You are on page 1of 33

Explosion Proof - 220V 50 Hz

Prepared for:
Engineered Systems & Products
8121 Virginia Pine Court
Richmond VA 23237
Prepared by:
Automation Controls Inc.
200 Main Street
Newport News VA 23601
ACI Job No: 2008-085
Submittal for
Local Control Panel
Table of Contents
B. Datasheets - Power / Control Components
D. Drawings
C. Datasheets - Field Mounted Components
A. Datasheets - Enclosures / Accessories
E. Bill of Materials
F. Manufacturer Source Information
XP PUSHBUTTON
OPERATORS
(MOMENTARY)
EXPLOSION-PROOF/DUST TIGHT
CLASS I, GROUPS B, C & D;
CLASS II, GROUPS E, F & G;
CLASS III;
NEMA TYPE 4, 4X, 7 & 9
UL 698 Industrial Control Equipment for Use
in Hazardous (Classified) Locations.
UL 1203 Explosion-Proof and Dust-Ignition-
Proof Electrical Equipment for Use in
Hazardous (Classified) Locations.
CSA C22.2 No. 30-M1986 Explosion-Proof
Enclosures for Use in Class I Hazardous
Locations.
FEATURES
Operator bodies are black anodized & teflon-
impregnated.
Operating shafts are stainless steel.
3/4-14 NPSM threaded body size.
Explosion-proof operators are suitable for panel or
surface mount applications.
Long Series: Accommodates up to 2 1/2 thick
enclosure wall thickness.
Short Series: Accommodates up to 1 thick
enclosure wall thickness.
Momentary pushbuttons are available in flush and
extended versions.
Momentary pushbuttons are molded thermoplastic
protected by a machined aluminum guard.
Mushroom Pushbuttons are 1 1/2 dia. aluminum.
See Contact Block Information sheet for mounting
and rating information.
Standard Pushbutton, Mushroom Pushbutton- 2 1/2
centers, Jumbo Mushroom-min. 2 5/8 centers.
AKRON ELECTRIC, INC.
Manufacturers of Explosion-Proof Enclosures & Electrical Systems
www.akronelectric.com
1025 Eagon St. Barberton, Ohio 44203 Ph:(330) 745-8891 Fax:(330) 745-2504 Toll Free:(800) 275-2535
e-mail: sales@akronelectric.com
N
E
W

I
N

S
T
O
C
K
Jumbo Jumbo
Contact Button Standard Standard Standard Mushroom Mushroom
Block Color Flush Extended Mushroom (Red) E-Stop (Red)
No Contact Green XPBSFG XPBSEG XPMHSG XPJMSR XPJMSR (e-stop)
Black XPBSFB XPBSEB
Red XPBSFR XPBSER XPMHSR
1 NO Green XPBSFGA XPBSEGA XPMHSGA
(A) Black XPBSFBA XPBSEBA
Red XPBSFRA XPBSERA XPMHSRA XPJMSRA XPJMSRA (e-stop)
1 NC Green XPBSFGB XPBSEGB XPMHSGB
(B) Black XPBSFBB XPBSEBB
Red XPBSFRB XPBSERB XPMHSRB XPJMSRB XPJMSRB (e-stop)
1 NO/1 NC Green XPBSFGC XPBSEGC XPMHSGC
(C) Black XPBSFBC XPBSEBC
Red XPBSFRC XPBSERC XPMHSRC XPJMSRC XPJMSRC (e-stop)
2 NO/2 NC Green XPBSFGP XPBSEGP XPMHSGP
(P) Black XPBSFBP XPBSEBP
300V Red XPBSFRP XPBSERP XPMHSRP XPJMSRP XPJMSRP (e-stop)
2 NO/ 2 NC Green XPBSFG2C XPBSEG2C XPMHSG2C
(2C)(2BLKS) Black XPBSFB2C XPBSEB2C
600V Red XPBSFR2C XPBSER2C XPMHSR2C XPJMSR2C XPJMSR2C (e-stop)
04/16/03
ORDERING INFORMATION
CATALOG NUMBER
Note: For long barrel operators, substitute L for S.
Example: XPBSFG to XPBLFG
LR86146
FILE NO. E139669
FILE NO. E181300
FILE NO. E203605
XPL SERIES
PILOT LIGHTS
EXPLOSION-PROOF/PIGTAIL STYLE
CLASS I, GROUPS B, C & D;
CLASS II, GROUPS E, F & G; NEMA 4, 4X, 7 & 9
Your search for a high quality XP LED pilot
light is over. We make them in our factory
and they are always kept IN STOCK.
660% LONGER LIFE
than ordinary incandescent bulbs
Extended times between relamping
Higher Quality
Better Price
Always IN STOCK
FEATURES
Explosion-Proof Pilot Lights are suitable for panel
or surface mount applications.
Standard sealed construction and can be relamped
from the front by removal of lens cap.
Fully threaded barrel 3/4-14 NPSM threads.
Corrosion and impact resistant diecast aluminum
lens guard.
SPECIFICATIONS:
XPL Pilot Light Series is equipped with bayonet
base receptacles and 12, 24, 48, 120, 240 volt
LED lamps. LED lamps have an operating life
upwards to 100,000 hours @ 25C ambient
temperature. Specify voltage desired.
Factory installed or field installable transfomer,
terminal or finger safe terminal kits available.
Available light bulb colors are Red, White, Blue,
Green & Amber.
Two lengths available:
Long Series Accommodates up to 2 1/2
enclosure wall thickness
Short Series Accommodates up to 1 1/2
enclosure wall thickness
AKRON ELECTRIC, INC.
Manufacturers of Explosion-Proof Enclosures & Electrical Systems
www.akronelectric.com
1025 Eagon St. Barberton, Ohio 44203 Ph:(330) 745-8891 Fax:(330) 745-2504 Toll Free:(800) 275-2535
e-mail: sales@akronelectric.com
N
E
W

I
N

S
T
O
C
K
SELECT BARREL LENGTH
SB= SHORT BARREL, LB= LONG BARREL
SELECT LED LAMP VOLTAGE
12, 24, 48, 120, 240
SELECT COLOR
R= RED, W= WHITE, B= BLUE, G= GREEN, A= AMBER
EXAMPLE: XPL PILOT LIGHT, SHORT BARREL, RED, 120V
XPLSB-120R
03/03/03
LR86146
ORDER INFORMATION
FILE NO. E203605
See price list for replacement parts available.
XP 2 & 3 POSITION
SELECTOR
SWITCHES
EXPLOSION-PROOF/DUST TIGHT
CLASS I, GROUPS B, C & D;
CLASS II, GROUPS E, F & G;
CLASS III,
NEMA TYPE 4, 4X, 7 & 9
UL 698 Industrial Control Equipment for Use
in Hazardous (Classified) Locations.
UL 1203 Explosion-Proof and Dust-Ignition-Proof
Electrical Equipment for Use in Hazardous (Classified)
Locations.
CSA C22.2 No. 30-M1986 Explosion-Proof Enclosures
for Use in Class I Hazardous Locations.
AKRON ELECTRIC, INC.
Manufacturers of Explosion-Proof Enclosures & Electrical Systems
www.akronelectric.com
1025 Eagon St. Barberton, Ohio 44203 Ph:(330) 745-8891 Fax:(330) 745-2504 Toll Free:(800) 275-2535
e-mail: sales@akronelectric.com
N
E
W

I
N

S
T
O
C
K
Contact Operator Position Part
Block Left Right Number
NONE L --- R XP2SS
L >> R XP2RS
L << R XP2LS
1NO L --- R XP2SSA
(A) L >> R XP2RSA
L << R XP2LSA
1NO/1NC L --- R XP2SSC
(C) L >> R XP2RSC
L << R XP2LSC
2NO/2NC L --- R XP2SSP
(P) L >> R XP2RSP
300V (1 BLOCK) L << R XP2LSP
2NO/2NC L --- R XP2SSD
(D) L >> R XP2RSD
600V (2 BLOCKS) L << R XP2LSD
02/12/03
Order Information 2-Position Order Information 3-Position
LR86146
FILE NO. E139669
FILE NO. E181300
FILE NO. E203605
KEY: --- MAINTAINED
>> SPRING RETURNED FROM LEFT
<< SPRING RETURN FROM RIGHT
Explosion-proof selector switches are
suitable for panel or surface mount applications.
Long Series: Accommodates up to 2 1/2 thick
enclosure wall thickness.
Short Series: Accommodates up to 1 thick
enclosure wall thickness.
FEATURES
Selector switch available in 2 or 3 position.
Operator bodies are black anodized
& teflon-impregnated.
3/4-14 NPSM threaded body size.
Operating shafts are stainless steel.
Contact Operator Position Part
Block Left Center Right Number
NONE L --- C --- R XP3SS
L >> C << R XP3CS
L >> C --- R XP3RS
L --- C << R XP3LS
1 NO L --- C --- R XP3SSA
(A) L >> C << R XP3CSA
L >> C --- R XP3RCA
L --- C << R XP3LSA
1 NO/ 1NC L --- C --- R XP3SSC
(C) L >> C << R XP3CSC
L >> C --- R XP3RSC
L --- C << R XPSLSC
2 NO/ 2NC L --- C --- R XP3SSP
(P) L >> C << R XP3CSP
300V (1 BLOCK) L >> C --- R XP3RSP
L --- C << R XP3LSP
2 NO/ 2NC L --- C --- R XP3SSD
(D) L >> C << R XP3CSD
600V (2 BLOCKS) L >> C --- R XP3RSD
L --- C << R XP3LSD
6-21
DE2
Discount
Schedule 3/00
2000 Square D
All Rights Reserved
6
C
I
R
C
U
I
T

