You are on page 1of 96

Power Distribution Systems 1.

0-1
January 2003
Ref. No. 0015

Power Distribution
Systems
Contents
Description Page Description Page
Power Distribution Systems Grounding/Ground Fault Protection
System Design Grounding — Equipment,
Basic Principles. . . . . . . . . . . 1.1-1 System, MV System,
LV System . . . . . . . . . . . . . . 1.3-8 1
Modern Electric Power
Technologies . . . . . . . . . . . 1.1-1 Ground Fault Protection . . . . 1.3-12
Goals of System Design . . . 1.1-2 Lightning and Surge
Protection . . . . . . . . . . . . . . 1.3-15
Voltage Classifications; BILs —
Basic Impulse Levels . . . . . 1.1-4 Grounding Electrodes . . . . . . . . 1.3-15
3-phase Transformer Power Quality
Winding Connections . . . . 1.1-5 Terms, Technical Overview . 1.3-16
Types of Systems — Radial, Harmonics and
Loop, Selective, Two-Source, Nonlinear Loads . . . . . . . . . 1.3-20
Sparing Transformer, Spot Other Considerations
Network, Distribution . . . . 1.1-6
Secondary Voltages . . . . . . . 1.3-22
Health Care Facility
Energy Conservation . . . . . . 1.3-23
Design Considerations . . . 1.1-14
Building Control Systems . . 1.3-23
System Analysis
Cogeneration. . . . . . . . . . . . . 1.3-24
Systems Analysis . . . . . . . . . 1.2-1
Emergency Power. . . . . . . . . 1.3-24
Short Circuit Currents . . . . . 1.2-2
Peak Shaving. . . . . . . . . . . . . 1.3-25
Fault Current Waveform
Relationships . . . . . . . . . . . 1.2-3 Computer Power . . . . . . . . . . 1.3-25
Fault Current Calculations Sound Levels. . . . . . . . . . . . . 1.3-27
and Methods Index . . . . . . 1.2-4 Reference Data
Determine X and R from IEEE Protective Relay
Transformer Loss Data . . . 1.2-19 Numbers . . . . . . . . . . . . . . . 1.4-1
Voltage Drop . . . . . . . . . . . . . 1.2-20 Codes and Standards . . . . . . 1.4-4
System Application Considerations Motor Protective
Capacitors Device Data . . . . . . . . . . . . . 1.4-6
Capacitor Switching Chart of Short Circuit Currents
Device Selections. . . . . . . . 1.3-1 for Transformers. . . . . . . . . 1.4-7
Motor Power Factor Transformer Full Load Amperes
Correction . . . . . . . . . . . . . . 1.3-3 and Impedances . . . . . . . . . 1.4-8
Protection/Coordination Transformer Losses . . . . . . . 1.4-9
Overcurrent Protection Power Equipment Losses. . . 1.4-10
and Coordination . . . . . . . . 1.3-5 NEMA Enclosure Definitions 1.4-10
Cable R, X, Z Data . . . . . . . . . 1.4-11
Conductor Ampacities . . . . . 1.4-13
Conductor Temperature
Ratings . . . . . . . . . . . . . . . . 1.4-14
Conduit Fill . . . . . . . . . . . . . . 1.4-16
Formulas and Terms . . . . . . . 1.4-19
Seismic Requirements . . . . . 1.4-20

Designing a Distribution System

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.0-2 Power Distribution Systems
January 2003
Ref. No. 0016

This page intentionally left blank.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-1
January 2003 System Design
Ref. No. 0017

Basic Principles The basic principles or factors requir-


ing consideration during design of
Modern Electric Power
The best distribution system is one the power distribution system include: Technologies
that will, cost effectively and safely,
■ Functions of structure, present Several new factors to consider in
supply adequate electric service to
and future. modern power distribution systems
both present and future probable
■ Life and flexibility of structure. result from two relatively recent
loads — this section is included to aid
changes. The first recent change is
in selecting, designing and installing ■ Locations of service entrance and
such a system. distribution equipment, locations
the beginnings of utility deregulation. 1
The traditional dependence on the
and characteristics of loads,
The function of the electric power utility for problem analysis; energy
locations of unit substations.
distribution system in a building or conservation measurements and
■ Demand and diversity factors techniques; and a simplified cost
installation site is to receive power at
of loads. structure for electricity will change
one or more supply points and deliver
it to the individual lamps, motors, and ■ Sources of power. to some degree in the next decades.
all other electrically operated devices. ■ Continuity and quality of power The second change is less obvious
The importance of the distribution available and required. to the designer yet will have an impact
system to the function of a building ■ Energy efficiency and management. on the types of equipment and sys-
makes it almost imperative that the tems being designed. It is the dimin-
■ Distribution and utilization voltages.
best system be designed and installed. ishing quantity of qualified building
■ Bus and/or cable feeders. electrical operators; maintenance
In order to design the best distribution ■ Switchgear and distribution departments; and facility engineers.
system, the system design engineer equipment.
must have information concerning the Modern electric power technologies
■ Power and lighting panelboards
loads and a knowledge of the various may be of use to the designer and
and motor control centers.
types of distribution systems that are building owner in addressing these
applicable. The various categories of ■ Types of lighting fixtures. new challenges. The advent of micro-
buildings have many specific design ■ Installation methods. processor devices (smart devices)
challenges, but certain basic principles ❑ Degree of power equipment into power distribution equipment has
are common to all. Such principles, monitoring. expanded facility owners’ options and
if followed, will provide a soundly capabilities, allowing for automated
executed design. communication of vital power system
information (both energy data and
system operation information) and
electrical equipment control.
These technologies may be grouped as:
■ Power monitoring and control.
■ Building management systems
interfaces.
■ Lighting control.
■ Automated energy management.

Various sections of this guide cover


the application and selection of such
systems and components that may be
incorporated into the power equip-
ment being designed. See Sections 2
and 28.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-2 Power Distribution Systems
System Design January 2003
Ref. No. 0018

Goals of System Design 2. Minimum Initial Investment:


The owner’s overall budget for
4. Maximum Flexibility and
Expandability: In many industrial
When considering the design of an first cost purchase and installa- manufacturing plants, electrical
electrical distribution system for a tion of the electrical distribution utilization loads are periodically
given customer and facility, the electri- system and electrical utilization relocated or changed requiring
cal engineer must consider alternate equipment will be a key factor changes in the electrical distribu-
design approaches which best fit the in determining which of various tion system. Consideration of the
following overall goals. alternate system designs are to be layout and design of the electrical
1 selected. When trying to minimize distribution system to accommo-
1. Safety: The No. 1 goal is to design initial investment for electrical date these changes must be con-
a power system which will not equipment, consideration should sidered. For example, providing
present any electrical hazard to be given to the cost of installation, many smaller transformers or
the people who utilize the facility, floor space requirements and pos- loadcenters associated with a
and/or the utilization equipment sible extra cooling requirements as given area or specific groups of
fed from the electrical system. well as the initial purchase price. machinery may lend more flexibil-
It is also important to design a ity for future changes than one
system which is inherently safe 3. Maximum Service Continuity: large transformer; the use of plug-
for the people who are responsi- The degree of service continuity in busways to feed selected equip-
ble for electrical equipment and reliability needed will vary ment in lieu of conduit and wire
maintenance and upkeep. depending on the type and use may facilitate future revised equip-
of the facility as well as the loads ment layouts.
The National Electrical CodeT or processes being supplied by
(NEC) as well as local electrical the electrical distribution system. In addition, consideration must be
codes provide minimum stan- For example, for a smaller com- given to future building expansion,
dards and requirements in mercial office building a power and/or increased load require-
the area of wiring design and outage of considerable time, say ments due to added utilization
protection, wiring methods and several hours, may be acceptable, equipment when designing the
materials as well as equipment for whereas in a larger commercial electrical distribution system.
general use with the overall goal building or industrial plant only In many cases considering trans-
of providing safe electrical distri- a few minutes may be acceptable. formers with increased capacity
bution systems and equipment. In other facilities such as hospitals, or fan cooling to serve unexpected
The NEC also covers minimum many critical loads permit a maxi- loads as well as including spare
requirements for special occupan- mum of 10 seconds outage and additional protective devices and/
cies including hazardous loca- certain loads, such as real-time or provision for future addition of
tions and special use type facilities computers, cannot tolerate a loss these devices may be desirable.
such as health care facilities, of power for even a few cycles. Also to be considered is increasing
places of assembly, theaters, etc. appropriate circuit capacities or
Typically, service continuity and quantities for future growth.
and the equipment and systems reliability can be increased by:
located in these facilities. Special Power monitoring communication
equipment and special conditions A. Supplying multiple utility power systems connected to electronic
such as emergency systems, sources or services. metering can provide the trending
standby systems and communica- and historical data necessary for
B. Supplying multiple connection
tion systems are also covered in future capacity growth.
paths to the loads served.
the code.
C. Using short-time rated power
It is the responsibility of the
circuit breakers.
design engineer to be familiar
with the code requirements as D. Providing alternate customer-
well as the customer’s facility, owned power sources such as
process, and operating procedures; generators or batteries supplying
to design a system which protects uninterruptable power supplies.
personnel from electrical live
conductors and utilizes adequate E. Selecting the highest quality elec-
circuit protective devices which trical equipment and conductors.
will selectively isolate overloaded F. Using the best installation methods.
or faulted circuits or equipment
as quickly as possible. G. Designing appropriate system
alarms, monitoring and diagnostics.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-3
January 2003 System Design
Ref. No. 0019

5. Maximum Electrical Efficiency 7. Maximum Power Quality: Summary


(Minimum Operating Costs): The power input requirements of
Electrical efficiency can generally all utilization equipment has to be It is to be expected that the engineer
be maximized by designing sys- considered including the accept- will never have complete load infor-
tems that minimize the losses in able operating range of the equip- mation available when the system is
conductors, transformers and utili- ment and the electrical distribution designed. The engineer will have to
zation equipment. Proper voltage system has to be designed to meet expand the information made avail-
level selection plays a key factor in these needs. For example, what able to him on the basis of experience
this area and will be discussed is the required input voltage, cur- with similar problems. Of course, it 1
later. Selecting equipment, such rent, power factor requirement? is desirable that the engineer has as
as transformers, with lower oper- Consideration to whether the much definite information as possible
ating losses, generally means loads are affected by harmonics concerning the function, requirements,
higher first cost and increased (multiples of the basic 60 cycle and characteristics of the utilization
floor space requirements; thus, per second sine wave) or generate devices. The engineer should know
there is a balance to be considered harmonics must be taken into whether certain loads function
between the owner’s utility energy account as well as transient separately or together as a unit,
change for the losses in the trans- voltage phenomena. the magnitude of the demand of the
former or other equipment versus loads viewed separately and as units,
the owner’s first cost budget and The above goals are interrelated the rated voltage and frequency of the
cost of money. and in some ways contradictory. devices, their physical location with
As more redundancy is added to respect to each other and with respect
6. Minimum Maintenance Cost: the electrical system design along to the source and the probability and
Usually the simpler the electrical with the best quality equipment possibility of the relocation of load
system design and the simpler to maximize service continuity, devices and addition of loads
the electrical equipment, the less flexibility and expandability, and in the future.
the associated maintenance costs power quality, the more initial
and operator errors. As electrical investment and maintenance Coupled with this information, a
systems and equipment become are increased. Thus, the designer knowledge of the major types of electric
more complicated to provide must weigh each factor based power distribution systems equips the
greater service continuity or on the type of facility, the loads engineers to arrive at the best system
flexibility, the maintenance costs to be served, the owner’s past design for the particular building.
and chance for operator error experience and criteria. It is beyond the scope of this book to
increases. The systems should be present a detailed discussion of loads
designed with an alternate power that might be found in each of several
circuit to take electrical equipment types of buildings. Assuming that the
(requiring periodic maintenance) design engineer has assembled the
out of service without dropping necessary load data, the following
essential loads. Use of drawout pages discuss some of the various
type protective devices such as types of electrical distribution systems
breakers and combination starters being utilized today. A discussion of
can also minimize maintenance short circuit calculations, coordination,
cost and out-of-service time. voltage selection, voltage drop, ground
fault protection, motor protection, and
other specific equipment protection
is presented.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-4 Power Distribution Systems
System Design January 2003
Ref. No. 0020

Voltage Classifications Table 1.1-3. Metal-Enclosed Switchgear


Voltage and Insulation Levels
Voltage Recommendations by
ANSI and IEEE standards define (From ANSI C37.20.3-1987) Motor Horsepower
various voltage classifications for Rated Maximum Impulse Factors affecting the selection of
single-phase and 3-phase systems. Voltage (kV rms) Withstand (kV) motor operating voltage include:
The terminology used divides voltage
4.76 60 ■ Motor, motor starter and cable
classes into: 8.25 75 first cost.
15.0 95
1 ■ Low voltage
15.5 110
■ Motor, motor starter and cable
■ Medium voltage installation cost.
25.8 125
■ High voltage 38.0 150 ■ Motor and cable losses.
■ Extra-high voltage ■ Motor availability.
Table 1.1-4. Liquid-Immersed Transformers ■ Voltage drop.
■ Ultra-high voltage
Voltage and Basic Lightning Impulse
Insulation Levels (BIL) ■ Qualifications of the building
Table 1.1-1 presents the nominal sys- operating staff; and many more.
tem voltages for these classifications. (From ANSI/IEEE C57.12.00-1993)
Applica- Nominal BIL The following table is based in part
Table 1.1-1. Standard Nominal System tion System (kV crest) 1 on the above factors and experience.
Voltages and Voltage Ranges Voltage
Since all the factors affecting the selec-
(From IEEE Standard 141-1993) (kV rms)
tion are rarely known, it is only an
Voltage Nominal System Voltage Distribu- 1.2 30 — — — approximate guideline.
Class 3-Wire 4-Wire tion 2.5 45 — — —
5.0 60 — — — Table 1.1-6. Selection of Motor Horsepower
Low Voltage 240/120 208Y/120
8.7 75 — — — Ratings as a Function of System Voltage
240 240/120
15.0 95 — — — Motor Voltage Motor System
480 480Y/277
25.0 150 125 — — (Volts) Hp Range Voltage
600 —
34.5 200 150 125 —
Medium Voltage 2,400 4160Y/2400 460 up to 500 480
46.0 250 200 — —
4,160 8320Y/4800 2,300 250 to 2000 2,400
69.0 350 250 — —
4,800 12000Y/6930 4,000 250 to 3000 4,160
6,900 12470Y/7200 Power 1.2 45 30 — —
2.5 60 45 — — 4,600 250 to 3000 4,800
13,200 13200Y/7620
5.0 75 60 — — 13,200 above 2000 13,800
13,800 13800Y/7970
23,000 20780Y/12000 8.7 95 75 — —
34,500 22860Y/13200 15.0 110 95 — —
46,000 24940Y/14400 25.0 150 — — —
69,000 34500Y/19920
34.5 200 — — —
High Voltage 115,000 — 46.0 250 200 — —
138,000 — 69.0 350 250 — —
161,000 —
115.0 550 450 350 —
230,000 —
138.0 650 550 450 —
Extra-High Voltage 345,000 — 161.0 750 650 550 —
500,000 —
230.0 900 825 750 650
765,000 —
345.0 1,175 1,050 900 —
Ultra-High Voltage 1,100,000 — 500.0 1,675 1,550 1,425 1,300
765.0 2,050 1,925 1,800 —
BIL — Basic Impulse Levels 1 BIL values in bold typeface are listed as
standard. Others listed are in common use.
ANSI standards define recommended
and required BIL levels for: Table 1.1-5. Dry-Type Transformers Voltage and Basic Lightning Impulse Insulation Levels (BIL)
(From ANSI/IEEE C57.12.01-1989)
■ Metal-Clad Switchgear
(typically vacuum breakers). Nominal System BIL (kV crest)
Voltage (kV rms) 10 20 30 45 60 95 110 125 150 200
■ Metal-Enclosed Switchgear (typi-
cally load interrupters, switches). 1.2 S 1 1 — — — — — — —
■ Liquid Immersed Transformers. 2.5 — S 1 1 — — — — — —
5.0 — — S 1 1 — — — — —
■ Dry-Type Transformers.
8.7 — — — S 1 1 — — — —
Tables 1.1-2 through 1.1-5 contain 15.0 — — — — S 1 1 — — —
those values. 25.0 — — — — — 2 S 1 1 —
34.5 — — — — — — — 2 S 1
Table 1.1-2. Metal-Clad Switchgear Voltage
and Insulation Levels (From ANSI C37.20.2-1993) Note: S = Standard values.
1 = Optional higher levels where exposure to overvoltage occurs and
Rated Maximum Impulse
Voltage (kV rms) Withstand (kV)
higher protection margins are required.
2 = Lower levels where surge arrester protective devices can be applied
4.76 60 with lower spark-over levels.
8.25 95
15.0 95
27.0 125
38.0 150

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-5
January 2003 System Design
Ref. No. 0021

Table 1.1-7. 3-Phase Transformer Winding Connections


Phasor Notes
Diagram

DELTA-DELTA Connection 1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a 3-wire service or a 4-wire service with a mid-tap ground.
Phasor H2 X2
Diagram:

1
H1 H3 X1 X3

Angular Displacement (Degrees): 0

DELTA-WYE Connection 1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a 3-wire service or a 4-wire grounded service with XO grounded.
Phasor H2 X2 3. With XO grounded, the transformer acts as a ground source for the
Diagram:
secondary system.
4. Fundamental and harmonic frequency zero-sequence currents in the secondary
X1 X0
lines supplied by the transformer do not flow in the primary lines. Instead the
zero sequence currents circulate in the closed delta primary windings.
H1 H3 X3 5. When supplied from an effectively grounded primary system does not see load
unbalances and ground faults in the secondary system.
Angular Displacement (Degrees): 30

WYE-DELTA Connection 1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a 3-wire service or a 4-wire delta service with a mid-tap ground.
Phasor H2 X2 3. Grounding the primary neutral of this connection would create a ground source
Diagram:
for the primary system. This could subject the transformer to severe overloading
during a primary system disturbance or load unbalance.
X1
4. Frequently installed with mid-tap ground on one leg when supplying
combination 3-phase and single-phase load where the 3-phase load is much
H1 H3 larger than single-phase load.
X3
5. When used in 25 kV and 35 kV 3-phase 4-wire primary systems,
Angular Displacement (Degrees): 30 ferroresonance can occur when energizing or de-energizing the transformer
using single-pole switches located at the primary terminals. With smaller kVA
transformers the probability of ferroresonance is higher.
WYE-WYE Connection 1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a 3-wire service only, even if XO is grounded.
Phasor H2 X2 3. This connection is incapable of furnishing a stabilized neutral and its use may
Diagram:
result in phase-to-neutral overvoltage (neutral shift) as a result of unbalanced
phase-to-neutral load.
X0 4. If a 3-phase unit is built on a three-legged core, the neutral point of the primary
windings is practically locked at ground potential.
H1 H3 X1 X3

Angular Displacement (Degrees): 0

GROUNDED WYE-WYE Connection 1. Suitable for 4-wire effectively grounded source only.
2. Suitable for a 3-wire service or for 4-wire grounded service with XO grounded.
Phasor H2 X2 3. 3-phase transformers with this connection may experience stray flux tank
Diagram: heating during certain external system unbalances unless the core configuration
utilized provides a return path for the flux.
H0 X0 4. Fundamental and harmonic frequency zero-sequence currents in the secondary
lines supplied by the transformer also flow in the primary lines (and primary
H1 H3 X1 X3 neutral conductor).
5. Ground relay for the primary system may see load unbalances and ground
Angular Displacement (Degrees): 0 faults in the secondary system. This must be considered when coordinating
overcurrent protective devices.
6. 3-phase transformers with the neutral points of the high voltage and low
voltage windings connected together internally and brought out through an
HOXO bushing should not be operated with the HOXO bushing ungrounded
(floating). To do so can result in very high voltages in the secondary systems.
DELTA-DELTA Connection with Tap 1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a 3-wire service or a 4-wire service with a mid-tap ground.
Phasor H2 X2 3. When using the tap for single-phase circuits the single-phase load kVA should
Diagram: not exceed 5% of the 3-phase kVA rating of the transformer. The 3-phase rating
X4
of the transformer is also substantially reduced.

H1 H3 X1 X3

Angular Displacement (Degrees): 0

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-6 Power Distribution Systems
System Design January 2003
Ref. No. 0022

Types of Systems Low voltage feeder circuits run from


the switchgear or switchboard assem-
A fault on the secondary low voltage
bus or in the source transformer will
In the great majority of cases, power blies to panelboards that are located interrupt service to all loads. Service
is supplied by the utility to a building closer to their respective loads as cannot be restored until the necessary
at the utilization voltage. In practically shown in Figure 1.1-1. repairs have been made. A low voltage
all of these cases, the distribution of feeder circuit fault will interrupt service
Each feeder is connected to the switch- to all loads supplied over that feeder.
power within the building is achieved
gear or switchboard bus through a
through the use of a simple radial dis-
1 tribution system. This system is the first
circuit breaker or other overcurrent A modern and improved form of the
protective device. A relatively small conventional simple radial system
type described on the following pages.
number of circuits are used to distribute distributes power at a primary voltage.
In those cases where utility service is power to the loads from the switch- The voltage is stepped down to
available at the building at some volt- gear or switchboard assemblies and utilization level in the several load
age higher than the utilization voltage panelboards. areas within the building typically
to be used, the system design engi- through secondary unit substation
Since the entire load is served from a transformers. The transformers are
neer has a choice of a number of types
single source, full advantage can be usually connected to their associated
of systems which the engineer may
taken of the diversity among the loads. load bus through a circuit breaker, as
use. This discussion covers several
This makes it possible to minimize the shown in Figure 1.1-2. Each secondary
major types of distribution systems
installed transformer capacity. How- unit substation is an assembled unit
and practical modifications of them.
ever, the voltage regulation and effi- consisting of a 3-phase, liquid-filled
1. Simple Radial. ciency of this system may be poor or air-cooled transformer, an integrally
because of the low voltage feeders connected primary fused switch, and
2. Loop-Primary System — and single source. The cost of the low
Radial Secondary System. low voltage switchgear or switchboard
voltage-feeder circuits and their asso- with circuit breakers or fused switches.
3. Primary Selective System — ciated circuit breakers are high when Circuits are run to the loads from these
Secondary Radial System. the feeders are long and the peak low voltage protective devices.
demand is above 1000 kVA.
4. Two-Source Primary —
Secondary Selective System.
5. Sparing Transformer System. Primary Fused Switch
6. Simple Spot Network. Transformer
7. Medium Voltage Distribution
System Design. 600V Class
Switchboard
1. Simple Radial System
The conventional simple radial system
Distribution
receives power at the utility supply Dry-Type
voltage at a single substation and steps Transformer
the voltage down to the utilization level.
In those cases where the customer Distribution MCC Distribution Lighting
receives his supply from the primary Panel Panel Panelboard
system and owns the primary switch
and transformer along with the second-
ary low voltage switchboard or switch- Figure 1.1-1. Simple Radial System
gear, the equipment may take the form
of a separate primary switch, separate
transformer, and separate low voltage
switchgear or switchboard. This equip- 52 Primary Main Breaker
ment may be combined in the form of
an outdoor pad-mounted transformer
with internal primary fused switch 52 52 52 52 52 52 Primary Feeder Breakers
and secondary main breaker feeding
an indoor switchboard.
Another alternative would be a
secondary unit substation where
the primary fused switch, transformer
and secondary switchgear or switch-
board are designed and installed as
a close coupled single assembly.
Secondary Unit
In those cases where the utility owns the Primary Substation
primary equipment and transformer, the Cables
supply to the customer is at the utiliza-
tion voltage, and the service equipment
then becomes low voltage main distri-
bution switchgear or a switchboard. Figure 1.1-2. Primary and Secondary Simple Radial System

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-7
January 2003 System Design
Ref. No. 0023

Since each transformer is located In addition, if only one primary fuse on break switches with load side bus
within a specific load area, it must a circuit opens, the secondary loads are connection) sectionalizing switches
have sufficient capacity to carry the then single phased, causing damage to and primary load break fused switch
peak load of that area. Consequently, low voltage motors. as shown in Figure 1.1-4.
if any diversity exists among the load
area, this modified primary radial Another approach to reducing costs When pad-mounted compartmental-
system requires more transformer is to eliminate the primary feeder ized transformers are utilized, they are
capacity than the basic form of the breakers completely, and utilize a furnished with loop feed oil immersed
simple radial system. However, single primary main breaker or fused gang operated load break sectionaliz- 1
because power is distributed to the switch for protection of a single pri- ing switches and drawout current
load areas at a primary voltage, losses mary feeder circuit with all secondary limiting fuses in dry wells as shown
are reduced, voltage regulation is unit sub-stations supplied from this in Figure 1.1-5. By operating the
improved, feeder circuit costs are circuit. Although this system results appropriate sectionalizing switches,
reduced substantially, and large low in less initial equipment cost, system it is possible to disconnect any section
voltage feeder circuit breakers are reliability is reduced drastically since of the loop conductors from the rest of
eliminated. In many cases the inter- a single fault in any part of the primary the system. In addition, by opening the
rupting duty imposed on the load conductor would cause an outage to transformer primary switch (or remov-
circuit breakers is reduced. all loads within the facility. ing the load break drawout fuses in the
pad-mounted transformer) it is possible
This modern form of the simple radial 2. Loop Primary System — to disconnect any transformer from
system will usually be lower in initial Radial Secondary System the loop.
investment than most other types of
primary distribution systems for build- This system consists of one or more A key interlocking scheme is normally
ings in which the peak load is above “PRIMARY LOOPS” with two or more recommended to prevent closing all
1000 kVA. A fault on a primary feeder transformers connected on the loop. sectionalizing devices in the loop. Each
circuit or in one transformer will cause This system is typically most effective primary loop sectionalizing switch and
an outage to only those secondary when two services are available from the feeder breakers to the loop are
loads served by that feeder or trans- the utility as shown in Figure 1.1-3. Each interlocked such that to be closed they
former. In the case of a primary main primary loop is operated such that one require a key (which is held captive
bus fault or a utility service outage, of the loop sectionalizing switches is until the switch or breaker is opened)
service is interrupted to all loads until kept open to prevent parallel operation and one less key than the number of
the trouble is eliminated. of the sources. When secondary unit key interlock cylinders is furnished.
substations are utilized, each trans- An extra key is provided to defeat the
Reducing the number of transformers former has its own duplex (2-load interlock under qualified supervision.
per primary feeder by adding more
primary feeder circuits will improve
the flexibility and service continuity
of this system; the ultimate being one Primary Main Breaker 1 52 52 Primary Main Breaker 2
secondary unit substation per primary
feeder circuit. This of course increases 52
the investment in the system but Tie
minimizes the extent of an outage 52 52 Breaker 52 52 Loop Feeder Breaker
resulting from a transformer or
primary feeder fault. Loop A
Loop B
Primary connections from one second-
ary unit substation to the next second- NC NO NC NC
ary unit substation can be made with Fault Sensors
“double” lugs on the unit substation
primary switch as shown, or with sep-
arable connectors made in manholes
or other locations.
Depending on the load kVA connected
to each primary circuit and if no ground
fault protection is desired for either the
primary feeder conductors and trans- NC NC NO NC NC NC
formers connected to that feeder or
the main bus, the primary main and/or
feeder breakers may be changed to
primary fused switches. This will sig-
nificantly reduce the first cost, but also
decrease the level of conductor and
equipment protection. Thus, should
a fault or overload condition occur,
downtime increases significantly and Secondary Unit Substations Consisting of:
higher costs associated with increased Duplex Primary Switches/Fused Primary Switches/
Transformer and Secondary Main Feeder Breakers
damage levels and the need for fuse
replacement is typically encountered. Figure 1.1-3. Loop Primary — Radial Secondary System

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-8 Power Distribution Systems
System Design January 2003
Ref. No. 0024

When a primary feeder conductor fault


Loop Loop occurs, the associated loop feeder
Feeder Feeder
breaker opens and interrupts service
Load Break to all loads up to the normally open 52
Loop Switches
primary loop load break switch
(typically half of the loads). Once it is Loop A Loop A
determined which section of primary
cable has been faulted, the loop sec-
1 tionalizing switches on each side of In cases where only one primary line
Fused is available, the use of a single primary
Disconnect the faulted conductor can be opened,
breaker provides the loop connections
Switch the loop sectionalizing switch which to the loads as shown here.
had been previously left open then
closed and service restored to all Figure 1.1-6. Single Primary Feeder —
secondary unit substations while Loop System
the faulted conductor is replaced.
If the fault should occur in a conductor A basic primary loop system which
directly on the load side of one of the utilizes a single primary feeder breaker
loop feeder breakers, the loop feeder connected directly to two loop feeder
breaker is kept open after tripping and switches which in turn then feed the
Figure 1.1-4. Secondary Unit Substation loop is shown in Figure 1.1-6. In this basic
Loop Switching the next load side loop sectionalizing
switch manually opened so that the system the loop may be normally
faulted conductor can be sectionalized operated with one of the loop section-
Loop Loop
and replaced. alizing switches open as described
Feeder Feeder above or with all loop sectionalizing
Load Break Note: Under this condition, all secondary switches closed. If a fault occurs in the
Loop Switches unit substations are supplied through the basic primary loop system, the single
other loop feeder circuit breaker, and thus loop feeder breaker trips, and second-
all conductors around the loop should be
ary loads are lost until the faulted con-
sized to carry the entire load connected to
the loop. Increasing the number of primary
ductor is found and eliminated from
loops (two loops shown in Figure 1.1-6) the loop by opening the appropriate
Load Break loop sectionalizing switches and then
Drawout Fuses will reduce the extent of the outage from a
conductor fault, but will also increase the reclosing the breaker.
system investment.
3. Primary Selective System —
When a transformer fault or overload
occurs, the transformer primary fuses
Secondary Radial System
open, and the transformer primary The primary selective — secondary
switch manually opened, disconnect- radial system, as shown in Figure 1.1-7,
ing the transformer from the loop, differs from those previously described
and leaving all other secondary unit in that it employs at least two primary
Figure 1.1-5. Pad-Mounted Transformer substation loads unaffected. feeder circuits in each load area. It is
Loop Switching
In addition, the two primary main Primary Metal-Clad
breakers which are normally closed
and primary tie breaker which is nor- Switchgear Lineup
52 52 Primary Main Breaker
mally open are either mechanically
or electrically interlocked to prevent Bus A 52 Bus B
paralleling the incoming source lines.
For slightly added cost, an automatic 52 52 52 52 Primary Feeder Breaker
throw-over scheme can be added
between the two main breakers and Feeder A1 Feeder B1 Feeder B2
tie breaker. During the more common To Other
Feeder A2 Substations
event of a utility outage, the automatic
transfer scheme provides significantly NO
reduced power outage time.
The system in Figure 1.1-3 has higher NC
costs than in Figure 1.1-2, but offers
increased reliability and quick restora- NO Typical Secondary Unit
tion of service when 1) a utility outage Substation Duplex Primary
Switch/Fuses
occurs, 2) a primary feeder conductor Transformer/600V Class
NC
fault occurs, or 3) a transformer fault Secondary Switchgear
or overload occurs.
NO
Should a utility outage occur on one of
the incoming lines, the associated pri- NC
mary main breaker is opened and the
tie breaker closed either manually or
through an automatic transfer scheme. Figure 1.1-7. Basic Primary Selective — Radial Secondary System

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-9
January 2003 System Design
Ref. No. 0025

designed so that when one primary or most of the loads, may more than
circuit is out of service, the remaining Primary offset the greater cost. Having two-
Feeders
feeder or feeders have sufficient sources allows for either manual or
capacity to carry the total load. Half automatic transfer of the two primary
of the transformers are normally Non-Load Break main breakers and tie breaker should
connected to each of the two feeders. Selector Switches one of the sources become unavailable.
Inter-
When a fault occurs on one of the lock
primary feeders, only half of the Load Break The primary selective-secondary radial
Disconnect
load in the building is dropped. system, however, may be less costly or 1
Fuses more costly than a primary loop —
Duplex fused switches as shown in secondary radial system of Figure 1.1-3
Figure 1.1-7 and detailed in Figure 1.1-8 depending on the physical location
are the normal choice for this type of the transformers while offering
of system. Each duplex fused switch comparable downtime and reliability.
consists of two (2) load break 3-pole The cost of conductors for the two
switches each in their own separate types of systems may vary greatly
structure, connected together by bus depending on the location of the
bars on the load side. Typically, the transformers and loads within the
load break switch closest to the Figure 1.1-9. Fused Selector Switch in facility and greatly override primary
transformer includes a fuse assembly One Structure switching equipment cost differences
with fuses. Mechanical and/or key between the two systems.
interlocking is furnished such that This means limited cable space espe-
both switches cannot be closed at cially if double lugs are furnished for 4. Two-Source Primary —
the same time (to prevent parallel each line as shown in Figure 1.1-7 and
should a faulted primary conductor Secondary Selective System
operation) and interlocking such that
access to either switch or fuse assem- have to be changed, both lines would This system uses the same principle
bly cannot be obtained unless both have to be deenergized for safe of duplicate sources from the power
switches are opened. changing of the faulted conductors. supply point utilizing two primary
In Figure 1.1-7 when a primary feeder main breakers and a primary tie breaker.
fault occurs the associated feeder The two primary main breakers and
Primary primary tie breaker being either
Feeders breaker opens, and the transformers
normally supplied from the faulted manually or electrically interlocked
feeder are out of service. Then manu- to prevent closing all three at the same
Load Break
ally, each primary switch connected to time and paralleling the sources. Upon
Switches loss of voltage on one source, a man-
the faulted line must be opened and
then the alternate line primary switch ual or automatic transfer to the alter-
can be closed connecting the trans- nate source line may be utilized to
former to the live feeder, thus restoring restore power to all primary loads.
Fuses
service to all loads. Note that each of the Each transformer secondary is
primary circuit conductors for Feeder arranged in a typical double-ended
A1 and B1 must be sized to handle the unit substation arrangement as shown
sum of the loads normally connected in Figure 1.1-10. The two secondary
to both A1 and B1. Similar sizing of main breakers and secondary tie
Feeders A2 and B2, etc., is required. breaker of each unit substation are
If a fault occurs in one transformer, again either mechanically or electrically
the associated primary fuses blow interlocked to prevent parallel opera-
Figure 1.1-8. Duplex Fused Switch in and interrupts the service to just tion. Upon loss of secondary source
Two Structures the load served by that transformer. voltage on one side, manual or auto-
Service cannot be restored to the matic transfer may be utilized to transfer
As an alternate to the duplex switch the loads to the other side, thus restor-
arrangement, a non-load break selector loads normally served by the faulted
transformer until the transformer ing power to all secondary loads.
switch mechanically interlocked with a
load break fused switch can be utilized is repaired or replaced. This arrangement permits quick resto-
as shown in Figure 1.1-9. The non-load ration of service to all loads when a
Cost of the primary selective —
break selector switch is physically primary feeder or transformer fault
secondary radial system is greater
located in the rear of the load break occurs by opening the associated sec-
than that of the simple primary radial
fused switch, thus only requiring one ondary main and closing the second-
system of Figure 1.1-1 because of the
structure and a lower cost and floor ary tie breaker. If the loss of secondary
additional primary main breakers, tie
space savings over the duplex voltage has occurred because of a pri-
breaker, two-sources, increased num-
arrangement. The non-load break mary feeder fault with the associated
ber of feeder breakers, the use of pri-
switch is mechanically interlocked to primary feeder breaker opening, then
mary-duplex or selector switches, and
prevent its operation unless the load all secondary loads normally served
the greater amount of primary feeder
break switch is opened. The main by the faulted feeder would have to
cable required. The benefits from the
disadvantage of the selector switch is be transferred to the opposite primary
reduction in the amount of load lost
that conductors from both circuits are feeder. This means each primary
when a primary feeder is faulted, plus
terminated in the same structure. feeder conductor must be sized to
the quick restoration of service to all
carry the load on both sides of all the
secondary buses it is serving under

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-10 Power Distribution Systems
System Design January 2003
Ref. No. 0026

secondary emergency transfer. If the In either of the above emergency con- transformer is typically about 2/3 base
loss of voltage was due to a failure of ditions, the in-service transformer of nameplate kVA rating. Typically these
one of the transformers in the double- a double-ended unit substation would transformers are furnished with
ended unit substation, then the associ- have to have the capability of serving fan-cooling and/or lower than normal
ated primary fuses would open taking the loads on both sides of the tie temperature rise such that under
only the failed transformer out breaker. For this reason, transformers emergency conditions they can carry
of service, and then only the secondary utilized in this application have equal on a continuous basis the maximum
loads normally served by the faulted kVA rating on each side of the double- load on both sides of the secondary
1 transformer would have to be trans- ended unit substation and the normal tie breaker. Because of this spare
ferred to the opposite transformer. operating maximum load on each transformer capacity, the voltage
regulation provided by the double-
ended unit substation system under
normal conditions is better than that
of the systems previously discussed.
52 52 Primary Main Breakers
The double-ended unit substation
52 arrangement can be utilized in
conjunction with any of the previous
52 52 52 52 Primary Feeder Breakers systems discussed which involve two
primary sources. Although not recom-
To Other Substations mended, if allowed by the utility,
To Other Substations
momentary re-transfer of loads to the
Typical restored source may be made closed
Double-Ended transition (anti-parallel interlock
Unit schemes would have to be defeated)
Substation for either the primary or secondary
systems. Under this condition, all
equipment interrupting and momentary
ratings should be suitable for the fault
current available from both sources.
For double-ended unit substations
equipped with ground fault systems
special consideration to transformer
Primary Fused Transformer Tie Breaker Secondary Main Breaker neutral grounding and equipment
Switch operation should be made — see
“grounding and ground fault protec-
Figure 1.1-10. Two-Source Primary — Secondary Selective System tion.” Where two single-ended unit
substations are connected together
by external tie conductors, it is recom-
mended that a tie breaker be furnished
at each end of the tie conductors.

5. Sparing Transformer System


K K K
The sparing transformer system con-
cept came into use as an alternative
to the capital intensive double-ended
secondary unit substation distribution
system (see Two-Source Primary —
Sparing Transformer Secondary Selective System). It essen-
tially replaces double-ended substations
with single-ended substations and one
K K or more “sparing” transformer substa-
tions all interconnected on a common
secondary bus (see Figure 1.1-11).
Generally no more than 3 to 5 single-
Typical Secondary Busway Loop ended substations are on a sparing loop.
The essence of this design philosophy
is that conservatively designed and
loaded transformers are highly reliable
K K electrical devices and rarely fail.
Typical Single-Ended Substation Therefore, providing a single common
backup transformer for a group of
transformers in lieu of a backup trans-
former for each and every transformer
Figure 1.1-11. Sparing Transformer System System Design still maintains a high
degree of continuity of service.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-11
January 2003 System Design
Ref. No. 0027

Referring to Figure 1.1-11, it is appar- In facilities with no qualified electrical The major advantage of the secondary
ent that the sparing concept backs up power operators, an open transition network system is continuity of ser-
primary switch and primary cable fail- with key interlocking is often a prudent vice. No single fault anywhere on the
ure as well. Restoration of lost or failed design. Note each pair of “main primary system will interrupt service
utility power is accomplished similarly breaker/tie breaker” key cylinders to any of the system’s loads. Most
to primary selective scheme previously should be uniquely keyed to prevent faults will be cleared without inter-
discussed. It is therefore important to any paralleled source operations. rupting service to any load. Another
use an automatic throwover system in outstanding advantage that the net-
a two source lineup of primary switch- Careful sizing of these transformers work system offers is its flexibility 1
gear to restore utility power as dis- as well as careful specification of the to meet changing and growing load
cussed in the “Two-Source Primary” transformers is required for reliability. conditions at minimum cost and
scheme — see Figure 1.1-10. Low temperature rise specified with minimum interruption in service to
continuous overload capacity or other loads on the network. In addition
A major advantage of the sparing upgraded types of transformers to flexibility and service reliability, the
transformer system is the typically should be considered. secondary network system provides
lower base kVA of each transformer. exceptionally uniform and good volt-
In a double-ended substation design, One disadvantage to this system is
the external secondary tie system, age regulation, and its high efficiency
each transformer must be rated to materially reduces the costs of
carry the sum of the loads of two see Figure 1.1-11. As shown, all single-
ended substations are tied together on system losses.
transformers and usually requires the
addition of cooling fans to accomplish the secondary with a tie busway or Three major differences between the
this rating. In the “sparing” concept cable system. Location of substations network system and the simple radial
each transformer carries only its own is therefore limited because of voltage system account for the outstanding
load, which is typically not a fan- drop and cost considerations. advantages of the network. First,
cooled rating. As base kVA declines, Routing of busway, if used, must be a network protector is connected in
first cost, size, losses, secondary main carefully layed out. It should also be the secondary leads of each network
breaker ampacity, and short circuit noted, that a tie busway or cable fault transformer in place of, or in addition
current (and potentially secondary will essentially prevent the use of the to, the secondary main breaker, as
breaker interrupting capacities and, sparing transformer until it is repaired. shown in Figure 1.1-12. Also, the
therefore, cost) are reduced. Major Commonly, the single-ended substa- secondaries of each transformer in
space savings is also a benefit of tions and the sparing transformer a given location (spot) are connected
this system. must be clustered. This can also be together by a switchgear or ring bus
an advantage, as more kVA can be from which the loads are served over
The sparing transformer system short radial feeder circuits. Finally, the
operates as follows: supported from a more compact
space layout. primary supply has sufficient capacity
■ All main breakers, including the to carry the entire building load with-
sparing main breaker are normally 6. Simple Spot Network Systems out overloading when any one primary
closed; the tie breakers are normally feeder is out of service.
The AC secondary network system
open. is the system that has been used for A network protector is a specially
■ Once a transformer (or primary many years to distribute electric power designed heavy duty air power
cable or primary switch/fuse) fails, in the high-density, downtown areas breaker, spring close with electrical
the associated secondary main of cities, usually in the form of utility motor-charged mechanism, or motor
breaker is opened. The associated grids. Modifications of this type of operated mechanism, with a network
tie breaker is then closed, which system make it applicable to serve relay to control the status of the pro-
restores power to the single-ended loads within buildings. tector (tripped or closed). The network
substation bus. relay is usually a solid-state micropro-
■ Schemes which require the main cessor-based component integrated
to be opened before the tie is closed
(“open transition”), and which allow
any tie to be closed before the Typical Feeder
substation main is opened, Primary Circuit
(“closed transition”) are possible. To Other
Networks
Network Transformer
With a closed transition scheme it is
common to add a timer function that Network Protector
opens the tie breaker unless either Fuses
main breaker is opened within a time
Optional Main, 50/51
interval. This closed transition allows Relaying and/or
power to be transferred to the sparing Network Disconnect Tie Tie
transformer without interruption, such Drawout
Low Voltage
as for routine maintenance, and then LV Feeder NC NC Switchgear
back to the substation. This closed
transition transfer has an advantage in
some facilities, however, appropriate Customer Customer Customer
Loads Loads Loads
interrupting capacities and bus
bracing must be specified suitable for
the momentary parallel operation. Figure 1.1-12. Three-Source Spot Network

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-12 Power Distribution Systems
System Design January 2003
Ref. No. 0028

into the protector enclosure which have been made, the system can be They are also economical when
functions to automatically close the restored to normal operating condi- compared to two transformer double-
protector only when the voltage tions by closing the primary feeder ended substations with normally
conditions are such that its associated breaker. All network protectors opened tie breakers.
transformer will supply power to the associated with that feeder will
secondary network loads, and to auto- close automatically. 7. Medium Voltage Distribution
matically open the protector when System Design
power flows from the secondary to the The chief purpose of the network bus
1 network transformer. The purpose of normally closed ties is to provide for
a. Single Bus, Figure 1.1-13
the network protector is to protect the the sharing of loads and a balancing
of load currents for each primary ser- The sources (utility and/or genera-
integrity of the network bus voltage
vice and transformer regardless of tor(s)) are connected to a single bus.
and the loads served from it against
the condition of the primary services. All feeders are connected to the same
transformer and primary feeder faults
bus. Generators are used where
by quickly disconnecting the defective Also, the ties provide a means for cogeneration is employed.
feeder-transformer pair from the isolating and sectionalizing ground
network when backfeed occurs. fault events within the switchgear
network bus, thereby saving a portion Utility
The simple spot network system
resembles the secondary-selective of the loads from service interruptions,
radial system in that each load area yet isolating the faulted portion for G
is supplied over two or more primary corrective action.
feeders through two or more trans- The use of spot network systems
formers. In network systems, the provides users with several important
transformers are connected through advantages. First, they save trans-
network protectors to a common bus, former capacity. Spot networks permit
as shown in Figure 1.1-12, from which equal loading of transformers under 52 52
loads are served. Since the transform- all conditions. Also, networks yield
ers are connected in parallel, a primary lower system losses and greatly
feeder or transformer fault does not Main Bus
improve voltage conditions. The volt-
cause any service interruption to the age regulation on a network system
loads. The paralleled transformers is such that both lights and power can
supplying each load bus will normally be fed from the same load bus. Much
carry equal load currents, whereas larger motors can be started across- 52
equal loading of the two separate the-line than on a simple radial
transformers supplying a substation in system. This can result in simplified
the secondary-selective radial system motor control and permits the use One of Several Feeders
is difficult to obtain. The interrupting of relatively large low voltage motors
duty imposed on the outgoing feeder with their less expensive control.
breakers in the network will be greater Figure 1.1-13. Single Bus
Finally, network systems provide a
with the spot network system. greater degree of flexibility in adding This configuration is the simplest
The optimum size and number of pri- future loads; they can be connected system, however, outage of the utility
to the closest spot network bus. results in total outage.
mary feeders can be used in the spot
network system because the loss of Spot network systems are economical Normally the generator does not have
any primary feeder and its associated for buildings which have heavy con- adequate capacity for the entire load.
transformers does not result in the centrations of loads covering small A properly relayed system equipped
loss of any load even for an instant. areas, with considerable distance with load shedding, automatic voltage/
In spite of the spare capacity usually between areas, and light loads within frequency control may be able to
supplied in network systems, savings the distances separating the concen- maintain partial system operation.
in primary switchgear and secondary trated loads. They are commonly used
switchgear costs often result when Any future addition of breakers to the
in hospitals, high rise office buildings, bus will require a shutdown of the bus,
compared to a radial system design and institutional buildings where a
with similar spare capacity. This since there is no tie breaker.
high degree of service reliability is
occurs in many radial systems required from the utility sources. b. Single Bus with Two-Sources from the
because more and smaller feeders Cogeneration equipment is not recom- Utility, Figure 1.1-14
are often used in order to minimize mended for use on networks unless
the extent of any outage when a Same as the single bus, except that
the protectors are manually opened two utility sources are available.
primary fault event occurs. and the utility source completely This system is operated normally with
In spot networks, when a fault occurs disconnected and isolated from the the main breaker to one source open.
on a primary feeder or in a trans- temporary generator sources. Spot Upon loss of the normal service the
former, the fault is isolated from the network systems are especially eco- transfer to the standby Normally
system through the automatic tripping nomical where three or more primary open (NO) breaker can be automatic
of the primary feeder circuit breaker feeders are available. Principally, this or manual. Automatic transfer is pre-
and all of the network protectors asso- is due to supplying each load bus ferred for rapid service restoration
ciated with that feeder circuit. This through three or more transformers especially in unattended stations.
operation does not interrupt service to and the reduction in spare cable
any loads. After the necessary repairs and transformer capacity required.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-13
January 2003 System Design
Ref. No. 0029

