Archi tectural Testi ng

1140 Lincoln Avenue


Springdale, PA 15144
phone: 724-275-7100
fax: 724-275-7102
www.archtest.com








AAMA/WDMA/CSA 101/I.S.2/A440-05
TEST REPORT

Rendered to:

IDEAL WINDOW MANUFACTURING

SERIES/MODEL: NC Professional
PerfectFit 1 & 2
Lifescapes
Majestic Picture Window (781/981 frame)

PRODUCT TYPE: New Construction PVC Fixed Windows


Summary of Results
Title Test Specimen #1 Test Specimen #2
Primary Product Designator
FW-C35 1829 x 1829
(72 x 72)
FW-C50 1422 x 1422*
(56 x 56*)
Design Pressure 1680 Pa (35.11 psf) 2400 Pa (50.16 psf)
Operating Force (in motion) N/A N/A
Air Infiltration
<0.05 L/s/m
2

(<0.01 cfm/ft
2
)
0.10 L/s/m
2

(0.02 cfm/ft
2
)
Water Penetration Resistance Test
Pressure
360 Pa (7.52 psf) 360 Pa (7.52 psf)
Uniform Load Structural Test Pressure 2520 Pa (52.66 psf) 3600 Pa (75.24 psf)
Forced Entry Resistance Grade 10 N/A

Test Completion Date: 02/03/09

Reference must be made to Report No. 88690.02-501-44, dated 07/27/10 for complete test
specimen description and data.

Archi tectural Testi ng

















































1140 Lincoln Avenue
Springdale, PA 15144
phone: 724-275-7100
fax: 724-275-7102
www.archtest.com





AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT

Rendered to:

IDEAL WINDOW MANUFACTURING
200 West 7th Street, P.O. Box 48
Bayonne, New J ersey 07002-0048

Report No.: 88690.02-501-44
Test Dates: 01/21/09
Through: 02/03/09
Report Date: 07/27/10
Expiration Date: 02/03/13

Project Summary: Architectural Testing, Inc. was contracted by Chelsea Building Products to
perform testing on two Series/Model 730/930, PVC fixed windows. The samples tested
successfully met the performance requirements for the following ratings: Test Specimen #1:
FW-C35 1829 x 1829 (72 x 72); Test Specimen #2: FW-C50 1422 x 1422* (56 x 56*). This
report is a reissue of the original Report No. 88690.01-501-44. This report is reissued in the
name of Ideal Window Manufacturing through written authorization of Chelsea Building
Products. Test specimen description and results are reported herein. The samples were
provided by the client.

General Note: An asterisk (*) next to the size designation indicates that the size tested for
optional performance was smaller than the Gateway test size for the product type and class.

Test Specification: The test specimens were evaluated in accordance with
AAMA/WDMA/CSA 101/I.S.2/A440-05, Standard/Specification for Windows, Doors, and Unit
Skylights.

Test Specimen Description:

Series/Model: NC Professional
PerfectFit 1 & 2
Lifescapes
Majestic Picture Window (781/981 frame)

Product Type: New Construction PVC Fixed Windows

Archi tectural Testi ng
















88690.02-501-44
Page 2 of 8


Test Specimen #1: FW-C35 1829 x 1829 (72 x 72)

Overall Size: 1829 mm (72") wide by 1829 mm (72") high

Fixed DLO Size: 1695 mm (66-3/4") wide by 1695 mm (66-3/4") high

Overall Area: 3.35 m
2
(36.0 ft
2
)

Test Specimen Description: (Continued)

Test Specimen #1: FW-C35 1829 x 1829 (72 x 72) (Continued)

Glazing Type: The unit was glazed with nominal 7/8" thick sealed insulating glass
fabricated from two sheets of 3/16" thick clear annealed glass separated by a "U"
shaped steel spacer system, single sealed.

Test Specimen #2: FW-C50 1422 x 1422* (56 x 56)*

Overall Size: 1422 mm (56") wide by 1422 mm (56") high

Fixed DLO Size: 1289 mm (50-3/4") wide by 1289 mm (50-3/4") high

Overall Area: 2.02 m
2
(21.8 ft
2
)

Glazing Type: The unit was glazed with nominal 7/8" thick sealed insulating glass
fabricated from two sheets of 1/8" thick clear annealed glass separated by a "U" shaped
steel spacer system, single sealed.

