QUICK PROGRAMMING GUIDE FOR ALARM CONTROL PANEL 62

ATTENTION: This quick programming guide presents the most used programming ADDRESSES when installing the CA62 alarm control panel,
and their parameters / attributes.
General Programming Structure:
1. Enter engineer code (7777 by default);
2. Enter a 4-digit ADDRESS number;
3. Enter ADDRESS parameter(s) or attribute(s);
4. Use ENT button to confirm or CLR button to reject the
entered data - back to item 2;
5. Use CLR button to exit the engineer menu.

CONFIRM
ADDRESS

CODE

PARAMETER
EXIT

REJECT

General Programming Rules:


1. You can access the engineer programming menu only when the system is disarmed!
2. To enable a parameter (type 1, 2 ... 6) press a digit number corresponding to the respective parameter number. The next pressing of the same
number will disable the parameter.
3. To enable a parameter (type NO, YES) press a random digit number. The next pressing of a random digit number will disable the parameter.

Exit

ENGINEER CODE

MENU: GENERAL PARAMETERS

ADDRESS

DESCRIPTION

0000

Changing the engineer code

Enter new code - 4 or 6 digits

0020

Walk test

Test the zones one by one for correct indication in opening

0030

Setting the clock

Enter sequentially HH: (hour:minutes)

ENT

0031

Setting the date

Enter sequentially DD: (day:mount)

ENT

0040

Chime signal

ACTION / PARAMETERS

NO

ENT
CLR

ENT

YES

MENU: CODES

1000

Default configuration

ENT

Enter a number of default configuration: 0, 1, 2 or 3

Note: The alarm control panel 62 supports 4 default configurations, as every of them include different range of general parameters
programmed by default. After realizing a full hardware reset of the CA62 control panel the default configuration number 0 is set on.

1010

ENT

User Code 01*


1. DISARM

3. BYPASS
ZONES

2. STAY ARM

4. PROGRAM 5. PARTITION 6. PARTITION

* All other User codes are programmed in the same way but on separate addresses, respectively 10, for codes xx= from 02 to 20.

MENU: ZONES

2010

Enter the
type of
ZONE 01

Only one Zone type can be selected. Zone 01 and Zone 07 are Keypads Zones.
0. Unused 1. EntryExit

2011

2. Follow

5. Panic

6. Tamper 7. Medical

8. KeySwitch

9. Auxiliary

ENT
2. Bypass

3. Stay ARM

4. Force
ARM

5. Double

ZONE 01 Attachment

6. E/E Final
ARM

ENT

ZONE 01 Attributes 2
1. Bell Delay

2015

4. Fire

ZONE 01 Attributes 1
1. AutoBypass

2012

3. Instant

ENT

2. Silent
Panic

Partition
Partition

ENT

3. Video On
Armed

4. Write to
LOG

5. Chime

CLR

ADDRESS
2020

DESCRIPTION

ACTION / PARAMETERS

Enter the
type of
ZONE 02*

Only one Zone type can be selected.


0. Unused 1. EntryExit

2021

2. Follow

5. Panic

6. Tamper 7. Medical

8. KeySwitch

9. Auxiliary

ENT

ZONE 02 Attachment

2. Bypass

Partition
Partition

2026

4. Fire

ZONE 02 Attributes 1
1. AutoBypass

2025

3. Instant

ENT

3. Stay ARM

4. Force
ARM

5. Double

6. E/E Final
ARM

ENT
ENT

ZONE 02 Hardware
1. EOL

2. Fast /Regular
(10/250ms)

3. Power-up
delay

4. Doubling

* All other ZONES are programmed in the same way but on separate addresses, respectively 20, as is a zone number from 03 to 12.

MENU: PGM OUTPUTS


3010

ENT

PGM 01 Parameters 1**


1. ALARM

3011

2. PANIC

4. FIRE

5. FIRE RESET 6. ON / OFF

ENT

PGM 01 Parameters 2
1. MEDICAL 2. PS/ BYPASS

3012

3. TAMPER

PGM 01 Attachment

Partition
Partition

3. SIREN

4. TECH. TRBL 5. Pulse/Latch 6. POLARITY

ENT

** PGM 02, PGM 03 and PGM 04 are programmed analogically as PGM 01 but on separate addresses, respectively 30, as xx is output
number from 02 to 04. It is recommended to use the PGM 04 output for connecting of a siren. PGM 04 is coresponding to the " SIREN "
output on the PCB.

MENU: PARTITIONS
4010

Exit time for Partition ***

Enter exit time from 00 up to 99 sec.

ENT

4011

Entry time for Partition ***

Enter entry time from 00 up to 99 sec.

ENT

4012

Bell time for Partition ***

Enter bell time from 00 up to 99 min.

