Product Specification

High Speed Section Insulator 25 kV AC


Type HS25

1 2 3

Features Advantages of the HS25 Technical Specifications

2 2 3

Product specification Section Insulator HS25.doc

09.09.2011/MW Page 1 of 6

Arthur Flury AG CH-4543 Deitingen

1 Features
25 kV High Speed Section Insulator
25 kV High Speed Section Insulator for speed up to 200 km/h with 2 Teflon coated glass fiber rods, revolvable in case of wear, runners made of copper, arcing horns of stainless steel, with contact wire clamps for up to 193 mm contact wire, with 4 turnbuckles for adjustment of the height and 4 suspension cables of bronze 10 mm, all parts are made of non corrosive materials, in accordance to the following summary drawings.

2 Advantages of the HS25


Jig available for a very short installation time, easy to install and to regulate. (Usable for Installation and Maintanance) For speed up to 200 km/h with exelence dynamic performane All parts are made of non corrosive materials Revolvable insulator rod in case of wear, which gives a service life of more than 4 million pantograph passages The arcing horn layout guarantees a quick extinguishing of arcs Teflon coated glass fiber rods are more than 20 years in service, excellent long term behaviors The guaranteed breaking load of each glass fiber rod is more than 100 kN The sealed end fittings and the PTFE guarantee that absolutely no pollution and no ultraviolet radiation will enter to the Epoxy resin glass fiber bar Breaking load of the Section Insulator 120 kN Breaking load of the insulator rod 100 kN/each Recommended service load 22.5 kN (for 1 contact wire) Resistant against short circuits

Product specification Section Insulator HS25.doc

09.09.2011/MW Page 2 of 6

Arthur Flury AG CH-4543 Deitingen

3 Technical Specifications
3.1 Range of working conditions
Scope of application: The section insulator shall be applicable as sectioning point for two sections of electric overhead contact system of single phase, 50/60 Hz, 25 kV AC electrified railroad. It has to accept voltages up to 29 kV as well. Type of the overhead contact system: Automatically tensioned or fixed simple or compound catenary systems. System height: 0.8 m 2.0 m Specifications and cross-sections of the contact wire: The neutral section insulator can be used for 85 193 mm copper or copperalloy contact wire. The overall dimensions and the alloy of the contact wire shall be stated by the customer. Tension range of contact wire: 8 - 22.5 kN The range of the contact wire tensile load shall be stated by the customer. Specification and cross section of the messenger wire: The NS fits to different kinds of messenger wire cables. The exact size shall be given by the customer. Tension range of the catenary: 10 25 kN The exact value shall be given by the customer. Running speed: 0 200 km/h Properties of pantograph: It works with single arm pantograph with carbon strip used at normal operation. The static pressure of the collector shall be 70 - 120 N. Number of pantograph passages: 2 4 Million for the total live time of the insulator rods

Product specification Section Insulator HS25.doc

09.09.2011/MW Page 3 of 6

Arthur Flury AG CH-4543 Deitingen

Ambient temperature: Outdoor equipments - 40 C to + 50 C Altitude above sea-level: 0 3000 m Relative humidity: 90 % per month 95 % per day Thickness of ice-coating: < 10 mm Wind speed: 35 m/s Earthquake resistance: The S.I. is resistant against earthquake shocks to 8 degrees. Others have to be stated by the customer. Mixed Traffic: The HS25 is able to work under mixed tractions of electric and diesel locomotives running. In heavy polluted area of diesel locomotive traffic and installations inside a tunnel, the insulator rods shall be cleaned with a towel and cleaning solution at minimum every year. Trains shall not stop with the exhaust channel directly under the Section Insulator.

Product specification Section Insulator HS25.doc

09.09.2011/MW Page 4 of 6

Arthur Flury AG CH-4543 Deitingen

3.2 Performance and technical requirements


Table 1 Electrical requirements
1 2 3 4 5 6 7 8 9 Power frequency withstand voltage dry Power frequency withstand voltage wet Lightning impulse withstand voltage Power frequency pollution withstand voltage acc. to IEC 507 (224kg/m) Creepage distance Insulation resistance Leakage current Arc withstand property Water absorbtion

Insulator rod
>400 kV >150 kV >500 kV 36 kV 1100 mm >600 MOhm <190 A 0

Section Insulator
>90 kV >80 kV >150 kV 36 kV 1100mm >600 MOhm <190 A 5.4 kA for 0.125sec 0

Table 2 Mechanical requirements


1 2 Destructive tensile load Starting sliding load between fittings and contact wire Bending strength Max twist Max. deflection Vibration performance Wearability

Insulator rod
>100 kN -

Section Insulator
>120 kN No sliding until fully breaking load of contact wire 6 mm Resistant against vibrations 5 Runners > 5 x 10 passages

3 4 5 6 7

350 Nm 90 on 1500mm 6 mm Resistant against vibrations 6 > 2 x 10 passages in laboratory

Product specification Section Insulator HS25.doc

09.09.2011/MW Page 5 of 6

Arthur Flury AG CH-4543 Deitingen

3.3 Technical Service and Training


The manufacturer shall offer the instruction manuals for assembly and drawings in the quotation. The manufacturer shall send on customers request an engineer to work on site for training of the customers staff. The manufacturer shall state the name, specifications and quantity of the relevant spare parts, materials and special tools and instruments to be supplied with the section insulators during delivery.

3.4 Technical documents


Drawings The manufacturer shall furnish the assembly drawing (including main dimensions and total weight) and drawings of all components and fastenings etc. of the section insulator and shall make a description of the name, quantity, size, material and unit weight of all components, and anti-corrosive measures of steel components. Installation, maintenance and other technical documents Each box with 2 Section Insulators shall contain 1 installation instruction as well as one assembly drawing. Mark and packing The marking and packing shall be against the customers instructions. Packing in proper seaworthy cardboard boxes. 2 section insulators shall be packed in one box.

Product specification Section Insulator HS25.doc

09.09.2011/MW Page 6 of 6