You are on page 1of 18

ATT-TP-76205,

AT&T ELECTRONIC EQUIPMENT


ENCLOSURE / CABINET (EEE/C) STANDARD.
Abstract:
AT&T ELECTRONIC EQUIPMENT ENCLOSURE / CABINET (EEE/C) STANDARD for use by Original
Equipment Manufactures (OEM) and others.
Audience:
Telecommunications Equipment Suppliers, Original Equipment Manufactures (OEM).
Region(s): All AT&T Networks Wireline, Core and Mobility.
Effective Date: 08/26/09
Published : Issue 0, 08/26/09
Expires On: NA
Related Documents: Telcordia GR3108 issue 2, GR487 issue 3, GR950 issue 1, GR-3142
Issue 1, AT&T-TP-76200
Canceled Documents: N/A
Issuing Department: 22 State, Network C&E Staff
Business Unit: AT&T OPERATIONS Inc.
Points Of Contact: See Contact List .
Author(s): Jeffrey Smith, js4394


Table Of Contents
INTRODUCTION
Reason For Current Issue
1. General 1
1.1. Requirements and Objectives 1
1.2. Purpose 1
1.3. Scope 1
1.4. Definitions 2
1.5. AT&T-TP76205 Internet Web Site 2
1.6. Product Evaluation Process 2
1.7. Requirement Levels 3
1.8. Product Change Notices (PCNs) 3
1.8.1. Letter of Attestation. 3
1.8.2. Retesting Requirement. 3
2. AT&T OPERATIONS Requirements 4
2.1. Basic Test Lab safety requirements 4
2.2. Controlled Environmental Remote Terminal Structures (CEVs, Huts, CECs,
CUEs, etc) and Customer Premise. 4
2.3. Manual Transfer Switches (MTS) Requirements 4
2.3.1. Code Standards Compliance 4
2.3.2. Configuration 5
2.3.3. Construction 5
2.3.3.1. Branch Breakers 5
2.3.3.2. Finish 5
2.3.3.3. Security 6
2.3.3.4. Access 6
2.3.3.5. Mounting 6
2.3.3.6. Size 6
2.3.4. Service Entrance - Conduit Access 6
2.3.5. Bonding 6
2.3.6. Convenience Outlet 7
2.3.7. Generator Receptacle 7
2.3.8. Indicator Lights 7
2.4. Permanent Generator Requirements 7
2.4.1. Code Standards Compliance 7
2.4.1.1. National Standards Bodies 7
2.4.1.2. NFPA-110 7
2.4.1.3. NFPA 37 7
2.4.1.4. UL 2200 8
2.4.1.5. UL 1008 8
2.4.2. Housing Standards 8
2.4.2.1. Impact 8
2.4.2.2. Corrosion 8
2.4.2.3. Wind Resistance 8
2.4.2.4. Paint 8
2.4.3. Noise Standards 9
2.4.3.1. Sound Pressure Level 9
2.5. EEE / C Requirements. 9
2.6. Generic Outside Building Mounted Electronic Equipment Enclosures (iNID,
H-ONT, ONT) 9
2.7. Laboratory Accreditation Requirements 9
2.8. Additional AT&T Operations Requirements 10
2.9. Alarms Requirements for EEE / C. 10
2.9.1. AT&T Operations Alarm Standards Technical Manual 10
2.9.2. TP76450 11
2.9.3. Alarm Panel Capacity 11
2.9.4. Generator Retrieval Alarm 11
2.10. Bonding and grounding requirements for EEE / C 11
2.10.1. AT&T Grounding Positions 11
2.10.2. Auxiliary Ground Buss Bars 11
2.10.3. Number 2 Ground Leads Terminations. 11
2.10.4. Method and Procedures Documentation. 11
2.11. Battery requirements for EEE / C. 12
2.11.1. Battery Technology 12
2.11.2. Battery Cable Requirements 12
2.11.3. Battery Circuit Breaker Location. 12
2.11.4. Battery Backup 12
2.12. Wire and cable Bend radii requirement. 12
2.13. Network Elements, DC Power feeds requirements for EEE / C 12
2.13.1. DC Powered Equipment Voltage. 13
2.14. Fiber cable terminations for EEE / C. 13
2.14.1. Fiber Termination Panels Sizing. 13
2.14.2. Pre-Terminated OSP fiber cables 13
2.14.3. Fusion Splices 13
2.15. Conduit plate access for EEE / C 13
2.16. Air Filters within EEE / C 13
2.17. Acoustic Noise 13
2.18. Equipment Racks 14
2.19. Over Voltage Protection 14
2.19.1. Gas Tube Design 14
2.19.2. High Density Over Voltage Protection Blocks 14
2.20. EEE / C DC Fuse Requirements 14
2.20.1. Fuse Installation 14
2.20.2. Dummy Fuses 14
2.20.3. Spare Fuse Position Label 14
2.21. Fan Access 14
2.22. Annual Commercial Power Usage 15
2.23. EEE / C M&P and Drawings. 15
2.23.1. Mounting Applications and Alarm Verification 15
2.23.2. Torque Values 15
2.23.3. Wiring Schematics 15
2.23.4. Elevation Drawings 15
2.23.5. Computer Generated Thermal Analyses 15
2.23.6. DC Power Consumption 15
2.24. EEE / C Photographs 16
2.24.1. Doors Closed 16
2.24.2. Doors Open 16
2.24.3. Format 16
2.25. Product suppliers Explosion sheet. 16
2.26. RETROFIT NETWORK ELEMENTS 16
2.26.1. Thermal Analyses 16
2.26.2. Data Gathering 16
2.27. Reasons for Reissue 17
2.28. Effective Date of this Issue 17
2.29. Comments 17
3. GR Tests Checklist 17
3.1. Product Suppliers Responsibilities. 17
3.2. GR Checklist Summary 17
3.3. GR3108 issue II Checklist 17
3.4. GR487 issue III Checklist 21
3.5. GR950 Issue II Checklist 23
4. HAZARDOUS SUBSTANCES DECLARATION 29
4.1. Form HSD, Page 2 30
4.1.1. Product Declaration 30
4.2. Form HSD, Page 3 32
4.2.1. Hazardous Material #1 32
5. AT&T-TP-76205 PRODUCT EVALUATION PROCESS 32
5.1. EEE / C Approval Process, 32
5.2. Documentation 32
5.2.1. Test Report Documentation Package (most preferred) 33
5.2.2. Letter of Attestation (only with prior AT&T approval, normally used with legacy vendors),
34
5.2.3. Product Change Notice Statement 35
6. APPENDIX B: AT&T-TP-76205 PRODUCT CHANGE TEST GUIDELINES 35
6.1. Purpose 35
6.2. 5.2. General 36
6.3. Approval by Similarity 36
6.3.1. Acceptance of a new EEE/C by similarity as compared with a previously Approved
Product. 37
7. Acknowledgements 37
8. Contact List 37
A.1. Document Specific Acronyms 38
A.2. Acronyms Dictionary 38
Revision Log 38
ACRONYMS 38
Reason for Current Issue

