Setting NU-LEC CAPM4 Recloser Controllers in the Computer-Aided Protection Engineering System (CAPE)

Prepared for CAPE Users' Group

June 20-21, 2000

Electrocon International, Inc. Ann Arbor, Michigan

Georgia Power Company Atlanta, Georgia

This document is the sole property of Electrocon International, Inc. and is provided to the CAPE Users Group for its own use only. It may not be supplied to any third party, or copied or reproduced in any form, without the express written permission of Electrocon International, Inc. All copies and reproductions shall be the property of Electrocon International, Inc. and must bear this ownership statement in its entirety.

Setting NU-LEC CAPM4 Recloser

2000 Users Group Meeting

Application Notes on Setting NU-LEC CAPM4 Recloser Controllers I. Recloser Models

This is a summary of the data a CAPE user must provide for the NU-LEC Switchgear Operating System model CAPM-4. Typical STYLE used in CAPE is as follows: Style CAPM-4 Properties General purpose controller style for model CAPM4, suitable for use with all applicable NU-LEC switchgear.

For details of the recloser, refer to the description in the NU-LEC Publication N00-101 (Switchgear Operating System User Manual) and to NU-LECs recloser setting program, Windows SOS. II. Recloser Elements

The recloser contains phase, ground and SEF (sensitive earth fault) overcurrent elements, with separate settings possible for each of up to four operations. Element Ground TCC1 Ground TCC2 Ground TCC3 Ground TCC4 Phase TCC1 Phase TCC2 Phase TCC3 Phase TCC4 SEF TCC1 SEF TCC2 SEF TCC3 SEF TCC4 III. Description Ground operation on 1st shot Ground operation on 2nd shot Ground operation on 3rd shot Ground operation on 4th shot Phase operation on 1st shot Phase operation on 2nd shot Phase operation on 3rd shot Phase operation on 4th shot Sensitive Earth Fault operation on 1st shot Sensitive Earth Fault operation on 2nd shot Sensitive Earth Fault operation on 3rd shot Sensitive Earth Fault operation on 4th shot

Overcurrent Timing Curves

There are eight NU-LEC timing curves defined by equations. The following table lists the parameters used for each curve model:

Setting NU-LEC CAPM4 Recloser

2000 Users Group Meeting Polynomial Terms

Curve Type
Definite Time IEC 255 Extremely Inverse IEC 255 Standard Inverse IEC 255 Very Inverse IEEE Std. Extremely Inverse IEEE Std. Moderately Inverse IEEE Std. Very Inverse Instantaneous

Code
5 8 8 8 9 9 9 5

1
1 80 0.14 13.5 28.2 0.051 5 19.61 0.01

2
0 2 0.02 1 0 0 0 0

3
0 1 1 1 2 0.02 2 0

4
0 1 1 1 1 1 1 0

5
0 0 0 0 0.1217 0.114 0.491 0

6
0 0 0 0 0 0 0 0

In addition, there are a number of timing curves defined by data points, which are similar to the curves defined for the Cooper Form 4C, as listed below: TCC010 TCC101 TCC102 TCC103 TCC104 TCC105 TCC106 TCC107 TCC111 TCC112 TCC113 IV. Recloser Taps TCC114 TCC115 TCC116 TCC117 TCC118 TCC119 TCC120 TCC121 TCC122 TCC131 TCC132 TCC133 TCC134 TCC135 TCC136 TCC137 TCC138 TCC139 TCC140 TCC141 TCC142 TCC151 TCC152 TCC161 TCC162 TCC163 TCC164 TCC165 TCC200 TCC201 TCC202

When placing a recloser, set the following taps. Only the settings with Internal Name shown in bold are actually used in the Program Model for this recloser. Note: the CAPM 2 and CAPM 4 both use the same program model within CAPE. All currents are set as primary amps or as multiples of another pickup setting. Tap Name
Auto Reclose Ground Protection SEF Protection Cold Load Pickup Work Tag

Internal Name
AUTO_RCLS GND_PROT SGF_PROT CLP_PROT WORK_TAG

Tap Descriptions
ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF

Setting NU-LEC CAPM4 Recloser


Phase Trip Current Earth Trip Current SEF Trip Current Phase Threshold Mult. Earth Threshold Mult. Cold Load Multiplier Cold Load Time Single Shot Trip Single Shot Time Reset Time Trips to Lockout SEF Trips to Lockout Loss of Phase Protection Loss of Phase Volts Loss of Phase Timeout SEF Availability Fault Reset Time Maximum Time Sequence Control Live Load Blocking Phase Protection Type 1 Phase Time Multiplier 1 Phase Definite Time 1 Phase Instantaneous 1 Phase Minimum Time 1 Phase Additional Time 1 Earth Protection Type 1 Earth Time Multiplier 1 Earth Definite Time 1 Earth Instantaneous 1 Earth Minimum Time 1 Earth Additional Time 1 Dead Time 1 SEF Definite Time 1 Phase Protection Type 2 Phase Time Multiplier 2 Phase Definite Time 2 Phase Instantaneous 2 Phase Minimum Time 2 PHS_MIN_TRIP GND_MIN_TRIP SGF_MIN_TRIP PHS_THRSH_MULT GND_THRSH_MULT CLP_MULT CLP_TIME SS_TRIP SS_TIME RESET_TIME LO_TRIP SGF_LO_TRIP LOP_PROT LOP_VOLTS LOP_TIME SGF_AVAIL FLT_RESET_TIME MAX_TIME SEQ_CTRL LLB_PROT PHS_TCC1_ID PHS_TCC1_TMULT PHS_TCC1_DEFTIME PHS_TCC1_INST_MULT PHS_TCC1_TMIN PHS_TCC1_ADDER GND_TCC1_ID GND_TCC1_TMULT GND_TCC1_DEFTIME GND_TCC1_INST_MULT GND_TCC1_TMIN GND_TCC1_ADDER TCC1_DEAD_TIME SGF_TCC1_DEFTIME PHS_TCC2_ID PHS_TCC2_TMULT PHS_TCC2_DEFTIME PHS_TCC2_INST_MULT PHS_TCC2_TMIN