B
R
E
A
K
E
R
S
Thermal-Magnetic Molded Case
100 Ampere Frame
Class 650
q FCL 2-pole circuit breaker built using 3-pole module.
j FCL circuit breakers are not rated for 250 Vdc.
F Frame 100 A, Thermal-Magnetic (240 Vac)
Continuous
Current Rating
@ 40C
AC Magnetic
Trip Settings
Standard Interrupting
Terminal
Wire
Range
Hold Trip Catalog Number Price
1-Pole, 120 Vac
15
20
25
30
275
275
275
275
600
600
600
600
FAL12015
FAL12020
FAL12025
FAL12030
$126.
126.
126.
126.
AL50FA
#14-#4 AWG Cu or
#12-#4 AWG Al
35
40
45
50
60
70
80
90
100
400
400
400
400
800
800
800
900
900
850
850
850
850
1450
1450
1450
1700
1700
FAL12035
FAL12040
FAL12045
FAL12050
FAL12060
FAL12070
FAL12080
FAL12090
FAL12100
126.
126.
126.
126.
126.
166.
166.
166.
166.
AL100FA
#14-#1/0 AWG Cu
or #12-#1/0 AWG Al
2-Pole, 240 Vac
15
20
25
30
275
275
275
275
600
600
600
600
FAL22015
FAL22020
FAL22025
FAL22030
$211.
211.
211.
211.
AL50FA
#14-#4 AWG Cu or
#12-#4 AWG Al
35
40
45
50
60
70
80
90
100
400
400
400
400
800
800
800
900
900
850
850
850
850
1450
1450
1450
1700
1700
FAL22035
FAL22040
FAL22045
FAL22050
FAL22060
FAL22070
FAL22080
FAL22090
FAL22100
211.
211.
211.
211.
211.
345.
345.
345.
345.
AL100FA
#14-#1/0 AWG Cu
or #12-#1/0 AWG Al
3-Pole, 240 Vac
15
20
25
30
275
275
275
275
600
600
600
600
FAL32015
FAL32020
FAL32025
FAL32030
$314.
314.
314.
314.
AL50FA
#14-#4 AWG Cu or
#12-#4 AWG Al
35
40
45
50
60
70
80
90
100
400
400
400
400
800
800
800
900
900
850
850
850
850
1450
1450
1450
1700
1700
FAL32035
FAL32040
FAL32045
FAL32050
FAL32060
FAL32070
FAL32080
FAL32090
FAL32100
314.
314.
314.
314.
314.
447.
447.
447.
447.
AL100FA
#14-#1/0 AWG Cu
or #12-#1/0 AWG Al
F Frame 100 A, Thermal-Magnetic (480 Vac)
Continuous
Current
Rating
@ 40C
AC Magnetic
Trip Settings
Standard
Interrupting
Extra High
Interrupting
Terminal
Wire
Range
FC Lugs
Hold Trip
Catalog
Number
Price
Catalog
Number
Price
1-Pole, 277 Vac, 125 Vdc
15
20
25
30
275
275
275
275
600
600
600
600
FAL14015
FAL14020
FAL14025
FAL14030
$159.
159.
159.
159.
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
AL50FA
#14-#4 AWG Cu or
#12-#4 AWG Al
. . .
35
40
45
50
60
70
80
90
100
400
400
400
400
800
800
800
900
900
850
850
850
850
1450
1450
1450
1700
1700
FAL14035
FAL14040
FAL14045
FAL14050
FAL14060
FAL14070
FAL14080
FAL14090
FAL14100
159.
159.
159.
159.
159.
198.
198.
198.
198.
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
. . .
AL100FA
#14-#1/0 AWG Cu or
#12-#1/0 AWG Al
. . .
2-Pole, 480 Vac, 250 Vdcjq
15
20
25
30
275
275
275
275
600
600
600
600
FAL24015
FAL24020
FAL24025
FAL24030
$387.
387.
387.
387.
FCL24015
FCL24020
FCL24025
FCL24030
$ 919.
919.
919.
919.
AL50FA
#14-#4 AWG Cu or
#12-#4 AWG Al
CU30FA4
1-#14-#10 AWG
CU only
35
40
45
50
60
70
80
90
100
400
400
400
400
800
800
800
900
900
850
850
850
850
1450
1450
1450
1700
1700
FAL24035
FAL24040
FAL24045
FAL24050
FAL24060
FAL24070
FAL24080
FAL24090
FAL24100
387.
387.
387.
387.
387.
500.
500.
500.
500.
FCL24035
FCL24040
FCL24045
FCL24050
FCL24060
FCL24070
FCL24080
FCL24090
FCL24100
919.
919.
919.
919.
919.
1131.
1131.
1131.
1131.
AL100FA
#14-#1/0 AWG Cu or
#12-#1/0 AWG Al
AL100FA4
1-#14-#3 AWG CU
or
1-#12-#1 AWG AL
3-Pole, 480 Vac, 250 Vdcj
15
20
25
30
275
275
275
275
600
600
600
600
FAL34015
FAL34020
FAL34025
FAL34030
$496.
496.
496.
496.
FCL34015
FCL34020
FCL34025
FCL34030
$1149.
1149.
1149.
1149.
AL50FA
#14-#4 AWG Cu or
#12-#4 AWG Al
CU30FA4
1-#14-#10 AWG
CU only
35
40
45
50
60
70
80
90
100
400
400
400
400
800
800
800
900
900
850
850
850
850
1450
1450
1450
1700
1700
FAL34035
FAL34040
FAL34045
FAL34050
FAL34060
FAL34070
FAL34080
FAL34090
FAL34100
496.
496.
496.
496.
496.
587.
587.
587.
587.
FCL34035
FCL34040
FCL34045
FCL34050
FCL34060
FCL34070
FCL34080
FCL34090
FCL34100
1149.
1149.
1149.
1149.
1149.
1413.
1413.
1413.
1413.
AL100FA
#14-#1/0 AWG Cu or
#12-#1/0 AWG Al
AL100FA4
1-#14-#3 AWG CU
or
1-#12-#1 AWG AL
FAL
1-pole
15-100 Amperes
FAL/FHL
2-pole
15-100 Amperes
FAL/FHL/FCL
3-pole
15-100 Amperes
I-LINE is a Registered Trademark of Square D Company or related companies.
Accessories ...........................................................................Pages 6-376-39
Optional Lugs ........................................................................ Pages 6-40, 6-41
Dimensions ...............................................................................Page 6-45, 6-46
Enclosures ..............................................................................Pages 6-476-50
Catalog Numbering System.............................................................. Page 6-23
Interrupting Ratings (kA)
FAL240 FAL480 FCL
240 V 10 18 (1P), 25 (2, 3P) 100
480 V . . . 18 65
600 V . . . . . . . . .
Thermal-magnetic molded case circuit breakers
shown on Pages 6-21 thru 6-25 are permanent trip UL
Listed, CSA certied, IEC rated, and also meet the
requirements of Federal Specication WC375B/GEN
as indicated on Pages 6-4 thru 6-8. For I-LINE

molded
case circuit breakers, see listings on Pages 8-248-34.
6-41
DE2
Discount
Schedule 3/00
2000 Square D
All Rights Reserved
6
C
I
R
C
U
I
T

B
R
E
A
K
E
R
S
Molded Case Lugs
Class 690

f Unless otherwise specied, wire sizes apply to both aluminum and copper conductors.
k All P-frame circuit breakers require terminal pads for mounting lugs of any type. See Page 6-40.
t These lug kits cannot be used on I-LINE

circuit breakers.
Power Distribution Connectors for Circuit Breakers for Field Replacement of Mechanical Lugs
UL Listed Field-installable VERSAtile Lug Kits
Circuit Breaker
Type
VERSAtile
System Rangef
Dimension
A
(In)
VERSA-
CRIMP

Tool Type
Max.
Lugs
Per
Terminal
Kit
Catalog
Number
Lug
Qty.
Per Kit
Price
Per
Kit
Aluminum Compression Lug Kits
EDB, EGB, EJB,
FD, FG, FJ
#8-#1/0 AWG 1.375 VC-6 Series 1 VC100FD 3 $ 65.
FA, FH, FC, FI #8-#1/0 AWG 1.3 VC-6 Series 1 VC100FA 3 65.
KA, KH, KC, KI #4 AWG-300 kcmil 1.5 VC-6 Series 1 VC250KA3 3 123.
KA, KH, KC, KI 250-350 kcmil 1.5 VC-6 Series 1 VC250KA35 3 123.
LA, LH, Q4 250-350 kcmil 1.25 VC-6 Series 2 VC400LA35 2 123.
LA, LH, Q4 #4 AWG-300 kcmil 1.0 VC-6 Series 2 VC400LA3 2 123.
LA, LH, Q4 #2/0 AWG-500 kcmil 2.2 VC-6 Series 1 VC400LA5 1 60.
LA, LH, Q4
500-750 kcmil Al or 500
kcmil Cu
2.5
VC-6 FT or
VC-8
1 VC400LA7 1 82.
LC, LI, LE, LX, LXIt #4 AWG-300 kcmil 1.05 VC-6 Series 2 VC600LI3 2 83.
LC, LI, LE, LX, LXIt #2/0 AWG-500 kcmil 3.20 VC-6 Series 2 VC600LI5 2 85.
LC, LI, LE, LX, LXIt 500-750 kcmil 3.45
VC-6FT or
VC-8C
1 VC600LI7 1 85.
ME2, MX2 #4 AWG-300 kcmil 1.5 VC-6 Series 1 VC250ME3 3 123.
ME2, MX2 250-350 kcmil 1.5 VC-6 Series 1 VC250ME35 3 123.
ME4, MX4 #2/0 AWG-500 kcmil 2.2 VC-6 Series 1 VC400ME5 1 60.
ME4, MX4
500-750 kcmil Al or 500
kcmil Cu
2.5
VC-6 FT or
VC-8
1 VC400ME7 1 82.
MA, MH, ME, MX #2/0 AWG-500 kcmil 1.9 VC-6 Series 2 VC600MA5 2 186.
MA, MH, ME, MX
500-750 kcmil Al or 500
kcmil Cu
2.1
VC-6 FT or
VC-8
2 VC800MA7 2 198.
NA, NC, NE, NX #2/0 AWG-500 kcmil 3.3 VC-6 Series 4 VC1200NE5 4 598.
NA, NC, NE, NX
500-750 kcmil Al or 500
kcmil Cu
3.6
VC-6 FT or
VC-8
4 VC1200NE7 4 598.
PAF, PHF, PXF, PEFk #2/0 AWG-500 kcmil k VC-6 Series 6-8 VC2000PA5 1 61.
PAF, PHF, PCFk
PXF, PEF
500-750 kcmil Al
or 500 kcmil Cu
k
VC-6 FT or
VC-8
6-8 VC2500PA7 2 61.
Copper Compression Lug Kits
EDB, EGB, EJB,
FD, FG, FJ
#6-#1/0 AWG 1.375 VC-6 Series 1 CVC100FD 3 $ 65.
FA, FH, FC, FI #6-#1/0 AWG Cu 1.4 VC-6 Series 1 CVC100FA 3 65.
KA, KH, KC, KI #2/0 AWG-300 kcmil Cu 1.5 VC-6 Series 1 CVC250KA3 3 124.
LA, LH, Q4 #2/0 AWG-300 kcmil Cu 1.3 VC-6 Series 2 CVC400LA3 2 124.
LA, LH, Q4 250-500 kcmil Cu 2.3 VC-6 Series 1 CVC400LA5 1 60.
LC, LI, LE, LX, LXIt 250-500 kcmil 3.20 VC-6 Series 1 CVC600LI5 1 85.
ME4, MX4 250-500 kcmil Cu 2.6 VC-6 Series 1 CVC400ME5 1 60.
MA, MH, ME, MX 250-500 kcmil Cu 2.4 VC-6 Series 2 CVC600MA5 2 186.
NA, NC, NE, NX 250-500 kcmil Cu 3.3 VC-6 Series 4 CVC1200NE5 4 599.
NA, NC, NE, NX 500-750 kcmil Cu 3.6 VC-6 Series 4 CVC1200NE7 4 599.
Can be used for multiple load connections on one circuit breaker. Use in place of
standard distribution blocks to save space and time.
Field-installable kits, including tin plated aluminum connectors and all necessary
mounting hardware are available for Square D FA, KA, LA, Q4, MA, ME and MX
molded case circuit breakers.
Connectors are UL Listed:
For use on OFF end of circuit breaker when the OFF end is the load end.
For use in UL508 Industrial Control applications only.
For copper wire only.
q Not for use with I-LINE mounted circuit breakers.
u When using ne stranded wire, increased cross sectional area may cause maximum wire size to be reduced.
Use
With
Circuit Breakerq
Cicuit
Breaker
Ampere
Rating
Number of Wires
Per Terminal
& Wire Rangeu
Catalog
Number
Lug
Quantity
Per Kit
Dimension
A
(In.)
Price
Per
Kit
FAL, FHL, FCL
15-100 6-#14-#6 AWG Cu PDC6FA6 3 1.0 $ 58.
15-100 3-#14-#2 AWG Cu PDC3FA2 3 1.2 58.
KAL, KHL
70-250 6-#14-#4 AWG Cu PDC6KA4 3 1.0 109.
70-250
2-#14-#1 AWG Cu
1-#12-#2/0 AWG Cu
PDC3KA20 3 1.5 109.
LAL, LHL, Q4L
125-400
6-#12-#2/0 AWG Cu
12-#14-#4 AWG Cu
PDC6LA20
PDC12LA4
1
1
2.25
1.25
82.
125-400
3-#14-#2 AWG Cu
1-#2-250 kcmil Cu
PDC4LA250 1 2.0 82.
MAL, MHL,
MEL, MXL
125-1000
6-#12-#2/0 AWG Cu
12-#14-#4 AWG Cu
PDC6MA20
PDC12MA4
1
1
0.0
0.0
82.
FAL Circuit Breaker
With Three PDC6FA6 Installed.
MAL Circuit Breaker
With Three PDC6MA20 Installed
CVC100FA VC250KA3 CVC400LA5 VC400LA7
PDC6FA6
PDC6KA4
PDC12LA4
VERSA-CRIMP and I-LINE are Registered Trademarks of Square D Company.
VERSAtile is a Trademark of Square D Company.
Extremity
of
Molded Case
w/Mechanical
Lugs
A See Table
Crimp lug or
power distribution connectors
extension past
end of
circuit breaker
A See Table
VC1200NE5
CVC600MA5
2001 Schneider Electric All Rights Reserved 1
Bulletin No. 8291-0014D
October 2001
Raleigh, NC USA
The SDSA1175 Secondary Surge Arrester is designed and listed for
indoor or outdoor installation and surge protection of single-phase three-
wire 120/240 Vac 60 Hz electrical services and major appliances. Two
SDSA1175 Secondary Surge Arresters can be installed to provide
protection on 208Y/120 Vac three-phase four-wire services.
NOTE: Use on solidly grounded systems only.
CAUTION
HAZARD OF EQUIPMENT DAMAGE.
Megger

or hi-potential tests will damage this surge protective device.


