Objective

SINAMICS V20 Firmware Upgrading Process

Overview
:
The Analogue input of V20 was updated from 10 bit to 12 bit in the FW version 3.51.06. So, V20 drive
whose firmware version less than FW3.51.06 need to be updated to FW3.51.06 or higher.
Note: It is mandatory to do parameter calibration after upgrading firmware from lower version to
3.51.06 or higher.
If the V20 drive has already version 3.51.06 or newer version then it does not needed parameter
calibration after firmware up gradation.
The version information of V20 can be found in the parameter r0964.

Parameter
r0964[0]
r0964[1]
r0964[2]
r0964[3]
r0964[4]
r0964[5]
r0964[6]

Description
Company(Siemens=42)
Product Type
Firmware Version
Firmware date (yy)
Firmware date (ddmm)
Number of inverter Objects
Firmware Version

Values
42
8001
350
2012
2806
1
2400

From above it is clear that the firmware version is 3.50. so, it is mandatory to do calibration after
upgrading to FW 3.51.06 or higher.

TC-MC-GMC-C-0011-FY14

Following is the process to update the SINAMICS V20 drive firmware to 3.51.06 or
higher.
Step 1: Copy the delivered LM3_crc.rec,Im3_load.rec and sectstage.bin file to SD/MMC.
Step 2: Insert the SD/MMC card into the SINAMICS V20 Parameter Loader.

Step 3: Switch-off the V20 drive incoming AC power supply.


Step 4: Plug-in the Parameter Loader into the SINAMICS V20 drive.

TC-MC-GMC-C-0011-FY14
SINAMICS V20 Firmware Updating Process

Page 2 of 5 S

Step 5: Press the white button to active the inverter. Updating starts automatically and the LED is
lit up.

Step6: Observe the LED status as it gives the result of firmware updating process.
LED

Firmware
updation

Status

Status

Continuously Lit

In process

Flash at 0.5 Hz

Success

Flash at 0.2 Hz

Fail

Description

Firmware updation is continue


Firmware updation is successfully completed
Firmware updation is failed

TC-MC-GMC-C-0011-FY14
SINAMICS V20 Firmware Updating Process

Page 3 of 5 S

Following is the process to calibrate after updating SINAMICS V20 drive firmware to
3.51.06 or higher.
Step1: After successful updation of SINAMICS V20 drive firmware ,remove the Parameter loader
unit from drive.
Step2: Switch-on the V20 drive incoming AC power supply.
Step3: Set parameter P3950=1.
Step4: Read the following parameters from the drive and note it down.
Parameter
P3935[0]
P3936[0]
P3936[1]
P3903[0]
P3904[0]
P3904[1]
P3937
P3938

Value
508
692
356
508
900
779
58
856

Step5: Calculate the calibration value by multiplying 4 to the above parameter values as below.
Parameter
P3935[0]
P3936[0]
P3936[1]
P3903[0]
P3904[0]
P3904[1]
P3937
P3938

Calibration Value
4*P3935[0]
4*P39360]
4*P3936[1]
4*P3903[0]
4*P3904[0]
4*P3904[1]
4*P3937
4*P3938

Set
Value
2032
2768
1424
2032
3600
3116
232
3424

TC-MC-GMC-C-0011-FY14
SINAMICS V20 Firmware Updating Process

Page 4 of 5 S

Step6: Set the calibrated value in to the parameters as below.


Parameter

Value

P3935[0]
P3936[0]

2032
2768

P3936[1]

1424

P3903[0]
P3904[0]
P3904[1]

2032
3600
3116

P3937

232

P3938

3424

Step7: Power off the drive. The setting will be applied in the next round power cycle.

TC-MC-GMC-C-0011-FY14
SINAMICS V20 Firmware Updating Process

Page 5 of 5 S