In order to simulate the performance of AC System Energy plus need the performance curves of the system. The performance of a VRF AC system is based on multiple performance characteristics. The cooling model inputs for a VRF AC system are: Rated Total Cooling Capacity 5.2 kW Rated Cooling COP 3.25 Minimum Outdoor Temperature in Cooling Mode -5 O C Maximum Outdoor Temperature in Cooling Mode 46 O C Cooling Capacity Ratio Modifier Function of Low Temperature Curve Name DaikinCAPFTLow Cooling Capacity Ratio Boundary Curve Name VRFBoundary Cooling Capacity Ratio Modifier Function of High Temperature Curve Name DaikinCAPFTHi Cooling Energy Input Ratio Modifier Function of Low Temperature CurveName DaikinEIRFTLow Cooling Energy Input Ratio Boundary Curve Name VRFBoundary Cooling Energy Input Ratio Modifier Function of High Temperature CurveName DakinEIRFTHi
Cooling Energy Input Ratio Modifier Function of Low Part-Load Ratio CurveName CoolingPLR Cooling Part-Load Fraction Correlation Curve Name PLRFraction 40 | P age Full-load performance data defines the variations of capacity and power when outdoor or indoor conditions changes. Part-load performance identifies how the capacity and power change when variable compressor changes speed.
Table 9 shows typical information provided by manufacturer of the system which is used in this study, using tabular representations. From this information, full-load capacity and power performance curves can be developed. The data here is presented as an absolute value Tabular data with rated condition highlighted, as shown in Table 9 (i.e., 5.2 kW rated total capacity, 3.81 rated Sensible Heat capacity and 1.6 kW rated power).
4.2.3.1 Cooling Performance Curves The operating capacity of the VRF system is calculated based on the rated cooling capacity and the actual operating conditions. The operating conditions describing cooling performance are outdoor dry-bulb (DB) temperature entering the condenser and average indoor wet-bulb (IWB) temperature entering the active zone terminal units. The first step in defining cooling performance is plotting the manufacturers data from Table 9 to represent the relation of cooling capacity with Indoor WBT and outdoor DBT.
Figure 21 Cooling Capacity Ratio as a Function of Outdoor Drybulb and Indoor Wetbulb Temperature It is evident from the plotted manufacturers data in Figure 21 that the system performance behavior changes at 30 0 C. 0.80 0.85 0.90 0.95 1.00 1.05 1.10 1.15 1.20 1.25 1.30 20 25 30 32 35 40 C o o l i n g
C a p a c i t y
R a t i o
Outdoor Drybulb Temperature 14 16 18 19 22 24 Indoor Wetbulb 42 | P age We can therefore conclude that the boundary curve equation for our system can be defined as BI =30 and the corresponding energy Plus class object definition is shown in the Figure 22.