Turn off all power supplying the equipment and isolate the surge
protective device before testing.
Failure to follow these precautions can result in equipment
damage.
INTRODUCTION
PRECAUTIONS
SDSA1175 Series 001
Secondary Surge Arrester
Instruction Bulletin
DANGER
HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION.
This equipment must be installed and serviced only by qualified
electrical personnel in accordance with National and Local Electrical
Codes.
Turn off all power supplying this equipment before working on or
inside equipment.
Always use a properly rated voltage sensing device to confirm power
is off.
Replace all devices, doors, and covers before turning on power to
this equipment.
Do not apply petroleum-based products to non-metallic parts.
Failure to follow these instructions will result in death or serious
injury.
2001 Schneider Electric All Rights Reserved 2
Bulletin No. 8291-0014D
October 2001
SDSA1175 Series 001 Secondary Surge Arrester
Instruction Bulletin
INSTALLATION
0.5 in. [13 mm] knockout (trade size)
Actual hole size .875 in. [22 mm]
Nut
Figure 1: Mounting SDSA Unit
NOTE: The secondary surge arrester must
be installed in an accessible location (not
within walls). When installing secondary
surge arrester inside a QO or HOM load
center, do not remove an enclosure
knockout. Use optional QOSAMK surge
arrester mounting kit. Refer to instructions
included with the QOSAMK kit.
1. Turn off all power supplying this equipment before working on or
inside equipment.
2. See Figure 1.
3. Confirm SDSA is rated for your system by comparing voltage
measurements to the Line Voltage (L-L, L-N) on the product label.
4. Install in accordance with article 280 of the National Electric Code.
5. Confirm that the electrical terminals used to attach this device are
identified for these conductors.
6. Twist conductors 1/2 turn or more for every 12 inches of length.
7. Keep conductor length as short as possible with no sharp bends.
8. Do not loop or coil wires.
9. Ensure a high quality ground is in place.
10. Install cover and/or close door on equipment.
Diagnostic Operation
LED ON = Normal operation
LED OFF = Fault, check phase voltage, breakers (if used) and
connections. If OK, replace unit. (see Figure 3)
General Specifications
Product Catalog No. SDSA1175
Max Surge Current 36 kA/Phase
Housing Rating Type 4X
Product Weight .525 lb
Connection Method Parallel, #14 AWG Stranded Wire
Thermal Fusing Yes
Operating Temperature -40 to +160F (-40 to +70C)
Operating Frequency 50/60 Hz
Diagnostics Green Status LED
Product Standards UL 1449-2nd Ed, cUL, ANSI/IEEE C62.11
Surge Arrester/TVSS
ON = OK
Figure 3: Diagnostic Operation
OFF = Fault
Figure 2: Wiring Diagrams
Single-phase
Three-wire 120/240 Vac
Two Surge Arresters on 208Y/120 Vac
Three-phase Four-wire Service
Black
Black
White
Black
Black
White
Black
Black
White
Square D
8001 Hwy 64 East
Knightdale, NC 27545 USA
1-888-SquareD (1-888-778-2733)
www.SquareD.com
Electrical equipment should be serviced only by qualified personnel. No responsibility is
assumed by Schneider Electric for any consequences arising out of the use of this material.
This document is not intended as an instruction manual for untrained persons.
2.250
[57]
2.250
[57]
2.685
[68]
1.935
[49]
Figure 4: Dimensions
Dimensions:
in.
[mm]
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
8
I
E
C

C
O
N
T
A
C
T
O
R
S

A
N
D

S
T
A
R
T
E
R
S
18-2 2007 Schneider Electric
All Rights Reserved
Contactors &
Overload Relays
TeSys D-Line Non-reversing
Refer to Catalog 8502CT9901

a Complete catalog number with coil voltage code from table on page 18-3; example, LC1D09G7.
b For DC version of these devices replace the 'C' with 'P' (ex LC1D40004**) becomes LP1D40004**).
c On LC1D09 - LC1D32 and LC1DT20 through LC1DT40, for ring tongue versions add '6' to the catalog number prior to adding the voltage code
(ex, LC1D09G7 becomes LC1D096G7). No Price adder for this modification.
d On LC1D09 - LC1D32, for spring terminals versions add '3' to the catalog number prior to adding the voltage code (ex., LC1D09G7 becomes
LC1D093G7). No price adder for this modification.
D-Line contactor accessories . . . . . . . . . . . . . . . . . . . . . . pages 18-6 to 18-9
D-Line overload relay accessories. . . . . . . . . . . . . . . . . . . . . . . . . page 18-14
D-Line replacement coils . . . . . . . . . . . . . . . . . . . . . . . . pages 18-16 to 18-18
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 18-40 to 18-46
LC1D09
LC1D093
LC1D115
LRD22
Table 18.1: 3- or 4-Pole Screw Terminal Connections
Maximum Horsepower Ratings
Maximum Current
Utilization
Categories
No of Poles
Instantaneous
Auxiliary
Contacts
Catalog
Number a
$ Price
Single Phase Three Phase
Inductive
AC3
Amperes
Resistive
AC1
Amperes
N.O. N.C. N.O. N.C.
115 V
hp
230 V
hp
200 V
hp
230 V
hp
460 V
hp
575 V
hp
AC Coils DC Coils
0.5 1 2 2 5 7.5 9
20
3
0
1 1
LC1D09 cd 94.00 119.00
4 LC1DT20 c 94.00 119.00
2 2 LC1D098 c 94.00 119.00
1 2 3 3 7.5 10 12
25
3
0
1 1
LC1D12 cd 119.00 149.00
4 LC1DT25 c 119.00 149.00
2 2 LC1D128 c 119.00 149.00
1 3 5 5 10 15 18
32
3
0
1 1
LC1D18 cd 136.00 160.00
4 LC1DT32 c 149.00 183.00
2 2 LC1D188 c 149.00 183.00
2 3 7.5 7.5 15 20 25
40
3
0
1 1
LC1D25 cd 151.00 181.00
4 LC1DT40 c 193.00 240.00
2 2 LC1D258 c 193.00 240.00
2 5 10 10 20 30 32 50 3 0 1 1 LC1D32 cd 172.00 213.00
3 5 10 10 30 30 40
60
3
0
1 1 LC1D40 296.00 275.00
4
0 0
LC1D40004 b 296.00 353.00
2 2 LC1D40008 b 296.00 353.00
3 7.5 15 15 40 40 50
80
3
0 1 1
LC1D50 234.00 291.00
5 10 20 20 50 50 65 3 LC1D65 322.00 379.00
4 0
0 0
LC1D65004 b 446.00 503.00
2 2 LC1D65008 b 446.00 503.00
7.5 15 25 30 60 60 80
125
3
0
1 1 LC1D80 363.00 420.00
4
0 0
LC1D80004 b 489.00 524.00
2 2 LC1D80008 b 489.00 524.00
30 40 75 100 115
200
3
0
1 1
LC1D115 479.00 479.00
40 50 100 125 150 3 LC1D150 696.00 696.00
4 0 0 LC1D115004 630.00 630.00
Table 18.2: D-Line Overload Relays Ambient Compensated, Bi-Metallic Direct Mount
Current Setting
Range Amperes
For Direct Mounting
to LC1ttt
Class 10 with
Single Phase
Sensitivity
Class 10 without
Single Phase
Sensitivity
Class 20 with
Single Phase
Sensitivity
Class 20 without
Single Phase
Sensitivity
$ Price
0.100.16
D09D32
LRD01 LR3D01
60.00
0.160.25 LRD02 LR3D02
0.250.40 LRD03 LR3D03
0.400.63 LRD04 LR3D04
0.631 LRD05 LR3D05
11.6 LRD06 LR3D06
1.62.5 LRD07 LR3D07
2.54 LRD08 LR3D08 LRD1508 LR3D1508A1
46 LRD10 LR3D10 LRD1510 LR3D1510A1
5.58 D09D32 LRD12 LR3D12 LRD1512 LR3D1512A1
62.00
710 D09D32 LRD14 LR3D14 LRD1514 LR3D1514A1
913 D12D32 LRD16 LR3D16 LRD1516 LR3D1516A1
1218 D18D32 LRD21 LR3D021 LRD1521 LR3D1521A1
1624 D25D32 LRD22 LR3D22
1725 D25D32 LR3D1522A1
2332 D25D32 LRD32 LR3D32
73.00
2328 D25D32 LRD1530 LR3D1530A1
2532 D25D32 LRD1532 LR3D1532A1
3038 D32 LRD35 LR3D35
1725 D40D80 LRD3322 LR3D3322 LR2D3522 LR3D3522
107.00
2332 D40D80 LRD3353 LR3D3353 LR2D3553 LR3D3553
3040 D40D80 LRD3355 LR3D3355 LR2D3555 LR3D3555
3750 D50D80 LRD3357 LR3D3357 LR2D3557 LR3D3557
4865 D50D80 LRD3359 LR3D3359 LR2D3559 LR3D3559
5570 D65D80 LRD3361 LR3D3361 LR2D3561 LR3D3561
127.00 6380 D65D80 LRD3363 LR3D3363 LR2D3563 LR3D3563
80104 D80 LRD3365
80104 D115D150 LRD4365
362.00 95120 D115D150 LRD4367
110140 D150 LRD4369
Table 18.3: D-Line Overload Relays Solid State
Current Setting Range Amperes
For Direct Mounting Beneath
Contractor LC1
Class 10 Class 20 $ Price
60100 D115D150 LR9D5367 LR9D5567 298.00
90150 D115D150 LR9D5369 LR9D5569 298.00
I12
Discount
Schedule
Modified
1/21/08
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
8
I
E
C

C
O
N
T
A
C
T
O
R
S

A
N
D

S
T
A
R
T
E
R
S
2007 Schneider Electric
All Rights Reserved
18-3
Contactors &
Overload Relays
TeSys F-Line Non-reversing
Refer to Catalog 8502CT9901
a Complete part number by adding coil voltage code from table below. For example: LC1F115G7. All contactors (except F780) include 1 N.O. coil
interlock contact.
b When mounting overload relays LR9F557 to LR9F571 directly beneath the contactor, supporting the relays with a mounting plate is recommended.
With overload relays LR9F775 to LR9F781, use of a support mounting plate is mandatory.
c IEC standard 60947-4 specifies the following trip times when the overload relay senses 7.2 times the setting current:
Class 10 between 4 and 10 seconds
Class 20 between 6 and 20 seconds
d Interconnection kit LA7F407 is required to mount an LR9F71 to an LC1F185.
e Not available for LC1D40 - LC1D150
f Not available for LC1D115 or LC1D150
g Not available for LC1F780
The 600 V coils for the LC1F400 - LC1F630 do not include an auxiliary contact for holding circuits.
h For additional voltage codes refer to the IEC Contactor and Starter Catalog 8502CT9901.
i For use with F265F330 only.
F-Line contactor accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 18-9
F-Line overload relay accessories . . . . . . . . . . . . . . . . . . . . . . . . .page 18-14
F-Line replacement coils and parts . . . . . . . . . . . pages 18-11, 18-17, 18-19
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 18-42 to 18-49
LC1F115
Table 18.4: 2-, 3-, and 4-Pole Contactors
Standard power ratings of 3-phase motors 50/60 Hz in
category AC-3
Maximum Current
Number of
Poles
Catalog
Number a
$ Price 200 V
208 V
220 V
240 V
460 V
480 V
575 V
600 V
AC-3 AC-1
Panel Mount with Screws
HP HP HP HP A A
30 40 75 100 115 200
3 LC1F115 479.00
4 LC1F1154 630.00
40 50 100 125 150 250
3 LC1F150 696.00
4 LC1F1504 825.00
50 60 125 150 185 275
3 LC1F185 938.00
4 LC1F1854 1439.00
Current Rated 225 315
3 LC1F225 1167.00
4 LC1F2254 1935.00
60 75 150 175 265 350
3 LC1F265 1179.00
4 LC1F2654 1646.00
75 100 200 250 330 400
3 LC1F330 1621.00
4 LC1F3304 1846.00
100 125 250 300 400 500
2 LC1F4002 1521.00
3 LC1F400 1874.00
4 LC1F4004 2133.00
150 200 400 500 500 700
2 LC1F5002 4324.00
3 LC1F500 4970.00
4 LC1F5004 5617.00
250 300 600 800 630 1000
2 LC1F6302 5917.00
3 LC1F630 6872.00
4 LC1F6304 7582.00
Current Rated 780 1600
3 LC1F780 7788.00
4 LC1F7804 9940.00
450 800 900 800 1000 3 LC1F800 6676.00
Table 18.5: 3-Phase Overload Relays Solid State Separate Mount b
Current Setting Range
Amps
For Direct Mounting to Contactor
LC1/CR1F
Class 10 Trip c
Catalog Number
Class 20 c
Catalog Number
$ Price
3050 F115F185 LR9F5357 LR9F5557 298.00
4880 F115F185 LR9F5363 LR9F5563 298.00
60100 F115F185 LR9F5367 LR9F5567 298.00
90150 F115F185 LR9F5369 LR9F5569 298.00
132220 F185 d F265 LR9F5371 LR9F5571 298.00
200330 F265F500 LR9F7375b LR9F7575b 333.00
300500 F265F500 LR9F7379b LR9F7579b 737.00
380630 F400F630 LR9F7381b LR9F7581b 905.00
Table 18.6: Coil Voltage Codes h
Contactor Hz 24 V 48 V 110 V 120 V 125 V 208 V 220 V 240 V 250 V 440 V 480 V 600 V
AC
D09D150 50/60 B7 E7 F7 G7 LE7 M7 U7 T7 e X7 ef
LC1D40LC1D150 only
60 B6 E6 F6 G6 L6 M6 U6 T6 X6 f
50 B5 E5 F5 M5 e U5
F115, F150, and F185
50 B5 E5 F5 M5 U5
60 B6 E6 F6 G6 L6 M6 U6 Q5 SC
F265, and F330 40400 B7 E7 F7 G7 L7 M7 U7 S7i X7
F400 F780 40400 E7 F7 G7 L7 M7 U7 N7 X7 g
DC
D09D32 Low Consumption BL EL FL ML UL
D09D150 BD ED FD GD MD UD RD
F115-F330 BD ED FD GD MD UD RD
F400F780 ED FD GD MD UD RD
Table 18.7: Coil Voltage Codes for AC and DC Voltages for F800 (includes built-in surge supressor)
Volts AC/DC 24 48 110 120 127 208 220 240 277 380 415 440 480 575 600 660
50/60 HZ FW FW FW MW MW QW QW QW
I12
Discount
Schedule
Modified
1/21/08
16-19
TeSys Overload Relays
D-Line Bimetallic
2004 Schneider Electric
All Rights Reserved
6/14/04
www.SquareD.com
For the most up-to-date information
1
6
I
E
C