Again, the closing of the tie breaker can The third tie breaker allows any bus to
Utility #1 Utility #2 be manual or automatic. The state- be fed from any utility source.
ments made for the retransfer of
scheme B apply to this scheme also. Caution for Figures 1.1-14, 1.1-15 and
Normal Standby 1.1-16: If continuous paralleling of
sources is planned, reverse current,
Utility #1 Utility #2
reverse power and other appropriate
relaying protection should be added.
When both sources are paralleled for 1
any amount of time, the fault current
52 NC 52 NO available on the load side of the main
device is the sum of the available fault
current from each source plus the
52 NC 52 NC
motor fault contribution. It is required
Loads that bus bracing, feeder breakers and
NO
Bus #1 Bus #2 all load side equipment is rated for
52 the increased available fault current.
Figure 1.1-14. Single Bus with Two-Sources
Summary
Retransfer to the “Normal” can be
closed transition subject to the approval 52 52 The configurations shown are based
of the utility. Closed transition momen- on using metal-clad medium voltage
tarily (5 – 10 cycles) parallels both drawout switchgear. The service
utility sources. Caution: when both continuity required from electrical
Load Load systems makes the use of single
sources are paralleled, the fault current
available on the load side of the main source systems impractical.
Figure 1.1-15. Two-Source Utility with
device is the sum of the available fault Tie Breaker In the design of a modern medium
current from each source plus the motor voltage system the engineer should:
fault contribution. It is recommended If looped or primary selective distribu-
that the short circuit ratings of the bus, tion system for the loads is used, the 1. Design a system as simple as
feeder breakers and all load side buses can be extended without a shut- possible.
equipment are rated for the increased down by closing the tie breaker and
transferring the loads to the other bus. 2. Limit an outage to as small a
available fault current. If the utility
portion of the system as possible.
requires open transfer, the disconnec- This configuration is more expensive
tion of motors from the bus must be than 6. The system is not limited to two 3. Provide means for expanding the
ensured by means of suitable time delay buses only. Another advantage is that system without major shutdowns.
on reclosing as well as supervision of the design may incorporate momentary
the bus voltage and its phase with 4. Relay the system so that only the
paralleling of buses on retransfer after
respect to the incoming source voltage. faulted part is removed from
the failed line has been restored to pre-
service, and damage to it is mini-
This busing scheme does not preclude vent another outage. See the Caution
mized consistent with selectivity.
the use of cogeneration, but requires for Figures 1.1-14, 1.1-15 and 1.1-16.
the use of sophisticated automatic syn- 5. Specify and apply all equipment
In Figure 1.1-16, closing of the tie
chronizing and synchronism checking within its published ratings and
breaker following the opening of a
controls, in addition to the previously national standards pertaining to
main breaker can be manual or auto-
mentioned load shedding, automatic the equipment and its installation.
matic. However since a bus can be fed
frequency and voltage controls. through two tie breakers the control
This configuration is more expensive scheme should be designed to make
than the scheme shown in Figure 1.1-13, the selection.
but service restoration is quicker. Again,
a utility outage results in total outage to Utility #1 Utility #2 Utility #3
the load until transfer occurs. Extension
of the bus or adding breakers requires
a shutdown of the bus.
If paralleling sources, reverse current,
reverse power, and other appropriate
relaying protection should be added
52 NC 52 NC 52 NC
as requested by the utility.
c. Multiple Sources with Tie Breaker, NO NO
Bus #1 Bus #2 Bus #3
Figure 1.1-15 and Figure 1.1-16 52 52
This configuration is similar to configu-
ration 6. It differs significantly in that
both utility sources normally carry the 52 NO 52 Typical Feeer 52 52 52 NO
loads and also by the incorporation
of a normally open tie breaker. The Tie Busway
outage to the system load for a utility
outage is limited to half of the system.
Figure 1.1-16. Triple-Ended Arrangement

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-14 Power Distribution Systems
System Design January 2003
Ref. No. 0030

Health Care Facilities ■ NFPA 101 — Life Safety Code. The electrical system requirements for
the Essential Electrical System (EES)
■ NFPA 110 — Standard for Emergency
Health Care Facilities are defined by and Standby Power Systems. vary according to the type of health
NFPA (National Fire Protection Agency) ■ NFPA 111 — Standard on Stored
care facility. Health care facilities are
as “Buildings or portions of buildings Electrical Energy Emergency and categorized by NFPA 99 as Type 1,
in which medical, dental, psychiatric, Standby Power Systems. Type 2 or, Type 3 facilities. Some
nursing, obstetrical, or surgical care example health care facilities, classi-
are provided.” Due to the critical These NFPA guidelines represent the fied by Type, are summarized in the
1 nature of the care being provided at most industry recognized standard following Table 1.1-8.
these facilities and their increasing requirements for health care electrical
design. However, the electrical design Table 1.1-8. Health Care Facilities
dependence on electrical equipment
for preservation of life, health care engineer should consult with the Description Definition EES Type
facilities have special requirements for authorities having jurisdiction over Hospitals NFPA 99 Chap. 12 Type 1
the design of their electrical distribu- the local region for specific electrical Nursing Homes NFPA 99 Chap. 16 Type 2
tion systems. These requirements are distribution requirements. Limited Care
typically much more stringent than Facilities NFPA 99 Chap. 17 Type 2
commercial or industrial facilities. Health Care Electrical System Ambulatory
The following section summarizes Requirements Surgical
some of the unique requirements Facilities NFPA 99 Chap. 13 Type 3 1
Health care electrical systems usually Other Health
of health care facility design. Care Facilities NFPA 99 Chap. 13 Type 3 1
consist of two parts:
There are several agencies and organi- 1 If electrical life support or critical care areas
zations that develop requirements for 1. Non-essential or Normal Electrical are present then facility is classified as Type 1.
health care electrical distribution sys- System.
tem design. The following is a listing 2. Essential Electrical System.
Type 1 Essential Electrical
of some of the specific NFPA (National Systems (EES)
Fire Protection Agency) standards that All electrical power in a health care
affect health care facility design and facility is important, though some Type 1 Essential Electrical Systems
implementation: loads are not critical to the safe opera- (EES) have the most stringent require-
tion of the facility. These “non-essential” ments for providing continuity of
■ NFPA 37 — Standard for Stationary or “normal” loads include things such electrical service and will, therefore,
Combustion Engines and Gas as general lighting, general lab equip- be the focus of this section. Type 1
Turbines. ment, non-critical service equipment, EES requirements meet or exceed
■ NFPA 70 — National Electrical Code. patient care areas, etc. These loads are the requirements for Type 2 and
not required to be fed from an alter- Type 3 facilities.
■ NFPA 99 — Health Care Facilities.
nate source of power.

Normal Source Normal Source Normal Source Emergency Power Supply

Non-Essential Loads Non-Essential Loads

Manual Transfer Switch

Equipment Life Safety Critical


Delayed Automatic Transfer Switch System Branch Branch
Emergency System
Automatic (Non-Delaying)
Transfer Switch Essential Electrical System

Figure 1.1-17. Typical Large Hospital Electrical System — Type 1 Facility

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-15
January 2003 System Design
Ref. No. 0031

Sources: Type 1 systems are required Table 1.1-9. Type 1 EES Applicable Codes B. Critical Branch — supplies power
to have a minimum of two independent Description Standard Section for task illumination, fixed equip-
sources of electrical power. A normal ment, selected receptacles and
source that generally supplies the Design NFPA 99 3-4.1.1.1 selected power circuits for areas
entire facility and one or more alter- Sources NFPA 99 3-4.1.1 (2-4) related to patient care. The
Uses NFPA 99 3-4.1.1.5
nate sources that supply power when Emergency
purpose of the critical branch
the normal source is interrupted. The Power Supply is to provide power to a limited
alternate source(s) must be an on-site Classification NFPA 110 2-2 number of receptacles and loca-
generator driven by a prime mover Distribution NFPA 99 3-4.2 tions to reduce load and minimize 1
unless a generator(s) exists as the NEC 517-30 the chances of fault conditions.
normal power source. In the case The transfer switch(es) feeding the
where a generator(s) is utilized as the Systems and Branches of Service: The critical branch must be automatic
normal source, it is permissible for the Type 1 EES consists of two separate type. They are permitted to have
alternate source to be a utility feed. power systems capable of supplying appropriate time delays that will
Alternate source generators must be power considered essential for life follow the restoration of the life
classified as Type 10, Class X, Level 1 safety and effective facility operation safety branch but should have
gensets per NFPA 110 2-2 capable of during an interruption of the normal power restored within 10 seconds
providing power to the load in a maxi- power source. They are the Emergency of normal source power loss.
mum of 10 seconds. Typically, the System and the Equipment System. The critical branch provides power
alternate sources of power are to circuits serving the following
supplied to the loads through a series 1. Emergency System — consists of areas and functions:
of automatic and/or manual transfer circuits essential to life safety and
switches. (See Section 26.) The critical patient care. 1. Critical care areas.
transfer switches can be non-delayed The Emergency System is an electrical 2. Isolated Power Systems in
automatic, delayed automatic, or sub-system that must be fed from an special environments.
manual transfer depending on the automatic transfer switch or series of 3. Task illumination and selected
requirements of the specific branch automatic transfer switches. This receptacles in the following
of the EES that they are feeding. It is Emergency System consists of two patient care areas: infant
permissible to feed multiple branches mandatory branches that provide power nurseries, medication prep
or systems of the EES from a single to systems and functions essential to areas, pharmacy, selected
automatic transfer switch provided life safety and critical patient care. acute nursing areas, psychiatric
that the maximum demand on the bed areas, ward treatment
EES does not exceed 150 kVA. This A. Life Safety Branch — supplies rooms, nurses’ stations.
configuration is typically seen in power for lighting, receptacles,
smaller health care facilities that and equipment to perform the 4. Specialized patient care task
must meet Type 1 EES requirements. following functions: illumination, where needed.
(See Figure 1.1-18.) 5. Nurse call systems.
1. Illumination of means of egress.
6. Blood, bone and tissue banks.
2. Exit signs and exit direction signs.
Normal Source 7. Telephone equipment rooms
3. Alarms and alerting systems. and closets.
Alternate 4. Emergency communications 8. Task illumination, selected
Source systems. receptacles, and selected
5. Task illumination, battery power circuits for the following:
G chargers for battery powered general care beds (at least
lighting, and select receptacles one duplex receptacle), angio-
at the generator. graphic labs, cardiac catheter-
6. Elevator lighting control, com- ization labs, coronary care
munication and signal systems. units, hemodialysis rooms,
selected emergency room
7. Automatic doors used for egress. treatment areas, human
Non-Essential These are the only functions physiology labs, intensive care
Loads permitted to be on the life safety units, selected postoperative
branch. Life Safety Branch equip- recovery rooms.
Entire Essential ment and wiring must be entirely
Electric System
9. Additional circuits and single-
(150 kVA or Less) independent of all other loads and phase fraction motors as needed
branches of service. This includes for effective facility operation.
Figure 1.1-18. Small Hospital Electrical separation of raceways, boxes or
System — Single EES Transfer Switch cabinets. Power must be supplied
to the Life Safety Branch from a
non-delayed automatic transfer
switch.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-16 Power Distribution Systems
System Design January 2003
Ref. No. 0032

Table 1.1-10. Type 1 — Emergency System The following equipment must be must be configured such that the loads
Applicable Codes arranged for delayed automatic or will not cause the generator to over-
Description Standard Section manual transfer to the emergency load and must be shed in the event the
power supply: generator enters an overload condition.
General NFPA 99 3-4.2.2.2
NEC 517-31 1. Select heating equipment. Ground Fault Protection — per NFPA
Life Safety NFPA 99 3-4.2.2.2(b) 2. Select elevators. 70 NEC article 230-95, ground fault
Branch NEC 517-32 protection is required on any feeder or
3. Supply, return and exhaust
1 Critical Branch NFPA 99 3-4.2.2.2(c)
ventilating systems for surgical,
service disconnect 1000A or larger on
NEC 517-33 systems with line to ground voltages of
obstetrical, intensive care, 150 volts or greater and phase-to-phase
Wiring NFPA 99 3-4.2.2.4
NEC 517-30(c)
coronary care, nurseries, and voltages of 600 volts or less. For health
emergency treatment areas. care facilities (of any type), a second
2. Equipment System — consists of 4. Supply, return and exhaust level of ground fault protection is
major electrical equipment necessary ventilating systems for airborne required to be on the next level of
for patient care and Type 1 operation. infectious/isolation rooms, labs feeder downstream. This second level
and medical areas where hazard- of ground fault is only required for
The Equipment System is a subsystem ous materials are used. feeders that serve patient care areas
of the EES that consists of large electri- and equipment intended to support life.
cal equipment loads needed for patient 5. Hyperbaric facilities.
100% selective coordination of the two
care and basic hospital operation. 6. Hypobaric facilities. levels of ground fault protection must
Loads on the Equipment System that 7. Autoclaving equipment. be achieved with a minimum six-cycle
are essential to generator operation are separation between the upstream and
required to be fed by a non-delayed 8. Controls for equipment listed above.
downstream device.
automatic transfer switch. 9. Other selected equipment in
kitchens, laundries, radiology NEC 517-17 prohibits the installation
The following equipment must be rooms, and central refrigeration of ground fault protection between the
arranged for delayed automatic transfer as selected. on-site generator(s) and any EES transfer
to the emergency power supply: switch or on the load side of a transfer
Table 1.1-11. Type 1 — Equipment System
1. Central suction systems for medical switch feeding EES circuits. (See Figure
Applicable Codes
and surgical functions. 1.1-19 — Additional Level of Ground
Description Standard Section Fault). The intent of this code section is
2. Sump pumps and other equipment
General NFPA 99 3-4.2.2.3 to prevent a ground fault that causes a
required for the safe operation of
NEC 517-34 trip on the normal system to also cause
a major apparatus.
Equipment NFPA 99 3-4.2.2.3(c)-(e) a trip on the emergency system. Such
3. Compressed air systems for NEC 517-34(a)-(b) an event could result in complete power
medical and surgical functions. loss of both normal and emergency
4. Smoke control and stair Any loads served by the generator that power sources and could not be recov-
pressurization systems. are not approved as outlined above as ered until the source of the ground
part of the Essential Electrical System fault was located and isolated from
5. Kitchen hood supply and exhaust
must be connected through a separate the system. To prevent this condition,
systems, if required to operate
transfer switch. These transfer switches NEC 700-26 removes the
during a fire.

Normal Source Normal Source(s)


G
Generator Breakers are
Typically Supplied with
480/277V ➀ 480/277V ➀ 480/277V ➀ Ground Fault Alarm
Only. (NEC 700-26)
1000A Service 1000A Service 1000A Service
GF GF GF
or Larger Entrance or Larger Entrance or Larger Entrance
Additional Level
of Ground Fault
is not Permitted
Between Generator
Additional Level and EES Transfer
GF GF GF GF GF of Ground Fault GF GF GF GF GF GF Switches.
Protection (NEC 517-17a(1))

Non-Essential Loads Non-Essential Loads

GF = Ground Fault Protection Required Additional Level of Ground Fault is


not Permitted on Load Side of EES
Transfer Switches. (NEC 517-17a(2))
Essential Electrical System

Figure 1.1-19. Additional Level of Ground Fault Protection


1 Ground fault protection is required for service disconnects 1000 amperes and larger or systems with less than 600 volts phase-to-phase and greater
than 150 volts to ground per NEC 230-95.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.1-17
January 2003 System Design
Ref. No. 0033

ground fault protection requirement event of a single line-to-ground be tested for a minimum of 30 minutes
for the emergency system source. fault and maintains circuit continuity. under the criteria defined in NFPA 110.
Typically, the emergency system Electronic Line Isolation Monitors
generator(s) are equipped with ground (LIM) are used to monitor and display One method to automate the task
fault alarms that do not automatically leakage currents to ground. When of monthly generator tests is through
disconnect during a ground fault. leakage current thresholds are the use of PowerNetE communica-
exceeded, visible and/or audible tions. With the PowerNet integrated
Table 1.1-12. Ground Fault Protection alarms are initiated to alert occupants metering, monitoring and control
Applicable Codes of a possible hazardous condition. system, a facility maintenance director 1
Description Standard Section This alarm occurs without interrupting can initiate a generator test, control/
power to allow for the safe conclusion monitor loads, meter/monitor genera-
Services NEC 230-95 tor test points and create a JCAHO
Feeders NEC 215-10 of critical procedures. (For more in
depth information on Isolated Power compliant report automatically from
Additional Level NEC 517-17 a central PC. The report contains all
NFPA 99 3-3.2.1.5 Systems see Section 36.)
metered values, test results, date/time
Alternate Source NEC 700-26 Table 1.1-13. Wet Location Applicable Codes information, etc. necessary to satisfy
NEC 700-7 (d) JCAHO requirements. This automated
Description Standard Section
generator testing procedure reduces
Wet Locations — A wet location in a General NFPA 99 3-3.2.1.2(f) the labor, training and inaccuracies
health care facility is any patient care NEC 517-20 that occur during manual emergency
area that is normally subject to wet Isolated Power NFPA 99 3-3.2.2 power system tests. (See Power
conditions while patients are present. Systems NEC 517-160 Monitoring Section 2.)
Typical wet locations can include oper-
ating rooms, anesthetizing locations, Maintenance and Testing Table 1.1-14. Maintenance and Testing
dialysis locations, etc. (Patient beds, Regular maintenance and testing of Applicable Codes
toilets, sinks, are not considered wet the electrical distribution system in Description Standard Section
locations.) These wet locations require a health care facility is necessary to
special protection to guard against Grounding NFPA 99 3-3.3.2
ensure proper operation in an emer-
electric shock. The ground fault current gency and, in some cases, to maintain Emergency Power NFPA 99 3-4.4.1.1
in these areas must be limited not to System JCAHO EC.2.14(d)
government accreditation. Any health
exceed 6 mA. care facility receiving Medicare or Generator NFPA 110 6-4.2
Medicaid reimbursement from the Transfer Switches NFPA 110 6-4.5
In areas where the interruption of power
is permissible, ground fault circuit government must be accredited by the Breakers NFPA 99 3-4.4.1.2
Joint Commission on Accreditation of NFPA 110 6-4.6
interrupters (GFCI) can be employed.
GFCIs will interrupt a circuit when Health Care Organizations (JCAHO).
JCAHO has established a group of Routine maintenance should be per-
ground fault current exceeds the
standards called the Environment of formed on circuit breakers, transfer
present level (typically 2-5 mA).
Care, which must be met for health switches, switchgear, generator equip-
In areas where the interruption of care facility accreditation. Included in ment, etc. by trained professionals
power cannot be tolerated, protection these standards is the regular testing to ensure the most reliable electrical
from ground fault currents is accom- of the emergency (alternate) power system possible. See Section 40 for
plished through the use of an Isolated system(s). The emergency power sys- Cutler-Hammer Engineering Services
Power System. Isolated Power Sys- tem must be tested in accordance with and Systems (CHESS), which provides
tems provide power to an area that is NFPA 110 Standard for Emergency and engineers, trained in development
isolated from ground (or ungrounded). Standby Power Systems guidelines at and execution of annual preventative
This type of system limits the amount intervals not less than 20 days and not maintenance procedures of health care
of current that flows to ground in the exceeding 40 days. Generators must facility electrical distribution systems.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.1-18 Power Distribution Systems
System Design January 2003
Ref. No. 0034

This page intentionally left blank.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-1
January 2003 System Analysis
Ref. No. 0035

Systems Analysis The principal types of computer


programs utilized to provide system
Short circuit calculations define
momentary fault currents for LV
A major consideration in the studies include: breaker and fuse duty and bus
design of a distribution system is to bracings at any selected location in
■ Short circuit — identify 3-phase and the system and also determine the
ensure that it provides the required
line-to-ground fault currents and effect on the system after removal
quality of service to the various
system impedances. of lines due to breaker operation or
loads. This includes serving each
load under normal conditions and, ■ Circuit breaker duty — identify scheduled line outages. With the use
under abnormal conditions, providing asymmetrical fault current based of computer programs it is possible 1
the desired protection to service on X/R ratio. to identify the fault current at any bus,
and system apparatus so that ■ Protective device coordination — in every line or source connected to
interruptions of service are minimized determine characteristics and set- the fault bus, or to it and every adja-
consistent with good economic and tings of medium voltage protective cent bus, or to it and every bus which
mechanical design. relays and fuses, and entire low is one and two buses away, or currents
voltage circuit breaker and fuse in every line or source in the system.
Under normal conditions, the impor- coordination. The results of these calculations
tant technical factors include voltage permit optimizing service to the loads
■ Load flow — simulate normal
profile, losses, load flow, effects of while properly applying distribution
load conditions of system voltages,
motor starting, service continuity and apparatus within their intended limits.
power factor, line and transformer
reliability. The prime considerations
loadings. The following additional studies
under faulted conditions are apparatus
protection, fault isolation and service ■ Motor starting — identify system should be considered depending
continuity. During the system prelimi- voltages, motor terminal voltage, upon the type and complexity of the
nary planning stage, before selection motor accelerating torque, and distribution system, the type of facility
of the distribution apparatus, several motor accelerating time when and the type of loads to be connected
distribution systems should be ana- starting large motors. to the system:
lyzed and evaluated including both
■ Harmonic Analysis
economic and technical factors. Dur-
ing this stage if system size or com- ■ Transient Stability
plexity warrant, it may be appropriate ■ Insulation Coordination
to provide a thorough review of each ■ Grounding Study
system under both normal and ■ Switching Transient
abnormal conditions.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-2 Power Distribution Systems
System Analysis January 2003
Ref. No. 0036

Short Circuit Currents — The AC component is not constant


if rotating machines are connected
rated secondary current. Limiting the
power source fault capacity will thereby
General to the system because the impedance reduce the maximum fault current from
of this apparatus is not constant. The the transformer.
The amount of current available in a rapid variation of motor and generator
short circuit fault is determined by the impedance is due to these factors: The electric network which determines
capacity of the system voltage sources the short circuit current consists of an
and the impedances of the system, Subtransient Reactance (x" d ), deter- AC driving voltage equal to the pre-
1 including the fault. Constituting voltage mines fault current during the first fault system voltage and an imped-
sources are the power supply (utility cycle, and after about 6 cycles this ance corresponding to that observed
or on-site generation) plus all rotating value increases to the transient reac- when looking back into the system
machines connected to the system at tance. It is used for the calculation from the fault location. In medium
the time of the fault. A fault may be of the momentary interrupting and/or and high voltage work, it is generally
either an arcing or bolted fault. In an momentary withstand duties of satisfactory to regard reactance as the
arcing fault, part of the circuit voltage is equipment and/or system. entire impedance; resistance may be
consumed across the fault and the total neglected. However, this is normally
fault current is somewhat smaller than Transient Reactance (x'd ), which deter- permissible only if the X/R ratio of the
for a bolted fault, so the latter is the mines fault current after about 6 cycles medium voltage system is equal to or
worst condition, and therefore is the and this value in 1/2 to 2 seconds more than 25. In low voltage (1000 volts
value sought in the fault calculations. increases to the value of the synchro- and below) calculations, it is usually
nous reactance. It is used in the setting worthwhile to attempt greater accuracy
Basically, the short circuit current is of the phase OC relays of generators by including resistance with reactance
determined by applying Ohm’s Law and medium voltage circuit breakers. in dealing with impedance. It is for this
to an equivalent circuit consisting of reason, plus ease of manipulating the
a constant voltage source and a time Synchronous Reactance (xd), which
determines fault current after steady various impedances of cables and
varying impedance. A time varying buses and transformers of the low
impedance is used in order to account state condition is reached. It has no
effect as far as short circuit calcula- voltage circuits, that computer studies
for the changes in the effective voltages are recommended before final selection
of the rotating machines during the tions are concerned but is useful in
the determination of relay settings. of apparatus and system arrangements.
fault. In an AC system, the resulting
short circuit current starts out higher Transformer Impedance, in percent, is When evaluating the adequacy
in magnitude than the final steady defined as that percent of rated primary of short circuit ratings of medium
state value and asymmetrical (due voltage that must be applied to the voltage circuit breakers and fuses,
to the DC offset) about the X-axis. transformer to produce rated current both the rms symmetrical value and
The current then decays toward a flowing in the secondary, with second- asymmetrical value of the short circuit
lower symmetrical steady-state value. ary shorted through zero resistance. current should be determined.
The time varying characteristic of the Therefore, assuming the primary
impedance accounts for the symmetri- For low voltage circuit breakers and
voltage can be sustained (generally fuses, the rms symmetrical value
cal decay in current. The ratio of the referred to as an infinite or unlimited
reactive and resistive components (X/R should be determined along with
supply), the maximum current a trans- either: the X/R ratio of the fault at
ratio) accounts for the DC decay, see former can deliver to a fault condition is
Figure 1.2-1. The fault current consists the device or the asymmetrical short
the quantity of (100 divided by percent circuit current.
of an exponentially decreasing direct- impedance) times the transformer
current component superimposed
upon a decaying alternating-current.
The rate of decay of both the DC and Total Current - A Wholly Offset
AC components depends upon the Asymmetrical Alternating Wave
ratio of reactance to resistance (X/R) 3.0
rms Value of Total Current
of the circuit. The greater this ratio, Alternating Component -
the longer the current remains higher 2.5
Symmetrical Wave
than the steady-state value which it rms Value of
2.0
would eventually reach. Alternating Component

The total fault current is not symmetrical 1.5


Scale of Curent Values

with respect to the time-axis because


of the direct-current component, 1.0
hence it is called asymmetrical current.
0.5
The DC component depends on the
point on the voltage wave at which 1 2 3 4
0
the fault is initiated.
See Table 1.2-1 for multiplying factors 0.5
that relate the rms asymmetrical value
of Total Current to the rms symmetri- -1.0
cal value, and the peak asymmetrical Direct Component - The Axis
-1.5 of Symmetrical Wave Time in Cycles of
value of Total Current to the rms a 60 Hz Wave
symmetrical value. -2.0

Figure 1.2-1. Structure of an Asymmetrical Current Wave

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-3
January 2003 System Analysis
Ref. No. 0037

Fault Current Waveform Relationships


The following Table 1.2-1 describes the Based on a 60 Hz system and t = 1/2 cycle
relationship between fault current (ANSI/IEEEC37.13.1990/10.1.4)
peak values, rms symmetrical values – 2 π 60
----------------
and rms asymmetrical values depend- 120 –π
Ip  ---------------- 
X⁄R
----------
ing on the calculated X/R ratio. The Peak multiplication factor = ----- = 2  1 + e  = 2 1 + e X ⁄ R 
I    
table is based on the following general  
formulas: 1
( – 2 ) ( 2 π 60 )
– ωt -------------------------------
 ------------ 120 –2 π
1. Ip = I 2  1 + e X ⁄ R I rms asym -------------------------------
X⁄R
------------
X⁄R
  rms multiplication factor = ------------------------------ = 1 + 2e = 1 + 2e
  I

– 2ωt Example for X/R =15


---------------
X⁄R
2. I rms asym = I 1 + 2e –π
 ------- 
Peak mf = 2  1 + e 15  = 2.5612
Where:  
 
I = Symmetrical rms current
–2 π
Ip = Peak current ----------
15
rms mf = 1 + 2e = 1.5217
e = 2.718
ω=2πf
f = Frequency in Hz
t = Time in seconds

Table 1.2-1. Relation of X/R Ratio to Multiplication Factor

2.8

2.7
PEAK MAXIMUM ASYMMETRICAL

RMS MAXIMUM ASYMMETRICAL


Based Upon: rms Asym = DC 2 + rms Sym2
2.6 with DC Va
V
Value
RMS SYMMETRICAL

Taken at Current Peak


T
Ta

RMS SYMMETRICAL
2.5

2.4

2.3

2.2 1.8
R
TO
C
FA

2.1 1.7
N
FACTOR =

O
TI

FACTOR =
CA

2.0 1.6
LI
IP
ATION FA

LT

1.9 1.5
U

ATION FA
M

R
AK

TO
AT

C
PE

1.8 FA 1.4
PEAK MULTIPLICA

AT

N
TIO
RMS MULTIPLICA

1.7 L ICA 1.3


IP
LT

LT
L

MU
LT
L

1.6 S 1.2
RM

1.5 1.1

1.4
1 1.5 2 2.5 3 4 5 6 7 8 9 10 15 20 25 30 40 50 60 70 80 90 100
CIRCUIT X/R RATIO
A
AT (T
TAN PHASE)
TA

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-4 Power Distribution Systems
System Analysis January 2003
Ref. No. 0038

Fault Current Calculations Synchronous Motors — Use 5.0 times


motor full load current (impedance
Medium Voltage Motors
value of 20%). If known, use actual values otherwise
The calculation of asymmetrical cur-
use the values indicated for the same
rents is a laborious procedure since
When the motor load is not known, type of motor.
the degree of asymmetry is not the
the following assumptions generally
same on all three phases. It is common
practice to calculate the rms symmetri-
are made: Calculation Methods
cal fault current, with the assumption 208Y/120V Systems The following pages describe various
1 being made that the DC component methods of calculating short circuit
■ Assume 50% lighting and 50%
has decayed to zero, and then apply currents for both medium and low
motor load.
a multiplying factor to obtain the first voltage systems. A summary of the
half-cycle rms asymmetrical current, or types of methods and types of calcula-
which is called the “momentary cur- tions is as follows:
rent.” For medium voltage systems ■ Assume motor feedback contribu-
tion of twice full load current of ■ Medium Voltage Switchgear —
(defined by IEEE as greater than 1000
transformer. exact method . . . . . . . . . Page 1.2-5
volts up to 69,000 volts) the multiply-
ing factor is established by NEMA T ■ Medium Voltage Switchgear —
240/480/600V 3-Phase, 3-Wire Systems quick check table . . . . . . Page 1.2-7
and ANSI standards depending upon
the operating speed of the breaker; ■ Assume 100% motor load. ■ Medium Voltage Switchgear
for low voltage systems, 600 volts and or Example 1 — verify ratings of
below, the multiplying factor is usually breakers . . . . . . . . . . . . . Page 1.2-8
1.17 (based on generally accepted ■ Assume motors 25% synchronous ■ Medium Voltage Switchgear
use of X/R ratio of 6.6 representing a and 75% induction. Example 2 — verify ratings
source short circuit power factor of of breakers with rotating
or
15%). These values take into account loads . . . . . . . . . . . . . . . . Page 1.2-9
that medium voltage breakers are ■ Assume motor feedback contribu- ■ Medium Voltage Switchgear
rated on maximum asymmetry tion of four times full load current Example 3 — verify ratings
and low voltage breakers are of transformer. of breakers with
rated average asymmetry. generators . . . . . . . . . . . Page 1.2-10
480Y/277V Systems in Commercial Buildings
To determine the motor contribution ■ Assume 50% induction motor load. ■ Medium Voltage Fuses —
during the first half-cycle fault current, exact method . . . . . . . . . Page 1.2-11
when individual motor horsepower or ■ Power Breakers — asymmetry
load is known, then the subtransient derating factors . . . . . . . Page 1.2-11
reactances found in the IEEE Red ■ Assume motor feedback contribu-
tion of two times full load current ■ Molded Case Breakers — asymmetry
should be used. When the system derating factors . . . . . . . Page 1.2-12
motor load is unknown, the following of transformer or source.
assumptions generally are made: ■ Short Circuit Calculations —
or short cut method for
Induction Motors — Use 4.0 times ■ For industrial plants, make same a system . . . . . . . . . . . . . Page 1.2-13
motor full load current (impedance assumptions as for 3-phase, 3-wire ■ Short Circuit Calculations —
value of 25%). systems (above). short cut method for
end of cable . . . . . . . . . . Page 1.2-15
■ Short Circuit Calculations —
short cut method for end of
cable chart method . . . . Page 1.2-16
■ Short Circuit Currents —
chart of transformers 300 to
3750 kVA . . . . . . . . . . . . . Page 1.4-7

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-5
January 2003 System Analysis
Ref. No. 0039

Fault Current Calculations For example, consider the following case: momentary and fault close
rating is also acceptable).
for Specific Equipment Assume a 12.47 kV system with
20,000 amperes symmetrical available. Note: If the system available fault current
The purpose of the fault current calcu- In order to determine if an Eaton’s were 22,000 amperes symmetrical, this
lations is to determine the fault current Cutler-Hammer Type 150 VCP-W 500 breaker could not be utilized even though
at the location of a circuit breaker, fuse vacuum breaker is suitable for this the “Maximum Symmetrical Interrupting
Capability” is greater than 22,000 since
or other fault interrupting device in application, check the following:
Test 1 calculation is not satisfied.
order to select a device adequate for the
From Table 6.0-1 in Section 6 under 1
calculated fault current or to check the For approximate calculations, Table 1.2-2
thermal and momentary ratings of non- column “Rated Maximum Voltage”
V = 15 kV, under column “Rated short provides typical values of % reactance
interrupting devices. When the devices (X) and X/R values for various rotating
to be used are ANSI-rated devices, the circuit Current” I = 18 kA, “Rated
Voltage Range Factor” K = 1.3. equipment and transformers. For sim-
fault current must be calculated and the plification purposes, the transformer
device selected as per ANSI standards. Test 1 for V/Vo x I or 15 kV/12.47 kV x impedance (Z) has been assumed to be
The calculation of available fault cur- 18 kA = 21.65; also check K x I (which primarily reactance (X). In addition, the
rent and system X/R rating is utilized is shown in the column headed resistance (R) for these simplified cal-
to verify adequate bus bar bracing “Maximum Symmetrical Interrupting culations has been ignored. For detailed
and momentary withstand ratings of Capability”) or 1.3 x 18 kA = 23.4 kA. calculations, the values from the IEEE
devices such as contactors. Since both of these numbers are Red Book Standard 141, for rotating
greater than the available system fault machines, and ANSI C57 and/or C37
Medium Voltage VCP-W current of 20,000 amperes, the breaker for transformers should be utilized.
is acceptable (assumes the breaker’s
Metal-Clad Switchgear
Table 1.2-2. Reactance X for E/X Amperes
The applicable ANSI Standards C37
is the latest applicable edition. The System Reactance X Used for Typical Values and Range
Component on Component Base
following is a review of the meaning
of the ratings. (See Section 6.) Short Circuit Close and Latch % Reactance X/R Ratio
Duty (Momentary)
The Rated Maximum Voltage
2-Pole Turbo Generator X X 9 (7 – 14) 80 (40 – 120)
This designates the upper limit of 4-Pole Turbo Generator X X 15 (12 – 17) 80 (40 – 120)
design and operation of a circuit Hydro Generator with Damper Wedges X X 20 (13 – 32) 30 (10 – 60)
breaker. For example, a circuit breaker and Synchronous Condensers
with a 4.76 kV rated maximum voltage Hydro Generator without Damper .75X .75X 16 (16 – 50) 30 (10 – 60)
cannot be used in a 4.8 kV system. Windings
All Synchronous Motors 1.5X 1.0X 20 (13 – 35) 30 (10 – 60)
K-Rated Voltage Factor
Ind. Motors Above 1000 hp, 1800 Rpm 1.5X 1.0X 17 (15 – 25) 30 (15 – 40)
The rated voltage divided by this factor and Above 250 hp, 3600 Rpm
determines the system kV a breaker can
All Other Induction Motors 50 hp 3.0X 1.2X 17 (15 – 25) 15 (2 – 40)
be applied up to the short circuit kVA and Above
rating calculated by the formula
Ind. Motors Below 50 hp and Neglect Neglect — —
All Single-Phase Motors
3 × Rated SC Current × Rated Max. Voltage
Distribution System from Remote X X As Specified 15 (5 – 15)
Transformers or Calculated
Rated Short Circuit Current
Current Limiting Reactors X X As Specified 80 (40 – 120)
This is the symmetrical rms value of or Calculated
current that the breaker can interrupt
Transformers
at rated maximum voltage. It should
be noted that the product 3 x 4.76 x OA to 10 MVA, 69 kV X X 8.0 18 (7 – 24)
29,000 = 239,092 kVA is less than the OA to 10 MVA, above 69 kV X X 8.0 to 10.5 18 (7 – 24)
nominal 250,000 kVA listed. This FOA 12 to 30 MVA X X Depends on 20 (7 – 30)
Primary
rating (29,000 amperes) is also the FOA 40 to 100 MVA X X Windings BIL 38 (32 – 44)
base quantity that all the “related” Rating
capabilities are referred to.
Maximum Symmetrical Interrupting Table 1.2-3. Typical System X/R Ratio Range (for Estimating Purposes)
Capability Type of Circuit X/R Range
This is expressed in rms symmetrical Remote generation through other types of circuits such as transformers rated 10 MVA 15 or less
amperes or kiloamperes and is K x I or smaller for each 3-phase bank, transmission lines, distribution feeders, etc.
rated; 29,000 x 1.24 = 35,960 rounded Remote generation connected through transformer rated 10 MVA to 100 MVA 15 – 40
to 36 kA. for each 3-phase bank, where the transformers provide 90 percent or more
of the total equivalent impedance to the fault point.
This is the rms symmetrical current Remote generation connected through transformers rated 100 MVA or larger 30 – 50
that the breaker can interrupt down to for each 3-phase bank where the transformers provide 90 percent or more
a voltage = maximum rated voltage of the total equivalent impedance to the fault point.
divided by K (for example, 4.76/1.24 = Synchronous machines connected through transformers rated 25 to 100 MVA 30 – 50
3.85). If this breaker is applied in a for each 3-phase bank.
system rated at 2.4 kV the calculated Synchronous machines connected through transformers rated 100 MVA and larger. 40 – 60
fault current must be less than 36 kA. Synchronous machines connected directly to the bus or through reactors. 40 – 120

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-6 Power Distribution Systems
System Analysis January 2003
Ref. No. 0040

The Close and Latch Capability impedances and their X/R ratios are Step 3: Reduce the reactance network
This is also a related quantity expressed given in Tables 1.2-2 and 1.2-3. to an equivalent reactance. Call this
in rms asymmetrical amperes by 1.6 x reactance XI.
The ANSI Standard C37.010 allows the
maximum symmetrical interrupting use of the X values only in determin- Step 4: Set-up the same network for
capability. For example 1.6 x 36 = 57.6 ing the E/X value of a fault current. The resistance values.
or 58 kA, or 1.6 K x rated short circuit R values are used to determine the X/R
current. ratio, in order to apply the proper mul- Step 5: Reduce the resistance network
to an equivalent resistance. Call this
1 Another way of expressing the close tiplying factor, to account for the total
resistance RI. The above calculations
and latch rating is in terms of the peak fault clearing time, asymmetry, and
decrement of the fault current. of XI and RI may be calculated by
current, which is the instantaneous several computer programs.
value of the current at the crest. ANSI The steps in the calculation of fault
Standard C37.09 indicates that the currents and breaker selection are Step 6: Calculate the E/XI value, where
ratio of the peak to rms asymmetrical described hereinafter: E is the prefault value of the voltage at
value for any asymmetry of 100% to the point of fault nominally assumed
20% (percent asymmetry is defined as Step 1: Collect the X and R data of the 1.0 pu.
the ratio of DC component of the fault circuit elements. Convert to a common X
in per unit to 2 ) varies not more than kVA and voltage base. If the reactances Step 7: Determine X/R = ------I as
previously calculated. RI
±2% from a ratio of 1.69. Therefore the and resistances are given either in
close and latch current expressed in ohms or per unit on a different voltage Step 8: Go to the proper curve for
terms of the peak amperes is = 1.6 x or kVA base, all should be changed the type of fault under consideration
1.69 x K x rated short circuit current. to the same kVA and voltage base. (3-phase, phase-to-phase, phase-to-
This caution does not apply where ground), type of breaker at the location
In the calculation of faults for the pur- the base voltages are the same as
poses of breaker selection the rotating (2, 3, 5 or 8 cycles), and contact parting
the transformation ratio. time to determine the multiplier to the
machine impedances specified in
ANSI Standard C37.010 Article 5.4.1 Step 2: Construct the sequence calculated E/XI.
should be used. The value of the networks and connect properly for the See Figures 1.2-2, 1.2-3 and 1.2-4 for
impedances and their X/R ratios type of fault under consideration. Use 5-cycle breaker multiplying factors.
should be obtained from the equip- the X values required by ANSI Stan- Use Figure 1.2-4 if the short circuit is
ment manufacturer. At initial short cir- dard C37.010 for the “interrupting” fed predominantly from generators
cuit studies, data from manufacturers duty value of the short circuit current. removed from the fault by two or more
is not available. Typical values of

130 130 130

120 120 120


8

7
5

110 110 110


4
6

12
10
5

100
6
100 100
4

4
3

90 90 90 3

80 80 80
IME
Ratio X/R
Ratio X/R

Ratio X/R
TIME

70 70
GT

70
IN
ING

RT

60 60 60
PA
ART

50 50
AC
T P

50
NT
AC

CO
NT

40 40 40
CO

30 30 30
5-CYCLE 5-CYCLE 5-CYCLE
BREAKER BREAKER BREAKER
20 20 20

10 10 10

1.0 1.1 1.2 1.3 1.4 1.0 1.1 1.2 1.3 1.4 1.0 1.1 1.2 1.3 1.4
Multiplying Factors for E / X Amperes Multiplying Factors for E / X Amperes Multiplying Factors for E / X Amperes

Figure 1.2-2. 3-phase Fault Multiplying Figure 1.2-3. Line-to-Ground Fault Multiplying Figure 1.2-4. 3-phase and Line-to-Ground
Factors Which Include Effects of AC and Factors Which Include Effects of AC and Fault Multiplying Factors Which Include
DC Decrement DC Decrement Effects of DC Decrement Only

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-7
January 2003 System Analysis
Ref. No. 0041

transformations or the per unit reac- Section 5 of ANSI C37 provides further Application Quick Check Table
tance external to the generation is 1.5 guidance for medium voltage breaker For application of circuit breakers in a
times or more than the subtransient application. radial system supplied from a single
reactance of the generation on a com- source transformer. Short circuit duty
mon base. Also use Figure 1.2-4 where Reclosing Duty
was determined using E/X amperes
the fault is supplied by a utility only. ANSI Standard C37.010 indicates the and 1.0 multiplying factor for X/R ratio
reduction factors to use when circuit of 15 or less and 1.25 multiplying
Step 9: Interrupting duty short circuit breakers are used as reclosers. Cutler- factor for X/R ratios in the range of
current = E/XI x MFx = E/X2. Hammer VCP-W breakers are listed at 15 to 40.
1
Step 10: Construct the sequence 100% rating factor for reclosing.
(positive, negative and zero) networks Table 1.2-4. Application Quick Check Table
properly connected for the type of
Source Operating Voltage
fault under consideration. Use the Transformer kV
X values required by ANSI Standard MVA Rating
C37.010 for the “Close and Latch” Motor Load 2.4 4.16 6.6 12 13.8
duty value of the short circuit current.
100% 0%
Step 11: Reduce the network to an
1 1.5
equivalent reactance. Call the reac- 1.5 2 50 VCP-W 250
tance X. Calculate E/X x 1.6 if the 2 2.5 12 kA 50 VCP-W 250 150 VCP-W 500 150 VCP-W 500 150 VCP-W 500
breaker close and latch capability is 2.5 3 10.1 kA 23 kA 22.5 kA 19.6 kA
given in rms amperes or E/X x 2.7 if 3 3.75
the breaker close and latch capability 3.75 5 50 VCP-W 250
is given in peak or crest amperes. 5 7.5 36 kA 50 VCP-W 250
7.5 10 50 VCP-W 350 33.2 kA
Step 12: Select a breaker whose:
10 1 10 49 kA
a. Maximum voltage rating exceeds 10 12 1
the operating voltage of the system: 12 15 50 VCP-W 350 75 VCP-W 500
46.9 kA 41.3 kA
E V max
b. ------- ≤ I × -------------- ≤ KI 15 20
X2 Vo
20 1 20 Breaker Type and 150 VCP-W 750 150 VCP-W 750
25 Symmetrical Interrupting Capacity 35 kA 30.4 kA
See Table 6.0-1, Section 6. 30 at the Operating Voltage

50 1 150 VCP-W 1000 150 VCP-W 1000


Where: 46.3 kA 40.2 kA
I = Rated short circuit current 1 Transformer impedance 6.5% or more, all other transformer impedances are 5.5% or more.
Vmax = Rated maximum voltage
Application Above 3,300 Feet (1,000 m) Table 1.2-5. Application Above 3,300 Feet
of the breaker (1,000 m)
The rated one-minute power frequency
VD = Actual system voltage withstand voltage, the impulse with- Altitude in Correction Factor
stand voltage, the continuous current Feet (Meters) Current Voltage
KI = Maximum symmetrical
rating, and the maximum voltage rating
interrupting capacity 3,300 (1,006) (and Below) 1.00 1.00
must be multiplied by the appropriate
5,000 (1,524) 0.99 0.95
c. E/X x 1.6 ≤ rms closing and correction factors below to obtain 10,000 (3,048) 0.96 0.80
latching capability of the breaker modified ratings which must equal or
exceed the application requirements.
and/or
Note: Intermediate values may be obtained
E/X x 2.7 ≤ Crest closing and by interpolation.
latching capability of the breaker.
The ANSI standards do not require the
inclusion of resistances in the calcula-
tion of the required interrupting and
close and latch capabilities. Thus the
calculated values are conservative.
However, when the capabilities of
existing switchgears are investigated,
the resistances should be included.
For single line-to-ground faults the
symmetrical interrupting capability
is 1.15 x the symmetrical interrupting
capability at any operating voltage
but not to exceed the maximum
symmetrical capability of the breaker.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-8 Power Distribution Systems
System Analysis January 2003
Ref. No. 0042

Application on Symmetrical Current Rating Basis For 3-Phase Fault


E
Example 1 — Fault Calculations I 3-Phase = -----
X
Given a circuit breaker interrupting and momentary rating in the table below,
verify the adequacy of the ratings for a system without motor loads, as shown. where X is ohms per phase and E is
the highest typical line-to-neutral
Table 1.2-6. Short Circuit Duty operating voltage or
Type V Max. 3-Phase Symmetrical Interrupting Capability Close and Latch or
1 Breaker at V Max. Max. KI at 4.16 kV Oper. Voltage Momentary I
I 3-Phase = ----B-
X
50VCP – W250 4.76 kV 29 kA 36 kA 4.76 58 kA I3
----------- (29) = 33.2 kA I1 where X is per unit reactance
4.16
LG Symmetrical Interrupting Capability IB is base current
— 36 kA 1.15 (33.2) = 38.2 kA I2
3.75 MVA
Base current I B = −−−−−−−−−−−−−−−−−−− = .52 kA
Note: Interrupting capabilities I1 and I2 at operating voltage must not exceed maximum 3 ( 4.16 kV )
symmetrical interrupting capability Kl.
I .52
Check capabilities I1, I2 and I3 on the following utility system where there is no I 3-Phase = ----1- = ------------------ = 8.6 kA Sym.
X .0604
motor contribution to short circuit.
24,200 Watts Load Losses X
System −− = 9 (is less than 15)
R
13.8 kV
On 13.8 kV System, 3.75 MVA Base would use 1.0 multiplying factor for
X short circuit duty, therefore, short
= 15 3.75 MVA circuit duty is 8.6 kA sym. for 3-phase
R Z = --------------------------------- = .01 pu or 1%
375 MVA fault I1 and momentary duty is 8.6 x
375 MVA 2
1.6 = 13.7 kA I3.
Available 2 2 2 2X 
Z = X + R = R  -------2- + 1 For Line-to-Ground Fault
R 
3E 3I B
I LG = --------------------------- = --------------------------
-
Z 1 1 2X 1 + X 0 2X 1 + X 0
R = ----------------------- = ---------------- = ------------------ = .066%
˙
13.8 kV 2 266 15.03
X
-------- + 1 For this system, X0 is the zero sequence
2
3750 kVA R reactance of the transformer which
is equal to the transformer positive
X sequence reactance and X1 is the posi-
X = ----- ( R ) = 15 (.066) = .99% tive sequence reactance of the system.
R
4.16 kV Transformer Standard 5.5% Impedance Therefore,
has a ±7.5% Manufacturing Tolerance
3(.52)
I LG = −−−−−−−−−−−−−−−−−−−−−−−−−− = 9.1 kA Sym.
50VPC-W250 5.50 Standard Impedance 2(.0604) + .0505
–.41 (–7.5% Tolerance)
Transformer Z = Using 1.0 multiplying factor (see
5.09%
Table 1.2-7), short-circuit duty = 9.1 kA
Sym. LG (I2)
Answer
Figure 1.2-5. Example 1 — One Line Diagram The 50VCP-W250 breaker capabilities
From transformer losses per unit or percent exceed the duty requirements and
R is calculated may be applied.

