8V 3.2Ah(20hr)

The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte is absorbed by separators and plates and thus immobilized. Should the battery be accidentally overcharged producing hydrogen and oxygen, special one-way valves allow the gases to escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely sealed and is, therefore, maintenance-free, leak proof and usable in any position. Battery Construction
Component Raw material Positive plate Lead dioxide Negative plate Lead Container ABS Cover ABS Safety valve Rubber Terminal Copper Separator Fiberglass Electrolyte Sulfuric acid

General Features
G

Performance Characteristics Nominal Voltage 8V Number of cell 4 Design Life 5 years Nominal Capacity 77oF(25oC) 20 hour rate (0.16A, 7V) 3.2Ah 10 hour rate (0.31A, 7V) 3.1Ah 5 hour rate (0.6A, 7V) 3Ah 1 hour rate (2.2A, 6.4V) 2.2Ah Internal Resistance 21mOhms Fully Charged battery 77oF(25oC) Self-Discharge 3% of capacity declined per month at 20oC(average) Operating Temperature Range Discharge -20~60oC Charge -10~60oC Storage -20~60oC o o 48A(5s) Max. Discharge Current 77 F(25 C) Short Circuit Current Charge Methods: Constant Voltage Charge Cycle use Maximum charging current Temperature compensation Standby use Temperature compensation 160A 77oF(25oC) 2.30-2.35VPC 1.28A -20mV/oC 2.23-2.27VPC -13.2mV/oC

G G G

G G

Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance or water adding. Not restricted for air transport-complies with IATA/ICAO Special Provision A67. UL-recognized component. Can be mounted in any orientation. Computer designed lead, calcium tin alloy grid for high power density. Long service life, float or cyclic applications. Maintenance-free operation. Low self discharge.

Dimensions and Weight Length(mm / inch) Width(mm / inch) Height(mm / inch) Total Height(mm / inch) Approx. Weight(Kg / lbs) 68 / 2.68 49 / 1.93 91 / 3.58 91 / 3.58 0.85 / 1.87

Discharge Constant Current (Amperes at 77oF25oC)


End Point Volts/Cell 1.60V 1.65V 1.70V 1.75V 1.80V 5min 10min 15min 30min 13.1 12.4 11.7 11.0 10.3 8.90 8.47 8.03 7.58 7.13 6.20 5.93 5.64 5.35 5.05 3.80 3.65 3.49 3.32 3.15 1h 2.20 2.12 2.04 1.95 1.85 3h 0.91 0.88 0.85 0.82 0.78 5h 0.65 0.64 0.62 0.60 0.58 10h 0.33 0.32 0.32 0.31 0.30 20h 0.17 0.16 0.16 0.16 0.16

Discharge Constant Power (Watts at 77oF25oC)


End Point Volts/Cell 1.60V 1.65V 1.70V 1.75V 1.80V 5min 10min 15min 30min 45min 23.3 21.9 20.4 19.0 17.6 15.7 14.7 13.8 12.9 12.0 12.00 11.40 10.70 10.00 9.37 7.33 6.97 6.59 6.21 5.82 5.30 5.06 4.80 4.54 4.28 1h 4.10 3.93 3.75 3.56 3.37 2h 2.42 2.35 2.27 2.18 2.08 3h 1.81 1.77 1.72 1.67 1.61 5h 1.24 1.22 1.19 1.17 1.14

(Note)The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values.

page1 of 2

www.vision-batt.com

CP832
Discharge characteristic (25 C)
8.6 8.0 Voltage(v) 7.4 6.6 6.0 60 5.4 40 0 0 1 2 3 5 min Discharge time 10 20 30 60 2 3 5 h 10 20 30 20 0 0.10 0.05 0 140 120 100 80 0.25 0.20 0.15 10.0 9.4 8.6 8.0 7.4 Voltage Current
O

8V3.2Ah

Charged Volume

(%) (XCA) (V)

Constant voltage charging characteristic O (0.25CA,25 C)

CHARGED VOLUME CHARGE VOLTAGE

CHARGING CURRENT

10

12

14

16

18

20

Charging time (hours)

Relationship between charging voltage and temperature


(V/12V) (V/CELL) (V/8V) (V/6V) (V/4V)

Self-discharge characteristic
110 100 Capacity(%) 90 80 70 60 50
o

15.6 15.0 14.4 13.8 13.2

10.4 10.0 9.6 9.2 8.8

7.8 7.5 7.2 6.9 6.6

5.2 5.0 4.8 4.6 4.4

2.6 2.5 2.4 2.3 2.2

Cycl

e Us

S t an db

y Use

-10

10

20

30

40

50

60

40

Ambient temperature( oC)

8 10 12 14 Storage time: months

16

18

20

Life characteristics of Standby use


120

Cycle service life in relation to depth of discharge


120

100

100 Capacity(%) 80 60 40 20 0 200 400 600 800 1000 Number of cycles(cycles) 1200 1400

Capacity(%)

80

60

Testing conditions:floating voltage:2.27 to 2.30V Cell ambient temperature: 25 oC(77 oF)


40

100% D.O.D. 50% D.O.D.

30% Depth of discharge

20

2 Life(year)

Temperature effects on float life


10 120 100 Life(years) Capacity (%) 80 60 40 20 0.1 0 -20

Temperature effects on capacity

2.30V Cell 1

C 0 .0 5 0 .1 C C 2 . 0

1 .0 C 2 .0 C 3 .0 C

10

20

30

40

50

60

-10

10

20

30

40

50( o C)

Temperature( oC)