S
T
Y
L
E

C
O
N
T
A
C
T
O
R
S

A
N
D

S
T
A
R
T
E
R
S

Ambient Compensated bi-metallic overload relays
LRD overload relays are designed for direct mounting to D-line contactors. To mount these overloads separately,
select separate mount kits from the table below.
a When using mounting plates, separate mounting kits are also required.
b Part number to be completed by adding coil voltage code.
c The time that the LA7D03 can remain energized depends on its rest time; 1 s pulse wth 9 s rest time; 5 s pulse with 30 s rest time; 10 s pulse with
90 s rest time; maximum pulse duration of 20 s with rest time of 300 s. Consumption on inrush and sealed : < 100 VA
d Not available for LRD01-D32, LR3D01-D32.
D-Line overload relays
Current Setting
Range
Amperes
For direct
mounting to
LC1ttt
Class 10 with
Single Phase
Sensitivity
Class 10 without
Single Phase
Sensitivity
Class 20 with
Single Phase
Sensitivity
Class 20
without Single Phase
Sensitivity
Price
.10.16 D09D32 LRD01 LR3D01 . . . . . .
$ 60.00
.16.25 D09D32 LRD02 LR3D02 . . . . . .
.25.40 D09D32 LRD03 LR3D03 . . . . . .
.40.63 D09D32 LRD04 LR3D04 . . . . . .
.631 D09D32 LRD05 LR3D05 . . . . . .
11.6 D09D32 LRD06 LR3D06 . . . . . .
1.62.5 D09D32 LRD07 LR3D07 . . . . . .
2.54 D09D32 LRD08 LR3D08 LRD1508 LR3D1508A1
46 D09D32 LRD10 LR3D10 LRD1510 LR3D1510A1
5.58 D09D32 LRD12 LR3D12 LRD1512 LR3D1512A1
62.00
710 D09D32 LRD14 LR3D14 LRD1514 LR3D1514A1
913 D12D32 LRD16 LR3D16 LRD1516 LR3D1516A1
1218 D18D32 LRD21 LR3D21 LRD1521 LR3D1521A1
1624 D25D32 LRD22 LR3D22 . . . . . .
1725 D25D32 . . . . . . LRD1522 LR3D1522A1
2332 D25D32 LRD32 LR3D32 . . . . . .
73.00
2328 D25D32 . . . . . . LRD1530 LR3D1530A1
2532 D25D32 . . . . . . LRD1532 LR3D1532A1
3038 D32 LRD35 LR3D35 . . . . . .
1725 D40D80 LRD3322 LR3D3322 LR2D3522 LR3D3522
107.00
2332 D40D80 LRD3353 LR3D3353 LR2D3553 LR3D3553
3040 D40D80 LRD3355 LR3D3355 LR2D3555 LR3D3555
3750 D50D80 LRD3357 LR3D3357 LR2D3557 LR3D3557
4865 D50D80 LRD3359 LR3D3359 LR2D3559 LR3D3559
5570 D65D80 LRD3361 LR3D3361 LR2D3561 LR3D3561
127.00 6380 D65D80 LRD3363 LR3D3363 LR2D3563 LR3D3563
80104 D80 LRD3365 . . . . . . . . .
80104 D115D150 LRD4365 . . . . . . . . .
362.00 95120 D115D150 LRD4367 . . . . . . . . .
110140 D150 LRD4369 . . . . . . . . .
Mounting Kits and Platesa
Description For use with overload relays: Catalog Number Price
Separate mounting kits for mounting to 35 mm
omega rail or for panel mounting with screws
LRD0135 and LR3D0135 LAD7B10 $ 8.70
LRD15tt LAD7B105 10.40
LR2D15tt LA7D1064 8.70
LR2D25tt LA7D2064 13.10
LRD3ttt, LR3D3ttt, LR2D35tt LA7D3064 17.50
Mounting plates for screw mounting
at 110 mm (4.3") centers
LRD0135, LR3D0135, LR2D15tt DX1AP25 11.00
LR2D25tt DX1AP26 12.00
LRD3ttt, LR3D3ttt, LR2D35tt LA7D902 16.40
Accessories
Description For use with
Standard
Packaging
Catalog
Number
Price
Pre wiring kit allows direct connection of the N.C. contact
of relay LRD01D32 or LR3D01D32 to the contactor
LC1D09 through D18 10 LAD7C1 $ 8.70
LC1D25, D32 10 LAD7C2 8.70
Stop button locking device All relays except LRD01D32, LR3D01D32 and LR9D 10 LA7D901 2.20
Remote stop/tripping or electrical resetc
LRD01D32, LR3D0132 1 LAD703b 43.70
All relays except LRD01D32, LR3D01D31 1 LA7D03b 43.70
Reset by exible cable 500 mm (19.6 in.) LRD01D32 1 LAD7305 100.00
Control Circuit Voltages for LA7D03 and LAD703
Volts 12 24 48 110 220/230 380/400 415/440
AC 50/60 Hz Jd B E F M Q N
DC J B E F M . . . . . .
LRD22
LA7D901
LA7D03
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16-30
For additional information, reference Catalog #8502CT9901R5/03.
6/14/04
I12
Discount
Schedule
www.SquareD.com
FOR CURRENT INFORMATION
15-6 2/02
2002 Schneider Electric
all rights reserved
Accessories
Auxiliary Contacts, Time Delay, Mechanical Latch
1
5
I
E
C

S
T
Y
L
E

C
O
N
T
A
C
T
O
R
S

A
N
D

S
T
A
R
T
E
R
S
a Including 1 N.O. + 1 N.C. make before break contacts.
b 1 block only can be mounted on the LC1/LP1 D25 and D32; 2 blocks can be mounted on the LC1/LP1 D40 to D80.
c 1 block may be added to each side of the contactor, see limitations below
d For low consumption coils only one 2 front mounted two contact block allowed. No side mounted contact blocks allowed.
e Device supplied with 4 grounding terminal points.
f Scale range is expanded between 0.1 and 0.6 seconds on the dial for more accurate settings at the lower end of the range.
g With switching time of 40 ms 15 ms between the opening of the N.C. contact to the closing of the N.O. contact.
h Does not include internal coil clearing contact.
i Coil Voltages for LA6 DK mechanical latch blocks
Standard, instantaneous auxiliary contact blocks
Snap-On
Mounting
Number of
Contacts
Composition
Catalog Number Price
N.O. N.C.
To the front of
LC k D09 to D150d
4
2 2 LADN22 $40.10
1 3 LADN13 40.10
4 0 LADN40 40.10
0 4 LADN04 40.10
3 1 LADN31 40.10
2 2 LADC22 a 40.10
2
1 1 LADN11 20.00
2 0 LADN20 20.00
0 2 LADN02 20.00
To the front of
LC k D25 to D150
1 1 0 LADN10 b 12.70
0 1 LADN01 b 12.70
To the side of
LC k D09 to D150
2 1 1 LAD8N11c 20.00
2 0 LAD8N20c 20.00
Instantaneous blocks with dusttight auxiliary contacts (IP54) NEMA Type 12
Snap-On
Mounting
Standard
Contacts
Dusttight
Contacts
Catalog Number Price
N.O. N.C. N.O. N.C.
To the front of
LC k D09 to D80
LP k D09 to D80
... ... 2 ... LA1DX20 $63.
2 ... 2 ... LA1DZ40 79.
1 1 2 ... LA1DZ31 79.
... ... 2 ... LA1DY20e 74.
Pneumatic time delay contact blocks
Snap-On
Mounting
Time Delay
Contacts
Type
Range of
Time Delay
Catalog
Number
Price
To the front of
LCkD09 to D150
LPkD09 to D150
1 1
On
energization
(on delay)
0.1 to 3 s f LADT0 $127.
0.1 to 30 s LADT2 127.
10 to 180 s LADT4 127.
1 to 30 sg LADS2 127.
1 1
On
de-energization
(off-delay)
0.1 to 3 s f LADR0 127.
0.1 to 30 s LADR2 127.
10 to 180 s LADR4 127.
Mechanical latch blocks with manual or electrical unlatch
Front snap-on
mounting onto
Application
Catalog number
to be completed
by the code corresponding
to the coil voltage
Price
LCk/LPk D09 to D65 For silent operation and energy conservation LA6DK10ih $74.
LC1 D80 to D150
LP1 D80
For silent operation and energy conservation LA6DK20ih 74.
Volts 12 24 32/36 42/48 60/72 100 110/127 200/208 220/240 380/415 440/480 500/600
AC or DC J B C E EN K F L M Q R S
Front Mounted
Auxiliary Blocks
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 15-2515-27
For additional information, reference Catalog #8502CT9901R2/01 or D-FAX

#5497, 5498, 5799, 5500, 5501, 5502.


I12
Discount
Schedule
6-42
DE2
Discount
Schedule 3/00
2000 Square D
All Rights Reserved
6
C
I
R
C
U
I
T