31,000 Watts Full Load 24.2 kW With this application, short cuts could
R = -------------------------------- = .0065 pu or .65%
– 6,800 Watts No Load 3750 kVA have been taken for a quicker check of
the application. If we assume unlim-
2 2 2 2
ited short circuit available at 13.8 kV
Transformer X = Z –R (5.09) – (.65) = 25.91 – .42 = 25.48 and that Trans. Z = X
X = 5.05% I .52
Then I 3-Phase = ----B- = -------------- = 9.5 kA Sym.
X .055
X R X/R
13.8 kV System .99% .066% 15 X/R ratio 15 or less multiplying factor
Transformer 5.05% .65% 8 is 1.0 for short circuit duty.
System Total 6.04% .716 % 9
The short circuit duty is then 9.5 kA
or .0604 pu .00716 pu
Sym. (I1, I2) and momentary duty is
9.5 x 1.6 kA = 15.2 kA (I3).

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-9
January 2003 System Analysis
Ref. No. 0043

Example 2 — Fault Calculations


Given the system shown with motor 13.8 kV System
loads, calculate the fault currents X = 15
and determine proper circuit breaker 21 kA Sym. Available
13.8 kV R
selection.
X = 5.5% X
All calculations on per unit basis. 7500 kVA Z = 5.53% = 10
R = 0.55% R
7.5 MVA Base
1
7.5 MVA 6.9 kV
Base Current I B = ------------------------------- = .628 kA
3 6.9 kV 1

X R X/R
13.8 kV System
.628 (6.9) X
X = ----------- --------------- = .015 .015 .001 15 X
21 (13.8) = 25 = 35
R R
Transformer .055 .0055 10 2 3
197A FL 173A FL
Total Source Transformer .070 pu .0065 pu 11 X''d = 20% X''d = 25%

3000 hp Synchronous Motor


3000 hp
(.628) 2500 hp
X = .20 ------------------- = .638 pu at 7.5 MVA base 1.0 PF
.197 Syn. Ind.

2500 hp Ind. Motor


(.628) Figure 1.2-6. Example 2 — One Line Diagram
X = .25 ------------------- = .908 pu at 7.5 MVA base
(.173)
Source of Interrupting Momentary X X (1) 1
Short Circuit Current E/X Amperes E/X Amperes R R (X) R
E I
I 3-Ph = ----- = ----B- where X on per unit base I3 Source Transformer .628 .628 11 11
X X .070
= 8.971
.070
= 8.971
.070
= 157

Table 1.2-7. Multiplying Factor for E/X I1 3000 hp Syn. Motor .628 .628 25 = 39
= .656 = .984 25
Amperes (ANSI C37.010, 1979, Figures 1.1-8, (1.5) .638 .638 .638
1.1-9, and 1.1-10) I1 2500 hp Syn. Motor .628
= .461
.628
= .691 35 35 = 39
(1.5) .908 .908 .908
System Type VCP-W Vacuum
X/R Circuit Breaker I3F = 10.088 10.647 Total 1/R = 235
Rated Interrupting Time, 5 Cycle or 10.1 kA x 1.6
17.0 kA Momentary Duty
Type of Fault
Ratio 3-Phase LG 3-Phase & LG
IB .628
Source of Short Circuit Total X = -------
- = -------------- = .062
I 3F 10.1
Local Remote

1 1.00 1.00 1.00 X


15 1 1.00 1.00 1.00
System ----- = .062 (235) = 14.5 is a Multiplying Factor of 1.0 from Table 1.2-7
R
20 1.00 1.02 1.05
25 1.00 1.06 1.10 Table 1.2-8. Short Circuit Duty = 10.1 kA
30 1.04 1.10 1.13
Breaker V 3-Phase Symmetrical Interrupting Capability Close and Latch
36 1.06 1.14 1.17
Type Max. at V Max. Max. KI at 6.9 kV Oper. Voltage or Momentary
40 1.08 1.16 1.22
45 1.12 1.19 1.25
50 1.13 1.22 1.27 75VCP-W500 8.25 kV 33 kA 41 kA 8.25 (33) = 39.5 kA 66 kA
55 1.14 1.25 1.30 6.9
60 1.16 1.26 1.32 150VCP-W500 15 kV 18 kA 23 kA 15 (18) (39.1) = 23 kA 37 kA
65 1.17 1.28 1.33 6.9
70 1.19 1.29 1.35 (But not to exceed KI)
75 1.20 1.30 1.36
80 1.21 1.31 1.37 Answer
85 — — 1.38
90 1.22 1.32 1.39
Either breaker could be properly
95 — — 1.40 applied, but price will make the type
100 1.23 1.33 1.41 150VCP-W500 the more economical
100 1.24 1.34 1.42 selection.
120 1.24 1.35 1.43
130 1.24 1.35 1.43
1 Where system X/R ratio is 15 or less, the
Multiplying Factor is 1.0.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-10 Power Distribution Systems
System Analysis January 2003
Ref. No. 0044

Example 3 — Fault Calculations Answer


Check breaker application or generator bus for the system of generators shown. The 50VCP-W250 breaker could be
Each generator is 7.5 MVA, 4.16 kV 1040 amperes full load, I B = 1.04 kA applied.

Sub transient reactance Xd” = 11% or, X = 0.11 pu


X
Gen ----- ratio is 30
1 R

1 1 1 1 3 1 1 1 1 3
−−−− = −− + −− + −− = −− and −−− = −− + −− + −− = −−
XS X X X X RS R R R R

G1 G2 G3
X R X X X
or X S = ----- and R S = ---- Therefore, System --------S = ----- = Gen ----- = 30
3 3 RS R R

Since generator neutral grounding reactors are used to limit the I LG to I3-phase or
below, we need only check the I3 short circuit duty.

I I I 31 3(1.04) 4.16 kV
I B Phase = ----B- + ----B- + ----B- + ----------B- = ----------------------- = 28.4 kA Symmetrical E/X Amperes
X X X X .11

X
System ----- of 30 is a Multiplying Factor of 1.04 from Table 1.2-7.
R
Short-circuit duty is 28.4 (1.04) = 29.5 kA Symmetrical
3-Phase Symmetrical Interrupting Capability Figure 1.2-7. Example 3 — One-Line Diagram
Breaker Type V Max. at V Max. Max. KI at 4.16 kV Oper. Voltage
50VCP-W250 4.76 kV 29 kA 36 kA 4.76
(29) = 33.2 kA
4.16

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-11
January 2003 System Analysis
Ref. No. 0045

Medium Voltage Fuses Calculation of the Fuse Required Low Voltage Power Circuit
Interrupting Rating: Breakers Type MagnumE DS,
There are two basic types of medium
voltage fuses. The following definitions Step 1 — Convert the fault from
the utility to percent or per unit on DSII or DSLII
are taken from ANSI Standard C37.40.
a convenient voltage and kVA base. The steps for calculating the fault cur-
Expulsion Fuse (Unit) rent for the selection of a low voltage
Step 2 — Collect the X and R data of all power circuit breaker are the same as
A vented fuse (unit) in which the
the other circuit elements and convert those used for medium voltage circuit
expulsion effect of the gases produced
to a percent or per unit on a conve- breakers except that where the con-
1
by internal arcing, either alone or aided
nient kVA and voltage base same as nected loads to the low voltage bus
by other mechanisms, results in current
that used in Step 1. Use the substran- includes induction and synchronous
interruption.
sient X and R for all generators and motor loads. The assumption is made
Current-Limiting Fuse (Unit) motors. that in 208Y/120-volt systems the
A fuse unit that, when its current- Step 3 — Construct the sequence contribution from motors is 2 times the
responsive element is melted by a networks using reactances and connect full load current of step-down trans-
current within the fuse’s specified properly for the type of fault under former. This corresponds to an assumed
current- limiting range, abruptly consideration and reduce to a single 50% motor aggregate impedance on a
introduces a high resistance to equivalent reactance. kVA base equal to the transformer kVA
reduce current magnitude and rating or 50% motor load. For 480-,
duration, resulting in subsequent Step 4 — Construct the sequence 480Y/277- and 600-volt systems the
current interruption. networks using resistances and assumption is made that the contribu-
connect properly for the type of tion from the motors is four times
There are two classes of fuses; fault under consideration and reduce the full load current of the step-down
power and distribution. They are to a single equivalent resistance. transformer which corresponds to an
distinguished from each other by assumed 25% aggregate motor imped-
the current ratings and minimum Step 5 — Calculate the E/XI value,
ance on a kVA base equal to the trans-
melting type characteristics. where E is the prefault value of the
former kVA rating or 100% motor load.
voltage at the point of fault normally
The current limiting ability of a assumed 1.0 in pu. For 3-phase faults In low voltage systems which contain
current limiting fuse is specified by E/XI is the fault current to be used in generators the subtransient reactance
its threshold ratio, peak let-through determining the required interrupting should be used.
current and I2t characteristics. capability of the fuse.
If the X/R to the point of fault is greater
Interrupting Ratings of Fuses Note: It is not necessary to calculate a than 6.6, a derating multiplying factor
Modern fuses are rated in amperes single phase-to-phase fault current. This (MF) must be applied. The X/R ratio is
rms symmetrical. They also have a current is very nearly 3 /2 x 3-phase fault. calculated in the same manner as that
The line-to-ground fault may exceed the
listed asymmetrical rms rating which for medium voltage circuit breakers.
3-phase fault for fuses located in generating
is 1.6 x the symmetrical rating. stations with solidly grounded neutral Calculated symmetrical amperes x
generators, or in delta-wye transformers
Refer to ANSI/IEEE C37.48 for fuse MF ≤ breaker interrupting rating.
with the wye solidly grounded, where the
interrupting duty guidelines. sum of the positive and negative sequence The multiplying factor MF can be
impedances on the high voltage side (delta) calculated by the formula:
is smaller than the impedance of the
transformer. – ( π ) ⁄ ( X/R )
2 [ 1 + 2.718 ]
MF = −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
For single line-to-ground fault; 2.29
X I = X I (+) + X I (–) + X I (0) If the X/R of system feeding the
breaker is not known, use X/R = 15.
E For fused breakers by the formula:
I f = ------ × 3
XI
– ( 2π ) ⁄ ( X/R )
1 + 2 × ( 2.718 )
MF = −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Step 6 — Select a fuse whose 1.25
published interrupting rating
exceeds the calculated fault current. If the X/R of the system feeding the
breaker is not known, use X/R = 20.
Table 1.2-1 should be used where
older fuses asymmetrically rated are Refer to Table 1.2-9 for the standard
involved. ranges of X/R and Power Factors used
in testing and rating low voltage break-
The voltage rating of power fuses used ers. Refer to Table 1.2-10 for the circuit
on 3-phase systems should equal breaker interrupting rating multiplying
or exceed the maximum line-to-line factors to be used when the calculated
voltage rating of the system. Current X/R ratio or power factor at the point
limiting fuses for 3-phase systems the breaker is to be applied in the
should be so applied that the fuse power distribution system falls outside
voltage rating is equal to or less than of the Table 1.2-9 X/R or power factors
1.41 x nominal system voltage. used in testing and rating the circuit
breakers. MF is always greater than 1.0.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-12 Power Distribution Systems
System Analysis January 2003
Ref. No. 0046

Molded Case Breakers and Refer to Table 1.2-9 for the standard cover most applications. Established
Insulated Case Type SPB Breakers ranges of X/R and power factors used standard values include the following:
The method of fault calculation is the in testing and rating low voltage
breakers. Refer to Table 1.2-10 for Table 1.2-9. Standard Test Power Factors
same as that for low voltage power
circuit breakers. Again the calculated the circuit breaker interrupting rating Interrupting Power Factor X/R Test
de-rating factors to be used when the Rating in kA Test Range Range
fault current x MF ≤ breaker interrupt-
ing capacity. Because molded case calculated X/R ratio or power factor Molded Case Circuit Breaker
breakers are tested at lower X/R ratios at the point the breaker is to be applied 10 or Less .45 – .50 1.98 – 1.73
1 the MFs are different than those for in the power distribution system falls Over 10 to 20 .25 – .30 3.87 – 3.18
outside of the Table 1.2-9 X/R or power Over 20 .15 – .20 6.6 – 4.9
low voltage power circuit breakers.
factors used in testing and rating the Low Voltage Power Circuit Breaker
circuit breakers.
– π ⁄ − −
X2 All .15 Maximum 6.6 Minimum
1 + 2.718  R 2
MF = ---------------------------------------------------- Normally the short circuit power factor
For distribution systems where the
– π ⁄ − −1
X or X/R ratio of a distribution system
 R 1 calculated short circuit current X/R
1 + 2.718 need not be considered in applying
ratio differs from the standard values
low voltage circuit breakers. This is
given in the above table, circuit breaker
X 1 ⁄ R 1 = test X/R value. because the ratings established in
interrupting rating derating factors from
the applicable standard are based
the following table should be applied.
on power factor values which amply
X 2 ⁄ R 2 = X/R at point where breaker
is applied.
Table 1.2-10. Circuit Breaker Interrupting Rating Derating Factors
% P.F. X/R Interrupting Rating
MCB PCB
>10 kA
< / = 10 kA < / = 20 kA >20 kA Unfused Fused

50 1.73 1.000 1.000 1.000 1.000 1.000


30 3.18 .847 1.000 1.000 1.000 1.000
25 3.87 .805 .950 1.000 1.000 1.000
20 4.90 .762 .899 1.000 1.000 1.000
15 6.59 .718 .847 .942 1.000 .939
12 8.27 .691 .815 .907 .962 .898
10 9.95 .673 .794 .883 .937 .870
8.5 11.72 .659 .778 .865 .918 .849
7 14.25 .645 .761 .847 .899 .827
5 19.97 .627 .740 .823 .874 .797

Note: These are derating factors applied to the breaker and are the inverse of MF.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-13
January 2003 System Analysis
Ref. No. 0047

Short Circuit Calculations — Short Cut Method


Determination of Short Circuit Current
Note 1: Transformer impedance generally relates to self-ventilated rating (e.g., with OA/FA/FOA transformer use OA base).
Note 2: kV refers to line-to-line voltage in kilovolts.
Note 3: Z refers to line-to-neutral impedance of system to fault where R + jX = Z.
Note 4: When totaling the components of system Z, arithmetic combining of impedances as “ohms Z”. “per unit Z”. etc., is considered a
short cut or approximate method; proper combining of impedances (e.g., source, cables transformers, conductors, etc). should use 1
individual R and X components. This Total Z = Total R + j Total X (See IEEE “Red Book” Standard No. 141).

1. Select convenient kVA base for system to


be studied.
kVA base 2
2. Change per unit, or percent, impedance from (a) Per unit = pu impedance kVA base 2 = −−−−−−−−−−−−−−− × (pu impedance on kVA base 1)
kVA base 1
one kVA base to another:
kVA base 2
(b) Percent = % impedance kVA base 2 = −−−−−−−−−−−−−−− × (% impedance on kVA base 1)
kVA base 1
percent impedance (ohms impedance) (kVA base)
3. Change ohms, or percent or per-unit, etc.: (a) Per unit impedance = pu Z = −−−−−−−−−−−−−−−−−−−−−−−−−− = −−−−−−−−−−(−kV
−−−−−2−−−−−−−−−− −−−−−−−−−−−−−−
) ( 1000 )
100
(ohms impedance) (kVA base)
(b) % impedance = % Z = −−−−−−−−−−−−−−−−2−−−−−−−−−− −−−−−−−−−−−−−−
( kV ) ( 10 )
(% impedance) ( kV )2 (10)
(c) Ohms impedance = −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
kVA base

4. Change power-source impedance to per-unit (a) — if utility fault capacity given in kVA
or percent impedance on kVA base as selected
for this study: kVA base in study
Per-unit impedance = pu Z = -------------------------------------------------------------------------------------------
power-source kVA fault capacity

(b) — if utility fault capacity given in rms symmetrical short circuit amperes

kVA base in study


Per-unit impedance = pu Z = ----------------------------------------------------------------------------------------------------------------
(short-circuit current) ( 3 )(kV of source)

5. Change motor rating to kVA: (a) — motor kVA — ( 3 ) (kV) (I) where I = motor nameplate full-load amperes
(b) — if 1.0 power factor synchronous motor kVA = (0.8) (hp)
(c) — if 0.8 power factor synchronous motor kVA = (1.0) (hp)
(d) — if induction motor kVA = (1.0) (hp)

3-phase kVA 1-phase kVA


6. Determine symmetrical short circuit current: (a) Base current = I Base = −−−−−−−−−−−−−−−−− or −−−−−−−−−−−−−−−−−−−−−−−
( 3 ) ( kV ) kV line-to-neutral
1.0
(b) Per unit I SC = −−−−−
puZ

(c) rms Symmetrical current = ISC = (pu ISC) (IBase Amperes)

3-phase kVA base 1-phase kVA base


(d) rms Symmetrical current = Amperes = -------------------------------------------------- or --------------------------------------------------
( puZ ) ( 3 ) ( kV ) ( puZ ) ( kV )
(3-phase kVA base) (100) 1-phase kVA base (100)
(e) = ---------------------------------------------------------------------- or ------------------------------------------------------------------
(%Z) ( 3 ) ( kV ) (%Z) ( kV )
(kV) (1000)
(g) = -----------------------------------
3 (ohms Z)
kVA base (kVA base) (100) ( kV )2 ( 1000 )
(a) Symmetrical short circuit kVA = -------------------------- = ---------------------------------------------- = ----------------------------------
7. Determine symmetrical short circuit kVA: ( puZ ) %Z ohms Z
3(line-to-neutral kV) 2 ( 1000 )
(b) = -----------------------------------------------------------------------------
(ohms Z)

8. Determine line-to-line short circuit current: (a) — from 3-phase transformer — approx. 86% of 3-phase current
(b) — three single-phase transformers (e.g., 75 kVA, Z = 2%) calculate same as one 3-phase unit
(i.e., 3 x 75 kVA = 225 kVA, Z = 2%).
(c) — from single-phase transformer — see Page 1.2-15.

9. Determine motor contribution (or feedback) as


source of fault current:
(a) — synchronous motor — 5 times motor full load current (impedance 20%) See IEEE
(b) — induction motor — 4 times motor full-load current (impedance 25%) Standard No. 141 j
(c) — motor loads not individually identified, use contribution from group of motors as follows:
— on 208Y/120 volt systems — 2.0 times transformer full-load current
— on 240-480-600 volt 3-phase, 3-wire systems — 4.0 times transformer full-load current
— on 480Y/277 volt 3-phase, 4-wire systems
— In commercial buildings, 2.0 times transformers full-load current (50% motor load)
— In industrial plants, 4.0 times transformer full-load current (100% motor load)

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-14 Power Distribution Systems
System Analysis January 2003
Ref. No. 0048

Example Number 1
How to Calculate Short Circuit Currents at Ends of Conductors

A. System Diagram B. Impedance Diagram (Using “Short Cut” Method for Combining Impedances
and Sources).
A B C
1 Utility Source 500 MVA
V
VA
Major Contribution
Utility

Cables
Transformer
Switchboard Fault
1,000 kVA
V
VA
5.75%
480 Volts Cables

Cable Fault
Switchboard Fault

.002 pu 1.00 pu 1.00 pu 1.00 pu


100 Feet (30 m)
3 – 350 kcmil Cable
in Steel Conduit
A B C .0575 pu .027 pu .027 pu .027 pu
Switchboard Fault
Mixed Load — Motors and Lighting
Each Feeder — 100 Feet (30 m) of 3 – 350 kcmil
Cable in Steel Conduit Feeding Lighting and .027 pu
250 kVA of Motors
Cable Fault

Cable Fault
Combining Series Impedances: ZTO L = 1 + Z2 + ... +Zn

1 = 1 + 1 + ... 1
Combining Parallel Impedances:
C. Conductor impedance from Table 1.4-18, ZTOTAL Z1 Z2 Zn
Page 1.4-11. Conductors: 3 – 350 kcmil cop-
per, single conductors Circuit length: 100 feet
(30 m), in steel (magnetic) conduit Impedance .0595 pu .342 pu .0507 pu
Z = 0.00619 ohms/100 feet (30 m). E .0777 pu
ZTOT = 0.00619 ohms (100 circuit feet)
.027 pu .027 pu
D. Fault current calculations (combining imped-
ances arithmetically, using approximate
“Short Cut” method — see Note 4,
Page 1.2-13)
Equation
Step (See Page 1.2-13) Calculation
1 – Select 1000 kVA as most convenient base, since all data except utility source is on
secondary of 1000 kVA transformer.
kVA base 1000
2 4(a) Utility per unit impedance = Z pu = ------------------------------------------- = --------------------- = 0.002 pu
utility fault kVA 500.000

%Z 5.75
3 3(a) Transformer per unit impedance = Z pu = ---------- = ----------- = 0.0575 pu
100 100

kVA base 1000


4 4(a) and Motor contribution per unit impedance = Z pu = ---------------------------------------- = -------------------- = 1.00 pu
9(c) 4 x motor kVA 4 x 250

5 3(a) Cable impedance in ohms (see above) = 0.00619 ohms


(ohms)(kVA base) (0.00619)(1000)
Cable impedance per unit = Z pu = -------------------------------------------------
2
- = ------------------------------------------
2
- = 0.027pu
(kV) (1000) (0.480) (1000)

6 6(d) Total impedance to switchboard fault = 0.0507 pu (see diagram above)


3-phase kVA base 1000
Symmetrical short circuit current at switchboard fault = −−−−−−−−−−−−−−−−−−−−−−−− = −−−−−−−−−−−−−−−−−−−−−−−−−−− = 23,720 amperes rms
( Z pu ) ( 3 ) ( kV ) ( 0.0507 ) ( 3 ) ( 0.480 )

7 6(d) Total impedance to cable fault = 0.0777 pu (see diagram above)


3-phase kVA base 1000
Symmetrical short circuit current at cable fault = −−−−−−−−−−−−−−−−−−−−−−−− = −−−−−−−−−−−−−−−−−−−−−−−−−−− = 15, 480 amperes rms
( Z pu ) ( 3 ) ( kV ) ( 0.0777 ) ( 3 ) ( 0.480 )

Figure 1.2-8. Example Number 1

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-15
January 2003 System Analysis
Ref. No. 0049

Example Number 2
Fault Calculation — Secondary Side of Single-Phase Transformer

A. System Diagram Deriving Transformer R and X:


R = 0.1498 Z
480-Volt 3-Phase Switchboard Bus at 50,000 Amp Symmetrical, X/R = 6.6 X = 0.9887 Z{ X

R
= 6.6 X = 6.6 R

2 2 2 2 2 2 2
1
Z= X +R = ( 6.6R ) + R = 43.56R + R = 44.56R = 6.6753R
100 Ft. Two #2/0 Copper Conductors, Magnetic Conduit R = 0.0104 Ohms
{
X = 0.0051 Ohms Z
R= −−−−−−−− R = 0.1498Z
6.6753
75 kVA
V Single-Phase 480-120/240 Volts; Z = 2.8%, R = 1.64%, X = 2.27%
VA
X = 6.6R X = 0.9887Z

120 Volts
F2
Half-winding of Transformer
{ Multiply % R by 1.5
Multiply % X by 1.2 } Reference: IEEE Standard No. 141
240 V
Full-winding of Transformer
F1

B. Impedance Diagram — Fault F1 C. Impedance Diagram — Fault F2

RSyst = 0.00054 RSyst = 0.00356 RSyst = 0.00054 XSyst = 0.00356

RCond = 0.00677 RCond = 0.00332 RCond = 0.00677 XCond = 0.00332

RTfmr = 0.0164 RTfmr = 0.0227 RTfmr = 0.0246 XTfmr = 0.0272

RTotal
T
To = 0.02371 RTotal
T
To = 0.02958 RTotal
T
To = 0.03191 XTotal
T
To = 0.03408
F1 F1 F2 F2

D. Impedance and Fault Current Calculations — 75 kVA Base


Note: To account for the outgoing and return paths of single-phase circuits (conductors,
systems, etc.) use twice the 3-phase values of R and X.
75
ZSyst = −−−−−−−−−−−−−−−−−−−−−−−−−−− = 0.0018 pu (From Page 1.2-13 RSyst = 2 (0.1498 x Z) = 0.00054 pu
3 × 0.480 × 50,000 Formula 4(b) )
XSyst = 2 (0.9887 x Z) = 0.00356 pu
ohms × kVA Base 0.0104 × 75
ZCond = −−−−−−−−−−−2−−−−−−−−−−−−−− (From Page 1.2-13 RCond = 2  −−−−−−2−−−−−−−−−−− = 0.00677 pu
( kV ) × 1000 Formula 3(a) )  0.48 × 1000
0.0051 × 75 
XCond = 2  −−−−−−−−− −−−−−−−−−− = 0.00332 pu
 ( 0.48 ) 2 × 1000
1.64
Full-winding of Transformer (75 kVA Base) RTfmr = −−−−− = 0.0164 pu
100
2.27
XTfmr = −−−−− = 0.0277 pu
100
1.64
Half-winding of Transformer (75 kVA Base) RTfmr = 1.5 ( −−−−− ) = 0.0246 pu
100
2.27
XTfmr = 1.2 ( −−−−− ) = 0.0272 pu
100

Impedance to Fault F1 — Full Winding 2 2


Z= ( 0.02371 ) + ( 0.02958 ) = 0.03791 pu
Impedance to Fault F2 — Half Winding
Z= 2 2 = 0.04669 pu
Short circuit current F1 = 75 ÷ (0.03791 x 0.240 kV) = 8,243 Ampere Symmetrical ( 0.03191 ) + ( 0.03408 )
Short circuit current F2 = 75 ÷ (0.04669 x 0.120 kV) = 13,386 Ampere Symmetrical

Figure 1.2-9. Example Number 2

Method 1: Short Cut Methods 277 volts/30,000 amperes = 0.00923 Next, 277 volts/0.01196 ohms = 23,160
ohms (source impedance) amperes rms at load side of conductors
This method uses the approximation
of adding Zs instead of the accurate Conductor ohms for 500 kcmil conduc-
method of Rs and Xs. tor from reference data in this section X 30,000 amperes available
in magnetic conduit is 0.00546 ohms
For Example: For a 480/277-volt sys- per 100 feet (30 m). For 100 feet (30 m)
tem with 30,000 amperes symmetrical and 2 conductors per phase we have: 100 feet (30 m)
available at the line side of a conductor 2 – 500 kcmil per phase
run of 100 feet (30 m) of 2 – 500 kcmil 0.00546/2 = 0.00273 ohms (conductor
per phase and neutral, the approxi- impedance)
mate fault current at the load side end X If = 23,160 amperes
of the conductors can be calculated Add source and conductor impedance or
as follows. 0.00923 + 0.00273 = 0.01196 total ohms Figure 1.2-10. Short Circuit Diagram

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-16 Power Distribution Systems
System Analysis January 2003
Ref. No. 0050

Method 2: Short Circuit Current Readout Step Four


Chart Approximate Method The readout obtained from the charts Select the specific curve for the con-
is the rms symmetrical amperes avail- ductor size being used. If your conduc-
The chart method is based on the tor size is something other than the
following: able at the given distance from the
transformer. The circuit breaker should sizes shown on the chart, refer to the
Motor Contribution have an interrupting capacity at least conductor conversion Table 1.2-11.
For system voltages of 120/208 volts, as large as this value. Step Five
1 it is reasonable to assume that the Enter the chart along the bottom hori-
connected load consists of 50% motor How to Use the Short Circuit Charts zontal scale with the distance (in feet)
load, and that the motors will contribute from the transformer to the fault point.
four times their full load current into a Step One
Draw a vertical line up the chart to the
fault. For system voltages of 240 and Obtain the following data:
point where it intersects the selected
480 volts, it is reasonable to assume curve. Then draw a horizontal line to
1. System voltage
that the connected load consists of the left from this point to the scale
100% motor load, and that the motors 2. Transformer kVA rating along the left side of the chart.
will contribute four times their full load (from transformer nameplate)
current into a fault. These motor con- Step Six
tributions have been factored into 3. Transformer impedance
The value obtained from the left-hand
each curve as if all motors were con- (from transformer nameplate)
vertical scale is the fault current (in
nected to the transformer terminals. 4. Primary source fault energy thousands of amperes) available at the
available in kVA (from electric fault point.
Feeder Conductors
utility or distribution system
The conductor sizes most commonly For a more exact determination, see the
engineers)
used for feeders from molded case cir- formula method. It should be noted
cuit breakers are shown. For conductor Step Two that even the most exact methods
sizes not shown, the following table Select the applicable chart from the for calculating fault energy use some
has been included for conversion to following pages. The charts are approximations and some assumptions.
equivalent arrangements. In some cases grouped by secondary system voltage Therefore, it is appropriate to select a
it may be necessary to interpolate for which is listed with each transformer. method which is sufficiently accurate
unusual feeder ratings. Table 1.2-11 is Within each group, the chart for the for the purpose, but not more burden-
based on using copper conductor. lowest kVA transformer is shown first, some than is justified. The charts
followed in ascending order to the which follow make use of simplifica-
Table 1.2-11. Conductor Conversion tions which are reasonable under
(Based on Using Copper Conductor) highest rated transformer.
most circumstances and will almost
If Your Use Equivalent Step Three certainly yield answers which are on
Conductor is: Arrangement the safe side. This may, in some cases,
Select the family of curves that is closest
3 – No. 4/0 Cables 2 – 500 kcmil to the “available source kVA.” The black lead to application of circuit breakers
4 – No. 2/0 Cables 2 – 500 kcmil line family of curves is for a source of having interrupting ratings higher than
3 – 2000 kcmil Cables 4 – 750 kcmil 500,000 kVA. The lower value line (in necessary, but should eliminate the
5 – 400 kcmil Cables 4 – 750 kcmil red) family of curves is for a source of possibility of applying units which will
6 – 300 kcmil Cables 4 – 750 kcmil 50,000 kVA. You may interpolate not be safe for the possible fault duty.
800 Ampere Busway 2 – 500 kcmil between curves if necessary, but for
1000 Ampere Busway 2 – 500 kcmil values above 100,000 kVA it is appro-
1600 Ampere Busway 4 – 750 kcmil
priate to use the 500,000 kVA curves.

UTILITY KVA
V
VA

12.5

10.0

250 kcmil
W
WG
7.5 W
WG

5.0

2.5

0
0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T

Figure 1.2-11. 225 kVA Transformer/4.5% Impedance/208 Volts

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-17
January 2003 System Analysis
Ref. No. 0051

KV kcmil A
kcmil
Fault Current in Thousands of Amperes (Sym.)

30

Fault Current in Thousands of Amperes (Sym.)


60
kcmil
B
25 50
#4 A F 50,000 F 50,000
F
20 B 40 1
F

15 30

10 20 W
WG

5 10

0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.2-12. 300 kVA Transformer/4.5% Impedance/208 Volts Figure 1.2-15. 1000 kVA Transformer/5.5% Impedance/208 Volts

B
KV A
Fault Current in Thousands of Amperes (Sym.)

30 120
F

25 100
F 50,000
W
WG

20 80 B

15 60 F
4
2
10 40

5 20 #4 AWG
A
AW

0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.2-13. 500 kVA Transformer/4.5% Impedance/208 Volts Figure 1.2-16. 1500 kVA Transformer/5.5% Impedance/208 Volts

A A
Fault Current in Thousands of Amperes (Sym.)

60 120 –

– B
50 100 W
WG
F 50,000 F 50,000
W
WG

40 B 80

F
F
30 60

20 40
4– kcmil

10 20

0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.2-14. 750 kVA Transformer/5.5% Impedance/208 Volts Figure 1.2-17. 2000 kVA Transformer/5.5% Impedance/208 Volts

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-18 Power Distribution Systems
System Analysis January 2003
Ref. No. 0052

A A
Fault Current in Thousands of Amperes (Sym.)

Fault Current in Thousands of Amperes (Sym.)


12 30
W
WG
B
10 25
B F 50,000 F 50,000

F
1 8 20

6 4 15
2 4 – 750 kcmil
2

4 10

2 5

0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.2-18. 300 kVA Transformer/4.5% Impedance/480 Volts Figure 1.2-21. 1000 kVA Transformer/5.5% Impedance/480 Volts

A A
Fault Current in Thousands of Amperes (Sym.)

Fault Current in Thousands of Amperes (Sym.)

30 60

25 50 kcmil
F 50,000 F 50,000

#4 AWG
A
AW
20 40
– B

15 B #1/0 AWG
A
AW 30
#4 AWG
A
AW F

10 20
4 750 kcmil

5 10

0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.2-19. 500 kVA Transformer/4.5% Impedance/480 Volts Figure 1.2-22. 1500 kVA Transformer/5.5% Impedance/480 Volts

A A
Fault Current in Thousands of Amperes (Sym.)

Fault Current in Thousands of Amperes (Sym.)

30 60 4– kcmil

750
25 500 50 B W
WG
F 50,000 F 50,000

20 B 40

F
F
15 30

4– kcmil
10 20

#4 A
5 10

0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.2-20. 750 kVA Transformer/5.5% Impedance/480 Volts Figure 1.2-23. 2000 kVA Transformer/5.5% Impedance/480 Volts

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-19
January 2003 System Analysis
Ref. No. 0053

Determining X and R Values How to Estimate Short Method 2:


Circuit Currents at Transformer Refer to Page 1.4-7 in the Reference
from Transformer Loss Data section, and use appropriate row of
Secondaries: data based on transformer kVA and
Method 1:
primary short circuit current available.
Given a 500 kVA, 5.5% Z transformer Method 1:
This will yield more accurate results
with 9000W total loss; 1700W no-load To obtain 3-phase rms symmetrical and allow for including motor short
loss; 7300W load loss and primary short circuit current available at circuit contribution.
voltage of 480V. transformer secondary terminals, 1
2 use the formula:
3 ×  −−−−−−−−−−−−−−−−− × R = 7300 Watts
500
 3 × 0.480 100
I SC = I FLC × ------------
%Z
%R = .0067 ohms
where %Z is the transformer impedance
0.0067 × 500 in percent, from Table 1.4-5 through
%R = −−−−−−−−−−−−−−−−−−2−− = 1.46% 1.4-8, Page 1.4-8.
10 × 0.48
This is the maximum 3-phase symmet-
2 2
%X = 5.5 – 1.46 = 5.30% rical bolted-fault current, assuming
sustained primary voltage during fault,
Method 2: i.e., an infinite or unlimited primary
Using same values above. power source (zero source impedance).
Since the power source must always
2
I R Losses have some impedance this a conserva-
%R = −−10
−−−−−−−−−−−−−−−
× kVA tive value; actual fault current will be
somewhat less.
7300
−−−−−−−−−−−−− = 1.46 Note: This will not include motor short
10 × 500
circuit contribution.
2 2
%X = 5.5 – 1.46 = 5.30%

See Tables 1.4-9 through 1.4-12 on


Page 1.4-9 for loss data on transformers.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-20 Power Distribution Systems
System Analysis January 2003
Ref. No. 0054

Voltage Drop Table 1.2-12. Temperature Correction Factors


for Voltage Drop
To select minimum conductor size:
1. Determine maximum desired
Voltage Drop Tables Conductor Percent Correction voltage drop, in volts.
Size Power Factors %
Note: Busway voltage drop tables are 2. Divide voltage drop by (amperes x
shown in Section 23 of this catalog. 100 90 80 70 60 circuit feet).
No. 14 to No. 4 5.0 4.7 4.7 4.6 4.6
Tables for calculating voltage drop for No. 2 to 3/0 5.0 4.2 3.7 3.5 3.2
3. Multiply by 100.
1 copper and aluminum conductors, in 4/0 to 500 kcmil 5.0 3.1 2.6 2.3 1.9 4. Find nearest lower voltage drop
either magnetic (steel) or nonmagnetic 600 to 1000 kcmil 5.0 2.6 2.1 1.5 1.3
value in tables, in correct column
(aluminum or non-metallic) conduit,
for type of conductor, conduit and
appear on Page 1.2-21. These tables Calculations power factor. Read conductor size
give voltage drop per ampere per
for that value.
100 feet (30 m) of circuit length To calculate voltage drop:
(not conductor length). 1. Multiply current in amperes by 5. Where this results in an oversized
the length of the circuit in feet to cable, verify cable lug sizes for
Tables are based on the following
get ampere-feet (circuit length, molded case breakers and fusible
conditions: switches. Where lug size available
not conductor length).
1. Three or four single conductors in is exceeded, go to next higher
a conduit, random lay. For three- 2. Divide by 100. rating.
conductor cable, actual voltage
3. Multiply by proper voltage drop Example:
drop will be approximately the
value in tables. Result is voltage
same for small conductor sizes A 3-phase, 4-wire lighting feeder on
drop.
and high power factors. Actual a 208-volt circuit is 250 feet (76.2 m)
voltage drop will be from 10 to Example: long. The load is 175 amperes at 90%
15% lower for larger conductor A 460-volt, 100-hp motor, running at PF. It is desired to use aluminum con-
sizes and lower power factors. 80% PF, draws 124 amperes full-load ductors in aluminum conduit. What
current. It is fed by three 2/0 copper size conductor is required to limit the
2. Voltage drops are phase-to-phase,
conductors in steel conduit. The feeder voltage drop to 2% phase-to-phase?
for 3-phase, 3-wire or 3-phase,
4-wire 60 Hz circuits. For other length is 150 feet (46 m). What is the 1. VD = −−− 2−− × 208 = 4.16 volts
circuits, multiply voltage drop voltage drop in the feeder? What is 100
given in the tables by the follow- the percentage voltage drop?
2. −−−−−4.16
−−−−−−−−−−
ing correction factors: 1. 124 amperes x 150 feet (46 m) = 175 × 250 = 0.0000951
3-phase, 4-wire, 18,600 ampere-feet
phase-to-neutral x 0.577 3. 0.0000951 × 100 = 0.00951
2. Divided by 100 = 186
1-phase, 2-wire x 1.155 4. In table, under Aluminum Conduc-
1-phase, 3-wire, 3. Table: 2/0 copper, magnetic conduit, tors, nonmagnetic conduit, 90%
phase-to-phase x 1.155 80% PF = 0.0187 PF, the nearest lower value is
1-phase, 3-wire, 186 x 0.0187 = 3.48 volts drop 0.0091. Conductor required is
phase-to-neutral x 0.577 3.48 x 100 = 0.76% drop 500 kcmil. (Size 4/0 THW would
460 have adequate ampacity, but the
3. Voltage drops are for a conductor
temperature of 75°C. They may be 4. Conclusion: .76% voltage drop is voltage drop would be excessive).
used for conductor temperatures very acceptable
between 60°C and 90°C with
reasonable accuracy (within ±5%).
However, correction factors in
the table below can be applied if
desired. The values in the table are
in percent of total voltage drop.
For conductor temperature of 60°C –
SUBTRACT the percentage from
Table 1.2-12.
For conductor temperature of 90°C –
ADD the percentage from Table 1.2-12.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-21
January 2003 System Analysis
Ref. No. 0055

Table 1.2-13. Voltage Drop — Volts per Ampere per 100 Feet (30 m); 3-Phase, Phase-to-Phase
Conductor Size Magnetic Conduit (Steel) Nonmagnetic Conduit (Aluminum or Nonmetallic)
AWG Load Power Factor, % Load Power Factor, %
or kcmil
60 70 80 90 100 60 70 80 90 100
Copper Conductors
14 .3390 .3910 .4430 .4940 .5410 .3370 .3900 .4410 .4930 .5410
12 .2170 .2490 .2810 .3130 .3410 .2150 .2480 .2800 .3120 .3410
10 .1390 .1590 .1790 .1980 .2150 .1370 .1580 .1780 .1970 .2150 1
8 .0905 .1030 .1150 .1260 .1350 .0888 .1010 .1140 .1250 .1350
6 .0595 .0670 .0742 .0809 .0850 .0579 .0656 .0730 .0800 .0849
4 .0399 .0443 .0485 .0522 .0534 .0384 .0430 .0473 .0513 .0533
2 .0275 .0300 .0323 .0342 .0336 .0260 .0287 .0312 .0333 .0335
1 .0233 .0251 .0267 .0279 .0267 .0218 .0238 .0256 .0270 .0266
1/0 .0198 .0211 .0222 .0229 .0213 .0183 .0198 .0211 .0220 .0211
2/0 .0171 .0180 .0187 .0190 .0170 .0156 .0167 .0176 .0181 .0169
3/0 .0148 .0154 .0158 .0158 .0136 .0134 .0141 .0147 .0149 .0134
4/0 .0130 .0134 .0136 .0133 .0109 .0116 .0121 .0124 .0124 .0107
250 .0122 .0124 .0124 .0120 .0094 .0107 .0111 .0112 .0110 .0091
300 .0111 .0112 .0111 .0106 .0080 .0097 .0099 .0099 .0096 .0077
350 .0104 .0104 .0102 .0096 .0069 .0090 .0091 .0091 .0087 .0066
500 .0100 .0091 .0087 .0080 .0053 .0078 .0077 .0075 .0070 .0049
600 .0088 .0086 .0082 .0074 .0046 .0074 .0072 .0070 .0064 .0042
750 .0084 .0081 .0077 .0069 .0040 .0069 .0067 .0064 .0058 .0035
1000 .0080 .0077 .0072 .0063 .0035 .0064 .0062 .0058 .0052 .0029
Aluminum Conductors
12 .3296 .3811 .4349 .4848 .5330 .3312 .3802 .4328 .4848 .5331
10 .2133 .2429 .2741 .3180 .3363 .2090 .2410 .2740 .3052 .3363
8 .1305 .1552 .1758 .1951 .2106 .1286 .1534 .1745 .1933 .2115
6 .0898 .1018 .1142 .1254 .1349 .0887 .1011 .1127 .1249 .1361
4 .0595 .0660 .0747 .0809 .0862 .0583 .0654 .0719 .0800 .0849
2 .0403 .0443 .0483 .0523 .0535 .0389 .0435 .0473 .0514 .0544
1 .0332 .0357 .0396 .0423 .0428 .0318 .0349 .0391 .0411 .0428
1/0 .0286 .0305 .0334 .0350 .0341 .0263 .0287 .0322 .0337 .0339
2/0 .0234 .0246 .0275 .0284 .0274 .0227 .0244 .0264 .0274 .0273
3/0 .0209 .0220 .0231 .0241 .0217 .0160 .0171 .0218 .0233 .0222
4/0 .0172 .0174 .0179 .0177 .0170 .0152 .0159 .0171 .0179 .0172
250 .0158 .0163 .0162 .0159 .0145 .0138 .0144 .0147 .0155 .0138
300 .0137 .0139 .0143 .0144 .0122 .0126 .0128 .0133 .0132 .0125
350 .0130 .0133 .0128 .0131 .0100 .0122 .0123 .0119 .0120 .0101
500 .0112 .0111 .0114 .0099 .0076 .0093 .0094 .0094 .0091 .0072
600 .0101 .0106 .0097 .0090 .0063 .0084 .0085 .0085 .0081 .0060
750 .0095 .0094 .0090 .0084 .0056 .0081 .0080 .0078 .0072 .0051
1000 .0085 .0082 .0078 .0071 .0043 .0069 .0068 .0065 .0058 .0038

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-22 Power Distribution Systems
System Analysis January 2003
Ref. No. 0056

Voltage Drop Considerations Computer Equipment: With the Motor Starting: Motor inrush on start-
proliferation of data-processing and ing must be limited to minimize voltage
The first consideration for voltage computer- or microprocessor-con- dips. Table 1.2-14 on the next page will
drop is that under the steady-state trolled manufacturing, the sensitivity help select the proper type of motor
conditions of normal load, the voltage of computers to voltage has become starter for various motors, and to select
at the utilization equipment must be an important consideration. Severe generators of adequate size to limit
adequate. Fine-print notes in the NEC dips of short duration can cause a voltage dip. See Section 30 for
recommend sizing feeders and branch computer to “crash” — shut down additional data on reduced voltage
1 circuits so that the maximum voltage completely, and other voltage tran- motor starting.
drop-in either does not exceed 3%, sients caused by starting and stopping
with the total voltage drop for feeders motors can cause data-processing Where the power is supplied by a
and branch circuits not to exceed 5%, errors. While voltage drops must utility network, the motor inrush can
for efficiency of operation. (Fine print be held to a minimum, in many be assumed to be small compared
notes in the NEC are not mandatory.) cases computers will require special to the system capacity, and voltage
power-conditioning equipment to at the source can be assumed to
In addition to steady-state conditions, be constant during motor starting.
voltage drop under transient condi- operate properly.
Voltage dip resulting from motor
tions, with sudden high-current, short- Industrial Plants: Where large motors starting can be calculated on the basis
time loads, must be considered. The exist, and unit substation transformers of the voltage drop in the conductors
most common loads of this type are are relatively limited in size, voltage between the power source and
motor inrush currents during starting. dips of as much as 20% may be per- the motor resulting from the inrush
These loads cause a voltage dip on missible in some cases, if they do not current. Where the utility system is
the system as a result of the voltage occur too frequently. Lighting is often limited, the utility will often specify the
drop in conductors, transformers and supplied from separate transformers, maximum permissible inrush current
generators under the high current. and is minimally affected by voltage or the maximum hp motor they will
This voltage dip can have numerous dips in the power systems. However, it permit to be started across-the-line.
adverse effects on equipment in the is usually best to limit dips to between
system, and equipment and conduc- 5 and 10% at most. One critical consid- If the power source is a transformer,
tors must be designed and sized to eration is that a large voltage dip can and the inrush kVA or current of the
minimize these problems. In many cause a dropout (opening) of magnetic motor being started is small compared
cases, reduced-voltage starting of motor contactors and control relays. to the full-rated kVA or current of the
motors to reduce inrush current The actual dropout voltage varies con- transformer, the transformer voltage
will be necessary. siderably among starters of different dip will be small and may be ignored.
manufacturers. The only standard that As the motor inrush becomes a signifi-
Recommended Limits of exists is that of NEMA, which states cant percentage of the transformer
Voltage Variation that a starter must not drop out at 85% full-load rating, an estimate of the
of its nominal coil voltage, allowing transformer voltage drop must be
General Illumination: Flicker in added to the conductor voltage drop
incandescent lighting from voltage only a 15% dip. While most starters
will tolerate considerably more volt- to obtain the total voltage drop to the
dip can be severe; lumen output drops motor. Accurate voltage drop calcula-
about three times as much as the age dip before dropping out, limiting
dip to 15% is the only way to ensure tion would be complex and depend
voltage dips. That is, a 10% drop in upon transformer and conductor
voltage will result in a 30% drop in continuity of operation in all cases.
resistance, reactance, and impedance,
light output. While the lumen output X-Ray Equipment: Medical x-ray and as well as motor inrush current and
drop in fluorescent lamps is roughly similar diagnostic equipment, such as power factor. However, an approxima-
proportional to voltage drop, if the CAT-scanners, are extremely sensitive tion can be made on the basis of the
voltage dips about 25%, the lamp will to low voltage. They present a small, low power-factor motor inrush current
go out momentarily and then restrike. steady load to the system until the (30 – 40%) and impedance of the trans-
For high-intensity discharge (HID) instant the x-ray tube is “fired.” This former. For example, if a 480V trans-
lamps such as mercury vapor, high- presents a brief but extremely high former has an impedance of 5%, and
pressure sodium or metal halide, if the instantaneous momentary load. In the motor inrush current is 25% of the
lamp goes out because of an excessive some modern x-ray equipment, the transformer full-load current (FLC),
voltage dip, it will not restrike until it firing is repeated rapidly to create then the worst case voltage drop will
has cooled. This will require several multiple images. The voltage regula- be 0.25 x 5%, or 1.25%. The allowable
minutes. These lighting flicker effects tion must be maintained within the motor inrush current is determined by
can be annoying, and in the case of manufacturer’s limits, usually 2 to 3%, the total permissible voltage drop in
HID lamps, sometimes serious. In under these momentary loads, to transformer and conductors.
areas where close work is being done, ensure proper x-ray exposure.
such as drafting rooms, precision
assembly plants, and the like, even
a slight variation, if repeated, can be
very annoying, and reduce efficiency.
Voltage variation in such areas should
be held to 2 or 3% under motor-start-
ing or other transient conditions.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.2-23
January 2003 System Analysis
Ref. No. 0057

Table 1.2-14. Factors Governing Voltage Drop


Type of Starting Starting How Starting Starting Torque per Unit of Full-Load Amperes
Motor 1 Torque Current 2 Started Current Full Load Torque per kVA Generator
% Full-Load 3 Motor Rpm Capacity for Each
1% Voltage Drop
1750 1150 3 850

Design B Normal Normal Across-the-Line 600 – 700 1.5 1.35 1.25 .0109 – .00936
Resistance 480 – 560 ➁ .96 .87 .80 .0136 – .0117
Autotransformer 375 – 450 ➁ .96 .87 .80 .0170 – .0146 1
Design C Normal Low Across-the-Line 500 – 600 1.5 1.35 1.25 .0131 – .0109
Resistance 400 – 480 ➁ .96 .87 .80 .0164 – .01365
Autotransformer 320 – 400 ➁ .96 .87 .80 .0205 – .0170
Design D High Low Across-the-Line 500 – 600 — .2 to 2.5 — .0131 – .0109
Resistance 400 – 480 ➁ — 1.28 to 1.6 — .0164 – .01365
Autotransformer 320 – 400 ➁ — 1.28 to 1.6 — .0205 – .0170
Design E Normal High Across-the-Line 800 – 1000 — — — —
Wound Rotor High Low Secondary Controller 100% current — — — —
for 100% — — — —
Torque — — — .0655
Synchronous (for compressors) Low — Across-the-Line 300 40% Starting, 40% Pull-In .0218
Synchronous (for centrifugal pumps) Low — Across-the-Line 450 – 550 60% Starting, 110% Pull-In .0145 – .0118
Autotransformer 288 – 350 4 38% Starting, 110% Pull-In .0228 – .0197
1 Consult NEMA MG-1 sections 1 and 12 for the exact definition of the design letter.
2 In each case, a solid-state reduced voltage starter can be adjusted and controlled to provide the required inrush current and torque characteristics.
3 Where accuracy is important, request the code letter of the the motor and starting and breakdown torques from the motor vendor.
4 Using 80% taps.