Issue Number 1 Date 08/26/09 Description
Published By Jeffrey Smith

Date 08/26/09 ATTUID js4394


INTRODUCTION
1. General
AT&T is issuing this document to assist OEM and Product Suppliers in there effort to bring new products
to market at AT&T.
1.1. Requirements and Objectives
The objective of this AT&T TP76205 is to provide the basic standards for product suppliers to follow for
the configuration and construction of EEE / Cs. The following Telcordia documents are considered the
basic standards: Telcordia GR3108 issue 2, GR487 issue 3, GR950 issue 1 GR-3142 Issue 1.
In addition to the Telcordia standards mentioned above, the electronics equipment, Network Elements,
and hardware contained within such EEE / Cs must also meet AT&T TP76200 and/or other applicable
AT&T TP documents.
1.2. Purpose
The purpose of this document is to provide product suppliers with the Telcordia documents, standards,
and AT&T requirements that may differ from or exceed Telcordia Generic Requirements (GR). A
product's compliance with the requirements and objectives of this document will not be the sole basis for
the acceptance of the product. However, noncompliance with one or more of the requirements or
objectives of this document may be the basis for a product's denial of approval for use.
1.3. Scope
Unless otherwise stated, the requirements contained herein apply to EEE / C systems, and their
supporting equipment intended for installation in all of AT&T network outside of the Telecom Central
Office (CO) and not within the customers building. This includes AT&T mobility. Requirements for
network electronics that may be deployed within the EEE/C are covered by ATT-TP-76200 and are
excluded from this document. This excludes equipment buildings, equipment areas within buildings,
controlled environmental vaults and customer locations.


1.4. Definitions
A. The term product supplier / vendor / OEM as used throughout this document refers to the equipment
manufacturer or agent of the equipment manufacturer, whichever is appropriate for the product being
considered.
B. The term company representative / AT&T as used throughout this document refers to the AT&T
OPERATIONS, employee representing AT&T OPERATIONS.
C. The term Electronic Equipment Enclosures / Cabinet (EEE/C) as used throughout this document refers
to the AT&T metallic or non metallic containers suitable for use outside the four walls of a
telecommunication building that may contain Network and/or Mobility electronic elements that provide but
are not limited to Voice, Data, and Entertainment services.
D. Requirements are those product features that must be provided by the equipment manufacturer. The
words "shall" and "must" are used throughout this document to identify requirements.
E. Objectives are product features that are desired for the long term use or application. The word should
is used throughout this document to identify objectives.
F. The term Network as used throughout this document refers to the AT&T Telecom network that provides
but is not limited to Voice, Data, and Entertainment.
G. The term Mobility as used throughout this document refers to the AT&T wireless network or cellular
equipment that provides but is not limited to Voice, Data, and Entertainment.
H. The term Radio Frequency (RF) Backhaul as used throughout this document refers to the AT&T
wireless network backhaul equipment that provides but is not limited to Voice, and Data.
1.5. AT&T-TP76205 Internet Web Site
Copies of this document and general information about AT&T OPERATIONSs environmental equipment
standards may be found at. https://ebiznet.sbc.com/sbcnebs/
1.6. Product Evaluation Process
AT&T requires GR test reports be forwarded to AT&T OPERATIONS for review before the product will be
approved for use. To meet the needs of the business, AT&T may authorize an exception, with the
submission of a Letter Of Attestation from the OEM for incomplete test results. Completed test reports are
still required to be submitted in a time frame negotiated with the AT&T SME, see list in item 8.

