Zone Sizing Summary for G Floor (BF&PB Area)

Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type G Floor (BF&PB Area) TERM VRF Number of zones Floor Area Location 3 6676.5 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Peak zone sensible load Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 257.3 34.1 23.7 Design Air Flow (CFM) 14067 1864 1298 Minimum Air Flow (CFM) 14067 1864 1298 Time of Peak Load Sep 1500 Jul 1500 Oct 1500 Maximum Heating Load (MBH) 17.7 1.7 1.5 Zone Floor Area (ft) 5257.3 922.3 496.9

Zone Name Zone 1 Zone 2 Zone 3

Zone CFM/ft 2.68 2.02 2.61

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 390.4 42.9 30.4 Sens Coil Load (MBH) 286.9 34.4 24.5 Coil Entering DB / WB (F) 79.3 / 68.0 76.9 / 66.1 77.4 / 66.3 Coil Leaving DB / WB (F) 60.4 / 59.3 59.7 / 58.7 59.8 / 58.8 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500 Aug 1500 Oct 1500

Zone Name Zone 1 Zone 2 Zone 3

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 Htg Coil Water Flow @20.0 F (gpm) 0.00 0.00 0.00

Zone Name Zone 1 Zone 2 Zone 3

Heating Coil Load (MBH) 0.0 0.0 0.0

Fan Design AirFlow (CFM) 14067 1864 1298

Fan Motor (BHP) 0.000 0.000 0.000

Fan Motor (kW) 0.000 0.000 0.000

OA Vent Design AirFlow (CFM) 1696 55 75

Space Loads and Airflows


Cooling Sensible (MBH) 257.3 34.1 23.7 Time of Load Sep 1500 Jul 1500 Oct 1500 Air Flow (CFM) 14067 1864 1298 Heating Load (MBH) 17.7 1.7 1.5 Floor Area (ft) 5257.3 922.3 496.9

Zone Name / Space Name Zone 1 BF Longue Zone 2 GF L.Lobby and Corridor Zone 3 GF Waiting Area

Mult. 1 1 1

Space CFM/ft 2.68 2.02 2.61

Hourly Analysis Program v4.61

Page 1 of 73

Zone Sizing Summary for G Floor (FHall&Rec)


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type G Floor (FHall&Rec) TERM VRF Number of zones Floor Area Location 4 5765.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Peak zone sensible load Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 201.1 26.7 15.9 34.1 Design Air Flow (CFM) 10996 1460 867 1864 Minimum Air Flow (CFM) 10996 1460 867 1864 Time of Peak Load Aug 1600 Aug 1600 Jul 1900 Jul 1500 Maximum Heating Load (MBH) 19.6 3.1 2.4 1.7 Zone Floor Area (ft) 4035.0 511.0 297.3 922.3

Zone Name Zone 1 Zone 2 Zone 3 Zone 4

Zone CFM/ft 2.73 2.86 2.92 2.02

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 311.7 34.3 18.0 45.5 Sens Coil Load (MBH) 223.4 27.0 15.1 34.4 Coil Entering DB / WB (F) 79.0 / 68.0 76.9 / 66.3 76.5 / 66.0 76.9 / 66.6 Coil Leaving DB / WB (F) 60.1 / 59.1 59.7 / 58.7 60.3 / 59.3 59.7 / 58.8 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500 Jul 1600 Jul 1900 Aug 1500

Zone Name Zone 1 Zone 2 Zone 3 Zone 4

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 Htg Coil Water Flow @20.0 F (gpm) 0.00 0.00 0.00 0.00

Zone Name Zone 1 Zone 2 Zone 3 Zone 4

Heating Coil Load (MBH) 0.0 0.0 0.0 0.0

Fan Design AirFlow (CFM) 10996 1460 867 1864

Fan Motor (BHP) 0.000 0.000 0.000 0.000

Fan Motor (kW) 0.000 0.000 0.000 0.000

OA Vent Design AirFlow (CFM) 1242 56 0 55

Space Loads and Airflows


Cooling Sensible (MBH) 201.1 26.7 15.9 34.1 Time of Load Aug 1600 Aug 1600 Jul 1900 Jul 1500 Air Flow (CFM) 10996 1460 867 1864 Heating Load (MBH) 19.6 3.1 2.4 1.7 Floor Area (ft) 4035.0 511.0 297.3 922.3

Zone Name / Space Name Zone 1 Functional Hall Zone 2 Front Office Zone 3 Preparation Area Zone 4 GF L.Lobby and Corridor

Mult. 1 1 1 1

Space CFM/ft 2.73 2.86 2.92 2.02

Hourly Analysis Program v4.61

Page 2 of 73

Zone Sizing Summary for L1-JS1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-JS1 TERM SPLT-FC Number of zones Floor Area Location 1 267.8 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 15.6 Design Air Flow (CFM) 853 Minimum Air Flow (CFM) 853 Time of Peak Load Aug 0900 Maximum Heating Load (MBH) 1.5 Zone Floor Area (ft) 267.8

Zone Name Zone 1

Zone CFM/ft 3.19

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.0 Sens Coil Load (MBH) 15.4 Coil Entering DB / WB (F) 76.4 / 65.5 Coil Leaving DB / WB (F) 59.6 / 58.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 853

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 26

Space Loads and Airflows


Cooling Sensible (MBH) 15.6 Time of Load Aug 0900 Air Flow (CFM) 853 Heating Load (MBH) 1.5 Floor Area (ft) 267.8

Zone Name / Space Name Zone 1 L1-JS1

Mult. 1

Space CFM/ft 3.19

Hourly Analysis Program v4.61

Page 3 of 73

Zone Sizing Summary for L1-SS1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS1 TERM SPLT-FC Number of zones Floor Area Location 1 239.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 20.4 Design Air Flow (CFM) 1117 Minimum Air Flow (CFM) 1117 Time of Peak Load Sep 1600 Maximum Heating Load (MBH) 2.5 Zone Floor Area (ft) 239.0

Zone Name Zone 1

Zone CFM/ft 4.67

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 22.0 Sens Coil Load (MBH) 19.8 Coil Entering DB / WB (F) 77.1 / 65.9 Coil Leaving DB / WB (F) 60.6 / 59.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1117

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 20.4 Time of Load Sep 1600 Air Flow (CFM) 1117 Heating Load (MBH) 2.5 Floor Area (ft) 239.0

Zone Name / Space Name Zone 1 L1-SS1

Mult. 1

Space CFM/ft 4.67

Hourly Analysis Program v4.61

Page 4 of 73

Zone Sizing Summary for L1-SS2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS2 TERM SPLT-FC Number of zones Floor Area Location 1 239.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 20.1 Design Air Flow (CFM) 1099 Minimum Air Flow (CFM) 1099 Time of Peak Load Oct 1600 Maximum Heating Load (MBH) 1.1 Zone Floor Area (ft) 239.0

Zone Name Zone 1

Zone CFM/ft 4.60

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 21.5 Sens Coil Load (MBH) 19.4 Coil Entering DB / WB (F) 77.1 / 65.9 Coil Leaving DB / WB (F) 60.7 / 59.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1099

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 20.1 Time of Load Oct 1600 Air Flow (CFM) 1099 Heating Load (MBH) 1.1 Floor Area (ft) 239.0

Zone Name / Space Name Zone 1 L1-SS2

Mult. 1

Space CFM/ft 4.60

Hourly Analysis Program v4.61

Page 5 of 73

Zone Sizing Summary for L1-SS25


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS25 TERM SPLT-FC Number of zones Floor Area Location 1 199.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.2 Design Air Flow (CFM) 666 Minimum Air Flow (CFM) 666 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 199.6

Zone Name Zone 1

Zone CFM/ft 3.34

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.0 Sens Coil Load (MBH) 11.8 Coil Entering DB / WB (F) 76.7 / 65.9 Coil Leaving DB / WB (F) 60.2 / 59.2 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 666

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.2 Time of Load Jul 0900 Air Flow (CFM) 666 Heating Load (MBH) 0.8 Floor Area (ft) 199.6

Zone Name / Space Name Zone 1 L1-SS25

Mult. 1

Space CFM/ft 3.34

Hourly Analysis Program v4.61

Page 6 of 73

Zone Sizing Summary for L1-SS26


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS26 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.7 Design Air Flow (CFM) 693 Minimum Air Flow (CFM) 693 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.9 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.22

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.6 Sens Coil Load (MBH) 12.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 693

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.7 Time of Load Jul 0900 Air Flow (CFM) 693 Heating Load (MBH) 0.9 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L1-SS26