With an engine generator as the Starting ratio = Short-Cut Method


source of power, the type of starter
Percent voltage drop × gen. kVA × 1000 Column 7 in Table 1.2-14 has been
that will limit the inrush depends on −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− worked out to simplify checking.
the characteristics of the generator. F.L. amperes × volts × 3 × reg. of gen.
Although automatic voltage regulators The figures were obtained by using
are usually used with all AC engine- From the nameplate data on the motor the formula above and assuming
generators, the initial dip in voltage is the full-load amperes of a 7-1/2 hp. 1 kVA generator capacity and 1%
caused by the inherent regulation of 220-volt, 1750 rpm, 3-phase, squirrel- voltage drop.
the generator and occurs too rapidly cage motor is 19.0 amperes. Therefore: Example:
for the voltage regulator to respond.
Starting current (%F.L.) = Assuming a project having a
It will occur whether or not a regulator
1000 kVA generator, where the
is installed. Consequently, the percent 10 × 100 × 1000
of initial voltage drop depends on the −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− = 3.45 or 345%. voltage variation must not exceed
19.0 × 220 × 3 × 0.40 10%. Can a 75 hp, 1750 rpm, 220-volt,
ratio of the starting kVA taken by the
3-phase, squirrel-cage motor be
motor to the generator capacity, the From Table 1.2-14, a NEMA design C started without objectionable lamp
inherent regulation of the generator, or NEMA design D motor with an flicker (or 10% voltage drop)?
the power-factor of the load thrown autotransformer starter gives
on the generator, and the percentage approximately this starting ratio. From tables in the circuit protective
load carried by the generator. It could also be obtained from a devices reference section the full-load
properly set solid-state adjustable amperes of this size and type of motor
A standard 80% power-factor engine- reduced voltage starter. is 158.0 amperes. To convert to same
type generator (which would be
basis as column 7, 158 amperes must
used where power is to be supplied The choice will depend upon the be divided by the generator capacity
to motor loads) has an inherent torque requirements of the load since and % voltage drop, or:
regulation of approximately 40% the use of an autotransformer starter
from no-load to full-load. This means reduces the starting torque in direct 158
that a 50% variation in load would proportion to the reduction in starting −−−−−−−−−−−−−−− = 0.0158 amperes per kVA
1000 × 10 per 1% voltage drop
cause approximately 20% variation current. In other words, a NEMA
in voltage (50% x 40% = 20%). design C motor with an autotrans- Checking against the table, 0.0158 falls
former would have a starting torque within the .0170 – .0146 range. This
Assume that a 100 kVA, 80% PF of approximately full-load (see Table
engine-type generator is supplying indicates that a general-purpose
1.2-14) whereas the NEMA design D motor with autotransformer starting
the power and that the voltage drop motor under the same conditions
should not exceed 10%. Can a 7-1/2 hp, can be used.
would have a starting torque of
220-volt, 1750 rpm, 3-phase, squirrel- approximately 1-1/2 times full-load.
cage motor be started without
exceeding this voltage drop? Note: If a resistance starter were used for
the same motor terminal voltage, the start-
ing torque would be the same as that
obtained with autotransformer type, but the
starting current would be higher, as shown.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.2-24 Power Distribution Systems
System Analysis January 2003
Ref. No. 0058

The calculation results in conservative results. The engineer If the receiving end voltage, load current and power factor
should provide to the engine-generator vendor the starting (PF) are known.
kVA of all motors that we will be connected to, the generator
and their starting sequence. The engineer should also specify 2 2
E VD = ( E R cosθ + I R ) + ( E R sinθ + I X ) – E R
the maximum allowable drop. The engineer should request
that the engine-generator vendor consider the proper gener- ER is the receiving end voltage.
ator size when closed-transition autotransformer reduced
voltage starters, and soft-start solid-state starter are used; Exact Method 2 — If receiving or sending mVA and its
1 so the most economical method of installation is obtained. power factor are known at a known sending or receiving
voltage.
Approximate Method
2
Voltage Drop 2 2 ( ZMVA R )
- + 2ZMVA R cos ( γ – θ R )
E S = E R + ---------------------------------
2
E VD = IR cosθ + IX sinθ ER

where Abbreviations are same as below “Exact Method.” or


2
Exact Methods 2 2 ( ZMVA R )
- – 2ZMVA S cos ( γ – θ S )
E R = E S + ---------------------------------
2
Voltage Drop ES
Exact Method 1 — If sending end voltage and load PF where:
are known.
ER = Receiving Line-Line voltage
2 2 in kV
E VD = E S + IR cosθ + IX sinθ – E S – ( IX cosθ – IR sinθ )
ES = Sending Line-Line voltage
where: in kV
EVD = Voltage drop, line-to-neutral, volts MVAR = Receiving 3-phase mVA
ES = Source voltage, line-to-neutral, volts MVAS = Sending 3-phase mVA
I = Line (Load) current, amperes Z = Impedance between and
receiving ends
R = Circuit (branch, feeder) resistance, ohms
γ = The angle of impedance Z
X = Circuit (branch, feeder) reactance, ohms
θR = Receiving end PF
cosθ = Power factor of load, decimal
θS = Sending end PF, positive
sinθ = Reactive factor of load, decimal when lagging

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-1
January 2003 System Application Considerations
Ref. No. 0059
Capacitors

Capacitor Switching We recommend that such application


be referred to the Cutler-Hammer
Low Voltage Capacitor Switching
Device Selections business. Circuit breakers and switches for use
with a capacitor must have a current
Medium Voltage A breaker specified for capacitor rating in excess of rated capacitor
switching should include as applicable: current to provide for overcurrent from
Capacitor Switching overvoltages at fundamental frequency
1. Rated maximum voltage. and harmonic currents. The following
Capacitance switching constitutes
severe operating duty for a circuit 2. Rated frequency. percent of the capacitor-rated current 1
breaker. At the time the breaker opens should be used as a general guideline:
at near current zero the capacitor is 3. Rated open wire line charging
switching current. Fused and unfused
fully charged. After interruption, when
switches . . . . . . . . . . . . . . . . . . . 165%
the alternating voltage on the source 4. Rated isolated cable charging and
side of the breaker reaches its opposite shunt capacitor switching current. Molded case breaker or
maximum, the voltage that appears equivalent . . . . . . . . . . . . . . . . . 150%
across the contacts of the open circuited 5. Rated back-to-back cable charging
breaker is at least twice the normal and back-to-back capacitor switch- DSII power circuit breakers. . . . . 135%
line-to-neutral voltage of the circuit. ing current. Magnum DS power
If a breakdown occurs across the open circuit breaker . . . . . . . . . . . . . . 135%
contact the arc is reestablished. Due to 6. Rated transient overvoltage factor.
the circuit constants on the supply side 7. Rated transient inrush current and Contactors:
of the breaker, the voltage across the its frequency. Open type . . . . . . . . . . . . . . . . . . . 135%
open contact can reach three times the
normal line-to-neutral voltage. After 8. Rated interrupting time. Enclosed type . . . . . . . . . . . . . . . . 150%
it is interrupted and with subsequent
alternation of the supply side voltage, 9. Rated capacitive current The NEC, Section 460-8(c)(4), requires
the voltage across the open contact is switching life. the disconnecting means to be rated not
even higher. less than 135% of the rated capacitor
10. Grounding of system and current (for 600V and below).
ANSI Standard C37.06 (indoor oilless capacitor bank.
circuit breakers) indicates the preferred Loadbreak interrupter switches are
ratings of Eaton’s Cutler-Hammer type permitted by ANSI/IEEE Standard
VCP-W vacuum breaker. For capacitor C37.30 to switch capacitance but
switching careful attention should be they must have tested ratings for the
paid to the notes accompanying the purpose. Refer to Cutler-Hammer
table. The definition of the terms are type MVS ratings.
in ANSI Standard C37.04 Article 5.13
(for the latest edition). The application
guide ANSI/IEEE Standard C37.012
covers the method of calculation
of the quantities covered by C37.06
Standard.
Note that the definitions in C37.04
make the switching of two capacitors
banks in close proximity to the switch-
gear bus a back-to-back mode of
switching. This classification requires
a definite purpose circuit breaker
(breakers specifically designed for
capacitance switching).

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-2 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0060
Capacitors

Table 1.3-1. Recommended Switching Devices 1


Capacitor Amperes Capacitor Amperes
Rating Rating
Volts kvar Capacitor Safety Molded Power Volts kvar Capacitor Safety Molded Power
Rated Switch Case Breaker Breaker Rated Switch Case Breaker Breaker
Current Fuse Rating Trip Rating Trip Rating Current Fuse Rating Trip Rating Trip Rating

240 2.5 6.0 15 15 15 600 5 4.8 15 15 15


1 5
7.5
12.0
18.0
20
30
20
30
20
30
7.5
10
7.2
9.6
15
20
15
15
15
15
10 24.1 40 40 40 15 14.4 25 30 20
15 36.1 60 70 50 20 19.2 35 30 30
20 48.1 80 90 70 25 24.1 40 40 40
25 60 100 100 90 30 28.9 50 50 40
30 72.2 125 125 100 35 33.6 60 50 50
45 108 200 175 150 40 38.5 70 70 70
50 120 200 200 175 45 43.3 80 70 70
60 144 250 225 200 50 48.1 80 100 70
75 180 300 275 250 60 57.8 100 100 90
90 217 400 350 300 75 72.2 125 125 100
100 240 400 400 350 80 77.0 150 125 125
120 289 500 500 400 100 96.2 175 150 150
125 301 500 500 450 120 115 200 175 175
135 325 600 500 500 125 120 200 200 175
150 361 600 600 500 150 144 250 225 200
180 433 800 700 600 160 154 300 250 225
200 480 800 800 700 180 173 300 300 250
225 541 900 900 800 200 192 350 300 300
240 578 1000 900 800 225 217 400 350 300
250 602 1000 900 900 240 231 400 350 350
270 650 1200 1000 1000 250 241 400 400 350
300 720 1200 — 1200 300 289 500 500 400
360 866 1600 — 1200 320 306 600 500 500
375 903 1500 — 1200 360 347 600 600 500
480 2 2.41 15 15 15 375 361 600 600 500
5 6.01 15 15 15 400 385 700 600 600
7.5 9.0 15 15 15 450 433 800 700 600
10 12.0 20 20 20 1 Switching device ratings are based on percentage of capacitor-rated
15 18.0 30 30 30 current as indicated (above). The interrupting rating of the switch must
20 24.0 40 40 40 be selected to match the system fault current available at the point of
25 30.0 50 50 50 capacitor application. Whenever a capacitor bank is purchased with
30 36.1 60 70 50 less than the ultimate kvar capacity of the rack or enclosure, the switch
35 42 70 70 60 rating should be selected based on the ultimate kvar capacity —
not the initial installed capacity.
40 48.1 80 100 70
45 54 90 100 80
50 60.1 100 100 90
60 72.2 125 125 100
75 90.2 150 150 125
80 96.2 175 150 150
90 108 200 175 150
100 120 200 200 175
120 144 250 225 200
125 150 250 225 200
150 180 300 300 250
160 192 350 300 300
180 216 400 350 300
200 241 400 400 350
225 271 500 500 400
240 289 500 500 400
250 301 500 500 400
300 361 600 600 500
320 385 700 600 600
360 433 800 700 600
375 451 800 700 600
400 481 800 800 800
450 541 900 900 800

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-3
January 2003 System Application Considerations
Ref. No. 0061
Capacitors

Motor Power Factor % AR — percent reduction in line


current due to the capacitor. A
To derate a capacitor used on a system
voltage lower than the capacitor volt-
Correction capacitor located on the motor side age rating, such as a 240-volt capacitor
of the overload relay reduces line used on a 208-volt system, use the
Tables 1.3-2 and 1.3-3 contain sug- current through the relay. Therefore, following formula:
gested maximum capacitor ratings a different overload relay and/or
for induction motors switched with setting may be necessary. The reduc- Actual kvar =
the capacitor. The data is general in tion in line current may be determined 2
nature and representative of general by measuring line current with and
( Applied Voltage )
Nameplate kvar × ---------------------------------------------------------------------2- 1
purpose induction motors of standard without the capacitor or by calculation ( Nameplate Voltage )
design. The preferable means to select as follows:
capacitor ratings is based on the For the kVAC required to correct the
“maximum recommended kvar” (Original PF) power factor from a given value of
% AR = 100 – 100 × −−−−−−−−−−−−−−−−−−−−−−−
information available from the motor (Improved PF) COS φ1 to COS φ2, the
manufacturer. If this is not possible formula is:
or feasible, the tables can be used. If a capacitor is used with a lower kvar
rating than listed in tables, the % AR kVAC = KW (tan phase1 – tan phase2)
An important point to remember can be calculated as follows:
is that if the capacitor used with the Capacitors cause a voltage rise.
motor is too large, self-excitation may Actual kvar At light load periods the capacitive
% AR = Listed % AR × −−−−−−−−−−−−−−−−−−−−−− voltage rise can raise the voltage at
cause a motor-damaging overvoltage kvar in Table
when the motor and capacitor combi- the location of the capacitors to an
nation is disconnected from the line. The tables can also be used for other unacceptable level. This voltage rise
In addition, high transient torques motor ratings as follows: can be calculated approximately by
capable of damaging the motor shaft the formula
A. For standard 60 Hz motors
or coupling can occur if the motor operating at 50 Hz: MVA R
is reconnected to the line while kvar = 1.7 – 1.4 of kvar listed % VR = −−−−−−−−−−−−
rotating and still generating a voltage MVA SC
% AR = 1.8 – 1.35 of % AR listed
of self-excitation.
B. For standard 50 Hz motors MVAR is the capacitor rating and
Definitions operating at 50 Hz: MVASC is the system short circuit
kvar — rating of the capacitor in kvar = 1.4 – 1.1 of kvar listed capacity.
reactive kilovolt-amperes. This value % AR = 1.4 – 1.05 of % AR listed With the introduction of variable speed
is approximately equal to the motor drives and other harmonic current
no-load magnetizing kilovars. C. For standard 60 Hz wound-rotor
motors: generating loads, the capacitor imped-
kvar = 1.1 of kvar listed ance value determined must not be
% AR= 1.05 of % AR listed resonant with the inductive reactances
of the system. This matter is discussed
Note: For A, B, C, the larger multipliers apply further under the heading “Harmonics
for motors of higher speeds; i.e., 3600 rpm = and Non-Linear Loads.”
1.7 mult., 1800 rpm = 1.65 mult., etc.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-4 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0062
Capacitors

Induction-Motor/Capacitor Application Tables for Motors


(Manufactured in 1956 or Later) 230-, 460- and 575-Volt Motors
Table 1.3-2. Recommended Maximum Capacitance Values for NEMA Design B Motors
Induction Motor Nominal Motor Speed in Rpm and Number of Poles
Horsepower 3600 1800 1200 900 720 600
Rating 2 4 6 8 10 12
1 kvar % AR kvar % AR kvar % AR kvar % AR kvar % AR kvar % AR

5 2 13 2 17 3 23 3 28 4 36 5 49
7.5 2.5 13 3 16 3 19 4 25 6 33 7.5 46
10 3 12 3 14 4 18 5 24 6 30 10 39
15 5 11 5 14 5 17 7.5 21 7.5 27 10 34
20 6 10 6 13 7.5 16 7.5 20 10 25 15 31
25 7.5 10 6 13 7.5 16 10 19 10 23 20 31
30 7.5 10 7.5 12 10 16 10 18 15 21 20 28
40 7.5 10 10 11 15 15 15 18 15 20 25 28
50 10 10 15 11 20 15 20 18 20 19 30 28
60 10 9 15 11 25 14 20 17 25 19 35 27
75 15 9 20 10 25 13 25 14 30 16 40 19
100 20 9 25 10 30 11 30 13 35 15 45 17
125 25 9 30 9 30 11 40 13 40 14 50 17
150 25 9 30 9 35 11 45 12 50 13 60 17
200 35 9 40 9 50 10 60 12 70 13 80 17
250 40 9 50 8 60 10 70 12 80 12 100 17
300 45 9 60 8 70 10 80 12 90 12 110 17
350 50 9 70 7 80 10 100 12 100 12 125 16
400 70 8 70 7 80 10 110 12 125 12 150 16
450 75 7 80 7 100 9 120 11 125 12 150 16
500 90 7 90 7 120 9 125 11 140 12 175 16

Table 1.3-3. Recommended Maximum Capacitance Values for NEMA Design C Motors
Induction Motor Nominal Motor Speed in Rpm and Number of Poles
Horsepower 1800 1200 900 720
Rating 4 6 8 10
kvar % AR kvar % AR kvar % AR kvar % AR

5 2 18 2.5 23 4 29 — —
7.5 3 18 3 19 4 25 — —
10 3 15 4 17 5 22 — —
15 4 15 5 17 7.5 20 — —
20 4 15 5 17 7.5 19 — —
25 5 13 5 15 10 19 — —
30 5 13 7.5 15 10 19 20 23
40 10 13 10 15 15 18 — —
50 15 13 10 15 20 18 25 23
60 15 12 20 15 25 18 25 23
75 20 11 20 13 30 17 35 23
100 25 10 25 12 40 17 40 17
125 30 10 35 11 40 14 45 16
150 35 9 40 10 45 13 50 12
200 45 9 50 10 60 13 60 12
250 50 8 60 10 70 13 75 12
300 60 8 70 10 80 12 80 12
350 70 8 75 9 90 12 100 12

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-5
January 2003 System Application Considerations
Ref. No. 0063
Protection and Coordination

Overcurrent Protection utilization circuit, (d) equipment


damage or withstand characteristics,
running and with all upstream devices,
except that CB B will trip first on low
and Coordination (e) calculation of maximum short level ground faults.
circuit currents (and ground fault
Overcurrents in a power distribution currents if ground fault protection is B — CB (600A) coordinates selec-
system can occur as a result of both included) possible at each protective tively with all upstream and down-
normal (motor starting, transformer device location, (f) understanding of stream devices, except will trip before
inrush, etc.) and abnormal (overloads, operating characteristics and available A on limited ground faults, since A
ground fault, line-to-line fault, etc.) adjustments of each protective device, has no ground fault trips. 1
conditions. In either case, the funda-
mental purposes of current-sensing
(g) any special overcurrent protection C — Main CB (1600A) coordinates
requirements including utility limita- selectively with all downstream
protective devices are to detect the tions. Refer to (Figure 1.3-1).
abnormal overcurrent and with proper devices and with primary fuse D,
coordination, to operate selectively Standard definitions have been estab- for all faults on load side of CB.
to protect equipment, property and lished for overcurrent protective D — Primary fuse (250A, 4,160V)
personnel while minimizing the out- devices covering ratings, operation coordinates selectively with all
age of the remainder of the system. and application systems. secondary protective devices. Curve
With the increase in electric power
consumption over the past few M — Motor (100 hp). Dashed line converted to 480V basis. Clears trans-
shows initial inrush current, starting former inrush point (12 x FLC for 0.1 sec),
decades, dependence on the contin- indicating that fuse will not blow on
ued supply of this power has also current during 9-sec. acceleration, and
drop to 124A normal running current, inrush. Fuse is underneath right-half of
increased so that the direct costs ANSI 3-phase withstand curve, indicat-
of power outages have risen signifi- all well below CB A trip curve.
ing fuse will protect transformer for
cantly. Power outages can create dan- A — CB (175A) coordinates selec- high-magnitude faults up to ANSI rating.
gerous and unsafe conditions as a tively with motor M on starting and
result of failure of lighting, elevators,
ventilation, fire pumps, security sys-
SCALE X 100 = CURRENT IN AMPERES AT 480 VOLTS
tems, communications systems, and

10,000
1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400
500
600
700
800
900
the like. In addition, economic loss

70
80
90
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
900 900
4.16 kV 250 MVA
from outages can be extremely high 800
700
800
700

as a result of com-puter downtime, 600


500
600
500

or, especially in industrial process 400 400

B
plants, interruption of production. 300 300

A D
200 200
Protective equipment must be adjusted C

and maintained in order to function D


100 250 Amperes 100
properly when a current abnormality 90
80 1000
90
80
70 70
occurs, but coordination begins during 60
kVA
5.75%
4,160 V ∆ 60
50 480/277 V
power system design with the knowl- 40
50

ANSI 3-Phase 19,600 Amperes 40


edgeable analysis and selection and 30 Thru Fault 30

application of each overcurrent protec- 20


Protection Curve
(More Than 10 in C 1,600 Amperes 20
tive device in the series circuit from Lifetime)

the power source(s) to each load appa- B 24,400 Amperes


10 10
ratus. The objective of coordination is 9
8 600 Amperes 9
8
7 7
to localize the overcurrent disturbance M

TIME IN SECONDS
TIME IN SECONDS

6 6

so that the protective device closest to 5


4
20,000 Amperes
5
4
the fault on the power-source side has 3 3
175 Amperes
the first chance to operate; but each A
2 B C 2
preceding protective device upstream
toward the power source should be
1 1
capable, within its designed settings .9
.8 100 hp –
.9
.8
M
of current and time, to provide backup .7
.6
124 Amperes FLC .7
.6

and affect the isolation if the fault .5


.4 X = Available fault current
.5
.4
persists. Sensitivity of coordination .3
including motor
contribution. .3

is the degree to which the protective Ground


.2 Fault Trip .2
devices can minimize the damage C
to the faulted equipment.
.1 .1
.09 .09
To study and accomplish coordination .08
.07
.08
.07
.06 Transformer .06
requires (a) a one-line diagram, the .05
B Inrush .05

roadmap of the power distribution .04 .04


Max. 3-Phase

system, showing all protective devices


4.16 kV Fault

.03 .03

A
480V Fault

and the major or important distribution .02 .02

and utilization apparatus, (b) identifi-


Max.

cation of desired degrees of power .01 .01


70
80
90
100

200

300

400
500
600
700
800
900
1000

2000

3000

4000
5000
6000
7000
8000
9000
10,000

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
continuity or criticality of loads
SCALE X 100 = CURRENT IN AMPERES AT 480 VOLTS
throughout system, (c) definition
of operating-current characteristics Figure 1.3-1. Time-Current Characteristic Curves for Typical Power Distribution System
(normal, peak, starting) of each Protective Devices Coordination Analysis.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-6 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0064
Protection and Coordination

Delta-Wye secondary side short circuit owner has its own medium or higher Specify true rms sensing devices in
is not reflected to the primary by the voltage distribution the settings or order to avoid false trips due to rapid
relation ratings of all upstream devices should currents or spikes. Specify tripping
be checked. elements with I2t or I4t feature for
V improved coordination with other
I P = −−−S × I S If perfect coordination is not feasible,
VP devices having I2t or I4t (such as
then lack of coordination should be OPTIME trip units) characteristics,
limited to the smallest part of the system. and fuses.
for L-L and L-G faults. For line-to-line fault
1 the secondary (low voltage) side fault Application data is available for all In general for systems such as shown
current is 0.866 x I 3-phase fault current. protective equipment to permit sys- in the example:
tems to be designed for adequate
However the primary (high voltage) side
overcurrent protection and coordina- 1. The settings or ratings of the pri-
fault is the same as if the secondary
tion. For circuit breakers of all types, mary side fuse and main breaker
fault was a 3-phase fault. Therefore
time-current curves permit selection of must not exceed the settings
in close, coordination studies the
instantaneous and inverse-time trips. allowed by NEC Article 450.
knee of the short-time pickup setting
For more complex circuit breakers,
should be multiplied by 2. At 12 x IFL the minimum melting
with solid state trip units, trip curves
include long- and short-time delays, as time characteristic of the fuse
−−−−1−−−− or 1.1547 well as ground-fault tripping, with a should be higher than 0.1 second.
0.866
wide range of settings and features to 3. The primary fuse should be to the
before it is compared to the minimum provide selectivity and coordination. left of the transformer damage
melting time of the fuse curve. In the For current-limiting circuit breakers, curve as much as possible. The
example shown, 4000 amperes 30 sec., fuses, and circuit breakers with inte- correction factor for a single line-
the 30-sec. trip time should be com- gral fuses, not only are time-current to-ground factor must be applied
pared to the MMT (minimum melt characteristic curves available, but to the damage curve.
time) of the fuse curve at 4000 x 1.1547 also data on current-limiting per-
= 4619 amperes. In this case there is formance and protection for down- 4. The setting of the short-time delay
adequate clearance to the fuse curve. stream devices. element must be checked against
the fuse MMT after it is corrected
In the example shown the ANSI 3-phase In a fully rated system, all circuit break- for line-to-line faults.
through fault protection curve must ers must have an interrupting capacity
be multiplied by 0.577 and replotted adequate for the maximum available 5. The maximum fault current must
in order to determine the protection fault current at their point of applica- be indicated at the load side of
given by the primary for single line tion. All breakers are equipped with each protective device.
to ground fault in the secondary. long-time-delay (and possibly short
6. The setting of a feeder protective
delay) and instantaneous overcurrent
Maximum 480V 3-phase fault indicated. device must comply with Article
trip devices. A main breaker may have
240 and Article 430 of the NEC.
Maximum 4160V 3-phase fault indicated, short time-delay tripping to allow
It also must allow the starting
converted to 480V basis. a feeder breaker to isolate the fault
and acceleration of the largest
while power is maintained to all the
4160 motor on the feeder while carrying
I 480 V = I 4160 V × −−−−−−− remaining feeders.
480 all the other loads on the feeder.
A selective or fully coordinated system
Trip elements equipped with zone
The ANSI protection curves are speci- permits maximum service continuity.
selective interlocking, trip without
fied in ANSI C57.109 for liquid-filled The tripping characteristics of each
intentional time delay unless a
transformers and C57.12.59 for dry- overcurrent device in the system must
restraint signal is received from
type transformers. be selected and set so that the breaker
a protective device downstream.
nearest the fault opens to isolate the
Illustrative examples such as shown Breakers equipped with this feature
faulted circuit, while all other breakers
here start the coordination study from reduce the damage at the point of
remain closed, continuing power to
the lowest rated device proceeding fault if the fault occurs at a location
the entire unfaulted part of the system.
upstream. In practice the setting or between the zone of protection.
All breakers must have an interrupting
rating of the utility’s protective device capacity not less than the maximum The upstream breaker upon receipt
sets the upper limit. Even in cases available short circuit current at their of the restraint signal will not trip until
where the customer owns the medium point of application. A selective its time-delay setting times out. If the
voltage or higher distribution system, system is a fully-rated system with breaker immediately downstream of
the setting or rating of the lowest set tripping devices chosen and adjusted the fault does not open, then after
protective device source determines to provide the desired selectivity. timing out, the upstream breaker
the settings of the downstream The tripping characteristics of each will trip.
devices and the coordination. There- overcurrent device should not overlap,
fore the coordination study should but should maintain a minimum time Breakers equipped with ground fault
start at the present setting or rating interval for devices in series (to allow trip elements should also be specified
of the upstream device and work for normal operating tolerances) at all to include zone interlocking for the
towards the lowest rated device. If current values. Generally, a maximum ground fault trip element.
this procedure results in unacceptable of four low voltage circuit breakers can
settings, the setting or rating of the be operated selectively in series, with
upstream device should be reviewed. the feeder or branch breaker down-
Where the utility is the sole source stream furthest from the source.
they should be consulted. Where the

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-7
January 2003 System Application Considerations
Ref. No. 0065
Protection and Coordination

To assure complete coordination, the Suggested Ground Fault Settings Any of these current-limiting devices
time-trip characteristics of all devices — fuses, fused breakers, or current-
in series should be plotted on a single For the main devices: limiting breakers — cannot only clear
sheet of standard log-log paper. A ground fault pickup setting equal these large faults safely, but also will
Devices of different-voltage systems to 20 – 30% of the main breaker rating limit the Ip and I2t let-through signifi-
can be plotted on the same sheet by but not to exceed 1200 amperes, and cantly to prevent damage to apparatus
converting their current scales, using a time delay equal to the delay of the downstream, extending their zone of
the voltage ratios, to the same voltage- short time element, but not to exceed protection. Without the current limita-
basis. Such a coordination plot is 1 second. tion of the upstream device, the fault 1
shown on Page 1.3-5. In this manner, current could exceed the withstand
primary fuses and circuit breaker For the feeder ground fault setting: capability of the downstream equip-
relays on the primary side of a substa- A setting equal to 20 – 30% of the ment. Underwriters Laboratories tests
tion transformer can be coordinated feeder ampacity and a time delay to and lists these series combinations.
with the low voltage breakers. Trans- coordinate with the setting of the main Application information is available
former damage points, based on ANSI (at least 6 cycles below the main). for combinations which have been
standards, and low voltage cable tested and ULT-listed for safe opera-
heating limits can be plotted on this If the desire to selectively coordinate tion downstream from DSLII, TRI-PAC,
set of curves to assure that apparatus ground fault devices results in settings and Current-Limit-R, or Series C break-
limitations are not exceeded. which do not offer adequate damage ers of various ratings, under high
protection against arcing single line- available fault currents.
Ground-fault curves may also be ground faults, the design engineer
included in the coordination study should decide between coordination Protective devices in electrical distri-
if ground-fault protection is provided, and damage limitation. bution systems may be properly coor-
but care must be used in interpreting dinated when the systems are designed
their meaning. For low voltage systems with high- and built, but that is no guarantee that
magnitude available short circuit they will remain coordinated. System
Article 230-95 of NEC requires ground- currents, common in urban areas and changes and additions, plus power
fault protection of equipment shall be large industrial installations, several source changes, frequently modify the
provided for solidly grounded wye solutions are available. High interrupt- protection requirements, sometimes
electrical services of more than 150 ing Series CT molded case breakers, causing loss of coordination and even
volts to ground, but not exceeding current-limiting circuit breakers, or increasing fault currents beyond the
600 volts phase-to-phase for each current-limiting fuses, limiters integral ratings of some devices. Consequently,
service disconnect rated 1000 amperes with molded-case circuit breakers periodic study of protective-device
or more. (TRI-PACT) or mounted on power cir- settings and ratings is as important for
cuit breakers (Type DSLII) can be used safety and preventing power outages
The rating of the service disconnect
to handle these large fault currents. To as is periodic maintenance of the
shall be considered to be the rating
provide current limiting, these devices distribution system.
of the largest fuse that can be installed
must clear the fault completely within
or the highest continuous current
the first half-cycle, limiting the peak
trip setting for which the actual over-
current (Ip) and heat energy (I2t) let-
current device installed in a circuit
through to considerably less than
breaker is rated or can be adjusted.
what would have occurred without
The maximum allowable settings are: the device. For a fully fusible system,
1200 amperes pickup, 1 second or less rule-of-thumb fuse ratios or more accu-
trip delay at currents of 3000 amperes rate I2t curves can be used to provide
or greater. selectivity and coordination. For fuse-
breaker combinations, the fuse should
The characteristics of the ground-fault be selected (coordinated) so as to per-
trip elements create coordination mit the breaker to handle those over-
problems with downstream devices loads and faults within its capacity;
not equipped with ground fault the fuse should operate before or
protection. The National Electrical with the breaker only on large faults,
Code exempts fire pumps and contin- approaching the interrupting capacity
uous industrial processes from this of the breaker, to minimize fuse
requirement. blowing. Recently, unfused, truly
It is recommended that in solidly current-limiting circuit breakers with
grounded 480/277-volt systems where interrupting ratings adequate for
main breakers are equipped with the largest systems (Type Series C,
ground fault trip elements that the FDC, JDC, KDC, LDC and NDC
feeder breakers be equipped with frames or Type Current-Limit-RT)
ground-fault trip elements as well. have become available.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-8 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0066
Grounding/Ground Fault Protection

Grounding with such an object while grounded


could be seriously injured or killed.
The equipment grounding system
must be bonded to the grounding
Grounding encompasses several dif- In addition, current flow from the acci- electrode at the source or service;
ferent but interrelated aspects of elec- dental grounding of an energized part however, it may be also connected
trical distribution system design and of the system could generate sufficient to ground at many other points.
construction, all of which are essential heat (often with arcing) to start a fire. This will not cause problems with
to the safety and proper operation of To prevent the establishment of such the safe operation of the electrical
the system and equipment supplied by unsafe potential difference requires distribution system. Where computers,
1 it. Among these are equipment ground- that (1) the equipment grounding data processing, or microprocessor-
ing, system grounding, static and conductor provide a return path for based industrial process control
lightning protection, and connection ground fault currents of sufficiently systems are installed, the equipment
to earth as a reference (zero) potential. low impedance to prevent unsafe grounding system must be designed
voltage drop, and (2) the equipment to minimize interference with their
1. Equipment Grounding grounding conductor be large enough proper operation. Often, isolated
to carry the maximum ground fault grounding of this equipment, or
Equipment grounding is essential
current, without burning off, for suffi- isolated electrical supply systems are
to safety of personnel. Its function is
cient time to permit protective devices required to protect microprocessors
to ensure that all exposed noncurrent-
(ground fault relays, circuit breakers, from power system “noise” that does
carrying metallic parts of all structures
fuses) to clear the fault. The grounded not in any way affect motors or other
and equipment in or near the electrical
conductor of the system (usually the electrical equipment. Such systems
distribution system are at the same
neutral conductor), although grounded must use single-point ground concept
potential, and that this is the zero
at the source, must not be used for to minimize “noise” and still meet
reference potential of the earth. Equip-
equipment grounding. the NEC requirements. Any separate
ment grounding is required by both the
isolated ground mat must be tied to
National Electrical Code (Article 250) The equipment grounding conductor the rest of the facility ground mat
and the National Electrical Safety Code may be the metallic conduit or race- system for NEC compliance.
regardless of how the power system is way of the wiring system, or a sepa-
grounded. Equipment grounding also rate equipment grounding conductor,
provides a return path for ground fault
2. System Grounding
run with the circuit conductors, as
currents, permitting protective devices permitted by NEC. If a separate equip- System grounding connects the
to operate. Accidental contact of an ment grounding conductor is used, it electrical supply, from the utility, from
energized conductor of the system may be bare or insulated; if insulated, transformer secondary windings, or
with an improperly grounded noncur- the insulation must be green, green from a generator, to ground. A system
rent-carry metallic part of the system with yellow stripe or green tape. can be solidly grounded (no inten-
(such as a motor frame or panelboard Conductors with green insulation tional impedance to ground), imped-
enclosure) would raise the potential of may not be used for any purpose ance grounded (through a resistance
the metal object above ground poten- other than for equipment grounding. or reactance), or ungrounded (with
tial. Any person coming in contact no intentional connection to ground.