1.7. Requirement Levels
Equipment must demonstrate conformance to subsets of requirements contained in AT&T TP76205
depending on the intended application and deployment environments of the equipment. The Product
Supplier shall provide GR3108 or GR950 test results for the electronics and service effecting components
intended for use within GR487 or GR950 structure and or any requirements that exceed GR3108.
Equipment must conform to requirements (R) for each location and/or application for which it is intended.
OUTSIDE PLANT (OSP) Typically OSP network locations are between the outside of the four walls of
the COs, Non-CO buildings and Customer Premises. There are four levels of OSP environments:
OSP Class One refers to Controlled protected environments typically OSP Huts, CEVs, and other
OSP enclosures with active HVAC environment per Telcordia GR-3108-CORE ISSUE 2.
OSP Class Two refers to Protected equipment in outside environment, per Telcordia GR-3108-CORE
ISSUE 2.
OSP Class Three refers to Protected equipment in outside severe environment per Telcordia GR-
3108-CORE ISSUE 2.
OSP Class Four refers to Unprotected environment directly exposed to the weather, per Telcordia
GR-3108-CORE ISSUE 2.

1.8. Product Change Notices (PCNs)
Reference GR-209-CORE Issue 5, February 2006. PCNs must be evaluated for their effect on the
equipments AT&TTP-76205 compliance.
1.8.1. Letter of Attestation.
When it is determined by the manufacturer, using sound engineering judgment that a hardware or
software change does not impact the equipments AT&T-TP-76205 compliance, the manufacturer may
submit a letter of attestation to this effect.
NOTE:
Except when it is obvious that the PCN will not affect the equipments compliance. AT&T
OPERATIONS recommends that an accredited, third party, independent laboratory evaluate
whether testing is required to verify compliance.
1.8.2. Retesting Requirement.
When the manufacturer, a test lab or AT&T OPERATIONS determines that the PCN may affect the
equipments AT&TTP-
76205 compliance, the modified equipment must be tested per AT&T-TP-76205
NOTE:
Depending on engineering judgment, not all requirements may need to be tested.
2. AT&T OPERATIONS Requirements
2.1. Basic Test Lab safety requirements
The equipment under test shall provide for the safety of personnel and property. However, due to needs
of the business and the fact that the lab is staffed by personnel trained to work with prototype equipment,
there are times when it may be necessary for equipment to be placed into labs that has not been verified
in compliance to safety standards. In those cases, it is incumbent upon the manufacturer to assure the
equipment is safe to operate. If equipment does not meet the above objective, the manufacturer shall
submit a notarized Letter of Attestation (LOA) that the equipment meets industry electrical safety,
electromagnetic emissions and fire safety standards.
NOTE:
All applicable AT&T-TP-76205, TP76200 and AT&T-TP-76450 requirements must be evaluated as in
conformance prior to deployment into the network.
2.2. Controlled Environmental Remote Terminal Structures
(CEVs, Huts, CECs, CUEs, etc) and Customer Premise.
This document does not cover technical requirements for RT structures (CEVs, Huts, CECs, CUEs, etc)
or network equipment installed at customer premise locations. Technical requirements for relay racks,
indoor customer premise cabinet enclosures, indoor wall-mount cabinet configurations and the network
equipment installed therein are covered within AT&T-TP-76200
2.3. Manual Transfer Switches (MTS) Requirements
2.3.1. Code Standards Compliance
All proposed MTS shall adhere to all applicable national and local safety codes and standards including:
1. UL 891 or UL 67, Manual Transfer Switches; listed for use as service entrance equipment.
2. MTS should be constructed of Aluminum and conform to UL 3R rainproof criteria. Aluminum shall be no
less than 0.125 thick. Stainless steel hardware shall be 316 alloys. The cabinet shall meet GR487 issue
III Corrosion Resistance-salt fog test section. The cabinet shall meet UL 891 3R weatherproof rating.
2.3.2. Configuration
The MTS will have a main service entrance feed from commercial power. The MTS will have branch
breakers designed to feed collocated EEE/C. The MTS shall be designed for installation as wall, cabinet,
pad, pole, or H-frame mountable by use of optional mounting hardware that meets GR 487 issue III or UL
891 3R. All protection devices shall consist of circuit breakers; fuses shall not be permitted.
2.3.3. Construction
The MTS cabinets shall consist of a single enclosure equipped with a dead front design and hinged
access door. The cabinet shall be completely factory assembled with circuit breakers, generator circuit
breaker, interlock (slide bar), wire connectors, and accessories. The interior shall be designed to permit
circuit breaker replacement without disturbing adjacent components and without removing the main bus
connectors.
2.3.3.1. Branch Breakers
Branch circuit breakers shall be provided as part of the AC service entrance panel. These breakers shall
be plug-on, molded case, circuit breakers equipped with thermal-magnetic, quick-break, trip free on faults,
thermal-inverse time delay element and magnetic instantaneous trip coil in each ungrounded phase
conductor, or approved equivalent. The preference would be a Square D breaker QO type. Branch
circuits shall be arranged using double row construction and shall be numbered by the manufacturer. The
breaker circuit numbers on the dead front panel shall be odd umbers on the left and even numbers on the
right. All circuit breaker connections shall be suitable for use of 75C wire. The circuit breakers
configurations shall be available as separately purchasable kits (if required for replacement). All load
