Okoguard-Okolon TS-CPE Type RHH or RHW-2 or USE-2, VW-1, FT-4, CSA RW-90

Copper Conductor/90C Wet or Dry

UL
R

Okoguard-Okolon TS-CPE is Okonites trade name for its composite insulation system consisting of a layer of EPR and covered with a chlorinated polyethylene (CPE) thermoset compound. The advantages of Okoguard EPR, with a proven track record of over 40 years as a medium voltage insulation, are now offered in low voltage cables. Okolon TS-CPE is Okonite's trade name for its chlorinated polyethylene (CPE) thermoset compound. Okoguard-Okolon TS-CPE 600 Volt Power and Control Cables are recommended for use in all low voltage circuits where continuity of service is the prime consideration. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, directly buried in the earth, or lashed to a messenger for aerial installation. These cables may also be installed in cable tray (size 1/0 AWG and larger per NEC 392.2). Uncoated soft copper per ASTM B-3. Solid per ASTM B-3. Sizes smaller than #8 are compress stranded per ASTM B-8. Sizes #8 and larger are compact stranded per ASTM B-496. Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70 and UL Standards 44 and 854. Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2 or USE-2, VW-1. Sizes 1/0 AWG and larger are also marked sunlight resistant, for use in cable tray. Listed by CSA as RW-90, -40C, FT1 (1/0 and larger: FT4), sunlight resistant.

Sizes 1/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.

Passes the IEEE 383 Vertical Tray Flame Test. (sizes #6 AWG and larger) Passes the IEEE 1202 Vertical Tray Flame Test. (sizes 1/0 AWG & larger) Extreme heat resistance;
90C continuous rating, wet or dry 130C emergency overload rating 250C short circuit rating

Exceptional resistance to deformation at high temperature. Stable electrical properties. Low SIC and power factor. Low moisture absorption. Mechanically rugged. Resistant to weather, most oils, acids and alkalies. More flexible, easier to install and terminate than XLPE insulation.

OKONITE 5 1/0 AWG CU OKOGUARD EP TS-CPE (UL)

UL and CSA Listed.

14-9 8 Uncoated, Copper Conductor Composite Okoguard/Okolon TS-CPE Insulation 6-2 1-4/0 250-500 750-1000

30 45 45 55 65 80

15 15 30 45 65 65

Okoguard-Okolon TS-CPE Type RHH or RHW-2 or USE-2, VW-1, FT-4, CSA RW-90
Copper Conductor/90C Wet or Dry

UL
R

112-24-2061 s 112-24-2071 112-24-2091 s 112-24-2101 112-24-2121 s 112-24-2131 112-24-2171 s 112-24-2191 s 112-24-2221 s 112-24-2251 s 112-24-2311 112-24-2331 s 112-24-2351 s 112-24-2371 112-24-2391 s 112-24-2411 s 112-24-2431 s 112-24-2471 s 112-24-2531 s 112-24-2591 s 112-24-2651
s

14 14 12 12 10 10 9 8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

1 7 1 7 1 7 19 7 7 7 7 19 19 19 19 19 37 37 37 61 61

45 45 45 45 45 45 45 60 75 75 75 100 100 100 100 100 130 130 130 145 145

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.91 1.91 1.91 2.54 2.54 2.54 2.54 2.54 3.30 3.30 3.30 3.68 3.68

0.16 0.17 0.18 0.19 0.20 0.21 0.23 0.27 0.33 0.38 0.43 0.52 0.56 0.60 0.64 0.70 0.80 0.89 1.01 1.21 1.36

4.06 4.57 4.57 4.83 5.08 5.33 5.84 6.86 8.38 9.75 11.00 13.16 14.10 15.14 16.33 17.68 20.32 22.61 25.65 30.73 34.54

23 25 32 34 46 49 58 75 119 173 257 340 414 507 622 766 938 1265 1750 2590 3391

28 30 37 39 51 54 63 82 130

15 15 20 20 30 30 30 55 75

15 15 20 20 30 30 30 50 65

24 24 30 30 42 42 48 55 75

184 95 280 130 372 150 446 170 539 195 654 225 805 260 993 290 1320 350 1827 430 2690 535 3568 615

85 97 115 130 130 156 150 179 175 204 200 242 230 278 255 317 310 384 380 477 475 598 545 689

Visit Okonite's web site, www.okonite.com, for the most up to date dimensions.
Available from our Customer Service Centers. are based on Table 310.16 of the National Electrical Code for these 90C rated conductors at an ambient temperature of 30C. The 75C wet column is provided for additional information. The ampacities shown apply to open runs of cable, installation in any approved raceway, direct burial in the earth, or as aerial cable on a messenger. Derating for more than three current carrying conductors within a raceway is in accordance with NEC Sectiion 310.15.B.2. 5 6 7 Based on three (3) conductors in a single enclosed or exposed conduit. Capacities based on 40C air ambient using ICEA methods. For 30C ambient multiply values by 1.10; for 50C multiply by .90. For other ambients or installation conditions refer to Engineering Data Book EHB. For ampacities in cable tray, see NEC Section 392.11.B.

To order a color other than black, change the last digit of the catalog number as follows: White Red Green 2 3 4 Orange Blue Yellow

Example: To order #14/Sol - Red, the catalog number would be 112-24-2063.