B
R
E
A
K
E
R
S
QOU Unit Mount
Miniature Circuit Breakers
Class 720
k Terminal lug wire size 1 #14 - #2 AWG Cu or Al.
k Reversible line and load lugs for convenient ush or
surface mount wiring.
k DIN mount (symmetrical rail 35 x 7.5 DIN/EN 50 022).
k UL Listed as HACR type 15-70 A.
k Field installable quick connectors.
k Single handle with internal common trip.
k UL Listed 48 Vdc (5,000 AIR).
k Bulk pack circuit breakers do not have mounting feet
included.
Special Ordering Instructions:
For Bulk Packed QOU Circuit Breakers and
Accessories
QOU circuit breakers and accessories must be ordered in
multiples of the quantities listed. Units provided in
standard quantity of one are individually packaged:
standard quantities greater than one are bulk packed. Bulk
packed circuit breakers do not include mounting brackets.
EXAMPLE:
Individual pack small quantity orders: To receive ve
QOU220 circuit breakers, order ve individual QOU220
circuit breakers at $55.00 each. Product will be individually
packaged, and will include necessary mounting feet.
Bulk pack large quantity order. To order 440 QOU220
circuit breakers using bulk packaging, order 440
QOU220B at $53.00 each. Product will be packaged in 22
packages of 20 pieces each. Product will not include
mounting feet. To order mounting feet, order 880 pieces of
QOUMFB2. Product will be packaged in eleven packages
of 80 pieces each.
For QOUQ Low Amp Circuit Breakers with Four Point
Quick Connect Terminals
QOUQ Low Amp circuit breakers with four point quick
connect terminals are provided with permanent factory
installed terminals which are afxed to the Load or OFF
end of the circuit breaker. This special terminal will
accommodate up to four 1/4 inch female quick connect
wire terminations. Total ampacity of these connections
must not exceed the rating of the circuit breaker. Price
addition is $5.60 for single-pole, $11.20 for 2-pole and
$16.80 for 3-pole circuit breakers.
EXAMPLE:
To order QOUQ circuit breakers, change the Catalog
Number prex from QOU to QOUQ. To order a
QOU220 with factory installed four point quick connect
terminals, order one QOUQ220 circuit breaker at $55.00
each plus $5.60 per pole (a total price of $65.60).
Low Ampere QOU
Miniature Circuit
Breakers
General Specications
Common to All Low
Ampere QOU Circuit
Breakers
d UL Recognized Component, Supplementary Protector.
Note: See ordering instructions above left, all catalog numbers ending in B must be
ordered in bulk package quantities.
Low Ampere QOU Series 3 Circuit Breaker
No. of
Poles
Description AIR Rating
Voltage
Rating
Ampere
Rating
Catalog Number
Unit
Price
Order
Qty.
One
Thermal-
Magnetic
Circuit
Breaker
10,000
AIR
120/240
Vac
10
QOU110
QOU110B
$ 25.50
24.00
1
40
5,000
AIR
277
Vac
10
QYU110d
QYU110Bd
77.00
76.00
1
40
10,000
AIR
120/240
Vac
15
QOU115
QOU115B
25.50
24.00
1
40
15
QOU115HM
QOU115HMB
25.50
24.00
1
40
5,000
AIR
277
Vac
15
QYU115d
QYU115Bd
77.00
76.00
1
40
10,000
AIR
120/240
Vac
20
QOU120
QOU120B
25.50
24.00
1
40
20
QOU120HM
QOU120HMB
25.50
24.00
1
40
5,000
AIR
277
Vac
20
QYU120d
QYU120Bd
77.00
76.00
1
40
10,000
AIR
120/240
Vac
25
QOU125
QOU125B
25.50
24.00
1
40
5,000
AIR
277
Vac
25
QYU125d
QYU125Bd
77.00
76.00
1
40
10,000
AIR
120/240
Vac
30
QOU130
QOU130B
25.50
24.00
1
40
5,000
AIR
277
Vac
30
QYU130d
QYU130Bd
77.00
76.00
1
40
10,000
AIR
120/240
Vac
35
QOU135
QOU135B
25.50
24.00
1
40
40
QOU140
QOU140B
25.50
24.00
1
40
45
QOU145
QOU145B
25.50
24.00
1
40
50
QOU150
QOU150B
25.50
24.00
1
40
60
QOU160
QOU160B
25.50
24.00
1
40
70
QOU170
QOU170B
49.40
44.90
1
40
Two
Thermal-
Magnetic
Circuit
Breaker
10,000
AIR
120/240
Vac
10
QOU210
QOU210B
55.00
53.00
1
20
15
QOU215
QOU215B
55.00
53.00
1
20
240
Vac
15
QOU215H
QOU215HB
107.00
102.00
1
20
120/240
Vac
20
QOU220
QOU220B
55.00
53.00
1
20
240
Vac
20
QOU220H
QOU220HB
107.00
102.00
1
20
120/240
Vac
25
QOU225
QOU225B
55.00
53.00
1
20
240
Vac
25
QOU225H
QOU225HB
107.00
102.00
1
20
120/240
Vac
30
QOU230
QOU230B
55.00
53.00
1
20
240
Vac
30
QOU230H
QOU230HB
107.00
102.00
1
20
120/240
Vac
35
QOU235
QOU235B
55.00
53.00
1
20
40
QOU240
QOU240B
55.00
53.00
1
20
45
QOU245
QOU245B
55.00
53.00
1
20
50
QOU250
QOU250B
55.00
53.00
1
20
Non-Auto
Switch
N/A 240 Vac 60
QOU200
QOU200B
55.00
53.00
1
20
Thermal-
Magnetic
Circuit
Breaker
10,000
AIR
120/240
Vac
60
QOU260
QOU260B
55.00
53.00
1
20
70
QOU270
QOU270B
109.00
107.00
1
20
Three
Thermal-
Magnetic
Circuit
Breaker
10,000
AIR
240
Vac
10
QOU310
QOU310B
181.00
178.00
1
40
15
QOU315
QOU315B
181.00
178.00
1
40
20
QOU320
QOU320B
181.00
178.00
1
40
25
QOU325
QOU325B
181.00
178.00
1
40
30
QOU330
QOU330B
181.00
178.00
1
40
35
QOU335
QOU335B
181.00
178.00
1
40
40
QOU340
QOU340B
181.00
178.00
1
40
45
QOU345
QOU345B
181.00
178.00
1
40
50
QOU350
QOU350B
181.00
178.00
1
40
60
QOU360
QOU360B
181.00
178.00
1
40
Non-Auto
Switch
N/A 240 Vac 60
QOU300
QOU300B
181.00
178.00
1
40
Interrupting Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6-2
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Pages 6-37, 6-38, 6-43
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 6-45, 6-46
12-16
CP8
Discount
Schedule 3/00
2000 Square D
All Rights Reserved
1
2
T
R
A
N
S
F
O
R
M
E
R
S
Industrial Control Transformers
Class 9070
Type TF: Factory Installed Primary and Secondary Fuse Blocks
aSee Page 12-13 for triple ratings on this voltage code.
DimensionsType TF Only
q Dimensions with FINGERSAFE

covers installed.
f Dimensions with fuse pullers installed.
Field Installed Fuse Options
Primary and Secondary Fusing
Primary Fusing
Factory Installed Secondary Fuse Clips
D1:240 x 480-120
Field-Installable Secondary Fuse Clips
c SF41 can be installed on the following voltage codes: D1, D5, D24, D3, D4,
D51, D2, D23, D14, D25, D20, D95, D19.
UL/CSA
VA
CE VA Type
D1a
240 X 480
120
I
D2
240 x 480
24
I
D3
208
120
I
D5a
600
120
I
D20
208/230/460
115
II
D23
120/240
24
I
50 50 TF50 $ 50.00 $ 56.00 $ 56.00 $ 56.00 $ 82.00 $ 56.00
75 75 TF75 56.00 . . . . . . . . . . . . 64.00
100 100 TF100 61.00 70.00 70.00 70.00 89.00 70.00
150 150 TF150 65.00 84.00 84.00 84.00 109.00 84.00
200 200 TF200 77.00 . . . . . . . . . 134.00 89.00
250 160 TF250 87.00 . . . . . . . . . . . . 116.00
300 200 TF300 95.00 129.00 129.00 129.00 166.00 129.00
350 250 TF350 100.00 . . . . . . . . . . . . 131.00
500 300 TF500 120.00 158.00 158.00 158.00 185.00 158.00
750 500 TF750 161.00 . . . . . . . . . . . . . . .
1000 630 TF1000 194.00 . . . . . . . . . . . . . . .
1500 1000 TF1500 269.00 . . . . . . . . . . . . . . .
2000 1500 TF2000 324.00 . . . . . . . . . . . . . . .
VA Key
Figure A B C Dq E F Gf SLOT
I II III
25 VA . . . . . . 3 3.09 3.00 4.00 3.84 2.00 2.50 4.20 .20 x .38
. . . . . . 25 VA 3 4.00 3.43 4.00 4.80 2.00 2.50 4.20 .20 X .48
50 VA 25 VA . . . 3 3.09 3.00 4.00 3.84 2.00 2.50 4.20 .20 x .38
. . . . . . 50 VA 3 4.19 3.43 4.25 4.99 2.38 2.81 4.45 .20 X .48
75 VA 50 VA . . . 3 3.34 3.38 4.25 4.09 2.38 2.81 4.45 .20 X .48
. . . 75 VA . . . 3 3.59 3.75 4.55 4.34 2.88 3.13 4.75 .20 x .38
. . . . . . 75 VA 3 4.88 3.75 4.55 5.68 2.88 3.13 4.75 .20 x .38
100 VA . . . . . . 3 3.34 3.38 4.25 4.09 2.38 2.81 4.45 .20 X .48
. . . . . . 100 VA 3 4.88 3.75 4.55 5.68 2.88 3.13 4.75 .20 x .38
150 VA 100 VA . . . 3 3.59 3.75 4.55 4.34 2.88 3.13 4.75 .20 x .38
200 VA 150 VA . . . 3 3.59 3.75 4.55 4.34 2.88 3.13 4.75 .20 x .38
250 VA . . . 150 VA 3 5.25 3.75 4.55 6.05 2.88 3.13 4.75 .20 x .38
300 VA 200 VA 200 VA 3 4.70 4.50 5.10 5.50 2.56 3.75 5.30 .20 x .38
350 VA 250 VA 250 VA 3 5.09 4.50 5.10 5.89 3.00 3.75 5.30 .20 x .38
. . . 300 VA . . . 3 5.09 4.50 5.10 5.89 3.00 3.75 5.30 .20 x .38
. . . . . . 300 VA 3 5.46 4.50 5.10 6.26 3.56 3.75 5.30 .20 x .38
500 VA 350 VA . . . 3 5.46 4.50 5.10 6.26 3.56 3.75 5.30 .20 x .38
. . . . . . 350 VA 3 5.46 4.50 5.10 6.26 3.56 3.75 5.30 .20 x .38
750 VA 500 VA 500 VA 3 5.66 5.25 5.73 6.46 3.43 4.38 5.93 .28 X .56
1000 VA 750 VA 750 VA 3 6.04 5.25 5.73 6.84 4.31 4.38 5.93 .28 X .56
1500 VA 1000 VA 1000 VA 3 5.81 7.06 7.46 6.61 4.13 5.81 7.66 .28 X .56
2000 VA 1500 VA 1500 VA 3 7.04 7.06 7.46 7.84 4.56 5.81 7.66 .28 X .56
Type
Type Accessory Key
Description Price
I II III, IV
FB-3A 25-200 25-150 N/A
Three pole fuse block for primary
fusing, accomodates 1-1/2" x
13/32" midget fuse (2 rejection
and 1 non-rejection)
$26.40
FB-3B
250-
2000
200-
1500
25-
1500
Three pole fuse block for primary
and secondary fusing, accomo-
dates 1-1/2" x 13/32" midget fuse
(2 rejection and 1 non-rejection)
26.40
Type
Type Accessory Key
Description Price
I II III, IV
FB-2A 25-200 25-150 N/A
Two pole fuse block for primary
and secondary fusing, accommo-
dates 1-1/2" x 13/32" midget fuse
(2 rejection)
$22.70
FB-2B
250-
2000
200-
1500
25-
1500
Two pole fuse block for primary
fusing, accomodates 1-1/2" x 13/
32" midget fuse (2 rejection)
22.70
UL/CSA VA CE VA Catalog Number Price
50 50 9070T50D1SF41 $ 40.30
100 100 9070T100D1SF41 52.00
150 150 9070T150D1SF41 55.00
250 160 9070T250D1SF41 79.00
500 300 9070T500D1SF41 113.00
750 500 9070T750D1SF41 154.00
Type
Type Accessory Key
Description Price
I II III, IV
SF25A 25-200 25-150 N/A
Secondary fuse block accom-
modates 1-1/4" x 1/4" fuse
$6.60
SF25B
250-
2000
200-
1500
25-
1500
Secondary fuse block accom-
modates 1-1/4" x 1/4" fuse
6.60
SF41Ac 25-200 25-150 N/A
Secondary fuse clip accommo-
dates 1-1/2" x 13/32" midget
fuse
5.40
SF41Bc N/A
200-
2000
25-
2000
Secondary fuse clip accom-
modates 1-1/2" x 13/32" midget
fuse
5.40
FB-1A 25-200 25-150 N/A
One pole fuse block for second-
ary fusing, accomodates 1-1/2"
x 13/32" midget fuse (1 non-
rejection)
15.80
FB-1B
250-
2000
200-
1500
25-
1500
One pole fuse block for second-
ary fusing, accomodates 1-1/2"
x 13/32" midget fuse (1 non-
rejection)
15.80
How to Order:
To Order Specify: Catalog Number
k Class Number
k Type Number
k Voltage Code
k Field Fuse Option
Class Type Voltage Code
9070 TF500 D1
9070 FB-3B
A
D
B
C
G
E
F
FINGERSAFE is a Registered
Trademark of Square D Company
or related companies.
3-21-00
N99238 Rev. A
CC-TRON

FNQ-R
Time-Delay Fuses
1, 600 Volt, to 30 Amps
Form No. FNQ-R
Page 1 of 2
BIF Doc #1014
Bussmann

1.5"
(0.031)
(38.1mm)
.41"
(0.005)
(10.3mm)
Dimensional Data
General Information:
The Bussmann CC-TRON

