64 TISH 1-2 HIGH MEDIA TEMP. CONTROLLER YOKOGAWA UT150L-RN YOKOGAWA UT150L TYPE J DUPLEX THERMOCOUPLE TE1-1 (SEE NOTE) 6 B
94 TZ 4-1 MODULATION MOTOR HTR HONEYWELL M7284C1000 HONEYWELL M7284C1000 120 VOLTS 50/60HZ, 27 VA BLACK WHITE BROWN T1 BROWN T2
65
95
125
66
96
126
67
97 +
127
68
98 TIC/TISH/TISL 1-1 MODULATING CONTROLLER YOKOGAWA UT150-AN/AL/RET/Z TO 165 TO BY 1-1 (12) H12
24 VOLTS
128
INPUT 1 69 8 99 AC/DC 10 VOLTAGE CONTROL 14 OUTPUT ALARM 1 N.O. ALARM 2 N.O. 74 3 RSB (+) 4 RSA (-) 76 5 SG 77 107 H3 14 HMT1 13 HI MEDIA TEMP NO 153 NC
G INPUT 4-20MA + H10 129 LO MEDIA LEVEL LML1 H17 H18 9 5 FROM 151 125 TO HOT OIL PUMPS MEDIA CIRCULATION PUMP CIRCULATING PUMP SS130 MOTOR STARTER CIRCUIT OFF ON MC 1-1 H19 OX 130 BREAKER AUXILIARY CONTACT AUXILIARY PUMP 1 SS132 OFF ON H54 OX AUXILIARY PUMP 2 SS133 OFF ON H55 OX AUXILIARY PUMP 3 SS134 OFF ON H56 OX
RED CAM IS LOW FIRE (RED WIRE COMMON & BLUE NO) BLUE CAM IS HIGH FIRE (BLACK/RED COMMON & BLACK/BLUE NO)
70
YOKOGAWA UT150 6 B 14 OUTPUT 4-20MA 15 + FROM 164 TO TZ 4-1 (-) H11 SHLD GND TO 166 TO BY 1-1 (11) H13 FROM 165 SHLD TO TZ 4-1 (F)
MC 1-1 A1 A2
130
71
15
101
131
72
13
12
102
132
MC 7-1 A1 A2
INPUT 1 103 8 -
73
MC 7-2 A1 A2
11 +
133
104
AC/DC 10 VOLTAGE ALARM 1 N.O. ALARM 2 N.O. H4 14 BC1 13 BNR TEMP OFF NO 153 NC
134
MC 7-3 A1 A2
75
AUX.OUT 4-20MA 2
105
13
12
135
OPTIONAL MEDIA CIRCULATION MOTOR CONTROLLER NO 132 NC OPTIONAL MEDIA CIRCULATION MOTOR CONTROLLER NO 133 NC OPTIONAL MEDIA CIRCULATION MOTOR CONTROLLER NO 134 NC
106
11 +
136
78
108
3 TMR STOP
137
TDR-1 FUNCTION: B TIME RANGE: 10 SECONDS SET TIME @ 5 SECONDS H57 TIME DELAY RELAY 3RP1505-1BQ30 B1
138
79
109
139
A1
A2
80
110
140
NOTE: USE PDSL 1-1 WITH TDR-1 ON HCS HEATERS. DO NOT INSTALL TDR-1 ON HC HEATERS.
81
111
82
112
83
113
84
114
85
115
86
116
87
117
88
118
89
NOTE ABOUT THERMOCOUPLES HC HEATERS. Two duplex thermocouples are installed on HC heaters. HC heaters have a manifold with outlets for multiple hot oil circuits. One of the thermocouples is installed in the manifold. The other is installed in the outlet of the helical coil. Although each thermocouple has two independent sensors, only one sensor in each thermocouple is used. Sensor TE1-1 is connected to the high media temperature controller. Sensor TE1-2 is not used. Sensor TE2-1 is connected to the modulating controller. TE2-2 is not used. HCS HEATERS. One duplex thermocouple is installed on HCS heaters. HCS heaters are for single hot oil circuits and do not have a manifold. The thermocouple is installed in the outlet of the helical coil. Both sensors of the thermocouple are used. Sensor TE1-1 is connected to the high media temperature controller. Sensor TE1-2 is connected to the modulating controller.