Mult. 1

Space CFM/ft 3.22

Hourly Analysis Program v4.61

Page 7 of 73

Zone Sizing Summary for L1-SS27


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS27 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.7 Design Air Flow (CFM) 693 Minimum Air Flow (CFM) 693 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.9 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.22

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.6 Sens Coil Load (MBH) 12.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 693

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.7 Time of Load Jul 0900 Air Flow (CFM) 693 Heating Load (MBH) 0.9 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L1-SS27

Mult. 1

Space CFM/ft 3.22

Hourly Analysis Program v4.61

Page 8 of 73

Zone Sizing Summary for L1-SS28


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS28 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.7 Design Air Flow (CFM) 693 Minimum Air Flow (CFM) 693 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.9 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.22

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.6 Sens Coil Load (MBH) 12.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 693

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.7 Time of Load Jul 0900 Air Flow (CFM) 693 Heating Load (MBH) 0.9 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L1-SS28

Mult. 1

Space CFM/ft 3.22

Hourly Analysis Program v4.61

Page 9 of 73

Zone Sizing Summary for L1-SS29


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS29 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.7 Design Air Flow (CFM) 693 Minimum Air Flow (CFM) 693 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.9 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.22

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.6 Sens Coil Load (MBH) 12.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 693

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.7 Time of Load Jul 0900 Air Flow (CFM) 693 Heating Load (MBH) 0.9 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L1-SS29

Mult. 1

Space CFM/ft 3.22

Hourly Analysis Program v4.61

Page 10 of 73

Zone Sizing Summary for L1-SS3


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS3 TERM SPLT-FC Number of zones Floor Area Location 1 239.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 20.1 Design Air Flow (CFM) 1099 Minimum Air Flow (CFM) 1099 Time of Peak Load Oct 1600 Maximum Heating Load (MBH) 1.1 Zone Floor Area (ft) 239.0

Zone Name Zone 1

Zone CFM/ft 4.60

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 21.5 Sens Coil Load (MBH) 19.4 Coil Entering DB / WB (F) 77.1 / 65.9 Coil Leaving DB / WB (F) 60.7 / 59.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1099

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 20.1 Time of Load Oct 1600 Air Flow (CFM) 1099 Heating Load (MBH) 1.1 Floor Area (ft) 239.0

Zone Name / Space Name Zone 1 L1-SS3

Mult. 1

Space CFM/ft 4.60

Hourly Analysis Program v4.61

Page 11 of 73

Zone Sizing Summary for L1-SS30


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS30 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.7 Design Air Flow (CFM) 693 Minimum Air Flow (CFM) 693 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.9 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.22

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.6 Sens Coil Load (MBH) 12.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 693

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.7 Time of Load Jul 0900 Air Flow (CFM) 693 Heating Load (MBH) 0.9 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L1-SS30

Mult. 1

Space CFM/ft 3.22

Hourly Analysis Program v4.61

Page 12 of 73

Zone Sizing Summary for L1-SS31


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS31 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 13.5 Design Air Flow (CFM) 738 Minimum Air Flow (CFM) 738 Time of Peak Load Jul 1900 Maximum Heating Load (MBH) 2.2 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.43

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 15.6 Sens Coil Load (MBH) 13.3 Coil Entering DB / WB (F) 76.8 / 65.8 Coil Leaving DB / WB (F) 60.1 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 738

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 13.5 Time of Load Jul 1900 Air Flow (CFM) 738 Heating Load (MBH) 2.2 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L1-SS31

Mult. 1

Space CFM/ft 3.43

Hourly Analysis Program v4.61

Page 13 of 73

Zone Sizing Summary for L1-SS4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS4 TERM SPLT-FC Number of zones Floor Area Location 1 239.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 20.1 Design Air Flow (CFM) 1099 Minimum Air Flow (CFM) 1099 Time of Peak Load Oct 1600 Maximum Heating Load (MBH) 1.1 Zone Floor Area (ft) 239.0

Zone Name Zone 1

Zone CFM/ft 4.60

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 21.5 Sens Coil Load (MBH) 19.4 Coil Entering DB / WB (F) 77.1 / 65.9 Coil Leaving DB / WB (F) 60.7 / 59.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1099

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 20.1 Time of Load Oct 1600 Air Flow (CFM) 1099 Heating Load (MBH) 1.1 Floor Area (ft) 239.0

Zone Name / Space Name Zone 1 L1-SS4

Mult. 1

Space CFM/ft 4.60

Hourly Analysis Program v4.61

Page 14 of 73

Zone Sizing Summary for L1-SS5


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS5 TERM SPLT-FC Number of zones Floor Area Location 1 239.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 20.1 Design Air Flow (CFM) 1099 Minimum Air Flow (CFM) 1099 Time of Peak Load Oct 1600 Maximum Heating Load (MBH) 1.1 Zone Floor Area (ft) 239.0

Zone Name Zone 1

Zone CFM/ft 4.60

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 21.5 Sens Coil Load (MBH) 19.4 Coil Entering DB / WB (F) 77.1 / 65.9 Coil Leaving DB / WB (F) 60.7 / 59.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1099

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 20.1 Time of Load Oct 1600 Air Flow (CFM) 1099 Heating Load (MBH) 1.1 Floor Area (ft) 239.0

Zone Name / Space Name Zone 1 L1-SS5

Mult. 1

Space CFM/ft 4.60

Hourly Analysis Program v4.61

Page 15 of 73

Zone Sizing Summary for L1-SS6


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS6 TERM SPLT-FC Number of zones Floor Area Location 1 239.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 20.1 Design Air Flow (CFM) 1099 Minimum Air Flow (CFM) 1099 Time of Peak Load Oct 1600 Maximum Heating Load (MBH) 1.1 Zone Floor Area (ft) 239.0

Zone Name Zone 1

Zone CFM/ft 4.60

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 21.5 Sens Coil Load (MBH) 19.4 Coil Entering DB / WB (F) 77.1 / 65.9 Coil Leaving DB / WB (F) 60.7 / 59.6 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1099

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 20.1 Time of Load Oct 1600 Air Flow (CFM) 1099 Heating Load (MBH) 1.1 Floor Area (ft) 239.0

Zone Name / Space Name Zone 1 L1-SS6

Mult. 1

Space CFM/ft 4.60

Hourly Analysis Program v4.61

Page 16 of 73

Zone Sizing Summary for L1-SS7


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS7 TERM SPLT-FC Number of zones Floor Area Location 1 197.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 Design Air Flow (CFM) 675 Minimum Air Flow (CFM) 675 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 197.7

Zone Name Zone 1

Zone CFM/ft 3.41

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.1 Sens Coil Load (MBH) 12.0 Coil Entering DB / WB (F) 76.9 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 675

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 Time of Load Oct 1500 Air Flow (CFM) 675 Heating Load (MBH) 0.8 Floor Area (ft) 197.7

Zone Name / Space Name Zone 1 L1-SS7

Mult. 1

Space CFM/ft 3.41

Hourly Analysis Program v4.61

Page 17 of 73

Zone Sizing Summary for L1-SS8


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L1-SS8 TERM SPLT-FC Number of zones Floor Area Location 1 197.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 Design Air Flow (CFM) 675 Minimum Air Flow (CFM) 675 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 197.7

Zone Name Zone 1

Zone CFM/ft 3.41

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.1 Sens Coil Load (MBH) 12.0 Coil Entering DB / WB (F) 76.9 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 675

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 Time of Load Oct 1500 Air Flow (CFM) 675 Heating Load (MBH) 0.8 Floor Area (ft) 197.7

Zone Name / Space Name Zone 1 L1-SS8

Mult. 1

Space CFM/ft 3.41

Hourly Analysis Program v4.61

Page 18 of 73

Zone Sizing Summary for L2-JS1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-JS1 TERM SPLT-FC Number of zones Floor Area Location 1 267.8 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 15.0 Design Air Flow (CFM) 818 Minimum Air Flow (CFM) 818 Time of Peak Load Aug 0900 Maximum Heating Load (MBH) 1.4 Zone Floor Area (ft) 267.8

Zone Name Zone 1

Zone CFM/ft 3.05

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 17.0 Sens Coil Load (MBH) 14.5 Coil Entering DB / WB (F) 76.7 / 65.9 Coil Leaving DB / WB (F) 60.2 / 59.2 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 818

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 26

Space Loads and Airflows


Cooling Sensible (MBH) 15.0 Time of Load Aug 0900 Air Flow (CFM) 818 Heating Load (MBH) 1.4 Floor Area (ft) 267.8

