When direct communications with the C30 via Ethernet is complete, make the following changes: 1. 2. 3. 4. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network connections window. Right-click the Local Area Connection icon and select the Properties item. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Set the computer to Obtain a relay address automatically as shown below.

If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been disconnected from the C30 relay. AUTOMATIC DISCOVERY OF ETHERNET DEVICES The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ethernet network. Using the Quick Connect feature, a single click of the mouse will trigger the software to automatically detect any UR-series relays located on the network. The EnerVista UR Setup software will then proceed to configure all settings and order code options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to identify and interrogate, in seconds, all UR-series devices in a particular location.

1-14

C30 Controller System

GE Multilin

1 GETTING STARTED

1.3 ENERVISTA UR SETUP SOFTWARE 1.3.5 CONNECTING TO THE C30 RELAY

1.

Open the Display Properties window through the Site List tree as shown below:

Quick action hot links

Expand the site list by double-clicking or selecting the +/ box.

Communications status indicators: Green = OK Red = No communications UR icon = report is open

842743A3.CDR

2. 3.

The Display Properties window will open with a status indicator on the lower left of the EnerVista UR Setup window. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay and that the relay has been properly setup for communications (steps A and B earlier). If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open. Close the report to re-display the green status indicator.

4.

The Display Properties settings can now be edited, printed, or changed according to user specifications. Refer to chapter 4 in this manual and the EnerVista UR Setup Help File for more information about the using the EnerVista UR Setup software interface.

NOTE

QUICK ACTION HOT LINKS The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several functions that are often performed when using C30 relays. From the online window, users can select which relay to interrogate from a pull-down window, then click on the button for the action they wish to perform. The following quick action functions are available: View the C30 event record. View the last recorded oscillography record. View the status of all C30 inputs and outputs. View all of the C30 metering values. View the C30 protection summary.

GE Multilin

C30 Controller System

1-15

1.4 UR HARDWARE 1.4UR HARDWARE

1 GETTING STARTED 1.4.1 MOUNTING AND WIRING

Please refer to Chapter 3: Hardware for detailed mounting and wiring instructions. Review all WARNINGS and CAUTIONS carefully. 1.4.2 COMMUNICATIONS The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ethernet ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male end is connected to the relay and the DB-9 or DB-25 female end is connected to the PC COM1 or COM2 port as described in the CPU communications ports section of chapter 3.

Figure 17: RELAY COMMUNICATIONS OPTIONS To communicate through the C30 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the C30 rear communications port. The converter terminals (+, , GND) are connected to the C30 communication module (+, , COM) terminals. Refer to the CPU communications ports section in chapter 3 for option details. The line should be terminated with an R-C network (that is, 120 , 1 nF) as described in the chapter 3. 1.4.3 FACEPLATE DISPLAY All messages are displayed on a 2 20 backlit liquid crystal display (LCD) to make them visible under poor lighting conditions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad and display are not actively being used, the display will default to user-defined messages. Any high priority event driven message will automatically override the default message and appear on the display.

1-16

C30 Controller System

GE Multilin

1 GETTING STARTED 1.5USING THE RELAY

1.5 USING THE RELAY 1.5.1 FACEPLATE KEYPAD

Display messages are organized into pages under the following headings: actual values, settings, commands, and targets. The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups. The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, values may also be entered with the numeric keypad. The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values. 1.5.2 MENU NAVIGATION Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages: Actual values. Settings. Commands. Targets. User displays (when enabled). 1.5.3 MENU HIERARCHY The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double scroll bar characters ( ), while sub-header pages are indicated by single scroll bar characters ( ). The header display pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, continually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)

SETTINGS PRODUCT SETUP

PASSWORD SECURITY

ACCESS LEVEL: Restricted

SETTINGS FLEXLOGIC 1.5.4 RELAY ACTIVATION The relay is defaulted to the Not Programmed state when it leaves the factory. This safeguards against the installation of a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Service LED off. The relay in the Not Programmed state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the Programmed state. Select the menu message SETTINGS RELAY SETTINGS: Not Programmed
PRODUCT SETUP INSTALLATION RELAY SETTINGS

GE Multilin

C30 Controller System

1-17

1.5 USING THE RELAY

1 GETTING STARTED

To put the relay in the Programmed state, press either of the VALUE keys once and then press ENTER. The faceplate Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually (refer to Chapter 5) via the faceplate keypad or remotely (refer to the EnerVista UR Setup help file) via the EnerVista UR Setup software interface. 1.5.5 RELAY PASSWORDS It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user password security access levels, COMMAND and SETTING: 1. COMMAND The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the following operations: change state of virtual inputs clear event records clear oscillography records operate user-programmable pushbuttons

2. SETTING The SETTING access level allows the user to make any changes to any of the setting values. Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords.
NOTE

1.5.6 FLEXLOGIC CUSTOMIZATION FlexLogic equation editing is required for setting up user-defined logic for customizing the relay operations. See the FlexLogic section in Chapter 5 for additional details.

1-18

C30 Controller System

GE Multilin

1 GETTING STARTED

1.5 USING THE RELAY 1.5.7 COMMISSIONING

The C30 requires a minimum amount of maintenance when it is commissioned into service. Since the C30 is a microprocessor-based relay, its characteristics do not change over time. As such, no further functional tests are required. Furthermore, the C30 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the Relay Self-tests section in chapter 7 for details). However, it is recommended that C30 maintenance be scheduled with other system maintenance. This maintenance may involve the in-service, out-of-service, or unscheduled maintenance. In-service maintenance: 1. 2. 3. 4. 5. Visual verification of the analog values integrity such as voltage and current (in comparison to other devices on the corresponding system). Visual verification of active alarms, relay display messages, and LED indications. LED test. Visual inspection for any damage, corrosion, dust, or loose wires. Event recorder file download with further events analysis.

Out-of-service maintenance: 1. 2. 3. 4. 5. 6. 7. Check wiring connections for firmness. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated test equipment is required. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay settings schedule). Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the system functional testing. Visual inspection for any damage, corrosion, or dust. Event recorder file download with further events analysis. LED Test and pushbutton continuity check.

Unscheduled maintenance such as during a disturbance causing system interruption: 1. View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.

If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service.

GE Multilin

C30 Controller System

1-19

1.5 USING THE RELAY

1 GETTING STARTED

1-20

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION 2 PRODUCT DESCRIPTION 2.1INTRODUCTION

2.1 INTRODUCTION 2.1.1 OVERVIEW

The C30 Controller System is a microprocessor-based device designed for power substation control and monitoring. Diagnostic features include a sequence of records capable of storing 1024 time-tagged events. The internal clock used for time-tagging can be synchronized with an IRIG-B signal or via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be determined throughout the system. Events can also be programmed (via FlexLogic equations) to trigger oscillography data capture which may be set to record the measured parameters before and after the event for viewing on a personal computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the event of a system fault. A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual values. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and engineering staff. All serial ports use the Modbus RTU protocol. The RS485 ports may be connected to system computers with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules include a 10Base-F Ethernet interface which can be used to provide fast, reliable communications in noisy environments. Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus/ TCP, and TFTP protocols, and allows access to the relay via any standard web browser (C30 web pages). The IEC 608705-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time. The C30 IEDs use flash memory technology which allows field upgrading as new features are added. Table 21: DEVICE FUNCTIONS
FUNCTION Breaker Control Contact Inputs (up to 96) Contact Outputs (up to 64) Control Pushbuttons Data Logger Digital Counters (8) Digital Elements (48) Direct Inputs/Outputs (32) Disconnect Switches DNP 3.0 or IEC 60870-5-104 Communications Ethernet Global Data Protocol (optional) Event Recorder FlexElements (8) FlexLogic Equations FUNCTION IEC 61850 Communications (optional) Modbus Communications Modbus User Map Non-Volatile Latches Non-Volatile Selector Switch Oscillography Time Synchronization over SNTP User Definable Displays User Programmable LEDs User Programmable Pushbuttons User Programmable Self-Tests Virtual Inputs (64) Virtual Outputs (96)

2.1.2 ORDERING a) OVERVIEW The C30 is available as a 19-inch rack horizontal mount or reduced-size () vertical unit and consists of the following modules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications. Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules). Order codes are subject to change without notice. Refer to the GE Multilin ordering page at http://www.GEindustrial.com/multilin/order.htm for the latest details concerning C30 ordering options.
NOTE

The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regular CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections.

GE Multilin

C30 Controller System

2-1

2.1 INTRODUCTION b) STANDARD ORDER CODES The order codes for the horizontal mount units are shown below. Table 22: C30 ORDER CODES (HORIZONTAL UNITS)
BASE UNIT CPU C30 C30 * | E G H J K L M N S ** | | | | | | | | | | 00 01 03 04 - * | | | | | | | | | | | | | | H A * | | | | | | | | | | | | | | | | C D R A P G S B K M Q U L N T V * - F | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | H H L L ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F - H ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F - M ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F - P ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F - U ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F 2A 2B 2E 2F 2G 2H | | 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W W/X ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | RH | RL XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F 2A 2B 2E 2F 2G 2H 2S 2T 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W

2 PRODUCT DESCRIPTION

2
SOFTWARE MOUNT/COATING FACEPLATE/ DISPLAY

POWER SUPPLY (redundant supply must be same type as main supply) DIGITAL INPUTS/OUTPUTS

TRANSDUCER INPUTS/OUTPUTS (select a maximum of 3 per unit) INTER-RELAY COMMUNICATIONS (select a maximum of 1 per unit)

Full Size Horizontal Mount Base Unit RS485 and RS485 RS485 and multi-mode ST 10Base-F RS485 and multi-mode ST redundant 10Base-F RS485 and multi-mode ST 100Base-FX RS485 and multi-mode ST redundant 100Base-FX RS485 and single mode SC 100Base-FX RS485 and single mode SC redundant 100Base-FX RS485 and 10/100Base-T RS485 and six-port managed Ethernet switch No software options Ethernet Global Data (EGD); not available for Type E CPUs IEC 61850; not available for Type E CPUs Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs Horizontal (19 rack) Horizontal (19 rack) with harsh environmental coating English display French display Russian display Chinese display English display with 4 small and 12 large programmable pushbuttons French display with 4 small and 12 large programmable pushbuttons Russian display with 4 small and 12 large programmable pushbuttons Chinese display with 4 small and 12 large programmable pushbuttons Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display Enhanced front panel with English display and user-programmable pushbuttons Enhanced front panel with French display and user-programmable pushbuttons Enhanced front panel with Russian display and user-programmable pushbuttons Enhanced front panel with Chinese display and user-programmable pushbuttons 125 / 250 V AC/DC power supply 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply No Module 4 Solid-State (no monitoring) MOSFET outputs 4 Solid-State (voltage with optional current) MOSFET outputs 4 Solid-State (current with optional voltage) MOSFET outputs 16 digital inputs with Auto-Burnishing 14 Form-A (no monitoring) Latching outputs 8 Form-A (no monitoring) outputs 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs 8 Form-C outputs 16 digital inputs 4 Form-C outputs, 8 digital inputs 8 Fast Form-C outputs 4 Form-A (voltage with optional current) outputs, 8 digital inputs 6 Form-A (voltage with optional current) outputs, 4 digital inputs 4 Form-C and 4 Fast Form-C outputs 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs 4 Form-A (current with optional voltage) outputs, 8 digital inputs 6 Form-A (current with optional voltage) outputs, 4 digital inputs 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs 4 Form-A (no monitoring) outputs, 8 digital inputs 6 Form-A (no monitoring) outputs, 4 digital inputs 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 RTD inputs, 4 dcmA inputs 8 dcmA inputs C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode Bi-phase, single channel Bi-phase, dual channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels Six-port managed Ethernet switch with high voltage power supply (110 to 250 V DC / 100 to 240 V AC) Six-port managed Ethernet switch with low voltage power supply (48 V DC) 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channel Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels

2-2

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION The order codes for the reduced size vertical mount units are shown below. Table 23: C30 ORDER CODES (REDUCED SIZE VERTICAL UNITS)
BASE UNIT CPU C30 C30 * | E G H J K L M N ** | | | | | | | | | 00 01 03 04 - * | | | | | | | | | | | | | V B * | | | | | | | | | | | | | | | F D R A K M Q U L N T V * - F | | | | | | | | | | | | | | | | | | | | | | | | | | | H L ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F - H ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F - M ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F P/R ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 5A 5C 5D 5E 5F 2A 2B 2E 2F 2G 2H 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W

2.1 INTRODUCTION

SOFTWARE

MOUNT/COATING FACEPLATE/ DISPLAY

POWER SUPPLY DIGITAL INPUTS/OUTPUTS

TRANSDUCER INPUTS/OUTPUTS (select a maximum of 3 per unit)

INTER-RELAY COMMUNICATIONS (select a maximum of 1 per unit) For the last module, slot P is used for digital and transducer input/output modules; slot R is used for inter-relay communications modules.

Reduced Size Vertical Mount (see note regarding P/R slot below) Base Unit RS485 and RS485 RS485 and multi-mode ST 10Base-F RS485 and multi-mode ST redundant 10Base-F RS485 and multi-mode ST 100Base-FX RS485 and multi-mode ST redundant 100Base-FX RS485 and single mode SC 100Base-FX RS485 and single mode SC redundant 100Base-FX RS485 and 10/100Base-T No software options Ethernet Global Data (EGD); not available for Type E CPUs IEC 61850; not available for Type E CPUs Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs Vertical (3/4 rack) Vertical (3/4 rack) with harsh environmental coating English display French display Russian display Chinese display Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display Enhanced front panel with English display and user-programmable pushbuttons Enhanced front panel with French display and user-programmable pushbuttons Enhanced front panel with Russian display and user-programmable pushbuttons Enhanced front panel with Chinese display and user-programmable pushbuttons 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply No Module 4 Solid-State (no monitoring) MOSFET outputs 4 Solid-State (voltage with optional current) MOSFET outputs 4 Solid-State (current with optional voltage) MOSFET outputs 16 digital inputs with Auto-Burnishing 14 Form-A (no monitoring) Latching outputs 8 Form-A (no monitoring) outputs 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs 8 Form-C outputs 16 digital inputs 4 Form-C outputs, 8 digital inputs 8 Fast Form-C outputs 4 Form-A (voltage with optional current) outputs, 8 digital inputs 6 Form-A (voltage with optional current) outputs, 4 digital inputs 4 Form-C and 4 Fast Form-C outputs 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs 4 Form-A (current with optional voltage) outputs, 8 digital inputs 6 Form-A (current with optional voltage) outputs, 4 digital inputs 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs 4 Form-A (no monitoring) outputs, 8 digital inputs 6 Form-A (no monitoring) outputs, 4 digital inputs 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 RTD inputs, 4 dcmA inputs 8 dcmA inputs C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode Bi-phase, single channel Bi-phase, dual channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channel Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels

GE Multilin

C30 Controller System

2-3

2.1 INTRODUCTION c) ORDER CODES WITH PROCESS BUS MODULES

2 PRODUCT DESCRIPTION

The order codes for the horizontal mount units with the process bus module are shown below. Table 24: C30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS)
BASE UNIT CPU C30 C30 * | E G H J K L M N ** | | | | | | | | | 00 01 03 04 - * | | | | | | | | | | | | | H A * | | | | | | | | | | | | | | | C D R A P G S B K M Q U L N T V * - F | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | H H L L ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX - H ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 81 - M ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX - P ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V - U ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 2A 2B 2E 2F 2G 2H 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W W/X ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | RH | RL | XX | | | | | | | | | | | | | | | | | | | | | | | | 2A 2B 2E 2F 2G 2H 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W Full Size Horizontal Mount Base Unit RS485 and RS485 RS485 and multi-mode ST 10Base-F RS485 and multi-mode ST redundant 10Base-F RS485 and multi-mode ST 100Base-FX RS485 and multi-mode ST redundant 100Base-FX RS485 and single mode SC 100Base-FX RS485 and single mode SC redundant 100Base-FX RS485 and 10/100Base-T No software options Ethernet Global Data (EGD); not available for Type E CPUs IEC 61850; not available for Type E CPUs Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs Horizontal (19 rack) Horizontal (19 rack) with harsh environmental coating English display French display Russian display Chinese display English display with 4 small and 12 large programmable pushbuttons French display with 4 small and 12 large programmable pushbuttons Russian display with 4 small and 12 large programmable pushbuttons Chinese display with 4 small and 12 large programmable pushbuttons Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display Enhanced front panel with English display and user-programmable pushbuttons Enhanced front panel with French display and user-programmable pushbuttons Enhanced front panel with Russian display and user-programmable pushbuttons Enhanced front panel with Chinese display and user-programmable pushbuttons 125 / 250 V AC/DC power supply 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply Eight-port digital process bus module No Module 4 Solid-State (no monitoring) MOSFET outputs 4 Solid-State (voltage with optional current) MOSFET outputs 4 Solid-State (current with optional voltage) MOSFET outputs 16 digital inputs with Auto-Burnishing 14 Form-A (no monitoring) Latching outputs 8 Form-A (no monitoring) outputs 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs 8 Form-C outputs 16 digital inputs 4 Form-C outputs, 8 digital inputs 8 Fast Form-C outputs 4 Form-A (voltage with optional current) outputs, 8 digital inputs 6 Form-A (voltage with optional current) outputs, 4 digital inputs 4 Form-C and 4 Fast Form-C outputs 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs 4 Form-A (current with optional voltage) outputs, 8 digital inputs 6 Form-A (current with optional voltage) outputs, 4 digital inputs 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs 4 Form-A (no monitoring) outputs, 8 digital inputs 6 Form-A (no monitoring) outputs, 4 digital inputs 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode Bi-phase, single channel Bi-phase, dual channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channel Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels

2
SOFTWARE MOUNT/COATING FACEPLATE/ DISPLAY

POWER SUPPLY (redundant supply must be same type as main supply) PROCESS BUS MODULE DIGITAL INPUTS/OUTPUTS

INTER-RELAY COMMUNICATIONS (select a maximum of 1 per unit)

2-4

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION

2.1 INTRODUCTION

The order codes for the reduced size vertical mount units with the process bus module are shown below. Table 25: C30 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS)
BASE UNIT CPU C30 C30 * | E G H J K L M N ** | | | | | | | | | 00 01 03 04 - * | | | | | | | | | | | | | V B * | | | | | | | | | | | | | | | F D R A K M Q U L N T V * - F | | | | | | | | | | | | | | | | | | | | | | | | | | | H L ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX - H ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 81 - M ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX P/R ** | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | XX 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 2A 2B 2E 2F 2G 2H 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W Reduced Size Vertical Mount (see note regarding P/R slot below) Base Unit RS485 and RS485 RS485 and multi-mode ST 10Base-F RS485 and multi-mode ST redundant 10Base-F RS485 and multi-mode ST 100Base-FX RS485 and multi-mode ST redundant 100Base-FX RS485 and single mode SC 100Base-FX RS485 and single mode SC redundant 100Base-FX RS485 and 10/100Base-T No software options Ethernet Global Data (EGD); not available for Type E CPUs IEC 61850; not available for Type E CPUs Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs Vertical (3/4 rack) Vertical (3/4 rack) with harsh environmental coating English display French display Russian display Chinese display Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display Enhanced front panel with English display and user-programmable pushbuttons Enhanced front panel with French display and user-programmable pushbuttons Enhanced front panel with Russian display and user-programmable pushbuttons Enhanced front panel with Chinese display and user-programmable pushbuttons 125 / 250 V AC/DC power supply 24 to 48 V (DC only) power supply Eight-port digital process bus module No Module 4 Solid-State (no monitoring) MOSFET outputs 4 Solid-State (voltage with optional current) MOSFET outputs 4 Solid-State (current with optional voltage) MOSFET outputs 16 digital inputs with Auto-Burnishing 14 Form-A (no monitoring) Latching outputs 8 Form-A (no monitoring) outputs 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs 8 Form-C outputs 16 digital inputs 4 Form-C outputs, 8 digital inputs 8 Fast Form-C outputs 4 Form-A (voltage with optional current) outputs, 8 digital inputs 6 Form-A (voltage with optional current) outputs, 4 digital inputs 4 Form-C and 4 Fast Form-C outputs 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs 4 Form-A (current with optional voltage) outputs, 8 digital inputs 6 Form-A (current with optional voltage) outputs, 4 digital inputs 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs 4 Form-A (no monitoring) outputs, 8 digital inputs 6 Form-A (no monitoring) outputs, 4 digital inputs 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode Bi-phase, single channel Bi-phase, dual channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channel Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels

SOFTWARE

MOUNT/COATING FACEPLATE/ DISPLAY

POWER SUPPLY PROCESS BUS MODULE DIGITAL INPUTS/OUTPUTS

INTER-RELAY COMMUNICATIONS (select a maximum of 1 per unit) For the last module, slot P is used for digital and transducer input/output modules; slot R is used for inter-relay communications modules.

2.1.3 REPLACEMENT MODULES Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or faceplate, please provide the serial number of your existing unit. Not all replacement modules may be applicable to the C30 relay. Only the modules specified in the order codes are available as replacement modules.
NOTE

Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http:// www.GEindustrial.com/multilin/order.htm for the latest details concerning C30 ordering options.
NOTE

GE Multilin

C30 Controller System

2-5

2.1 INTRODUCTION The replacement module order codes for the horizontal mount units are shown below. Table 26: ORDER CODES FOR REPLACEMENT MODULES, HORIZONTAL UNITS
POWER SUPPLY (redundant supply only available in horizontal units; must be same type as main supply) CPU UR | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | ** 1H 1L RH RH 9E 9G 9H 9J 9K 9L 9M 9N 9S 3C 3D 3R 3A 3P 3G 3S 3B 3K 3M 3Q 3U 3L 3N 3T 3V 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 8F 8G 8H 8J 8L 8M 8N 8R 2A 2B 2E 2F 2G 2H 2S 2T 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W 5A 5C 5D 5E 5F * | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |

2 PRODUCT DESCRIPTION

2
FACEPLATE/DISPLAY

DIGITAL INPUTS AND OUTPUTS

CT/VT MODULES (NOT AVAILABLE FOR THE C30)

INTER-RELAY COMMUNICATIONS

TRANSDUCER INPUTS/OUTPUTS

125 / 250 V AC/DC 24 to 48 V (DC only) redundant 125 / 250 V AC/DC redundant 24 to 48 V (DC only) RS485 and RS485 (Modbus RTU, DNP 3.0) RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and Redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and multi-mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and single mode SC 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and 10/100Base-T RS485 and six-port managed Ethernet switch Horizontal faceplate with keypad and English display Horizontal faceplate with keypad and French display Horizontal faceplate with keypad and Russian display Horizontal faceplate with keypad and Chinese display Horizontal faceplate with keypad, user-programmable pushbuttons, and English display Horizontal faceplate with keypad, user-programmable pushbuttons, and French display Horizontal faceplate with keypad, user-programmable pushbuttons, and Russian display Horizontal faceplate with keypad, user-programmable pushbuttons, and Chinese display Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display Enhanced front panel with English display and user-programmable pushbuttons Enhanced front panel with French display and user-programmable pushbuttons Enhanced front panel with Russian display and user-programmable pushbuttons Enhanced front panel with Chinese display and user-programmable pushbuttons 4 Solid-State (no monitoring) MOSFET outputs 4 Solid-State (voltage with optional current) MOSFET outputs 4 Solid-State (current with optional voltage) MOSFET outputs 16 digital inputs with Auto-Burnishing 14 Form-A (no monitoring) Latching outputs 8 Form-A (no monitoring) outputs 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs 8 Form-C outputs 16 digital inputs 4 Form-C outputs, 8 digital inputs 8 Fast Form-C outputs 4 Form-A (voltage with optional current) outputs, 8 digital inputs 6 Form-A (voltage with optional current) outputs, 4 digital inputs 4 Form-C and 4 Fast Form-C outputs 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs 4 Form-A (current with optional voltage) outputs, 8 digital inputs 6 Form-A (current with optional voltage) outputs, 4 digital inputs 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs 4 Form-A (no monitoring) outputs, 8 digital inputs 6 Form-A (no monitoring) outputs, 4 digital inputs 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs Standard 4CT/4VT Sensitive Ground 4CT/4VT Standard 8CT Sensitive Ground 8CT Standard 4CT/4VT with enhanced diagnostics Sensitive Ground 4CT/4VT with enhanced diagnostics Standard 8CT with enhanced diagnostics Sensitive Ground 8CT with enhanced diagnostics C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode Bi-phase, single channel Bi-phase, dual channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels Six-port managed Ethernet switch with high voltage power supply (110 to 250 V DC / 100 to 240 V AC) Six-port managed Ethernet switch with low voltage power supply (48 V DC) 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channel Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER IEEE C37.94, 820 nm, multimode, LED, 1 Channel IEEE C37.94, 820 nm, multimode, LED, 2 Channels 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs

2-6

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION The replacement module order codes for the reduced-size vertical mount units are shown below. Table 27: ORDER CODES FOR REPLACEMENT MODULES, VERTICAL UNITS
POWER SUPPLY CPU UR | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | ** 1H 1L 9E 9G 9H 9J 9K 9L 9M 9N 3F 3D 3R 3K 3K 3M 3Q 3U 3L 3N 3T 3V 4A 4B 4C 4D 4L 67 6A 6B 6C 6D 6E 6F 6G 6H 6K 6L 6M 6N 6P 6R 6S 6T 6U 6V 8F 8G 8H 8J 8L 8M 8N 8R 2A 2B 2E 2F 2G 2H 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M 7N 7P 7Q 7R 7S 7T 7W 5A 5C 5D 5E 5F * | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 125 / 250 V AC/DC 24 to 48 V (DC only) RS485 and RS485 (Modbus RTU, DNP 3.0) RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and Redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and multi-mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and single mode SC 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0) RS485 and 10/100Base-T Vertical faceplate with keypad and English display Vertical faceplate with keypad and French display Vertical faceplate with keypad and Russian display Vertical faceplate with keypad and Chinese display Enhanced front panel with English display Enhanced front panel with French display Enhanced front panel with Russian display Enhanced front panel with Chinese display Enhanced front panel with English display and user-programmable pushbuttons Enhanced front panel with French display and user-programmable pushbuttons Enhanced front panel with Russian display and user-programmable pushbuttons Enhanced front panel with Chinese display and user-programmable pushbuttons 4 Solid-State (no monitoring) MOSFET outputs 4 Solid-State (voltage with optional current) MOSFET outputs 4 Solid-State (current with optional voltage) MOSFET outputs 16 digital inputs with Auto-Burnishing 14 Form-A (no monitoring) Latching outputs 8 Form-A (no monitoring) outputs 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs 8 Form-C outputs 16 digital inputs 4 Form-C outputs, 8 digital inputs 8 Fast Form-C outputs 4 Form-A (voltage with optional current) outputs, 8 digital inputs 6 Form-A (voltage with optional current) outputs, 4 digital inputs 4 Form-C and 4 Fast Form-C outputs 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs 4 Form-A (current with optional voltage) outputs, 8 digital inputs 6 Form-A (current with optional voltage) outputs, 4 digital inputs 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs 4 Form-A (no monitoring) outputs, 8 digital inputs 6 Form-A (no monitoring) outputs, 4 digital inputs 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs Standard 4CT/4VT Sensitive Ground 4CT/4VT Standard 8CT Sensitive Ground 8CT Standard 4CT/4VT with enhanced diagnostics Sensitive Ground 4CT/4VT with enhanced diagnostics Standard 8CT with enhanced diagnostics Sensitive Ground 8CT with enhanced diagnostics C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode Bi-phase, single channel Bi-phase, dual channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels 1550 nm, single-mode, LASER, 1 Channel 1550 nm, single-mode, LASER, 2 Channel Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels 820 nm, multi-mode, LED, 1 Channel 1300 nm, multi-mode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 Channels 1300 nm, multi-mode, LED, 2 Channels 1300 nm, single-mode, ELED, 2 Channels 1300 nm, single-mode, LASER, 2 Channels Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel RS422, 2 Channels 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed) 8 RTD inputs 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed) 4 dcmA inputs, 4 RTD inputs 8 dcmA inputs

2.1 INTRODUCTION

FACEPLATE/DISPLAY

DIGITAL INPUTS/OUTPUTS

CT/VT MODULES (NOT AVAILABLE FOR THE C30)

INTER-RELAY COMMUNICATIONS

TRANSDUCER INPUTS/OUTPUTS

GE Multilin

C30 Controller System

2-7

2.2 SPECIFICATIONS

2 PRODUCT DESCRIPTION

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE 2.2.1 USER-PROGRAMMABLE ELEMENTS FLEXLOGIC
Programming language: Reverse Polish Notation with graphical visualization (keypad programmable)

LED TEST
Initiation: Number of tests: Duration of full test: Test sequence 1: Test sequence 2: Test sequence 3: Number of displays: Lines of display: Parameters: Invoking and scrolling: from any digital input or user-programmable condition 3, interruptible at any time approximately 3 minutes all LEDs on all LEDs off, one LED at a time on for 1 s all LEDs on, one LED at a time off for 1 s 16 2 20 alphanumeric characters up to 5, any Modbus register addresses keypad, or any user-programmable condition, including pushbuttons

Lines of code: Internal variables: Supported operations:

512 64 NOT, XOR, OR (2 to 16 inputs), AND (2 to 16 inputs), NOR (2 to 16 inputs), NAND (2 to 16 inputs), latch (reset-dominant), edge detectors, timers any logical variable, contact, or virtual input 32 0 to 60000 (ms, sec., min.) in steps of 1 0 to 60000 (ms, sec., min.) in steps of 1 4 (A through D) 40 (0 through 1 of pickup) 80 (1 through 20 of pickup) 0 to 65535 ms in steps of 1 up to 256 logical variables grouped under 16 Modbus addresses any logical variable, contact, or virtual input 8 any analog actual value, or two values in differential mode level, delta over, under 90.000 to 90.000 pu in steps of 0.001 0.1 to 50.0% in steps of 0.1 20 ms to 60 days

Inputs: Number of timers: Pickup delay: Dropout delay:

USER-DEFINABLE DISPLAYS

FLEXCURVES
Number: Reset points: Operate points: Time delay:

CONTROL PUSHBUTTONS
Number of pushbuttons: 7 Operation: drive FlexLogic operands

USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL)


Number of pushbuttons: 12 (standard faceplate); 16 (enhanced faceplate) Mode: Display message: Drop-out timer: Autoreset timer: Hold timer: self-reset, latched 2 lines of 20 characters each 0.00 to 60.00 s in steps of 0.05 0.2 to 600.0 s in steps of 0.1 0.0 to 10.0 s in steps of 0.1 2 1 to 7 in steps of 1 time-out or acknowledge 3.0 to 60.0 s in steps of 0.1 step-up and 3-bit restore from non-volatile memory or synchronize to a 3-bit control input or synch/ restore mode 6 two 8-bit integers via FlexLogic operands any FlexLogic operand < 8 ms at 60 Hz, < 10 ms at 50 Hz 48 any FlexLogic operand 0.000 to 999999.999 s in steps of 0.001 0.000 to 999999.999 s in steps of 0.001 3% or 4 ms, whichever is greater

FLEX STATES
Number: Programmability:

FLEXELEMENTS
Number of elements: Operating signal:

SELECTOR SWITCH
Number of elements: Upper position limit: Selecting mode: Time-out timer: Control inputs: Power-up mode:

Operating signal mode: signed or absolute value Operating mode: Comparator direction: Pickup Level: Hysteresis: Delta dt:

Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001

NON-VOLATILE LATCHES
Type: Number: Output: Execution sequence: set-dominant or reset-dominant 16 (individually programmed) stored in non-volatile memory as input prior to protection, control, and FlexLogic 48 plus trip and alarm from any logical variable, contact, or virtual input self-reset or latched

8-BIT SWITCH
Number of elements: Input signals: Control signal: Response time:

USER-PROGRAMMABLE LEDs
Number: Programmability: Reset mode:

DIGITAL ELEMENTS
Number of elements: Operating signal: Pickup delay: Dropout delay: Timing accuracy:

2-8

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION

2.2 SPECIFICATIONS 2.2.2 MONITORING

OSCILLOGRAPHY
Maximum records: Sampling rate: Triggers: 64 64 samples per power cycle any element pickup, dropout, or operate; digital input change of state; digital output change of state; FlexLogic equation AC input channels; element state; digital input state; digital output state in non-volatile memory 1024 events to 1 microsecond any element pickup, dropout, or operate; digital input change of state; digital output change of state; self-test events in non-volatile memory

DATA LOGGER
Number of channels: Parameters: Sampling rate: Trigger: Mode: Storage capacity: 1 to 16 any available analog actual value 15 to 3600000 ms in steps of 1 any FlexLogic operand continuous or triggered (NN is dependent on memory) 1-second rate: 01 channel for NN days 16 channels for NN days 60-minute rate: 01 channel for NN days 16 channels for NN days

Data: Data storage:

EVENT RECORDER
Capacity: Time-tag: Triggers:

Data storage:

2.2.3 INPUTS CONTACT INPUTS


Dry contacts: Wet contacts: Selectable thresholds: Tolerance: Recognition time: Debounce time: 1000 maximum 300 V DC maximum 17 V, 33 V, 84 V, 166 V 10% < 1 ms 0.0 to 16.0 ms in steps of 0.5 Sensing current: Range: Accuracy: Isolation:

RTD INPUTS
Types (3-wire): 100 Platinum, 100 & 120 Nickel, 10 Copper 5 mA 50 to +250C 2C 36 V pk-pk 1 to 10 V pk-pk TTL 22 k 2 kV

Contacts per common return: 4

IRIG-B INPUT
Amplitude modulation: DC shift: Input impedance: Isolation:

Continuous current draw:3 mA (when energized)

CONTACT INPUTS WITH AUTO-BURNISHING


Dry contacts: Wet contacts: Selectable thresholds: Tolerance: Recognition time: Debounce time: 1000 maximum 300 V DC maximum 17 V, 33 V, 84 V, 166 V 10% < 1 ms 0.0 to 16.0 ms in steps of 0.5

REMOTE INPUTS (IEC 61850 GSSE/GOOSE)


Number of input points: 64, configured from 64 incoming bit pairs Number of remote devices: 32 Default states on loss of comms.: On, Off, Latest/Off, Latest/On Number of remote DPS inputs: 5

Contacts per common return: 2

Continuous current draw:3 mA (when energized) Auto-burnish impulse current: 50 to 70 mA Duration of auto-burnish impulse: 25 to 50 ms

DIRECT INPUTS
Number of input points: 32 No. of remote devices: Ring configuration: Data rate: CRC: 16 Yes, No 64 or 128 kbps 32-bit Default states on loss of comms.: On, Off, Latest/Off, Latest/On

DCMA INPUTS
Current input (mA DC): Input impedance: Conversion range: Accuracy: Type: 0 to 1, 0 to +1, 1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable) 379 10% 1 to + 20 mA DC 0.2% of full scale Passive

CRC alarm: Responding to: Rate of messages failing the CRC Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1 Unreturned message alarm: Responding to: Rate of unreturned messages in the ring configuration Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1

GE Multilin

C30 Controller System

2-9

2.2 SPECIFICATIONS TELEPROTECTION


Number of input points: 16 No. of remote devices: Ring configuration: Data rate: CRC: 3 No 64 or 128 kbps 32-bit Default states on loss of comms.: On, Off, Latest/Off, Latest/On

2 PRODUCT DESCRIPTION

2.2.4 POWER SUPPLY LOW RANGE


Nominal DC voltage: Minimum DC voltage: Maximum DC voltage: Voltage loss hold-up: 24 to 48 V 20 V 60 V 20 ms duration at nominal

ALL RANGES
Volt withstand: Power consumption: 2 Highest Nominal Voltage for 10 ms typical = 15 to 20 W/VA maximum = 50 W/VA contact factory for exact order code consumption

NOTE: Low range is DC only.

HIGH RANGE
Nominal DC voltage: Minimum DC voltage: Maximum DC voltage: Nominal AC voltage: Minimum AC voltage: Maximum AC voltage: Voltage loss hold-up: 125 to 250 V 88 V 300 V 100 to 240 V at 50/60 Hz 88 V at 25 to 100 Hz 265 V at 25 to 100 Hz 200 ms duration at nominal

INTERNAL FUSE RATINGS


Low range power supply: 8 A / 250 V High range power supply: 4 A / 250 V

INTERRUPTING CAPACITY
AC: DC: 100 000 A RMS symmetrical 10 000 A

2.2.5 OUTPUTS FORM-A RELAY


Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous:
VOLTAGE
24 V 48 V 125 V 250 V

FORM-C AND CRITICAL FAILURE RELAY


Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous:
VOLTAGE
24 V 48 V 125 V 250 V

6A
CURRENT
1A 0.5 A 0.3 A 0.2 A

8A
CURRENT
1A 0.5 A 0.3 A 0.2 A

Break (DC inductive, L/R = 40 ms):

Break (DC inductive, L/R = 40 ms):

Operate time: Contact material:

< 4 ms silver alloy

Operate time: Contact material: Make and carry:


INPUT VOLTAGE 250 V DC 120 V DC 48 V DC 24 V DC

< 8 ms silver alloy 0.1 A max. (resistive load)


IMPEDANCE 2 W RESISTOR 20 K 5 K 2 K 2 K 1 W RESISTOR 50 K 2 K 2 K 2 K

LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: Break at L/R of 40 ms: Operate time: Contact material: Control: Control mode: Applicable voltage: Trickle current: Threshold current: 6A 0.25 A DC max. < 4 ms silver alloy separate operate and reset inputs operate-dominant or reset-dominant approx. 15 to 250 V DC approx. 1 to 2.5 mA approx. 80 to 100 mA

FAST FORM-C RELAY


Minimum load impedance:

FORM-A VOLTAGE MONITOR

Note: values for 24 V and 48 V are the same due to a required 95% voltage drop across the load impedance.

Operate time:

< 0.6 ms

FORM-A CURRENT MONITOR

Internal Limiting Resistor: 100 , 2 W

2-10

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION SOLID-STATE OUTPUT RELAY


Operate and release time: <100 s Maximum voltage: Make and carry: for 0.2 s: for 0.03 s Breaking capacity:
UL508 Utility application (autoreclose scheme) 5 ops / 0.2 s-On, 0.2 s-Off within 1 minute Industrial application

2.2 SPECIFICATIONS DIRECT OUTPUTS


Output points: 32 1 to 1 mA, 0 to 1 mA, 4 to 20 mA 12 k for 1 to 1 mA range 12 k for 0 to 1 mA range 600 for 4 to 20 mA range 0.75% of full-scale for 0 to 1 mA range 0.5% of full-scale for 1 to 1 mA range 0.75% of full-scale for 0 to 20 mA range 1.5 kV any FlexAnalog quantity

265 V DC

DCMA OUTPUTS
Range: Max. load resistance:

Maximum continuous current: 5 A at 45C; 4 A at 65C 30 A as per ANSI C37.90 300 A

Accuracy:

99% Settling time to a step change: 100 ms Isolation:


10000 ops / 0.2 s-On, 30 s-Off

Operations/ interval

5000 ops / 1 s-On, 9 s-Off 1000 ops / 0.5 s-On, 0.5 s-Off

Driving signal:

Upper and lower limit for the driving signal: 90 to 90 pu in steps of 0.001

Break capability (0 to 250 V DC)

3.2 A L/R = 10 ms 1.6 A L/R = 20 ms 0.8 A L/R = 40 ms 10 A L/R = 40 ms 10 A L/R = 40 ms

ETHERNET SWITCH (HIGH VOLTAGE, TYPE 2S)


Nominal DC voltage: Minimum DC voltage: Maximum DC voltage: Input Current: Nominal AC voltage: 110 to 240 V DC 88 V DC 300 V DC 0.9 A DC maximum 100 to 240 V AC, 0.26 to 0.16 A/26 to 39 VA at 50/60 Hz 85 V AC, 0.31 A/22 VA at 50/60 Hz 265 V AC, 0.16 A/42 VA at 50/60 Hz 3 A / 350 V AC, Ceramic, Axial SLO BLO; Manufacturer: Conquer; Part number: SCD-A 003 48 V DC, 0.31 A/15 W 30 V DC, 0.43 A/16 W 60 V DC 5 A / 350 V AC, Ceramic, Axial SLO BLO; Manufacturer: Conquer; Part number: SCD-A 005

IRIG-B OUTPUT
Amplitude: Maximum load: Time delay: Isolation: 10 V peak-peak RS485 level 100 ohms 1 ms for AM input 40 s for DC-shift input 2 kV

Minimum AC voltage: Maximum AC voltage: Internal fuse:

CONTROL POWER EXTERNAL OUTPUT (FOR DRY CONTACT INPUT)


Capacity: Isolation: 100 mA DC at 48 V DC 300 Vpk

ETHERNET SWITCH (LOW VOLTAGE, TYPE 2T)


Nominal voltage: Minimum voltage: Maximum voltage: Internal fuse:

REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)


Standard output points: 32 User output points: 32

GE Multilin

C30 Controller System

2-11

2.2 SPECIFICATIONS

2 PRODUCT DESCRIPTION 2.2.6 COMMUNICATIONS

RS232
Front port: 19.2 kbps, Modbus RTU Up to 115 kbps, Modbus RTU, isolated together at 36 Vpk 1200 m 2 kV

ETHERNET SWITCH FIBER OPTIC PORTS


Maximum fiber segment length calculation: The maximum fiber segment length between two adjacent switches or between a switch and a device is calculated as follows. First, calculate the optical power budget (OPB) of each device using the manufacturers data sheets. OPB = P T ( MIN ) P R ( MIN ) where OPB = optical power budget, PT = transmitter output power, and PR = receiver sensitivity.
FIBER TYPE 10MB MULTIMODE 100MB MULTI- 100MB SINGLEMODE MODE 1310 nm ST 20 dBm 30 dBm 10 dB 14 dBm 2 km full/half yes 1310 nm SC 15 dBm 30 dBm 15 dB 7 dBm 15 km full/half yes

RS485
1 or 2 rear ports:

Typical distance: Isolation:

ETHERNET (FIBER)
PARAMETER

Wavelength Connector Transmit power Receiver sensitivity Power budget Maximum input power Typical distance Duplex Redundancy

820 nm ST 20 dBm 30 dBm 10 dB 7.6 dBm 1.65 km full/half yes

The worst case optical power budget (OPBWORST) is then calculated by taking the lower of the two calculated power budgets, subtracting 1 dB for LED aging, and then subtracting the total insertion loss. The total insertion loss is calculated by multiplying the number of connectors in each single fiber path by 0.5 dB. For example, with a single fiber cable between the two devices, there will be a minimum of two connections in either transmit or receive fiber paths for a total insertion loss of 1db for either direction: Total insertion loss = number of connectors 0.5 dB = 2 0.5 dB = 1.0 dB The worst-case optical power budget between two type 2T or 2S modules using a single fiber cable is: OPB WORST = OPB 1 dB (LED aging) total insertion loss 10dB 1dB 1dB = 8dB To calculate the maximum fiber length, divide the worst-case optical power budget by the cable attenuation per unit distance specified in the manufacturer data sheets. For example, typical attenuation for 62.5/125 m glass fiber optic cable is approximately 2.8 dB per km. In our example, this would result in the following maximum fiber length: OPB WORST (in dB) Maximum fiber length = -----------------------------------------------------cable loss (in dB/km) 8 dB = -------------------------- = 2.8km 2.8 dB/km The customer must use the attenuation specified within the manufacturer data sheets for accurate calculation of the maximum fiber length.

The UR-2S and UR-2T only support 100 Mb multimode

ETHERNET (10/100 MB TWISTED PAIR)


Modes: Connector: 10 MB, 10/100 MB (auto-detect) RJ45

SNTP clock synchronization error: <10 ms (typical)

ETHERNET SWITCH 10/100BASE-T PORTS


Connector type: RJ45 MAXIMUM 10 MBPS ETHERNET SEGMENT LENGTHS Unshielded twisted pair: 100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS 10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.) 100Base-TX (CAT 5 UTP):100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.)

2-12

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION

2.2 SPECIFICATIONS 2.2.7 INTER-RELAY COMMUNICATIONS

SHIELDED TWISTED-PAIR INTERFACE OPTIONS


INTERFACE TYPE RS422 G.703 TYPICAL DISTANCE 1200 m 100 m

TYPICAL LINK DISTANCE


EMITTER TYPE 820 nm LED, multimode 1300 nm LED, multimode 1300 nm ELED, single mode 1300 nm Laser, single mode 1550 nm Laser, single-mode CABLE TYPE 62.5/125 m 62.5/125 m 9/125 m 9/125 m 9/125 m CONNECTOR TYPE ST ST ST ST ST TYPICAL DISTANCE 1.65 km 3.8 km 11.4 km 64 km 105 km

NOTE

RS422 distance is based on transmitter power and does not take into consideration the clock source provided by the user.

LINK POWER BUDGET


EMITTER, FIBER TYPE 820 nm LED, Multimode 1300 nm LED, Multimode 1300 nm ELED, Singlemode 1300 nm Laser, Singlemode 1550 nm Laser, Singlemode TRANSMIT POWER 20 dBm 21 dBm 23 dBm 1 dBm +5 dBm RECEIVED SENSITIVITY 30 dBm 30 dBm 32 dBm 30 dBm 30 dBm POWER BUDGET 10 dB 9 dB 9 dB 29 dB 35 dB

NOTE

Typical distances listed are based on the following assumptions for system loss. As actual losses will vary from one installation to another, the distance covered by your system may vary.
2 dB 3 dB/km 1 dB/km 0.35 dB/km 0.25 dB/km One splice every 2 km, at 0.05 dB loss per splice.

CONNECTOR LOSSES (TOTAL OF BOTH ENDS)


ST connector

NOTE

These power budgets are calculated from the manufacturers worst-case transmitter power and worst case receiver sensitivity. The power budgets for the 1300nm ELED are calculated from the manufacturer's transmitter power and receiver sensitivity at ambient temperature. At extreme temperatures these values will deviate based on component tolerance. On average, the output power will decrease as the temperature is increased by a factor 1dB / 5C.

FIBER LOSSES
820 nm multimode 1300 nm multimode 1300 nm singlemode 1550 nm singlemode Splice losses:

NOTE

SYSTEM MARGIN
3 dB additional loss added to calculations to compensate for all other losses. Compensated difference in transmitting and receiving (channel asymmetry) channel delays using GPS satellite clock: 10 ms

MAXIMUM OPTICAL INPUT POWER


EMITTER, FIBER TYPE 820 nm LED, Multimode 1300 nm LED, Multimode 1300 nm ELED, Singlemode 1300 nm Laser, Singlemode 1550 nm Laser, Singlemode MAX. OPTICAL INPUT POWER 7.6 dBm 11 dBm 14 dBm 14 dBm 14 dBm

2.2.8 ENVIRONMENTAL AMBIENT TEMPERATURES


Storage temperature: 40 to 85C Operating temperature: 40 to 60C; the LCD contrast may be impaired at temperatures less than 20C

OTHER
Altitude: Pollution degree: Overvoltage category: Ingress protection: 2000 m (maximum) II II IP20 front, IP10 back

HUMIDITY
Humidity: operating up to 95% (non-condensing) at 55C (as per IEC60068-2-30 variant 1, 6days).

GE Multilin

C30 Controller System

2-13

2.2 SPECIFICATIONS

2 PRODUCT DESCRIPTION 2.2.9 TYPE TESTS

C30 TYPE TESTS


TEST Dielectric voltage withstand Impulse voltage withstand REFERENCE STANDARD EN60255-5 EN60255-5 IEC61000-4-18 / IEC60255-22-1 EN61000-4-2 / IEC60255-22-2 EN61000-4-3 / IEC60255-22-3 EN61000-4-4 / IEC60255-22-4 EN61000-4-5 / IEC60255-22-5 EN61000-4-6 / IEC60255-22-6 EN61000-4-7 / IEC60255-22-7 IEC60255-11 CISPR11 / CISPR22 / IEC60255-25 IEC60255-21-1 IEC60255-21-2 IEC60255-21-3 IEC61000-4-8 IEC61000-4-9 IEC61000-4-10 IEC61000-4-11 IEC61000-4-12 IEC61000-4-16 IEC61000-4-17 IEC60529 IEC60068-2-1 IEC60068-2-2 IEC60068-2-30 IEEE/ANSI C37.90.1 IEEE/ANSI C37.90.2 UL508 UL C22.2-14 UL1053 TEST LEVEL 2.3 kV 5 kV 2.5 kV CM, 1 kV DM Level 3 Level 3 Class A and B Level 3 and 4 Level 3 Class A and B 12% ripple, 200 ms interrupts Class A Class 1 Class 1 Class 1 Level 5 Level 4 Level 4 0, 40, 70, 80% dips; 250 / 300 cycle interrupts 2.5 kV CM, 1 kV DM Level 4 15% ripple IP40 front, IP10 back 40C for 16 hours 85C for 16 hours 6 days, variant 1 2.5 kV, 1 MHz 20 V/m, 80 MHz to 1 GHz e83849 NKCR e83849 NKCR7 e83849 NKCR

Damped oscillatory Electrostatic discharge RF immunity Fast transient disturbance Surge immunity Conducted RF immunity Power frequency immunity Voltage interruption and ripple DC Radiated and conducted emissions Sinusoidal vibration Shock and bump Seismic Power magnetic immunity Pulse magnetic immunity Damped magnetic immunity Voltage dip and interruption Damped oscillatory Conducted RF immunity, 0 to 150 kHz Voltage ripple Ingress protection Cold Hot Humidity Damped oscillatory RF immunity Safety Safety Safety

2.2.10 PRODUCTION TESTS THERMAL


Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process.

2-14

C30 Controller System

GE Multilin

2 PRODUCT DESCRIPTION

2.2 SPECIFICATIONS 2.2.11 APPROVALS

APPROVALS
COMPLIANCE CE compliance APPLICABLE COUNCIL DIRECTIVE Low voltage directive EMC directive North America ------ACCORDING TO EN60255-5 EN60255-26 / EN50263 EN61000-6-5 UL508 UL1053 C22.2 No. 14

2.2.12 MAINTENANCE MOUNTING


Attach mounting brackets using 20 inch-pounds (2 inch-pounds) of torque.

CLEANING
Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used. Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration of electrolytic capacitors.

NOTE

GE Multilin

C30 Controller System

2-15

2.2 SPECIFICATIONS

2 PRODUCT DESCRIPTION

2-16

C30 Controller System

GE Multilin

3 HARDWARE 3 HARDWARE 3.1DESCRIPTION a) HORIZONTAL UNITS

3.1 DESCRIPTION 3.1.1 PANEL CUTOUT

The C30 Controller System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional userprogrammable pushbuttons and LED indicators. The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access the keypad or RS232 communications port. The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment. The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay.

11.016 [279,81 mm] 9.687 [246,05 mm]

17.56 [446,02 mm]

7.460 [189,48 mm] 6.995 [177,67 mm] 6.960 [176,78 mm]

19.040 [483,62 mm]


842807A1.CDR

Figure 31: C30 HORIZONTAL DIMENSIONS (ENHANCED PANEL)

GE Multilin

C30 Controller System

3-1

3.1 DESCRIPTION

3 HARDWARE

18.370 [466,60 mm] 0.280 [7,11 mm] Typ. x 4 CUT-OUT

4.000 [101,60 mm]

17.750 [450,85 mm]

842808A1.CDR

Figure 32: C30 HORIZONTAL MOUNTING (ENHANCED PANEL)

Figure 33: C30 HORIZONTAL MOUNTING AND DIMENSIONS (STANDARD PANEL) b) VERTICAL UNITS The C30 Controller System is available as a reduced size () vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators. The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access the keypad or RS232 communications port. The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent equipment.

3-2

C30 Controller System

GE Multilin

3 HARDWARE

3.1 DESCRIPTION

The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay.
7.482 11.015 1.329

15.000

14.025

13.560

4.000

9.780

843809A1.CDR

Figure 34: C30 VERTICAL DIMENSIONS (ENHANCED PANEL)

GE Multilin

C30 Controller System

3-3

3.1 DESCRIPTION

3 HARDWARE

UR SERIES

Figure 35: C30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For details on side mounting C30 devices with the enhanced front panel, refer to the following documents available online from the GE Multilin website. GEK-113180: UR-series UR-V side-mounting front panel assembly instructions. GEK-113181: Connecting the side-mounted UR-V enhanced front panel to a vertical UR-series device. GEK-113182: Connecting the side-mounted UR-V enhanced front panel to a vertically-mounted horizontal UR-series device.

For details on side mounting C30 devices with the standard front panel, refer to the figures below.

3-4

C30 Controller System

GE Multilin

3 HARDWARE

3.1 DESCRIPTION

Figure 36: C30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL)

GE Multilin

C30 Controller System

3-5

3.1 DESCRIPTION

3 HARDWARE

Figure 37: C30 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL) 3.1.2 MODULE WITHDRAWAL AND INSERTION Module withdrawal and insertion may only be performed when control power has been removed from the unit. Inserting an incorrect module type into a slot may result in personal injury, damage to the unit or connected equipment, or undesired operation! Proper electrostatic discharge protection (for example, a static strap) must be used when coming in contact with modules while the relay is energized!
WARNING

WARNING

The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced with like modules in their original factory configured slots. The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the C30.

3-6

C30 Controller System

GE Multilin

3 HARDWARE

3.1 DESCRIPTION

842812A1.CDR

Figure 38: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE) The standard faceplate can be opened to the left, once the sliding latch on the right side has been pushed up, as shown below. This allows for easy accessibility of the modules for withdrawal.

Figure 39: UR MODULE WITHDRAWAL AND INSERTION (STANDARD FACEPLATE) To properly remove a module, the ejector/inserter clips, located at the top and bottom of each module, must be pulled simultaneously. Before performing this action, control power must be removed from the relay. Record the original location of the module to ensure that the same or replacement module is inserted into the correct slot. Modules with current input provide automatic shorting of external CT circuits. To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/ inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These connectors must be individually disconnected from the module before it can be removed from the chassis.
NOTE

GE Multilin

C30 Controller System

3-7

3.1 DESCRIPTION

3 HARDWARE

The 4.0x release of the C30 relay includes new hardware modules.The new CPU modules are specified with codes 9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
NOTE

All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are only compatible with the new hardware modules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older hardware modules. 3.1.3 REAR TERMINAL LAYOUT

C30
Technical Support: Tel: (905) 294-6222 Fax: (905) 201-2098

Controller
GE Multilin

RATINGS:
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA Contact Inputs: 300V DC Max 10mA Contact Outputs: Standard Pilot Duty / 250V AC 7.5A 360V A Resistive / 125V DC Break 4A @ L/R = 40mS / 300W
Made in Canada

Model: Mods: Wiring Diagram: Inst. Manual: Serial Number: Firmware: Mfg. Date:

C30D00HCHF8AH6AM6BP8BX7A 000 ZZZZZZ D MAZB98000029 D 1998/01/05

http://www.GEIndustrial.com/Multilin

K
c

J
b a

H
c

G
b a

b
Tx1

a 1 2
CH1

b 1 2
Tx1

a 1 2 3 4 5 6 7 8

1 2

Rx1

3
Tx1

3 4
CH1 Tx Rx CH2

3 4 5 6

Rx1

Tx2

Rx2

IN

Tx2

7 8

Tx2

OUT

Rx2

Optional Ethernet switch

Optional direct input/output module

Optional Optional contact contact input/output input/output module module

CPU module (Ethernet not available when ordered with Ethernet switch)

CH2

Power supply module


834720A3.CDR

Figure 310: REAR TERMINAL VIEW Do not touch any rear terminals while the relay is energized!
WARNING

The relay follows a convention with respect to terminal number assignments which are three characters long assigned in order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following figure for an example of rear terminal assignments.

3-8

C30 Controller System

GE Multilin

3 HARDWARE

3.1 DESCRIPTION

Figure 311: EXAMPLE OF MODULES IN F AND H SLOTS

GE Multilin

C30 Controller System

3-9

3.2 WIRING 3.2WIRING

3 HARDWARE 3.2.1 TYPICAL WIRING

NOTE: This diagram is based on the following order code: C30-H00-HCH-F6B-H6E-M6G-P6K-U6D-W6D This diagram provides an example of how the device is wired, not specifically how to wire the device. Please refer to the Instruction Manual for additional details on wiring based on various configurations.

W1a W1c W2a W2c W1b


W3a W3c W4a W4c W3b

CONTACT INPUT W1a CONTACT INPUT W1c CONTACT INPUT W2a CONTACT INPUT W2c COMMON W1b CONTACT INPUT W3a CONTACT INPUT W3c CONTACT INPUT W4a CONTACT INPUT W4c COMMON W3b CONTACT INPUT W5a CONTACT INPUT W5c CONTACT INPUT W6a CONTACT INPUT W6c COMMON W5b CONTACT INPUT W7a CONTACT INPUT W7c CONTACT INPUT W8a CONTACT INPUT W8c COMMON W7b SURGE

CONTACT INPUT 1a CONTACT INPUT 1c CONTACT INPUT 2a CONTACT INPUT U2c COMMON U1b CONTACT INPUT U3a CONTACT INPUT U3c CONTACT INPUT U4a CONTACT INPUT U4c COMMON U3b CONTACT INPUT U5a CONTACT INPUT U5c CONTACT INPUT U6a CONTACT INPUT U6c COMMON U5b CONTACT INPUT U7a CONTACT INPUT U7c CONTACT INPUT U8a CONTACT INPUT U8c COMMON U7b SURGE P1

U1a U1c U2a U2c U1b


U3a U3c U4a U4c U3b

6D

DIGITAL INPUTS/OUTPUTS

DIGITAL INPUTS/OUTPUTS

VOLTAGE AND CURRENT SUPERVISION

H7a H7c H8a H8c H7b


H8b

CONTACT INPUT H7a CONTACT INPUT H7c CONTACT INPUT H8a CONTACT INPUT H8c COMMON H7b SURGE
I

DIGITAL INPUTS/OUTPUTS

H1a H1b H1c H2a H2b H2c H3a H3b H3c H4a H4b H4c H5a H5c H6a H6c H5b

H1

6E

6K

W7a W7c W8a W8c W7b W8b

GE Consumer & Industrial Multilin

DIGITAL INPUTS/OUTPUTS

W5a W5c W6a W6c W5b

6D

U5a U5c U6a U6c U5b U7a U7c U8a U8c U7b U8b
P1a P1b P1c P2a P2b P2c P3a P3b P3c P4a P4b P4c P5a P5b P5c P6a P6b P6c P7a P7b P7c P8a P8b P8c M1a M1b M1c M2a M2b M2c M3a M3b M3c M4a M4b M4c M5a M5c M6a M6c M5b

C30 CONTROLLER

H2

P2

H3

P3

H4 CONTACT INPUT H5a CONTACT INPUT H5c CONTACT INPUT H6a CONTACT INPUT H6c COMMON H5b

P4

P5

P6

P7

P8

6G

6B

TC 1

VOLTAGE SUPERVISION

H2

M2

V I

TC 2

H3

M3

V I

H4

M4

H5

DIGITAL INPUTS/OUTPUTS

H6 CONTACT INPUT H7a CONTACT INPUT H7c CONTACT INPUT H8a CONTACT INPUT H8c COMMON H7b SURGE

DIGITAL INPUTS/OUTPUTS

CONTACT INPUT M5a CONTACT INPUT M5c CONTACT INPUT M6a CONTACT INPUT M6c COMMON M5b CONTACT INPUT M7a CONTACT INPUT M7c CONTACT INPUT M8a CONTACT INPUT M8c COMMON M7b SURGE

( DC ONLY )

H8b

DC

AC or DC

B 1b B 1a B 2b B 3a B 3b B5b HI B 6b LO B 6a B 8a B 8b

CRITICAL FAILURE 48 VDC OUTPUT CONTROL POWER SURGE FILTER

POWER SUPPLY

Fibre Optic

Tx1 10BaseFL

RS-232
NORMAL ALTERNATE COM 1

Rx1
Tx2

DB-9
9H

10BaseFL
Rx2

(front)

Ground at Remote Device

Shielded twisted pairs

10BaseT

Co-axial * Co-axial Co-axial

D1a D2a D3a D4b D4a

RS485 COM 2
com

CONTACTS SHOWN WITH NO CONTROL POWER

IRIG-B Input

BNC BNC
No. 10AWG Minimum GROUND BUS

IRIG-B Output

Co-axial * - For IRIG-B Input only use one terminal as input

CPU

834721A4.CDR
MODULE ARRANGEMENT

MODULES MUST BE GROUNDED IF TERMINAL IS PROVIDED

D
9 CPU

B
1 Power Supply

Input/ Input/ output output


* Optional

Input/ Input/ output output

*
(Rear View)

6 6 Input/ Input/ output output

Figure 312: TYPICAL WIRING DIAGRAM

3-10

C30 Controller System

H1a H1b H1c H2a H2b H2c H3a H3b H3c H4a H4b H4c H5a H5b H5c H6a H6b H6c H7a H7c H8a H8c H7b

H1

M1

M7a M7c M8a M8c M7b


M8b
UR TXD RXD COMPUTER

SGND

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

8 3 RXD 2 TXD 20 7 SGND 6 4 5 22


25 PIN CONNECTOR

9 PIN CONNECTOR

GE Multilin

3 HARDWARE

3.2 WIRING 3.2.2 DIELECTRIC STRENGTH

The dielectric strength of the UR-series module hardware is shown in the following table: Table 31: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE TYPE 1 1 1 2 3 4 5 6 7 9 MODULE FUNCTION FROM Power supply Power supply Power supply Reserved Reserved Reserved Analog inputs/outputs Digital inputs/outputs G.703 RS422 CPU High (+); Low (+); () 48 V DC (+) and () Relay terminals N/A N/A N/A All except 8b All All except 2b, 3a, 7b, 8a All except 6a, 7b, 8a All TERMINALS TO Chassis Chassis Chassis N/A N/A N/A Chassis Chassis Chassis Chassis Chassis DIELECTRIC STRENGTH (AC) 2000 V AC for 1 minute 2000 V AC for 1 minute 2000 V AC for 1 minute N/A N/A N/A < 50 V DC 2000 V AC for 1 minute 2000 V AC for 1 minute < 50 V DC 2000 V AC for 1 minute

Filter networks and transient protection clamps are used in the hardware to prevent damage caused by high peak voltage transients, radio frequency interference (RFI), and electromagnetic interference (EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one minute. 3.2.3 CONTROL POWER CONTROL POWER SUPPLIED TO THE RELAY MUST BE CONNECTED TO THE MATCHING POWER SUPPLY RANGE OF THE RELAY. IF THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY OCCUR! The C30 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be avoided by powering the relays up once a year.

CAUTION

NOTE

The power supply module can be ordered for two possible voltage ranges, with or without a redundant power option. Each range has a dedicated input connection for proper operation. The ranges are as shown below (see the Technical specifications section of chapter 2 for additional details): Low (LO) range: 24 to 48 V (DC only) nominal. High (HI) range: 125 to 250 V nominal.

The power supply module provides power to the relay and supplies power for dry contact input connections. The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the Typical wiring diagram earlier). The critical failure relay is a form-C device that will be energized once control power is applied and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks detect a critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize. For high reliability systems, the C30 has a redundant option in which two C30 power supplies are placed in parallel on the bus. If one of the power supplies become faulted, the second power supply will assume the full load of the relay without any interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay of the module will also indicate a faulted power supply. An LED on the front of the control power module shows the status of the power supply:
LED INDICATION CONTINUOUS ON ON / OFF CYCLING OFF POWER SUPPLY OK Failure Failure

GE Multilin

C30 Controller System

3-11

3.2 WIRING

3 HARDWARE

AC or DC

NOTE: 14 gauge stranded wire with suitable disconnect devices is recommended.

AC or DC

Heavy copper conductor or braided wire

3
Switchgear ground bus

FILTER SURGE

LOW

HIGH

GND

B8b B8a B6a B6b B5b


CONTROL POWER

OPTIONAL ETHERNET SWITCH

UR-series protection system

827759AA.CDR

Figure 313: CONTROL POWER CONNECTION 3.2.4 PROCESS BUS MODULES The C30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applications, including protection functions, FlexLogic, metering, and communications. The IEC 61850 process bus system offers the following benefits. Drastically reduces labor associated with design, installation, and testing of protection and control applications using the C30 by reducing the number of individual copper terminations. Integrates seamlessly with existing C30 applications, since the IEC 61850 process bus interface module replaces the traditional CT/VT modules. Communicates using open standard IEC 61850 messaging.

For additional details on the HardFiber system, refer to GE publication GEK-113500: HardFiber System Instruction Manual. 3.2.5 CONTACT INPUTS AND OUTPUTS Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs, the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A output, there are options of using current or voltage detection for feature supervision, depending on the module ordered. The terminal configuration for contact inputs is different for the two applications. The contact inputs are grouped with a common return. The C30 has two versions of grouping: four inputs per common return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used. The four inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs sharing one common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D module). The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot position and row number. However, since there are two contact inputs per row, these names are assigned by module slot position, row number, and column position.

3-12

C30 Controller System

GE Multilin

3 HARDWARE

3.2 WIRING

Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open, and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose output is set to logic On = 1 when the current in the circuit is above the threshold setting. The voltage monitor is set to On = 1 when the current is above about 1 to 2.5 mA, and the current monitor is set to On = 1 when the current exceeds about 80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be used to seal-in the output contact until an external contact has interrupted current flow. Block diagrams are shown below for form-A and solid-state relay outputs with optional voltage monitor, optional current monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs.
If Idc 80mA, Cont Op 1 = IOn otherwise Cont Op 1 = IOff If Idc 1mA, Cont Op 1 = VOn otherwise Cont Op 1 = VOff

~#a I ~#b V ~#c a) Voltage with optional current monitoring Voltage monitoring only
If Idc 1mA, Cont Op 1 = VOn otherwise Cont Op 1 = VOff

~#a I ~#b V ~#c

Load

Load

Both voltage and current monitoring


If Idc 80mA, Cont Op 1 = IOn otherwise Cont Op 1 = IOff If Idc 1mA, Cont Op 1 = VOn otherwise Cont Op 1 = VOff

~#a V I ~#b ~#c b) Current with optional voltage monitoring Current monitoring only
If Idc 80mA, Cont Op 1 = IOn otherwise Cont Op 1 = IOff

~#a V I ~#b ~#c

Load

Load

Both voltage and current monitoring (external jumper a-b is required)

~#a

~#b Load ~#c c) No monitoring

+
827862A3.CDR

Figure 314: FORM-A AND SOLID-STATE CONTACT OUTPUTS WITH VOLTAGE AND CURRENT MONITORING The operation of voltage and current monitors is reflected with the corresponding FlexLogic operands (CONT OP # VON, CONT OP # VOFF, and CONT OP # ION) which can be used in protection, control, and alarm logic. The typical application of the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the control command. Refer to the Digital elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be applied for breaker trip circuit integrity monitoring. Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to be used for low voltage accessible applications, it is the customers responsibility to ensure proper insulation levels! USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS
NOTE

WARNING

For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may continue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as an impedance. The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the formA contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is used as a source, a 500 , 10 W resistor is appropriate. In this configuration, the voltage across either the form-A contact or the resistor can be used to monitor the state of the output.

GE Multilin

C30 Controller System

3-13

3.2 WIRING

3 HARDWARE

Wherever a tilde ~ symbol appears, substitute with the slot position of the module; wherever a number sign # appears, substitute the contact number
NOTE

NOTE

When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the FlexLogic operand driving the contact output should be given a reset delay of 10 ms to prevent damage of the output contact (in situations when the element initiating the contact output is bouncing, at values in the region of the pickup value).

Table 32: CONTACT INPUT AND OUTPUT MODULE ASSIGNMENTS


~6A MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~6B MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5 ~6 ~7a, ~7c ~8a, ~8c Form-A Form-A Form-C Form-C Form-C Form-C 2 Inputs 2 Inputs ~6C MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Form-C Form-C Form-C Form-C Form-C Form-C Form-C Form-C ~6D MODULE TERMINAL ASSIGNMENT ~1a, ~1c ~2a, ~2c ~3a, ~3c ~4a, ~4c ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c OUTPUT 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c

Form-A Form-A Form-C Form-C 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~6E MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-C Form-C Form-C Form-C 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~6F MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Fast Form-C Fast Form-C Fast Form-C Fast Form-C Fast Form-C Fast Form-C Fast Form-C Fast Form-C

~6G MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-A Form-A Form-A Form-A 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~6H MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5 ~6 ~7a, ~7c ~8a, ~8c Form-A Form-A Form-A Form-A Form-A Form-A 2 Inputs 2 Inputs

~6K MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Form-C Form-C Form-C Form-C Fast Form-C Fast Form-C Fast Form-C Fast Form-C

~6L MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-A Form-A Form-C Form-C 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~6M MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5 ~6 ~7a, ~7c ~8a, ~8c Form-A Form-A Form-C Form-C Form-C Form-C 2 Inputs 2 Inputs

~6N MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-A Form-A Form-A Form-A 2 Inputs 2 Inputs 2 Inputs 2 Inputs

3-14

C30 Controller System

GE Multilin

3 HARDWARE

3.2 WIRING

~6P MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5 ~6 ~7a, ~7c ~8a, ~8c Form-A Form-A Form-A Form-A Form-A Form-A 2 Inputs 2 Inputs

~6R MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-A Form-A Form-C Form-C 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~6S MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5 ~6 ~7a, ~7c ~8a, ~8c Form-A Form-A Form-C Form-C Form-C Form-C 2 Inputs 2 Inputs

~6T MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-A Form-A Form-A Form-A 2 Inputs 2 Inputs 2 Inputs 2 Inputs

3
~6U MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5 ~6 ~7a, ~7c ~8a, ~8c Form-A Form-A Form-A Form-A Form-A Form-A 2 Inputs 2 Inputs ~6V MODULE TERMINAL OUTPUT OR ASSIGNMENT INPUT ~1 ~2 ~3 ~4 ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c Form-A Form-A Form-C 2 Outputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs ~67 MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Form-A Form-A Form-A Form-A Form-A Form-A Form-A Form-A ~4A MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Not Used Solid-State Not Used Solid-State Not Used Solid-State Not Used Solid-State

~4B MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Not Used Solid-State Not Used Solid-State Not Used Solid-State Not Used Solid-State

~4C MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT Not Used Solid-State Not Used Solid-State Not Used Solid-State Not Used Solid-State

~4D MODULE TERMINAL ASSIGNMENT ~1a, ~1c ~2a, ~2c ~3a, ~3c ~4a, ~4c ~5a, ~5c ~6a, ~6c ~7a, ~7c ~8a, ~8c OUTPUT 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs 2 Inputs

~4L MODULE TERMINAL ASSIGNMENT ~1 ~2 ~3 ~4 ~5 ~6 ~7 ~8 OUTPUT 2 Outputs 2 Outputs 2 Outputs 2 Outputs 2 Outputs 2 Outputs 2 Outputs Not Used

GE Multilin

C30 Controller System

3-15

3.2 WIRING

3 HARDWARE

842762A2.CDR

Figure 315: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2)

3-16

C30 Controller System

GE Multilin

3 HARDWARE

3.2 WIRING

V I

V I

~2

~2

~2

~3

~4

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b ~ 8b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

~ 8b

SURGE

~3

~3

~4

~4

~5

~5

~6

~6

~7

~8

V I

V I

~2

~2

V I

V I

~4

~4

~ 8b

SURGE

V I

~5

~ 5a ~ 5c ~ 6a ~ 6c ~ 5b ~ 7a ~ 7c ~ 8a ~ 8c ~ 7b ~ 8b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE

~ 5a DIGITAL I/O ~ 5c ~ 6a ~ 6c ~ 5b ~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

6R
~1

~2

~3

~4

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b ~ 8b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE

~ 7a DIGITAL I/O ~ 7c ~ 8a ~ 8c ~ 7b

6S
~1

~2

~3

~4 ~ 5a ~ 5c ~ 6a ~ 6c ~ 5b ~ 7a ~ 7c ~ 8a ~ 8c ~ 7b ~ 8b
CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE

~ 5a DIGITAL I/O ~ 5c ~ 6a ~ 6c ~ 5b ~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

6T
~1

~2

~3

~4

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c

~5

~6

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b ~ 8b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON SURGE

~ 7a DIGITAL I/O ~ 7c ~ 8a ~ 8c ~ 7b

6U

~1

~2

~3

~4

~5

~6

842763A2.CDR

Figure 316: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT AND SOLID STATE OUTPUT CONNECTIONS FOR PROPER FUNCTIONALITY.
CAUTION

GE Multilin

C30 Controller System

~6

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

~ 8b

SURGE

~3

~3

~ 5a ~ 5c ~ 6a ~ 6c ~ 5b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON

~ 5a DIGITAL I/O ~ 5c ~ 6a ~ 6c ~ 5b

DIGITAL I/O

6N
~1

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON

~ 7a DIGITAL I/O ~ 7c ~ 8a ~ 8c ~ 7b

6P

~1

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c ~ 5a ~ 5b ~ 5c ~ 6a ~ 6b ~ 6c ~ 7a ~ 7b ~ 7c ~ 8a ~ 8b ~ 8c

~1

~ 5a ~ 5c ~ 6a ~ 6c ~ 5b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON

~ 5a DIGITAL I/O ~ 5c ~ 6a ~ 6c ~ 5b

6K

6L
~1

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c

~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

CONTACT IN CONTACT IN CONTACT IN CONTACT IN COMMON

~ 7a DIGITAL I/O ~ 7c ~ 8a ~ 8c ~ 7b

6M
~1

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c ~ 5a ~ 5b ~ 5c ~ 6a ~ 6b ~ 6c

3
~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c ~ 5a ~ 5b ~ 5c ~ 6a ~ 6b ~ 6c

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c ~ 5a ~ 5b ~ 5c ~ 6a ~ 6b ~ 6c

~ 1a ~ 1b ~ 1c ~ 2a ~ 2b ~ 2c ~ 3a ~ 3b ~ 3c ~ 4a ~ 4b ~ 4c ~ 5a ~ 5b ~ 5c ~ 6a ~ 6b ~ 6c

3-17

3.2 WIRING CONTACT INPUTS:

3 HARDWARE

A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power supply module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group has its own common (negative) terminal which must be connected to the DC negative terminal (B3a) of the power supply module. When a dry contact closes, a current of 1 to 3 mA will flow through the associated circuit. A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this contact is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external source must be connected to the relay common (negative) terminal of each contact group. The maximum external source voltage for this arrangement is 300 V DC. The voltage threshold at which each group of four contact inputs will detect a closed contact input is programmable as 17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.

(Dry)

DIGITAL I/O ~ 7a + CONTACT IN ~ 7c + CONTACT IN ~ 8a + CONTACT IN ~ 8c + CONTACT IN ~ 7b COMMON ~ 8b SURGE

6B ~ 7a ~ 7c ~ 8a ~ 8c ~ 7b

(Wet)

24-250V

DIGITAL I/O 6B ~ 7a + CONTACT IN ~ 7a ~ 7c + CONTACT IN ~ 7c ~ 8a + CONTACT IN ~ 8a ~ 8c + CONTACT IN ~ 8c ~ 7b COMMON ~ 7b ~ 8b SURGE

B 1b CRITICAL B 1a FAILURE B 2b B 3a 48 VDC OUTPUT B 3b + B 5b HI+ CONTROL B 6b LO+ POWER B 6a B 8a SURGE B 8b FILTER

POWER SUPPLY

827741A4.CDR

Figure 317: DRY AND WET CONTACT INPUT CONNECTIONS Wherever a tilde ~ symbol appears, substitute with the slot position of the module.
NOTE

Contact outputs may be ordered as form-a or form-C. The form-A contacts may be connected for external circuit supervision. These contacts are provided with voltage and current monitoring circuits used to detect the loss of DC voltage in the circuit, and the presence of DC current flowing through the contacts when the form-A contact closes. If enabled, the current monitoring can be used as a seal-in signal to ensure that the form-A contact does not attempt to break the energized inductive coil circuit and weld the output contacts. There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply.
NOTE

3-18

C30 Controller System

GE Multilin

3 HARDWARE USE OF CONTACT INPUTS WITH AUTO-BURNISHING:

3.2 WIRING

The contact inputs sense a change of the state of the external device contact based on the measured current. When external devices are located in a harsh industrial environment (either outdoor or indoor), their contacts can be exposed to various types of contamination. Normally, there is a thin film of insulating sulfidation, oxidation, or contaminates on the surface of the contacts, sometimes making it difficult or impossible to detect a change of the state. This film must be removed to establish circuit continuity an impulse of higher than normal current can accomplish this. The contact inputs with auto-burnish create a high current impulse when the threshold is reached to burn off this oxidation layer as a maintenance to the contacts. Afterwards the contact input current is reduced to a steady-state current. The impulse will have a 5 second delay after a contact input changes state.
current 50 to 70 mA

3
3 mA time 25 to 50 ms
842749A1.CDR

Figure 318: CURRENT THROUGH CONTACT INPUTS WITH AUTO-BURNISHING Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with autoburnishing allow currents up to 50 to 70 mA at the first instance when the change of state was sensed. Then, within 25 to 50 ms, this current is slowly reduced to 3 mA as indicated above. The 50 to 70 mA peak current burns any film on the contacts, allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing starts when external device contact bouncing is over. Another important difference between the auto-burnishing input module and the regular input modules is that only two contact inputs have common ground, as opposed to four contact inputs sharing one common ground (refer to the Contact Input and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources. Consequently, the threshold voltage setting is also defined per group of two contact inputs. The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP switch for each contact, for a total of 16 inputs.
CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = OFF

CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = OFF

CONTACT INPUT 1 AUTO-BURNISH = OFF CONTACT INPUT 2 AUTO-BURNISH = ON

CONTACT INPUT 1 AUTO-BURNISH = ON CONTACT INPUT 2 AUTO-BURNISH = ON


842751A1.CDR

Figure 319: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope.
NOTE

GE Multilin

C30 Controller System

3-19

3.2 WIRING

3 HARDWARE 3.2.6 TRANSDUCER INPUTS/OUTPUTS

Transducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance temperature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and convert these signals into a digital format for use as required. Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configure virtually any analog quantity used in the relay to drive the analog outputs. Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three terminals per row with a total of eight rows. A given row may be used for either inputs or outputs, with terminals in column "a" having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/ output channel, the name of the channel is assigned using the module slot position and row number.

Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs require a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde ~ symbol appears, substitute with the slot position of the module.
NOTE

Figure 320: TRANSDUCER INPUT/OUTPUT MODULE WIRING

3-20

C30 Controller System

GE Multilin

3 HARDWARE

3.2 WIRING 3.2.7 RS232 FACEPLATE PORT

A 9-pin RS232C serial port is located on the C30 faceplate for programming with a personal computer. All that is required to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors. The baud rate for this port is fixed at 19200 bps.
NOTE

Figure 321: RS232 FACEPLATE PORT CONNECTION 3.2.8 CPU COMMUNICATION PORTS a) OPTIONS In addition to the faceplate RS232 port, the C30 provides two additional communication ports or a managed six-port Ethernet switch, depending on the installed CPU module. The CPU modules do not require a surge ground connection.
NOTE

Table 33: CPU MODULE COMMUNICATIONS


CPU TYPE 9E 9G 9H 9J 9K 9L 9M COM1 RS485 10Base-F and 10Base-T Redundant 10Base-F 100Base-FX Redundant 100Base-FX 100Base-FX Redundant 100Base-FX COM2 RS485 RS485 RS485 RS485 RS485 RS485 RS485

GE Multilin

C30 Controller System

3-21

3.2 WIRING

3 HARDWARE

Shielded twisted-pairs

Ground at remote device

D1b D2b D3b D1a D2a D3a D4b D4a

+
COMMON

Rx1 Rx2

100Base-FL 100Base-F

NORMAL ALTERNATE RS485 COM2 IRIG-B input

RS485 COM1 RS485 COM2 IRIG-B input

Tx2

Shielded twisted-pairs

+
COMMON

+
BNC BNC

Ground at remote device

D1a D2a D3a D4b D4a

+
COMMON

+
BNC BNC

Co-axial cable

CPU

Co-axial cable Co-axial cable

IRIG-B output

IRIG-B output

Co-axial cable

Rx1

10Base-FL 10Base-T

NORMAL

COM1 9G

MM fiber optic cable

Tx1

Shielded twisted-pairs

Shielded twisted-pairs

Ground at remote device

D1a D2a D3a D4b D4a

+
COMMON

RS485 COM2 IRIG-B input IRIG-B output CPU

Ground at remote device

D1a D2a D3a D4b D4a

+
COMMON

RS485 COM2 IRIG-B input IRIG-B output

+
BNC BNC

+
BNC BNC

Co-axial cable Co-axial cable

Co-axial cable

Rx1

10Base-FL

NORMAL ALTERNATE

100Base-FL

NORMAL COM1 RS485 COM2 IRIG-B input IRIG-B output

Tx2

Rx2 10Base-F

Shielded twisted-pairs

10Base-T

BNC Co-axial cable

BNC Co-axial cable

IRIG-B output

9J

Rx1

100Base-FL

NORMAL COM1 RS485 COM2 IRIG-B input

100Base-FL Shielded twisted-pairs 100Base-F

NORMAL ALTERNATE RS485 COM2 IRIG-B input

Ground at remote device

D1a D2a D3a D4b D4a


Co-axial cable

+
COMMON

+
BNC BNC

Ground at remote device

D1a D2a D3a D4b D4a

+
COMMON

+
BNC BNC

IRIG-B output

CPU

IRIG-B output

Co-axial cable

842765A7.CDR

Figure 322: CPU MODULE COMMUNICATIONS WIRING b) RS485 PORTS RS485 data transmission and reception are accomplished over a single twisted pair with transmit and receive data alternating over the same two wires. Through the use of these ports, continuous monitoring and control from a remote computer, SCADA system or PLC is possible. To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be observed. For instance, the relays must be connected with all RS485 + terminals connected together, and all RS485 terminals connected together. The COM terminal should be connected to the common wire inside the shield, when provided. To avoid loop currents, the shield should be grounded at one point only. Each relay should also be daisy chained to the next one in the link. A maximum of 32 relays can be connected in this manner without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible to use commercially available repeaters to increase the number of relays on a single channel to more than 32. Star or stub connections should be avoided entirely. Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the communication link. For this reason, surge protection devices are internally provided at both communication ports. An isolated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all equipment should have similar transient protection devices installed.

3-22

C30 Controller System

GE Multilin

CPU

Co-axial cable

Co-axial cable

COM1 9M

MM fiber optic cable

CPU

Co-axial cable

BNC

Tx1

SM fiber optic cable

CPU

Ground at remote device

D1a D2a D3a D4b D4a

+
COMMON

RS485 COM2 IRIG-B input

Ground at remote device

D1a D2a D3a D4b D4a


Co-axial cable

+
COMMON

+
BNC

9L

Tx1

COM1 9H

MM fiber optic cable

SM fiber optic cable

CPU

Co-axial cable

9S

CPU

COM1 9K

MM fiber optic cable

Tx1

9E

3 HARDWARE Both ends of the RS485 circuit should also be terminated with an impedance as shown below.

3.2 WIRING

Figure 323: RS485 SERIAL CONNECTION c) 10BASE-FL AND 100BASE-FX FIBER OPTIC PORTS ENSURE THE DUST COVERS ARE INSTALLED WHEN THE FIBER IS NOT IN USE. DIRTY OR SCRATCHED CONNECTORS CAN LEAD TO HIGH LOSSES ON A FIBER LINK.
CAUTION

OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.
CAUTION

The fiber optic communication ports allow for fast and efficient communications between relays at 10 Mbps or 100 Mbps. Optical fiber may be connected to the relay supporting a wavelength of 820 nm in multi-mode or 1310 nm in multi-mode and single-mode. The 10 Mbps rate is available for CPU modules 9G and 9H; 100Mbps is available for modules 9H, 9J, 9K, 9L, 9M, 9N, 9P, and 9R. The 9H, 9K, 9M, and 9R modules have a second pair of identical optical fiber transmitter and receiver for redundancy. The optical fiber sizes supported include 50/125 m, 62.5/125 m and 100/140 m for 10 Mbps. The fiber optic port is designed such that the response times will not vary for any core that is 100 m or less in diameter, 62.5 m for 100 Mbps. For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers, the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connector, only a quarter turn of the coupling is required.

GE Multilin

C30 Controller System

3-23

3.2 WIRING

3 HARDWARE 3.2.9 IRIG-B

IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within 1 millisecond. The IRIG time code formats are serial, width-modulated codes which can be either DC level shifted or amplitude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized.

GPS SATELLITE SYSTEM


GPS CONNECTION OPTIONAL

3
IRIG-B TIME CODE GENERATOR
(DC SHIFT OR AMPLITUDE MODULATED SIGNAL CAN BE USED)

RELAY
4B 4A RG58/59 COAXIAL CABLE + BNC (IN) IRIG-B(+) IRIG-B(-) RECEIVER

BNC (OUT) REPEATER

TO OTHER DEVICES (DC-SHIFT ONLY)

827756A5.CDR

Figure 324: IRIG-B CONNECTION The IRIG-B repeater provides an amplified DC-shift IRIG-B signal to other equipment. By using one IRIG-B serial connection, several UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down.

Figure 325: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping.
NOTE

3-24

C30 Controller System

GE Multilin

3 HARDWARE 3.3DIRECT INPUT/OUTPUT COMMUNICATIONS

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3.3.1 DESCRIPTION

The C30 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the communications channels provided by these modules to exchange digital state information between relays. This feature is available on all UR-series relay models except for the L90 Line Differential relay. The communications channels are normally connected in a ring configuration as shown below. The transmitter of one module is connected to the receiver of the next module. The transmitter of this second module is then connected to the receiver of the next module in the ring. This is continued to form a communications ring. The figure below illustrates a ring of four UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx to UR1-Rx. A maximum of sixteen (16) UR-series relays can be connected in a single ring
UR #1
Tx Rx Tx Rx Tx Rx Tx Rx
842006A1.CDR

UR #2

UR #3

UR #4

Figure 326: DIRECT INPUT AND OUTPUT SINGLE CHANNEL CONNECTION The interconnection for dual-channel Type 7 communications modules is shown below. Two channel modules allow for a redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The required connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring.
Tx1 Rx1 Tx2 Rx2 Tx1

UR #1

UR #2

Rx1 Tx2 Rx2 Tx1

UR #3

Rx1 Tx2 Rx2 Tx1

UR #4

Rx1 Tx2 Rx2


842007A1.CDR

Figure 327: DIRECT INPUT AND OUTPUT DUAL CHANNEL CONNECTION The following diagram shows the connection for three UR-series relays using two independent communication channels. UR1 and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication channels can be of different types, depending on the Type 7 modules used. To allow the direct input and output data to crossover from channel 1 to channel 2 on UR2, the DIRECT I/O CHANNEL CROSSOVER setting should be Enabled on UR2. This forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.

GE Multilin

C30 Controller System

3-25

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

3 HARDWARE

UR #1

Tx Rx

Channel #1
Tx1

UR #2

Rx1 Tx2 Rx2

Channel #2

UR #3

Tx Rx
842013A1.CDR

Figure 328: DIRECT INPUT AND OUTPUT SINGLE/DUAL CHANNEL COMBINATION CONNECTION The interconnection requirements are described in further detail in this section for each specific variation of type 7 communications module. These modules are listed in the following table. All fiber modules use ST type connectors. Not all the direct input and output communications modules may be applicable to the C30 relay. Only the modules specified in the order codes are available as direct input and output communications modules.
NOTE

Table 34: CHANNEL COMMUNICATION OPTIONS (Sheet 1 of 2)


MODULE 2A 2B 2E 2F 2G 2H 2S 2T 72 73 74 75 76 77 7A 7B 7C 7D 7E 7F 7G 7H 7I 7J 7K 7L 7M SPECIFICATION C37.94SM, 1300 nm, single-mode, ELED, 1 channel single-mode C37.94SM, 1300 nm, single-mode, ELED, 2 channel single-mode Bi-phase, 1 channel Bi-phase, 2 channel IEEE C37.94, 820 nm, 128 kbps, multi-mode, LED, 1 channel IEEE C37.94, 820 nm, 128 kbps, multi-mode, LED, 2 channels Six-port managed Ethernet switch with high voltage power supply Six-port managed Ethernet switch with low voltage power supply 1550 nm, single-mode, laser, 1 channel 1550 nm, single-mode, laser, 2 channels Channel 1 - RS422; channel 2 - 1550 nm, single-mode, laser Channel 1 - G.703; channel 2 - 1550 nm, single-mode, laser IEEE C37.94, 820 nm, 64 kbps, multi-mode, LED, 1 channel IEEE C37.94, 820 nm, 64 kbps, multi-mode, LED, 2 channels 820 nm, multi-mode, LED, 1 channel 1300 nm, multi-mode, LED, 1 channel 1300 nm, single-mode, ELED, 1 channel 1300 nm, single-mode, laser, 1 channel Channel 1: G.703, Channel 2: 820 nm, multi-mode Channel 1: G.703, Channel 2: 1300 nm, multi-mode Channel 1: G.703, Channel 2: 1300 nm, single-mode ELED 820 nm, multi-mode, LED, 2 channels 1300 nm, multi-mode, LED, 2 channels 1300 nm, single-mode, ELED, 2 channels 1300 nm, single-mode, LASER, 2 channels Channel 1: RS422, channel: 820 nm, multi-mode, LED Channel 1: RS422, channel 2: 1300 nm, multi-mode, LED

3-26

C30 Controller System

GE Multilin

3 HARDWARE Table 34: CHANNEL COMMUNICATION OPTIONS (Sheet 2 of 2)


MODULE 7N 7P 7Q 7R 7S 7T 7V 7W SPECIFICATION Channel 1: RS422, channel 2: 1300 nm, single-mode, ELED Channel 1: RS422, channel 2: 1300 nm, single-mode, laser Channel 1: G.703, channel 2: 1300 nm, single-mode, laser G.703, 1 channel G.703, 2 channels RS422, 1 channel RS422, 2 channels, 2 clock inputs RS422, 2 channels

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.
CAUTION

3.3.2 FIBER: LED AND ELED TRANSMITTERS

The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
Module: Connection Location: 7A / 7B / 7C Slot X 7H / 7I / 7J Slot X

RX1 TX1

RX1 TX1

RX2 TX2 1 Channel 2 Channels


831719A2.CDR

Figure 329: LED AND ELED FIBER MODULES 3.3.3 FIBER-LASER TRANSMITTERS The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module.
Module: Connection Location: 72/ 7D Slot X TX1 RX1 73/ 7K Slot X TX1 RX1

TX2 RX2

1 Channel

2 Channels

831720A3.CDR

Figure 330: LASER FIBER MODULES When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver.
WARNING

GE Multilin

C30 Controller System

3-27

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

3 HARDWARE 3.3.4 G.703 INTERFACE

a) DESCRIPTION The following figure shows the 64K ITU G.703 co-directional interface configuration. The G.703 module is fixed at 64 kbps. The SETTINGS setting is not applicable to this module.
NOTE

PRODUCT SETUP

DIRECT I/O

DIRECT I/O DATA RATE

AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Connecting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.
Shield

Inter-relay communications

G.703 channel 1

Tx Rx Tx + Rx +

Surge
Shield Tx Rx Tx + Rx +

G.703 channel 2

Surge

X 1a X 1b X 2a X 2b X 3a X 3b X 6a X 6b X 7a X 7b X 8a X 8b

7S

842773A2.CDR

Figure 331: G.703 INTERFACE CONFIGURATION The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrangement of these pins, see the Rear terminal assignments section earlier in this chapter. All pin interconnections are to be maintained for a connection to a multiplexer.
7S
Tx Rx Tx + Rx + Tx Rx Tx + Rx +

G.703 CHANNEL 1

G.703 CHANNEL 1

SURGE
Shld. Tx -

SURGE
Shld. Tx Tx + Rx +

COMM.

Tx + Rx +

SURGE

SURGE
831727A3.CDR

Figure 332: TYPICAL PIN INTERCONNECTION BETWEEN TWO G.703 INTERFACES Pin nomenclature may differ from one manufacturer to another. Therefore, it is not uncommon to see pinouts numbered TxA, TxB, RxA and RxB. In such cases, it can be assumed that A is equivalent to + and B is equivalent to .

NOTE

b) G.703 SELECTION SWITCH PROCEDURES 1. Remove the G.703 module (7R or 7S). The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order to release the module for removal. Before performing this action, control power must be removed from the relay. The original location of the module should be recorded to help ensure that the same or replacement module is inserted into the correct slot. Remove the module cover screw. Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw.

2. 3. 4. 5.

3-28

C30 Controller System

COMM.

G.703 CHANNEL 2

Rx -

Rx -

G.703 CHANNEL 2

7S

Shld.

X 1a X 1b X 2a X 2b X 3a X 3b X 6a X 6b X 7a X 7b X 8a X 8b

X 1a X 1b X 2a X 2b X 3a X 3b X 6a X 6b X 7a X 7b X 8a X 8b

Shld.

GE Multilin

3 HARDWARE 6.

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.

Figure 333: G.703 TIMING SELECTION SWITCH SETTING Table 35: G.703 TIMING SELECTIONS
SWITCHES S1 S5 and S6 FUNCTION OFF octet timing disabled ON octet timing 8 kHz S5 = OFF and S6 = OFF loop timing mode S5 = ON and S6 = OFF internal timing mode S5 = OFF and S6 = ON minimum remote loopback mode S5 = ON and S6 = ON dual loopback mode

c) G.703 OCTET TIMING If octet timing is enabled (on), this 8 kHz signal will be asserted during the violation of bit 8 (LSB) necessary for connecting to higher order systems. When C30s are connected back to back, octet timing should be disabled (off). d) G.703 TIMING MODES There are two timing modes for the G.703 module: internal timing mode and loop timing mode (default). Internal Timing Mode: The system clock is generated internally. Therefore, the G.703 timing selection should be in the internal timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set for octet timing (S1 = OFF) and timing mode to internal timing (S5 = ON and S6 = OFF). Loop Timing Mode: The system clock is derived from the received line signal. Therefore, the G.703 timing selection should be in loop timing mode for connections to higher order systems. For connection to a higher order system (URto-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF).

GE Multilin

C30 Controller System

3-29

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS The switch settings for the internal and loop timing modes are shown below:

3 HARDWARE

842752A1.CDR

e) G.703 TEST MODES

In minimum remote loopback mode, the multiplexer is enabled to return the data from the external interface without any processing to assist in diagnosing G.703 line-side problems irrespective of clock rate. Data enters from the G.703 inputs, passes through the data stabilization latch which also restores the proper signal polarity, passes through the multiplexer and then returns to the transmitter. The differential received data is processed and passed to the G.703 transmitter module after which point the data is discarded. The G.703 receiver module is fully functional and continues to process data and passes it to the differential Manchester transmitter module. Since timing is returned as it is received, the timing source is expected to be from the G.703 line side of the interface.

DMR

G7X

DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver

DMX

G7R
842774A1.CDR

Figure 334: G.703 MINIMUM REMOTE LOOPBACK MODE In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/ transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module. Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing. One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface.

DMR

G7X

DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver

DMX

G7R
842775A1.CDR

Figure 335: G.703 DUAL LOOPBACK MODE

3-30

C30 Controller System

GE Multilin

3 HARDWARE

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3.3.5 RS422 INTERFACE

a) DESCRIPTION There are two RS422 inter-relay communications modules available: single-channel RS422 (module 7T) and dual-channel RS422 (module 7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 24 twisted shielded pair cable is recommended for external connections. These modules are protected by optically-isolated surge suppression devices. The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows: Site 1: Terminate shield to pins 6a or 7b or both. Site 2: Terminate shield to COM pin 2b.

The clock terminating impedance should match the impedance of the line.
Single-channel RS422 module Dual-channel RS422 module

Clock
COM

Tx Rx Tx + Rx + Shield

Surge

RS422 channel 2

Clock
COM

~ indicates the slot position

Surge

842776A3.CDR

Figure 336: RS422 INTERFACE CONNECTIONS The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W. All pin interconnections are to be maintained for a connection to a multiplexer.

Figure 337: TYPICAL PIN INTERCONNECTION BETWEEN TWO RS422 INTERFACES b) TWO-CHANNEL APPLICATION VIA MULTIPLEXERS The RS422 interface may be used for single channel or two channel applications over SONET/SDH or multiplexed systems. When used in single-channel applications, the RS422 interface links to higher order systems in a typical fashion observing transmit (Tx), receive (Rx), and send timing (ST) connections. However, when used in two-channel applications, certain criteria must be followed since there is one clock input for the two RS422 channels. The system will function correctly if the following connections are observed and your data module has a terminal timing feature. Terminal timing is a common feature to most synchronous data units that allows the module to accept timing from an external source. Using the terminal timing feature, two channel applications can be achieved if these connections are followed: The send timing outputs from the multiplexer (data module 1), will connect to the clock inputs of the URRS422 interface in the usual fashion. In addition, the send timing outputs of data module 1 will also be paralleled to the terminal timing inputs of data module 2. By using this configuration, the timing for both data modules and both URRS422 channels will be derived from a single clock source. As a result, data sampling for both of the URRS422 channels will be synchronized via the send timing leads on data module 1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions.

GE Multilin

C30 Controller System

Inter-relay communications

~ 3b ~ 3a ~ 2a ~ 4b ~ 6a ~ 7a ~ 8b ~ 2b ~ 8a

Rx

Rx Tx + Rx + Shield

Rx + Shield

Inter-relay comms.