breakers shall have a minimum interrupt rating of 22kAIC. Unused breaker positions shall be covered with
blanks.
2.3.3.2. Finish
The paint shall be a powder coat with a color of almond or Bell system green. It is a requirement to meet
GR487 issue III, the Paint section of GR487 issue III or, at a minimum UL 3R.
2.3.3.3. Security
The cabinet door shall be equipped with a three-point latch and have provision to accept a padlock
mechanism.
2.3.3.4. Access
All access to the internal components of the cabinet shall be via the front hinged door.
2.3.3.5. Mounting
All cabinets shall be provided with mounting holes and weather tight plugs.
2.3.3.6. Size
The cabinet shall have sufficient gutter (internal cable routing paths) space to meet the minimum bend
radius code requirements. Over all outside measurements may vary to best accommodate the needs of
the business.
2.3.4. Service Entrance - Conduit Access
The MTS shall be listed for use as service entrance panel and / or load center. The service entrance
conductors shall be capable of entering from the top or bottom of the cabinet. The cabinet shall be
equipped with internal or external steel or schedule 40 PVC conduit no less than 2.5 inches no more than
3 inches in diameter for commercial power feeder cable. AC service from the commercial power company
to the meter base may enter from the bottom of the cabinet via this conduit or it may enter directly into the
meter base. The cabinet shall have provisions for mounting a power meter base either on the top or on a
side. The commercial power meter base may need to be covered and locked for security but equipped
with a viewing port for the meter. Service entry from the meter base may be from the top or from the side.
The cabinet shall permit external conduit access on the top, bottom, left and right sides. Preformed
concentric knockouts are preferable but not mandatory. Where provided, knockouts shall support
sufficient variations in conduit size to preclude the need to drill or punch additional holes to accommodate
conventional size conduit. A knockout should be available to allow for pulling the retrieve engine
alarm wiring from the MTS into the associated EEE/C.
2.3.5. Bonding
All cabinets shall be factory bonded for service entrance applications. The internal ground bar should be
sized to accept a #2 gauge ground wire from the site ground ring.
2.3.6. Convenience Outlet
There may be an optional single 20A GFCI (NEMA 5-20R) duplex outlet and associated branch circuit
breaker. This outlet must be rated for indoor and outdoor use.
2.3.7. Generator Receptacle
A generator receptacle and associated interlocked circuit breaker shall be required. This receptacle shall
be capable of being located on the top left side, top right side, or bottom. These receptacles may have the
additional requirement of being recessed and covered. The single phase 100A and 200A Hubbell
connectors are the most prevalent in the current network and their configuration will be regionally specific.
2.3.8. Indicator Lights
Lights to indicate the presence of commercial and generator power are required.
2.4. Permanent Generator Requirements
2.4.1. Code Standards Compliance
All proposed power systems shall adhere to all applicable national and local safety codes and standards
including:
2.4.1.1. National Standards Bodies
NFPA 70, National Electrical Code (NEC);
2.4.1.2. NFPA-110
NFPA 110, Standard for Emergency and Standby Power Systems;
2.4.1.3. NFPA 37
NFPA 37, Standard for Stationary Combustion Engines;
2.4.1.4. UL 2200
UL 2200, Stationary Engine Generator Assemblies;
2.4.1.5. UL 1008
UL 1008, Automatic Transfer Switches.
2.4.2. Housing Standards
NOTE:
The following four requirements are from Telcordia GR-487-CORE Issue 3, Detailed Requirements
for Electronic Equipment Cabinets. AT&T may consider alternative methods for meeting the intent
of these requirements.
2.4.2.1. Impact
The housing shall meet the impact requirement, RE3-199, specified in GR-487, Issue 3.
2.4.2.2. Corrosion
The housing shall meet the corrosion resistance requirement, RE3-203, specified in GR-487, Issue 3.
[The vendor may choose to provide different levels of corrosion resistance including one for a coastal/salt
environment.]
2.4.2.3. Wind Resistance
The housing shall meet the wind resistance requirement, RE3-197, specified in GR-487, Issue 3. The
manufacturer shall define the mounting pad dimensions and composition necessary to meet this
requirement.
2.4.2.4. Paint
The housing paint (or other protective covering) shall meet the requirements specified in Section 3.6 of
GR-487, Issue 3.
2.4.3. Noise Standards
These generators will be deployed in a variety of environments from rural to suburban residential areas.
The units must comply with any local noise ordinances. They should be quiet enough so as not to be
perceived as a nuisance by neighbors.
2.4.3.1. Sound Pressure Level
With the generator operating at full load in its enclosure, the sound pressure level, measured in dB with
an a weighting, shall not exceed 70 dBA.
NOTE:
[Measurement to be made at a distance of 7 meters from the exhaust orifice and 1.5 meters above
ground level
at eight equally spaced intervals around the generator and averaged to provide this level.]
2.5. EEE / C Requirements.
EEE / C shall meet the basic required (R) sections of AT&T-TP-76200, Telcordia GR3108 issue 2, GR487
issue 3, GR950 issue 2. AT&T reserves the right to add specific conditional requirements (CR) or wave
requirements to meet the needs of AT&T business. See section 3 for GR Tests Checklists.
2.6. Generic Outside Building Mounted Electronic Equipment
Enclosures (iNID, H-ONT, ONT)
Unless otherwise stated in this section, OSP electronic equipment enclosures mounted on the outside of