The following descriptions apply to all specimens.

Finish: All PVC finish was white.

Frame Construction: The extruded PVC frame was of mitered and welded corner
construction.

Weatherstripping: No weatherstripping was utilized.

Glazing Details: The glass was set from the interior against a double-sided adhesive tape
and secured with rigid vinyl glazing beads.

Archi tectural Testi ng
















88690.02-501-44
Page 3 of 8


Test Specimen Description: (Continued)

Drainage:

Description Quantity Location

1-1/2" wide by 5/16" 2 Exterior sill face, one at
high weepslot with flap each end

3/8" wide by 3/16" 2 Sill glazing channel, one at
deep weepslot each end

1" wide by 3/16" 2 Sill intermediate wall, one at each
deep weephole end

Hardware: No hardware was utilized.

Reinforcement: No reinforcement was utilized.

Installation: The unit was installed in a wood buck constructed from Spruce-Pine-Fir
lumber construction and secured through the nail fin with #8 x 1" long screws spaced
approximately 11" on center, and beginning 2" in from each corner. The nail fin perimeter
was sealed with a silicone sealant. A nominal 3/16" gap was maintained at the perimeter
between the frame and wood buck.

Test Results: The temperature during testing was 21C (70 F). The results are tabulated as
follows:

Paragraph Title of Test - Test Method Results Allowed

Test Specimen #1: FW-C35 1829 x 1829 (72 x 72)

5.3.2.1 Air Leakage Resistance per ASTM E 283
75 Pa (1.6 psf) <0.05 L/s/m
2
1.5 L/s/m
2

(<0.01 cfm/ft
2
) (0.3 cfm/ft
2
) max.

Note #1: The tested specimen meets (or exceeds) the performance levels specified in
AAMA/WDMA/CSA 101/I.S.2/A440-05 for air leakage resistance.

5.3.3.2 Water Penetration Resistance per ASTM E 547 See Note #2

Note #2: The client opted to start at a pressure higher than the minimum required. Those
results are listed under "Optional Performance".

Archi tectural Testi ng
















88690.02-501-44
Page 4 of 8


Test Results: (Continued)

Paragraph Title of Test - Test Method Results Allowed

Test Specimen #1: FW-C35 1829 x 1829 (72 x 72) (Continued)

5.3.4.2 Uniform Load Deflection per ASTM E 330 See Note #2

5.3.4.3 Uniform Load Structural per ASTM E 330 See Note #2

5.3.5 Forced Entry Resistance per ASTM F 588

Type: D Grade: 10

Disassembly Test No entry No entry
Sash/Panel Manipulation Test No entry No entry
Lock Hardware Manipulation Test No entry No entry

5.3.6.2 Thermoplastic Corner Weld Test Meets as stated Meets as stated

Optional Performance

4.4.2.6 Water Penetration Resistance per ASTM E 547
360 Pa (7.52 psf) No leakage No leakage

4.4.2.6 Uniform Load Deflection per ASTM E 330
(Deflections were taken on the right jamb)
(Loads were held for 10 seconds)
1680 Pa (35.11 psf) (positive) 0.3 mm (0.01") See Note #3
1680 Pa (35.11 psf) (negative) 0.3 mm (0.01") See Note #3

4.4.2.6 Uniform Load Structural per ASTM E 330
(Permanent sets were taken on the right jamb)
(Loads were held for 10 seconds)
2520 Pa (52.66 psf) (positive) <0.3 mm (<0.01") 0.8 mm (0.03") max.
2520 Pa (52.66 psf) (negative) 0.3 mm (0.01") 0.8 mm (0.03") max.

Archi tectural Testi ng
















88690.02-501-44
Page 5 of 8


Test Results: (Continued)

Paragraph Title of Test - Test Method Results Allowed

Test Specimen #2: FW-C50 1422 x 1422* (56 x 56*)

5.3.2.1 Air Leakage Resistance per ASTM E 283
75 Pa (1.6 psf) 0.10 L/s/m
2
1.5 L/s/m
2

(0.02 cfm/ft
2
) (0.3 cfm/ft
2
) max.