(FNQ-R) was designed to meet


the needs of control circuit transformer protection.
Current-limitation protects down stream components
against damaging thermal and magnetic effects of short-
circuit currents.
Rejection feature. FNQ-R fuses meet the U.L. 508, para-
graph 19.2.4 requirement that control circuit fuses used in
equipment listed for use with more than 10,000 ampere
available must have an adequate interrupting rating and
must be rejection type.
High inrush time-delay. Control circuit transformers can
experience inrush currents up to 85 times their full-load
current rating. FNQ-R fuses can be sized according to
NEC and U.L. requirements and still allow the high inrush
currents, with significantly more time-delay than the U.L.
minimum value of 12 seconds at 200% for Class CC fuses.
Melamine tube. Nickel-plated brass endcaps.
Carton Quantity and Weight
Ampere Carton
Weight*
Ratings Qty. Lbs. Kg.
-30 10 .200 .091
*Weight per carton
Electrical Ratings (Catalog Symbol and Amperes)
FNQ-R- FNQ-R-1 FNQ-R-3 FNQ-R-8
FNQ-R- FNQ-R-1 FNQ-R-3 FNQ-R-9
FNQ-R- FNQ-R-1 FNQ-R-4 FNQ-R-10
FNQ-R- FNQ-R-1 FNQ-R-4 FNQ-R-12
FNQ-R- FNQ-R-1 FNQ-R-5 FNQ-R-15
FNQ-R- FNQ-R-2 FNQ-R-5 FNQ-R-17
FNQ-R- FNQ-R-2 FNQ-R-6 FNQ-R-20
FNQ-R-1 FNQ-R-2 FNQ-R-6 FNQ-R-25
FNQ-R-1 FNQ-R-2 FNQ-R-7 FNQ-R-30
FNQ-R-1 FNQ-R-3 FNQ-R-7
Catalog Symbol: FNQ-R
Time-Delay
Application: Circuit Transformer Protection
Ampere Rating: to 30 Amperes
Voltage Rating: 600 Volts AC (or less)
Interrupting Rating: 200,000A RMS Sym. (U.L.)
Agency Approvals:
U.L. Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273
CSA Certified, Class CC CSA, Class 1422-01,
File 53787HRC-MISC
12-30 amp is 300 Vdc and 10 KAIC.
Maximum Acceptable Rating of Overcurrent Device*
Maximum Rating of Overcurrent
Rated Primary Protective Device Expressed As A
Current Percent of Transformer Primary
(Amperes) Current Rating
Less than 2A 500**
2A to less than 9A 167
9A or more 125
*U.L. 508, Table 19.3.
**300% for other than motor control applications.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Time-Delay Ferrule Fuse FNM
13/32 x 1-1/2
Form No. FNM
Page 1 of 2
BIF Doc #2028
Bussmann

1-18-00
N99107 Rev. A
Carton Quantity and Weight
Ampere Carton Weight
Ratings Qty Lbs. Kg.
0-30 10 .125 .057
FNM-12
FNM-15

32 Volts AC
FNM-20
FNM-25
FNM-30
-

-
Electrical Ratings (Catalog Symbol and Amperes)
250 Volts AC IR 250 Volts AC IR 250 Volts AC IR 125 Volts AC
1.5"
(0.031)
(38.1mm)
.41"
(0.004)
(10.3mm)
CATALOG SYMBOL: FNM
TIME-DELAY
1/10 TO 30 AMPERES
INTERRUPTING RATING - SEE CHART BELOW
UL LISTED: STD. 248-14, 0-10/250V AC; 12-15/125V AC
FILE #E19180, GUIDE #JDYX
CSA CERTIFIED: 1-10/250V AC; CLASS 1422-01,
12-15/125V AC; FILE 53787
DC RATING: 1-15A rated 125V DC and 1.6 KAIC.
FNM-1/10
FNM-1/8
FNM-15/100
FNM-2/10
FNM-1/4
FNM-3/10
FNM-4/10
FNM-1/2
FNM-6/10
FNM-3/4
FNM-8/10
FNM-1

FNM-1-1/8
FNM-1-1/4
FNM-1-4/10
FNM-1-1/2
FNM-1-6/10
FNM-1-8/10
FNM-2
FNM-2-1/4
FNM-2-1/2
FNM-2-8/10
FNM-3
FNM-3-2/10
FNM-3-1/2
FNM-4
FNM-4-1/2
FNM-5
FNM-5-6/10
FNM-6
FNM-6-1/4
FNM-7
FNM-8
FNM-9
FNM-10

Fuseblock Catalog Numbers


Poles Terminal Type
Screw With Pressure Plate Box
Quick Connect w/Quick Connect Lug
1 BM6031SQ BM6031PQ BM6031B
2 BM6032SQ BM6032PQ BM6032B
3 BM6033SQ BM6033PQ BM6033B
35A@
250VAC
10,000
@
125VAC
100A@
250VAC
10,000
@
125VAC
200A@
250VAC
10,000 @
125VAC
10,000
@ 125V AC
Fibre tube.
For circuits with high inrush currents.
Formerly designated 5AB.
Fusetron