Zone Name / Space Name Zone 1 L2-JS1

Mult. 1

Space CFM/ft 3.05

Hourly Analysis Program v4.61

Page 19 of 73

Zone Sizing Summary for L2-SS1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS1 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Sep 1500 Maximum Heating Load (MBH) 2.3 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 19.2 Sens Coil Load (MBH) 17.1 Coil Entering DB / WB (F) 76.8 / 65.6 Coil Leaving DB / WB (F) 60.2 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Sep 1500 Air Flow (CFM) 953 Heating Load (MBH) 2.3 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L2-SS1

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 20 of 73

Zone Sizing Summary for L2-SS2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS2 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L2-SS2

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 21 of 73

Zone Sizing Summary for L2-SS25


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS25 TERM SPLT-FC Number of zones Floor Area Location 1 199.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 11.7 Design Air Flow (CFM) 638 Minimum Air Flow (CFM) 638 Time of Peak Load Jul 0800 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 199.6

Zone Name Zone 1

Zone CFM/ft 3.19

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.5 Sens Coil Load (MBH) 11.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 638

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 11.7 Time of Load Jul 0800 Air Flow (CFM) 638 Heating Load (MBH) 0.8 Floor Area (ft) 199.6

Zone Name / Space Name Zone 1 L2-SS25

Mult. 1

Space CFM/ft 3.19

Hourly Analysis Program v4.61

Page 22 of 73

Zone Sizing Summary for L2-SS26


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS26 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L2-SS26

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 23 of 73

Zone Sizing Summary for L2-SS27


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS27 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L2-SS27

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 24 of 73

Zone Sizing Summary for L2-SS28


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS28 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L2-SS28

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 25 of 73

Zone Sizing Summary for L2-SS29


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS29 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L2-SS29

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 26 of 73

Zone Sizing Summary for L2-SS3


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS3 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L2-SS3

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 27 of 73

Zone Sizing Summary for L2-SS30


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS30 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.7 Design Air Flow (CFM) 693 Minimum Air Flow (CFM) 693 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.9 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.22

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.6 Sens Coil Load (MBH) 12.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 693

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.7 Time of Load Jul 0900 Air Flow (CFM) 693 Heating Load (MBH) 0.9 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L2-SS30

Mult. 1

Space CFM/ft 3.22

Hourly Analysis Program v4.61

Page 28 of 73

Zone Sizing Summary for L2-SS31


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:55AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS31 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 13.5 Design Air Flow (CFM) 738 Minimum Air Flow (CFM) 738 Time of Peak Load Jul 1900 Maximum Heating Load (MBH) 2.2 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.43

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 15.6 Sens Coil Load (MBH) 13.3 Coil Entering DB / WB (F) 76.8 / 65.8 Coil Leaving DB / WB (F) 60.1 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 738

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 13.5 Time of Load Jul 1900 Air Flow (CFM) 738 Heating Load (MBH) 2.2 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L2-SS31

Mult. 1

Space CFM/ft 3.43

Hourly Analysis Program v4.61

Page 29 of 73

Zone Sizing Summary for L2-SS4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS4 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L2-SS4

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 30 of 73

Zone Sizing Summary for L2-SS5


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS5 TERM SPLT-FC Number of zones Floor Area Location 1 199.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 11.7 Design Air Flow (CFM) 638 Minimum Air Flow (CFM) 638 Time of Peak Load Jul 0800 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 199.6

Zone Name Zone 1

Zone CFM/ft 3.19

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.5 Sens Coil Load (MBH) 11.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 638

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 11.7 Time of Load Jul 0800 Air Flow (CFM) 638 Heating Load (MBH) 0.8 Floor Area (ft) 199.6

Zone Name / Space Name Zone 1 L2-SS25

Mult. 1

Space CFM/ft 3.19

Hourly Analysis Program v4.61

Page 31 of 73

Zone Sizing Summary for L2-SS6


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS6 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L2-SS6

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 32 of 73

Zone Sizing Summary for L2-SS7


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS7 TERM SPLT-FC Number of zones Floor Area Location 1 197.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 Design Air Flow (CFM) 675 Minimum Air Flow (CFM) 675 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 197.7

Zone Name Zone 1

Zone CFM/ft 3.41

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.1 Sens Coil Load (MBH) 12.0 Coil Entering DB / WB (F) 76.9 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 675

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 Time of Load Oct 1500 Air Flow (CFM) 675 Heating Load (MBH) 0.8 Floor Area (ft) 197.7

Zone Name / Space Name Zone 1 L1-SS7

Mult. 1

Space CFM/ft 3.41

Hourly Analysis Program v4.61

Page 33 of 73

Zone Sizing Summary for L2-SS8


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L2-SS8 TERM SPLT-FC Number of zones Floor Area Location 1 197.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 Design Air Flow (CFM) 675 Minimum Air Flow (CFM) 675 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 197.7

Zone Name Zone 1

Zone CFM/ft 3.41

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.1 Sens Coil Load (MBH) 12.0 Coil Entering DB / WB (F) 76.9 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 675

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 Time of Load Oct 1500 Air Flow (CFM) 675 Heating Load (MBH) 0.8 Floor Area (ft) 197.7

Zone Name / Space Name Zone 1 L2-SS7

Mult. 1

Space CFM/ft 3.41

Hourly Analysis Program v4.61

Page 34 of 73

Zone Sizing Summary for L3-JS1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-JS1 TERM SPLT-FC Number of zones Floor Area Location 1 267.8 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 15.0 Design Air Flow (CFM) 818 Minimum Air Flow (CFM) 818 Time of Peak Load Aug 0900 Maximum Heating Load (MBH) 1.4 Zone Floor Area (ft) 267.8

Zone Name Zone 1

Zone CFM/ft 3.05

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 17.0 Sens Coil Load (MBH) 14.5 Coil Entering DB / WB (F) 76.7 / 65.9 Coil Leaving DB / WB (F) 60.2 / 59.2 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 818

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 26

Space Loads and Airflows


Cooling Sensible (MBH) 15.0 Time of Load Aug 0900 Air Flow (CFM) 818 Heating Load (MBH) 1.4 Floor Area (ft) 267.8

Zone Name / Space Name Zone 1 L3-JS1

Mult. 1

Space CFM/ft 3.05

Hourly Analysis Program v4.61

Page 35 of 73

Zone Sizing Summary for L3-SS1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS1 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Sep 1500 Maximum Heating Load (MBH) 2.3 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 19.2 Sens Coil Load (MBH) 17.1 Coil Entering DB / WB (F) 76.8 / 65.6 Coil Leaving DB / WB (F) 60.2 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jul 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Sep 1500 Air Flow (CFM) 953 Heating Load (MBH) 2.3 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L3-SS1

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 36 of 73

Zone Sizing Summary for L3-SS2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS2 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L3-SS2

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 37 of 73

Zone Sizing Summary for L3-SS25


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS25 TERM SPLT-FC Number of zones Floor Area Location 1 199.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 11.7 Design Air Flow (CFM) 638 Minimum Air Flow (CFM) 638 Time of Peak Load Jul 0800 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 199.6

Zone Name Zone 1

Zone CFM/ft 3.19

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.5 Sens Coil Load (MBH) 11.4 Coil Entering DB / WB (F) 76.6 / 65.8 Coil Leaving DB / WB (F) 60.0 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0900

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 638

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 11.7 Time of Load Jul 0800 Air Flow (CFM) 638 Heating Load (MBH) 0.8 Floor Area (ft) 199.6

Zone Name / Space Name Zone 1 L3-SS25

Mult. 1

Space CFM/ft 3.19

Hourly Analysis Program v4.61

Page 38 of 73

Zone Sizing Summary for L3-SS26


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS26 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L3-SS26

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 39 of 73

Zone Sizing Summary for L3-SS27


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS27 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L3-SS27

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 40 of 73

Zone Sizing Summary for L3-SS28


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS28 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L3-SS28

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 41 of 73

Zone Sizing Summary for L3-SS29


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS29 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L3-SS29

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 42 of 73

Zone Sizing Summary for L3-SS3


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS3 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L3-SS3

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 43 of 73

Zone Sizing Summary for L3-SS30


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS30 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.1 Design Air Flow (CFM) 663 Minimum Air Flow (CFM) 663 Time of Peak Load Jul 0900 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.08

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 Sens Coil Load (MBH) 11.7 Coil Entering DB / WB (F) 76.5 / 65.9 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 663

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 12.1 Time of Load Jul 0900 Air Flow (CFM) 663 Heating Load (MBH) 0.8 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L3-SS30