3. Medium Voltage System: Grounding


Table 1.3-4. Features of Ungrounded and Grounded Systems (from ANSI C62.92)
Description A B C D E
Ungrounded Solidly Grounded Reactance Grounded Resistance Grounded Resonant Grounded

(1) Apparatus Fully insulated Lowest Partially graded Partially graded Partially graded
Insulation
(2) Fault to Usually low Maximum value rarely Cannot satisfactorily be Low Negligible except when
Ground Current higher than 3-phase short reduced below one-half Petersen coil is short
circuit current or one-third of values for circuited for relay
solid grounding purposes when it may
compare with solidly-
grounded systems
(3) Stability Usually unimportant Lower than with other Improved over solid Improved over solid Is eliminated from
methods but can be grounding particularly grounding particularly consideration during
made satisfactory by use if used at receiving end if used at receiving end single line-to-ground
of high-speed breakers of system of system faults unless neutralizer
is short circuited to
isolate fault by relays
(4) Relaying Difficult Satisfactory Satisfactory Satisfactory Requires special
provisions but can be
made satisfactory
(5) Arcing Likely Unlikely Possible if reactance is Unlikely Unlikely
Grounds excessive
(6) Localizing Effect of fault transmitted Effect of faults localized Effect of faults localized to Effect of faults Effect of faults
Faults as excess voltage on to system or part of system or part of system transmitted as excess transmitted as excess
sound phases to all system where they occur where they occur unless voltage on sound phases voltage on sound phases
parts of conductively reactance is quite high to all parts of conduc- to all parts of conduc-
connected network tively connected network tively connected network
(7) Double Likely Likely Unlikely unless Unlikely unless Seem to be more likely
Faults reactance is quite high resistance is quite high but conclusive informa-
and insulation weak and insulation weak tion not available

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-9
January 2003 System Application Considerations
Ref. No. 0067
Grounding/Ground Fault Protection

Table 1.3-4. Features of Ungrounded and Grounded Systems (Continued)


Description A B C D E
Ungrounded Solidly Grounded Reactance Grounded Resistance Grounded Resonant Grounded

(8) Lightning Ungrounded neutral Highest efficiency and If reactance is very high Arresters for ungrounded, Ungrounded neutral
Protection service arresters must be lowest cost arresters for ungrounded neutral service usually service arresters must
applied at sacrifice in cost neutral service must be must be applied at be applied at sacrifice
and efficiency applied at sacrifice in cost sacrifice in cost and in cost and efficiency
and efficiency efficiency
(9) Telephone Will usually be low Will be greatest in Will be reduced from Will be reduced from Will be low in magnitude
1
Interference except in cases of double magnitude due to higher solidly grounded values solidly grounded values except in cases of double
faults or electrostatic fault currents but can faults or series resonance
induction with neutral be quickly cleared at harmonic frequencies,
displaced but duration particularly with high but duration may be great
may be great speed breakers
(10) Radio May be quite high during Minimum Greater than for Greater than for May be high during faults
Interference faults or when neutral solidly grounded, solidly grounded,
is displayed when faults occur when faults occur
(11) Line Will inherently clear Must be isolated for Must be isolated for Must be isolated for Need not be isolated but
Availability themselves if total length each fault each fault each fault will inherently clear itself
of interconnected line is in about 60 to 80 percent
low and require isolation of faults
from system in increas-
ing percentages as length
becomes greater
(12) Adaptability Cannot be interconnected Satisfactory indefinitely Satisfactory indefinitely Satisfactory with solidly- Cannot be interconnected
to Interconnec- unless interconnecting with reactance-grounded with solidly-grounded or reactance-grounded unless interconnected
tion system is ungrounded systems systems systems with proper system is resonant
or isolating transformers attention to relaying grounded or isolating
are used transformers are used.
Requires coordination
between interconnected
systems in neutralizer
settings
(13) Circuit Interrupting capacity Same interrupting Interrupting capacity Interrupting capacity Interrupting capacity
Breakers determined by capacity as required for determined by 3-phase determined by 3-phase determined by 3-phase
3-phase conditions 3-phase short circuit will fault conditions fault conditions fault conditions
practically always be
satisfactory
(14) Operating Ordinarily simple but Simple Simple Simple Taps on neutralizers must
Procedure possibility of double be changed when major
faults introduces compli- system switching is per-
cation in times of trouble formed and difficulty may
arise in interconnected
systems. Difficult to tell
where faults are located
(15) Total Cost High, unless conditions Lowest Intermediate Intermediate Highest unless the arc
are such that arc tends suppressing characteris-
to extinguish itself, when tic is relied on to eliminate
transmission circuits may transmission circuits
be eliminated, reducing when it may be lowest
total cost for the particular types
of service

Because the method of grounding The aforementioned definition is of of the 3-phase current at the point
affects the voltage rise of the unfaulted significance in medium voltage distri- of fault. Damage to cable shields must
phases above ground, ANSI C62.92 bution systems with long lines and be checked. Although this fact is not
classifies systems from the point of with grounded sources removed dur- a problem except in small cables, it is
view of grounding in terms of a ing light load periods so that in some a good idea to supplement the cable
coefficient of grounding locations in the system the X0 /X1, shields returns of ground fault current
R0 /X1 may exceed the defining limits. to prevent damage, by installing an
Highest Power Frequency Other standards (cable and lightning equipment grounding conductor.
rms Line – Ground Voltage arrester) allow the use of 100% rated
COG = --------------------------------------------------------------------------------------------- The burdens on the current transform-
rms Line – Line Voltage at Fault cables and arresters selected on the
Location with the Fault Removed basis of an effectively grounded ers must be checked also (for satura-
system only where the criteria in the tion considerations), where residually
This same standard also defines connected ground relays are used
above are met. In effectively grounded
systems as effectively grounded when and the current transformers supply
system the line-to-ground fault current
COG ≤ .8 such a system would have current to phase relays and meters.
is high and there is no significant
X0 /X1 ≤ 3.0 and R0 /X1 ≤ 1.0. Any other
voltage rise in the unfaulted phases. If ground sensor current transformers
grounding means that does not satisfy
these conditions at any point in a With selective ground fault isolation (zero sequence type) are used they
system is not effectively grounded. the fault current should be at least 60% must be of high burden capacity.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-10 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0068
Grounding/Ground Fault Protection

Table 1.3-5 taken from ANSI-C62.92 current transformers rating of the Grounding Point
indicates the characteristics of the source. This rule will provide sensitive The most commonly used grounding
various methods of grounding. differential protection for wye-con- point is the neutral of the system or the
nected generators and transformers neutral point created by means of a
Reactance Grounding against line-to-ground faults near the zigzag or a wye-broken delta grounding
It is generally used in the grounding neutral. Of course, if the installation transformer in a system which was oper-
of the neutrals of generators directly of ground fault differential protection ating as an ungrounded delta system.
connected to the distribution system is feasible, or ground sensor current
1 bus, in order to limit the line-to-ground transformers are used, sensitive differ- In general, it is a good practice that all
fault to somewhat less than the 3-phase ential relaying in resistance grounded source neutrals be grounded with the
fault at the generator terminals. If the system with greater fault limitation same grounding impedance magnitude.
reactor is so sized, in all probability is feasible. In general, ground sensor However, neutrals should not be tied
the system will remain effectively current transformers (zero sequence) together to a single resistor. Where
grounded. do not have high burden capacity. one of the medium voltage sources is
Resistance grounded systems limit the the utility, their consent for impedance
Resistance Grounded circulating currents of triple harmonics grounding must be obtained.
Medium voltage systems in general and limit the damage at the point
should be low resistance grounded. The neutral impedance must have a
of fault. This method of grounding
The ground fault is typically limited to voltage rating at least equal to the rated
is not suitable for line-to-neutral
about 200A – 400A but less than 1000 line-to-neutral voltage class of the sys-
connection of loads.
amperes (a cable shield consideration). tem. It must have at least a 10-second
With a properly sized resistor and On medium voltage systems, 100% rating equal to the maximum future
relaying application, selective fault cable insulation is rated for phase-to- line-to-ground fault current and a con-
isolation is feasible. The fault limit neutral voltage. If continued operation tinuous rating to accommodate the
provided has a bearing on whether with one phase faulted to ground is triple harmonics that may be present.
residually connected relays are used desired, increased insulation thick-
or ground sensor current transformers ness is required. For 100% insulation, 4. Low Voltage System: Grounding
are used for ground fault relaying. fault clearance is recommended within Solidly grounded 3-phase systems
one minute; for 133% insulation, one (Figure 1.3-2) are usually wye-
In general, where residually connected hour is acceptable; for indefinite connected, with the neutral point
ground relays are used (51N), the fault operation, as long as necessary, grounded. Less common is the “red-
current at each grounded source 173% insulation is required. leg” or high-leg delta, a 240V system
should not be limited to less than the
supplied by some utilities with one
Table 1.3-5. Characteristics of Grounding winding center-tapped to provide 120V
Grounding Classes Ratios of Symmetrical Percent Fault Per Unit Transient
to ground for lighting. This 240V,
and Means Component Parameters ➀ Current LG Voltage 3-phase, 4-wire system is used where
120V lighting load is small compared
X0/X1 R0/X1 R0/X0 2 3
to 240V power load, because the
A. Effectively ➃ installation is low in cost to the utility.
1. Effective 0-3 0-1 — >60 ≤2
2. Very effective 0-1 0-0.1 — >95 <1.5 A corner-grounded 3-phase delta
system is sometimes found, with
B. Noneffectively
1. Inductance one phase grounded to stabilize all
a. Low Inductance 3-10 0-1 — >25 <2.3 voltages to ground. Better solutions
b. High Inductance >10 — <2 <25 ≤2.73 8 are available for new installations.
2. Resistance
a. Low Resistance 0-10 — ≥2 <25 <2.5
b. High Resistance — >100 ≤(-1) <1 ≤2.73 Phase A
3. Inductance and Resistance >10 — >2 <10 ≤2.73 • • • Phase B
4. Resonant 5 — — <1 ≤2.73 N
5. Ungrounded/Capacitance • Phase C
a. Range A -∞ to -40 6 — — <8 ≤3 9 • Neutral
b. Range B -40 to 0 — — >8 >3 79
1 Values of the coefficient of grounding (expressed as a percentage of maximum phase-to-phase Grounded Wye
voltage) corresponding to various combinations of these ratios are shown in the ANSI C62.92

2
Appendix figures. Coefficient of grounding affects the selection of arrester ratings. • Phase B
Ground-fault current in percentage of the 3-phase short circuit value.
3 Transient line-to-ground voltage, following the sudden initiation of a fault in per unit of the crest • • • Phase C
Phase A
of the prefault line-to-ground operating voltage for a simple, linear circuit.
4 In linear circuits, Class A1 limits the fundamental line-to-ground voltage on an unfaulted phase to • Neutral
138% of the prefault voltage; Class A2 to less than 110%.
5 See ANSI 62.92 para. 7.3 and precautions given in application sections. Center-Tapped (High-Leg) Delta
6 Usual isolated neutral (ungrounded) system for which the zero-sequence reactance is capacitive
(negative).
7 Same as NOTE (6) and refer to ANSI 62.92 para. 7.4. Each case should be treated on its own merit.
• Phase A
8 Under restriking arcing ground fault conditions (e.g., vacuum breaker interrupter operation), this • • Phase B
9
value can approach 500%. • Phase C
Under arcing ground fault conditions, this value can easily reach 700% but is essentially unlimited.
Corner-Grounded Delta

Figure 1.3-2. Solidly Grounded Systems

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-11
January 2003 System Application Considerations
Ref. No. 0069
Grounding/Ground Fault Protection

Ungrounded systems (Figure 1.3-3) Selecting the Low Voltage System With one phase grounded, the voltage
can be either wye or delta, although Grounding Method to ground of the other two phases
the ungrounded delta system is far There is no one “best” distribution rises 73%, to full phase-to-phase
more common. system for all applications. In choosing voltage. In low voltage systems this
among solidly grounded, resistance is not important, since conductors
grounded, or ungrounded power are insulated for 600V.
• Phase A
distribution, the characteristics of the A low voltage resistance grounded
system must be weighed against the 1
• • Phase B
Phase C requirements of power loads, lighting
system is normally grounded so that
the single line-to-ground fault current
Ungrounded Delta loads, continuity of service, safety, exceeds the capacitive charging
and cost. current of the system. If data for the
Phase A charging current is not available use
• • • Phase B Under ground-fault conditions, each
N system behaves very differently. A 40 – 50 ohm resistor in the neutral
• Phase C solidly grounded system produces of the transformer.
Ungrounded Wye high fault currents, usually with arcing, In commercial and institutional
and the faulted circuit must be cleared installations, such as office buildings,
Figure 1.3-3. Ungrounded Systems on first fault within a fraction of a shopping centers, schools, and hospi-
second to minimize damage. An tals, lighting loads are often 50% or
Resistance-grounded systems ungrounded system will pass limited
(Figure 1.3-4) are simplest with a wye more of the total load. In addition, a
current into the first ground fault — feeder outage on first ground fault is
connection, grounding the neutral only the charging current of the sys-
point directly through the resistor. seldom crucial — even in hospitals,
tem, caused by the distributed capaci- which have emergency power in criti-
Delta systems can be grounded by tance to ground of the system wiring
means of a zig-zag or other grounding cal areas. For these reasons, a solidly
and equipment. In low voltage sys- grounded wye distribution, with the
transformer. Wye broken delta trans- tems, this is rarely more than 1 or 2
former banks may also be used. neutral used for lighting circuits, is
amperes. Therefore, on first ground usually the most economical, effective,
fault an ungrounded system can con- and convenient design. In some
Phase A tinue in service, making it desirable instances it is an NEC requirement.
• • • Phase B where power outages cannot be toler-
N ated. However, if the ground fault is In industrial installations, the effect
R • Phase C intermittent, sputtering or arcing, a of a shutdown caused by a single
high voltage — as much as 6 to 8 times ground fault could be disastrous.
phase voltage — can be built up across An interrupted process could cause
Resistance-Grounded Wye the system capacitance, from the the loss of all the materials involved,
phase conductors to ground. Similar often ruin the process equipment
• • Phase A high voltages can occur as a result of itself, and sometimes create extremely
resonance between system capaci- dangerous situations for operating
• • • Phase B
tance and the inductances of trans- personnel. On the other hand, lighting
• Phase C
• formers and motors in the system. The is usually only a small fraction of the
N • phase-to-phase voltage is not affected. total industrial electrical load. A solidly
R • This high transient phase-to-ground grounded neutral circuit conductor
voltage can puncture insulation at is not imperative and, when required,
weak points, such as motor windings, can be obtained from inexpensive
Delta With Derived Neutral Resistance- and is a frequent cause of multiple lighting transformers.
Grounded Using Zig-Zag Transformer motor failures on ungrounded sys-
tems. Locating a first fault on an Because of the ability to continue in
ungrounded system can be difficult. operation with one ground fault on
Figure 1.3-4. Resistance-Grounded Systems the system, many existing industrial
If, before the first fault is cleared, a
This derives a neutral point, which second ground fault occurs on a differ- plants use ungrounded delta distribu-
can be either solidly or impedance- ent phase, even on a different, remote tion. Today, new installations can have
grounded. If the grounding transformer feeder, it is a high-current phase-to- all the advantages of service continuity
has sufficient capacity, the neutral cre- ground-to-phase fault, usually arcing, of the ungrounded delta, yet minimize
ated can be solidly grounded and used that can cause severe damage if at the problems of the system, such as
as part of a 3-phase, 4-wire system. least one of the grounds is not cleared the difficulty of locating the first
Most transformer-supplied systems immediately. If the second circuit is ground fault, risk of damage from a
are either solidly grounded or resis- remote, enough current may not flow second ground fault, and damage tran-
tance grounded. Generator neutrals to cause protection to operate. This sient overvoltages. A high-resistance
are often grounded through a reactor, can leave high voltages and stray grounded wye distribution can con-
to limit ground-fault (zero sequence) currents on structures and jeopardize tinue in operation with a ground fault
currents to values the generator can personnel. on the system, will not develop tran-
withstand. sient overvoltages, and, because the
In general, where loads will be con- ground point is established, locating
nected line-to-neutral, solidly grounded a ground fault is less difficult than
systems are used. High resistance on an ungrounded system especially
grounded systems are used as substi- when a “pulsing contactor” design is
tutes for ungrounded systems where applied. When combined with sensi-
high system availability is required. tive ground-fault protection, damage

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-12 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0070
Grounding/Ground Fault Protection

from a second ground fault can be this makes ground fault protection
Main
nearly eliminated. Ungrounded delta mandatory on 480Y/277-volt services,
systems can be converted to high- but not on 208Y/120-volt services. On a
resistance grounded systems, using 208-volt system, the voltage to ground Service
Neutral

a zig-zag or other grounding trans- is 120 volts. If a ground fault occurs, Transformer
GFR
former to derive a neutral, with similar the arc goes out at current zero, and Sensor
Typical
Feeder
benefits. While the majority of manu- the voltage to ground is often too low Ground Bus

facturing plants use solidly grounded to cause it to restrike. Therefore, arc-


1 systems, in many instances, the high- ing ground faults on 208-volt systems Main Bonding
Jumper
Typical
resistance grounded distribution will tend to be self-extinguishing. On a Grounding Equipment 4W Load
be the most advantageous. 480-volt system, with 277 volts to Electrode Grounding
Conductor Conductor
ground, restrike usually takes place
Ground Fault Protection after current zero, and the arc tends to
be self-sustaining, causing severe and Figure 1.3-5. Ground Return Sensing Method
A ground fault normally occurs in one
of two ways: By accidental contact of increasing damage, until the fault is When an energized conductor faults
an energized conductor with normally cleared by a protective device. to grounded metal, the fault current
grounded metal, or as a result of The NEC requires ground fault protec- returns along the ground return path to
an insulation failure of an energized tion only on the service disconnecting the neutral of the source transformer.
conductor. When an insulation failure means. This protection works so fast This path includes the main bonding
occurs, the energized conductor con- that for ground faults on feeders, or jumper — as shown in Figure 1.3-5.
tacts normally noncurrent-carrying even branch circuits, it will often open A current sensor on this conductor
grounded metal, which is bonded to the service disconnect before the (which can be a conventional bar-type
or part of the equipment grounding feeder or branch circuit overcurrent or window type CT) will respond to
conductor. In a solidly grounded sys- device can operate. This is highly ground fault currents only. Normal
tem, the fault current returns to the undesirable, and in the NEC (230-95) neutral currents resulting from
source primarily along the equipment a Fine Print Note (FPN) states that unbalanced loads will return along
grounding conductors, with a small additional ground fault protective the neutral conductor and will not be
part using parallel paths such as build- equipment will be needed on feeders detected by the ground return sensor.
ing steel or piping. If the ground return and branch circuits where maximum This is an inexpensive method of sens-
impedance were as low as that of the continuity of electric service is neces- ing ground faults where only minimum
circuit conductors, ground fault cur- sary. Unless it is acceptable to discon- protection per NEC (230-95) is desired.
rents would be high, and the normal nect the entire service on a ground For it to operate properly, the neutral
phase overcurrent protection would fault almost anywhere in the system, must be grounded in only one place
clear them with little damage. Unfortu- such additional stages of ground as indicated in Figure 1.3-5. In many
nately, the impedance of the ground fault protection must be provided. installations, the servicing utility
return path is usually higher, the fault At least two stages of protection are grounds the neutral at the transformer
itself is usually arcing and the imped- mandatory in health care facilities and additional grounding is required
ance of the arc further reduces the (NEC Sec. 517-17). in the service equipment per NEC
fault current. In a 480Y/277-volt sys-
Overcurrent protection is designed to (250-24(a)(2)). In such cases, and others
tem, the voltage drop across the arc
protect conductors and equipment including multiple source with multiple,
can be from 70 to 140V. The resulting
against currents that exceed their interconnected neutral ground points,
ground fault current is rarely enough
ampacity or rating under prescribed residual or zero sequence sensing
to cause the phase overcurrent protec-
time values. An overcurrent can result methods should be employed.
tion device to open instantaneously
and prevent damage. Sometimes, the from an overload, short circuit or (high A second method of detecting ground
ground fault is below the trip setting of level) ground fault condition. When faults involves the use of a zero
the protective device and it does not currents flow outside the normal sequence sensing method, as illus-
trip at all until the fault escalates and current path to ground, supplementary trated in Figure 1.3-6. This sensing
extensive damage is done. For these ground fault protection equipment will method requires a single, specially-
reasons, low level ground protection be required to sense low-level ground designed sensor either of a toroidal
devices with minimum time delay set- fault currents and initiate the protec- or rectangular shaped configuration.
tings are required to rapidly clear tion required. Normal phase over- This core balance current transformer
ground faults. This is emphasized by current protection devices provide surrounds all the phase and neutral
the NEC requirement that a ground no protection against low-level conductors in a typical 3-phase, 4-wire
fault relay on a service shall have a ground faults. distribution system. The sensing
maximum delay of one second for method is based on the fact that the
There are three basic means of sens-
faults of 3000 amperes or more. vectorial sum of the phase and neutral
ing ground faults. The most simple
and direct method is the ground return currents in any distribution circuit will
The NEC (Sec. 230-95) requires that
method as illustrated in Figure 1.3-5. equal zero unless a ground fault condi-
ground fault protection, set at no more
This sensing method is based on tion exists downstream from the sensor.
than 1200 amperes, be provided for
the fact that all currents supplied All currents that flow only in the circuit
each service disconnecting means
by a transformer must return to conductors, including balanced or
rated 1000 amperes or more on solidly
that transformer. unbalanced phase-to-phase and phase-
grounded wye services of more than
to-neutral normal or fault currents, and
150 volts to ground, but not exceeding
harmonic currents, will result in zero
600 volts phase-to-phase. Practically,

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-13
January 2003 System Application Considerations
Ref. No. 0071
Grounding/Ground Fault Protection

sensor output. However, should any neutral. In a residual sensing scheme, NEC (230-95) or in multi-tier schemes
conductor become grounded, the fault the relationship of the polarity mark- where additional levels of ground fault
current will return along the ground ings — as noted by the “X” on each protection are desired for added service
path — not the normal circuit conduc- sensor — is critical. Since the vectorial continuity. Additional grounding points
tors — and the sensor will have an sum of the currents in all the conduc- may be employed upstream of the resid-
unbalanced magnetic flux condition tors will total zero under normal, non- ual sensors but, not on the load side.
and a sensor output will be generated ground faulted conditions, it is impera-
to actuate the ground fault relay. tive that proper polarity connections Both the zero sequence and residual
are employed to reflect this condition. sensing methods have been com- 1
monly referred to as “vectorial
Zero
Sequence
Alternate
Sensor
summation” methods.
Sensor Location Sensor
Residual
Main
Polarity
Marks
Sensors Most distribution systems can utilize
either of the three sensing methods
Main
exclusively or a combination of the
sensing methods depending upon
Neutral
the complexity of the system and
Neutral
the degree of service continuity
GFR Typical
Feeder
and selective coordination desired.
Typical
GFR Feeder Different methods will be required
depending upon the number of
Typical supply sources and the number and
4W Load Typical
4W Load location of system grounding points.

Figure 1.3-6. Zero Sequence Sensing Method As an example, one of the more
Figure 1.3-7. Residual Sensing Method frequently used systems where
Zero sequence sensors are available continuity of service to critical loads
with various window openings for As with the zero sequence sensing
is a factor is the dual source system
circuits with small or large conduct- method, the resultant residual sensor
illustrated in Figure 1.3-8. This system
ors, and even with large rectangular output to the ground fault relay or inte-
utilizes tie-point grounding as permit-
windows to fit over bus bars or multi- gral ground fault tripping circuit will
ted under NEC Sec. 250-24(a)(3).
ple large size conductors in parallel. be zero if all currents flow only in the
The use of this grounding method is
Some sensors have split cores for circuit conductors. Should a ground
limited to services that are dual fed
installation over existing conductors fault occur, the current from the
(double-ended) in a common enclosure
without disturbing the connections. faulted conductor will return along the
or grouped together in separate enclo-
ground path, rather than on the other
sures and employing a secondary tie.
This method of sensing ground faults circuit conductors, and the residual
can be employed on the main discon- sum of the sensor outputs will not be This scheme utilizes individual sensors
nect where minimum protection per zero. When the level of ground fault connected in ground return fashion.
NEC (230-95) is desired. It can also be current exceeds the pre-set current Under tie breaker closed operating
easily employed in multi-tier systems and time delay settings, a ground conditions either the M1 sensor or M2
where additional levels of ground fault fault tripping action will be initiated. sensor could see neutral unbalance
protection are desired for added ser- currents and possibly initiate an
vice continuity. Additional grounding This method of sensing ground faults
improper tripping operation. However,
points may be employed upstream of can be economically applied on main
with the polarity arrangements of these
the sensor but, not on the load side. service disconnects where circuit
two sensors along with the tie breaker
breakers with integral ground fault
auxiliary switch (T/a) and interconnec-
Ground fault protection employing protection are provided. It can be used
tions as shown, this possibility is
ground return or zero sequence sens- in minimum protection schemes per
ing methods can be accomplished by
the use of separate ground fault relays Main 1 Tie Main 2
(GFRs) and disconnects equipped with
standard shunt trip devices or by cir-
Source GFR GFR GFR Source
cuit breakers with integral ground fault 1 1 T 2 2
protection with external connections M1 M2
Neutral a a Neutral
arranged for these modes of sensing. Ta

The third basic method of detecting M2


M1
ground faults involves the use of mul- Sensor Tie Sensor
tiple current sensors connected in a Typical Sensor Typical
Feeder Feeder
residual sensing method as illustrated
in Figure 1.3-7. This is a very common
sensing method used with circuit
breakers equipped with electronic trip
units and integral ground fault protec- Typical Typical
4W Load 4W Load
tion. The 3-phase sensors are required
for normal phase overcurrent protec- Center Point
Grounding Electrode
tion. Ground fault sensing is obtained
with the addition of an identically
rated sensor mounted on the Figure 1.3-8. Dual Source System — Single Point Grounding

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-14 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0072
Grounding/Ground Fault Protection

eliminated. Selective ground fault types may be employed to accomplish GFR next upstream from the fault and
tripping coordination between the the desired end results. that device will operate instantaneously
tie breaker and the two main circuit to clear the fault with minimum dam-
breakers is achieved by pre-set current Since the NEC (230-95) limits the age and maximum service continuity.
pickup and time delay settings between maximum setting of the ground fault This operating mode permits all GFRs
devices GFR/1, GFR/2 and GFR/T. protection used on service equipment to operate instantaneously for a fault
to 1200A (and timed tripping at 3000A within their zone and still provide
The advantages of increased service for one second), to prevent tripping complete selectivity between zones.
1 continuity offered by this system can of the main service disconnect on a The National Electrical Manufacturers
only be effectively utilized if additional feeder ground fault, ground fault Association (NEMA) states, in their
levels of ground fault protection are protection must be provided on all the application guide for ground fault
added on each downstream feeder. feeders. To maintain maximum service protection, that zone interlocking is
Some users prefer individual ground- continuity, more than two levels (zones) necessary to minimize damage from
ing of the transformer neutrals. In such of ground fault protection will be ground faults. A 2-wire connection
cases a partial differential ground fault required, so that ground fault outages is required to carry the restraining
scheme should be used for the mains can be localized and service interrup- signal from the GFRs in one zone to
and tie breaker. tion minimized. To obtain selectivity the GFRs in the next zone.
between different levels of ground
An example of a residual partial differ- fault relays, time delay settings should Circuit breakers with integral ground
ential scheme is shown in Figure 1.3-9. be employed with the GFR furthest fault protection and standard circuit
The scheme typically relies upon the downstream having the minimum breakers with shunt trips activated
vector sum of at least two neutral time delay. This will allow the GFR by the ground fault relay are ideal for
sensors in combination with each nearest the fault to operate first. ground fault protection. Many fused
breakers’ 3-phase sensors. To reduce With several levels of protection, this switches over 1200A, and Cutler-
the complexity of the drawing, each will reduce the level of protection for Hammer Type FDP fusible switches
of the breakers’ 3-phase sensors have faults within the upstream GFR zones. in ratings from 400A to 1200A, are
not been shown. It is absolutely critical Zone interlocking was developed for listed by UL as suitable for ground
that the sensors’ polarities are sup- GFRs to overcome this problem. fault protection. Fusible switches so
plied as shown, the neutral sensor listed must be equipped with a shunt
ratings of the mains and tie are the GFRs (or circuit breakers with integral trip, and be able to open safely on
same, and that there are no other ground fault protection) with zone faults up to 12 times their rating.
grounds on the neutral bus made interlocking are coordinated in a
downstream of points shown. system to operate in a time delayed Power distribution systems differ
mode for ground faults occurring most widely from each other, depending
An infinite number of ground fault remote from the source. However, this upon the requirements of each user,
protection schemes can be developed time delayed mode is only actuated and total system overcurrent protec-
depending upon the number of alternate when the GFR next upstream from the tion, including ground fault currents,
sources, the number of grounding fault sends a restraining signal to the must be individually designed to meet
points and system interconnections upstream GFRs. The absence of a these needs. Experienced and knowl-
involved. Depending upon the individ- restraining signal from a downstream edgeable engineers must consider the
ual system configuration, either mode GFR is an indication that any occurring power sources (utility or on-site), the
of sensing or a combination of all ground fault is within the zone of the effects of outages and costs of down-
time, safety for people and equipment,
initial and lifecycle costs, and many
Power Power
Transformer
other factors. They must apply protec-
Transformer
tive devices, analyzing the time-current
characteristics, fault interrupting
capacity, and selectivity and coordina-
X
X
X
X
tion methods to provide the most safe
Neutral Neutral
Sensor Main Sensor Main and cost-effective distribution system.
Main Breaker 52-1 Breaker 52-2 Main
Breaker Breaker Further Information
52-1 52-2 ■ AD 29-762 — Type GFR Ground
Phase A, Phase A, Fault Protection System.
Tie Breaker
Phase B, 52-T Phase B, ■ TD.44A.01.T.E — Type DSII Metal-
Phase C Phase C Enclosed Low Voltage Switchgear.
Neutral X
Neutral ■ IB 32-698A — C-HRG “Safe Ground”
Neutral Sensor X
Tie Breaker 52-T
Low Voltage High-Resistance
Trip Unit
Trip Unit

Typical X
Typical X Pulsing Ground System.
X X
4-Wire 4-Wire ■ PRSC-4E — System Neutral Ground-
Feeder 52-1 52-T 52-2 Feeder ing and Ground Fault Protection
a a a (ABB Publication).
■ PB 2.2 — NEMA Application Guide
4-Wire Load 4-Wire Load
Trip Unit Trip Unit Trip Unit for Ground Fault Protective Devices
Main Breaker Tie Breaker Main Breaker for Equipment.
52-1 52-T 52-2 ■ IEEE Standard 142 — Grounding of
Industrial and Commercial Power
Figure 1.3-9. Dual Source System — Multiple Point Grounding Systems (Green Book).

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-15
January 2003 System Application Considerations
Ref. No. 0073
Grounding/Ground Fault Protection

Lightning and Surge Protection The preferred grounding electrode The electrical distribution system and
is a metal underground water pipe in equipment ground must be connected
Physical protection of buildings direct contact with the earth for at least to this grounding electrode system by
from direct damage from lightning 10 feet (3 m). However, because under- a grounding electrode conductor. All
is beyond the scope of this section. ground water piping is often plastic other grounding electrodes, such as
Requirements will vary with geo- outside the building, or may later be those for the lightning protection sys-
graphic location, building type and replaced by plastic piping, the NEC tem, the telephone system, television
environment, and many other factors requires this electrode to be supple- antenna and cable TV system grounds,
(see IEEE/ANSI Standard 142, Ground- mented by and bonded to at least one and computer systems, must be bonded 1
ing of Industrial and Commercial other grounding electrode, such as to this grounding electrode system.
Power Systems). Any lightning protec- the effectively grounded metal frame
tion system must be grounded, and of the building, a concrete-encased Further Information
the lightning protection ground must electrode, a copper conductor ground ■ IEEE/ANSI Standard 142 — Ground-
be bonded to the electrical equipment ring encircling the building, or a made ing Industrial and Commercial
grounding system. electrode such as one or more driven Power Systems (Green Book).
ground rods or a buried plate. Where ■ IEEE Standard 241 — Electric Power
Grounding Electrodes any of these electrodes are present, Systems in Commercial Buildings
At some point, the equipment and they must be bonded together into (Gray Book).
system grounds must be connected one grounding electrode system. ■ IEEE Standard 141 — Electric Power
to the earth by means of a grounding Distribution for Industrial Plants
electrode system. One of the most effective grounding
electrodes is the concrete-encased (Red Book).
Outdoor substations usually use a electrode, sometimes called the Ufer
ground grid, consisting of a number of ground, named after the man who
ground rods driven into the earth and developed it. It consists of at least 20
bonded together by buried copper feet (6 m) of steel reinforcing bars or
conductors. The required grounding rods not less than 1/2 inches (12.7 mm)
electrode system for a building is in diameter, or at least 20 feet (6 m)
spelled out in the NEC, Sec. 250-C. of bare copper conductor, size No. 4
AWG or larger, encased in at least 2
inches (50.8 mm) of concrete. It must
be located within and near the bottom
of a concrete foundation or footing
that is in direct contact with the earth.
Tests have shown this electrode to
provide a low-resistance earth ground
even in poor soil conditions.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-16 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0074
Power Quality

Power Quality Terms Defining the Problem Before applying power-conditioning


equipment to solve power quality
Power quality problems can be viewed
Technical Overview as the difference between the quality problems, the site should be checked
of the power supplied and the quality for wiring and grounding problems.
Introduction of the power required to reliably Sometimes, correcting a relatively
Ever since the inception of the electric operate the load equipment. With inexpensive wiring error, such as a
utility industry, utilities have sought to this viewpoint, power quality prob- loose connection or a reversed neutral
provide their customers with reliable lems can be resolved in three ways: and ground wire, can avoid a more
1 power maintaining a steady voltage by reducing the variations in the expensive power conditioning solution.
and frequency. Sensitive electronic loads power supply (power disturbances), Power Quality Terms
deployed today by electrical energy by improving the load equipment’s
tolerance to those variations, or by Power Disturbance: Any deviation
users require strict requirements for
inserting some interface equipment from the nominal value (or from some
the quality of power delivered to loads.
(known as power conditioning equip- selected thresholds based on load
For electronic equipment, power ment) between the electrical supply tolerance) of the input AC power
disturbances are defined in terms of and the sensitive load(s) to improve characteristics.
amplitude and duration by the elec- the compatibility of the two. Practical- Total Harmonic Distortion or Distortion
tronic operating envelope. Electronic ity and cost usually determine the Factor: The ratio of the root-mean-
systems may be damaged and dis- extent to which each option is used. square of the harmonic content to the
rupted, with shortened life expectancy.
As in all problem solving, the problem root-mean-square of the fundamental
The proliferation of computers, vari- must be clearly defined before it can quantity, expressed as a percentage
able frequency motor drives and other be resolved. Many methods are used of the fundamental.
electronically controlled equipment is to define power quality problems. Crest Factor: Ratio between the
placing a greater demand on power For example, one option is a thorough peak value (crest) and rms value
producers for a disturbance-free on-site investigation which includes of a periodic waveform.
source of power. Not only do these inspecting wiring and grounding for
types of equipment require quality errors, monitoring the power supply Apparent (Total) Power Factor: The
power for proper operation; many for power disturbances, investigating ratio of the total power input in watts
times, these types of equipment are equipment sensitivity to power distur- to the total volt-ampere input.
also the sources of power distur- bances, and determining the load
bances that corrupt the quality of Sag: An rms reduction in the AC
disruption and consequential effects
power in a given facility. voltage, at the power frequency, for
(costs), if any. In this way, the power
the duration from a half-cycle to a few
Power Quality is defined according quality problem can be defined,
seconds. An undervoltage would have
to IEEE Standard 1100 as the concept alternative solutions developed,
a duration greater than several seconds.
of powering and grounding electronic and optimal solution chosen. Another
equipment in a manner that is suitable option is to buy power conditioning Interruption: The complete loss of
to the operation of that equipment. equipment to correct any and all voltage for a time period.
IEEE Standard 1159 notes that “within perceived power quality problems
without any on-site investigation. Transient: A sub-cycle disturbance
the industry, alternate definitions or in the AC waveform that is evidenced
interpretations of power quality have Sometimes this approach is not by a sharp brief discontinuity of the
been used, reflecting different points practical because of limitations in waveform. May be of either polarity
of view.” time; expense is not justified for and may be additive to or subtractive
In addressing power quality problems smaller installations; monitoring for from the nominal waveform.
at an existing site, or in the design power disturbances may be needed
over an extended period of time to Surge or Impulse: See transient.
stages of a new building, engineers
need to specify different services or capture infrequent disturbances; Noise: Unwanted electrical signals
mitigating technologies. The lowest the exact sensitivities of the load that produce undesirable effects
cost and highest value solution is to equipment may be unknown and in the circuits of control systems
selectively apply a combination of dif- difficult to determine; and finally, in which they occur.
ferent products and services as follows: the investigative approach tends
to solve only observed problems. Common-Mode Noise: The noise volt-
Key Services/Technologies in the Thus unobserved or potential age that appears equally and in phase
“Power Quality” Industry: problems may not be considered from each current-carrying conductor
in the solution. For instance, when to ground.
■ Power quality surveys, analysis planning a new facility, there is no
and studies. site to investigate. Therefore, Normal-Mode Noise: Noise signals
■ Power monitoring. power quality solutions are often measurable between or among active
■ Grounding products and services. implemented to solve potential or circuit conductors feeding the subject
perceived problems on a preventive load, but not between the equipment
■ Surge protection. grounding conductor or associated
basis instead of a thorough
■ Voltage regulation. signal reference structure and the active
on-site investigation.
■ Harmonic solutions. circuit conductors. See Figure 3.1-2 on
■ Lightning protection (ground rods, Page 3.1-7 for additional information
hardware, etc.). on Power Quality Terms.
■ Uninterruptible Power Supply (UPS)
or Motor-Generator (M-G) set.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-17
January 2003 System Application Considerations
Ref. No. 0075
Power Quality

Methodology for Ensuring Effective Power The proliferation of communication The benefit of implementing cascaded
Quality to Electronic Loads and computer network systems network protection is shown in
The Power Quality Pyramid is an effec- has increased the need for proper Figure 1.3-11. Combined, the two
tive guide for addressing power quality grounding and wiring of AC and data/ stages of protection at the service
problems at an existing facility. The communication lines. In addition to entrance and branch panel locations
framework is also effective for specify- reviewing AC grounding and bonding reduce the IEEE 62.41 recommended
ing engineers who are designing a practices, it is necessary to prevent test wave (C3 – 20 kV, 3 kA) to less than
new facility. Power quality starts with ground loops from affecting the signal 200V voltage, a harmless disturbance
grounding (the base of the pyramid) reference point. level for 120V rated sensitive loads. 1
and then moves upward to address 2. Surge Protection Devices (SPDs) are If only building entrance feeder protec-
the potential issues. This simple, recommended as the next stage power tion were provided, the let-through
yet proven methodology, will provide quality solutions. NFPA, UL96A, IEEE voltage will be approximately 950V
the most cost-effective approach. Emerald Book and equipment manu- in a 277/480V system exposed to
As we move higher up the pyramid, facturers recommend the use of surge induced lightning surges. This level
the cost per kVA of mitigating potential protectors. The transient voltage surge of let-through voltage can cause
problems increase and the quality suppressors (also called TVSS) shunt degradation or physical damage
of the power increases (Refer to short duration voltage disturbances to of most electronic loads.
Figure 1.3-10). ground, thereby preventing the surge
from affecting electronic loads. When The system approach views the
installed as part of the facility-wide electrical distribution layout as one
design, SPDs are cost-effective system and attempts to maximize
compared to all other solutions equipment reliability and productivity.
Cost Per kVA

(on a $/kVA basis). By identifying the critical, non-critical


and disturbance generating loads
The IEEE Emerald book recommends within a facility, and reviewing the
the use of a two-stage protection internal power distribution network,
concept. For large surge currents, a determination of where to install
diversion is best accomplished in mitigating equipment can be made.
two stages: the first diversion should
be performed at the service entrance The most effective and economic
to the building. Then, any residual solution for protecting a large number
5. Uninterruptible Power Supply of loads is to install parallel SPDs at
(UPS, Gen. Sets, etc.) voltage resulting from the action can
be dealt with by a second protective the building service entrance feeder
4. Harmonic Distortion and panelboard locations. This
device at the power panel of the com-
3. Voltage Regulation puter room (or other critical loads). reduces the cost of protection for
2. Surge Protection multiple sensitive loads.
1. Grounding
Input - high energy
Figure 1.3-10. Power Quality Pyramid TVSS
transient disturbance; IEEE Category
CP
TVSS C3 Impulse 20,000V; 10,000A
20,000V
1. Grounding represents the founda- 480V 120/208V
PEAK VOLTAGE

tion of a reliable power distribution


system. Grounding and wiring prob- Computer or Best achievable
Sensitive
performance with single TVSS
lems can be the cause of up to 80% of Stage 1 Protection Loads
at main panel (950V, at Stage 1)
all power quality problems. All other (Service Entrance) Stage 2 Protection
(Branch Location)
forms of power quality solutions are 800V
System Test Parameters:
dependent upon good grounding IEEE C62.41[10] and C62.45 [10] 400V
procedures. The following grounding test procedures using category; 0
standards are useful references: 480V main entrance panels; 25 uS 50 uS
TIME (MICROSECONDS)
100 feet (30 m) of 3-phase wire;
■ IEEE Green Book (Standard 142). 480/208V distribution transformer; Two stage (cascade
■ IEEE Emerald Book (Standard 1100). and 208V branch panel. approach) achieves best
possible protection (less
■ UL 96A, Installation Requirements = SPD or TVSS than 200V at Stage 2)
for Lightning Protection Systems.
■ IAEI 1996 (International Association Figure 1.3-11. Cascaded Network Protection
of Electrical Inspectors) Soars Book
on Grounding.
■ EC&M — Practical Guide to Quality
Power for Electronic Equipment.
■ Military Handbook — Grounding
Bonding and Shielding of Electronic
Equipment.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-18 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0076
Power Quality

The recommended system approach ■ Building entrance SPDs protect Lead length has the greatest effect on
for installing SPDs is summarized in the facility against large external the actual level of protection realized.
Figure 1.3-12. transients, including lightning. Twisting of the installation wires is
■ SPDs are bi-directional and prevent the second most important installation
transient and noise disturbances consideration. By twisting the installa-
1. tion wires, the area between wires is
Identify Critical Loads from feeding back within a system
when installed at distribution or reduced and the mutual inductance
branch panels. affect minimized.
1 2.
■ Two levels of protection safeguard
Identify Non-Critical Loads Increasing the diameter of the installation
sensitive loads from physical wires is of negligible benefit. Induc-
damage or operational upset. tance is a “skin effect” phenomenon and
3.
Identify Noise and a function of wire circumference. Since
Side Mounted SPD vs. Integral SPD
Disturbance Generating Loads only a marginal reduction in inductance
Historically, surge suppression devices is achieved when the diameter of the
were purchased as stand-alone installation conductors is increased,
4. devices and installed next to a panel-
Review Internal Power Distribution Layout the use of large diameter wire results
board, switchboard or motor control in only minimal improvement (see
center by an electrical contractor. Figure 1.3-14).
5. In 1995 gear manufacturers began
Identify Facility Exposure to integrating SPD devices into electrical Further benefits provided by integrated
Expected Levels of Disturbance
distribution equipment to increase surge suppression designs are the
the level of protection provided elimination of field installation costs and
6. against surge and noise disturbances. the amount of expensive “outboard”
Apply Mitigating Equipment to: wall space taken up by side mounted
a) Service Entrance Main Panels Directly connecting the surge sup- SPD devices.
b) Key Sub-Panels presser to the bus bar of electrical
c) Critical Loads Building Entrance Feeder Installation
distribution equipment results in
d) Data and Communication Lines
the best possible level of protection. Considerations
Compared to side mounted devices, Installing a SPD device immediately
Figure 1.3-12. System Approach for Installing SPDs connecting the SPD unit to the bus after the switchgear or switchboard
There may be critical loads within bar eliminates the need for lead wires main breaker is the optimal location
a facility that require a higher level and reduces the let-through voltage for protecting against external distur-
of protection. Such loads are essential up to 50% (see Figure 1.3-13). bances such as lightning. When placed
for the health and safety of personnel Given that surges are high frequency in this location, the disturbance is
or responsible for critical operations disturbances, the inductance of the “intercepted” by the SPD and reduced
within a facility. An example is a installation wiring increases the to a minimum before reaching the
computer that controls a processing let-through voltage of the protective distribution and/or branch panel(s).
line/operation. A series SPD is best device. Figure 1.3-14 shows that
suited for protecting such loads. The use of a disconnect breaker
for every inch of lead length, the eliminates the need to de-energize
Advantages of the System Approach are: let-through voltage is increased by the building entrance feeder equip-
an additional 15V to 25V above the ment should the SPD fail or require
■ The lowest possible investment manufacturers stated suppression isolation for Megger testing.
in mitigating equipment to protect performance.
a facility.

208Y/120 Panelboard
(integrated versus side mounted SPD)

1000 Side Mounted SPD Device


Side Mounted SPD SPD Integrated
Let-Through Voltage at Bus Bar

(assuming 14-inch (355.6 mm) lead length to bus)


used for Retrofit into Panelboards,
Applications Switchboards, MCCs 800

600

N 400
SPD
Integrated SPD
SPD (direct bus bar connection)
200

GRO UND G RO UND


0
Surge
Event
G -200
G -2.00 0.00 2.00 4.00 6.00 8.00 10.00
N
\
Microseconds

Figure 1.3-13. Performance Comparison of Side Mounted vs. Integrated SPD

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-19
January 2003 System Application Considerations
Ref. No. 0077
Power Quality

A common convention in the past has


Additional Let-Through Voltage Using IEEE C1(6000V, 3000A)[3] been to install lightning arrestors
Additional Let-Through Voltage ➀

Waveform (UL 1449 Test Wave)[12] within MCCs used in building entrance
900 14 AWG applications. The level of protection
800 209V (23%) 10 AWG offered by these devices is inadequate
700
600 4 AWG for today’s sensitive loads.
673V (75%)
500
400 The typical let-through voltage of a
300 surge arrester using the IEEE C62.41 1
200 C1 test waveform (6000V, 3000A) is
100
0
between 1500V and 2000V. This is a
3 Feet (914.4 mm) 1 Foot (304.8 mm) far lower level of protection compared
Lead Length Lead Length, to the 800V let-through voltage for
Loose Wiring Twisted Wires Twisted Wires a 480V wye SPD.

Figure 1.3-14. The Effect of Installation Lead Length on Let-Through Voltage Downstream MCCs may include a
1
panelboard feeding electronic loads.
Additional to UL 1449 ratings.
In such applications, the SPD can
The size or capacity of a suppressor is Smaller surge capacity SPDs (120 kA be integrated into the panelboard
measured in surge current per phase. per phase) are installed at branch pan- or between the transformer and
Larger suppressors rated at approxi- elboards where power disturbances panelboard lugs. This prevents
mately 250 kA per phase should be are of lower energy but occur much power disturbances from affecting
installed at the service entrance to more frequently. This level of surge the electronic loads connected to
survive high-energy surges associated current rating should result in a the panelboard.
with lightning. greater than 25 year life expectancy.
In all cases, whether at the service
A 250 kA per phase surge rating allows When isolated ground systems are entrance feeder, sub-feed or branch
for over a 25 year life expectancy used, the SPD should be installed such locations, the SPD units installed in
assuming an IEEE defined high that any common mode surges are MCCs should be mounted in a wrap-
exposure environment. Lower surge shunted to the safety ground. per with stabs to minimize installation
rating devices may be utilized; how- lead length, time and cost.
ever, device reliability and long-term The use of a disconnect breaker is
performance may be compromised. optional. The additional let-through In facilities with busway systems,
voltage resulting from the increased the first stage of protection is typically
For aerial structures, the 99.8 percen- inductance caused by the disconnect integrated into the service entrance
tile recorded lightning stroke current switch is about 50V to 60V. This increase switchgear. The second stage of pro-
is less than 220 kA. The magnitude of in disturbance voltage can result in tection is a SPD installed in a bus plug
surges conducted or induced into a process disruption and downtime. with stabs allowing for easy, minimal
facility electrical distribution system is lead length installation.
considerably lower given the presence Motor Control Center and Busway
of multiple paths for the surge to travel Installation Considerations Surge protection should be placed
along. It is for this reason that IEEE Increasingly, motor control centers ahead of any critical loads to prevent
C62.41 recommends the C3 (20 kV, (MCC) power VFDs, solid-state over- the primary stage let-through voltage
10 kA) test wave for testing SPDs load relays, electronic soft starters, from disrupting operations.
installed at building entrance feeders. electronic metering and relaying Installing Dataline Surge Protection
equipment require protection from
SPDs with surge ratings greater than Most facilities also have communica-
power disturbances.
250 kA are not required. The incremental tion lines that are potential sources
benefit is minimal and the additional When utilized in service entrance for external surges. As identified by
cost difficult to justify. applications, MCC SPDs provide the the Power Quality Pyramid, proper
first stage of protection against external grounding of communication lines is
Installing Panelboard high-energy power disturbances. To essential for dependable operation.
Surge Protection Devices reduce incoming power disturbances This concept is seconded by NEC
Wherever possible, consultants, speci- to the lowest level possible, the surge Article 800 which states that all data,
fiers and application engineers should protector should be installed onto the power and cable lines be grounded
ensure similar loads are fed from the bus bar in the main incoming structure. and bonded.
same source. In this way, disturbance-
If there is no room in the main Power disturbances such as lightning
generating loads are separated from
structure, the SPD should be installed can elevate the ground potential
electronic circuits affected by power
in a cell located at the top of the first between two communicating pieces
disturbances. For example; motor
or second structure. In this fashion, of electronic equipment with different
loads, HVAC systems and other linear
external disturbances are “intercepted” ground references. The result is current
loads should be separated from the
(clamped to a safe let-through voltage) flowing through the data cable causing
sensitive process control equipment
before entering the facility electrical component failure, terminal lock-up,
employed within petroleum and
distribution system. data corruption and interference.
petrochemical facilities.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-20 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0078
Power Quality

NFPA 780 D — 4.8 warns that “surge critical to reliable operation of mission loads far below their ratings, because
suppression devices should be installed critical equipment, a common design the harmonic currents cause greater
on all wiring entering or leaving elec- error is to assume UPS systems solve heating than the same number of rms
tronic equipment, usually power, data all power quality problems. Given the amperes of 60 Hz current. This results
or communication wiring.” high cost per kVA of UPS, generators, from increased eddy current and
etc., (including capital, efficiency and hysteresis losses in the iron cores,
Surge suppressers should be installed maintenance costs) and the use of and skin effect in the conductors of the
at both ends of a data or communica- more decentralized network systems, windings. In addition, the harmonic
1 tion cable. In those situations where the technology is often applied at currents acting on the impedance of
one end of the cable is not connected specific loads only. To prevent light- the source cause harmonics in the
into an electronic circuit (e.g., contac- ning or other surge related damage, source voltage, which is then applied
tor coil), protection on the electronic IEEE (Standard 1100) recommends to other loads such as motors, causing
end only is acceptable. surge protection ahead of UPS and them to overheat.
To prevent the coupling or inducing of associated bypass circuits.
Some of the harmonic voltages are
power disturbances into communica- negative sequence (rotation is ACB
tion lines, the following should be Harmonics and Nonlinear Loads
instead of ABC). The second, fifth,
avoided: Until recently, most electrical loads eighth, and eleventh harmonics are
were linear. The instantaneous current negative sequence harmonics. Triple
■ Data cables should not be run over
was directly proportional to the instan- harmonics can be zero sequence
fluorescent lighting fixtures.
taneous voltage at any instant, though harmonics and are in phase.
■ Data cables should not be in the lagging by some time depending
vicinity of electric motors. on the power factor. However, loads In addition to the above, 3-phase non-
■ The right category cable should that are switched or pulsed, such as linear loads contain small quantities of
be used to ensure transmission rectifiers, thyristors, and switching even and third harmonics although in
performance. power supplies, are nonlinear. an unbalanced 3-phase system feeding
■ Data cables must be grounded at With the proliferation of electronic 3-phase non-linear loads the unbalance
both ends when communicating equipment such as computers, UPS may cause even harmonics to exist.
between buildings. systems, variable speed drives,
In general, as the order of a harmonic
programmable logic controllers, and
Reference Section 35 for detailed gets higher, its amplitude becomes
the like, nonlinear loads have become
information on SPDs. smaller as a percentage of the funda-
a significant part of many installations.
mental frequency.
3. Voltage Regulation (i.e., sags or Other types of harmonic-producing
overvoltage) disturbances are gener- loads include arcing devices (arc The harmonics also complicate the
ally site- or load-dependent. A variety furnaces, fluorescent lights) and iron- application of capacitors for power
of mitigating solutions are available core saturable devices (transformers, factor correction. If at a harmonic
depending upon the load sensitivity, especially during energization). frequency the capacitors capacitive
fault duration/magnitude and the impedance at the frequency equals
Nonlinear load currents vary widely
specific problems encountered. It is the system’s reactive impedance at the
from a sinusoidal wave shape; often
recommended to install monitoring same frequency, as viewed at the point
they are discontinuous pulses. This
equipment on the AC power lines to of application of the capacitor, the
means that they are extremely high
assess the degree and frequency of harmonic voltage and current can
in harmonic content. The harmonics
occurrences of voltage regulation reach dangerous magnitudes. At the
create numerous problems in electrical
problems. The captured data will allow same time that harmonics create prob-
systems and equipment. The rms
for the proper solution selection. lems in the application of power factor
value of current is not easy to deter-
correction capacitors, they lower the
4. Harmonics seldom affect the opera- mine, and true rms measurements are
actual power factor. The rotating
tion of microprocessor-based loads. necessary for metering and relaying to
meters used by the utilities for watt-
Mitigating equipment is usually not prevent improper operation of protec-
hour and varhour measurements do
required to prevent operating prob- tive devices. Devices that measure
not detect the distortion component
lems with electronic loads. Engineers time on the basis of wave shape, such
caused by the harmonics. Rectifiers
are often more concerned about the as many generator speed and synchro-
with diode front ends and large DC
effects of increased neutral current nizing controls, will fail to maintain
side capacitor banks have displace-
on the electrical distribution system proper output frequency or to permit
ment power factor of 90% to 95%.
(i.e., neutral conductors, transform- paralleling of generators. It is impor-
More recent electronic meters are
ers). Readings from a power quality tant that with standby generators the
capable of metering the true kVA kW
meter will determine the level of dis- harmonic content of the current of the
hours taken by the circuit.
tortion and identify site-specific prob- loads that will be transferred to the
lems. Effective distribution layout and standby generator be reviewed with Single-phase power supplies for
other considerations can be addressed the generator manufacturer to ensure computer and fixture ballasts are
during the design stage to mitigating that the voltage and frequency controls rich in third harmonics and their
harmonic problems. Harmonics related will operate satisfactorily. Standby odd multiples.
problems can be investigated and generators may need to be de-rated
when serving harmonic-producing With a 3-phase, 4-wire system, if the
solved once loads are up and running. 60 Hz phase currents are balanced
loads. Computers will crash as their
5. Uninterruptible Power is often the internal timing clocks fail. (equal), the neutral current is zero.
last component to be selected in the However, triplens and their odd multiple
design process. While the proper Transformers, generators, and UPS harmonics are additive in the neutral.
selection and application of UPS is systems will overheat and often fail at