Dual-Element fuse.
If 250V AC is needed for 12-30 amps, use FNW series.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
1
!
DUAL RANGE INPUT (20 mA or 10 VDC)
!
24 VDC TRANSMITTER POWER
!
MAX AND MIN READING MEMORY
!
16 POINT SCALING FOR NON-LINEAR PROCESSES
!
PROGRAMMABLE FUNCTION KEYS / USER INPUTS
!
FOUR SETPOINT ALARM OUTPUTS (W/Plug-in card)
!
COMMUNICATION AND BUS CAPABILITIES (W/Plug-in card)
!
ANALOG OUTPUT SIGNAL (W/Plug-in card)
!
PC SOFTWARE AVAILABLE FOR METER CONFIGURATION
!
9 DIGIT TOTALIZER (INTEGRATOR) WITH BATCHING
!
NEMA 4X/IP65 SEALED FRONT BEZEL
!
EASY STEP BY STEP INSTRUCTIONS
GENERAL DESCRIPTION
The PAXP (PAX Process Input Meter) offers many features and performance
capabilities to suit a wide range of industrial applications. The meter employs
advanced technology for stable, drift free readout, while incorporating features
that provide flexibility now and in the future with plug-in option cards. The
plug-in card options allow the opportunity to configure the meter for present
applications, while providing easy upgrades for future needs.
The Process Meter has two inputs: 0 to 20 mA DC or 0 to 10 VDC. A built-
in 24 VDC supply powers remote transmitters. The meter incorporates a 16-
point input scaling feature for compensation of non-linear processes.
The meter provides a Max and Min reading memory with programmable
capture time. The capture time is used to prevent detection of false max and min
readings which may occur during start-up or unusual process events.
The signal totalizer (integrator) can be used to compute a time-input product.
This can be used to provide a readout of totalized flow, calculate service
intervals of motors and pumps, etc. The totalizer can also accumulate batch
weighing operations.
The meter has four setpoint outputs, implemented on Plug-in cards. The
Plug-in cards provide dual FORM-C relays (5 A), quad FORM-A relays (3 A)
or either sinking or sourcing quad open collector logic outputs. The setpoint
alarms can be configured in modes to suit a variety of control and alarm
requirements.
- High and low absolute, high and low deviation and band acting
- Balanced or unbalanced hysteresis
- On and off delay timers
- Auto reset or latching modes
- Reverse phase output and/or panel indicator
- Selection of alternate list of setpoint values
Plug-in cards also facilitate bus communications. These include RS232,
RS485 and DeviceNet. Readout values and setpoint alarm values can be
controlled through the bus. Additionally, the meter has features that allow a
remote computer to directly control the outputs of the meter. This is useful
during commissioning phases and diagnostic use. With a communication card
installed, set-up software allows configuration from a PC. The configuration
data can be saved to a file for later recall.
A linear DC output signal is available as a plug-in card. The card provides
either 20 mA or 10 V signals. The output can be scaled independent of the input
range.
The features of the linear output cards are:
- Output tracks either input, totalizer, max or min readings
- Programmable output update times
Once the meter has been initially configured, the parameter list may be
locked out from further modification in its entirety or only the setpoint values
can be made accessible.
The meter has been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
MODEL PAX - 1/8 DIN PROCESS INPUT PANEL METER
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.4) H x 5" (127) W.
UL Recognized Component,
File #E179259
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
Bulletin No. PAXP-D
Drawing No. LP0408
Revised 12/00
Tel +1 (717) 767-6511
Fax +1 (717) 764-6587
www.redlion-controls.com
4-4
MicroLogix 1000 / 1761 Controller
System Overview
General Specifications
24V dc Sensor
Power
200 mA max. with 200 F capacitive load max. (for
1761-L10BWA, -L16BWA, -L20BWA-5A, and
-L32BWA only)
Power Cycles 50,000 minimum
Operating Temp. 0 to 55 C (32 to 131 F) for horizontal mounting
0 to 40 C (32 to 104 F) for vertical mounting
Storage Temp. -40 to 85 C (-40 to 185 F)
Humidity 5 to 95% (without condensation)
Shock Operating: 10g peak acceleration (7.5g DIN rail mounted)
1
(111 ms duration), 3 times each direction, each axis
Non-operating: 20g peak acceleration (111 ms duration), 3
times each direction, each axis
Vibration Operating: 5 Hz to 2kHz, 0.381 mm (0.015 in.)
peak-to-peak/2.5g panel mounted
2
, 1hr per axis
Non-operating: 5 Hz to 2 kHz, 0.762 mm (0.030 in.)
peak-to-peak/5g panel mounted, 1hr per axis
Terminal Screw
Torque
0.9 N-m maximum (8.0 pound-inch)
Electrostatic
Discharge
IEC801-2 @ 8 KV
Radiated
Susceptibility
IEC801-3 @ 10V/m, 27M - 1000M Hz
3V/m, 87M - 108M Hz, 174 - 230M Hz, and
470M - 790M Hz
Fast Transient IEC801-4 @ 2 KV Power Supply, 1 KV I/O
Isolation 1500V ac
Memory Type EEPROM
Memory Size 1K words (approximtely 737 instruction words,
437 data words)
1
Relays are derated an additional 2.5g on 32 I/O controllers.
2
DIN rail mounted controller is 1g.
Weight and Dimensions
Cat. No.
1761-
Weight:
kg (lb)
Height:
mm (in.)
Width:
mm (in.)
Depth:
mm (in.)
1
L10BWA 0.2 (0.5)
80 (3 15) 120 (4 72) 40 (1 57)
L10BWB 0.2 (0.5)
80 (3.15) 120 (4.72) 40 (1.57)
L16AWA 0.4 (0.9) 133 (5.24)
L16BWA 0.4 (0.8) 120 (4.72)
L20AWA-5A 80 (3.15) 73 (2.87)
L20BWA-5A 0.6 (1.2)
( ) ( )
L20BWB-5A
( )
200 (7 87)
L32AWA
200 (7.87)
L32BWA 0.6 (1.2) 80 (3.15) 73 (2.87)
L32AAA
( ) ( ) ( )
L16BBB 0.2 (0.5)
80 (3 15) 120 (4 72)
L16BWB 0.2 (0.5)
80 (3.15) 120 (4.72)
40 (1 57)
L32BBB
0 4 (0 8) 80 (3 15) 200 (7 87)
40 (1.57)
L32BWB
0.4 (0.8) 80 (3.15) 200 (7.87)
1
Add approximately 13 mm (0.51 in.) when using the 1761-CBL-PM02 or the
1761-CBL-HM02 communication cable.
Analog Input Specifications
Voltage Range $10.5V 1LSB
Current Range 0-20mA 1LSB
Data Format Natural binary 16-bit signed integer
Voltage Input Impedance 210k W
Current Input Impedance 160k W
Resolution 16 bits (it is also a function of the input filter
selection)
Overall Accuracy 0 to 55 C $0.7% of full scale
Analog Output Specifications
Voltage Range 0-10V 1LSB
Current Range 4-20mA 1LSB
Data Format Natural binary 16-bit signed integer
Step Response 2.5ms @ 95%
Load Range 0-500
Current Output Coding (4-20mA
1LSB, 0-10V 1LSB)
0-32,767
Resolution 15 bits
Overall Accuracy 0 to 55 C $1.0% of full scale
4-6
MicroLogix 1000 / 1761 Controller
MicroLogix 1000 Controller Selection
Catalog Number I/O Digital Inputs Analog Inputs Digital Outputs Analog Outputs
Real
Input Power
Apparent
Input Power
1761-L10BWA 10 6 inputs
24V dc sink/source
0 4 contact outputs 0 13W @ 120V ac
14W @ 240V ac
24VA @ 120V ac
32VA @ 240V ac
1761-L10BWB 10 6 inputs
24V dc sink/source
0 4 contact outputs 0 5W @ 24V dc 5VA @ 24V dc
1761-L16AWA 16 10 inputs
120V ac
0 6 contact outputs 0 7W @ 120V ac
8W @ 240V ac
15VA @ 120V ac
21VA @ 240 ac
1761-L32AWA 32 20 inputs
120V ac
0 12 contact outputs 0 9.1W @ 120V ac
10.6W @ 240V ac
19VA @ 120V ac
25VA @ 240V ac
1761-L16BWA 16 10 inputs
24V dc sink/source
0 6 contact outputs 0 14W @ 120V ac
15W @ 240V ac
26VA @ 120V ac
33VA @ 240V ac
1761-L32BWA 32 20 inputs
24V dc sink/source
0 12 contact outputs 0 15W @ 120V ac
16W @ 240V ac
29VA @ 120V ac
36VA @ 240V ac
1761-L32AAA 32 20 inputs
120V ac
0 10 triac outputs,
120/240V ac
2 contact outputs
0 7W @ 120V ac
9W @ 240V ac
16VA @ 120V ac
22VA @ 240V ac
1761-L16BWB 16 10 inputs
24V dc sink/source
0 6 contact outputs 0 5W @ 24V dc 5VA @ 24V dc
1761-L32BWB 32 20 inputs
24V dc sink/source
0 12 contact outputs 0 7W @ 24V dc 7VA @ 24V dc
1761-L16BBB 16 10 inputs
24V dc
sink/source
0 4 source 24V dc
outputs
2 contact outputs
0 5W @ 24V dc 5VA @ 24V dc
1761-L32BBB 32 20 inputs
24V dc sink/source
0 10 source 24V dc
outputs
2 contact outputs
0 7W @ 24V dc 7VA @ 24V dc
1761-L20AWA-5A 25 12 inputs
120V ac
2 voltage ($10V)
2 current (0-20mA)
8 contact outputs 1 voltage/current
(0-10V, 4-20mA)
12W @ 120V ac
13W @ 240V ac
20VA @ 120V ac
27VA @ 240V ac
1761-L20BWA-5A 25 12 inputs
24V dc sink/source
2 voltage ($10V)
2 current (0-20mA)
8 contact outputs 1 voltage/current
(0-10V, 4-20mA)
18W @ 120V ac
19W @ 240V ac
30VA @ 120V ac
38VA @ 240V ac
1761-L20BWB-5A 25 20 inputs
24V dc sink/source
2 voltage ($10V)
2 current (0-20mA)
8 contact outputs 1 voltage/current
(0-10V, 4-20mA)
7W @ 24V dc 10VA @ 24V dc
4-7
MicroLogix 1000 / 1761 Controller
MicroLogix 1000 Controller Selection
Transformer Load Memory Size
Timers/ Counters
Maximum
Program Scan
Time/Kword I/O Scan Time
Communication
Port Catalog Number
33VA @ 120V ac
35VA @ 240V ac
1K words
(approximately 737
instr ction words; 437
40 timers;
32 counters
fixed
2ms (typical) 0.21ms (typical) RS-232-C (Can be
configured for
comm nic tion thr
1761-L10BWA
not applicable
instruction words; 437
data-table words)
fixed communication thru
1761-NET-AIC in a
DH-485 network)
1761-L10BWB
18VA @ 120V ac
20VA @ 240V ac
DH-485 network)
1761-L16AWA
23VA @ 120V ac
27VA @ 240V ac
1761-L32AWA
35VA @ 120V ac
38VA @ 240V ac
1761-L16BWA
38VA @ 120V ac
40VA @ 240V ac
1761-L32BWA
18VA @ 120V ac
23VA @ 240V ac
1761-L32AAA
not applicable 1761-L16BWB
not applicable 1761-L32BWB
not applicable 1761-L16BBB
not applicable 1761-L32BBB
30VA @ 120V ac
33VA @ 240V ac
1761-L20AWA-5A
45VA @ 120V ac
48VA @ 240V ac
1761-L20BWA-5A
not applicable 1761-L20BWB-5A
DeviceNet Interfaces
Catalog Number /
Product Function Communication Interface
Communication Rates
Supported (bit/s) Current Load
1761-NET-DNI
DeviceNet RS-232-C
Interface
Lets you connect a MicroLogix controller (or other
controller with an RS-232-C port) to the DeviceNet
network. This allows the controller to function as a
DeviceNet slave node to provide 16 words of input
data and 16 words of output data that can be
exchanged with the DeviceNet scanner. This also
allows peer-to peer messaging between controllers.
Lets you connect a PC-compatible computer to the
DeviceNet network for peer-to peer messaging, for
programming, and for on-line monitoring.
Dual-shielded twisted pair
(DeviceNet network)
DeviceNet-
selectable
125k
250k
500k
RS-232-C
selectable
1200
2400
4800
9600
19200
38400
DeviceNet:
0 - 200mA
(@ 11 - 25V)
For more information, see DeviceNet Product Overview, publication DN-2.5.
Bulletin 1492
Accessories
12-174
Mounting Rails
DIN Mounting Rails
Dimensions shown in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
0.218" (5.5 mm) x 0.50" (12.7 mm) slotted mounting holes every 3" (76.2 mm) starting 1.69" (42.9 mm) from end.
Item Description Pcs./Pkg. Dimensions
199-DR1
Symmetrical Rail
35 mm x 7.5 mm
3.28' (1 m) long
Zinc-Plated, Yellow
Chromated Steel
EN50022
DIN #3
10
199-DR4
Heavy Duty
Symmetrical Rail
35 mm x 15 mm
3.28' (1 m) long
Zinc-Plated, Yellow
Chromated Steel
EN50022
DIN #3
5
1492-DR3
Mini 15 mm x 5.5 mm
Rail 3.28' (1 m) long
Zinc-Plated, Yellow
Chromated Steel
EN50045
DIN #2
5
1492-DR5
Symmetrical Rail
35 mm x 7.5 mm
3.28' (1 m) long
Copper-Free
Aluminum EN50022
For 1492 Terminal
Blocks Only
DIN #3
10
1492-DR6
Symmetrical Rail
35 mm x 7.5 mm
2.26" (57.4 mm) high
3.28' (1 m) long
Copper-Free
Aluminum
For 1492 Terminal
Blocks Only
DIN #3
2
1492-DR7
Symmetrical Rail
35 mm x 7.5 mm
2.80" (71.0 mm) high
3.28' (1 m) long
Angled 30
Zinc-Plated,
Chromated Steel
DIN #3
2
0.04
(1.0)
1.97 (50.0) 0.98
(25.0)
0.20
(5.2 )
1.38
(35.0)
1.06
(27.0)
0.30
(7.5)
0.03 R
(0.8)
0.49
(12.5)
#1032 or M5 Recommended Maximum Mounting Screw Size
0.04
(1.0)
1.38
(35.0)
0.94
(24.0)
0.59
(15.0)
0.05 R
(1.2)
0.09
(2.4)
0.98
(25.0)
0.21
(5.3)
0.49
(12.5)
0.59
(15.0)
0.04
(1.0)
0.33
(8.5)
0.22
(5.5)
0.17
(4.3)
0.32
(8.0)
SLOT DETAIL
#832 or M4 Recommended Maximum Mounting Screw Size
0.04
(1.0)
0.30
(7.5)
1.97 (50.0) 0.98
(25.0)
0.22
(5.5)
1.38
(35.0)
1.06
(27.0)
0.49
(12.5)
0.03 R
(0.8)
#1224 or M5 Recommended Maximum Mounting Screw Size
0.875 Dia.
(22.2)
0.75
(19.1)
2.26
(57.4)
6 (152.4) 1.69
(42.9)
1.38
(35.0)
2.26
(57.4)
0.88
(22.4)
0.30
(7.5)
1.14
(29.0)
Wire insulator plug for wire access through rail use Heyco
0.84
(21.3)
1.13
(28.7)
1.87
(47.5)
2.80
(71.0)
30
For mounting rail details, see Cat. No. 199-DR1
Bulletin 1492
IEC Terminal Blocks
12-12
Standard Feed-Through Blocks
May only be used as a marking surface. Cannot be installed over a center jumper.
Cat. no. is not complete. See page 12-173.
1492-W3 1492-W4 1492-W6
Dimensions are not
intended to be used for
manufacturing purposes.
Note: Height dimension is
measured from top of
rail to top of terminal
block.
Specifications Single-circuit terminal block. Single-circuit terminal block. Single-circuit terminal block.
Approvals EEx e II CSA IEC EEx e II CSA IEC EEx e II CSA IEC
Voltage Rating
600V
AC/DC
550V
600V
AC/DC
800V
AC/DC
600V
AC/DC
550V
600V
AC/DC
800V
AC/DC
600V
AC/DC
550V
600V
AC/DC
800V
AC/DC
Maximum Current 20 A 24 A 20 A 24 A 30 A 32 A 30 A 32 A 40 A 41 A 40 A 41 A
Wire Range (Rated Cross Section)
#30-#14
AWG
2.5 mm
2
#22-#14
AWG
0.5-2.5
mm
2
#22-#10
AWG
4.0 mm
2
#22-#10
AWG
0.5-4
mm
2
#22-#10
AWG
6.0 mm
2
#22-#10
AWG
0.5-6
mm
2
Wire Strip Length 0.39" (10 mm) 0.35" (9 mm) 0.47" (12 mm)
Recommended Tightening Torque 5.05.6 lb-in. (0.6 Nm) 5.05.6 lb-in. (0.6 Nm) 5.66.8 lb-in. (0.7 Nm)
Density 61 pcs./ft (200/m) 50 pcs./ft (166/m) 43 pcs./ft (142/m)
Insulation Temperature Range 40+195F (40+90C) 40+195F (40+90C) 40+195F (40+90C)
Terminal Blocks Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
Color: Gray 1492-W3 50 1492-W4 50 1492-W6 50
Red 1492-W3-RE 50 1492-W4-RE 50 1492-W6-RE 50
Blue 1492-W3-B 50 1492-W4-B 50 1492-W6-B 50
Black 1492-W3-BL 50 1492-W4-BL 50 1492-W6-BL 50
Green 1492-W3-G 50 1492-W4-G 50 1492-W6-G 50
Yellow 1492-W3-Y 50 1492-W4-Y 50 1492-W6-Y 50
Orange 1492-W3-OR 50 1492-W4-OR 50 1492-W6-OR 50
White 1492-W3-W 50 1492-W4-W 50 1492-W6-W 50
Brown 1492-W3-BR 50 1492-W4-BR 50 1492-W5-BR 50
Accessories (page 12-172) Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
Mounting Rails:
1 m Symmetrical DIN (Steel) 199-DR1 10 199-DR1 10 199-DR1 10
1 m Symmetrical DIN (Aluminum) 1492-DR5 10 1492-DR5 10 1492-DR5 10
1 m Hi-Rise Sym. DIN (Aluminum) 1492-DR6 2 1492-DR6 2 1492-DR6 2
1 m Angled Hi-Rise Sym. DIN
(Steel)
1492-DR7 2 1492-DR7 2 1492-DR7 2
End Barrier 1492-EB3 50 1492-EB3 50 1492-EB10 50
End Anchors:
DIN Rail Normal Duty
1492-EA35 50 1492-EA35 50 1492-EA35 50
DIN Rail Heavy Duty 1492-EAH35 10 1492-EAH35 10 1492-EAH35 10
Jumpers:
Insulated Side Jumper 1492-SJ5-10 (10-pole) 10
1492-N42 (2-pole)
1492-SJ6-10 (10-pole)
50
10
Center Jumper 50-pole 1492-CJ5-50 5 1492-CJ6-50 5
Center Jumper 40-pole 1492-CJ7-40 5
Center Jumper 10-pole 1492-CJ5-10 10 1492-CJ6-10 10 1492-CJ7-10 10
Center Jumper 3-pole 1492-CJ5-3 10 1492-CJ6-3 10 1492-CJ7-3 10
Center Jumper 2-pole 1492-CJ5-2 10 1492-CJ6-2 10 1492-CJ7-2 10
Center Jumper Link 1492-CJL5 10 1492-CJL6 10 1492-CJL7 10
Center Jumper Cover White 1492-CJCW5 20 1492-CJCW6 20 1492-CJCW6 20
Other Accessories:
Partition Plate 1492-PP3 50 1492-PP3 50 1492-PP10 50
Separation Plate 1492-SP3 50 1492-SP3 50
Test Plug 1492-TP28 10 1492-TP28 10
Test Plug Adapter 1492-TA285 10 1492-TA40 10 1492-TA40 10
Electrical Warning Plate (4-pole) 1492-EWP5-4 10 1492-EWP6-4 10 1492-EWP7-4 10
Group Marking Carrier 1492-GM35 10 1492-GM35 10 1492-GM35 10
Marking Systems:
Snap-in Marker Cards
1492-SM5X9
1492-SM5X12
5 1492-SM6X12 5 1492-SM6X12 5
Individual Marker Tabs
(single char.)
1492-MP5 5 1492-MP 5 1492-MP 5
1.78" (45.3 mm)
1
.
3
8
"
(
3
5
m
m
)
0.20"
(5 mm) 1.78" (45.3 mm)
1
.
3
8
"
(
3
5
m
m
)
0.24"
(6 mm) 1.87" (47.6 mm)
1
.
6
1
"
(
4
1
m
m
)
0.28"
(7 mm)
Bulletin 1492
Accessories
12-188
12
Marking Systems, Continued
Marker Cards
IEC Marking Systems
Marking System Hardware/Software
The Plotter Pen Point, the Adapter, and the Ink are all required for a complete refillable pen. Note: The refillable pen should be used when faster
ink drying times and superior ink adhesion are desired.
Recommended for maintaining refillable pen.
Description Cat. No. Pcs./Pkg.
Plotter Starter Kit
Plotter and Cable
Software
Base Plate:
1492-PLTKIT 1
(6) IEC Spacers
(6) SM5X5 Spacers
(6) SMN Spacers
(4) Disposable Pens
Software 1492-PLSOFT 1
Plotter Pen Point 1492-PLPEN 1
Adapter 1492-PLADAPT 1
Ink 1492-PLINK 1
Cleaning Kit 1492-PLCLEAN 1
Cleaning Solution 1492-PLSOLN 1
Disposable Plotter Pen 1492-DISPEN 4
Entrelec Marking Kit 1492-PLTENTR 1
Phoenix Marking Kit 1492-PLTPHX 1
Wieland Marking Kit 1492-PLTSSWIEL 1
Wago Marking Kit 1492-PLTWAGO 1
Weidmuller Marking Kit 1492-PLTWEID 1
Cat. No. No. of Labels/Card
1492-SM5X5 100
1492-SM5X9 100
1492-SM5X12 100
1492-SM6X9 100
1492-SM6X12 100
1492-SM8X9 100
1492-SM8X12 100
1492-SMN81 100
1492-SMN83 50
Computer System Requirements
Personal computer with 80486 processor
Microsoft Windows version 3.1 or later (for
enhanced performance Windows 95 is
recommended)
8 MB hard disk space
3.5 or 5.25 inch high-density floppy disk
drive
Monitor supported by Windows (VGA or
better)
One open serial communication port
(COM1throughCOM4) for printing markers
Bulletin 1492
Accessories
12-178
End Barriers
IEC
Note: Height dimension of products that mount on rail is from top of rail to top of end barrier.
1492-EB3, 1492-EB3-Y,
1492-EB10, 1492-EB10-Y,
1492-EBM3, 1492-EBM4
Cat. No. A B C
1492-EB3
1492-EB3-Y
1.46"
(37 mm)
1.38"
(35 mm)
0.06"
(1.5 mm)
1492-EB10
1492-EB10-Y
1.77"
(45 mm)
1.61"
(41 mm)
0.06"
(1.5 mm)
1492-EBM3
1.10"
(28 mm)
0.97"
(24.6 mm)
0.06"
(1.5 mm)
1492-EBM4
1.22"
(31 mm)
1.09"
(27.7 mm)
0.06"
(1.5 mm)
1492-EBMD1
1492-EBTS3
A
B
C
1.65" (42 mm)
1
.
3
2
"
(
3
3
.
5
m
m
)
0.06"
(1.5 mm)
2.61" (66.2 mm)
1
.
7
4
"
(
4
4
.
1
m
m
)
0.06"
(1.5 mm)
1492-EB16, 1492-EB35,
1492-EBD4N
Cat. No. A B C
1492-EB16
2.17"
(55 mm)
2.15"
(54.5 mm)
0.08"
(2 mm)
1492-EB35
2.36"
(60 mm)
2.80"
(71 mm)
0.08"
(2 mm)
1492-EBD4N
3.50"
(89 mm)
1.97"
(50 mm)
0.08"
(2 mm)
1492-EBD3
1492-EBTF3
A
B
C
2.44" (62 mm)
1
.
9
1
"
(
4
8
.
6
m
m
)
0.06"
(1.5 mm)
3.51" (89.1 mm)
1
.
7
4
"
(
4
4
.
1
m
m
)
0.06"
(1.5 mm)
1492-EBKD6
1492-EB3TW
1492-EBKD3
2.95" (75 mm)
1
.
9
3
"
(
4
9
m
m
)
0.08"
(2 mm)
1.79" (45.4 mm)
1
.
6
4
"
(
4
1
.
6
m
m
)
0.06"
(1.5 mm)
1.81" (46 mm)
1
.
3
5
"
(
3
4
.
3
m
m
)
0.06"
(1.5 mm)
Bulletin 1492
IEC Terminal Block Accessories
12-146 Visit our website: www.ab.com/catalogs
End Anchors and End Retainers/Partition Plates/Separation Plates
End Anchors and End Retainers
Partition Plates Separation Plates
Dimensions
Width x Length x
Height Used With Color Cat. No.
Pcs/
Pkg
0.005 x 3.15 x 2.48 in
(0.13 x 80 x 63 mm)
1492-JD3, JD3C,
JD3F, JD3DF,
JD3DR, JD3RB,
JD3RC, JD3SS
Gray 1492-PPJD3 20
0.005 x 3.54 x 2.51 in
(0.13 x 90.1 x 63.8 mm)
1492-JD3P,
JDG3P
Natural 1492-PPJD3P 20
0.08 x 1.57 x 1.20 in
(2 x 40 x 30.5 mm)
1492-WM3, WM4,
WMG3, WMG4
Gray 1492-PPM3 50
0.014 x 2.28 x 1.51 in
(0.35 x 58 x 38.3 mm)
1492-WMD1 Gray 1492-PPMD1 50
0.06 x 1.85 x 1.57 in
(1.5 x 47 x 40 mm)
1492-W3, W4,
WG4
Gray 1492-PP3 50
0.06 x 2.17 x 1.81 in
(1.5 x 55 x 46 mm)
1492-W6, W10,
W16S, W4TW,
WG6, WG10S,
WG16S
Gray 1492-PP10 50
0.014 x 2.88 x 1.85 in
(0.35 x 73.2 x 47.1 mm)
1492-WTF3,
WTS3
Natural 1492-PPTS3 50
0.06 x 1.93 x 2.36 in
(1.5 x 49 x 60 mm)
1492-J3, J4, J6,
J10, J2Q, J3TW,
J3F, JG2Q, JG3,
JG3TW, JKD3,
JKD3TP, J3P,
J3PTP, JTC3
Gray 1492-EBJ16 20
Blue 1492-EBJ16-B 20
Yellow 1492-EBJ16-Y 20
Dimensions
Width x Length x
Height Used With Color Cat. No.
Pcs/
Pkg
0.014 x 1.76 x 1.57 in
(0.35 x 44.8 x 40.0 mm)
1492-W3, W4 Natural 1492-SP3 50
Photo
Dimensions
Width x Length x Height
Tightening
Torque Markers
Used
With Color Cat. No.
Pcs/
Pkg
0.31 x 2.20 x 1.85 in
(8 x 56 x 47 mm)
4.4 lbin
(0.5 Nm)
1492-M7X12
1492-M8X5
199-DR1, 199-DR2,
1492-DR4, 1492-DR5,
1492-DR6, 1492-DR7,
1492-DR8, 1492-DR9
Gray 1492-EAJ35 100
0.48 x 2.20 x 2.48 in
(12.2 x 56 x 63 mm)
4.4 lbin
(0.5 Nm)
1492-M7X12
1492-M5X5
199-DR1, 199-DR2,
1492-DR4, 1492-DR5,
1492-DR6, 1492-DR7,
1492-DR8, 1492-DR9
Gray 1492-EAHJ35 50
0.31 x 1.06 x 1.06 in
(8 x 27 x 27 mm)
3.5 lbin
(0.9 Nm)
1492-M5X5 1492-DR3 Gray 1492-EAJ15 50
0.24 x 2.19 x 1.63 in
(6 x 55.6 x 41.5 mm)