Tx +

RS422

RS422 channel 1

7W

7T

Tx

~ 3b ~ 3a ~ 2a ~ 4b ~ 6a ~ 5b ~ 5a ~ 4a ~ 6b ~ 7b ~ 7a ~ 8b ~ 2b ~ 8a

Tx

3-31

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

3 HARDWARE

Data module 1
Signal name

7W

Tx1(+) Tx1(-)

RS422 CHANNEL 1

Rx1(+) Rx1(-) Shld.

CLOCK

+ Tx2(+) Tx2(-)

RS422 CHANNEL 2

Rx2(+) Rx2(-) Shld. com

SURGE

W 2a W 3b W 4b W 3a W 6a W 7a W 8b W 4a W 5b W 6b W 5a W 7b W 2b W 8a

SD(A) - Send data SD(B) - Send data RD(A) - Received data RD(B) - Received data RS(A) - Request to send (RTS) RS(B) - Request to send (RTS) RT(A) - Receive timing RT(B) - Receive timing CS(A) - Clear To send CS(B) - Clear To send Local loopback Remote loopback Signal ground ST(A) - Send timing ST(B) - Send timing

INTER-RELAY COMMUNICATIONS

Data module 2
Signal name TT(A) - Terminal timing TT(B) - Terminal timing SD(A) - Send data SD(B) - Send data RD(A) - Received data RD(B) - Received data RS(A) - Request to send (RTS) RS(B) - Request to send (RTS) CS(A) - Clear To send CS(B) - Clear To send Local loopback Remote loopback Signal ground ST(A) - Send timing ST(B) - Send timing 831022A3.CDR

Figure 338: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the C30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they may vary depending on the manufacturer. c) TRANSMIT TIMING The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is important to confirm clock and data transitions to ensure proper system operation. For example, the following figure shows the positive edge of the Tx clock in the center of the Tx data bit.

Tx Clock

Tx Data

Figure 339: CLOCK AND DATA TRANSITIONS d) RECEIVE TIMING The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data. NRZI-MARK is an edge-type, invertible, self-clocking code.

3-32

C30 Controller System

GE Multilin

3 HARDWARE

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

To recover the Rx clock from the data-stream, an integrated DPLL (digital phase lock loop) circuit is utilized. The DPLL is driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a data clock that can be used as the SCC (serial communication controller) receive clock. 3.3.6 RS422 AND FIBER INTERFACE The following figure shows the combined RS422 plus Fiber interface configuration at 64K baud. The 7L, 7M, 7N, 7P, and 74 modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external RS422 connections and the shield should be grounded only at one end. For the direct fiber channel, power budget issues should be addressed properly. When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed maximum optical input power to the receiver.
WARNING

Rx1 + Shield

Tx2

Rx2

Fiber channel 2 Surge

~ 8a

842777A1.CDR

Figure 340: RS422 AND FIBER INTERFACE CONNECTION Connections shown above are for multiplexers configured as DCE (data communications equipment) units. 3.3.7 G.703 AND FIBER INTERFACE The figure below shows the combined G.703 plus fiber interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and 75 modules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer) and channel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external G.703 connections connecting the shield to pin 1a at one end only. For the direct fiber channel, power budget issues should be addressed properly. See previous sections for additional details on the G.703 and fiber interfaces. When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver.
WARNING

Shield Tx Rx Tx + Rx +

G.703 channel 1

Surge

Tx2 Rx2

Fiber channel 2

842778A1.CDR

Figure 341: G.703 AND FIBER INTERFACE CONNECTION

GE Multilin

C30 Controller System

7E, 7F, 7G, Inter-relay communications 7Q,75

~ 1a ~ 1b ~ 2a ~ 2b ~ 3a ~ 3b

Inter-relay comms.

~ 1a ~ 1b ~ 2b ~ 2a ~ 3a ~ 3b ~ 4b ~ 6a

COM Tx1 + Rx1 Tx1

RS422 channel 1

7L, 7M, 7N, 7P, 74

Clock (channel 1)

3-33

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

3 HARDWARE 3.3.8 IEEE C37.94 INTERFACE

The UR-series IEEE C37.94 communication modules (modules types 2G, 2H, 76, and 77) are designed to interface with IEEE C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and output applications for firmware revisions 3.30 and higher. The IEEE C37.94 standard defines a point-to-point optical link for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard provides for speeds up to 64n kbps, where n = 1, 2,, 12. The UR-series C37.94 communication modules are either 64 kbps (with n fixed at 1) for 128 kbps (with n fixed at 2). The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps. The specifications for the module are as follows:. IEEE standard: C37.94 for 1 128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2 64 kbps optical fiber interface (for 76 and 77 modules). Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber. Fiber optic mode: multi-mode. Fiber optic cable length: up to 2 km. Fiber optic connector: type ST. Wavelength: 830 40 nm. Connection: as per all fiber optic connections, a Tx to Rx connection is required.

The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94 standard as shown below.

The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a non-compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard, as shown below.

The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The functions of these control switches is shown below.

842753A1.CDR

3-34

C30 Controller System

GE Multilin

3 HARDWARE

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

For the internal timing mode, the system clock is generated internally. therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured. For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection should be in loop timing mode for connections to higher order systems. The IEEE C37.94 communications module cover removal procedure is as follows: 1. Remove the IEEE C37.94 module (type 2G, 2H, 76, or 77 module): The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order to release the module for removal. Before performing this action, control power must be removed from the relay. The original location of the module should be recorded to help ensure that the same or replacement module is inserted into the correct slot. 2. 3. 4. 5. 6. Remove the module cover screw. Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above). Replace the top cover and the cover screw. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.

Figure 342: IEEE C37.94 TIMING SELECTION SWITCH SETTING

GE Multilin

C30 Controller System

3-35

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

3 HARDWARE 3.3.9 C37.94SM INTERFACE

The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94 compliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-mode fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard provides for speeds up to 64n kbps, where n = 1, 2,, 12. The UR-series C37.94SM communication module is 64 kbps only with n fixed at 1. The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps. The specifications for the module are as follows: Emulated IEEE standard: emulates C37.94 for 1 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps). Fiber optic cable type: 9/125 m core diameter optical fiber. Fiber optic mode: single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver. Fiber optic cable length: up to 10 km. Fiber optic connector: type ST. Wavelength: 1300 40 nm. Connection: as per all fiber optic connections, a Tx to Rx connection is required.

The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that supports C37.94SM as shown below.

It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below.

The UR-series C37.94SM communication module has six (6) switches that are used to set the clock configuration. The functions of these control switches is shown below.

842753A1.CDR

For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.

3-36

C30 Controller System

GE Multilin

3 HARDWARE

3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS

For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection should be in loop timing mode for connections to higher order systems. The C37.94SM communications module cover removal procedure is as follows: 1. Remove the C37.94SM module (modules 2A or 2B): The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order to release the module for removal. Before performing this action, control power must be removed from the relay. The original location of the module should be recorded to help ensure that the same or replacement module is inserted into the correct slot. 2. 3. 4. 5. 6. Remove the module cover screw. Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above). Replace the top cover and the cover screw. Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.

Figure 343: C37.94SM TIMING SELECTION SWITCH SETTING

GE Multilin

C30 Controller System

3-37

3.4 MANAGED ETHERNET SWITCH MODULES 3.4MANAGED ETHERNET SWITCH MODULES

3 HARDWARE 3.4.1 OVERVIEW

The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU modules with revisions 5.5x and higher. The modules communicate to the C30 through an internal Ethernet port (referred to as the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST 100Base-FX ports. The Ethernet switch module should be powered up before or at the same time as the C30. Otherwise, the switch module will not be detected on power up and the EQUIPMENT MISMATCH: ORDERCODE XXX self-test warning will be issued. 3.4.2 MANAGED ETHERNET SWITCH MODULE HARDWARE

NOTE

The type 2S and 2T managed Ethernet switch modules provide two 10/100Base-T and four multimode ST 100Base-FX external Ethernet ports accessible through the rear of the module. In addition, a serial console port is accessible from the front of the module (requires the front panel faceplate to be open). The pin assignment for the console port signals is shown in the following table. Table 36: CONSOLE PORT PIN ASSIGNMENT
PIN 1 2 3 4 5 6 to 9 SIGNAL CD RXD TXD N/A GND N/A DESCRIPTION Carrier detect (not used) Receive data (input) Transmit data (output) Not used Signal ground Not used

Two 10/100Base-T ports

Four 100Base-FX multimode ports with ST connectors

RS232 console port

Independent power supply. Options: 2S: high-voltage 2T: low-voltage

FRONT VIEW

REAR VIEW

842867A2.CDR

Figure 344: MANAGED ETHERNET SWITCHES HARDWARE

3-38

C30 Controller System

GE Multilin

3 HARDWARE The wiring for the managed Ethernet switch module is shown below.
Rx1 Rx2 Rx1 Rx1

3.4 MANAGED ETHERNET SWITCH MODULES

100Base-FX 100Base-FX 100Base-FX 100Base-FX

MM fiber optic cable MM fiber optic cable MM fiber optic cable 100Base-T cable 100Base-T cable 110 to 250 V DC 100 to 240 V AC

Tx2 Tx1 Tx1

Fiber ports

10/100Base-T 10/100Base-T

Copper ports CPU Power supply

+ W1a W2b W1a GROUND

842835A1.CDR

Figure 345: MANAGED ETHERNET SWITCH MODULE WIRING 3.4.3 MANAGED SWITCH LED INDICATORS The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status. The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX ports have one LED to indicate linkup and activity.

2S / 2T

MM fiber optic cable

Tx1

Connection speed indicator (OFF = 10 Mbps; ON = 100 Mbps) Link indicator (ON = link active; FLASHING = activity) Duplex mode indicator (OFF = half-duplex; ON = full-duplex)

Link indicator (ON = link active; FLASHING = activity)

842868A2.CDR

Figure 346: ETHERNET SWITCH LED INDICATORS 3.4.4 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE A suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. The Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your network administrator to determine if the default IP address, subnet mask or default gateway needs to be modified. Do not connect to network while configuring the switch module.
CAUTION

GE Multilin

C30 Controller System

3-39

3.4 MANAGED ETHERNET SWITCH MODULES a) CONFIGURING THE SWITCH MODULE IP SETTINGS

3 HARDWARE

In our example configuration of both the Switchs IP address and subnet mask must be changed to 3.94.247.229 and 255.255.252.0 respectively. The IP address, subnet mask and default gateway can be configured using either EnerVista UR Setup software, the Switchs Secure Web Management (SWM), or through the console port using CLI. 1. Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item to open the Ethernet switch configuration window.

2.

Enter 3.94.247.229 in the IP Address field and 255.255.252.0 in the Subnet Mask field, then click OK. The software will send the new settings to the C30 and prompt as follows when complete.

3.

Cycle power to the C30 and switch module to activate the new settings.

b) SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE The C30 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file contains the advanced configuration details for the switch not contained within the standard C30 settings file. This feature allows the switch module settings to be saved locally before performing firmware upgrades. Saving settings files is also highly recommended before making any change to the module configuration or creating new setting files. The following procedure describes how to save local settings files for the Ethernet switch module. 1. 2. Select the desired device from site tree in the online window. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File > Retreive Settings File item from the device settings tree.

3-40

C30 Controller System

GE Multilin

3 HARDWARE

3.4 MANAGED ETHERNET SWITCH MODULES

The system will request the name and destination path for the settings file.

3.

Enter an appropriate folder and file name and click Save.

All settings files will be saved as text files and the corresponding file extension automatically assigned. c) UPLOADING ETHERNET SWITCH SETTINGS FILES TO THE MODULE The following procedure describes how to upload local settings files to the Ethernet switch module. It is highly recommended that the current settings are saved to a settings file before uploading a new settings file. It is highly recommended to place the switch offline while transferring setting files to the switch. When transferring settings files from one switch to another, the user must reconfigure the IP address.
NOTE

1. 2.

Select the desired device from site tree in the online window. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File > Transfer Settings File item from the device settings tree. The system will request the name and destination path for the settings file.

3.

Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open.

The settings file will be transferred to the Ethernet switch and the settings uploaded to the device.

GE Multilin

C30 Controller System

3-41

3.4 MANAGED ETHERNET SWITCH MODULES

3 HARDWARE 3.4.5 UPLOADING C30 SWITCH MODULE FIRMWARE

a) DESCRIPTION This section describes the process for upgrading firmware on a UR-2S or UR-2T switch module. There are several ways of updating firmware on a switch module: Using the EnerVista UR Setup software. Serially using the C30 switch module console port. Using FTP or TFTP through the C30 switch module console port.

It is highly recommended to use the EnerVista UR Setup software to upgrade firmware on a C30 switch module. Firmware upgrades using the serial port, TFTP, and FTP are described in detail in the switch module manual.

NOTE

b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch 1. Log into the switch using the EnerVista web interface. The default switch login ID is manager and the default password is manager.
NOTE

The firmware version installed on the switch will appear on the lower left corner of the screen.

Version: 2.1 beta

842869A1.CDR

2.

Using the EnerVista UR Setup program, select the Settings > Product Setup > Communications > Ethernet Switch > Firmware Upload menu item.

3-42

C30 Controller System

GE Multilin

3 HARDWARE

3.4 MANAGED ETHERNET SWITCH MODULES

The following popup screen will appear warning that the settings will be lost when the firmware is upgraded.

It is highly recommended that you save the switch settings before upgrading the firmware.
NOTE

3.

After saving the settings file, proceed with the firmware upload by selecting Yes to the above warning. Another window will open, asking you to point to the location of the firmware file to be uploaded.

4.

Select the firmware file to be loaded on to the Switch, and select the Open option.

The following window will pop up, indicating that the firmware file transfer is in progress.

If the firmware load was successful, the following window will appear:

Note

GE Multilin

C30 Controller System

3-43

3.4 MANAGED ETHERNET SWITCH MODULES The switch will automatically reboot after a successful firmware file transfer.
NOTE

3 HARDWARE

5.

Once the firmware has been successfully uploaded to the switch module, load the settings file using the procedure described earlier. 3.4.6 ETHERNET SWITCH SELF-TEST ERRORS

The following table provides details about Ethernet module self-test errors. Be sure to enable the ETHERNET SWITCH FAIL setting in the PRODUCT SETUP USER-PROGRAMMABLE SELF-TESTS menu COMMUNICATIONS ETHand the relevant PORT 1 EVENTS through PORT 6 EVENTS settings under the PRODUCT SETUP ERNET SWITCH menu.

Table 37: ETHERNET SWITCH SELF-TEST ERRORS


ACTIVATION SETTING (SET AS ENABLED) ETHERNET SWITCH FAIL EVENT NAME ETHERNET MODULE OFFLINE EVENT CAUSE No response has been received from the Ethernet module after five successive polling attempts. POSSIBLE CAUSES Loss of switch power. IP/gateway/subnet. Incompatibility between the CPU and the switch module. UR port (port 7) configured incorrectly or blocked Switch IP address assigned to another device in the same network. Ethernet connection broken. An inactive ports events have been enabled. The C30 failed to see the switch module on power-up, because switch wont power up or is still powering up. To clear the fault, cycle power to the C30.

PORT 1 EVENTS to PORT 6 EVENTS No setting required; the C30 will read the state of a general purpose input/output port on the main CPU upon power-up and create the error if there is a conflict between the input/ output state and the order code.

ETHERNET PORT 1 OFFLINE to ETHERNET PORT 6 OFFLINE EQUIPMENT MISMATCH: Card XXX Missing

An active Ethernet port has returned a FAILED status. The C30 has not detected the presence of the Ethernet switch via the bus board.

3-44

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4.1.1 INTRODUCTION

4 HUMAN INTERFACES 4.1ENERVISTA UR SETUP SOFTWARE INTERFACE

The EnerVista UR Setup software provides a graphical user interface (GUI) as one of two human interfaces to a UR device. The alternate human interface is implemented via the devices faceplate keypad and display (refer to the Faceplate interface section in this chapter). The EnerVista UR Setup software provides a single facility to configure, monitor, maintain, and trouble-shoot the operation of relay functions, connected over local or wide area communication networks. It can be used while disconnected (off-line) or connected (on-line) to a UR device. In off-line mode, settings files can be created for eventual downloading to the device. In on-line mode, you can communicate with the device in real-time. The EnerVista UR Setup software, provided with every C30 relay, can be run from any computer supporting Microsoft Windows 95, 98, NT, 2000, ME, and XP. This chapter provides a summary of the basic EnerVista UR Setup software interface features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software interface. 4.1.2 CREATING A SITE LIST To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerVista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the C30 section in Chapter 1 for details. 4.1.3 ENERVISTA UR SETUP OVERVIEW a) ENGAGING A DEVICE The EnerVista UR Setup software may be used in on-line mode (relay connected) to directly communicate with the C30 relay. Communicating relays are organized and grouped by communication interfaces and into sites. Sites may contain any number of relays selected from the UR-series of relays. b) USING SETTINGS FILES The EnerVista UR Setup software interface supports three ways of handling changes to relay settings: In off-line mode (relay disconnected) to create or edit relay settings files for later download to communicating relays. While connected to a communicating relay to directly modify any relay settings via relay data view windows, and then save the settings to the relay. You can create/edit settings files and then write them to the relay while the interface is connected to the relay.

Settings files are organized on the basis of file names assigned by the user. A settings file contains data pertaining to the following types of relay settings: Device definition Product setup FlexLogic Control elements Inputs/outputs Testing

Factory default values are supplied and can be restored after any changes. The following communications settings are not transferred to the C30 with settings files. Modbus Slave Address Modbus IP Port Number RS485 COM1 Baud Rate RS485 COM1 Parity COM1 Minimum Response Time RS485 COM2 Baud Rate RS485 COM2 Parity

GE Multilin

C30 Controller System

4-1

4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE COM2 Minimum Response Time COM2 Selection RRTD Slave Address RRTD Baud Rate IP Address IP Subnet Mask Gateway IP Address Ethernet Sub Module Serial Number Network Address NSAP IEC61850 Config GOOSE ConfRev c) CREATING AND EDITING FLEXLOGIC

4 HUMAN INTERFACES

You can create or edit a FlexLogic equation in order to customize the relay. You can subsequently view the automatically generated logic diagram. d) VIEWING ACTUAL VALUES

You can view real-time relay data such as input/output status and measured parameters. e) VIEWING TRIGGERED EVENTS While the interface is in either on-line or off-line mode, you can view and analyze data generated by triggered specified parameters, via one of the following: Event Recorder facility: The event recorder captures contextual data associated with the last 1024 events, listed in chronological order from most recent to oldest. Oscillography facility: The oscillography waveform traces and digital states are used to provide a visual display of power system and relay operation data captured during specific triggered events.

f) FILE SUPPORT Execution: Any EnerVista UR Setup file which is double clicked or opened will launch the application, or provide focus to the already opened application. If the file was a settings file (has a URS extension) which had been removed from the Settings List tree menu, it will be added back to the Settings List tree menu. Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop target for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any Windows Explorer directory folder are each mutually a file drag source and drop target. New files which are dropped into the Settings List window are added to the tree which is automatically sorted alphabetically with respect to settings file names. Files or individual menu items which are dropped in the selected device menu in the Site List window will automatically be sent to the on-line communicating device. g) FIRMWARE UPGRADES The firmware of a C30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The corresponding instructions are provided by the EnerVista UR Setup Help file under the topic Upgrading Firmware. Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default values, minimum/maximum values, data type, and item size) may change slightly from version to version of firmware. The addresses are rearranged when new features are added or existing features are enhanced or modified. The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable, self-test message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This message does not signal any problems when appearing after firmware upgrades.

NOTE

4-2

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4.1.4 ENERVISTA UR SETUP MAIN WINDOW

The EnerVista UR Setup software main window supports the following primary display components: 1. 2. 3. 4. 5. 6. 7. 8. 9. Title bar which shows the pathname of the active data view. Main window menu bar. Main window tool bar. Site list control bar window. Settings list control bar window. Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar.

10. Quick action hot links.

3 10 4

842786A2.CDR

Figure 41: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW

GE Multilin

C30 Controller System

4-3

4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4.2EXTENDED ENERVISTA UR SETUP FEATURES

4 HUMAN INTERFACES 4.2.1 SETTINGS TEMPLATES

Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An example of this is a substation that has ten similar feeders protected by ten UR-series F60 relays. In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows engineers to configure and test these common settings, then lock them so they are not available to users. For example, these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate on the specific settings. The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers installing the devices. These will be settings such as protection element pickup values and CT and VT ratios. The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings templates can be applied to both settings files (settings file templates) and online devices (online settings templates). The functionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the C30 firmware are at versions 5.40 or higher.
NOTE

a) ENABLING THE SETTINGS TEMPLATE The settings file template feature is disabled by default. The following procedure describes how to enable the settings template for UR-series settings files. 1. 2. Select a settings file from the offline window of the EnerVista UR Setup main screen. Right-click on the selected device or settings file and select the Template Mode > Create Template option.

The settings file template is now enabled and the file tree displayed in light blue. The settings file is now in template editing mode. Alternatively, the settings template can also be applied to online settings. The following procedure describes this process. 1. 2. Select an installed device from the online window of the EnerVista UR Setup main screen. Right-click on the selected device and select the Template Mode > Create Template option.

The software will prompt for a template password. This password is required to use the template feature and must be at least four characters in length. 3. Enter and re-enter the new password, then click OK to continue.

The online settings template is now enabled. The device is now in template editing mode. b) EDITING THE SETTINGS TEMPLATE The settings template editing feature allows the user to specify which settings are available for viewing and modification in EnerVista UR Setup. By default, all settings except the FlexLogic equation editor settings are locked. 1. 2. 3. 4. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable.

4-4

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the phase time overcurrent settings window in edit mode.

Figure 42: SETTINGS TEMPLATE VIEW, ALL SETTINGS SPECIFIED AS LOCKED 5. Specify which settings to make viewable by clicking on them. The setting available to view will be displayed against a yellow background as shown below.

Figure 43: SETTINGS TEMPLATE VIEW, TWO SETTINGS SPECIFIED AS EDITABLE 6. 7. Click on Save to save changes to the settings template. Proceed through the settings tree to specify all viewable settings.

c) ADDING PASSWORD PROTECTION TO A TEMPLATE It is highly recommended that templates be saved with password protection to maximize security. The following procedure describes how to add password protection to a settings file template. 1. 2. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option.

GE Multilin

C30 Controller System

4-5

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

4 HUMAN INTERFACES

The software will prompt for a template password. This password must be at least four characters in length.

3.

Enter and re-enter the new password, then click OK to continue.

The settings file template is now secured with password protection. When templates are created for online settings, the password is added during the initial template creation step. It does not need to be added after the template is created.
NOTE

d) VIEWING THE SETTINGS TEMPLATE

Once all necessary settings are specified for viewing, users are able to view the settings template on the online device or settings file. There are two ways to specify the settings view with the settings template feature: Display only those settings available for editing. Display all settings, with settings not available for editing greyed-out.

Use the following procedure to only display settings available for editing. 1. 2. 3. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen. Apply the template by selecting the Template Mode > View In Template Mode option. Enter the template password then click OK to apply the template.

Once the template has been applied, users will only be able to view and edit the settings specified by the template. The effect of applying the template to the phase time overcurrent settings is shown below.

Phase time overcurrent settings window without template applied.

Phase time overcurrent window with template applied via the Template Mode > View In Template Mode command. The template specifies that only the Pickup and Curve settings be available.
842858A1.CDR

Figure 44: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND

4-6

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain editable settings. The effect of applying the template to a typical settings tree view is shown below.

Typical settings tree view without template applied.

Typical settings tree view with template applied via the Template Mode > View In Template Mode command.
842860A1.CDR

Figure 45: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND Use the following procedure to display settings available for editing and settings locked by the template. 1. 2. 3. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen. Apply the template by selecting the Template Mode > View All Settings option. Enter the template password then click OK to apply the template.

Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.

Phase time overcurrent settings window without template applied.

Phase time overcurrent window with template applied via the Template Mode > View All Settings command. The template specifies that only the Pickup and Curve settings be available.
842859A1.CDR

Figure 46: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND e) REMOVING THE SETTINGS TEMPLATE It may be necessary at some point to remove a settings template. Once a template is removed, it cannot be reapplied and it will be necessary to define a new settings template. 1. 2. 3. Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue.

GE Multilin

C30 Controller System

4-7

4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4. Verify one more time that you wish to remove the template by clicking Yes.

4 HUMAN INTERFACES

The EnerVista software will remove all template information and all settings will be available. 4.2.2 SECURING AND LOCKING FLEXLOGIC EQUATIONS The UR allows users to secure parts or all of a FlexLogic equation, preventing unauthorized viewing or modification of critical FlexLogic applications. This is accomplished using the settings template feature to lock individual entries within FlexLogic equations. Secured FlexLogic equations will remain secure when files are sent to and retrieved from any UR-series device. a) LOCKING FLEXLOGIC EQUATION ENTRIES

The following procedure describes how to lock individual entries of a FlexLogic equation. 1. 2. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the settings template feature. Select the FlexLogic > FlexLogic Equation Editor settings menu item. By default, all FlexLogic entries are specified as viewable and displayed against a yellow background. The icon on the upper right of the window will also indicate that EnerVista UR Setup is in EDIT mode. 3. Specify which entries to lock by clicking on them. The locked entries will be displayed against a grey background as shown in the example below.

Figure 47: LOCKING FLEXLOGIC ENTRIES IN EDIT MODE 4. 5. 6. Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation.

4-8

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

Once the template has been applied, users will only be able to view and edit the FlexLogic entries not locked by the template. The effect of applying the template to the FlexLogic entries in the above procedure is shown below.

Typical FlexLogic entries without template applied.

Typical FlexLogic entries locked with template via the Template Mode > View In Template Mode command.
842861A1.CDR

Figure 48: LOCKING FLEXLOGIC ENTRIES THROUGH SETTING TEMPLATES The FlexLogic entries are also shown as locked in the graphical view (as shown below) and on the front panel display.

Figure 49: SECURED FLEXLOGIC IN GRAPHICAL VIEW b) LOCKING FLEXLOGIC EQUATIONS TO A SERIAL NUMBER A settings file and associated FlexLogic equations can also be locked to a specific UR serial number. Once the desired FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. 1. 2. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item.

GE Multilin

C30 Controller System

4-9

4.2 EXTENDED ENERVISTA UR SETUP FEATURES The following window is displayed.

4 HUMAN INTERFACES

Figure 410: TYPICAL SETTINGS FILE PROPERTIES WINDOW

3.

Enter the serial number of the C30 device to lock to the settings file in the Serial # Lock field.

The settings file and corresponding secure FlexLogic equations are now locked to the C30 device specified by the serial number. 4.2.3 SETTINGS FILE TRACEABILITY A traceability feature for settings files allows the user to quickly determine if the settings in a C30 device have been changed since the time of installation from a settings file. When a settings file is transfered to a C30 device, the date, time, and serial number of the C30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This information can be compared with the C30 actual values at any later date to determine if security has been compromised. The traceability information is only included in the settings file if a complete settings file is either transferred to the C30 device or obtained from the C30 device. Any partial settings transfers by way of drag and drop do not add the traceability information to the settings file.

SETTINGS FILE TRANSFERRED TO UR-SERIES DEVICE

The serial number and last setting change date are stored in the UR-series device.

The serial number of the UR-series device and the file transfer date are added to the settings file when settings files are transferred to the device. Compare transfer dates in the settings file and the UR-series device to determine if security has been compromised.

SERIAL NUMBER AND TRANSFER DATE SENT BACK TO ENERVISTA AND ADDED TO SETTINGS FILE.

842864A1.CDR

Figure 411: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows.

4-10

C30 Controller System

GE Multilin

4 HUMAN INTERFACES 1. 2.

4.2 EXTENDED ENERVISTA UR SETUP FEATURES

The transfer date of a setting file written to a C30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes have been made to the relay configuration since the settings file was saved.

a) SETTINGS FILE TRACEABILITY INFORMATION The serial number and file transfer date are saved in the settings files when they sent to an C30 device. The C30 serial number and file transfer date are included in the settings file device definition within the EnerVista UR Setup offline window as shown in the example below.

Traceability data in settings file device definition

4
842863A1.CDR

Figure 412: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below.

Traceability data in settings report

842862A1.CDR

Figure 413: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA

GE Multilin

C30 Controller System

4-11

4.2 EXTENDED ENERVISTA UR SETUP FEATURES b) ONLINE DEVICE TRACEABILITY INFORMATION

4 HUMAN INTERFACES

The C30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.

Traceability data in online device actual values page

842865A1.CDR

Figure 414: TRACEABILITY DATA IN ACTUAL VALUES WINDOW This infomormation if also available from the front panel display through the following actual values:
ACTUAL VALUES ACTUAL VALUES PRODUCT INFO PRODUCT INFO MODEL INFORMATION MODEL INFORMATION SERIAL NUMBER LAST SETTING CHANGE

c) ADDITIONAL TRACEABILITY RULES

The following additional rules apply for the traceability feature If the user changes any settings within the settings file in the offline window, then the traceability information is removed from the settings file. If the user creates a new settings file, then no traceability information is included in the settings file. If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file.

4-12

C30 Controller System

GE Multilin

4 HUMAN INTERFACES 4.3FACEPLATE INTERFACE a) ENHANCED FACEPLATE

4.3 FACEPLATE INTERFACE 4.3.1 FACEPLATE

The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional userprogrammable pushbuttons. The faceplate is hinged to allow easy access to the removable modules.

Five column LED indicator panel

Display Keypad

4
Front panel RS232 port

User-programmable pushbuttons 1 to 16
Figure 415: UR-SERIES ENHANCED FACEPLATE b) STANDARD FACEPLATE

842810A1.CDR

The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional userprogrammable pushbuttons. The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal arrangement of the faceplate panels.
LED panel 1 LED panel 2 LED panel 3

Front panel RS232 port

Display

Small user-programmable (control) pushbuttons 1 to 7

User-programmable pushbuttons 1 to 12

Keypad
827801A7.CDR

Figure 416: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS

GE Multilin

C30 Controller System

4-13

4.3 FACEPLATE INTERFACE

4 HUMAN INTERFACES

The following figure shows the vertical arrangement of the faceplate panels for relays ordered with the vertical option.

DISPLAY

MENU

HELP

MESSAGE

ESCAPE

KEYPAD

ENTER

VALUE

+/-

LED PANEL 3

4
STATUS

LED PANEL 2
EVENT CAUSE VOLTAGE CURRENT FREQUENCY OTHER PHASE A PHASE B PHASE C NEUTRAL/GROUND

IN SERVICE TROUBLE TEST MODE TRIP ALARM PICKUP

RESET USER 1 USER 2 USER 3

LED PANEL 1

Figure 417: UR-SERIES STANDARD VERTICAL FACEPLATE PANELS 4.3.2 LED INDICATORS a) ENHANCED FACEPLATE The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event cause LEDs, and the next four columns contain the 48 user-programmable LEDs. The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions can also be reset via the SETTINGS INPUT/OUTPUTS RESETTING menu). The RS232 port is intended for connection to a portable PC. The USER keys are not used in this unit.

Figure 418: TYPICAL LED INDICATOR PANEL FOR ENHANCED FACEPLATE The status indicators in the first column are described below. IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed.

827830A1.CDR

842811A1.CDR

4-14

C30 Controller System

GE Multilin

4 HUMAN INTERFACES TROUBLE: This LED indicates that the relay has detected an internal problem. TEST MODE: This LED indicates that the relay is in test mode.

4.3 FACEPLATE INTERFACE

TRIP: This LED indicates that the FlexLogic operand serving as a trip switch has operated. This indicator always latches; as such, a reset command must be initiated to allow the latch to be reset. ALARM: This LED indicates that the FlexLogic operand serving as an alarm switch has operated. This indicator is never latched. PICKUP: This LED indicates that an element is picked up. This indicator is never latched.

The event cause indicators in the first column are described below. Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either Enabled or Latched. If a protection element target setting is Enabled, then the corresponding event cause LEDs remain on as long as operate operand associated with the element remains asserted. If a protection element target setting is Latched, then the corresponding event cause LEDs turn on when the operate operand associated with the element is asserted and remain on until the RESET button on the front panel is pressed after the operand is reset. All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate operands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs. VOLTAGE: This LED indicates voltage was involved. CURRENT: This LED indicates current was involved. FREQUENCY: This LED indicates frequency was involved. OTHER: This LED indicates a composite function was involved. PHASE A: This LED indicates phase A was involved. PHASE B: This LED indicates phase B was involved. PHASE C: This LED indicates phase C was involved. NEUTRAL/GROUND: This LED indicates that neutral or ground was involved. In the C30 Controller System, only the OTHER indicator is applicable and indicates that a digital element was involved.
NOTE

The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is userdefined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label package of every C30, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels. b) STANDARD FACEPLATE The standard faceplate consists of three panels with LED indicators, keys, and a communications port. The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions INPUT/OUTPUTS RESETTING menu). The RS232 port is intended for connection can also be reset via the SETTINGS to a portable PC. The USER keys are not used in this unit.

GE Multilin

C30 Controller System

4-15

4.3 FACEPLATE INTERFACE

4 HUMAN INTERFACES

STATUS

EVENT CAUSE VOLTAGE CURRENT FREQUENCY OTHER PHASE A PHASE B PHASE C NEUTRAL/GROUND

IN SERVICE TROUBLE TEST MODE TRIP ALARM PICKUP

RESET USER 1 USER 2 USER 3

842781A1.CDR

Figure 419: LED PANEL 1 STATUS INDICATORS: IN SERVICE: Indicates that control power is applied; all monitored inputs/outputs and internal systems are OK; the relay has been programmed. TROUBLE: Indicates that the relay has detected an internal problem. TEST MODE: Indicates that the relay is in test mode. TRIP: Indicates that the selected FlexLogic operand serving as a Trip switch has operated. This indicator always latches; the reset command must be initiated to allow the latch to be reset. ALARM: Indicates that the selected FlexLogic operand serving as an Alarm switch has operated. This indicator is never latched. PICKUP: Indicates that an element is picked up. This indicator is never latched.

EVENT CAUSE INDICATORS: Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either Enabled or Latched. If a protection element target setting is Enabled, then the corresponding event cause LEDs remain on as long as operate operand associated with the element remains asserted. If a protection element target setting is Latched, then the corresponding event cause LEDs turn on when the operate operand associated with the element is asserted and remain on until the RESET button on the front panel is pressed after the operand is reset. All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate operands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs. VOLTAGE: Not used. CURRENT: Not used. FREQUENCY: Not used. OTHER: Indicates a digital element was involved. PHASE A: Not used. PHASE B: Not used. PHASE C: Not used. NEUTRAL/GROUND: Not used.

USER-PROGRAMMABLE INDICATORS: The second and third provide 48 amber LED indicators whose operation is controlled by the user. Support for applying a customized label beside every LED is provided. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program the operation of the LEDs on these panels.

4-16

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.3 FACEPLATE INTERFACE

USER-PROGRAMMABLE LEDS

USER-PROGRAMMABLE LEDS

842782A1.CDR

Figure 420: LED PANELS 2 AND 3 (INDEX TEMPLATE) DEFAULT LABELS FOR LED PANEL 2: The default labels are intended to represent: GROUP 1...6: The illuminated GROUP is the active settings group. Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support six setting groups. For convenience of users using earlier firmware revisions, the relay panel shows eight setting groups. Please note that the LEDs, despite their default labels, are fully user-programmable.

NOTE

The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in the following section. 4.3.3 CUSTOM LABELING OF LEDS a) ENHANCED FACEPLATE The following procedure requires the pre-requisites listed below. EnerVista UR Setup software is installed and operational. The C30 settings have been saved to a settings file. The C30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http:// www.GEindustrial.com/multilin/support/ur and printed. Small-bladed knife.

This procedure describes how to create custom LED labels for the enhanced front panel display. 1. Start the EnerVista UR Setup software.

GE Multilin

C30 Controller System

4-17

4.3 FACEPLATE INTERFACE 2.

4 HUMAN INTERFACES

Select the Front Panel Report item at the bottom of the menu tree for the settings file. The front panel report window will be displayed.

4
Figure 421: FRONT PANEL REPORT WINDOW 3. 4. 5. 6. Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the C30 front panel label cutout sheet into a printer and press the Print button in the front panel report window. When printing is complete, fold the sheet along the perforated lines and punch out the labels. Remove the C30 label insert tool from the package and bend the tabs as described in the following procedures. These tabs will be used for removal of the default and custom LED labels. It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part number facing the user.
NOTE

The label package shipped with every C30 contains the three default labels shown below, the custom label template sheet, and the label removal tool. If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match them. If you require custom labels, follow the procedures below to remove the original labels and insert the new ones. The following procedure describes how to setup and use the label removal tool. 1. Bend the tabs at the left end of the tool upwards as shown below.

4-18

C30 Controller System

GE Multilin

4 HUMAN INTERFACES 2. Bend the tab at the center of the tool tail as shown below.

4.3 FACEPLATE INTERFACE

The following procedure describes how to remove the LED labels from the C30 enhanced front panel and insert the custom labels. 1. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from the relay.

2.

Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED label.

GE Multilin

C30 Controller System

4-19

4.3 FACEPLATE INTERFACE 3. Remove the tool and attached LED label as shown below.

4 HUMAN INTERFACES

4.

Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below.

The following procedure describes how to remove the user-programmable pushbutton labels from the C30 enhanced front panel and insert the custom labels. 1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the bent tab is pointing away from the relay.

4-20

C30 Controller System

GE Multilin

4 HUMAN INTERFACES 2.

4.3 FACEPLATE INTERFACE

Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label.

3.

Remove the tool and attached user-programmable pushbutton label as shown below.

GE Multilin

C30 Controller System

4-21

4.3 FACEPLATE INTERFACE 4.

4 HUMAN INTERFACES

Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the buttons, as shown below.

4
b) STANDARD FACEPLATE Custom labeling of an LED-only panel is facilitated through a Microsoft Word file available from the following URL: http://www.GEindustrial.com/multilin/support/ur/ This file provides templates and instructions for creating appropriate labeling for the LED panel. The following procedures are contained in the downloadable file. The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. 1. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014).

F60

FEEDER MANAGEMENT RELAY

Push in and gently lift up the cover.


842771A1.CDR

2.

Pop out the LED module and/or the blank module with a screwdriver as shown below. Be careful not to damage the plastic covers.

( LED MODULE )

( BLANK MODULE )

F60

FEEDER MANAGEMENT RELAY

842722A1.CDR

3. 4.

Place the left side of the customized module back to the front panel frame, then snap back the right side. Put the clear Lexan front cover back into place.

4-22

C30 Controller System

GE Multilin

4 HUMAN INTERFACES The following items are required to customize the C30 display module: Black and white or color printer (color preferred). Microsoft Word 97 or later software for editing the template.

4.3 FACEPLATE INTERFACE

1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069), and a custom module cover (GE Multilin Part Number: 1502-0015).

The following procedure describes how to customize the C30 display module: 1. 2. 3. 4. 5. Open the LED panel customization template with Microsoft Word. Add text in places of the LED x text placeholders on the template(s). Delete unused place holders as required. When complete, save the Word file to your local PC for future use. Print the template(s) to a local printer. From the printout, cut-out the Background Template from the three windows, using the cropmarks as a guide. Put the Background Template on top of the custom display module (GE Multilin Part Number: 1513-0069) and snap the clear custom module cover (GE Multilin Part Number: 1502-0015) over it and the templates. 4.3.4 DISPLAY All messages are displayed on a 2 20 backlit liquid crystal display (LCD) to make them visible under poor lighting conditions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad and display are not actively being used, the display will default to user-defined messages. Any high priority event driven message will automatically override the default message and appear on the display. 4.3.5 KEYPAD Display messages are organized into pages under the following headings: actual values, settings, commands, and targets. The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups. The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alternatively, values may also be entered with the numeric keypad. The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values. 4.3.6 BREAKER CONTROL a) INTRODUCTION The C30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic operand. A setting is provided to assign names to each breaker; this user-assigned name is used for the display of related flash messages. These features are provided for two breakers; the user may use only those portions of the design relevant to a single breaker, which must be breaker 1. For the following discussion it is assumed the SETTINGS FUNCTION setting is "Enabled" for each breaker. b) CONTROL MODE SELECTION AND MONITORING Installations may require that a breaker is operated in the three-pole only mode (3-pole), or in the one and three-pole (1pole) mode, selected by setting. If the mode is selected as three-pole, a single input tracks the breaker open or closed position. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be in agreement to indicate the position of the breaker.
SYSTEM SETUP For the following discussion it is assumed the SETTINGS 1(2) PUSH BUTTON CONTROL setting is Enabled for each breaker. BREAKERS BREAKER 1(2) BREAKER SYSTEM SETUP BREAKERS BREAKER 1(2) BREAKER

GE Multilin

C30 Controller System

4-23

4.3 FACEPLATE INTERFACE c) FACEPLATE (USER KEY) CONTROL

4 HUMAN INTERFACES

After the 30 minute interval during which command functions are permitted after a correct command password, the user cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state. d) CONTROL OF TWO BREAKERS For the following example setup, the (Name) field represents the user-programmed variable name. For this application (setup shown below), the relay is connected and programmed for both breaker 1 and breaker 2. The USER 1 key performs the selection of which breaker is to be operated by the USER 2 and USER 3 keys. The USER 2 key is used to manually close the breaker and the USER 3 key is used to manually open the breaker. ENTER COMMAND PASSWORD This message appears when the USER 1, USER 2, or USER 3 key is pressed and a is required; i.e. if COMMAND PASSWORD is enabled and no commands have been issued within the last 30 minutes.

COMMAND PASSWORD

Press USER 1 To Select Breaker

This message appears if the correct password is entered or if none is required. This message will be maintained for 30 seconds or until the USER 1 key is pressed again. This message is displayed after the USER 1 key is pressed for the second time. Three possible actions can be performed from this state within 30 seconds as per items (1), (2) and (3) below: If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is pressed again within that time, a signal is created that can be programmed to operate an output relay to close breaker 1. If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is pressed again within that time, a signal is created that can be programmed to operate an output relay to open breaker 1. If the USER 1 key is pressed at this step, this message appears showing that a different breaker is selected. Three possible actions can be performed from this state as per (1), (2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers. Pressing keys other than USER 1, 2 or 3 at any time aborts the breaker control function.

BKR1-(Name) SELECTED USER 2=CLS/USER 3=OP


(1)

USER 2 OFF/ON To Close BKR1-(Name)


(2)

USER 3 OFF/ON To Open BKR1-(Name)


(3)

BKR2-(Name) SELECTED USER 2=CLS/USER 3=OP

e) CONTROL OF ONE BREAKER For this application the relay is connected and programmed for breaker 1 only. Operation for this application is identical to that described above for two breakers. 4.3.7 MENUS a) NAVIGATION Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily followed by a header display page menu item. Each press of the MENU key advances through the following main heading pages: Actual values. Settings. Commands. Targets. User displays (when enabled).

4-24

C30 Controller System

GE Multilin

4 HUMAN INTERFACES b) HIERARCHY

4.3 FACEPLATE INTERFACE

The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double scroll bar characters ( ), while sub-header pages are indicated by single scroll bar characters ( ). The header display pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, continually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)

SETTINGS PRODUCT SETUP

PASSWORD SECURITY

ACCESS LEVEL: Restricted

SETTINGS FLEXLOGIC c) EXAMPLE MENU NAVIGATION ACTUAL VALUES STATUS Press the MENU key until the header for the first Actual Values page appears. This page contains system and relay status information. Repeatedly press the MESSAGE keys to display the other actual value headers. Press the MENU key until the header for the first page of Settings appears. This page contains settings to configure the relay.

SETTINGS PRODUCT SETUP

SETTINGS FLEXLOGIC

Press the MESSAGE DOWN key to move to the next Settings page. This page contains settings for FlexLogic. Repeatedly press the MESSAGE UP and DOWN keys to display the other setting headers and then back to the first Settings page header. From the Settings page one header (Product Setup), press the MESSAGE RIGHT key once to display the first sub-header (Password Security). Press the MESSAGE RIGHT key once more and this will display the first setting for Password Security. Pressing the MESSAGE DOWN key repeatedly will display the remaining setting messages for this sub-header. Press the MESSAGE LEFT key once to move back to the first sub-header message.

PASSWORD SECURITY ACCESS LEVEL: Restricted PASSWORD SECURITY DISPLAY PROPERTIES FLASH MESSAGE TIME: 1.0 s DEFAULT MESSAGE INTENSITY: 25%

Pressing the MESSAGE DOWN key will display the second setting sub-header associated with the Product Setup header. Press the MESSAGE RIGHT key once more and this will display the first setting for Display Properties. To view the remaining settings associated with the Display Properties subheader, repeatedly press the MESSAGE DOWN key. The last message appears as shown.

GE Multilin

C30 Controller System

4-25

4.3 FACEPLATE INTERFACE

4 HUMAN INTERFACES 4.3.8 CHANGING SETTINGS

a) ENTERING NUMERICAL DATA Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define what values are acceptable for a setting. FLASH MESSAGE TIME: 1.0 s MINIMUM: MAXIMUM: 0.5 10.0 For example, select the SETTINGS setting.
PRODUCT SETUP DISPLAY PROPERTIES FLASH

MESSAGE TIME

Press the HELP key to view the minimum and maximum values. Press the HELP key again to view the next context sensitive help message.

Two methods of editing and storing a numerical setting value are available. 0 to 9 and decimal point: The relay numeric keypad works the same as that of any electronic calculator. A number is entered one digit at a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MESSAGE LEFT key or pressing the ESCAPE key, returns the original value to the display. VALUE keys: The VALUE UP key increments the displayed value by the step value, up to the maximum value allowed. While at the maximum value, pressing the VALUE UP key again will allow the setting selection to continue upward from the minimum value. The VALUE DOWN key decrements the displayed value by the step value, down to the minimum value. While at the minimum value, pressing the VALUE DOWN key again will allow the setting selection to continue downward from the maximum value. As an example, set the flash message time setting to 2.5 seconds. Press the appropriate numeric keys in the sequence 2 . 5". The display message will change as the digits are being entered. Until ENTER is pressed, editing changes are not registered by the relay. Therefore, press ENTER to store the new value in memory. This flash message will momentarily appear as confirmation of the storing process. Numerical values which contain decimal places will be rounded-off if more decimal place digits are entered than specified by the step value.

FLASH MESSAGE TIME: 2.5 s NEW SETTING HAS BEEN STORED

b) ENTERING ENUMERATION DATA Enumeration settings have data values which are part of a set, whose members are explicitly defined by a name. A set is comprised of two or more members. ACCESS LEVEL: Restricted For example, the selections available for ACCESS LEVEL are "Restricted", "Command", "Setting", and "Factory Service".

Enumeration type values are changed using the VALUE keys. The VALUE UP key displays the next selection while the VALUE DOWN key displays the previous selection. ACCESS LEVEL: Setting NEW SETTING HAS BEEN STORED If the ACCESS LEVEL needs to be "Setting", press the VALUE keys until the proper selection is displayed. Press HELP at any time for the context sensitive help messages. Changes are not registered by the relay until the ENTER key is pressed. Pressing ENTER stores the new value in memory. This flash message momentarily appears as confirmation of the storing process.

c) ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters.

4-26

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.3 FACEPLATE INTERFACE

There are several places where text messages may be programmed to allow the relay to be customized for specific applications. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages. For example: to enter the text, Breaker #1. 1. 2. 3. 4. 5. Press the decimal to enter text edit mode. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1. Press ENTER to store the text. If you have any problem, press HELP to view context sensitive help. Flash messages will sequentially appear for several seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.

d) ACTIVATING THE RELAY RELAY SETTINGS: Not Programmed When the relay is powered up, the Trouble LED will be on, the In Service LED off, and this message displayed, indicating the relay is in the "Not Programmed" state and is safeguarding (output relays blocked) against the installation of a relay whose settings have not been entered. This message remains until the relay is explicitly put in the "Programmed" state.

To change the RELAY SETTINGS: "Not Programmed" mode to "Programmed", proceed as follows: 1. 2. 3. 4. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the display. Press the MESSAGE RIGHT key until the PASSWORD SECURITY message appears on the display. Press the MESSAGE DOWN key until the INSTALLATION message appears on the display. Press the MESSAGE RIGHT key until the RELAY SETTINGS: Not Programmed message is displayed. SETTINGS

SETTINGS PRODUCT SETUP

PASSWORD SECURITY DISPLAY PROPERTIES

INSTALLATION

RELAY SETTINGS: Not Programmed

5. 6.

After the RELAY SETTINGS: Not Programmed message appears on the display, press the VALUE keys change the selection to "Programmed". Press the ENTER key. RELAY SETTINGS: Programmed NEW SETTING HAS BEEN STORED

RELAY SETTINGS: Not Programmed 7.

When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on.

e) ENTERING INITIAL PASSWORDS The C30 supports password entry from a local or remote connection.

GE Multilin

C30 Controller System

4-27

4.3 FACEPLATE INTERFACE

4 HUMAN INTERFACES

Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords enables this functionality. To enter the initial setting (or command) password, proceed as follows: 1. 2. 3. 4. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the display. Press the MESSAGE RIGHT key until the ACCESS LEVEL message appears on the display. Press the MESSAGE DOWN key until the CHANGE LOCAL PASSWORDS message appears on the display. Press the MESSAGE RIGHT key until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message appears on the display. PASSWORD SECURITY ACCESS LEVEL: Restricted CHANGE LOCAL PASSWORDS CHANGE COMMAND PASSWORD: No CHANGE SETTING PASSWORD: No ENCRYPTED COMMAND PASSWORD: --------ENCRYPTED SETTING PASSWORD: --------5. 6. 7. 8. After the CHANGE...PASSWORD message appears on the display, press the VALUE UP or DOWN key to change the selection to Yes. Press the ENTER key and the display will prompt you to ENTER NEW PASSWORD. Type in a numerical password (up to 10 characters) and press the ENTER key. When the VERIFY NEW PASSWORD is displayed, re-type in the same password and press ENTER. CHANGE SETTING PASSWORD: No CHANGE SETTING PASSWORD: Yes ENTER NEW PASSWORD: ########## VERIFY NEW PASSWORD: ########## NEW PASSWORD HAS BEEN STORED 9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) Password will be active.

f) CHANGING EXISTING PASSWORD To change an existing password, follow the instructions in the previous section with the following exception. A message will prompt you to type in the existing password (for each security level) before a new password can be entered. In the event that a password has been lost (forgotten), submit the corresponding encrypted password from the PASSWORD SECURITY menu to the Factory for decoding. g) INVALID PASSWORD ENTRY When an incorrect command or setting password has been entered via the faceplate interface three times within a 3-minute time span, the LOCAL ACCESS DENIED FlexLogic operand will be set to On and the C30 will not allow settings or command level access via the faceplate interface for the next five minutes, or in the event that an incorrect Command Or Set-

4-28

C30 Controller System

GE Multilin

4 HUMAN INTERFACES

4.3 FACEPLATE INTERFACE

ting password has been entered via the any external communications interface three times within a 3-minute time span, the REMOTE ACCESS DENIED FlexLogic operand will be set to On and the C30 will not allow settings or command access via the any external communications interface for the next five minutes. In the event that an incorrect Command or Setting password has been entered via the any external communications interface three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic operand will be set to On and the C30 will not allow Settings or Command access via the any external communications interface for the next ten minutes. The REMOTE ACCESS DENIED FlexLogic operand will be set to Off after the expiration of the ten-minute timeout.

GE Multilin

C30 Controller System

4-29

4.3 FACEPLATE INTERFACE

4 HUMAN INTERFACES

4-30

C30 Controller System

GE Multilin

5 SETTINGS 5 SETTINGS 5.1OVERVIEW

5.1 OVERVIEW 5.1.1 SETTINGS MAIN MENU

SETTINGS PRODUCT SETUP

SECURITY DISPLAY PROPERTIES CLEAR RELAY RECORDS COMMUNICATIONS MODBUS USER MAP REAL TIME CLOCK OSCILLOGRAPHY DATA LOGGER USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE SELF TESTS CONTROL PUSHBUTTONS USER-PROGRAMMABLE PUSHBUTTONS FLEX STATE PARAMETERS USER-DEFINABLE DISPLAYS DIRECT I/O TELEPROTECTION INSTALLATION

See page 5-5. See page 5-9. See page 5-10. See page 5-11. See page 5-33. See page 5-34. See page 5-35. See page 5-37. See page 5-38. See page 5-41. See page 5-42. See page 5-43. See page 5-48. See page 5-49. See page 5-51. See page 5-59. See page 5-59.

SETTINGS SYSTEM SETUP

BREAKERS SWITCHES

See page 5-62. See page 5-66.

SETTINGS FLEXLOGIC

FLEXLOGIC EQUATION EDITOR

See page 5-81.

GE Multilin

C30 Controller System

5-1

5.1 OVERVIEW FLEXLOGIC TIMERS FLEXELEMENTS NON-VOLATILE LATCHES SETTINGS CONTROL ELEMENTS SELECTOR SWITCH DIGITAL ELEMENTS DIGITAL COUNTERS 8-BIT SWITCHES PID REGULATOR

5 SETTINGS

See page 5-81. See page 5-82. See page 5-86.

See page 5-87. See page 5-93. See page 5-96. See page 5-98.

SETTINGS INPUTS / OUTPUTS

CONTACT INPUTS VIRTUAL INPUTS CONTACT OUTPUTS VIRTUAL OUTPUTS REMOTE DEVICES REMOTE INPUTS REMOTE DPS INPUTS REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUTPUTS UserSt BIT PAIRS RESETTING DIRECT INPUTS DIRECT OUTPUTS TELEPROTECTION

See page 5-103. See page 5-105. See page 5-106. See page 5-108. See page 5-109. See page 5-110. See page 5-111. See page 5-111. See page 5-112. See page 5-112. See page 5-113. See page 5-113. See page 5-117.

5-2

C30 Controller System

GE Multilin

5 SETTINGS IEC 61850 GOOSE ANALOGS IEC 61850 GOOSE UINTEGERS SETTINGS TRANSDUCER I/O DCMA INPUTS RTD INPUTS DCMA OUTPUTS

5.1 OVERVIEW

See page 5-119. See page 5-120.

See page 5-121. See page 5-122. See page 5-124.

SETTINGS TESTING

TEST MODE FUNCTION: Disabled TEST MODE FORCING: On FORCE CONTACT INPUTS FORCE CONTACT OUTPUTS

See page 5-126. See page 5-126. See page 5-127. See page 5-128.

GE Multilin

C30 Controller System

5-3

5.1 OVERVIEW

5 SETTINGS 5.1.2 INTRODUCTION TO ELEMENTS

The main characteristics of an element are shown on the element logic diagram. This includes the inputs, settings, fixed logic, and the output operands generated (abbreviations used on scheme logic diagrams are defined in Appendix F). FUNCTION setting: This setting programs the element to be operational when selected as Enabled. The factory default is Disabled. Once programmed to Enabled, any element associated with the function becomes active and all options become available. NAME setting: This setting is used to uniquely identify the element. PICKUP DELAY setting: This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup and operate output states. RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the Operate output state and the return to logic 0 after the input transits outside the defined pickup range. BLOCK setting: The default output operand state of all comparators is a logic 0 or flag not set. The comparator remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise the comparator. The BLOCK input is used as one of the inputs to RUN control. TARGET setting: This setting is used to define the operation of an element target message. When set to Disabled, no target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to Self-Reset, the target message and LED indication follow the operate state of the element, and self-resets once the operate element condition clears. When set to Latched, the target message and LED indication will remain visible after the element output returns to logic 0 until a RESET command is received by the relay. EVENTS setting: This setting is used to control whether the pickup, dropout or operate states are recorded by the event recorder. When set to Disabled, element pickup, dropout or operate are not recorded as events. When set to Enabled, events are created for: (Element) PKP (pickup) (Element) DPO (dropout) (Element) OP (operate) The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not 0.

5-4

C30 Controller System

GE Multilin

5 SETTINGS 5.2PRODUCT SETUP a) MAIN MENU


PATH: SETTINGS PRODUCT SETUP SECURITY

5.2 PRODUCT SETUP 5.2.1 SECURITY

SECURITY

ACCESS LEVEL: Restricted


MESSAGE

Range: Restricted, Command, Setting, Factory Service (for factory use only)

CHANGE LOCAL PASSWORDS ACCESS SUPERVISION DUAL PERMISSION SECURITY ACCESS PASSWORD ACCESS EVENTS: Disabled

See page 56. See page 57. See page 58.


Range: Disabled, Enabled

MESSAGE

MESSAGE

MESSAGE

Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level is not available and intended for factory use only. The following operations are under command password supervision: Changing the state of virtual inputs. Clearing the event records. Clearing the oscillography records. Changing the date and time. Clearing the data logger. Clearing the user-programmable pushbutton states.

The following operations are under setting password supervision: Changing any setting. Test mode operation.

The command and setting passwords are defaulted to 0 when the relay is shipped from the factory. When a password is set to 0, the password security feature is disabled. The C30 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords enables this functionality. When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used. The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder. The local setting and command sessions are initiated by the user through the front panel display and are disabled either by the user or by timeout (via the setting and command level access timeout settings). The remote setting and command sessions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout. The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands. ACCESS LOC SETG OFF: Asserted when local setting access is disabled. ACCESS LOC SETG ON: Asserted when local setting access is enabled. ACCESS LOC CMND OFF: Asserted when local command access is disabled. ACCESS LOC CMND ON: Asserted when local command access is enabled.

GE Multilin

C30 Controller System

5-5

5.2 PRODUCT SETUP ACCESS REM SETG OFF: Asserted when remote setting access is disabled. ACCESS REM SETG ON: Asserted when remote setting access is enabled. ACCESS REM CMND OFF: Asserted when remote command access is disabled. ACCESS REM CMND ON: Asserted when remote command access is enabled.

5 SETTINGS

The appropriate events are also logged in the Event Recorder as well. The FlexLogic operands and events are updated every five seconds. A command or setting write operation is required to update the state of all the remote and local security operands shown above.
NOTE

b) LOCAL PASSWORDS
PATH: SETTINGS PRODUCT SETUP SECURITY CHANGE LOCAL PASSWORDS Range: No, Yes

CHANGE LOCAL PASSWORDS


MESSAGE

CHANGE COMMAND PASSWORD: No CHANGE SETTING PASSWORD: No ENCRYPTED COMMAND PASSWORD: ---------ENCRYPTED SETTING PASSWORD: ----------

Range: No, Yes

MESSAGE

Range: 0 to 9999999999 Note: ---------- indicates no password Range: 0 to 9999999999 Note: ---------- indicates no password

MESSAGE

Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters. When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to Yes via the front panel interface, the following message sequence is invoked: 1. 2. 3. ENTER NEW PASSWORD: ____________. VERIFY NEW PASSWORD: ____________. NEW PASSWORD HAS BEEN STORED.

To gain write access to a Restricted setting, program the ACCESS LEVEL setting in the main security menu to Setting and then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the password is correctly entered, access will be allowed. Accessibility automatically reverts to the Restricted level according to the access level timeout setting values. If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD. If the setting and command passwords are identical, then this one password allows access to both commands and settings.
NOTE

c) REMOTE PASSWORDS The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the Settings > Product Setup > Password Security menu item to open the remote password settings window.

Figure 51: REMOTE PASSWORD SETTINGS WINDOW Proper passwords are required to enable each command or setting level access. A command or setting password consists of 1 to 10 numerical characters and are initially programmed to 0. The following procedure describes how the set the command or setting password.

5-6

C30 Controller System

GE Multilin

5 SETTINGS 1. 2. 3. 4. Enter the new password in the Enter New Password field. Re-enter the password in the Confirm New Password field.

5.2 PRODUCT SETUP

Click the Change button. This button will not be active until the new password matches the confirmation password. If the original password is not 0, then enter the original password in the Enter Password field and click the Send Password to Device button.

5.

The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.

If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password value. d) ACCESS SUPERVISION
PATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION

ACCESS SUPERVISION
MESSAGE

ACCESS LEVEL TIMEOUTS INVALID ATTEMPTS BEFORE LOCKOUT: 3 PASSWORD LOCKOUT DURATION: 5 min
Range: 2 to 5 in steps of 1

Range: 5 to 60 minutes in steps of 1

MESSAGE

The following access supervision settings are available. INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be entered within a three-minute time span before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED or REMOTE ACCESS DENIED FlexLogic operands are set to On. These operands are returned to the Off state upon expiration of the lockout. PASSWORD LOCKOUT DURATION: This setting specifies the time that the C30 will lockout password access after the number of invalid password entries specified by the INVALID ATTEMPS BEFORE LOCKOUT setting has occurred.

The C30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic operand is asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be used to protect against both unauthorized and accidental access attempts. The UNAUTHORIZED ACCESS operand is reset with the COMMANDS CLEAR RECORDS RESET UNAUTHORIZED ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The operand does not generate events or targets. If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed with event logs or targets enabled.

GE Multilin

C30 Controller System

5-7

5.2 PRODUCT SETUP The access level timeout settings are shown below.
PATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION ACCESS LEVEL TIMEOUTS Range: 5 to 480 minutes in steps of 1

5 SETTINGS

ACCESS LEVEL TIMEOUTS


MESSAGE

COMMAND LEVEL ACCESS TIMEOUT: 5 min SETTING LEVEL ACCESS TIMEOUT: 30 min

Range: 5 to 480 minutes in steps of 1

These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note that the access level will set as restricted if control power is cycled. COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access) required to return to restricted access from the command password level. SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access) required to return to restricted access from the command password level.

e) DUAL PERMISSION SECURITY ACCESS


PATH: SETTINGS PRODUCT SETUP SECURITY DUAL PERMISSION SECURITY ACCESS Range: selected FlexLogic operands (see below)

DUAL PERMISSION SECURITY ACCESS


MESSAGE

LOCAL SETTING AUTH: On REMOTE SETTING AUTH: On ACCESS AUTH TIMEOUT: 30 min.

Range: FlexLogic operand

Range: 5 to 480 minutes in steps of 1

MESSAGE

The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended upload of settings to a relay through the local or remote interfaces interface. The following settings are available through the local (front panel) interface only. LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision. Valid values for the FlexLogic operands are either On (default) or any physical Contact Input ~~ On value. If this setting is On, then local setting access functions as normal; that is, a local setting password is required. If this setting is any contact input on FlexLogic operand, then the operand must be asserted (set as on) prior to providing the local setting password to gain setting access. If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel. REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision. If this setting is On (the default setting), then remote setting access functions as normal; that is, a remote password is required). If this setting is Off, then remote setting access is blocked even if the correct remote setting password is provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to providing the remote setting password to gain setting access. ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable when the LOCAL SETTING AUTH setting is programmed to any operand except On. The state of the FlexLogic operand is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer programmed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.

5-8

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product Setup > Security menu item to display the security settings window.

The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision. If this setting is On (the default setting), then remote setting access functions as normal; that is, a remote password is required). If this setting is Off, then remote setting access is blocked even if the correct remote setting password is provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to providing the remote setting password to gain setting access. The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable when the Remote Settings Authorization setting is programmed to any operand except On or Off. The state of the FlexLogic operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. 5.2.2 DISPLAY PROPERTIES
PATH: SETTINGS PRODUCT SETUP DISPLAY PROPERTIES

DISPLAY PROPERTIES
MESSAGE

LANGUAGE: English FLASH MESSAGE TIME: 1.0 s DEFAULT MESSAGE TIMEOUT: 300 s DEFAULT MESSAGE INTENSITY: 25 % SCREEN SAVER FEATURE: Disabled SCREEN SAVER WAIT TIME: 30 min CURRENT CUT-OFF LEVEL: 0.020 pu VOLTAGE CUT-OFF LEVEL: 1.0 V

Range: English; English, French; English, Russian; English, Chinese (range dependent on order code) Range: 0.5 to 10.0 s in steps of 0.1

Range: 10 to 900 s in steps of 1

MESSAGE

MESSAGE

Range: 25%, 50%, 75%, 100% Visible only if a VFD is installed Range: Disabled, Enabled Visible only if an LCD is installed Range: 1 to 65535 min. in steps of 1 Visible only if an LCD is installed Range: 0.002 to 0.020 pu in steps of 0.001

MESSAGE

MESSAGE

MESSAGE

Range: 0.1 to 1.0 V secondary in steps of 0.1

MESSAGE

Some relay messaging characteristics can be modified to suit different situations using the display properties settings. LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The range is dependent on the order code of the relay. FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several seconds in response to certain key presses during setting programming. These messages override any normal messages. The duration of a flash message on the display can be changed to accommodate different reading rates. DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values.

GE Multilin

C30 Controller System

5-9

5.2 PRODUCT SETUP

5 SETTINGS

DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be attenuated during default message display. During keypad interrogation, the display always operates at full brightness. SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the C30 has a liquid crystal display (LCD) and control its backlighting. When the SCREEN SAVER FEATURE is Enabled, the LCD backlighting is turned off after the DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, providing that no keys have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting is turned on. CURRENT CUT-OFF LEVEL: This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value) are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The C30 applies a cutoff value to the magnitudes and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the cut-off level for the sensitive ground input is 10 times lower that the CURRENT CUT-OFF LEVEL setting value. Raw current samples available via oscillography are not subject to cut-off. VOLTAGE CUT-OFF LEVEL: This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements (at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero, while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The C30 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by communications protocols. Raw samples of the voltages available via oscillography are not subject cut-off. Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals as valid measurements. Unless dictated otherwise by a specific application, the default settings of 0.02 pu for CURRENT CUT-OFF LEVEL and 1.0 V for VOLTAGE CUT-OFF LEVEL are recommended. 5.2.3 CLEAR RELAY RECORDS

NOTE

PATH: SETTINGS

PRODUCT SETUP

CLEAR RELAY RECORDS

CLEAR RELAY RECORDS


MESSAGE

CLEAR EVENT RECORDS: Off CLEAR OSCILLOGRAPHY? No CLEAR DATA LOGGER: Off RESET UNAUTH ACCESS: Off CLEAR DIR I/O STATS: Off

Range: FlexLogic operand

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

MESSAGE

Range: FlexLogic operand. Valid only for units with Direct I/O module.

Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programmable pushbuttons to clear specific records are typical applications for these commands. Since the C30 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect. Clearing records with user-programmable operands is not protected by the command password. However, user-programmable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programmable pushbuttons can provide extra security if required. For example, to assign User-Programmable Pushbutton 1 to clear demand records, the following settings should be applied. 1. Assign the clear demand function to Pushbutton 1 by making the following change in the SETTINGS CLEAR RELAY RECORDS menu:
CLEAR DEMAND: PUSHBUTTON 1 ON PRODUCT SETUP

5-10

C30 Controller System

GE Multilin

5 SETTINGS 2.

5.2 PRODUCT SETUP


PRODUCT

SETUP

Set the properties for User-Programmable Pushbutton 1 by making the following changes in the SETTINGS USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: Self-reset PUSHBTN 1 DROP-OUT TIME: 0.20 s

5.2.4 COMMUNICATIONS a) MAIN MENU


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS

COMMUNICATIONS

SERIAL PORTS NETWORK MODBUS PROTOCOL DNP PROTOCOL DNP / IEC104 POINT LISTS IEC 61850 PROTOCOL WEB SERVER HTTP PROTOCOL TFTP PROTOCOL IEC 60870-5-104 PROTOCOL SNTP PROTOCOL EGD PROTOCOL ETHERNET SWITCH

See below. See page 512. See page 513. See page 513. See page 516. See page 518. See page 529. See page 529. See page 530. See page 531. See page 531. See page 533.

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

GE Multilin

C30 Controller System

5-11

5.2 PRODUCT SETUP b) SERIAL PORTS


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS SERIAL PORTS

5 SETTINGS

SERIAL PORTS

RS485 COM1 BAUD RATE: 19200


MESSAGE

RS485 COM1 PARITY: None RS485 COM1 RESPONSE MIN TIME: 0 ms RS485 COM2 BAUD RATE: 19200 RS485 COM2 PARITY: None RS485 COM2 RESPONSE MIN TIME: 0 ms

Range: 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 33600, 38400, 57600, 115200. Only active if CPU Type E is ordered. Range: None, Odd, Even Only active if CPU Type E is ordered Range: 0 to 1000 ms in steps of 10 Only active if CPU Type E is ordered Range: 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 33600, 38400, 57600, 115200 Range: None, Odd, Even

MESSAGE

MESSAGE

MESSAGE

Range: 0 to 1000 ms in steps of 10

MESSAGE

The C30 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of these ports may be connected to a computer running EnerVista UR Setup. This software can download and upload setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC or PC using the RS485 ports. For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after each transmission.

NOTE

c) NETWORK
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK Range: Standard IP address format Not shown if CPU Type E is ordered. Range: Standard IP address format Not shown if CPU Type E is ordered. Range: Standard IP address format Not shown if CPU Type E is ordered. Range: Select to enter the OSI NETWORK ADDRESS. Not shown if CPU Type E is ordered. Range: Half-Duplex, Full-Duplex Not shown if CPU Type E or N is ordered.

NETWORK

IP ADDRESS: 0.0.0.0
MESSAGE

SUBNET IP MASK: 0.0.0.0 GATEWAY IP ADDRESS: 0.0.0.0 OSI NETWORK ADDRESS (NSAP) ETHERNET OPERATION MODE: Full-Duplex

MESSAGE

MESSAGE

MESSAGE

These messages appear only if the C30 is ordered with an Ethernet card. The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a setting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays behind a router). By setting a different TCP/UDP PORT NUMBER for a given protocol on each UR-series relay, the router can map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured to use the correct port number if these settings are used. When the NSAP address, any TCP/UDP port number, or any user map setting (when used with DNP) is changed, it will not become active until power to the relay has been cycled (off-on).
NOTE

5-12

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

Do not set more than one protocol to the same TCP/UDP PORT NUMBER, as this will result in unreliable operation of those protocols.
WARNING

d) MODBUS PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL Range: 1 to 254 in steps of 1

MODBUS PROTOCOL

MODBUS SLAVE ADDRESS: 254 MODBUS TCP PORT NUMBER: 502

Range: 1 to 65535 in steps of 1

MESSAGE

The serial communication ports utilize the Modbus protocol, unless configured for DNP or IEC 60870-5-104 operation (see descriptions below). This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device only. When using Modbus protocol on the RS232 port, the C30 will respond regardless of the MODBUS SLAVE ADDRESS programmed. For the RS485 ports each C30 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher address starting at 1. Refer to Appendix B for more information on the Modbus protocol. Changes to the MODBUS TCP PORT NUMBER setting will not take effect until the C30 is restarted.
NOTE

e) DNP PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL Range: see sub-menu below

DNP PROTOCOL

DNP CHANNELS DNP ADDRESS: 65519 DNP NETWORK CLIENT ADDRESSES DNP TCP/UDP PORT NUMBER: 20000 DNP UNSOL RESPONSE FUNCTION: Disabled DNP UNSOL RESPONSE TIMEOUT: 5 s DNP UNSOL RESPONSE MAX RETRIES: 10 DNP UNSOL RESPONSE DEST ADDRESS: 1 DNP CURRENT SCALE FACTOR: 1 DNP VOLTAGE SCALE FACTOR: 1 DNP POWER SCALE FACTOR: 1 DNP ENERGY SCALE FACTOR: 1

Range: 0 to 65519 in steps of 1

MESSAGE

Range: see sub-menu below

MESSAGE

Range: 1 to 65535 in steps of 1

MESSAGE

Range: Enabled, Disabled

MESSAGE

Range: 0 to 60 s in steps of 1

MESSAGE

Range: 1 to 255 in steps of 1

MESSAGE

Range: 0 to 65519 in steps of 1

MESSAGE

MESSAGE

Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000 Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000 Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000 Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000

MESSAGE

MESSAGE

MESSAGE

GE Multilin

C30 Controller System

5-13

5.2 PRODUCT SETUP DNP PF SCALE FACTOR: 1 DNP OTHER SCALE FACTOR: 1 DNP CURRENT DEFAULT DEADBAND: 30000 DNP VOLTAGE DEFAULT DEADBAND: 30000 DNP POWER DEFAULT DEADBAND: 30000 DNP ENERGY DEFAULT DEADBAND: 30000 DNP PF DEFAULT DEADBAND: 30000 DNP OTHER DEFAULT DEADBAND: 30000 DNP TIME SYNC IIN PERIOD: 1440 min DNP MESSAGE FRAGMENT SIZE: 240 DNP OBJECT 1 DEFAULT VARIATION: 2 DNP OBJECT 2 DEFAULT VARIATION: 2 DNP OBJECT 20 DEFAULT VARIATION: 1 DNP OBJECT 21 DEFAULT VARIATION: 1 DNP OBJECT 22 DEFAULT VARIATION: 1 DNP OBJECT 23 DEFAULT VARIATION: 2 DNP OBJECT 30 DEFAULT VARIATION: 1 DNP OBJECT 32 DEFAULT VARIATION: 1 DNP NUMBER OF PAIRED CONTROL POINTS: 0 DNP TCP CONNECTION TIMEOUT: 120 s

5 SETTINGS
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000 Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000 Range: 0 to 100000000 in steps of 1

MESSAGE

MESSAGE

MESSAGE

Range: 0 to 100000000 in steps of 1

MESSAGE

Range: 0 to 100000000 in steps of 1

MESSAGE

Range: 0 to 100000000 in steps of 1

MESSAGE

Range: 0 to 100000000 in steps of 1

MESSAGE

Range: 0 to 100000000 in steps of 1

MESSAGE

Range: 1 to 10080 min. in steps of 1

MESSAGE

Range: 30 to 2048 in steps of 1

MESSAGE

5
MESSAGE MESSAGE

Range: 1, 2

Range: 1, 2

Range: 1, 2, 5, 6

MESSAGE

Range: 1, 2, 9, 10

MESSAGE

Range: 1, 2, 5, 6

MESSAGE

Range: 1, 2, 5, 6

MESSAGE

Range: 1, 2, 3, 4, 5

MESSAGE

Range: 1, 2, 3, 4, 5, 7

MESSAGE

Range: 0 to 32 in steps of 1

MESSAGE

Range: 10 to 300 s in steps of 1

MESSAGE

The C30 supports the Distributed Network Protocol (DNP) version 3.0. The C30 can be used as a DNP slave device connected to multiple DNP masters (usually an RTU or a SCADA master station). Since the C30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the C30 at one time. The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the IEC 60870-5-104 FUNCTION setting is set to Enabled, the DNP protocol will not be operational. When this setting is changed it will not become active until power to the relay has been cycled (off-to-on).

NOTE

5-14

C30 Controller System

GE Multilin

5 SETTINGS The DNP Channels sub-menu is shown below.


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP CHANNELS

5.2 PRODUCT SETUP

DNP CHANNELS

DNP CHANNEL 1 PORT: NETWORK


MESSAGE

DNP CHANNEL 2 PORT: COM2 - RS485

Range: NONE, COM1 - RS485, COM2 - RS485, FRONT PANEL - RS232, NETWORK - TCP, NETWORK - UDP Range: NONE, COM1 - RS485, COM2 - RS485, FRONT PANEL - RS232, NETWORK - TCP, NETWORK - UDP

The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can be used only in non-Ethernet UR relays. When this setting is set to Network - TCP, the DNP protocol can be used over TCP/IP on channels 1 or 2. When this value is set to Network - UDP, the DNP protocol can be used over UDP/IP on channel 1 only. Refer to Appendix E for additional information on the DNP protocol. Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings will take effect only after power has been cycled to the relay.
NOTE

The DNP NETWORK CLIENT ADDRESS settings can force the C30 to respond to a maximum of five specific DNP masters. The settings in this sub-menu are shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOL DNP NETWORK CLIENT ADDRESSES

DNP NETWORK CLIENT ADDRESSES


MESSAGE

CLIENT ADDRESS 1: 0.0.0.0 CLIENT ADDRESS 2: 0.0.0.0 CLIENT ADDRESS 3: 0.0.0.0 CLIENT ADDRESS 4: 0.0.0.0 CLIENT ADDRESS 5: 0.0.0.0

Range: standard IP address

Range: standard IP address

Range: standard IP address

MESSAGE

Range: standard IP address

MESSAGE

Range: standard IP address

MESSAGE

The DNP UNSOL RESPONSE FUNCTION should be Disabled for RS485 applications since there is no collision avoidance mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the C30 waits for a DNP master to confirm an unsolicited response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the C30 retransmits an unsolicited response without receiving confirmation from the master; a value of 255 allows infinite re-tries. The DNP UNSOL RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which unsolicited responses are sent is determined by the C30 from the current TCP connection or the most recent UDP message. The DNP scale factor settings are numbers used to scale analog input point values. These settings group the C30 analog input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to 1000, all DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the C30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within certain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value will be 10 times larger). The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These settings group the C30 analog input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the default deadband value for all analog input points of that type. For example, to trigger unsolicited responses from the C30 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting should be set to 15. Note that these settings are the deadband default values. DNP object 34 points can be used to change deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and re-applied to the C30, the default deadbands will be in effect.

GE Multilin

C30 Controller System

5-15

5.2 PRODUCT SETUP

5 SETTINGS

DEADBAND
NOTE

The C30 relay does not support power metering. As such, the DNP POWER SCALE FACTOR and DNP POWER DEFAULT settings are not applicable.

The C30 relay does not support energy metering. As such, the DNP ENERGY SCALE FACTOR and DNP ENERGY DEFAULT DEADBAND settings are not applicable.
NOTE

The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the C30. Changing this time allows the DNP master to send time synchronization commands more or less often, as required. The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be necessary which can provide for more robust data transfer over noisy communication channels. When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays, check the DNP Points Lists C30 web page to view the points lists. This page can be viewed with a web browser by entering the C30 IP address to access the C30 Main Menu, then by selecting the Device Information Menu > DNP Points Lists menu item.

NOTE

The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings allow the user to select the DNP default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in appendix E for additional details. The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single physical or virtual control point in an IED. In the C30 relay, DNP binary outputs are mapped to virtual inputs. However, some legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to support the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The C30 can be configured to support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED CONTROL POINTS setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired operate on a one-to-one basis. The DNP ADDRESS setting is the DNP slave address. This number identifies the C30 on a DNP communications link. Each DNP slave should be assigned a unique address. The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be aborted by the C30. This frees up the connection to be re-used by a client. Relay power must be re-cycled after changing the DNP TCP CONNECTION TIMEOUT setting for the changes to take effect.
NOTE

f) DNP / IEC 60870-5-104 POINT LISTS


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS Range: see sub-menu below

DNP / IEC104 POINT LISTS


MESSAGE

BINARY INPUT / MSP POINTS ANALOG INPUT / MME POINTS

Range: see sub-menu below

The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning FlexLogic operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.

5-16

C30 Controller System

GE Multilin

5 SETTINGS The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS

5.2 PRODUCT SETUP

BINARY INPUT / MSP POINTS

BINARY INPUT / MSP POINTS


MESSAGE

Point: Off Point: Off

0 1

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

Point: Off

255

Range: FlexLogic operand

Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by assigning an appropriate FlexLogic operand. Refer to the Introduction to FlexLogic section in this chapter for the full range of assignable operands. The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT / MME POINTS

ANALOG INPUT / MME POINTS


MESSAGE

Point: Off Point: Off

0 1

Range: any FlexAnalog parameter

Range: any FlexAnalog parameter

MESSAGE

Point: Off

255

Range: any FlexAnalog parameter

Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is configured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the full range of assignable parameters. The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first Off value. Since DNP / IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first Off point are ignored. Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the C30 is restarted.
NOTE

NOTE

GE Multilin

C30 Controller System

5-17

5.2 PRODUCT SETUP g) IEC 61850 PROTOCOL


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL

5 SETTINGS

IEC 61850 PROTOCOL

GSSE / GOOSE CONFIGURATION SERVER CONFIGURATION IEC 61850 LOGICAL NODE NAME PREFIXES MMXU DEADBANDS GGIO1 STATUS CONFIGURATION GGIO2 CONTROL CONFIGURATION GGIO4 ANALOG CONFIGURATION GGIO5 UINTEGER CONFIGURATION REPORT CONTROL CONFIGURATION XCBR CONFIGURATION XSWI CONFIGURATION

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

5
MESSAGE MESSAGE

The C30 Controller System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.

The C30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The C30 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme. The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION

GSSE / GOOSE CONFIGURATION


MESSAGE

TRANSMISSION RECEPTION

The main transmission menu is shown below:

5-18

C30 Controller System

GE Multilin

5 SETTINGS
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL

5.2 PRODUCT SETUP


GSSE/GOOSE... TRANSMISSION

TRANSMISSION

GENERAL GSSE FIXED GOOSE CONFIGURABLE GOOSE

MESSAGE

MESSAGE

MESSAGE

The general transmission settings are shown below:


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... GSSE/GOOSE... TRANSMISSION GENERAL

GENERAL

DEFAULT GSSE/GOOSE UPDATE TIME: 60 s

Range: 1 to 60 s in steps of 1

The DEFAULT GSSE/GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote output state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This setting controls the steady-state heartbeat time interval. The DEFAULT GSSE/GOOSE UPDATE TIME setting is applicable to GSSE, fixed C30 GOOSE, and configurable GOOSE. The GSSE settings are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... GSSE/GOOSE... TRANSMISSION GSEE

GSSE

GSSE FUNCTION: Enabled


MESSAGE

Range: Enabled, Disabled

GSSE ID: GSSEOut DESTINATION MAC: 000000000000

Range: 65-character ASCII string

Range: standard MAC address

MESSAGE

These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted. The GSSE ID setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This string identifies the GSSE message to the receiving device. In C30 releases previous to 5.0x, this name string was represented by the RELAY NAME setting. The fixed GOOSE settings are shown below:
PATH: SETTINGS PRODUCT... COMMUNICATIONS IEC 61850... GSSE/GOOSE... TRANSMISSION FIXED GOOSE

FIXED GOOSE

GOOSE FUNCTION: Disabled


MESSAGE

Range: Enabled, Disabled

GOOSE ID: GOOSEOut DESTINATION MAC: 000000000000 GOOSE VLAN PRIORITY: 4 GOOSE VLAN ID: 0 GOOSE ETYPE APPID: 0

Range: 65-character ASCII string

Range: standard MAC address

MESSAGE

Range: 0 to 7 in steps of 1

MESSAGE

Range: 0 to 4095 in steps of 1

MESSAGE

Range: 0 to 16383 in steps of 1

MESSAGE

GE Multilin

C30 Controller System

5-19

5.2 PRODUCT SETUP These settings are applicable to fixed (DNA/UserSt) GOOSE only.

5 SETTINGS

The GOOSE ID setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message. This string identifies the GOOSE message to the receiving device. In revisions previous to 5.0x, this name string was represented by the RELAY NAME setting. The DESTINATION MAC setting allows the destination Ethernet MAC address to be set. This address must be a multicast address; the least significant bit of the first byte must be set. In C30 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the C30) and setting the multicast bit. The GOOSE VLAN PRIORITY setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE messages to have higher priority than other Ethernet data. The GOOSE ETYPE APPID setting allows the selection of a specific application ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the GOOSE VLAN PRIORITY and GOOSE ETYPE APPID settings are required by IEC 61850. The configurable GOOSE settings are shown below.
PATH: SETTINGS... COMMUNICATIONS IEC 61850... GSSE... TRANSMISSION CONFIGURABLE GOOSE 1(8)

CONFIGURABLE GOOSE 1
MESSAGE

CONFIG GSE 1 FUNCTION: Enabled CONFIG GSE 1 ID: GOOSEOut_1 CONFIG GSE 1 DST MAC: 010CDC010000 CONFIG GSE 1 VLAN PRIORITY: 4 CONFIG GSE 1 VLAN ID: 0 CONFIG GSE 1 ETYPE APPID: CONFIG GSE 1 CONFREV: 0

Range: Enabled, Disabled

Range: 65-character ASCII string

Range: standard MAC address

MESSAGE

Range: 0 to 7 in steps of 1

MESSAGE

Range: 0 to 4095 in steps of 1

MESSAGE

Range: 0 to 16383 in steps of 1

MESSAGE

Range: 0 to 4294967295 in steps of 1

MESSAGE

1
Range: Aggressive, Medium, Relaxed, Heartbeat

MESSAGE

CONFIG GSE 1 RESTRANS CURVE: Relaxed CONFIG GSE 1 DATASET ITEMS

MESSAGE

Range: 64 data items; each can be set to all valid MMS data item references for transmitted data

The configurable GOOSE settings allow the C30 to be configured to transmit a number of different datasets within IEC 61850 GOOSE messages. Up to eight different configurable datasets can be configured and transmitted. This is useful for intercommunication between C30 IEDs and devices from other manufacturers that support IEC 61850. The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the C30. The C30 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data transfer between devices. Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected. Datasets 1 and 2 should be used for high-speed transmission of data that is required for applications such as transfer tripping, blocking, and breaker fail initiate. At least one digital status value needs to be configured in the required dataset to enable transmission of configured data. Configuring analog data only to dataset 1 or 2 will not activate transmission. Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every 100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any changes have been made. If any changes in the data items are detected, these changes will be transmitted through a GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent. For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no changes in the data items are detected.

5-20

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE messages due to an oscillation being created that is triggering a message. The C30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components. If erroneously oscillation is detected, the C30 will stop sending GOOSE messages from the dataset for a minimum period of one second. Should the oscillation persist after the one second time-out period, the C30 will continue to block transmission of the dataset. The C30 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error message on the front panel display, where XXX denotes the data item detected as oscillating. For versions 5.70 and higher, the C30 supports four retransmission schemes: aggressive, medium, relaxed, and heartbeat. The aggressive scheme is only supported in fast type 1A GOOSE messages (GOOSEOut 1 and GOOSEOut 2). For slow GOOSE messages (GOOSEOut 3 to GOOSEOut 8) the aggressive scheme is the same as the medium scheme. The details about each scheme are shown in the following table. Table 51: GOOSE RETRANSMISSION SCHEMES
SCHEME Aggressive SQ NUM 0 1 2 3 4 5 Medium 0 1 2 3 4 5 Relaxed 0 1 2 3 4 5 Heartbeat 0 1 2 3 4 5 TIME FROM THE EVENT 0 ms 4 ms 8 ms 16 ms Heartbeat Heartbeat 0 ms 16 ms 32 ms 64 ms Heartbeat Heartbeat 0 ms 100 ms 200 ms 700 ms Heartbeat Heartbeat 0 ms Heartbeat Heartbeat Heartbeat Heartbeat Heartbeat TIME BETWEEN MESSAGES 0 ms 4 ms 4 ms 8 ms Heartbeat Heartbeat 0 ms 16 ms 16 ms 32 ms Heartbeat Heartbeat 0 ms 100 ms 100 ms 500 ms Heartbeat Heartbeat 0 ms Heartbeat Heartbeat Heartbeat Heartbeat Heartbeat COMMENT Event T1 T1 T2 T0 T0 Event T1 T1 T2 T0 T0 Event T1 T1 T2 T0 T0 Event T1 T1 T2 T0 T0 TIME ALLOWED TO LIVE IN MESSAGE 2000 ms 2000 ms 2000 ms Heartbeat * 4, 5 Heartbeat * 4, 5 Heartbeat * 4, 5 2000 ms 2000 ms 2000 ms Heartbeat * 4, 5 Heartbeat * 4, 5 Heartbeat * 4, 5 2000 ms 2000 ms 2000 ms Heartbeat * 4, 5 Heartbeat * 4, 5 Heartbeat * 4, 5 2000 ms 2000 ms 2000 ms Heartbeat * 4, 5 Heartbeat * 4, 5 Heartbeat * 4, 5

The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data transfer between UR-series IEDs. IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to the IEC 61850 IED configuration section later in this appendix). The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The general steps required for transmission configuration are:

GE Multilin

C30 Controller System

5-21

5.2 PRODUCT SETUP 1. 2. 3. Configure the transmission dataset. Configure the GOOSE service settings. Configure the data.

5 SETTINGS

The general steps required for reception configuration are: 1. 2. 3. Configure the reception dataset. Configure the GOOSE service settings. Configure the data.

This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status value, its associated quality flags, and a floating point analog value. The following procedure illustrates the transmission configuration. 1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION GOOSE 1 CONFIG GSE 1 DATASET ITEMS settings menu: COMMUNICATION CONFIGURABLE GOOSE CONFIGURABLE

Set ITEM 1 to GGIO1.ST.Ind1.q to indicate quality flags for GGIO1 status indication 1. Set ITEM 2 to GGIO1.ST.Ind1.stVal to indicate the status value for GGIO1 status indication 1. Set ITEM 3 to MMXU1.MX.Hz.mag.f to indicate the analog frequency magnitude for MMXU1 (the metered frequency for SRC1).

The transmission dataset now contains a quality flag, a single point status Boolean value, and a floating point analog value. The reception dataset on the receiving device must exactly match this structure.

2.

Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION RABLE GOOSE 1 settings menu: TRANSMISSION

COMMUNICATION CONFIGURABLE GOOSE CONFIGU-

3.

Set CONFIG GSE 1 FUNCTION to Enabled. Set CONFIG GSE 1 ID to an appropriate descriptive string (the default value is GOOSEOut_1). Set CONFIG GSE 1 DST MAC to a multicast address (for example, 01 00 00 12 34 56). Set the CONFIG GSE 1 VLAN PRIORITY; the default value of 4 is OK for this example. Set the CONFIG GSE 1 VLAN ID value; the default value is 0, but some switches may require this value to be 1. Set the CONFIG GSE 1 ETYPE APPID value. This setting represents the ETHERTYPE application ID and must match the configuration on the receiver (the default value is 0). Set the CONFIG GSE 1 CONFREV value. This value changes automatically as described in IEC 61850 part 7-2. For this example it can be left at its default value.
COMMUNICATION IEC 61850 PROTO-

COL

Configure the data by making the following changes in the PRODUCT SETUP GGIO1 STATUS CONFIGURATION settings menu:

4.

Set GGIO1 INDICATION 1 to a FlexLogic operand used to provide the status of GGIO1.ST.Ind1.stVal (for example, a contact input, virtual input, a protection element status, etc.).
COMMUNICATION

IEC 61850 PROTOCOL

Configure the MMXU1 Hz Deadband by making the following changes in the PRODUCT SETUP MMXU DEADBANDS MMXU1 DEADBANDS settings menu:

Set MMXU1 HZ DEADBAND to 0.050%. This will result in an update to the MMXU1.MX.mag.f analog value with a change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency.

The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. 1. Configure the reception dataset by making the following changes in the PRODUCT SETUP
61850 PROTOCOL GSSE/GOOSE CONFIGURATION 1 CONFIG GSE 1 DATASET ITEMS settings menu: RECEPTION CONFIGURABLE GOOSE COMMUNICATION IEC CONFIGURABLE GOOSE

Set ITEM 1 to GGIO3.ST.Ind1.q to indicate quality flags for GGIO3 status indication 1.

5-22

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

Set ITEM 2 to GGIO3.ST.Ind1.stVal to indicate the status value for GGIO3 status indication 1. Set ITEM 3 to GGIO3.MX.AnIn1.mag.f to indicate the analog magnitude for GGIO3 analog input 1.

The reception dataset now contains a quality flag, a single point status Boolean value, and a floating point analog value. This matches the transmission dataset configuration above. 2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS REMOTE DEVICE 1 settings menu: 3.
REMOTE DEVICES

Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter GOOSEOut_1. Set REMOTE DEVICE 1 ETYPE APPID to match the ETHERTYPE application ID from the transmitting device. This is 0 in the example above. Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using configurable GOOSE 1 in this example, program this value as GOOSEIn 1.
REMOTE INPUTS REMOTE

INPUT 1

Configure the Boolean data by making the following changes in the INPUTS/OUTPUTS settings menu: Set REMOTE IN 1 DEVICE to GOOSEOut_1.

4.

Set REMOTE IN 1 ITEM to Dataset Item 2. This assigns the value of the GGIO3.ST.Ind1.stVal single point status item to remote input 1.
IEC 61850 GOOSE ANALOG

INPUTS

Configure the analog data by making the following changes in the INPUTS/OUTPUTS settings menu: Set the IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE to 60.000. Enter Hz for the IEC61850 GOOSE ANALOG INPUT 1 UNITS setting.

The GOOSE analog input 1 can now be used as a FlexAnalog value in a FlexElement or in other settings. The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in the sending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting of the sending device. Remote input 1 can now be used in FlexLogic equations or other settings. The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a complete SCD file is created by third party substation configurator software. For intercommunication between C30 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the C30 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN support). Set the CONFIG GSE 1 FUNCTION function to Disabled when configuration changes are required. Once changes are entered, return the CONFIG GSE 1 FUNCTION to Enabled and restart the unit for changes to take effect.
NOTE

PATH:...TRANSMISSION

CONFIGURABLE GOOSE 1(8)

CONIFIG GSE 1(64) DATA TIMES

ITEM 1(64)

CONFIG GSE 1 DATASET ITEMS

ITEM 1: GGIO1.ST.Ind1.stVal

Range: all valid MMS data item references for transmitted data

To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated quality flags, the following dataset items can be selected: GGIO1.ST.Ind1.stVal and GGIO1.ST.Ind1.q. The C30 will then create a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages containing the defined dataset.

GE Multilin

C30 Controller System

5-23

5.2 PRODUCT SETUP

5 SETTINGS

The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items for reception:
PATH:...RECEPTION CONFIGURABLE GOOSE 1(8) CONIFIG GSE 1(64) DATA ITEMS Range: all valid MMS data item references for transmitted data

CONFIG GSE 1 DATASET ITEMS

ITEM 1: GGIO1.ST.Ind1.stVal

The configurable GOOSE settings allow the C30 to be configured to receive a number of different datasets within IEC 61850 GOOSE messages. Up to eight different configurable datasets can be configured for reception. This is useful for intercommunication between C30 IEDs and devices from other manufacturers that support IEC 61850. For intercommunication between C30 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset contains the same DNA and UserSt bit pairs that are included in GSSE messages. To set up a C30 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): GGIO3.ST.Ind1.stVal and GGIO3.ST.Ind2.stVal. The C30 will then create a dataset containing these two data items. The Boolean status values from these data items can be utilized as remote input FlexLogic operands. First, the REMOTE DEVICE 1(16) DATASET setting must be set to contain dataset GOOSEIn 1 (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settings must be set to Dataset Item 1 and Dataset Item 2. These remote input FlexLogic operands will then change state in accordance with the status values of the data items in the configured dataset. Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (noninstantaneous) values can be transmitted. Received values are used to populate the GGIO3.XM.AnIn1 and higher items. Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up). The main menu for the IEC 61850 server configuration is shown below.

PATH: SETTINGS

PRODUCT SETUP

COMMUNICATIONS

IEC 61850 PROTOCOL

SERVER CONFIGURATION

SERVER CONFIGURATION
MESSAGE

IED NAME: IECDevice LD INST: LDInst LOCATION: Location IEC/MMS TCP PORT NUMBER: 102 INCLUDE NON-IEC DATA: Enabled SERVER SCANNING: Disabled

Range: up to 32 alphanumeric characters

Range: up to 32 alphanumeric characters

Range: up to 80 alphanumeric characters

MESSAGE

Range: 1 to 65535 in steps of 1

MESSAGE

Range: Disabled, Enabled

MESSAGE

Range: Disabled, Enabled

MESSAGE

The IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_) character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is a variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node. The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDE NON-IEC DATA setting determines whether or not the UR MMS domain will be available. This domain contains a large number of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC 61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be Disabled. The SERVER SCANNING feature should be set to Disabled when IEC 61850 client/server functionality is not required. IEC 61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/ server communication. If the GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled to increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node status values in the C30. Clients will still be able to connect to the server (C30 relay), but most data values will not be updated. This setting does not affect GOOSE/GSSE operation.

5-24

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

Changes to the IED NAME setting, LD INST setting, and GOOSE dataset will not take effect until the C30 is restarted.
NOTE

The main menu for the IEC 61850 logical node name prefixes is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... IEC 61850 LOGICAL NODE NAME PREFIXES

IEC 61850 LOGICAL NODE NAME PREFIXES


MESSAGE

PIOC LOGICAL NODE NAME PREFIXES PTOC LOGICAL NODE NAME PREFIXES

MESSAGE

PTRC LOGICAL NODE NAME PREFIXES

The IEC 61850 logical node name prefix settings are used to create name prefixes to uniquely identify each logical node. For example, the logical node PTOC1 may have the name prefix abc. The full logical node name will then be abcMMXU1. Valid characters for the logical node name prefixes are upper and lowercase letters, numbers, and the underscore (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the C30 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL MMXU DEADBANDS

MMXU DEADBANDS

MMXU1 DEADBANDS MMXU2 DEADBANDS MMXU3 DEADBANDS MMXU4 DEADBANDS

MESSAGE

MESSAGE

MESSAGE

The MMXU deadband settings represent the deadband values used to determine when the update the MMXU mag and cVal values from the associated instmag and instcVal values. The mag and cVal values are used for the IEC 61850 buffered and unbuffered reports. These settings correspond to the associated db data items in the CF functional constraint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value shall represent the percentage of difference between the maximum and minimum in units of 0.001%. Thus, it is important to know the maximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband. The minimum value for all quantities is 0; the maximum values are as follows: phase current: 46 phase CT primary setting neutral current: 46 ground CT primary setting voltage: 275 VT ratio setting power (real, reactive, and apparent): 46 phase CT primary setting 275 VT ratio setting frequency: 90 Hz power factor: 2

GE Multilin

C30 Controller System

5-25

5.2 PRODUCT SETUP The GGIO1 status configuration points are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850...

5 SETTINGS

GGIO1 STATUS CONFIGURATION Range: 8 to 128 in steps of 8

GGIO1 STATUS CONFIGURATION


MESSAGE

NUMBER OF STATUS POINTS IN GGIO1: 8 GGIO1 INDICATION Off GGIO1 INDICATION Off

MESSAGE

1 2

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

GGIO1 INDICATION 128 Off

Range: FlexLogic operand

The NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of Ind (single point status indications) that are instantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect until the C30 is restarted. The GGIO2 control configuration points are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... GGIO2 CONTROL... Range: 0, 1, or 2 GGIO2 CF SPSCO 1(64)

GGIO2 CF SPCSO 1

GGIO2 CF SPCSO 1 CTLMODEL: 1

The GGIO2 control configuration settings are used to set the control model for each input. The available choices are 0 (status only), 1 (direct control), and 2 (SBO with normal security). The GGIO2 control points are used to control the C30 virtual inputs. The GGIO4 analog configuration points are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... GGIO4 ANALOG CONFIGURATION Range: 4 to 32 in steps of 4

GGIO4 ANALOG CONFIGURATION


MESSAGE

NUMBER OF ANALOG POINTS IN GGIO4: GGIO4 ANALOG 1 MEASURED VALUE GGIO4 ANALOG 2 MEASURED VALUE

MESSAGE

MESSAGE

GGIO4 ANALOG 32 MEASURED VALUE

The NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value is changed, the C30 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly configured number of analog points.