single family residences, MDUs, and small business shall meet the applicable requirements:
Intelligent Network Interface Devices (iNIDs) and Home Optical Network Terminal (H-ONT) All INID
and H-ONT type products shall meet the requirements set forth in Telcordia GR-3142-CORE Issue 1,
June 2008 Generic Requirements for Intelligent Network Interface Devices (iNIDs)
Optical Network Terminal (ONT)- All ONT type products shall meet the requirements set forth in
Telcordia GR-950-CORE Issue 2, December 1998 Generic Requirements for Optical Network Unit (ONU)
Closures
2.7. Laboratory Accreditation Requirements
AT&T OPERATIONS will only accept test reports submitted by testing laboratories that are accredited by
an accreditation agency (e.g., the American Association for Laboratory Accreditation or the National
Voluntary Laboratory Accreditation Program) that is recognized by the National Cooperation for
Laboratory Accreditation.
The scope of accreditation must include the test standards referenced in test reports.
AT&T OPERATIONS will accept test reports that include test data generated at non-accredited test
laboratories if the tests are witnessed and verified by a representative from a company that operates an
accredited test laboratory.
Records shall be retained that clearly demonstrate that the individual who witnessed the test has the
appropriate expertise and competence. Submitted test reports shall clearly distinguish test data
generated in-house at an accredited laboratory from witnessed and verified test data. The test report shall
also contain a statement attesting to the compliance of the testing to applicable standards.
Test laboratories located outside of the United States shall be accredited in accordance with ISO/IEC
Guide 25 or ISO/IEC 17025. This accreditation must be performed by a nationally recognized accrediting
body operating in accordance with ISO/IEC Guide 58. Testing performed outside of the United States by
a non-accredited laboratory or manufacturers performed testing may be accepted if witnessed by a U.S.
Nationally Recognized Testing Laboratory.
Each test report submitted to AT&T Operations shall contain accreditation and scope information or a
letter containing this information may be forwarded for our files.
2.8. Additional AT&T Operations Requirements
The following is for notification purposes only. Refer to the directions given by AT&T to obtain further
information on these subjects.
2.9. Alarms Requirements for EEE / C.
2.9.1. ATT TP-76450
All manufacturers submitting network equipment for review and consideration should pay specific
attention to TP76450 for minimum alarm and interconnection requirements.
https://ebiznet.sbc.com/sbcnebs/.
2.9.2. Alarm Panel Capacity
EEE / C alarm panel should provide a means to terminate and cross connect up to sixteen Housekeeping
/ Environmental alarm contact points.
2.9.3. Generator Retrieval Alarm
All EEE / C fed by commercial power via a Power Transfer Switch (PTS) shall have provisions for a
separate conduit run and termination point for a Generator Retrieval Alarm.
2.10. Bonding and grounding requirements for EEE / C
2.10.1. AT&T Grounding Positions
In the Network, EEE / C six of the eight positions on the dual lug Principle Ground Buss bar shall be left
for Telco use.
These shall be vacant from the factory.
2.10.2. Auxiliary Ground Buss Bars
If additional grounding positions are necessary to maintain six vacant positions, a second or larger
Ground Buss Bar must
be installed. It is preferred to be located in the same general area.
2.10.3. Number 2 Ground Leads Terminations.
The EEE / C eight position dual lug Principle Ground Buss bar shall accommodate terminating two # 2
solid tinned copper grounds leads. Consideration of the placement of PGBB to accommodate a minimum
bend radius for the installation of the # 2 GRD leads.
2.10.4. Method and Procedures Documentation.
All pad or pole mounted EEE / C installation method and procedures shall include text referring to the
construction and use of a ground ring system as called for in AT&T-TP-76416
2.11. Battery requirements for EEE / C.
2.11.1. Battery Technology
All EEE / C shall accommodate Valve Regulated Lead Acid (VRLA) or Nickel Cadmium (Ni-Cad) battery
technologies.
2.11.2. Battery Cable Requirements
All EEE / C shall have epoxy sealed, nickel plated, no inspection hole battery cable terminations to
prevent migration of battery salts and corrosion.
2.11.3. Battery Circuit Breaker Location.
All EEE / C shall have battery circuit breakers located within the electronic equipment or splice chambers.
(GR3108 class 2 environment)
2.11.4. Battery Backup
The battery backup standard shall be a minimum 8 hours of backup power under full load for telephony
services. AT&T reserves the right to alter this requirement on a case by case basis.
2.12. Wire and cable Bend radii requirement.
All wiring and cabling must adhere to the wire and cabling manufactures bend radius specifications
2.13. Network Elements, DC Power feeds requirements for
EEE / C
All Network Elements that carry customer service that require A and B power feeds shall have A and B
DC power feeds from the NE to the DC power source. AT&T reserves the right to alter this requirement
on a case by case basis.
Dual A and B primary and secondary DC power feed circuits are required for dual input Network
Elements carrying customer service installed in CEV, HUT, and Customer Premise Remote Terminal
applications regardless of whether single or dual DC power sources are employed.
2.13.1. DC Powered Equipment Voltage.
All DC powered equipment within EEE / C shall operate on -48V power feeds. AT&T reserves the right to
alter this requirement on a case by case base. (Example +/- 24 VDC)
2.14. Fiber cable terminations for EEE / C.