2000 Users Group Meeting


10 1260 Amps 10 1260 Amps 4 20 Amps 1.0 10.0 1.0 10.0 1.0 5.0 1 480 min 1 4 1 - 180 sec 5 180 sec 1 - 4 1 4 ON/OFF 1000 15000 volts 0.1 100.0 sec ON/OFF 50 - 800 ms 2.0 - 180.0 sec, OFF ON/OFF ON/OFF CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec 0.5 180 sec 0.5 180 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec

Setting NU-LEC CAPM4 Recloser


Phase Additional Time 2 Earth Protection Type 2 Earth Time Multiplier 2 Earth Definite Time 2 Earth Instantaneous 2 Earth Minimum Time 2 Earth Additional Time 2 Dead Time 2 SEF Definite Time 2 Phase Protection Type 3 Phase Time Multiplier 3 Phase Definite Time 3 Phase Instantaneous 3 Phase Minimum Time 3 Phase Additional Time 3 Earth Protection Type 3 Earth Time Multiplier 3 Earth Definite Time 3 Earth Instantaneous 3 Earth Minimum Time 3 Earth Additional Time 3 Dead Time 3 SEF Definite Time 3 Phase Protection Type 4 Phase Time Multiplier 4 Phase Definite Time 4 Phase Instantaneous 4 Phase Minimum Time 4 Phase Additional Time 4 Earth Protection Type 4 Earth Time Multiplier 4 Earth Definite Time 4 Earth Instantaneous 4 Earth Minimum Time 4 Earth Additional Time 4 SEF Definite Time 4 High Current Lockout HCL Lockout Current HCL Active Trip Number PHS_TCC2_ADDER GND_TCC2_ID GND_TCC2_TMULT GND_TCC2_DEFTIME GND_TCC2_INST_MULT GND_TCC2_TMIN GND_TCC2_ADDER TCC2_DEAD_TIME SGF_TCC2_DEFTIME PHS_TCC3_ID PHS_TCC3_TMULT PHS_TCC3_DEFTIME PHS_TCC3_INST_MULT PHS_TCC3_TMIN PHS_TCC3_ADDER GND_TCC3_ID GND_TCC3_TMULT GND_TCC3_DEFTIME GND_TCC3_INST_MULT GND_TCC3_TMIN GND_TCC3_ADDER TCC3_DEAD_TIME SGF_TCC3_DEFTIME PHS_TCC4_ID PHS_TCC4_TMULT PHS_TCC4_DEFTIME PHS_TCC4_INST_MULT PHS_TCC4_TMIN PHS_TCC4_ADDER GND_TCC4_ID GND_TCC4_TMULT GND_TCC4_DEFTIME GND_TCC4_INST_MULT GND_TCC4_TMIN GND_TCC4_ADDER SGF_TCC4_DEFTIME HCL_PROT HCL_AMPS HCL_TRIP

2000 Users Group Meeting


0.0 2.0 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec 0.5 180 sec 0.5 180 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec 0.5 180 sec 0.5 180 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec CAPM-4 Time Curves 0.05 2.00 0.5 100 sec 1 30, OFF 0.0 2.0 sec 0.0 2.0 sec 0.5 180 sec ON/OFF 10 16000 Amps 1 4

Setting NU-LEC CAPM4 Recloser


Inrush Restraint Inrush Restraint Time Inrush Restraint Multiplier INRUSH_PROT INRUSH_TIME INRUSH_MULT

2000 Users Group Meeting


ON/OFF 0.05 - 30.0 sec 1 - 30

V.

Element Settings

On the element forms, set only the necessary contact logic codes; other settings are taken from the common taps. You can also change the settings from CAPE CG using the forms or using DRAG_CURVE. The new common taps are computed automatically from the element settings. VI. Contact Logic Element
Ground TCC1 Ground TCC2 Ground TCC3 Ground TCC4 Phase TCC1 Phase TCC2 Phase TCC3 Phase TCC4 SEF TCC1 SEF TCC2 SEF TCC3 SEF TCC4

Suggested contact logic codes: Contact Logic Code


GND_TCC1 GND_TCC2 GND_TCC3 GND_TCC4 PHS_TCC1 PHS_TCC2 PHS_TCC3 PHS_TCC4 SEF_TCC1 SEF_TCC2 SEF_TCC3 SEF_TCC4

If there are duplicates from other reclosers in the same LZOP, you may add the prefix "CAPM_" , e.g. "CAPM_GND_TCC1". The LZOP LOGIC (e.g. CAPM_TRIP) for all elements is
PHS_TCC1 OR PHS_TCC2 OR PHS_TCC3 OR PHS_TCC4 OR GND_TCC1 OR GND_TCC2 OR GND_TCC3 OR GND_TCC4 OR SEF_TCC1 OR SEF_TCC2 OR SEF_TCC3 OR SEF_TCC4

To prevent an element from tripping the logical breakers in its local zone of protection (LZOP), omit its contact-logic code from this expression. For only the first trip elements, the expression would be:
PHS_TCC1 OR GND_TCC1 OR SEF_TCC1