5-26

C30 Controller System

GE Multilin

5 SETTINGS The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS PRODUCT... COMMUNICATIONS IEC 61850... GGIO4...

5.2 PRODUCT SETUP

GGIO4 ANALOG 1(32) MEASURED VALUE

GGIO4 ANALOG 1 MEASURED VALUE


MESSAGE

ANALOG IN Off ANALOG IN 0.000 ANALOG IN 0.000 ANALOG IN 0.000

1 VALUE: 1 DB: 1 MIN: 1 MAX:

Range: any FlexAnalog value

Range: 0.000 to 100.000 in steps of 0.001

MESSAGE

Range: 1000000000.000 to 1000000000.000 in steps of 0.001 Range: 1000000000.000 to 1000000000.000 in steps of 0.001

MESSAGE

These settings are configured as follows. ANALOG IN 1 VALUE: This setting selects the FlexAnalog value to drive the instantaneous value of each GGIO4 analog status value (GGIO4.MX.AnIn1.instMag.f). ANALOG IN 1 DB: This setting specifies the deadband for each analog value. Refer to IEC 61850-7-1 and 61850-7-3 for details. The deadband is used to determine when to update the deadbanded magnitude from the instantaneous magnitude. The deadband is a percentage of the difference between the maximum and minimum values. ANALOG IN 1 MIN: This setting specifies the minimum value for each analog value. Refer to IEC 61850-7-1 and 61850-7-3 for details. This minimum value is used to determine the deadband. The deadband is used in the determination of the deadbanded magnitude from the instantaneous magnitude. ANALOG IN 1 MAX: This setting defines the maximum value for each analog value. Refer to IEC 61850-7-1 and 61850-7-3 for details. This maximum value is used to determine the deadband. The deadband is used in the determination of the deadbanded magnitude from the instantaneous magnitude. Note that the ANALOG IN 1 MIN and ANALOG IN 1 MAX settings are stored as IEEE 754 / IEC 60559 floating point numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded to the closest possible floating point number.

NOTE

The GGIO5 integer configuration points are shown below:


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... GGIO5 ANALOG CONFIGURATION Range: Off, any FlexInteger parameter

GGIO5 UINTEGER CONFIGURATION


MESSAGE

GGIO5 UINT In Off GGIO5 UINT In Off

MESSAGE

1: 2:

Range: Off, any FlexInteger parameter

GGIO5 UINT 1n 16: Off

Range: Off, any FlexInteger parameter

The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16 unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of GGIO1 (binary status values). The settings allow the selection of FlexInteger values for each GGIO5 integer value point. It is intended that clients use GGIO5 to access generic integer values from the C30. Additional settings are provided to allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger values to the GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points. GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger value to drive each GGIO5 integer status value (GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.

GE Multilin

C30 Controller System

5-27

5.2 PRODUCT SETUP The report control configuration settings are shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850... REPORT...

5 SETTINGS

REPORT 1(6) CONFIGURATION

REPORT 1 CONFIGURATION
MESSAGE

REPORT 1 RptID: REPORT 1 OptFlds: REPORT 1 BufTm: REPORT 1 TrgOps: REPORT 1 IntgPd: 0 0

Range: up to 66 alphanumeric characters

Range: 0 to 65535 in steps of 1

Range: 0 to 4294967295 in steps of 1

MESSAGE

0
Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 4294967295 in steps of 1

MESSAGE

Changes to the report configuration will not take effect until the C30 is restarted. Please disconnect any IEC 61850 client connection to the C30 prior to making setting changes to the report configuration. Disconnecting the rear Ethernet connection from the C30 will disconnect the IEC 61850 client connection.
NOTE

The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XCBR CONFIGURATION

XCBR CONFIGURATION
MESSAGE

XCBR1 ST.LOC OPERAND Off XCBR2 ST.LOC OPERAND Off

MESSAGE

Range: FlexLogic operand

Range: FlexLogic operand

XCBR6 ST.LOC OPERAND Off CLEAR XCBR1 OpCnt: No CLEAR XCBR2 OpCnt: No

Range: FlexLogic operand

Range: No, Yes

MESSAGE

Range: No, Yes

MESSAGE

MESSAGE

CLEAR XCBR6 OpCnt: No

Range: No, Yes

The CLEAR XCBR1 OpCnt setting represents the breaker operating counter. As breakers operate by opening and closing, the XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to 0 for XCBR1.

5-28

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL XSWI CONFIGURATION

XSWI CONFIGURATION
MESSAGE

XSWI1 ST.LOC OPERAND Off XSWI2 ST.LOC OPERAND Off

MESSAGE

Range: FlexLogic operand

Range: FlexLogic operand

XSWI24 ST.LOC OPERAND Off CLEAR XSWI1 OpCnt: No CLEAR XSWI2 OpCnt: No

Range: FlexLogic operand

Range: No, Yes

MESSAGE

Range: No, Yes

MESSAGE

MESSAGE

CLEAR XSWI24 OpCnt: No

Range: No, Yes

The CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate by opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to 0 for XSWI1. Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by network routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN functionality.

NOTE

h) WEB SERVER HTTP PROTOCOL


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS WEB SERVER HTTP PROTOCOL Range: 1 to 65535 in steps of 1

WEB SERVER HTTP PROTOCOL

HTTP TCP PORT NUMBER: 80

The C30 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft Internet Explorer or Mozilla Firefox. This feature is available only if the C30 has the ethernet option installed. The web pages are organized as a series of menus that can be accessed starting at the C30 Main Menu. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web browser on the computer simply by entering the IP address of the C30 into the Address box on the web browser. i) TFTP PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS TFTP PROTOCOL Range: 1 to 65535 in steps of 1

TFTP PROTOCOL

TFTP MAIN UDP PORT NUMBER: 69


MESSAGE

TFTP DATA UDP PORT 1 NUMBER: 0 TFTP DATA UDP PORT 2 NUMBER: 0

Range: 0 to 65535 in steps of 1

Range: 0 to 65535 in steps of 1

MESSAGE

The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the C30 over a network. The C30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the C30 contains a list and description of all available files (event records, oscillography, etc.).

GE Multilin

C30 Controller System

5-29

5.2 PRODUCT SETUP j) IEC 60870-5-104 PROTOCOL


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-104 PROTOCOL Range: Enabled, Disabled

5 SETTINGS

IEC 60870-5-104 PROTOCOL


MESSAGE

IEC 60870-5-104 FUNCTION: Disabled IEC TCP PORT NUMBER: 2404 IEC NETWORK CLIENT ADDRESSES IEC COMMON ADDRESS OF ASDU: 0 IEC CYCLIC DATA PERIOD: 60 s IEC CURRENT DEFAULT THRESHOLD: 30000 IEC VOLTAGE DEFAULT THRESHOLD: 30000 IEC POWER DEFAULT THRESHOLD: 30000 IEC ENERGY DEFAULT THRESHOLD: 30000 IEC OTHER DEFAULT THRESHOLD: 30000

Range: 1 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 1 to 65535 s in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

5
MESSAGE

Range: 0 to 65535 in steps of 1

The C30 supports the IEC 60870-5-104 protocol. The C30 can be used as an IEC 60870-5-104 slave device connected to a maximum of two masters (usually either an RTU or a SCADA master station). Since the C30 maintains two sets of IEC 60870-5-104 data change buffers, no more than two masters should actively communicate with the C30 at one time. The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing M_ME_NC_1 analog data. These settings group the C30 analog data into types: current, voltage, power, energy, and other. Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger spontaneous responses from the C30 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD setting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of measured value, short floating point value) points can be used to change threshold values, from the default, for each individual M_ME_NC_1 analog point. Whenever power is removed and re-applied to the C30, the default thresholds will be in effect. The C30 relay does not support power metering. As such, the IEC POWER DEFAULT THRESHOLD setting is not applicable.
NOTE

The C30 relay does not support energy metering. As such, the IEC ENERGY DEFAULT THRESHOLD setting is not applicable.
NOTE

NOTE

The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION setting is set to Enabled, the DNP protocol will not be operational. When this setting is changed it will not become active until power to the relay has been cycled (off-to-on).

5-30

C30 Controller System

GE Multilin

5 SETTINGS k) SNTP PROTOCOL


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS SNTP PROTOCOL Range: Enabled, Disabled

5.2 PRODUCT SETUP

SNTP PROTOCOL

SNTP FUNCTION: Disabled


MESSAGE

SNTP SERVER IP ADDR: 0.0.0.0 SNTP UDP PORT NUMBER: 123

Range: Standard IP address format

Range: 0 to 65535 in steps of 1

MESSAGE

The C30 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the C30 can obtain clock time over an Ethernet network. The C30 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a dedicated product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported. If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the C30 clock for as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If either SNTP or IRIG-B is enabled, the C30 clock value cannot be changed using the front panel keypad. To use SNTP in unicast mode, SNTP SERVER IP ADDR must be set to the SNTP/NTP server IP address. Once this address is set and SNTP FUNCTION is Enabled, the C30 attempts to obtain time values from the SNTP/NTP server. Since many time values are obtained and averaged, it generally takes three to four minutes until the C30 clock is closely synchronized with the SNTP/NTP server. It may take up to two minutes for the C30 to signal an SNTP self-test error if the server is offline. To use SNTP in broadcast mode, set the SNTP SERVER IP ADDR setting to 0.0.0.0 and SNTP FUNCTION to Enabled. The C30 then listens to SNTP messages sent to the all ones broadcast address for the subnet. The C30 waits up to eighteen minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error. The UR-series relays do not support the multicast or anycast SNTP functionality. l) EGD PROTOCOL
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS EGD PROTOCOL

EGD PROTOCOL

FAST PROD EXCH 1 CONFIGURATION


MESSAGE

SLOW PROD EXCH 1 CONFIGURATION SLOW PROD EXCH 2 CONFIGURATION

MESSAGE

The C30 Controller System is provided with optional Ethernet Global Data (EGD) communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The Ethernet Global Data (EGD) protocol feature is not available if CPU Type E is ordered. The relay supports one fast Ethernet Global Data (EGD) exchange and two slow EGD exchanges. There are 20 data items in the fast-produced EGD exchange and 50 data items in each slow-produced exchange. Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes. The relay can be configured to produce EGD data exchanges, and other devices can be configured to consume EGD data exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the exchange production rate can be configured. EGD cannot be used to transfer data between UR-series relays. The relay supports EGD production only. An EGD exchange will not be transmitted unless the destination address is non-zero, and at least the first data item address is set to a valid Modbus register address. Note that the default setting value of 0 is considered invalid.

GE Multilin

C30 Controller System

5-31

5.2 PRODUCT SETUP The settings menu for the fast EGD exchange is shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS EGD PROTOCOL

5 SETTINGS

FAST PROD EXCH 1 CONFIGURATION

FAST PROD EXCH 1 CONFIGURATION


MESSAGE

EXCH 1 FUNCTION: Disable EXCH 1 DESTINATION: 0.0.0.0 EXCH 1 DATA RATE: 1000 ms EXCH 1 DATA ITEM 1: 0

Range: Disable, Enable

Range: standard IP address

Range: 50 to 1000 ms in steps of 1

MESSAGE

MESSAGE

Range: 0 to 65535 in steps of 1 (Modbus register address range)

MESSAGE

EXCH 1 DATA ITEM 20: 0

Range: 0 to 65535 in steps of 1 (Modbus register address range)

Fast exchanges (50 to 1000 ms) are generally used in control schemes. The C30 has one fast exchange (Exchange 1) and two slow exchanges (Exchanges 2 and 3). The settings menu for the slow EGD exchanges is shown below:
PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS EGD PROTOCOL SLOW PROD EXCH 1(2) CONFIGURATION

SLOW PROD EXCH 1 CONFIGURATION

EXCH 1 FUNCTION: Disable EXCH 1 DESTINATION: 0.0.0.0 EXCH 1 DATA RATE: 1000 ms EXCH 1 DATA ITEM 1: 0

Range: Disable, Enable

Range: standard IP address

MESSAGE

Range: 500 to 1000 ms in steps of 1

MESSAGE

MESSAGE

Range: 0 to 65535 in steps of 1 (Modbus register address range in decimal)

MESSAGE

EXCH 1 DATA ITEM 50: 0

Range: 0 to 65535 in steps of 1 (Modbus register address range in decimal)

Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the fast and slow exchanges are described below: EXCH 1 DESTINATION: This setting specifies the destination IP address of the produced EGD exchange. This is usually unicast or broadcast. EXCH 1 DATA RATE: This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms, the exchange data will be updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data will be updated and sent once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a setting range of 500 to 1000 ms. EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any data from the C30 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format. Refer to Appendix B for the complete Modbus memory map. Note that the Modbus memory map displays shows addresses in hexadecimal format; as such, it will be necessary to convert these values to decimal format before entering them as values for these setpoints. To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item. That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values), only the first Modbus address is required. The EGD exchange configured with these settings contains the data items up to the first setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid Modbus addresses and the fourth is 0, the produced EGD exchange will contain three data items.

5-32

C30 Controller System

GE Multilin

5 SETTINGS m) ETHERNET SWITCH


PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS ETHERNET SWITCH

5.2 PRODUCT SETUP

ETHERNET SWITCH

SWITCH IP ADDRESS: 127.0.0.1 SWITCH MODBUS TCP PORT NUMBER: 502 PORT 1 EVENTS: Disabled PORT 2 EVENTS: Disabled

Range: standard IP address format

Range: 1 to 65535 in steps of 1

MESSAGE

Range: Enabled, Disabled

MESSAGE

Range: Enabled, Disabled

MESSAGE

MESSAGE

PORT 6 EVENTS: Disabled

Range: Enabled, Disabled

These settings appear only if the C30 is ordered with an Ethernet switch module (type 2S or 2T). The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings are used in advanced network configurations. Please consult the network administrator before making changes to these settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings. The PORT 1 EVENTS through PORT 6 EVENTS settings allow Ethernet switch module events to be logged in the event recorder. 5.2.5 MODBUS USER MAP
PATH: SETTINGS PRODUCT SETUP MODBUS USER MAP

MODBUS USER MAP

ADDRESS VALUE: ADDRESS VALUE:

1: 0 2: 0

0 0

Range: 0 to 65535 in steps of 1

Range: 0 to 65535 in steps of 1

MESSAGE

MESSAGE

ADDRESS 256: VALUE: 0

Range: 0 to 65535 in steps of 1

The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired address in the ADDRESS line (this value must be converted from hex to decimal format). The corresponding value is displayed in the VALUE line. A value of 0 in subsequent register ADDRESS lines automatically returns values for the previous ADDRESS lines incremented by 1. An address value of 0 in the initial register means none and values of 0 will be displayed for all registers. Different ADDRESS values can be entered as required in any of the register positions.

GE Multilin

C30 Controller System

5-33

5.2 PRODUCT SETUP

5 SETTINGS 5.2.6 REAL TIME CLOCK

PATH: SETTINGS

PRODUCT SETUP

REAL TIME CLOCK

REAL TIME CLOCK


MESSAGE

IRIG-B SIGNAL TYPE: None REAL TIME CLOCK EVENTS: Disabled LOCAL TIME OFFSET FROM UTC: 0.0 hrs DAYLIGHT SAVINGS TIME: Disabled DST START MONTH: April DST START DAY: Sunday DST START DAY INSTANCE: First DST START HOUR: 2:00 DST STOP MONTH: April DST STOP DAY: Sunday DST STOP DAY INSTANCE: First DST STOP HOUR: 2:00

Range: None, DC Shift, Amplitude Modulated

Range: Disabled, Enabled

Range: 24.0 to 24.0 hrs in steps of 0.5

MESSAGE

Range: Disabled, Enabled

MESSAGE

Range: January to December (all months)

MESSAGE

Range: Sunday to Saturday (all days of the week)

MESSAGE

Range: First, Second, Third, Fourth, Last

MESSAGE

Range: 0:00 to 23:00

MESSAGE

Range: January to December (all months)

MESSAGE

Range: Sunday to Saturday (all days of the week)

MESSAGE

Range: First, Second, Third, Fourth, Last

MESSAGE

Range: 0:00 to 23:00

MESSAGE

The date and time can be synchronized a known time base and to other relays using an IRIG-B signal. It has the same accuracy as an electronic watch, approximately 1 minute per month. If an IRIG-B signal is connected to the relay, only the SET DATE AND TIME menu to manually set the relay clock. current year needs to be entered. See the COMMANDS The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record. The LOCAL TIME OFFSET FROM UTC setting is used to specify the local time zone offset from Universal Coordinated Time (Greenwich Mean Time) in hours. This setting has two uses. When the C30 is time synchronized with IRIG-B, or has no permanent time synchronization, the offset is used to calculate UTC time for IEC 61850 features. When the C30 is time synchronized with SNTP, the offset is used to determine the local time for the C30 clock, since SNTP provides UTC time. The daylight savings time (DST) settings can be used to allow the C30 clock can follow the DST rules of the local time zone. Note that when IRIG-B time synchronization is active, the DST settings are ignored. The DST settings are used when the C30 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used. Only timestamps in the event recorder and communications protocols are affected by the daylight savings time settings. The reported real-time clock value does not change.
NOTE

5-34

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP 5.2.7 OSCILLOGRAPHY

a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY

OSCILLOGRAPHY

NUMBER OF RECORDS: 15
MESSAGE

Range: 1 to 64 in steps of 1

TRIGGER MODE: Automatic Overwrite TRIGGER POSITION: 50% TRIGGER SOURCE: Off AC INPUT WAVEFORMS: 16 samples/cycle DIGITAL CHANNELS ANALOG CHANNELS

Range: Automatic Overwrite, Protected

Range: 0 to 100% in steps of 1

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Off; 8, 16, 32, 64 samples/cycle

MESSAGE

MESSAGE

MESSAGE

Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger. Oscillography records are triggered by a programmable FlexLogic operand. Multiple oscillography records may be captured simultaneously. The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscillography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES RECORDS OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sample configurations with corresponding cycles/record. Table 52: OSCILLOGRAPHY CYCLES/RECORD EXAMPLE
RECORDS 1 1 8 8 8 8 8 8 32 CT/VTS 1 1 1 1 2 2 2 2 2 SAMPLE RATE 8 16 16 16 16 16 32 64 64 DIGITALS 0 16 16 16 16 64 64 64 64 ANALOGS 0 0 0 4 4 16 16 16 16 CYCLES/ RECORD 1872.0 1685.0 276.0 219.5 93.5 93.5 57.6 32.3 9.5

A new record may automatically overwrite an older record if TRIGGER MODE is set to Automatic Overwrite. Set the TRIGGER POSITION to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of 25% consists of 25% pre- and 75% post-trigger data. The TRIGGER SOURCE is always captured in oscillography and may be any FlexLogic parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per cycle. The AC INPUT WAVEFORMS setting determines the sampling rate at which AC input signals (that is, current and voltage) are stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.

GE Multilin

C30 Controller System

5-35

5.2 PRODUCT SETUP

5 SETTINGS

When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.
WARNING

b) DIGITAL CHANNELS
PATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY DIGITAL CHANNELS

DIGITAL CHANNELS

DIGITAL CHANNEL Off DIGITAL CHANNEL Off

1: 2:

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

MESSAGE

DIGITAL CHANNEL 63: Off

Range: FlexLogic operand

A DIGITAL 1(63) CHANNEL setting selects the FlexLogic operand state recorded in an oscillography trace. The length of each oscillography trace depends in part on the number of parameters selected here. Parameters set to Off are ignored. Upon startup, the relay will automatically prepare the parameter list. c) ANALOG CHANNELS
PATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY ANALOG CHANNELS

ANALOG CHANNELS

ANALOG CHANNEL Off ANALOG CHANNEL Off

1: 2:

Range: Off, any FlexAnalog parameter See Appendix A for complete list. Range: Off, any FlexAnalog parameter See Appendix A for complete list.

MESSAGE

MESSAGE

ANALOG CHANNEL 16: Off

Range: Off, any FlexAnalog parameter See Appendix A for complete list.

These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace depends in part on the number of parameters selected here. Parameters set to Off are ignored. The parameters available in a given relay are dependent on: The type of relay, The type and number of CT/VT hardware modules installed, and The type and number of analog input hardware modules installed.

Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding parameter to be displayed. All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows: <slot_letter><terminal_number><I or V><phase A, B, or C, or 4th input> The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB designates the IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear.

5-36

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP 5.2.8 DATA LOGGER

PATH: SETTINGS

PRODUCT SETUP

DATA LOGGER

DATA LOGGER

DATA LOGGER MODE: Continuous


MESSAGE

Range: Continuous, Trigger

DATA LOGGER TRIGGER: Off DATA LOGGER RATE: 60000 ms DATA LOGGER CHNL Off DATA LOGGER CHNL Off 1: 2:

Range: FlexLogic operand

Range: 15 to 3600000 ms in steps of 1

MESSAGE

MESSAGE

Range: Off, any FlexAnalog parameter. See Appendix A: FlexAnalog Parameters for complete list. Range: Off, any FlexAnalog parameter. See Appendix A: FlexAnalog Parameters for complete list.

MESSAGE

MESSAGE

DATA LOGGER CHNL 16: Off DATA LOGGER CONFIG: 0 CHNL x 0.0 DAYS

Range: Off, any FlexAnalog parameter. See Appendix A: FlexAnalog Parameters for complete list. Range: Not applicable - shows computed data only

MESSAGE

The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis. All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost. For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Example storage capacities for a system frequency of 60 Hz are shown in the following table. Table 53: DATA LOGGER STORAGE CAPACITY EXAMPLE
SAMPLING RATE 15 ms CHANNELS 1 8 9 16 1000 ms 1 8 9 16 60000 ms 1 8 9 16 3600000 ms 1 8 9 DAYS 0.1 0.1 0.1 0.1 0.7 0.1 0.1 0.1 45.4 5.6 5 2.8 2727.5 340.9 303 STORAGE CAPACITY 954 s 120 s 107 s 60 s 65457 s 8182 s 7273 s 4091 s 3927420 s 490920 s 436380 s 254460 s 235645200 s 29455200 s 26182800 s

Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE

DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to Continuous, the data logger will actively record any configured channels at the rate as defined by the DATA LOGGER RATE. The

GE Multilin

C30 Controller System

5-37

5.2 PRODUCT SETUP

5 SETTINGS

data logger will be idle in this mode if no channels are configured. When set to Trigger, the data logger will begin to record any configured channels at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic operand. The data logger will ignore all subsequent triggers and will continue to record data until the active record is full. Once the data logger is full a CLEAR DATA LOGGER command is required to clear the data logger record before a new record can be started. Performing the CLEAR DATA LOGGER command will also stop the current record and reset the data logger to be ready for the next trigger. DATA LOGGER TRIGGER: This setting selects the signal used to trigger the start of a new data logger record. Any FlexLogic operand can be used as the trigger source. The DATA LOGGER TRIGGER setting only applies when the mode is set to Trigger. DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded. DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/ VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of parameters via the relay keypad/display entering this number via the relay keypad will cause the corresponding parameter to be displayed. DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not selected to Off without over-writing old data. 5.2.9 USER-PROGRAMMABLE LEDS

a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS

USER-PROGRAMMABLE LEDS
MESSAGE

LED TEST TRIP & ALARM LEDS USER-PROGRAMMABLE LED1 USER-PROGRAMMABLE LED2

See below See page 540. See page 540.

MESSAGE

MESSAGE

MESSAGE

USER-PROGRAMMABLE LED48

b) LED TEST
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST Range: Disabled, Enabled.

LED TEST

LED TEST FUNCTION: Disabled


MESSAGE

LED TEST CONTROL: Off

Range: FlexLogic operand

When enabled, the LED test can be initiated from any digital input or user-programmable condition such as user-programmable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all LEDs, including the LEDs of the optional user-programmable pushbuttons. The test consists of three stages. 1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is burned. This stage lasts as long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test will end.

5-38

C30 Controller System

GE Multilin

5 SETTINGS 2.

5.2 PRODUCT SETUP

All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead to more than one LED being turned on from a single logic point. This stage can be interrupted at any time. All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more than one LED being turned off from a single logic point. This stage can be interrupted at any time.

3.

When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and monitoring features. However, the LED control mechanism accepts all the changes to LED states generated by the relay and stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress. A dedicated FlexLogic operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is initiated, the LED TEST INITIATED event is stored in the event recorder. The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL setting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed.

READY TO TEST
Reset the LED TEST IN PROGRESS operand

rising edge of the control input

Start the software image of the LEDs

Restore the LED states from the software image

Set the LED TEST IN PROGRESS operand control input is on

STAGE 1 (all LEDs on)


dropping edge of the control input Wait 1 second

time-out (1 minute)

rising edge of the control input

STAGE 2 (one LED on at a time)

rising edge of the control input

Wait 1 second

rising edge of the control input

STAGE 3 (one LED off at a time)

rising edge of the control input

842011A1.CDR

Figure 52: LED TEST SEQUENCE APPLICATION EXAMPLE 1: Assume one needs to check if any of the LEDs is burned through user-programmable pushbutton 1. The following settings should be applied. Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: Self-reset PUSHBTN 1 DROP-OUT TIME: 0.10 s

GE Multilin

C30 Controller System

5-39

5.2 PRODUCT SETUP

5 SETTINGS

Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS LED TEST menu:
LED TEST FUNCTION: Enabled LED TEST CONTROL: PUSHBUTTON 1 ON

The test will be initiated when the user-programmable pushbutton 1 is pressed. The pushbutton should remain pressed for as long as the LEDs are being visually inspected. When finished, the pushbutton should be released. The relay will then automatically start stage 2. At this point forward, test may be aborted by pressing the pushbutton. APPLICATION EXAMPLE 2: Assume one needs to check if any LEDs are burned as well as exercise one LED at a time to check for other failures. This is to be performed via user-programmable pushbutton 1. After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next, release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. c) TRIP AND ALARM LEDS
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS TRIP & ALARM LEDS Range: FlexLogic operand

TRIP & ALARM LEDS

TRIP LED INPUT: Off ALARM LED INPUT: Off

Range: FlexLogic operand

MESSAGE

The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each indicator can be programmed to become illuminated when the selected FlexLogic operand is in the logic 1 state. d) USER-PROGRAMMABLE LED 1(48)
PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LED 1(48) Range: FlexLogic operand

USER-PROGRAMMABLE LED 1
MESSAGE

LED 1 OPERAND: Off LED 1 TYPE: Self-Reset

Range: Self-Reset, Latched

There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illuminate when the selected FlexLogic operand is in the logic 1 state. For the standard faceplate, the LEDs are located as follows. LED Panel 2: user-programmable LEDs 1 through 24 LED Panel 3: user programmable LEDs 25 through 48

For the enhanced faceplate, the LEDs are located as follows. LED column 2: user-programmable LEDs 1 through 12 LED column 3: user-programmable LEDs 13 through 24 LED column 4: user-programmable LEDs 25 through 36 LED column 5: user-programmable LEDs 37 through 48

Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs. The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the LED 1 TYPE setting is Self-Reset (the default setting), the LED illumination will track the state of the selected LED operand. If the LED 1 TYPE setting is Latched, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communications channel, or from any programmed operand, even if the LED operand state de-asserts.

5-40

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

Table 54: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS


SETTING LED 1 operand LED 2 operand LED 3 operand LED 4 operand LED 5 operand LED 6 operand LED 7 operand LED 8 operand LED 9 operand LED 10 operand LED 11 operand LED 12 operand PARAMETER Off Off Off Off Off Off Off Off Off Off Off Off SETTING LED 13 operand LED 14 operand LED 15 operand LED 16 operand LED 17 operand LED 18 operand LED 19 operand LED 20 operand LED 21 operand LED 22 operand LED 23 operand LED 24 operand PARAMETER Off Off Off Off Off Off Off Off Off Off Off Off

5.2.10 USER-PROGRAMMABLE SELF TESTS


PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE SELF TESTS

USER-PROGRAMMABLE SELF TESTS


MESSAGE

DIRECT RING BREAK FUNCTION: Enabled DIRECT DEVICE OFF FUNCTION: Enabled REMOTE DEVICE OFF FUNCTION: Enabled PRI. ETHERNET FAIL FUNCTION: Disabled SEC. ETHERNET FAIL FUNCTION: Disabled BATTERY FAIL FUNCTION: Enabled SNTP FAIL FUNCTION: Enabled IRIG-B FAIL FUNCTION: Enabled ETHERNET SWITCH FAIL FUNCTION: Disabled

Range: Disabled, Enabled. Valid for units equipped with Direct Input/Output module. Range: Disabled, Enabled. Valid for units equipped with Direct Input/Output module. Range: Disabled, Enabled. Valid for units that contain a CPU with Ethernet capability. Range: Disabled, Enabled. Valid for units that contain a CPU with a primary fiber port. Range: Disabled, Enabled. Valid for units that contain a CPU with a redundant fiber port. Range: Disabled, Enabled.

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

Range: Disabled, Enabled. Valid for units that contain a CPU with Ethernet capability. Range: Disabled, Enabled.

MESSAGE

Range: Disabled, Enabled.

MESSAGE

All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most of the minor alarms can be disabled if desired. When in the Disabled mode, minor alarms will not assert a FlexLogic operand, write to the event recorder, or display target messages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the Enabled mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. To enable the Ethernet switch failure function, ensure that the ETHERNET SWITCH FAIL FUNCTION is Enabled in this menu.
NOTE

GE Multilin

C30 Controller System

5-41

5.2 PRODUCT SETUP

5 SETTINGS 5.2.11 CONTROL PUSHBUTTONS

PATH: SETTINGS

PRODUCT SETUP

CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1(7) Range: Disabled, Enabled

CONTROL PUSHBUTTON 1
MESSAGE

CONTROL PUSHBUTTON 1 FUNCTION: Disabled CONTROL PUSHBUTTON 1 EVENTS: Disabled

Range: Disabled, Enabled

There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front panels. These are user-programmable and can be used for various applications such as performing an LED test, switching setting groups, and invoking and scrolling though user-programmable displays. The location of the control pushbuttons are shown in the following figures.

Control pushbuttons
842813A1.CDR

Figure 53: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the C30 is ordered with the twelve user-programmable pushbutton option.
STATUS IN SERVICE TROUBLE TEST MODE TRIP ALARM PICKUP EVENT CAUSE VOLTAGE CURRENT FREQUENCY OTHER PHASE A PHASE B PHASE C NEUTRAL/GROUND USER 3 USER 2 USER 1 RESET

THREE STANDARD CONTROL PUSHBUTTONS

USER 4 USER 5 USER 6 USER 7

FOUR EXTRA OPTIONAL CONTROL PUSHBUTTONS

842733A2.CDR

Figure 54: CONTROL PUSHBUTTONS (STANDARD FACEPLATE) Control pushbuttons are not typically used for critical operations and are not protected by the control password. However, by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons. Each control pushbutton asserts its own FlexLogic operand. These operands should be configured appropriately to perform the desired function. The operand remains asserted as long as the pushbutton is pressed and resets when the pushbutton is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation will be recognized by various features that may use control pushbuttons as inputs. An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously a given key must be released before the next one can be pressed.

5-42

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

SETTING

CONTROL PUSHBUTTON 1 FUNCTION: Enabled=1 SETTINGS SYSTEM SETUP/ BREAKERS/BREAKER 1/ BREAKER 1 PUSHBUTTON CONTROL: Enabled=1 SYSTEM SETUP/ BREAKERS/BREAKER 2/ BREAKER 2 PUSHBUTTON CONTROL: Enabled=1

When applicable

AND

RUN OFF ON TIMER 0 100 msec FLEXLOGIC OPERAND CONTROL PUSHBTN 1 ON 842010A2.CDR

Figure 55: CONTROL PUSHBUTTON LOGIC 5.2.12 USER-PROGRAMMABLE PUSHBUTTONS

PATH: SETTINGS

PRODUCT SETUP

USER-PROGRAMMABLE PUSHBUTTONS

USER PUSHBUTTON 1(16)

USER PUSHBUTTON 1

PUSHBUTTON 1 FUNCTION: Disabled PUSHBTN 1 ID TEXT: PUSHBTN 1 ON TEXT: PUSHBTN 1 OFF TEXT: PUSHBTN 1 HOLD: 0.0 s PUSHBTN 1 SET: Off PUSHBTN 1 RESET: Off PUSHBTN 1 AUTORST: Disabled PUSHBTN 1 AUTORST DELAY: 1.0 s PUSHBTN 1 REMOTE: Off PUSHBTN 1 LOCAL: Off PUSHBTN 1 DROP-OUT TIME: 0.00 s PUSHBTN 1 LED CTL: Off PUSHBTN 1 MESSAGE: Disabled PUSHBUTTON 1 EVENTS: Disabled

Range: Self-Reset, Latched, Disabled

Range: Up to 20 alphanumeric characters

MESSAGE

Range: Up to 20 alphanumeric characters

MESSAGE

Range: Up to 20 alphanumeric characters

MESSAGE

Range: 0.0 to 10.0 s in steps of 0.1

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Disabled, Enabled

MESSAGE

Range: 0.2 to 600.0 s in steps of 0.1

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: 0 to 60.00 s in steps of 0.05

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Disabled, Normal, High Priority

MESSAGE

Range: Disabled, Enabled

MESSAGE

GE Multilin

C30 Controller System

5-43

5.2 PRODUCT SETUP

5 SETTINGS

The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of entering digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered with the relay. Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons. Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.

The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below.

USER LABEL 1

USER LABEL 2

USER LABEL 3

USER LABEL 4

USER LABEL 5

USER LABEL 6

USER LABEL 7

USER LABEL 8

USER LABEL 9

USER LABEL 10

USER LABEL 11

USER LABEL 12

USER LABEL 13

USER LABEL 14

USER LABEL 15

USER LABEL 16

842814A1.CDR

Figure 56: USER-PROGRAMMABLE PUSHBUTTONS (ENHANCED FACEPLATE) The user-configurable pushbuttons for the standard faceplate are shown below.

1
USER LABEL

3
USER LABEL

5
USER LABEL

7
USER LABEL

9
USER LABEL

11
USER LABEL

2
USER LABEL

4
USER LABEL

6
USER LABEL

8
USER LABEL

10
USER LABEL

12
USER LABEL
842779A1.CDR

Figure 57: USER-PROGRAMMABLE PUSHBUTTONS (STANDARD FACEPLATE) Both the standard and enhanced faceplate pushbuttons can be custom labeled with a factory-provided template, available online at http://www.GEmultilin.com. The EnerVista UR Setup software can also be used to create labels for the enhanced faceplate. Each pushbutton asserts its own On and Off FlexLogic operands (for example, PUSHBUTTON 1 ON and PUSHBUTTON 1 OFF). These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is active, the ANY PB ON operand will be asserted. Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the corresponding pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic operand through the PUSHBTN 1 LED CTL setting. The pushbuttons can be automatically controlled by activating the operands assigned to the PUSHBTN 1 SET (for latched and self-reset mode) and PUSHBTN 1 RESET (for latched mode only) settings. The pushbutton reset status is declared when the PUSHBUTTON 1 OFF operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent on whether latched or self-reset mode is programmed. Latched mode: In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the PUSHBTN 1 SET setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set state until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is stored in non-volatile memory and maintained through a loss of control power. The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET setting or by directly pressing the associated active front panel pushbutton.

5-44

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY settings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker location (feeder number) must be selected prior to command execution. The selection must reset automatically if control is not executed within a specified time period. Self-reset mode: In self-reset mode, a pushbutton will remain active for the time it is pressed (the pulse duration) plus the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via FlexLogic, the pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand remains assigned to the PUSHBTN 1 SET setting has no effect on the pulse duration.
TIME

The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the PUSHBTN 1 DROP-OUT setting expires. The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the pushbutton. This allows the user-programmable pushbuttons to properly operate during power cycling events and various system disturbances that may cause transient assertion of the operating signals.

NOTE

The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL and PUSHBTN 1 REMOTE settings, respectively. If local locking is applied, the pushbutton will ignore set and reset commands executed through the front panel pushbuttons. If remote locking is applied, the pushbutton will ignore set and reset commands executed through FlexLogic operands. The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control operations to prevent the pushbutton function from being activated and ensuring one-at-a-time select operation. The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate inhibit of the local and remote operation simplifies the implementation of local/remote control supervision. Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off. PUSHBUTTON 1 FUNCTION: This setting selects the characteristic of the pushbutton. If set to Disabled, the pushbutton is not active and the corresponding FlexLogic operands (both On and Off) are de-asserted. If set to SelfReset, the control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically pressed or virtually pressed via a FlexLogic operand assigned to the PUSHBTN 1 SET setting. When in Self-Reset mode and activated locally, the pushbutton control logic asserts the On corresponding FlexLogic operand as long as the pushbutton is being physically pressed, and after being released the deactivation of the operand is delayed by the drop out timer. The Off operand is asserted when the pushbutton element is deactivated. If the pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding On FlexLogic operand only for the time period specified by the PUSHBTN 1 DROP-OUT TIME setting. If set to Latched, the control logic alternates the state of the corresponding FlexLogic operand between On and Off on each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the Latched mode, the states of the FlexLogic operands are stored in a non-volatile memory. Should the power supply be lost, the correct state of the pushbutton is retained upon subsequent power up of the relay. PUSHBTN 1 ID TEXT: This setting specifies the top 20-character line of the user-programmable message and is intended to provide ID information of the pushbutton. Refer to the User-definable displays section for instructions on how to enter alphanumeric characters from the keypad. PUSHBTN 1 ON TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is displayed when the pushbutton is in the on position. Refer to the User-definable displays section for instructions on entering alphanumeric characters from the keypad. PUSHBTN 1 OFF TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is displayed when the pushbutton is activated from the on to the off position and the PUSHBUTTON 1 FUNCTION is Latched. This message is not displayed when the PUSHBUTTON 1 FUNCTION is Self-reset as the pushbutton operand status is implied to be Off upon its release. The length of the Off message is configured with the PRODUCT SETUP DISPLAY PROPERTIES FLASH MESSAGE TIME setting. PUSHBTN 1 HOLD: This setting specifies the time required for a pushbutton to be pressed before it is deemed active. This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.

GE Multilin

C30 Controller System

5-45

5.2 PRODUCT SETUP

5 SETTINGS

PUSHBTN 1 SET: This setting assigns the FlexLogic operand serving to operate the pushbutton element and to assert PUSHBUTTON 1 ON operand. The duration of the incoming set signal must be at least 100 ms. PUSHBTN 1 RESET: This setting assigns the FlexLogic operand serving to reset pushbutton element and to assert PUSHBUTTON 1 OFF operand. This setting is applicable only if pushbutton is in latched mode. The duration of the incoming reset signal must be at least 50 ms. PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable only if the pushbutton is in the Latched mode. PUSHBTN 1 AUTORST DELAY: This setting specifies the time delay for automatic reset of the pushbutton when in the latched mode. PUSHBTN 1 REMOTE: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings. PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. PUSHBTN 1 DROP-OUT TIME: This setting applies only to Self-Reset mode and specifies the duration of the pushbutton active status after the pushbutton has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration. This setting is required to set the duration of the pushbutton operating pulse. PUSHBTN 1 LED CTL: This setting assigns the FlexLogic operand serving to drive pushbutton LED. If this setting is Off, then LED operation is directly linked to PUSHBUTTON 1 ON operand. PUSHBTN 1 MESSAGE: If pushbutton message is set to High Priority, the message programmed in the PUSHBTN 1 and PUSHBTN 1 ON TEXT settings will be displayed undisturbed as long as PUSHBUTTON 1 ON operand is asserted. The high priority option is not applicable to the PUSHBTN 1 OFF TEXT setting.
ID

This message can be temporary removed if any front panel keypad button is pressed. However, ten seconds of keypad inactivity will restore the message if the PUSHBUTTON 1 ON operand is still active. If the PUSHBTN 1 MESSAGE is set to Normal, the message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings will be displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than time period specified by FLASH MESSAGE TIME setting. After the flash time is expired, the default message or other active target message is displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or any new target or message becomes active. The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and will be displayed in PUSHBTN 1 ID only if pushbutton element is in the Latched mode. The PUSHBTN 1 OFF TEXT message as Normal if the PUSHBTN 1 MESSAGE setting is High Priority or Normal. conjunction with will be displayed

PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder.

5-46

C30 Controller System

GE Multilin

5 SETTINGS The user-programmable pushbutton logic is shown below.


FLEXLOGIC OPERAND PUSHBUTTON 1 OFF TIMER 200 ms 0 SETTING Function = Enabled = Latched = Self-Reset

5.2 PRODUCT SETUP

LATCHED
OR

LATCHED/SELF-RESET

To user-programmable pushbuttons logic sheet 2, 842024A2

SETTING Local Lock Off = 0


AND

Non-volatile latch
S

SETTING Remote Lock Off = 0 SETTING Hold TPKP 0


AND

TIMER 50 ms
R

Latch

0
OR

TIMER 50 ms 0

OR

SETTING Set Off = 0

AND

SETTING Reset Off = 0

OR
AND AND

OR

PUSHBUTTON ON

To user-programmable pushbuttons logic sheet 2, 842024A2

5
SETTING Drop-Out Timer 0

SETTING Autoreset Function = Enabled = Disabled

SETTING Autoreset Delay TPKP


AND

0
AND

FLEXLOGIC OPERAND PUSHBUTTON 1 ON

TIMER 200 ms 0
AND

OR

TRST
842021A3.CDR

Figure 58: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2)

GE Multilin

C30 Controller System

5-47

5.2 PRODUCT SETUP

5 SETTINGS

LCD MESSAGE ENGAGE MESSAGE SETTING Flash Message Time 0


OR AND

LATCHED

SETTINGS Top Text = XXXXXXXXXX On Text = XXXXXXXXXX

TRST

From user-programmable pushbuttons logic sheet 1, 842021A3

Instantaneous reset * FLEXLOGIC OPERAND PUSHBUTTON 1 OFF

LATCHED/SELF-RESET

AND

PUSHBUTTON ON

FLEXLOGIC OPERAND PUSHBUTTON 1 ON

SETTING Message Priority = Disabled = High Priority = Normal

The message is temporarily removed if any keypad button is pressed. Ten (10) seconds of keypad inactivity restores the message.
AND

LCD MESSAGE ENGAGE MESSAGE SETTINGS Top Text


OR

= XXXXXXXXXX On Text = XXXXXXXXXX

SETTING Flash Message Time 0


AND

TRST Instantaneous reset * PUSHBUTTON 1 LED LOGIC


1. If pushbutton 1 LED control is set to off. Pushbutton 1 LED

Instantaneous reset will be executed if any front panel button is pressed or any new target or message becomes active.

FLEXLOGIC OPERAND PUSHBUTTON 1 ON PUSHBUTTON 2 ON PUSHBUTTON 3 ON

FLEXLOGIC OPERAND PUSHBUTTON 1 ON FLEXLOGIC OPERAND ANY PB ON


2. If pushbutton 1 LED control is not set to off.

OR

SETTING PUSHBTN 1 LED CTL = any FlexLogic operand

Pushbutton 1 LED

PUSHBUTTON 16 ON The enhanced front panel has 16 operands; the standard front panel has 12
842024A2.CDR

Figure 59: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 2 of 2) User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via EnerVista UR Setup with the Maintenance > Enable Pushbutton command. 5.2.13 FLEX STATE PARAMETERS
PATH: SETTINGS PRODUCT SETUP FLEX STATE PARAMETERS

NOTE

FLEX STATE PARAMETERS


MESSAGE

PARAMETER Off PARAMETER Off

MESSAGE

1: 2:

Range: FlexLogic operand

Range: FlexLogic operand

PARAMETER 256: Off

Range: FlexLogic operand

This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient monitoring. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are packed so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which are of interest to the user are available in a minimum number of Modbus registers.

5-48

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

The state bits may be read out in the Flex States register array beginning at Modbus address 0900h. Sixteen states are packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommodate the 256 state bits. 5.2.14 USER-DEFINABLE DISPLAYS a) MAIN MENU
PATH: SETTINGS PRODUCT SETUP USER-DEFINABLE DISPLAYS

USER-DEFINABLE DISPLAYS
MESSAGE

INVOKE AND SCROLL: Off USER DISPLAY USER DISPLAY

MESSAGE

Range: FlexLogic operand

1 2

Range: up to 20 alphanumeric characters

Range: up to 20 alphanumeric characters

MESSAGE

USER DISPLAY 16

Range: up to 20 alphanumeric characters

This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing sequence in the USER DISPLAYS menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus facilitate text entry and Modbus register data pointer options for defining the user display content. Once programmed, the user-definable displays can be viewed in two ways. KEYPAD: Use the MENU key to select the USER DISPLAYS menu item to access the first user-definable display (note that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The DISPLAY PROPERdisplay disappears after the default message time-out period specified by the PRODUCT SETUP TIES DEFAULT MESSAGE TIMEOUT setting. USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate the programmed displays. On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by showing the last user-definable display shown during the previous activity. From this moment onward, the operand acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first one. The INVOKE AND SCROLL input and the DOWN key operate concurrently. When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay will start to cycle through the user displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user display, not at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.

GE Multilin

C30 Controller System

5-49

5.2 PRODUCT SETUP b) USER DISPLAY 1(16)


PATH: SETTINGS PRODUCT SETUP USER-DEFINABLE DISPLAYS USER DISPLAY 1(16)

5 SETTINGS

USER DISPLAY 1

DISP 1 TOP LINE: DISP 1 BOTTOM LINE: DISP 1 ITEM 1 0 DISP 1 ITEM 2 0 DISP 1 ITEM 3 0 DISP 1 ITEM 4 0 DISP 1 ITEM 5: 0

Range: up to 20 alphanumeric characters

Range: up to 20 alphanumeric characters

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Range: 0 to 65535 in steps of 1

MESSAGE

Any existing system display can be automatically copied into an available user display by selecting the existing display and pressing the ENTER key. The display will then prompt ADD TO USER DISPLAY LIST?. After selecting Yes, a message indicates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus are automatically configured with the proper content this content may subsequently be edited. This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user display. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the start of a data field - the length of the data field needs to be accounted for. Up to five separate data fields can be entered in a user display - the nth tilde (~) refers to the nth item. A User Display may be entered from the faceplate keypad or the EnerVista UR Setup interface (preferred for convenience). The following procedure shows how to enter text characters in the top and bottom lines from the faceplate keypad: 1. 2. 3. 4. 5. 6. 7. Select the line to be edited. Press the decimal key to enter text edit mode. Use either VALUE key to scroll through the characters. A space is selected like a character. Press the decimal key to advance the cursor to the next position. Repeat step 3 and continue entering characters until the desired text is displayed. The HELP key may be pressed at any time for context sensitive help information. Press the ENTER key to store the new settings.

To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the faceplate keypad, use the number keypad. Use the value of 0 for any items not being used. Use the HELP key at any selected system display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this conversion). Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays will show in sequence, changing every 4 seconds. While viewing a user display, press the ENTER key and then select the Yes option to remove the display from the user display list. Use the MENU key again to exit the user displays menu.

5-50

C30 Controller System

GE Multilin

5 SETTINGS An example user display setup and result is shown below: USER DISPLAY 1 DISP 1 TOP LINE: Current X ~ A
MESSAGE

5.2 PRODUCT SETUP

Shows user-defined text with first Tilde marker.

DISP 1 BOTTOM LINE: Current Y ~ A DISP 1 ITEM 1: 6016 DISP 1 ITEM 2: 6357 DISP 1 ITEM 3: 0 DISP 1 ITEM 4: 0 DISP 1 ITEM 5: 0

Shows user-defined text with second Tilde marker.

MESSAGE

Shows decimal form of user-selected Modbus Register Address, corresponding to first Tilde marker. Shows decimal form of user-selected Modbus Register Address, corresponding to 2nd Tilde marker. This item is not being used - there is no corresponding Tilde marker in Top or Bottom lines. This item is not being used - there is no corresponding Tilde marker in Top or Bottom lines. This item is not being used - there is no corresponding Tilde marker in Top or Bottom lines.

MESSAGE

MESSAGE

MESSAGE

MESSAGE

USER DISPLAYS

Current X Current Y

0.850 A 0.327 A

Shows the resultant display content.

5.2.15 DIRECT INPUTS AND OUTPUTS a) MAIN MENU


PATH: SETTINGS PRODUCT SETUP DIRECT I/O

DIRECT I/O

DIRECT OUTPUT DEVICE ID: 1


MESSAGE

Range: 1 to 16

DIRECT I/O CH1 RING CONFIGURATION: Yes DIRECT I/O CH2 RING CONFIGURATION: Yes DIRECT I/O DATA RATE: 64 kbps DIRECT I/O CHANNEL CROSSOVER: Disabled CRC ALARM CH1 CRC ALARM CH2 UNRETURNED MESSAGES ALARM CH1 UNRETURNED MESSAGES ALARM CH2

Range: Yes, No

Range: Yes, No

MESSAGE

Range: 64 kbps, 128 kbps

MESSAGE

Range: Disabled, Enabled

MESSAGE

MESSAGE

See page 557. See page 557. See page 558. See page 558.

MESSAGE

MESSAGE

MESSAGE

Direct inputs and outputs are intended for exchange of status information (inputs and outputs) between UR-series relays connected directly via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GSSE, except that communications takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that support two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output

GE Multilin

C30 Controller System

5-51

5.2 PRODUCT SETUP

5 SETTINGS

messages both ways around a ring configuration. On type 7 cards that support one channel, direct output messages are sent only in one direction. Messages will be resent (forwarded) when it is determined that the message did not originate at the receiver. Direct output message timing is similar to GSSE message timing. Integrity messages (with no state changes) are sent at least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by the following FlexLogic operands: 1. 2.
DIRECT RING BREAK (direct input/output ring break). This FlexLogic operand indicates that direct output messages

sent from a UR-series relay are not being received back by the relay.
DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic operands indicate that direct

output messages from at least one direct device are not being received. Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID. The DIRECT OUTPUT DEVICE ID setting identifies the relay in all direct output messages. All UR-series IEDs in a ring should have unique numbers assigned. The IED ID is used to identify the sender of the direct input and output message.
CH2 RING CONFIGURATION

If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O is Yes), all direct output messages should be received back. If not, the direct input/output ring break self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic operand.

Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communications cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each bridge.

5-52

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

Table 55: DIRECT INPUT AND OUTPUT DATA RATES


MODULE 74 7L 7M 7P 7T 7W 7V 2A 2B 2G 2H 76 77 75 7E 7F 7G 7Q 7R 7S CHANNEL Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 1 Channel 2 Channel 1 Channel 1 Channel 1 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 2 Channel 1 Channel 1 Channel 2 SUPPORTED DATA RATES 64 kbps 64 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps, 128 kbps 64 kbps 64 kbps 64 kbps 128 kbps 128 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps 64 kbps

The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.
NOTE

The DIRECT I/O CHANNEL CROSSOVER setting applies to C30s with dual-channel communication cards and allows crossing over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network regardless of the physical media of the two communication channels. The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic operands (flags, bits) to be exchanged.

GE Multilin

C30 Controller System

5-53

5.2 PRODUCT SETUP EXAMPLE 1: EXTENDING THE INPUT/OUTPUT CAPABILITIES OF A UR-SERIES RELAY

5 SETTINGS

Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional input and output and programmable logic requirements. The two IEDs are connected via single-channel digital communication cards as shown in the figure below.

TX1

UR IED 1
RX1

TX1

UR IED 2
RX1
842711A1.CDR

Figure 510: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O DATA RATE: 128 kbps

Yes

For UR-series IED 2:

DIRECT OUTPUT DEVICE ID: 2 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O DATA RATE: 128 kbps

Yes

The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is, from device 1 to device 2, and from device 2 to device 1. Different communications cards can be selected by the user for this back-to-back connection (for example: fiber, G.703, or RS422). EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION A simple interlocking busbar protection scheme could be accomplished by sending a blocking signal from downstream devices, say 2, 3, and 4, to the upstream device that monitors a single incomer of the busbar, as shown below.

UR IED 1

BLOCK

UR IED 2

UR IED 3

UR IED 4

842712A1.CDR

Figure 511: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application.

5-54

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

TX1

RX1

UR IED 1
RX2 TX2

RX1

TX2

RX2

TX1

UR IED 2
TX1 RX2 TX2

UR IED 4
RX1

TX2

RX2

UR IED 3
RX1 TX1

842716A1.CDR

Figure 512: INTERLOCKING BUS PROTECTION SCHEME VIA DIRECT INPUTS/OUTPUTS In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 2:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 3:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 4:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

Message delivery time is approximately 0.2 of power system cycle (at 128 kbps) times number of bridges between the origin and destination. Dual-ring configuration effectively reduces the maximum communications distance by a factor of two. In this configuration the following delivery times are expected (at 128 kbps) if both rings are healthy: IED 1 to IED 2: 0.2 of power system cycle; IED 1 to IED 3: 0.4 of power system cycle; IED 1 to IED 4: 0.2 of power system cycle; IED 2 to IED 3: 0.2 of power system cycle; IED 2 to IED 4: 0.4 of power system cycle; IED 3 to IED 4: 0.2 of power system cycle. If one ring is broken (say TX2-RX2) the delivery times are as follows: IED 1 to IED 2: 0.2 of power system cycle; IED 1 to IED 3: 0.4 of power system cycle; IED 1 to IED 4: 0.6 of power system cycle; IED 2 to IED 3: 0.2 of power system cycle; IED 2 to IED 4: 0.4 of power system cycle; IED 3 to IED 4: 0.2 of power system cycle. A coordinating timer for this bus protection scheme could be selected to cover the worst case scenario (0.4 of a power system cycle). Upon detecting a broken ring, the coordination time should be adaptively increased to 0.6 of a power system cycle. The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns.

GE Multilin

C30 Controller System

5-55

5.2 PRODUCT SETUP EXAMPLE 3: PILOT-AIDED SCHEMES Consider the three-terminal line protection application shown below:
UR IED 1

5 SETTINGS

UR IED 2

UR IED 3

842713A1.CDR

Figure 513: THREE-TERMINAL LINE APPLICATION A permissive pilot-aided scheme could be implemented in a two-ring configuration as shown below (IEDs 1 and 2 constitute a first ring, while IEDs 2 and 3 constitute a second ring):

TX1

RX1

RX2

UR IED 1
RX1 TX1

UR IED 2
TX2

5
RX1

UR IED 3
TX1
842714A1.CDR

Figure 514: SINGLE-CHANNEL OPEN LOOP CONFIGURATION In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 2:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 3:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

In this configuration the following delivery times are expected (at 128 kbps): IED 1 to IED 2: 0.2 of power system cycle; IED 1 to IED 3: 0.5 of power system cycle; IED 2 to IED 3: 0.2 of power system cycle. In the above scheme, IEDs 1 and 3 do not communicate directly. IED 2 must be configured to forward the messages as explained in the Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below.

5-56

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP

TX2

TX1

RX1

RX2

UR IED 1
RX1 RX2 TX2

UR IED 2
TX1

TX1

RX1

UR IED 3
RX2 TX2
842715A1.CDR

Figure 515: DUAL-CHANNEL CLOSED LOOP (DUAL-RING) CONFIGURATION In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 2:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

For UR-series IED 3:


DIRECT OUTPUT DEVICE ID: 1 DIRECT I/O CH1 RING CONFIGURATION: DIRECT I/O CH2 RING CONFIGURATION:

Yes Yes

In this configuration the following delivery times are expected (at 128 kbps) if both the rings are healthy: IED 1 to IED 2: 0.2 of power system cycle; IED 1 to IED 3: 0.2 of power system cycle; IED 2 to IED 3: 0.2 of power system cycle. The two communications configurations could be applied to both permissive and blocking schemes. Speed, reliability and cost should be taken into account when selecting the required architecture. b) CRC ALARM CH1(2)
PATH: SETTINGS PRODUCT SETUP DIRECT I/O CRC ALARM CH1(2) Range: Enabled, Disabled

CRC ALARM CH1

CRC ALARM CH1 FUNCTION: Disabled


MESSAGE

CRC ALARM CH1 MESSAGE COUNT: 600 CRC ALARM CH1 THRESHOLD: 10 CRC ALARM CH1 EVENTS: Disabled

Range: 100 to 10000 in steps of 1

Range: 1 to 1000 in steps of 1

MESSAGE

Range: Enabled, Disabled

MESSAGE

The C30 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter adds up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the CRC ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC ALARM FlexLogic operand is set. When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT setting, both the counters reset and the monitoring process is restarted.

GE Multilin

C30 Controller System

5-57

5.2 PRODUCT SETUP

5 SETTINGS

The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based output. Latching and acknowledging conditions - if required - should be programmed accordingly. The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that failed the CRC check is available as the ACTUAL VALUES STATUS DIRECT INPUTS CRC FAIL COUNT CH1 actual value. Message count and length of the monitoring window: To monitor communications integrity, the relay sends 1 message per second (at 64 kbps) or 2 messages per second (128 kbps) even if there is no change in the direct outputs. For example, setting the CRC ALARM CH1 MESSAGE COUNT to 10000, corresponds a time window of about 160 minutes at 64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity, the monitoring time interval will shorten. This should be taken into account when determining the CRC ALARM CH1 MESSAGE COUNT setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC ALARM CH1 MESSAGE COUNT should be set to 10 60 1 = 600. Correlation of failed CRC and bit error rate (BER): The CRC check may fail if one or more bits in a packet are corrupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain assumptions an approximation can be made as follows. A direct input and output packet containing 20 bytes results in 160 bits of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 104 implies 1 bit error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet, having 1 failed packet for every 63 received is about equal to a BER of 104.

c) UNRETURNED MESSAGES ALARM CH1(2)


PATH: SETTINGS PRODUCT SETUP DIRECT I/O UNRETURNED MESSAGES ALARM CH1(2) Range: Enabled, Disabled

UNRETURNED MESSAGES ALARM CH1

UNRET MSGS ALARM CH1 FUNCTION: Disabled UNRET MSGS ALARM CH1 MESSAGE COUNT: 600 UNRET MSGS ALARM CH1 THRESHOLD: 10 UNRET MSGS ALARM CH1 EVENTS: Disabled

Range: 100 to 10000 in steps of 1

MESSAGE

Range: 1 to 1000 in steps of 1

MESSAGE

Range: Enabled, Disabled

MESSAGE

The C30 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unreturned messages. This function counts all the outgoing messages and a separate counter adds the messages have failed to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS ALARM CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1 UNRET ALM FlexLogic operand is set. When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE COUNT setting, both the counters reset and the monitoring process is restarted. The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based output. Latching and acknowledging conditions, if required, should be programmed accordingly. The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration. The total number of unreturned input and output messages is available as the ACTUAL VALUES STATUS DIRECT INPUTS UNRETURNED MSG COUNT CH1 actual value.

5-58

C30 Controller System

GE Multilin

5 SETTINGS

5.2 PRODUCT SETUP 5.2.16 TELEPROTECTION

PATH: SETTINGS

PRODUCT SETUP

TELEPROTECTION

TELEPROTECTION

TELEPROTECTION FUNCTION: Disabled


MESSAGE

Range: Disabled, Enabled

NUMBER OF TERMINALS: 2 NUMBER OF COMM CHANNELS: 1 LOCAL RELAY ID NUMBER: 0 TERMINAL 1 RELAY ID NUMBER: 0 TERMINAL 2 RELAY ID NUMBER: 0

Range: 2, 3

Range: 1, 2

MESSAGE

Range: 0 to 255 in steps of 1

MESSAGE

Range: 0 to 255 in steps of 1

MESSAGE

Range: 0 to 255 in steps of 1

MESSAGE

Digital teleprotection functionality is designed to transfer protection commands between two or three relays in a secure, fast, dependable, and deterministic fashion. Possible applications are permissive or blocking pilot schemes and direct transfer trip (DTT). Teleprotection can be applied over any analog or digital channels and any communications media, such as direct fiber, copper wires, optical networks, or microwave radio links. A mixture of communication media is possible. Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted continuously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel data is achieved by using CRC-32 on the data packet. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive as such, they cannot be used simulatneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and vice versa.

NOTE

NUMBER OF TERMINALS: Specifies whether the teleprotection system operates between two peers or three peers. NUMBER OF CHANNELS: Specifies how many channels are used. If the NUMBER OF TERMINALS is 3 (three-terminal system), set the NUMBER OF CHANNELS to 2. For a two-terminal system, the NUMBER OF CHANNELS can set to 1 or 2 (redundant channels). LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER: In installations that use multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line is from the correct relays. The teleprotection function performs this check by reading the message ID sent by transmitting relays and comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inadvertently set to loopback mode or data is being received from a wrong relay by checking the ID on a received channel. If an incorrect ID is found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL FlexLogic operand is set, driving the event with the same name and blocking the teleprotection inputs. For commisCHANNEL TESTS VALIDITY OF sioning purposes, the result of channel identification is also shown in the STATUS CHANNEL CONFIGURATION actual value. The default value of 0 for the LOCAL RELAY ID NUMBER indicates that relay ID is not to be checked. On two- terminals two-channel systems, the same LOCAL RELAY ID NUMBER is transmitted over both channels; as such, only the TERMINAL 1 ID NUMBER has to be programmed on the receiving end. 5.2.17 INSTALLATION

PATH: SETTINGS

PRODUCT SETUP

INSTALLATION

INSTALLATION

RELAY SETTINGS: Not Programmed


MESSAGE

Range: Not Programmed, Programmed

RELAY NAME: Relay-1

Range: up to 20 alphanumeric characters

GE Multilin

C30 Controller System

5-59

5.2 PRODUCT SETUP

5 SETTINGS

To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output relay until RELAY SETTINGS is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The UNIT NOT PROGRAMMED self-test error message is displayed until the relay is put into the "Programmed" state. The RELAY NAME setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet communications channel using the IEC 61850 protocol.

5-60

C30 Controller System

GE Multilin

5 SETTINGS 5.3REMOTE RESOURCES

5.3 REMOTE RESOURCES 5.3.1 REMOTE RESOURCES CONFIGURATION

When C30 is ordered with a process card module as a part of HardFiber system, then an additional Remote Resources menu tree is available in EnerVista UR Setup software to allow configuring HardFiber system.

Figure 516: REMOTE RESOURCES CONFIGURATION MENU The remote resources settings configure a C30 with a process bus module to work with devices called Bricks. Remote resources configuration is only available through the EnerVista UR Setup software, and is not available through the C30 front panel. A Brick provides eight AC measurements, along with contact inputs, DC analog inputs, and contact outputs, to be the remote interface to field equipment such as circuit breakers and transformers. The C30 with a process bus module has access to all of the capabilities of up to eight Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the C30 process card and specific Brick. The relay is then configured to measure specific currents, voltages and contact inputs from those Bricks, and to control specific outputs. The configuration process for remote resources is straightforward and consists of the following steps. Configure the field units. This establishes the point-to-point connection between a specific port on the relay process bus module, and a specific digital core on a specific Brick. This is a necessary first step in configuring a process bus relay. Configure the AC banks. This sets the primary and secondary quantities and connections for currents and voltages. AC bank configuration also provides a provision for redundant measurements for currents and voltages, a powerful reliability improvement possible with process bus. Configure signal sources. This functionality of the C30 has not changed other than the requirement to use currents and voltages established by AC bank configuration under the remote resources menu. Configure field contact inputs, field contact outputs, RTDs, and transducers as required for the application's functionality. These inputs and outputs are the physical interface to circuit breakers, transformers, and other equipment. They replace the traditional contact inputs and outputs located at the relay to virtually eliminate copper wiring. Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are distinct binary channels that provide high-speed protection quality signaling between relays through a Brick.

For additional information on how to configure a relay with a process bus module, please refer to GE publication number GEK-113500: HardFiber System Instruction Manual.

GE Multilin

C30 Controller System

5-61

5.4 SYSTEM SETUP 5.4SYSTEM SETUP


PATH: SETTINGS SYSTEM SETUP BREAKERS BREAKER 1 Range: Disabled, Enabled

5 SETTINGS 5.4.1 BREAKERS

BREAKER 1

BREAKER 1 FUNCTION: Disabled


MESSAGE

BREAKER1 PUSH BUTTON CONTROL: Disabled BREAKER 1 NAME: Bkr 1 BREAKER 1 MODE: 3-Pole BREAKER 1 OPEN: Off BREAKER 1 BLK OPEN: Off BREAKER 1 CLOSE: Off BREAKER 1 BLK CLOSE: Off BREAKER 1 A/3P CLSD: Off BREAKER 1 A/3P OPND: Off BREAKER 1 B CLOSED: Off BREAKER 1 B OPENED: Off BREAKER 1 C CLOSED: Off BREAKER 1 C OPENED: Off BREAKER 1 Toperate: 0.070 s BREAKER 1 EXT ALARM: Off BREAKER 1 ALARM DELAY: 0.000 s MANUAL CLOSE RECAL1 TIME: 0.000 s BREAKER 1 OUT OF SV: Off BREAKER 1 EVENTS: Disabled

Range: Disabled, Enabled

Range: up to 6 alphanumeric characters

MESSAGE

Range: 3-Pole, 1-Pole

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: 0.000 to 2.000 s in steps of 0.001

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: 0.000 to 1 000 000.000 s in steps of 0.001

MESSAGE

Range: 0.000 to 1 000 000.000 s in steps of 0.001

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Disabled, Enabled

MESSAGE

5-62

C30 Controller System

GE Multilin

5 SETTINGS

5.4 SYSTEM SETUP

A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only information concerning programming of the associated settings is covered here. These features are provided for two or more breakers; a user may use only those portions of the design relevant to a single breaker, which must be breaker 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the C30. The following settings are available for each breaker control element. BREAKER 1 FUNCTION: This setting enables and disables the operation of the breaker control feature. BREAKER1 PUSH BUTTON CONTROL: Set to Enable to allow faceplate push button operations. BREAKER 1 NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used in flash messages related to breaker 1. BREAKER 1 MODE: This setting selects 3-pole mode, where all breaker poles are operated simultaneously, or 1pole mode where all breaker poles are operated either independently or simultaneously. BREAKER 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to open breaker 1. BREAKER 1 BLK OPEN: This setting selects an operand that prevents opening of the breaker. This setting can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA. BREAKER 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay to close breaker 1. BREAKER 1 BLK CLOSE: This setting selects an operand that prevents closing of the breaker. This setting can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA. BREAKER 1 A/3P CLOSED: This setting selects an operand, usually a contact input connected to a breaker auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when the breaker is closed. If the BREAKER 1 MODE setting is selected as 3-Pole, this setting selects a single input as the operand used to track the breaker open or closed position. If the mode is selected as 1-Pole, the input mentioned above is used to track phase A and the BREAKER 1 B and BREAKER 1 C settings select operands to track phases B and C, respectively. BREAKER 1 A/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed 52/b status input to create a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the inverted BREAKER 1 CLOSED status signal can be used. BREAKER 1 B CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the breaker phase B closed position as above for phase A. BREAKER 1 B OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the breaker phase B opened position as above for phase A. BREAKER 1 C CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the breaker phase C closed position as above for phase A. BREAKER 1 C OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the breaker phase C opened position as above for phase A. BREAKER 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 52/a and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the BREAKER 1 BAD STATUS FlexLogic operand is asserted from alarm or blocking purposes. BREAKER 1 EXT ALARM: This setting selects an operand, usually an external contact input, connected to a breaker alarm reporting contact. BREAKER 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation of the poles. MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after an operator has initiated a manual close command to operate a circuit breaker. BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service.

GE Multilin

C30 Controller System

5-63

5.4 SYSTEM SETUP

5 SETTINGS

SETTING BREAKER 1 FUNCTION = Enabled = Disabled SETTING BREAKER 1 BLOCK OPEN Off = 0 D60, L60, and L90 devices only from trip output FLEXLOGIC OPERANDS TRIP PHASE A TRIP PHASE B TRIP PHASE C TRIP 3-POLE SETTING BREAKER 1 OPEN Off = 0
OR

AND

FLEXLOGIC OPERANDS BREAKER 1 OFF CMD BREAKER 1 TRIP A BREAKER 1 TRIP B BREAKER 1 TRIP C

AND

AND

AND

61850 Select & Open


USER 3 OFF/ON To open BRK1-(Name)
AND

BKR ENABLED

To breaker control logic sheet 2, 842025A1

SETTING BREAKER 1 PUSHBUTTON CONTROL = Enabled


AND

USER 2 OFF/ON To open BRK1-(Name)

OR

SETTING BREAKER 1 CLOSE Off = 0

AND

OR

FLEXLOGIC OPERAND
AND

61850 Select & Close


C60, D60, L60, and L90 relays from recloser FLEXLOGIC OPERAND AR CLOSE BKR 1 SETTING BREAKER 1 BLOCK CLOSE Off = 0

SETTING MANUAL CLOSE RECAL1 TIME

BREAKER 1 MNL CLS

AND

FLEXLOGIC OPERAND
OR AND

BREAKER 1 ON CMD
827061AS.CDR

Figure 517: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the C30 is in Programmed mode and not in the local control mode.
NOTE

5-64

C30 Controller System

GE Multilin

5 SETTINGS

5.4 SYSTEM SETUP

from breaker control logic sheet 1, 827061AR

BKR ENABLED

SETTING BREAKER 1 MODE


= 3-Pole = 1-Pole

FLEXLOGIC OPERAND
AND OR AND

BREAKER 1 CLOSED

BREAKER 1 CLOSED (DEFAULT)

FLEXLOGIC OPERAND
AND AND OR

BREAKER 1 OPEN

SETTING BREAKER 1 A/3P CLSD = Off


AND

BREAKER 1 OPEN (DEFAULT)

FLEXLOGIC OPERAND
AND

BREAKER 1 DISCREP

SETTING BREAKER 1 B CLSD


= Off

SETTING BREAKER 1 ALARM DELAY


AND

0 FLEXLOGIC OPERAND SETTING BREAKER 1 C CLSD


= Off
OR AND AND

BREAKER 1 TROUBLE
Note: the BREAKER 1 TROUBLE LED can be latched using FlexLogic

BREAKER 1 TROUBLE (DEFAULT)

SETTING BREAKER 1 EXT ALARM


= Off
XOR

FLEXLOGIC OPERAND SETTING BREAKER 1 Toperate


AND OR

BREAKER 1 BAD STATUS FLEXLOGIC OPERANDS

SETTING BREAKER 1 A/3P OPND = Off

0
AND

AND AND AND

BREAKER 1 A BAD ST BREAKER 1 A CLSD BREAKER 1 A OPEN BREAKER 1 A INTERM

SETTING BREAKER 1 Toperate

AND

FLEXLOGIC OPERANDS
AND

XOR

SETTING BREAKER 1 B OPENED = Off

0
AND

AND AND AND

BREAKER 1 B BAD ST BREAKER 1 B CLSD BREAKER 1 B OPEN BREAKER 1 B INTERM

SETTING BREAKER 1 Toperate

AND

FLEXLOGIC OPERANDS
AND XOR

SETTING BREAKER 1 C OPENED = Off

0
AND

AND AND AND

BREAKER 1 C BAD ST BREAKER 1 C CLSD BREAKER 1 C OPEN BREAKER 1 C INTERM

AND

FLEXLOGIC OPERANDS
AND AND

SETTING BREAKER 1 OUT OF SV


= Off

AND XOR AND

BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS

842025A1.CDR

Figure 518: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2)

GE Multilin

C30 Controller System

5-65

5.4 SYSTEM SETUP

5 SETTINGS 5.4.2 DISCONNECT SWITCHES

PATH: SETTINGS

SYSTEM SETUP

SWITCHES

SWITCH 1 Range: Disabled, Enabled

SWITCH 1

SWITCH 1 FUNCTION: Disabled


MESSAGE

SWITCH 1 NAME: SW 1 SWITCH 1 MODE: 3-Pole SWITCH 1 OPEN: Off SWITCH 1 BLK OPEN: Off SWITCH 1 CLOSE: Off SWITCH 1 BLK CLOSE: Off SWTCH 1 A/3P CLSD: Off SWTCH 1 A/3P OPND: Off SWITCH 1 B CLOSED: Off SWITCH 1 B OPENED: Off SWITCH 1 C CLOSED: Off SWITCH 1 C OPENED: Off SWITCH 1 Toperate: 0.070 s SWITCH 1 ALARM DELAY: 0.000 s SWITCH 1 EVENTS: Disabled

Range: up to 6 alphanumeric characters

Range: 3-Pole, 1-Pole

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: 0.000 to 2.000 s in steps of 0.001

MESSAGE

Range: 0.000 to 1 000 000.000 s in steps of 0.001

MESSAGE

Range: Disabled, Enabled

MESSAGE

The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to create an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the C30. SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element. SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used in flash messages related to disconnect switch 1. SWITCH 1 MODE: This setting selects 3-pole mode, where all disconnect switch poles are operated simultaneously, or 1-pole mode where all disconnect switch poles are operated either independently or simultaneously.

5-66

C30 Controller System

GE Multilin

5 SETTINGS

5.4 SYSTEM SETUP

SWITCH 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to open disconnect switch 1. SWITCH 1 BLK OPEN: This setting selects an operand that prevents opening of the disconnect switch. This setting can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA. SWITCH 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay to close disconnect switch 1. SWITCH 1 BLK CLOSE: This setting selects an operand that prevents closing of the disconnect switch. This setting can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA. SWTCH 1 A/3P CLSD: This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when the disconnect switch is closed. If the SWITCH 1 MODE setting is selected as 3-Pole, this setting selects a single input as the operand used to track the disconnect switch open or closed position. If the mode is selected as 1-Pole, the input mentioned above is used to track phase A and the SWITCH 1 B and SWITCH 1 C settings select operands to track phases B and C, respectively. SWITCH 1 A/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed 52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not available, then the inverted SWITCH 1 CLOSED status signal can be used. SWITCH 1 B CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A. SWITCH 1 B OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A. SWITCH 1 C CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A. SWITCH 1 C OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A. SWITCH 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 52/a and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has expired, the SWITCH 1 BAD STATUS FlexLogic operand is asserted from alarm or blocking purposes. SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the C30 is in Programmed mode and not in the local control mode.
NOTE

GE Multilin

C30 Controller System

5-67

5.4 SYSTEM SETUP

5 SETTINGS

SETTING SWITCH 1 FUNCTION = Disabled = Enabled SETTING SWITCH 1 OPEN


= Off
OR AND

FLEXLOGIC OPERAND SWITCH 1 OFF CMD

SETTING SWITCH 1 BLK OPEN


= Off

61850 Select & Open

SETTING SWITCH 1 CLOSE


= Off
OR AND

FLEXLOGIC OPERAND SWITCH 1 ON CMD

SETTING SWITCH 1 BLK CLOSE


= Off

61850 Select & Close

SETTING SWITCH 1 MODE


= 3-Pole = 1-Pole

FLEXLOGIC OPERAND
AND OR AND

SWITCH 1 CLOSED

FLEXLOGIC OPERAND
AND OR AND

SWITCH 1 OPEN

SETTING SWTCH 1 A/3P CLSD


= Off
AND AND

FLEXLOGIC OPERAND SWITCH 1 DISCREP

SETTING SWITCH 1 B CLOSED


= Off

SETTING SWITCH 1 ALARM DELAY


AND

0 FLEXLOGIC OPERAND
OR AND AND

SWITCH 1 TROUBLE

SETTING SWITCH 1 C CLOSED


= Off

FLEXLOGIC OPERAND SETTING SWITCH 1 Toperate


AND XOR OR

SWITCH 1 BAD STATUS FLEXLOGIC OPERANDS

SETTING SWTCH 1 A/3P OPND


= Off

0
AND

AND AND AND

SWITCH 1 A BAD ST SWITCH 1 A CLSD SWITCH 1 A OPEN SWITCH 1 A INTERM

SETTING SWITCH 1 Toperate

AND

FLEXLOGIC OPERANDS
AND XOR

SETTING SWITCH 1 B OPENED


= Off

0
AND

AND AND AND

SWITCH 1 B BAD ST SWITCH 1 B CLSD SWITCH 1 B OPEN SWITCH 1 B INTERM

SETTING SWITCH 1 Toperate

AND

FLEXLOGIC OPERANDS
AND XOR

SETTING SWITCH 1 C OPENED


= Off

0
AND

AND AND

SWITCH 1 C BAD ST SWITCH 1 C CLSD SWITCH 1 C OPEN SWITCH 1 C INTERM

AND

AND 842026A3.CDR

Figure 519: DISCONNECT SWITCH SCHEME LOGIC

5-68

C30 Controller System

GE Multilin

5 SETTINGS 5.5FLEXLOGIC

5.5 FLEXLOGIC 5.5.1 INTRODUCTION TO FLEXLOGIC

To provide maximum flexibility to the user, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon which individual features are designed is fixed, and all other logic, from digital input signals through elements or combinations of elements to digital outputs, is variable. The user has complete control of all variable logic through FlexLogic. In general, the system receives analog and digital inputs which it uses to produce analog and digital outputs. The major sub-systems of a generic UR-series relay involved in this process are shown below.

Figure 520: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the C30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital 1 is represented by a 'set' flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output. The state of the contact input can be displayed locally or viewed remotely via the communications facilities provided. If a simple scheme where a contact input is used to block an element is desired, this selection is made when programming the element. This capability also applies to the other features that set flags: elements, virtual inputs, remote inputs, schemes, and human operators. If more complex logic than presented above is required, it is implemented via FlexLogic. For example, if it is desired to have the closed state of contact input H7a and the operated state of the phase undervoltage element block the operation of the phase time overcurrent element, the two control input states are programmed in a FlexLogic equation. This equation ANDs the two control inputs to produce a virtual output which is then selected when programming the phase time overcurrent to be used as a blocking input. Virtual outputs can only be created by FlexLogic equations. Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic minimizes the requirement for auxiliary components and wiring while making more complex schemes possible.

GE Multilin

C30 Controller System

5-69

5.5 FLEXLOGIC

5 SETTINGS

The logic that determines the interaction of inputs, elements, schemes and outputs is field programmable through the use of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is available internally and on the communication ports for other relays to use (distributed FlexLogic). FlexLogic allows users to customize the relay through a series of equations that consist of operators and operands. The operands are the states of inputs, elements, schemes and outputs. The operators are logic gates, timers and latches (with set and reset inputs). A system of sequential operations allows any combination of specified operands to be assigned as inputs to specified operators to create an output. The final output of an equation is a numbered register called a virtual output. Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a seal-in or other type of feedback. A FlexLogic equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0. Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of parameters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, i.e. flag set) or 0 (=OFF, i.e. flag not set). Each equation is evaluated at least 4 times every power system cycle. Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of operands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 56: C30 FLEXLOGIC OPERAND TYPES
OPERAND TYPE Contact Input STATE On Off EXAMPLE FORMAT Cont Ip On Cont Ip Off Cont Op 1 Ion Cont Op 1 VOn Cont Op 1 VOff DIRECT INPUT 1 On Dig Element 1 PKP Dig Element 1 DPO Dig Element 1 OP CHARACTERISTICS [INPUT IS 1 (= ON) IF...] Voltage is presently applied to the input (external contact closed). Voltage is presently not applied to the input (external contact open). Current is flowing through the contact. Voltage exists across the contact. Voltage does not exists across the contact. The direct input is presently in the ON state. The input operand is at logic 1. This operand is the logical inverse of the above PKP operand. The input operand has been at logic 1 for the programmed pickup delay time, or has been at logic 1 for this period and is now at logic 0 but the reset timer has not finished timing. The number of pulses counted is above the set number. The number of pulses counted is equal to the set number. The number of pulses counted is below the set number. Logic 1 Logic 0 The remote input is presently in the ON state. The virtual input is presently in the ON state. The virtual output is presently in the set state (i.e. evaluation of the equation which produces this virtual output results in a "1").

Contact Output (type Form-A contact only) Direct Input Element (Digital)

Current On Voltage On Voltage Off On Pickup Dropout Operate

Element (Digital Counter)

Higher than Equal to Lower than On Off On On On

Counter 1 HI Counter 1 EQL Counter 1 LO On Off REMOTE INPUT 1 On Virt Ip 1 On Virt Op 1 On

Fixed Remote Input Virtual Input Virtual Output

5-70

C30 Controller System

GE Multilin

5 SETTINGS The operands available for this relay are listed alphabetically by types in the following table. Table 57: C30 FLEXLOGIC OPERANDS (Sheet 1 of 4)
OPERAND TYPE CONTROL PUSHBUTTONS OPERAND SYNTAX CONTROL PUSHBTN 1 ON CONTROL PUSHBTN 2 ON CONTROL PUSHBTN 3 ON CONTROL PUSHBTN 4 ON CONTROL PUSHBTN 5 ON CONTROL PUSHBTN 6 ON CONTROL PUSHBTN 7 ON DIRECT DEVICE 1On DIRECT DEVICE 16On DIRECT DEVICE 1Off DIRECT DEVICE 16Off DIR IO CH1 CRC ALARM DIR IO CH2 CRC ALARM DIR IO CH1 UNRET ALM DIR IO CH2 UNRET ALM ELEMENT: Eight-bit switch 8BIT SWITCH 1 BIT 0 8BIT SWITCH 1 BIT 1 8BIT SWITCH 1 BIT 2 8BIT SWITCH 1 BIT 3 8BIT SWITCH 1 BIT 4 8BIT SWITCH 1 BIT 5 8BIT SWITCH 1 BIT 6 8BIT SWITCH 1 BIT 7 8BIT SWITCH 2 to 8BIT SWITCH 6 ELEMENT: Breaker control BREAKER 1 OFF CMD BREAKER 1 ON CMD BREAKER 1 A BAD ST BREAKER 1 A INTERM BREAKER 1 A CLSD BREAKER 1 A OPEN BREAKER 1 B BAD ST BREAKER 1 A INTERM BREAKER 1 B CLSD BREAKER 1 B OPEN BREAKER 1 C BAD ST BREAKER 1 A INTERM BREAKER 1 C CLSD BREAKER 1 C OPEN BREAKER 1 BAD STATUS BREAKER 1 CLOSED BREAKER 1 OPEN BREAKER 1 DISCREP BREAKER 1 TROUBLE BREAKER 1 MNL CLS BREAKER 1 TRIP A BREAKER 1 TRIP B BREAKER 1 TRIP C BREAKER 1 ANY P OPEN BREAKER 1 ONE P OPEN BREAKER 1 OOS BREAKER 2... ELEMENT: Digital counters Counter 1 HI Counter 1 EQL Counter 1 LO Counter 2 to Counter 8 OPERAND DESCRIPTION Control pushbutton 1 is being pressed Control pushbutton 2 is being pressed Control pushbutton 3 is being pressed Control pushbutton 4 is being pressed Control pushbutton 5 is being pressed Control pushbutton 6 is being pressed Control pushbutton 7 is being pressed Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1

5.5 FLEXLOGIC

DIRECT DEVICES

DIRECT INPUT/ OUTPUT CHANNEL MONITORING

The rate of direct input messages received on channel 1 and failing the CRC exceeded the user-specified level. The rate of direct input messages received on channel 2 and failing the CRC exceeded the user-specified level. The rate of returned direct input/output messages on channel 1 exceeded the user-specified level (ring configurations only). The rate of returned direct input/output messages on channel 2 exceeded the user-specified level (ring configurations only). Bit 0 of eight-bit switch 1 asserted (the least significant bit) Bit 1 of eight-bit switch 1 asserted Bit 2 of eight-bit switch 1 asserted Bit 3 of eight-bit switch 1 asserted Bit 4 of eight-bit switch 1 asserted Bit 5 of eight-bit switch 1 asserted Bit 6 of eight-bit switch 1 asserted Bit 7 of eight-bit switch 1 asserted (the most significant bit) Same set of operands as shown for 8 BIT SWITCH 1 above Breaker 1 open command initiated Breaker 1 close command initiated Breaker 1 phase A bad status is detected (discrepancy between the 52/a and 52/b contacts) Breaker 1 phase A intermediate status is detected (transition from one position to another) Breaker 1 phase A is closed Breaker 1 phase A is open Breaker 1 phase B bad status is detected (discrepancy between the 52/a and 52/b contacts) Breaker 1 phase A intermediate status is detected (transition from one position to another) Breaker 1 phase B is closed Breaker 1 phase B is open Breaker 1 phase C bad status is detected (discrepancy between the 52/a and 52/b contacts) Breaker 1 phase A intermediate status is detected (transition from one position to another) Breaker 1 phase C is closed Breaker 1 phase C is open Breaker 1 bad status is detected on any pole Breaker 1 is closed Breaker 1 is open Breaker 1 has discrepancy Breaker 1 trouble alarm Breaker 1 manual close Breaker 1 trip phase A command Breaker 1 trip phase B command Breaker 1 trip phase C command At least one pole of breaker 1 is open Only one pole of breaker 1 is open Breaker 1 is out of service Same set of operands as shown for BREAKER 1 Digital counter 1 output is more than comparison value Digital counter 1 output is equal to comparison value Digital counter 1 output is less than comparison value Same set of operands as shown for Counter 1

GE Multilin

C30 Controller System

5-71

5.5 FLEXLOGIC Table 57: C30 FLEXLOGIC OPERANDS (Sheet 2 of 4)


OPERAND TYPE ELEMENT: Digital elements OPERAND SYNTAX Dig Element 1 PKP Dig Element 1 OP Dig Element 1 DPO Dig Element 2 to Dig Element 48 ELEMENT: FlexElements FxE 1 PKP FxE 1 OP FxE 1 DPO FxE 2 to FxE 8 ELEMENT Non-volatile latches ELEMENT: PID regulator LATCH 1 ON LATCH 1 OFF LATCH 2 to LATCH 16 PID 1 RAISE PID 1 LOWER PID 2 RAISE PID 2 LOWER PID 3 RAISE PID 3 LOWER PID 4 RAISE PID 4 LOWER SELECTOR 1 POS Y SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 SELECTOR 1 STP ALARM SELECTOR 1 BIT ALARM OPERAND DESCRIPTION Digital Element 1 is picked up Digital Element 1 is operated Digital Element 1 is dropped out Same set of operands as shown for Dig Element 1 FlexElement 1 has picked up FlexElement 1 has operated FlexElement 1 has dropped out Same set of operands as shown for FxE 1 Non-volatile latch 1 is ON (Logic = 1) Non-volatile latch 1 is OFF (Logic = 0) Same set of operands as shown for LATCH 1

5 SETTINGS

ELEMENT: Selector switch

5
ELEMENT: Disconnect switch

SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 2 SWITCH 1 OFF CMD SWITCH 1 ON CMD SWITCH 1 A BAD ST SWITCH 1 A INTERM SWITCH 1 A CLSD SWITCH 1 A OPEN SWITCH 1 B BAD ST SWITCH 1 A INTERM SWITCH 1 B CLSD SWITCH 1 B OPEN SWITCH 1 C BAD ST SWITCH 1 A INTERM SWITCH 1 C CLSD SWITCH 1 C OPEN SWITCH 1 BAD STATUS SWITCH 1 CLOSED SWITCH 1 OPEN SWITCH 1 DISCREP SWITCH 1 TROUBLE SWITCH 2... ELEMENT: Teleprotection channel tests TELEPRO CH1 FAIL TELEPRO CH2 FAIL TELEPRO CH1 ID FAIL TELEPRO CH2 ID FAIL TELEPRO CH1 CRC FAIL TELEPRO CH2 CRC FAIL TELEPRO CH1 PKT LOST TELEPRO CH2 PKT LOST

Selector switch 1 is in Position Y (mutually exclusive operands) First bit of the 3-bit word encoding position of selector 1 Second bit of the 3-bit word encoding position of selector 1 Third bit of the 3-bit word encoding position of selector 1 Position of selector 1 has been pre-selected with the stepping up control input but not acknowledged Position of selector 1 has been pre-selected with the 3-bit control input but not acknowledged Position of selector 1 has been pre-selected but not acknowledged Position of selector switch 1 is undetermined or restored from memory when the relay powers up and synchronizes to the three-bit input Same set of operands as shown above for SELECTOR 1 Disconnect switch 1 open command initiated Disconnect switch 1 close command initiated Disconnect switch 1 phase A bad status is detected (discrepancy between the 52/a and 52/b contacts) Disconnect switch 1 phase A intermediate status is detected (transition from one position to another) Disconnect switch 1 phase A is closed Disconnect switch 1 phase A is open Disconnect switch 1 phase B bad status is detected (discrepancy between the 52/a and 52/b contacts) Disconnect switch 1 phase A intermediate status is detected (transition from one position to another) Disconnect switch 1 phase B is closed Disconnect switch 1 phase B is open Disconnect switch 1 phase C bad status is detected (discrepancy between the 52/a and 52/b contacts) Disconnect switch 1 phase A intermediate status is detected (transition from one position to another) Disconnect switch 1 phase C is closed Disconnect switch 1 phase C is open Disconnect switch 1 bad status is detected on any pole Disconnect switch 1 is closed Disconnect switch 1 is open Disconnect switch 1 has discrepancy Disconnect switch 1 trouble alarm Same set of operands as shown for SWITCH 1 Channel 1 failed Channel 2 failed The ID check for a peer relay on channel 1 has failed The ID check for a peer relay on channel 2 has failed CRC detected packet corruption on channel 1 CRC detected packet corruption on channel 2 CRC detected lost packet on channel 1 CRC detected lost packet on channel 2

5-72

C30 Controller System

GE Multilin

5 SETTINGS Table 57: C30 FLEXLOGIC OPERANDS (Sheet 3 of 4)


OPERAND TYPE ELEMENT: Teleprotection inputs/outputs OPERAND SYNTAX TELEPRO INPUT 1-1 On TELEPRO INPUT 1-16 On TELEPRO INPUT 2-1 On TELEPRO INPUT 2-16 On TRIP BUS 1 PKP TRIP BUS 1 OP TRIP BUS 2... FIXED OPERANDS Off On INPUTS/OUTPUTS: Contact inputs Cont Ip 1 Cont Ip 2 Cont Ip 1 Cont Ip 2 Cont Op 1 Cont Op 2 On On Off Off IOn IOn OPERAND DESCRIPTION Flag is set, Logic =1 Flag is set, Logic =1 Flag is set, Logic =1 Flag is set, Logic =1 Asserted when the trip bus 1 element picks up. Asserted when the trip bus 1 element operates. Same set of operands as shown for TRIP BUS 1

5.5 FLEXLOGIC

ELEMENT Trip bus

Logic = 0. Does nothing and may be used as a delimiter in an equation list; used as Disable by other features. Logic = 1. Can be used as a test setting. (will not appear unless ordered) (will not appear unless ordered) (will not appear unless ordered) (will not appear unless ordered) (will not appear unless ordered) (will not appear unless ordered)

INPUTS/OUTPUTS: Contact outputs, current (from detector on form-A output only) INPUTS/OUTPUTS: Contact outputs, voltage (from detector on form-A output only) INPUTS/OUTPUTS Direct inputs INPUTS/OUTPUTS: Remote doublepoint status inputs

Cont Op 1 Cont Op 2 Cont Op 1 Cont Op 2

VOn VOn VOff VOff

(will not appear unless ordered) (will not appear unless ordered) (will not appear unless ordered) (will not appear unless ordered) Flag is set, logic=1 Flag is set, logic=1 Asserted while the remote double-point status input is in the bad state. Asserted while the remote double-point status input is in the intermediate state. Asserted while the remote double-point status input is off. Asserted while the remote double-point status input is on. Same set of operands as per REMDPS 1 above Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Asserted when the front panel IN SERVICE LED is on. Asserted when the front panel TROUBLE LED is on. Asserted when the front panel TEST MODE LED is on. Asserted when the front panel TRIP LED is on. Asserted when the front panel ALARM LED is on. Asserted when the front panel PICKUP LED is on. Asserted when the front panel VOLTAGE LED is on. Asserted when the front panel CURRENT LED is on. Asserted when the front panel FREQUENCY LED is on. Asserted when the front panel OTHER LED is on. Asserted when the front panel PHASE A LED is on. Asserted when the front panel PHASE B LED is on. Asserted when the front panel PHASE C LED is on. Asserted when the front panel NEUTRAL/GROUND LED is on. An LED test has been initiated and has not finished. Asserted when user-programmable LED 1 is on. The operand above is available for user-programmable LEDs 2 through 48.

DIRECT INPUT 1 On DIRECT INPUT 32 On RemDPS Ip 1 BAD RemDPS Ip 1 INTERM RemDPS Ip 1 OFF RemDPS Ip 1 ON REMDPS Ip 2...

INPUTS/OUTPUTS: Remote inputs INPUTS/OUTPUTS: Virtual inputs INPUTS/OUTPUTS: Virtual outputs LED INDICATORS: Fixed front panel LEDs

REMOTE INPUT 1 On REMOTE INPUT 32 On Virt Ip 1 On Virt Ip 64 On Virt Op 1 On Virt Op 96 On LED IN SERVICE LED TROUBLE LED TEST MODE LED TRIP LED ALARM LED PICKUP LED VOLTAGE LED CURRENT LED FREQUENCY LED OTHER LED PHASE A LED PHASE B LED PHASE C LED NEUTRAL/GROUND LED TEST IN PROGRESS LED USER 1 LED USER 2 to 48

LED INDICATORS: LED test LED INDICATORS: User-programmable LEDs

GE Multilin

C30 Controller System

5-73

5.5 FLEXLOGIC Table 57: C30 FLEXLOGIC OPERANDS (Sheet 4 of 4)


OPERAND TYPE PASSWORD SECURITY OPERAND SYNTAX ACCESS LOC SETG OFF ACCESS LOC SETG ON ACCESS LOC CMND OFF ACCESS LOC CMND ON ACCESS REM SETG OFF ACCESS REM SETG ON ACCESS REM CMND OFF ACCESS REM CMND ON UNAUTHORIZED ACCESS REMOTE DEVICE 1 On REMOTE DEVICE 16 On REMOTE DEVICE 1 Off REMOTE DEVICE 16 Off RESETTING RESET OP RESET OP (COMMS) RESET OP (OPERAND) RESET OP (PUSHBUTTON) SELFDIAGNOSTICS ANY MAJOR ERROR ANY MINOR ERROR ANY SELF-TESTS BATTERY FAIL DIRECT DEVICE OFF DIRECT RING BREAK EQUIPMENT MISMATCH ETHERNET SWITCH FAIL FLEXLOGIC ERR TOKEN IRIG-B FAILURE LATCHING OUT ERROR MAINTENANCE ALERT PORT 1 OFFLINE PORT 2 OFFLINE PORT 3 OFFLINE PORT 4 OFFLINE PORT 5 OFFLINE PORT 6 OFFLINE PRI ETHERNET FAIL PROCESS BUS FAILURE REMOTE DEVICE OFF RRTD COMM FAIL SEC ETHERNET FAIL SNTP FAILURE SYSTEM EXCEPTION TEMP MONITOR UNIT NOT PROGRAMMED TEMP MONITOR PUSHBUTTON 1 ON PUSHBUTTON 1 OFF ANY PB ON PUSHBUTTON 2 to 12 OPERAND DESCRIPTION

5 SETTINGS

Asserted when local setting access is disabled. Asserted when local setting access is enabled. Asserted when local command access is disabled. Asserted when local command access is enabled. Asserted when remote setting access is disabled. Asserted when remote setting access is enabled. Asserted when remote command access is disabled. Asserted when remote command access is enabled. Asserted when a password entry fails while accessing a password protected level of the C30. Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Flag is set, logic=1 Reset command is operated (set by all three operands below). Communications source of the reset command. RESETTING menu) source Operand (assigned in the INPUTS/OUTPUTS of the reset command. Reset key (pushbutton) source of the reset command. Any of the major self-test errors generated (major error) Any of the minor self-test errors generated (minor error) Any self-test errors generated (generic, any error) See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets See description in Chapter 7: Commands and targets Asserted while the ambient temperature is greater than the maximum operating temperature (80C) Pushbutton number 1 is in the On position Pushbutton number 1 is in the Off position Any of twelve pushbuttons is in the On position Same set of operands as PUSHBUTTON 1

REMOTE DEVICES

TEMPERATURE MONITOR USERPROGRAMMABLE PUSHBUTTONS

Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID (identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in the FlexLogic operands table above. The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic are listed in the FlexLogic operators table.

5-74

C30 Controller System

GE Multilin

5 SETTINGS

5.5 FLEXLOGIC

Table 58: FLEXLOGIC GATE CHARACTERISTICS


GATES NOT OR AND NOR NAND XOR NUMBER OF INPUTS 1 2 to 16 2 to 16 2 to 16 2 to 16 2 OUTPUT IS 1 (= ON) IF... input is 0 any input is 1 all inputs are 1 all inputs are 0 any input is 0 only one input is 1

Table 59: FLEXLOGIC OPERATORS


TYPE Editor End One-shot SYNTAX INSERT DELETE END DESCRIPTION Insert a parameter in an equation list. Delete a parameter from an equation list. The first END encountered signifies the last entry in the list of processed FlexLogic parameters. One shot that responds to a negative going edge. One shot that responds to both the positive and negative going edges. Logical NOT 2 input OR gate 16 input OR gate 2 input AND gate 16 input AND gate 2 input NOR gate 16 input NOR gate 2 input NAND gate 16 input NAND gate 2 input Exclusive OR gate Latch (set, reset): reset-dominant A one shot refers to a single input gate that generates a pulse in response to an edge on the input. The output from a one shot is True (positive) for only one pass through the FlexLogic equation. There is a maximum of 64 one shots. Operates on the previous parameter. Operates on the 2 previous parameters. Operates on the 16 previous parameters. Operates on the 2 previous parameters. Operates on the 16 previous parameters. Operates on the 2 previous parameters. Operates on the 16 previous parameters. Operates on the 2 previous parameters. Operates on the 16 previous parameters. Operates on the 2 previous parameters. The parameter preceding LATCH(S,R) is the reset input. The parameter preceding the reset input is the set input. The timer is started by the preceding parameter. The output of the timer is TIMER #. The virtual output is set by the preceding parameter NOTES

POSITIVE ONE SHOT One shot that responds to a positive going edge. NEGATIVE ONE SHOT DUAL ONE SHOT

Logic gate

NOT OR(2) OR(16) AND(2) AND(16) NOR(2) NOR(16) NAND(2) NAND(16) XOR(2) LATCH (S,R)

Timer

TIMER 1 TIMER 32 = Virt Op 1 = Virt Op 96

Timer set with FlexLogic timer 1 settings. Timer set with FlexLogic timer 32 settings. Assigns previous FlexLogic operand to virtual output 1. Assigns previous FlexLogic operand to virtual output 96.

Assign virtual output

5.5.2 FLEXLOGIC RULES When forming a FlexLogic equation, the sequence in the linear array of parameters must follow these general rules: 1. 2. 3. 4. Operands must precede the operator which uses the operands as inputs. Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as an input to two or more operators. Assigning the output of an operator to a virtual output terminates the equation. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used once. If this rule is broken, a syntax error will be declared.

GE Multilin

C30 Controller System

5-75

5.5 FLEXLOGIC

5 SETTINGS 5.5.3 FLEXLOGIC EVALUATION

Each equation is evaluated in the order in which the parameters have been entered. FlexLogic provides latches which by definition have a memory action, remaining in the set state after the set input has been asserted. However, they are volatile; that is, they reset on the re-application of control power. When making changes to settings, all FlexLogic equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic during testing, for example, it is suggested to power the unit down and then back up. 5.5.4 FLEXLOGIC EXAMPLE This section provides an example of implementing logic for a typical application. The sequence of the steps is quite important as it should minimize the work necessary to develop the relay settings. Note that the example presented in the figure below is intended to demonstrate the procedure, not to solve a specific application situation. In the example below, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only a part of the full set of equations used. When using FlexLogic, it is important to make a note of each virtual output used a virtual output designation (1 to 96) can only be properly assigned once.
VIRTUAL OUTPUT 1 State=ON VIRTUAL OUTPUT 2 State=ON Set LATCH OR #1 XOR DIGITAL ELEMENT 1 State=Pickup DIGITAL ELEMENT 2 State=Operated AND Timer 1 Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed
827025A2.vsd

NOTE

VIRTUAL INPUT 1 State=ON

Reset Timer 2 OR #2 Time Delay on Dropout (200 ms) Operate Output Relay H1

Figure 521: EXAMPLE LOGIC SCHEME 1. Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic operators. If this is not possible, the logic must be altered until this condition is satisfied. Once this is done, count the inputs to each gate to verify that the number of inputs does not exceed the FlexLogic limits, which is unlikely but possible. If the number of inputs is too high, subdivide the inputs into multiple gates to produce an equivalent. For example, if 25 inputs to an AND gate are required, connect Inputs 1 through 16 to AND(16), 17 through 25 to AND(9), and the outputs from these two gates to AND(2). Inspect each operator between the initial operands and final virtual outputs to determine if the output from the operator is used as an input to more than one following operator. If so, the operator output must be assigned as a virtual output. For the example shown above, the output of the AND gate is used as an input to both OR#1 and Timer 1, and must therefore be made a virtual output and assigned the next available number (i.e. Virtual Output 3). The final output must also be assigned to a virtual output as virtual output 4, which will be programmed in the contact output section to operate relay H1 (that is, contact output H1).

5-76

C30 Controller System

GE Multilin

5 SETTINGS

5.5 FLEXLOGIC

Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and virtual output 4 as shown below.
VIRTUAL OUTPUT 1 State=ON VIRTUAL OUTPUT 2 State=ON VIRTUAL INPUT 1 State=ON XOR DIGITAL ELEMENT 1 State=Pickup DIGITAL ELEMENT 2 State=Operated AND Timer 1 Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3
827026A2.VSD

Set LATCH OR #1 Reset Timer 2 OR #2 Time Delay on Dropout (200 ms) VIRTUAL OUTPUT 4

Figure 522: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS 2. Prepare a logic diagram for the equation to produce virtual output 3, as this output will be used as an operand in the virtual output 4 equation (create the equation for every output that will be used as an operand first, so that when these operands are required they will already have been evaluated and assigned to a specific virtual output). The logic for virtual output 3 is shown below with the final output assigned.
DIGITAL ELEMENT 2 State=Operated AND(2) CONTACT INPUT H1c State=Closed
827027A2.VSD

VIRTUAL OUTPUT 3

Figure 523: LOGIC FOR VIRTUAL OUTPUT 3 3. Prepare a logic diagram for virtual output 4, replacing the logic ahead of virtual output 3 with a symbol identified as virtual output 3, as shown below.
VIRTUAL OUTPUT 1 State=ON VIRTUAL OUTPUT 2 State=ON VIRTUAL INPUT 1 State=ON XOR DIGITAL ELEMENT 1 State=Pickup Timer 1 VIRTUAL OUTPUT 3 State=ON CONTACT INPUT H1c State=Closed Time Delay on Pickup (800 ms)
827028A2.VSD

Set LATCH OR #1 Reset Timer 2 OR #2 Time Delay on Dropout (200 ms)

VIRTUAL OUTPUT 4

Figure 524: LOGIC FOR VIRTUAL OUTPUT 4 4. Program the FlexLogic equation for virtual output 3 by translating the logic into available FlexLogic parameters. The equation is formed one parameter at a time until the required logic is complete. It is generally easier to start at the output end of the equation and work back towards the input, as shown in the following steps. It is also recommended to list operator inputs from bottom to top. For demonstration, the final output will be arbitrarily identified as parameter 99, and each preceding parameter decremented by one in turn. Until accustomed to using FlexLogic, it is suggested that a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared, as shown below.

GE Multilin

C30 Controller System

5-77

5.5 FLEXLOGIC

5 SETTINGS

01 02 03 04 05
.....

97 98 99
827029A1.VSD

Figure 525: FLEXLOGIC WORKSHEET 5. Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." 98: The gate preceding the output is an AND, which in this case requires two inputs. The operator for this gate is a 2input AND so the parameter is AND(2). Note that FlexLogic rules require that the number of inputs to most types of operators must be specified to identify the operands for the gate. As the 2-input AND will operate on the two operands preceding it, these inputs must be specified, starting with the lower.

97: This lower input to the AND gate must be passed through an inverter (the NOT operator) so the next parameter is NOT. The NOT operator acts upon the operand immediately preceding it, so specify the inverter input next. 96: The input to the NOT gate is to be contact input H1c. The ON state of a contact input can be programmed to be set when the contact is either open or closed. Assume for this example the state is to be ON for a closed contact. The operand is therefore Cont Ip H1c On. 95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital element 2. This operand is "DIG ELEM 2 OP". Writing the parameters in numerical order can now form the equation for virtual output 3: [95] [96] [97] [98] [99] DIG ELEM 2 OP Cont Ip H1c On NOT AND(2) = Virt Op 3

It is now possible to check that this selection of parameters will produce the required logic by converting the set of parameters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 3 diagram as a check.

95 96 97 98 99

FLEXLOGIC ENTRY n: DIG ELEM 2 OP FLEXLOGIC ENTRY n: Cont Ip H1c On FLEXLOGIC ENTRY n: NOT FLEXLOGIC ENTRY n: AND (2) FLEXLOGIC ENTRY n: =Virt Op 3

AND

VIRTUAL OUTPUT 3

827030A2.VSD

Figure 526: FLEXLOGIC EQUATION FOR VIRTUAL OUTPUT 3 6. Repeating the process described for virtual output 3, select the FlexLogic parameters for Virtual Output 4. 99: The final output of the equation is virtual output 4 which is parameter = Virt Op 4". 98: The operator preceding the output is timer 2, which is operand TIMER 2". Note that the settings required for the timer are established in the timer programming section.

5-78

C30 Controller System

GE Multilin

5 SETTINGS 97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter OR(3). 96: The lowest input to OR #2 is operand Cont Ip H1c On. 95: The center input to OR #2 is operand TIMER 1". 94: The input to timer 1 is operand Virt Op 3 On". 93: The upper input to OR #2 is operand LATCH (S,R).

5.5 FLEXLOGIC

92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR, which is parameter OR(4). 91: The lowest input to OR #1 is operand Virt Op 3 On". 90: The input just above the lowest input to OR #1 is operand XOR(2). 89: The lower input to the XOR is operand DIG ELEM 1 PKP. 88: The upper input to the XOR is operand Virt Ip 1 On". 87: The input just below the upper input to OR #1 is operand Virt Op 2 On". 86: The upper input to OR #1 is operand Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand Virt Op 4 On". The equation for virtual output 4 is: [85] [86] [87] [88] [89] [90] [91] [92] [93] [94] [95] [96] [97] [98] [99] Virt Op 4 On Virt Op 1 On Virt Op 2 On Virt Ip 1 On DIG ELEM 1 PKP XOR(2) Virt Op 3 On OR(4) LATCH (S,R) Virt Op 3 On TIMER 1 Cont Ip H1c On OR(3) TIMER 2 = Virt Op 4

It is now possible to check that the selection of parameters will produce the required logic by converting the set of parameters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 4 diagram as a check.

GE Multilin

C30 Controller System

5-79

5.5 FLEXLOGIC

5 SETTINGS

85 86 87 88 89 90 91 92 93 94 95 96 97 98 99

FLEXLOGIC ENTRY n: Virt Op 4 On FLEXLOGIC ENTRY n: Virt Op 1 On FLEXLOGIC ENTRY n: Virt Op 2 On FLEXLOGIC ENTRY n: Virt Ip 1 On FLEXLOGIC ENTRY n: DIG ELEM 1 PKP FLEXLOGIC ENTRY n: XOR FLEXLOGIC ENTRY n: Virt Op 3 On FLEXLOGIC ENTRY n: OR (4) FLEXLOGIC ENTRY n: LATCH (S,R) FLEXLOGIC ENTRY n: Virt Op 3 On FLEXLOGIC ENTRY n: TIMER 1 FLEXLOGIC ENTRY n: Cont Ip H1c On FLEXLOGIC ENTRY n: OR (3) FLEXLOGIC ENTRY n: TIMER 2 FLEXLOGIC ENTRY n: =Virt Op 4

Set LATCH XOR OR Reset

OR

T2

VIRTUAL OUTPUT 4

T1

827031A2.VSD

5
7.

Figure 527: FLEXLOGIC EQUATION FOR VIRTUAL OUTPUT 4 Now write the complete FlexLogic expression required to implement the logic, making an effort to assemble the equation in an order where Virtual Outputs that will be used as inputs to operators are created before needed. In cases where a lot of processing is required to perform logic, this may be difficult to achieve, but in most cases will not cause problems as all logic is calculated at least four times per power frequency cycle. The possibility of a problem caused by sequential processing emphasizes the necessity to test the performance of FlexLogic before it is placed in service. In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On NOT AND(2) = Virt Op 3 Virt Op 4 On Virt Op 1 On Virt Op 2 On Virt Ip 1 On DIG ELEM 1 PKP XOR(2) Virt Op 3 On OR(4) LATCH (S,R) Virt Op 3 On TIMER 1 Cont Ip H1c On OR(3) TIMER 2 = Virt Op 4 END In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of feedback, in this case, used to create a seal-in effect with the latch, and is correct.

5-80

C30 Controller System

GE Multilin

5 SETTINGS 8.

5.5 FLEXLOGIC

The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past. Testing can be simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations will then only be evaluated up to the first "END" operator. The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and the "INSERT" and "DELETE" commands can be used to modify equations. 5.5.5 FLEXLOGIC EQUATION EDITOR

PATH: SETTINGS

FLEXLOGIC

FLEXLOGIC EQUATION EDITOR

FLEXLOGIC EQUATION EDITOR


MESSAGE

FLEXLOGIC ENTRY END FLEXLOGIC ENTRY END

1: 2:

Range: FlexLogic operands

Range: FlexLogic operands

MESSAGE

FLEXLOGIC ENTRY 512: END

Range: FlexLogic operands

There are 512 FlexLogic entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Element is selected as a FlexLogic entry, the associated state flag will never be set to 1. The +/ key may be used when editing FlexLogic equations from the keypad to quickly scan through the major parameter types. 5.5.6 FLEXLOGIC TIMERS
PATH: SETTINGS FLEXLOGIC FLEXLOGIC TIMERS FLEXLOGIC TIMER 1(32) Range: millisecond, second, minute

FLEXLOGIC TIMER 1
MESSAGE

TIMER 1 TYPE: millisecond TIMER 1 PICKUP DELAY: 0 TIMER 1 DROPOUT DELAY: 0

Range: 0 to 60000 in steps of 1

Range: 0 to 60000 in steps of 1

MESSAGE

There are 32 identical FlexLogic timers available. These timers can be used as operators for FlexLogic equations. TIMER 1 TYPE: This setting is used to select the time measuring unit. TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".

GE Multilin

C30 Controller System

5-81

5.5 FLEXLOGIC

5 SETTINGS 5.5.7 FLEXELEMENTS

PATH: SETTING

FLEXLOGIC

FLEXELEMENTS

FLEXELEMENT 1(8) Range: Disabled, Enabled

FLEXELEMENT 1

FLEXELEMENT 1 FUNCTION: Disabled


MESSAGE

FLEXELEMENT 1 NAME: FxE1 FLEXELEMENT 1 +IN: Off FLEXELEMENT 1 -IN: Off FLEXELEMENT 1 INPUT MODE: Signed FLEXELEMENT 1 COMP MODE: Level FLEXELEMENT 1 DIRECTION: Over FLEXELEMENT 1 PICKUP: 1.000 pu FLEXELEMENT 1 HYSTERESIS: 3.0% FLEXELEMENT 1 dt UNIT: milliseconds FLEXELEMENT 1 dt: 20 FLEXELEMENT 1 PKP DELAY: 0.000 s FLEXELEMENT 1 RST DELAY: 0.000 s FLEXELEMENT 1 BLK: Off FLEXELEMENT 1 TARGET: Self-reset FLEXELEMENT 1 EVENTS: Disabled

Range: up to 6 alphanumeric characters

Range: Off, any analog actual value parameter

MESSAGE

Range: Off, any analog actual value parameter

MESSAGE

Range: Signed, Absolute

MESSAGE

Range: Level, Delta

MESSAGE

Range: Over, Under

MESSAGE

Range: 90.000 to 90.000 pu in steps of 0.001

MESSAGE

Range: 0.1 to 50.0% in steps of 0.1

MESSAGE

Range: milliseconds, seconds, minutes

MESSAGE

Range: 20 to 86400 in steps of 1

MESSAGE

Range: 0.000 to 65.535 s in steps of 0.001

MESSAGE

Range: 0.000 to 65.535 s in steps of 0.001

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Self-reset, Latched, Disabled

MESSAGE

Range: Disabled, Enabled

MESSAGE

A FlexElement is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed number or its absolute value could be used as per user's choice. The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice.

5-82

C30 Controller System

GE Multilin

5 SETTINGS

5.5 FLEXLOGIC

SETTING FLEXELEMENT 1 FUNCTION: Enabled = 1 Disabled = 0 SETTING FLEXELEMENT 1 BLK: AND Off = 0 SETTINGS FLEXELEMENT 1 +IN: RUN Actual Value FLEXELEMENT 1 -IN: Actual Value

SETTINGS FLEXELEMENT 1 INPUT MODE: FLEXELEMENT 1 COMP MODE: FLEXELEMENT 1 DIRECTION: FLEXELEMENT 1 PICKUP: FLEXELEMENT 1 INPUT HYSTERESIS: FLEXELEMENT 1 dt UNIT: FLEXELEMENT 1 dt: SETTINGS FLEXELEMENT 1 PKP DELAY: FLEXELEMENT 1 RST DELAY: FLEXLOGIC OPERANDS FxE 1 OP

+ -

tPKP tRST

FxE 1 DPO FxE 1 PKP

ACTUAL VALUE FlexElement 1 OpSig


842004A3.CDR

Figure 528: FLEXELEMENT SCHEME LOGIC The FLEXELEMENT 1 +IN setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if this setting is set to Off. For proper operation of the element at least one input must be selected. Otherwise, the element will not assert its output operands. This FLEXELEMENT 1 IN setting specifies the second (inverted) input to the FlexElement. Zero is assumed as the input if this setting is set to Off. For proper operation of the element at least one input must be selected. Otherwise, the element will not assert its output operands. This input should be used to invert the signal if needed for convenience, or to make the element respond to a differential signal such as for a top-bottom oil temperature differential alarm. The element will not operate if the two input signals are of different types, for example if one tries to use active power and phase angle to build the effective operating signal. The element responds directly to the differential signal if the FLEXELEMENT 1 INPUT MODE setting is set to Signed. The element responds to the absolute value of the differential signal if this setting is set to Absolute. Sample applications for the Absolute setting include monitoring the angular difference between two phasors with a symmetrical limit angle in both directions; monitoring power regardless of its direction, or monitoring a trend regardless of whether the signal increases of decreases. The element responds directly to its operating signal as defined by the FLEXELEMENT 1 +IN, FLEXELEMENT 1 IN and FLEXELEMENT 1 INPUT MODE settings if the FLEXELEMENT 1 COMP MODE setting is set to Level. The element responds to the rate of change of its operating signal if the FLEXELEMENT 1 COMP MODE setting is set to Delta. In this case the FLEXELEMENT 1 dt UNIT and FLEXELEMENT 1 dt settings specify how the rate of change is derived. The FLEXELEMENT 1 DIRECTION setting enables the relay to respond to either high or low values of the operating signal. The following figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP and FLEXELEMENT 1 HYSTERESIS settings.

GE Multilin

C30 Controller System

5-83

5.5 FLEXLOGIC

5 SETTINGS

FLEXELEMENT 1 PKP

FLEXELEMENT DIRECTION = Over

HYSTERESIS = % of PICKUP
PICKUP

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT DIRECTION = Under

HYSTERESIS = % of PICKUP
PICKUP

FlexElement 1 OpSig
842705A1.CDR

Figure 529: FLEXELEMENT DIRECTION, PICKUP, AND HYSTERESIS In conjunction with the FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra characteristics as shown in the figure below.
FLEXELEMENT 1 PKP

FLEXELEMENT DIRECTION = Over; FLEXELEMENT INPUT MODE = Signed;

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT DIRECTION = Over; FLEXELEMENT INPUT MODE = Absolute;

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed;

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute;

FlexElement 1 OpSig
842706A2.CDR

Figure 530: FLEXELEMENT INPUT MODE SETTING

5-84

C30 Controller System

GE Multilin

5 SETTINGS

5.5 FLEXLOGIC

The FLEXELEMENT 1 PICKUP setting specifies the operating threshold for the effective operating signal of the element. If set to Over, the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to Under, the element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value. The FLEXELEMENT 1 HYSTERESIS setting controls the element dropout. It should be noticed that both the operating signal and the pickup threshold can be negative facilitating applications such as reverse power alarm protection. The FlexElement can be programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP setting is entered in per-unit values using the following definitions of the base units: Table 510: FLEXELEMENT BASE UNITS
dcmA FREQUENCY PHASE ANGLE POWER FACTOR RTDs SOURCE CURRENT SOURCE POWER SOURCE VOLTAGE BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured under the +IN and IN inputs. fBASE = 1 Hz BASE = 360 degrees (see the UR angle referencing convention) PFBASE = 1.00 BASE = 100C IBASE = maximum nominal primary RMS value of the +IN and IN inputs PBASE = maximum value of VBASE IBASE for the +IN and IN inputs VBASE = maximum nominal primary RMS value of the +IN and IN inputs

The FLEXELEMENT 1 HYSTERESIS setting defines the pickupdropout relation of the element by specifying the width of the hysteresis loop as a percentage of the pickup value as shown in the FlexElement direction, pickup, and hysteresis diagram. The FLEXELEMENT 1 DT UNIT setting specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to Delta. The FLEXELEMENT 1 DT setting specifies duration of the time interval for the rate of change mode of operation. This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to Delta. This FLEXELEMENT 1 PKP DELAY setting specifies the pickup delay of the element. The FLEXELEMENT 1 RST DELAY setting specifies the reset delay of the element.

GE Multilin

C30 Controller System

5-85

5.5 FLEXLOGIC

5 SETTINGS 5.5.8 NON-VOLATILE LATCHES

PATH: SETTINGS

FLEXLOGIC

NON-VOLATILE LATCHES

LATCH 1(16) Range: Disabled, Enabled

LATCH 1

LATCH 1 FUNCTION: Disabled


MESSAGE

LATCH 1 TYPE: Reset Dominant LATCH 1 SET: Off LATCH 1 RESET: Off LATCH 1 TARGET: Self-reset LATCH 1 EVENTS: Disabled

Range: Reset Dominant, Set Dominant

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Self-reset, Latched, Disabled

MESSAGE

Range: Disabled, Enabled

MESSAGE

The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below: LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant. LATCH 1 SET: If asserted, the specified FlexLogic operands 'sets' Latch 1. LATCH 1 RESET: If asserted, the specified FlexLogic operand 'resets' Latch 1.
SETTING

LATCH N TYPE Reset Dominant

LATCH N SET ON OFF ON OFF

LATCH N RESET OFF OFF ON ON OFF ON OFF ON

LATCH N ON ON Previous State OFF OFF ON ON Previous State OFF

LATCH N OFF OFF Previous State ON ON OFF OFF Previous State ON

LATCH 1 FUNCTION: Disabled=0 Enabled=1 SETTING LATCH 1 SET: Off=0 SETTING LATCH 1 SET: Off=0

SETTING LATCH 1 TYPE: RUN

Set Dominant

ON ON OFF OFF

FLEXLOGIC OPERANDS SET LATCH 1 ON LATCH 1 OFF

RESET

842005A1.CDR

Figure 531: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC

5-86

C30 Controller System

GE Multilin

5 SETTINGS 5.6CONTROL ELEMENTS

5.6 CONTROL ELEMENTS 5.6.1 OVERVIEW

Control elements are generally used for control rather than protection. See the Introduction to Elements section at the beginning of this chapter for further information. 5.6.2 SELECTOR SWITCH
PATH: SETTINGS CONTROL ELEMENTS SELECTOR SWITCH SELECTOR SWITCH 1(2) Range: Disabled, Enabled

SELECTOR SWITCH 1

SELECTOR 1 FUNCTION: Disabled SELECTOR 1 FULL RANGE: 7 SELECTOR 1 TIME-OUT: 5.0 s SELECTOR 1 STEP-UP: Off SELECTOR 1 STEP-UP MODE: Time-out SELECTOR 1 ACK: Off SELECTOR 1 3BIT A0: Off SELECTOR 1 3BIT A1: Off SELECTOR 1 3BIT A2: Off SELECTOR 1 3BIT MODE: Time-out SELECTOR 1 3BIT ACK: Off SELECTOR 1 POWER-UP MODE: Restore SELECTOR 1 TARGETS: Self-reset SELECTOR 1 EVENTS: Disabled

Range: 1 to 7 in steps of 1

MESSAGE

Range: 3.0 to 60.0 s in steps of 0.1

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Time-out, Acknowledge

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Time-out, Acknowledge

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Restore, Synchronize, Sync/Restore

MESSAGE

Range: Self-reset, Latched, Disabled

MESSAGE

Range: Disabled, Enabled

MESSAGE

The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group control or control of multiple logic sub-circuits in user-programmable logic. The element provides for two control inputs. The step-up control allows stepping through selector position one step at a time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows setting the selector to the position defined by a three-bit word. The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after timeout or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory. Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user setting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out of range.

GE Multilin

C30 Controller System

5-87

5.6 CONTROL ELEMENTS

5 SETTINGS

SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through available positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct threebit control word for programming the selector to a desired position, the change would take place only if the control word is within the range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established by setting the SELECTOR ALARM FlexLogic operand for 3 seconds. SELECTOR 1 TIME-OUT: This setting defines the time-out period for the selector. This value is used by the relay in the following two ways. When the SELECTOR STEP-UP MODE is Time-out, the setting specifies the required period of inactivity of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEPUP MODE is Acknowledge, the setting specifies the period of time for the acknowledging input to appear. The timer is re-started by any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT timer expires; otherwise, the change will not take place and an alarm will be set. SELECTOR 1 STEP-UP: This setting specifies a control input for the selector switch. The switch is shifted to a new position at each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1 FULL RANGE) to the first (position 1). Consecutive pulses of this control operand must not occur faster than every 50 ms. After each rising edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1: POS Z CHNG INITIATED target message is displayed, where Z the pre-selected position. The message is displayed for the time specified by the FLASH MESSAGE TIME setting. The pre-selected position is applied after the selector times out (Time-out mode), or when the acknowledging signal appears before the element times out (Acknowledge mode). When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically, a user-programmable pushbutton is configured as the stepping up control input. SELECTOR 1 STEP-UP MODE: This setting defines the selector mode of operation. When set to Time-out, the selector will change its position after a pre-defined period of inactivity at the control input. The change is automatic and does not require any explicit confirmation of the intent to change the selector's position. When set to Acknowledge, the selector will change its position only after the intent is confirmed through a separate acknowledging signal. If the acknowledging signal does not appear within a pre-defined period of time, the selector does not accept the change and an alarm is established by setting the SELECTOR STP ALARM output FlexLogic operand for 3 seconds. SELECTOR 1 ACK: This setting specifies an acknowledging input for the stepping up control input. The pre-selected position is applied on the rising edge of the assigned operand. This setting is active only under Acknowledge mode of operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the last activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input. SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit control word pre-selects the position using the following encoding convention:
A2 0 0 0 0 1 1 1 1 A1 0 0 1 1 0 0 1 1 A0 0 1 0 1 0 1 0 1 POSITION rest 1 2 3 4 5 6 7

The rest position (0, 0, 0) does not generate an action and is intended for situations when the device generating the three-bit control word is having a problem. When SELECTOR 1 3BIT MODE is Time-out, the pre-selected position is applied in SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is Acknowledge, the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging input. The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2) lock-out mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit control sequence is initiated, the stepping up input is inactive. SELECTOR 1 3BIT MODE: This setting defines the selector mode of operation. When set to Time-out, the selector changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not require explicit confirmation to change the selector position. When set to Acknowledge, the selector changes its posi-

5-88

C30 Controller System

GE Multilin

5 SETTINGS

5.6 CONTROL ELEMENTS

tion only after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a pre-defined period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT ALARM FlexLogic operand for 3 seconds. SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The preselected position is applied on the rising edge of the assigned FlexLogic operand. This setting is active only under the Acknowledge mode of operation. The acknowledging signal must appear within the time defined by the SELECTOR TIME-OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and three-bit control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accordingly). SELECTOR 1 POWER-UP MODE: This setting specifies the element behavior on power up of the relay. When set to Restore, the last position of the selector (stored in the non-volatile memory) is restored after powering up the relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and an alarm is set (SELECTOR 1 PWR ALARM). When set to Synchronize selector switch acts as follows. For two power cycles, the selector applies position 0 to the switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range) then the selector switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR ALARM). The operation of Synch/Restore mode is similar to the Synchronize mode. The only difference is that after an unsuccessful synchronization attempt, the switch will attempt to restore the position stored in the relay memory. The Synch/Restore mode is useful for applications where the selector switch is employed to change the setting group in redundant (two relay) protection schemes. SELECTOR 1 EVENTS: If enabled, the following events are logged:
EVENT NAME SELECTOR 1 POS Z SELECTOR 1 STP ALARM SELECTOR 1 BIT ALARM DESCRIPTION Selector 1 changed its position to Z. The selector position pre-selected via the stepping up control input has not been confirmed before the time out. The selector position pre-selected via the three-bit control input has not been confirmed before the time out.

GE Multilin

C30 Controller System

5-89

5.6 CONTROL ELEMENTS

5 SETTINGS

The following figures illustrate the operation of the selector switch. In these diagrams, T represents a time-out setting.
pre-existing position 2 changed to 4 with a pushbutton changed to 1 with a 3-bit input changed to 2 with a pushbutton changed to 7 with a 3-bit input

STEP-UP T T

3BIT A0 3BIT A1 3BIT A2 T T

POS 1 POS 2 POS 3 POS 4 POS 5

POS 6 POS 7 BIT 0 BIT 1 BIT 2

STP ALARM BIT ALARM ALARM


842737A1.CDR

Figure 532: TIME-OUT MODE

5-90

C30 Controller System

GE Multilin

5 SETTINGS

5.6 CONTROL ELEMENTS

pre-existing position 2

changed to 4 with a pushbutton

changed to 1 with a 3-bit input

changed to 2 with a pushbutton

STEP-UP ACK 3BIT A0 3BIT A1 3BIT A2 3BIT ACK POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM
842736A1.CDR

Figure 533: ACKNOWLEDGE MODE APPLICATION EXAMPLE Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1 through 3. The active setting group shall be available as an encoded three-bit word to the external device and SCADA via output contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of the control inputs. When the relay powers up, it should synchronize the setting group to the three-bit control input. Make the following changes to setting group control in the SETTINGS
SETTING GROUPS FUNCTION: Enabled SETTING GROUPS BLK: Off GROUP 2 ACTIVATE ON: SELECTOR 1 POS GROUP 3 ACTIVATE ON: SELECTOR 1 POS CONTROL ELEMENTS SETTING GROUPS

menu:

2" 3"

GROUP 4 ACTIVATE ON: GROUP 5 ACTIVATE ON: GROUP 6 ACTIVATE ON:

SELECTOR 1 POS 4" Off Off

SELECTOR SWITCH 1

Make the following changes to selector switch element in the SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:

GE Multilin

C30 Controller System

5-91

5.6 CONTROL ELEMENTS


SELECTOR 1 FUNCTION: Enabled SELECTOR 1 FULL-RANGE: 4 SELECTOR 1 STEP-UP MODE: Time-out SELECTOR 1 TIME-OUT: 5.0 s SELECTOR 1 STEP-UP: PUSHBUTTON 1 SELECTOR 1 ACK: Off

5 SETTINGS
SELECTOR 1 3BIT A0: CONT IP 1 ON SELECTOR 1 3BIT A1: CONT IP 2 ON SELECTOR 1 3BIT A2: CONT IP 3 ON SELECTOR 1 3BIT MODE: Time-out SELECTOR 1 3BIT ACK: Off SELECTOR 1 POWER-UP MODE: Synchronize

ON

Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following INPUTS/OUTPUTS CONTACT OUTPUTS menu: changes in the SETTINGS
OUTPUT H1 OPERATE: OUTPUT H2 OPERATE: OUTPUT H3 OPERATE:

SELECTOR 1 BIT 0" SELECTOR 1 BIT 1" SELECTOR 1 BIT 2"


PRODUCT

Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: Self-reset PUSHBUTTON 1 DROP-OUT TIME: 0.10 s

The logic for the selector switch is shown below:


SETTINGS SELECTOR 1 FULL RANGE: SELECTOR 1 STEP-UP MODE: SELECTOR 1 3BIT MODE: SETTINGS SELECTOR 1 TIME-OUT: SELECTOR 1 POWER-UP MODE: RUN FLEXLOGIC OPERANDS
step up

ACTUAL VALUE SELECTOR 1 POSITION

SELECTOR 1 FUNCTION: Enabled = 1 SELECTOR 1 STEP-UP: Off = 0 SELECTOR 1 ACK: Off = 0 SELECTOR 1 3BIT A0: Off = 0 SELECTOR 1 3BIT A1: Off = 0 SELECTOR 1 3BIT A2: Off = 0 SELECTOR 1 3BIT ACK: Off = 0

1
acknowledge

2 3 4

SELECTOR 1 POS 1 SELECTOR 1 POS 2 SELECTOR 1 POS 3 SELECTOR 1 POS 4 SELECTOR 1 POS 5 5 SELECTOR 1 POS 6 SELECTOR 1 POS 7 FLEXLOGIC OPERANDS SELECTOR 1 STP ALARM SELECTOR 1 BIT ALARM

three-bit control input

ON

3-bit acknowledge

OR

3-bit position out

SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2
842012A2.CDR

Figure 534: SELECTOR SWITCH LOGIC

5-92

C30 Controller System

GE Multilin

5 SETTINGS

5.6 CONTROL ELEMENTS 5.6.3 DIGITAL ELEMENTS

PATH: SETTINGS

CONTROL ELEMENTS

DIGITAL ELEMENTS

DIGITAL ELEMENT 1(48) Range: Disabled, Enabled

DIGITAL ELEMENT 1

DIGITAL ELEMENT 1 FUNCTION: Disabled DIG ELEM 1 NAME: Dig Element 1 DIG ELEM Off DIG ELEM DELAY: DIG ELEM DELAY: 1 INPUT: 1 PICKUP 0.000 s 1 RESET 0.000 s

Range: 16 alphanumeric characters

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: 0.000 to 999999.999 s in steps of 0.001

MESSAGE

Range: 0.000 to 999999.999 s in steps of 0.001

MESSAGE

MESSAGE

DIG ELEMENT 1 PICKUP LED: Enabled DIG ELEM Off 1 BLOCK:

Range: Disabled, Enabled

Range: FlexLogic operand

MESSAGE

MESSAGE

DIGITAL ELEMENT 1 TARGET: Self-reset DIGITAL ELEMENT 1 EVENTS: Disabled

Range: Self-reset, Latched, Disabled

Range: Disabled, Enabled

MESSAGE

There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic operand and present a target message and/or enable events recording depending on the output operand state. The digital element settings include a name which will be referenced in any target message, a blocking input from any selected FlexLogic operand, and a timer for pickup and reset delays for the output operand. DIGITAL ELEMENT 1 INPUT: Selects a FlexLogic operand to be monitored by the digital element. DIGITAL ELEMENT 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set to "0". DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to 0. DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to Disabled, the operation of the pickup LED is blocked.
SETTING DIGITAL ELEMENT 01 FUNCTION: Disabled = 0 Enabled = 1 SETTING DIGITAL ELEMENT 01 INPUT: Off = 0 SETTING DIGITAL ELEMENT 01 BLOCK: Off = 0

AND

SETTING DIGITAL ELEMENT 01 NAME: RUN INPUT = 1

SETTINGS DIGITAL ELEMENT 01 PICKUP DELAY: DIGITAL ELEMENT 01 RESET DELAY: tPKP tRST

FLEXLOGIC OPERANDS DIG ELEM 01 DPO DIG ELEM 01 PKP DIG ELEM 01 OP

827042A1.VSD

Figure 535: DIGITAL ELEMENT SCHEME LOGIC CIRCUIT MONITORING APPLICATIONS: Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A).

GE Multilin

C30 Controller System

5-93

5.6 CONTROL ELEMENTS

5 SETTINGS

As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the Cont Op 1 VOn FlexLogic operand will be set (for contact input 1 corresponding operands exist for each contact output). If the output circuit has a high resistance or the DC current is interrupted, the trickle current will drop below the threshold and the Cont Op 1 VOff FlexLogic operand will be set. Consequently, the state of these operands can be used as indicators of the integrity of the circuits in which form-A contacts are inserted. EXAMPLE 1: BREAKER TRIP CIRCUIT INTEGRITY MONITORING In many applications it is desired to monitor the breaker trip circuit integrity so problems can be detected before a trip operation is required. The circuit is considered to be healthy when the voltage monitor connected across the trip output contact detects a low level of current, well below the operating current of the breaker trip coil. If the circuit presents a high resistance, the trickle current will fall below the monitor threshold and an alarm would be declared. In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position.
UR-series device with form-A contacts

H1a
I

H1b
V

DC DC+

H1c

52a

Trip coil

I = current monitor V = voltage monitor

827073A2.CDR

Figure 536: TRIP CIRCUIT EXAMPLE 1 Assume the output contact H1 is a trip contact. Using the contact output settings, this output will be given an ID name; for example, Cont Op 1". Assume a 52a breaker auxiliary contact is connected to contact input H7a to monitor breaker status. Using the contact input settings, this input will be given an ID name, for example, Cont Ip 1", and will be set On when the breaker is closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR Setup example shown):

The PICKUP DELAY setting should be greater than the operating time of the breaker to avoid nuisance alarms.
NOTE

5-94

C30 Controller System

GE Multilin

5 SETTINGS EXAMPLE 2: BREAKER TRIP CIRCUIT INTEGRITY MONITORING

5.6 CONTROL ELEMENTS

If it is required to monitor the trip circuit continuously, independent of the breaker position (open or closed), a method to maintain the monitoring current flow through the trip circuit when the breaker is open must be provided (as shown in the figure below). This can be achieved by connecting a suitable resistor (see figure below) across the auxiliary contact in the trip circuit. In this case, it is not required to supervise the monitoring circuit with the breaker position the BLOCK setting is selected to Off. In this case, the settings are as follows (EnerVista UR Setup example shown).

UR-series device with form-A contacts

H1a
I

Values for resistor R

5
Power 2W 2W 2W 5W 5W 5W
827074A3.CDR

Power supply 24 V DC

Resistance 1000 5000 10000 25000 25000 50000

H1b
V

DC DC+

30 V DC 48 V DC 110 V DC 125 V DC 250 V DC

H1c

52a R Bypass resistor

Trip coil

I = current monitor V = voltage monitor

Figure 537: TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and solid-state contact with voltage monitoring.
NOTE

GE Multilin

C30 Controller System

5-95

5.6 CONTROL ELEMENTS

5 SETTINGS 5.6.4 DIGITAL COUNTERS

PATH: SETTINGS

CONTROL ELEMENTS

DIGITAL COUNTERS

COUNTER 1(8) Range: Disabled, Enabled

COUNTER 1

COUNTER 1 FUNCTION: Disabled


MESSAGE

COUNTER 1 NAME: Counter 1 COUNTER 1 UNITS: COUNTER 1 PRESET: 0 COUNTER 1 COMPARE: 0 COUNTER 1 UP: Off COUNTER 1 DOWN: Off COUNTER 1 BLOCK: Off CNT1 SET TO PRESET: Off COUNTER 1 RESET: Off COUNT1 FREEZE/RESET: Off COUNT1 FREEZE/COUNT: Off

Range: 12 alphanumeric characters

Range: 6 alphanumeric characters

MESSAGE

Range: 2,147,483,648 to +2,147,483,647

MESSAGE

Range: 2,147,483,648 to +2,147,483,647

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter. COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted. The units label will appear in the corresponding actual values status. COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case where a substitute relay is to be installed in place of an in-service relay, or while the counter is running. COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic output operands are provided to indicate if the present value is more than (HI), equal to (EQL), or less than (LO) the set value. COUNTER 1 UP: Selects the FlexLogic operand for incrementing the counter. If an enabled UP input is received when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to 2,147,483,648. COUNTER 1 DOWN: Selects the FlexLogic operand for decrementing the counter. If an enabled DOWN input is received when the accumulated value is at the limit of 2,147,483,648 counts, the counter will rollover to +2,147,483,647. COUNTER 1 BLOCK: Selects the FlexLogic operand for blocking the counting operation. All counter operands are blocked.

5-96

C30 Controller System

GE Multilin

5 SETTINGS

5.6 CONTROL ELEMENTS

CNT1 SET TO PRESET: Selects the FlexLogic operand used to set the count to the preset value. The counter will be set to the preset value in the following situations: 1. 2. 3. When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled and CNT1 SET TO PRESET operand is 0, the counter will be set to 0).
PRESET

When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO changing from 1 to 0 while the counter is running has no effect on the count).

When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 1 (when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value 0, the counter will be set to 0).

COUNTER 1 RESET: Selects the FlexLogic operand for setting the count to either 0 or the preset value depending on the state of the CNT1 SET TO PRESET operand. COUNTER 1 FREEZE/RESET: Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a separate register with the date and time of the operation, and resetting the count to 0. COUNTER 1 FREEZE/COUNT: Selects the FlexLogic operand for capturing (freezing) the accumulated count value into a separate register with the date and time of the operation, and continuing counting. The present accumulated value and captured frozen value with the associated date/time stamp are available as actual values. If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation.

SETTING
COUNTER 1 FUNCTION: Disabled = 0 Enabled = 1

SETTING
COUNTER 1 UP: Off = 0

AND

SETTINGS COUNTER 1 NAME: COUNTER 1 UNITS: COUNTER 1 PRESET: RUN

5
SETTING
COUNTER 1 COMPARE: Count more than Comp. Count equal to Comp. Count less than Comp.

SETTING
COUNTER 1 DOWN: Off = 0 CALCULATE VALUE

FLEXLOGIC OPERANDS COUNTER 1 HI COUNTER 1 EQL COUNTER 1 LO

SETTING
COUNTER 1 BLOCK: Off = 0 SET TO PRESET VALUE SET TO ZERO

SETTING
CNT 1 SET TO PRESET: Off = 0

ACTUAL VALUE
COUNTER 1 ACCUM:

AND AND OR
ACTUAL VALUES
COUNTER 1 FROZEN: STORE DATE & TIME Date & Time

SETTING
COUNTER 1 RESET: Off = 0

SETTING
COUNT1 FREEZE/RESET: Off = 0

OR
827065A1.VSD

SETTING
COUNT1 FREEZE/COUNT: Off = 0

Figure 538: DIGITAL COUNTER SCHEME LOGIC

GE Multilin

C30 Controller System

5-97

5.6 CONTROL ELEMENTS

5 SETTINGS 5.6.5 8-BIT SWITCHES

PATH: SETTINGS

CONTROL ELEMENTS

8-BIT SWITCHES

8-BIT SWITCH 1(6) Range: Disabled, Enabled

8-BIT SWITCH 1
MESSAGE

8BIT SWITCH 1 FUNCTION: Disabled 8BIT SW 1 ARG A0: Off 8BIT SW 1 ARG A1: Off

MESSAGE

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

8BIT SW 1 ARG A7: Off 8BIT SW 1 ARG B0: Off 8BIT SW 1 ARG B1: Off

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

MESSAGE

8BIT SW 1 ARG B7: Off 8BIT SW 1 CONTROL: Off

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

This feature allows switching between two input arguments defined by 8 bits each. The bits are specified by FlexLogic operands. The feature could be viewed as an integrated two-position switch for 8 logic signals. Typically this element is applied in conjunction with the Digitizer and 8-bit Comparator features. 8BIT SW 1 ARG A0 to 8BIT SW 1 ARG A7: These settings specify FlexLogic operands that constitute the first (A) input of the switch. These operands are routed to the output operands if the control input is in the "Off" position. BIT SW 1 ARG B0 to 8BIT SW 1 ARG B7: These settings specify FlexLogic operands that constitute the second (B) input of the switch. These operands are routed to the output operands if the control input is in the "On" position. 8BIT SW 1 CONTROL: This setting specifies FlexLogic operands to control the routing between the A and B inputs of the switch. If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control operand is in the "On" state, the second (B) input is switched to the output. The switching takes place instantaneously.

5-98

C30 Controller System

GE Multilin

5 SETTINGS

5.6 CONTROL ELEMENTS

SETTING 8BIT SWITCH 1 FUNCTION: Enabled = 1 SETTINGS 8BIT SW 1 ARG A0: Off = 0 8BIT SW 1 ARG B0: Off = 0 8BIT SW 1 ARG A1: Off = 0 8BIT SW 1 ARG B1: Off = 0 8BIT SW 1 ARG A2: Off = 0 8BIT SW 1 ARG B2: Off = 0 8BIT SW 1 ARG A3: Off = 0 8BIT SW 1 ARG B3: Off = 0 8BIT SW 1 ARG A4: Off = 0 8BIT SW 1 ARG B4: Off = 0 8BIT SW 1 ARG A5: Off = 0 8BIT SW 1 ARG B5: Off = 0 8BIT SW 1 ARG A6: Off = 0 8BIT SW 1 ARG B6: Off = 0 8BIT SW 1 ARG A7: Off = 0 8BIT SW 1 ARG B7: Off = 0 SETTING 8BIT SW 1 CONTROL: Off = 0
842017A1.CDR

RUN

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 0

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 1

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 2

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 3

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 4

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 5

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 6

Off On

FLEXLOGIC OPERAND 8BIT SWITCH 1 BIT 7

Figure 539: 8-BIT SWITCH LOGIC

GE Multilin

C30 Controller System

5-99

5.6 CONTROL ELEMENTS

5 SETTINGS 5.6.6 PID REGULATOR

PATH: SETTINGS

CONTROL ELEMENTS

PID REGULATOR

PID 1(4) REGULATOR Range: Enabled, Disabled

PID 1 REGULATOR
MESSAGE

PID 1 FUNCTION: Disabled PID 1 SAMPLE TIME: 0.05 s PID 1 PROCESS SIGNAL: Off PID 1 SETPOINT SIGNAL: 0.00 PID 1 TRACKING SIGNAL: Off PID 1 PROPORTIONAL GAIN: 1.00 PID 1 SETPOINT WEIGHTING: 1.00 PID 1 INTEG. TIME CONST.: 1.00 sec PID 1 ANTIWINDUP: Disabled PID 1 AW TIME CONST.: 1.00 sec PID 1 DERIV. TIME CONST.: 1.00 s PID 1 DERIVATIVE LIMIT: 10 PID 1 MAX: 10 PID 1 MIN: 10 PID 1 Tmin: 500 ms PID 1 DEAD TIME: 1.00 sec PID 1 BLK: Off PID 1 TARGET: Self-reset PID 1 EVENTS: Disabled

Range: 0.05 to 30.00 s in steps of 0.01

Range: Off, any FlexAnalog parameter

MESSAGE

Range: -99999.99 to 99999.99 in steps of 0.01

MESSAGE

Range: Off, any FlexAnalog parameter

MESSAGE

Range: 0.01 to 100.00 in steps of 0.01

MESSAGE

Range: 0.01 to 1.00 in steps of 0.01

MESSAGE

Range: 0.00 to 600.00 s in steps of 0.01

MESSAGE

Range: Enabled, Disabled

MESSAGE

Range: 0.00 to 600.00 s in steps of 0.01

MESSAGE

Range: 0.00 to 600.00 s in steps of 0.01

MESSAGE

Range: 1 to 20 in steps of 1

MESSAGE

Range: -10000 to 10000 in steps of 1

MESSAGE

Range: -10000 to 10000 in steps of 1

MESSAGE

Range: 100 to 1000 ms in steps of 1

MESSAGE

Range: 1 to 20 s in steps of 1

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Self-reset, Latched, Disabled

MESSAGE

Range: Enabled, Disabled

MESSAGE

5-100

C30 Controller System

GE Multilin

5 SETTINGS A general form of a PID regulator in the s domain is shown below.


+ + y r + e K Ti + + 1 Tt + 1 s i -1 sKTd 1+sTd/N d + + p +

5.6 CONTROL ELEMENTS

Figure 540: PID BLOCK DIAGRAM The following terms apply to the block diagram: y is the process signal r is the setpoint signal w is the tracking signal u is the regulator output K is the proportional gain b is the setpoint weighting Td is the derivative time constant N is the derivative limit Ti is the integral time constant Tt is the anti-windup time constant

In discrete form, the equations for the regulator are: e( k) = r(k ) y( k) p ( k ) = K ( br ( k ) y ( k ) ) kT d N Td d ( k ) = ----------------------- d ( k 1 ) ----------------------- ( y ( k ) y ( k 1 ) ) T d + NT S T d + NT S u(k) = p(k) + i(k) + d(k) TS KT S e ( k ) i ( k + 1 ) = i ( k ) + ---------------------- + ------ ( w ( k ) u ( k ) ) AW Tt Ti Where TS is the sampling time and AW is a flag which enables anti-windup. The incremental form of the above equation is: Du ( k ) = u ( k ) u ( k 1 ) = Dp ( k ) + Di ( k ) + Dd ( k ) Where:
(EQ 5.2)

(EQ 5.1)

GE Multilin

C30 Controller System

5-101

5.6 CONTROL ELEMENTS Dp ( k ) = p ( k ) p ( k 1 ) = K ( br ( k ) y ( k ) br ( k 1 ) + y ( k 1 ) ) Di ( k ) = i ( k ) p ( k 1 ) TS KT S = e ( k 1 ) ---------- + AW ( w ( k 1 ) ) v ( k 1 ) ) ------ Ti Tt Dd ( k ) = d ( k ) d ( k 1 ) T d KN Td = Dd ( k 1 ) ----------------------- + ( y ( k ) ( 2y ( k 1 ) + y ( k 2 ) ) ) ----------------------T d + NT S T d + NT S The PID regulator logic is shown below.

5 SETTINGS

(EQ 5.3)

SETTING Function: Enabled = 1 SETTING Blocked: Off = 0 SETTING &

u>Tmin

&

SETTING Dead Time Tdead |u| ms

u>0
&

FLEXOPERAND PID 1 LOWER

FLEXOPERAND

SETTING Ts, K, b, Ti, Tt Td, N,


run AW

&

PID 1 RAISE

u<0

Antiwindup: Enabled = 1 SETTING Process: Setpoint: Tracking:

8u PID u

ACTUAL VALUE PID 1 DELTA OUT

SETTING max, min Out=MAX(min,MIN(max,u))


ACTUAL VALUE SETPOINT

ACTUAL VALUE PID 1 OUT

Figure 541: PID REGULATOR LOGIC

5-102

C30 Controller System

GE Multilin

5 SETTINGS 5.7INPUTS AND OUTPUTS


PATH: SETTINGS INPUTS/OUTPUTS CONTACT INPUTS

5.7 INPUTS AND OUTPUTS 5.7.1 CONTACT INPUTS

CONTACT INPUTS CONTACT INPUT H5a CONTACT INPUT H5a ID: Cont Ip 1 CONTACT INPUT H5a DEBNCE TIME: 2.0 ms CONTACT INPUT H5a EVENTS: Disabled

Range: up to 12 alphanumeric characters

MESSAGE

Range: 0.0 to 16.0 ms in steps of 0.5

MESSAGE

Range: Disabled, Enabled

MESSAGE

CONTACT INPUT xxx CONTACT INPUT THRESHOLDS


MESSAGE

Ips H5a,H5c,H6a,H6c THRESHOLD: 33 Vdc Ips H7a,H7c,H8a,H8c THRESHOLD: 33 Vdc

Range: 17, 33, 84, 166 Vdc

Range: 17, 33, 84, 166 Vdc

MESSAGE

MESSAGE

Ips xxx,xxx,xxx,xxx THRESHOLD: 33 Vdc

Range: 17, 33, 84, 166 Vdc

The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each group of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules) which contact inputs are available and then display settings for only those inputs. An alphanumeric ID may be assigned to a contact input for diagnostic, setting, and event recording purposes. The CONTACT IP X On (Logic 1) FlexLogic operand corresponds to contact input X being closed, while CONTACT IP X Off corresponds to contact input X being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to overcome contact bouncing conditions. As this time differs for different contact types and manufacturers, set it as a maximum contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT INPUT EVENTS is set to Enabled, every change in the contact input state will trigger an event. A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the figure below. The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a usersettable debounce time in order for the C30 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated (debounced), the contact input asserts a corresponding FlexLogic operand and logs an event as per user setting. A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the contact input into the Event Recorder (mark no. 2 in the diagram). Protection and control elements, as well as FlexLogic equations and timers, are executed eight times in a power system cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic operand reflecting the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the figure below). The update is performed at the beginning of the protection pass so all protection and control functions, as well as FlexLogic equations, are fed with the updated states of the contact inputs.

GE Multilin

C30 Controller System

5-103

5.7 INPUTS AND OUTPUTS

5 SETTINGS

The FlexLogic operand response time to the contact input change is equal to the debounce time setting plus up to one protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration of the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically a delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is below 1msec. For example, 8 protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a contact debounce time setting of 3.0 ms, the FlexLogic operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1 ms. These time limits depend on how soon the protection pass runs after the debouncing time. Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 s accuracy using the time of the first scan corresponding to the new state (mark no. 2 below). Therefore, the time stamp reflects a change in the DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the debounce timer. Keep in mind that the associated FlexLogic operand is asserted/de-asserted later, after validating the change. The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks no.1, 2, 3, and 4 in the figure below) and HIGH-LOW (marks no. 5, 6, 7, and 8 below) transitions.

INPUT VOLTAGE

USER-PROGRAMMABLE THRESHOLD

1
At this time, the new (HIGH) contact state is validated

3
The FlexLogic operand is going to be asserted at this protection pass
TM

6
Time stamp of the first scan corresponding to the new validated state is logged in the SOE record

5
At this time, the new (LOW) contact state is validated

5
RAW CONTACT STATE

Time stamp of the first scan corresponding to the new validated state is logged in the SOE record

7
The FlexLogicTM operand is going to be de-asserted at this protection pass

DEBOUNCE TIME (user setting)

4
FLEXLOGICTM OPERAND

SCAN TIME (0.5 msec)

The FlexLogicTM operand changes reflecting the validated contact state

DEBOUNCE TIME (user setting)

The FlexLogicTM operand changes reflecting the validated contact state

PROTECTION PASS (8 times a cycle controlled by the frequency tracking mechanism)

842709A1.cdr

Figure 542: INPUT CONTACT DEBOUNCING MECHANISM AND TIME-STAMPING SAMPLE TIMING Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This value should be selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V sources and 166 for 250 V sources. For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it in the Event Records menu, make the following settings changes:
CONTACT INPUT H5A ID: "Breaker Closed CONTACT INPUT H5A EVENTS: "Enabled"

(52b)"

Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.

5-104

C30 Controller System

GE Multilin

5 SETTINGS

5.7 INPUTS AND OUTPUTS 5.7.2 VIRTUAL INPUTS

PATH: SETTINGS

INPUTS/OUTPUTS

VIRTUAL INPUTS

VIRTUAL INPUT 1(64) Range: Disabled, Enabled

VIRTUAL INPUT

VIRTUAL INPUT 1 FUNCTION: Disabled VIRTUAL INPUT Virt Ip 1 VIRTUAL INPUT TYPE: Latched 1 ID: 1

Range: Up to 12 alphanumeric characters

MESSAGE

Range: Self-Reset, Latched

MESSAGE

MESSAGE

VIRTUAL INPUT 1 EVENTS: Disabled

Range: Disabled, Enabled

MANDS

There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the COMmenu) and communications protocols. All virtual input operands are defaulted to Off (logic 0) unless the appropriate input signal is received. If the VIRTUAL INPUT x FUNCTION is to Disabled, the input will be forced to off (logic 0) regardless of any attempt to alter the input. If set to Enabled, the input operates as shown on the logic diagram and generates output FlexLogic operands in response to received input signals and the applied settings. There are two types of operation: self-reset and latched. If VIRTUAL INPUT x TYPE is Self-Reset, when the input signal transits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic equations and then return to off. If set to Latched, the virtual input sets the state of the output operand to the same state as the most recent received input. The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the operand is to be used anywhere other than internally in a FlexLogic equation, it will likely have to be lengthened in time. A FlexLogic timer with a delayed reset can perform this function.
SETTING
VIRTUAL INPUT 1 FUNCTION:

NOTE

Disabled=0 Enabled=1
AND

S Latch R
OR

Virtual Input 1 to ON = 1 Virtual Input 1 to OFF = 0


AND

SETTING
VIRTUAL INPUT 1 ID:

SETTING VIRTUAL INPUT 1 TYPE: Latched Self - Reset

(Flexlogic Operand) Virt Ip 1

AND
827080A2.CDR

Figure 543: VIRTUAL INPUTS SCHEME LOGIC

GE Multilin

C30 Controller System

5-105

5.7 INPUTS AND OUTPUTS

5 SETTINGS 5.7.3 CONTACT OUTPUTS

a) DIGITAL OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1 Range: Up to 12 alphanumeric characters

CONTACT OUTPUT H1

CONTACT OUTPUT H1 ID Cont Op 1 OUTPUT H1 OPERATE: Off OUTPUT H1 SEAL-IN: Off CONTACT OUTPUT H1 EVENTS: Enabled

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Disabled, Enabled

MESSAGE

Upon startup of the relay, the main processor will determine from an assessment of the modules installed in the chassis which contact outputs are available and present the settings for only these outputs. An ID may be assigned to each contact output. The signal that can OPERATE a contact output may be any FlexLogic operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic operand may be used to SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so. For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A contacts (see the trip circuit example in the Digital elements section). The monitor will set a flag (see the specifications for Form-A). The name of the FlexLogic operand set by the monitor, consists of the output relay designation, followed by the name of the flag; for example, CONT OP 1 ION. In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect operation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in the trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the C30 using the CONT OP 1 ION FlexLogic operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: Cont Op 1" OUTPUT H1 OPERATE: any suitable FlexLogic OUTPUT H1 SEAL-IN: Cont Op 1 IOn CONTACT OUTPUT H1 EVENTS: Enabled

operand

b) LATCHING OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS CONTACT OUTPUT H1a Range: Up to 12 alphanumeric characters

CONTACT OUTPUT H1a

OUTPUT H1a ID L-Cont Op 1 OUTPUT H1a OPERATE: Off OUTPUT H1a RESET: Off OUTPUT H1a TYPE: Operate-dominant OUTPUT H1a EVENTS: Disabled

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

Range: Operate-dominant, Reset-dominant

MESSAGE

Range: Disabled, Enabled

MESSAGE

5-106

C30 Controller System

GE Multilin

5 SETTINGS

5.7 INPUTS AND OUTPUTS

The C30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and populates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware before executing any other functions of the relay (such as protection and control features or FlexLogic). The latching output modules, either as a part of the relay or as individual modules, are shipped from the factory with all latching contacts opened. It is highly recommended to double-check the programming and positions of the latching contacts when replacing a module. Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring capabilities for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test error is declared. The error is signaled by the LATCHING OUT ERROR FlexLogic operand, event, and target message. OUTPUT H1a OPERATE: This setting specifies a FlexLogic operand to operate the close coil of the contact. The relay will seal-in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off), any activity of the OPERATE input, such as subsequent chattering, will not have any effect. With both the OPERATE and RESET inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting. OUTPUT H1a RESET: This setting specifies a FlexLogic operand to operate the trip coil of the contact. The relay will seal-in this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any activity of the RESET input, such as subsequent chattering, will not have any effect. With both the OPERATE and RESET inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting. OUTPUT H1a TYPE: This setting specifies the contact response under conflicting control inputs; that is, when both the OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact will close if set to Operate-dominant and will open if set to Reset-dominant.

Application Example 1: A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The following settings should be applied. Program the Latching Outputs by making the following changes in the SETTINGS CONTACT OUTPUT H1a menu (assuming an H4L module): PUTS
OUTPUT H1a OPERATE: PUSHBUTTON 1 ON OUTPUT H1a RESET: PUSHBUTTON 2 ON INPUTS/OUTPUTS CONTACT OUT-

Program the pushbuttons by making the following changes in the PRODUCT SETUP USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus: TONS
PUSHBUTTON 1 FUNCTION: Self-reset PUSHBTN 1 DROP-OUT TIME: 0.00 s

USER-PROGRAMMABLE PUSHBUT-

PUSHBUTTON 2 FUNCTION: Self-reset PUSHBTN 2 DROP-OUT TIME: 0.00 s

Application Example 2: A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
INPUTS/OUTPUTS Program the Latching Outputs by making the following changes in the SETTINGS PUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module): OUTPUT H1a OPERATE: VO1 OUTPUT H1a RESET: VO2 OUTPUT H1c OPERATE: VO2 OUTPUT H1c RESET: VO1 CONTACT OUT-

Since the two physical contacts in this example are mechanically separated and have individual control inputs, they will not operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time may occur. Therefore, a pair of contacts programmed to be a multi-contact relay will not guarantee any specific sequence of operation (such as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the control inputs as shown in the next application example. Application Example 3: A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement this functionality as described below:

GE Multilin

C30 Controller System

5-107

5.7 INPUTS AND OUTPUTS Write the following FlexLogic equation (EnerVista UR Setup example shown):

5 SETTINGS

Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.
PUTS

Program the Latching Outputs by making the following changes in the SETTINGS INPUTS/OUTPUTS CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: VO1 OUTPUT H1a RESET: VO4 OUTPUT H1c OPERATE: VO2 OUTPUT H1c RESET: VO3

CONTACT OUT-

Application Example 4: A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1 is high, and should stay opened when VO1 is low. Program the relay as follows.

Write the following FlexLogic equation (EnerVista UR Setup example shown):

PUTS

Program the Latching Outputs by making the following changes in the SETTINGS CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: VO1 OUTPUT H1a RESET: VO2

INPUTS/OUTPUTS

CONTACT OUT-

5.7.4 VIRTUAL OUTPUTS


PATH: SETTINGS INPUTS/OUTPUTS VIRTUAL OUTPUTS VIRTUAL OUTPUT 1(96)

VIRTUAL OUTPUT

VIRTUAL OUTPUT Virt Op 1

1 ID

Range: Up to 12 alphanumeric characters

MESSAGE

VIRTUAL OUTPUT 1 EVENTS: Disabled

Range: Disabled, Enabled

There are 96 virtual outputs that may be assigned via FlexLogic. If not assigned, the output will be forced to OFF (Logic 0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings would be programmed as follows:

5-108

C30 Controller System

GE Multilin

5 SETTINGS
VIRTUAL OUTPUT 1 ID: "Trip" VIRTUAL OUTPUT 1 EVENTS: "Disabled"

5.7 INPUTS AND OUTPUTS

5.7.5 REMOTE DEVICES a) REMOTE INPUTS/OUTPUTS OVERVIEW Remote inputs and outputs provide a means of exchanging digital state information between Ethernet-networked devices. The IEC 61850 GSSE (Generic Substation State Event) and GOOSE (Generic Object Oriented Substation Event) standards are used. The IEC 61850 specification requires that communications between devices be implemented on Ethernet. For UR-series relays, Ethernet communications is provided on all CPU modules except type 9E.
NOTE

The sharing of digital point state information between GSSE/GOOSE equipped relays is essentially an extension to FlexLogic, allowing distributed FlexLogic by making operands available to/from devices on a common communications network. In addition to digital point states, GSSE/GOOSE messages identify the originator of the message and provide other information required by the communication specification. All devices listen to network messages and capture data only from messages that have originated in selected devices. IEC 61850 GSSE messages are compatible with UCA GOOSE messages and contain a fixed set of digital points. IEC 61850 GOOSE messages can, in general, contain any configurable data items. When used by the remote input/output feature, IEC 61850 GOOSE messages contain the same data as GSSE messages. Both GSSE and GOOSE messages are designed to be short, reliable, and high priority. GOOSE messages have additional advantages over GSSE messages due to their support of VLAN (virtual LAN) and Ethernet priority tagging functionality. The GSSE message structure contains space for 128 bit pairs representing digital point state information. The IEC 61850 specification provides 32 DNA bit pairs that represent the state of two pre-defined events and 30 user-defined events. All remaining bit pairs are UserSt bit pairs, which are status bits representing user-definable events. The C30 implementation provides 32 of the 96 available UserSt bit pairs. The IEC 61850 specification includes features that are used to cope with the loss of communication between transmitting and receiving devices. Each transmitting device will send a GSSE/GOOSE message upon a successful power-up, when the state of any included point changes, or after a specified interval (the default update time) if a change-of-state has not occurred. The transmitting device also sends a hold time which is set greater than three times the programmed default time required by the receiving device. Receiving devices are constantly monitoring the communications network for messages they require, as recognized by the identification of the originating device carried in the message. Messages received from remote devices include the message time allowed to live. The receiving relay sets a timer assigned to the originating device to this time interval, and if it has not received another message from this device at time-out, the remote device is declared to be non-communicating, so it will use the programmed default state for all points from that specific remote device. If a message is received from a remote device before the time allowed to live expires, all points for that device are updated to the states contained in the message and the hold timer is restarted. The status of a remote device, where Offline indicates non-communicating, can be displayed. The remote input/output facility provides for 64 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a C30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GOOSE message is programmed in the SETTINGS GSSE/GOOSE CONFIGURATION TRANSMISSION FIXED GOOSE GOOSE ID setting. Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message is programmed in the SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE TRANSMISSION GSSE GSSE ID setting. CONFIGURATION In C30 releases previous to 5.0x, these name strings were represented by the RELAY NAME setting.

GE Multilin

C30 Controller System

5-109

5.7 INPUTS AND OUTPUTS c) REMOTE DEVICES: ID OF DEVICE FOR RECEIVING GSSE MESSAGES
PATH: SETTINGS INPUTS/OUTPUTS REMOTE DEVICES REMOTE DEVICE 1(16)

5 SETTINGS

REMOTE DEVICE

REMOTE DEVICE 1 ID: Remote Device 1 REMOTE DEVICE 1 ETYPE APPID: 0 REMOTE DEVICE 1 DATASET: Fixed

Range: up to 20 alphanumeric characters

Range: 0 to 16383 in steps of 1

MESSAGE

Range: Fixed, GOOSE 1 through GOOSE 8

MESSAGE

Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row) the exact identification (ID) assigned to those devices. The REMOTE DEVICE 1 ETYPE APPID setting is only used with GOOSE messages; they are not applicable to GSSE messages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corresponding settings on the sending device. The REMOTE DEVICE 1 DATASET setting provides for the choice of the C30 fixed (DNA/UserSt) dataset (that is, containing DNA and UserSt bit pairs), or one of the configurable datasets. Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this reason, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic operands. However, GGIO3 data can be read by IEC 61850 clients.

5
PATH: SETTINGS INPUTS/OUTPUTS REMOTE INPUTS REMOTE INPUT 1(64)

5.7.6 REMOTE INPUTS

REMOTE INPUT 1

REMOTE INPUT Remote Ip 1


MESSAGE

1 ID:

Range: up to 12 alphanumeric characters

REMOTE IN 1 DEVICE: Remote Device 1 REMOTE IN None 1 ITEM:

Range: 1 to 16 inclusive

MESSAGE

Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32, Config Item 1 to Config Item 64 Range: On, Off, Latest/On, Latest/Off

MESSAGE

REMOTE IN 1 DEFAULT STATE: Off REMOTE IN 1 EVENTS: Disabled

Range: Disabled, Enabled

MESSAGE

Remote Inputs that create FlexLogic operands at the receiving relay are extracted from GSSE/GOOSE messages originating in remote devices. Each remote input can be selected from a list consisting of 64 selections: DNA-1 through DNA-32 and UserSt-1 through UserSt-32. The function of DNA inputs is defined in the IEC 61850 specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function of UserSt inputs is defined by the user selection of the FlexLogic operand whose state is represented in the GSSE/GOOSE message. A user must program a DNA point from the appropriate FlexLogic operand. Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local use. This programming is performed via the three settings shown above. The REMOTE INPUT 1 ID setting allows the user to assign descriptive text to the remote input. The REMOTE IN 1 DEVICE setting selects the number (1 to 16) of the remote device which originates the required signal, as previously assigned to the remote device via the setting REMOTE DEVICE 1(16) ID (see the Remote devices section). The REMOTE IN 1 ITEM setting selects the specific bits of the GSSE/GOOSE message required. The REMOTE IN 1 DEFAULT STATE setting selects the logic state for this point if the local relay has just completed startup or the remote device sending the point is declared to be non-communicating. The following choices are available:

5-110

C30 Controller System

GE Multilin

5 SETTINGS Setting REMOTE IN 1 DEFAULT STATE to On value defaults the input to logic 1. Setting REMOTE IN 1 DEFAULT STATE to Off value defaults the input to logic 0.

5.7 INPUTS AND OUTPUTS

Setting REMOTE IN 1 DEFAULT STATE to Latest/On freezes the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, the input will default to logic 1. When communication resumes, the input becomes fully operational. Setting REMOTE IN 1 DEFAULT STATE to Latest/Off freezes the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, the input will default to logic 0. When communication resumes, the input becomes fully operational. For additional information on GSSE/GOOOSE messaging, refer to the Remote devices section in this chapter.
NOTE

5.7.7 REMOTE DOUBLE-POINT STATUS INPUTS


PATH: SETTINGS INPUTS/OUTPUTS REMOTE DPS INPUTS REMOTE DPS INPUT 1(5) Range: up to 12 alphanumeric characters

REMOTE DPS INPUT 1

REM DPS IN 1 ID: RemDPS Ip 1 REM DPS IN 1 DEV: Remote Device 1 REM DPS IN 1 ITEM: None REM DPS IN 1 EVENTS: Disabled

Range: Remote Device 1 to Remote Device 16

MESSAGE

Range: None, Dataset Item 1 to Dataset Item 64

MESSAGE

Range: Enabled, Disabled

MESSAGE

Remote double-point status inputs are extracted from GOOSE messages originating in the remote device. Each remote double point status input must be programmed to replicate the logic state of a specific signal from a specific remote device for local use. This functionality is accomplished with the five remote double-point status input settings. REM DPS IN 1 ID: This setting assigns descriptive text to the remote double-point status input. REM DPS IN 1 DEV: This setting selects a remote device ID to indicate the origin of a GOOSE message. The range is selected from the remote device IDs specified in the Remote devices section. REM DPS IN 1 ITEM: This setting specifies the required bits of the GOOSE message.

The configurable GOOSE dataset items must be changed to accept a double-point status item from a GOOSE dataset COMMUNICATION IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION (changes are made in the SETTINGS RECEPTION CONFIGURABLE GOOSE CONFIGIGURABLE GOOSE 1(8) CONFIG GSE 1 DATASET ITEMS menus). Dataset items configured to receive any of GGIO3.ST.IndPos1.stV to GGIO3.ST.IndPos5.stV will accept double-point status information that will be decoded by the remote double-point status inputs configured to this dataset item. The remote double point status is recovered from the received IEC 61850 dataset and is available as through the RemDPS Ip 1 BAD, RemDPS Ip 1 INTERM, RemDPS Ip 1 OFF, and RemDPS Ip 1 ON FlexLogic operands. These operands can then be used in breaker or disconnect control schemes. 5.7.8 REMOTE OUTPUTS a) DNA BIT PAIRS
PATH: SETTINGS INPUTS/OUTPUTS REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUPUTS DNA- 1(32) BIT PAIR Range: FlexLogic operand

REMOTE OUTPUTS DNA- 1 BIT PAIR


MESSAGE

DNA- 1 OPERAND: Off DNA- 1 EVENTS: Disabled

Range: Disabled, Enabled

GE Multilin

C30 Controller System

5-111

5.7 INPUTS AND OUTPUTS

5 SETTINGS

Remote outputs (1 to 32) are FlexLogic operands inserted into GSSE/GOOSE messages that are transmitted to remote devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic operand. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted. Table 511: IEC 61850 DNA ASSIGNMENTS
DNA 1 2 IEC 61850 DEFINITION Test ConfRev FLEXLOGIC OPERAND IEC 61850 TEST MODE IEC 61850 CONF REV

b) USERST BIT PAIRS


PATH: SETTINGS INPUTS/OUTPUTS REMOTE OUTPUTS UserSt BIT PAIRS REMOTE OUTPUTS UserSt- 1(32) BIT PAIR

REMOTE OUTPUTS UserSt- 1 BIT PAIR


MESSAGE

UserSt- 1 OPERAND: Off UserSt- 1 EVENTS: Disabled

Range: FlexLogic operand

Range: Disabled, Enabled

Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the message must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select the operand which represents a specific UserSt function (as selected by the user) to be transmitted. The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of state of any selected digital point. This setting is located in the PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION settings menu.

5
NOTE

DEFAULT GSSE/GOOSE UPDATE TIME: 60 s

Range: 1 to 60 s in steps of 1

For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the Remote Devices section. 5.7.9 RESETTING
PATH: SETTINGS INPUTS/OUTPUTS RESETTING

RESETTING

RESET OPERAND: Off

Range: FlexLogic operand

Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition has cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel, or any programmed operand. When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which are stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each create the RESET OP FlexLogic operand. Each individual source of a RESET command also creates its individual operand RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting shown above selects the operand that will create the RESET OP (OPERAND) operand.

5-112

C30 Controller System

GE Multilin

5 SETTINGS

5.7 INPUTS AND OUTPUTS 5.7.10 DIRECT INPUTS/OUTPUTS

a) DIRECT INPUTS
PATH: SETTINGS INPUTS/OUTPUTS DIRECT INPUTS DIRECT INPUT 1(32) Range: up to 12 alphanumeric characters

DIRECT INPUT

DIRECT INPUT 1 NAME: Dir Ip 1 DIRECT INPUT DEVICE ID: 1 1

Range: 1 to 16

MESSAGE

MESSAGE

DIRECT INPUT 1 BIT NUMBER: 1 DIRECT INPUT 1 DEFAULT STATE: Off DIRECT INPUT 1 EVENTS: Disabled

Range: 1 to 32

Range: On, Off, Latest/On, Latest/Off

MESSAGE

Range: Enabled, Disabled

MESSAGE

These settings specify how the direct input information is processed. The DIRECT INPUT 1 NAME setting allows the user to assign a descriptive name to the direct input. The DIRECT INPUT 1 DEVICE ID represents the source of direct input 1. The specified direct input is driven by the device identified here. The DIRECT INPUT 1 BIT NUMBER is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit identified as DIRECT INPUT 1 BIT NUMBER. This corresponds to the direct output number of the sending device. The DIRECT INPUT 1 DEFAULT STATE represents the state of the direct input when the associated direct device is offline. The following choices are available: Setting DIRECT INPUT 1 DEFAULT STATE to On value defaults the input to Logic 1. Setting DIRECT INPUT 1 DEFAULT STATE to Off value defaults the input to Logic 0. Setting DIRECT INPUT 1 DEFAULT STATE to Latest/On freezes the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 1. When communication resumes, the input becomes fully operational. Setting DIRECT INPUT 1 DEFAULT STATE to Latest/Off freezes the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 0. When communication resumes, the input becomes fully operational.

b) DIRECT OUTPUTS
PATH: SETTINGS INPUTS/OUTPUTS DIRECT OUTPUTS DIRECT OUTPUT 1(32) Range: up to 12 alphanumeric characters

DIRECT OUTPUT

DIRECT OUT Dir Out 1 DIRECT OUT Off

1 NAME: 1 OPERAND:

Range: FlexLogic operand

MESSAGE

MESSAGE

DIRECT OUTPUT 1 EVENTS: Disabled

Range: Enabled, Disabled

The DIRECT OUT 1 NAME setting allows the user to assign a descriptive name to the direct output. The DIR OUT 1 OPERAND is the FlexLogic operand that determines the state of this direct output. c) APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs.

GE Multilin

C30 Controller System

5-113

5.7 INPUTS AND OUTPUTS EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A C30 RELAY

5 SETTINGS

Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The two IEDs are connected via single-channel digital communication cards as shown below.
TX1

UR IED 1
RX1

TX1

UR IED 2
RX1

Figure 544: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5 and bit number 12 are used, as an example): UR IED 1:
DIRECT INPUT 5 DEVICE ID = 2 DIRECT INPUT 5 BIT NUMBER = 12

UR IED 2:

DIRECT OUT 12 OPERAND

= Cont Ip 1 On

The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON. EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION

A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below.

UR IED 1

BLOCK

UR IED 2

UR IED 3

UR IED 4

842712A1.CDR

Figure 545: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1 would trip the bus upon detecting a fault and applying a short coordination time delay. The following settings should be applied (assume Bit 3 is used by all 3 devices to sent the blocking signal and Direct Inputs 7, 8, and 9 are used by the receiving device to monitor the three blocking signals): UR IED 2: UR IED 3: UR IED 4: UR IED 1:
DIRECT OUT 3 OPERAND: "PHASE IOC1 OP" DIRECT OUT 3 OPERAND: "PHASE IOC1 OP" DIRECT OUT 3 OPERAND: "PHASE IOC1 OP" DIRECT INPUT 7 DEVICE ID: "2" DIRECT INPUT 7 BIT NUMBER: "3" DIRECT INPUT 7 DEFAULT STATE: select DIRECT INPUT 8 DEVICE ID: "3" DIRECT INPUT 8 BIT NUMBER: "3" DIRECT INPUT 8 DEFAULT STATE: select

"On" for security, select "Off" for dependability

"On" for security, select "Off" for dependability

5-114

C30 Controller System

GE Multilin

5 SETTINGS
DIRECT INPUT 9 DEVICE ID: "4" DIRECT INPUT 9 BIT NUMBER: "3" DIRECT INPUT 9 DEFAULT STATE: select

5.7 INPUTS AND OUTPUTS

"On" for security, select "Off" for dependability

Now the three blocking signals are available in UR IED 1 as DIRECT INPUT 7 ON, DIRECT INPUT 8 ON, and DIRECT INPUT 9 ON. Upon losing communications or a device, the scheme is inclined to block (if any default state is set to On), or to trip the bus on any overcurrent condition (all default states set to Off). EXAMPLE 2: PILOT-AIDED SCHEMES Consider a three-terminal line protection application shown in the figure below.
UR IED 1 UR IED 2

UR IED 3

842713A1.CDR

Figure 546: THREE-TERMINAL LINE APPLICATION Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown below. The scheme output operand HYB POTT TX1 is used to key the permission.

TX1

RX1

RX2

UR IED 1
RX1 TX1

UR IED 2
TX2

RX1

UR IED 3
TX1
842714A1.CDR

Figure 547: SINGLE-CHANNEL OPEN-LOOP CONFIGURATION In the above architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a bridge. The following settings should be applied: UR IED 1:
DIRECT OUT 2 OPERAND: "HYB POTT TX1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2) DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: "4" (effectively, this is a message from DIRECT OUT 2 OPERAND: "HYB POTT TX1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2) DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: "3" (effectively, this is a message from DIRECT INPUT 5 DEVICE ID: "1" DIRECT INPUT 5 BIT NUMBER: "2" DIRECT INPUT 6 DEVICE ID: "3" DIRECT INPUT 6 BIT NUMBER: "2"

IED 3)

UR IED 3:

IED 1)

UR IED 2:

GE Multilin

C30 Controller System

5-115

5.7 INPUTS AND OUTPUTS


DIRECT OUT 2 OPERAND: "HYB POTT TX1" DIRECT OUT 3 OPERAND: "DIRECT INPUT 5" DIRECT OUT 4 OPERAND: "DIRECT INPUT 6"

5 SETTINGS

(forward a message from 1 to 3) (forward a message from 3 to 1)

Signal flow between the three IEDs is shown in the figure below:
UR IED 1
DIRECT OUT 2 = HYB POTT TX1 DIRECT INPUT 5 DIRECT INPUT 6

UR IED 2
DIRECT INPUT 5 DIRECT OUT 2 = HYB POTT TX1 DIRECT OUT 4 = DIRECT INPUT 6 DIRECT OUT 3 = DIRECT INPUT 5 DIRECT INPUT 6

UR IED 3

DIRECT INPUT 5 DIRECT INPUT 6

DIRECT OUT 2 = HYB POTT TX1


842717A1.CDR

Figure 548: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT EXAMPLE 3 In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct inputs 5 and 6 should be ANDed in FlexLogic and the resulting operand configured as the permission to trip (HYB POTT RX1 setting).

5-116

C30 Controller System

GE Multilin

5 SETTINGS

5.7 INPUTS AND OUTPUTS 5.7.11 TELEPROTECTION INPUTS AND OUTPUTS

a) OVERVIEW The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create distributed protection and control schemes via dedicated communications channels. Some examples are directional comparison pilot schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection functionality. The teleprotection function must be enabled to utilize the inputs. b) TELEPROTECTION INPUTS
PATH: SETTINGS INPUTS/OUTPUTS TELEPROTECTION TELEPROT INPUTS Range: Off, On, Latest/Off, Latest/On

TELEPROT INPUTS

TELEPROT INPUT 1-1 DEFAULT: Off TELEPROT INPUT 1-2 DEFAULT: Off

Range: Off, On, Latest/Off, Latest/On

MESSAGE

MESSAGE

TELEPROT INPUT 1-16 DEFAULT: Off TELEPROT INPUT 2-1 DEFAULT: Off TELEPROT INPUT 2-2 DEFAULT: Off

Range: Off, On, Latest/Off, Latest/On

Range: Off, On, Latest/Off, Latest/On

MESSAGE

Range: Off, On, Latest/Off, Latest/On

MESSAGE

MESSAGE

TELEPROT INPUT 2-16 DEFAULT: Off

Range: Off, On, Latest/Off, Latest/On

Setting the TELEPROT INPUT ~~ DEFAULT setting to On defaults the input to logic 1 when the channel fails. A value of Off defaults the input to logic 0 when the channel fails. The Latest/On and Latest/Off values freeze the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for Latest/On and logic 0 for Latest/Off.

GE Multilin

C30 Controller System

5-117

5.7 INPUTS AND OUTPUTS c) TELEPROTECTION OUTPUTS


PATH: SETTINGS INPUTS/OUTPUTS TELEPROTECTION TELEPROT OUTPUTS Range: FlexLogic operand

5 SETTINGS

TELEPROT OUTPUTS

TELEPROT OUTPUT 1-1: Off TELEPROT OUTPUT 1-2: Off

Range: FlexLogic operand

MESSAGE

MESSAGE

TELEPROT OUTPUT 1-16: Off TELEPROT OUTPUT 2-1: Off TELEPROT OUTPUT 2-2: Off

Range: FlexLogic operand

Range: FlexLogic operand

MESSAGE

Range: FlexLogic operand

MESSAGE

MESSAGE

TELEPROT OUTPUT 2-16: Off

Range: FlexLogic operand

As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of communication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each channel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand on both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays.
UR-1
ACTUAL VALUES CHANNEL 1 STATUS: SETTING TELEPROT OUTPUT 1-1: (same for 1-2...1-16) Off (Flexlogic Operand) SETTING TELEPROT INPUT 1-1 DEFAULT: (same for 1-2...1-16) FLEXLOGIC OPERAND
TELEPRO INPUT 1-1 On

UR-2
SETTING TELEPROT INPUT 1-1 DEFAULT: (same for 1-2...1-16) On Off OR FLEXLOGIC OPERAND
TELEPRO INPUT 1-1 On

Fail OK ACTUAL VALUES CHANNEL 1 STATUS:

(same for 1-2...1-16)

Communication channel #1
(Teleprotection I/O Enabled)
SETTING
TELEPROT OUTPUT 1-1:

On OR Off

Fail OK

(same for 1-2...1-16)

(same for 1-2...1-16)

Off (Flexlogic Operand)

ACTUAL VALUES CHANNEL 2 STATUS: SETTING TELEPROT OUTPUT 2-1: (same for 1-2...1-16) Off (Flexlogic Operand) SETTING TELEPROT INPUT 2-1 DEFAULT: (same for 1-2...1-16) FLEXLOGIC OPERAND
TELEPRO INPUT 2-1 On

SETTING TELEPROT INPUT 2-1 DEFAULT: (same for 2-2...2-16) On Off

UR-2 or UR-3

Fail OK ACTUAL VALUES CHANNEL 2 STATUS:

FLEXLOGIC OPERAND OR (same for 2-2...2-16)


TELEPRO INPUT 2-1 On

Communication channel #2
(On 3-terminal system or 2-terminal with redundant channel)
SETTING (same for 2-2...2-16)
TELEPROT OUTPUT 2-1:

On OR Off

Fail OK

(same for 1-2...1-16)

Off (Flexlogic Operand)

842750A2.CDR

Figure 549: TELEPROTECTION INPUT/OUTPUT PROCESSING

5-118

C30 Controller System

GE Multilin

5 SETTINGS

5.7 INPUTS AND OUTPUTS 5.7.12 IEC 61850 GOOSE ANALOGS

PATH: SETTINGS

INPUTS/OUTPUTS

IEC 61850 GOOSE ANALOGS

GOOSE ANALOG INPUT 1(16) Range: 1000000.000 to 1000000.000 in steps of 0.001

GOOSE ANALOG INPUT 1


MESSAGE

ANALOG 1 DEFAULT: 1000.000 ANALOG 1 DEFAULT MODE: Default Value GOOSE ANALOG UNITS: 1

Range: Default Value, Last Known

Range: up to 4 alphanumeric characters

MESSAGE

MESSAGE

GOOSE ANALOG 1 PU: 1.000

Range: 0.000 to 1000000000.000 in steps of 0.001

The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series devices. The following settings are available for each GOOSE analog input. ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline and the ANALOG 1 DEFAULT MODE is set to Default Value.This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting, not all possible values can be stored. Some values may be rounded to the closest possible floating point number. ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is Last Known, the value of the GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is Default Value, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting. GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual values display of the corresponding GOOSE analog input value. GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAnalog values in other C30 features, such as FlexElements. The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.

Table 512: GOOSE ANALOG INPUT BASE UNITS


ELEMENT dcmA FREQUENCY PHASE ANGLE POWER FACTOR RTDs SOURCE CURRENT SOURCE POWER SOURCE VOLTAGE BASE UNITS BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured under the +IN and IN inputs. fBASE = 1 Hz BASE = 360 degrees (see the UR angle referencing convention) PFBASE = 1.00 BASE = 100C IBASE = maximum nominal primary RMS value of the +IN and IN inputs PBASE = maximum value of VBASE IBASE for the +IN and IN inputs VBASE = maximum nominal primary RMS value of the +IN and IN inputs

The GOOSE analog input FlexAnalog values are available for use in other C30 functions that use FlexAnalog values.

GE Multilin

C30 Controller System

5-119

5.7 INPUTS AND OUTPUTS

5 SETTINGS 5.7.13 IEC 61850 GOOSE INTEGERS

PATH: SETTINGS

INPUTS/OUTPUTS

IEC 61850 GOOSE UINTEGERS

GOOSE UINTEGER INPUT 1(16) Range: 0 to 429496295 in steps of 1

GOOSE UINTEGER INPUT 1


MESSAGE

UINTEGER 1 DEFAULT: 1000 UINTEGER 1 DEFAULT MODE: Default Value

Range: Default Value, Last Known

The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two URseries devices. The following settings are available for each GOOSE uinteger input. UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is offline and the UINTEGER 1 DEFAULT MODE is set to Default Value.This setting is stored as a 32-bit unsigned integer number. UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is Last Known, the value of the GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is Default Value, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.

The GOOSE integer input FlexInteger values are available for use in other C30 functions that use FlexInteger values.

5-120

C30 Controller System

GE Multilin

5 SETTINGS 5.8TRANSDUCER INPUTS AND OUTPUTS


PATH: SETTINGS TRANSDUCER I/O DCMA INPUTS

5.8 TRANSDUCER INPUTS AND OUTPUTS 5.8.1 DCMA INPUTS


DCMA INPUT F1(W8) Range: Disabled, Enabled

DCMA INPUT F1

DCMA INPUT F1 FUNCTION: Disabled


MESSAGE

DCMA INPUT F1 ID: DCMA Ip 1 DCMA INPUT F1 UNITS: A DCMA INPUT F1 RANGE: 0 to -1 mA DCMA INPUT F1 MIN VALUE: 0.000 DCMA INPUT F1 MAX VALUE: 0.000

Range: up to 20 alphanumeric characters

Range: 6 alphanumeric characters

MESSAGE

MESSAGE

Range: 0 to 1 mA, 0 to +1 mA, 1 to +1 mA, 0 to 5 mA, 0 to 10mA, 0 to 20 mA, 4 to 20 mA Range: 9999.999 to +9999.999 in steps of 0.001

MESSAGE

Range: 9999.999 to +9999.999 in steps of 0.001

MESSAGE

Hardware and software is provided to receive signals from external transducers and convert these signals into a digital format for use as required. The relay will accept inputs in the range of 1 to +20 mA DC, suitable for use with most common transducer output ranges; all inputs are assumed to be linear over the complete range. Specific hardware details are contained in chapter 3. Before the dcmA input signal can be used, the value of the signal measured by the relay must be converted to the range and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies this process by internally scaling the output from the external transducer and displaying the actual primary parameter. dcmA input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with the settings shown here. The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up, the relay will automatically generate configuration settings for every channel, based on the order code, in the same general manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as the channel number. The relay generates an actual value for each available input channel. Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5F transducer module installed in slot F. The function of the channel may be either Enabled or Disabled. If Disabled, no actual values are created for the channel. An alphanumeric ID is assigned to each channel; this ID will be included in the channel actual value, along with the programmed units associated with the parameter measured by the transducer, such as volts, C, megawatts, etc. This ID is also used to reference the channel as the input parameter to features designed to measure this type of parameter. The DCMA INPUT F1 RANGE setting specifies the mA DC range of the transducer connected to the input channel. The DCMA INPUT F1 MIN VALUE and DCMA INPUT F1 MAX VALUE settings are used to program the span of the transducer in primary units. For example, a temperature transducer might have a span from 0 to 250C; in this case the DCMA INPUT F1 MIN VALUE value is 0 and the DCMA INPUT F1 MAX VALUE value is 250. Another example would be a watts transducer with a span from 20 to +180 MW; in this case the DCMA INPUT F1 MIN VALUE value would be 20 and the DCMA INPUT F1 MAX VALUE value 180. Intermediate values between the min and max values are scaled linearly.

GE Multilin

C30 Controller System

5-121

5.8 TRANSDUCER INPUTS AND OUTPUTS

5 SETTINGS 5.8.2 RTD INPUTS

PATH: SETTINGS

TRANSDUCER I/O

RTD INPUTS

RTD INPUT F1(W8) Range: Disabled, Enabled

RTD INPUT F1

RTD INPUT F1 FUNCTION: Disabled


MESSAGE

RTD INPUT F1 ID: RTD Ip 1 RTD INPUT F1 TYPE: 100 Nickel

Range: Up to 20 alphanumeric characters

MESSAGE

Range: 100 Nickel, 10 Copper, 100 Platinum, 120 Nickel

Hardware and software is provided to receive signals from external resistance temperature detectors and convert these signals into a digital format for use as required. These channels are intended to be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3. RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with the settings shown here. The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up, the relay will automatically generate configuration settings for every channel, based on the order code, in the same general manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as the channel number. The relay generates an actual value for each available input channel. Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5C transducer module installed in the first available slot.

The function of the channel may be either Enabled or Disabled. If Disabled, there will not be an actual value created for the channel. An alphanumeric ID is assigned to the channel; this ID will be included in the channel actual values. It is also used to reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of RTD connected to the channel configures the channel. Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In FlexElements, the operate level is scaled to a base of 100C. For example, a trip level of 150C is achieved by setting the operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type.

5-122

C30 Controller System

GE Multilin

5 SETTINGS

5.8 TRANSDUCER INPUTS AND OUTPUTS

Table 513: RTD TEMPERATURE VS. RESISTANCE


TEMPERATURE C 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 F 58 40 22 4 14 32 50 68 86 104 122 140 158 176 194 212 230 248 266 284 302 320 338 356 374 392 410 428 446 464 482 RESISTANCE (IN OHMS) 100 PT (DIN 43760) 80.31 84.27 88.22 92.16 96.09 100.00 103.90 107.79 111.67 115.54 119.39 123.24 127.07 130.89 134.70 138.50 142.29 146.06 149.82 153.58 157.32 161.04 164.76 168.47 172.46 175.84 179.51 183.17 186.82 190.45 194.08 120 NI 86.17 92.76 99.41 106.15 113.00 120.00 127.17 134.52 142.06 149.79 157.74 165.90 174.25 182.84 191.64 200.64 209.85 219.29 228.96 238.85 248.95 259.30 269.91 280.77 291.96 303.46 315.31 327.54 340.14 353.14 366.53 100 NI 71.81 77.30 82.84 88.45 94.17 100.00 105.97 112.10 118.38 124.82 131.45 138.25 145.20 152.37 159.70 167.20 174.87 182.75 190.80 199.04 207.45 216.08 224.92 233.97 243.30 252.88 262.76 272.94 283.45 294.28 305.44 10 CU 7.10 7.49 7.88 8.26 8.65 9.04 9.42 9.81 10.19 10.58 10.97 11.35 11.74 12.12 12.51 12.90 13.28 13.67 14.06 14.44 14.83 15.22 15.61 16.00 16.39 16.78 17.17 17.56 17.95 18.34 18.73

GE Multilin

C30 Controller System

5-123

5.8 TRANSDUCER INPUTS AND OUTPUTS

5 SETTINGS 5.8.3 DCMA OUTPUTS

PATH: SETTINGS

TRANSDUCER I/O

DCMA OUTPUTS

DCMA OUTPUT F1(W8) Range: Off, any analog actual value parameter

DCMA OUTPUT F1

DCMA OUTPUT F1 SOURCE: Off


MESSAGE

DCMA OUTPUT F1 RANGE: 1 to 1 mA DCMA OUTPUT F1 MIN VAL: 0.000 pu DCMA OUTPUT F1 MAX VAL: 1.000 pu

Range: 1 to 1 mA, 0 to 1 mA, 4 to 20 mA

Range: 90.000 to 90.000 pu in steps of 0.001

MESSAGE

Range: 90.000 to 90.000 pu in steps of 0.001

MESSAGE

Hardware and software is provided to generate dcmA signals that allow interfacing with external equipment. Specific hardware details are contained in chapter 3. The dcmA output channels are arranged in a manner similar to transducer input or CT and VT channels. The user configures individual channels with the settings shown below. The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the relay automatically generates configuration settings for every channel, based on the order code, in the same manner used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as the channel number. Both the output range and a signal driving a given output are user-programmable via the following settings menu (an example for channel M5 is shown).

The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently rescales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The following equation is applied: I min if x < MIN VAL = I max if x > MAX VAL k ( x MIN VAL ) + I min otherwise

I out

(EQ 5.4)

where:

x is a driving signal specified by the SOURCE setting Imin and Imax are defined by the RANGE setting k is a scaling constant calculated as: I max I min k = -----------------------------------------------MAX VAL MIN VAL
(EQ 5.5)

VAL

The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, e.g. when MAX VAL MIN < 0.1 pu. The resulting characteristic is illustrated in the following figure.

Imax
OUTPUT CURRENT

Imin
DRIVING SIGNAL MIN VAL MAX VAL
842739A1.CDR

Figure 550: DCMA OUTPUT CHARACTERISTIC

5-124

C30 Controller System

GE Multilin

5 SETTINGS The dcmA output settings are described below.

5.8 TRANSDUCER INPUTS AND OUTPUTS

DCMA OUTPUT F1 SOURCE: This setting specifies an internal analog value to drive the analog output. Actual values (FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as sources driving dcmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters. DCMA OUTPUT F1 RANGE: This setting allows selection of the output range. Each dcmA channel may be set independently to work with different ranges. The three most commonly used output ranges are available. DCMA OUTPUT F1 MIN VAL: This setting allows setting the minimum limit for the signal that drives the output. This setting is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit values. The base units are defined in the same manner as the FlexElement base units. DCMA OUTPUT F1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This setting is used to control the mapping between an internal analog value and the output current. The setting is entered in per-unit values. The base units are defined in the same manner as the FlexElement base units. The DCMA OUTPUT F1 MIN VAL and DCMA OUTPUT F1 MAX VAL settings are ignored for power factor base units (i.e. if the DCMA OUTPUT F1 SOURCE is set to FlexAnalog value based on power factor measurement).
NOTE

GE Multilin

C30 Controller System

5-125

5.9 TESTING 5.9TESTING


PATH: SETTINGS TESTING TEST MODE

5 SETTINGS 5.9.1 TEST MODE

SETTINGS TESTING
MESSAGE

TEST MODE FUNCTION: Disabled TEST MODE FORCING: On

Range: Disabled, Isolated, Forcible

Range: FlexLogic operand

The C30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay faceplate by a Test Mode LED indicator. The test mode may be in any of three states: disabled, isolated, or forcible. In the Disabled mode, C30 operation is normal and all test features are disabled. In the Isolated mode, the C30 is prevented from performing certain control actions, including tripping via contact outputs. All relay contact outputs, including latching outputs, are disabled. Channel tests and phasor measurement unit tests remain usable on applicable UR-series models. In the Forcible mode, the operand selected by the TEST MODE FORCING setting controls the relay inputs and outputs. If the test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is Off, the C30 inputs and outputs operate normally. If the test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is On, the C30 contact inputs and outputs are forced to the values specified in the following sections. Forcing may be controlled by manually changing the operand selected by the TEST MODE FORCING setting between on and off, or by selecting a user-programmable pushbutton, contact input, or communication-based input operand. Channel tests and phasor measurement unit tests remain usable on applicable UR-series models. Communications based inputs and outputs remain fully operational in test mode. If a control action is programmed using direct inputs and outputs or remote inputs and outputs, then the test procedure must take this into account.
NOTE

When in Forcible mode, the operand selected by the TEST MODE FORCING setting dictates further response of the C30 to testing conditions. To force contact inputs and outputs through relay settings, set TEST MODE FORCING to On. To force contact inputs and outputs through a user-programmable condition, such as FlexLogic operand (pushbutton, digital input, communication-based input, or a combination of these), set TEST MODE FORCING to the desired operand. The contact input or output is forced when the selected operand assumes a logic 1 state. The C30 remains fully operational in test mode, allowing for various testing procedures. In particular, the protection and control elements, FlexLogic, and communication-based inputs and outputs function normally. The only difference between the normal operation and the test mode is the behavior of the input and output contacts. The contact inputs can be forced to report as open or closed or remain fully operational, whereas the contact outputs can be forced to open, close, freeze, or remain fully operational. The response of the digital input and output contacts to the test mode is programmed individually for each input and output using the force contact inputs and force contact outputs test functions described in the following sections. The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED indicator, and by the critical fail relay, as shown in the following table.

5-126

C30 Controller System

GE Multilin

5 SETTINGS

5.9 TESTING

Table 514: TEST MODE OPERATION


TEST MODE FUNCTION Disabled TEST MODE FORCING OPERAND No effect IN-SERVICE LED Unaffected TEST MODE LED Off CRITICAL FAIL RELAY Unaffected INPUT AND OUTPUT BEHAVIOR

Contact outputs and inputs are under normal operation. Channel tests and PMU tests not operational (where applicable). Contact outputs are disabled and contact inputs are operational. Channel tests and PMU tests are also operational (where applicable). Contact inputs and outputs are controlled by the force contact input and force contact output functions. Channel tests and PMU tests are operational (where applicable). Contact outputs and inputs are under normal operation. Channel tests and PMU tests are also operational (where applicable).

Isolated

No effect

Off

On

Deenergized Deenergized

Forcible

On (logic 1)

Off

Flashing

Off (logic 0)

Off

Flashing

Deenergized

The TEST MODE FUNCTION setting can only be changed by a direct user command. Following a restart, power up, settings upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a C30 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states. 5.9.2 FORCE CONTACT INPUTS
PATH: SETTINGS TESTING FORCE CONTACT INPUTS

FORCE CONTACT INPUTS


MESSAGE

FORCE Cont Ip 1 :Disabled FORCE Cont Ip 2 :Disabled

MESSAGE

Range: Disabled, Open, Closed

Range: Disabled, Open, Closed

FORCE Cont Ip xx :Disabled

Range: Disabled, Open, Closed

The relay digital inputs (contact inputs) could be pre-programmed to respond to the test mode in the following ways: If set to Disabled, the input remains fully operational. It is controlled by the voltage across its input terminals and can be turned on and off by external circuitry. This value should be selected if a given input must be operational during the test. This includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence. If set to Open, the input is forced to report as opened (Logic 0) for the entire duration of the test mode regardless of the voltage across the input terminals. If set to Closed, the input is forced to report as closed (Logic 1) for the entire duration of the test mode regardless of the voltage across the input terminals.

The force contact inputs feature provides a method of performing checks on the function of all contact inputs. Once enabled, the relay is placed into test mode, allowing this feature to override the normal function of contact inputs. The Test Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as Disabled, Open, or Closed. All contact input operations return to normal when all settings for this feature are disabled.

GE Multilin

C30 Controller System

5-127

5.9 TESTING

5 SETTINGS 5.9.3 FORCE CONTACT OUTPUTS

PATH: SETTINGS

TESTING

FORCE CONTACT OUTPUTS

FORCE CONTACT OUTPUTS


MESSAGE

FORCE Cont Op 1 :Disabled FORCE Cont Op 2 :Disabled

MESSAGE

Range: Disabled, Energized, De-energized, Freeze

Range: Disabled, Energized, De-energized, Freeze

FORCE Cont Op xx :Disabled

Range: Disabled, Energized, De-energized, Freeze

The relay contact outputs can be pre-programmed to respond to the test mode. If set to Disabled, the contact output remains fully operational. If operates when its control operand is logic 1 and will resets when its control operand is logic 0. If set to Energized, the output will close and remain closed for the entire duration of the test mode, regardless of the status of the operand configured to control the output contact. If set to De-energized, the output will open and remain opened for the entire duration of the test mode regardless of the status of the operand configured to control the output contact. If set to Freeze, the output retains its position from before entering the test mode, regardless of the status of the operand configured to control the output contact. These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Second, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided. Example 1: Initiating test mode through user-programmable pushbutton 1

For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as Latched (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1 should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational. The required settings are shown below. To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the SETTINGS TESTING TEST MODE menu: TEST MODE FUNCTION: Enabled and TEST MODE INITIATE: PUSHBUTTON 1 ON Make the following changes to configure the contact inputs and outputs. In the SETTINGS INPUTS and FORCE CONTACT OUTPUTS menus, set:
TESTING FORCE CONTACT

FORCE Cont Ip 1: Disabled, FORCE Cont Ip 2: Open, FORCE Cont Ip 3: Open, and FORCE Cont Ip 4: FORCE Cont Op 1: Freeze, FORCE Cont Op 2: De-energized, FORCE Cont Op 3: Energized, and FORCE Cont Op 4: Disabled

Closed

Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1 In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1. Both the pushbutton and the remote input will be programmed as Latched. Write the following FlexLogic equation:

PUSHBUTTONS

Set the user-programmable pushbutton as latching by changing SETTINGS PRODUCT SETUP USER-PROGRAMMABLE USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION to Latched. To enable either pushbutton 1 or remote input 1 to initiate the Test mode, make the following changes in the SETTINGS TESTING TEST MODE menu:
TEST MODE FUNCTION:

Enabled and TEST MODE INITIATE: VO1

5-128

C30 Controller System

GE Multilin

6 ACTUAL VALUES 6 ACTUAL VALUES 6.1OVERVIEW

6.1 OVERVIEW 6.1.1 ACTUAL VALUES MAIN MENU

ACTUAL VALUES STATUS

CONTACT INPUTS VIRTUAL INPUTS REMOTE INPUTS REMOTE DPS INPUTS TELEPROTECTION INPUTS CONTACT OUTPUTS VIRTUAL OUTPUTS REMOTE DEVICES STATUS REMOTE DEVICES STATISTICS SELECTOR SWITCHES DIGITAL COUNTERS FLEX STATES ETHERNET DIRECT INPUTS DIRECT DEVICES STATUS IEC 61850 GOOSE UINTEGERS EGD PROTOCOL STATUS TELEPROT CH TESTS ETHERNET SWITCH

See page 6-3. See page 6-3. See page 6-3. See page 6-4. See page 6-4. See page 6-4. See page 6-5. See page 6-5. See page 6-5. See page 6-6. See page 6-6. See page 6-6. See page 6-6. See page 6-7. See page 6-7. See page 6-8. See page 6-8. See page 6-9. See page 6-9.

ACTUAL VALUES METERING

FLEXELEMENTS IEC 61850 GOOSE ANALOGS

See page 6-10. See page 6-10.

GE Multilin

C30 Controller System

6-1

6.1 OVERVIEW

6 ACTUAL VALUES

TRANSDUCER I/O DCMA INPUTS TRANSDUCER I/O RTD INPUTS ACTUAL VALUES RECORDS EVENT RECORDS OSCILLOGRAPHY DATA LOGGER

See page 6-10. See page 6-10.

See page 6-12. See page 6-12. See page 6-13.

ACTUAL VALUES PRODUCT INFO

MODEL INFORMATION FIRMWARE REVISIONS

See page 6-14. See page 6-14.

6-2

C30 Controller System

GE Multilin

6 ACTUAL VALUES 6.2STATUS


PATH: ACTUAL VALUES STATUS CONTACT INPUTS

6.2 STATUS 6.2.1 CONTACT INPUTS

CONTACT INPUTS

Cont Ip 1 Off
MESSAGE

Range: On, Off

Cont Ip 2 Off

Range: On, Off

MESSAGE

Cont Ip xx Off

Range: On, Off

The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact input. For example, Cont Ip 1 refers to the contact input in terms of the default name-array index. The second line of the display indicates the logic state of the contact input. 6.2.2 VIRTUAL INPUTS
PATH: ACTUAL VALUES STATUS VIRTUAL INPUTS

VIRTUAL INPUTS

Virt Ip 1 Off
MESSAGE

Range: On, Off

Virt Ip 2 Off

Range: On, Off

MESSAGE

Virt Ip 64 Off

Range: On, Off

The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual input. For example, Virt Ip 1 refers to the virtual input in terms of the default name. The second line of the display indicates the logic state of the virtual input. 6.2.3 REMOTE INPUTS
PATH: ACTUAL VALUES STATUS REMOTE INPUTS

REMOTE INPUTS

REMOTE INPUT STATUS: Off


MESSAGE

1 2

Range: On, Off

REMOTE INPUT STATUS: Off

Range: On, Off

MESSAGE

REMOTE INPUT 32 STATUS: Off

Range: On, Off

The present state of the 32 remote inputs is shown here. The state displayed will be that of the remote point unless the remote device has been established to be Offline in which case the value shown is the programmed default state for the remote input.

GE Multilin

C30 Controller System

6-3

6.2 STATUS

6 ACTUAL VALUES 6.2.4 REMOTE DOUBLE-POINT STATUS INPUTS

PATH: ACTUAL VALUES

STATUS

REMOTE DPS INPUTS

REMOTE DPS INPUTS

REMOTE DPS INPUT STATUS: Bad REMOTE DPS INPUT STATUS: Bad

1 2

Range: On, Off, Intermediate, Bad

Range: On, Off, Intermediate, Bad

MESSAGE

MESSAGE

REMOTE DPS INPUT STATUS: Bad

Range: On, Off, Intermediate, Bad

The present state of the remote double-point status inputs is shown here. The actual values indicate if the remote doublepoint status inputs are in the on (close), off (open), intermediate, or bad state. 6.2.5 TELEPROTECTION INPUTS
PATH: ACTUAL VALUES STATUS TELEPROTECTION INPUTS

TELEPROTECTION INPUTS
MESSAGE

TELEPROTECTION INPUT 1-1: Off TELEPROTECTION INPUT 1-2: Off

MESSAGE

Range: Off, On

Range: Off, On

TELEPROTECTION INPUT 1-16: Off TELEPROTECTION INPUT 2-1: Off TELEPROTECTION INPUT 2-2: Off

Range: Off, On

Range: Off, On

MESSAGE

6
MESSAGE MESSAGE

Range: Off, On

TELEPROTECTION INPUT 2-16: Off

Range: Off, On

The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed will be that of corresponding remote output unless the channel is declared failed. 6.2.6 CONTACT OUTPUTS
PATH: ACTUAL VALUES STATUS CONTACT OUTPUTS

CONTACT OUTPUTS

Cont Op 1 Off Cont Op 2 Off

Range: On, Off, VOff, VOn, IOn, IOff

Range: On, Off, VOff, VOn, IOn, IOff

MESSAGE

MESSAGE

Cont Op xx Off

Range: On, Off, VOff, VOn, IOn, IOff

The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, Cont Op 1 refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output.

6-4

C30 Controller System

GE Multilin

6 ACTUAL VALUES

6.2 STATUS

For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE

6.2.7 VIRTUAL OUTPUTS


PATH: ACTUAL VALUES STATUS VIRTUAL OUTPUTS

VIRTUAL OUTPUTS

Virt Op Off Virt Op Off

1 2

Range: On, Off

Range: On, Off

MESSAGE

MESSAGE

Virt Op 96 Off

Range: On, Off

The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual output. For example, Virt Op 1 refers to the virtual output in terms of the default name-array index. The second line of the display indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output. 6.2.8 REMOTE DEVICES a) STATUS
PATH: ACTUAL VALUES STATUS REMOTE DEVICES STATUS

REMOTE DEVICES STATUS


MESSAGE

All REMOTE DEVICES ONLINE: No REMOTE DEVICE 1 STATUS: Offline REMOTE DEVICE 2 STATUS: Offline

MESSAGE

Range: Yes, No

Range: Online, Offline

Range: Online, Offline

MESSAGE

REMOTE DEVICE 16 STATUS: Offline

Range: Online, Offline

The present state of up to 16 programmed remote devices is shown here. The ALL REMOTE DEVICES ONLINE message indicates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required remote device is not online. b) STATISTICS
PATH: ACTUAL VALUES STATUS REMOTE DEVICES STATISTICS REMOTE DEVICE 1(16)

REMOTE DEVICE

REMOTE DEVICE StNum: REMOTE DEVICE SqNum:

1 0 1 0

MESSAGE

Statistical data (two types) for up to 16 programmed remote devices is shown here. The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of at least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.

GE Multilin

C30 Controller System

6-5

6.2 STATUS

6 ACTUAL VALUES 6.2.9 SELECTOR SWITCHES

PATH: ACTUAL VALUES

STATUS

SELECTOR SWITCHES

SELECTOR SWITCHES

SELECTOR SWITCH 1 POSITION: 0/7 SELECTOR SWITCH 2 POSITION: 0/7

Range: Current Position / 7

Range: Current Position / 7

MESSAGE

The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the actual value. 6.2.10 DIGITAL COUNTERS
PATH: ACTUAL VALUES STATUS DIGITAL COUNTERS DIGITAL COUNTERS Counter 1(8)

DIGITAL COUNTERS Counter 1


MESSAGE

Counter 1 0 Counter 1 0

ACCUM: FROZEN:

MESSAGE

Counter 1 FROZEN: YYYY/MM/DD HH:MM:SS Counter 1 0 MICROS:

MESSAGE

The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and time stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.

6
PATH: ACTUAL VALUES STATUS FLEX STATES

6.2.11 FLEX STATES

FLEX STATES

PARAM Off
MESSAGE

1: Off 2: Off

Range: Off, On

PARAM Off

Range: Off, On

MESSAGE

PARAM 256: Off Off

Range: Off, On

There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit. 6.2.12 ETHERNET
PATH: ACTUAL VALUES STATUS ETHERNET

ETHERNET

ETHERNET PRI LINK STATUS: OK


MESSAGE

Range: Fail, OK

ETHERNET SEC LINK STATUS: OK

Range: Fail, OK

These values indicate the status of the primary and secondary Ethernet links.

6-6

C30 Controller System

GE Multilin

6 ACTUAL VALUES

6.2 STATUS 6.2.13 DIRECT INPUTS

PATH: ACTUAL VALUES

STATUS

DIRECT INPUTS

DIRECT INPUTS

AVG MSG RETURN TIME CH1: 0 ms


MESSAGE

UNRETURNED MSG COUNT CH1: 0 CRC FAIL COUNT CH1: 0 AVG MSG RETURN TIME CH2: 0 ms UNRETURNED MSG COUNT CH2: 0 CRC FAIL COUNT CH2: 0 DIRECT INPUT On DIRECT INPUT On

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

1: 2:

MESSAGE

MESSAGE

DIRECT INPUT 32: On

The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last ten messages. There are two return times for dual-channel communications modules. The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command. The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input. 6.2.14 DIRECT DEVICES STATUS
PATH: ACTUAL VALUES STATUS DIRECT DEVICES STATUS

DIRECT DEVICES STATUS


MESSAGE

DIRECT DEVICE 1 STATUS: Offline DIRECT DEVICE 2 STATUS: Offline

MESSAGE

Range: Offline, Online

Range: Offline, Online

DIRECT DEVICE 16 STATUS: Offline

Range: Offline, Online

These actual values represent the state of direct devices 1 through 16.

GE Multilin

C30 Controller System

6-7

6.2 STATUS

6 ACTUAL VALUES 6.2.15 IEC 61850 GOOSE INTEGERS

PATH: ACTUAL VALUES

STATUS

IEC 61850 GOOSE UINTEGERS

IEC 61850 GOOSE UINTEGERS


MESSAGE

UINT INPUT 0 UINT INPUT 0

1 2

MESSAGE

UINT INPUT 16 0

The C30 Controller System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.

The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received via IEC 61850 GOOSE messages sent from other devices. 6.2.16 EGD PROTOCOL STATUS a) FAST EXCHANGE
PATH: ACTUAL VALUES STATUS EGD PROTOCOL STATUS PRODUCER STATUS FAST EXCHANGE 1

FAST EXCHANGE 1

FAST EXCHANGE 1 SIGNATURE: 0 FAST EXCHANGE 1 DATA LENGTH: 0

MESSAGE

These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size for the fast EGD exchange is displayed. b) SLOW EXCHANGE
PATH: ACTUAL VALUES STATUS EGD PROTOCOL STATUS PRODUCER STATUS SLOW EXCHANGE 1(2)

SLOW EXCHANGE 1

SLOW EXCHANGE 1 SIGNATURE: 0 SLOW EXCHANGE 1 DATA LENGTH: 0

MESSAGE

These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size for the slow EGD exchanges are displayed.

6-8

C30 Controller System

GE Multilin

6 ACTUAL VALUES

6.2 STATUS 6.2.17 TELEPROTECTION CHANNEL TESTS

PATH: ACTUAL VALUES

STATUS

TELEPROT CH TESTS

TELEPROT CH TESTS

CHANNEL 1 STATUS: n/a CHANNEL 1 LOST PACKETS: 1 CHANNEL 2 STATUS: n/a CHANNEL 2 LOST PACKETS: 1 VALIDITY OF CHANNEL CONFIGURATION: FAIL

Range: n/a, FAIL, OK

Range: 1 to 65535 in steps of 1

MESSAGE

Range: n/a, FAIL, OK

MESSAGE

Range: 1 to 65535 in steps of 1

MESSAGE

Range: n/a, FAIL, OK

MESSAGE

The status information for two channels is shown here. CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is OK, teleprotection is enabled and data is being received from the remote terminal; If the value is FAIL, teleprotection enabled and data is not being received from the remote terminal. If n/a, teleprotection is disabled. CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the COMMANDS CLEAR RECORDS menu. VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the FAIL message will be displayed. The N/A value appears if the local relay ID is set to a default value of 0, the channel is failed, or if the teleprotection inputs/outputs are not enabled. 6.2.18 ETHERNET SWITCH
PATH: ACTUAL VALUES STATUS ETHERNET SWITCH

ETHERNET SWITCH

SWITCH 1 PORT STATUS: OK SWITCH 2 PORT STATUS: OK

Range: FAIL, OK

Range: FAIL, OK

MESSAGE

MESSAGE

SWITCH 6 PORT STATUS: OK SWITCH MAC ADDRESS: 00A0F40138FA

Range: FAIL, OK

Range: standard MAC address format

MESSAGE

These actual values appear only if the C30 is ordered with an Ethernet switch module (type 2S or 2T). The status information for the Ethernet switch is shown in this menu. SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on the Ethernet switch. If the value is OK, then data is being received from the remote terminal; If the value is FAIL, then data is not being received from the remote terminal or the port is not connected. SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module.

GE Multilin

C30 Controller System

6-9

6.3 METERING 6.3METERING


PATH: ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(8)

6 ACTUAL VALUES 6.3.1 FLEXELEMENTS

FLEXELEMENT 1

FLEXELEMENT 1 OpSig: 0.000 pu

The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units. Table 61: FLEXELEMENT BASE UNITS
dcmA FREQUENCY PHASE ANGLE POWER FACTOR RTDs SOURCE CURRENT SOURCE POWER SOURCE VOLTAGE BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured under the +IN and IN inputs. fBASE = 1 Hz BASE = 360 degrees (see the UR angle referencing convention) PFBASE = 1.00 BASE = 100C IBASE = maximum nominal primary RMS value of the +IN and IN inputs PBASE = maximum value of VBASE IBASE for the +IN and IN inputs VBASE = maximum nominal primary RMS value of the +IN and IN inputs

6.3.2 IEC 61580 GOOSE ANALOG VALUES


PATH: ACTUAL VALUES METERING IEC 61850 GOOSE ANALOGS

IEC 61850 GOOSE ANALOGS


MESSAGE

ANALOG INPUT 0.000 ANALOG INPUT 0.000

MESSAGE

1 2

ANALOG INPUT 16 0.000

The C30 Controller System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.

The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received via IEC 61850 GOOSE messages sent from other devices. 6.3.3 TRANSDUCER INPUTS/OUTPUTS
PATH: ACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xx

DCMA INPUT xx

DCMA INPUT xx 0.000 mA

Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value followed by the programmed units.
PATH: ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xx

RTD INPUT xx

RTD INPUT xx -50 C

6-10

C30 Controller System

GE Multilin

6 ACTUAL VALUES

6.3 METERING

Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and the bottom line as the value.

GE Multilin

C30 Controller System

6-11

6.4 RECORDS 6.4RECORDS


PATH: ACTUAL VALUES RECORDS EVENT RECORDS

6 ACTUAL VALUES 6.4.1 EVENT RECORDS

EVENT RECORDS

EVENT: XXXX RESET OP(PUSHBUTTON)

MESSAGE

EVENT: 3 POWER ON EVENT: 2 POWER OFF EVENT: 1 EVENTS CLEARED

EVENT 3 DATE: 2000/07/14 EVENT 3 TIME: 14:53:00.03405 Date and Time Stamps

MESSAGE

MESSAGE

The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the event trigger. Refer to the COMMANDS CLEAR RECORDS menu for clearing event records. 6.4.2 OSCILLOGRAPHY
PATH: ACTUAL VALUES RECORDS OSCILLOGRAPHY

OSCILLOGRAPHY

FORCE TRIGGER? No
MESSAGE

Range: No, Yes

NUMBER OF TRIGGERS: 0 AVAILABLE RECORDS: 0 CYCLES PER RECORD: 0.0 LAST CLEARED DATE: 2000/07/14 15:40:16

MESSAGE

MESSAGE

MESSAGE

This menu allows the user to view the number of triggers involved and number of oscillography traces available. The CYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillography section of chapter 5 for additional details.
CLEAR RECORDS

A trigger can be forced here at any time by setting Yes to the FORCE TRIGGER? command. Refer to the COMMANDS menu for information on clearing the oscillography records.

6-12

C30 Controller System

GE Multilin

6 ACTUAL VALUES

6.4 RECORDS 6.4.3 DATA LOGGER

PATH: ACTUAL VALUES

RECORDS

DATA LOGGER

DATA LOGGER

OLDEST SAMPLE TIME: 2000/01/14 13:45:51


MESSAGE

NEWEST SAMPLE TIME: 2000/01/14 15:21:19

The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken. It will be static until the log gets full, at which time it will start counting at the defined sampling rate. The NEWEST SAMPLE TIME represents the time the most recent samples were taken. It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the COMMANDS
CLEAR RECORDS

menu for clearing data logger records.

GE Multilin

C30 Controller System

6-13

6.5 PRODUCT INFORMATION 6.5PRODUCT INFORMATION


PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION

6 ACTUAL VALUES 6.5.1 MODEL INFORMATION

MODEL INFORMATION

ORDER CODE LINE 1: C30-E00-HCH-F6A-H6A ORDER CODE LINE 2: ORDER CODE LINE 3: ORDER CODE LINE 4: SERIAL NUMBER: ETHERNET MAC ADDRESS 000000000000 MANUFACTURING DATE: 0 CT/ VT ADVANCED DIAG ACTIVE: No OPERATING TIME: 0:00:00 LAST SETTING CHANGE: 1970/01/01 23:11:19

Range: standard GE multilin order code format; example order code shown Range: standard GE multilin order code format

MESSAGE

Range: standard GE multilin order code format

MESSAGE

Range: standard GE multilin order code format

MESSAGE

Range: standard GE multilin serial number format

MESSAGE

Range: standard Ethernet MAC address format

MESSAGE

Range: YYYY/MM/DD HH:MM:SS

MESSAGE

Range: Yes, No

MESSAGE

Range: opearting time in HH:MM:SS

MESSAGE

Range: YYYY/MM/DD HH:MM:SS

MESSAGE

The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.

6
PATH: ACTUAL VALUES PRODUCT INFO FIRMWARE REVISIONS

6.5.2 FIRMWARE REVISIONS

FIRMWARE REVISIONS

C30 Controller REVISION: 5.8x MODIFICATION FILE NUMBER: 0 BOOT PROGRAM REVISION: 3.01 FRONT PANEL PROGRAM REVISION: 0.08 COMPILE DATE: 2004/09/15 04:55:16 BOOT DATE: 2004/09/15 16:41:32

Range: 0.00 to 655.35 Revision number of the application firmware. Range: 0 to 65535 (ID of the MOD FILE) Value is 0 for each standard firmware release. Range: 0.00 to 655.35 Revision number of the boot program firmware. Range: 0.00 to 655.35 Revision number of faceplate program firmware. Range: Any valid date and time. Date and time when product firmware was built. Range: Any valid date and time. Date and time when the boot program was built.

MESSAGE

MESSAGE

MESSAGE

MESSAGE

MESSAGE

The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed.

6-14

C30 Controller System

GE Multilin

7 COMMANDS AND TARGETS 7 COMMANDS AND TARGETS 7.1COMMANDS

7.1 COMMANDS 7.1.1 COMMANDS MENU

COMMANDS

MESSAGE

COMMANDS VIRTUAL INPUTS COMMANDS CLEAR RECORDS COMMANDS SET DATE AND TIME COMMANDS RELAY MAINTENANCE

MESSAGE

MESSAGE

MESSAGE

The commands menu contains relay directives intended for operations personnel. All commands can be protected from unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash message appears after successfully command entry: COMMAND EXECUTED 7.1.2 VIRTUAL INPUTS
PATH: COMMANDS VIRTUAL INPUTS

COMMANDS VIRTUAL INPUTS

Virt Ip Off Virt Ip Off

1 2

Range: Off, On

Range: Off, On

MESSAGE

Virt Ip 64 Off

Range: Off, On

The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1).

GE Multilin

C30 Controller System

7-1

7.1 COMMANDS

7 COMMANDS AND TARGETS 7.1.3 CLEAR RECORDS

PATH: COMMANDS

CLEAR RECORDS

COMMANDS CLEAR RECORDS

CLEAR EVENT RECORDS? No CLEAR OSCILLOGRAPHY? No CLEAR DATA LOGGER? No CLEAR UNAUTHORIZED ACCESS? No CLEAR DIRECT I/O COUNTERS? No CLEAR TELEPROTECT COUNTERS? No CLEAR ALL RELAY RECORDS? No

Range: No, Yes

Range: No, Yes

Range: No, Yes

Range: No, Yes

Range: No, Yes. Valid only for units with Direct Input/ Output module. Range: No, Yes

Range: No, Yes

This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a command setting to Yes and pressing the ENTER key. After clearing data, the command setting automatically reverts to No. 7.1.4 SET DATE AND TIME
PATH: COMMANDS SET DATE AND TIME

COMMANDS SET DATE AND TIME

SET DATE AND TIME: 2000/01/14 13:47:03

(YYYY/MM/DD HH:MM:SS)

The date and time can be entered here via the faceplate keypad only if the IRIG-B or SNTP signal is not in use. The time setting is based on the 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this command. The new time will take effect at the moment the ENTER key is clicked.

7-2

C30 Controller System

GE Multilin

7 COMMANDS AND TARGETS

7.1 COMMANDS 7.1.5 RELAY MAINTENANCE

PATH: COMMANDS

RELAY MAINTENANCE

COMMANDS RELAY MAINTENANCE

PERFORM LAMPTEST? No UPDATE ORDER CODE? No SERVICE COMMAND: 0

Range: No, Yes

Range: No, Yes

Range: 0, 101

This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated by changing a command setting to Yes and pressing the ENTER key. The command setting will then automatically revert to No. The service command is activated by entering a numerical code and pressing the ENTER key. The PERFORM LAMPTEST command turns on all faceplate LEDs and display pixels for a short duration. The UPDATE ORDER CODE command causes the relay to scan the backplane for the hardware modules and update the order code to match. If an update occurs, the following message is shown. UPDATING... PLEASE WAIT There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER CODE NOT UPDATED message will be shown. The SERVICE COMMAND is used to perform specific C30 service actions. Presently, there is only one service action available. Code 101 is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than 101 is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in the background while the C30 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the C30 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all selfchecking variables are reset to their initial state and diagnostics will restart from scratch.

GE Multilin

C30 Controller System

7-3

7.2 TARGETS 7.2TARGETS

7 COMMANDS AND TARGETS 7.2.1 TARGETS MENU

TARGETS

MESSAGE

DIGITAL ELEMENT LATCHED

1:

Displayed only if targets for this element are active. Example shown. Displayed only if targets for this element are active. Example shown.

MESSAGE

DIGITAL ELEMENT 48: LATCHED


MESSAGE

The status of any active targets will be displayed in the targets menu. If no targets are active, the display will read NO
ACTIVE TARGETS:

7.2.2 TARGET MESSAGES When there are no active targets, the first target to become active will cause the display to immediately default to that message. If there are active targets and the user is navigating through other messages, and when the default message timer times out (i.e. the keypad has not been used for a determined period of time), the display will again default back to the target message. The range of variables for the target messages is described below. Phase information will be included if applicable. If a target message status changes, the status with the highest priority will be displayed. Table 71: TARGET MESSAGE PRIORITY STATUS
PRIORITY 1 2 3 ACTIVE STATUS OP PKP LATCHED DESCRIPTION element operated and still picked up element picked up and timed out element had operated but has dropped out

If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED indicates that the minimal relay settings have not been programmed. 7.2.3 RELAY SELF-TESTS a) DESCRIPTION The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major and minor) are listed in the tables below. When either type of self-test error occurs, the Trouble LED Indicator will turn on and a target message displayed. All errors record an event in the event recorder. Latched errors can be cleared by pressing the RESET key, providing the condition is no longer present. Major self-test errors also result in the following: The critical fail relay on the power supply module is de-energized. All other output relays are de-energized and are prevented from further operation. The faceplate In Service LED indicator is turned off. A RELAY OUT OF SERVICE event is recorded.

7-4

C30 Controller System

GE Multilin

7 COMMANDS AND TARGETS b) MAJOR SELF-TEST ERROR MESSAGES The major self-test errors are listed and described below. MODULE FAILURE___: Contact Factory (xxx) Latched target message: Yes. Description of problem: Module hardware failure detected. How often the test is performed: Module dependent.

7.2 TARGETS

What to do: Contact the factory and supply the failure code noted in the display. The xxx text identifies the failed module (for example, F8L). INCOMPATIBLE H/W: Contact Factory (xxx)

Latched target message: Yes. Description of problem: One or more installed hardware modules is not compatible with the C30 order code. How often the test is performed: Module dependent. What to do: Contact the factory and supply the failure code noted in the display. The xxx text identifies the failed module (for example, F8L). EQUIPMENT MISMATCH: with 2nd line detail

Latched target message: No. Description of problem: The configuration of modules does not match the order code stored in the C30. How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five seconds. What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If the problem persists, contact the factory. FLEXLOGIC ERROR: with 2nd line detail

Latched target message: No. Description of problem: A FlexLogic equation is incorrect. How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified. What to do: Finish all equation editing and use self tests to debug any errors. UNIT NOT PROGRAMMED: Check Settings

Latched target message: No. Description of problem: The PRODUCT SETUP grammed.
INSTALLATION RELAY SETTINGS

setting indicates the C30 is not proINSTALLATION RELAY SETTINGS

How often the test is performed: On power up and whenever the PRODUCT SETUP setting is altered. What to do: Program all settings and then set PRODUCT SETUP
INSTALLATION

RELAY SETTINGS

to Programmed.

GE Multilin

C30 Controller System

7-5

7.2 TARGETS c) MINOR SELF-TEST ERROR MESSAGES

7 COMMANDS AND TARGETS

Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in chapter 5 for additional details. MAINTENANCE ALERT: Replace Battery Latched target message: Yes. Description of problem: The battery is not functioning. How often the test is performed: The battery is monitored every five seconds. The error message is displayed after 60 seconds if the problem persists. What to do: Replace the battery located in the power supply module (1H or 1L).

MAINTENANCE ALERT: Direct I/O Ring Break Latched target message: No. Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring. How often the test is performed: Every second. What to do: Check direct input and output configuration and wiring.

MAINTENANCE ALERT: ENET MODULE OFFLINE Latched target message: No. Description of problem: The C30 has failed to detect the Ethernet switch. How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures. What to do: Check the C30 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on the Ethernet switch. Check the power to the switch.

MAINTENANCE ALERT: ENET PORT # OFFLINE Latched target message: No. Description of problem: The Ethernet connection has failed for the specified port. How often the test is performed: Every five seconds. What to do: Check the Ethernet port connection on the switch.

MAINTENANCE ALERT: **Bad IRIG-B Signal** Latched target message: No. Description of problem: A bad IRIG-B input signal has been detected. How often the test is performed: Monitored whenever an IRIG-B signal is received. What to do: Ensure the following: The IRIG-B cable is properly connected. Proper cable functionality (that is, check for physical damage or perform a continuity test). The IRIG-B receiver is functioning. Check the input signal level (it may be less than specification).

7-6

C30 Controller System

GE Multilin

7 COMMANDS AND TARGETS If none of these apply, then contact the factory. MAINTENANCE ALERT: Port ## Failure Latched target message: No. Description of problem: An Ethernet connection has failed. How often the test is performed: Monitored every five seconds. What to do: Check Ethernet connections. Port 1 is the primary port and port 2 is the secondary port.

7.2 TARGETS

MAINTENANCE ALERT: SNTP Failure Latched target message: No. Description of problem: The SNTP server is not responding. How often the test is performed: Every 10 to 60 seconds. What to do: Check SNTP configuration and network connections.

MAINTENANCE ALERT: 4L Discrepancy Latched target message: No. Description of problem: A discrepancy has been detected between the actual and desired state of a latching contact output of an installed type 4L module. How often the test is performed: Upon initiation of a contact output state change. What to do: Verify the state of the output contact and contact the factory if the problem persists.

MAINTENANCE ALERT: GGIO Ind xxx oscill Latched target message: No. Description of problem: A data item in a configurable GOOSE data set is oscillating. How often the test is performed: Upon scanning of each configurable GOOSE data set. What to do: The xxx text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to this item.

DIRECT I/O FAILURE: COMM Path Incomplete Latched target message: No. Description of problem: A direct device is configured but not connected. How often the test is performed: Every second. What to do: Check direct input and output configuration and wiring.

REMOTE DEVICE FAIL: COMM Path Incomplete Latched target message: No. Description of problem: One or more GOOSE devices are not responding.

GE Multilin

C30 Controller System

7-7

7.2 TARGETS

7 COMMANDS AND TARGETS

How often the test is performed: Event driven. The test is performed when a device programmed to receive GOOSE messages stops receiving. This can be from 1 to 60 seconds, depending on GOOSE packets. What to do: Check GOOSE setup.

TEMP MONITOR: OVER TEMPERATURE Latched target message: Yes. Description of problem: The ambient temperature is greater than the maximum operating temperature (+80C). How often the test is performed: Every hour. What to do: Remove the C30 from service and install in a location that meets operating temperature standards.

UNEXPECTED RESTART: Press RESET key Latched target message: Yes. Description of problem: Abnormal restart from modules being removed or inserted while the C30 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. How often the test is performed: Event driven. What to do: Contact the factory.

7-8

C30 Controller System

GE Multilin

8 SECURITY 8 SECURITY 8.1PASSWORD SECURITY

8.1 PASSWORD SECURITY 8.1.1 OVERVIEW

Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level is not available and intended for factory use only. The following operations are under command password supervision: Changing the state of virtual inputs. Clearing the event records. Clearing the oscillography records. Changing the date and time. Clearing the data logger. Clearing the user-programmable pushbutton states.

The following operations are under setting password supervision: Changing any setting. Test mode operation.

The command and setting passwords are defaulted to 0 when the relay is shipped from the factory. When a password is set to 0, the password security feature is disabled. The C30 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords enables this functionality. When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used. The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder. The local setting and command sessions are initiated by the user through the front panel display and are disabled either by the user or by timeout (via the setting and command level access timeout settings). The remote setting and command sessions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout. The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands. ACCESS LOC SETG OFF: Asserted when local setting access is disabled. ACCESS LOC SETG ON: Asserted when local setting access is enabled. ACCESS LOC CMND OFF: Asserted when local command access is disabled. ACCESS LOC CMND ON: Asserted when local command access is enabled. ACCESS REM SETG OFF: Asserted when remote setting access is disabled. ACCESS REM SETG ON: Asserted when remote setting access is enabled. ACCESS REM CMND OFF: Asserted when remote command access is disabled. ACCESS REM CMND ON: Asserted when remote command access is enabled.

The appropriate events are also logged in the Event Recorder as well. The FlexLogic operands and events are updated every five seconds. A command or setting write operation is required to update the state of all the remote and local security operands shown above.
NOTE

GE Multilin

C30 Controller System

8-1

8.1 PASSWORD SECURITY

8 SECURITY 8.1.2 PASSWORD SECURITY MENU

PATH: SETTINGS

PRODUCT SETUP

SECURITY

SECURITY

ACCESS LEVEL: Restricted


MESSAGE

Range: Restricted, Command, Setting, Factory Service (for factory use only)

CHANGE LOCAL PASSWORDS ACCESS SUPERVISION DUAL PERMISSION SECURITY ACCESS PASSWORD ACCESS EVENTS: Disabled

See page 82. See page 83. See page 84.


Range: Disabled, Enabled

MESSAGE

MESSAGE

MESSAGE

8.1.3 LOCAL PASSWORDS


PATH: SETTINGS PRODUCT SETUP SECURITY CHANGE LOCAL PASSWORDS Range: No, Yes

CHANGE LOCAL PASSWORDS


MESSAGE

CHANGE COMMAND PASSWORD: No CHANGE SETTING PASSWORD: No ENCRYPTED COMMAND PASSWORD: ---------ENCRYPTED SETTING PASSWORD: ----------

Range: No, Yes

MESSAGE

Range: 0 to 9999999999 Note: ---------- indicates no password Range: 0 to 9999999999 Note: ---------- indicates no password

MESSAGE

Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters. When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to Yes via the front panel interface, the following message sequence is invoked: 1. 2. 3. ENTER NEW PASSWORD: ____________. VERIFY NEW PASSWORD: ____________. NEW PASSWORD HAS BEEN STORED.

To gain write access to a Restricted setting, program the ACCESS LEVEL setting in the main security menu to Setting and then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the password is correctly entered, access will be allowed. Accessibility automatically reverts to the Restricted level according to the access level timeout setting values. If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD. If the setting and command passwords are identical, then this one password allows access to both commands and settings.
NOTE

8-2

C30 Controller System

GE Multilin

8 SECURITY

8.1 PASSWORD SECURITY 8.1.4 REMOTE PASSWORDS

The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the Settings > Product Setup > Password Security menu item to open the remote password settings window.

Figure 81: REMOTE PASSWORD SETTINGS WINDOW Proper passwords are required to enable each command or setting level access. A command or setting password consists of 1 to 10 numerical characters and are initially programmed to 0. The following procedure describes how the set the command or setting password. 1. 2. 3. 4. Enter the new password in the Enter New Password field. Re-enter the password in the Confirm New Password field. Click the Change button. This button will not be active until the new password matches the confirmation password. If the original password is not 0, then enter the original password in the Enter Password field and click the Send Password to Device button.

5.

The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.

If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password value. 8.1.5 ACCESS SUPERVISION
PATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION

ACCESS SUPERVISION
MESSAGE

ACCESS LEVEL TIMEOUTS INVALID ATTEMPTS BEFORE LOCKOUT: 3 PASSWORD LOCKOUT DURATION: 5 min
Range: 2 to 5 in steps of 1

Range: 5 to 60 minutes in steps of 1

MESSAGE

GE Multilin

C30 Controller System

8-3

8.1 PASSWORD SECURITY The following access supervision settings are available.

8 SECURITY

INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be entered within a three-minute time span before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED or REMOTE ACCESS DENIED FlexLogic operands are set to On. These operands are returned to the Off state upon expiration of the lockout. PASSWORD LOCKOUT DURATION: This setting specifies the time that the C30 will lockout password access after the number of invalid password entries specified by the INVALID ATTEMPS BEFORE LOCKOUT setting has occurred.

The C30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic operand is asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be used to protect against both unauthorized and accidental access attempts. The UNAUTHORIZED ACCESS operand is reset with the COMMANDS CLEAR RECORDS RESET UNAUTHORIZED ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The operand does not generate events or targets. If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed with event logs or targets enabled. The access level timeout settings are shown below.
PATH: SETTINGS PRODUCT SETUP SECURITY ACCESS SUPERVISION ACCESS LEVEL TIMEOUTS Range: 5 to 480 minutes in steps of 1

ACCESS LEVEL TIMEOUTS


MESSAGE

COMMAND LEVEL ACCESS TIMEOUT: 5 min SETTING LEVEL ACCESS TIMEOUT: 30 min

Range: 5 to 480 minutes in steps of 1

These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note that the access level will set as restricted if control power is cycled. COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access) required to return to restricted access from the command password level. SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access) required to return to restricted access from the command password level. 8.1.6 DUAL PERMISSION SECURITY ACCESS
PATH: SETTINGS PRODUCT SETUP SECURITY DUAL PERMISSION SECURITY ACCESS Range: selected FlexLogic operands (see below)

DUAL PERMISSION SECURITY ACCESS


MESSAGE

LOCAL SETTING AUTH: On REMOTE SETTING AUTH: On ACCESS AUTH TIMEOUT: 30 min.

Range: FlexLogic operand

Range: 5 to 480 minutes in steps of 1

MESSAGE

The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended upload of settings to a relay through the local or remote interfaces interface. The following settings are available through the local (front panel) interface only. LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision. Valid values for the FlexLogic operands are either On (default) or any physical Contact Input ~~ On value. If this setting is On, then local setting access functions as normal; that is, a local setting password is required. If this setting is any contact input on FlexLogic operand, then the operand must be asserted (set as on) prior to providing the local setting password to gain setting access.

8-4

C30 Controller System

GE Multilin

8 SECURITY

8.1 PASSWORD SECURITY

If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel. REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision. If this setting is On (the default setting), then remote setting access functions as normal; that is, a remote password is required). If this setting is Off, then remote setting access is blocked even if the correct remote setting password is provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to providing the remote setting password to gain setting access. ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable when the LOCAL SETTING AUTH setting is programmed to any operand except On. The state of the FlexLogic operand is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer programmed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.

The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product Setup > Security menu item to display the security settings window.

The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision. If this setting is On (the default setting), then remote setting access functions as normal; that is, a remote password is required). If this setting is Off, then remote setting access is blocked even if the correct remote setting password is provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to providing the remote setting password to gain setting access. The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable when the Remote Settings Authorization setting is programmed to any operand except On or Off. The state of the FlexLogic operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.

GE Multilin

C30 Controller System

8-5

8.2 SETTINGS SECURITY 8.2SETTINGS SECURITY

8 SECURITY 8.2.1 SETTINGS TEMPLATES

Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An example of this is a substation that has ten similar feeders protected by ten UR-series F60 relays. In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows engineers to configure and test these common settings, then lock them so they are not available to users. For example, these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate on the specific settings. The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers installing the devices. These will be settings such as protection element pickup values and CT and VT ratios. The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings templates can be applied to both settings files (settings file templates) and online devices (online settings templates). The functionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the C30 firmware are at versions 5.40 or higher.
NOTE

a) ENABLING THE SETTINGS TEMPLATE The settings file template feature is disabled by default. The following procedure describes how to enable the settings template for UR-series settings files. 1. 2. Select a settings file from the offline window of the EnerVista UR Setup main screen. Right-click on the selected device or settings file and select the Template Mode > Create Template option.

The settings file template is now enabled and the file tree displayed in light blue. The settings file is now in template editing mode. Alternatively, the settings template can also be applied to online settings. The following procedure describes this process. 1. 2. Select an installed device from the online window of the EnerVista UR Setup main screen. Right-click on the selected device and select the Template Mode > Create Template option.

The software will prompt for a template password. This password is required to use the template feature and must be at least four characters in length. 3. Enter and re-enter the new password, then click OK to continue.

The online settings template is now enabled. The device is now in template editing mode. b) EDITING THE SETTINGS TEMPLATE The settings template editing feature allows the user to specify which settings are available for viewing and modification in EnerVista UR Setup. By default, all settings except the FlexLogic equation editor settings are locked. 1. 2. 3. 4. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Edit Template option to place the device in template editing mode. Enter the template password then click OK. Open the relevant settings windows that contain settings to be specified as viewable.

8-6

C30 Controller System

GE Multilin

8 SECURITY

8.2 SETTINGS SECURITY

By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the phase time overcurrent settings window in edit mode.

Figure 82: SETTINGS TEMPLATE VIEW, ALL SETTINGS SPECIFIED AS LOCKED 5. Specify which settings to make viewable by clicking on them. The setting available to view will be displayed against a yellow background as shown below.

Figure 83: SETTINGS TEMPLATE VIEW, TWO SETTINGS SPECIFIED AS EDITABLE 6. 7. Click on Save to save changes to the settings template. Proceed through the settings tree to specify all viewable settings.

c) ADDING PASSWORD PROTECTION TO A TEMPLATE It is highly recommended that templates be saved with password protection to maximize security. The following procedure describes how to add password protection to a settings file template. 1. 2. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option.

GE Multilin

C30 Controller System

8-7

8.2 SETTINGS SECURITY

8 SECURITY

The software will prompt for a template password. This password must be at least four characters in length.

3.

Enter and re-enter the new password, then click OK to continue.

The settings file template is now secured with password protection. When templates are created for online settings, the password is added during the initial template creation step. It does not need to be added after the template is created.
NOTE

d) VIEWING THE SETTINGS TEMPLATE Once all necessary settings are specified for viewing, users are able to view the settings template on the online device or settings file. There are two ways to specify the settings view with the settings template feature: Display only those settings available for editing. Display all settings, with settings not available for editing greyed-out.

Use the following procedure to only display settings available for editing. 1. 2. 3. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen. Apply the template by selecting the Template Mode > View In Template Mode option. Enter the template password then click OK to apply the template.

Once the template has been applied, users will only be able to view and edit the settings specified by the template. The effect of applying the template to the phase time overcurrent settings is shown below.

8
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via the Template Mode > View In Template Mode command. The template specifies that only the Pickup and Curve settings be available.
842858A1.CDR

Figure 84: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND

8-8

C30 Controller System

GE Multilin

8 SECURITY

8.2 SETTINGS SECURITY

Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain editable settings. The effect of applying the template to a typical settings tree view is shown below.

Typical settings tree view without template applied.

Typical settings tree view with template applied via the Template Mode > View In Template Mode command.
842860A1.CDR

Figure 85: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND Use the following procedure to display settings available for editing and settings locked by the template. 1. 2. 3. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen. Apply the template by selecting the Template Mode > View All Settings option. Enter the template password then click OK to apply the template.

Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.

Phase time overcurrent settings window without template applied.

Phase time overcurrent window with template applied via the Template Mode > View All Settings command. The template specifies that only the Pickup and Curve settings be available.
842859A1.CDR

Figure 86: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND e) REMOVING THE SETTINGS TEMPLATE It may be necessary at some point to remove a settings template. Once a template is removed, it cannot be reapplied and it will be necessary to define a new settings template. 1. 2. 3. Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue.

GE Multilin

C30 Controller System

8-9

8.2 SETTINGS SECURITY 4. Verify one more time that you wish to remove the template by clicking Yes.

8 SECURITY

The EnerVista software will remove all template information and all settings will be available. 8.2.2 SECURING AND LOCKING FLEXLOGIC EQUATIONS The UR allows users to secure parts or all of a FlexLogic equation, preventing unauthorized viewing or modification of critical FlexLogic applications. This is accomplished using the settings template feature to lock individual entries within FlexLogic equations. Secured FlexLogic equations will remain secure when files are sent to and retrieved from any UR-series device. a) LOCKING FLEXLOGIC EQUATION ENTRIES The following procedure describes how to lock individual entries of a FlexLogic equation. 1. 2. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the settings template feature. Select the FlexLogic > FlexLogic Equation Editor settings menu item. By default, all FlexLogic entries are specified as viewable and displayed against a yellow background. The icon on the upper right of the window will also indicate that EnerVista UR Setup is in EDIT mode. 3. Specify which entries to lock by clicking on them. The locked entries will be displayed against a grey background as shown in the example below.

8
Figure 87: LOCKING FLEXLOGIC ENTRIES IN EDIT MODE 4. 5. 6. Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic equation.

8-10

C30 Controller System

GE Multilin

8 SECURITY

8.2 SETTINGS SECURITY

Once the template has been applied, users will only be able to view and edit the FlexLogic entries not locked by the template. The effect of applying the template to the FlexLogic entries in the above procedure is shown below.

Typical FlexLogic entries without template applied.

Typical FlexLogic entries locked with template via the Template Mode > View In Template Mode command.
842861A1.CDR

Figure 88: LOCKING FLEXLOGIC ENTRIES THROUGH SETTING TEMPLATES The FlexLogic entries are also shown as locked in the graphical view (as shown below) and on the front panel display.

8
Figure 89: SECURED FLEXLOGIC IN GRAPHICAL VIEW b) LOCKING FLEXLOGIC EQUATIONS TO A SERIAL NUMBER A settings file and associated FlexLogic equations can also be locked to a specific UR serial number. Once the desired FlexLogic entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. 1. 2. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item.

GE Multilin

C30 Controller System

8-11

8.2 SETTINGS SECURITY The following window is displayed.

8 SECURITY

Figure 810: TYPICAL SETTINGS FILE PROPERTIES WINDOW 3. Enter the serial number of the C30 device to lock to the settings file in the Serial # Lock field.

The settings file and corresponding secure FlexLogic equations are now locked to the C30 device specified by the serial number. 8.2.3 SETTINGS FILE TRACEABILITY A traceability feature for settings files allows the user to quickly determine if the settings in a C30 device have been changed since the time of installation from a settings file. When a settings file is transfered to a C30 device, the date, time, and serial number of the C30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This information can be compared with the C30 actual values at any later date to determine if security has been compromised. The traceability information is only included in the settings file if a complete settings file is either transferred to the C30 device or obtained from the C30 device. Any partial settings transfers by way of drag and drop do not add the traceability information to the settings file.

SETTINGS FILE TRANSFERRED TO UR-SERIES DEVICE

The serial number and last setting change date are stored in the UR-series device.

8
The serial number of the UR-series device and the file transfer date are added to the settings file when settings files are transferred to the device. Compare transfer dates in the settings file and the UR-series device to determine if security has been compromised.

SERIAL NUMBER AND TRANSFER DATE SENT BACK TO ENERVISTA AND ADDED TO SETTINGS FILE.

842864A1.CDR

Figure 811: SETTINGS FILE TRACEABILITY MECHANISM With respect to the above diagram, the traceability feature is used as follows.

8-12

C30 Controller System

GE Multilin

8 SECURITY 1. 2.

8.2 SETTINGS SECURITY

The transfer date of a setting file written to a C30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes have been made to the relay configuration since the settings file was saved.

a) SETTINGS FILE TRACEABILITY INFORMATION The serial number and file transfer date are saved in the settings files when they sent to an C30 device. The C30 serial number and file transfer date are included in the settings file device definition within the EnerVista UR Setup offline window as shown in the example below.

Traceability data in settings file device definition

842863A1.CDR

Figure 812: DEVICE DEFINITION SHOWING TRACEABILITY DATA This information is also available in printed settings file reports as shown in the example below.

Traceability data in settings report

842862A1.CDR

Figure 813: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA

GE Multilin

C30 Controller System

8-13

8.2 SETTINGS SECURITY b) ONLINE DEVICE TRACEABILITY INFORMATION

8 SECURITY

The C30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.

Traceability data in online device actual values page

842865A1.CDR

Figure 814: TRACEABILITY DATA IN ACTUAL VALUES WINDOW This infomormation if also available from the front panel display through the following actual values:
ACTUAL VALUES ACTUAL VALUES PRODUCT INFO PRODUCT INFO MODEL INFORMATION MODEL INFORMATION SERIAL NUMBER LAST SETTING CHANGE

c) ADDITIONAL TRACEABILITY RULES The following additional rules apply for the traceability feature If the user changes any settings within the settings file in the offline window, then the traceability information is removed from the settings file. If the user creates a new settings file, then no traceability information is included in the settings file. If the user converts an existing settings file to another revision, then any existing traceability information is removed from the settings file. If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings file.

8-14

C30 Controller System

GE Multilin

8 SECURITY 8.3ENERVISTA SECURITY MANAGEMENT SYSTEM

8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8.3.1 OVERVIEW

The EnerVista security management system is a role-based access control (RBAC) system that allows a security administrator to easily manage the security privileges of multiple users. This allows for access control of URPlus-series devices by multiple personnel within a substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security management system is disabled by default to allow the administrator direct access to the EnerVista software after installation. It is recommended that security be enabled before placing the device in service. 8.3.2 ENABLING THE SECURITY MANAGEMENT SYSTEM The EnerVista security management system is disabled by default. This allows access to the device immediately after installation. When security is disabled, all users are granted administrator access. 1. Select the Security > User Management menu item to open the user management configuration window.

2.

Check the Enable Security box in the lower-left corner to enable the security management system.

Security is now enabled for the EnerVista UR Setup software. It will now be necessary to enter a username and password upon starting the software. 8.3.3 ADDING A NEW USER The following pre-requisites are required to add new users to the EnerVista security management system. The user adding the new user must have administrator rights. The EnerVista security management system must be enabled.

The following procedure describes how to add new users. 1. 2. Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length.

GE Multilin

C30 Controller System

8-15

8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 3. Select the user access rights by checking one or more of the fields shown.

8 SECURITY

The access rights are described in the following table Table 81: ACCESS RIGHTS SUMMARY
FIELD Delete Entry Actual Values Settings Commands Event Recorder FlexLogic Update Info DESCRIPTION Checking this box will delete the user when exiting the user management configuration window. Checking this box allows the user to read actual values. Checking this box allows the user to read setting values. Checking this box allows the user to execute commands. Checking this box allows the user to use the digital fault recorder. Checking this box allows the user to read FlexLogic values. Checking this box allows the user to write to any function to which they have read privileges. When any of the Settings, Event Recorder, and FlexLogic boxes are checked by themselves, the user is granted read access. When any of these are checked in conjunction with the Update Info box, they are granted read and write access. The user will not be granted write access to functions that are not checked, even if the Update Info field is checked. When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights.

Admin

4.

Click OK to add the new user to the security management system. 8.3.4 MODIFYING USER PRIVILEGES

The following pre-requisites are required to modify user privileges in the EnerVista security management system. The user modifying the privileges must have administrator rights. The EnerVista security management system must be enabled.

The following procedure describes how to modify user privileges. 1. 2. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field.

8-16

C30 Controller System

GE Multilin

8 SECURITY 3.

8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM

Modify the user access rights by checking or clearing one or more of the fields shown.

The access rights are described in the following table Table 82: ACCESS RIGHTS SUMMARY
FIELD Delete Entry Actual Values Settings Commands Event Recorder FlexLogic Update Info DESCRIPTION Checking this box will delete the user when exiting the user management configuration window. Checking this box allows the user to read actual values. Checking this box allows the user to read setting values. Checking this box allows the user to execute commands. Checking this box allows the user to use the digital fault recorder. Checking this box allows the user to read FlexLogic values. Checking this box allows the user to write to any function to which they have read privileges. When any of the Settings, Event Recorder, and FlexLogic boxes are checked by themselves, the user is granted read access. When any of these are checked in conjunction with the Update Info box, they are granted read and write access. The user will not be granted write access to functions that are not checked, even if the Update Info field is checked. When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights.

Admin

4.

Click OK to save the changes to user to the security management system.

GE Multilin

C30 Controller System

8-17

8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM

8 SECURITY

8-18

C30 Controller System

GE Multilin

APPENDIX A

A.1 PARAMETER LISTS A.1.1 FLEXANALOG ITEMS

AppendicesAPPENDIX A FlexAnalog and FlexInteger ParametersA.1Parameter Lists

A
TABLE A1: FLEXANALOG DATA ITEMS (Sheet 1 of 3)
ADDRESS 13504 13506 13508 13510 13512 13514 13516 13518 13520 13522 13524 13526 13528 13530 13532 13534 13536 13538 13540 13542 13544 13546 13548 13550 13552 13553 13554 13555 13556 13557 13558 13559 13560 13561 13562 13563 13564 13565 13566 13567 13568 13569 13570 13571 13572 FLEXANALOG NAME DCMA Inputs 1 Value DCMA Inputs 2 Value DCMA Inputs 3 Value DCMA Inputs 4 Value DCMA Inputs 5 Value DCMA Inputs 6 Value DCMA Inputs 7 Value DCMA Inputs 8 Value DCMA Inputs 9 Value DCMA Inputs 10 Value DCMA Inputs 11 Value DCMA Inputs 12 Value DCMA Inputs 13 Value DCMA Inputs 14 Value DCMA Inputs 15 Value DCMA Inputs 16 Value DCMA Inputs 17 Value DCMA Inputs 18 Value DCMA Inputs 19 Value DCMA Inputs 20 Value DCMA Inputs 21 Value DCMA Inputs 22 Value DCMA Inputs 23 Value DCMA Inputs 24 Value RTD Inputs 1 Value RTD Inputs 2 Value RTD Inputs 3 Value RTD Inputs 4 Value RTD Inputs 5 Value RTD Inputs 6 Value RTD Inputs 7 Value RTD Inputs 8 Value RTD Inputs 9 Value RTD Inputs 10 Value RTD Inputs 11 Value RTD Inputs 12 Value RTD Inputs 13 Value RTD Inputs 14 Value RTD Inputs 15 Value RTD Inputs 16 Value RTD Inputs 17 Value RTD Inputs 18 Value RTD Inputs 19 Value RTD Inputs 20 Value RTD Inputs 21 Value UNITS mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA mA ------------------------------------------DESCRIPTION dcmA input 1 actual value dcmA input 2 actual value dcmA input 3 actual value dcmA input 4 actual value dcmA input 5 actual value dcmA input 6 actual value dcmA input 7 actual value dcmA input 8 actual value dcmA input 9 actual value dcmA input 10 actual value dcmA input 11 actual value dcmA input 12 actual value dcmA input 13 actual value dcmA input 14 actual value dcmA input 15 actual value dcmA input 16 actual value dcmA input 17 actual value dcmA input 18 actual value dcmA input 19 actual value dcmA input 20 actual value dcmA input 21 actual value dcmA input 22 actual value dcmA input 23 actual value dcmA input 24 actual value RTD input 1 actual value RTD input 2 actual value RTD input 3 actual value RTD input 4 actual value RTD input 5 actual value RTD input 6 actual value RTD input 7 actual value RTD input 8 actual value RTD input 9 actual value RTD input 10 actual value RTD input 11 actual value RTD input 12 actual value RTD input 13 actual value RTD input 14 actual value RTD input 15 actual value RTD input 16 actual value RTD input 17 actual value RTD input 18 actual value RTD input 19 actual value RTD input 20 actual value RTD input 21 actual value

GE Multilin

C30 Controller System

A-1

A.1 PARAMETER LISTS TABLE A1: FLEXANALOG DATA ITEMS (Sheet 2 of 3)

APPENDIX A

ADDRESS 13573 13574 13575 13576 13577 13578 13579 13580 13581 13582 13583 13584 13585 13586 13587 13588 13589 13590 13591 13592 13593 13594 13595 13596 13597 13598 13599 24459 32768 39425 39427 39429 39431 39433 39435 39437 39439 45584 45586 45588 45590 45592 45594 45596 45598 45600 45602

FLEXANALOG NAME RTD Inputs 22 Value RTD Inputs 23 Value RTD Inputs 24 Value RTD Inputs 25 Value RTD Inputs 26 Value RTD Inputs 27 Value RTD Inputs 28 Value RTD Inputs 29 Value RTD Inputs 30 Value RTD Inputs 31 Value RTD Inputs 32 Value RTD Inputs 33 Value RTD Inputs 34 Value RTD Inputs 35 Value RTD Inputs 36 Value RTD Inputs 37 Value RTD Inputs 38 Value RTD Inputs 39 Value RTD Inputs 40 Value RTD Inputs 41 Value RTD Inputs 42 Value RTD Inputs 43 Value RTD Inputs 44 Value RTD Inputs 45 Value RTD Inputs 46 Value RTD Inputs 47 Value RTD Inputs 48 Value Active Setting Group Tracking Frequency FlexElement 1 Value FlexElement 2 Value FlexElement 3 Value FlexElement 4 Value FlexElement 5 Value FlexElement 6 Value FlexElement 7 Value FlexElement 8 Value GOOSE Analog In 1 GOOSE Analog In 2 GOOSE Analog In 3 GOOSE Analog In 4 GOOSE Analog In 5 GOOSE Analog In 6 GOOSE Analog In 7 GOOSE Analog In 8 GOOSE Analog In 9 GOOSE Analog In 10

UNITS --------------------------------------------------------Hz -------------------------------------

DESCRIPTION RTD input 22 actual value RTD input 23 actual value RTD input 24 actual value RTD input 25 actual value RTD input 26 actual value RTD input 27 actual value RTD input 28 actual value RTD input 29 actual value RTD input 30 actual value RTD input 31 actual value RTD input 32 actual value RTD input 33 actual value RTD input 34 actual value RTD input 35 actual value RTD input 36 actual value RTD input 37 actual value RTD input 38 actual value RTD input 39 actual value RTD input 40 actual value RTD input 41 actual value RTD input 42 actual value RTD input 43 actual value RTD input 44 actual value RTD input 45 actual value RTD input 46 actual value RTD input 47 actual value RTD input 48 actual value Current setting group Tracking frequency FlexElement 1 actual value FlexElement 2 actual value FlexElement 3 actual value FlexElement 4 actual value FlexElement 5 actual value FlexElement 6 actual value FlexElement 7 actual value FlexElement 8 actual value IEC 61850 GOOSE analog input 1 IEC 61850 GOOSE analog input 2 IEC 61850 GOOSE analog input 3 IEC 61850 GOOSE analog input 4 IEC 61850 GOOSE analog input 5 IEC 61850 GOOSE analog input 6 IEC 61850 GOOSE analog input 7 IEC 61850 GOOSE analog input 8 IEC 61850 GOOSE analog input 9 IEC 61850 GOOSE analog input 10

A-2

C30 Controller System

GE Multilin

APPENDIX A TABLE A1: FLEXANALOG DATA ITEMS (Sheet 3 of 3)


ADDRESS 45604 45606 45608 45610 45612 45614 FLEXANALOG NAME GOOSE Analog In 11 GOOSE Analog In 12 GOOSE Analog In 13 GOOSE Analog In 14 GOOSE Analog In 15 GOOSE Analog In 16 UNITS ------------DESCRIPTION IEC 61850 GOOSE analog input 11 IEC 61850 GOOSE analog input 12 IEC 61850 GOOSE analog input 13 IEC 61850 GOOSE analog input 14 IEC 61850 GOOSE analog input 15 IEC 61850 GOOSE analog input 16

A.1 PARAMETER LISTS

A.1.2 FLEXINTEGER ITEMS

Table A2: FLEXINTEGER DATA ITEMS


ADDRESS 9968 9970 9972 9974 9976 9978 9980 9982 9984 9986 9988 9990 9992 9994 9996 9998 FLEXINTEGER NAME GOOSE UInt Input 1 GOOSE UInt Input 2 GOOSE UInt Input 3 GOOSE UInt Input 4 GOOSE UInt Input 5 GOOSE UInt Input 6 GOOSE UInt Input 7 GOOSE UInt Input 8 GOOSE UInt Input 9 GOOSE UInt Input 10 GOOSE UInt Input 11 GOOSE UInt Input 12 GOOSE UInt Input 13 GOOSE UInt Input 14 GOOSE UInt Input 15 GOOSE UInt Input 16 UNITS --------------------------------DESCRIPTION IEC61850 GOOSE UInteger input 1 IEC61850 GOOSE UInteger input 2 IEC61850 GOOSE UInteger input 3 IEC61850 GOOSE UInteger input 4 IEC61850 GOOSE UInteger input 5 IEC61850 GOOSE UInteger input 6 IEC61850 GOOSE UInteger input 7 IEC61850 GOOSE UInteger input 8 IEC61850 GOOSE UInteger input 9 IEC61850 GOOSE UInteger input 10 IEC61850 GOOSE UInteger input 11 IEC61850 GOOSE UInteger input 12 IEC61850 GOOSE UInteger input 13 IEC61850 GOOSE UInteger input 14 IEC61850 GOOSE UInteger input 15 IEC61850 GOOSE UInteger input 16

GE Multilin

C30 Controller System

A-3

A.1 PARAMETER LISTS

APPENDIX A

A-4

C30 Controller System

GE Multilin

APPENDIX B APPENDIX B MODBUS COMMUNICATIONSB.1MODBUS RTU PROTOCOL

B.1 MODBUS RTU PROTOCOL B.1.1 INTRODUCTION

The UR-series relays support a number of communications protocols to allow connection to equipment such as personal computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus RTU protocol is the most basic protocol supported by the UR. Modbus is available via RS232 or RS485 serial links or via ethernet (using the Modbus/TCP specification). The following description is intended primarily for users who wish to develop their own master communication drivers and applies to the serial Modbus RTU protocol. Note that: The UR always acts as a slave device, meaning that it never initiates communications; it only listens and responds to requests issued by a master computer. For Modbus, a subset of the Remote Terminal Unit (RTU) protocol format is supported that allows extensive monitoring, programming, and control functions using read and write register commands. B.1.2 PHYSICAL LAYER The Modbus RTU protocol is hardware-independent so that the physical layer can be any of a variety of standard hardware configurations including RS232 and RS485. The relay includes a faceplate (front panel) RS232 port and two rear terminal communications ports that may be configured as RS485, fiber optic, 10Base-T, or 10Base-F. Data flow is half-duplex in all configurations. See chapter 3 for details on communications wiring. Each data byte is transmitted in an asynchronous format consisting of 1 start bit, 8 data bits, 1 stop bit, and possibly 1 parity bit. This produces a 10 or 11 bit data frame. This can be important for transmission through modems at high bit rates (11 bit data frames are not supported by many modems at baud rates greater than 300). The baud rate and parity are independently programmable for each communications port. Baud rates of 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 33600, 38400, 57600, or 115200 bps are available. Even, odd, and no parity are available. Refer to the Communications section of chapter 5 for further details. The master device in any system must know the address of the slave device with which it is to communicate. The relay will not act on a request from a master if the address in the request does not match the relays slave address (unless the address is the broadcast address see below). A single setting selects the slave address used for all ports, with the exception that for the faceplate port, the relay will accept any address when the Modbus RTU protocol is used. B.1.3 DATA LINK LAYER Communications takes place in packets which are groups of asynchronously framed byte data. The master transmits a packet to the slave and the slave responds with a packet. The end of a packet is marked by dead-time on the communications line. The following describes general format for both transmit and receive packets. For exact details on packet formatting, refer to subsequent sections describing each function code. Table B1: MODBUS PACKET FORMAT
DESCRIPTION SLAVE ADDRESS FUNCTION CODE DATA CRC DEAD TIME SIZE 1 byte 1 byte N bytes 2 bytes 3.5 bytes transmission time

SLAVE ADDRESS: This is the address of the slave device that is intended to receive the packet sent by the master and to perform the desired action. Each slave device on a communications bus must have a unique address to prevent bus contention. All of the relays ports have the same address which is programmable from 1 to 254; see chapter 5 for details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an exception to this rule; it will act on a message containing any slave address. A master transmit packet with slave address 0 indicates a broadcast command. All slaves on the communication link take action based on the packet, but none respond to the master. Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored.

GE Multilin

C30 Controller System

B-1

B.1 MODBUS RTU PROTOCOL

APPENDIX B

FUNCTION CODE: This is one of the supported functions codes of the unit which tells the slave what action to perform. See the Supported Function Codes section for complete details. An exception response from the slave is indicated by setting the high order bit of the function code in the response packet. See the Exception Responses section for further details. DATA: This will be a variable number of bytes depending on the function code. This may include actual values, settings, or addresses sent by the master to the slave or by the slave to the master. CRC: This is a two byte error checking code. The RTU version of Modbus includes a 16-bit cyclic redundancy check (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device receives a packet in which an error is indicated by the CRC, the slave device will not act upon or respond to the packet thus preventing any erroneous operations. See the CRC-16 Algorithm section for details on calculating the CRC. DEAD TIME: A packet is terminated when no data is received for a period of 3.5 byte transmission times (about 15 ms at 2400 bps, 2 ms at 19200 bps, and 300 s at 115200 bps). Consequently, the transmitting device must not allow gaps between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves start listening for a new packet from the master except for the addressed slave. B.1.4 CRC-16 ALGORITHM

The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one continuous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial (11000000000000101B). The 16-bit remainder of the division is appended to the end of the packet, MSByte first. The resulting packet including CRC, when divided by the same polynomial at the receiver will give a zero remainder if no transmission errors have occurred. This algorithm requires the characteristic polynomial to be reverse bit ordered. The most significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder. A C programming language implementation of the CRC algorithm will be provided upon request. Table B2: CRC-16 ALGORITHM
SYMBOLS: --> A Alow Ahigh CRC i,j (+) N Di G shr (x) ALGORITHM: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. data transfer 16 bit working register low order byte of A high order byte of A 16 bit CRC-16 result loop counters logical EXCLUSIVE-OR operator total number of data bytes i-th data byte (i = 0 to N-1) 16 bit characteristic polynomial = 1010000000000001 (binary) with MSbit dropped and bit order reversed right shift operator (th LSbit of x is shifted into a carry flag, a '0' is shifted into the MSbit of x, all other bits are shifted right one location) FFFF (hex) --> A 0 --> i 0 --> j Di (+) Alow --> Alow j + 1 --> j shr (A) Is there a carry? Is j = 8? i + 1 --> i Is i = N? A --> CRC No: go to 3; Yes: continue No: go to 8; Yes: G (+) A --> A and continue. No: go to 5; Yes: continue

B-2

C30 Controller System

GE Multilin

APPENDIX B B.2MODBUS FUNCTION CODES

B.2 MODBUS FUNCTION CODES B.2.1 SUPPORTED FUNCTION CODES

Modbus officially defines function codes from 1 to 127 though only a small subset is generally needed. The relay supports some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail.
FUNCTION CODE HEX 03 04 05 06 10 DEC 3 4 5 6 16 Read holding registers Read holding registers Force single coil Preset single register Preset multiple registers Read actual values or settings Read actual values or settings Execute operation Store single setting Store multiple settings MODBUS DEFINITION GE MULTILIN DEFINITION

B.2.2 READ ACTUAL VALUES OR SETTINGS (FUNCTION CODE 03/04H) This function code allows the master to read one or more consecutive data registers (actual values or settings) from a relay. Data registers are always 16-bit (two-byte) values transmitted with high order byte first. The maximum number of registers that can be read in a single packet is 125. See the Modbus memory map table for exact details on the data registers. Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The C30 interpretation allows either function code to be used for reading one or more consecutive data registers. The data starting address will determine the type of data being read. Function codes 03h and 04h are therefore identical. The following table shows the format of the master and slave packets. The example shows a master device requesting three register values starting at address 4050h from slave device 11h (17 decimal); the slave device responds with the values 40, 300, and 0 from registers 4050h, 4051h, and 4052h, respectively. Table B3: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION PACKET FORMAT SLAVE ADDRESS FUNCTION CODE DATA STARTING ADDRESS - high DATA STARTING ADDRESS - low NUMBER OF REGISTERS - high NUMBER OF REGISTERS - low CRC - low CRC - high EXAMPLE (HEX) 11 04 40 50 00 03 A7 4A SLAVE RESPONSE PACKET FORMAT SLAVE ADDRESS FUNCTION CODE BYTE COUNT DATA #1 - high DATA #1 - low DATA #2 - high DATA #2 - low DATA #3 - high DATA #3 - low CRC - low CRC - high EXAMPLE (HEX) 11 04 06 00 28 01 2C 00 00 0D 60

GE Multilin

C30 Controller System

B-3

B.2 MODBUS FUNCTION CODES

APPENDIX B B.2.3 EXECUTE OPERATION (FUNCTION CODE 05H)

This function code allows the master to perform various operations in the relay. Available operations are shown in the Summary of operation codes table below. The following table shows the format of the master and slave packets. The example shows a master device requesting the slave device 11h (17 decimal) to perform a reset. The high and low code value bytes always have the values FF and 00 respectively and are a remnant of the original Modbus definition of this function code. Table B4: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION PACKET FORMAT SLAVE ADDRESS FUNCTION CODE OPERATION CODE - high OPERATION CODE - low CODE VALUE - high CODE VALUE - low CRC - low CRC - high EXAMPLE (HEX) 11 05 00 01 FF 00 DF 6A SLAVE RESPONSE PACKET FORMAT SLAVE ADDRESS FUNCTION CODE OPERATION CODE - high OPERATION CODE - low CODE VALUE - high CODE VALUE - low CRC - low CRC - high EXAMPLE (HEX) 11 05 00 01 FF 00 DF 6A

Table B5: SUMMARY OF OPERATION CODES FOR FUNCTION 05H


OPERATION CODE (HEX) 0000 0001 0005 0006 1000 to 103F DEFINITION NO OPERATION RESET CLEAR EVENT RECORDS CLEAR OSCILLOGRAPHY VIRTUAL IN 1 to 64 ON/OFF DESCRIPTION Does not do anything. Performs the same function as the faceplate RESET key. Performs the same function as the faceplate CLEAR EVENT RECORDS menu command. Clears all oscillography records. Sets the states of Virtual Inputs 1 to 64 either ON or OFF.

B.2.4 STORE SINGLE SETTING (FUNCTION CODE 06H) This function code allows the master to modify the contents of a single setting register in an relay. Setting registers are always 16 bit (two byte) values transmitted high order byte first. The following table shows the format of the master and slave packets. The example shows a master device storing the value 200 at memory map address 4051h to slave device 11h (17 dec). Table B6: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION PACKET FORMAT SLAVE ADDRESS FUNCTION CODE DATA STARTING ADDRESS - high DATA STARTING ADDRESS - low DATA - high DATA - low CRC - low CRC - high EXAMPLE (HEX) 11 06 40 51 00 C8 CE DD SLAVE RESPONSE PACKET FORMAT SLAVE ADDRESS FUNCTION CODE DATA STARTING ADDRESS - high DATA STARTING ADDRESS - low DATA - high DATA - low CRC - low CRC - high EXAMPLE (HEX) 11 06 40 51 00 C8 CE DD

B-4

C30 Controller System

GE Multilin

APPENDIX B

B.2 MODBUS FUNCTION CODES B.2.5 STORE MULTIPLE SETTINGS (FUNCTION CODE 10H)

This function code allows the master to modify the contents of a one or more consecutive setting registers in a relay. Setting registers are 16-bit (two byte) values transmitted high order byte first. The maximum number of setting registers that can be stored in a single packet is 60. The following table shows the format of the master and slave packets. The example shows a master device storing the value 200 at memory map address 4051h, and the value 1 at memory map address 4052h to slave device 11h (17 decimal). Table B7: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION PACKET FORMAT SLAVE ADDRESS FUNCTION CODE DATA STARTING ADDRESS - hi DATA STARTING ADDRESS - lo NUMBER OF SETTINGS - hi NUMBER OF SETTINGS - lo BYTE COUNT DATA #1 - high order byte DATA #1 - low order byte DATA #2 - high order byte DATA #2 - low order byte CRC - low order byte CRC - high order byte EXAMPLE (HEX) 11 10 40 51 00 02 04 00 C8 00 01 12 62 SLAVE RESPONSE PACKET FORMAT SLAVE ADDRESS FUNCTION CODE DATA STARTING ADDRESS - hi DATA STARTING ADDRESS - lo NUMBER OF SETTINGS - hi NUMBER OF SETTINGS - lo CRC - lo CRC - hi EXMAPLE (HEX) 11 10 40 51 00 02 07 64

B.2.6 EXCEPTION RESPONSES Programming or operation errors usually happen because of illegal data in a packet. These errors result in an exception response from the slave. The slave detecting one of these errors sends a response packet to the master with the high order bit of the function code set to 1. The following table shows the format of the master and slave packets. The example shows a master device sending the unsupported function code 39h to slave device 11. Table B8: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION PACKET FORMAT SLAVE ADDRESS FUNCTION CODE CRC - low order byte CRC - high order byte EXAMPLE (HEX) 11 39 CD F2 SLAVE RESPONSE PACKET FORMAT SLAVE ADDRESS FUNCTION CODE ERROR CODE CRC - low order byte CRC - high order byte EXAMPLE (HEX) 11 B9 01 93 95

GE Multilin

C30 Controller System

B-5

B.3 FILE TRANSFERS B.3FILE TRANSFERS a) DESCRIPTION

APPENDIX B B.3.1 OBTAINING RELAY FILES VIA MODBUS

The UR relay has a generic file transfer facility, meaning that you use the same method to obtain all of the different types of files from the unit. The Modbus registers that implement file transfer are found in the "Modbus File Transfer (Read/Write)" and "Modbus File Transfer (Read Only)" modules, starting at address 3100 in the Modbus Memory Map. To read a file from the UR relay, use the following steps: 1. Write the filename to the "Name of file to read" register using a write multiple registers command. If the name is shorter than 80 characters, you may write only enough registers to include all the text of the filename. Filenames are not case sensitive. Repeatedly read all the registers in "Modbus File Transfer (Read Only)" using a read multiple registers command. It is not necessary to read the entire data block, since the UR relay will remember which was the last register you read. The "position" register is initially zero and thereafter indicates how many bytes (2 times the number of registers) you have read so far. The "size of..." register indicates the number of bytes of data remaining to read, to a maximum of 244. Keep reading until the "size of..." register is smaller than the number of bytes you are transferring. This condition indicates end of file. Discard any bytes you have read beyond the indicated block size. If you need to re-try a block, read only the "size of.." and "block of data", without reading the position. The file pointer is only incremented when you read the position register, so the same data block will be returned as was read in the previous operation. On the next read, check to see if the position is where you expect it to be, and discard the previous block if it is not (this condition would indicate that the UR relay did not process your original read request).

2.

3. 4.

The UR relay retains connection-specific file transfer information, so files may be read simultaneously on multiple Modbus connections. b) OTHER PROTOCOLS All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols (for example, TFTP or MMS). c) COMTRADE, OSCILLOGRAPHY, AND DATA LOGGER FILES Oscillography and data logger files are formatted using the COMTRADE file format per IEEE PC37.111 Draft 7c (02 September 1997). The files may be obtained in either text or binary COMTRADE format. d) READING OSCILLOGRAPHY FILES Familiarity with the oscillography feature is required to understand the following description. Refer to the Oscillography section in Chapter 5 for additional details. The Oscillography Number of Triggers register is incremented by one every time a new oscillography file is triggered (captured) and cleared to zero when oscillography data is cleared. When a new trigger occurs, the associated oscillography file is assigned a file identifier number equal to the incremented value of this register; the newest file number is equal to the Oscillography_Number_of_Triggers register. This register can be used to determine if any new data has been captured by periodically reading it to see if the value has changed; if the number has increased then new data is available. The Oscillography Number of Records register specifies the maximum number of files (and the number of cycles of data per file) that can be stored in memory of the relay. The Oscillography Available Records register specifies the actual number of files that are stored and still available to be read out of the relay. Writing Yes (i.e. the value 1) to the Oscillography Clear Data register clears oscillography data files, clears both the Oscillography Number of Triggers and Oscillography Available Records registers to zero, and sets the Oscillography Last Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace nnn with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT

B-6

C30 Controller System

GE Multilin

APPENDIX B e) READING DATA LOGGER FILES

B.3 FILE TRANSFERS

Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chapter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files. datalog.cfg and datalog.dat To read the entire data logger in ASCII COMTRADE format, read the following files. dataloga.cfg and dataloga.dat To limit the range of records to be returned in the COMTRADE files, append the following to the filename before writing it: To read from a specific time to the end of the log: <space> startTime To read a specific range of records: <space> startTime <space> endTime Replace <startTime> and <endTime> with Julian dates (seconds since Jan. 1 1970) as numeric text.

f) READING EVENT RECORDER FILES To read the entire event recorder contents in ASCII format (the only available format), use the following filename: EVT.TXT To read from a specific record to the end of the log, use the following filename: EVTnnn.TXT (replace nnn with the desired starting record number) To read from a specific record to another specific record, use the following filename: EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number) B.3.2 MODBUS PASSWORD OPERATION The C30 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords enables this functionality. When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used. The command password is set up at memory location 4000. Storing a value of 0 removes command password protection. When reading the password setting, the encrypted value (zero if no password is set) is returned. Command security is required to change the command password. Similarly, the setting password is set up at memory location 4002. These are the same settings and encrypted values found in the SETTINGS PRODUCT SETUP PASSWORD SECURITY menu via the keypad. Enabling password security for the faceplate display will also enable it for Modbus, and vice-versa. To gain command level security access, the command password must be entered at memory location 4008. To gain setting level security access, the setting password must be entered at memory location 400A. The entered setting password must match the current setting password setting, or must be zero, to change settings or download firmware. Command and setting passwords each have a 30 minute timer. Each timer starts when you enter the particular password, and is re-started whenever you use it. For example, writing a setting re-starts the setting password timer and writing a command register or forcing a coil re-starts the command password timer. The value read at memory location 4010 can be used to confirm whether a command password is enabled or disabled (a value of 0 represents disabled). The value read at memory location 4011 can be used to confirm whether a setting password is enabled or disabled. Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the passwords must be re-entered after disconnecting and re-connecting on TCP/IP.

GE Multilin

C30 Controller System

B-7

B.4 MEMORY MAPPING B.4MEMORY MAPPING

APPENDIX B B.4.1 MODBUS MEMORY MAP

Table B9: MODBUS MEMORY MAP (Sheet 1 of 39)


ADDR 0000 0002 0010 0020 0022 0040 0090 0093 00A0 00B0 00C0 0200 0204 0220 0248 0280 REGISTER NAME UR Product Type Product Version Serial Number Manufacturing Date Modification Number Order Code Ethernet MAC Address Reserved (13 items) CPU Module Serial Number CPU Supplier Serial Number Ethernet Sub Module Serial Number (8 items) Self Test States (2 items) LED Column n State, n = 1 to 10 (10 items) Display Message Last Key Pressed Simulated keypress -- write zero before each keystroke RANGE 0 to 65535 0 to 655.35 --0 to 4294967295 0 to 65535 ------------0 to 4294967295 0 to 65535 --0 to 47 0 to 42 UNITS ----------------------0 --------STEP 1 0.01 --1 1 ------------1 1 --1 1 FORMAT F001 F001 F203 F050 F001 F204 F072 F001 F203 F203 F203 F143 F501 F204 F530 F190 DEFAULT 0 1 0 0 0 Order Code x 0 0 (none) (none) (none) 0 0 (none) 0 (None) 0 (No key -- use between real keys) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) Product Information (Read Only)

Product Information (Read Only -- Written by Factory)

Self Test Targets (Read Only) Front Panel (Read Only)

Keypress Emulation (Read/Write)

Virtual Input Commands (Read/Write Command) (64 modules) 0400 0401 0402 0403 0404 0405 0406 0407 0408 0409 040A 040B 040C 040D 040E 040F 0410 0411 0412 0413 0414 0415 0416 0417 0418 0419 041A 041B Virtual Input 1 State Virtual Input 2 State Virtual Input 3 State Virtual Input 4 State Virtual Input 5 State Virtual Input 6 State Virtual Input 7 State Virtual Input 8 State Virtual Input 9 State Virtual Input 10 State Virtual Input 11 State Virtual Input 12 State Virtual Input 13 State Virtual Input 14 State Virtual Input 15 State Virtual Input 16 State Virtual Input 17 State Virtual Input 18 State Virtual Input 19 State Virtual Input 20 State Virtual Input 21 State Virtual Input 22 State Virtual Input 23 State Virtual Input 24 State Virtual Input 25 State Virtual Input 26 State Virtual Input 27 State Virtual Input 28 State 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 --------------------------------------------------------1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108

B-8

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 2 of 39)


ADDR 041C 041D 041E 041F 0420 0421 0422 0423 0424 0425 0426 0427 0428 0429 042A 042B 042C 042D 042E 042F 0430 0431 0432 0433 0434 0435 0436 0437 0438 0439 043A 043B 043C 043D 043E 043F 0800 0802 0804 0806 0808 0810 0818 0820 0828 0830 0838 0900 1000 REGISTER NAME Virtual Input 29 State Virtual Input 30 State Virtual Input 31 State Virtual Input 32 State Virtual Input 33 State Virtual Input 34 State Virtual Input 35 State Virtual Input 36 State Virtual Input 37 State Virtual Input 38 State Virtual Input 39 State Virtual Input 40 State Virtual Input 41 State Virtual Input 42 State Virtual Input 43 State Virtual Input 44 State Virtual Input 45 State Virtual Input 46 State Virtual Input 47 State Virtual Input 48 State Virtual Input 49 State Virtual Input 50 State Virtual Input 51 State Virtual Input 52 State Virtual Input 53 State Virtual Input 54 State Virtual Input 55 State Virtual Input 56 State Virtual Input 57 State Virtual Input 58 State Virtual Input 59 State Virtual Input 60 State Virtual Input 61 State Virtual Input 62 State Virtual Input 63 State Virtual Input 64 State Digital Counter 1 Value Digital Counter 1 Frozen Digital Counter 1 Frozen Time Stamp Digital Counter 1 Frozen Time Stamp us ...Repeated for Digital Counter 2 ...Repeated for Digital Counter 3 ...Repeated for Digital Counter 4 ...Repeated for Digital Counter 5 ...Repeated for Digital Counter 6 ...Repeated for Digital Counter 7 ...Repeated for Digital Counter 8 FlexState Bits (16 items) Element Operate States (64 items) 0 to 65535 0 to 65535 ----1 1 RANGE 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 -2147483647 to 2147483647 -2147483647 to 2147483647 0 to 4294967295 0 to 4294967295 UNITS --------------------------------------------------------------------------------STEP 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

B.4 MEMORY MAPPING

FORMAT F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F108 F004 F004 F050 F003

DEFAULT 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 0 0 0

Digital Counter States (Read Only Non-Volatile) (8 modules)

FlexStates (Read Only) F001 F502 0 0 Element States (Read Only)

GE Multilin

C30 Controller System

B-9

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 3 of 39)
ADDR 1080 1200 REGISTER NAME Formatted user-definable displays (16 items) User Map Values (256 items) Target Sequence Number of Targets Target to Read Target Message Contact Input States (6 items) Virtual Input States (8 items) Contact Output States (4 items) Contact Output Current States (4 items) Contact Output Voltage States (4 items) Virtual Output States (6 items) Contact Output Detectors (4 items) Remote Device States Remote Input States (4 items) Remote Devices Online Remote Double-Point Status Input 1 State Remote Double-Point Status Input 2 State Remote Double-Point Status Input 3 State Remote Double-Point Status Input 4 State Remote Double-Point Status Input 5 State Direct input states (6 items) Direct outputs average message return time 1 Direct outputs average message return time 2 Direct inputs/outputs unreturned message count - Ch. 1 Direct inputs/outputs unreturned message count - Ch. 2 Direct device states Reserved Direct inputs/outputs CRC fail count 1 Direct inputs/outputs CRC fail count 2 Ethernet primary fibre channel status Ethernet secondary fibre channel status Data logger channel count Time of oldest available samples Time of newest available samples Data logger duration Reset Unauthorized Access Remote double-point status input 1 device Remote double-point status input 1 item Remote double-point status input 1 name Remote double-point status input 1 events ... Repeated for double-point status input 2 RANGE --0 to 65535 0 to 65535 0 to 65535 0 to 65535 --0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 1 0 to 3 0 to 3 0 to 3 0 to 3 0 to 3 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 2 0 to 2 0 to 16 0 to 4294967295 0 to 4294967295 0 to 999.9 0 to 1 1 to 32 0 to 128 1 to 64 0 to 1 UNITS --------------------------------------------ms ms ----------------channel seconds seconds days ----------STEP --1 1 1 1 --1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.1 1 1 1 1 1 FORMAT F200 F001 F001 F001 F001 F200 F500 F500 F500 F500 F500 F500 F500 F500 F500 F126 F605 F605 F605 F605 F605 F500 F001 F001 F001 F001 F500 F001 F001 F001 F134 F134 F001 F050 F050 F001 F126 F001 F156 F205 F102

APPENDIX B

DEFAULT (none) 0 0 0 0 . 0 0 0 0 0 0 0 0 0 0 (No) 3 (Bad) 3 (Bad) 3 (Bad) 3 (Bad) 3 (Bad) 0 0 0 0 0 0 0 0 0 0 (Fail) 0 (Fail) 0 0 0 0 0 (No) 1 0 (None) "Rem Ip 1" 0 (Disabled)

User Displays Actuals (Read Only) Modbus User Map Actuals (Read Only) Element Targets (Read Only) 14C0 14C1 14C2 14C3 1500 1508 1510 1518 1520 1528 1530 1540 1542 1550 1551 1552 1553 1554 1555 15C0 15C8 15C9 15CA 15CB 15D0 15D1 15D2 15D3 1610 1611 1618 1619 161B 161D 2230 2620 2621 2622 2628 2629

Element Targets (Read/Write) Element Targets (Read Only) Digital Input/Output States (Read Only)

Remote Input/Output States (Read Only)

Platform Direct Input/Output States (Read Only)

Ethernet Fibre Channel Status (Read/Write)

Data Logger Actuals (Read Only)

Passwords Unauthorized Access (Read/Write Command) Remote double-point status inputs (read/write setting registers)

B-10

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 4 of 39)


ADDR 2632 263B 2644 26B0 26B1 26B2 26B3 26B4 26B5 26B6 26B7 26B8 26B9 26BA 26BB 26BC 26BD 26BE 26BF 26F0 26F2 26F4 26F6 26F8 26FA 26FC 26FE 2700 2702 2704 2706 2708 270A 270C 270E 2B00 2D00 2D80 2E00 2F00 2F80 3000 3001 3002 3004 3005 3011 REGISTER NAME ... Repeated for double-point status input 3 ... Repeated for double-point status input 4 ... Repeated for double-point status input 5 IEC 61850 GGIO5 uinteger input 1 operand IEC 61850 GGIO5 uinteger input 2 operand IEC 61850 GGIO5 uinteger input 3 operand IEC 61850 GGIO5 uinteger input 4 operand IEC 61850 GGIO5 uinteger input 5 operand IEC 61850 GGIO5 uinteger input 6 operand IEC 61850 GGIO5 uinteger input 7 operand IEC 61850 GGIO5 uinteger input 8 operand IEC 61850 GGIO5 uinteger input 9 operand IEC 61850 GGIO5 uinteger input 10 operand IEC 61850 GGIO5 uinteger input 11 operand IEC 61850 GGIO5 uinteger input 12 operand IEC 61850 GGIO5 uinteger input 13 operand IEC 61850 GGIO5 uinteger input 14 operand IEC 61850 GGIO5 uinteger input 15 operand IEC 61850 GGIO5 uinteger input 16 operand IEC 61850 received uinteger 1 IEC 61850 received uinteger 2 IEC 61850 received uinteger 3 IEC 61850 received uinteger 4 IEC 61850 received uinteger 5 IEC 61850 received uinteger 6 IEC 61850 received uinteger 7 IEC 61850 received uinteger 8 IEC 61850 received uinteger 9 IEC 61850 received uinteger 10 IEC 61850 received uinteger 11 IEC 61850 received uinteger 12 IEC 61850 received uinteger 13 IEC 61850 received uinteger 14 IEC 61850 received uinteger 15 IEC 61850 received uinteger 16 FlexStates, one per register (256 items) Contact Input States, one per register (96 items) Contact Output States, one per register (64 items) Virtual Output States, one per register (96 items) Remote Device States, one per register (16 items) Remote Input States, one per register (64 items) Oscillography Number of Triggers Oscillography Available Records Oscillography Last Cleared Date Oscillography Number Of Cycles Per Record Oscillography Force Trigger Oscillography Clear Data --------------------------------0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 65535 0 to 65535 0 to 400000000 0 to 65535 0 to 1 0 to 1 ------------------------------------------------------------------------------------------------------------------------1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

IEC 61850 GGIO5 configuration (read/write setting registers) F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F612 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F108 F108 F108 F108 F155 F108 F001 F001 F050 F001 F126 F126 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 (Off) 0 (Off) 0 (Off) 0 (Off) 0 (Offline) 0 (Off) 0 0 0 0 0 (No) 0 (No)

IEC 61850 received integers (read only actual values)

Expanded FlexStates (Read Only) Expanded Digital Input/Output states (Read Only)

Expanded Remote Input/Output Status (Read Only)

Oscillography Values (Read Only)

Oscillography Commands (Read/Write Command)

GE Multilin

C30 Controller System

B-11

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 5 of 39)
ADDR 3100 3200 REGISTER NAME Name of file to read Character position of current block within file Size of currently-available data block Block of data from requested file (122 items) Events Since Last Clear Number of Available Events Event Recorder Last Cleared Date Event Recorder Clear Command DCMA Inputs 1 Value DCMA Inputs 2 Value DCMA Inputs 3 Value DCMA Inputs 4 Value DCMA Inputs 5 Value DCMA Inputs 6 Value DCMA Inputs 7 Value DCMA Inputs 8 Value DCMA Inputs 9 Value DCMA Inputs 10 Value DCMA Inputs 11 Value DCMA Inputs 12 Value DCMA Inputs 13 Value DCMA Inputs 14 Value DCMA Inputs 15 Value DCMA Inputs 16 Value DCMA Inputs 17 Value DCMA Inputs 18 Value DCMA Inputs 19 Value DCMA Inputs 20 Value DCMA Inputs 21 Value DCMA Inputs 22 Value DCMA Inputs 23 Value DCMA Inputs 24 Value RTD Input 1 Value RTD Input 2 Value RTD Input 3 Value RTD Input 4 Value RTD Input 5 Value RTD Input 6 Value RTD Input 7 Value RTD Input 8 Value RTD Input 9 Value RTD Input 10 Value RTD Input 11 Value RTD Input 12 Value RTD Input 13 Value RTD Input 14 Value RTD Input 15 Value RTD Input 16 Value RANGE --0 to 4294967295 0 to 65535 0 to 65535 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 1 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -9999999 to 9999999 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 UNITS ----------------------------------------------------------------C C C C C C C C C C C C C C C C STEP --1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 FORMAT F204 F003 F001 F001 F003 F003 F050 F126 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F004 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002

APPENDIX B

DEFAULT (none) 0 0 0 0 0 0 0 (No) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Modbus file transfer (read/write) Modbus file transfer values (read only) 3202 3203 3400 3402 3404 3406 34C0 34C2 34C4 34C6 34C8 34CA 34CC 34CE 34D0 34D2 34D4 34D6 34D8 34DA 34DC 34DE 34E0 34E2 34E4 34E6 34E8 34EA 34EC 34EE 34F0 34F1 34F2 34F3 34F4 34F5 34F6 34F7 34F8 34F9 34FA 34FB 34FC 34FD 34FE 34FF

Event recorder actual values (read only)

Event recorder commands (read/write) DCMA Input Values (Read Only) (24 modules)

RTD Input Values (Read Only) (48 modules)

B-12

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 6 of 39)


ADDR 3500 3501 3502 3503 3504 3505 3506 3507 3508 3509 350A 350B 350C 350D 350E 350F 3510 3511 3512 3513 3514 3515 3516 3517 3518 3519 351A 351B 351C 351D 351E 351F 3560 3570 4000 4002 4008 400A 4010 4011 4012 4013 4014 4015 4016 4017 4018 4019 REGISTER NAME RTD Input 17 Value RTD Input 18 Value RTD Input 19 Value RTD Input 20 Value RTD Input 21 Value RTD Input 22 Value RTD Input 23 Value RTD Input 24 Value RTD Input 25 Value RTD Input 26 Value RTD Input 27 Value RTD Input 28 Value RTD Input 29 Value RTD Input 30 Value RTD Input 31 Value RTD Input 32 Value RTD Input 33 Value RTD Input 34 Value RTD Input 35 Value RTD Input 36 Value RTD Input 37 Value RTD Input 38 Value RTD Input 39 Value RTD Input 40 Value RTD Input 41 Value RTD Input 42 Value RTD Input 43 Value RTD Input 44 Value RTD Input 45 Value RTD Input 46 Value RTD Input 47 Value RTD Input 48 Value Direct Device States, one per register (8 items) Direct Input States, one per register (96 items) Command Password Setting Setting Password Setting Command Password Entry Setting Password Entry Command password status Setting password status Control password access timeout Setting password access timeout Invalid password attempts Password lockout duration Password access events Local setting authorization Remote setting authorization Access authorization timeout RANGE -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 -32768 to 32767 0 to 1 0 to 1 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 1 0 to 1 5 to 480 5 to 480 2 to 5 5 to 60 0 to 1 1 to 65535 0 to 65535 5 to 480 UNITS C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C ----------------minutes minutes --minutes ------minutes STEP 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

B.4 MEMORY MAPPING

FORMAT F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F002 F155 F108 F003 F003 F003 F003 F102 F102 F001 F001 F001 F001 F102 F300 F300 F001

DEFAULT 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 (Offline) 0 (Off) 0 0 0 0 0 (Disabled) 0 (Disabled) 5 30 3 5 0 (Disabled) 1 1 30

Expanded Direct Input/Output Status (Read Only)

Passwords (Read/Write Command) Passwords (Read/Write Setting) Passwords (Read/Write)

Passwords (read only actual values)

Passwords (read/write settings)

GE Multilin

C30 Controller System

B-13

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 7 of 39)
ADDR 4040 4048 REGISTER NAME Invoke and Scroll Through User Display Menu Operand LED Test Function LED Test Control Language Flash Message Time Default Message Timeout Default Message Intensity Screen Saver Feature Screen Saver Wait Time Current Cutoff Level Voltage Cutoff Level COM1 minimum response time COM2 minimum response time Modbus Slave Address RS485 Com1 Baud Rate RS485 Com1 Parity RS485 Com2 Baud Rate RS485 Com2 Parity IP Address IP Subnet Mask Gateway IP Address Network Address NSAP DNP Channel 1 Port DNP Channel 2 Port DNP Address Reserved DNP Client Addresses (2 items) TCP Port Number for the Modbus protocol TCP/UDP Port Number for the DNP Protocol TCP Port Number for the HTTP (Web Server) Protocol Main UDP Port Number for the TFTP Protocol Data Transfer UDP Port Numbers for the TFTP Protocol (zero means automatic) (2 items) DNP Unsolicited Responses Function DNP Unsolicited Responses Timeout DNP unsolicited responses maximum retries DNP unsolicited responses destination address Ethernet operation mode DNP current scale factor DNP voltage scale factor DNP power scale factor DNP energy scale factor DNP power scale factor DNP other scale factor DNP current default deadband DNP voltage default deadband DNP power default deadband DNP energy default deadband DNP other default deadband DNP IIN time synchronization bit period RANGE 0 to 65535 0 to 1 0 to 65535 0 to 3 0.5 to 10 10 to 900 0 to 3 0 to 1 1 to 65535 0.002 to 0.02 0.1 to 1 0 to 1000 0 to 1000 1 to 254 0 to 11 0 to 2 0 to 11 0 to 2 0 to 4294967295 0 to 4294967295 0 to 4294967295 --0 to 4 0 to 4 0 to 65519 0 to 1 0 to 4294967295 1 to 65535 1 to 65535 1 to 65535 1 to 65535 0 to 65535 0 to 1 0 to 60 1 to 255 0 to 65519 0 to 1 0 to 8 0 to 8 0 to 8 0 to 8 0 to 8 0 to 8 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 1 to 10080 UNITS --------s s ----min pu V ms ms ----------------------------------------s ----------------------------min STEP 1 1 1 1 0.1 1 1 1 1 0.001 0.1 10 10 1 1 1 1 1 1 1 1 --1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 FORMAT F300 F102 F300 F531 F001 F001 F101 F102 F001 F001 F001 F001 F001 F001 F112 F113 F112 F113 F003 F003 F003 F074 F177 F177 F001 F001 F003 F001 F001 F001 F001 F001 F102 F001 F001 F001 F192 F194 F194 F194 F194 F194 F194 F001 F001 F001 F001 F001 F001

APPENDIX B

DEFAULT 0 0 (Disabled) 0 0 (English) 10 300 0 (25%) 0 (Disabled) 30 20 10 0 0 254 8 (115200) 0 (None) 8 (115200) 0 (None) 56554706 4294966272 56554497 0 0 (None) 0 (None) 1 0 0 502 20000 80 69 0 0 (Disabled) 5 10 1 0 (Half-Duplex) 2 (1) 2 (1) 2 (1) 2 (1) 2 (1) 2 (1) 30000 30000 30000 30000 30000 1440

User Display Invoke (Read/Write Setting) LED Test (Read/Write Setting) 4049 404F 4050 4051 4052 4053 4054 4055 4056 407E 407F 4080 4083 4084 4085 4086 4087 4089 408B 408D 409A 409B 409C 409D 409E 40A3 40A4 40A5 40A6 40A7 40A9 40AA 40AB 40AC 40AD 40AE 40AF 40B0 40B1 40B2 40B3 40B4 40B6 40B8 40BA 40BE 40C0

Preferences (Read/Write Setting)

Communications (Read/Write Setting)

B-14

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 8 of 39)


ADDR 40C1 40C2 40C4 40C6 40C8 40C9 40CA 40E0 40E1 40E2 40E3 40E4 40E6 40E8 40EA 40EC 40EE 40F0 4104 4005 4140 4141 4142 4143 4144 4145 4146 4147 4148 414A 414B 414C 414D 414E 414F 4150 4151 4154 4155 4156 4157 4158 4159 415A 4168 4169 416B 4170 4181 REGISTER NAME DNP message fragment size DNP client address 3 DNP client address 4 DNP client address 5 DNP number of paired binary output control points DNP TCP connection timeout Reserved (22 items) TCP port number for the IEC 60870-5-104 protocol IEC 60870-5-104 protocol function IEC 60870-5-104 protocol common address of ASDU IEC 60870-5-104 protocol cyclic data transmit period IEC 60870-5-104 current default threshold IEC 60870-5-104 voltage default threshold IEC 60870-5-104 power default threshold IEC 60870-5-104 energy default threshold IEC 60870-5-104 power default threshold IEC 60870-5-104 other default threshold IEC 60870-5-104 client address (5 items) IEC 60870-5-104 redundancy port Reserved (59 items) DNP object 1 default variation DNP object 2 default variation DNP object 20 default variation DNP object 21 default variation DNP object 22 default variation DNP object 23 default variation DNP object 30 default variation DNP object 32 default variation Ethernet switch IP address Ethernet switch Modbus IP port number Ethernet switch Port 1 Events Ethernet switch Port 2 Events Ethernet switch Port 3 Events Ethernet switch Port 4 Events Ethernet switch Port 5 Events Ethernet switch Port 6 Events Ethernet switch MAC address Ethernet switch Port 1 Status Ethernet switch Port 2 Status Ethernet switch Port 3 Status Ethernet switch Port 4 Status Ethernet switch Port 5 Status Ethernet switch Port 6 Status Switch Firmware Version Simple Network Time Protocol (SNTP) function Simple Network Time Protocol (SNTP) server IP address Simple Network Time Protocol (SNTP) UDP port number Data Logger Clear Data Logger Channel Settings (16 items) RANGE 30 to 2048 0 to 4294967295 0 to 4294967295 0 to 4294967295 0 to 32 10 to 65535 0 to 1 1 to 65535 0 to 1 0 to 65535 1 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 4294967295 0 to 1 0 to 1 1 to 2 1 to 3 0 to 3 0 to 3 0 to 3 0 to 3 1 to 5 0 to 5 0 to 4294967295 1 to 65535 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 --0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0.00 to 99.99 0 to 1 0 to 4294967295 1 to 65535 0 to 1 --UNITS --------------------s ----------------------------------------------------------------------------STEP 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.01 1 1 1 1 ---

B.4 MEMORY MAPPING

FORMAT F001 F003 F003 F003 F001 F001 F001 F001 F102 F001 F001 F001 F001 F001 F001 F001 F001 F003 F126 F001 F001 F001 F523 F524 F523 F523 F001 F525 F003 F001 F102 F102 F102 F102 F102 F102 F072 F134 F134 F134 F134 F134 F134 F001 F102 F003 F001 F126 F600

DEFAULT 240 0 0 0 0 120 0 2404 0 (Disabled) 0 60 30000 30000 30000 30000 30000 30000 0 0 (No) 0 2 2 0 (1) 0 (1) 0 (1) 0 (1) 1 0 (1) 3232235778 502 0 (Disabled) 0 (Disabled) 0 (Disabled) 0 (Disabled) 0 (Disabled) 0 (Disabled) 0 0 (Fail) 0 (Fail) 0 (Fail) 0 (Fail) 0 (Fail) 0 (Fail) 0 0 (Disabled) 0 123 0 (No) 0

Ethernet switch (Read/Write Setting)

Ethernet switch (Read Only Actual Values)

Simple Network Time Protocol (Read/Write Setting)

Data Logger Commands (Read/Write Command) Data Logger (Read/Write Setting)

GE Multilin

C30 Controller System

B-15

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 9 of 39)
ADDR 4191 4192 4193 41A0 41A2 41A4 41A6 41A7 41A8 41A9 41AA 41AB 41AC 41AD 41AE 41AF 41B0 41B1 41C0 41C1 41C2 41C3 41C4 41D0 4200 4260 4261 4280 4281 4282 4284 4286 4288 428A 428C 428E 4290 4292 4294 4296 4298 429A 429C 429E 42A0 42A2 42A4 42A6 42A8 REGISTER NAME Data Logger Mode Data Logger Trigger Data Logger Rate Real Time Clock Set Time SR Date Format SR Time Format IRIG-B Signal Type Clock Events Enable / Disable Time Zone Offset from UTC Daylight Savings Time (DST) Function Daylight Savings Time (DST) Start Month Daylight Savings Time (DST) Start Day Daylight Savings Time (DST) Start Day Instance Daylight Savings Time (DST) Start Hour Daylight Savings Time (DST) Stop Month Daylight Savings Time (DST) Stop Day Daylight Savings Time (DST) Stop Day Instance Daylight Savings Time (DST) Stop Hour Oscillography Number of Records Oscillography Trigger Mode Oscillography Trigger Position Oscillography Trigger Source Oscillography AC Input Waveforms Oscillography Analog Channel n (16 items) Oscillography Digital Channel n (63 items) Trip LED Input FlexLogic Operand Alarm LED Input FlexLogic Operand FlexLogic Operand to Activate LED User LED type (latched or self-resetting) ...Repeated for User-Programmable LED 2 ...Repeated for User-Programmable LED 3 ...Repeated for User-Programmable LED 4 ...Repeated for User-Programmable LED 5 ...Repeated for User-Programmable LED 6 ...Repeated for User-Programmable LED 7 ...Repeated for User-Programmable LED 8 ...Repeated for User-Programmable LED 9 ...Repeated for User-Programmable LED 10 ...Repeated for User-Programmable LED 11 ...Repeated for User-Programmable LED 12 ...Repeated for User-Programmable LED 13 ...Repeated for User-Programmable LED 14 ...Repeated for User-Programmable LED 15 ...Repeated for User-Programmable LED 16 ...Repeated for User-Programmable LED 17 ...Repeated for User-Programmable LED 18 ...Repeated for User-Programmable LED 19 ...Repeated for User-Programmable LED 20 ...Repeated for User-Programmable LED 21 RANGE 0 to 1 0 to 65535 15 to 3600000 0 to 235959 0 to 4294967295 0 to 4294967295 0 to 2 0 to 1 24 to 24 0 to 1 0 to 11 0 to 6 0 to 4 0 to 23 0 to 11 0 to 6 0 to 4 0 to 23 1 to 64 0 to 1 0 to 100 0 to 65535 0 to 4 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 1 UNITS ----ms ----------hours ----------------------% ----------------STEP 1 1 1 1 1 1 1 1 0.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 FORMAT F260 F300 F003 F050 F051 F052 F114 F102 F002 F102 F237 F238 F239 F001 F237 F238 F239 F001 F001 F118 F001 F300 F183 F600 F300 F300 F300 F300 F127

APPENDIX B

DEFAULT 0 (continuous) 0 60000 0 0 0 0 (None) 0 (Disabled) 0 0 (Disabled) 0 (January) 0 (Sunday) 0 (First) 2 0 (January) 0 (Sunday) 0 (First) 2 15 0 (Auto. Overwrite) 50 0 2 (16 samples/cycle) 0 0 0 0 0 1 (Self-Reset)

Clock (Read/Write Command)

Clock (Read/Write Setting)

Oscillography (Read/Write Setting)

Trip and Alarm LEDs (Read/Write Setting)

User Programmable LEDs (Read/Write Setting) (48 modules)

B-16

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 10 of 39)


ADDR 42AA 42AC 42AE 42B0 42B2 42B4 42B6 42B8 42BA 42BC 42BE 42C0 42C2 42C4 42C6 42C8 42CA 42CC 42CE 42D0 42D2 42D4 42D6 42D8 42DA 42DC 42DE 43E0 43E1 4441 4442 4443 4444 4445 4446 4447 4448 4449 4700 4701 4704 4705 4706 4707 4708 4709 470A 470B 470D 470E 4710 REGISTER NAME ...Repeated for User-Programmable LED 22 ...Repeated for User-Programmable LED 23 ...Repeated for User-Programmable LED 24 ...Repeated for User-Programmable LED 25 ...Repeated for User-Programmable LED 26 ...Repeated for User-Programmable LED 27 ...Repeated for User-Programmable LED 28 ...Repeated for User-Programmable LED 29 ...Repeated for User-Programmable LED 30 ...Repeated for User-Programmable LED 31 ...Repeated for User-Programmable LED 32 ...Repeated for User-Programmable LED 33 ...Repeated for User-Programmable LED 34 ...Repeated for User-Programmable LED 35 ...Repeated for User-Programmable LED 36 ...Repeated for User-Programmable LED 37 ...Repeated for User-Programmable LED 38 ...Repeated for User-Programmable LED 39 ...Repeated for User-Programmable LED 40 ...Repeated for User-Programmable LED 41 ...Repeated for User-Programmable LED 42 ...Repeated for User-Programmable LED 43 ...Repeated for User-Programmable LED 44 ...Repeated for User-Programmable LED 45 ...Repeated for User-Programmable LED 46 ...Repeated for User-Programmable LED 47 ...Repeated for User-Programmable LED 48 Relay Programmed State Relay Name User Programmable Detect Ring Break Function User Programmable Direct Device Off Function User Programmable Remote Device Off Function User Programmable Primary Ethernet Fail Function User Programmable Secondary Ethernet Fail Function User Programmable Battery Fail Function User Programmable SNTP Fail Function User Programmable IRIG-B Fail Function User Programmable Ethernet Switch Fail Function Breaker 1 function Breaker 1 name Breaker 1 mode Breaker 1 open Breaker 1 close Breaker 1 phase A / three-pole closed Breaker 1 phase B closed Breaker 1 phase C closed Breaker 1 external alarm Breaker 1 alarm delay Breaker 1 pushbutton control Breaker 1 manual close recall time Breaker 1 out of service 0 to 1 --0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 0 to 1 --0 to 1 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 1000000 0 to 1 0 to 1000000 0 to 65535 ----------------------------------------s --s --1 --1 1 1 1 1 1 1 1 1 1 --1 1 1 1 1 1 1 0.001 1 0.001 1 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Installation (Read/Write Setting) F133 F202 F102 F102 F102 F102 F102 F102 F102 F102 F102 F102 F206 F157 F300 F300 F300 F300 F300 F300 F003 F102 F003 F300 0 (Not Programmed) Relay-1 1 (Enabled) 1 (Enabled) 1 (Enabled) 0 (Disabled) 0 (Disabled) 1 (Enabled) 1 (Enabled) 1 (Enabled) 0 (Disabled) 0 (Disabled) Bkr 1" 0 (3-Pole) 0 0 0 0 0 0 0 0 (Disabled) 0 0

User Programmable Self Tests (Read/Write Setting)

Breaker control (read/write settings)

GE Multilin

C30 Controller System

B-17

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 11 of 39)
ADDR 4711 4712 4713 4714 4715 4716 4717 4718 4719 4A00 4C00 4C0A 4C14 4C19 4C20 4C40 4C60 4C80 4CA0 4CC0 4CE0 4D00 4D20 4D40 4D60 4D80 4DA0 4DC0 4DE0 4E00 4E01 4E0B 4E15 4E1F 4E20 4E21 4E22 4E23 4E24 4E25 4E26 4E27 4E28 4E29 4E2A 4E54 4E7E 4EA8 4ED2 4EFC 4F26 REGISTER NAME Breaker 1 block open Breaker 1 block close Breaker 1 phase A / three-pole opened Breaker 1 phase B opened Breaker 1 phase C opened Breaker 1 operate time Breaker 1 events Reserved ...Repeated for breaker 2 Modbus Address Settings for User Map (256 items) User-Definable Display 1 Top Line Text User-Definable Display 1 Bottom Line Text Modbus Addresses of Display 1 Items (5 items) Reserved (7 items) ...Repeated for User-Definable Display 2 ...Repeated for User-Definable Display 3 ...Repeated for User-Definable Display 4 ...Repeated for User-Definable Display 5 ...Repeated for User-Definable Display 6 ...Repeated for User-Definable Display 7 ...Repeated for User-Definable Display 8 ...Repeated for User-Definable Display 9 ...Repeated for User-Definable Display 10 ...Repeated for User-Definable Display 11 ...Repeated for User-Definable Display 12 ...Repeated for User-Definable Display 13 ...Repeated for User-Definable Display 14 ...Repeated for User-Definable Display 15 ...Repeated for User-Definable Display 16 User Programmable Pushbutton 1 Function User Programmable Pushbutton 1 Top Line User Programmable Pushbutton 1 On Text User Programmable Pushbutton 1 Off Text User Programmable Pushbutton 1 Drop-Out Time User Programmable Pushbutton 1 Target User Programmable Pushbutton 1 Events User Programmable Pushbutton 1 LED Operand User Programmable Pushbutton 1 Autoreset Delay User Programmable Pushbutton 1 Autoreset Function User Programmable Pushbutton 1 Local Lock User Programmable Pushbutton 1 Message Priority User Programmable Pushbutton 1 Remote Lock User Programmable Pushbutton 1 Reset User Programmable Pushbutton 1 Set ...Repeated for User Programmable Pushbutton 2 ...Repeated for User Programmable Pushbutton 3 ...Repeated for User Programmable Pushbutton 4 ...Repeated for User Programmable Pushbutton 5 ...Repeated for User Programmable Pushbutton 6 ...Repeated for User Programmable Pushbutton 7 ...Repeated for User Programmable Pushbutton 8 0 to 2 ------0 to 60 0 to 2 0 to 1 0 to 65535 0 to 600 0 to 1 0 to 65535 0 to 2 0 to 65535 0 to 65535 0 to 65535 --------s ------s ------------1 ------0.05 1 1 1 0.05 1 1 1 1 1 1 F109 F202 F202 F202 F001 F109 F102 F300 F001 F102 F300 F220 F300 F300 F300 0 to 65535 ----0 to 65535 ------------1 ----1 --F001 F202 F202 F001 F001 RANGE 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 2 0 to 1 --UNITS ----------s ----STEP 1 1 1 1 1 0.001 1 --FORMAT F300 F300 F300 F300 F300 F001 F102 ---

APPENDIX B

DEFAULT 0 0 0 0 0 70 0 (Disabled) ---

Modbus User Map (Read/Write Setting) 0 0 0 User Displays Settings (Read/Write Setting) (16 modules)

User Programmable Pushbuttons (Read/Write Setting) (12 modules) 2 (Disabled) (none) (none) (none) 0 0 (Self-reset) 0 (Disabled) 0 0 0 (Disabled) 0 0 (Disabled) 0 0 0

B-18

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 12 of 39)


ADDR 4F50 4F7A 4FA4 4FCE 5000 5400 5401 5407 5413 5426 5439 544C 545F 5472 5485 5498 54AB 54BE 54D1 54E4 54F7 550A 551D 5530 5543 5556 5569 557C 558F 55A2 55B5 55C8 55DB 55EE 5601 5614 5627 563A 564D 5660 5673 5686 5699 56AC 56BF 56D2 56E5 56F8 570B 571E 5731 5744 REGISTER NAME ...Repeated for User Programmable Pushbutton 9 ...Repeated for User Programmable Pushbutton 10 ...Repeated for User Programmable Pushbutton 11 ...Repeated for User Programmable Pushbutton 12 FlexLogic Entry (512 items) RTD Input 1 Function RTD Input 1 ID RTD Input 1 Type ...Repeated for RTD Input 2 ...Repeated for RTD Input 3 ...Repeated for RTD Input 4 ...Repeated for RTD Input 5 ...Repeated for RTD Input 6 ...Repeated for RTD Input 7 ...Repeated for RTD Input 8 ...Repeated for RTD Input 9 ...Repeated for RTD Input 10 ...Repeated for RTD Input 11 ...Repeated for RTD Input 12 ...Repeated for RTD Input 13 ...Repeated for RTD Input 14 ...Repeated for RTD Input 15 ...Repeated for RTD Input 16 ...Repeated for RTD Input 17 ...Repeated for RTD Input 18 ...Repeated for RTD Input 19 ...Repeated for RTD Input 20 ...Repeated for RTD Input 21 ...Repeated for RTD Input 22 ...Repeated for RTD Input 23 ...Repeated for RTD Input 24 ...Repeated for RTD Input 25 ...Repeated for RTD Input 26 ...Repeated for RTD Input 27 ...Repeated for RTD Input 28 ...Repeated for RTD Input 29 ...Repeated for RTD Input 30 ...Repeated for RTD Input 31 ...Repeated for RTD Input 32 ...Repeated for RTD Input 33 ...Repeated for RTD Input 34 ...Repeated for RTD Input 35 ...Repeated for RTD Input 36 ...Repeated for RTD Input 37 ...Repeated for RTD Input 38 ...Repeated for RTD Input 39 ...Repeated for RTD Input 40 ...Repeated for RTD Input 41 ...Repeated for RTD Input 42 ...Repeated for RTD Input 43 ...Repeated for RTD Input 44 ...Repeated for RTD Input 45 0 to 65535 0 to 1 --0 to 3 --------1 1 --1 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Flexlogic (Read/Write Setting) F300 F102 F205 F174 16384 0 (Disabled) RTD Ip 1 0 (100 ohm Platinum) RTD Inputs (Read/Write Setting) (48 modules)

GE Multilin

C30 Controller System

B-19

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 13 of 39)
ADDR 5757 576A 577D 5800 5801 5802 5803 5808 5810 5818 5820 5828 5830 5838 5840 5848 5850 5858 5860 5868 5870 5878 5880 5888 5890 5898 58A0 58A8 58B0 58B8 58C0 58C8 58D0 58D8 58E0 58E8 58F0 58F8 7300 7301 7307 730B 730E 730F 7311 7313 7318 7330 7348 7360 7378 7390 REGISTER NAME ...Repeated for RTD Input 46 ...Repeated for RTD Input 47 ...Repeated for RTD Input 48 FlexLogic Timer 1 Type FlexLogic Timer 1 Pickup Delay FlexLogic Timer 1 Dropout Delay Reserved (5 items) ...Repeated for FlexLogic Timer 2 ...Repeated for FlexLogic Timer 3 ...Repeated for FlexLogic Timer 4 ...Repeated for FlexLogic Timer 5 ...Repeated for FlexLogic Timer 6 ...Repeated for FlexLogic Timer 7 ...Repeated for FlexLogic Timer 8 ...Repeated for FlexLogic Timer 9 ...Repeated for FlexLogic Timer 10 ...Repeated for FlexLogic Timer 11 ...Repeated for FlexLogic Timer 12 ...Repeated for FlexLogic Timer 13 ...Repeated for FlexLogic Timer 14 ...Repeated for FlexLogic Timer 15 ...Repeated for FlexLogic Timer 16 ...Repeated for FlexLogic Timer 17 ...Repeated for FlexLogic Timer 18 ...Repeated for FlexLogic Timer 19 ...Repeated for FlexLogic Timer 20 ...Repeated for FlexLogic Timer 21 ...Repeated for FlexLogic Timer 22 ...Repeated for FlexLogic Timer 23 ...Repeated for FlexLogic Timer 24 ...Repeated for FlexLogic Timer 25 ...Repeated for FlexLogic Timer 26 ...Repeated for FlexLogic Timer 27 ...Repeated for FlexLogic Timer 28 ...Repeated for FlexLogic Timer 29 ...Repeated for FlexLogic Timer 30 ...Repeated for FlexLogic Timer 31 ...Repeated for FlexLogic Timer 32 dcmA Inputs 1 Function dcmA Inputs 1 ID Reserved 1 (4 items) dcmA Inputs 1 Units dcmA Inputs 1 Range dcmA Inputs 1 Minimum Value dcmA Inputs 1 Maximum Value Reserved (5 items) ...Repeated for dcmA Inputs 2 ...Repeated for dcmA Inputs 3 ...Repeated for dcmA Inputs 4 ...Repeated for dcmA Inputs 5 ...Repeated for dcmA Inputs 6 ...Repeated for dcmA Inputs 7 0 to 1 --0 to 65535 --0 to 6 -9999.999 to 9999.999 -9999.999 to 9999.999 0 to 65535 ----------------1 --1 --1 0.001 0.001 1 F102 F205 F001 F206 F173 F004 F004 F001 0 to 2 0 to 60000 0 to 60000 0 to 65535 --------1 1 1 1 F129 F001 F001 F001 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Flexlogic Timers (Read/Write Setting) (32 modules)

0 (millisecond) 0 0 0

dcmA Inputs (Read/Write Setting) (24 modules) 0 (Disabled) DCMA I 1" 0 mA 6 (4 to 20 mA) 4000 20000 0

B-20

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 14 of 39)


ADDR 73A8 73C0 73D8 73F0 7408 7420 7438 7450 7468 7480 7498 74B0 74C8 74E0 74F8 7510 7528 7540 7541 7544 7545 7546 7547 7548 7549 754A 754B 754C 754D 754E 754F 7550 7552 7553 7555 756A 757F 7594 75A9 75BE 75D3 7B60 7B61 7B6B 7B75 7B7F 7B80 7B81 7B82 7B83 7B84 7B85 REGISTER NAME ...Repeated for dcmA Inputs 8 ...Repeated for dcmA Inputs 9 ...Repeated for dcmA Inputs 10 ...Repeated for dcmA Inputs 11 ...Repeated for dcmA Inputs 12 ...Repeated for dcmA Inputs 13 ...Repeated for dcmA Inputs 14 ...Repeated for dcmA Inputs 15 ...Repeated for dcmA Inputs 16 ...Repeated for dcmA Inputs 17 ...Repeated for dcmA Inputs 18 ...Repeated for dcmA Inputs 19 ...Repeated for dcmA Inputs 20 ...Repeated for dcmA Inputs 21 ...Repeated for dcmA Inputs 22 ...Repeated for dcmA Inputs 23 ...Repeated for dcmA Inputs 24 Disconnect switch 1 function Disconnect switch 1 name Disconnect switch 1 mode Disconnect switch 1 open Disconnect switch 1 block open Disconnect switch 1 close Disconnect switch 1 block close Disconnect switch 1 phase A / three-pole closed Disconnect switch 1 phase A / three-pole opened Disconnect switch 1 phase B closed Disconnect switch 1 phase B opened Disconnect switch 1 phase C closed Disconnect switch 1 phase C opened Disconnect switch 1 operate time Disconnect switch 1 alarm delay Disconnect switch 1 events Reserved (2 items) ...Repeated for disconnect switch 2 ...Repeated for disconnect switch 3 ...Repeated for disconnect switch 4 ...Repeated for disconnect switch 5 ...Repeated for disconnect switch 6 ...Repeated for disconnect switch 7 ...Repeated for disconnect switch 8 User Programmable Pushbutton 1 Function User Programmable Pushbutton 1 Top Line User Programmable Pushbutton 1 On Text User Programmable Pushbutton 1 Off Text User Programmable Pushbutton 1 Drop-Out Time User Programmable Pushbutton 1 Target User Programmable Pushbutton 1 Events User Programmable Pushbutton 1 LED Operand User Programmable Pushbutton 1 Autoreset Delay User Programmable Pushbutton 1 Autoreset Function User Programmable Pushbutton 1 Local Lock 0 to 2 ------0 to 60 0 to 2 0 to 1 0 to 65535 0 to 600 0 to 1 0 to 65535 --------s ------s ----1 ------0.05 1 1 1 0.05 1 1 0 to 1 --0 to 1 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 2 0 to 1000000 0 to 1 ----------------------------s s ----1 --1 1 1 1 1 1 1 1 1 1 1 0.001 0.001 1 --RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Disconnect switches (read/write settings) F102 F206 F157 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F001 F003 F102 --0 (Disabled) SW 1" 0 (3-Pole) 0 0 0 0 0 0 0 0 0 0 70 0 0 (Disabled) ---

User Programmable Pushbuttons (Read/Write Setting) (16 modules) F109 F202 F202 F202 F001 F109 F102 F300 F001 F102 F300 2 (Disabled) (none) (none) (none) 0 0 (Self-reset) 0 (Disabled) 0 0 0 (Disabled) 0

GE Multilin

C30 Controller System

B-21

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 15 of 39)
ADDR 7B86 7B87 7B88 7B89 7B8A 7B8B 7BB6 7BE1 7C0C 7C37 7C62 7C8D 7CB8 7CE3 7D0E 7D39 7D64 7D8F 7DBA 7DE5 8300 8301 8309 8311 8312 8318 8330 8348 8360 8378 83E0 83E1 83E3 83F0 83F1 83F3 83F4 8400 8401 8403 8404 8418 8500 8501 8503 8504 8536 8568 REGISTER NAME User Programmable Pushbutton 1 Message Priority User Programmable Pushbutton 1 Remote Lock User Programmable Pushbutton 1 Reset User Programmable Pushbutton 1 Set User Programmable Pushbutton 1 Hold ...Repeated for User Programmable Pushbutton 2 ...Repeated for User Programmable Pushbutton 3 ...Repeated for User Programmable Pushbutton 4 ...Repeated for User Programmable Pushbutton 5 ...Repeated for User Programmable Pushbutton 6 ...Repeated for User Programmable Pushbutton 7 ...Repeated for User Programmable Pushbutton 8 ...Repeated for User Programmable Pushbutton 9 ...Repeated for User Programmable Pushbutton 10 ...Repeated for User Programmable Pushbutton 11 ...Repeated for User Programmable Pushbutton 12 ...Repeated for User Programmable Pushbutton 13 ...Repeated for User Programmable Pushbutton 14 ...Repeated for User Programmable Pushbutton 15 ...Repeated for User Programmable Pushbutton 16 Switch 1 Function Switch 1 Argument A Bits (8 items) Switch 1 Argument B Bits (8 items) Switch 1 Control Reserved (6 items) ...Repeated for Switch 2 ...Repeated for Switch 3 ...Repeated for Switch 4 ...Repeated for Switch 5 ...Repeated for Switch 6 EGD Fast Producer Exchange 1 Signature EGD Fast Producer Exchange 1 Configuration Time EGD Fast Producer Exchange 1 Size EGD Slow Producer Exchange 1 Signature EGD Slow Producer Exchange 1 Configuration Time EGD Slow Producer Exchange 1 Size ...Repeated for module number 2 EGD Fast Producer Exchange 1 Function EGD Fast Producer Exchange 1 Destination EGD Fast Producer Exchange 1 Data Rate EGD Fast Producer Exchange 1 Data Item 1 (20 items) Reserved (80 items) EGD Slow Producer Exchange 1 Function EGD Fast Producer Exchange 1 Destination EGD Slow Producer Exchange 1 Data Rate EGD Slow Producer Exchange 1 Data Item 1 (50 items) Reserved (50 items) ...Repeated for EGD Exchange 2 0 to 1 0 to 4294967295 50 to 1000 0 to 65535 --0 to 1 0 to 4294967295 500 to 1000 0 to 65535 ------ms --------ms ----1 1 50 1 --1 1 50 1 --F102 F003 F001 F001 F001 F102 F003 F001 F001 F001 0 to 65535 0 to 4294967295 0 to 65535 0 to 65535 0 to 4294967295 0 to 65535 ------------1 --1 1 --1 F001 F003 F001 F001 F003 F001 0 to 1 0 to 65535 0 to 65535 0 to 65535 0 to 65535 ----------1 1 1 1 1 F102 F300 F300 F300 F001 RANGE 0 to 2 0 to 65535 0 to 65535 0 to 65535 0 to 10 UNITS --------s STEP 1 1 1 1 0.1 FORMAT F220 F300 F300 F300 F001

APPENDIX B

DEFAULT 0 (Disabled) 0 0 0 1

Switch (Read/Write Setting) (6 modules) 0 (Disabled) 0 0 0 0

EGD Fast Production Status (Read Only) 0 0 0 0 0 0

EGD Slow Production Status (Read Only) (2 modules)

EGD Fast Production (Read/Write Setting) 0 (Disabled) 0 1000 0 0 0 (Disabled) 0 1000 0 0

EGD Slow Production (Read/Write Setting) (2 modules)

B-22

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 16 of 39)


ADDR 8800 8A00 8A01 8A09 8A0A 8A0C 8A0E 8A0F 8A10 8A11 8A12 8A14 8A28 8A3C 8A50 8A64 8A78 8A8C 8AA0 8AB4 8AC8 8ADC 8AF0 8B04 8B18 8B2C 8B40 8B54 8B68 8B7C 8B90 8BA4 8BB8 8BCC 8BE0 8BF4 8C08 8C1C 8C30 8C44 8C58 8C6C 8C80 8C94 8CA8 8CBC 8CD0 8CE4 8CF8 8D0C 8D20 8D34 REGISTER NAME FlexState Parameters (256 items) Digital Element 1 Function Digital Element 1 Name Digital Element 1 Input Digital Element 1 Pickup Delay Digital Element 1 Reset Delay Digital Element 1 Block Digital Element 1 Target Digital Element 1 Events Digital Element 1 Pickup LED Reserved (2 items) ...Repeated for Digital Element 2 ...Repeated for Digital Element 3 ...Repeated for Digital Element 4 ...Repeated for Digital Element 5 ...Repeated for Digital Element 6 ...Repeated for Digital Element 7 ...Repeated for Digital Element 8 ...Repeated for Digital Element 9 ...Repeated for Digital Element 10 ...Repeated for Digital Element 11 ...Repeated for Digital Element 12 ...Repeated for Digital Element 13 ...Repeated for Digital Element 14 ...Repeated for Digital Element 15 ...Repeated for Digital Element 16 ...Repeated for Digital Element 17 ...Repeated for Digital Element 18 ...Repeated for Digital Element 19 ...Repeated for Digital Element 20 ...Repeated for Digital Element 21 ...Repeated for Digital Element 22 ...Repeated for Digital Element 23 ...Repeated for Digital Element 24 ...Repeated for Digital Element 25 ...Repeated for Digital Element 26 ...Repeated for Digital Element 27 ...Repeated for Digital Element 28 ...Repeated for Digital Element 29 ...Repeated for Digital Element 30 ...Repeated for Digital Element 31 ...Repeated for Digital Element 32 ...Repeated for Digital Element 33 ...Repeated for Digital Element 34 ...Repeated for Digital Element 35 ...Repeated for Digital Element 36 ...Repeated for Digital Element 37 ...Repeated for Digital Element 38 ...Repeated for Digital Element 39 ...Repeated for Digital Element 40 ...Repeated for Digital Element 41 ...Repeated for Digital Element 42 RANGE --0 to 1 --0 to 65535 0 to 999999.999 0 to 999999.999 0 to 65535 0 to 2 0 to 1 0 to 1 --UNITS --------s s ----------STEP --1 --1 0.001 0.001 1 1 1 1 ---

B.4 MEMORY MAPPING

FORMAT F300 F102 F203 F300 F003 F003 F300 F109 F102 F102 F001

DEFAULT 0 0 (Disabled) Dig Element 1 0 0 0 0 0 (Self-reset) 0 (Disabled) 1 (Enabled) 0

FlexState Settings (Read/Write Setting) Digital Elements (Read/Write Setting) (48 modules)

GE Multilin

C30 Controller System

B-23

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 17 of 39)
ADDR 8D48 8D5C 8D70 8D84 8D98 8DAC 8E00 8E01 8E02 8E03 8E04 8E05 8E06 8E07 8E08 8E09 8E0A 8E0B 8E0C 8E0D 8E0E 8E0F 8E10 8E11 8E12 8E13 8E14 8E15 8E16 8E16 8E18 8E20 8E40 8E60 8E80 8EA0 9000 9001 9004 9005 9006 9007 9008 9009 900A 900C 900D 900F 9010 9011 9012 9013 REGISTER NAME ...Repeated for Digital Element 43 ...Repeated for Digital Element 44 ...Repeated for Digital Element 45 ...Repeated for Digital Element 46 ...Repeated for Digital Element 47 ...Repeated for Digital Element 48 Trip Bus 1 Function Trip Bus 1 Block Trip Bus 1 Pickup Delay Trip Bus 1 Reset Delay Trip Bus 1 Input 1 Trip Bus 1 Input 2 Trip Bus 1 Input 3 Trip Bus 1 Input 4 Trip Bus 1 Input 5 Trip Bus 1 Input 6 Trip Bus 1 Input 7 Trip Bus 1 Input 8 Trip Bus 1 Input 9 Trip Bus 1 Input 10 Trip Bus 1 Input 11 Trip Bus 1 Input 12 Trip Bus 1 Input 13 Trip Bus 1 Input 14 Trip Bus 1 Input 15 Trip Bus 1 Input 16 Trip Bus 1 Latching Trip Bus 1 Reset Trip Bus 1 Target Trip Bus 1 Events Reserved (8 items) ...Repeated for Trip Bus 2 ...Repeated for Trip Bus 3 ...Repeated for Trip Bus 4 ...Repeated for Trip Bus 5 ...Repeated for Trip Bus 6 FlexElement 1 Function FlexElement 1 Name FlexElement 1 InputP FlexElement 1 InputM FlexElement 1 Compare FlexElement 1 Input FlexElement 1 Direction FlexElement 1 Hysteresis FlexElement 1 Pickup FlexElement 1 DeltaT Units FlexElement 1 DeltaT FlexElement 1 Pickup Delay FlexElement 1 Reset Delay FlexElement 1 Block FlexElement 1 Target FlexElement 1 Events 0 to 1 --0 to 65535 0 to 65535 0 to 1 0 to 1 0 to 1 0.1 to 50 -90 to 90 0 to 2 20 to 86400 0 to 65.535 0 to 65.535 0 to 65535 0 to 2 0 to 1 --------------% pu ----s s ------1 --1 1 1 1 1 0.1 0.001 1 1 0.001 0.001 1 1 1 F102 F206 F600 F600 F516 F515 F517 F001 F004 F518 F003 F001 F001 F300 F109 F102 0 to 1 --0 to 600 0 to 600 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 1 0 to 65535 0 to 2 0 to 1 ------s s ------------------------------------------1 --0.01 0.01 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 --F102 F300 F001 F001 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F300 F102 F300 F109 F102 F001 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Trip Bus (Read/Write Setting) 0 (Disabled) 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 (Disabled) 0 0 (Self-reset) 0 (Disabled) 0

FlexElement (Read/Write Setting) (16 modules) 0 (Disabled) FxE 1 0 0 0 (LEVEL) 0 (SIGNED) 0 (OVER) 30 1000 0 (Milliseconds) 20 0 0 0 0 (Self-reset) 0 (Disabled)

B-24

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 18 of 39)


ADDR 9014 9028 903C 9050 9064 9078 908C 90A0 90B4 90C8 90DC 90F0 9104 9118 912C 9300 9301 9302 9304 9306 930C 9312 9318 931E 9324 932A 9330 9336 933C 9342 9348 934E 9354 935A 9360 9366 936C 9372 9378 937E 9384 938A 9400 9406 940C 9418 9424 9430 943C 9448 9454 9460 REGISTER NAME ...Repeated for FlexElement 2 ...Repeated for FlexElement 3 ...Repeated for FlexElement 4 ...Repeated for FlexElement 5 ...Repeated for FlexElement 6 ...Repeated for FlexElement 7 ...Repeated for FlexElement 8 ...Repeated for FlexElement 9 ...Repeated for FlexElement 10 ...Repeated for FlexElement 11 ...Repeated for FlexElement 12 ...Repeated for FlexElement 13 ...Repeated for FlexElement 14 ...Repeated for FlexElement 15 ...Repeated for FlexElement 16 dcmA Output 1 Source dcmA Output 1 Range dcmA Output 1 Minimum dcmA Output 1 Maximum ...Repeated for dcmA Output 2 ...Repeated for dcmA Output 3 ...Repeated for dcmA Output 4 ...Repeated for dcmA Output 5 ...Repeated for dcmA Output 6 ...Repeated for dcmA Output 7 ...Repeated for dcmA Output 8 ...Repeated for dcmA Output 9 ...Repeated for dcmA Output 10 ...Repeated for dcmA Output 11 ...Repeated for dcmA Output 12 ...Repeated for dcmA Output 13 ...Repeated for dcmA Output 14 ...Repeated for dcmA Output 15 ...Repeated for dcmA Output 16 ...Repeated for dcmA Output 17 ...Repeated for dcmA Output 18 ...Repeated for dcmA Output 19 ...Repeated for dcmA Output 20 ...Repeated for dcmA Output 21 ...Repeated for dcmA Output 22 ...Repeated for dcmA Output 23 ...Repeated for dcmA Output 24 Direct Input 1 Name Direct Output 1 Name ...Repeated for Direct Input/Output 2 ...Repeated for Direct Input/Output 3 ...Repeated for Direct Input/Output 4 ...Repeated for Direct Input/Output 5 ...Repeated for Direct Input/Output 6 ...Repeated for Direct Input/Output 7 ...Repeated for Direct Input/Output 8 ...Repeated for Direct Input/Output 9 0 to 96 1 to 96 ----1 1 0 to 65535 0 to 2 90 to 90 90 to 90 ----pu pu 1 1 0.001 0.001 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

dcmA Outputs (Read/Write Setting) (24 modules) F600 F522 F004 F004 0 0 (1 to 1 mA) 0 1000

Direct Input/Output Names (Read/Write Setting) (96 modules) F205 F205 Dir Ip 1 Dir Out 1

GE Multilin

C30 Controller System

B-25

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 19 of 39)
ADDR 946C 9478 9484 9490 949C 94A8 94B4 94C0 94CC 94D8 94E4 94F0 94FC 9508 9514 9520 952C 9538 9544 9550 955C 9568 9574 9910 9912 9913 9916 9919 991C 991F 9922 9925 9928 992B 992E 9931 9934 9937 993A 993D 9A01 9A03 9A05 9A07 9A09 9A0B 9A0D 9A0F 9B00 9B01 9B02 REGISTER NAME ...Repeated for Direct Input/Output 10 ...Repeated for Direct Input/Output 11 ...Repeated for Direct Input/Output 12 ...Repeated for Direct Input/Output 13 ...Repeated for Direct Input/Output 14 ...Repeated for Direct Input/Output 15 ...Repeated for Direct Input/Output 16 ...Repeated for Direct Input/Output 17 ...Repeated for Direct Input/Output 18 ...Repeated for Direct Input/Output 19 ...Repeated for Direct Input/Output 20 ...Repeated for Direct Input/Output 21 ...Repeated for Direct Input/Output 22 ...Repeated for Direct Input/Output 23 ...Repeated for Direct Input/Output 24 ...Repeated for Direct Input/Output 25 ...Repeated for Direct Input/Output 26 ...Repeated for Direct Input/Output 27 ...Repeated for Direct Input/Output 28 ...Repeated for Direct Input/Output 29 ...Repeated for Direct Input/Output 30 ...Repeated for Direct Input/Output 31 ...Repeated for Direct Input/Output 32 IEC61850 GOOSE UInteger 1 default value IEC61850 GOOSE UInteger input 1 mode ...Repeated for IEC61850 GOOSE UInteger 2 ...Repeated for IEC61850 GOOSE UInteger 3 ...Repeated for IEC61850 GOOSE UInteger 4 ...Repeated for IEC61850 GOOSE UInteger 5 ...Repeated for IEC61850 GOOSE UInteger 6 ...Repeated for IEC61850 GOOSE UInteger 7 ...Repeated for IEC61850 GOOSE UInteger 8 ...Repeated for IEC61850 GOOSE UInteger 9 ...Repeated for IEC61850 GOOSE UInteger 10 ...Repeated for IEC61850 GOOSE UInteger 11 ...Repeated for IEC61850 GOOSE UInteger 12 ...Repeated for IEC61850 GOOSE UInteger 13 ...Repeated for IEC61850 GOOSE UInteger 14 ...Repeated for IEC61850 GOOSE UInteger 15 ...Repeated for IEC61850 GOOSE UInteger 16 FlexElement 1 Actual FlexElement 2 Actual FlexElement 3 Actual FlexElement 4 Actual FlexElement 5 Actual FlexElement 6 Actual FlexElement 7 Actual FlexElement 8 Actual Teleprotection Function Teleprotection Number of Terminals Teleprotection Number of Channels
-2147483.647 to 2147483.647 -2147483.647 to 2147483.647 -2147483.647 to 2147483.647 -2147483.647 to 2147483.647 -2147483.647 to 2147483.647 -2147483.647 to 2147483.647 -2147483.647 to 2147483.647 -2147483.647 to 2147483.647

APPENDIX B

RANGE

UNITS

STEP

FORMAT

DEFAULT

IEC 61850 received integers (read/write setting registers) 0 to 429496295 0 to 1 ----1 1 F003 F491 1000 0 (Default Value)

FlexElement Actuals (Read Only) (16 modules) ----------------------0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 1 1 1 F004 F004 F004 F004 F004 F004 F004 F004 F102 F001 F001 0 0 0 0 0 0 0 0 0 (Disabled) 2 1

Teleprotection Inputs/Outputs (Read/Write Settings) 0 to 1 2 to 3 1 to 2

B-26

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 20 of 39)


ADDR 9B03 9B04 9B05 9B06 9B10 9B30 9B50 9B70 9B90 9B91 9B92 9B93 9B94 9B95 9BA0 9BA1 9BB0 9BC0 A210 A211 A280 A281 A282 A283 A284 A285 A286 A287 A288 A289 A28A A28B A28C A28D A28E A298 A300 A400 A700 A701 A702 A703 A704 A705 A706 A70A A714 A71E REGISTER NAME Teleprotection Local Relay ID Teleprotection Terminal 1 ID Teleprotection Terminal 2 ID Reserved (10 items) Teleprotection Input 1-n Default States (16 items) Teleprotection Input 2-n Default States (16 items) Teleprotection Output 1-n Operand (16 items) Teleprotection Output 2-n Operand (16 items) Teleprotection Clear Lost Packets Teleprotection Channel 1 Status Teleprotection Channel 1 Number of Lost Packets Teleprotection Channel 2 Status Teleprotection Channel 2 Number of Lost Packets Teleprotection Network Status Teleprotection Channel 1 Input States Teleprotection Channel 2 Input States Teleprotection Input 1 States, 1 per register (16 items) Teleprotection Input 2 States, 1 per register (16 items) Selector switch 1 position Selector switch 2 position Selector 1 Function Selector 1 Range Selector 1 Timeout Selector 1 Step Up Selector 1 Step Mode Selector 1 Acknowledge Selector 1 Bit0 Selector 1 Bit1 Selector 1 Bit2 Selector 1 Bit Mode Selector 1 Bit Acknowledge Selector 1 Power Up Mode Selector 1 Target Selector 1 Events Reserved (10 items) ...Repeated for Selector 2 DNP/IEC 60870-5-104 Binary Input Points (256 items) DNP/IEC 60870-5-104 Analog Input Points (256 items) Non-Volatile Latch 1 Function Non-Volatile Latch 1 Type Non-Volatile Latch 1 Set Non-Volatile Latch 1 Reset Non-Volatile Latch 1 Target Non-Volatile Latch 1 Events Reserved (4 items) ...Repeated for Non-Volatile Latch 2 ...Repeated for Non-Volatile Latch 3 ...Repeated for Non-Volatile Latch 4 0 to 65535 0 to 65535 0 to 1 0 to 1 0 to 65535 0 to 65535 0 to 2 0 to 1 --------------------1 1 1 1 1 1 1 1 --RANGE 0 to 255 0 to 255 0 to 255 0 to 1 0 to 3 0 to 3 0 to 65535 0 to 65535 0 to 1 0 to 2 0 to 65535 0 to 2 0 to 65535 0 to 2 0 to 1 0 to 1 0 to 1 0 to 1 1 to 7 1 to 7 0 to 1 1 to 7 3 to 60 0 to 65535 0 to 1 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 1 0 to 65535 0 to 2 0 to 2 0 to 1 --UNITS --------------------------------------------s ------------------------STEP 1 1 1 --1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.1 1 1 1 1 1 1 1 1 1 1 1 1

B.4 MEMORY MAPPING

FORMAT F001 F001 F001 F001 F086 F086 F300 F300 F126 F134 F001 F134 F001 F134 F500 F500 F108 F108 F001 F001 F102 F001 F001 F300 F083 F300 F300 F300 F300 F083 F300 F084 F109 F102 F001

DEFAULT 0 0 0 0 0 (Off) 0 (Off) 0 0 0 (No) 1 (OK) 0 1 (OK) 0 2 (n/a) 0 0 0 (Off) 0 (Off) 0 1 0 (Disabled) 7 50 0 0 (Time-out) 0 0 0 0 0 (Time-out) 0 0 (Restore) 0 (Self-reset) 0 (Disabled) 0

Teleprotection Inputs/Outputs Commands (Read/Write Command) Teleprotection Channel Tests (Read Only)

Selector switch actual values (read only)

Selector switch settings (read/write, 2 modules)

DNP/IEC Points (Read/Write Setting) F300 F300 F102 F519 F300 F300 F109 F102 F001 0 0 0 (Disabled) 0 (Reset Dominant) 0 0 0 (Self-reset) 0 (Disabled) 0

Non Volatile Latches (Read/Write Setting) (16 modules)

GE Multilin

C30 Controller System

B-27

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 21 of 39)
ADDR A728 A732 A73C A746 A750 A75A A764 A76E A778 A782 A78C A796 A800 A801 A807 A80A A80B A80C A80D A80F A811 A812 A813 A814 A815 A820 A840 A860 A880 A8A0 A8C0 A8E0 AA00 AA02 AA03 AA05 AA07 AA0E AA15 AA1C AA23 AA2A AA31 AA38 AA3F AA46 AA4D AA54 AA5B AA62 AA69 REGISTER NAME ...Repeated for Non-Volatile Latch 5 ...Repeated for Non-Volatile Latch 6 ...Repeated for Non-Volatile Latch 7 ...Repeated for Non-Volatile Latch 8 ...Repeated for Non-Volatile Latch 9 ...Repeated for Non-Volatile Latch 10 ...Repeated for Non-Volatile Latch 11 ...Repeated for Non-Volatile Latch 12 ...Repeated for Non-Volatile Latch 13 ...Repeated for Non-Volatile Latch 14 ...Repeated for Non-Volatile Latch 15 ...Repeated for Non-Volatile Latch 16 Digital Counter 1 Function Digital Counter 1 Name Digital Counter 1 Units Digital Counter 1 Block Digital Counter 1 Up Digital Counter 1 Down Digital Counter 1 Preset Digital Counter 1 Compare Digital Counter 1 Reset Digital Counter 1 Freeze/Reset Digital Counter 1 Freeze/Count Digital Counter 1 Set To Preset Reserved (11 items) ...Repeated for Digital Counter 2 ...Repeated for Digital Counter 3 ...Repeated for Digital Counter 4 ...Repeated for Digital Counter 5 ...Repeated for Digital Counter 6 ...Repeated for Digital Counter 7 ...Repeated for Digital Counter 8 IEC 61850 GOOSE analog 1 default value IEC 61850 GOOSE analog input 1 mode IEC 61850 GOOSE analog input 1 units IEC 61850 GOOSE analog input 1 per-unit base ...Repeated for IEC 61850 GOOSE analog input 2 ...Repeated for IEC 61850 GOOSE analog input 3 ...Repeated for IEC 61850 GOOSE analog input 4 ...Repeated for IEC 61850 GOOSE analog input 5 ...Repeated for IEC 61850 GOOSE analog input 6 ...Repeated for IEC 61850 GOOSE analog input 7 ...Repeated for IEC 61850 GOOSE analog input 8 ...Repeated for IEC 61850 GOOSE analog input 9 ...Repeated for IEC 61850 GOOSE analog input 10 ...Repeated for IEC 61850 GOOSE analog input 11 ...Repeated for IEC 61850 GOOSE analog input 12 ...Repeated for IEC 61850 GOOSE analog input 13 ...Repeated for IEC 61850 GOOSE analog input 14 ...Repeated for IEC 61850 GOOSE analog input 15 ...Repeated for IEC 61850 GOOSE analog input 16 1000000 to 1000000 0 to 1 --0 to 999999999.999 --------0.001 1 --0.001 F060 F491 F207 F060 0 to 1 ----0 to 65535 0 to 65535 0 to 65535 2147483647 to 2147483647 2147483647 to 2147483647 0 to 65535 0 to 65535 0 to 65535 0 to 65535 ----------------------------1 ----1 1 1 1 1 1 1 1 1 --F102 F205 F206 F300 F300 F300 F004 F004 F300 F300 F300 F300 F001 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Digital Counter (Read/Write Setting) (8 modules) 0 (Disabled) Counter 1" (none) 0 0 0 0 0 0 0 0 0 0

IEC 61850 received analog settings (read/write) 1000 0 (Default Value) (none) 1

B-28

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 22 of 39)


ADDR AB24 AB25 AB26 AB27 AB28 AB29 AB2A AB2B AB2C AB2D AB2E AB2F AB30 AB33 AC0B AC53 AC7A AC98 ACB6 ACFE AD01 AD13 AD25 AD34 AD43 AD55 AD67 AD73 ADE2 AE3C AECF AED0 AED1 AED3 AED5 AED7 AED9 AEDB AEDD AEDF AEE1 AEE3 AEE5 AEE7 AEE9 AEEB AEED AEEF AEF1 AEF3 AEF5 REGISTER NAME Operand for IEC 61850 XCBR1.ST.Loc status Command to clear XCBR1 OpCnt (operation counter) Operand for IEC 61850 XCBR2.ST.Loc status Command to clear XCBR2 OpCnt (operation counter) Operand for IEC 61850 XCBR3.ST.Loc status Command to clear XCBR3 OpCnt (operation counter) Operand for IEC 61850 XCBR4.ST.Loc status Command to clear XCBR4 OpCnt (operation counter) Operand for IEC 61850 XCBR5.ST.Loc status Command to clear XCBR5 OpCnt (operation counter) Operand for IEC 61850 XCBR6.ST.Loc status Command to clear XCBR6 OpCnt (operation counter) IEC 61850 logical node LPHD1 name prefix IEC 61850 logical node PIOCx name prefix (72 items) IEC 61850 logical node PTOCx name prefix (24 items) IEC 61850 logical node PTUVx name prefix (13 items) IEC 61850 logical node PTOVx name prefix (10 items) IEC 61850 logical node PDISx name prefix (10 items) IEC 61850 logical node RBRFx name prefix (24 items) IEC 61850 logical node RPSBx name prefix IEC 61850 logical node RRECx name prefix (6 items) IEC 61850 logical node MMXUx name prefix (6 items) IEC 61850 logical node GGIOx name prefix (5 items) IEC 61850 logical node RFLOx name prefix (5 items) IEC 61850 logical node XCBRx name prefix (6 items) IEC 61850 logical node PTRCx name prefix (6 items) IEC 61850 logical node PDIFx name prefix (6 items) IEC 61850 logical node MMXNx name prefix (6 items) IEC 61850 logical node CSWIx name prefix (6 items) IEC 61850 logical node XSWIx name prefix (6 items) Operand for IEC 61850 XSWI1.ST.Loc status Command to clear XSWI1 OpCnt (operation counter) Repeated for IEC 61850 XSWI2 Repeated for IEC 61850 XSWI3 Repeated for IEC 61850 XSWI4 Repeated for IEC 61850 XSWI5 Repeated for IEC 61850 XSWI6 Repeated for IEC 61850 XSWI7 Repeated for IEC 61850 XSWI8 Repeated for IEC 61850 XSWI9 Repeated for IEC 61850 XSWI10 Repeated for IEC 61850 XSWI11 Repeated for IEC 61850 XSWI12 Repeated for IEC 61850 XSWI13 Repeated for IEC 61850 XSWI14 Repeated for IEC 61850 XSWI15 Repeated for IEC 61850 XSWI16 Repeated for IEC 61850 XSWI17 Repeated for IEC 61850 XSWI18 Repeated for IEC 61850 XSWI19 Repeated for IEC 61850 XSWI20 RANGE 0 to 65535 0 to 1 0 to 65535 0 to 1 0 to 65535 0 to 1 0 to 65535 0 to 1 0 to 65535 0 to 1 0 to 65535 0 to 1 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65535 0 to 1 UNITS ----------------------------------------------------------------STEP 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

B.4 MEMORY MAPPING

FORMAT F300 F126 F300 F126 F300 F126 F300 F126 F300 F126 F300 F126 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 F300 F126

DEFAULT 0 0 (No) 0 0 (No) 0 0 (No) 0 0 (No) 0 0 (No) 0 0 (No) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) (none) 0 0 (No)

IEC 61850 XCBR configuration (read/write settings)

IEC 61850 LN name prefixes (read/write settings)

IEC 61850 XSWI configuration (read/write settings)

GE Multilin

C30 Controller System

B-29

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 23 of 39)
ADDR AEF7 AEF9 AEFB AEFD REGISTER NAME Repeated for IEC 61850 XSWI21 Repeated for IEC 61850 XSWI22 Repeated for IEC 61850 XSWI23 Repeated for IEC 61850 XSWI24 Number of analog points in GGIO4 IEC 61850 GGIO4 analog input 1 value IEC 61850 GGIO4 analog input 1 deadband IEC 61850 GGIO4 analog input 1 minimum IEC 61850 GGIO4 analog input 1 maximum ...Repeated for IEC 61850 GGIO4 analog input 2 ...Repeated for IEC 61850 GGIO4 analog input 3 ...Repeated for IEC 61850 GGIO4 analog input 4 ...Repeated for IEC 61850 GGIO4 analog input 5 ...Repeated for IEC 61850 GGIO4 analog input 6 ...Repeated for IEC 61850 GGIO4 analog input 7 ...Repeated for IEC 61850 GGIO4 analog input 8 ...Repeated for IEC 61850 GGIO4 analog input 9 ...Repeated for IEC 61850 GGIO4 analog input 10 ...Repeated for IEC 61850 GGIO4 analog input 11 ...Repeated for IEC 61850 GGIO4 analog input 12 ...Repeated for IEC 61850 GGIO4 analog input 13 ...Repeated for IEC 61850 GGIO4 analog input 14 ...Repeated for IEC 61850 GGIO4 analog input 15 ...Repeated for IEC 61850 GGIO4 analog input 16 ...Repeated for IEC 61850 GGIO4 analog input 17 ...Repeated for IEC 61850 GGIO4 analog input 18 ...Repeated for IEC 61850 GGIO4 analog input 19 ...Repeated for IEC 61850 GGIO4 analog input 20 ...Repeated for IEC 61850 GGIO4 analog input 21 ...Repeated for IEC 61850 GGIO4 analog input 22 ...Repeated for IEC 61850 GGIO4 analog input 23 ...Repeated for IEC 61850 GGIO4 analog input 24 ...Repeated for IEC 61850 GGIO4 analog input 25 ...Repeated for IEC 61850 GGIO4 analog input 26 ...Repeated for IEC 61850 GGIO4 analog input 27 ...Repeated for IEC 61850 GGIO4 analog input 28 ...Repeated for IEC 61850 GGIO4 analog input 29 ...Repeated for IEC 61850 GGIO4 analog input 30 ...Repeated for IEC 61850 GGIO4 analog input 31 ...Repeated for IEC 61850 GGIO4 analog input 32 IEC 61850 Logical Node LPHD1 Name Prefix IEC 61850 Logical Node PIOCx Name Prefix (72 items) IEC 61850 Logical Node PTOCx Name Prefix (24 items) IEC 61850 Logical Node PTUVx Name Prefix (12 items) IEC 61850 Logical Node PTOVx Name Prefix (8 items) IEC 61850 Logical Node PDISx Name Prefix (10 items) IEC 61850 Logical Node RRBFx Name Prefix (24 items) IEC 61850 Logical Node RPSBx Name Prefix IEC 61850 Logical Node RRECx Name Prefix (6 items) IEC 61850 Logical Node MMXUx Name Prefix (6 items) 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 --------------------1 1 1 1 1 1 1 1 1 1 F206 F206 F206 F206 F206 F206 F206 F206 F206 F206 4 to 32 --0.001 to 100 1000000000000 to 1000000000000 1000000000000 to 1000000000000 ----% ----4 --0.001 0.001 0.001 F001 F600 F003 F060 F060 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

IEC 61850 GGIO4 general analog configuration settings (read/write) AF00 AF10 AF11 AF13 AF15 AF17 AF1E AF25 AF2C AF33 AF3A AF41 AF48 AF4F AF56 AF5D AF64 AF6B AF72 AF79 AF80 AF87 AF8E AF95 AF9C AFA3 AFAA AFB1 AFB8 AFBF AFC6 AFCD AFD4 AFDB AFE2 AFE9 AB30 AB33 AC0B AC53 AC77 AC8F ACAD ACF5 ACF8 AD0A 4 0 100000 0 1000000 IEC 61850 GGIO4 analog input points configuration settings (read/write)

IEC 61850 Logical Node Name Prefixes (Read/Write Setting) (None) (None) (None) (None) (None) (None) (None) (None) (None) (None)

B-30

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 24 of 39)


ADDR AD1C AD28 AD37 AD3D AD43 AD4F B01C B01D B013 B03F B040 B043 B064 B067 B068 B069 B06A B06C B06D B07D B08D B0B5 B06B B0B7 B0C0 B0C2 B0C4 B0C6 B0C8 B0CA B0CC B0CE B0D0 B0D2 B0D4 B0D6 B0D8 B0DA B0DC B0DE B0E0 B0E2 B0E4 B0E6 B0E8 B0EA B0EC B0EE B0F0 B0F2 B0F4 REGISTER NAME IEC 61850 Logical Node GGIOx Name Prefix (4 items) IEC 61850 Logical Node RFLOx Name Prefix (5 items) IEC 61850 Logical Node XCBRx Name Prefix (2 items) IEC 61850 Logical Node PTRCx Name Prefix (2 items) IEC 61850 Logical Node PDIFx Name Prefix (4 items) IEC 61850 Logical Node MMXNx Name Prefix (37 items) Default GOOSE/GSSE Update Time IEC 61850 GSSE Function (GsEna) IEC 61850 GSSE ID IEC 61850 GOOSE Function (GoEna) IEC 61850 GSSE Destination MAC Address IEC 61850 Standard GOOSE ID IEC 61850 Standard GOOSE Destination MAC Address IEC 61850 GOOSE VLAN Transmit Priority IEC 61850 GOOSE VLAN ID IEC 61850 GOOSE ETYPE APPID Reserved (2 items) TCP Port Number for the IEC 61850 / MMS Protocol IEC 61850 Logical Device Name IEC 61850 Logical Device Instance IEC 61850 LPHD Location Include non-IEC 61850 Data IEC 61850 Server Data Scanning Function Reserved (15 items) IEC 61850 MMXU TotW Deadband 1 IEC 61850 MMXU TotVAr Deadband 1 IEC 61850 MMXU TotVA Deadband 1 IEC 61850 MMXU TotPF Deadband 1 IEC 61850 MMXU Hz Deadband 1 IEC 61850 MMXU PPV.phsAB Deadband 1 IEC 61850 MMXU PPV.phsBC Deadband 1 IEC 61850 MMXU PPV.phsCA Deadband 1 IEC 61850 MMXU PhV.phsADeadband 1 IEC 61850 MMXU PhV.phsB Deadband 1 IEC 61850 MMXU PhV.phsC Deadband 1 IEC 61850 MMXU A.phsA Deadband 1 IEC 61850 MMXU A.phsB Deadband 1 IEC 61850 MMXU A.phsC Deadband 1 IEC 61850 MMXU A.neut Deadband 1 IEC 61850 MMXU W.phsA Deadband 1 IEC 61850 MMXU W.phsB Deadband 1 IEC 61850 MMXU W.phsC Deadband 1 IEC 61850 MMXU VAr.phsA Deadband 1 IEC 61850 MMXU VAr.phsB Deadband 1 IEC 61850 MMXU VAr.phsC Deadband 1 IEC 61850 MMXU VA.phsA Deadband 1 IEC 61850 MMXU VA.phsB Deadband 1 IEC 61850 MMXU VA.phsC Deadband 1 IEC 61850 MMXU PF.phsA Deadband 1 IEC 61850 MMXU PF.phsB Deadband 1 IEC 61850 MMXU PF.phsC Deadband 1 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 0.001 to 100 % % % % % % % % % % % % % % % % % % % % % % % % % % % 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 0.001 RANGE 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 0 to 65534 1 to 60 0 to 1 --0 to 1 ------0 to 7 0 to 4095 0 to 16383 0 to 1 1 to 65535 ------0 to 1 0 to 1 UNITS ------------s --------------------------------STEP 1 1 1 1 1 1 1 1 --1 ------1 1 1 1 1 ------1 1

B.4 MEMORY MAPPING

FORMAT F206 F206 F206 F206 F206 F206 F001 F102 F209 F102 F072 F209 F072 F001 F001 F001 F001 F001 F213 F213 F204 F102 F102

DEFAULT (None) (None) (None) (None) (None) (None) 60 1 (Enabled) GSSEOut 0 (Disabled) 0 GOOSEOut 0 4 0 0 0 102 IECName LDInst Location 0 (Disabled) 0 (Disabled)

IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)

IEC 61850 Server Configuration (Read/Write Settings/Commands)

IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules) F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 F003 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000

GE Multilin

C30 Controller System

B-31

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 25 of 39)
ADDR B0F6 B12C B162 B198 B1CE B280 B2A1 B2A2 B2A4 B2A5 B2A7 B2CE B2F5 B31C B343 B36A B391 B3B8 B3DF B406 B42D B454 B47B B4A2 B4C9 B500 B501 B5A0 B5A1 B5C2 B5C5 B5C6 B5C7 B5C8 B5CA B5CB B60B B676 B6E1 B74C B7B7 B822 B88D B900 B940 B980 B9C0 BA00 BA40 REGISTER NAME ...Repeated for Deadband 2 ...Repeated for Deadband 3 ...Repeated for Deadband 4 ...Repeated for Deadband 5 ...Repeated for Deadband 6 IEC 61850 Report Control 1 RptID IEC 61850 Report Control 1 OptFlds IEC 61850 Report Control 1 BufTm IEC 61850 Report Control 1 TrgOps IEC 61850 Report Control 1 IntgPd ...Repeated for Report 2 ...Repeated for Report 3 ...Repeated for Report 4 ...Repeated for Report 5 ...Repeated for Report 6 ...Repeated for Report 7 ...Repeated for Report 8 ...Repeated for Report 9 ...Repeated for Report 10 ...Repeated for Report 11 ...Repeated for Report 12 ...Repeated for Report 13 ...Repeated for Report 14 ...Repeated for Report 15 ...Repeated for Report 16 Number of Status Indications in GGIO1 IEC 61850 GGIO1 Indication operands (128 items) IEC 61850 Configurable GOOSE Function IEC 61850 Configurable GOOSE ID Configurable GOOSE Destination MAC Address IEC 61850 Configurable GOOSE VLAN Transmit Priority IEC 61850 Configurable GOOSE VLAN ID IEC 61850 Configurable GOOSE ETYPE APPID IEC 61850 Configurable GOOSE ConfRev IEC 61850 Configurable GOOSE Retransmission Curve Configurable GOOSE Dataset Items for Transmission (64 items) ...Repeated for Module 2 ...Repeated for Module 3 ...Repeated for Module 4 ...Repeated for Module 5 ...Repeated for Module 6 ...Repeated for Module 7 ...Repeated for Module 8 Configurable GOOSE Dataset Items for Transmission ...Repeated for Module 2 ...Repeated for Module 3 ...Repeated for Module 4 ...Repeated for Module 5 ...Repeated for Module 6 0 to 128 --1 F233 8 to 128 --0 to 1 ----0 to 7 0 to 4095 0 to 16383 1 to 4294967295 0 to 3 0 to 542 ----------------------8 1 1 ----1 1 1 1 1 1 F001 F300 F102 F209 F072 F001 F001 F001 F003 F611 F232 --0 to 65535 0 to 4294967295 0 to 65535 0 to 4294967295 ------------1 1 1 1 F209 F001 F003 F001 F003 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

IEC 61850 Report Settings (Read/Write Setting) (14 modules) 0 0 0 0

IEC 61850 GGIO1 Configuration Settings (Read/Write Setting) 8 0 0 (None) GOOSEOut_x_ 0 4 0 0 1 3 (Relaxed) 0 (None)

IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)

IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (8 modules) 0 (None)

B-32

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 26 of 39)


ADDR BA80 BAC0 BB00 BB06 BB07 BB08 BB10 BB18 BB20 BB28 BB30 BB38 BB40 BB48 BB50 BB58 BB60 BB68 BB70 BB78 BB80 BB88 BB90 BB98 BBA0 BBA8 BBB0 BBB8 BBC0 BBC8 BBD0 BBD8 BBE0 BBE8 BBF0 BBF8 BC00 BC08 BC10 BC18 BC20 BC28 BC30 BC38 BC40 BC48 BC50 BC58 BC60 BC68 BC70 BC78 BC80 REGISTER NAME ...Repeated for Module 7 ...Repeated for Module 8 Contact Input 1 Name Contact Input 1 Events Contact Input 1 Debounce Time ...Repeated for Contact Input 2 ...Repeated for Contact Input 3 ...Repeated for Contact Input 4 ...Repeated for Contact Input 5 ...Repeated for Contact Input 6 ...Repeated for Contact Input 7 ...Repeated for Contact Input 8 ...Repeated for Contact Input 9 ...Repeated for Contact Input 10 ...Repeated for Contact Input 11 ...Repeated for Contact Input 12 ...Repeated for Contact Input 13 ...Repeated for Contact Input 14 ...Repeated for Contact Input 15 ...Repeated for Contact Input 16 ...Repeated for Contact Input 17 ...Repeated for Contact Input 18 ...Repeated for Contact Input 19 ...Repeated for Contact Input 20 ...Repeated for Contact Input 21 ...Repeated for Contact Input 22 ...Repeated for Contact Input 23 ...Repeated for Contact Input 24 ...Repeated for Contact Input 25 ...Repeated for Contact Input 26 ...Repeated for Contact Input 27 ...Repeated for Contact Input 28 ...Repeated for Contact Input 29 ...Repeated for Contact Input 30 ...Repeated for Contact Input 31 ...Repeated for Contact Input 32 ...Repeated for Contact Input 33 ...Repeated for Contact Input 34 ...Repeated for Contact Input 35 ...Repeated for Contact Input 36 ...Repeated for Contact Input 37 ...Repeated for Contact Input 38 ...Repeated for Contact Input 39 ...Repeated for Contact Input 40 ...Repeated for Contact Input 41 ...Repeated for Contact Input 42 ...Repeated for Contact Input 43 ...Repeated for Contact Input 44 ...Repeated for Contact Input 45 ...Repeated for Contact Input 46 ...Repeated for Contact Input 47 ...Repeated for Contact Input 48 ...Repeated for Contact Input 49 --0 to 1 0 to 16 ----ms --1 0.5 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Contact Inputs (Read/Write Setting) (96 modules) F205 F102 F001 Cont Ip 1 0 (Disabled) 20

GE Multilin

C30 Controller System

B-33

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 27 of 39)
ADDR BC88 BC90 BC98 BCA0 BCA8 BCB0 BCB8 BCC0 BCC8 BCD0 BCD8 BCE0 BCE8 BCF0 BCF8 BD00 BD08 BD10 BD18 BD20 BD28 BD30 BD38 BD40 BD48 BD50 BD58 BD60 BD68 BD70 BD78 BD80 BD88 BD90 BD98 BDA0 BDA8 BDB0 BDB8 BDC0 BDC8 BDD0 BDD8 BDE0 BDE8 BDF0 BDF8 BE00 BE30 BE31 BE37 BE38 REGISTER NAME ...Repeated for Contact Input 50 ...Repeated for Contact Input 51 ...Repeated for Contact Input 52 ...Repeated for Contact Input 53 ...Repeated for Contact Input 54 ...Repeated for Contact Input 55 ...Repeated for Contact Input 56 ...Repeated for Contact Input 57 ...Repeated for Contact Input 58 ...Repeated for Contact Input 59 ...Repeated for Contact Input 60 ...Repeated for Contact Input 61 ...Repeated for Contact Input 62 ...Repeated for Contact Input 63 ...Repeated for Contact Input 64 ...Repeated for Contact Input 65 ...Repeated for Contact Input 66 ...Repeated for Contact Input 67 ...Repeated for Contact Input 68 ...Repeated for Contact Input 69 ...Repeated for Contact Input 70 ...Repeated for Contact Input 71 ...Repeated for Contact Input 72 ...Repeated for Contact Input 73 ...Repeated for Contact Input 74 ...Repeated for Contact Input 75 ...Repeated for Contact Input 76 ...Repeated for Contact Input 77 ...Repeated for Contact Input 78 ...Repeated for Contact Input 79 ...Repeated for Contact Input 80 ...Repeated for Contact Input 81 ...Repeated for Contact Input 82 ...Repeated for Contact Input 83 ...Repeated for Contact Input 84 ...Repeated for Contact Input 85 ...Repeated for Contact Input 86 ...Repeated for Contact Input 87 ...Repeated for Contact Input 88 ...Repeated for Contact Input 89 ...Repeated for Contact Input 90 ...Repeated for Contact Input 91 ...Repeated for Contact Input 92 ...Repeated for Contact Input 93 ...Repeated for Contact Input 94 ...Repeated for Contact Input 95 ...Repeated for Contact Input 96 Contact Input n Threshold, n = 1 to 24 (24 items) Virtual Input 1 Function Virtual Input 1 Name Virtual Input 1 Programmed Type Virtual Input 1 Events 0 to 3 0 to 1 --0 to 1 0 to 1 ----------1 1 --1 1 F128 F102 F205 F127 F102 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Contact Input Thresholds (Read/Write Setting) 1 (33 Vdc) 0 (Disabled) Virt Ip 1 0 (Latched) 0 (Disabled) Virtual Inputs (Read/Write Setting) (64 modules)

B-34

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 28 of 39)


ADDR BE39 BE3C BE48 BE54 BE60 BE6C BE78 BE84 BE90 BE9C BEA8 BEB4 BEC0 BECC BED8 BEE4 BEF0 BEFC BF08 BF14 BF20 BF2C BF38 BF44 BF50 BF5C BF68 BF74 BF80 BF8C BF98 BFA4 BFB0 BFBC BFC8 BFD4 BFE0 BFEC BFF8 C004 C010 C01C C028 C034 C040 C04C C058 C064 C070 C07C C088 C094 C0A0 C0AC REGISTER NAME Reserved (3 items) ...Repeated for Virtual Input 2 ...Repeated for Virtual Input 3 ...Repeated for Virtual Input 4 ...Repeated for Virtual Input 5 ...Repeated for Virtual Input 6 ...Repeated for Virtual Input 7 ...Repeated for Virtual Input 8 ...Repeated for Virtual Input 9 ...Repeated for Virtual Input 10 ...Repeated for Virtual Input 11 ...Repeated for Virtual Input 12 ...Repeated for Virtual Input 13 ...Repeated for Virtual Input 14 ...Repeated for Virtual Input 15 ...Repeated for Virtual Input 16 ...Repeated for Virtual Input 17 ...Repeated for Virtual Input 18 ...Repeated for Virtual Input 19 ...Repeated for Virtual Input 20 ...Repeated for Virtual Input 21 ...Repeated for Virtual Input 22 ...Repeated for Virtual Input 23 ...Repeated for Virtual Input 24 ...Repeated for Virtual Input 25 ...Repeated for Virtual Input 26 ...Repeated for Virtual Input 27 ...Repeated for Virtual Input 28 ...Repeated for Virtual Input 29 ...Repeated for Virtual Input 30 ...Repeated for Virtual Input 31 ...Repeated for Virtual Input 32 ...Repeated for Virtual Input 33 ...Repeated for Virtual Input 34 ...Repeated for Virtual Input 35 ...Repeated for Virtual Input 36 ...Repeated for Virtual Input 37 ...Repeated for Virtual Input 38 ...Repeated for Virtual Input 39 ...Repeated for Virtual Input 40 ...Repeated for Virtual Input 41 ...Repeated for Virtual Input 42 ...Repeated for Virtual Input 43 ...Repeated for Virtual Input 44 ...Repeated for Virtual Input 45 ...Repeated for Virtual Input 46 ...Repeated for Virtual Input 47 ...Repeated for Virtual Input 48 ...Repeated for Virtual Input 49 ...Repeated for Virtual Input 50 ...Repeated for Virtual Input 51 ...Repeated for Virtual Input 52 ...Repeated for Virtual Input 53 ...Repeated for Virtual Input 54 RANGE --UNITS --STEP ---

B.4 MEMORY MAPPING

FORMAT F001

DEFAULT 0

GE Multilin

C30 Controller System

B-35

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 29 of 39)
ADDR C0B8 C0C4 C0D0 C0DC C0E8 C0F4 C100 C10C C118 C124 C130 C136 C137 C138 C140 C148 C150 C158 C160 C168 C170 C178 C180 C188 C190 C198 C1A0 C1A8 C1B0 C1B8 C1C0 C1C8 C1D0 C1D8 C1E0 C1E8 C1F0 C1F8 C200 C208 C210 C218 C220 C228 C230 C238 C240 C248 C250 C258 C260 C268 C270 REGISTER NAME ...Repeated for Virtual Input 55 ...Repeated for Virtual Input 56 ...Repeated for Virtual Input 57 ...Repeated for Virtual Input 58 ...Repeated for Virtual Input 59 ...Repeated for Virtual Input 60 ...Repeated for Virtual Input 61 ...Repeated for Virtual Input 62 ...Repeated for Virtual Input 63 ...Repeated for Virtual Input 64 Virtual Output 1 Name Virtual Output 1 Events Reserved ...Repeated for Virtual Output 2 ...Repeated for Virtual Output 3 ...Repeated for Virtual Output 4 ...Repeated for Virtual Output 5 ...Repeated for Virtual Output 6 ...Repeated for Virtual Output 7 ...Repeated for Virtual Output 8 ...Repeated for Virtual Output 9 ...Repeated for Virtual Output 10 ...Repeated for Virtual Output 11 ...Repeated for Virtual Output 12 ...Repeated for Virtual Output 13 ...Repeated for Virtual Output 14 ...Repeated for Virtual Output 15 ...Repeated for Virtual Output 16 ...Repeated for Virtual Output 17 ...Repeated for Virtual Output 18 ...Repeated for Virtual Output 19 ...Repeated for Virtual Output 20 ...Repeated for Virtual Output 21 ...Repeated for Virtual Output 22 ...Repeated for Virtual Output 23 ...Repeated for Virtual Output 24 ...Repeated for Virtual Output 25 ...Repeated for Virtual Output 26 ...Repeated for Virtual Output 27 ...Repeated for Virtual Output 28 ...Repeated for Virtual Output 29 ...Repeated for Virtual Output 30 ...Repeated for Virtual Output 31 ...Repeated for Virtual Output 32 ...Repeated for Virtual Output 33 ...Repeated for Virtual Output 34 ...Repeated for Virtual Output 35 ...Repeated for Virtual Output 36 ...Repeated for Virtual Output 37 ...Repeated for Virtual Output 38 ...Repeated for Virtual Output 39 ...Repeated for Virtual Output 40 ...Repeated for Virtual Output 41 --0 to 1 ----------1 --F205 F102 F001 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Virtual Outputs (Read/Write Setting) (96 modules) Virt Op 1 0 (Disabled) 0

B-36

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 30 of 39)


ADDR C278 C280 C288 C290 C298 C2A0 C2A8 C2B0 C2B8 C2C0 C2C8 C2D0 C2D8 C2E0 C2E8 C2F0 C2F8 C300 C308 C310 C318 C320 C328 C330 C338 C340 C348 C350 C358 C360 C368 C370 C378 C380 C388 C390 C398 C3A0 C3A8 C3B0 C3B8 C3C0 C3C8 C3D0 C3D8 C3E0 C3E8 C3F0 C3F8 C400 C408 C410 C418 C420 REGISTER NAME ...Repeated for Virtual Output 42 ...Repeated for Virtual Output 43 ...Repeated for Virtual Output 44 ...Repeated for Virtual Output 45 ...Repeated for Virtual Output 46 ...Repeated for Virtual Output 47 ...Repeated for Virtual Output 48 ...Repeated for Virtual Output 49 ...Repeated for Virtual Output 50 ...Repeated for Virtual Output 51 ...Repeated for Virtual Output 52 ...Repeated for Virtual Output 53 ...Repeated for Virtual Output 54 ...Repeated for Virtual Output 55 ...Repeated for Virtual Output 56 ...Repeated for Virtual Output 57 ...Repeated for Virtual Output 58 ...Repeated for Virtual Output 59 ...Repeated for Virtual Output 60 ...Repeated for Virtual Output 61 ...Repeated for Virtual Output 62 ...Repeated for Virtual Output 63 ...Repeated for Virtual Output 64 ...Repeated for Virtual Output 65 ...Repeated for Virtual Output 66 ...Repeated for Virtual Output 67 ...Repeated for Virtual Output 68 ...Repeated for Virtual Output 69 ...Repeated for Virtual Output 70 ...Repeated for Virtual Output 71 ...Repeated for Virtual Output 72 ...Repeated for Virtual Output 73 ...Repeated for Virtual Output 74 ...Repeated for Virtual Output 75 ...Repeated for Virtual Output 76 ...Repeated for Virtual Output 77 ...Repeated for Virtual Output 78 ...Repeated for Virtual Output 79 ...Repeated for Virtual Output 80 ...Repeated for Virtual Output 81 ...Repeated for Virtual Output 82 ...Repeated for Virtual Output 83 ...Repeated for Virtual Output 84 ...Repeated for Virtual Output 85 ...Repeated for Virtual Output 86 ...Repeated for Virtual Output 87 ...Repeated for Virtual Output 88 ...Repeated for Virtual Output 89 ...Repeated for Virtual Output 90 ...Repeated for Virtual Output 91 ...Repeated for Virtual Output 92 ...Repeated for Virtual Output 93 ...Repeated for Virtual Output 94 ...Repeated for Virtual Output 95 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

GE Multilin

C30 Controller System

B-37

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 31 of 39)
ADDR C428 C430 C431 C432 C433 C440 C446 C447 C448 C449 C44A C44B C44C C458 C464 C470 C47C C488 C494 C4A0 C4AC C4B8 C4C4 C4D0 C4DC C4E8 C4F4 C500 C50C C518 C524 C530 C53C C548 C554 C560 C56C C578 C584 C590 C59C C5A8 C5B4 C5C0 C5CC C5D8 C5E4 C5F0 C5FC C608 C614 REGISTER NAME ...Repeated for Virtual Output 96 Test Mode Function Force VFD and LED Test Mode Forcing Clear All Relay Records Command Contact Output 1 Name Contact Output 1 Operation Contact Output 1 Seal In Latching Output 1 Reset Contact Output 1 Events Latching Output 1 Type Reserved ...Repeated for Contact Output 2 ...Repeated for Contact Output 3 ...Repeated for Contact Output 4 ...Repeated for Contact Output 5 ...Repeated for Contact Output 6 ...Repeated for Contact Output 7 ...Repeated for Contact Output 8 ...Repeated for Contact Output 9 ...Repeated for Contact Output 10 ...Repeated for Contact Output 11 ...Repeated for Contact Output 12 ...Repeated for Contact Output 13 ...Repeated for Contact Output 14 ...Repeated for Contact Output 15 ...Repeated for Contact Output 16 ...Repeated for Contact Output 17 ...Repeated for Contact Output 18 ...Repeated for Contact Output 19 ...Repeated for Contact Output 20 ...Repeated for Contact Output 21 ...Repeated for Contact Output 22 ...Repeated for Contact Output 23 ...Repeated for Contact Output 24 ...Repeated for Contact Output 25 ...Repeated for Contact Output 26 ...Repeated for Contact Output 27 ...Repeated for Contact Output 28 ...Repeated for Contact Output 29 ...Repeated for Contact Output 30 ...Repeated for Contact Output 31 ...Repeated for Contact Output 32 ...Repeated for Contact Output 33 ...Repeated for Contact Output 34 ...Repeated for Contact Output 35 ...Repeated for Contact Output 36 ...Repeated for Contact Output 37 ...Repeated for Contact Output 38 ...Repeated for Contact Output 39 ...Repeated for Contact Output 40 0 to 1 0 to 1 0 to 65535 0 to 1 --0 to 65535 0 to 65535 0 to 65535 0 to 1 0 to 1 ------------------------1 1 1 1 --1 1 1 1 1 --F245 F126 F300 F126 F205 F300 F300 F300 F102 F090 F001 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Mandatory (Read/Write Setting) 0 (Disabled) 0 (No) 1 0 (No) Cont Op 1" 0 0 0 1 (Enabled) 0 (Operate-dominant) 0

Clear commands (read/write) Contact Outputs (Read/Write Setting) (64 modules)

B-38

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 32 of 39)


ADDR C620 C62C C638 C644 C650 C65C C668 C674 C680 C68C C698 C6A4 C6B0 C6BC C6C8 C6D4 C6E0 C6EC C6F8 C704 C710 C71C C728 C734 C750 C760 C761 C762 C764 C766 C768 C76A C76C C772 C773 C774 C77F C781 C782 C7A0 C800 C880 C881 C882 C883 C884 C888 REGISTER NAME ...Repeated for Contact Output 41 ...Repeated for Contact Output 42 ...Repeated for Contact Output 43 ...Repeated for Contact Output 44 ...Repeated for Contact Output 45 ...Repeated for Contact Output 46 ...Repeated for Contact Output 47 ...Repeated for Contact Output 48 ...Repeated for Contact Output 49 ...Repeated for Contact Output 50 ...Repeated for Contact Output 51 ...Repeated for Contact Output 52 ...Repeated for Contact Output 53 ...Repeated for Contact Output 54 ...Repeated for Contact Output 55 ...Repeated for Contact Output 56 ...Repeated for Contact Output 57 ...Repeated for Contact Output 58 ...Repeated for Contact Output 59 ...Repeated for Contact Output 60 ...Repeated for Contact Output 61 ...Repeated for Contact Output 62 ...Repeated for Contact Output 63 ...Repeated for Contact Output 64 FlexLogic operand which initiates a reset Control Pushbutton 1 Function Control Pushbutton 1 Events ...Repeated for Control Pushbutton 2 ...Repeated for Control Pushbutton 3 ...Repeated for Control Pushbutton 4 ...Repeated for Control Pushbutton 5 ...Repeated for Control Pushbutton 6 ...Repeated for Control Pushbutton 7 Clear Event Records operand Clear Oscillography operand Clear Data Logger operand Clear Unauthorized Access operand Clear Platform Direct Input/Output Statistics operand Reserved (13 items) Force Contact Input x State (96 items) Force Contact Output x State (64 items) Direct Device ID Direct I/O Channel 1 Ring Configuration Function Platform Direct I/O Data Rate Direct I/O Channel 2 Ring Configuration Function Platform Direct I/O Crossover Function Direct input/output clear counters command 0 to 65535 0 to 65535 0 to 65535 0 to 65535 0 to 65535 --0 to 2 0 to 3 1 to 16 0 to 1 64 to 128 0 to 1 0 to 1 0 to 1 --------------------kbps ------1 1 1 1 1 --1 1 1 1 64 1 1 1 0 to 65535 0 to 1 0 to 1 ------1 1 1 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Reset (Read/Write Setting) F300 F102 F102 0 0 (Disabled) 0 (Disabled) Control Pushbuttons (Read/Write Setting) (7 modules)

Clear Records (Read/Write Setting) F300 F300 F300 F300 F300 F001 F144 F131 F001 F126 F001 F126 F102 F126 0 0 0 0 0 0 0 (Disabled) 0 (Disabled) 1 0 (No) 64 0 (No) 0 (Disabled) 0 (No)

Force Contact Inputs/Outputs (Read/Write Settings)

Direct Inputs/Outputs (Read/Write Setting)

Direct input/output commands (Read/Write Command)

GE Multilin

C30 Controller System

B-39

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 33 of 39)
ADDR C890 C891 C892 C893 C894 C898 C89C C8A0 C8A4 C8A8 C8AC C8B0 C8B4 C8B8 C8BC C8C0 C8C4 C8C8 C8CC C8D0 C8D4 C8D8 C8DC C8E0 C8E4 C8E8 C8EC C8F0 C8F4 C8F8 C8FC C900 C904 C908 C90C CA10 CA11 CA12 CA14 CA16 CA18 CA1A CA1C CA1E CA20 CA22 CA24 CA26 CA28 CA2A CA2C CA2E REGISTER NAME Direct Input 1 Device Number Direct Input 1 Number Direct Input 1 Default State Direct Input 1 Events ...Repeated for Direct Input 2 ...Repeated for Direct Input 3 ...Repeated for Direct Input 4 ...Repeated for Direct Input 5 ...Repeated for Direct Input 6 ...Repeated for Direct Input 7 ...Repeated for Direct Input 8 ...Repeated for Direct Input 9 ...Repeated for Direct Input 10 ...Repeated for Direct Input 11 ...Repeated for Direct Input 12 ...Repeated for Direct Input 13 ...Repeated for Direct Input 14 ...Repeated for Direct Input 15 ...Repeated for Direct Input 16 ...Repeated for Direct Input 17 ...Repeated for Direct Input 18 ...Repeated for Direct Input 19 ...Repeated for Direct Input 20 ...Repeated for Direct Input 21 ...Repeated for Direct Input 22 ...Repeated for Direct Input 23 ...Repeated for Direct Input 24 ...Repeated for Direct Input 25 ...Repeated for Direct Input 26 ...Repeated for Direct Input 27 ...Repeated for Direct Input 28 ...Repeated for Direct Input 29 ...Repeated for Direct Input 30 ...Repeated for Direct Input 31 ...Repeated for Direct Input 32 Direct Output 1 Operand Direct Output 1 Events ...Repeated for Direct Output 2 ...Repeated for Direct Output 3 ...Repeated for Direct Output 4 ...Repeated for Direct Output 5 ...Repeated for Direct Output 6 ...Repeated for Direct Output 7 ...Repeated for Direct Output 8 ...Repeated for Direct Output 9 ...Repeated for Direct Output 10 ...Repeated for Direct Output 11 ...Repeated for Direct Output 12 ...Repeated for Direct Output 13 ...Repeated for Direct Output 14 ...Repeated for Direct Output 15 ...Repeated for Direct Output 16 0 to 65535 0 to 1 ----1 1 F300 F102 RANGE 0 to 16 0 to 96 0 to 3 0 to 1 UNITS --------STEP 1 1 1 1 FORMAT F001 F001 F086 F102

APPENDIX B

DEFAULT 0 0 0 (Off) 0 (Disabled)

Direct inputs (Read/Write Setting) (96 modules)

Platform Direct Outputs (Read/Write Setting) (96 modules) 0 0 (Disabled)

B-40

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 34 of 39)


ADDR CA30 CA32 CA34 CA36 CA38 CA3A CA3C CA3E CA40 CA42 CA44 CA46 CA48 CA4A CA4C CA4E CAD0 CAD1 CAD2 CAD3 CAD4 CAD8 CAD9 CADA CADB CADC CAE0 CAE1 CAE2 CAE3 CAE4 CAE8 CAE9 CAEA CAEB CAEC CB00 CB21 CB22 CB23 CB24 CB48 CB6C CB90 CBB4 CBD8 CBFC CC20 CC44 CC68 CC8C CCB0 REGISTER NAME ...Repeated for Direct Output 17 ...Repeated for Direct Output 18 ...Repeated for Direct Output 19 ...Repeated for Direct Output 20 ...Repeated for Direct Output 21 ...Repeated for Direct Output 22 ...Repeated for Direct Output 23 ...Repeated for Direct Output 24 ...Repeated for Direct Output 25 ...Repeated for Direct Output 26 ...Repeated for Direct Output 27 ...Repeated for Direct Output 28 ...Repeated for Direct Output 29 ...Repeated for Direct Output 30 ...Repeated for Direct Output 31 ...Repeated for Direct Output 32 Direct Input/Output Channel 1 CRC Alarm Function Direct I/O Channel 1 CRC Alarm Message Count Direct Input/Output Channel 1 CRC Alarm Threshold Direct Input/Output Channel 1 CRC Alarm Events Reserved (4 items) Direct Input/Output Channel 2 CRC Alarm Function Direct I/O Channel 2 CRC Alarm Message Count Direct Input/Output Channel 2 CRC Alarm Threshold Direct Input/Output Channel 2 CRC Alarm Events Reserved (4 items) Direct I/O Ch 1 Unreturned Messages Alarm Function Direct I/O Ch 1 Unreturned Messages Alarm Msg Count Direct I/O Ch 1 Unreturned Messages Alarm Threshold Direct I/O Ch 1 Unreturned Messages Alarm Events Reserved (4 items) Direct IO Ch 2 Unreturned Messages Alarm Function Direct I/O Ch 2 Unreturned Messages Alarm Msg Count Direct I/O Ch 2 Unreturned Messages Alarm Threshold Direct I/O Channel 2 Unreturned Messages Alarm Events Reserved (4 items) Remote Device 1 GSSE/GOOSE Application ID Remote Device 1 GOOSE Ethernet APPID Remote Device 1 GOOSE Dataset Remote Device 1 in PMU Scheme ...Repeated for Device 2 ...Repeated for Device 3 ...Repeated for Device 4 ...Repeated for Device 5 ...Repeated for Device 6 ...Repeated for Device 7 ...Repeated for Device 8 ...Repeated for Device 9 ...Repeated for Device 10 ...Repeated for Device 11 ...Repeated for Device 12 ...Repeated for Device 13 0 to 1 100 to 10000 1 to 1000 0 to 1 1 to 1000 0 to 1 100 to 10000 1 to 1000 0 to 1 1 to 1000 0 to 1 100 to 10000 1 to 1000 0 to 1 1 to 1000 0 to 1 100 to 10000 1 to 1000 0 to 1 ----0 to 16383 0 to 8 0 to 1 ------------------------------------------------1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 --1 1 1 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Direct Input/Output Alarms (Read/Write Setting) F102 F001 F001 F102 F001 F102 F001 F001 F102 F001 F102 F001 F001 F102 F001 F102 F001 F001 F102 F001 F209 F001 F184 F126 0 (Disabled) 600 10 0 (Disabled) 10 0 (Disabled) 600 10 0 (Disabled) 10 0 (Disabled) 600 10 0 (Disabled) 10 0 (Disabled) 600 10 0 (Disabled) 10 Remote Device 1 0 0 (Fixed) 0 (No)

Remote Devices (Read/Write Setting) (16 modules)

GE Multilin

C30 Controller System

B-41

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 35 of 39)
ADDR CCD4 CCF8 CD1C CD40 CD64 CD88 CDAC CDD0 CDF4 CE18 CE3C CE60 CE84 CEA8 CECC CEF0 CF14 CF38 CF5C CFA0 CFA1 CFA2 CFA3 CFA4 CFAA CFB4 CFBE CFC8 CFD2 CFDC CFE6 CFF0 CFFA D004 D00E D018 D022 D02C D036 D040 D04A D054 D05E D068 D072 D07C D086 D090 D09A D0A4 D0AE D0B8 D0C2 REGISTER NAME ...Repeated for Device 14 ...Repeated for Device 15 ...Repeated for Device 16 ...Repeated for Device 17 ...Repeated for Device 18 ...Repeated for Device 19 ...Repeated for Device 20 ...Repeated for Device 21 ...Repeated for Device 22 ...Repeated for Device 23 ...Repeated for Device 24 ...Repeated for Device 25 ...Repeated for Device 26 ...Repeated for Device 27 ...Repeated for Device 28 ...Repeated for Device 29 ...Repeated for Device 30 ...Repeated for Device 31 ...Repeated for Device 32 Remote Input 1 Device Remote Input 1 Item Remote Input 1 Default State Remote Input 1 Events Remote Input 1 Name ...Repeated for Remote Input 2 ...Repeated for Remote Input 3 ...Repeated for Remote Input 4 ...Repeated for Remote Input 5 ...Repeated for Remote Input 6 ...Repeated for Remote Input 7 ...Repeated for Remote Input 8 ...Repeated for Remote Input 9 ...Repeated for Remote Input 10 ...Repeated for Remote Input 11 ...Repeated for Remote Input 12 ...Repeated for Remote Input 13 ...Repeated for Remote Input 14 ...Repeated for Remote Input 15 ...Repeated for Remote Input 16 ...Repeated for Remote Input 17 ...Repeated for Remote Input 18 ...Repeated for Remote Input 19 ...Repeated for Remote Input 20 ...Repeated for Remote Input 21 ...Repeated for Remote Input 22 ...Repeated for Remote Input 23 ...Repeated for Remote Input 24 ...Repeated for Remote Input 25 ...Repeated for Remote Input 26 ...Repeated for Remote Input 27 ...Repeated for Remote Input 28 ...Repeated for Remote Input 29 ...Repeated for Remote Input 30 1 to 16 0 to 64 0 to 3 0 to 1 1 to 64 ----------1 1 1 1 1 F001 F156 F086 F102 F205 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Remote Inputs (Read/Write Setting) (64 modules) 1 0 (None) 0 (Off) 0 (Disabled) Rem Ip 1

B-42

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 36 of 39)


ADDR D0CC D0D6 D0E0 D0EA D0F4 D0FE D108 D112 D11C D126 D130 D13A D144 D14E D158 D162 D16C D176 D180 D18A D194 D19E D1A8 D1B2 D1BC D1C6 D1D0 D1DA D1E4 D1EE D1F8 D202 D20C D216 D220 D221 D222 D224 D228 D22C D230 D234 D238 D23C D240 D244 D248 D24C D250 D254 D258 D25C D260 REGISTER NAME ...Repeated for Remote Input 31 ...Repeated for Remote Input 32 ...Repeated for Remote Input 33 ...Repeated for Remote Input 34 ...Repeated for Remote Input 35 ...Repeated for Remote Input 36 ...Repeated for Remote Input 37 ...Repeated for Remote Input 38 ...Repeated for Remote Input 39 ...Repeated for Remote Input 40 ...Repeated for Remote Input 41 ...Repeated for Remote Input 42 ...Repeated for Remote Input 43 ...Repeated for Remote Input 44 ...Repeated for Remote Input 45 ...Repeated for Remote Input 46 ...Repeated for Remote Input 47 ...Repeated for Remote Input 48 ...Repeated for Remote Input 49 ...Repeated for Remote Input 50 ...Repeated for Remote Input 51 ...Repeated for Remote Input 52 ...Repeated for Remote Input 53 ...Repeated for Remote Input 54 ...Repeated for Remote Input 55 ...Repeated for Remote Input 56 ...Repeated for Remote Input 57 ...Repeated for Remote Input 58 ...Repeated for Remote Input 59 ...Repeated for Remote Input 60 ...Repeated for Remote Input 61 ...Repeated for Remote Input 62 ...Repeated for Remote Input 63 ...Repeated for Remote Input 64 Remote Output DNA 1 Operand Remote Output DNA 1 Events Reserved (2 items) ...Repeated for Remote Output 2 ...Repeated for Remote Output 3 ...Repeated for Remote Output 4 ...Repeated for Remote Output 5 ...Repeated for Remote Output 6 ...Repeated for Remote Output 7 ...Repeated for Remote Output 8 ...Repeated for Remote Output 9 ...Repeated for Remote Output 10 ...Repeated for Remote Output 11 ...Repeated for Remote Output 12 ...Repeated for Remote Output 13 ...Repeated for Remote Output 14 ...Repeated for Remote Output 15 ...Repeated for Remote Output 16 ...Repeated for Remote Output 17 0 to 65535 0 to 1 0 to 1 ------1 1 1 RANGE UNITS STEP

B.4 MEMORY MAPPING

FORMAT

DEFAULT

Remote Output DNA Pairs (Read/Write Setting) (32 modules) F300 F102 F001 0 0 (Disabled) 0

GE Multilin

C30 Controller System

B-43

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 37 of 39)
ADDR D264 D268 D26C D270 D274 D278 D27C D280 D284 D288 D28C D290 D294 D298 D29C D2A0 D2A1 D2A2 D2A4 D2A8 D2AC D2B0 D2B4 D2B8 D2BC D2C0 D2C4 D2C8 D2CC D2D0 D2D4 D2D8 D2DC D2E0 D2E4 D2E8 D2EC D2F0 D2F4 D2F8 D2FC D300 D304 D308 D30C D310 D314 D318 D31C D320 D321 D322 REGISTER NAME ...Repeated for Remote Output 18 ...Repeated for Remote Output 19 ...Repeated for Remote Output 20 ...Repeated for Remote Output 21 ...Repeated for Remote Output 22 ...Repeated for Remote Output 23 ...Repeated for Remote Output 24 ...Repeated for Remote Output 25 ...Repeated for Remote Output 26 ...Repeated for Remote Output 27 ...Repeated for Remote Output 28 ...Repeated for Remote Output 29 ...Repeated for Remote Output 30 ...Repeated for Remote Output 31 ...Repeated for Remote Output 32 Remote Output UserSt 1 Operand Remote Output UserSt 1 Events Reserved (2 items) ...Repeated for Remote Output 2 ...Repeated for Remote Output 3 ...Repeated for Remote Output 4 ...Repeated for Remote Output 5 ...Repeated for Remote Output 6 ...Repeated for Remote Output 7 ...Repeated for Remote Output 8 ...Repeated for Remote Output 9 ...Repeated for Remote Output 10 ...Repeated for Remote Output 11 ...Repeated for Remote Output 12 ...Repeated for Remote Output 13 ...Repeated for Remote Output 14 ...Repeated for Remote Output 15 ...Repeated for Remote Output 16 ...Repeated for Remote Output 17 ...Repeated for Remote Output 18 ...Repeated for Remote Output 19 ...Repeated for Remote Output 20 ...Repeated for Remote Output 21 ...Repeated for Remote Output 22 ...Repeated for Remote Output 23 ...Repeated for Remote Output 24 ...Repeated for Remote Output 25 ...Repeated for Remote Output 26 ...Repeated for Remote Output 27 ...Repeated for Remote Output 28 ...Repeated for Remote Output 29 ...Repeated for Remote Output 30 ...Repeated for Remote Output 31 ...Repeated for Remote Output 32 IEC 61850 GGIO2.CF.SPCSO1.ctlModel Value IEC 61850 GGIO2.CF.SPCSO2.ctlModel Value IEC 61850 GGIO2.CF.SPCSO3.ctlModel Value 0 to 2 0 to 2 0 to 2 ------1 1 1 F001 F001 F001 0 to 65535 0 to 1 0 to 1 ------1 1 1 F300 F102 F001 RANGE UNITS STEP FORMAT

APPENDIX B

DEFAULT

Remote Output UserSt Pairs (Read/Write Setting) (32 modules) 0 0 (Disabled) 0

IEC 61850 GGIO2 Control Configuration (Read/Write Setting) (64 modules) 2 2 2

B-44

C30 Controller System

GE Multilin

APPENDIX B Table B9: MODBUS MEMORY MAP (Sheet 38 of 39)


ADDR D323 D324 D325 D326 D327 D328 D329 D32A D32B D32C D32D D32E D32F D330 D331 D332 D333 D334 D335 D336 D337 D338 D339 D33A D33B D33C D33D D33E D33F D340 D341 D342 D343 D344 D345 D346 D347 D348 D349 D34A D34B D34C D34D D34E D34F D350 D351 D352 D353 D354 D355 D356 D357 D358 REGISTER NAME IEC 61850 GGIO2.CF.SPCSO4.ctlModel Value IEC 61850 GGIO2.CF.SPCSO5.ctlModel Value IEC 61850 GGIO2.CF.SPCSO6.ctlModel Value IEC 61850 GGIO2.CF.SPCSO7.ctlModel Value IEC 61850 GGIO2.CF.SPCSO8.ctlModel Value IEC 61850 GGIO2.CF.SPCSO9.ctlModel Value IEC 61850 GGIO2.CF.SPCSO10.ctlModel Value IEC 61850 GGIO2.CF.SPCSO11.ctlModel Value IEC 61850 GGIO2.CF.SPCSO12.ctlModel Value IEC 61850 GGIO2.CF.SPCSO13.ctlModel Value IEC 61850 GGIO2.CF.SPCSO14.ctlModel Value IEC 61850 GGIO2.CF.SPCSO15.ctlModel Value IEC 61850 GGIO2.CF.SPCSO16.ctlModel Value IEC 61850 GGIO2.CF.SPCSO17.ctlModel Value IEC 61850 GGIO2.CF.SPCSO18.ctlModel Value IEC 61850 GGIO2.CF.SPCSO19.ctlModel Value IEC 61850 GGIO2.CF.SPCSO20.ctlModel Value IEC 61850 GGIO2.CF.SPCSO21.ctlModel Value IEC 61850 GGIO2.CF.SPCSO22.ctlModel Value IEC 61850 GGIO2.CF.SPCSO23.ctlModel Value IEC 61850 GGIO2.CF.SPCSO24.ctlModel Value IEC 61850 GGIO2.CF.SPCSO25.ctlModel Value IEC 61850 GGIO2.CF.SPCSO26.ctlModel Value IEC 61850 GGIO2.CF.SPCSO27.ctlModel Value IEC 61850 GGIO2.CF.SPCSO28.ctlModel Value IEC 61850 GGIO2.CF.SPCSO29.ctlModel Value IEC 61850 GGIO2.CF.SPCSO30.ctlModel Value IEC 61850 GGIO2.CF.SPCSO31.ctlModel Value IEC 61850 GGIO2.CF.SPCSO32.ctlModel Value IEC 61850 GGIO2.CF.SPCSO33.ctlModel Value IEC 61850 GGIO2.CF.SPCSO34.ctlModel Value IEC 61850 GGIO2.CF.SPCSO35.ctlModel Value IEC 61850 GGIO2.CF.SPCSO36.ctlModel Value IEC 61850 GGIO2.CF.SPCSO37.ctlModel Value IEC 61850 GGIO2.CF.SPCSO38.ctlModel Value IEC 61850 GGIO2.CF.SPCSO39.ctlModel Value IEC 61850 GGIO2.CF.SPCSO40.ctlModel Value IEC 61850 GGIO2.CF.SPCSO41.ctlModel Value IEC 61850 GGIO2.CF.SPCSO42.ctlModel Value IEC 61850 GGIO2.CF.SPCSO43.ctlModel Value IEC 61850 GGIO2.CF.SPCSO44.ctlModel Value IEC 61850 GGIO2.CF.SPCSO45.ctlModel Value IEC 61850 GGIO2.CF.SPCSO46.ctlModel Value IEC 61850 GGIO2.CF.SPCSO47.ctlModel Value IEC 61850 GGIO2.CF.SPCSO48.ctlModel Value IEC 61850 GGIO2.CF.SPCSO49.ctlModel Value IEC 61850 GGIO2.CF.SPCSO50.ctlModel Value IEC 61850 GGIO2.CF.SPCSO51.ctlModel Value IEC 61850 GGIO2.CF.SPCSO52.ctlModel Value IEC 61850 GGIO2.CF.SPCSO53.ctlModel Value IEC 61850 GGIO2.CF.SPCSO54.ctlModel Value IEC 61850 GGIO2.CF.SPCSO55.ctlModel Value IEC 61850 GGIO2.CF.SPCSO56.ctlModel Value IEC 61850 GGIO2.CF.SPCSO57.ctlModel Value RANGE 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 UNITS ------------------------------------------------------------------------------------------------------------STEP 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

B.4 MEMORY MAPPING

FORMAT F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001 F001

DEFAULT 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

GE Multilin

C30 Controller System

B-45

B.4 MEMORY MAPPING Table B9: MODBUS MEMORY MAP (Sheet 39 of 39)
ADDR D359 D35A D35B D35C D35D D35E D380 D382 D384 D388 D38C D390 D394 D398 D39C D3A0 D3A4 D3A8 D3AC D3B0 D3B4 D3B8 D3BC D3C0 D3C4 D3C8 D3CC D3D0 D3D4 D3D8 D3DC D3E0 D3E4 D3E8 D3EC D3F0 D3F4 D3F8 D3FC ED00 ED01 ED07 ED09 REGISTER NAME IEC 61850 GGIO2.CF.SPCSO58.ctlModel Value IEC 61850 GGIO2.CF.SPCSO59.ctlModel Value IEC 61850 GGIO2.CF.SPCSO60.ctlModel Value IEC 61850 GGIO2.CF.SPCSO61.ctlModel Value IEC 61850 GGIO2.CF.SPCSO62.ctlModel Value IEC 61850 GGIO2.CF.SPCSO63.ctlModel Value Remote Device 1 StNum Remote Device 1 SqNum ...Repeated for Remote Device 2 ...Repeated for Remote Device 3 ...Repeated for Remote Device 4 ...Repeated for Remote Device 5 ...Repeated for Remote Device 6 ...Repeated for Remote Device 7 ...Repeated for Remote Device 8 ...Repeated for Remote Device 9 ...Repeated for Remote Device 10 ...Repeated for Remote Device 11 ...Repeated for Remote Device 12 ...Repeated for Remote Device 13 ...Repeated for Remote Device 14 ...Repeated for Remote Device 15 ...Repeated for Remote Device 16 ...Repeated for Remote Device 17 ...Repeated for Remote Device 18 ...Repeated for Remote Device 19 ...Repeated for Remote Device 20 ...Repeated for Remote Device 21 ...Repeated for Remote Device 22 ...Repeated for Remote Device 23 ...Repeated for Remote Device 24 ...Repeated for Remote Device 25 ...Repeated for Remote Device 26 ...Repeated for Remote Device 27 ...Repeated for Remote Device 28 ...Repeated for Remote Device 29 ...Repeated for Remote Device 30 ...Repeated for Remote Device 31 ...Repeated for Remote Device 32 FlexLogic displays active Reserved (6 items) Last settings change date Template bitmask (750 items) 0 to 1 --0 to 4294967295 0 to 65535 --------1 --1 1 F102 --F050 F001 RANGE 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 4294967295 0 to 4294967295 UNITS ----------------STEP 1 1 1 1 1 1 1 1 FORMAT F001 F001 F001 F001 F001 F001 F003 F003

APPENDIX B

DEFAULT 2 2 2 2 2 2 0 0

Remote Device Status (Read Only) (16 modules)

Setting file template values (read only) 1 (Enabled) --0 0

B-46

C30 Controller System

GE Multilin

APPENDIX B

B.4 MEMORY MAPPING B.4.2 DATA FORMATS

F001 UR_UINT16 UNSIGNED 16 BIT INTEGER

F051 UR_UINT32 DATE in SR format (alternate format for F050) First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January, 2=February,...,12=December; Day: 1 to 31 in steps of 1 Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1

F002 UR_SINT16 SIGNED 16 BIT INTEGER

F003 UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers) High order word is stored in the first register. Low order word is stored in the second register.

F052 UR_UINT32 TIME in SR format (alternate format for F050) First 16 bits are Hours/Minutes (HH:MM:xx.xxx). Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm; Minutes: 0 to 59 in steps of 1 Last 16 bits are Seconds 1=00.001,...,59999=59.999s) (xx:xx:.SS.SSS): 0=00.000s,

F004 UR_SINT32 SIGNED 32 BIT INTEGER (2 registers) High order word is stored in the first register/ Low order word is stored in the second register.

F060 FLOATING_POINT IEEE FLOATING POINT (32 bits)

F005 UR_UINT8 UNSIGNED 8 BIT INTEGER

F070 HEX2 2 BYTES - 4 ASCII DIGITS

F006 UR_SINT8 SIGNED 8 BIT INTEGER

F071 HEX4 4 BYTES - 8 ASCII DIGITS

F011 UR_UINT16 FLEXCURVE DATA (120 points) A FlexCurve is an array of 120 consecutive data points (x, y) which are interpolated to generate a smooth curve. The y-axis is the user defined trip or operation time setting; the x-axis is the pickup ratio and is pre-defined. Refer to format F119 for a listing of the pickup ratios; the enumeration value for the pickup ratio indicates the offset into the FlexCurve base address where the corresponding time value is stored.

F072 HEX6 6 BYTES - 12 ASCII DIGITS

F073 HEX8 8 BYTES - 16 ASCII DIGITS

F074 HEX20 20 BYTES - 40 ASCII DIGITS

F012 DISPLAY_SCALE DISPLAY SCALING (unsigned 16-bit integer) MSB indicates the SI units as a power of ten. LSB indicates the number of decimal points to display. Example: Current values are stored as 32 bit numbers with three decimal places and base units in Amps. If the retrieved value is 12345.678 A and the display scale equals 0x0302 then the displayed value on the unit is 12.35 kA.

F083 ENUMERATION: SELECTOR MODES 0 = Time-Out, 1 = Acknowledge

F084 ENUMERATION: SELECTOR POWER UP 0 = Restore, 1 = Synchronize, 2 = Sync/Restore

F040 UR_UINT48 48-BIT UNSIGNED INTEGER

F086 ENUMERATION: DIGITAL INPUT DEFAULT STATE 0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On

F050 UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER) Gives the current time in seconds elapsed since 00:00:00 January 1, 1970.

GE Multilin

C30 Controller System

B-47

B.4 MEMORY MAPPING

APPENDIX B

F090 ENUMERATION: LATCHING OUTPUT TYPE 0 = Operate-dominant, 1 = Reset-dominant

F110 ENUMERATION: CONTACT OUTPUT LED CONTROL 0 = Trip, 1 = Alarm, 2 = None

F100 ENUMERATION: VT CONNECTION TYPE 0 = Wye; 1 = Delta

F112 ENUMERATION: RS485 BAUD RATES


bitmask 0 value 300 1200 2400 4800 bitmask 4 5 6 7 value 9600 19200 38400 57600 bitmask 8 9 10 11 value 115200 14400 28800 33600

F101 ENUMERATION: MESSAGE DISPLAY INTENSITY 0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%

1 2 3

F102 ENUMERATION: DISABLED/ENABLED 0 = Disabled; 1 = Enabled

F113 ENUMERATION: PARITY 0 = None, 1 = Odd, 2 = Even

F104 ENUMERATION: RESET TYPE 0 = Instantaneous, 1 = Timed, 2 = Linear

F114 ENUMERATION: IRIG-B SIGNAL TYPE 0 = None, 1 = DC Shift, 2 = Amplitude Modulated

F105 ENUMERATION: LOGIC INPUT 0 = Disabled, 1 = Input 1, 2 = Input 2

F115 ENUMERATION: BREAKER STATUS 0 = Auxiliary A, 1 = Auxiliary B

F106 ENUMERATION: PHASE ROTATION 0 = ABC, 1 = ACB

F116 ENUMERATION: NEUTRAL OVERVOLTAGE CURVES 0 = Definite Time, 1 = FlexCurve A, 2 = FlexCurve B, 3 = FlexCurve C

F108 ENUMERATION: OFF/ON 0 = Off, 1 = On

F117 ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS 0 = 172 cycles, 1 = 336 cycles, 2 = 718 cycles, 3 = 159 cycles

F109 ENUMERATION: CONTACT OUTPUT OPERATION 0 = Self-reset, 1 = Latched, 2 = Disabled

F118 ENUMERATION: OSCILLOGRAPHY MODE 0 = Automatic Overwrite, 1 = Protected

B-48

C30 Controller System

GE Multilin

APPENDIX B
bitmask element

B.4 MEMORY MAPPING

F119 ENUMERATION: FLEXCURVE PICKUP RATIOS


mask 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 value 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.48 0.50 0.52 0.54 0.56 0.58 0.60 0.62 0.64 0.66 0.68 0.70 0.72 0.74 0.76 0.78 0.80 0.82 0.84 0.86 mask 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 value 0.88 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 1.03 1.05 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40 2.50 2.60 2.70 2.80 mask 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 value 2.90 3.00 3.10 3.20 3.30 3.40 3.50 3.60 3.70 3.80 3.90 4.00 4.10 4.20 4.30 4.40 4.50 4.60 4.70 4.80 4.90 5.00 5.10 5.20 5.30 5.40 5.50 5.60 5.70 5.80 mask 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 value 5.90 6.00 6.50 7.00 7.50 8.00 8.50 9.00 9.50 10.00 10.50 11.00 11.50 12.00 12.50 13.00 13.50 14.00 14.50 15.00 15.50 16.00 16.50 17.00 17.50 18.00 18.50 19.00 19.50 20.00

21 24 25 32 33 34 35 36 37 38 39 40 41 42 43 48 49 50 51 52 53 56 57 60 61 64 65 66 67 68 69 70 71 72 73

Phase Time Overcurrent 6 Phase Directional Overcurrent 1 Phase Directional Overcurrent 2 Neutral Instantaneous Overcurrent 1 Neutral Instantaneous Overcurrent 2 Neutral Instantaneous Overcurrent 3 Neutral Instantaneous Overcurrent 4 Neutral Instantaneous Overcurrent 5 Neutral Instantaneous Overcurrent 6 Neutral Instantaneous Overcurrent 7 Neutral Instantaneous Overcurrent 8 Neutral Instantaneous Overcurrent 9 Neutral Instantaneous Overcurrent 10 Neutral Instantaneous Overcurrent 11 Neutral Instantaneous Overcurrent 12 Neutral Time Overcurrent 1 Neutral Time Overcurrent 2 Neutral Time Overcurrent 3 Neutral Time Overcurrent 4 Neutral Time Overcurrent 5 Neutral Time Overcurrent 6 Neutral Directional Overcurrent 1 Neutral Directional Overcurrent 2 Negative Sequence Directional Overcurrent 1 Negative Sequence Directional Overcurrent 2 Ground Instantaneous Overcurrent 1 Ground Instantaneous Overcurrent 2 Ground Instantaneous Overcurrent 3 Ground Instantaneous Overcurrent 4 Ground Instantaneous Overcurrent 5 Ground Instantaneous Overcurrent 6 Ground Instantaneous Overcurrent 7 Ground Instantaneous Overcurrent 8 Ground Instantaneous Overcurrent 9 Ground Instantaneous Overcurrent 10 Ground Instantaneous Overcurrent 11 Ground Instantaneous Overcurrent 12 Ground Time Overcurrent 1 Ground Time Overcurrent 2 Ground Time Overcurrent 3 Ground Time Overcurrent 4 Ground Time Overcurrent 5 Ground Time Overcurrent 6 Negative Sequence Instantaneous Overcurrent 1 Negative Sequence Instantaneous Overcurrent 2 Opposite Phase Rotation Negative Sequence Time Overcurrent 1 Negative Sequence Time Overcurrent 2 Negative Sequence Overvoltage Phase Undervoltage 1 Phase Undervoltage 2 Auxiliary Overvoltage 1 Phase Overvoltage 1

F122 ENUMERATION: ELEMENT INPUT SIGNAL TYPE 0 = Phasor, 1 = RMS

74 75 80 81

F123 ENUMERATION: CT SECONDARY 0 = 1 A, 1 = 5 A

82 83 84 85 96

F124 ENUMERATION: LIST OF ELEMENTS


bitmask 16 17 18 19 20 element Phase Time Overcurrent 1 Phase Time Overcurrent 2 Phase Time Overcurrent 3 Phase Time Overcurrent 4 Phase Time Overcurrent 5

97 101 112 113 120 144 145 148 152

GE Multilin

C30 Controller System

B-49

B.4 MEMORY MAPPING


bitmask 154 156 336 337 388 element Compensated Overvoltage 1 Neutral Overvoltage 1 Setting Group Reset Selector 1 Selector 2 Control pushbutton 1 Control pushbutton 2 Control pushbutton 3 Control pushbutton 4 Control pushbutton 5 Control pushbutton 6 Control pushbutton 7 FlexElement 1 FlexElement 2 FlexElement 3 FlexElement 4 FlexElement 5 FlexElement 6 FlexElement 7 FlexElement 8 Non-volatile Latch 1 Non-volatile Latch 2 Non-volatile Latch 3 Non-volatile Latch 4 Non-volatile Latch 5 Non-volatile Latch 6 Non-volatile Latch 7 Non-volatile Latch 8 Non-volatile Latch 9 Non-volatile Latch 10 Non-volatile Latch 11 Non-volatile Latch 12 Non-volatile Latch 13 Non-volatile Latch 14 Non-volatile Latch 15 Non-volatile Latch 16 8-bit Switch 1 8-bit Switch 2 8-bit Switch 3 8-bit Switch 4 8-bit Switch 5 8-bit Switch 6 Digital Counter 1 Digital Counter 2 Digital Counter 3 Digital Counter 4 Digital Counter 5 Digital Counter 6 Digital Counter 7 Digital Counter 8 Digital Element 1 Digital Element 2 bitmask 694 695 696 697 698 699 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 738 739 842 843 844 845 846 847 849 element Digital Element 3 Digital Element 4 Digital Element 5 Digital Element 6 Digital Element 7 Digital Element 8 Digital Element 9 Digital Element 10 Digital Element 11 Digital Element 12 Digital Element 13 Digital Element 14 Digital Element 15 Digital Element 16 Digital Element 17 Digital Element 18 Digital Element 19 Digital Element 20 Digital Element 21 Digital Element 22 Digital Element 23 Digital Element 24 Digital Element 25 Digital Element 26 Digital Element 27 Digital Element 28 Digital Element 29 Digital Element 30 Digital Element 31 Digital Element 32 Digital Element 33 Digital Element 34 Digital Element 35 Digital Element 36 Digital Element 37 Digital Element 38 Digital Element 39 Digital Element 40 Digital Element 41 Digital Element 42 Digital Element 43 Digital Element 44 Digital Element 45 Digital Element 46 Digital Element 47 Digital Element 48 Trip Bus 1 Trip Bus 2 Trip Bus 3 Trip Bus 4 Trip Bus 5 Trip Bus 6 RTD Input 1

APPENDIX B

389 390 391 392 393 394 395 396 400 401 402 403 404 405 406 407 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 536 537 538 539 540 541 544 545 546 547 548 549 550 551 692 693

B-50

C30 Controller System

GE Multilin

APPENDIX B
bitmask 850 851 852 853 854 855 856 857 858 859 860 861 862 863 864 865 866 867 868 869 870 871 872 873 874 875 876 877 878 879 880 881 882 883 884 885 886 887 888 889 890 891 892 893 894 895 896 900 901 902 903 904 905 element RTD Input 2 RTD Input 3 RTD Input 4 RTD Input 5 RTD Input 6 RTD Input 7 RTD Input 8 RTD Input 9 RTD Input 10 RTD Input 11 RTD Input 12 RTD Input 13 RTD Input 14 RTD Input 15 RTD Input 16 RTD Input 17 RTD Input 18 RTD Input 19 RTD Input 20 RTD Input 21 RTD Input 22 RTD Input 23 RTD Input 24 RTD Input 25 RTD Input 26 RTD Input 27 RTD Input 28 RTD Input 29 RTD Input 30 RTD Input 31 RTD Input 32 RTD Input 33 RTD Input 34 RTD Input 35 RTD Input 36 RTD Input 37 RTD Input 38 RTD Input 39 RTD Input 40 RTD Input 41 RTD Input 42 RTD Input 43 RTD Input 44 RTD Input 45 RTD Input 46 RTD Input 47 RTD Input 48 User-Programmable Pushbutton 1 User-Programmable Pushbutton 2 User-Programmable Pushbutton 3 User-Programmable Pushbutton 4 User-Programmable Pushbutton 5 User-Programmable Pushbutton 6 bitmask 906 907 908 909 910 911 912 913 914 915 920 921 922 923 924 925 926 927 968 969 element

B.4 MEMORY MAPPING

User-Programmable Pushbutton 7 User-Programmable Pushbutton 8 User-Programmable Pushbutton 9 User-Programmable Pushbutton 10 User-Programmable Pushbutton 11 User-Programmable Pushbutton 12 User-Programmable Pushbutton 13 User-Programmable Pushbutton 14 User-Programmable Pushbutton 15 User-Programmable Pushbutton 16 Disconnect switch 1 Disconnect switch 2 Disconnect switch 3 Disconnect switch 4 Disconnect switch 5 Disconnect switch 6 Disconnect switch 7 Disconnect switch 8 Breaker 1 Breaker 2

F125 ENUMERATION: ACCESS LEVEL 0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service

F126 ENUMERATION: NO/YES CHOICE 0 = No, 1 = Yes

F127 ENUMERATION: LATCHED OR SELF-RESETTING 0 = Latched, 1 = Self-Reset

F128 ENUMERATION: CONTACT INPUT THRESHOLD 0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC

F129 ENUMERATION: FLEXLOGIC TIMER TYPE 0 = millisecond, 1 = second, 2 = minute

F130 ENUMERATION: SIMULATION MODE 0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault

F131 ENUMERATION: FORCED CONTACT OUTPUT STATE 0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze

GE Multilin

C30 Controller System

B-51

B.4 MEMORY MAPPING


Bitmask Error Unit Not Programmed System Exception Latching Output Discrepancy Ethernet Switch Fail Maintenance Alert 01 SNTP Failure --Primary Ethernet Fail Secondary Ethernet Fail Temperature Monitor Process Bus Trouble Brick Trouble Field RTD Trouble Field TDR Trouble Remote Device Offline Direct Device Offline Direct Input/Output Ring Break Any Minor Error Any Major Error Unit Not Calibrated ------Watchdog Error Low On Memory --Module Failure 01 Module Failure 02 Module Failure 03 Module Failure 04 Module Failure 05 Module Failure 06 Module Failure 07 Module Failure 08 Module Failure 09 Incompatible Hardware Module Failure 10 Module Failure 11 Module Failure 12

APPENDIX B

F133 ENUMERATION: PROGRAM STATE 0 = Not Programmed, 1 = Programmed

13 14 15 16

F134 ENUMERATION: PASS/FAIL 0 = Fail, 1 = OK, 2 = n/a

17 18 19 20 21

F135 ENUMERATION: GAIN CALIBRATION 0 = 0x1, 1 = 1x16

22 23 24 25

F136 ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS 0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles 3 = 3 x 64 cycles, 4 = 1 x 128 cycles

26 27 28 29 30 31

F137 ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON FUNCTION 0 = Disabled, 1 = Self-Reset, 2 = Latched

32 33 34 35 36

F138 ENUMERATION: OSCILLOGRAPHY FILE TYPE 0 = Data File, 1 = Configuration File, 2 = Header File

37 38 43 44 45

F140 ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE, DISABLED 0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V, 3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A, 6 = Notched 2 A

46 47 48 49 50 51 52

F141 ENUMERATION: SELF TEST ERRORS


Bitmask 0 1 2 3 4 5 6 7 8 9 10 11 12 Error Any Self Tests IRIG-B Failure Port 1 Offline Port 2 Offline Port 3 Offline Port 4 Offline Port 5 Offline Port 6 Offline RRTD Communcations Failure Voltage Monitor FlexLogic Error Token Equipment Mismatch Process Bus Failure

53 54 55

F142 ENUMERATION: EVENT RECORDER ACCESS FILE TYPE 0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause

F143 UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number) A bit value of 0 = no error, 1 = error

F144 ENUMERATION: FORCED CONTACT INPUT STATE 0 = Disabled, 1 = Open, 2 = Closed

B-52

C30 Controller System

GE Multilin

APPENDIX B
bitmask definition Test Mode Isolated Test Mode Forcible Test Mode Disabled

B.4 MEMORY MAPPING

F145 ENUMERATION: ALPHABET LETTER


bitmask type 0 1 2 3 4 5 6 null A B C D E F bitmask type 7 8 9 10 11 12 13 G H I J K L M bitmask type 14 15 16 17 18 19 20 N O P Q R S T bitmask type 21 22 23 24 25 26 U V W X Y Z

26 27 28 29 30 31 32 33 34

Temperature Warning On Temperature Warning Off Unauthorized Access System Integrity Recovery System Integrity Recovery 06 System Integrity Recovery 07

F146 ENUMERATION: MISCELLANEOUS EVENT CAUSES


bitmask 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 definition Events Cleared Oscillography Triggered Date/time Changed Default Settings Loaded Test Mode Forcing On Test Mode Forcing Off Power On Power Off Relay In Service Relay Out Of Service Watchdog Reset Oscillography Clear Reboot Command Led Test Initiated Flash Programming Fault Report Trigger User Programmable Fault Report Trigger --Reload CT/VT module Settings --Ethernet Port 1 Offline Ethernet Port 2 Offline Ethernet Port 3 Offline Ethernet Port 4 Offline Ethernet Port 5 Offline Ethernet Port 6 Offline

F151 ENUMERATION: RTD SELECTION


bitmask 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RTD# NONE RTD 1 RTD 2 RTD 3 RTD 4 RTD 5 RTD 6 RTD 7 RTD 8 RTD 9 RTD 10 RTD 11 RTD 12 RTD 13 RTD 14 RTD 15 RTD 16 bitmask 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RTD# RTD 17 RTD 18 RTD 19 RTD 20 RTD 21 RTD 22 RTD 23 RTD 24 RTD 25 RTD 26 RTD 27 RTD 28 RTD 29 RTD 30 RTD 31 RTD 32 bitmask 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 RTD# RTD 33 RTD 34 RTD 35 RTD 36 RTD 37 RTD 38 RTD 39 RTD 40 RTD 41 RTD 42 RTD 43 RTD 44 RTD 45 RTD 46 RTD 47 RTD 48

F152 ENUMERATION: SETTING GROUP 0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3 4 = Group 4, 5 = Group 5, 6 = Group 6

F155 ENUMERATION: REMOTE DEVICE STATE 0 = Offline, 1 = Online

GE Multilin

C30 Controller System

B-53

B.4 MEMORY MAPPING

APPENDIX B

F156 ENUMERATION: REMOTE INPUT BIT PAIRS


bitmask 0 1 value NONE DNA-1 DNA-2 DNA-3 DNA-4 DNA-5 DNA-6 DNA-7 DNA-8 DNA-9 DNA-10 DNA-11 DNA-12 DNA-13 DNA-14 DNA-15 DNA-16 DNA-17 DNA-18 DNA-19 DNA-20 DNA-21 DNA-22 DNA-23 DNA-24 DNA-25 DNA-26 DNA-27 DNA-28 DNA-29 DNA-30 DNA-31 DNA-32 UserSt-1 UserSt-2 bitmask 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 128 value UserSt-3 UserSt-4 UserSt-5 UserSt-6 UserSt-7 UserSt-8 UserSt-9 UserSt-10 UserSt-11 UserSt-12 UserSt-13 UserSt-14 UserSt-15 UserSt-16 UserSt-17 UserSt-18 UserSt-19 UserSt-20 UserSt-21 UserSt-22 UserSt-23 UserSt-24 UserSt-25 UserSt-26 UserSt-27 UserSt-28 UserSt-29 UserSt-30 UserSt-31 UserSt-32 Dataset Item 1 Dataset Item 2 Dataset Item 3 Dataset Item 64

F167 ENUMERATION: SIGNAL SOURCE 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34

F168 ENUMERATION: INRUSH INHIBIT FUNCTION 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd

F170 ENUMERATION: LOW/HIGH OFFSET and GAIN TRANSDUCER INPUT/OUTPUT SELECTION 0 = LOW, 1 = HIGH

F171 ENUMERATION: TRANSDUCER CHANNEL INPUT TYPE 0 = dcmA IN, 1 = Ohms IN, 2 = RTD IN, 3 = dcmA OUT, 4 = RRTD IN

F172 ENUMERATION: SLOT LETTERS


bitmask 0 1 2 3 slot F G H J bitmask 4 5 6 7 slot K L M N bitmask 8 9 10 11 slot P R S T bitmask 12 13 14 15 slot U V W X

F173 ENUMERATION: DCMA INPUT/OUTPUT RANGE


bitmask 0 1 2 3 4 5 6 dcmA input/output range 0 to 1 mA 0 to 1 mA 1 to 1 mA 0 to 5 mA 0 to 10 mA 0 to 20 mA 4 to 20 mA

F157 ENUMERATION: BREAKER MODE 0 = 3-Pole, 1 = 1-Pole F174 ENUMERATION: TRANSDUCER RTD INPUT TYPE 0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel, 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper

F159 ENUMERATION: BREAKER AUX CONTACT KEYING 0 = 52a, 1 = 52b, 2 = None

F175 ENUMERATION: PHASE LETTERS 0 = A, 1 = B, 2 = C

F166 ENUMERATION: AUXILIARY VT CONNECTION TYPE 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca

B-54

C30 Controller System

GE Multilin

APPENDIX B

B.4 MEMORY MAPPING

F177 ENUMERATION: COMMUNICATION PORT 0 = None, 1 = COM1-RS485, 2 = COM2-RS485, 3 = Front Panel-RS232, 4 = Network - TCP, 5 = Network - UDP

F190 ENUMERATION: SIMULATED KEYPRESS


bitmsk 0 keypress --use between real keys 1 2 3 4 5 6 7 8 9 0 Decimal Point Plus/Minus Value Up Value Down Message Up Message Down Message Left Message Right Menu Help Escape --bitmsk 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 43 44 45 46 47 48 49 50 keypress Reset User 1 User 2 User 3 User-programmable key 1 User-programmable key 2 User-programmable key 3 User-programmable key 4 User-programmable key 5 User-programmable key 6 User-programmable key 7 User-programmable key 8 User-programmable key 9 User-programmable key 10 User-programmable key 11 User-programmable key 12 User-programmable key 13 User-programmable key 14 User-programmable key 15 User-programmable key 16 User 4 (control pushbutton) User 5 (control pushbutton) User 6 (control pushbutton) User 7 (control pushbutton)

F178 ENUMERATION: DATA LOGGER RATES 0 = 1 sec, 1 = 1 min, 2 = 5 min, 3 = 10 min, 4 = 15 min, 5 = 20 min, 6 = 30 min, 7 = 60 min, 8 = 15 ms, 9 = 30 ms, 10 = 100 ms, 11 = 500 ms

1 2 3 4 5 6

F180 ENUMERATION: PHASE/GROUND 0 = PHASE, 1 = GROUND

7 8 9 10 11

F181 ENUMERATION: ODD/EVEN/NONE 0 = ODD, 1 = EVEN, 2 = NONE

12 13 14 15

F183 ENUMERATION: AC INPUT WAVEFORMS


bitmask 0 1 2 3 4 definition Off 8 samples/cycle 16 samples/cycle 32 samples/cycle 64 samples/cycle

16 17 18 19 20 21 22

F192 ENUMERATION: ETHERNET OPERATION MODE F184 ENUMERATION: REMOTE DEVICE GOOSE DATASET
value 0 1 2 3 4 5 6 7 8 GOOSE dataset Off GooseIn 1 GooseIn 2 GooseIn 3 GooseIn 4 GooseIn 5 GooseIn 6 GooseIn 7 GooseIn 8

0 = Half-Duplex, 1 = Full-Duplex

F194 ENUMERATION: DNP SCALE 0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000, 7 = 100000, 8 = 0.001

F199 ENUMERATION: DISABLED/ENABLED/CUSTOM 0 = Disabled, 1 = Enabled, 2 = Custom

F185 ENUMERATION: PHASE A,B,C, GROUND SELECTOR 0 = A, 1 = B, 2 = C, 3 = G

F200 TEXT40: 40-CHARACTER ASCII TEXT 20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB

F186 ENUMERATION: MEASUREMENT MODE 0 = Phase to Ground, 1 = Phase to Phase

F201 TEXT8: 8-CHARACTER ASCII PASSCODE 4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB

GE Multilin

C30 Controller System

B-55

B.4 MEMORY MAPPING

APPENDIX B

F202 TEXT20: 20-CHARACTER ASCII TEXT 10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB

F232 ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS FOR TRANSMISSION


value GOOSE dataset item None GGIO1.ST.Ind1.q GGIO1.ST.Ind1.stVal GGIO1.ST.Ind2.q GGIO1.ST.Ind2.stVal GGIO1.ST.Ind128.q GGIO1.ST.Ind128.stVal MMXU1.MX.TotW.mag.f MMXU1.MX.TotVAr.mag.f MMXU1.MX.TotVA.mag.f MMXU1.MX.TotPF.mag.f MMXU1.MX.Hz.mag.f MMXU1.MX.PPV.phsAB.cVal.mag.f MMXU1.MX.PPV.phsAB.cVal.ang.f MMXU1.MX.PPV.phsBC.cVal.mag.f MMXU1.MX.PPV.phsBC.cVal.ang.f MMXU1.MX.PPV.phsCA.cVal.mag.f MMXU1.MX.PPV.phsCA.cVal.ang.f MMXU1.MX.PhV.phsA.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.ang.f MMXU1.MX.PhV.phsB.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.ang.f MMXU1.MX.PhV.phsC.cVal.mag.f MMXU1.MX.PhV.phsC.cVal.ang.f MMXU1.MX.A.phsA.cVal.mag.f MMXU1.MX.A.phsA.cVal.ang.f MMXU1.MX.A.phsB.cVal.mag.f MMXU1.MX.A.phsB.cVal.ang.f MMXU1.MX.A.phsC.cVal.mag.f MMXU1.MX.A.phsC.cVal.ang.f MMXU1.MX.A.neut.cVal.mag.f MMXU1.MX.A.neut.cVal.ang.f MMXU1.MX.W.phsA.cVal.mag.f MMXU1.MX.W.phsB.cVal.mag.f MMXU1.MX.W.phsC.cVal.mag.f MMXU1.MX.VAr.phsA.cVal.mag.f MMXU1.MX.VAr.phsB.cVal.mag.f MMXU1.MX.VAr.phsC.cVal.mag.f MMXU1.MX.VA.phsA.cVal.mag.f MMXU1.MX.VA.phsB.cVal.mag.f MMXU1.MX.VA.phsC.cVal.mag.f MMXU1.MX.PF.phsA.cVal.mag.f MMXU1.MX.PF.phsB.cVal.mag.f MMXU1.MX.PF.phsC.cVal.mag.f MMXU2.MX.TotW.mag.f MMXU2.MX.TotVAr.mag.f MMXU2.MX.TotVA.mag.f MMXU2.MX.TotPF.mag.f

F203 TEXT16: 16-CHARACTER ASCII TEXT

0 1 2

F204 TEXT80: 80-CHARACTER ASCII TEXT

3 4 255

F205 TEXT12: 12-CHARACTER ASCII TEXT

256 257 258

F206 TEXT6: 6-CHARACTER ASCII TEXT

259 260 261

F207 TEXT4: 4-CHARACTER ASCII TEXT

262 263 264 265

F208 TEXT2: 2-CHARACTER ASCII TEXT

266 267 268

F213 TEXT32: 32-CHARACTER ASCII TEXT

269 270 271

F220 ENUMERATION: PUSHBUTTON MESSAGE PRIORITY


value 0 1 2 priority Disabled Normal High Priority

272 273 274 275 276 277 278 279 280

F222 ENUMERATION: TEST ENUMERATION 0 = Test Enumeration 0, 1 = Test Enumeration 1

281 282 283 284

F226 ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER METHOD 0 = None, 1 = GSSE, 2 = GOOSE

285 286 287 288 289 290

F227 ENUMERATION: RELAY SERVICE STATUS 0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service

291 292 293 294 295 296 297

B-56

C30 Controller System

GE Multilin

APPENDIX B
value 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 GOOSE dataset item MMXU2.MX.Hz.mag.f MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.PhV.phsA.cVal.mag.f MMXU2.MX.PhV.phsA.cVal.ang.f MMXU2.MX.PhV.phsB.cVal.mag.f MMXU2.MX.PhV.phsB.cVal.ang.f MMXU2.MX.PhV.phsC.cVal.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU2.MX.A.phsA.cVal.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU2.MX.A.phsB.cVal.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU2.MX.A.phsC.cVal.mag.f MMXU2.MX.A.phsC.cVal.ang.f MMXU2.MX.A.neut.cVal.mag.f MMXU2.MX.A.neut.cVal.ang.f MMXU2.MX.W.phsA.cVal.mag.f MMXU2.MX.W.phsB.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU2.MX.VAr.phsC.cVal.mag.f MMXU2.MX.VA.phsA.cVal.mag.f MMXU2.MX.VA.phsB.cVal.mag.f MMXU2.MX.VA.phsC.cVal.mag.f MMXU2.MX.PF.phsA.cVal.mag.f MMXU2.MX.PF.phsB.cVal.mag.f MMXU2.MX.PF.phsC.cVal.mag.f MMXU3.MX.TotW.mag.f MMXU3.MX.TotVAr.mag.f MMXU3.MX.TotVA.mag.f MMXU3.MX.TotPF.mag.f MMXU3.MX.Hz.mag.f MMXU3.MX.PPV.phsAB.cVal.mag.f MMXU3.MX.PPV.phsAB.cVal.ang.f MMXU3.MX.PPV.phsBC.cVal.mag.f MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU3.MX.A.phsA.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU3.MX.A.phsB.cVal.mag.f value 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 GOOSE dataset item

B.4 MEMORY MAPPING

MMXU3.MX.A.phsB.cVal.ang.f MMXU3.MX.A.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU3.MX.A.neut.cVal.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU3.MX.W.phsA.cVal.mag.f MMXU3.MX.W.phsB.cVal.mag.f MMXU3.MX.W.phsC.cVal.mag.f MMXU3.MX.VAr.phsA.cVal.mag.f MMXU3.MX.VAr.phsB.cVal.mag.f MMXU3.MX.VAr.phsC.cVal.mag.f MMXU3.MX.VA.phsA.cVal.mag.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU4.MX.TotVAr.mag.f MMXU4.MX.TotVA.mag.f MMXU4.MX.TotPF.mag.f MMXU4.MX.Hz.mag.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.PhV.phsA.cVal.mag.f MMXU4.MX.PhV.phsA.cVal.ang.f MMXU4.MX.PhV.phsB.cVal.mag.f MMXU4.MX.PhV.phsB.cVal.ang.f MMXU4.MX.PhV.phsC.cVal.mag.f MMXU4.MX.PhV.phsC.cVal.ang.f MMXU4.MX.A.phsA.cVal.mag.f MMXU4.MX.A.phsA.cVal.ang.f MMXU4.MX.A.phsB.cVal.mag.f MMXU4.MX.A.phsB.cVal.ang.f MMXU4.MX.A.phsC.cVal.mag.f MMXU4.MX.A.phsC.cVal.ang.f MMXU4.MX.A.neut.cVal.mag.f MMXU4.MX.A.neut.cVal.ang.f MMXU4.MX.W.phsA.cVal.mag.f MMXU4.MX.W.phsB.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f

GE Multilin

C30 Controller System

B-57

B.4 MEMORY MAPPING


value 404 405 406 407 408 GOOSE dataset item MMXU4.MX.PF.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU5.MX.TotVAr.mag.f MMXU5.MX.TotVA.mag.f MMXU5.MX.TotPF.mag.f MMXU5.MX.Hz.mag.f MMXU5.MX.PPV.phsAB.cVal.mag.f MMXU5.MX.PPV.phsAB.cVal.ang.f MMXU5.MX.PPV.phsBC.cVal.mag.f MMXU5.MX.PPV.phsBC.cVal.ang.f MMXU5.MX.PPV.phsCA.cVal.mag.f MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU5.MX.A.phsA.cVal.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU5.MX.A.phsB.cVal.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU5.MX.A.phsC.cVal.mag.f MMXU5.MX.A.phsC.cVal.ang.f MMXU5.MX.A.neut.cVal.mag.f MMXU5.MX.A.neut.cVal.ang.f MMXU5.MX.W.phsA.cVal.mag.f MMXU5.MX.W.phsB.cVal.mag.f MMXU5.MX.W.phsC.cVal.mag.f MMXU5.MX.VAr.phsA.cVal.mag.f MMXU5.MX.VAr.phsB.cVal.mag.f MMXU5.MX.VAr.phsC.cVal.mag.f MMXU5.MX.VA.phsA.cVal.mag.f MMXU5.MX.VA.phsB.cVal.mag.f MMXU5.MX.VA.phsC.cVal.mag.f MMXU5.MX.PF.phsA.cVal.mag.f MMXU5.MX.PF.phsB.cVal.mag.f MMXU5.MX.PF.phsC.cVal.mag.f MMXU6.MX.TotW.mag.f MMXU6.MX.TotVAr.mag.f MMXU6.MX.TotVA.mag.f MMXU6.MX.TotPF.mag.f MMXU6.MX.Hz.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f MMXU6.MX.PPV.phsBC.cVal.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f MMXU6.MX.PPV.phsCA.cVal.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f MMXU6.MX.PhV.phsA.cVal.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f MMXU6.MX.PhV.phsB.cVal.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f value 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 GOOSE dataset item MMXU6.MX.PhV.phsC.cVal.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f MMXU6.MX.A.phsA.cVal.mag.f MMXU6.MX.A.phsA.cVal.ang.f MMXU6.MX.A.phsB.cVal.mag.f MMXU6.MX.A.phsB.cVal.ang.f MMXU6.MX.A.phsC.cVal.mag.f MMXU6.MX.A.phsC.cVal.ang.f MMXU6.MX.A.neut.cVal.mag.f MMXU6.MX.A.neut.cVal.ang.f MMXU6.MX.W.phsA.cVal.mag.f MMXU6.MX.W.phsB.cVal.mag.f MMXU6.MX.W.phsC.cVal.mag.f MMXU6.MX.VAr.phsA.cVal.mag.f MMXU6.MX.VAr.phsB.cVal.mag.f MMXU6.MX.VAr.phsC.cVal.mag.f MMXU6.MX.VA.phsA.cVal.mag.f MMXU6.MX.VA.phsB.cVal.mag.f MMXU6.MX.VA.phsC.cVal.mag.f MMXU6.MX.PF.phsA.cVal.mag.f MMXU6.MX.PF.phsB.cVal.mag.f MMXU6.MX.PF.phsC.cVal.mag.f GGIO4.MX.AnIn1.mag.f GGIO4.MX.AnIn2.mag.f GGIO4.MX.AnIn3.mag.f GGIO4.MX.AnIn4.mag.f GGIO4.MX.AnIn5.mag.f GGIO4.MX.AnIn6.mag.f GGIO4.MX.AnIn7.mag.f GGIO4.MX.AnIn8.mag.f GGIO4.MX.AnIn9.mag.f GGIO4.MX.AnIn10.mag.f GGIO4.MX.AnIn11.mag.f GGIO4.MX.AnIn12.mag.f GGIO4.MX.AnIn13.mag.f GGIO4.MX.AnIn14.mag.f GGIO4.MX.AnIn15.mag.f GGIO4.MX.AnIn16.mag.f GGIO4.MX.AnIn17.mag.f GGIO4.MX.AnIn18.mag.f GGIO4.MX.AnIn19.mag.f GGIO4.MX.AnIn20.mag.f GGIO4.MX.AnIn21.mag.f GGIO4.MX.AnIn22.mag.f GGIO4.MX.AnIn23.mag.f GGIO4.MX.AnIn24.mag.f GGIO4.MX.AnIn25.mag.f GGIO4.MX.AnIn26.mag.f GGIO4.MX.AnIn27.mag.f GGIO4.MX.AnIn28.mag.f GGIO4.MX.AnIn29.mag.f GGIO4.MX.AnIn30.mag.f GGIO4.MX.AnIn31.mag.f

APPENDIX B

409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456

B-58

C30 Controller System

GE Multilin

APPENDIX B
value 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 GOOSE dataset item GGIO4.MX.AnIn32.mag.f GGIO5.ST.UIntIn1.q GGIO5.ST.UIntIn1.stVal GGIO5.ST.UIntIn2.q GGIO5.ST.UIntIn2.stVal GGIO5.ST.UIntIn3.q GGIO5.ST.UIntIn3.stVal GGIO5.ST.UIntIn4.q GGIO5.ST.UIntIn4.stVal GGIO5.ST.UIntIn5.q GGIO5.ST.UIntIn5.stVal GGIO5.ST.UIntIn6.q GGIO5.ST.UIntIn6.stVal GGIO5.ST.UIntIn7.q GGIO5.ST.UIntIn7.stVal GGIO5.ST.UIntIn8.q GGIO5.ST.UIntIn8.stVal GGIO5.ST.UIntIn9.q GGIO5.ST.UIntIn9.stVal GGIO5.ST.UIntIn10.q GGIO5.ST.UIntIn10.stVal GGIO5.ST.UIntIn11.q GGIO5.ST.UIntIn11.stVal GGIO5.ST.UIntIn12.q GGIO5.ST.UIntIn12.stVal GGIO5.ST.UIntIn13.q GGIO5.ST.UIntIn13.stVal GGIO5.ST.UIntIn14.q GGIO5.ST.UIntIn14.stVal GGIO5.ST.UIntIn15.q GGIO5.ST.UIntIn15.stVal GGIO5.ST.UIntIn16.q GGIO5.ST.UIntIn16.stVal value 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 GOOSE dataset item GGIO3.MX.AnIn7.mag.f GGIO3.MX.AnIn8.mag.f GGIO3.MX.AnIn9.mag.f

B.4 MEMORY MAPPING

GGIO3.MX.AnIn10.mag.f GGIO3.MX.AnIn11.mag.f GGIO3.MX.AnIn12.mag.f GGIO3.MX.AnIn13.mag.f GGIO3.MX.AnIn14.mag.f GGIO3.MX.AnIn15.mag.f GGIO3.MX.AnIn16.mag.f GGIO3.MX.AnIn17.mag.f GGIO3.MX.AnIn18.mag.f GGIO3.MX.AnIn19.mag.f GGIO3.MX.AnIn20.mag.f GGIO3.MX.AnIn21.mag.f GGIO3.MX.AnIn22.mag.f GGIO3.MX.AnIn23.mag.f GGIO3.MX.AnIn24.mag.f GGIO3.MX.AnIn25.mag.f GGIO3.MX.AnIn26.mag.f GGIO3.MX.AnIn27.mag.f GGIO3.MX.AnIn28.mag.f GGIO3.MX.AnIn29.mag.f GGIO3.MX.AnIn30.mag.f GGIO3.MX.AnIn31.mag.f GGIO3.MX.AnIn32.mag.f GGIO3.ST.IndPos1.stVal GGIO3.ST.IndPos2.stVal GGIO3.ST.IndPos3.stVal GGIO3.ST.IndPos4.stVal GGIO3.ST.IndPos5.stVal GGIO3.ST.UIntIn1.q GGIO3.ST.UIntIn1.stVal GGIO3.ST.UIntIn2.q GGIO3.ST.UIntIn2.stVal GGIO3.ST.UIntIn3.q GGIO3.ST.UIntIn3.stVal GGIO3.ST.UIntIn4.q GGIO3.ST.UIntIn4.stVal GGIO3.ST.UIntIn5.q GGIO3.ST.UIntIn5.stVal GGIO3.ST.UIntIn6.q GGIO3.ST.UIntIn6.stVal GGIO3.ST.UIntIn7.q GGIO3.ST.UIntIn7.stVal GGIO3.ST.UIntIn8.q GGIO3.ST.UIntIn8.stVal GGIO3.ST.UIntIn9.q GGIO3.ST.UIntIn9.stVal GGIO3.ST.UIntIn10.q GGIO3.ST.UIntIn10.stVal GGIO3.ST.UIntIn11.q GGIO3.ST.UIntIn11.stVal

F233 ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS FOR RECEPTION


value 0 1 2 3 4 127 128 129 130 131 132 133 134 GOOSE dataset item None GGIO3.ST.Ind1.q GGIO3.ST.Ind1.stVal GGIO3.ST.Ind2.q GGIO3.ST.Ind2.stVal GGIO1.ST.Ind64q GGIO1.ST.Ind64.stVal GGIO3.MX.AnIn1.mag.f GGIO3.MX.AnIn2.mag.f GGIO3.MX.AnIn3.mag.f GGIO3.MX.AnIn4.mag.f GGIO3.MX.AnIn5.mag.f GGIO3.MX.AnIn6.mag.f

169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187

GE Multilin

C30 Controller System

B-59

B.4 MEMORY MAPPING


value 188 189 190 191 192 GOOSE dataset item GGIO3.ST.UIntIn12.q GGIO3.ST.UIntIn12.stVal GGIO3.ST.UIntIn13.q GGIO3.ST.UIntIn13.stVal GGIO3.ST.UIntIn14.q GGIO3.ST.UIntIn14.stVal GGIO3.ST.UIntIn15.q GGIO3.ST.UIntIn15.stVal GGIO3.ST.UIntIn16.q GGIO3.ST.UIntIn16.stVal Value 0 1 2 Function Disabled Isolated Forcible value 3 4 instance Fourth Last

APPENDIX B

F254 ENUMERATION: TEST MODE FUNCTION

193 194 195 196 197

F237 ENUMERATION: REAL TIME CLOCK MONTH


value 0 1 2 3 4 5 6 7 8 9 10 11 month January February March April May June July August September October November December

F260 ENUMERATION: DATA LOGGER MODE 0 = Continuous, 1 = Trigger

F300 UR_UINT16: FLEXLOGIC BASE TYPE (6-bit type) The FlexLogic BASE type is 6 bits and is combined with a 9 bit descriptor and 1 bit for protection element to form a 16 bit value. The combined bits are of the form: PTTTTTTDDDDDDDDD, where P bit if set, indicates that the FlexLogic type is associated with a protection element state and T represents bits for the BASE type, and D represents bits for the descriptor. The values in square brackets indicate the base type with P prefix [PTTTTTT] and the values in round brackets indicate the descriptor range. [0] Off(0) this is boolean FALSE value [0] On (1) this is boolean TRUE value [2] CONTACT INPUTS (1 to 96) [3] CONTACT INPUTS OFF (1 to 96) [4] VIRTUAL INPUTS (1 to 64) [6] VIRTUAL OUTPUTS (1 to 96) [10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64) [11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64) [12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64) [13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64) [14] REMOTE INPUTS (1 to 32) [28] INSERT (via keypad only) [32] END [34] NOT (1 INPUT) [36] 2 INPUT XOR (0) [38] LATCH SET/RESET (2 inputs) [40] OR (2 to 16 inputs) [42] AND (2 to 16 inputs) [44] NOR (2 to 16 inputs) [46] NAND (2 to 16 inputs) [48] TIMER (1 to 32) [50] ASSIGN VIRTUAL OUTPUT (1 to 96) [52] SELF-TEST ERROR (see F141 for range) [56] ACTIVE SETTING GROUP (1 to 6) [62] MISCELLANEOUS EVENTS (see F146 for range) [64 to 127] ELEMENT STATES

F238 ENUMERATION: REAL TIME CLOCK DAY


value 0 1 2 3 4 5 6 day Sunday Monday Tuesday Wednesday Thursday Friday Saturday

F239 ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS TIME START DAY INSTANCE
value 0 1 2 instance First Second Third

B-60

C30 Controller System

GE Multilin

APPENDIX B

B.4 MEMORY MAPPING

F400 UR_UINT16: CT/VT BANK SELECTION


bitmask 0 1 2 3 4 5 bank selection Card 1 Contact 1 to 4 Card 1 Contact 5 to 8 Card 2 Contact 1 to 4 Card 2 Contact 5 to 8 Card 3 Contact 1 to 4 Card 3 Contact 5 to 8

F504 BITFIELD: 3-PHASE ELEMENT STATE


bitmask 0 1 2 3 4 5 6 7 element state Pickup Operate Pickup Phase A Pickup Phase B Pickup Phase C Operate Phase A Operate Phase B Operate Phase C

F491 ENUMERATION: ANALOG INPUT MODE 0 = Default Value, 1 = Last Known F505 BITFIELD: CONTACT OUTPUT STATE 0 = Contact State, 1 = Voltage Detected, 2 = Current Detected F500 UR_UINT16: PACKED BITFIELD First register indicates input/output state with bits 0 (MSB) to 15 (LSB) corresponding to input/output state 1 to 16. The second register indicates input/output state with bits 0 to 15 corresponding to input/output state 17 to 32 (if required) The third register indicates input/output state with bits 0 to 15 corresponding to input/output state 33 to 48 (if required). The fourth register indicates input/output state with bits 0 to 15 corresponding to input/output state 49 to 64 (if required). The number of registers required is determined by the specific data item. A bit value of 0 = Off and 1 = On. F511 BITFIELD: 3-PHASE SIMPLE ELEMENT STATE F501 UR_UINT16: LED STATUS Low byte of register indicates LED status with bit 0 representing the top LED and bit 7 the bottom LED. A bit value of 1 indicates the LED is on, 0 indicates the LED is off. 0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C F507 BITFIELD: COUNTER ELEMENT STATE 0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than

F509 BITFIELD: SIMPLE ELEMENT STATE 0 = Operate

F515 ENUMERATION ELEMENT INPUT MODE 0 = Signed, 1 = Absolute

F502 BITFIELD: ELEMENT OPERATE STATES Each bit contains the operate state for an element. See the F124 format code for a list of element IDs. The operate bit for element ID X is bit [X mod 16] in register [X/16].

F516 ENUMERATION ELEMENT COMPARE MODE 0 = Level, 1 = Delta

F518 ENUMERATION: FLEXELEMENT UNITS 0 = Milliseconds, 1 = Seconds, 2 = Minutes

F519 ENUMERATION: NON-VOLATILE LATCH 0 = Reset-Dominant, 1 = Set-Dominant

F522 ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE 0 = 1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA

GE Multilin

C30 Controller System

B-61

B.4 MEMORY MAPPING

APPENDIX B

F523 ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT VARIATION


bitmask 0 default variation 1 2 5 6

F600 UR_UINT16: FLEXANALOG PARAMETER Corresponds to the Modbus address of the value used when this parameter is selected. Only certain values may be used as FlexAnalogs (basically all metering quantities used in protection).

1 2 3

F605 ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT STATUS


Enumeration 0 1 Remote DPS input status Intermediate Off On Bad

F524 ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION


bitmask 0 1 2 3 Default Variation 1 2 9 10

2 3

F606 ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT


Enumeration 0 1 Remote double-point status input None Remote input 1 Remote input 2 Remote input 3 Remote input 64

F525 ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION


bitmask 0 1 2 3 4 5 default variation 1 2 3 4 5 7

2 3 64

F611 ENUMERATION: GOOSE RETRANSMISSION SCHEME


Enumeration 0 1 2 3 Configurable GOOSE retransmission scheme Heartbeat Aggressive Medium Relaxed

F530 ENUMERATION: FRONT PANEL INTERFACE KEYPRESS


value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 keypress None Menu Message Up 7 8 9 Help Message Left 4 5 6 Escape Message Right 1 2
~

value 15 16 17 18 19 20 21 22 23 24 25 26 31 32

keypress 3 Enter Message Down 0 Decimal +/ Value Up Value Down Reset User 1 User 2 User 3 User PB 1 User PB 2
~

value 33 34 35 36 37 38 39 40 41 42 44 45 46 47

keypress User PB 3 User PB 4 User PB 5 User PB 6 User PB 7 User PB 8 User PB 9 User PB 10 User PB 11 User PB 12 User 4 User 5 User 6 User 7

F612 UR_UINT16: FLEXINTEGER PARAMETER This 16-bit value corresponds to the Modbus address of the selected FlexInteger paramter. Only certain values may be used as FlexIntegers.

F531 ENUMERATION: LANGUAGE 0 = English, 1 = French, 2 = Chinese, 3 = Russian

B-62

C30 Controller System

GE Multilin

APPENDIX C APPENDIX C IEC 61850 COMMUNICATIONSC.1OVERVIEW

C.1 OVERVIEW C.1.1 INTRODUCTION

The IEC 61850 standard is the result of electric utilities and vendors of electronic equipment to produce standardized communications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, substation design and configuration, testing, environmental and project standards. The complete set includes: IEC 61850-1: Introduction and overview IEC 61850-2: Glossary IEC 61850-3: General requirements IEC 61850-4: System and project management IEC 61850-5: Communications and requirements for functions and device models IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs IEC 61850-7-1: Basic communication structure for substation and feeder equipment - Principles and models IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract communication service interface (ACSI) IEC 61850-7-3: Basic communication structure for substation and feeder equipment Common data classes IEC 61850-7-4: Basic communication structure for substation and feeder equipment Compatible logical node classes and data classes IEC 61850-8-1: Specific Communication Service Mapping (SCSM) Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3 IEC 61850-9-1: Specific Communication Service Mapping (SCSM) Sampled values over serial unidirectional multidrop point to point link IEC 61850-9-2: Specific Communication Service Mapping (SCSM) Sampled values over ISO/IEC 8802-3 IEC 61850-10: Conformance testing

These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with any IEC 61850 implementation obtain this document set. C.1.2 COMMUNICATION PROFILES IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer of real-time data. This protocol has been in existence for several of years and provides a set of services suitable for the transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract services in IEC 61850-8-1. The C30 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the C30 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the C30 to have an IP address to establish communications. These COMMUNICATIONS NETWORK menu. Note that the C30 addresses are located in the SETTINGS PRODUCT SETUP supports IEC 61850 over the TP4/CLNP or TCP/IP stacks, and also operation over both stacks simultaneously. It is possible to have up to five simultaneous connections (in addition to DNP and Modbus/TCP (non-IEC 61850) connections). Client/server: This is a connection-oriented type of communication. The connection is initiated by the client, and communication activity is controlled by the client. IEC 61850 clients are often substation computers running HMI programs or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, transformer tap changers, or bay controllers. Peer-to-peer: This is a non-connection-oriented, high speed type of communication usually between substation equipment such as protection relays. GSSE and GOOSE are methods of peer-to-peer communication. Substation configuration language (SCL): A substation configuration language is a number of files used to describe the configuration of substation equipment. Each configured device has an IEC Capability Description (ICD) file. The substation single line information is stored in a System Specification Description (SSD) file. The entire substation configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individual ICD files and the SSD file.

GE Multilin

C30 Controller System

C-1

C.2 SERVER DATA ORGANIZATION C.2SERVER DATA ORGANIZATION

APPENDIX C C.2.1 OVERVIEW

IEC 61850 defines an object-oriented approach to data and services. An IEC 61850 physical device can contain one or more logical device(s). Each logical device can contain many logical nodes. Each logical node can contain many data objects. Each data object is composed of data attributes and data attribute components. Services are available at each level for performing various functions, such as reading, writing, control commands, and reporting. Each C30 IED represents one IEC 61850 physical device. The physical device contains one logical device, and the logical device contains many logical nodes. The logical node LPHD1 contains information about the C30 IED physical device. The logical node LLN0 contains information about the C30 IED logical device. C.2.2 GGIO1: DIGITAL STATUS VALUES

The GGIO1 logical node is available in the C30 to provide access to as many 128 digital status points and associated timestamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients. It is intended that clients use GGIO1 in order to access digital status values from the C30. Configuration settings are provided to allow the selection of the number of digital status indications available in GGIO1 (8 to 128), and to allow the choice of the C30 FlexLogic operands that drive the status of the GGIO1 status indications. Clients can utilize the IEC 61850 buffered and unbuffered reporting features available from GGIO1 in order to build sequence of events (SOE) logs and HMI display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the chances of missing data state changes. Unbuffered reporting should generally be used for local status display. C.2.3 GGIO2: DIGITAL CONTROL VALUES The GGIO2 logical node is available to provide access to the C30 virtual inputs. Virtual inputs are single-point control (binary) values that can be written by clients. They are generally used as control inputs. GGIO2 provides access to the virtual inputs through the IEC 61850 standard control model (ctlModel) services: Status only. Direct control with normal security. SBO control with normal security.

Configuration settings are available to select the control model for each point. Each virtual input used through GGIO2 should have its VIRTUAL INPUT 1(64) FUNCTION setting programmed as Enabled and its corresponding GGIO2 CF SPSCO1(64) CTLMODEL setting programmed to the appropriate control configuration. C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE DATA The GGIO3 logical node is available to provide access for clients to values received via configurable GOOSE messages. The values of the digital status indications and analog values in GGIO3 originate in GOOSE messages sent from other devices. C.2.5 GGIO4: GENERIC ANALOG MEASURED VALUES The GGIO4 logical node provides access to as many as 32 analog value points, as well as associated timestamps and quality flags. The data content must be configured before the data can be used. GGIO4 provides analog values for access by clients. It is intended that clients use GGIO4 to access generic analog values from the C30. Configuration settings allow the selection of the number of analog values available in GGIO4 (4 to 32) and the choice of the FlexAnalog values that determine the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available from GGIO4 in order to obtain the analog values provided by GGIO4.

C-2

C30 Controller System

GE Multilin

APPENDIX C

C.2 SERVER DATA ORGANIZATION C.2.6 MMXU: ANALOG MEASURED VALUES

A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a C30 current and voltage source. There is one MMXU available for each conSYSTEM SETUP SIGNAL SOURCES menu). MMXU1 provides data figurable source (programmed in the SETTINGS from C30 source 1, and MMXU2 provides data from C30 source 2. MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3. The selection of appropriate deadband settings for the C30 is described in chapter 5 of this manual. IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes provide the following data for each source: MMXU1.MX.TotW: three-phase real power MMXU1.MX.TotVAr: three-phase reactive power MMXU1.MX.TotVA: three-phase apparent power MMXU1.MX.TotPF: three-phase power factor MMXU1.MX.Hz: frequency MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle MMXU1.MX.A.phsA: phase A current magnitude and angle MMXU1.MX.A.phsB: phase B current magnitude and angle MMXU1.MX.A.phsC: phase C current magnitude and angle MMXU1.MX.A.neut: ground current magnitude and angle MMXU1.MX.W.phsA: phase A real power MMXU1.MX.W.phsB: phase B real power MMXU1.MX.W.phsC: phase C real power MMXU1.MX.VAr.phsA: phase A reactive power MMXU1.MX.VAr.phsB: phase B reactive power MMXU1.MX.VAr.phsC: phase C reactive power MMXU1.MX.VA.phsA: phase A apparent power MMXU1.MX.VA.phsB: phase B apparent power MMXU1.MX.VA.phsC: phase C apparent power MMXU1.MX.PF.phsA: phase A power factor MMXU1.MX.PF.phsB: phase B power factor MMXU1.MX.PF.phsC: phase C power factor C.2.7 PROTECTION AND OTHER LOGICAL NODES The following list describes the protection elements for all UR-series relays. The C30 relay will contain a subset of protection elements from this list. PDIF: bus differential, transformer instantaneous differential, transformer percent differential, current differential

GE Multilin

C30 Controller System

C-3

C.2 SERVER DATA ORGANIZATION PDIS: phase distance, ground distance

APPENDIX C

PIOC: phase instantaneous overcurrent, neutral instantaneous overcurrent, ground instantaneous overcurrent, negative-sequence instantaneous overcurrent. PTOC: phase time overcurrent, neutral time overcurrent, ground time overcurrent, negative-sequence time overcurrent, neutral directional overcurrent, negative-sequence directional overcurrent PTUV: phase undervoltage, auxiliary undervoltage, third harmonic neutral undervoltage PTOV: phase overvoltage, neutral overvoltage, auxiliary overvoltage, negative sequence overvoltage RBRF: breaker failure RREC: autoreclosure RPSB: power swing detection RFLO: fault locator XCBR: breaker control XSWI: circuit switch CSWI: switch controller

The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the C30 protection elements, these flags take their values from the pickup and operate FlexLogic operands for the corresponding element. Some protection elements listed above contain directional start values. For example, the directional start value for PDIS1 is PDIS1.ST.Str.dirGeneral. This value is built from the directional FlexLogic operands for the element. The RFLO logical node contains the measurement of the distance to fault calculation in kilometers. This value originates in the fault locator function. The XCBR logical node is directly associated with the breaker control feature. XCBR1.ST.Loc: This is the state of the XCBR1 local/remote switch. A setting is provided to assign a FlexLogic operand to determine the state. When local mode is true, IEC 61850 client commands will be rejected. XCBR1.ST.Opcnt: This is an operation counter as defined in IEC 61850. Command settings are provided to allow the counter to be cleared. XCBR1.ST.Pos: This is the position of the breaker. The breaker control FlexLogic operands are used to determine this state. If the breaker control logic indicates that the breaker, or any single pole of the breaker, is closed, then the breaker position state is on. If the breaker control logic indicates that the breaker is open, then the breaker position state is off. XCBR1.ST.BlkOpn: This is the state of the block open command logic. When true, breaker open commands from IEC 61850 clients will be rejected. XCBR1.ST.BlkCls: This is the state of the block close command logic. When true, breaker close commands from IEC 61850 clients will be rejected. XCBR1.CO.Pos: This is where IEC 61850 clients can issue open or close commands to the breaker. SBO control with normal security is the only supported IEC 61850 control model. XCBR1.CO.BlkOpn: This is where IEC 61850 clients can issue block open commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model.

C-4

C30 Controller System

GE Multilin

APPENDIX C C.3SERVER FEATURES AND CONFIGURATION

C.3 SERVER FEATURES AND CONFIGURATION C.3.1 BUFFERED/UNBUFFERED REPORTING

IEC 61850 buffered and unbuffered reporting is provided in the GGIO1 logical nodes (for binary status values) and MMXU1 to MMXU6 (for analog measured values). Report settings can be configured using the EnerVista UR Setup software, substation configurator software, or via an IEC 61850 client. The following items can be configured: TrgOps: Trigger options. The following bits are supported by the C30: Bit 1: data-change Bit 4: integrity Bit 5: general interrogation

OptFlds: Option Fields. The following bits are supported by the C30: Bit 1: sequence-number Bit 2: report-time-stamp Bit 3: reason-for-inclusion Bit 4: data-set-name Bit 5: data-reference Bit 6: buffer-overflow (for buffered reports only) Bit 7: entryID (for buffered reports only) Bit 8: conf-revision Bit 9: segmentation

IntgPd: Integrity period. BufTm: Buffer time. C.3.2 FILE TRANSFER

MMS file services are supported to allow transfer of oscillography, event record, or other files from a C30 relay. C.3.3 TIMESTAMPS AND SCANNING The timestamp values associated with all IEC 61850 data items represent the time of the last change of either the value or quality flags of the data item. To accomplish this functionality, all IEC 61850 data items must be regularly scanned for data changes, and the timestamp updated when a change is detected, regardless of the connection status of any IEC 61850 clients. For applications where there is no IEC 61850 client in use, the IEC 61850 SERVER SCANNING setting can be programmed as Disabled. If a client is in use, this setting should be programmed as Enabled to ensure the proper generation of IEC 61850 timestamps. C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the C30. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the IEDNAME and LD INST settings. The default values for these strings are IEDName and LDInst. These values should be changed to reflect a logical naming convention for all IEC 61850 logical devices in the system. C.3.5 LOCATION The LPHD1 logical node contains a data attribute called location (LPHD1.DC.PhyNam.location). This is a character string meant to describe the physical location of the C30. This attribute is programmed through the LOCATION setting and its default value is Location. This value should be changed to describe the actual physical location of the C30.

GE Multilin

C30 Controller System

C-5

C.3 SERVER FEATURES AND CONFIGURATION

APPENDIX C C.3.6 LOGICAL NODE NAME PREFIXES

IEC 61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of: a five or six-character name prefix. a four-character standard name (for example, MMXU, GGIO, PIOC, etc.). a one or two-character instantiation index.

Complete names are of the form xxxxxxPIOC1, where the xxxxxx character string is configurable. Details regarding the logical node naming rules are given in IEC 61850 parts 6 and 7-2. It is recommended that a consistent naming convention be used for an entire substation project. C.3.7 CONNECTION TIMING

A built-in TCP/IP connection timeout of two minutes is employed by the C30 to detect dead connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the C30. This frees up the connection to be used by other clients. Therefore, when using IEC 61850 reporting, clients should configure report control block items such that an integrity report will be issued at least every 2 minutes (120000 ms). This ensures that the C30 will not abort the connection. If other MMS data is being polled on the same connection at least once every 2 minutes, this timeout will not apply. C.3.8 NON-IEC 61850 DATA The C30 relay makes available a number of non-IEC 61850 data items. These data items can be accessed through the UR MMS domain. IEC 61850 data can be accessed through the standard IEC 61850 logical device. To access the nonIEC data items, the INCLUDE NON-IEC DATA setting must be Enabled. C.3.9 COMMUNICATION SOFTWARE UTILITIES The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a C30 relay with an MMS browser, such as the MMS Object Explorer and AXS4-MMS DDE/OPC server from Sisco Inc.

C-6

C30 Controller System

GE Multilin

APPENDIX C

C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE C.4.1 OVERVIEW

C.4GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

IEC 61850 specifies two types of peer-to-peer data transfer services: Generic Substation State Events (GSSE) and Generic Object Oriented Substation Events (GOOSE). GSSE services are compatible with UCA 2.0 GOOSE. IEC 61850 GOOSE services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ethertype Application ID configuration. The support for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Because of the additional features of GOOSE services versus GSSE services, it is recommended that GOOSE be used wherever backwards compatibility with GSSE (or UCA 2.0 GOOSE) is not required. Devices that transmit GSSE and/or GOOSE messages also function as servers. Each GSSE publisher contains a GSSE control block to configure and control the transmission. Each GOOSE publisher contains a GOOSE control block to configure and control the transmission. The transmission is also controlled via device settings. These settings can be seen in the ICD and/or SCD files, or in the device configuration software or files. IEC 61850 recommends a default priority value of 4 for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More details are specified in IEC 61850 part 8-1. IEC 61850 recommends that the Ethertype Application ID number be configured according to the GOOSE source. In the C30, the transmitted GOOSE Application ID number must match the configured receive Application ID number in the receiver. A common number may be used for all GOOSE transmitters in a system. More details are specified in IEC 61850 part 8-1. C.4.2 GSSE CONFIGURATION IEC 61850 Generic Substation Status Event (GSSE) communication is compatible with UCA GOOSE communication. GSSE messages contain a number of double point status data items. These items are transmitted in two pre-defined data structures named DNA and UserSt. Each DNA and UserSt item is referred to as a bit pair. GSSE messages are transmitted in response to state changes in any of the data points contained in the message. GSSE messages always contain the same number of DNA and UserSt bit pairs. Depending the on the configuration, only some of these bit pairs may have values that are of interest to receiving devices. The GSSE FUNCTION, GSSE ID, and GSSE DESTINATION MAC ADDRESS settings are used to configure GSSE transmission. GSSE FUNCTION is set to Enabled to enable the transmission. If a valid multicast Ethernet MAC address is entered for the GSSE DESTINATION MAC ADDRESS setting, this address will be used as the destination MAC address for GSSE messages. If a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the C30 will use the source Ethernet MAC address as the destination, with the multicast bit set. C.4.3 FIXED GOOSE The C30 supports two types of IEC 61850 Generic Object Oriented Substation Event (GOOSE) communication: fixed GOOSE and configurable GOOSE. All GOOSE messages contain IEC 61850 data collected into a dataset. It is this dataset that is transferred using GOOSE message services. The dataset transferred using the C30 fixed GOOSE is the same data that is transferred using the GSSE feature; that is, the DNA and UserSt bit pairs. The FlexLogic operands that determine the state of the DNA and UserSt bit pairs are configurable via settings, but the fixed GOOSE dataset always contains the same DNA/UserSt data structure. Upgrading from GSSE to GOOSE services is simply a matter of enabling fixed GOOSE and disabling GSSE. The remote inputs and outputs are configured in the same manner for both GSSE and fixed GOOSE. It is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between URseries IEDs. Configurable GOOSE may be used for implementations that require GOOSE data transfer between UR-series IEDs and devices from other manufacturers. C.4.4 CONFIGURABLE GOOSE The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the C30. The C30 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data transfer between devices.

GE Multilin

C30 Controller System

C-7

C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

APPENDIX C

Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected. Dataset 1 should be used for high-speed transmission of data that is required for applications such as transfer tripping, blocking, and breaker fail initiate. At least one digital status value needs to be configured in dataset 1 to enable transmission of all data configured for dataset 1. Configuring analog data only to dataset 1 will not activate transmission. Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every 100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any changes have been made. If any changes in the data items are detected, these changes will be transmitted through a GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent. For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no changes in the data items are detected. The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE messages due to an oscillation being created that is triggering a message.

The C30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components. If erroneously oscillation is detected, the C30 will stop sending GOOSE messages from the dataset for a minimum period of one second. Should the oscillation persist after the one second time-out period, the C30 will continue to block transmission of the dataset. The C30 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error message on the front panel display, where XXX denotes the data item detected as oscillating. The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data transfer between UR-series IEDs. IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setupsoftware can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to the IEC 61850 IED configuration section later in this appendix). The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The general steps required for transmission configuration are: 1. 2. 3. Configure the transmission dataset. Configure the GOOSE service settings. Configure the data.

The general steps required for reception configuration are: 1. 2. 3. Configure the reception dataset. Configure the GOOSE service settings. Configure the data.

This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status value, its associated quality flags, and a floating point analog value. The following procedure illustrates the transmission configuration. 1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIG GSE 1 DATASET ITEMS settings menu: GOOSE 1 COMMUNICATION CONFIGURABLE GOOSE CONFIGURABLE

Set ITEM 1 to GGIO1.ST.Ind1.q to indicate quality flags for GGIO1 status indication 1. Set ITEM 2 to GGIO1.ST.Ind1.stVal to indicate the status value for GGIO1 status indication 1.

The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception dataset on the receiving device must exactly match this structure. 2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP
IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION RABLE GOOSE 1 settings menu: TRANSMISSION COMMUNICATION CONFIGURABLE GOOSE CONFIGU-

C-8

C30 Controller System

GE Multilin

APPENDIX C 3.

C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

Set CONFIG GSE 1 FUNCTION to Enabled. Set CONFIG GSE 1 ID to an appropriate descriptive string (the default value is GOOSEOut_1). Set CONFIG GSE 1 DST MAC to a multicast address (for example, 01 00 00 12 34 56). Set the CONFIG GSE 1 VLAN PRIORITY; the default value of 4 is OK for this example. Set the CONFIG GSE 1 VLAN ID value; the default value is 0, but some switches may require this value to be 1. Set the CONFIG GSE 1 ETYPE APPID value. This setting represents the Ethertype application ID and must match the configuration on the receiver (the default value is 0). Set the CONFIG GSE 1 CONFREV value. This value changes automatically as described in IEC 61850 part 7-2. For this example it can be left at its default value.
COMMUNICATION IEC 61850 PROTO-

COL

Configure the data by making the following changes in the PRODUCT SETUP GGIO1 STATUS CONFIGURATION settings menu:

Set GGIO1 INDICATION 1 to a FlexLogic operand used to provide the status of GGIO1.ST.Ind1.stVal (for example, a contact input, virtual input, a protection element status, etc.).

The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. 1. Configure the reception dataset by making the following changes in the PRODUCT SETUP
GSSE/GOOSE CONFIGURATION 61850 PROTOCOL 1 CONFIG GSE 1 DATASET ITEMS settings menu: RECEPTION CONFIGURABLE GOOSE COMMUNICATION IEC CONFIGURABLE GOOSE

Set ITEM 1 to GGIO3.ST.Ind1.q to indicate quality flags for GGIO3 status indication 1. Set ITEM 2 to GGIO3.ST.Ind1.stVal to indicate the status value for GGIO3 status indication 1.

The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point analog value. This matches the transmission dataset configuration above. 2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS REMOTE DEVICE 1 settings menu: 3.
REMOTE DEVICES

Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter GOOSEOut_1. Set REMOTE DEVICE 1 ETYPE APPID to match the Ethertype application ID from the transmitting device. This is 0 in the example above. Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using configurable GOOSE 1 in this example, program this value as GOOSEIn 1.
REMOTE INPUTS REMOTE INPUT 1

Configure the data by making the following changes in the INPUTS/OUTPUTS settings menu: Set REMOTE IN 1 DEVICE to GOOSEOut_1.

Set REMOTE IN 1 ITEM to Dataset Item 2. This assigns the value of the GGIO3.ST.Ind1.stVal single point status item to remote input 1.

Remote input 1 can now be used in FlexLogic equations or other settings. The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a complete SCD file is created by third party substation configurator software. C.4.5 ETHERNET MAC ADDRESS FOR GSSE/GOOSE Ethernet capable devices each contain a unique identifying address called a Media Access Control (MAC) address. This address cannot be changed and is unique for each Ethernet device produced worldwide. The address is six bytes in length and is usually represented as six hexadecimal values (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as the source address of the frame. Each Ethernet frame also contains a destination address. The destination address can be different for each Ethernet frame depending on the intended destination of the frame.

GE Multilin

C30 Controller System

C-9

C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

APPENDIX C

A special type of destination address called a multicast address is used when the Ethernet frame can be received by more than one device. An Ethernet MAC address is multicast when the least significant bit of the first byte is set (for example, 01 00 00 00 00 00 is a multicast address). GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the C30 is configured to use an automated multicast MAC scheme. If the C30 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destination MAC will be the same as the local MAC address, but with the multicast bit set. Thus, if the local MAC address is 00 A0 F4 01 02 03, then the destination MAC address will be 01 A0 F4 01 02 03. C.4.6 GSSE ID AND GOOSE ID SETTINGS GSSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in IEC 61850 part 8-1 as GsID. This is a programmable 65-character string. This string should be chosen to provide a descriptive name of the originator of the GSSE message. GOOSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in IEC 61850 part 8-1 as GoID. This programmable 65-character string should be a descriptive name of the originator of the GOOSE message. GOOSE messages also contain two additional character strings used for identification of the message: DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block. These strings are automatically populated and interpreted by the C30; no settings are required.

C-10

C30 Controller System

GE Multilin

APPENDIX C

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C.5.1 OVERVIEW

C.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP The C30 can be configured for IEC 61850 via the EnerVista UR Setup software as follows. 1. 2. 3.

An ICD file is generated for the C30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other vendors) for system configuration. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.

The configuration process is illustrated below.


Creating ICD (GE Multilin) IEC 61850 related configuration for the IED (GSSE/GOOSE, server, logical node prefixes, MMXU deadbands, GGIO2 control, etc.)

C
Process of creating ICD (vendor 2) Process of creating ICD (vendor 3) Process of creating ICD (vendor N)

IED (UR-series) OR Setting files (.URS) EnerVista UR Setup

ICD file 2 ICD file 1

ICD file 3

ICD file N

System specification data

Import

System specification tool

SSD file System configurator

System Configuration (network, crosscommunications, IED setting modification, etc.)

SCD file

Updating IED with new configuration (GE Multilin) EnerVista UR Setup Vendor specific tool for updating new configuration to IED (vendor 2) Vendor specific tool for updating new configuration to IED (vendor 3) Vendor specific tool for updating new configuration to IED (vendor N)

URS 1

URS 2

URS X

Write settings file to device

Write settings file to other devices

UR relay 1

UR relay 2

UR relay X

Vendor relay 2 Ethernet

Vendor relay 3

Vendor relay N

842790A1.CDR

Figure 01: IED CONFIGURATION PROCESS The following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC 61850: BDA: Basic Data Attribute, that is not structured DAI: Instantiated Data Attribute DO: Data Object type or instance, depending on the context

GE Multilin

C30 Controller System

C-11

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP DOI: Instantiated Data Object IED: Intelligent Electronic Device LDInst: Instantiated Logical Device LNInst: Instantiated Logical Node

APPENDIX C

SCL: Substation Configuration Description Language. The configuration language is an application of the Extensible Markup Language (XML) version 1.0. SDI: Instantiated Sub DATA; middle name part of a structured DATA name UR: GE Multilin Universal Relay series URI: Universal Resource Identifier URS: UR-series relay setting file XML: Extensible Markup Language

The following SCL variants are also used: ICD: IED Capability Description CID: Configured IED Description SSD: System Specification Description SCD: Substation Configuration Description

The following IEC related tools are referenced in the procedures that describe the IED configuration process for IEC 61850: System configurator or Substation configurator: This is an IED independent system level tool that can import or export configuration files defined by IEC 61850-6. It can import configuration files (ICD) from several IEDs for system level engineering and is used to add system information shared by different IEDs. The system configuration generates a substation related configuration file (SCD) which is fed back to the IED configurator (for example, EnerVista UR Setup) for system related IED configuration. The system configurator should also be able to read a system specification file (SSD) to use as base for starting system engineering, or to compare it with an engineered system for the same substation. IED configurator: This is a vendor specific tool that can directly or indirectly generate an ICD file from the IED (for example, from a settings file). It can also import a system SCL file (SCD) to set communication configuration parameters (that is, required addresses, reception GOOSE datasets, IDs of incoming GOOSE datasets, etc.) for the IED. The IED configurator functionality is implemented in the GE Multilin EnerVista UR Setup software. C.5.2 CONFIGURING IEC 61850 SETTINGS Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED. For example, the IED name and logical device instance can be specified to uniquely identify the IED within the substation, or transmission GOOSE datasets created so that the system configurator can configure the cross-communication links to send GOOSE messages from the IED. Once the IEC 61850 settings are configured, the ICD creation process will recognize the changes and generate an ICD file that contains the updated settings. Some of the IED settings will be modified during they system configuration process. For example, a new IP address may be assigned, line items in a Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the C30 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file. These settings can be configured either directly through the relay panel or through the EnerVista UR Setup software (preferred method). The full list of IEC 61850 related settings for are as follows: Network configuration: IP address, IP subnet mask, and default gateway IP address (access through the Settings > Product Setup > Communications > Network menu tree in EnerVista UR Setup). Server configuration: IED name and logical device instance (access through the Settings > Product Setup > Communications > IEC 61850 > Server Configuration menu tree in EnerVista UR Setup). Logical node prefixes, which includes prefixes for all logical nodes except LLN0 (access through the Settings > Product Setup > Communications > IEC 61850 > Logical Node Prefixes menu tree in EnerVista UR Setup).

C-12

C30 Controller System

GE Multilin

APPENDIX C

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

MMXU deadbands, which includes deadbands for all available MMXUs. The number of MMXUs is related to the number of CT/VT modules in the relay. There are two MMXUs for each CT/VT module. For example, if a relay contains two CT/VT modules, there will be four MMXUs available (access through the Settings > Product Setup > Communications > IEC 61850 > MMXU Deadbands menu tree in EnerVista UR Setup). GGIO1 status configuration, which includes the number of status points in GGIO1 as well as the potential internal mappings for each GGIO1 indication. However only the number of status points will be used in the ICD creation process (access through the Settings > Product Setup > Communications > IEC 61850 > GGIO1 Status Configuration menu tree in EnerVista UR Setup). GGIO2 control configuration, which includes ctlModels for all SPCSOs within GGIO2 (access through the Settings > Product Setup > Communications > IEC 61850 > GGIO2 Control Configuration menu tree in EnerVista UR Setup). Configurable transmission GOOSE, which includes eight configurable datasets that can be used for GOOSE transmission. The GOOSE ID can be specified for each dataset (it must be unique within the IED as well as across the whole substation), as well as the destination MAC address, VLAN priority, VLAN ID, ETYPE APPID, and the dataset items. The selection of the dataset item is restricted by firmware version; for version 5.8x, only GGIO1.ST.Indx.stVal and GGIO1.ST.Indx.q are valid selection (where x is between 1 to N, and N is determined by number of GGIO1 status points). Although configurable transmission GOOSE can also be created and altered by some third-party system configurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Communications > IEC 61850 > GSSE/GOOSE Configuration > Transmission > Tx Configurable GOOSE menu tree in EnerVista UR Setup). Configurable reception GOOSE, which includes eight configurable datasets that can be used for GOOSE reception. However, unlike datasets for transmission, datasets for reception only contains dataset items, and they are usually created automatically by process of importing the SCD file (access through the Settings > Product Setup > Communications > IEC 61850 > GSSE/GOOSE Configuration > Reception > Rx Configurable GOOSE menu tree in EnerVista UR Setup). Remote devices configuration, which includes remote device ID (GOOSE ID or GoID of the incoming transmission GOOSE dataset), ETYPE APPID (of the GSE communication block for the incoming transmission GOOSE), and DATASET (which is the name of the associated reception GOOSE dataset). These settings are usually done automatically by process of importing SCD file (access through the Settings > Inputs/Outputs > Remote Devices menu tree in EnerVista UR Setup). Remote inputs configuration, which includes device (remote device ID) and item (which dataset item in the associated reception GOOSE dataset to map) values. Only the items with cross-communication link created in SCD file should be mapped. These configurations are usually done automatically by process of importing SCD file (access through the Settings > Inputs/Outputs > Remote Inputs menu tree in EnerVista UR Setup). C.5.3 ABOUT ICD FILES

The SCL language is based on XML, and its syntax definition is described as a W3C XML Schema. ICD is one type of SCL file (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four major sections: Header Communication IEDs DataTypeTemplates

GE Multilin

C30 Controller System

C-13

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP The root file structure of an ICD file is illustrated below.
SCL Header (id, version, revision, toolID, nameStructure)

APPENDIX C

Communication

IED (name, type, manufacture, configVersion)

DataTypeTemplates
842795A1.CDR

Figure 02: ICD FILE STRUCTURE, SCL (ROOT) NODE

The Header node identifies the ICD file and its version, and specifies options for the mapping of names to signals The Communication node describes the direct communication connection possibilities between logical nodes by means of logical buses (sub-networks) and IED access ports. The communication section is structured as follows.
Communication SubNetwork (name) ConnectedAP (iedName, apName) Address P (type) Text Other P elements

GSE (IdInst, cbName) Address P (type) Text


842796A1.CDR

Other GSE elements

Other P elements

Figure 03: ICD FILE STRUCTURE, COMMUNICATIONS NODE The SubNetwork node contains all access points which can (logically) communicate with the sub-network protocol and without the intervening router. The ConnectedAP node describes the IED access point connected to this sub-network. The Address node contains the address parameters of the access point. The GSE node provides the address element for stating the control block related address parameters, where IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. The IED node describes the (pre-)configuration of an IED: its access points, the logical devices, and logical nodes instantiated on it. Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED.

C-14

C30 Controller System

GE Multilin

APPENDIX C

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

IED (name, type, manufacture, configVersion) Services DynAssoication GetDirectory GetDateObjectDefinition DataObjectDirectory AccessPoint (name) Server Authentication (none) LDevice (inst) LN0 (InType, InClass, inst) DataSet (name) FCDA (fc, doName, daName, IdInst, prefix, InClass, InInst) Other FCDA elements Other DataSet elements ReportControl (name, datSet, intgPd, rptID, confRev, buffered) TrgOps (dchg) OptFields (seqNum) RptEnabled GetDataSetValue SetDataSetValue DataSetDirectory ConfDataSet (max, maxAttributes) ReadWrite TimerActivatedControl ConfReportControl (max) ConfLogControl (max) GSEDir GOOSE (max) GSSE (max)

GetCBValues

Other ReportControl elements

DOI (name) SDI (name) DAI (name) Val Other DOI elements SDI (name) DAI (name) GSEControl (name, datSet, type, confRev, appID) Other GSEControl elements LN (InType, InClass, prefix, inst) DataSet (name) FCDA (IdInst, prefix, InClass, InInst, doName, fc) Other FCDA elements Other DataSet elements ReportControl (name, datSet, intgPd, rptID, confRev, buffered) TrgOps (dchg) Other ReportControl elements DOI (name) SDI (name) DAI (name) Val Other DOI elements SDI (name) DAI (name) Val Other LN elements Text Text OptFields (seqNum) RptEnabled Val Text Text

Other LDevice elements

842797A1.CDR

Figure 04: ICD FILE STRUCTURE, IED NODE

GE Multilin

C30 Controller System

C-15

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

APPENDIX C

The DataTypeTemplates node defines instantiable logical node types. A logical node type is an instantiable template of the data of a logical node. A LnodeType is referenced each time that this instantiable type is needed with an IED. A logical node type template is built from DATA (DO) elements, which again have a DO type, which is derived from the DATA classes (CDC). DOs consist of attributes (DA) or of elements of already defined DO types (SDO). The attribute (DA) has a functional constraint, and can either have a basic type, be an enumeration, or a structure of a DAType. The DAType is built from BDA elements, defining the structure elements, which again can be BDA elements of have a base type such as DA.
DataTypeTemplates LNodeType (id, InClass) DO (name, type) Other DO elements

Other LNodeType elements DOType (id, cdc) SDO (name, type) Other SDO elements DA (name, fc, bType, type) Other DA elements Val Text

Other DOType elements

DAType (id) BDA (name, bType, type) Other BDA elements Other DAType elements EnumType (id) EnumVal (ord) Text

Other EnumVal elements

Other EnumType elements


842798A1.CDR

Figure 05: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE

C-16

C30 Controller System

GE Multilin

APPENDIX C

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C.5.4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP

An ICD file can be created directly from a connected C30 IED or from an offline C30 settings file with the EnerVista UR Setup software using the following procedure: 1. Right-click the connected UR-series relay or settings file and select Create ICD File.

2.

The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file.

The time to create an ICD file from the offline C30 settings file is typically much quicker than create an ICD file directly from the relay. C.5.5 ABOUT SCD FILES System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI version 4.6 or above and ASE Visual SCL Beta 0.12). Although the configuration tools vary from one vendor to another, the procedure is pretty much the same. First, a substation project must be created, either as an empty template or with some system information by importing a system specification file (SSD). Then, IEDs are added to the substation. Since each IED is represented by its associated ICD, the ICD files are imported into the substation project, and the system configurator validates the ICD files during the importing process. If the ICD files are successfully imported into the substation project, it may be necessary to perform some additional minor steps to attach the IEDs to the substation (see the system configurator manual for details). Once all IEDs are inserted into the substation, further configuration is possible, such as: assigning network addresses to individual IEDs customizing the prefixes of logical nodes creating cross-communication links (configuring GOOSE messages to send from one IED to others)

When system configurations are complete, the results are saved to an SCD file, which contains not only the configuration for each IED in the substation, but also the system configuration for the entire substation. Finally, the SCD file is passed back to the IED configurator (vendor specific tool) to update the new configuration into the IED. The SCD file consists of at least five major sections:

GE Multilin

C30 Controller System

C-17

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP Header Substation Communication IED section (one or more) DataTypeTemplates

APPENDIX C

The root file structure of an SCD file is illustrated below.


SCL Header (id, version, revision, toolID, nameStructure)

Substation

Communication

IED Section (IED 1)

IED Section (IED 2)

Other IED Sections

DataTypeTemplates
842791A1.CDR

Figure 06: SCD FILE STRUCTURE, SCL (ROOT) NODE Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters:
Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment

EquipmentContainer VoltageLevel Bay Voltage

PowerSystemResource Function SubFunction GeneralEquipment


842792A1.CDR

Figure 07: SCD FILE STRUCTURE, SUBSTATION NODE

C-18

C30 Controller System

GE Multilin

APPENDIX C

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

The Communication node describes the direct communication connection possibilities between logical nodes by means of logical buses (sub-networks) and IED access ports. The communication section is structured as follows.
Communication SubNetwork (name) ConnectedAP (IED 1) Address P (type) Text Other P elements GSE (IdInst, cbName) Address P (type) Other GSE elements Other P elements ConnectedAP (IED 2) Address P (type) Text Other P elements GSE (IdInst, cbName) Text

Address P (type) Text Other GSE elements Other P elements

Other ConnectedAP elements


842793A1.CDR

Figure 08: SCD FILE STRUCTURE, COMMUNICATIONS NODE The SubNetwork node contains all access points which can (logically) communicate with the sub-network protocol and without the intervening router. The ConnectedAP node describes the IED access point connected to this sub-network. The Address node contains the address parameters of the access point. The GSE node provides the address element for stating the control block related address parameters, where IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block.

GE Multilin

C30 Controller System

C-19

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP The IED Section node describes the configuration of an IED.
IED Section (IED 1) AccessPoint (name) Server Authentication (none) LDevice (inst) LN0 (InType, InClass, inst)

APPENDIX C

DataSet elements ReportControl elements

DOI elements Inputs

ExtRef (iedName, ldInst, prefix, lnClass, lnInst, doName, daName, intAddr)

Other ExtRef elements

GSEControl elements

842794A1.CDR

Figure 09: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the C30 with the new configuration from an SCD file with the EnerVista UR Setup software. 1. Right-click anywhere in the files panel and select the Import Contents From SCD File item.

2.

Select the saved SCD file and click Open.

C-20

C30 Controller System

GE Multilin

APPENDIX C 3.

C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series settings file for each IED.

4. 5. 6.

After the URS file is created, modify any settings (if required). To update the relay with the new settings, right-click on the settings file in the settings tree and select the Write Settings File to Device item. The software will prompt for the target device. Select the target device from the list provided and click Send. The new settings will be updated to the selected device.

GE Multilin

C30 Controller System

C-21

C.6 ACSI CONFORMANCE C.6ACSI CONFORMANCE

APPENDIX C C.6.1 ACSI BASIC CONFORMANCE STATEMENT

SERVICES CLIENT-SERVER ROLES B11 B12 B21 B22 B23 Server side (of Two-party Application-Association) Client side (of Two-party Application-Association) SCSM: IEC 61850-8-1 used SCSM: IEC 61850-9-1 used SCSM: IEC 61850-9-2 used SCSM: other Publisher side Subscriber side Publisher side Subscriber side

SERVER/ PUBLISHER c1 ---

UR-FAMILY

Yes

SCSMS SUPPORTED Yes

B24 B31 B32 B41 B42

GENERIC SUBSTATION EVENT MODEL (GSE) O --O --Yes Yes

TRANSMISSION OF SAMPLED VALUE MODEL (SVC)

NOTE

c1: shall be "M" if support for LOGICAL-DEVICE model has been declared O: Optional M: Mandatory C.6.2 ACSI MODELS CONFORMANCE STATEMENT

SERVICES IF SERVER SIDE (B11) SUPPORTED M1 M2 M3 M4 M5 M6 M7 M7-1 M7-2 M7-3 M7-4 M7-5 M7-6 M7-7 M7-8 M7-9 M7-10 M8 M8-1 M8-2 M8-3 Logical device Logical node Data Data set Substitution Setting group control REPORTING Buffered report control sequence-number report-time-stamp reason-for-inclusion data-set-name data-reference buffer-overflow entryID BufTm IntgPd GI Unbuffered report control sequence-number report-time-stamp reason-for-inclusion

SERVER/ PUBLISHER c2 c3 c4 c5 O O O

UR-FAMILY

Yes Yes Yes Yes

Yes

Yes

C-22

C30 Controller System

GE Multilin

APPENDIX C
SERVICES M8-4 M8-5 M8-6 M8-7 M8-8 M9 M9-1 M10 M11 data-set-name data-reference BufTm IntgPd GI Logging Log control IntgPd Log Control GOOSE M12-1 M12-2 M13 M14 M15 M16 M17 entryID DataReflnc GSSE Multicast SVC Unicast SVC Time File transfer O O O M O O M O O O SERVER/ PUBLISHER

C.6 ACSI CONFORMANCE


UR-FAMILY

Yes Yes

IF GSE (B31/32) IS SUPPORTED

Yes

IF SVC (B41/B42) IS SUPPORTED

Yes Yes

NOTE

c2: shall be "M" if support for LOGICAL-NODE model has been declared c3: shall be "M" if support for DATA model has been declared c4: shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared c5: shall be "M" if support for Report, GSE, or SMV models has been declared M: Mandatory C.6.3 ACSI SERVICES CONFORMANCE STATEMENT

In the table below, the acronym AA refers to Application Associations (TP: Two Party / MC: Multicast). The c6 to c10 entries are defined in the notes following the table.
SERVICES SERVER (CLAUSE 6) S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 ServerDirectory Associate Abort Release LogicalDeviceDirectory LogicalNodeDirectory GetAllDataValues GetDataValues SetDataValues GetDataDirectory GetDataDefinition TP TP TP TP TP TP TP TP M M M M M M M M O M M Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes APPLICATION ASSOCIATION (CLAUSE 7) AA: TP/MC SERVER/ PUBLISHER UR FAMILY

LOGICAL DEVICE (CLAUSE 8) LOGICAL NODE (CLAUSE 9)

DATA (CLAUSE 10)

GE Multilin

C30 Controller System

C-23

C.6 ACSI CONFORMANCE


SERVICES DATA SET (CLAUSE 11) S12 S13 S14 S15 S16 S17 S18 S19 S20 S21 S22 S23 GetDataSetValues SetDataSetValues CreateDataSet DeleteDataSet GetDataSetDirectory SetDataValues SelectActiveSG SelectEditSG SetSGValues ConfirmEditSGValues GetSGValues GetSGCBValues TP TP TP TP TP TP TP TP TP TP TP TP M O O O O M O O O O O O Yes Yes AA: TP/MC SERVER/ PUBLISHER UR FAMILY

APPENDIX C

SUBSTITUTION (CLAUSE 12) SETTING GROUP CONTROL (CLAUSE 13)

REPORTING (CLAUSE 14) BUFFERED REPORT CONTROL BLOCK (BRCB) S24 S24-1 S24-2 S24-3 S25 S26 S27 S27-1 S27-2 S27-3 S28 S29 Report data-change (dchg) qchg-change (qchg) data-update (dupd) GetBRCBValues SetBRCBValues Report data-change (dchg) qchg-change (qchg) data-update (dupd) GetURCBValues SetURCBValues LOG CONTROL BLOCK S30 S31 S32 S33 S34 GetLCBValues SetLCBValues LOG QueryLogByTime QueryLogByEntry GetLogStatusValues GOOSE-CONTROL-BLOCK S35 S36 S37 S38 S39 S40 S41 SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference MC TP c8 c9 Yes MC TP TP TP TP c8 c9 c9 O O Yes Yes Yes TP TP TP M M M TP TP M M TP TP c6 c6 Yes Yes TP TP TP c6 c6 c6 Yes Yes Yes Yes TP c6 Yes Yes

UNBUFFERED REPORT CONTROL BLOCK (URCB)

LOGGING (CLAUSE 14)

GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4)

C-24

C30 Controller System

GE Multilin

APPENDIX C
SERVICES S42 S43 S44 GetGSSEElementNumber GetGsCBValues SetGsCBValues MULTICAST SVC S45 S46 S47 S48 S49 S50 S51 S52 S53 S54 S55 S56 S57 S58 S59 S60 T1 SendMSVMessage GetMSVCBValues SetMSVCBValues UNICAST SVC SendUSVMessage GetUSVCBValues SetUSVCBValues Select SelectWithValue Cancel Operate Command-Termination TimeActivated-Operate GetFile SetFile DeleteFile GetFileAttributeValues Time resolution of internal clock (nearest negative power of 2 in seconds) Time accuracy of internal clock supported TimeStamp resolution (nearest value of 2n in seconds, accoridng to 5.5.3.7.3.3) TP TP TP TP TP TP TP TP TP MC TP TP c10 O O O O O M O O M O O M MC TP TP c10 O O AA: TP/MC TP TP TP SERVER/ PUBLISHER c9 O O

C.6 ACSI CONFORMANCE


UR FAMILY

Yes Yes

TRANSMISSION OF SAMPLE VALUE MODEL (SVC) (CLAUSE 16)

C
Yes Yes Yes

CONTROL (CLAUSE 16.4.8)

FILE TRANSFER (CLAUSE 20) Yes

Yes 20

TIME (CLAUSE 5.5)

T2 T3

20

NOTE

c6: shall declare support for at least one (BRCB or URCB) c7: shall declare support for at least one (QueryLogByTime or QueryLogAfter) c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage)

GE Multilin

C30 Controller System

C-25

C.7 LOGICAL NODES C.7LOGICAL NODES

APPENDIX C C.7.1 LOGICAL NODES TABLE

The UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantiation of each logical node is determined by the product order code. For example. the logical node PDIS (distance protection) is available only in the D60 Line Distance Relay. Table C1: IEC 61850 LOGICAL NODES (Sheet 1 of 3)
NODES L: SYSTEM LOGICAL NODES LPHD: Physical device information LLN0: Logical node zero P: LOGICAL NODES FOR PROTECTION FUNCTIONS PDIF: Differential PDIR: Direction comparison PDIS: Distance PDOP: Directional overpower PDUP: Directional underpower PFRC: Rate of change of frequency PHAR: Harmonic restraint PHIZ: Ground detector PIOC: Instantaneous overcurrent PMRI Motor restart inhibition PMSS: Motor starting time supervision POPF: Over power factor PPAM: Phase angle measuring PSCH: Protection scheme PSDE: Sensitive directional earth fault PTEF: Transient earth fault PTOC: Time overcurrent PTOF: Overfrequency PTOV: Overvoltage PTRC: Protection trip conditioning PTTR: Thermal overload PTUC: Undercurrent PTUV: Undervoltage PUPF: Underpower factor PTUF: Underfrequency PVOC: Voltage controlled time overcurrent PVPH: Volts per Hz PZSU: Zero speed or underspeed R: LOGICAL NODES FOR PROTECTION RELATED FUNCTIONS RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing --------Yes --Yes Yes Yes Yes --Yes ----------Yes --------------Yes --Yes Yes Yes --Yes ----------Yes Yes UR-FAMILY

C-26

C30 Controller System

GE Multilin

APPENDIX C Table C1: IEC 61850 LOGICAL NODES (Sheet 2 of 3)


NODES RSYN: Synchronism-check or synchronizing C: LOGICAL NODES FOR CONTROL CALH: Alarm handling CCGR: Cooling group control CILO: Interlocking CPOW: Point-on-wave switching CSWI: Switch controller G: LOGICAL NODES FOR GENERIC REFERENCES GAPC: Generic automatic process control GGIO: Generic process I/O GSAL: Generic security application I: LOGICAL NODES FOR INTERFACING AND ARCHIVING IARC: Archiving IHMI: Human machine interface ITCI: Telecontrol interface ITMI: Telemonitoring interface A: LOGICAL NODES FOR AUTOMATIC CONTROL ANCR: Neutral current regulator ARCO: Reactive power control ATCC: Automatic tap changer controller AVCO: Voltage control M: LOGICAL NODES FOR METERING AND MEASUREMENT MDIF: Differential measurements MHAI: Harmonics or interharmonics MHAN: Non phase related harmonics or interharmonic MMTR: Metering MMXN: Non phase related measurement MMXU: Measurement MSQI: Sequence and imbalance MSTA: Metering statistics S: LOGICAL NODES FOR SENSORS AND MONITORING SARC: Monitoring and diagnostics for arcs SIMG: Insulation medium supervision (gas) SIML: Insulation medium supervision (liquid) SPDC: Monitoring and diagnostics for partial discharges X: LOGICAL NODES FOR SWITCHGEAR XCBR: Circuit breaker XSWI: Circuit switch T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer ------------Yes Yes ----------------Yes Yes ----------------------Yes ----------Yes UR-FAMILY ---

C.7 LOGICAL NODES

GE Multilin

C30 Controller System

C-27

C.7 LOGICAL NODES Table C1: IEC 61850 LOGICAL NODES (Sheet 3 of 3)
NODES Z: LOGICAL NODES FOR FURTHER POWER SYSTEM EQUIPMENT ZAXN: Auxiliary network ZBAT: Battery ZBSH: Bushing ZCAB: Power cable ZCAP: Capacitor bank ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ------------------------------UR-FAMILY

APPENDIX C

ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component

C-28

C30 Controller System

GE Multilin

APPENDIX D APPENDIX D IEC 60870-5-104 COMMUNICATIONSD.1IEC 60870-5-104

D.1 IEC 60870-5-104 D.1.1 INTEROPERABILITY DOCUMENT used in

This document is adapted from the IEC 60870-5-104 standard. For ths section the boxes indicate the following: standard direction; not used; cannot be selected in IEC 60870-5-104 standard. 1. SYSTEM OR DEVICE: System Definition Controlling Station Definition (Master) Controlled Station Definition (Slave) 2. NETWORK CONFIGURATION: Point-to-Point Multiple Point-to-Point 3. PHYSICAL LAYER Transmission Speed (control direction):
Unbalanced Interchange Circuit V.24/V.28 Standard: 100 bits/sec. 200 bits/sec. 300 bits/sec. 600 bits/sec. 1200 bits/sec. Unbalanced Interchange Circuit V.24/V.28 Recommended if >1200 bits/s: 2400 bits/sec. 4800 bits/sec. 9600 bits/sec. Balanced Interchange Circuit X.24/X.27: 2400 bits/sec. 4800 bits/sec. 9600 bits/sec. 19200 bits/sec. 38400 bits/sec. 56000 bits/sec. 64000 bits/sec.

Multipoint Multipoint Star

Transmission Speed (monitor direction):


Unbalanced Interchange Circuit V.24/V.28 Standard: 100 bits/sec. 200 bits/sec. 300 bits/sec. 600 bits/sec. 1200 bits/sec. Unbalanced Interchange Circuit V.24/V.28 Recommended if >1200 bits/s: 2400 bits/sec. 4800 bits/sec. 9600 bits/sec. Balanced Interchange Circuit X.24/X.27: 2400 bits/sec. 4800 bits/sec. 9600 bits/sec. 19200 bits/sec. 38400 bits/sec. 56000 bits/sec. 64000 bits/sec.

4.

LINK LAYER
Address Field of the Link: Not Present (Balanced Transmission Only) One Octet Two Octets Structured Unstructured Balanced Transmision Unbalanced Transmission

Link Transmission Procedure:

Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard

GE Multilin

C30 Controller System

D-1

D.1 IEC 60870-5-104

APPENDIX D

When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low priority) with the indicated causes of transmission: The standard assignment of ADSUs to class 2 messages is used as follows: A special assignment of ADSUs to class 2 messages is used as follows: 5. APPLICATION LAYER Transmission Mode for Application Data: Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in this companion stanadard. Common Address of ADSU: One Octet Two Octets Information Object Address: One Octet Structured Unstructured

Two Octets Three Octets Cause of Transmission: One Octet

Two Octets (with originator address). Originator address is set to zero if not used. Maximum Length of APDU: 253 (the maximum length may be reduced by the system. Selection of standard ASDUs: For the following lists, the boxes indicate the following: selected in IEC 60870-5-104 standard. Process information in monitor direction
<1> := Single-point information <2> := Single-point information with time tag <3> := Double-point information <4> := Double-point information with time tag <5> := Step position information <6> := Step position information with time tag <7> := Bitstring of 32 bits <8> := Bitstring of 32 bits with time tag <9> := Measured value, normalized value <10> := Measured value, normalized value with time tag <11> := Measured value, scaled value <12> := Measured value, scaled value with time tag <13> := Measured value, short floating point value <14> := Measured value, short floating point value with time tag <15> := Integrated totals <16> := Integrated totals with time tag <17> := Event of protection equipment with time tag <18> := Packed start events of protection equipment with time tag <19> := Packed output circuit information of protection equipment with time tag <20> := Packed single-point information with status change detection M_SP_NA_1 M_SP_TA_1 M_DP_NA_1 M_DP_TA_1 M_ST_NA_1 M_ST_TA_1 M_BO_NA_1 M_BO_TA_1 M_ME_NA_1 M_NE_TA_1 M_ME_NB_1 M_NE_TB_1 M_ME_NC_1 M_NE_TC_1 M_IT_NA_1 M_IT_TA_1 M_EP_TA_1 M_EP_TB_1 M_EP_TC_1 M_SP_NA_1

used in standard direction;

not used;

cannot be

D-2

C30 Controller System

GE Multilin

APPENDIX D
<21> := Measured value, normalized value without quantity descriptor <30> := Single-point information with time tag CP56Time2a <31> := Double-point information wiht time tag CP56Time2a <32> := Step position information with time tag CP56Time2a <33> := Bitstring of 32 bits with time tag CP56Time2a <34> := Measured value, normalized value with time tag CP56Time2a <35> := Measured value, scaled value with time tag CP56Time2a <36> := Measured value, short floating point value with time tag CP56Time2a <37> := Integrated totals with time tag CP56Time2a <38> := Event of protection equipment with time tag CP56Time2a <39> := Packed start events of protection equipment with time tag CP56Time2a <40> := Packed output circuit information of protection equipment with time tag CP56Time2a

D.1 IEC 60870-5-104


M_ME_ND_1 M_SP_TB_1 M_DP_TB_1 M_ST_TB_1 M_BO_TB_1 M_ME_TD_1 M_ME_TE_1 M_ME_TF_1 M_IT_TB_1 M_EP_TD_1 M_EP_TE_1 M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set <30> to <40> are used. Process information in control direction
<45> := Single command <46> := Double command <47> := Regulating step command <48> := Set point command, normalized value <49> := Set point command, scaled value <50> := Set point command, short floating point value <51> := Bitstring of 32 bits <58> := Single command with time tag CP56Time2a <59> := Double command with time tag CP56Time2a <60> := Regulating step command with time tag CP56Time2a <61> := Set point command, normalized value with time tag CP56Time2a <62> := Set point command, scaled value with time tag CP56Time2a <63> := Set point command, short floating point value with time tag CP56Time2a <64> := Bitstring of 32 bits with time tag CP56Time2a C_SC_NA_1 C_DC_NA_1 C_RC_NA_1 C_SE_NA_1 C_SE_NB_1 C_SE_NC_1 C_BO_NA_1 C_SC_TA_1 C_DC_TA_1 C_RC_TA_1 C_SE_TA_1 C_SE_TB_1 C_SE_TC_1 C_BO_TA_1

Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used. System information in monitor direction
<70> := End of initialization M_EI_NA_1

System information in control direction


<100> := Interrogation command <101> := Counter interrogation command <102> := Read command <103> := Clock synchronization command (see Clause 7.6 in standard) <104> := Test command <105> := Reset process command <106> := Delay acquisition command <107> := Test command with time tag CP56Time2a C_IC_NA_1 C_CI_NA_1 C_RD_NA_1 C_CS_NA_1 C_TS_NA_1 C_RP_NA_1 C_CD_NA_1 C_TS_TA_1

GE Multilin

C30 Controller System

D-3

D.1 IEC 60870-5-104 Parameter in control direction


<110> := Parameter of measured value, normalized value <111> := Parameter of measured value, scaled value <112> := Parameter of measured value, short floating point value <113> := Parameter activation PE_ME_NA_1 PE_ME_NB_1 PE_ME_NC_1 PE_AC_NA_1

APPENDIX D

File transfer
<120> := File Ready <121> := Section Ready <122> := Call directory, select file, call file, call section <123> := Last section, last segment <124> := Ack file, ack section <125> := Segment <126> := Directory (blank or X, available only in monitor [standard] direction) F_FR_NA_1 F_SR_NA_1 F_SC_NA_1 F_LS_NA_1 F_AF_NA_1 F_SG_NA_1 C_CD_NA_1

Type identifier and cause of transmission assignments (station-specific parameters) In the following table: Shaded boxes are not required. Black boxes are not permitted in this companion standard. Blank boxes indicate functions or ASDU not used. X if only used in the standard direction
TYPE IDENTIFICATION CAUSE OF TRANSMISSION REQUEST BY GROUP <N> COUNTER REQ UNKNOWN INFORMATION OBJECT ADDR 46 UNKNOWN INFORMATION OBJECT ADDR 47 UNKNOWN COMMON ADDRESS OF ADSU 45 INTERROGATED BY GROUP <NUMBER> RETURN INFO CAUSED BY LOCAL CMD UNKNOWN CAUSE OF TRANSMISSION 44

NO. <1> <2> <3> <4> <5> <6> <7> <8> <9>

MNEMONIC M_SP_NA_1 M_SP_TA_1 M_DP_NA_1 M_DP_TA_1 M_ST_NA_1 M_ST_TA_1 M_BO_NA_1 M_BO_TA_1 M_ME_NA_1

3 X

5 X

10

11 X

12 X

13

20 to 36 X

D-4

C30 Controller System

UNKNOWN TYPE IDENTIFICATION 37 to 41

DEACTIVATION CONFIRMATION

ACTIVATION CONFIRMATION

ACTIVATION TERMINATION

REQUEST OR REQUESTED

BACKGROUND SCAN

PERIODIC, CYCLIC

FILE TRANSFER

SPONTANEOUS

DEACTIVATION

ACTIVATION

INITIALIZED

GE Multilin

APPENDIX D
TYPE IDENTIFICATION CAUSE OF TRANSMISSION

D.1 IEC 60870-5-104

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR 46

NO. <10> <11> <12> <13> <14> <15> <16> <17> <18> <19> <20> <21> <30> <31> <32> <33> <34> <35> <36> <37> <38> <39> <40> <45> <46> <47> <48> <49> <50> <51> <58> <59> <60>

MNEMONIC M_ME_TA_1 M_ME_NB_1 M_ME_TB_1 M_ME_NC_1 M_ME_TC_1 M_IT_NA_1 M_IT_TA_1 M_EP_TA_1 M_EP_TB_1 M_EP_TC_1 M_PS_NA_1 M_ME_ND_1 M_SP_TB_1 M_DP_TB_1 M_ST_TB_1 M_BO_TB_1 M_ME_TD_1 M_ME_TE_1 M_ME_TF_1 M_IT_TB_1 M_EP_TD_1 M_EP_TE_1 M_EP_TF_1 C_SC_NA_1 C_DC_NA_1 C_RC_NA_1 C_SE_NA_1 C_SE_NB_1 C_SE_NC_1 C_BO_NA_1 C_SC_TA_1 C_DC_TA_1 C_RC_TA_1

10

11

12

13

20 to 36

37 to 41

44

45

UNKNOWN INFORMATION OBJECT ADDR 47

REQUEST BY GROUP <N> COUNTER REQ

INTERROGATED BY GROUP <NUMBER>

RETURN INFO CAUSED BY LOCAL CMD

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN TYPE IDENTIFICATION

DEACTIVATION CONFIRMATION

ACTIVATION CONFIRMATION

ACTIVATION TERMINATION

REQUEST OR REQUESTED

BACKGROUND SCAN

PERIODIC, CYCLIC

FILE TRANSFER

SPONTANEOUS

DEACTIVATION

ACTIVATION

INITIALIZED

D
X X X X X X

GE Multilin

C30 Controller System

D-5

D.1 IEC 60870-5-104


TYPE IDENTIFICATION CAUSE OF TRANSMISSION

APPENDIX D

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR 46

NO.

MNEMONIC C_SE_TA_1 C_SE_TB_1 C_SE_TC_1 C_BO_TA_1 M_EI_NA_1*) C_IC_NA_1 C_CI_NA_1 C_RD_NA_1 C_CS_NA_1 C_TS_NA_1 C_RP_NA_1 C_CD_NA_1 C_TS_TA_1 P_ME_NA_1 P_ME_NB_1 P_ME_NC_1 P_AC_NA_1 F_FR_NA_1 F_SR_NA_1 F_SC_NA_1 F_LS_NA_1 F_AF_NA_1 F_SG_NA_1 F_DR_TA_1*)

10

11

12

13

20 to 36

37 to 41

44

45

<61> <62> <63> <64> <70> <100> <101> <102> <103> <104> <105> <106> <107> <110> <111> <112> <113> <120> <121> <122> <123> <124> <125> <126>

X X X X X X X X X X X X X X X

6.

BASIC APPLICATION FUNCTIONS Station Initialization: Remote initialization Cyclic Data Transmission: Cyclic data transmission Read Procedure: Read procedure

D-6

C30 Controller System

GE Multilin

UNKNOWN INFORMATION OBJECT ADDR 47

REQUEST BY GROUP <N> COUNTER REQ

INTERROGATED BY GROUP <NUMBER>

RETURN INFO CAUSED BY LOCAL CMD

UNKNOWN CAUSE OF TRANSMISSION

UNKNOWN TYPE IDENTIFICATION

DEACTIVATION CONFIRMATION

ACTIVATION CONFIRMATION

ACTIVATION TERMINATION

REQUEST OR REQUESTED

BACKGROUND SCAN

PERIODIC, CYCLIC

FILE TRANSFER

SPONTANEOUS

DEACTIVATION

ACTIVATION

INITIALIZED

APPENDIX D Spontaneous Transmission: Spontaneous transmission Double transmission of information objects with cause of transmission spontaneous:

D.1 IEC 60870-5-104

The following type identifications may be transmitted in succession caused by a single status change of an information object. The particular information object addresses for which double transmission is enabled are defined in a projectspecific list. Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1 Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1 Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1 Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project) Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1 Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1 Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1 Station interrogation: Global Group 1 Group 2 Group 3 Group 4 Clock synchronization: Clock synchronization (optional, see Clause 7.6) Command transmission: Direct command transmission Direct setpoint command transmission Select and execute command Select and execute setpoint command C_SE ACTTERM used No additional definition Short pulse duration (duration determined by a system parameter in the outstation) Long pulse duration (duration determined by a system parameter in the outstation) Persistent output Supervision of maximum delay in command direction of commands and setpoint commands Maximum allowable delay of commands and setpoint commands: 10 s Transmission of integrated totals: Mode A: Local freeze with spontaneous transmission Mode B: Local freeze with counter interrogation Mode C: Freeze and transmit by counter-interrogation commands Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously Counter read Counter freeze without reset Group 5 Group 6 Group 7 Group 8 Group 9 Group 10 Group 11 Group 12 Group 13 Group 14 Group 15 Group 16

GE Multilin

C30 Controller System

D-7

D.1 IEC 60870-5-104 Counter freeze with reset Counter reset General request counter Request counter group 1 Request counter group 2 Request counter group 3 Request counter group 4 Parameter loading: Threshold value Smoothing factor Low limit for transmission of measured values High limit for transmission of measured values

APPENDIX D

Parameter activation: Activation/deactivation of persistent cyclic or periodic transmission of the addressed object Test procedure: Test procedure File transfer: File transfer in monitor direction: Transparent file Transmission of disturbance data of protection equipment Transmission of sequences of events Transmission of sequences of recorded analog values File transfer in control direction: Transparent file Background scan: Background scan Acquisition of transmission delay: Acquisition of transmission delay Definition of time outs:
PARAMETER DEFAULT VALUE 30 s 15 s 10 s 20 s REMARKS Timeout of connection establishment Timeout of send or test APDUs Timeout for acknowlegements in case of no data messages t2 < t1 Timeout for sending test frames in case of a long idle state SELECTED VALUE 120 s 15 s 10 s 20 s

t0 t1 t2 t3

Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w):
PARAMETER DEFAULT VALUE 12 APDUs 8 APDUs REMARKS Maximum difference receive sequence number to send state variable Latest acknowledge after receiving w I-format APDUs SELECTED VALUE 12 APDUs 8 APDUs

k w

D-8

C30 Controller System

GE Multilin

APPENDIX D Maximum range of values k: Maximum range of values w: Portnumber:


PARAMETER Portnumber VALUE 2404 REMARKS In all cases

D.1 IEC 60870-5-104 1 to 32767 (215 1) APDUs, accuracy 1 APDU 1 to 32767 APDUs, accuracy 1 APDU Recommendation: w should not exceed two-thirds of k.

RFC 2200 suite: RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in the Internet as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen by the user of this standard. Ethernet 802.3 Serial X.21 interface Other selection(s) from RFC 2200 (list below if selected) D.1.2 POINT LIST
COMMUNICATIONS The IEC 60870-5-104 data points are configured through the SETTINGS PRODUCT SETUP menu. Refer to the Communications section of Chapter 5 for additional details. DNP /

IEC104 POINT LISTS

GE Multilin

C30 Controller System

D-9

D.1 IEC 60870-5-104

APPENDIX D

D-10

C30 Controller System

GE Multilin

APPENDIX E APPENDIX E DNP COMMUNICATIONSE.1DEVICE PROFILE DOCUMENT

E.1 DEVICE PROFILE DOCUMENT E.1.1 DNP V3.00 DEVICE PROFILE

The following table provides a Device Profile Document in the standard format defined in the DNP 3.0 Subset Definitions Document. Table E1: DNP V3.00 DEVICE PROFILE (Sheet 1 of 3) (Also see the IMPLEMENTATION TABLE in the following section) Vendor Name: General Electric Multilin Device Name: UR Series Relay Highest DNP Level Supported: For Requests: Level 2 For Responses: Level 2 Device Function: Master Slave

Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): Binary Inputs (Object 1) Binary Input Changes (Object 2) Binary Outputs (Object 10) Control Relay Output Block (Object 12) Binary Counters (Object 20) Frozen Counters (Object 21) Counter Change Event (Object 22) Frozen Counter Event (Object 23) Analog Inputs (Object 30) Analog Input Changes (Object 32) Analog Deadbands (Object 34) Time and Date (Object 50) File Transfer (Object 70) Internal Indications (Object 80) Maximum Data Link Frame Size (octets): Transmitted: 292 Received: 292 Maximum Data Link Re-tries: None Fixed at 3 Configurable Requires Data Link Layer Confirmation: Never Always Sometimes Configurable Maximum Application Fragment Size (octets): Transmitted: configurable up to 2048 Received: 2048 Maximum Application Layer Re-tries: None Configurable

GE Multilin

C30 Controller System

E-1

E.1 DEVICE PROFILE DOCUMENT Table E1: DNP V3.00 DEVICE PROFILE (Sheet 2 of 3) Requires Application Layer Confirmation: Never Always When reporting Event Data When sending multi-fragment responses Sometimes Configurable Timeouts while waiting for: Data Link Confirm: Complete Appl. Fragment: Application Confirm: Complete Appl. Response: Others: Transmission Delay: Need Time Interval: Select/Operate Arm Timeout: Binary input change scanning period: Analog input change scanning period: Counter change scanning period: Frozen counter event scanning period: Unsolicited response notification delay: Unsolicited response retry delay Sends/Executes Control Operations: WRITE Binary Outputs SELECT/OPERATE DIRECT OPERATE DIRECT OPERATE NO ACK Count > 1 Pulse On Pulse Off Latch On Latch Off Queue Clear Queue Never Never Never Never Never Never Never Never Never Never Never Always Always Always Always Always Always Always Always Always Always Always Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Configurable Configurable Configurable Configurable Configurable Configurable Configurable No intentional delay Configurable (default = 24 hrs.) 10 s 8 times per power system cycle 500 ms 500 ms 500 ms 100 ms configurable 0 to 60 sec. None None None None Fixed at ____ Fixed at ____ Fixed at 10 s Fixed at ____ Variable Variable Variable Variable

APPENDIX E

Configurable Configurable Configurable Configurable

Configurable Configurable Configurable Configurable

Explanation of Sometimes: Object 12 points are mapped to UR Virtual Inputs. The persistence of Virtual Inputs is determined by the VIRTUAL INPUT X TYPE settings. Both Pulse On and Latch On operations perform the same function in the UR; that is, the appropriate Virtual Input is put into the On state. If the Virtual Input is set to Self-Reset, it will reset after one pass of FlexLogic. The On/Off times and Count value are ignored. Pulse Off and Latch Off operations put the appropriate Virtual Input into the Off state. Trip and Close operations both put the appropriate Virtual Input into the On state.

E-2

C30 Controller System

GE Multilin

APPENDIX E Table E1: DNP V3.00 DEVICE PROFILE (Sheet 3 of 3) Reports Binary Input Change Events when no specific variation requested: Never Only time-tagged Only non-time-tagged Configurable Sends Unsolicited Responses: Never Configurable Only certain objects Sometimes (attach explanation) ENABLE/DISABLE unsolicited Function codes supported Default Counter Object/Variation: No Counters Reported Configurable (attach explanation) Default Object: 20 Default Variation: 1 Point-by-point list attached

E.1 DEVICE PROFILE DOCUMENT

Reports time-tagged Binary Input Change Events when no specific variation requested: Never Binary Input Change With Time Binary Input Change With Relative Time Configurable (attach explanation) Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change No other options are permitted.

Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits (Counter 8) 32 Bits (Counters 0 to 7, 9) Other Value: _____ Point-by-point list attached

Sends Multi-Fragment Responses: Yes No

GE Multilin

C30 Controller System

E-3

E.1 DEVICE PROFILE DOCUMENT

APPENDIX E E.1.2 IMPLEMENTATION TABLE

The following table identifies the variations, function codes, and qualifiers supported by the C30 in both request messages and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. Table E2: IMPLEMENTATION TABLE (Sheet 1 of 4)
OBJECT OBJECT VARIATION DESCRIPTION NO. NO. 1 0 Binary Input (Variation 0 is used to request default variation) REQUEST FUNCTION CODES (DEC) 1 (read) 22 (assign class) QUALIFIER CODES (HEX) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 06 (no range, or all) 07, 08 (limited quantity) 06 (no range, or all) 07, 08 (limited quantity) 06 (no range, or all) 07, 08 (limited quantity) 06 (no range, or all) 07, 08 (limited quantity) 00, 01(start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 07, 08 (limited quantity) 17, 28 (index) RESPONSE FUNCTION CODES (DEC) QUALIFIER CODES (HEX)

Binary Input

1 (read) 22 (assign class)

129 (response)

00, 01 (start-stop) 17, 28 (index) (see Note 2) 00, 01 (start-stop) 17, 28 (index) (see Note 2)

Binary Input with Status

1 (read) 22 (assign class)

129 (response)

0 1

Binary Input Change (Variation 0 is used to 1 (read) request default variation) Binary Input Change without Time 1 (read) Binary Input Change with Time Binary Input Change with Relative Time 1 (read) 1 (read)

E
10

2 3 0

129 (response) 130 (unsol. resp.) 129 (response 130 (unsol. resp.)

17, 28 (index) 17, 28 (index)

Binary Output Status (Variation 0 is used to 1 (read) request default variation)

Binary Output Status

1 (read)

129 (response)

00, 01 (start-stop) 17, 28 (index) (see Note 2)

12

20

Note 1:

129 (response) echo of request 3 (select) 4 (operate) 5 (direct op) 6 (dir. op, noack) 0 Binary Counter 1 (read) 00, 01(start-stop) 7 (freeze) 06(no range, or all) (Variation 0 is used to request default 8 (freeze noack) 07, 08(limited quantity) variation) 9 (freeze clear) 17, 28(index) 10 (frz. cl. noack) 22 (assign class) 1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 7 (freeze) 06 (no range, or all) 17, 28 (index) 8 (freeze noack) 07, 08 (limited quantity) (see Note 2) 9 (freeze clear) 17, 28 (index) 10 (frz. cl. noack) 22 (assign class) A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5 for details. This optimizes the class 0 poll data size. 1 Control Relay Output Block For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for changeevent objects, qualifiers 17 or 28 are always responded.) Cold restarts are implemented the same as warm restarts the C30 is not restarted, but the DNP process is restarted.

Note 2:

Note 3:

E-4

C30 Controller System

GE Multilin

APPENDIX E Table E2: IMPLEMENTATION TABLE (Sheet 2 of 4)


OBJECT OBJECT VARIATION DESCRIPTION NO. NO. 20 2 16-Bit Binary Counter contd REQUEST FUNCTION CODES (DEC) 1 (read) 7 (freeze) 8 (freeze noack) 9 (freeze clear) 10 (frz. cl. noack) 22 (assign class) 1 (read) 7 (freeze) 8 (freeze noack) 9 (freeze clear) 10 (frz. cl. noack) 22 (assign class) 1 (read) 7 (freeze) 8 (freeze noack) 9 (freeze clear) 10 (frz. cl. noack) 22 (assign class) 1 (read) 22 (assign class)

E.1 DEVICE PROFILE DOCUMENT

RESPONSE QUALIFIER FUNCTION CODES (HEX) CODES (DEC) 00, 01 (start-stop) 129 (response) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index)

QUALIFIER CODES (HEX) 00, 01 (start-stop) 17, 28 (index) (see Note 2)

32-Bit Binary Counter without Flag

00, 01 (start-stop) 129 (response) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index)

00, 01 (start-stop) 17, 28 (index) (see Note 2)

16-Bit Binary Counter without Flag

00, 01 (start-stop) 129 (response) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index)

00, 01 (start-stop) 17, 28 (index) (see Note 2)

21

22

23

Note 1:

00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 1 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 2 16-Bit Frozen Counter 1 (read) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 10 16-Bit Frozen Counter without Flag 1 (read) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 0 Counter Change Event (Variation 0 is used 1 (read) 06 (no range, or all) 07, 08 (limited quantity) to request default variation) 1 32-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 2 16-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 5 32-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 6 16-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 0 Frozen Counter Event (Variation 0 is used 1 (read) 06 (no range, or all) to request default variation) 07, 08 (limited quantity) 1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5 for details. This optimizes the class 0 poll data size. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for changeevent objects, qualifiers 17 or 28 are always responded.) Cold restarts are implemented the same as warm restarts the C30 is not restarted, but the DNP process is restarted.

Frozen Counter (Variation 0 is used to request default variation)

Note 2:

Note 3:

GE Multilin

C30 Controller System

E-5

E.1 DEVICE PROFILE DOCUMENT Table E2: IMPLEMENTATION TABLE (Sheet 3 of 4)


OBJECT OBJECT VARIATION DESCRIPTION NO. NO. 23 5 32-Bit Frozen Counter Event with Time contd 6 16-Bit Frozen Counter Event with Time 30

APPENDIX E

E
32

34

Note 1:

RESPONSE QUALIFIER FUNCTION QUALIFIER CODES (HEX) CODES (DEC) CODES (HEX) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 0 Analog Input (Variation 0 is used to request 1 (read) 00, 01 (start-stop) default variation) 22 (assign class) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 2 16-Bit Analog Input 1 (read) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 22 (assign class) 06 (no range, or all) 17, 28 (index) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 5 short floating point 1 (read) 22 (assign class) 06(no range, or all) 17, 28 (index) 07, 08(limited quantity) (see Note 2) 17, 28(index) 0 Analog Change Event (Variation 0 is used 1 (read) 06 (no range, or all) to request default variation) 07, 08 (limited quantity) 1 32-Bit Analog Change Event without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 2 16-Bit Analog Change Event without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 3 32-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 4 16-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) 07, 08 (limited quantity) 130 (unsol. resp.) 5 short floating point Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) without Time 07, 08 (limited quantity) 130 (unsol. resp.) 7 short floating point Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index) with Time 07, 08 (limited quantity) 130 (unsol. resp.) 0 Analog Input Reporting Deadband 1 (read) 00, 01 (start-stop) (Variation 0 is used to request default 06 (no range, or all) variation) 07, 08 (limited quantity) 17, 28 (index) 1 16-bit Analog Input Reporting Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 06 (no range, or all) 17, 28 (index) (default see Note 1) 07, 08 (limited quantity) (see Note 2) 17, 28 (index) 2 (write) 00, 01 (start-stop) 07, 08 (limited quantity) 17, 28 (index) A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5 for details. This optimizes the class 0 poll data size. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for changeevent objects, qualifiers 17 or 28 are always responded.) Cold restarts are implemented the same as warm restarts the C30 is not restarted, but the DNP process is restarted.

REQUEST FUNCTION CODES (DEC) 1 (read)

Note 2:

Note 3:

E-6

C30 Controller System

GE Multilin

APPENDIX E Table E2: IMPLEMENTATION TABLE (Sheet 4 of 4)


OBJECT OBJECT VARIATION DESCRIPTION NO. NO. 34 2 32-bit Analog Input Reporting Deadband REQUEST FUNCTION CODES (DEC) 1 (read)

E.1 DEVICE PROFILE DOCUMENT

contd

2 (write)

Short floating point Analog Input Reporting 1 (read) Deadband

50

Time and Date (default see Note 1)

1 (read) 2 (write)

QUALIFIER CODES (HEX) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 06 (no range, or all) 07, 08 (limited quantity) 17, 28 (index) 00, 01 (start-stop) 06 (no range, or all) 07 (limited qty=1) 08 (limited quantity) 17, 28 (index)

RESPONSE FUNCTION CODES (DEC) 129 (response)

QUALIFIER CODES (HEX) 00, 01 (start-stop) 17, 28 (index) (see Note 2)

129 (response)

00, 01 (start-stop) 17, 28 (index) (see Note 2) 00, 01 (start-stop) 17, 28 (index) (see Note 2)

129 (response)

52 60

2 0

Time Delay Fine Class 0, 1, 2, and 3 Data 1 (read) 20 (enable unsol) 21 (disable unsol) 22 (assign class) 1 (read) 22 (assign class) 1 (read) 20 (enable unsol) 21 (disable unsol) 22 (assign class) 1 (read) 22 (assign class) 29 (authenticate) 25 (open) 27 (delete) 26 (close) 30 (abort) 1 (read) 2 (write) 06 (no range, or all)

129 (response)

07 (limited quantity)
(quantity = 1)

1 2 3 4 70 0

Class 0 Data Class 1 Data Class 2 Data Class 3 Data File event - any variation

06 (no range, or all) 06 (no range, or all) 07, 08 (limited quantity)

2 3 4 5 6 7 80 1

File authentication File command File command status File transfer File transfer status File descriptor Internal Indications

06 (no range, or all) 07, 08 (limited quantity) 06 (no range, or all) 5b (free format) 129 (response) 5b (free format) 5b (free format) 5b (free format) 129 (response) 130 (unsol. resp.) 129 (response) 130 (unsol. resp.) 129 (response) 130 (unsol. resp.) 129 (response) 130 (unsol. resp.) 129 (response)

5b (free format)

5b (free format) 5b (free format) 5b (free format) 5b (free format) 00, 01 (start-stop)

28 (get file info.) 1 (read) 2 (write) (see Note 3) 13 (cold restart)

5b (free format) 00, 01 (start-stop)


(index =7)

00 (start-stop)
(index =7)

------Note 1:

No Object (function code only) see Note 3 No Object (function code only) 14 (warm restart) No Object (function code only) 23 (delay meas.) A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5 for details. This optimizes the class 0 poll data size. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for changeevent objects, qualifiers 17 or 28 are always responded.) Cold restarts are implemented the same as warm restarts the C30 is not restarted, but the DNP process is restarted.

Note 2:

Note 3:

GE Multilin

C30 Controller System

E-7

E.2 DNP POINT LISTS E.2DNP POINT LISTS

APPENDIX E E.2.1 BINARY INPUT POINTS

COMMUNICATIONS DNP / IEC104 POINT The DNP binary input data points are configured through the PRODUCT SETUP LISTS BINARY INPUT / MSP POINTS menu. Refer to the Communications section of Chapter 5 for additional details. When a freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter point.

BINARY INPUT POINTS Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read), 22 (assign class) Static Variation reported when variation 0 requested: 2 (Binary Input with status), Configurable Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1

E-8

C30 Controller System

GE Multilin

APPENDIX E

E.2 DNP POINT LISTS E.2.2 BINARY AND CONTROL RELAY OUTPUT

Supported Control Relay Output Block fields: Pulse On, Pulse Off, Latch On, Latch Off, Paired Trip, Paired Close. BINARY OUTPUT STATUS POINTS Object Number: 10 Request Function Codes supported: 1 (read) Default Variation reported when Variation 0 requested: 2 (Binary Output Status) CONTROL RELAY OUTPUT BLOCKS Object Number: 12 Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, noack)

Table E3: BINARY/CONTROL OUTPUTS


POINT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 NAME/DESCRIPTION Virtual Input 1 Virtual Input 2 Virtual Input 3 Virtual Input 4 Virtual Input 5 Virtual Input 6 Virtual Input 7 Virtual Input 8 Virtual Input 9 Virtual Input 10 Virtual Input 11 Virtual Input 12 Virtual Input 13 Virtual Input 14 Virtual Input 15 Virtual Input 16 Virtual Input 17 Virtual Input 18 Virtual Input 19 Virtual Input 20 Virtual Input 21 Virtual Input 22 Virtual Input 23 Virtual Input 24 Virtual Input 25 Virtual Input 26 Virtual Input 27 Virtual Input 28 Virtual Input 29 Virtual Input 30 Virtual Input 31 Virtual Input 32

Table E3: BINARY/CONTROL OUTPUTS


POINT 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 NAME/DESCRIPTION Virtual Input 33 Virtual Input 34 Virtual Input 35 Virtual Input 36 Virtual Input 37 Virtual Input 38 Virtual Input 39 Virtual Input 40 Virtual Input 41 Virtual Input 42 Virtual Input 43 Virtual Input 44 Virtual Input 45 Virtual Input 46 Virtual Input 47 Virtual Input 48 Virtual Input 49 Virtual Input 50 Virtual Input 51 Virtual Input 52 Virtual Input 53 Virtual Input 54 Virtual Input 55 Virtual Input 56 Virtual Input 57 Virtual Input 58 Virtual Input 59 Virtual Input 60 Virtual Input 61 Virtual Input 62 Virtual Input 63 Virtual Input 64

GE Multilin

C30 Controller System

E-9

E.2 DNP POINT LISTS

APPENDIX E E.2.3 COUNTERS

The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is performed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.

BINARY COUNTERS Static (Steady-State) Object Number: 20 Change Event Object Number: 22 Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear), 10 (freeze and clear, noack), 22 (assign class)

Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without time) Change Event Buffer Size: 10 Default Class for all points: 3 FROZEN COUNTERS Static (Steady-State) Object Number: 21 Change Event Object Number: 23 Request Function Codes supported: 1 (read)

Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event without time) Change Event Buffer Size: 10 Default Class for all points: 3 Table E4: BINARY AND FROZEN COUNTERS
POINT INDEX 0 1 2 3 4 5 6 7 8 9 NAME/DESCRIPTION Digital Counter 1 Digital Counter 2 Digital Counter 3 Digital Counter 4 Digital Counter 5 Digital Counter 6 Digital Counter 7 Digital Counter 8 Oscillography Trigger Count Events Since Last Clear

A counter freeze command has no meaning for counters 8 and 9. C30 Digital Counter values are represented as 32-bit integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.

E-10

C30 Controller System

GE Multilin

APPENDIX E

E.2 DNP POINT LISTS E.2.4 ANALOG INPUTS

LISTS

COMMUNICATIONS DNP / IEC104 POINT The DNP analog input data points are configured through the PRODUCT SETUP ANALOG INPUT / MME POINTS menu. Refer to the Communications section of Chapter 5 for additional details.

It is important to note that 16-bit and 32-bit variations of analog inputs are transmitted through DNP as signed numbers. Even for analog input points that are not valid as negative values, the maximum positive representation is 32767 for 16-bit values and 2147483647 for 32-bit values. This is a DNP requirement. The deadbands for all Analog Input points are in the same units as the Analog Input quantity. For example, an Analog Input quantity measured in volts has a corresponding deadband in units of volts. This is in conformance with DNP Technical Bulletin 9809-001: Analog Input Reporting Deadband. Relay settings are available to set default deadband values according to data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.

Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read), 2 (write, deadbands only), 22 (assign class) Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input) Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2

GE Multilin

C30 Controller System

E-11

E.2 DNP POINT LISTS

APPENDIX E

E-12

C30 Controller System

GE Multilin

APPENDIX F APPENDIX F MISCELLANEOUSF.1CHANGE NOTES

F.1 CHANGE NOTES F.1.1 REVISION HISTORY

Table F1: REVISION HISTORY


MANUAL P/N 1601-0088-A1 1601-0088-A2 1601-0088-A3 1601-0088-A4 1601-0088-A5 1601-0088-A6 1601-0088-A7 1601-0088-A7a 1601-0088-B1 1601-0088-B2 1601-0088-B3 1601-0088-B4 1601-0088-B5 1601-0088-B6 1601-0088-C1 1601-0088-C2 1601-0088-C3 1601-0088-C4 1601-0088-C5 1601-0088-C6 1601-0088-D1 1601-0088-D2 1601-0088-E1 1601-0088-E2 1601-0088-F1 1601-0088-F2 1601-0088-G1 1601-0088-G2 1601-0088-H1 1601-0088-H2 1601-0088-J1 1601-0088-K1 1601-0088-L1 1601-0088-M1 1601-0088-M2 1601-0088-N1 1601-0088-N2 1601-0088-P1 1601-0088-P2 1601-0088-R1 1601-0088-R2 1601-0088-R3 1601-0088-S1 1601-0088-S2 1601-0088-S3 REVISION 1.5x 1.6x 1.8x 1.8x 2.0x 2.2x 2.2x 2.2x 2.4x 2.4x 2.6x 2.8x 2.9x 2.6x 3.0x 3.1x 3.0x 3.1x 3.0x 3.1x 3.2x 3.2x 3.3x 3.3x 3.4x 3.4x 4.0x 4.0x 4.2x 4.2x 4.4x 4.6x 4.8x 4.9x 4.9x 5.0x 5.0x 5.2x 5.2x 5.4x 5.4x 5.4x 5.5x 5.5x 5.5x RELEASE DATE 19 February 1999 10 August 1999 29 October 1999 15 November 1999 17 December 1999 12 May 2000 14 June 2000 28 June 2000 08 September 2000 03 November 2000 09 March 2001 26 September 2001 03 December 2001 27 February 2004 02 July 2002 30 August 2002 18 November 2002 18 November 2002 11 February 2003 11 February 2003 11 February 2003 02 June 2003 01 May 2003 29 May 2003 10 December 2003 09 February 2004 23 March 2004 17 May 2004 30 June 2004 23 July 2004 15 September 2004 15 February 2005 05 August 2005 15 December 2005 27 February 2006 31 March 2006 26 May 2006 23 October 2006 24 January 2007 26 June 2007 31 August 2007 17 October 2007 7 December 2007 22 February 2008 12 March 2008 ECO N/A URC-003 URC-004 URC-008 URC-009 URC-011 URC-013 URC-013a URC-015 URC-017 URC-019 URC-022 URC-024 URX-120 URC-026 URC-028 URC-030 URC-031 URC-034 URC-035 URC-038 URX-084 URX-080 URX-089 URX-111 URX-115 URX-123 URX-136 URX-145 URX-151 URX-156 URX-176 URX-202 URX-208 URX-214 URX-217 URX-220 URX-230 URX-232 URX-242 URX-246 URX-251 URX-253 URX-258 URX-260

GE Multilin

C30 Controller System

F-1

F.1 CHANGE NOTES Table F1: REVISION HISTORY


MANUAL P/N 1601-0088-T1 1601-0088-U1 1601-0088-U2 1601-0088-V1 REVISION 5.6x 5.7x 5.7x 5.8x RELEASE DATE 27 June 2008 29 May 2009 30 September 2009 29 May 2010 ECO 08-0390 09-0938 09-1165 09-1457

APPENDIX F

F.1.2 CHANGES TO THE C30 MANUAL

Table F2: MAJOR UPDATES FOR C30 MANUAL REVISION V1


PAGE (U2) Title 2-1 2-5 2-13 3-21 3-39 4-28 5-6 5-17 --B-8 PAGE (V1) Title 2-1 2-5 2-13 3-21 3-38 4-28 5-7 5-18 5-100 B-8 C-3 CHANGE Update Update Update Update Update Update Update Update Update Add Update Update DESCRIPTION Manual part number to 1601-0088-V1 Updated ORDERING section Updated REPLACEMENT MODULES section Updated ENVIRONMENTAL specifications section Updated CPU COMMUNICATION PORTS section Updated MANAGED ETHERNET SWITCH MODULE HARDWARE section Updated INVALID PASSWORD ENTRY section Updated ACCESS SUPERVISION section Updated IEC 61850 PROTOCOL section Added PID REGULATOR section Updated MODBUS MEMORY MAP section Updated PROTECTION AND OTHER LOGICAL NODES section

C-3

Table F3: MAJOR UPDATES FOR C30 MANUAL REVISION U2


PAGE (U1) Title 1-1 2-8 2-13 2-14 2-14 4-14 5-17 5-65 C-7 PAGE (U2) Title 1-1 2-8 2-13 2-14 2-15 4-14 5-17 5-65 C-7 CHANGE Update Update Update Update Update Update Update Update Update Update DESCRIPTION Manual part number to 1601-0088-U2 Updated INSPECTION CHECKLIST section Updated USER-PROGRAMMABLE ELEMENTS specifications section Updated ENVIRONMENTAL specifications section Updated TYPE TESTS specifications section Updated APPROVALS specifications section Updated LED INDICATORS section Updated IEC 61850 PROTOCOL section Updated DISCONNECT SWITCHES section Updated CONFIGURABLE GOOSE section

Table F4: MAJOR UPDATES FOR C30 MANUAL REVISION U1 (Sheet 1 of 2)


PAGE (T1) Title PAGE (U1) Title CHANGE Update DESCRIPTION Manual part number to 1601-0088-U1

F-2

C30 Controller System

GE Multilin

APPENDIX F Table F4: MAJOR UPDATES FOR C30 MANUAL REVISION U1 (Sheet 2 of 2)
PAGE (T1) 2-9 2-13 2-14 3-2 3-12 4-1 5-4 5-17 5-60 5-64 5-69 5-90 5-100 ------7-2 7-5 ----B-8 B-46 PAGE (U1) 2-2 2-13 2-14 3-2 3-12 4-1 5-4 5-17 5-61 5-65 5-70 5-91 5-101 5-114 5-115 6-8 7-3 7-6 8-1 A-3 B-8 B-47 CHANGE Update Update Update Update Update Update Update Update Update Update Update Update Update Add Add Add Update Update Add Add Update Update DESCRIPTION Updated INPUTS specifications section Updated ENVIRONMENTAL specifications section Updated TYPE TESTS specifications section Updated VERTICAL UNITS sub-section Updated CONTACT INPUTS AND OUTPUTS section Updated USING SETTINGS FILES section Updated SECURITY section Updated IEC 61850 PROTOCOL sub-section Updated BREAKERS section Updated DISCONNECT SWITCHES section Updated FLEXLOGIC OPERANDS table Updated DIGITAL ELEMENTS section Updated CONTACT OUTPUTS section Added IEC 61850 GOOSE ANALOGS section Added IEC 61850 GOOSE INTEGERS section Added IEC 61850 GOOSE INTEGERS section Updated RELAY MAINTENANCE section Updated MINOR SELF-TEST ERRORS section Added SECURITY chapter Added FLEXINTEGER ITEMS section Updated MODBUS MEMORY MAP section Updated DATA FORMATS section

F.1 CHANGE NOTES

Table F5: MAJOR UPDATES FOR C30 MANUAL REVISION T1


PAGE (S3) Title 2-1 ------5-15 ------5-58 --5-107 --B-8 PAGE (T1) Title 2-1 3-12 4-22 5-7 5-17 5-59 5-60 5-64 5-69 5-105 5-119 6-4 B-8 CHANGE Update Update Add Add Add Update Add Add Add Update Add Update Add Update DESCRIPTION Manual part number to 1601-0088-T1 Updated ORDERING section Added PROCESS BUS MODULES section Added BREAKER CONTROL section Added DUAL PERMISSION SECURITY ACCESS section Updated IEC 61850 PROTOCOL section Added REMOTE RESOURCES Added BREAKERS section Added DISCONNECT SWITCHES section Updated FLEXLOGIC OPERANDS table Added REMOTE DOUBLE-POINT STATUS INPUTS section Updated TEST MODE section Added REMOTE DOUBLE-POINT STATUS INPUTS section Updated MODBUS MEMORY MAP section

GE Multilin

C30 Controller System

F-3

F.1 CHANGE NOTES

APPENDIX F

Table F6: MAJOR UPDATES FOR C30 MANUAL REVISION S3


PAGE (S2) Title 2-9 2-10 3-7 --7-4 B-8 PAGE (S3) Title 2-9 2-11 3-7 3-45 7-5 B-8 CHANGE Update Update Update Update Add Update Update DESCRIPTION Manual part number to 1601-0088-S3 Updated COMMUNICATIONS specifications section Updated INTER-RELAY COMMUNICATIONS specifications section Updated REAR TERMINAL LAYOUT section Added ETHERNET SWITCH SELF-TEST ERRORS section Updated MINOR SELF-TEST ERROR MESSAGES section Update MODBUS MEMORY MAP section

Table F7: MAJOR UPDATES FOR C30 MANUAL REVISION S2


PAGE (S1) Title 3-37 3-37 ----PAGE (S2) Title 3-38 3-38 3-41 3-41 CHANGE Update Update Update Add Add DESCRIPTION Manual part number to 1601-0088-S2 Updated MANAGED ETHERNET SWITCH OVERVIEW section Updated MANAGED ETHERNET SWITCH MODULE HARDWARE section Added UPLOADING C30 SWITCH MODULE FIRMWARE sub-section Added SELECTING THE PROPER SWITCH FIRMWARE VERSION sub-section

Table F8: MAJOR UPDATES FOR C30 MANUAL REVISION S1


PAGE (R3) PAGE (S1) Title 2-1 2-3 2-8 2-9 3-33 3-37 5-4 5-27 5-38 5-58 6-9 B-8 CHANGE Update Update Update Update Update Update Add Update Add Update Update Add Update DESCRIPTION Manual part number to 1601-0088-S1 Updated ORDER CODES section Updated REPLACEMENT MODULES section Updated OUTPUTS specifications section Updated COMMUNICATIONS specifications section Updated IEEE C37.94 INTERFACE section Added MANAGED ETHERNET SWITCH MODULES section Updated PASSWORD SECURITY section (now titled SECURITY) Added ETHERNET SWITCH sub-section Updated USER-PROGRAMMABLE PUSHBUTTONS section Updated FLEXLOGIC OPERANDS table Added ETHERNET SWITCH section Update MODBUS MEMORY MAP section for revision 5.5x

Title 2-1 2-3 2-8 2-9 3-33 --5-4 --5-36 5-54 --B-8

Table F9: MAJOR UPDATES FOR C30 MANUAL REVISION R3


PAGE (R2) Title --6-13 PAGE (R3) Title 4-4 6-13 CHANGE Update Add Update DESCRIPTION Manual part number to 1601-0088-R3 Added EXTENDED ENERVISTA UR SETUP FEATURES section Updated MODEL INFORMATION section

F-4

C30 Controller System

GE Multilin

APPENDIX F

F.1 CHANGE NOTES

Table F10: MAJOR UPDATES FOR C30 MANUAL REVISION R2


PAGE (R1) Title PAGE (R2) Title CHANGE Update DESCRIPTION Manual part number to 1601-0088-R2

Table F11: MAJOR UPDATES FOR C30 MANUAL REVISION R1


PAGE (P2) Title 2-1 3-1 3-4 4-4 4-5 4-6 4-12 5-4 5-28 5-32 5-33 5-39 7-3 B-7 B-8 --C-7 PAGE (R1) Title 2-1 3-1 3-5 4-4 4-5 4-8 4-20 5-4 5-29 5-33 5-34 5-41 7-3 B-7 B-8 C-2 C-7 CHANGE Update Update Update Update Update Update Update Update Update Update Update Update Update Update Update Update Add Update DESCRIPTION Manual part number to 1601-0088-R1 Updated ORDERING section Updated PANEL CUTOUT section Updated MODULE WITHDRAWAL AND INSERTION section Updated FACEPLATE section Updated LED INDICATORS section Updated CUSTOM LABELING OF LEDS section Updated ENTERING INITIAL PASSWORDS section Updated PASSWORD SECURITY section Updated USER-PROGRAMMABLE LEDS section Updated CONTROL PUSHBUTTONS section Updated USER-PROGRAMMABLE PUSHBUTTONS section Updated DIRECT INPUTS AND OUTPUTS section Updated RELAY SELF-TESTS section Updated MODBUS PASSWORD OPERATION section Updated MODBUS MEMORY MAP section Added GGIO4: GENERIC ANALOG MEASURED VALUES section Updated CONFIGURABLE GOOSE section

Table F12: MAJOR UPDATES FOR C30 MANUAL REVISION P2


PAGE (P1) Title 2-1 3-19 --A-1 PAGE (P2) Title 2-1 3-19 6-9 A-1 CHANGE Update Update Update Add Update DESCRIPTION Manual part number to 1601-0088-P2 Updated ORDERING section Updated CPU MODULE COMMUNICATIONS WIRING diagram to 842765A2 Added IEC 61850 GOOSE ANALOG VALUES section Updated FLEXANALOG PARAMETERS table

GE Multilin

C30 Controller System

F-5

F.2 ABBREVIATIONS F.2ABBREVIATIONS


A..................... Ampere AC .................. Alternating Current A/D ................. Analog to Digital AE .................. Accidental Energization, Application Entity AMP ............... Ampere ANG ............... Angle ANSI............... American National Standards Institute AR .................. Automatic Reclosure ASDU ............. Application-layer Service Data Unit ASYM ............. Asymmetry AUTO ............. Automatic AUX................ Auxiliary AVG ................ Average BER................ Bit Error Rate BF................... Breaker Fail BFI.................. Breaker Failure Initiate BKR................ Breaker BLK ................ Block BLKG.............. Blocking BPNT.............. Breakpoint of a characteristic BRKR ............. Breaker CAP................ Capacitor CC .................. Coupling Capacitor CCVT ............. Coupling Capacitor Voltage Transformer CFG................ Configure / Configurable .CFG............... Filename extension for oscillography files CHK................ Check CHNL ............. Channel CLS ................ Close CLSD.............. Closed CMND ............ Command CMPRSN........ Comparison CO.................. Contact Output COM............... Communication COMM............ Communications COMP ............ Compensated, Comparison CONN............. Connection CONT ............. Continuous, Contact CO-ORD......... Coordination CPU................ Central Processing Unit CRC ............... Cyclic Redundancy Code CRT, CRNT .... Current CSA................ Canadian Standards Association CT .................. Current Transformer CVT ................ Capacitive Voltage Transformer D/A ................. Digital to Analog DC (dc)........... Direct Current DD .................. Disturbance Detector DFLT .............. Default DGNST........... Diagnostics DI.................... Digital Input DIFF ............... Differential DIR ................. Directional DISCREP ....... Discrepancy DIST ............... Distance DMD ............... Demand DNP................ Distributed Network Protocol DPO ............... Dropout DSP................ Digital Signal Processor dt .................... Rate of Change DTT ................ Direct Transfer Trip DUTT.............. Direct Under-reaching Transfer Trip ENCRMNT ..... Encroachment EPRI............... Electric Power Research Institute .EVT ............... Filename extension for event recorder files EXT ................ Extension, External F ..................... Field FAIL................ Failure FD .................. Fault Detector FDH................ Fault Detector high-set FDL ................ Fault Detector low-set FLA................. Full Load Current FO .................. Fiber Optic

APPENDIX F F.2.1 STANDARD ABBREVIATIONS


FREQ ............. Frequency FSK................ Frequency-Shift Keying FTP ................ File Transfer Protocol FxE ................ FlexElement FWD............... Forward G .................... Generator GE.................. General Electric GND............... Ground GNTR............. Generator GOOSE.......... General Object Oriented Substation Event GPS ............... Global Positioning System HARM ............ Harmonic / Harmonics HCT ............... High Current Time HGF ............... High-Impedance Ground Fault (CT) HIZ ................. High-Impedance and Arcing Ground HMI ................ Human-Machine Interface HTTP ............. Hyper Text Transfer Protocol HYB ............... Hybrid I...................... Instantaneous I_0.................. Zero Sequence current I_1.................. Positive Sequence current I_2.................. Negative Sequence current IA ................... Phase A current IAB ................. Phase A minus B current IB ................... Phase B current IBC................. Phase B minus C current IC ................... Phase C current ICA................. Phase C minus A current ID ................... Identification IED................. Intelligent Electronic Device IEC................. International Electrotechnical Commission IEEE............... Institute of Electrical and Electronic Engineers IG ................... Ground (not residual) current Igd.................. Differential Ground current IN ................... CT Residual Current (3Io) or Input INC SEQ ........ Incomplete Sequence INIT ................ Initiate INST............... Instantaneous INV................. Inverse I/O .................. Input/Output IOC ................ Instantaneous Overcurrent IOV................. Instantaneous Overvoltage IRIG ............... Inter-Range Instrumentation Group ISO................. International Standards Organization IUV................. Instantaneous Undervoltage K0 .................. Zero Sequence Current Compensation kA................... kiloAmpere kV................... kiloVolt LED................ Light Emitting Diode LEO................ Line End Open LFT BLD ........ Left Blinder LOOP............. Loopback LPU................ Line Pickup LRA................ Locked-Rotor Current LTC ................ Load Tap-Changer M.................... Machine mA ................. MilliAmpere MAG............... Magnitude MAN............... Manual / Manually MAX ............... Maximum MIC ................ Model Implementation Conformance MIN ................ Minimum, Minutes MMI................ Man Machine Interface MMS .............. Manufacturing Message Specification MRT ............... Minimum Response Time MSG............... Message MTA................ Maximum Torque Angle MTR ............... Motor MVA ............... MegaVolt-Ampere (total 3-phase) MVA_A ........... MegaVolt-Ampere (phase A) MVA_B ........... MegaVolt-Ampere (phase B) MVA_C........... MegaVolt-Ampere (phase C)

F-6

C30 Controller System

GE Multilin

APPENDIX F
MVAR ............. MegaVar (total 3-phase) MVAR_A......... MegaVar (phase A) MVAR_B......... MegaVar (phase B) MVAR_C ........ MegaVar (phase C) MVARH .......... MegaVar-Hour MW................. MegaWatt (total 3-phase) MW_A ............ MegaWatt (phase A) MW_B ............ MegaWatt (phase B) MW_C ............ MegaWatt (phase C) MWH .............. MegaWatt-Hour N..................... Neutral N/A, n/a .......... Not Applicable NEG ............... Negative NMPLT ........... Nameplate NOM............... Nominal NSAP ............. Network Service Access Protocol NTR................ Neutral O .................... Over OC, O/C ......... Overcurrent O/P, Op........... Output OP .................. Operate OPER ............. Operate OPERATG...... Operating O/S ................. Operating System OSI ................. Open Systems Interconnect OSB................ Out-of-Step Blocking OUT................ Output OV .................. Overvoltage OVERFREQ ... Overfrequency OVLD ............. Overload P..................... Phase PC .................. Phase Comparison, Personal Computer PCNT ............. Percent PF................... Power Factor (total 3-phase) PF_A .............. Power Factor (phase A) PF_B .............. Power Factor (phase B) PF_C .............. Power Factor (phase C) PFLL............... Phase and Frequency Lock Loop PHS................ Phase PICS............... Protocol Implementation & Conformance Statement PKP ................ Pickup PLC ................ Power Line Carrier POS................ Positive POTT.............. Permissive Over-reaching Transfer Trip PRESS ........... Pressure PRI ................. Primary PROT ............. Protection PSEL .............. Presentation Selector pu ................... Per Unit PUIB............... Pickup Current Block PUIT ............... Pickup Current Trip PUSHBTN ...... Pushbutton PUTT.............. Permissive Under-reaching Transfer Trip PWM .............. Pulse Width Modulated PWR............... Power QUAD............. Quadrilateral R..................... Rate, Reverse RCA................ Reach Characteristic Angle REF ................ Reference REM ............... Remote REV................ Reverse RI.................... Reclose Initiate RIP ................. Reclose In Progress RGT BLD........ Right Blinder ROD ............... Remote Open Detector RST ................ Reset RSTR ............. Restrained RTD................ Resistance Temperature Detector RTU................ Remote Terminal Unit RX (Rx) .......... Receive, Receiver s ..................... second S..................... Sensitive

F.2 ABBREVIATIONS
SAT .................CT Saturation SBO ................Select Before Operate SCADA ...........Supervisory Control and Data Acquisition SEC ................Secondary SEL .................Select / Selector / Selection SENS ..............Sensitive SEQ ................Sequence SIR..................Source Impedance Ratio SNTP ..............Simple Network Time Protocol SRC ................Source SSB.................Single Side Band SSEL...............Session Selector STATS.............Statistics SUPN..............Supervision SUPV ..............Supervise / Supervision SV ...................Supervision, Service SYNC..............Synchrocheck SYNCHCHK....Synchrocheck T......................Time, transformer TC ...................Thermal Capacity TCP.................Transmission Control Protocol TCU ................Thermal Capacity Used TD MULT ........Time Dial Multiplier TEMP..............Temperature TFTP...............Trivial File Transfer Protocol THD ................Total Harmonic Distortion TMR ................Timer TOC ................Time Overcurrent TOV ................Time Overvoltage TRANS............Transient TRANSF .........Transfer TSEL...............Transport Selector TUC ................Time Undercurrent TUV.................Time Undervoltage TX (Tx)............Transmit, Transmitter U .....................Under UC...................Undercurrent UCA ................Utility Communications Architecture UDP ................User Datagram Protocol UL ...................Underwriters Laboratories UNBAL............Unbalance UR...................Universal Relay URC ................Universal Recloser Control .URS ...............Filename extension for settings files UV...................Undervoltage V/Hz ................Volts per Hertz V_0 .................Zero Sequence voltage V_1 .................Positive Sequence voltage V_2 .................Negative Sequence voltage VA ...................Phase A voltage VAB.................Phase A to B voltage VAG ................Phase A to Ground voltage VARH ..............Var-hour voltage VB ...................Phase B voltage VBA.................Phase B to A voltage VBG ................Phase B to Ground voltage VC...................Phase C voltage VCA ................Phase C to A voltage VCG ................Phase C to Ground voltage VF ...................Variable Frequency VIBR ...............Vibration VT ...................Voltage Transformer VTFF...............Voltage Transformer Fuse Failure VTLOS ............Voltage Transformer Loss Of Signal WDG ...............Winding WH..................Watt-hour w/ opt ..............With Option WRT................With Respect To X .....................Reactance XDUCER.........Transducer XFMR..............Transformer Z......................Impedance, Zone

GE Multilin

C30 Controller System

F-7

F.3 WARRANTY F.3WARRANTY

APPENDIX F F.3.1 GE MULTILIN WARRANTY

GE MULTILIN RELAY WARRANTY


General Electric Multilin Inc. (GE Multilin) warrants each relay it manufactures to be free from defects in material and workmanship under normal use and service for a period of 24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory. Repairs or replacement under warranty will be made without charge. Warranty shall not apply to any relay which has been subject to misuse, negligence, accident, incorrect installation or use not in accordance with instructions nor any unit that has been altered outside a GE Multilin authorized factory outlet.

GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for expenses sustained as a result of a relay malfunction, incorrect application or adjustment. For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard Conditions of Sale.

F-8

C30 Controller System

GE Multilin

INDEX
Index

Numerics
10BASE-F communications options ................................................. 3-21 description .................................................................... 3-23 interface ........................................................................ 3-33 redundant option ........................................................... 3-21 settings ......................................................................... 5-12 8-BIT SWITCH FlexLogic operands .................................................... 5-71 Modbus registers ........................................................... B-22 settings ......................................................................... 5-98 specifications .................................................................. 2-8

A
ABBREVIATIONS ............................................................... F-6 ACTIVATING THE RELAY ........................................1-17, 4-27 ACTUAL VALUES product information ........................................................ 6-14 ALARM LEDs ................................................................... 5-40 APPLICATION EXAMPLES breaker trip circuit integrity ............................................ 5-95 contact inputs .............................................................. 5-104 APPROVALS ................................................................... 2-15 ARCHITECTURE ............................................................. 5-69

B
BATTERY FAILURE ........................................................... 7-6 BINARY INPUT POINTS ..................................................... E-8 BINARY OUTPUT POINTS ................................................. E-9 BLOCK DIAGRAM .............................................................. 1-3 BLOCK SETTING ............................................................... 5-4 BREAKER CONTROL control of 2 breakers ...................................................... 4-24 description .................................................................... 4-23 dual breaker logic ..................................................5-64, 5-65 FlexLogic operands .................................................... 5-71 Modbus registers ........................................................... B-17 settings ......................................................................... 5-62 BRIGHTNESS .................................................................... 5-9

C
C37.94 COMMUNICATIONS ............................ 3-34, 3-35, 3-37 C37.94SM COMMUNICATIONS ........................................ 3-36 CE APPROVALS .............................................................. 2-15 CHANGES TO C30 MANUAL .............................................. F-2 CHANGES TO MANUAL .............................................. F-4, F-5 CHANNEL COMMUNICATION .......................................... 3-27 CHANNEL TESTS .............................................................. 6-9 CIRCUIT MONITORING APPLICATIONS .......................... 5-93 CLEANING ...................................................................... 2-15 CLEAR RECORDS .................................................... 5-10, 7-2 CLEAR RELAY RECORDS Modbus registers ........................................................... B-39 settings ......................................................................... 5-10 CLOCK setting date and time ....................................................... 7-2 settings ......................................................................... 5-34 COMMANDS MENU ........................................................... 7-1

COMMUNICATIONS 10BASE-F ................................................... 3-21, 3-23, 5-12 channel ......................................................................... 3-27 connecting to the UR ............................................... 1-8, 1-15 CRC-16 error checking .................................................... B-2 dnp .........................................................................5-13, E-1 EGD .............................................................................. 5-31 G.703 ............................................................................ 3-29 half duplex ...................................................................... B-1 HTTP ............................................................................. 5-29 IEC 60870-5-104 protocol............................................... 5-30 IEC 61850 ................................................................... 5-109 inter-relay communications ............................................. 2-13 Modbus .................................................. 5-13, 5-33, B-1, B-3 Modbus registers .......................................................... B-14 network ......................................................................... 5-12 overview ........................................................................ 1-16 RS232 ........................................................................... 3-21 RS485 ......................................................... 3-21, 3-23, 5-12 settings ............................. 5-12, 5-13, 5-19, 5-30, 5-31, 5-33 specifications ........................................................ 2-12, 2-13 UCA/MMS .................................................................... 5-111 web server ..................................................................... 5-29 COMTRADE ............................................................... B-6, B-7 CONDUCTED RFI ............................................................ 2-14 CONTACT INFORMATION .................................................. 1-1 CONTACT INPUTS actual values ................................................................... 6-3 dry connections ............................................................. 3-18 FlexLogic operands ..................................................... 5-73 Modbus registers ............................... B-10, B-11, B-33, B-34 settings ....................................................................... 5-103 specifications ................................................................... 2-9 thresholds ................................................................... 5-103 wet connections ............................................................. 3-18 CONTACT OUTPUTS actual values ................................................................... 6-4 FlexLogic operands ..................................................... 5-73 Modbus registers ........................................ B-10, B-11, B-38 settings ....................................................................... 5-106 CONTROL ELEMENTS ..................................................... 5-87 CONTROL POWER description ..................................................................... 3-12 specifications ................................................................. 2-11 CONTROL PUSHBUTTONS FlexLogic operands ..................................................... 5-71 Modbus registers .......................................................... B-39 settings ......................................................................... 5-42 specifications ................................................................... 2-8 COUNTERS actual values ................................................................... 6-6 settings ......................................................................... 5-96 CRC ALARM .................................................................... 5-57 CRC-16 ALGORITHM ........................................................ B-2 CRITICAL FAILURE RELAY ..................................... 2-10, 3-11 CSA APPROVAL .............................................................. 2-15

D
DATA FORMATS, MODBUS ............................................. B-47 DATA LOGGER clearing .................................................................. 5-10, 7-2 Modbus .......................................................................... B-7 Modbus registers ................................................. B-10, B-15 settings ......................................................................... 5-37

GE Multilin

C30 Controller System

INDEX
specifications ................................................................... 2-9 via COMTRADE .............................................................. B-6 DATE ................................................................................. 7-2 DCMA INPUTS ................................................................. 6-10 Modbus registers ..................................................B-12, B-20 settings ....................................................................... 5-121 specifications ................................................................... 2-9 DCMA OUTPUTS description..................................................................... 3-20 Modbus registers ...........................................................B-25 settings ....................................................................... 5-124 specifications ................................................................. 2-11 DESIGN ............................................................................. 1-3 DEVICE ID ..................................................................... 5-109 DEVICE PROFILE DOCUMENT ......................................... E-1 DIELECTRIC STRENGTH ................................................. 3-11 DIGITAL COUNTERS actual values ................................................................... 6-6 FlexLogic operands .................................................... 5-71 logic .............................................................................. 5-97 Modbus registers ................................................... B-9, B-28 settings ......................................................................... 5-96 DIGITAL ELEMENTS application example ....................................................... 5-94 FlexLogic operands .................................................... 5-72 logic .............................................................................. 5-93 Modbus registers ...........................................................B-23 settings ......................................................................... 5-93 DIGITAL OUTPUTS see entry for CONTACT OUTPUTS DIMENSIONS .............................................................. 3-1, 3-2 DIRECT DEVICES actual values ................................................................... 6-7 Modbus registers ...........................................................B-13 settings ....................................................................... 5-113 DIRECT I/O see also DIRECT INPUTS and DIRECT OUTPUTS application example ...........................................5-114, 5-115 configuration examples ........................ 5-51, 5-54, 5-57, 5-58 settings ............................................. 5-51, 5-57, 5-58, 5-113 DIRECT INPUTS actual values ................................................................... 6-7 application example ...........................................5-114, 5-115 clearing counters ............................................................. 7-2 FlexLogic operands .................................................... 5-73 Modbus registers ............. B-10, B-13, B-25, B-39, B-40, B-41 settings ....................................................................... 5-113 specifications ................................................................... 2-9 DIRECT INPUTS/OUTPUTS error messages ................................................................ 7-6 DIRECT OUTPUTS application example ...........................................5-114, 5-115 clearing counters ............................................................. 7-2 Modbus registers ...................... B-10, B-25, B-39, B-40, B-41 settings ....................................................................... 5-113 DISCONNECT SWITCH FlexLogic operands .................................................... 5-72 logic .............................................................................. 5-68 Modbus registers ...........................................................B-21 settings ......................................................................... 5-66 DISPLAY ......................................................... 1-16, 4-23, 5-9 DNA-1 BIT PAIR ............................................................. 5-111 DNP COMMUNICATIONS binary counters ..............................................................E-10 binary input points .......................................................... E-8 binary output points ........................................................ E-9 control relay output blocks .............................................. E-9 device profile document .................................................. E-1 frozen counters ............................................................. E-10 implementation table ....................................................... E-4 Modbus registers ........................................................... B-14 settings ..........................................................................5-13 DUPLEX, HALF ................................................................. B-1 DYNAMIC SWITCH see entry for 8-BIT SWITCH

E
EGD PROTOCOL actual values ................................................................... 6-8 Modbus registers ........................................................... B-22 settings ..........................................................................5-31 EIGHT-BIT SWITCH FlexLogic operands .....................................................5-71 Modbus registers ........................................................... B-22 settings ..........................................................................5-98 specifications .................................................................. 2-8 ELECTROSTATIC DISCHARGE ........................................2-14 ENERVISTA UR SETUP creating a site list ............................................................ 4-1 event recorder ................................................................. 4-2 firmware upgrades ........................................................... 4-2 installation ...................................................................... 1-5 introduction ..................................................................... 4-1 oscillography ................................................................... 4-2 overview ......................................................................... 4-1 requirements ................................................................... 1-5 EQUIPMENT MISMATCH ERROR ...................................... 7-5 ETHERNET actual values ................................................................... 6-6 configuration ................................................................... 1-8 error messages ............................................................... 7-7 Modbus registers ........................................................... B-10 quick connect .................................................................1-10 settings ..........................................................................5-12 ETHERNET SWITCH actual values ................................................................... 6-9 configuration ......................................................... 3-39, 3-40 hardware .......................................................................3-38 Modbus registers ........................................................... B-15 overview ........................................................................3-38 saving setting files .........................................................3-40 settings ..........................................................................5-33 uploading setting files .....................................................3-41 EVENT CAUSE INDICATORS .................................. 4-15, 4-16 EVENT RECORDER actual values ..................................................................6-12 clearing ...................................................................5-10, 7-2 Modbus ........................................................................... B-7 Modbus registers ........................................................... B-12 specifications .................................................................. 2-9 via EnerVista software ..................................................... 4-2 EVENTS SETTING ............................................................ 5-4 EXCEPTION RESPONSES ................................................. B-5

F
F485 ................................................................................1-16 FACEPLATE ............................................................... 3-1, 3-2 FACEPLATE PANELS .............................................. 4-13, 4-23 FAST FORM-C RELAY ......................................................2-10 FAST TRANSIENT TESTING .............................................2-14 FAX NUMBERS ................................................................. 1-1

ii

C30 Controller System

GE Multilin

INDEX
FEATURES ........................................................................ 2-1 FIRMWARE REVISION .................................................... 6-14 FIRMWARE UPGRADES .................................................... 4-2 FLASH MESSAGES ........................................................... 5-9 FLEX STATE PARAMETERS actual values ................................................................... 6-6 Modbus registers .................................................. B-11, B-23 settings ......................................................................... 5-48 specifications .................................................................. 2-8 FLEXCURVES specifications .................................................................. 2-8 FLEXELEMENTS actual values ................................................................. 6-10 direction ........................................................................ 5-84 FlexLogic operands .................................................... 5-72 hysteresis ..................................................................... 5-84 Modbus registers .................................................. B-24, B-26 pickup ........................................................................... 5-84 scheme logic ................................................................. 5-83 settings ........................................................ 5-82, 5-83, 5-85 specifications .................................................................. 2-8 FLEXLOGIC locking to a serial number ....................................... 4-9, 8-11 FLEXLOGIC editing with EnerVista UR Setup....................................... 4-2 equation editor .............................................................. 5-81 error messages ............................................................... 7-5 evaluation ..................................................................... 5-76 example ................................................................5-69, 5-76 gate characteristics ....................................................... 5-75 locking equation entries .......................................... 4-8, 8-10 Modbus registers ........................................................... B-19 operands ...............................................................5-70, 5-71 operators ...................................................................... 5-75 rules ............................................................................. 5-75 security .................................................................. 4-8, 8-10 specifications .................................................................. 2-8 timers ........................................................................... 5-81 worksheet ..................................................................... 5-77 FLEXLOGIC EQUATION EDITOR .................................. 5-81 FLEXLOGIC TIMERS Modbus registers ........................................................... B-20 settings ......................................................................... 5-81 FORCE CONTACT INPUTS ............................................ 5-127 FORCE CONTACT OUTPUTS ........................................ 5-128 FORCE TRIGGER ............................................................ 6-12 FORM-A RELAY high impedance circuits ................................................. 3-13 outputs ......................................................... 3-12, 3-13, 3-18 specifications ................................................................ 2-10 FORM-C RELAY outputs ..................................................................3-12, 3-18 specifications ................................................................ 2-10 FUNCTION SETTING ......................................................... 5-4 FUSE .............................................................................. 2-10

I
IEC 60870-5-104 PROTOCOL interoperability document ................................................ D-1 Modbus registers .......................................................... B-15 settings ......................................................................... 5-30 IEC 61850 GOOSE ANALOGS settings ....................................................................... 5-119 IEC 61850 GOOSE UINTEGERS settings ....................................................................... 5-120 IEC 61850 PROTOCOL device ID ..................................................................... 5-110 DNA2 assignments ....................................................... 5-112 error messages ................................................................ 7-7 Modbus registers ............. B-28, B-29, B-30, B-31, B-32, B-44 remote device settings ................................................. 5-109 remote inputs ............................................................... 5-110 settings ......................................................................... 5-18 UserSt-1 bit pair .......................................................... 5-112 IED .................................................................................... 1-2 IED SETUP ........................................................................ 1-5 IEEE C37.94 COMMUNICATIONS ................... 3-34, 3-35, 3-37 IMPORTANT CONCEPTS ...................................................1-4 IN SERVICE INDICATOR ........................................... 1-17, 7-4 INCOMPATIBLE HARDWARE ERROR ................................ 7-5 INPUTS contact inputs .............................................2-9, 5-103, 5-127 dcmA inputs ............................................................ 2-9, 3-20 direct inputs ..................................................................... 2-9 IRIG-B .................................................................... 2-9, 3-24 remote inputs ................................... 2-9, 5-109, 5-110, 5-111 RTD inputs ............................................................. 2-9, 3-20 virtual .......................................................................... 5-105 INSPECTION CHECKLIST .................................................. 1-1 INSTALLATION communications ............................................................. 3-22 RS485 ........................................................................... 3-23 settings ......................................................................... 5-59 INTELLIGENT ELECTRONIC DEVICE ................................. 1-2 INTER-RELAY COMMUNICATIONS .................................. 2-13 INTRODUCTION ................................................................ 1-2 IP ADDRESS .................................................................... 5-12 IRIG-B connection ..................................................................... 3-24 error messages ................................................................ 7-6 settings ......................................................................... 5-34 specifications .......................................................... 2-9, 2-11 ISO-9000 REGISTRATION ................................................ 2-15

K
KEYPAD ................................................................. 1-17, 4-23

G
G.703 .................................................... 3-28, 3-29, 3-30, 3-33 GSSE ................................................ 5-110, 5-111, 5-112, 6-5

L
LAMPTEST ........................................................................ 7-3 LANGUAGE ....................................................................... 5-9 LASER MODULE .............................................................. 3-27 LATCHING OUTPUTS application example .......................................... 5-107, 5-108 error messages ................................................................ 7-7 settings ....................................................................... 5-106 specifications ................................................................. 2-10 LED INDICATORS ................ 4-14, 4-15, 4-16, 4-17, 4-22, 5-40

H
HALF-DUPLEX .................................................................. B-1 HTTP PROTOCOL ........................................................... 5-29

GE Multilin

C30 Controller System

iii

INDEX
LED TEST FlexLogic operand ...................................................... 5-73 settings ......................................................................... 5-38 specifications ................................................................... 2-8 LINK POWER BUDGET .................................................... 2-13 LOGIC GATES ................................................................. 5-75 LOST PASSWORD ........................................ 5-6, 5-7, 8-2, 8-3 ORDER CODES, UPDATING ............................................. 7-3 ORDERING ............................................ 2-1, 2-2, 2-3, 2-4, 2-5 OSCILLATORY TRANSIENT TESTING ..............................2-14 OSCILLOGRAPHY actual values ..................................................................6-12 clearing ...................................................................5-10, 7-2 Modbus ........................................................................... B-6 Modbus registers .................................................. B-11, B-16 settings ..........................................................................5-35 specifications .................................................................. 2-9 via COMTRADE .............................................................. B-6 via EnerVista software ..................................................... 4-2 OSI NETWORK ADDRESS ................................................5-12 OUTPUTS contact outputs ............................................................ 5-106 control power .................................................................2-11 critical failure relay .........................................................2-10 Fast Form-C relay ..........................................................2-10 Form-A relay ....................................... 2-10, 3-12, 3-13, 3-18 Form-C relay ................................................ 2-10, 3-12, 3-18 IRIG-B ...........................................................................2-11 latching outputs ................................................... 2-10, 5-106 remote outputs .................................................. 5-111, 5-112 virtual outputs .............................................................. 5-108

M
MAINTENANCE COMMANDS ............................................. 7-3 MANUFACTURING DATE ................................................. 6-14 MEMORY MAP DATA FORMATS ......................................B-47 MENU HEIRARCHY ................................................ 1-17, 4-25 MENU NAVIGATION .......................................1-17, 4-24, 4-25 MODBUS data logger .............................................................. B-6, B-7 event recorder ................................................................ B-7 exception responses ....................................................... B-5 execute operation ........................................................... B-4 flex state parameters ..................................................... 5-49 function code 03/04h ....................................................... B-3 function code 05h ........................................................... B-4 function code 06h ........................................................... B-4 function code 10h ........................................................... B-5 introduction .................................................................... B-1 memory map data formats ..............................................B-47 obtaining files ................................................................. B-6 oscillography .................................................................. B-6 passwords ...................................................................... B-7 read/write settings/actual values ...................................... B-3 settings ................................................................ 5-13, 5-33 store multiple settings ..................................................... B-5 store single setting ......................................................... B-4 supported function codes ................................................ B-3 user map ..................................................... 5-33, B-10, B-18 MODEL INFORMATION .................................................... 6-14 MODIFICATION FILE NUMBER ........................................ 6-14 MODULE FAILURE ERROR ................................................ 7-5 MODULES communications ............................................................. 3-22 direct inputs/outputs ...................................................... 3-27 insertion ................................................................... 3-6, 3-7 order codes ..................................................................... 2-5 power supply ................................................................. 3-11 transducer I/O ............................................................... 3-20 withdrawal ................................................................ 3-6, 3-7 MOUNTING ................................................................. 3-1, 3-2

P
PANEL CUTOUT ........................................................ 3-1, 3-2 PARITY ............................................................................5-12 PASSWORD SECURITY .......................................5-6, 8-2, 8-3 FlexLogic operands ........................................................5-74 PASSWORDS changing ........................................................................4-28 for settings templates ............................................... 4-5, 8-7 lost password ..................................... 4-28, 5-6, 5-7, 8-2, 8-3 Modbus ........................................................................... B-7 Modbus registers .................................................. B-10, B-13 overview ........................................................................1-18 security .................................................................... 5-5, 8-1 settings .................................................................... 5-5, 8-1 PC SOFTWARE see entry for ENERVISTA UR SETUP PHONE NUMBERS ............................................................ 1-1 PID REGULATOR FlexLogic operands .....................................................5-72 settings ........................................................................ 5-100 POWER SUPPLY description .....................................................................3-11 low range .......................................................................2-10 specifications .................................................................2-10 PREFERENCES Modbus registers ........................................................... B-14 PROCESS BUS overview ........................................................................3-12 PRODUCT INFORMATION ........................................ 6-14, B-8 PRODUCT SETUP ...................................................... 5-5, 8-2 PRODUCTION TESTS ......................................................2-14 PUSHBUTTONS, USER-PROGRAMMABLE see USER-PROGRAMMBLE PUSHBUTTONS

N
NAMEPLATE ...................................................................... 1-1 NON-VOLATILE LATCHES FlexLogic operands .................................................... 5-72 Modbus registers ...........................................................B-27 settings ......................................................................... 5-86 specifications ................................................................... 2-8 NSAP ADDRESS .............................................................. 5-12

O
ONE SHOTS .................................................................... 5-75 OPERATING TEMPERATURE .......................................... 2-13 ORDER CODES ............................. 2-2, 2-3, 2-4, 2-5, 6-14, 7-3

R
REAL TIME CLOCK Modbus registers ........................................................... B-16 settings ..........................................................................5-34

iv

C30 Controller System

GE Multilin

INDEX
REAR TERMINAL ASSIGNMENTS ..................................... 3-8 REDUNDANT 10BASE-F .................................................. 3-21 RELAY ACTIVATION ....................................................... 4-27 RELAY ARCHITECTURE .................................................. 5-69 RELAY MAINTENANCE ..................................................... 7-3 RELAY NAME .................................................................. 5-60 RELAY NOT PROGRAMMED ........................................... 1-17 REMOTE DEVICES actual values ................................................................... 6-5 device ID ..................................................................... 5-110 error messages ............................................................... 7-7 FlexLogic operands .................................................... 5-74 Modbus registers ................................ B-10, B-11, B-41, B-46 settings ....................................................................... 5-109 statistics ......................................................................... 6-5 REMOTE DPS INPUTS actual values ................................................................... 6-4 settings ....................................................................... 5-111 REMOTE INPUTS actual values ................................................................... 6-3 FlexLogic operands .................................................... 5-73 Modbus registers ......................................... B-10, B-11, B-42 settings ....................................................................... 5-110 specifications .................................................................. 2-9 REMOTE OUTPUTS DNA-1 bit pair ............................................................. 5-111 Modbus registers .................................................. B-43, B-44 UserSt-1 bit pair .......................................................... 5-112 REPLACEMENT MODULES ................................. 2-5, 2-6, 2-7 RESETTING .......................................................... 5-74, 5-112 REVISION HISTORY .......................................................... F-1 RF IMMUNITY ................................................................. 2-14 RFI, CONDUCTED ........................................................... 2-14 RS232 configuration ................................................................... 1-9 specifications ................................................................ 2-12 wiring ............................................................................ 3-21 RS422 configuration ................................................................. 3-31 timing ............................................................................ 3-32 two-channel application ................................................. 3-31 with fiber interface ......................................................... 3-33 RS485 communications ............................................................ 3-21 configuration ................................................................... 1-7 description .................................................................... 3-23 specifications ................................................................ 2-12 RTD INPUTS actual values ................................................................. 6-10 Modbus registers .................................................. B-12, B-19 settings ....................................................................... 5-122 specifications .................................................................. 2-9 description ....................................................................... 7-4 error messages ................................................................ 7-6 FlexLogic operands ..................................................... 5-74 Modbus registers ............................................................ B-8 SERIAL NUMBER ............................................................. 6-14 SERIAL PORTS Modbus registers .......................................................... B-14 settings ......................................................................... 5-12 SETTINGS TEMPLATES description ................................................................ 4-4, 8-6 editing ...................................................................... 4-4, 8-6 enabling ................................................................... 4-4, 8-6 Modbus registers .......................................................... B-46 password protection .................................................. 4-5, 8-7 removing .................................................................. 4-7, 8-9 viewing ..................................................................... 4-6, 8-8 SETTINGS, CHANGING ................................................... 4-26 SIGNAL TYPES .................................................................. 1-3 SITE LIST, CREATING ....................................................... 4-1 SNTP PROTOCOL error messages ................................................................ 7-7 Modbus registers .......................................................... B-15 settings ......................................................................... 5-31 SOFTWARE installation ....................................................................... 1-5 see entry for ENERVISTA UR SETUP SOFTWARE ARCHITECTURE ............................................ 1-4 SOFTWARE, PC see entry for EnerVista UR Setup SPECIFICATIONS .............................................................. 2-8 ST TYPE CONNECTORS .................................................. 3-23 STANDARD ABBREVIATIONS ............................................F-6 STATUS INDICATORS ............................................ 4-14, 4-16 STORAGE TEMPERATURE .............................................. 2-13 SURGE IMMUNITY ........................................................... 2-14 SYNCHROCHECK actual values .......................................................... 6-8, 6-10

T
TARGET MESSAGES ......................................................... 7-4 TARGET SETTING ............................................................. 5-4 TARGETS MENU ............................................................... 7-4 TCP PORT NUMBER ........................................................ 5-29 TELEPROTECTION actual values ................................................................... 6-4 clearing counters ............................................................. 7-2 FlexLogic operands ............................................ 5-72, 5-73 logic ............................................................................ 5-118 Modbus registers ................................................. B-26, B-27 overview ...................................................................... 5-117 settings .................................................... 5-59, 5-117, 5-118 specifications ................................................................. 2-10 TEMPERATURE MONITOR ....................................... 5-74, 7-8 TERMINALS ....................................................................... 3-8 TESTING force contact inputs ...................................................... 5-127 force contact outputs .................................................... 5-128 lamp test ......................................................................... 7-3 self-test error messages ...................................................7-4 TIME .................................................................................. 7-2 TIMERS ........................................................................... 5-81 TRACEABILITY data ..................................................... 4-11, 4-12, 8-13, 8-14 overview ............................................................... 4-10, 8-12 rules ..................................................................... 4-12, 8-14 TRANSDUCER I/O

S
SALES OFFICE ................................................................. 1-1 SCAN OPERATION ............................................................ 1-4 SELECTOR SWITCH actual values ................................................................... 6-6 application example ....................................................... 5-91 FlexLogic operands .................................................... 5-72 logic .............................................................................. 5-92 Modbus registers ........................................................... B-27 settings ......................................................................... 5-87 specifications .................................................................. 2-8 timing ....................................................................5-90, 5-91 SELF-TESTS

GE Multilin

C30 Controller System

INDEX
actual values ................................................................. 6-10 settings .............................................................5-121, 5-122 specifications ................................................................... 2-9 wiring ............................................................................ 3-20 TRIP BUS FlexLogic operands .................................................... 5-73 Modbus registers ...........................................................B-24 TRIP LEDs ....................................................................... 5-40 TROUBLE INDICATOR .............................................. 1-17, 7-4 specifications .................................................................. 2-8 USER-PROGRAMMABLE PUSHBUTTONS FlexLogic operands .....................................................5-74 Modbus registers .................................................. B-18, B-21 settings ..........................................................................5-43 specifications .................................................................. 2-8 USER-PROGRAMMABLE SELF TESTS Modbus registers ........................................................... B-17 settings ..........................................................................5-41 USERST-1 BIT PAIR ....................................................... 5-112

U
UL APPROVAL ................................................................. 2-15 UNAUTHORIZED ACCESS commands ..................................................................... 5-10 resetting .......................................................................... 7-2 UNEXPECTED RESTART ERROR ...................................... 7-8 UNIT NOT PROGRAMMED ........................................ 5-60, 7-5 UNPACKING THE RELAY ................................................... 1-1 UNRETURNED MESSAGES ALARM ................................. 5-58 UPDATING ORDER CODE ................................................. 7-3 URPC see entry for ENERVISTA UR SETUP USER-DEFINABLE DISPLAYS example ........................................................................ 5-51 invoking and scrolling .................................................... 5-49 Modbus registers ..................................................B-14, B-18 settings ................................................................ 5-49, 5-51 specifications ................................................................... 2-8 USER-PROGRAMMABLE LEDs custom labeling ............................................................. 4-22 defaults ......................................................................... 4-17 description............................................................ 4-15, 4-16 Modbus registers ...........................................................B-16 settings ......................................................................... 5-40

V
VIBRATION TESTING .......................................................2-14 VIRTUAL INPUTS actual values ................................................................... 6-3 commands ...................................................................... 7-1 FlexLogic operands .....................................................5-73 logic ............................................................................ 5-105 Modbus registers .................................................... B-8, B-34 settings ........................................................................ 5-105 VIRTUAL OUTPUTS actual values ................................................................... 6-5 FlexLogic operands .....................................................5-73 Modbus registers ........................................................... B-36 settings ........................................................................ 5-108 VOLTAGE DEVIATIONS ...................................................2-14

W
WARRANTY ...................................................................... F-8 WEB SERVER PROTOCOL ...............................................5-29 WEBSITE .......................................................................... 1-1

vi

C30 Controller System

GE Multilin