2.14.1. Fiber Termination Panels Sizing.
All EEE / C fiber termination panels shall accommodate a minimum of 24 fibers. AT&T SME will provide
approved fiber termination panel information. AT&T reserves the right to adjust this requirement for the
needs of the business.
2.14.2. Pre-Terminated OSP fiber cables
Fiber panels shall be set up for pre-terminated OSP fiber cables.
2.14.3. Fusion Splices
Fiber panels and racking shall accommodate fusion splices as an in the field option.
2.15. Conduit plate access for EEE / C
Conduit access plates shall be split so the cabinet can slide into place. The seam must be seal and
installation documentation shall reflect the proper procedure.
2.16. Air Filters within EEE / C
For air filter information refer to TP76200 Fan Filter Requirements section.
2.17. Acoustic Noise
All EEE / C should meet GR487 Issue 3 R3-222 with a Conditional Requirement of CR3-223 at ATTs
request.
2.18. Equipment Racks
All EEE / C internal equipment racking shall meet 23 telcom standard footprint with an option of 19 per
an AT&T request.
2.19. Over Voltage Protection
2.19.1. Gas Tube Design
All Over voltage protection shall be of the Gas tube design.
2.19.2. High Density Over Voltage Protection Blocks
AT&T has an objective to move towards high density over voltage protection blocks.
2.20. EEE / C DC Fuse Requirements
2.20.1. Fuse Installation
All active DC Voltage fuse positions shall have fuses install by the Product Supplier.
2.20.2. Dummy Fuses
All inactive but reserved for future use DC fuse positions shall have Dummy fuses installed by Product
Supplier
2.20.3. Spare Fuse Position Label
Any DC fuse positions provided as spare fuses holders shall be labeled as spare fuse and have fuses
installed by Product Supplier.
2.21. Fan Access
All heat exchanger fans shall be accessible for replacement without the removal and or disconnection of
service effecting, Network Elements.
2.22. Annual Commercial Power Usage
All product supplier provided EEE / C method and procedures shall contain worst and typical case AC
power consumption in kWh/yr. All vendor provided EEE / C method and procedures shall contain the
recommended portable AC generator size in kW required for temporary powering of the EEE / C
2.23. EEE / C M&P and Drawings.
2.23.1. Mounting Applications and Alarm Verification
Product supplier shall provide EEE / C installation Method and Procedure for all mounting applications
and alarm verification (M&P on how to simulate an alarm).
2.23.2. Torque Values
M&P and wiring schematics must contain torque values for all fasteners.
2.23.3. Wiring Schematics
Product supplier shall provide EEE / C wiring schematics in a separate PDF formatted documents.
2.23.4. Elevation Drawings
Product supplier shall provide EEE / C equipment layout, front, rear and side elevation drawings as
applicable in separate
PDF formatted documents.
2.23.5. Computer Generated Thermal Analyses
Product suppliers shall provide computer generated thermal analyses of the EEE / C at maximum load
configuration at the time of approval. Soft copies of thermal reports shall be in PDF or other universal
read only format.
2.23.6. DC Power Consumption
Product suppliers shall provide the power consumption for each DC powered device within the fully
configured cabinet in a spreadsheet format i.e. watts or amps. The spreadsheet shall include a grand total
for the configuration.
2.24. EEE / C Photographs
2.24.1. Doors Closed
Product suppliers shall provide 2 dimensional photographs of all sides of the EEE / C with all doors
closed for use in an internal AT&T on line catalog.
2.24.2. Doors Open
Product suppliers shall provide photographs of all sides of the EEE / C with all doors open, showing the
equipment configuration. These photographs will be of sufficient quality and size to identify the major
components inside the EEE / C.
2.24.3. Format
All Photos shall be submitted in .jpg format.
2.25. Product suppliers Explosion sheet.
Product suppliers shall complete ATT Procurement detail major, and minor material explosion worksheets
provided by ATT SME.
2.26. RETROFIT NETWORK ELEMENTS
2.26.1. Thermal Analyses
All Product suppliers offering retrofit Network Elements shall have the ability to provide Thermal analyses
of third party Remote Terminals currently deployed. Note: some EEE / C are Manufacture Discontinued
which may require an onsite field visit by the NE OEM engineering representative.
2.26.2. Data Gathering
It is the Product Suppliers responsibility, with AT&T permission, to gather data on retrofit EEE / C
candidates.
2.27. Reasons for Reissue
2.28. Effective Date of this Issue
Compliance to new or modified requirements added to this issue of AT&T-TP-76205 will be required
immediately
2.29. Comments
Comments or questions regarding the content of this section should be directed to:
Jeffrey Smith, Sr Tech Support Analysis Network / Local Network,
240 N. Meridian Street, Room 1788
Indianapolis, IN.46240
317.685.2864, js4394@att.com:
3. GR Tests Checklist
Product Suppliers may be required to complete multiple GR Checklists depending on equipment being
offered and its application. At an entry level AT&T requires all Requirements (R) per GR to be met.
AT&T reserves the right to require Optional (O) or Conditional Requirements (CR) be met.
3.1. Product Suppliers Responsibilities.
Product Suppliers shall complete the GR checklist as required by AT&T SME
3.2. GR Checklist Summary
Product Suppliers shall provide a GR Checklist results summary in a spreadsheet format in addition to the
Lab reports.
3.3. GR3108 issue II Checklist
GR-3108 issue II Testing Checklist
Note; GR3108 reports are required for components and sub-components within in the EEE/C not subject to
ATT-TP-76200.
Microsoft Office
Excel Worksheet


