DOCUMENT No PCPL-0532-4-407-04-09-1

CABLES DATA SHEET

SECTION 4 PAGE 1 OF 4

DATA SHEET A1 1.0 1.1 1.2 1.3 1.4 1.5 1.6 2.0 a) Sl. No 1 a) b) c) d) e) 2 3 4 5 a) b) 6 7 SYSTEM PARTICULAR Nominal Power system Voltages Maximum system voltage for continuous operation System neutral earthing Fault level of the system to which the cable will be connected Ground temperature Design ambient temperature TYPE OF CABLE LAYING Laid side by side, touching Description Power Cables Type-A
3C As required Stranded AL 1.1kV XLPE

kV kV kA rms for Sec Deg C Deg C

0.415 .44 Solidly grounded 50kA 1 35 45 Above Ground/ Cable trench

DESCRIPTION OF CABLES Power Control Cables Cables Type-C1 Type-D 1C to 4C 2.5-70 Stranded Al XLPE PVC HR PVC GI Strip HR PVC 3C to 30C 1.5 & 2.5 Stranded Cu PVC PVC PVC GI Wire/Strip PVC Cu braid

Conductor NO. of wires Size (sq. mm) Stranded Material Core Insulation Material Filler Material Inner Sheath Material Armour Material
Type Outer Sheath Shield wire

Instrumentat ion Cables Type-E 3C to 9C 0.5 Stranded Cu twisted pair PVC PVC PVC GI Wire/Strip PVC Overall Cu braid

Instrumentat ion Cables Type-F IP/4P/10P 0.5 Stranded Cu PVC PVC PVC GI Wire/Strip PVC Individual Pair Cu braid

PVC PVC

GI Strip PVC

DATE:22.06.2006 ISSUE No: P0

DOCUMENT No PCPL-0532-4-407-04-09-1

CABLES DATA SHEET

SECTION 4 PAGE 2 OF 4

DATA SHEET-B SL. # DESCRIPTION UNIT Type of Cable, as per Data sheet A1& A2 A B C D E F

1.0 2.0 2.1 3.0 3.1 3.2 4.0 4.1

Name of Manufacturer Standards as Applicable for the Specified Types of Cables in Data Sheet A1 & A2 Yes/No Whether IS marked? Conductor A1/Cu Stranded Conductors as indicated in Data Sheets Conductor is tinned for Control, Instrumentation Cables Core Insulation PVC/XLPE Core Insulation a) Extruded / Wrapped / any special feature b) Dielectric strength Colour coding for cores a) For Power Cables b) For Control cables Inner Sheath Insulation PVC Outer Sheath Insulation PVC/XLPE Markings on outer sheath a)IS b)Length at one meter intervals Outer Serving/Sheath a) Type b) Fungicide and termite proof Armoura) Material b) Size Rated Voltage, suitable for Earthed system DATE:22.06.2006 ISSUE No: P0
Yes/No Yes/No

Ex/Wr
kV/Cm

4.2 5.0 6.0 6.1 7.0

Yes/No

7.1 8.0

DOCUMENT No PCPL-0532-4-407-04-09-1 SL. # DESCRIPTION

CABLES DATA SHEET UNIT

SECTION 4 PAGE 3 OF 4

Type of Cable, as per Data sheet A1& A2 A B C D E F

9.0

10.0

11.0 12.0

13.0 14.0 15.0

16.0 16.1 16.2 16.3 16.4

a) Conductor temperature for continuous ratings b) Conductor temperatures for 1 Sec short circuit current ratings c) Emergency overload temperature Screening Material, wherever applicable : a) Conductor screening b) Insulation (overall) screening Minimum bending radius Maximum length per drum and weight of drum for cable sizes: a) Up to 10 mm2 b) Up to 70 mm2 Sizes c) For sizes> Drum 70 mm2 (indicate for i) Length each specified ii) Weight size) Max. drum lengths for Control, Instrumentation, Cables Tolerance on drum length a) All tests will be carried out as per applicable standards and any other tests if specified in Section 3 or Data Sheet A1 & 2 of the Specification b) If No, give separate details or deviations here Other Parameters of Cables: Thickness of insulation Diameter under armour Diameter over armour Overall diameter

C C

Mm

m, Kg m, Kg mm2 m kg m m
Yes/No

mm mm mm mm

DATE:22.06.2006 ISSUE No: P0

DOCUMENT No PCPL-0532-4-407-04-09-1 SL. # DESCRIPTION

CABLES DATA SHEET UNIT

SECTION 4 PAGE 4 OF 4

Type of Cable, as per Data sheet A1& A2 A B C D E F

16.5 16.6 16.7 16.8 17.0 17.1 17.2 17.3 17.4 17.5

Weight/ Mtr Resistance/ kM Reactance/ kM Capacitance/ kM Derating factors for variations in: Ambient air temperature Ground temperature Depth of laying Soil Resistivity Method of laying

kGs Ohm Ohm F

DATE:22.06.2006 ISSUE No: P0