Figure 22Input values of Boundary curve object . A typical cooling capacity curve equation is given below CAPFI =o +b (I wB, ) +c (I wB, ) 2 +J (I c ) +c (I c ) 2 + + (I wB, )(I c ) Where: CAPFT=heat pump Cooling Capacity Ratio Modifier T WB,i =wet-bulb temperature of the air entering the cooling coil. a f =equation coefficients for Cooling Capacity Ratio Modifier T C =Temperature of the air entering the condenser The equation for the simulation model is generated by following algorithm defined below. 1) Sorting the manufacturers' data in the tabular form of CAPFT, Indoor Wet Bulb, and Outdoor Dry Bulb. 2) Prepare the data and compute the values for (WB 2 ), (DB 2 ) and (WB*DB) 3) The equation is generated using a regression analysis tool called Eureqa Formulize developed by Nutonian which is a scientific data mining software package that searches for mathematical patterns hidden in a data set. 43 | P age
Since the cooling capacity of the system cannot be defined by single curve, two different equations have been generated for high and low outdoor dry bulb temperature (i) Cooling Capacity Ratio Modifier Function of Low Temperatures Select the data from Table 9 that represent the cooling capacity ratio at low outdoor temperatures (i.e., data to the left of and including the boundary curve in Figure 21) and organize the indoor and outdoor temperatures according to the fundamental form of the CAPFT equation. The tabular data given by the manufacturer is in the form capacity(kW), in order to obtain the capacity curves the data must be converted to a cooling capacity ratio term (i.e., the data must be normalized). Table 10Regression Analysis for Creating Cooling Performance curve CAPFT IWB IWB^2 DB DB^2 IWB*DB Predicted CAPFT 1.025 14 196 20 400 280 1.02517 0.978846 14 196 25 625 350 0.977386 0.930769 14 196 30 900 420 0.930878 1.071154 16 256 20 400 320 1.07123 1.023077 16 256 25 625 400 1.02345 0.976923 16 256 30 900 480 0.976942 1.117308 18 324 20 400 360 1.1173 1.069231 18 324 25 625 450 1.06951 1.023077 18 324 30 900 540 1.02301 1.140385 19 361 20 400 380 1.14033 1.092308 19 361 25 625 475 1.09255 1.046154 19 361 30 900 570 1.04604 1.209615 22 484 20 400 440 1.20942 1.161538 22 484 25 625 550 1.16164 1.115385 22 484 30 900 660 1.11513 1.255769 24 576 20 400 480 1.25549 1.207692 24 576 25 625 600 1.2077 1.161538 24 576 30 900 720 1.1612
44 | P age
To do so we use the rated conditions as the reference point and Divide all capacity data by the Rated Total Cooling Capacity to yield cooling capacity ratio. Table below shows a typical spreadsheet layout of this data. CAPFI Low = 0.906616945+0.02303191162 IwB +2.552047779 -5 (B^2) 0.01070512808 B Table 11 Statistical data of Generated Cooling Performance Equation R^2 Goodness of Fit 0.999 Correlation Coefficient 0.999 MaximumError 0.001 Mean Squared Error 1.64E-07 Mean Absolute Error 2.44 E-04
(ii) Cooling Capacity Ratio Modifier Function of High Temperatures Similar analysis is done to create Cooling Capacity Ratio Modifier Function of High Temperatures and following equation is obtained CAPFI H =0.885+ 0.0231 IWB 0.009425 DB R^2 Goodness of Fit 0.999 Correlation Coefficient 0.999 MaximumError 0.001 Mean Squared Error 2.38E-07 Mean Absolute Error 0.000272
4.2.3.2 Cooling Energy Input Ratio Modifier The method used to create performance curve coefficients for cooling energy input ratio modifier function of temperatures is identical to the method used for cooling capacity ratio. Table 12 below shows the power input ratio data extracted from capacity tables provide by manufacturer. This data is normalized to the rated power input in order to create the performance curves. 45 | P age
Figure 23 Manufacturer's Data of Cooling Energy Input Ratio
0.76 0.86 0.96 1.06 20 25 30 32 35 40 P o w e r
I n p u t
R a t i o
Outdoor Dry Bulb Temperature 14 16 18 19 22 24 IWB 46 | P age
It is evident from the cooling energy input data plot Figure 23 that performance of the system changes at the outdoor temperature of 30 O C Therefore same boundary curve from cooling capacity curve is used The following equations are obtained from the analysis of manufacturers performance data.
EIRFI Low =0.4802+0.01317 B + 5.854 -5 wB 2 + 3.169 -5 B 2
R^2 Goodness of Fit 0.999035 Correlation Coefficient 0.99957 MaximumError 0.003891 Mean Squared Error 3.49E-06 Mean Absolute Error 0.001406
EIRFI HI =PIR = 0.4355 + 0.01484 B + 0.002364 wB R^2 Goodness of Fit 0.999525 Correlation Coefficient 0.999767 MaximumError 0.003136 Mean Squared Error 1.62E-06