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-21
January 2003 System Application Considerations
Ref. No. 0079
Power Quality

Even with the phase currents perfectly 6. Locate capacitors as far away Revised standard IEEE 519-1992 indi-
balanced, the harmonic currents in the (in terms of circuit impedance) cates the limits of current distortion
neutral can total 173% of the phase from non-linear loads. allowed at the PCC (Point of Common
current. This has resulted in over- Coupling) point on the system where
heated neutrals. The Computer and 7. When all the above do not the current distortion is calculated,
Business Equipment Manufacturers produce the desired reduction, usually the point of connection to
Association (CBEMA) recommends oversize the system components the utility or the main supply bus
that neutrals in the supply to electronic as the last resort, or derate the of the system.
equipment be oversized to at least equipment. 1
173% of the ampacity of the phase The standard also covers the harmonic
ANSI Standard C57.110 covers the limits of the supply voltage from the
conductors to prevent problems. procedure of derating standard
CBEMA also recommends derating utility or cogenerators.
(non-K-rated) transformers.
transformers, loading them to no more Table 1.3-7. Utility or Cogenerator Supply
than 50% to 70% of their nameplate This method is based on determining Voltage Harmonic Limits
kVA, based on a rule-of-thumb calcu- the load loss due to I2R loss including
Voltage 2.3-69 kV 69-138 kV >138 kV
lation, to compensate for harmonic the harmonic current plus the increase Range
heating effects. in the eddy current losses due the
harmonic currents. The winding eddy Maximum 3.0% 1.5% 1.0%
3-phase, 6-pulse rectifiers produce 5th, current loss under rated conditions Individual
7th, 11th, 13th...harmonics. 12-pulse, should be obtained from the trans- Harmonic
3-phase rectifiers produce 11th, 13th, former manufacturer, or the method Total 5.0% 2.5% 1.5%
23rd, 25th, etc. shown in C57.110 should be used. Harmonic
Distortion
In spite of all the concerns they cause, The K-rated transformers calculate
non-linear loads will continue to the sum of Ih2(pu) x h2 where Ih is the Vh
increase. Therefore, the design of harmonic current of the hth harmonic Percents are −−− x 100 for each harmonic
non-linear loads and the systems that V1
as per unit of the fundamental and h
supply them will have to be designed is the order of the harmonic. K is the
so that their adverse effects are factor that corrects the eddy current and
greatly reduced. loss under rated conditions to reduce
Such measures are: the effects of adverse heating due h = h max 1/2

Σ
to harmonics.  2
V thd =  V h 
1. Use multipulse conversion (AC 
to DC) equipment (greater than K-rated transformers have lower  h = 2 
6 pulses) to reduce the amplitude impedance than non-K-rated trans-
of the harmonics. former which should be considered
in the selection of the low voltage It is important for the system designer
2. Use active filters that reduce the side breakers. to know the harmonic content of the
harmonics taken from the system utility’s supply voltage because it will
by injecting harmonics equal to Table 1.3-6. Low Voltage System
affect the harmonic distortion of
and opposite to those generated Classification and Distortion Limits for 480V
Systems the system.
by the equipment.
Class C AN DF Table 1.3-7 is taken from IEEE
3. Where capacitors are required for Standard 519 Table 10.3.
a power factor correction, design Special Application 1 10 16,400 3%
General System 5 22,800 5%
the installation incorporating reac- Dedicated System 2 36,500 10%
tors as tuned filters to 5th, 7th,
1 Special systems are those where the rate
11th and 13th harmonics and high
of change of voltage of the notch might mis-
pass filters for higher harmonics. trigger an event. AN is volt-microseconds,
C is the impedance ratio of total impedance
4. Use ∆-∆ and ∆-Y transformers in to impedance at common point in system.
pairs as supply to conversion DF is distortion factor.
equipment. Their effect is the
same as that of multipulse equip- Table 1.3-8. Current Distortion Limits for General Distribution Systems (120V Through 69000V)
ment and should be considered Maximum Harmonic Current Distortion in Percent of IL
with 6-pulse equipment only. Individual Harmonic Order (Odd Harmonics)
5. Install reactors between the power ISC /IL <11 11 < h<17 17 < h<23 23 < h<35 35 < h TDD
supply and the conversion equip- <20 2 4.0 2.0 1.5 .6 .3 5.0
ment. They reduce the harmonic 20<50 7.0 3.5 2.5 1.0 .5 8.0
components of the current drawn 50<100 10.0 4.5 4.0 1.5 .7 12.0
by diode type conversion equip- 100<1000 12.0 5.5 5.0 2.0 1.0 15.0
ment with large filter capacitors. >1000 15.0 7.0 6.0 2.5 1.4 20.0
Another benefit is that they pro- 2 All power generation equipment is limited to these values of current distortion,
tect the filter capacitors from regardless of actual ISC/IL where:
switching surges produced ISC = Maximum short circuit current at PCC.
IL = Maximum demand load current (fundamental frequency component) at PCC.
by switched utility or medium
voltage system capacitor. Note: TDD = Total Demand Distortion.
Even harmonics are limited to 25% of the odd harmonic limits above.
Current distortions that result in a DC offset, e.g., half-wave converters, are not allowed.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-22 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0080
Other Considerations

Secondary Voltage Technical Factors resulting in full 120-volt output. Since


The principal advantage of the use of these transformers are usually located
The choice between 208Y/120V and close to the 120-volt loads, secondary
480Y/277V secondary distribution for higher secondary voltages in buildings
is that for a given load, less current voltage drop should not be a problem.
commercial and institutional buildings If it is, taps may be used to compensate
depends on several factors. The most means smaller conductors and lower
voltage drop. Also, a given conductor by raising the voltage at the transformer.
important of these are size and types
of loads (motors, fluorescent lighting, size can supply a large load at the Fault interruption by protective
same voltage drop in volts, but a lower
1 incandescent lighting, receptacles)
percentage voltage drop because of
devices may be more difficult at 480
and length of feeders. In general, large volts than at 208 volts for two principal
motor and fluorescent lighting loads, the higher supply voltage. Fewer or reasons. First, the 480-volt arc is more
and long feeders, will tend to make smaller circuits can be used to trans- difficult to interrupt than the 208-volt
the higher voltages, such as 480Y/277V, mit the power from the service arc. Second, the small impedances
more economical. Very large loads and entrance point to the final distribution in the system, such as bus or cable
long runs would indicate the use of points. Smaller conductors can be impedances, and upstream protective
medium voltage distribution and load- used in many branch circuits supply- device impedances, have less effect
center unit substations close to the ing power loads, and a reduction in in reducing fault currents at the higher
loads. Conversely, small loads, short the number of lighting branch circuits voltages. However, the interrupting
runs, and a high percentage of incan- is usually possible. ratings of circuit breakers and fuses at
descent lighting would favor lower It is easier to keep voltage drops within 480 volts have increased considerably
utilization voltages such as 208Y/120V. acceptable limits on 480-volt circuits in recent years, and protective devices
than on 208-volt circuits. When 120- are now available for any required
Industrial installations, with large fault duty at 480 volts. In addition,
motor loads, are almost always 480V, volt loads are supplied from a 480-volt
system through step-down transform- many of these protective devices
often ungrounded delta or resistance are current limiting, and can be used
grounded delta or wye systems (see ers, voltage drop in the 480-volt supply
conductors can be compensated for by to protect downstream equipment
section on ground fault protection). against these high fault currents.
the tap adjustments on the transformer,
Practical Factors
Since most low voltage distribution
equipment available is rated for up to
600 volts, and conductors are insulated
for 600 volts, the installation of 480-volt Elevator
Panel
systems uses the same techniques and
is essentially no more difficult, costly, Typical
or hazardous than for 208-volt systems.
The major difference is that an arc of 120 Typical Emergency
volts to ground tends to be self-extin- HVAC Lighting Panel
Panel
guishing, while an arc of 277 volts to (Typical Every
Third Floor)
ground tends to be self-sustaining and
likely to cause severe damage. For this
reason, the National Electrical Code 480Y/277V 208Y/120V Typical
Panel Panel
requires ground fault protection of Dry Type Transformer
equipment on grounded wye services 480∆-208Y/120V
(Typical Every Floor)
of more than 150 volts to ground but not
exceeding 600 volts phase-to-phase (for HVAC Busway Emergency Elevator
Feeder Riser Lighting Riser
practical purpose, 480Y/277V services), Riser
for any service disconnecting means
rated 1000 amperes or more. The
Building and Typical Typical
National Electrical Code permits voltage Miscellaneous
up to 300 volts to ground on circuits Loads
supplying permanently installed electric Typical

discharge lamp fixtures, provided the


luminaires do not have an integral man- Typical Typical
Spare
ual switch and are mounted at least
8 feet (2.4 m) above the floor. This per- ➀ ➀ ➀ ➀ ➀ ➀ ➀
mits a 3-phase, 4-wire, solidly grounded
480Y/277-volt system to supply directly
all of the fluorescent and high-intensity ➀ Include Ground 4000A
Automatic
Fault Trip. ➀ Transfer Switch
discharge (HID) lighting in a building at Main CB
277 volts, as well as motors at 480 volts. Gen. CB
Utility Emergency
CTs
While mercury-vapor HID lighting is Metering or Standby
PTs Generator
becoming obsolescent, other HID light-
Utility 4000A at 480Y/277V
ing, such as high-pressure sodium or Service 100,000A Available Fault Current
metal halide, is increasing in use, as
color rendition is improved, because Figure 1.3-15. Typical Power Distribution and Riser Diagram for a Commercial Office Building
of the economical high lumen output 1 Include ground fault trip.
of light per watt of power consumed.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-23
January 2003 System Application Considerations
Ref. No. 0081
Other Considerations

Economic Factors For any motor operating 10 or more average winding temperature rise at
Utilization equipment suitable for hours per day, it is recommended to full load. A better method would be
principal loads in most buildings use the energy-efficient types. These to evaluate transformer losses, based
is available for either 480-volt or motors have a premium cost of about on actual loading cycles throughout
208-volt systems. 3-phase motors 20% more than standard motors. the day, and consider the cost of
and their controls can be obtained Depending on loading, hours of use, losses as well as the initial cost of
for either voltage, and for a given and the cost of energy, the additional the transformers in purchasing.
horsepower are less costly at 480 initial cost could be repaid in energy
volts. Fluorescent and HID lamps can saved within a few months, and it HVAC systems have traditionally been 1
rarely takes more than two years. very wasteful of energy, often being
be used with either 277- or 120-volt designed for lowest first cost. This,
ballasts. However, in almost all cases, Since, over the life of a motor, the cost
of energy to operate it is many times too, is changing. For example, reheat
the installed equipment will have a systems are being replaced by variable
lower total cost at the higher voltage. the cost of the motor itself, any motor
with many hours of use should be of air volume systems, resulting in equal
the energy-efficient type. For motors comfort with substantial increases
Energy Conservation in efficiency. While the electrical engi-
operating lightly loaded a high per-
Because of the greatly increased cost centage of the time, energy-saving neer has little influence on the design
of electrical power, designers must devices, such as those based on the of the HVAC system, he/she can spec-
consider the efficiency of electrical NASA patents, can result in substantial ify that all motors with continuous
distribution systems, and design for savings, especially when combined or long duty cycles are specified as
energy conservation. In the past, espe- with solid-state starters. However, energy efficient types, and that the
cially in commercial buildings, design power factor control-type devices can variable-air-volume fans do not use
was for lowest first cost, because rarely be justified unless the motor is inlet vanes or outlet dampers, but
energy was inexpensive. Today, even loaded to less than 50% of its rating are driven by variable-speed drives.
in the speculative office building, oper- much of the time. Variable-speed drives can often be
ating costs are so high that energy- desirable on centrifugal compressor
conserving designs can justify their Where a motor drives a load with units as well. Since some of these
higher initial cost with a rapid payback variable output requirements such requirements will be in HVAC specifi-
and continuing savings. There are four as a centrifugal pump or a large fan, cations, it is important for the energy-
major sources of energy conservation customary practice has been to run conscious electrical engineer to work
in a commercial building — the lighting the motor at constant speed, and to closely with the HVAC engineer at
system, the motors and controls, the throttle the pump output or use inlet the design stage.
transformers, and the HVAC system. vanes or outlet dampers on the fan.
This is highly inefficient and wasteful Building Control Systems
The lighting system must take advan- of energy. In recent years, solid-state
tage of the newest equipment and In order to obtain the maximum bene-
variable-frequency, variable-speed fit from these energy-saving lighting,
techniques. New light sources, familiar drives for ordinary induction motors
light sources with higher efficiencies, power, and HVAC systems, they must
have been available, reliable, and be controlled to perform their func-
solid-state ballasts with dimming con- relatively inexpensive. Using a vari-
trols, use of daylight, environmental tions most efficiently. Constant moni-
able-speed drive, the throttling valves toring would be required for manual
design, efficient luminaires, computer- or inlet vanes or output dampers can
ized or programmed control, and the operation, so some form of automatic
be eliminated, saving their initial cost, control is required. The simplest of
like, are some of the methods that can and energy will be saved over the life
increase the efficiency of lighting sys- these energy-saving controls, often
of the system. An additional benefit very effective, is a time clock to turn
tems. They add up to providing the of both energy-efficient motors and
necessary amount of light, with the various systems on and off. Where
variable-speed drives (when operated flexible control is required, program-
desired color rendition, from the most at less than full speed) is that the
efficient sources, where and when it is mable controllers may be used. These
motors operate at reduced tempera- range from simple devices, similar to
needed, and not providing light where tures, resulting in increased motor life.
or when it is not necessary. Using the multifunction time clocks, up to full
best of techniques, office spaces that Transformers have inherent losses. microprocessor-based, fully program-
originally required as much as 3.5 Transformers, like motors, are mable devices, really small computers.
watts per square foot have been given designed for lower losses by using For complete control of all building
improved lighting, with less glare and more and better core materials, larger systems, computers with specialized
higher visual comfort, using as little as conductors, etc., and this results software can be used. Computers can
1.0 to 2.0 watts per square foot. In an in increased initial cost. Since the not only control lighting and HVAC
office building of 200,000 square feet 480-volt to 208Y/120-volt stepdown systems, and provide peak demand
(60,960 m), this could mean a saving of transformers in an office building control, to minimize the cost of energy,
400 kW, which, at $.05 per kWh, 250 days are usually energized 24 hours a day, but they can perform many other func-
per year, 10 hours per day, could save savings from lower losses can be tions. Fire detection and alarm systems
$50,000 per year in energy costs. Obvi- substantial, and should be considered can operate through the computer,
ously, efficient lighting is a necessity. in all transformer specifications. which can also perform auxiliary
One method of obtaining reduced functions such as elevator control
Motors and controls are another cause losses is to specify transformers with and building communication in case
of wasted energy that can be reduced. 220°C insulation systems designed of fire. Building security systems, such
New, energy efficient motor designs for 150°C average winding tempera- as closed-circuit television monitoring,
are available using more and better ture rise, with no more than 80°C door alarms, intruder sensing, can
core steel, and larger windings. (or sometimes 115°C) be performed by the same building
computer system.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-24 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0082
Other Considerations

The time clocks, programmable sometimes steam absorption-type having jurisdiction. Optional standby
controllers, and computers can air conditioning. Such cogeneration systems, not legally required, are also
obtain data from external sensors systems are now operating success- covered in the NEC (Article 702).
and control the lighting, motors, and fully in hospitals, shopping centers,
other equipment by means of hard high-rise apartment buildings and Emergency systems are intended to
wiring-separate wires to and from even commercial office buildings. supply power and illumination essen-
each piece of equipment. In the more tial for safety to human life, when the
complex systems, this would result in Where a cogeneration system is being normal supply fails. NEC requirements
1 a tremendous number of control considered, the electrical distribution are stringent, requiring periodic test-
wires, so other methods are frequently system becomes more complex. The ing under load and automatic transfer
used. A single pair of wires, with elec- interface with the utility company is criti- to emergency power supply on loss of
tronic digital multiplexing, can control cal, requiring careful relaying to protect normal supply. All wiring from emer-
or obtain data from many different both the utility and the cogeneration gency source to emergency loads
points. Sometimes, coaxial cable is system. Many utilities have stringent must be kept separate from all other
used with advanced signaling equip- requirements that must be incorporated wiring and equipment, in its own dis-
ment. Some systems dispense with into the system. Proper generator con- tribution and raceway system, except
control wiring completely, sending trol and protection is necessary, as well. in transfer equipment enclosures and
and receiving digital signals over the An on-site electrical generating plant similar locations. The most common
power wiring. The newest systems tied to an electrical utility, is a sophisti- power source for large emergency
may use fiber-optic cables to carry cated engineering design. loads is an engine-generator set, but
tremendous quantities of data, free the NEC also permits the emergency
Utilities require that when the supply (subject to local code require-
from electromagnetic interference. protective device at their substation
The method used will depend on ments) to be storage batteries, uninter-
opens that the device connecting a ruptible power supplies, a separate
the type, number, and complexity cogenerator to the utility open also.
of functions to be performed. emergency service, or a connection
One reason is that most cogenerators to the service ahead of the normal
Because building design and control are connected to feeders serving other service disconnecting means. Unit
for maximum energy saving is impor- customers. Utilities desire to reclose equipment for emergency illumina-
tant and complex, and frequently the feeder after a transient fault is tion, with a rechargeable battery, a
involves many functions and several cleared. Reclosing in most cases will charger to keep it at full capacity when
systems, it is necessary for the design damage the cogenerator if it had normal power is on, one or more
engineer to make a thorough building remained connected to their system. lamps, and a relay to connect the bat-
and environmental study, and to tery to the lamps on loss of normal
weigh the costs and advantages of Islanding is another reason why the power, is also permitted. Because
many systems. The result of good utility insists on the disconnection of of the critical nature of emergency
design can be economical, efficient the cogenerator. Islanding is the event power, ground fault protection is not
operation. Poor design can be wasteful, that after a fault in the utility’s system required. It is considered preferable
and extremely costly. is cleared by the operation of the to risk arcing damage, rather than to
protective devices, a part of the disconnect the emergency supply
Cogeneration system may continue to be supplied completely. On 480Y/277-volt emer-
by cogeneration. Such a condition is gency systems with protective devices
Cogeneration is another outgrowth of
dangerous to the utility’s operation rated 1000 amperes or more, a ground
the high cost of energy. Cogeneration
during restoration work. fault alarm is required if ground fault
is the production of electric power
concurrently with the production of protection is not provided.
Major cogenerators are connected to
steam, hot water, and similar energy the subtransmission or the transmis- Legally required standby systems, as
uses. The electric power can be the sion system of a utility. Major cogener- required by the governmental agency
main product, and steam or hot water ators have buy-sell agreements. In such having jurisdiction, are intended to
the by-product, as in most commercial cases utilities use a trip transfer scheme supply power to selected loads, other
installations, or the steam or hot water to trip the cogenerator breaker. than those classed as emergency
can be the most required product, systems, on loss of normal power.
and electric power a by-product, as in Guidelines that are given in ANSI
These are usually loads not essential
many industrial installations. In some Guide Standard 1001 are a good
to human safety, but loss of which
industries, cogeneration has been starting point, but the entire design
could create hazards or hamper rescue
common practice for many years, but should be coordinated with the utility.
or fire-fighting operations. NEC
until recently it has not been economi- requirements are similar to those for
cally feasible for most commercial Emergency Power emergency systems, except that wir-
installations. This has been changed Most areas have requirements for ing may occupy the same distribution
by the high cost of purchased energy, emergency and standby power and raceway system as the normal
plus a federal law (Public Utility Regu- systems. The National Electrical wiring if desired. Optional standby
latory Policies Act, known as PURPA) Code does not specifically call for systems are those not legally required,
that requires public utilities to purchase any emergency or standby power, and are intended to protect private
any excess power generated by the but does have requirements for business or property where life safety
cogeneration plant. In many cases, those systems when they are legally does not depend on performance of
practical commercial cogeneration mandated and classed as emergency the system. Optional systems can be
systems have been built that provide (Article 700) or standby (Article 701) treated as part of the normal building
some or all of the electric power by municipal, state, federal, or other wiring system. Both legally required
required, plus hot water, steam, and codes, or by any governmental agency

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-25
January 2003 System Application Considerations
Ref. No. 0083
Other Considerations

and optional standby systems should basis of peak demand over a small to the comments made under
be installed in such a manner that they interval. As a result, a new use for cogeneration as to separation from
will be fully available on loss of normal in-house generating capacity has the utility under fault conditions.
power. It is preferable to isolate these developed. Utilities measure demand
systems as much as possible, even charges on the basis of the maximum Computer Power
though not required by code. demand for electricity in any given Computers require a source of steady,
specific period (typically 15 or 30 constant-voltage, constant-frequency
Where the emergency or standby minutes) during the month. Some utili-
source, such as an engine generator ties have a demand “ratchet clause”
power, with no transients superim-
posed. Such “clean” power is not con-
1
or separate service, has capacity to that will continue demand charges on
supply the entire system, the transfer sistently available from utility sources,
a given peak demand for a full year, and utility power is further degraded
scheme can be either a full-capacity unless a higher peak results in even
automatic transfer switch, or, less by disturbances from the building
higher charges. One large load, com- power distribution system. Power
costly but equally effective, normal ing on at a peak time, can create higher
and emergency main circuit breakers, that is entirely satisfactory for motors,
electric demand charges for a year. Iighting, heating, and other familiar
electrically interlocked such that on
failure of the normal supply the emer- Obviously, reducing the peak demand uses in commercial or industrial build-
gency supply is connected to the load. can result in considerable savings in ings, can in computers cause loss of
However, if the emergency or standby the cost of electrical energy. For those data, output errors, incorrect computa-
source does not have capacity for the installations with engine generators tions, and even sudden computer
full load, as is usually the case, such a for emergency use, modern control shutdowns, or “crashes.” These
scheme would require automatic dis- systems (computers or programmable computer problems can be extremely
connection of the nonessential loads controllers) can monitor the peak costly, and correction can be very time
before transfer. Simpler and more eco- demand, and start the engine-generator consuming. For these reasons, raw
nomical in such a case is a separate to supply part of the demand as it incoming power is seldom used for
emergency bus, supplied through an approaches a preset peak value. The critical computer installations. Power
automatic transfer switch, to feed all engine-generator must be selected to the computers is conditioned to
critical loads. The transfer switch con- to withstand the required duty cycle. make it more satisfactory. The type
nects this bus to the normal supply, The simplest of these schemes trans- and degree of conditioning depends
in normal operation. On failure of the fer specific loads to the generator. on the types of power disturbances
normal supply, the engine-generator More complex schemes operate the present, the sensitivity of the com-
is started, and when it is up to speed generator in parallel with the normal puter installation, the cost of computer
the automatic switch transfers the utility supply. The savings in demand errors and interruptions, and the cost
emergency loads to this source. On charges can reduce the cost of owning of power improvement equipment.
return of the normal source, manual the emergency generator equipment. There are several categories of power
or automatic retransfer of the emer- disturbances. One of the most com-
gency loads can take place. In some instances, utilities with little
reserve capacity have helped finance mon is the transient, a sudden, rapid
the cost of some larger customer- rise (or dip) in voltage, either singly or
Peak Shaving as a damped oscillation, A single spike
owned generating equipment. In
Many installations now have emer- return, the customer agrees to take can be as brief as a few microseconds;
gency or standby generators. In the some or all of his load off the utility oscillatory transients may have a fre-
past, they were required for hospitals system and on to his own generator at quency of several hundred to several
and similar locations, but not common the request of the utility (with varying thousand kilohertz, lasting up to a full
in office buildings or shopping centers. limitations) when the utility load cycle. Transients can reach a peak sev-
However, many costly and unfortunate approaches capacity. In some cases, eral times the system voltage. Also
experiences during utility blackouts in the customer’s generator is paralleled very common are undervoltages,
recent years have led to the more fre- with the utility to help supply the peak where the system voltage sags 10%
quent installation of engine generators utility loads, with the utility buying the or more for a period as short as one
in commercial and institutional supplied power. Some utilities have or several cycles to as long as several
systems for safety and for supplying been able to delay large capital expen- hours or more. Much less common
important loads. Industrial plants, ditures for additional generating are overvoltages of 10% or more.
especially in process industries, capacity by such arrangements. Frequency deviations from 60 Hz
usually have some form of alternate are rarely a problem from the power
power source to prevent extremely It is important that the electrical sys- company; they may be a problem
costly shutdowns. These standby tem designer providing a substantial from on-site power generation. Least
generating systems are critical when source of emergency and standby frequent, but most serious when they
needed, but they are needed only power investigate the possibility of occur, are complete power outages,
infrequently. They represent a large using it for peak shaving, and even or blackouts.
capital investment. To be sure that of partial utility company financing.
their power will be available when Frequently, substantial savings in The technology to improve raw power
required, they should be tested power costs can be realized for a falls into two broad categories, power
periodically under load. small additional outlay in distribution enhancement and power synthesis.
and control equipment. Power enhancement takes the incom-
The cost of electric energy has risen to ing power, modifies and improves it by
new high levels in recent years, and Peak shaving equipment operating clipping spike peaks, filtering tran-
utilities bill on the basis not only of in parallel with the utility are subject sients and harmonics, regulating the
power consumed, but also on the voltage, isolating power line “noise,”

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-26 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0084
Other Considerations

and the like. Then the improved power can be located right in or adjacent to At the power source, the building ser-
is delivered to the computer. Power the computer room. The power center vice or the separately derived system
synthesis uses the incoming power consists of a shielded isolating (the computer power center or MG
only as a source of energy, from which transformer, often with 480-volt input set or UPS), the grounded conductor
it creates a new, completely isolated and 208Y/120-volt output as required (neutral) is connected to the grounding
power output waveform to supply to by the computers. This supplies a electrode. The ground bus should be
the computer. This generated or syn- distribution panelboard with circuits connected to the neutral at that point,
thesized output power is designed feeding flexible computer connection and only there, for equipotential
1 to meet computer requirements, cables under the raised computer- grounding. If any other grounding
regardless of the disturbances on room floor. The computer units electrodes are present on the premises,
the input power. plug into these cables. A transient such as for a lightning protection system,
suppressor is often included, and telephone or other communications
Power enhancement can be provided a constant-voltage transformer or systems, cable TV, and the like, they
by transient (spike) suppressors, voltage regulator may be used to must all be bonded to the power sys-
harmonic filters, voltage regulators, eliminate voltage variations. In tem grounding electrodes to make one
isolating transformers (best with a addition to the improvement in the grounding electrode system. Separate
Faraday shield), or a combination of quality of power, the computer power computer grounding electrodes, buried
some or all of these. Power synthesis center has some financial advantages. counterpoises, and similar schemes, may
can be provided by a wide variety Since it is an equipment unit, not part do more harm than good; if they are
of rotating motor-generator (MG) of the permanently installed premises present, they must also be bonded to
sets, static semiconductor rectifier- wiring system, it can be depreciated the power system grounding electrode.
inverters, or ferro-magnetic rapidly (in 5 to 8 years). It can be
synthesizers. Both MG sets and moved to a new location like other This will provide 60 Hz grounding for
rectifier-inverters can be connected computer equipment, making the fre- safety. However, most noise is of much
to a battery, which “floats” when quent rearrangement or relocation of higher frequencies, up to about 30 MHz.
normal power is available, and computer rooms easier and less costly. Ordinary conductors have a high
supplies power to the generator UPS systems are sometimes used impedance at noise frequencies. To
or inverted, with no interruption to supply computer power centers, provide effective noise grounding, an
apparent to the computers, on loss for maximum flexibility. additional high-frequency grounding
of normal power. This comprises the system must supplement the 60 Hz
so-called uninterruptible power supply Computer Grounding system. This requires conductors in a
(UPS), which, on loss of normal power, Because computers are so sensitive grid or mesh with sides of each square
continues power to the computer to electrical “noise” input, computer no more than 2 feet (609.6 mm) long.
while the batteries last. Typical battery grounding is extremely important. This signal reference grid can best be
time ranges from 5 minutes to 1 hour, Some computer suppliers, familiar formed by the raised floor stringers,
with 15 to 30 minutes most common. with the electronic needs of their if they are bolted to the pedestals to
Battery supplies are costly, so for most equipment but not with power sys- form good electrical connections. It
critical operations the UPS is further tems, have recommended computer can also be made of thin copper foil,
supplied by a standby generator, grounding schemes that separate with connections brazed or welded at
which comes on-line before the battery the computer grounding system from the intersections, placed under the
supply runs down and keeps the com- the power grounding system. This raised floor. The individual computer
puters operating as long as necessary. is unsafe, a violation of the National unit cabinets should be connected to
Electrical Code, and absolutely this high-frequency grid by the short-
In general, power enhancement is est possible leads, and the grid itself
less costly than power synthesis, but unnecessary. In fact, it may introduce
electrical noise into the computers, bonded to the ground bus by a single
provides less isolation and protection short connection.
for the computers. If power must be of rather than keep it out. It is possible
the highest quality, and must continue to ground computer systems with Where “isolated ground” plug-in
without interruption even if the normal maximum safety, meeting all NEC receptacles are used, they provide a
power source fails, only some form requirements, and minimizing noise separate grounding connection for
of static or rotary UPS can be used. input to the computers through the plug-and-cord-connected computer
Critical computers, such as used by grounding systems. Each separate equipment. The isolated grounds for
banks, communications systems, unit of computer equipment must be these receptacles should be run with
reservation systems, and the like, grounded (usually by the equipment the supply conductors, back to the
where outages cannot be tolerated, grounding conductor in the power source, and there connected to the
are usually supplied from a UPS cable), back to a common equipoten- common ground bus.
system, which is the most costly tial ground point at the power source
class of power conditioner. to the computers. The ground bus in Standard equipment grounding for
a computer power center is excellent exposed metal must also be provided.
The computer power center is an for this purpose. The computer units This will produce the radial equipoten-
increasingly popular method of should be individually grounded to tial grounding system that results in
supplying power to computers. It this point with radial connections, minimum ground-system noise to the
combines power enhancement, power and not interconnected with many computers, with no sacrifice in safety.
distribution, and equipotential com- grounds that form ground loops.
puter grounding in one unit, which

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.3-27
January 2003 System Application Considerations
Ref. No. 0085
Other Considerations

Sound Levels doubling of the distance from the Since values given in Table 1.3-10
source of sound to the listener. For are in general higher than those given
Sound Levels of Electrical Equipment example, if the level 6 feet (1.8 m) in Table 1.3-9, the difference must be
for Offices, Hospitals, Schools and from a transformer is 50 dB, the level attenuated by distance and by proper
Similar Buildings at a distance of 12 feet (3.7 m) would use of materials in the design of the
Insurance underwriters and building be 44 dB and at 24 feet (7.3 m) the building. An observer may believe that
owners desire and require that the level decreases to 38 dB, etc. However, a transformer is noisy because the
electrical apparatus be installed this rule applies only to equipment level in the room where it is located
for maximum safety and the least in large areas equivalent to an out- is high. Two transformers of the 1
interference with the normal use of of-door installation, with no nearby same sound output in the same
the property. Architects should take reflecting surfaces. room increase the sound level in
particular care with the designs for the room approximately 3 dB, and
Table 1.3-9. Typical Sound Levels three transformers by about 5 dB, etc.
hospitals, schools and similar build-
Description Average
ings to keep the sound perception of Decibel Sounds due to structure-transmitted
such equipment as motors, blowers Level (dB) vibrations originating from the trans-
and transformers to a minimum. former are lowered by mounting the
Radio, Recording and TV Studios 25 – 30
Even though transformers are Theatres and Music Rooms 30 – 35
transformers on vibration dampeners
relatively quiet, resonant conditions Hospitals, Auditoriums and Churches 35 – 40 or isolators. There are a number of
may exist near the equipment which Classrooms and Lecture Rooms 35 – 40
different sound vibration isolating
will amplify their normal 120 Hz Apartments and Hotels 35 – 45 materials which may be used with
hum. Therefore, it is important that Private Offices and Conference Rooms 40 – 45 good results. Dry-type power trans-
consideration be given to the reduc- Stores 45 – 55 formers are often built with an isolator
tion of amplitude and to the absorp- Residence (Radio, TV Off) mounted between the transformer
tion of energy at this frequency.
and Small Offices 53 support and case members. The natu-
Medium Office (3 to 10 Desks) 58 ral period of the core and coil structure
This problem begins in the designing
stages of the equipment and the build-
Residence (Radio, TV On) 60 when mounted on vibration dampen-
Large Store (5 or More Clerks) 61 ers is about 10% of the fundamental
ing. There are two points worthy of Factory Office 61
consideration: 1) What sound levels frequency. The reduction in the trans-
Large Office 64 mitted vibration is approximately 98%.
are desired in the normally occupied Average Factory 70
rooms of this building? 2) To effect Average Street 80
If the floor or beams beneath the trans-
this, what sound level in the equip- former are light and flexible, the isola-
ment room and what type of associ- Transformer Sound Levels tor must be softer or have improved
ated acoustical treatment will give the characteristics in order to keep the
Transformers emit a continuous 120 Hz transmitted vibrations to a minimum.
most economical installation overall? hum with harmonics when connected (Enclosure covers and ventilating lou-
A relatively high sound level in the to 60 Hz circuits. The fundamental vers are often improperly tightened
equipment room does not indicate frequency is the “hum” which annoys or gasketed and produce unnecessary
an abnormal condition within the people primarily because of its contin- noise). The building structure will
apparatus. However, absorption may uous nature. For purposes of reference, assist the dampeners if the trans-
be necessary if sound originating in sound measuring instruments convert former is mounted above heavy floor
an unoccupied equipment room is the different frequencies to 1000 Hz members or if mounted on a heavy
objectionable outside the room. and a 40 dB level. Transformer sound floor slab. Positioning of the trans-
Furthermore, added absorption levels based on NEMA publication TR-1 former in relation to walls and other
material usually is desirable if there is a are listed in Table 1.3-10. reflecting surfaces has a great effect
“build-up” of sound due to reflections. Table 1.3-10. Maximum Average Sound on reflected noise and resonances.
Levels — Decibels Often, placing the transformer at an
Some reduction or attenuation takes angle to the wall, rather than parallel
place through building walls, the kVA Liquid-Filled Dry-Type
Transformers Transformers to it, will reduce noise. Electrical con-
remainder may be reflected in various nections to a substation transformer
directions, resulting in a build-up or Self- Forced- Self- Forced-
Cooled Air Cooled Air should be made with flexible braid
apparent higher levels, especially if or conductors; connections to an
Rating Cooled Rating Cooled
resonance occurs because of room (OA) Rating (AA) Rating individually mounted transformer
dimensions or material characteristics. (FA) (FA) should be in flexible conduit.
Area Consideration 300 55 — 58 67
In determining permissible sound lev- 500 56 67 60 67
750 58 67 64 67
els within a building, it is necessary to
consider how the rooms are to be used 1000 58 67 64 67
1500 60 67 65 68
and what levels may be objectionable 2000 61 67 66 69
to occupants of the building. The
2500 62 67 68 71
ambient sound level values given in 3000 63 67 68 71
Table 1.3-9 are representative average 3750 64 67 70 73
values and may be used as a guide in 5000 65 67 71 73
determining suitable building levels. 6000 66 68 72 74
7500 67 69 73 75
Decrease in sound level varies at an
approximate rate of 6 decibels for each 10,000 68 70 — 76

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.3-28 Power Distribution Systems
System Application Considerations January 2003
Ref. No. 0086

This page intentionally left blank.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-1
January 2003 Reference Data
Ref. No. 0087
IEEE Protective Relay Numbers

Table 1.4-1. Select IEEE Device Numbers for Switchgear Apparatus


Device Function Definition Typical
Number Uses

2 Time-delay starting or closing relay A device which functions to give a desired amount Used for providing a time-delay for
of time delay before or after any point of operation re-transfer back to the normal source
in a switching sequence or protective relay system, in an automatic transfer scheme.
except as specifically provided by device functions
48, 62 and 79 described later.
19 Starting to running transition timer A device which operates to initiate or cause the Used to transfer a reduced voltage
1
automatic transfer of a machine from the starting starter from starting to running.
to the running power connection.
21 Distance relay A device which functions when the circuit —
admittance, impedance or reactance increases or
decreases beyond predetermined limits.
23 Temperature control device A device which functions to raise or to lower the Used as a thermostat to control
temperature of a machine or other apparatus, or space heaters in outdoor equipment.
of any medium, when its temperature falls below
or rises above, a predetermined level.
25 Synchronizing or synchronism check device A device which operates when two AC circuits are In a closed transition breaker
within the desired limits of frequency, phase angle transfer, a 25 relay is used to ensure
or voltage, to permit or cause the paralleling of two-sources are synchronized before
these two circuits. paralleling. Cutler-Hammer FP-5000
feeder protective relay.
27 Undervoltage relay A device which functions on a given value of Used to initiate an automatic transfer
undervoltage. when a primary source of power
is lost. Cutler-Hammer FP-5000
feeder protective relay.
30 Annunciator relay A non-automatically reset device that gives a Used to remotely indicate that a
number of separate visual indications upon the protective relay has functioned, or
functioning of protective devices, and which may that a circuit breaker has tripped.
also be arranged to perform a lockout function. Typically, a mechanical “drop” type
annunciator panel is used.
32 Directional power relay A relay which functions on a desired value of power Used to prevent reverse power
flow in a given direction, or upon reverse power from feeding an upstream fault.
resulting from arc back in the anode or cathode Often used when primary backup
circuits of a power rectifier. generation is utilized in a facility.
Cutler-Hammer FP-5000 feeder
protective relay.
33 Position switch A device which makes or breaks contact when the Used to indicate the position of a
main device or piece of apparatus, which has no drawout circuit breaker (TOC switch).
device function number, reaches a given point.
37 Undercurrent or underpower relay A relay which functions when the current or power Cutler-Hammer MP-3000 motor
flow decreases below a predetermined value. protective relay.
38 Bearing protective device A device which functions on excessive bearing Cutler-Hammer MP-3000 motor
temperature, or on other abnormal mechanical protective relay.
conditions, such as undue wear, which may
eventually result in excessive bearing temperature.
41 Field circuit breaker A device which functions to apply, or to remove, —
the field excitation of a machine.
46 Reverse-phase, or phase balance, current relay A relay which functions when the polyphase Cutler-Hammer FP-5000 feeder
currents are of reverse-phase sequence, or when protective relay and MP-3000
the polyphase currents are unbalanced or contain motor protective relay.
the negative phase-sequence components above
a given amount.
47 Phase-sequence voltage relay A relay which functions upon a predetermined Cutler-Hammer FP-5000 feeder
value of polyphase voltage in the desired phase protective relay.
sequence.
48 Incomplete sequence relay A relay that generally returns the equipment to the —
normal, or off, position and locks it out of the
normal starting, or operating or stopping sequence
is not properly completed within a predetermined
amount of time. If the device is used for alarm
purposes only, it should preferably be designated
as 48A (alarm).
49 Machine, or transformer, thermal relay A relay that functions when the temperature of a Cutler-Hammer MP-3000 motor
machine armature, or other load carrying winding protective relay.
or element of a machine, or the temperature
of a power rectifier or power transformer
(including a power rectifier transformer) exceeds
a predetermined value.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-2 Power Distribution Systems
Reference Data January 2003
Ref. No. 0088
IEEE Protective Relay Numbers

Table 1.4-1. Select IEEE Device Numbers for Switchgear Apparatus (Continued)
Device Function Definition Typical
Number Uses

50 Instantaneous overcurrent, or rate-of-rise relay A relay that functions instantaneously on an Used for tripping a circuit breaker
excessive value of current, or an excessive rate of instantaneously during a high level
current rise, thus indicating a fault in the apparatus short circuit. Can trip on phase-
of the circuit being protected. phase (50), phase-neutral (50N),
phase-ground (50G) faults.
1 Cutler-Hammer Digitrip 3000,
FP-5000 protective relays, MP-3000
motor protective relays.
51 AC time overcurrent relay A relay with either a definite or inverse time Used for tripping a circuit breaker
characteristic that functions when the current in an after a time delay during a sustained
AC circuit exceeds a predetermined value. overcurrent. Used for tripping a
circuit breaker instantaneously
during a high level short circuit .
Can trip on phase (51), neutral (51N)
or ground (51G) overcurrents.
Cutler-Hammer Digitrip 3000,
FP-5000 protective relays, MP-3000
motor protective relays.
52 AC circuit breaker A device that is used to close and interrupt an A term applied typically to medium
AC power circuit under normal conditions or to voltage circuit breakers, or low
interrupt this circuit under fault or emergency voltage power circuit breakers.
conditions. Cutler-Hammer VCP-W Vacuum
Circuit Breaker, Magnum DS
Low Voltage Power Circuit Breaker
55 Power factor relay A relay that operates when the power factor Cutler-Hammer FP-5000 feeder
in an AC circuit rises above or below a protective relay.
predetermined value.
59 Overvoltage relay A relay that functions on a given value of Used to trip a circuit breaker,
overvoltage. protecting downstream equipment
from sustained overvoltages.
Cutler-Hammer FP-5000 feeder
protective relay.
60 Voltage or current balance relay A relay that operates on a given difference in —
voltage, or current input or output of two circuits.
62 Time-delay stopping or opening relay A time-delay relay that serves in conjunction with Used in conjunction with a 27 device
the device that initiates the shutdown, stopping, to delay tripping of a circuit breaker
or opening operation in an automatic sequence. during a brief loss of primary voltage,
to prevent nuisance tripping.
63 Pressure switch A switch which operates on given values or on a Used to protect a transformer during
given rate of change of pressure. a rapid pressure rise during a short
circuit. This device will typically act
to open the protective devices above
and below the transformer. Typically
used with a 63-X auxiliary relay to
trip the circuit breaker.
64 Ground protective relay A relay that functions on a failure of the insulation Used to detect and act on a ground-
of a machine, transformer, or of other apparatus to fault condition. In a pulsing high
ground, or on flashover of a DC machine to ground. resistance grounding system, a 64
device will initiate the alarm.
66 Notching or jogging device A device that functions to allow only a specified Cutler-Hammer MP-3000 motor
number of operations of a given device, or protective relay.
equipment, or a specified number of successive
operations within a given time of each other. It also
functions to energize a circuit periodically or for
fractions of specified time intervals, or that is used
to permit intermittent acceleration or jogging of a
machine at low speeds for mechanical positioning.
67 AC directional overcurrent relay A relay that functions on a desired value of AC —
overcurrent flowing in a predetermined direction.
69 Permissive control device A device that is generally a two-position manually Used as a remote-local switch for
operated switch that in one position permits the circuit breaker control.
closing of a circuit breaker, or the placing of
equipment into operation, and in the other position
prevents the circuit breaker to the equipment from
being operated.
74 Alarm relay A device other than an annunciator, as covered —
under device number 30, which is used to operate,
or to operate in connection with, a visible or
audible alarm.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-3
January 2003 Reference Data
Ref. No. 0089
IEEE Protective Relay Numbers

Table 1.4-1. Select IEEE Device Numbers for Switchgear Apparatus (Continued)
Device Function Definition Typical
Number Uses

79 AC reclosing relay A relay that controls the automatic closing and Used to automatically reclose a
locking out of an AC circuit interrupter. circuit breaker after a trip, assuming
the fault has been cleared after the
power was removed from the circuit.
The recloser will lock-out after a
predetermined amount of failed 1
attempts to reclose. Cutler-Hammer
FP-5000 feeder protective relay.
81 Frequency relay A relay that functions on a predetermined value of Used to trip a generator circuit
frequency — either under or over or on normal breaker in the event the frequency
system frequency — or rate of change frequency. drifts above or below a given value.
Cutler-Hammer FP-5000 feeder
protective relay motor protective
relay.
83 Automatic selective control or transfer relay A relay that operates to select automatically Used to transfer control power
between certain sources or conditions in sources in a double-ended
equipment, or performs a transfer operation switchgear lineup.
automatically.
86 Locking-out relay An electrically operated hand, or electrically, reset Used in conjunction with protective
relay that functions to shut down and hold an relays to lock-out a circuit breaker
equipment out of service on the occurrence of (or multiple circuit breakers) after
abnormal conditions. a trip. Typically required to be
manually reset by an operator before
the breaker can be reclosed.
87 Differential protective relay A protective relay that functions on a percentage or Used to protect static equipment,
phase angle or other quantitative difference of two such as cable, bus or transformers,
currents or of some other electrical quantities. by measuring the current differential
between two points. Typically the
upstream and/or downstream circuit
breaker will be incorporated into the
“zone of protection.” Cutler-Hammer
FP-5000 feeder protective relay (87B).
94 Tripping or trip-free relay A relay that functions to trip a circuit breaker, —
contactor, or equipment, or to permit immediate
tripping by other devices, or to prevent immediate
reclosure of a circuit interrupter, in case it should
open automatically even though its closing circuit
is maintained closed.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-4 Power Distribution Systems
Reference Data January 2003
Ref. No. 0090
Codes and Standards