3.4. GR487 issue III Checklist
GR 487 issue III Testing Checklist
Microsoft Office
Excel Worksheet


3.5. GR950 Issue II Checklist
GR-950 issue II Testing Checklist
Microsoft Office
Excel 2003 Worksheet


4. HAZARDOUS SUBSTANCES DECLARATION


Supplier: Product Name: Product ID: Nomenclature (Acronym):
The supplier declares that it complies with all laws and regulations that apply to this product. Specifically,
the supplier shall declare if this product contains any hazardous substances listed by the regulatory
agencies (USEPA, US OSHA, state and local regulatory bodies) in excess of the allowabe maximum level
of content listed

The supplier shall complete Page 2 and Page 3 of this form to declare:
1. If the product contains hazardous substances as defined by the regulatory agencies (USEPA, US
OSHA, state and local regulatory bodies) and, if so, the supplier shall identify the material and the steps
that should be taken to mitigate it toxicity.
2. If the product contains any of the following hazardous substances, why the substances cannot be
removed.
Lead
Mercury
Cadmium
Hexavalent Chromium
Polybromonated biphenyls (PBBs)
Polybrominated diphenyl ethers (PBDE).
Please circle the correct answer.
(Company name) has caused this Letter of Declaration to be executed by its duly authorized
representative as of the date written below.
By: Title: Date: NOTE: This affidavit must be signed in front of a notary and notarized.