Note #1: The tested specimen meets (or exceeds) the performance levels specified in
AAMA/WDMA/CSA 101/I.S.2/A440-05 for air leakage resistance.

5.3.3.2 Water Penetration Resistance per ASTM E 547 See Note #2

Note #2: The client opted to start at a pressure higher than the minimum required. Those
results are listed under "Optional Performance".

5.3.4.2 Uniform Load Deflection per ASTM E 330 See Note #2

5.3.4.4 Uniform Load Structural per ASTM E 330 See Note #2

5.3.5 Forced Entry Resistance per ASTM F 588

Type: D Grade: 10

Disassembly Test No entry No entry
Sash/Panel Manipulation Test No entry No entry
Lock Hardware Manipulation Test No entry No entry

5.3.6.2 Thermoplastic Corner Weld Test Meets as stated Meets as stated

Optional Performance

4.4.2.6 Water Penetration Resistance per ASTM E 547
360 Pa (7.52 psf) No leakage No leakage

4.4.2.6 Uniform Load Deflection per ASTM E 330
(Deflections were taken on the right jamb)
(Loads were held for 10 seconds)
2400 Pa (50.16 psf) (positive) 0.3 mm (0.01") See Note #3
2400 Pa (50.16 psf) (negative) 0.3 mm (0.01") See Note #3

Archi tectural Testi ng
















88690.02-501-44
Page 6 of 8


Test Results: (Continued)

Paragraph Title of Test - Test Method Results Allowed

Test Specimen #2: FW-C50 1422 x 1422* (56 x 56*) (Continued)

Optional Performance (Continued)

4.4.2.6 Uniform Load Structural per ASTM E 330
(Permanent sets were taken on the right jamb)
(Loads were held for 10 seconds)
3600 Pa (75.24 psf) (positive) 0.3 mm (0.01") 0.8mm (0.03") max.
3600 Pa (75.24 psf) (negative) 0.3 mm (0.01") 0.8 mm (0.03") max.

Tape and film were not used to seal against air leakage during structural testing.

Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing
and are representative of the test specimen reported herein.

List of Official Observers:

Name Company

J oe Allison Architectural Testing, Inc.
Lynn George Architectural Testing, Inc.


Archi tectural Testi ng
















88690.02-501-44
Page 7 of 8


Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or
other pertinent project documentation will be retained by Architectural Testing, Inc. for a period
of four years from the original test date. At the end of this retention period, such materials shall
be discarded without notice and the service life of this report will expire.

Results obtained are tested values and were secured by using the designated test methods. No
conclusions of any kind regarding the adequacy or inadequacy of the glass in the test specimen
can be made. This report does not constitute certification of this product nor an opinion or
endorsement by this laboratory. It is the exclusive property of the client so named herein and
relates only to the specimen(s) tested. This report may not be reproduced, except in full, without
the written approval of Architectural Testing, Inc.

For ARCHITECTURAL TESTING, INC.




_________________________________________________ ____________________________________________________
J oseph E. Allison Lynn George
Senior Technician Director Regional Operations

J EA:sld

Attachments (pages): This report is complete only when all attachments listed are included.
Appendix-A: Alteration Addendum (1)
Appendix-B: Drawings: Complete drawings packet on file with Architectural Testing, Inc.


Archi tectural Testi ng
















88690.02-501-44
Page 8 of 8



Revision Log


Rev. # Date Page(s) Revision(s)
0 07/27/10 N/A Original report issue Reissued Report No.
88690.01-501-44 in the name of Ideal
Window Manufacturing.

























This report produced from controlled document template ATI 00156, revised 12/01/07.


Archi tectural Testi ng
















88690.02-501-44





Appendix A

Alteration Addendum


Note: No alterations were required.

Archi tectural Testi ng
















88690.02-501-44




Appendix B

Drawings

Note: Complete drawings packet on file with Architectural Testing, Inc.