1492-M5X10
1492-M5X5
199-DR1, 199-DR2,
1492-DR4, 1492-DR5,
1492-DR6, 1492-DR7,
1492-DR8, 1492-DR9
Gray 1492-ERL35 20
0.20 x 0.96 x 0.75 in
(5 x 24.5 x 19 mm)

1492-M5X10
1492-M5X5
1492-DR3 Gray 1492-ERL15 20
Bulletin_1492_IEC_Terminal_Block_Accessories.qxd 10/02/2004 12:06 Page 12-146
CXJ16246
ON
OFF
TRIP
RESET
200 Main Street Newport News, Virginia 23601
Phn: 757-599-6884, Fax: 757-599-0061
Automation Controls Inc.
Bill of Materials for: Engineered Systems & Products
H-O-A Explosion Proof (220V 1PH 2w 50HTZ) Project Name: ACI Job No: 2008-085
Bill of Material
H-O-A Explosion Proof (220V 1PH 2w 50HTZ) Panel Name: Panel(s)
Tag Qty Mfg Part No Description
Typical of 1
ENCL 1 AKRON CXJ16246 ENCLOSURE,NEMA 7
MCB 1 SD FAL22020 CB,MC,2 P,240V,10KAIC,020A
MCB PDB 1 SD PDC6-FA6 CB DIST LUG KIT,FOR FAL,3 P,600V,WITH (06) 14-6
SP1 1 SD SDSA1175 SURGE ARR,3 W,1 PH,36IN LEADS,120/240V,UL
SP1 1 SD QOSAMK MOUNTING BRACKET FOR SDSA SURGE ARRESTOR
MS-01 1 SD LC1-D25-G7 CONTACTOR,IEC,D LINE,600V,025A,1NO,1NC,120V
OL-01 1 SD LRD-14 OL RELAY,IEC,D LINE,007-10A,1NO,1NC,D09-D32
MS-AUX 1 SD LAD-8N11 AUX CONT,SIDE,1 NO 1 NC,IEC,D9-D38
CB-SP,FM 2 SD QOU110 CB,1 P,240V,10KAIC,010A,DIN MNT
XFMR 1 SD 9070TF-150-D1 XFMR,OPEN,1 PH,WITH FB,240/480V-120V,0150VA
F1,2 2 BUSS FNQ-R1-1/2 FUSE,600V,200KAIC,01.5A,13/32X1-1/2,TD
F3 1 BUSS FNM-1-6/10 FUSE,250V,10KAIC,01.6A,13/32X1-1/2,TD
DI-1 1 RL PAXP-0000-AO METER,PAXP,4-1/2,120V,PAX ASB,4-20mA,4-20mA,NEMA 4X
PLC 1 AB 1761-L20BWA-5A MICROLOGIX 1000,24VDC,12 24VDC IN,8 REL OUT,4 AI,1 AO
PLC 1 AB 1761-L20AWA-5A MICROLOGIX 1000,120V,12 120V IN,8 REL OUT,4 AI,1 AO
TB 1 AB 199-DR1 DIN RAIL,3FT
TB 30 AB 1492-W4 1 TIER,TERMINAL,600V,30A
TBTAGS 60 ACI 1492-SM6X12-ACI 1 TIER,MARKER,BLANK,FOR 1492-W4,W4P
TB 2 AB 1492-EB3 1 TIER,END BARRIER,FOR W4,W4P
TB 6 AB 1492-EAJ35 END ANCHOR
Page 1 of 1
E-Mail: Mail@acin.com
200 Main Street Newport News, Virginia 23601
Phn: 757-599-6884, Fax: 757-599-0061
Automation Controls Inc.
Bill of Materials for Engineered Systems & Products
H-O-A Explosion Proof (220V 1PH 2w 50HTZ Project Name
Manufacturer Data for all Bill of Materials items
Akron Electric Inc
1025 Eagon Street
Barberton OH 44203
Phone: 800-275-2535
Fax: 330-745-2504
Web: www.akronelectric.com
BOM Manufacturer Acronym: AKRON
Manufacturer Data
Allen Bradley
1201 South Second Street
Milwaukee WI 53204
Phone: 414-382-2000
Fax: 414-382-4444
Web: www.ab.com
BOM Manufacturer Acronym: AB
Manufacturer Data
Automation Controls
200 Main Street
Newport News VA 23601-4107
Phone: 757-599-6884
Fax: 757-599-0061
Web: www.acin.com
BOM Manufacturer Acronym: ACI
Manufacturer Data
Page 1 of 2
Bill of Materials for Engineered Systems & Products
H-O-A Explosion Proof (220V 1PH 2w 50HTZ Project Name
Manufacturer Data for all Bill of Materials items
Bussman
PO Box 14460
St Louis MO 63178-4460
Phone: 636-394-2877
Fax: 636-207-4825
Web: www.bussmann.com
BOM Manufacturer Acronym: BUSS
Manufacturer Data
Red Lion
20 Willow Springs Circle
York PA 17402
Phone: 717-767-6511
Fax: 717-764-0839
Web: www.redlion.net
BOM Manufacturer Acronym: RL
Manufacturer Data
Square D
1415 Roselle Road
Palatine IL 60067
Phone: 847-397-2600
Fax: 847-925-7500
Web: www.us.squared.com
BOM Manufacturer Acronym: SD
Manufacturer Data
Page 2 of 2

You might also like