Codes and Standards and the American National Standards Ground Bus
Institute (ANSI). Underwriters Labora- A bus to which the grounds from indi-
The National Electrical Code (NEC), tory (UL) has standards that equip-
NFPA Standard No. 70, is the most vidual pieces of equipment are con-
ment must meet before UL will list or nected and that, in turn, is connected
prevalent electrical code in the United label it. Most jurisdictions and OSHA
States. The NEC, which is revised to ground at one or more points.
require that where equipment listed
every three years, has no legal stand- as safe by a recognized laboratory is Ground Protection
ing of its own, until it is adopted as law available, unlisted equipment may not A method of protection in which faults
1 by a jurisdiction, which may be a city, be used. UL is by far the most widely to ground within the protected equip-
county, or state. Most jurisdictions accepted national laboratory, although
adopt the NEC in its entirety; some ment are detected.
Factory Mutual Insurance Company
adopt it with variations, usually more lists some equipment, and a number Ground Relay
rigid, to suit local conditions and of other testing laboratories have been A relay that by its design or application
requirements. A few large cities, such recognized and accepted. The Institute is intended to respond primarily to
as New York and Chicago, have their of Electrical and Electronic Engineers system ground faults.
own electrical codes, basically similar (IEEE) publishes a number of books
to the NEC. The designer must deter- (the “color book” series) on recom- Interrupting (Breaking) Current
mine which code applies in the area mended practices for the design of The current in a pole of a switching
of a specific project. industrial buildings, commercial build- device at the instant of initiation
The Occupational Safety and Health ings, emergency power systems, of the arc.
Act (OSHA) of 1970 sets uniform grounding, and the like. Most of these
IEEE standards have been adopted as Load-Interrupter Switch
national requirements for safety in the
workplace — anywhere that people are ANSI standards. They are excellent An interrupter switch designed to
employed. Originally OSHA adopted guides, although they are not in any interrupt currents not in excess of the
the 1971 NEC as rules for electrical way mandatory. continuous-current rating of the switch.
safety. As the NEC was amended every A design engineer should conform Note: It may be designed to close and
three years, the involved process for to all applicable codes, and require carry abnormal or short circuit currents
modifying a federal law such as OSHA equipment to be listed by UL or as specified.
made it impossible for the act to adopt another recognized testing laboratory
each new code revision. To avoid this Metal-Enclosed Low Voltage Power
wherever possible, and to meet ANSI
problem, the OSHA administration or NEMA standards. ANSI/IEEE recom- Circuit Breaker Switchgear
in 1981 adopted its own code, a con- mended practices should be followed Metal-enclosed power switchgear
densed version of the NEC containing to a great extent. In many cases, stan- including the following equipment as
only those provisions considered dards should be exceeded to get a required: (1) low voltage power circuit
related to occupational safety. OSHA system of the quality required. The breaker (fused or unfused), (2) bare
was amended to adopt this code, design goal should be a safe, efficient, bus and connections, (3) instrument
based on NFPA Standard 70E, Part 1, long-lasting, flexible, and economical and control power transformers,
which is now federal law. electrical distribution system. (4) instruments, meters, and relays,
The NEC, Article 90, Introduction, and (5) control wiring and accessory
Excerpts From ANSI/IEEE C37.100 Definitions devices. The low voltage power circuit
reads: 90-1.
for Power Switchgear breakers are contained in individual
(a) The purpose of this Code is the grounded metal compartments and
practical safeguarding of persons Available (Prospective) Short Circuit Current controlled remotely or from the front
and property from hazards arising The maximum current that the power of the panels. The circuit breakers may
from the use of electricity. system can deliver through a given cir- be stationary or removable. When
cuit point to any negligible impedance removable, mechanical interlocks
(b) This Code contains provisions con- short circuit applied at the given point. are provided to ensure a proper,
sidered necessary to safety. Compliance safe operating sequence.
therewith and proper maintenance will Basic Impulse Insulation Level (BIL)
result in an installation essentially free A reference impulse insulation Molded-Case Circuit Breaker
from hazard, but not necessarily effi- strength expressed in terms of the One that is assembled as an integral
cient, convenient, or adequate for good crest value of the withstand voltage of unit in a supporting and enclosing
service or expansion of electrical use. a standard full impulse voltage wave. housing of molded insulating material.
(c) This Code is not intended as a Direct-Current Component (of a Total Current) Stored-Energy Operation
design specification nor an instruction That portion of the total current which Operation by means of energy stored
manual for untrained persons. constitutes the asymmetry. in the mechanism itself prior to the
The NEC is a minimum safety completion of the operation and
Enclosed Switchboard
standard. Efficient and adequate sufficient to complete it under
design usually requires not just A deadfront switchboard that has an predetermined conditions.
meeting, but often exceeding NEC overall sheet metal enclosure (not
requirements to provide an effective, grille) covering back and ends of the
reliable, economical electrical system. entire assembly.
Note: Access to the enclosure is usually
Many equipment standards have been provided by doors or removable covers.
established by the National Electrical The tops may or may not be covered.
Manufacturers’ Association (NEMA)

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-5
January 2003 Reference Data
Ref. No. 0091
Codes and Standards

Switchboard Professional Organizations


A type of switchgear assembly that
American National Standards Institute National Fire Protection Association
consists of one or more panels with
electric devices mounted thereon, 11 West 42nd Street 1 Battery March Park
and associated framework. New York, New York 10036 P.O. Box 9101
212-642-4900 Quincy, MA 02269-9101
Switchgear 617-770-3000
Institute of Electrical and Electronics
A general term covering switching
and interrupting devices and their
Engineers Underwriters Laboratories 1
combination with associated control, 445 Hoes Lane 333 Pfingsten Road
metering, protective and regulating P.O. Box 1331 Northbrook, IL 60062-2096
devices. Also assemblies of these Piscataway, NJ 08855-1331 847-272-8129
devices with associated interconnec- 732-981-0060
International Conference of Building
tions, accessories, enclosures and International Association of Electrical Officials
supporting structures, used primarily
Inspectors 5360 Workman Mill Road
in connection with the generation,
transmission, distribution and 901 Waterfall Way, Suite 602 Whittier, CA 90601
conversion of electric power. Richardson, TX 75080-7702 800-284-4406
972-235-1455
Zone of Protection
National Electrical Manufacturers
The part of an installation guarded
Association
by a certain protection.
1300 North 17th Street, Suite 1847
Rosslyn, VA 22209
703-841-3200

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-6 Power Distribution Systems
Reference Data January 2003
Ref. No. 0092
Motor Protective Device Data

Motor Protection Table 1.4-2. 60 Hz, Recommended Protective Setting for Induction Motors
Hp Full Minimum Minimum Fuse Size Recommended Cutler-Hammer
Note: These recommendations are based Load Wire Size Conduit Size, NEC 430-152 Circuit Motor Circuit
on previous code interpretations. See the Amps 75°C Copper Inches (mm) Maximum Amps 1 Breaker 2 Protector
current NEC for exact up-to-date information. (NEC) Ampacity at THW THWN Time Non- Type GMCP/HMCP 3
FLA 125% FLA XHHN Delay Time
Size Amps Delay Amps Type Amps Adj. Range
In line with NEC 430-6(a), circuit breaker,
230 Volts, 3-Phase
HMCP and fuse rating selections are based
1 3.6 12 20 .50 (12.7) .50 (12.7) 10 15 15 ED 7 21 – 70
on full load currents for induction motors
1 running at speeds normal for belted
1-1/2
2
5.2
6.8
12
12
20
20
.50 (12.7)
.50 (12.7)
.50 (12.7)
.50 (12.7)
10
15
20
25
15
15
ED
ED
7
15
21 – 70
45 – 150
motors and motors with normal torque 3 9.6 12 20 .50 (12.7) .50 (12.7) 20 30 20 ED 15 45 – 150
characteristics using data shown taken 5 15.2 12 20 .50 (12.7) .50 (12.7) 30 50 30 ED 30 90 – 300
7-1/2 22 10 30 .50 (12.7) .50 (12.7) 40 70 50 ED 30 90 – 300
from NEC Tables 430-148 (single-phase)
10 28 8 50 .75 (19.1) .50 (12.7) 50 90 60 ED 50 150 – 500
and 430-150 (3-phase). Actual motor name- 15 42 6 65 1.00 (25.4) .75 (19.1) 80 150 90 ED 70 210 – 700
plate ratings shall be used for selecting 20 54 4 85 1.00 (25.4) 1.00 (25.4) 100 175 100 ED 100 300 – 1000
motor running overload protection. Motors 25 68 4 85 1.00 (25.4) 1.00 (25.4) 125 225 125 ED 100 300 – 1000
built special for low speeds, high torque 30 80 3 100 1.25 (31.8) 1.00 (25.4) 150 250 150 ED 150 450 – 1500
40 104 1 130 1.25 (31.8) 1.25 (31.8) 200 350 150 ED 150 450 – 1500
characteristics, special starting conditions
50 130 2/0 175 1.50 (38.1) 1.50 (38.1) 250 400 200 ED 150 750 – 2500
and applications will require other consid- 60 154 3/0 200 2.00 (50.8) 1.50 (38.1) 300 500 225 ED 250 1250 – 2500
erations as defined in the application 75 192 250 255 2.50 (63.5) 2.00 (50.8) 350 600 300 KD 400 2000 – 4000
section of the NEC. 100 248 350 310 2.50 (63.5) 2.50 (63.5) 450 800 400 KD 600 1800 – 6000
125 312 (2)3/0 400 (2)2.00 (50.8) (2)1.50 (38.1) 600 1000 500 LD 600 1800 – 6000
Circuit breaker, HMCP and fuse ampere 150 360 (2)4/0 460 (2)2.00 (50.8) (2)2.00 (50.8) 700 1200 600 LD — —
rating selections are in line with maximum 200 480 (2)350 620 (2)2.50 (63.5) (2)2.50 (63.5) 1000 1600 700 MD — —
rules given in NEC 430-52 and Table 430-152. 460 Volts, 3-Phase
Based on known characteristics of Cutler- 1 1.8 12 20 .50 (12.7) .50 (12.7) 6 6 15 EHD 3 9 – 30
Hammer type breakers, specific units are 1-1/2 2.6 12 20 .50 (12.7) .50 (12.7) 6 10 15 EHD 7 21 – 70
2 3.4 12 20 .50 (12.7) .50 (12.7) 6 15 15 EHD 7 21 – 70
recommended. The current ratings are
3 4.8 12 20 .50 (12.7) .50 (12.7) 10 15 15 EHD 7 21 – 70
no more than the maximum limits set by 5 7.6 12 20 .50 (12.7) .50 (12.7) 15 25 15 EHD 15 45 – 150
the NEC rules for motors with code letters 7-1/2 11 12 20 .50 (12.7) .50 (12.7) 20 35 25 EHD 15 45 – 150
F to V or without code letters. Motors with 10 14 12 20 .50 (12.7) .50 (12.7) 25 45 35 EHD 30 90 – 300
15 21 10 30 .50 (12.7) .50 (12.7) 40 70 45 EHD 30 90 – 300
lower code letters will require further 20 27 8 50 .75 (19.1) .50 (12.7) 50 90 50 EHD 50 150 – 500
considerations. 25 34 8 50 .75 (19.1) .50 (12.7) 60 110 70 EHD 50 150 – 500
In general, these selections were based on: 30 40 8 50 .75 (19.1) .50 (12.7) 70 125 70 EHD 70 210 – 700
40 52 6 65 1.00 (25.4) .75 (19.1) 100 175 100 EHD 100 300 – 1000
1. Ambient — Outside enclosure not 50 65 4 85 1.00 (25.4) 1.00 (25.4) 125 200 110 FDB 100 300 – 1000
more than 40°C (104°F). 60 77 3 100 1.25 (31.8) 1.00 (25.4) 150 250 125 FDB 150 450 – 1500
75 96 1 130 1.25 (31.8) 1.25 (31.8) 175 300 150 JD 150 450 – 1500
2. Motor starting — Infrequent starting, 100 124 2/0 175 1.50 (38.1) 1.50 (38.1) 225 400 175 JD 150 750 – 2500
stopping or reversing. 125 156 3/0 200 2.00 (50.8) 1.50 (38.1) 300 500 225 JD 250 1250 – 2500
150 180 4/0 230 2.00 (50.8) 2.00 (50.8) 350 600 250 JD 250 1250 – 2500
3. Motor accelerating time — 200 240 350 310 2.50 (63.5) 2.50 (63.5) 450 800 350 KD 400 2000 – 4000
10 seconds or less. 575 Volts, 3-Phase
4. Locked rotor — Maximum 6 times 1 1.4 12 20 .50 (12.7) .50 (12.7) 3 6 15 HFD 3 9 – 30
1-1/2 2.1 12 20 .50 (12.7) .50 (12.7) 6 10 15 HFD 3 9 – 30
motor FLA. 2 2.7 12 20 .50 (12.7) .50 (12.7) 6 10 15 HFD 7 21 – 70
5. Type HMCP motor circuit protector 3 3.9 12 20 .50 (12.7) .50 (12.7) 10 15 15 HFD 7 21 – 70
may not be set at more than 1300% of 5 6.1 12 20 .50 (12.7) .50 (12.7) 15 20 15 HFD 15 45 – 150
7-1/2 9 12 20 .50 (12.7) .50 (12.7) 20 30 20 HFD 15 45 – 150
the motor full-load current, to comply
10 11 12 20 .50 (12.7) .50 (12.7) 20 35 25 HFD 15 45 – 150
with the NEC, Section 430-52. (Except 15 17 12 20 .50 (12.7) .50 (12.7) 30 60 40 HFD 30 90 – 300
for new E rated motor which can be 20 22 10 30 .50 (12.7) .50 (12.7) 40 70 50 HFD 50 150 – 500
set up to 1700%.) 25 27 8 50 .50 (12.7) .50 (12.7) 50 90 60 HFD 50 150 – 500
30 32 8 50 .75 (19.1) .50 (12.7) 60 100 60 HFD 50 150 – 500
Circuit breaker selections are based on 40 41 6 65 1.00 (25.4) .75 (19.1) 80 125 80 HFD 70 210 – 700
types with standard interrupting ratings. 50 52 6 65 1.00 (25.4) .75 (19.1) 100 175 100 HFD 100 300 – 1000
Higher interrupting rating types may 60 62 4 85 1.00 (25.4) 1.00 (25.4) 110 200 125 HFD 100 300 – 1000
75 77 3 100 1.25 (31.8) 1.00 (25.4) 150 250 150 HFD 150 450 – 1500
be required to satisfy specific system
100 99 1 130 1.25 (31.8) 1.25 (31.8) 175 300 175 HJD 150 450 – 1500
application requirements. 125 125 2/0 175 1.50 (38.1) 1.50 (38.1) 225 400 200 HJD 250 875 – 1750
Cutler-Hammer type circuit breakers 150 144 3/0 200 2.00 (50.8) 1.50 (38.1) 300 450 225 HJD 250 1250 – 2500
200 192 250 255 2.50 (63.5) 2.00 (50.8) 350 600 300 HKD 400 2000 – 4000
rated less than 125 amperes are marked
115 Volts, Single-Phase
for application with 60/75°C wire. Wire
3/4 13.8 12 20 .50 (12.7) .50 (12.7) 25 45 30 ED Two-Pole Device
size selections shown are minimum 1 16 12 20 .50 (12.7) .50 (12.7) 30 50 35 ED Not Available
sizes based on the use of 75°C copper 1-1/2 20 10 30 .50 (12.7) .50 (12.7) 35 60 40 ED
wire per NEC Table 310-16. 2 24 10 30 .50 (12.7) .50 (12.7) 45 80 50 ED
3 34 8 50 .75 (19.1) .50 (12.7) 60 110 70 ED
Conduit sizes shown are minimum sizes 5 56 4 85 1.00 (25.4) .75 (19.1) 100 175 100 ED
for the type conductors (75°C) indicated 7-1/2 80 3 100 1.00 (25.4) 1.00 (25.4) 150 250 150 ED
and are based on the use of three conduc- 230 Volts, Single-Phase
tors for 3-phase motors and two conduc- 3/4 6.9 12 20 .50 (12.7) .50 (12.7) 15 25 15 ED Two-Pole Device
tors for single-phase motors. Conduits 1 8 12 20 .50 (12.7) .50 (12.7) 15 25 20 ED Not Available
1-1/2 10 12 20 .50 (12.7) .50 (12.7) 20 30 25 ED
with internal equipment grounding con-
2 12 12 20 .50 (12.7) .50 (12.7) 25 40 30 ED
ductors or conductors with different insu- 3 17 10 30 .50 (12.7) .50 (12.7) 30 60 40 ED
lation will require further considerations. 5 28 8 50 .50 (12.7) .50 (12.7) 50 90 60 ED
7-1/2 40 8 50 .75 (19.1) .50 (12.7) 70 125 80 ED
For motor full load currents of 208 and 200 1
volts, increase the corresponding 230-volt Consult fuse manufacturer’s catalog for smaller fuse ratings.
2 Types are for minimum interrupting capacity breakers. Ensure that the fault duty does not exceed
motor values by 10 and 15% respectively.
breaker’s I.C.
Wire and conduit sizes as well as equip- 3
ment ratings will vary accordingly. For specific motor circuit protector selection for a given motor inrush, see tables in Section 29.4.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-7
January 2003 Reference Data
Ref. No. 0093
Chart of Short Circuit Currents for Transformers

Table 1.4-3. Secondary Short Circuit Current of Typical Power Transformers


Trans- Maximum 208 Volts, 3-Phase 240 Volts, 3-Phase 480 Volts, 3-Phase 600 Volts, 3-Phase
former Short Rated Short Circuit Current Rated Short Circuit Current Rated Short Circuit Current Rated Short Circuit Current
Rating Circuit Load rms Symmetrical Amps Load rms Symmetrical Amps Load rms Symmetrical Amps Load rms Symmetrical Amps
3-Phase kVA Contin- Contin- Contin- Contin-
kVA and Available Trans- 50% Com- Trans- 100% Com- Trans- 100% Com- Trans- 100% Com-
uous former Motor bined uous former Motor bined uous former Motor bined uous former Motor bined
Impedance from Current, Current, Current, Current,
Percent Primary Alone Load Alone Load 2 Alone 1 Load 2 Alone 1 Load 2
Amps 1 2 Amps 1 Amps Amps
System

300 50,000 834 14,900 1700 16,600 722 12,900 2900 15,800 361 6400 1400 7800 289 5200 1200 6400
1
5% 100,000 834 15,700 1700 17,400 722 13,600 2900 16,500 361 6800 1400 8200 289 5500 1200 6700
150,000 834 16,000 1700 17,700 722 13,900 2900 16,800 361 6900 1400 8300 289 5600 1200 6800
250,000 834 16,300 1700 18,000 722 14,100 2900 17,000 361 7000 1400 8400 289 5600 1200 6800
500,000 834 16,500 1700 18,200 722 14,300 2900 17,200 361 7100 1400 8500 289 5700 1200 6900
Unlimited 834 16,700 1700 18,400 722 14,400 2900 17,300 361 7200 1400 8600 289 5800 1200 7000
500 50,000 1388 21,300 2800 25,900 1203 20,000 4800 24,800 601 10,000 2400 12,400 481 8000 1900 9900
5% 100,000 1388 25,200 2800 28,000 1203 21,900 4800 26,700 601 10,900 2400 13,300 481 8700 1900 10,600
150,000 1388 26,000 2800 28,800 1203 22,500 4800 27,300 601 11,300 2400 13,700 481 9000 1900 10,900
250,000 1388 26,700 2800 29,500 1203 23,100 4800 27,900 601 11,600 2400 14,000 481 9300 1900 11,200
500,000 1388 27,200 2800 30,000 1203 23,600 4800 28,400 601 11,800 2400 14,200 481 9400 1900 11,300
Unlimited 1388 27,800 2800 30,600 1203 24,100 4800 28,900 601 12,000 2400 14,400 481 9600 1900 11,500
750 50,000 2080 28,700 4200 32,900 1804 24,900 7200 32,100 902 12,400 3600 16,000 722 10,000 2900 12,900
5.75% 100,000 2080 32,000 4200 36,200 1804 27,800 7200 35,000 902 13,900 3600 17,500 722 11,100 2900 14,000
150,000 2080 33,300 4200 37,500 1804 28,900 7200 36,100 902 14,400 3600 18,000 722 11,600 2900 14,500
250,000 2080 34,400 4200 38,600 1804 29,800 7200 37,000 902 14,900 3600 18,500 722 11,900 2900 14,800
500,000 2080 35,200 4200 39,400 1804 30,600 7200 37,800 902 15,300 3600 18,900 722 12,200 2900 15,100
Unlimited 2080 36,200 4200 40,400 1804 31,400 7200 38,600 902 15,700 3600 19,300 722 12,600 2900 15,500
1000 50,000 2776 35,900 5600 41,500 2406 31,000 9800 40,600 1203 15,500 4800 20,300 962 12,400 3900 16,300
5.75% 100,000 2776 41,200 5600 46,800 2406 35,600 9800 45,200 1203 17,800 4800 22,600 962 14,300 3900 18,200
150,000 2776 43,300 5600 48,900 2406 37,500 9800 47,100 1203 18,700 4800 23,500 962 15,000 3900 18,900
250,000 2776 45,200 5600 50,800 2406 39,100 9800 48,700 1203 19,600 4800 24,400 962 15,600 3900 19,500
500,000 2776 46,700 5600 52,300 2406 40,400 9800 50,000 1203 20,200 4800 25,000 962 16,200 3900 20,100
Unlimited 2776 48,300 5600 53,900 2406 41,800 9800 51,400 1203 20,900 4800 25,700 962 16,700 3900 20,600
1500 50,000 4164 47,600 8300 55,900 3609 41,200 14,400 55,600 1804 20,600 7200 27,800 1444 16,500 5800 22,300
5.75% 100,000 4164 57,500 8300 65,800 3609 49,800 14,400 64,200 1804 24,900 7200 32,100 1444 20,000 5800 25,800
150,000 4164 61,800 8300 70,100 3609 53,500 14,400 57,900 1804 26,700 7200 33,900 1444 21,400 5800 27,200
250,000 4164 65,600 8300 73,900 3609 56,800 14,400 71,200 1804 28,400 7200 35,600 1444 22,700 5800 28,500
500,000 4164 68,800 8300 77,100 3609 59,600 14,400 74,000 1804 29,800 7200 37,000 1444 23,900 5800 29,700
Unlimited 4164 72,500 8300 80,800 3609 62,800 14,400 77,200 1804 31,400 7200 38,600 1444 25,100 5800 30,900
2000 50,000 — — — — — — — — 2406 24,700 9600 34,300 1924 19,700 7800 27,500
5.75% 100,000 — — — — — — — — 2406 31,000 9600 40,600 1924 24,800 7800 32,600
150,000 — — — — — — — — 2406 34,000 9600 43,600 1924 27,200 7800 35,000
250,000 — — — — — — — — 2406 36,700 9600 46,300 1924 29,400 7800 37,200
500,000 — — — — — — — — 2406 39,100 9600 48,700 1924 31,300 7800 39,100
Unlimited — — — — — — — — 2406 41,800 9600 51,400 1924 33,500 7800 41,300
2500 50,000 — — — — — — — — 3008 28,000 12,000 40,000 2405 22,400 9600 32,000
5.75% 100,000 — — — — — — — — 3008 36,500 12,000 48,500 2405 29,200 9600 38,800
150,000 — — — — — — — — 3008 40,500 12,000 52,500 2405 32,400 9600 42,000
250,000 — — — — — — — — 3008 44,600 12,000 56,600 2405 35,600 9600 45,200
500,000 — — — — — — — — 3008 48,100 12,000 60,100 2405 38,500 9600 48,100
Unlimited — — — — — — — — 3008 52,300 12,000 64,300 2405 41,800 9600 51,400
3000 50,000 — — — — — — — — 3609 30,700 14,000 44,700 2886 24,600 11,500 36,100
5.75% 100,000 — — — — — — — — 3609 41,200 14,000 55,200 2886 33,000 11,500 44,500
150,000 — — — — — — — — 3609 46,600 14,000 60,600 2886 37,300 11,500 48,800
250,000 — — — — — — — — 3609 51,900 14,000 65,900 2886 41,500 11,500 53,000
500,000 — — — — — — — — 3609 56,800 14,000 70,800 2886 45,500 11,500 57,000
Unlimited — — — — — — — — 3609 62,800 14,000 76,800 2886 50,200 11,500 61,700
3750 50,000 — — — — — — — — 4511 34,000 18,000 52,000 3608 27,200 14,400 41,600
5.75% 100,000 — — — — — — — — 4511 47,500 18,000 65,500 3608 38,000 14,400 52,400
150,000 — — — — — — — — 4511 54,700 18,000 72,700 3608 43,700 14,400 58,100
250,000 — — — — — — — — 4511 62,200 18,000 80,200 3608 49,800 14,400 64,200
500,000 — — — — — — — — 4511 69,400 18,000 87,400 3608 55,500 14,400 69,900
Unlimited — — — — — — — — 4511 78,500 18,000 96,500 3608 62,800 14,400 77,200
1 Short circuit capacity values shown correspond to kVA and impedances shown in this table. For impedances other than these, short circuit currents are
inversely proportional to impedance.
2 The motor’s short circuit current contributions are computed on the basis of motor characteristics that will give four times normal current. For 208
volts, 50% motor load is assumed while for other voltages 100% motor load is assumed. For other percentages, the motor short circuit current will be
in direct proportion.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-8 Power Distribution Systems
Reference Data January 2003
Ref. No. 0094
Transformer Full Load Amperes and Impedances

Table 1.4-4. Transformer Full-Load Current, 3-phase, Self-Cooled Ratings


Voltage, Line-to-Line
kVA 208 240 480 600 2,400 4,160 7,200 12,000 12,470 13,200 13,800 22,900 34,400

30 83.3 72.2 36.1 28.9 7.22 4.16 2.41 1.44 1.39 1.31 1.26 0.75 0.50
45 125 108 54.1 43.3 10.8 6.25 3.61 2.17 2.08 1.97 1.88 1.13 0.76
75 208 180 90.2 72.2 18.0 10.4 6.01 3.61 3.47 3.28 3.14 1.89 1.26
112-1/2 312 271 135 108 27.1 15.6 9.02 5.41 5.21 4.92 4.71 2.84 1.89
1 150 416 361 180 144 36.1 20.8 12.0 7.22 6.94 6.56 6.28 3.78 2.52
225 625 541 271 217 54.1 31.2 18.0 10.8 10.4 9.84 9.41 5.67 3.78
300 833 722 361 289 72.2 41.6 24.1 14.4 13.9 13.1 12.6 7.56 5.04
500 1388 1203 601 481 120 69.4 40.1 24.1 23.1 21.9 20.9 12.6 8.39
750 2082 1804 902 722 180 104 60.1 36.1 34.7 32.8 31.4 18.9 12.6
1000 2776 2406 1203 962 241 139 80.2 48.1 46.3 43.7 41.8 25.2 16.8
1500 4164 3608 1804 1443 361 208 120 72.2 69.4 65.6 62.8 37.8 25.2
2000 — 4811 2406 1925 481 278 160 96.2 92.6 87.5 83.7 50.4 33.6
2500 — — 3007 2406 601 347 200 120 116 109 105 63.0 42.0
3000 — — 3609 2887 722 416 241 144 139 131 126 75.6 50.4
3750 — — 4511 3608 902 520 301 180 174 164 157 94.5 62.9
5000 — — — 4811 1203 694 401 241 231 219 209 126 83.9
7500 — — — — 1804 1041 601 361 347 328 314 189 126
10,000 — — — — 2406 1388 802 481 463 437 418 252 168

Approximate Impedance Data


Table 1.4-5. Typical Impedances — Table 1.4-6. 15 kV Class Primary — Table 1.4-8. 600-Volt Primary Class
3-phase Transformers 1 Oil Liquid-Filled Substation Transformers Dry-Type Distribution Transformers
kVA Liquid-Filled kVA %Z %R %X X/R kVA %Z %R %X X/R
Network Padmount 65°C Rise 150°C Rise
112.5 5.00 1.71 4.70 2.75 3 7.93 6.60 4.40 0.67
37.5 — —
150 5.00 1.88 4.63 2.47 6 3.70 3.28 1.71 0.52
45 — —
225 5.00 1.84 4.65 2.52 9 3.42 1.94 2.81 1.45
50 — —
300 5.00 1.35 4.81 3.57 15 5.20 4.83 1.92 0.40
75 — 3.4
500 5.00 1.50 4.77 3.18 30 5.60 4.67 3.10 0.66
112.5 — 3.2
750 5.75 1.41 5.57 3.96 45 4.50 3.56 2.76 0.78
150 — 2.4
1000 5.75 1.33 5.59 4.21 75 4.90 3.47 3.46 1.00
225 — 3.3
1500 5.75 1.12 5.64 5.04 112.5 5.90 3.91 4.42 1.13
300 5.00 3.4
2000 5.75 0.93 5.67 6.10 150 6.20 4.07 4.68 1.15
500 5.00 4.6
2500 5.75 0.86 5.69 6.61 225 6.40 3.51 5.35 1.52
750 5.00 5.75
300 7.10 3.13 6.37 2.03
1000 5.00 5.75
Table 1.4-7. 15 kV Class Primary — 500 5.50 1.46 5.30 3.63
1500 7.00 5.75
2000 7.00 5.75 Dry-Type Substation Transformers 750 6.30 1.27 6.17 4.87
1000 6.50 1.08 6.41 5.93
2500 7.00 5.75 kVA %Z %R %X X/R
3000 — 6.50 115°C Rise
150°C Rise
3750 — 6.50 15 5.20 3.67 3.69 1.01
300 4.50 2.87 3.47 1.21
5000 — 6.50 30 4.60 4.33 1.54 0.36
500 5.75 2.66 5.10 1.92
1 45 3.70 3.11 2.00 0.64
Values are typical. For guaranteed values, 750 5.75 2.47 5.19 2.11
refer to transformer manufacturer. 75 4.60 2.53 3.84 1.52
1000 5.75 2.16 5.33 2.47 112.5 6.50 2.31 6.08 2.63
1500 5.75 1.87 5.44 2.90 150 6.20 3.53 5.09 1.44
2000 5.75 1.93 5.42 2.81
225 7.20 2.36 6.80 2.89
2500 5.75 1.74 5.48 3.15 300 6.30 1.93 6.00 3.10
80°C Rise 500 5.50 1.02 5.40 5.30
300 4.50 1.93 4.06 2.10 750 4.10 1.00 3.98 3.98
500 5.75 1.44 5.57 3.87 80°C Rise
750 5.75 1.28 5.61 4.38
15 2.30 2.00 1.14 0.57
1000 5.75 0.93 5.67 6.10
30 2.90 2.25 1.83 0.81
1500 5.75 0.87 5.68 6.51
45 2.90 1.78 2.29 1.29
2000 5.75 0.66 5.71 8.72
75 3.70 2.07 3.07 1.49
2500 5.75 0.56 5.72 10.22
112.5 4.30 2.49 3.51 1.41
150 4.10 1.70 3.73 2.19
225 5.30 1.42 5.11 3.59
300 3.30 1.00 3.14 3.14
500 4.50 0.62 4.46 7.19

Note: K factor rated distribution dry-type


transformers may have significantly lower
impedances.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-9
January 2003 Reference Data
Ref. No. 0095
Transformer Losses

Approximate Transformer Loss Data The 35% loading value in the NEMA stan-
dard reflects field studies which show that
Table 1.4-9. 15 kV Class Primary — Table 1.4-11. 600-Volt Primary Class installed dry-type transformers are actually
Oil Liquid-Filled Substation Transformers Dry-Type Distribution Transformers loaded far below base kVA most of the time.
kVA No Load Full Load kVA No Load Full Load
Watts Loss Watts Loss Watts Loss Watts Loss Transformer Losses at Reduced Loads
65°C Rise 150°C Rise Information on losses based on actual
112.5 550 2470 3 33 231 transformer test data can be obtained
150 545 3360 6 58 255 from the manufacturer. Transformer 1
225 650 4800 9 77 252 manufacturers provide no load watt
300 950 5000 15 150 875 losses and total watt losses in accor-
500 1200 8700 30 200 1600 dance with ANSI standards. The
750 1600 12,160 45 300 1900 calculated difference between the
1000 1800 15,100 75 400 3000 no load losses and the total losses
1500 3000 19,800 112.5 500 4900 are typically described as the load
2000 4000 22,600 150 600 6700
losses. Although transformer coils
2500 4500 26,000 225 700 8600 are manufactured with either aluminum
300 800 10,200
500 1700 9000
or copper conductors, the industry
Table 1.4-10. 15 kV Class Primary — has sometimes referred to these load
Dry-Type Substation Transformers 750 2200 11,700
losses as the “copper losses.”
1000 2800 13,600
kVA No Load Full Load
Watts Loss Watts Loss 115°C Rise Transformer losses for various loading
150°C Rise 15 150 700 can be estimated in the following
30 200 1500 manner. The no load watt losses of the
300 1600 10,200 45 300 1700 transformer are due to magnetization
500 1900 15,200
750 2700 21,200 75 400 2300 and are present whenever the trans-
112.5 500 3100 former is energized. The load watt
1000 3400 25,000 150 600 5900
1500 4500 32,600 losses are the difference between the
2000 5700 44,200 225 700 6000 no load watt losses and the full load
300 800 6600 watt losses. The load watt losses are
2500 7300 50,800 500 1700 6800
80°C Rise proportional to I2R and can be esti-
750 1500 9000 mated to vary with the transformer
300 1800 7600 80°C Rise
500 2300 9500
load by the square of the load current.
750 3400 13,000 15 200 500
30 300 975 For example, the approximate watts
1000 4200 13,500 loss data for a 1000 kVA oil-filled
45 300 1100
1500 5900 19,000
2000 6900 20,000 75 400 1950 substation transformer is shown in
112.5 600 3400 the table as having 1,800 watts no
2500 7200 21,200
150 700 3250 load losses and 15,100 watts full load
225 800 4000 losses, so the load losses are approxi-
300 1300 4300 mately 13,300 watts (15,100 – 1,800).
500 2200 5300 The transformer losses can be calcu-
lated for various loads as follows.
Table 1.4-12. 600-Volt Primary Class
Dry-Type Distribution Transformers — At 0% load:
NEMA TP- 1 Standard 1,800 watts
kVA No Load Full Load TP-1%
Losses in Losses in Efficiency At 50% load:
Watts Watts at 75ºC 1,800 watts + (13,300)(.5)2 =
and 35% 1,800 watts + 3,325 watts = 5,125 watts
Load
N.L. Total Minimum At 100% load:
Required 1,800 watts + 13,300 watts = 15,100 watts
15 80 822 97 At 110% load:
30 100 1674 97.5
45 170 1885 97.7 1,800 watts + (13,300)(1.1)2 =
75 230 2534 98 1,800 watts + 16,093 watts = 17,893 watts
112.5 360 3290 98.2
150 480 3552 98.3
Since transformer losses vary between
designs and manufacturers, additional
225 565 6783 98.5
300 730 7477 98.6
losses such as from cooling fans can
500 1350 8031 98.7 be ignored for these approximations.
Note: 1 watt hour = 3.413 Btu.
Note: Loss and efficiency data shown are
based on transformers that meet NEMA
optional standard TP-1 for energy savings.
NEMA TP-1 establishes maximum allowed
losses and minimum operating efficiencies
for each transformer size at reduced loading
equal to 35% of the transformer base kVA.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-10 Power Distribution Systems
Reference Data January 2003
Ref. No. 0096
Power Equipment Losses and Enclosures/Knockout Dimensions

Power Equipment Losses Enclosures


Table 1.4-13. Power Equipment Losses The following are reproduced from NEMA 250.
Equipment Watts
Table 1.4-14. Comparison of Specific Applications of Enclosures for Indoor Nonhazardous
Loss
Locations
Medium Voltage Switchgear (Indoor, 5 and 15 kV)
Provides a Degree of Protection Against the Type of Enclosures
1200 Ampere Breaker 600 Following Environmental Conditions 11 21 4 4X 5 6 6P 12 12K 13
2000 Ampere Breaker 1400
1 3000 Ampere Breaker 2000 Incidental Contact with the Enclosed Equipment X X X X X X X X X X
Medium Voltage Switchgear (Indoor, 5 and 15 kV) Falling Dirt X X X X X X X X X X
Falling Liquids and Light Splashing — X X X X X X X X X
600 Ampere Unfused Switch 500
1200 Ampere Unfused Switch 750 Circulating Dust, Lint, Fibers, and Flyings 2 — — X X — X X X X X
100 Ampere CL Fuses 840 Settling Airborne Dust, Lint, Fibers, and Flyings 2 — — X X X X X X X X
Hosedown and Splashing Water — — X X — X X — — —
Medium Voltage Starters (Indoor, 5 kV) Oil and Coolant Seepage — — — — — — — X X X
400 Ampere Starter FVNR 600 Oil or Coolant Spraying and Splashing — — — — — — — — — X
800 Ampere Starter FVNR 1000 Corrosive Agents — — — X — — X — — —
600 Ampere Fused Switch 500 Occasional Temporary Submersion — — — — — X X — — —
1200 Ampere Fused Switch 800 Occasional Prolonged Submersion — — — — — — X — — —
Low Voltage Switchgear (Indoor, 480 Volts) 1 These enclosures may be ventilated.
800 Ampere Breaker 400 2 These fibers and flying are nonhazardous materials and are not considered the Class III type
1600 Ampere Breaker 1000 ignitable fibers or combustible flyings. For Class III type ignitable fibers or combustible flyings
2000 Ampere Breaker 1500 see the National Electrical Code, Article 500.
3200 Ampere Breaker 2400
4000 Ampere Breaker 3000 Table 1.4-15. Comparison of Specific Applications of Enclosures for Outdoor Nonhazardous
5000 Ampere Breaker 4700 Locations
Fuse Limiters – 800 Ampere CB 200 Provides a Degree of Protection Against the Type of Enclosures
Fuse Limiters – 1600 Ampere CB 500 Following Environmental Conditions 3 3R 3 3S 4 4X 6 6P
Fuse Limiters – 2000 Ampere CB 750
Fuse Truck – 3200 Ampere CB 3600 Incidental Contact with the Enclosed Equipment X X X X X X X
Rain, Snow and Sleet 4 X X X X X X X
Fuse Truck – 4000 Ampere CB 4500
Sleet 5 — — X — — — —
Structures – 3200 Ampere 4000 Windblown Dust X — X X X X X
Structures – 4000 Ampere 5000 Hosedown — — — X X X X
Structures – 5000 Ampere 7000 Corrosive Agents — — — — X — X
High Resistance Grounding 1200 Occasional Temporary Submersion — — — — — X X
Panelboards (Indoor, 480 Volts) Occasional Prolonged Submersion — — — — — — X
3 These enclosures may be ventilated.
225 Ampere, 42 Circuit 300
4 External operating mechanisms are not required to be operable when the enclosure is ice covered.
Low Voltage Busway (Indoor, Copper, 480 Volts) 5 External operating mechanisms are operable when the enclosure is ice covered.
800 Ampere 44 per foot
1200 Ampere 60 per foot Table 1.4-16. Comparison of Specific Applications of Enclosures for Indoor Hazardous Locations
1350 Ampere 66 per foot
Provides a Degree of Protection Against Class Enclosure Types Enclosure Type
1600 Ampere 72 per foot Atmospheres Typically Containing 7 and 8, Class I Groups 6 9, Class II Groups 6
2000 Ampere 91 per foot (For Complete Listing, See NFPA 497M)
2500 Ampere 103 per foot A B C D E F G 10
3200 Ampere 144 per foot Acetylene I X — — — — — — —
4000 Ampere 182 per foot Hydrogen, Manufactured Gas I — X — — — — — —
5000 Ampere 203 per foot Diethyl Ether, Ethylene, Cyclopropane I — — X — — — — —
Motor Control Centers (Indoor, 480 Volts) Gasoline, Hexane, Butane, Naphtha, Propane,
Acetone, Toluene, Isoprene I — — — X — — — —
NEMA Size 1 Starter 39 Metal Dust II — — — — X — — —
NEMA Size 2 Starter 56 Carbon Black, Coal Dust, Coke Dust II — — — — — X — —
NEMA Size 3 Starter 92
Flour, Starch, Grain Dust II — — — — — — X —
NEMA Size 4 Starter 124 Fibers, Flyings 7 III — — — — — — X —
NEMA Size 5 Starter 244 Methane with or without Coal Dust MSHA — — — — — — — X
Structures 200 6 For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500.
Adjustable Frequency Drives (Indoor, 480 Volts) 7 Due to the characteristics of the gas, vapor, or dust, a product suitable for one Class or Group may
Adjustable Frequency Drives > 96% not be suitable for another Class or Group unless so marked on the product.
efficiency Note: If the installation is outdoors and/or additional protection is required by Tables 1.4-14 and
1.4-15, a combination-type enclosure is required.
Note: The information provided on power
equipment losses is generic data intended Table 1.4-17. Knockout Dimensions in Inches (mm)
to be used for sizing of HVAC equipment. Conduit Knockout Diameter Conduit Knockout Diameter
Trade Size Minimum Nominal Maximum Trade Size Minimum Nominal Maximum

.50 (12.7) .86 (21.8) .88 (22.2) .91 (23.0) 2.50 (63.5) 2.94 (74.6) 2.97 (75.4) 3.00 (76.2)
.75 (19.1) 1.09 (27.8) 1.11 (28.2) 1.14 (29.0) 3.00 (76.2) 3.56 (90.5) 3.59 (91.3) 3.63 (92.1)
1.00 (25.4) 1.36 (34.5) 1.38 (34.9) 1.41 (35.7) 3.50 (88.9) 4.06 (103.2) 4.13 (104.8) 4.16 (105.6)
1.25 (31.8) 1.72 (43.7) 1.73 (44.0) 1.77 (44.9) 4.00 (101.6) 4.56 (115.9) 4.64 (117.9) 4.67 (118.7)
1.50 (38.1) 1.96 (49.7) 1.98 (50.4) 2.11 (51.2) 5.00 (127.0) 5.63 (142.9) 5.72 (145.3) 5.75 (146.1)
2.00 (50.8) 2.43 (61.8) 2.47 (62.7) 2.50 (63.5) 6.00 (152.4) 6.70 (170.1) 6.81 (173.1) 6.84 (173.8)

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-11
January 2003 Reference Data
Ref. No. 0097
Conductor Resistance, Reactance, Impedance

Average Characteristics of diameters, and the like. Therefore, ■ For interlocked armored cable, use
data for medium voltage cables should magnetic conduit data for steel
600-Volt Conductors — be obtained from the manufacturer of armor and non-magnetic conduit
Ohms per 1000 Feet (305 m) the cable to be used. data for aluminum armor.
The tables below are average charac- ■ Z = X +R
2 2
teristics based on data from IEEE Stan- Application Notes
dard 141-1993. Values from different ■ Resistance and reactance are phase- ■ For busway impedance data, see
sources vary because of operating Section 23 of this catalog.
temperatures, wire stranding, insula-
to-neutral values, based on 60 Hz
AC, 3-phase, 4-wire distribution, in ■ For PF (power factor) values less
1
tion materials and thicknesses, overall ohms per 100 feet (30 m) of circuit than 1.0, the effective impedance Z e
diameters, random lay of multiple con- length (not total conductor lengths). is calculated from
ductors in conduit, conductor spacing, ■ Based upon conductivity of 100% Z e = R × PF + X sin (arc cos PF)
and other divergences in materials, for copper, 61% for aluminum.
test conditions and calculation meth- ■ For copper cable data, resistance
■ Based on conductor temperatures based on tinned copper at 60 Hz;
ods. These tables are for 600-volt 5 kV
of 75°C. Reactance values will have 600V and 5 kV nonshielded cable
and 15 kV conductors, at an average
negligible variation with tempera- based on varnished cambric insula-
temperature of 75°C. Other parameters
ture. Resistance of both copper tion; 5 kV shielded and 15 kV cable
are listed in the notes. For medium
and aluminum conductors will be based on neoprene insulation.
voltage cables, differences among
approximately 5% lower at 60°C or
manufacturers are considerably ■ For aluminum cable data, cable is
5% higher at 90°C. Data shown in
greater because of the wider variations cross-linked polyethylene insulated.
tables may be used without signifi-
in insulation materials and thick-
cant error between 60°C and 90°C.
nesses, shielding, jacketing, overall

Table 1.4-18. 60 Hz Impedance Data for 3-Phase Copper Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 75ºC (a) Three Single Conductors
Wire Size, In Magnetic Duct In Nonmagnetic Duct
AWG or 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z

8 .811 .0754 .814 .811 .0860 .816 .811 .0603 .813 .811 .0688 .814
8 (Solid) .786 .0754 .790 .786 .0860 .791 .786 .0603 .788 .786 .0688 .789
6 .510 .0685 .515 .510 .0796 .516 .510 .0548 .513 .510 .0636 .514
6 (Solid) .496 .0685 .501 .496 .0796 .502 .496 .0548 .499 .496 .0636 .500
4 .321 .0632 .327 .321 .0742 .329 .321 .0506 .325 .321 .0594 .326
4 (Solid) .312 .0632 .318 .312 .0742 .321 .312 .0506 .316 .312 .0594 .318
2 .202 .0585 .210 .202 .0685 .214 .202 .0467 .207 .202 .0547 .209
1 .160 .0570 .170 .160 .0675 .174 .160 .0456 .166 .160 .0540 .169
1/0 .128 .0540 .139 .128 .0635 .143 .127 .0432 .134 .128 .0507 .138
2/0 .102 .0533 .115 .103 .0630 .121 .101 .0426 .110 .102 .0504 .114
3/0 .0805 .0519 .0958 .0814 .0605 .101 .0766 .0415 .0871 .0805 .0484 .0939
4/0 .0640 .0497 .0810 .0650 .0583 .0929 .0633 .0398 .0748 .0640 .0466 .0792
250 .0552 .0495 .0742 .0557 .0570 .0797 .0541 .0396 .0670 .0547 .0456 .0712
300 .0464 .0493 .0677 .0473 .0564 .0736 .0451 .0394 .0599 .0460 .0451 .0644
350 .0378 .0491 .0617 .0386 .0562 .0681 .0368 .0393 .0536 .0375 .0450 .0586
400 .0356 .0490 .0606 .0362 .0548 .0657 .0342 .0392 .0520 .0348 .0438 .0559
450 .0322 .0480 .0578 .0328 .0538 .0630 .0304 .0384 .0490 .0312 .0430 .0531
500 .0294 .0466 .0551 .0300 .0526 .0505 .0276 .0373 .0464 .0284 .0421 .0508
600 .0257 .0463 .0530 .0264 .0516 .0580 .0237 .0371 .0440 .0246 .0412 .0479
750 .0216 .0495 .0495 .0223 .0497 .0545 .0194 .0356 .0405 .0203 .0396 .0445

Note: More tables on Page 1.4-12.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-12 Power Distribution Systems
Reference Data January 2003
Ref. No. 0098
Conductor Resistance, Reactance, Impedance