4.1. Form HSD, Page 2
4.1.1. Product Declaration

NOTE:
Answer No if no hazardous substance present per each directive, yes if present:
Should the suppliers products contain any of substances listed above, the supplier shall declare
the restricted substance and whether that the product falls into one of the following categories: .
A. The product contains the listed hazardous substances because no environmentally preferable
alternative exists for the banned chemical. The alternative is technically or scientifically
impracticable. [and] the negative environmental, health and/or consumer safety impacts outweigh
the benefits of alternative or does not meet AT&T OPERATIONS requirements of health and
safety or network reliability. The supplier has provided sufficient documentation based on
comprehensive environmental life cycle assessment (ISO 14040-ISO 14043) and reliability data.
B. Other: Explain (i.e the product contains the listed hazardous substance in excess of the
maximum concentration level. The supplier has provided separate corrective action plan
regarding the chemicals replacement.
This action plan shall include the specific actions and time lines required to replace or eliminate
the use of the restricted hazardous substance.)
E. 5. Description of component.
F. 6. Reasons for non-compliance
G. 7. If EPA hazardous materials are identified, complete Page 3
4.2. Form HSD, Page 3
Declaration of EPA Hazardous Materials Mitigation Procedures
Manufacturer Product Name
4.2.1. Hazardous Material #1
Identify steps to
Avoid Exposure
Avoid injury or further physical damage, if accidentally exposed:
Properly dispose of substance
Where are these steps identified in manufacturers documentation?
For each hazardous material identified for the product on Form HSD Page 2 complete the following (add
more as necessary):
NOTE:
Repeat as needed to list all Hazardous Material.
5. AT&T-TP-76205 PRODUCT EVALUATION PROCESS
5.1. EEE / C Approval Process,
ATT SME will provide details on the approval process to be followed.
5.2. Documentation
Documentation verifying that the product has been tested and conforms to applicable AT&T-TP-76205
requirements must be submitted to the company representative. There are two acceptable processes, for
supplying documentation verifying conformance, they are (1) Test Report Documentation Package and
(2) Letter of Attestation (only with prior AT&T approval).
5.2.1. Test Report Documentation Package (most preferred)
Product information shall be in an organized fashion and provided to the company representative. A cover
memo identifying included documentation should be included as a matter of convenience to facilitate the
evaluation process. If available, informative product awareness brochures should also be provided but
are not required.
Test Report Details
Test report must be submitted on the Testing facility stationary with points of contact information.
Photos of equipment under test are encouraged.
Test report number
Description of Equipment Under Test (EUT), including specific test configurations.
Location and date of test
Description of test equipment
Calibration dates of test equipment
Test case description with stated pass/fail/compliance criteria
Test result data
Assessment of whether equipment passed or failed the test
Detailed notes on any anomalies during test procedure
Detailed notes on any modifications made to the equipment in order to pass the test and detailed plans
to incorporate the modifications into the final product
The lab shall include a signed certification letter with the test report.
ATT reserves the right to require a Professional Engineer to certify the EEE/C structure in some
locations.
NOTE:
If the documentation is being submitted electronically the file name or file folder shall clearly
identify the files contents (e.g. GR-487 or 950 test data). Reference the file name in the Doc cell
for applicable requirements.
5.2.2. Letter of Attestation (only with prior AT&T approval,
normally used with legacy vendors)
AT&T OPERATIONS LETTER OF ATTESTATION
Network and Mobility Remote Terminal Electronic Equipment Cabinets / Enclosures Compliance to AT&T
Operations Technical Publication AT&T-TP-76205 Requirements
(Company name) hereby asserts, to the best of its knowledge, using good engineering judgment attests
the following EEE/C are compliant to ALL applicable AT&T OPERATIONS LEC Technical Publication
AT&T-TP-76205, TP76200 any and all applicable AT&T-TP documents. Products will also meet
Telecordia GR3108, 487 or 950 requirements. Product supplier shall also provide Compliance test data in
a timely manner.
Equipment vendor name:
Equipment model:
Name of test Facility/internal organization performing tests:
Date of test report(s):
Test report number(s):
Mark the AT&T-TP-76205 Requirements to which the equipment conforms.
Network Element GR3108 Requirement Level: Class 1, Class 2, Class 3 or Class 4
Cabinet and or Enclosures: GR487, or GR950.
(Company name) agrees that statements made in this letter may be audited by AT&T Operations via a
review of compliance confirmation data (the reports listed above), and that this data will be made
available to AT&T Operations within 20 business days of request. If the above equipment is determined to
not meet AT&T Operations requirements as attested to, __ (company name) __ acknowledges and
agrees that, at its expense, it will remedy any such non-compliance in accordance with the terms of the
contract under which the equipment was evaluated/purchased and/or licensed.
(Company name) has caused this Letter of attestation to be executed by its duly authorized
representative as of the date written below. (Company name)
By: _____________________________ Title: _____________________________ Date:
_____________________________
NOTE:
This affidavit must be signed in front of a notary and notarized Contact information to request test
reports
Name: _________________________________ Phone number: _________________________
NOTE:
Information describing the product must accompany the Letter of Attestation (e.g., brochures,
pamphlets etc.)Disclosure of modifications used to this equipment which are necessary to meet
AT&T-TP-76205 requirements:
5.2.3. Product Change Notice Statement
LETTER OF ATTESTATION - PCN
Equipment Compliance to AT&T Operations Technical Publication AT&T-TP-76205 Requirements
(Company name) hereby asserts, to the best of its knowledge, and pursuant conclusions drawn from
sound engineering judgment, that the PCN described below has been evaluated as having no significant
impact to the compliance of the equipment listed below to ALL applicable AT&T OPERATIONS LEC
Technical Publication AT&T-TP-76200 requirements, except as noted below
Equipment vendor name:
Equipment model PCN is for:
PCN Number:
Description of PCN:
AT&T-TP-76205 requirements NOT COVERED by this document (Describe the engineering justification
for concluding the PCN will not affect AT&T-TP-76205 compliance:
(Company name) has caused this Letter of Attestation to be executed by its duly authorized
representative as of the date written below.
By: _____________________________ Title: _____________________________ Date:
_____________________________ Phone number: ________________________
6. APPENDIX B: AT&T-TP-76205 PRODUCT CHANGE TEST
GUIDELINES
6.1. Purpose
The purpose of this appendix is to provide product suppliers a guide to help determine what tests may not
need to be performed on a product enhancement to verify conformance to AT&T-TP-76205 Ancillary
requirements.
6.2. 5.2. General
Some product enhancements are so minor that a complete retest of the product may not be necessary.
Typically, when a product supplier requests a re-test waiver to run tests on product enhancements, data
comparing the new product to the existing product is submitted to the company representative for
evaluation by AT&T Operations. Depending on the product under review, this data may include pictures,
descriptions of electrical components, etc. Each AT&T Operations product evaluation subject matter
expert (SME) then reviews this data and responds with an assessment of what tests are required. This
Appendix is a guideline only. It is the product suppliers responsibility to satisfactorily document that the
new product conforms to applicable requirements. This Appendix only applies to product enhancements
to equipment previously evaluated as in conformance to applicable AT&T-TP-76205 requirements and
approved for use in AT&T OPERATIONS.
Hardware upgrades/changes shall be revaluated if it involves:
Additional or revised hardware.
Activation of previously unused hardware
An increase in the amount of power (AC or DC) consumed.
Changes in increase of thermal load.
Changes to the internal or external air flows.
Changes that raise the over all cabinet or enclosure acoustic levels.
Changes to the cabinet or enclosures exterior that would affect solar loading (i.e change in paint color or
third party wrapping or applications).
Changes that would affect the weather tightness of the cabinet or enclosure.
Changes that would affect the EMI or FCC part 15 rating of the cabinet or enclosure.
Changes that would affect the original internal equipment layout.
Creating non factory authorized openings in the outer protective layer of material that protects the
electronic equipment from the environment.
6.3. Approval by Similarity
6.3.1. Acceptance of a new EEE/C by similarity as compared
with a previously Approved Product.
Generally, if a EEE /C having the same function, size, weight, physical and electrical properties as well as
possessing the same or similar material components to that of a product(s) that has been previously
tested and passed, the configuration need not be tested again. ATT reserves the right to determine if the
proposed product meets the criteria below or if additional testing is required.
A written statement is required from an approved testing lab and/or OEM validating the following
1. The material is indeed same or similar to an ATT approved product.
2. Product A contains the same or similar material as Product B
3. Product A has the same or similar physical and electrical characteristics as product B
4. Product A has the same or similar power and thermal characteristics as Product B.
5. Any dissimilarity between Product A and Product B.
7. Acknowledgements
BIJO ABRAHAM, B DUANE ARNOLD, MORGAN F BARNES, PAUL FEARN, MIKE KARSAS, KIM A
MALKOWSKI, JACK B. SPENCER JR., Steve Area
8. Contact List
Name ATTUID Phone # Department / Title
BIJO ABRAHAM ba2157 (214) 320-7919 SR TECH SUPPORT ANALYSIS
NTWK
B. DUANE ARNOLD ba5811 (817) 370-4002 AREA MGR NETWORK OPS
CTR
MORGAN F. BARNES mb0442 (205) 977-2790 SR TECH SUPPORT ANALYSIS
NTWK
PAUL FEARN hf4977 (214) 486-8228 SR TECH SUPPORT ANALYSIS
NTWK
MIKE KARSAS mk2428 (317) 265-2337 SR TECH SUPPORT ANALYSIS
NTWK
KIM A. MALKOWSK km3526 (614) 856-4405 SR TECH SUPPORT ANALYSIS
NTWK
JEFFREY A. SMITH js4394 (317) 685-2864 SR TECH SUPPORT ANALYSIS
NTWK
JACK B. SPENCER JR. js9082 (214) 486-8414 SR TECH SUPPORT ANALYSIS
NTWK
Steve Area sa7823 (785) 276-8024 SR TECH SUPPORT ANALYSIS NTWK
Revision Log
Issue Number Date Description Published By
Date ATTUID
Acronyms
A.1. Document Specific Acronyms
A.2. Acronyms Dictionary
Refer to ATT-000-000-020, Acronyms Dictionary.

You might also like