ENT

4016

Attributes Partition ***

ENT
1. One squeak 2. Two squeaks 3. Auto ARM
Enable
when ARM when DISARM

4. ARM
Full / Stay

*** The Partition is programmed analogically but on separate addresses: 4020, 4021, 4022, 4026.

MENU: PERIPHERAL DEVICES


7000

Keyboard address

7010

Keyboard 01 Settings ****

Displays on each keyboard its address configured with jumpers

ENT
ENT

1. Partition

2. Partition

3. Chime
Disable

4. Keyboard
zone

5. Silent panic 6. Zone enable

**** All other keyboards are programmed in the same way but at different addresses 70, as is a number of a keyboard from 02 to 08.

With a marked field are shown the parameters set by default after hardware or software reset of the CA62 control panel.

QUICK MANAGERS & USERS GUIDE FOR ALARM CONTROL PANEL 62


ATTENTION: This quick managers and users guide presents the most used programming ADDRESSES for daily working with the CA62 alarm
control panel.
CONFIRM
CODE
General Programming Structure - MANAGER & USER:
1. Enter manager (0000 by default) or user code;
2. Enter an ADDRESS number:
- 3-digit ADDRESS for the MANAGER Menus;
- 1-digit ADDRESS for the USER Menus.
3. Enter ADDRESS parameter(s) or attribute(s);
4. Use ENT button to confirm or CLR button to reject the entered data - back to item 2;
5. Use CLR button to exit the engineer menu.

ADDRESS

PARAMETER
EXIT

REJECT

Exit

MANAGER CODE

CLR

MENU: CODES

ADDRESS
010
011

DESCRIPTION
User code 01*

ACTION / PARAMETERS
ENT

Enter a 4 or 6-digits code combination for the User 01.

ENT

User Code 01 Attributes*


1. DISARM

012

Proximity card register*

013

Proximity card delete*

2. STAY ARM

3. BYPASS
ZONES

4. PROGRAM 5. PARTITION 6. PARTITION

Put the card close to the proximity reader.

ENT

ENT

* All other User codes are programmed in the same way but on separate addresses, respectively XXY, where XX is the number of the user
(from 02 to 20) and the Y is the number of the operation (from 0 to 3).
Example: At ADDRESS 051 the MANAGER will program the attributes for User code 05.

210

Chief Manager Code**

ENT

Enter a 4 or 6-digits code combination.

* * Up to 4 Managers are supported in system: 1 Chief and 3 Sub-managers. The code combinations for Sub-managers 1, 2 and3 are
programmed analogically at addresses 220 (Sub-manager 1), 230 (Sub-manager 2) and 240 (Sub-manager 3).

MENU: SYSTEM

300

Display LOG memory

400

Chime signal

Use t button to view previous the event and u to view the next.
NO
YES

ENT

500

Bypass zones

Press a digit number of the zone: 1 for ZONE 1, 2 for ZONE 2, ...,
9 for ZONE 9. Use the combinations: ARM+0 for ZONE 10,
ARM+1 for ZONE 11 and ARM+2 for ZONE 12.

600

Setting the clock

Enter sequentially HH: (hour:minutes)

ENT

601

Setting the date

Enter sequentially DD: (day:mount)

ENT

ENT

Exit

USER CODE

ADDRESS

CLR

DESCRIPTION

ACTION / PARAMETERS

Change own code

Enter 4 or 6-digits new code combination.

ENT

Display LOG memory

Use t button to view previous the event and u to view the next.

CLR

Chime signal

NO
YES

Bypass zones

ENT

Press a digit number of the zone: 1 for ZONE 1, 2 for ZONE 2, ...,
9 for ZONE 9. Use the combinations: ARM+0 for ZONE 10,
ARM+1 for ZONE 11 and ARM+2 for ZONE 12.

With a marked field are shown the parameters set by default after hardware or software reset of the CA62 control panel.

ENT

CLR

TECHNICAL TROUBLE INDICATION


LED Keyboard
(LED lighing up)

LCD Keyboard
(Digit in brackets)

Technical Trouble
No 220V power supply.
Battery low.
Fuse burned
No telephone line.
No communication available.
Active TAMPER within the system.

Any technical trouble in the panel will light up the Trouble indicator (blinking TRBL LED and/ or symbol "wrench"
according of the keyboard model). To view these problems enter the 0000 manager code and single-press
ENTER. The display will indicate a list of current problems.

HEXADECIMAL PROGRAMMING TABLE


BUTTONS
COMBINATIONS
LED 3 LED 4 LED 5 LED 6

ARM + 0

ARM + 1

ARM + 2

ARM + 3

ARM + 4

ARM + 5

Legend:
- The LED is off.
- The LED is on.
The expression "ARM + 1" means pressing the "ARM"
and "1" buttons in succession.

Detailed information for all available addresses in CA62 system and the
requirements for mounting and installation, you can find in Alarm Control
Panel CA62 - Installation and programming manual, number 18020603 available at your distributers office as a printed book, or as a PDF version
on our web site www.teletek-electronics.com.

18020630