Table 1.4-19. 60 Hz Impedance Data for 3-Phase Copper Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 75ºC (b) Three Conductor Cable
Wire Size, In Magnetic Duct and Steel Interlocked Armor In Nonmagnetic Duct and Aluminum Interlocked Armor
AWG or 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z

8 .811 .0577 .813 .811 .0658 .814 .811 .0503 .812 .811 .0574 .813
8 (Solid) .786 .0577 .788 .786 .0658 .789 .786 .0503 .787 .786 .0574 .788
6 .510 .0525 .513 .510 .0610 .514 .510 .0457 .512 .510 .0531 .513
1 6 (Solid) .496 .0525 .499 .496 .0610 .500 .496 .0457 .498 .496 .0531 .499
4 .321 .0483 .325 .321 .0568 .326 .321 .0422 .324 .321 .0495 .325
4 (Solid) .312 .0483 .316 .312 .0508 .317 .312 .0422 .315 .312 .0495 .316
2 .202 .0448 .207 .202 .0524 .209 .202 .0390 .206 .202 .0457 .207
1 .160 .0436 .166 .160 .0516 .168 .160 .0380 .164 .160 .0450 .166
1/0 .128 .0414 .135 .128 .0486 .137 .127 .0360 .132 .128 .0423 .135
2/0 .102 .0407 .110 .103 .0482 .114 .101 .0355 .107 .102 .0420 .110
3/0 .0805 .0397 .0898 .0814 .0463 .0936 .0766 .0346 .0841 .0805 .0403 .090
4/0 .0640 .0381 .0745 .0650 .0446 .0788 .0633 .0332 .0715 .0640 .0389 .0749
250 .0552 .0379 .0670 .0557 .0436 .0707 .0541 .0330 .0634 .0547 .0380 .0666
300 .0464 .0377 .0598 .0473 .0431 .0640 .0451 .0329 .0559 .0460 .0376 .0596
350 .0378 .0373 .0539 .0386 .0427 .0576 .0368 .0328 .0492 .0375 .0375 .0530
400 .0356 .0371 .0514 .0362 .0415 .0551 .0342 .0327 .0475 .0348 .0366 .0505
450 .0322 .0361 .0484 .0328 .0404 .0520 .0304 .0320 .0441 .0312 .0359 .0476
500 .0294 .0349 .0456 .0300 .0394 .0495 .0276 .0311 .0416 .0284 .0351 .0453
600 .0257 .0343 .0429 .0264 .0382 .0464 .0237 .0309 .0389 .0246 .0344 .0422
750 .0216 .0326 .0391 .0223 .0364 .0427 .0197 .0297 .0355 .0203 .0332 .0389

Table 1.4-20. 60 Hz Impedance Data for 3-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 90ºC (a) Three Single Conductors
Wire Size, In Magnetic Duct In Nonmagnetic Duct
AWG or 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z

6 .847 .053 .849 — — — .847 .042 .848 — — —


4 .532 .050 .534 .532 .068 .536 .532 .040 .534 .532 .054 .535
2 .335 .046 .338 .335 .063 .341 .335 .037 .337 .335 .050 .339
1 .265 .048 .269 .265 .059 .271 .265 .035 .267 .265 .047 .269
1/0 .210 .043 .214 .210 .056 .217 .210 .034 .213 .210 .045 .215
2/0 .167 .041 .172 .167 .055 .176 .167 .033 .170 .167 .044 .173
3/0 .133 .040 .139 .132 .053 .142 .133 .037 .137 .132 .042 .139
4/0 .106 .039 .113 .105 .051 .117 .105 .031 .109 .105 .041 .113
250 .0896 .0384 .0975 .0892 .0495 .102 .0894 .0307 .0945 .0891 .0396 .0975
300 .0750 .0375 .0839 .0746 .0479 .0887 .0746 .0300 .0804 .0744 .0383 .0837
350 .0644 .0369 .0742 .0640 .0468 .0793 .0640 .0245 .0705 .0638 .0374 .0740
400 .0568 .0364 .0675 .0563 .0459 .0726 .0563 .0291 .0634 .0560 .0367 .0700
500 .0459 .0355 .0580 .0453 .0444 .0634 .0453 .0284 .0535 .0450 .0355 .0573
600 .0388 .0359 .0529 .0381 .0431 .0575 .0381 .0287 .0477 .0377 .0345 .0511
700 .0338 .0350 .0487 .0332 .0423 .0538 .0330 .0280 .0433 .0326 .0338 .0470
750 .0318 .0341 .0466 .0310 .0419 .0521 .0309 .0273 .0412 .0304 .0335 .0452
1000 .0252 .0341 .0424 .0243 .0414 .0480 .0239 .0273 .0363 .0234 .0331 .0405

Table 1.4-21. 60 Hz Impedance Data for 3-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 90ºC (b) Three Conductor Cable
Wire Size, In Magnetic Duct and Steel Interlocked Armor In Nonmagnetic Duct and Aluminum Interlocked Armor
AWG or 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z

6 .847 .053 .849 — — — .847 .042 .848 — — —


4 .532 .050 .534 — — — .532 .040 .534 — — —
2 .335 .046 .338 .335 .056 .340 .335 .037 .337 .335 .045 .338
1 .265 .048 .269 .265 .053 .270 .265 .035 .267 .265 .042 .268
1/0 .210 .043 .214 .210 .050 .216 .210 .034 .213 .210 .040 .214
2/0 .167 .041 .172 .167 .049 .174 .167 .033 .170 .167 .039 .171
3/0 .133 .040 .139 .133 .048 .141 .133 .037 .137 .132 .038 .138
4/0 .106 .039 .113 .105 .045 .114 .105 .031 .109 .105 .036 .111
250 .0896 .0384 .0975 .0895 .0436 .100 .0894 .0307 .0945 .0893 .0349 .0959
300 .0750 .0375 .0839 .0748 .0424 .0860 .0746 .0300 .0804 .0745 .0340 .0819
350 .0644 .0369 .0742 .0643 .0418 .0767 .0640 .0245 .0705 .0640 .0334 .0722
400 .0568 .0364 .0675 .0564 .0411 .0700 .0563 .0291 .0634 .0561 .0329 .0650
500 .0459 .0355 .0580 .0457 .0399 .0607 .0453 .0284 .0535 .0452 .0319 .0553
600 .0388 .0359 .0529 .0386 .0390 .0549 .0381 .0287 .0477 .0380 .0312 .0492
700 .0338 .0350 .0487 .0335 .0381 .0507 .0330 .0280 .0433 .0328 .0305 .0448
750 .0318 .0341 .0466 .0315 .0379 .0493 .0309 .0273 .0412 .0307 .0303 .0431
1000 .0252 .0341 .0424 .0248 .0368 .0444 .0239 .0273 .0363 .0237 .0294 .0378

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-13
January 2003 Reference Data
Ref. No. 0099
Conductor Ampacities

Current Carrying Capacities of Copper and Aluminum and Copper-Clad Aluminum Conductors
From National Electrical Code (NEC), 1999 Edition (NFPA70-1999)
Table 1.4-22. Allowable Ampacities of Insulated Conductors Rated 0 – 2000 Volts, 60°C to 90°C (140°F to 194°F). Not more than three current-carrying
conductors in raceway, cable or earth (directly buried), based on ambient temperature of 30°C (86°F)
Size Temperature Rating of Conductor (See Table 310-13) Size
AWG or 60°C (140°F) 75°C (167°F) 90°C (194°F) 60°C (140°F) 75°C (167°F) 90°C (194°F) AWG or
kcmil kcmil
Types Types 1
TW, UF FEPW, RH, RHW, TBS, SA, SIS, TW, UF RH, RHW, THHW, TBS, SA, SIS,
THHW, THW, FEP, FEPB, MI, THW, THWN, THHN, THHW,
THWN, XHHW, RHH, RHW-2, XHHW, USE THW-2, THWN-2,
USE, ZW THHN, THHW, RHH, RHW-2,
THW-2, THWN-2, USE-2, XHH,
USE-2, XHH, XHHW, XHHW-2,
XHHW, XHHW-2, ZW-2
ZW-2
Copper Aluminum or Copper-Clad Aluminum

18 — — 14 — — — —
16 — — 18 — — — —
14 1 20 20 25 — — — —
12 1 25 25 30 20 20 25 12 1
10 1 30 35 40 25 30 35 10 1
8 40 50 55 30 40 45 8
6 55 65 75 40 50 60 6
4 70 85 95 55 65 75 4
3 85 100 110 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 150 85 100 115 1
1/0 125 150 170 100 120 135 1/0
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0
4/0 195 230 260 150 180 205 4/0
250 215 255 290 170 205 230 250
300 240 285 320 190 230 255 300
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500
600 355 420 475 285 340 385 600
700 385 460 520 310 375 420 700
750 400 475 535 320 385 435 750
800 410 490 555 330 395 450 800
900 435 520 585 355 425 480 900
1000 455 545 615 375 445 500 1000
1250 495 590 665 405 485 545 1250
1500 520 625 705 435 520 585 1500
1750 545 650 735 455 545 615 1750
2000 560 665 750 470 560 630 2000
Correction Factors
Ambient For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown Ambient
Temperature °C above by the appropriate factor shown below. Temperature °F

21 – 25 1.08 1.05 1.04 1.08 1.05 1.04 70 – 77


26 – 30 1.00 1.00 1.00 1.00 1.00 1.00 78 – 86
31 – 35 .91 .94 .96 .91 .94 .96 87 – 95
36 – 40 .82 .88 .91 .82 .88 .91 96 – 104
41 – 45 .71 .82 .87 .71 .82 .87 105 – 113
46 – 50 .58 .75 .82 .58 .75 .82 114 – 122
51 – 55 .41 .67 .76 .41 .67 .76 123 – 131
56 – 60 — .58 .71 — .58 .71 132 – 140
61 – 70 — .33 .58 — .33 .58 141 – 158
71 – 80 — — .41 — — .41 159 – 176
1 See NEC Section 240-3.
Note: For complete details of using Table 1.4-22, see NEC Article 310 in its entirety.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-14 Power Distribution Systems
Reference Data January 2003
Ref. No. 0100
Conductor Ampacities

Excerpts from NEC 240-3. 3. Devices Rated Over 800 Amperes. Cutler-Hammer Application Notes
Where the overcurrent device
Protection of Conductors is rated over 800 amperes, the
Note: UL listed circuit breakers rated 125A
or less shall be marked as being suitable for
Conductors, other than flexible cords ampacity of the conductors it pro- 60ºC (140ºF), 75ºC (167ºF) only or 60/75ºC
and fixture wires, shall be protected tects shall be equal to or greater (140/167ºF) wire. All Cutler-Hammer break-
against overcurrent in accordance with than the rating of the overcurrent ers rated 125A or less are marked 60/75ºC.
their ampacities as specified in Section device as defined in Section 240-6. All UL listed circuit breakers rated over
310-15, unless otherwise permitted or 125A are suitable for 75ºC conductors.
1 required in (a) through (g). 4. Small Conductors. Unless specifi- Conductors rated for higher temperatures
cally permitted in (e) through (g), may be used, but must not be loaded to
1. Power Loss Hazard. Conductor the overcurrent protection shall carry more current than the 75ºC ampacity
overload protection shall not be not exceed 15 amperes for No. 14, of that size conductor for equipment
required where the interruption of 20 amperes for No. 12, and marked or rated 75ºC or the 65ºC ampacity
the circuit would create a hazard, 30 amperes for No. 10 copper; or of that size conductor for equipment
marked or rated 65ºC. However, when
such as in a material handling 15 amperes for No. 12 and 25 applying derated factors, so long as the
magnet circuit or fire pump circuit. amperes for No. 10 aluminum and actual load does not exceed the lower of
Short circuit protection shall be copper-clad aluminum after any the derated ampacity or the 75ºC or 60ºC
provided. correction factors for ambient ampacity that applies.
temperature and number of
Note: FPN: See Standard for the Installation
of Centrifugal Fire Pumps, NFPA 20-1996.
conductors have been applied.
5. Tap Conductors. Tap conductors
2. Devices Rated 800 Amperes shall be permitted to be protected
or Less. The next higher standard against overcurrent in accordance
overcurrent device rating (above with Sections 210-19(d), 240-21,
the ampacity of the conductors 364-11, 364-12, and 430-53(d).
being protected) shall be permit-
ted to be used, provided all of the As used in this article, a tap con-
following conditions are met. ductor is defined as a conductor,
other than a service conductor
a. The conductors being pro- that has overcurrent protection
tected are not part of a multi- ahead of its point of supply, that
outlet branch circuit supplying exceeds the value permitted
receptacles for cord- and plug- for similar conductors that are
connected portable loads. protected as described elsewhere
b. The ampacity of the conductors in this section.
does not correspond with the
standard ampere rating of a
fuse or a circuit breaker without
overload trip adjustments
above its rating (but that shall
be permitted to have other
trip or rating adjustments).
c. The next higher standard rating
selected does not exceed 800
amperes.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-15
January 2003 Reference Data
Ref. No. 0101
Conductor Ampacities

Excerpts from NEC 310-15. Table 1.4-23. Adjustment Factors for More 3. Neutral Conductor
than Three Current-Carrying Conductors in a
Ampacities for Conductors Raceway or Cable a. A neutral conductor that carries
Rated 0 – 2000 Volts only the unbalanced current
Number of Percent of Values in Tables
Current-Carrying as Adjusted for Ambient
from other conductors of the
1. Tables. Ampacities for conductors same circuit shall not be
Conductors Temperature if Necessary
rated 0 to 2000 volts shall be as required to be counted when
specified in the Allowable Ampacity 4–6 80 applying the provisions of
Tables 310-16 through 310-19 and 7–9 70 Section 310-15(b)(2)(a). 1
Ampacity Tables 310-20 and 310-21 10 – 20 50
as modified by (1) through (7). 21 – 30 45 b. In a 3-wire circuit consisting
31 – 40 40 of two phase wires and the
Note: FPN: Tables 310-16 through 310-19 41 and Above 35 neutral of a 4-wire, 3-phase
are application tables for use in determining
conductor sizes on loads calculated in
wye-connected system, a
accordance with Article 220. Allowable Exception No. 1: Where conductors common conductor carries
ampacities result from consideration of of different systems, as provided in approximately the same
one or more of the following: Section 300-3, are installed in a common current as the line-to-neutral
raceway or cable, the derating factors load currents of the other con-
a. Temperature compatibility with shown in Table 1.4-23 shall apply to ductors and shall be counted
connected equipment, espe- the number of power and lighting when applying the provisions
cially at the connection points. conductors only (Articles 210, 215, of Section 310-15(b)(2)(a).
b. Coordination with circuit and 220 and 230). c. On a 4-wire, 3-phase wye circuit
system overcurrent protection. where the major portion of the
Exception No. 2: For conductors
c. Compliance with the require- installed in cable trays, the provisions load consists of non-linear
ments of product listings or of Section 318-11 shall apply. loads, harmonic currents are
certifications. See Section present in the neutral conductor;
110-3(b). Exception No. 3: Derating factors the neutral shall therefore be
d. Preservation of the safety shall not apply to conductors in considered a current-carrying
benefits of established indus- nipples having a length not exceeding conductor.
try practices and standardized 24 inches (610 mm).
4. Grounding or Bonding Conductor.
procedures. Exception No. 4: Derating factors shall
not apply to underground conductors A grounding or bonding conductor
2. Adjustment Factors shall not be counted when apply-
entering or leaving an outdoor trench
a. More than Three Current Carry- if those conductors have physical ing the provisions of Section
ing Conductors in a Raceway protection in the form of rigid metal 310-15(b)(2)(a).
or Cable. Where the number conduit, intermediate metal conduit,
of current carrying conductors or rigid nonmetallic conduit having
in a raceway or cable exceeds a length not exceeding 10 feet (3.0 m)
three, or where single conduc- and the number of conductors does
tors or multiconductor cables not exceed four.
are stacked or bundled longer
than 24 inches (610 mm) with- b. More than One Conduit, Tube,
out maintaining spacing and or Raceway. Spacing between
are not installed in raceways, conduits, tubing, or raceways
the allowable ampacity of each shall be maintained.
conductor shall be reduced as
shown in Table 1.4-23.
Note: FPN: See Appendix B, Table B-310-11,
for adjustment factors for more than three
current-carrying conductors in a raceway
or cable with load diversity.
Note: For complete details of using
Table 1.4-22, see NEC Article 310 in its
entirety.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-16 Power Distribution Systems
Reference Data January 2003
Ref. No. 0102
Conduit Fill

Conduit Fill
NEC 1999 — Appendix C (Table C1 Information) — Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size
Note: For other conduit types such as rigid, PVC, etc. see NEC Appendix C, Tables C2 through C12.

Table 1.4-24. Maximum Number of Conductors and Fixture Wires in Electrical Metallic Tubing (Based on Table 1, Chapter 9)
Type Conductor Size Trade Size Inches (mm)
(AWG/kcmil) 1/2 (12.7) 3/4 (19.1) 1 (25.4) 1-1/4 (31.8) 1-1/2 (38.1) 2 (50.8) 2-1/2 (63.5) 3 (76.2) 3-1/2 (88.9) 4 (101.6)
1
RH 14 6 10 16 28 39 64 112 169 221 282
12 4 8 13 23 31 51 90 136 177 227
RHH, RHW 14 4 7 11 20 27 46 80 120 157 201
RHW 12 3 6 9 17 23 38 66 100 131 167
RH 10 2 5 8 13 18 30 53 81 105 135
RHH 8 1 2 4 7 9 16 28 42 55 70
RHW 6 1 1 3 5 8 13 22 34 44 56
RHW-2 4 1 1 2 4 6 10 17 26 34 44
3 1 1 1 4 5 9 15 23 30 38
2 1 1 1 3 4 7 13 20 26 33
1 0 1 1 1 3 5 9 13 17 22
1/0 0 1 1 1 2 4 7 11 15 19
2/0 0 1 1 1 2 4 6 10 13 17
3/0 0 0 1 1 1 3 5 8 11 14
4/0 0 0 1 1 1 3 5 7 9 12
250 0 0 0 1 1 1 3 5 7 9
300 0 0 0 1 1 1 3 5 6 8
350 0 0 0 1 1 1 3 4 6 7
400 0 0 0 1 1 1 2 4 5 7
500 0 0 0 0 1 1 2 3 4 6
600 0 0 0 0 1 1 1 3 4 5
700 0 0 0 0 0 1 1 2 3 4
750 0 0 0 0 0 1 1 2 3 4
800 0 0 0 0 0 1 1 2 3 4
900 0 0 0 0 0 1 1 1 3 3
1000 0 0 0 0 0 1 1 1 2 3
1250 0 0 0 0 0 0 1 1 1 2
1500 0 0 0 0 0 0 1 1 1 1
1750 0 0 0 0 0 0 1 1 1 1
2000 0 0 0 0 0 0 1 1 1 1
TW 14 8 15 25 43 58 96 168 254 332 424
12 6 11 19 33 45 74 129 195 255 326
10 5 8 14 24 33 55 96 145 190 243
8 2 5 8 13 18 30 53 81 105 135
RHH 1 14 6 10 16 28 39 64 112 169 221 282
RHW 1
RHW-2 1
THHW
THW
THW-2
RHH 1 12 4 8 13 23 31 51 90 136 177 227
RHW 1 10 3 6 10 18 24 40 70 106 138 177
RHW-2 1
THHW
THW
RHH 1 8 1 4 6 10 14 24 42 63 83 106
RHW 1
RHW-2 1
THHW
THW
THW-2
1 Types RHH, RHW, and RHW-2 without outer covering.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-17
January 2003 Reference Data
Ref. No. 0103
Conduit Fill

Table 1.4-24. Maximum Number of Conductors and Fixture Wires in Electrical Metallic Tubing (Continued)
Type Conductor Size Trade Size Inches (mm)
(AWG/kcmil) 1/2 (12.7) 3/4 (19.1) 1 (25.4) 1-1/4 (31.8) 1-1/2 (38.1) 2 (50.8) 2-1/2 (63.5) 3 (76.2) 3-1/2 (88.9) 4 (101.6)

RHH 2 6 1 3 4 8 11 18 32 48 63 81
RHW 2 4 1 1 3 6 8 13 24 36 47 60
RHW-2 2 3 1 1 3 5 7 12 20 31 40 52
TW, THW 2 1 1 2 4 6 10 17 26 34 44
THHW
THW-2
1 1 1 1 3 4 7 12 18 24 31 1
1/0 0 1 1 2 3 6 10 16 20 26
2/0 0 1 1 1 3 5 9 13 17 22
3/0 0 1 1 1 2 4 7 11 15 19
4/0 0 0 1 1 1 3 6 9 12 16
250 0 0 1 1 1 3 5 7 10 13
300 0 0 1 1 1 2 4 6 8 11
350 0 0 0 1 1 1 4 6 7 10
400 0 0 0 1 1 1 3 5 7 9
500 0 0 0 1 1 1 3 4 6 7
600 0 0 0 1 1 1 2 3 4 6
700 0 0 0 0 1 1 1 3 4 5
750 0 0 0 0 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 3 5
900 0 0 0 0 0 1 1 2 3 4
1000 0 0 0 0 0 1 1 2 3 4
1250 0 0 0 0 0 1 1 1 2 3
1500 0 0 0 0 0 1 1 1 1 2
1750 0 0 0 0 0 0 1 1 1 2
2000 0 0 0 0 0 0 1 1 1 1
THHN 14 12 22 35 61 84 138 241 364 476 608
THWN 12 9 16 26 45 61 101 176 266 347 443
THWN-2 10 5 10 16 28 38 63 111 167 219 279
8 3 6 9 16 22 36 64 96 126 161
6 2 4 7 12 16 26 46 69 91 116
4 1 2 4 7 10 16 28 43 56 71
3 1 1 3 6 8 13 24 36 47 60
2 1 1 3 5 7 11 20 30 40 51
1 1 1 1 4 5 8 15 22 29 37
1/0 1 1 1 3 4 7 12 19 25 32
2/0 0 1 1 2 3 6 10 16 20 26
3/0 0 1 1 1 3 5 8 13 17 22
4/0 0 1 1 1 2 4 7 11 14 18
250 0 0 1 1 1 3 6 9 11 15
300 0 0 1 1 1 3 5 7 10 13
350 0 0 1 1 1 2 4 6 9 11
400 0 0 0 1 1 1 4 6 8 10
500 0 0 0 1 1 1 3 5 6 8
600 0 0 0 1 1 1 2 4 5 7
700 0 0 0 1 1 1 2 3 4 6
750 0 0 0 0 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 3 3 4
1000 0 0 0 0 1 1 1 2 3 4
FEP, FEPB 14 12 21 34 60 81 134 234 354 462 590
PFA, PFAH 12 9 15 25 43 59 98 171 258 337 430
TFE 10 6 11 18 31 42 70 122 185 241 309
8 3 6 10 18 24 40 70 106 138 177
6 2 4 7 12 17 28 50 75 98 126
4 1 3 5 9 12 20 35 53 69 88
3 1 2 4 7 10 16 29 44 57 73
2 1 1 3 6 8 13 24 36 47 60
PFA, PFAH 1 1 1 2 4 6 9 16 25 33 42
TFE
PFA, PFAH 1/0 1 1 1 3 5 8 14 21 27 35
TFE, Z 2/0 0 1 1 3 4 6 11 17 22 29
3/0 0 1 1 2 3 5 9 14 18 24
4/0 0 1 1 1 2 4 8 11 15 19
2 Types RHH, RHW, and RHW-2 without outer covering.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-18 Power Distribution Systems
Reference Data January 2003
Ref. No. 0104
Conduit Fill

Table 1.4-24. Maximum Number of Conductors and Fixture Wires in Electrical Metallic Tubing (Continued)
Type Conductor Size Trade Size Inches (mm)
(AWG/kcmil) 1/2 (12.7) 3/4 (19.1) 1 (25.4) 1-1/4 (31.8) 1-1/2 (38.1) 2 (50.8) 2-1/2 (63.5) 3 (76.2) 3-1/2 (88.9) 4 (101.6)

Z 14 14 25 41 72 98 161 282 426 556 711


12 10 18 29 51 69 114 200 302 394 504
10 6 11 18 31 42 70 122 185 241 309
8 4 7 11 20 27 44 77 117 153 195
1 6 3 5 8 14 19 31 54 82 107 137
4 1 3 5 9 13 21 37 56 74 94
3 1 2 4 7 9 15 27 41 54 69
2 1 1 3 6 8 13 22 34 45 57
1 1 1 2 4 6 10 18 28 36 46
XHH 14 8 15 25 43 58 96 168 254 332 424
XHHW 12 6 11 19 33 45 74 129 195 255 326
XHHW-2 10 5 8 14 24 33 55 96 145 190 243
ZW 8 2 5 8 13 18 30 53 81 105 135
6 1 3 6 10 4 22 39 60 78 100
4 1 2 4 7 10 16 28 43 56 72
3 1 1 3 6 8 14 24 36 48 61
2 1 1 3 5 7 11 20 31 40 51
XHH 1 1 1 1 4 5 8 15 23 30 38
XHHW 1/0 1 1 1 3 4 7 13 19 25 32
XHHW-2 2/0 0 1 1 2 3 6 10 16 21 27
3/0 0 1 1 1 3 5 9 13 17 22
4/0 0 1 1 1 2 4 7 11 14 18
250 0 0 1 1 1 3 6 9 12 15
300 0 0 1 1 1 3 5 8 10 13
350 0 0 1 1 1 2 4 7 9 11
400 0 0 0 1 1 1 4 6 8 10
500 0 0 0 1 1 1 3 5 6 8
600 0 0 0 1 1 1 2 4 5 6
700 0 0 0 0 1 1 2 3 4 6
750 0 0 0 0 1 1 1 3 4 5
800 0 0 0 0 1 1 1 3 4 5
900 0 0 0 0 1 1 1 3 3 4
1000 0 0 0 0 0 1 1 2 3 4
1250 0 0 0 0 0 1 1 1 2 3
1500 0 0 0 0 0 1 1 1 1 3
1750 0 0 0 0 0 0 1 1 1 2
2000 0 0 0 0 0 0 1 1 1 1

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-19
January 2003 Reference Data
Ref. No. 0105
Formulas and Terms

Table 1.4-25. Formulas for Determining Amperes, hp, kW, and kVA
To Direct Alternating Current
Find Current Single-Phase Two-Phase — 4-Wire 1 3-phase
hp × 746 hp × 746 hp × 746 hp × 746
Amperes (l) When −−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Horsepower is Known E × % eff E × % eff × pf 2 × E × % eff × pf 3 × E × % eff × pf
Amperes (l) When kW × 1000 kW × 1000 kW × 1000 kW × 1000
−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−
Kilowatts is Known E E × pf 2 × E × pf 3 × E × % pf
Amperes (l) When — kVA × 1000
−−−−−−−−−−−−−−−−−−
kVA × 1000
−−−−−−−−−−−−−−−−−−
kVA × 1000
−−−−−−−−−−−−−−−−
1
kVA is Known E 2×E 3×E
Kilowatts I×E l × E × pf l × E × 2 × pf l × E × 3 × pf
−−−−−−− −−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−
1000 1000 1000 1000
kVA — I×E I×E×2 I×E× 3
−−−−−−− −−−−−−−−−−−− −−−−−−−−−−−−−−−
1000 1000 1000
Horsepower (Output) I × E × % eff I × E × % eff × pf I × E × 2 × % eff × pf I × E × 3 × % eff × pf
−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
746 746 746 746
1 For 2-phase, 3-wire circuits the current in the common conductor is 2 times that in either of the two other conductors.
Note: Units of measurement and definitions for E (volts), I (amperes), and other abbreviations are given below under Common Electrical Terms.

Common Electrical Terms How to Compute Power Factor


Ampere (l) = unit of current or rate of flow of electricity Watts
Determining Watts pf = ----------------------------------------------
Volt (E) = unit of electromotive force Volts × Amperes

Ohm (R) = unit of resistance 1. 1. From watt-hour meter.


E Watts = rpm of disc x 60 x Kh
Ohms law: I = −− (DC or 100% pf)
R
Where Kh is meter constant
Megohm = 1,000,000 ohms
printed on face or nameplate
Volt Amperes (VA) = unit of apparent power of meter.
= E × l (single-phase)
If metering transformers are used,
= E×l× 3 above must be multiplied by the
Kilovolt Amperes (kVA) = 1000 volt-amperes transformer ratios.

Watt (W) = unit of true power 2. Directly from wattmeter reading.


Where:
= VA × pf
= .00134 hp Volts = line-to-line voltage as
measured by voltmeter.
Kilowatt (kW) = 1000 watts
Power Factor (pf) = ratio of true to apparent power Amperes = current measured in
W kW line wire (not neutral) by ammeter.
= -------- ------------
VA kVA Table 1.4-26. Temperature Conversion
Watthour (Wh) = unit of electrical work (F° to C°) C° = 5/9 (F°-32°)
= one watt for one hour (C° to F°) F° = 9/5(C°)+32°
= 3.413 Btu C° -15 -10 -5 0 5 10 15 20
= 2,655 foot. lbs. F° 5 14 23 32 41 50 59 68
Cº 25 30 35 40 45 50 55 60
Kilowatt-hour (kWh) = 1000 watthours F° 77 86 95 104 113 122 131 140
C° 65 70 75 80 85 90 95 100
Horsepower (hp) = measure of time rate of doing work F° 149 158 167 176 185 194 203 212
= equivalent of raising 33,000 lbs. one foot. in one minute
= 746 watts 1 Inch = 2.54 centimeters
1 Kilogram = 2.20 lbs.
Demand Factor = ratio of maximum demand to the total connected load
1 Square Inch = 1,273,200 circular mills
Diversity Factor = ratio of the sum of individual maximum demands of 1 Circular Mill = .785 square mil
the various subdivisions of a system to the maximum
1 Btu = 778 foot. lbs.
demand of the whole system
= 252 calories
Load Factor = ratio of the average load over a designated period 1 Year = 8,760 hours
of time to the peak load occurring in that period

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-20 Power Distribution Systems
Reference Data January 2003
Ref. No. 0106
Seismic Requirements

Seismic Requirements
General
Starting more than 10 years ago,
Eaton’s Cutler-Hammer business
embarked on a comprehensive pro-
gram centered around designing
1 and building electrical distribution
and control equipment capable of
meeting and exceeding the seismic
load requirements of the Uniform
Building Code (UBCT), the California
Building Code (CBC), and the Building
Official & Code Administration
(BOCAT) International. The entire
program has been updated to also
meet the Year 2000 International
Building Code (IBC) unified seismic
requirements.
These codes emphasize building
design requirements. Electrical
equipment and distribution system Uniform Building Code Seismic Zones
components are considered attach- 0 1 2A 2B 3 4
ments to the building. The equipment
is acceptable if it can withstand Those areas within
the seismic event and perform its No Minor Moderate Moderate Major Zone 3 determined
damage damage damage damage damage by the proximity to
function immediately afterwards.
certain major faults
A cooperative effort with the equip-
ment user, the building designer
and the equipment installer ensures Figure 1.4-1. UBC Seismic Zone Map of the United States
that the equipment is correctly
mounted to a foundation that can Uniform Building Code (UBC) States is shown in Figure 1.4-1
withstand the effects of an earthquake. (Figure 16-3 of the UBC, Chapter 16).
The 1997 Uniform Building Code, Ca is taken equal to the maximum
Cutler-Hammer electrical distribution Chapter 16 of Division IV-Earthquake of 0.44 x 1.5 = 0.66.
and power control equipment has Design, requires that structures and
been tested and seismically proven portions of structures shall be designed Ip: Is the Seismic Importance Factor
for requirements exceeding the UBC, to withstand the seismic ground motion (Table 16-K, page 2-30). It is taken
CBC, BOCA and the IBC. Over one specified in the codes. Section 1632 of as maximum and equal to 1.5.
hundred different assemblies repre- the codes — Lateral Force on Elements
of Structures, Nonstructural Compo- Wp: Is the Equipment Operating Weight.
senting all product lines have been
successfully tested and verified to nents and Equipment Supported by Therefore, the maximum theoretical
seismic levels higher than the maxi- Structures, and under subsection static seismic loads (including all the
mum seismic requirements specified Section 1632.1: General, states that: conservatism possible) are:
in the UBC, CBC, BOCA and the IBC. “Elements of structures and their
The equipment maintained structural attachments, permanent nonstructural F p = 4.0 × ( .44 × 1.5 ) × 1.5 × W p
integrity and demonstrated the ability components and their attachments,
to function before and immediately and the attachments for permanent The codes state that the design lateral
after the seismic tests. equipment supported by a structure accelerations and resultant loads, deter-
shall be designed to resist the total mined above, are static loads to be dis-
A technical paper, Earthquake Require- design seismic forces prescribed in tributed in proportion to the mass dist-
ments and Cutler-Hammer Distribution Section 1632.2.” ribution of the element or component.
and Control Equipment Seismic Therefore, assuming a uniformly distrib-
Capabilities (SA.125.01.S.E), provides Section 1632.2, Design for Total Lateral uted mass, the static loads computed in
a detailed explanation of the applicable Force, specifies that the total design lat- the above formula are imposed at the
seismic codes and the Cutler-Hammer eral static seismic force, Fp, is defined C.G. or at conservatively one half the
program to qualify equipment. as (see equation 32-1 in code, Page 2-18): height of the equipment from its base.
F p = 4.0 C a I p W p The complete Response Spectrum
Curve starts at 0.33g at 1.0 Hz, linearly
Where: increases to 2.15g at 2.15 Hz (Ts ).
Ca: Is the Seismic Coefficient for Zone 4, The peak spectral accelerations then
Table 16-Q. It is equal to a maximum covers a wide band of frequencies
of 0.44 Na where Na is Near Source up to 11 Hz (To) then gradually
Factor and is equal to a maximum decreases to 0.86 g (ZPA) at 33 Hz.
of 1.5 (see Table 16-S, page 2-35). This curve represents the complete
The Seismic Zone Map of the United 1997 UBC Design Response Spectrum.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-21
January 2003 Reference Data
Ref. No. 0107
Seismic Requirements

California Building Code


California Building Code adopted the 0.15
1997 UBC as the CBC-Title 24. The seis- 0.20
0.10
mic requirements are basically the same
0.10 0.15 0.10
as described in the UBC. When consider-
ing the maximum seismic requirements, 0.20 0.05 0.10
<0.05
the UBC and CBC are basically identical. 0.05 0.10 0.40
0.05
Again, as in the UBC, the Response 0.05 1
0.15 0.15 0.20
Spectrum Curve starts at 0.33g at 1.0 Hz, <0.05
0.20 0.15 0.10
linearly increases to 2.15g at 2.15 Hz (Ts). 0.40
The peak spectral accelerations then 0.40 0.20 0.10 0.15
0.05
cover a wide band of frequencies up 0.05
0.20 0.10
to 11 Hz (To) then gradually decreases 0.40 0.10 0.05
to 0.86g (ZPA) at 33 Hz. 0.10 0.05 0.10
0.40 <0.05
0.05 <0.05
Building Official and 0.40

Code Administrators (BOCA) <0.05

BOCA seismic requirements include


the following provisions:
A. Section 1612.1.3: Provides the
Seismic Ground Acceleration
Maps; Contour Map of Effective Figure 1.4-2. BOCA Contour Map of Effective Peak Velocity-Related Acceleration Coefficient (A v)
Peak Velocity-Related Accelera-
tion Coefficient (A v), Figure 1.4-21, Where: The ICC founders — the Building Offi-
and Contour Map of Effective Cc: Is the Seismic Coefficient (MCC, cials and Code Administrators (BOCA),
Peak Acceleration Coefficient (Aa), SWGR, Bus Ducts, etc.) and is taken the International Conference of Build-
(Figure 1612.1.3(1) and (2) of code). maximum equal to 2.0. ing Officials (ICBO), and the Southern
Building Code Congress International
According to the maps, the maxi- P: Is the Performance Criteria Factor for (SBCCIT) — created the ICC in response
mum effective peak acceleration Seismic Hazard Exposure Group III, to technical disparities among the
(Coefficient Aa) is equal to 0.4g. and is taken maximum equal to 1.5. three nationally recognized model
The maximum effective peak codes now in use in the U.S. The ICC
velocity related acceleration ac: Is the Attachment Amplification offers a single, complete set of con-
(Coefficient A v) is equal to 0.4g. Factor for Equipment resonance struction codes without regional limi-
+/-40% of the building resonance tations — the International IBC Codes.
B. Section 1612.1.4: Site-Specific and is taken equal to the maximum
Response Spectra, this section of 2.0. According to Chapter 16, Structure
does not provide a normalized Design, the seismic requirements of
RRS. The development of the site Wc: Is the Equipment Operating Weight. electrical equipment in buildings may
RRS is left up to the designer with The results are tabulated as follows: be computed in two steps. The first
certain limitations. step is to determine the maximum
Again, as in the UBC, the Response ground motion to be considered at the
C. Section 1612.1.5: Seismic Hazard Spectrum Curve starts at 0.5g at 1.0 Hz, site. The second step is to evaluate the
Exposure Groups (Table 1612.1.5) linearly increases to 1.6g at 3.2 Hz. The equipment mounting and attachments
for essential buildings and facili- peak spectral accelerations then covers inside the building or structure. The two
ties we used “Group III.” a wide band of frequencies up to 20 Hz sets are then evaluated to determine
then gradually decreases to 1.0gs (ZPA) appropriate seismic test requirements.
D. Section 1612.1.7: Seismic Perfor-
at 33 Hz. The ground motion, the in-structure
mance Category (Table 1612.1.7),
seismic requirements of the equipment,
for Effective Peak Velocity-Related
Acceleration (A v) above 0.2 and
ANSI C37.81 and the seismic response spectrum
The seismic requirements for Class 1E requirements are discussed below.
Seismic Hazard Exposure Group
III, the Seismic Performance switchgear in nuclear power plants A. Ground Motion
Category is defined as “E.” are defined in ANSI C37.81. Eaton’s
According to the proposed code, the
Cutler-Hammer business elected to
E. Section 1612.6.4: Mechanical first and most important step in the pro-
test the equipment to 2/3 of the
and Electrical Components cess is to determine the Maximum Con-
nuclear requirements.
and System Design, this section sidered Earthquake Spectral Response
specifies that mechanical and Acceleration at short periods of 0.2 sec-
Year 2000 onds (SS) and at a period of 1.0 second
electrical components and sys-
tems and their attachments shall International Building Code (IBC) (S1). These values are determined from
be designed to seismic force (F p) On December 9, 1994, the International a set of 24 Spectral Acceleration Maps
determined from the following Code Council (ICC) was established as which include numerous contour lines
formula (see Table 612.6.4): a nonprofit organization dedicated to indicating the severity of the earthquake
developing a single set of comprehen- requirements at a particular location
F p = A v C c Pa c W c sive and coordinated national codes. in the country.

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-22 Power Distribution Systems
Reference Data January 2003
Ref. No. 0108
Seismic Requirements

The maps indicate low to moderate


seismic requirements for the entire
country, with the exception of two
particular areas; the West Coast (the
State of California) and the Midwest
(the New Madrid areas). Areas with
the seismic requirements at the New
Madrid are approximately 40% higher
1 than the maximum requirements of
the West Coast.
The Design Response Spectrum/
Spectral accelerations are equal to
0.68g at zero period (ZPA), increase
linearly to a peak acceleration of 1.7g
at 0.146 seconds (or 6.9 Hz) and stay
constant to 0.73 seconds (or 1.37 Hz)
then gradually decrease to 1.24g at 1
second (or 1 Hz).
B. In-Structure Seismic Requirements
of Equipment
The code provides a formula for
computing the seismic requirements Uniform Building Code Seismic Zones
of electrical and mechanical equip- 0 1 2A 2B 3 4
ment inside a building or a structure.
The formula is designed for evaluating Those areas within
the equipment attachment to the No Minor Moderate Moderate Major Zone 3 determined
equipment foundations. damage damage damage damage damage by the proximity to
certain major faults
The seismic loads are defined in
Section 1621.1.4 as: Figure 1.4-3. Bellcore Earthquake Zone Map
F p = .4a p S DS W p ( 1 + 2 Z ⁄ h ) ⁄ ( R p ⁄ I p )
The following parameters produce the Bellcore Requirements
Where: maximum required force:
The Bellcore Generic Requirements
■ Z is taken equal to H (GR-63-CORE, Issue 1, dated 1995)
Fp : Seismic design force imposed at
(equipment on roof). for the Network Equipment-Building
the component’s C.G. and distrib-
■ Ip is taken equal to 1.5. System (NEBS) (Reference 10), and
uted relative to component mass
the Physical Protection Section 5.4 of
distribution. ■ Ap is taken equal to 2.5.
the code includes a map of the seismic
■ Rp is taken equal to 2.5. zones (Figure 1.4-3), as well as a pro-
ap : Component amplification factor
that varies from 1.00 to 2.50. ■ SDS is equal to 1.7g as computed in posed Response Spectrum Curve for
previous section. testing communication equipment.
SDS: Spectral acceleration, short The acceleration at C.G. of equipment Descriptions of the test requirements
period, as determined in the is then computed equal to: and test levels of equipment are
previous section. also included.
Acceleration = 0.4 x 2.5 x 1.7g (1 + 2) /
Wp: Component operating weight. (2.5/1.5) = 3.06g
Rp: Component response modification For equipment on grade, the accelera-
factor that varies from 1.0 to 5.0. tion at C.G. is then computed equal to:
Ip : Component importance factor that Acceleration = 0.4 x 2.5 x 1.7g (1 + 0) /
is either 1.0 or 1.5. (2.5 /1.5) = 1.02g
Z: Highest point of equipment in The base forces associated with the
a structure relative to grade static loads at the C.G. of the equipment
elevation. could be computed as 3.06/1.5 = 2.04g.
h: Average roof height of structure
relative to grade elevation.

For more information visit: www.cutler-hammer.eaton.com CA08104001E


Power Distribution Systems 1.4-23
January 2003 Reference Data
Ref. No. 0109
Seismic Requirements

Final Combined Requirements


10
To better compare all seismic levels 9
and determine the final envelope 8 IBC, New Madrid
7
CH Seismic Envelope

Acceleration (g peak)
seismic requirements, the UBC, CBC, 6
5
BOCA, Y2K IBC for California, Y2K IBC IBC, California
4
for New Madrid area, and Bellcore
final seismic requirements are plotted 3

in Figure 1.4-4. All curves are plotted


2
Equiv. Bellcore
1
at 5% damping.
An envelopment of the seismic levels
in the frequency range of 3.2 Hz to 1.0
.9
100 Hz is also shown. This level is .8
.7
taken as Cutler-Hammer generic seismic .6 BOCA
test requirements for all certifications. .5
UBC and CBC
.4
Eaton’s Cutler-Hammer business per-
.3
formed additional seismic test runs on
the equipment at approximately 120% .2
of the generic enveloping seismic
requirements (see Figure 1.4-5).
The testing is designed to establish .1
additional margin and prepare for 1 2 3 4 5 6 7 8 9 10
10
2 3 4 5 6 7 8 9 10
100
2 3 4 5 6 7 8 9 10
1000
Frequency Hz
future changes in the codes.

Figure 1.4-4. Required Response Spectrum Curve

10
9
8
7 120% of CH Seismic Envelope
Acceleration (g peak)

6
5 CH Seismic Envelope
4

1.0
.9
.8
.7
.6
.5

.4

.3

.2

.1
1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10
10 Frequency Hz 100 1000

Figure 1.4-5. Cutler-Hammer Test Required Response Spectrum Curve

CA08104001E For more information visit: www.cutler-hammer.eaton.com


1.4-24 Power Distribution Systems
Reference Data January 2003
Ref. No. 0110
Seismic Requirements

Product Specific Test Summaries


Table 1.4-27. Distribution Equipment Qualified
for Applications through Seismic Zone 4
Cutler-Hammer Equipment

Low Voltage Panelboards


Pow-R-Line C 1a, 2a, 3a, 4, 5p, F16,
SEISMIC
1
Column Type QUALIFIED
Low Voltage Switchboards
Pow-R-Line C
Pow-R-Line i
Multimeter TEST CERTIFICATE OF SEISMIC WITHSTAND CAPABILITY
Instant
IFS
The Eaton’s Cutler-Hammer equipment identified below was mounted onto a shake table and
Low Voltage Deadfront Switchboards tested in accordance with the earthquake requirements as specified in both the Uniform
Motor Control Centers Building Code and the California Building Code. As required by the codes, the equipment
AdvantageE demonstrated its ability to function after the seismic tests. The seismic capability of the
Series 2100 equipment exceeds the worst-case Zone 4 required levels, as illustrated in the figure below.
FreedomE 2100
Low Voltage Busway
Pow-R-Way and Associated Fittings
Pow-R-Way III and Associated Fittings Metal-Enclosed Low Voltage Switchgear – Magnum
Transfer Switch Equipment
Low Voltage Metal-Enclosed Switchgear
Type DS II
MagnumE
DS-VSR Size 5 Vacuum Starter The frequency sweep
tests revealed that the
Network Protectors lowest equipment natural
Submersible Type CMD and Type CM-22 frequency is:
Wall Mounted
Dry-Type Distribution Transformers 3.5 Hz Indoor
Types EP, EPT, DS, DT3 3.5 Hz Outdoor
Substation Transformers
Dry-Type
Liquid
Unitized Dry-Type Power Centers
750 kVA Maximum
Excitation Control Assemblies
MGR, PRX-400B, WDR1000, WDR2000,
WTA-300B
ECS 2100
3RD PARTY TEST ENGINEER IN CHARGE
Metal-Enclosed Load Interrupter Switchgear SIGNATURE/DATE OF CERTIFICATION/MODIFICATION

Type WLI 5, 15 and 38 kV TESTED BY For interpretation of testing data


Wyle Laboratories refer to Cutler-Hammer
Type WVB 5 and 15 kV September, 2000 Publication SA12501SE
Type MVS 5 and 15 kV
Drawing Number 69A1013H01
Medium Voltage Metal-Clad Switchgear
Type VacClad-W
Metal-Enclosed Non-Segregated Phase Bus
600V, 5 and 15 kV
Medium Voltage Control Figure 1.4-6. Sample Seismic Certificate
AmpgardT National Electrical Code and NEC are
Vacuum Replacement Circuit Breakers registered trademarks of the National
DHP-VR for DHP Switchgear Fire Protection Association, Quincy,
Loadcenters Mass. NEMA is the registered trade-
Heavy Duty Safety Switches mark and service mark of the National
Enclosed Control Electrical Manufacturers Association.
UL and CUL are federally registered
trademarks of Underwriters Laborato-
ries Inc. Uniform Building Code (UBC)
is a trademark of the International
Conference or Building Officials (ICBO).
BOCA is a registered trademark of
Building Officials and Code Adminis-
trators International, Inc. SBCCI is
a registered trademark of Southern
Building Code Congress International.
Equipment Seismic Label

For more information visit: www.cutler-hammer.eaton.com CA08104001E

You might also like