Mult. 1

Space CFM/ft 3.08

Hourly Analysis Program v4.61

Page 44 of 73

Zone Sizing Summary for L3-SS31


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS31 TERM SPLT-FC Number of zones Floor Area Location 1 215.3 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 13.5 Design Air Flow (CFM) 738 Minimum Air Flow (CFM) 738 Time of Peak Load Jul 1900 Maximum Heating Load (MBH) 2.2 Zone Floor Area (ft) 215.3

Zone Name Zone 1

Zone CFM/ft 3.43

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 15.6 Sens Coil Load (MBH) 13.3 Coil Entering DB / WB (F) 76.8 / 65.8 Coil Leaving DB / WB (F) 60.1 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Jun 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 738

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 23

Space Loads and Airflows


Cooling Sensible (MBH) 13.5 Time of Load Jul 1900 Air Flow (CFM) 738 Heating Load (MBH) 2.2 Floor Area (ft) 215.3

Zone Name / Space Name Zone 1 L3-SS31

Mult. 1

Space CFM/ft 3.43

Hourly Analysis Program v4.61

Page 45 of 73

Zone Sizing Summary for L3-SS4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS4 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L3-SS4

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 46 of 73

Zone Sizing Summary for L3-SS5


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS5 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L3-SS5

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 47 of 73

Zone Sizing Summary for L3-SS6


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS6 TERM SPLT-FC Number of zones Floor Area Location 1 236.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 17.4 Design Air Flow (CFM) 953 Minimum Air Flow (CFM) 953 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.0 Zone Floor Area (ft) 236.6

Zone Name Zone 1

Zone CFM/ft 4.03

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 18.9 Sens Coil Load (MBH) 16.9 Coil Entering DB / WB (F) 76.9 / 65.7 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 953

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 24

Space Loads and Airflows


Cooling Sensible (MBH) 17.4 Time of Load Oct 1500 Air Flow (CFM) 953 Heating Load (MBH) 1.0 Floor Area (ft) 236.6

Zone Name / Space Name Zone 1 L3-SS6

Mult. 1

Space CFM/ft 4.03

Hourly Analysis Program v4.61

Page 48 of 73

Zone Sizing Summary for L3-SS7


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS7 TERM SPLT-FC Number of zones Floor Area Location 1 197.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 Design Air Flow (CFM) 675 Minimum Air Flow (CFM) 675 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 197.7

Zone Name Zone 1

Zone CFM/ft 3.41

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.1 Sens Coil Load (MBH) 12.0 Coil Entering DB / WB (F) 76.9 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 675

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 Time of Load Oct 1500 Air Flow (CFM) 675 Heating Load (MBH) 0.8 Floor Area (ft) 197.7

Zone Name / Space Name Zone 1 L3-SS7

Mult. 1

Space CFM/ft 3.41

Hourly Analysis Program v4.61

Page 49 of 73

Zone Sizing Summary for L3-SS8


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L3-SS8 TERM SPLT-FC Number of zones Floor Area Location 1 197.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 Design Air Flow (CFM) 675 Minimum Air Flow (CFM) 675 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 0.8 Zone Floor Area (ft) 197.7

Zone Name Zone 1

Zone CFM/ft 3.41

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.1 Sens Coil Load (MBH) 12.0 Coil Entering DB / WB (F) 76.9 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.3 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 675

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 22

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 Time of Load Oct 1500 Air Flow (CFM) 675 Heating Load (MBH) 0.8 Floor Area (ft) 197.7

Zone Name / Space Name Zone 1 L3-SS8

Mult. 1

Space CFM/ft 3.41

Hourly Analysis Program v4.61

Page 50 of 73

Zone Sizing Summary for L4-Executive Longue


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Executive Longue TERM SPLT-FC Number of zones Floor Area Location 1 1313.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 102.1 Design Air Flow (CFM) 5582 Minimum Air Flow (CFM) 5582 Time of Peak Load Aug 1500 Maximum Heating Load (MBH) 14.6 Zone Floor Area (ft) 1313.6

Zone Name Zone 1

Zone CFM/ft 4.25

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 142.7 Sens Coil Load (MBH) 109.7 Coil Entering DB / WB (F) 77.7 / 66.6 Coil Leaving DB / WB (F) 59.4 / 58.4 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 5582

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 379

Space Loads and Airflows


Cooling Sensible (MBH) 102.1 Time of Load Aug 1500 Air Flow (CFM) 5582 Heating Load (MBH) 14.6 Floor Area (ft) 1313.6

Zone Name / Space Name Zone 1 L4-Executive Longue

Mult. 1

Space CFM/ft 4.25

Hourly Analysis Program v4.61

Page 51 of 73

Zone Sizing Summary for L4-Rm1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm1 TERM SPLT-FC Number of zones Floor Area Location 1 513.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 26.8 Design Air Flow (CFM) 1467 Minimum Air Flow (CFM) 1467 Time of Peak Load Aug 1600 Maximum Heating Load (MBH) 3.0 Zone Floor Area (ft) 513.6

Zone Name Zone 1

Zone CFM/ft 2.86

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 30.7 Sens Coil Load (MBH) 26.6 Coil Entering DB / WB (F) 76.7 / 65.6 Coil Leaving DB / WB (F) 59.9 / 58.8 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1467

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 41

Space Loads and Airflows


Cooling Sensible (MBH) 26.8 Time of Load Aug 1600 Air Flow (CFM) 1467 Heating Load (MBH) 3.0 Floor Area (ft) 513.6

Zone Name / Space Name Zone 1 L4-Rm1

Mult. 1

Space CFM/ft 2.86

Hourly Analysis Program v4.61

Page 52 of 73

Zone Sizing Summary for L4-Rm10


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm10 TERM SPLT-FC Number of zones Floor Area Location 1 481.9 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 25.3 Design Air Flow (CFM) 1385 Minimum Air Flow (CFM) 1385 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 481.9

Zone Name Zone 1

Zone CFM/ft 2.87

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 28.7 Sens Coil Load (MBH) 25.0 Coil Entering DB / WB (F) 76.7 / 65.6 Coil Leaving DB / WB (F) 59.9 / 58.9 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1385

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 39

Space Loads and Airflows


Cooling Sensible (MBH) 25.3 Time of Load Oct 1500 Air Flow (CFM) 1385 Heating Load (MBH) 1.6 Floor Area (ft) 481.9

Zone Name / Space Name Zone 1 L4-Rm10

Mult. 1

Space CFM/ft 2.87

Hourly Analysis Program v4.61

Page 53 of 73

Zone Sizing Summary for L4-Rm11


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm11 TERM SPLT-FC Number of zones Floor Area Location 1 493.7 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 26.1 Design Air Flow (CFM) 1429 Minimum Air Flow (CFM) 1429 Time of Peak Load Aug 1600 Maximum Heating Load (MBH) 3.0 Zone Floor Area (ft) 493.7

Zone Name Zone 1

Zone CFM/ft 2.89

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 29.5 Sens Coil Load (MBH) 25.6 Coil Entering DB / WB (F) 77.1 / 66.0 Coil Leaving DB / WB (F) 60.4 / 59.4 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1600

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1429

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 40

Space Loads and Airflows


Cooling Sensible (MBH) 26.1 Time of Load Aug 1600 Air Flow (CFM) 1429 Heating Load (MBH) 3.0 Floor Area (ft) 493.7

Zone Name / Space Name Zone 1 L4-Rm11

Mult. 1

Space CFM/ft 2.89

Hourly Analysis Program v4.61

Page 54 of 73

Zone Sizing Summary for L4-Rm2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm2 TERM SPLT-FC Number of zones Floor Area Location 1 502.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 26.1 Design Air Flow (CFM) 1429 Minimum Air Flow (CFM) 1429 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 502.0

Zone Name Zone 1

Zone CFM/ft 2.85

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 29.6 Sens Coil Load (MBH) 25.6 Coil Entering DB / WB (F) 76.7 / 65.7 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1429

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 40

Space Loads and Airflows


Cooling Sensible (MBH) 26.1 Time of Load Oct 1500 Air Flow (CFM) 1429 Heating Load (MBH) 1.6 Floor Area (ft) 502.0

Zone Name / Space Name Zone 1 L4-Rm2

Mult. 1

Space CFM/ft 2.85

Hourly Analysis Program v4.61

Page 55 of 73

Zone Sizing Summary for L4-Rm3


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm3 TERM SPLT-FC Number of zones Floor Area Location 1 502.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 26.1 Design Air Flow (CFM) 1429 Minimum Air Flow (CFM) 1429 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 502.0

Zone Name Zone 1

Zone CFM/ft 2.85

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 29.6 Sens Coil Load (MBH) 25.6 Coil Entering DB / WB (F) 76.7 / 65.7 Coil Leaving DB / WB (F) 60.1 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1429

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 40

Space Loads and Airflows


Cooling Sensible (MBH) 26.1 Time of Load Oct 1500 Air Flow (CFM) 1429 Heating Load (MBH) 1.6 Floor Area (ft) 502.0

Zone Name / Space Name Zone 1 L4-Rm3

Mult. 1

Space CFM/ft 2.85

Hourly Analysis Program v4.61

Page 56 of 73

Zone Sizing Summary for L4-Rm4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm4 TERM SPLT-FC Number of zones Floor Area Location 1 652.8 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 29.4 Design Air Flow (CFM) 1608 Minimum Air Flow (CFM) 1608 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 2.0 Zone Floor Area (ft) 652.8

Zone Name Zone 1

Zone CFM/ft 2.46

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 33.7 Sens Coil Load (MBH) 29.1 Coil Entering DB / WB (F) 76.9 / 65.8 Coil Leaving DB / WB (F) 60.1 / 59.0 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1608

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 49

Space Loads and Airflows


Cooling Sensible (MBH) 29.4 Time of Load Oct 1500 Air Flow (CFM) 1608 Heating Load (MBH) 2.0 Floor Area (ft) 652.8

Zone Name / Space Name Zone 1 L4-Rm4

Mult. 1

Space CFM/ft 2.46

Hourly Analysis Program v4.61

Page 57 of 73

Zone Sizing Summary for L4-Rm5


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm5 TERM SPLT-FC Number of zones Floor Area Location 1 502.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 25.9 Design Air Flow (CFM) 1415 Minimum Air Flow (CFM) 1415 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 502.0

Zone Name Zone 1

Zone CFM/ft 2.82

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 29.3 Sens Coil Load (MBH) 25.3 Coil Entering DB / WB (F) 76.8 / 65.8 Coil Leaving DB / WB (F) 60.2 / 59.2 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1415

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 40

Space Loads and Airflows


Cooling Sensible (MBH) 25.9 Time of Load Oct 1500 Air Flow (CFM) 1415 Heating Load (MBH) 1.6 Floor Area (ft) 502.0

Zone Name / Space Name Zone 1 L4-Rm5

Mult. 1

Space CFM/ft 2.82

Hourly Analysis Program v4.61

Page 58 of 73

Zone Sizing Summary for L4-Rm6


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm6 TERM SPLT-FC Number of zones Floor Area Location 1 502.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 25.9 Design Air Flow (CFM) 1415 Minimum Air Flow (CFM) 1415 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 502.0

Zone Name Zone 1

Zone CFM/ft 2.82

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 29.3 Sens Coil Load (MBH) 25.3 Coil Entering DB / WB (F) 76.8 / 65.8 Coil Leaving DB / WB (F) 60.2 / 59.2 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1415

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 40

Space Loads and Airflows


Cooling Sensible (MBH) 25.9 Time of Load Oct 1500 Air Flow (CFM) 1415 Heating Load (MBH) 1.6 Floor Area (ft) 502.0

Zone Name / Space Name Zone 1 L4-Rm6

Mult. 1

Space CFM/ft 2.82

Hourly Analysis Program v4.61

Page 59 of 73

Zone Sizing Summary for L4-Rm7


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm7 TERM SPLT-FC Number of zones Floor Area Location 1 502.0 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 25.9 Design Air Flow (CFM) 1415 Minimum Air Flow (CFM) 1415 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 502.0

Zone Name Zone 1

Zone CFM/ft 2.82

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 29.3 Sens Coil Load (MBH) 25.3 Coil Entering DB / WB (F) 76.8 / 65.8 Coil Leaving DB / WB (F) 60.2 / 59.2 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1415

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 40

Space Loads and Airflows


Cooling Sensible (MBH) 25.9 Time of Load Oct 1500 Air Flow (CFM) 1415 Heating Load (MBH) 1.6 Floor Area (ft) 502.0

Zone Name / Space Name Zone 1 L4-Rm7

Mult. 1

Space CFM/ft 2.82

Hourly Analysis Program v4.61

Page 60 of 73

Zone Sizing Summary for L4-Rm8


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm8 TERM SPLT-FC Number of zones Floor Area Location 1 531.9 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 24.1 Design Air Flow (CFM) 1318 Minimum Air Flow (CFM) 1318 Time of Peak Load Aug 0800 Maximum Heating Load (MBH) 2.2 Zone Floor Area (ft) 531.9

Zone Name Zone 1

Zone CFM/ft 2.48

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 27.9 Sens Coil Load (MBH) 23.7 Coil Entering DB / WB (F) 76.5 / 65.6 Coil Leaving DB / WB (F) 59.8 / 58.7 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 0800

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1318

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 42

Space Loads and Airflows


Cooling Sensible (MBH) 24.1 Time of Load Aug 0800 Air Flow (CFM) 1318 Heating Load (MBH) 2.2 Floor Area (ft) 531.9

Zone Name / Space Name Zone 1 L4-Rm8

Mult. 1

Space CFM/ft 2.48

Hourly Analysis Program v4.61

Page 61 of 73

Zone Sizing Summary for L4-Rm9


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type L4-Rm9 TERM SPLT-FC Number of zones Floor Area Location 1 481.9 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 25.3 Design Air Flow (CFM) 1385 Minimum Air Flow (CFM) 1385 Time of Peak Load Oct 1500 Maximum Heating Load (MBH) 1.6 Zone Floor Area (ft) 481.9

Zone Name Zone 1

Zone CFM/ft 2.87

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 28.7 Sens Coil Load (MBH) 25.0 Coil Entering DB / WB (F) 76.7 / 65.6 Coil Leaving DB / WB (F) 59.9 / 58.9 Water Flow @ 10.0 F (gpm) Time of Peak Load Sep 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 1385

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 39

Space Loads and Airflows


Cooling Sensible (MBH) 25.3 Time of Load Oct 1500 Air Flow (CFM) 1385 Heating Load (MBH) 1.6 Floor Area (ft) 481.9

Zone Name / Space Name Zone 1 L4-Rm9

Mult. 1

Space CFM/ft 2.87

Hourly Analysis Program v4.61

Page 62 of 73

Zone Sizing Summary for Loft Floor


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type Loft Floor TERM VRF Number of zones Floor Area Location 4 5783.2 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 23.7 34.1 37.2 178.4 Design Air Flow (CFM) 1298 1864 2036 9753 Minimum Air Flow (CFM) 1298 1864 2036 9753 Time of Peak Load Oct 1500 Jul 1500 Oct 1500 Aug 1600 Maximum Heating Load (MBH) 1.5 1.7 1.6 10.4 Zone Floor Area (ft) 496.9 922.3 618.2 3745.8

Zone Name Zone 1 Zone 2 Zone 3 Zone 4

Zone CFM/ft 2.61 2.02 3.29 2.60

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 30.0 42.2 43.1 290.5 Sens Coil Load (MBH) 24.5 34.4 37.1 208.6 Coil Entering DB / WB (F) 77.4 / 66.2 76.9 / 66.0 77.0 / 65.8 79.6 / 68.1 Coil Leaving DB / WB (F) 59.8 / 58.8 59.7 / 58.7 60.0 / 59.0 59.7 / 58.7 Water Flow @ 10.0 F (gpm) Time of Peak Load Oct 1500 Aug 1500 Oct 1500 Jul 1500

Zone Name Zone 1 Zone 2 Zone 3 Zone 4

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 Htg Coil Water Flow @20.0 F (gpm) 0.00 0.00 0.00 0.00

Zone Name Zone 1 Zone 2 Zone 3 Zone 4

Heating Coil Load (MBH) 0.0 0.0 0.0 0.0

Fan Design AirFlow (CFM) 1298 1864 2036 9753

Fan Motor (BHP) 0.000 0.000 0.000 0.000

Fan Motor (kW) 0.000 0.000 0.000 0.000

OA Vent Design AirFlow (CFM) 75 55 67 1424

Space Loads and Airflows


Cooling Sensible (MBH) 23.7 34.1 37.2 178.4 Time of Load Oct 1500 Jul 1500 Oct 1500 Aug 1600 Air Flow (CFM) 1298 1864 2036 9753 Heating Load (MBH) 1.5 1.7 1.6 10.4 Floor Area (ft) 496.9 922.3 618.2 3745.8

Zone Name / Space Name Zone 1 LF Waiting Area Zone 2 LF L.Lobby & Corridor Zone 3 LF Biz Center Zone 4 Indian Restaurant

Mult. 1 1 1 1

Space CFM/ft 2.61 2.02 3.29 2.60

Hourly Analysis Program v4.61

Page 63 of 73

Zone Sizing Summary for Lvl-1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type Lvl-1 TERM VRF Number of zones Floor Area Location 24 7282.1 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 12.3 12.3 12.3 14.4 14.1 14.1 12.3 11.4 11.2 11.2 11.2 11.2 12.2 12.2 18.0 5.1 20.9 16.9 14.2 45.0 38.9 30.5 29.9 Design Air Flow (CFM) 675 675 675 675 786 771 771 672 622 610 610 610 610 669 669 986 280 1143 922 777 2458 2125 1667 1633 Minimum Air Flow (CFM) 675 675 675 675 786 771 771 672 622 610 610 610 610 669 669 986 280 1143 922 777 2458 2125 1667 1633 Time of Peak Load Oct 1500 Oct 1500 Oct 1500 Oct 1500 Aug 1600 Aug 1600 Aug 1600 Oct 1500 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0900 Aug 0900 Oct 1500 Aug 1400 Oct 1500 Aug 0800 Jun 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1900 Maximum Heating Load (MBH) 0.8 0.8 0.8 0.8 0.7 0.9 0.9 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 1.0 0.4 2.4 1.8 1.3 3.6 2.1 0.5 1.9 Zone Floor Area (ft) 197.7 197.7 197.7 197.7 202.4 197.1 197.1 180.5 182.2 176.2 176.2 176.2 176.2 202.2 202.2 236.6 177.6 302.9 257.5 378.3 816.6 928.9 568.8 755.6

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24

Zone CFM/ft 3.41 3.41 3.41 3.41 3.88 3.91 3.91 3.72 3.41 3.46 3.46 3.46 3.46 3.31 3.31 4.17 1.58 3.77 3.58 2.05 3.01 2.29 2.93 2.16

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 14.0 14.0 14.0 14.0 16.0 15.8 15.8 13.8 12.8 12.7 12.7 12.7 12.7 13.9 Sens Coil Load (MBH) 12.0 12.0 12.0 12.0 14.0 13.8 13.8 12.2 11.0 10.9 10.9 10.9 10.9 11.9 Coil Entering DB / WB (F) 76.9 / 66.0 76.9 / 66.0 76.9 / 66.0 76.9 / 66.0 77.2 / 66.1 76.9 / 65.8 76.9 / 65.8 76.8 / 65.6 76.6 / 65.8 76.6 / 65.6 76.6 / 65.6 76.6 / 65.6 76.6 / 65.6 76.7 / 65.8 Coil Leaving DB / WB (F) 60.4 / 59.3 60.4 / 59.3 60.4 / 59.3 60.4 / 59.3 60.6 / 59.6 60.3 / 59.2 60.3 / 59.2 60.0 / 58.9 60.1 / 59.1 59.9 / 58.9 59.9 / 58.9 59.9 / 58.9 59.9 / 58.9 60.2 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500 Aug 1500 Aug 1500 Aug 1500 Aug 1600 Jul 1600 Jul 1600 Oct 1500 Jul 0800 Jul 0900 Jul 0900 Jul 0900 Jul 0900 Jul 1400 Page 64 of 73

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Hourly Analysis Program v4.61

Zone Sizing Summary for Lvl-1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Zone Name Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24

Total Coil Load (MBH) 13.9 19.8 6.9 23.1 18.5 16.8 49.4 45.3 34.3 35.1

Sens Coil Load (MBH) 11.9 17.6 5.2 20.4 16.1 13.9 43.1 38.1 29.8 29.3

Coil Entering DB / WB (F) 76.7 / 65.8 76.7 / 65.5 77.8 / 67.3 76.6 / 65.5 76.6 / 65.8 76.9 / 66.1 76.8 / 65.9 76.4 / 65.6 76.5 / 65.5 76.7 / 65.9

Coil Leaving DB / WB (F) 60.2 / 59.1 60.1 / 59.0 60.5 / 59.5 60.0 / 59.0 60.4 / 59.3 60.2 / 59.2 60.5 / 59.5 59.7 / 58.7 59.9 / 58.8 60.0 / 59.0

Water Flow @ 10.0 F (gpm) -

Time of Peak Load Jul 1400 Sep 1500 Jul 1600 Sep 1500 Jul 0900 Jul 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1800

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 Htg Coil Water Flow @20.0 F (gpm) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24

Heating Coil Load (MBH) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Fan Design AirFlow (CFM) 675 675 675 675 786 771 771 672 622 610 610 610 610 669 669 986 280 1143 922 777 2458 2125 1667 1633

Fan Motor (BHP) 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

Fan Motor (kW) 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

OA Vent Design AirFlow (CFM) 22 22 22 22 22 22 22 21 21 21 21 21 21 22 22 24 21 28 25 23 49 56 34 45

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 12.3 12.3 12.3 Time of Load Oct 1500 Oct 1500 Oct 1500 Oct 1500 Air Flow (CFM) 675 675 675 675 Heating Load (MBH) 0.8 0.8 0.8 0.8 Floor Area (ft) 197.7 197.7 197.7 197.7

Zone Name / Space Name Zone 1 L1-SS9 Zone 2 L1-SS10 Zone 3 L1-SS11 Zone 4 L1-SS12 Zone 5 Hourly Analysis Program v4.61

Mult. 1 1 1 1

Space CFM/ft 3.41 3.41 3.41 3.41

Page 65 of 73

Zone Sizing Summary for Lvl-1


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Zone Name / Space Name L1-SS13 Zone 6 L1-SS14 Zone 7 L1-SS15 Zone 8 L1-SS16 Zone 9 L1-SS17 Zone 10 L1-SS18 Zone 11 L1-SS19 Zone 12 L1-SS20 Zone 13 L1-SS21 Zone 14 L1-SS22 Zone 15 L1-SS23 Zone 16 L1-SS24 Zone 17 L1-BOH Zone 18 L1-JS2 Zone 19 L1-JS3 Zone 20 L1-Lift Lobby Zone 21 L1-Corridor3 (R) Zone 22 L1-Corridor2 (Mid) Zone 23 L1-Corridor-1 (Left) Zone 24 L1- FS Sitting

Mult. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Cooling Sensible (MBH) 14.4 14.1 14.1 12.3 11.4 11.2 11.2 11.2 11.2 12.2 12.2 18.0 5.1 20.9 16.9 14.2 45.0 38.9 30.5 29.9

Time of Load Aug 1600 Aug 1600 Aug 1600 Oct 1500 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0900 Aug 0900 Oct 1500 Aug 1400 Oct 1500 Aug 0800 Jun 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1900

Air Flow (CFM) 786 771 771 672 622 610 610 610 610 669 669 986 280 1143 922 777 2458 2125 1667 1633

Heating Load (MBH) 0.7 0.9 0.9 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 1.0 0.4 2.4 1.8 1.3 3.6 2.1 0.5 1.9

Floor Area (ft) 202.4 197.1 197.1 180.5 182.2 176.2 176.2 176.2 176.2 202.2 202.2 236.6 177.6 302.9 257.5 378.3 816.6 928.9 568.8 755.6

Space CFM/ft 3.88 3.91 3.91 3.72 3.41 3.46 3.46 3.46 3.46 3.31 3.31 4.17 1.58 3.77 3.58 2.05 3.01 2.29 2.93 2.16

Hourly Analysis Program v4.61

Page 66 of 73

Zone Sizing Summary for Lvl-2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type Lvl-2 TERM VRF Number of zones Floor Area Location 24 7237.2 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 12.3 12.3 12.3 14.4 14.1 14.1 12.3 11.4 11.2 11.2 11.2 11.2 12.2 12.2 10.6 5.1 20.9 16.9 13.6 45.0 37.3 29.0 27.6 Design Air Flow (CFM) 675 675 675 675 786 771 771 672 622 610 610 610 610 669 669 578 280 1143 922 745 2458 2041 1586 1509 Minimum Air Flow (CFM) 675 675 675 675 786 771 771 672 622 610 610 610 610 669 669 578 280 1143 922 745 2458 2041 1586 1509 Time of Peak Load Oct 1500 Oct 1500 Oct 1500 Oct 1500 Aug 1600 Aug 1600 Aug 1600 Oct 1500 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0900 Aug 0900 Jul 1400 Aug 1400 Oct 1500 Aug 0800 Jun 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1900 Maximum Heating Load (MBH) 0.8 0.8 0.8 0.8 0.7 0.9 0.9 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.7 0.4 2.4 1.8 1.2 3.6 2.0 0.5 1.7 Zone Floor Area (ft) 197.7 197.7 197.7 197.7 202.4 197.1 197.1 180.5 182.2 176.2 176.2 176.2 176.2 202.2 202.2 191.7 177.6 302.9 257.5 378.3 816.6 928.9 568.8 755.6

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24

Zone CFM/ft 3.41 3.41 3.41 3.41 3.88 3.91 3.91 3.72 3.41 3.46 3.46 3.46 3.46 3.31 3.31 3.02 1.58 3.77 3.58 1.97 3.01 2.20 2.79 2.00

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 13.9 13.9 13.9 15.9 15.7 15.7 13.8 12.8 12.7 12.7 12.7 12.7 13.9 Sens Coil Load (MBH) 12.0 12.0 12.0 12.0 14.1 13.8 13.8 12.2 11.0 10.9 10.9 10.9 10.9 11.9 Coil Entering DB / WB (F) 76.9 / 65.9 76.9 / 65.9 76.9 / 65.9 76.9 / 65.9 76.8 / 65.7 76.9 / 65.8 76.9 / 65.8 76.8 / 65.5 76.6 / 65.8 76.6 / 65.6 76.6 / 65.6 76.6 / 65.6 76.6 / 65.6 76.7 / 65.8 Coil Leaving DB / WB (F) 60.4 / 59.3 60.4 / 59.3 60.4 / 59.3 60.4 / 59.3 60.2 / 59.1 60.3 / 59.2 60.3 / 59.2 60.0 / 58.9 60.1 / 59.1 59.9 / 58.9 59.9 / 58.9 59.9 / 58.9 59.9 / 58.9 60.2 / 59.1 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500 Aug 1500 Aug 1500 Aug 1500 Sep 1500 Jul 1600 Jul 1600 Oct 1500 Jul 0800 Jul 0900 Jul 0900 Jul 0900 Jul 0900 Jul 1400 Page 67 of 73

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Hourly Analysis Program v4.61

Zone Sizing Summary for Lvl-2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Zone Name Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24

Total Coil Load (MBH) 13.9 12.5 6.9 23.0 18.5 16.4 49.3 42.9 32.8 32.6

Sens Coil Load (MBH) 11.9 10.6 5.2 20.4 16.1 13.5 43.1 35.9 28.4 27.0

Coil Entering DB / WB (F) 76.7 / 65.8 76.9 / 65.8 77.8 / 67.3 76.6 / 65.5 76.6 / 65.8 76.8 / 65.9 76.8 / 65.9 76.5 / 65.9 76.5 / 65.5 76.6 / 65.9

Coil Leaving DB / WB (F) 60.2 / 59.1 59.9 / 58.9 60.5 / 59.5 60.0 / 59.0 60.4 / 59.3 59.9 / 58.9 60.5 / 59.5 60.2 / 59.2 59.9 / 58.8 60.0 / 59.0

Water Flow @ 10.0 F (gpm) -

Time of Peak Load Jul 1400 Aug 1500 Jul 1600 Sep 1500 Jul 0900 Jul 1600 Aug 1600 Aug 0900 Jun 1800 Jul 1700

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 Htg Coil Water Flow @20.0 F (gpm) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24

Heating Coil Load (MBH) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Fan Design AirFlow (CFM) 675 675 675 675 786 771 771 672 622 610 610 610 610 669 669 578 280 1143 922 745 2458 2041 1586 1509

Fan Motor (BHP) 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

Fan Motor (kW) 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

OA Vent Design AirFlow (CFM) 22 22 22 22 22 22 22 21 21 21 21 21 21 22 22 22 21 28 25 23 49 56 34 45

Space Loads and Airflows


Cooling Sensible (MBH) 12.3 12.3 12.3 12.3 Time of Load Oct 1500 Oct 1500 Oct 1500 Oct 1500 Air Flow (CFM) 675 675 675 675 Heating Load (MBH) 0.8 0.8 0.8 0.8 Floor Area (ft) 197.7 197.7 197.7 197.7

Zone Name / Space Name Zone 1 L2-SS9 Zone 2 L2-SS10 Zone 3 L2-SS11 Zone 4 L2-SS12 Zone 5 Hourly Analysis Program v4.61

Mult. 1 1 1 1

Space CFM/ft 3.41 3.41 3.41 3.41

Page 68 of 73

Zone Sizing Summary for Lvl-2


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Zone Name / Space Name L2-SS13 Zone 6 L2-SS14 Zone 7 L2-SS15 Zone 8 L2-SS16 Zone 9 L2-SS17 Zone 10 L2-SS18 Zone 11 L2-SS19 Zone 12 L2-SS20 Zone 13 L2-SS21 Zone 14 L2-SS22 Zone 15 L2-SS23 Zone 16 L2-SS24 Zone 17 L2-BOH Zone 18 L2-JS2 Zone 19 L2-JS3 Zone 20 L2-Lift Lobby Zone 21 L2-Corridor3 (R) Zone 22 L2-Corridor2 (Mid) Zone 23 L2-Corridor-1 (Left) Zone 24 L2- FS Sitting

Mult. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Cooling Sensible (MBH) 14.4 14.1 14.1 12.3 11.4 11.2 11.2 11.2 11.2 12.2 12.2 10.6 5.1 20.9 16.9 13.6 45.0 37.3 29.0 27.6

Time of Load Aug 1600 Aug 1600 Aug 1600 Oct 1500 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0800 Aug 0900 Aug 0900 Jul 1400 Aug 1400 Oct 1500 Aug 0800 Jun 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1900

Air Flow (CFM) 786 771 771 672 622 610 610 610 610 669 669 578 280 1143 922 745 2458 2041 1586 1509

Heating Load (MBH) 0.7 0.9 0.9 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.7 0.4 2.4 1.8 1.2 3.6 2.0 0.5 1.7

Floor Area (ft) 202.4 197.1 197.1 180.5 182.2 176.2 176.2 176.2 176.2 202.2 202.2 191.7 177.6 302.9 257.5 378.3 816.6 928.9 568.8 755.6

Space CFM/ft 3.88 3.91 3.91 3.72 3.41 3.46 3.46 3.46 3.46 3.31 3.31 3.02 1.58 3.77 3.58 1.97 3.01 2.20 2.79 2.00

Hourly Analysis Program v4.61

Page 69 of 73

Zone Sizing Summary for Lvl-3,4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type Lvl-3,4 TERM VRF Number of zones Floor Area Location 28 9361.2 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 12.3 12.3 12.3 12.3 16.4 16.1 16.1 13.9 12.5 12.2 12.2 12.2 12.2 13.7 13.7 10.6 5.1 23.5 17.6 13.6 53.2 37.3 29.0 27.6 35.0 32.2 13.6 11.1 Design Air Flow (CFM) 675 675 675 675 897 879 879 763 686 670 670 670 670 748 748 578 280 1284 963 745 2908 2041 1586 1509 1914 1763 745 608 Minimum Air Flow (CFM) 675 675 675 675 897 879 879 763 686 670 670 670 670 748 748 578 280 1284 963 745 2908 2041 1586 1509 1914 1763 745 608 Time of Peak Load Oct 1500 Oct 1500 Oct 1500 Oct 1500 Aug 1600 Aug 1600 Aug 1600 Sep 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1400 Aug 1400 Sep 1600 Aug 0800 Jun 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1900 Jul 1800 Jul 0900 Jun 1600 Aug 1500 Maximum Heating Load (MBH) 0.8 0.8 0.8 0.8 1.1 1.3 1.3 1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 0.7 0.4 3.0 2.4 1.2 5.2 2.0 0.5 1.7 0.5 2.0 1.2 1.5 Zone Floor Area (ft) 197.7 197.7 197.7 197.7 202.4 197.1 197.1 180.5 182.2 176.2 176.2 176.2 176.2 202.2 202.2 191.7 177.6 302.9 257.5 378.3 816.6 928.9 568.8 755.6 649.5 881.2 378.3 215.0

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 Zone 26 Zone 27 Zone 28

Zone CFM/ft 3.41 3.41 3.41 3.41 4.43 4.46 4.46 4.22 3.76 3.80 3.80 3.80 3.80 3.70 3.70 3.02 1.58 4.24 3.74 1.97 3.56 2.20 2.79 2.00 2.95 2.00 1.97 2.83

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 13.9 13.9 13.9 13.9 18.3 17.8 17.8 15.3 14.1 14.0 Sens Coil Load (MBH) 12.0 12.0 12.0 12.0 16.2 15.9 15.9 13.6 12.3 12.2 Coil Entering DB / WB (F) 76.9 / 65.9 76.9 / 65.9 76.9 / 65.9 76.9 / 65.9 76.5 / 65.3 76.8 / 65.5 76.8 / 65.5 77.2 / 66.0 77.1 / 66.0 76.7 / 65.5 Coil Leaving DB / WB (F) 60.4 / 59.3 60.4 / 59.3 60.4 / 59.3 60.4 / 59.3 59.7 / 58.6 60.0 / 58.9 60.0 / 58.9 60.7 / 59.6 60.4 / 59.4 59.8 / 58.7 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500 Aug 1500 Aug 1500 Aug 1500 Jun 1600 Aug 1600 Aug 1600 Aug 1600 Jul 1600 Jun 1600 Page 70 of 73

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Hourly Analysis Program v4.61

Zone Sizing Summary for Lvl-3,4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Zone Name Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 Zone 26 Zone 27 Zone 28

Total Coil Load (MBH) 14.0 14.0 14.0 15.5 15.5 12.4 6.8 26.0 19.4 16.3 57.8 42.8 32.8 32.6 38.8 38.2 16.3 11.6

Sens Coil Load (MBH) 12.2 12.2 12.2 13.6 13.6 10.6 5.2 23.4 17.0 13.5 51.5 35.9 28.4 27.0 33.9 31.7 13.5 10.5

Coil Entering DB / WB (F) 76.7 / 65.5 76.7 / 65.5 76.7 / 65.5 76.9 / 65.7 76.9 / 65.7 76.9 / 65.8 77.8 / 67.2 76.5 / 65.1 76.6 / 65.6 76.8 / 65.9 76.3 / 65.3 76.5 / 65.9 76.5 / 65.5 76.6 / 65.9 76.6 / 65.7 76.5 / 65.8 76.8 / 65.9 76.2 / 65.2

Coil Leaving DB / WB (F) 59.8 / 58.7 59.8 / 58.7 59.8 / 58.7 60.0 / 58.9 60.0 / 58.9 59.9 / 58.9 60.5 / 59.5 59.6 / 58.5 60.2 / 59.1 59.9 / 58.8 59.8 / 58.8 60.2 / 59.2 59.9 / 58.8 60.0 / 59.0 60.2 / 59.1 59.8 / 58.8 59.9 / 58.8 60.1 / 59.0

Water Flow @ 10.0 F (gpm) -

Time of Peak Load Jun 1600 Jun 1600 Jun 1600 Aug 1500 Aug 1500 Aug 1500 Jul 1600 Sep 1600 Jun 1400 Jul 1600 Jun 1700 Aug 0900 Jun 1800 Jul 1700 Jun 1600 Jul 0900 Jul 1600 Aug 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 0.0 / 0.0 Htg Coil Water Flow @20.0 F (gpm) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 Zone 26 Zone 27 Zone 28

Heating Coil Load (MBH) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Fan Design AirFlow (CFM) 675 675 675 675 897 879 879 763 686 670 670 670 670 748 748 578 280 1284 963 745 2908 2041 1586 1509 1914 1763 745 608

Fan Motor (BHP) 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

Fan Motor (kW) 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000

OA Vent Design AirFlow (CFM) 22 22 22 22 22 22 22 21 21 21 21 21 21 22 22 22 21 28 25 23 49 56 34 45 39 53 23 0

Space Loads and Airflows

Hourly Analysis Program v4.61

Page 71 of 73

Zone Sizing Summary for Lvl-3,4


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Zone Name / Space Name Zone 1 L3-SS9 Zone 2 L3-SS10 Zone 3 L3-SS11 Zone 4 L3-SS12 Zone 5 L3-SS13 Zone 6 L3-SS14 Zone 7 L3-SS15 Zone 8 L3-SS16 Zone 9 L3-SS17 Zone 10 L3-SS18 Zone 11 L3-SS19 Zone 12 L3-SS20 Zone 13 L3-SS21 Zone 14 L3-SS22 Zone 15 L3-SS23 Zone 16 L3-SS24 Zone 17 L3-BOH Zone 18 L3-JS2 Zone 19 L3-JS3 Zone 20 L3-Lift Lobby Zone 21 L3-Corridor3 (R) Zone 22 L3-Corridor2 (Mid) Zone 23 L3-Corridor-1 (Left) Zone 24 L3- FS Sitting Zone 25 L4-Corridor-1 (Left) Zone 26 L4-Corridor2 (Mid) Zone 27 L4-Lift Lobby Zone 28 L4-BOH

Mult. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Cooling Sensible (MBH) 12.3 12.3 12.3 12.3 16.4 16.1 16.1 13.9 12.5 12.2 12.2 12.2 12.2 13.7 13.7 10.6 5.1 23.5 17.6 13.6 53.2 37.3 29.0 27.6 35.0 32.2 13.6 11.1

Time of Load Oct 1500 Oct 1500 Oct 1500 Oct 1500 Aug 1600 Aug 1600 Aug 1600 Sep 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1600 Jul 1400 Aug 1400 Sep 1600 Aug 0800 Jun 1600 Aug 1600 Jul 0900 Jul 1800 Aug 1900 Jul 1800 Jul 0900 Jun 1600 Aug 1500

Air Flow (CFM) 675 675 675 675 897 879 879 763 686 670 670 670 670 748 748 578 280 1284 963 745 2908 2041 1586 1509 1914 1763 745 608

Heating Load (MBH) 0.8 0.8 0.8 0.8 1.1 1.3 1.3 1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 0.7 0.4 3.0 2.4 1.2 5.2 2.0 0.5 1.7 0.5 2.0 1.2 1.5

Floor Area (ft) 197.7 197.7 197.7 197.7 202.4 197.1 197.1 180.5 182.2 176.2 176.2 176.2 176.2 202.2 202.2 191.7 177.6 302.9 257.5 378.3 816.6 928.9 568.8 755.6 649.5 881.2 378.3 215.0

Space CFM/ft 3.41 3.41 3.41 3.41 4.43 4.46 4.46 4.22 3.76 3.80 3.80 3.80 3.80 3.70 3.70 3.02 1.58 4.24 3.74 1.97 3.56 2.20 2.79 2.00 2.95 2.00 1.97 2.83

Hourly Analysis Program v4.61

Page 72 of 73

Zone Sizing Summary for Theme Bar


Project Name: minnandar hotel Prepared by: CPG Corp 04/14/2013 12:56AM

Air System Information


Air System Name Equipment Class Air System Type Theme Bar TERM SPLT-FC Number of zones Floor Area Location 1 4951.6 ft Yangon, Myanmar

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Space CFM Sum of space airflow rates Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Zone Sizing Data


Maximum Cooling Sensible (MBH) 320.2 Design Air Flow (CFM) 19539 Minimum Air Flow (CFM) 19539 Time of Peak Load Aug 1600 Maximum Heating Load (MBH) 33.5 Zone Floor Area (ft) 4951.6

Zone Name Zone 1

Zone CFM/ft 3.95

Terminal Unit Sizing Data - Cooling


Total Coil Load (MBH) 463.7 Sens Coil Load (MBH) 358.6 Coil Entering DB / WB (F) 78.8 / 68.0 Coil Leaving DB / WB (F) 61.7 / 60.7 Water Flow @ 10.0 F (gpm) Time of Peak Load Aug 1500

Zone Name Zone 1

Terminal Unit Sizing Data - Heating, Fan, Ventilation


Heating Coil Ent/Lvg DB (F) -1.0 / -1.0 Htg Coil Water Flow @20.0 F (gpm) 0.00

Zone Name Zone 1

Heating Coil Load (MBH) 0.0

Fan Design AirFlow (CFM) 19539

Fan Motor (BHP) 0.000

Fan Motor (kW) 0.000

OA Vent Design AirFlow (CFM) 2016

Space Loads and Airflows


Cooling Sensible (MBH) 35.9 25.4 26.4 26.1 114.3 129.3 Time of Load Oct 1500 Jul 0800 Mar 1600 Jul 1700 Aug 0800 Mar 1600 Air Flow (CFM) 1961 1389 1443 1426 6249 7071 Heating Load (MBH) 3.1 2.4 2.7 2.9 11.3 11.2 Floor Area (ft) 296.6 325.0 246.0 677.0 1703.5 1703.5

Zone Name / Space Name Zone 1 Theme Bar (Arc Bar Area) Theme Bar (Entrance ) Theme Bar (Open Terrace) Theme Bar (Square Table) Theme Bar Table Area (E) Theme Bar Table Area (W)

Mult. 1 1 1 1 1 1

Space CFM/ft 6.61 4.27 5.87 2.11 3.67 4.15

Hourly Analysis Program v4.61

Page 73 of 73