MultiLoad II

Communications Guide
Including:

MultiLoad II
MultiLoad II SMP
MultiLoad II Mobile

Part # 6077
Firmware Version 3/4.31.00
March 2011

Copyright Notice
Copyright 2000 - 2011 Toptech Systems, Inc.
The information contained in this document is proprietary and confidential. No part of this document may be copied, reproduced, or
transmitted in any medium without the express written permission of Toptech Systems, Inc.

Disclaimer
Toptech Systems assumes no responsibility for damages resulting from installation or use of its products. Toptech Systems will not be liable
for any claims of damage, lost data, or lost time as a result of using its products.

Toptech
Systems, Inc.
logo is a registered trademark of Toptech Systems, Inc.
TMS, TMS5, TMS6, RCU II Remote Control Unit, