Saf ety Clearance Recommendations f or T ransf ormer (on photo 10/0.4 kV transf ormer substation by FIMA)
Clearance Tables
1. Clearance from Outdoor Liquid Insulated Transformers to Buildings (NEC) 2. Clearance between Two Outdoor Liquid Insulated Transformers (NEC) 3. Dry Type Transformer in Indoor Installation (NES 420.21) 4. Dry Type Transformer in Outdoor Installation (NES 420.22) 5. Non Flammable Liquid-Insulated Transformer in Indoor Installation (NES 420.21) 6. Oil Insulated Transformer in Indoor Installation (NES 420.25) 7. Transformer Clearance from Building (IEEE Stand.) 8. Transformer Clearance Specifications (Stand. Georgia Power Company)
Less Flammable
0.9 Meter 7.6 Meter 15.2 Meter 7.6 Meter 15.2 Meter 30.5 Meter
Mineral Oil
7.6 Meter
15.2 Meter
30.5 Meter
Go to Content
> 19 m3
15.2 Meter
Go to Content
Go to Content
Go to Content
carry such gases to an environmentally safe area Above 112.5 KVA Installed in a transformer room of fire-resistant construction. separated from a fire-resistant barrier not less than 1.83 m (6 ft) horizontally and 3.7 m (12 ft) vertically
3.0 Meter
4.2 Meter
3.0 Meter
3.0 Meter
3.0 Meter
6.0 Meter
Fire safety clearances can be reduced by building a suitable masonry fire barrier wall (2.7 Meter wide and 4.5 Meter Tall) 0.9 Meter from the back or side of the Pad Mounted Transformer to the side of the combustible wall Front of the transformer must face away from the building. Go to Content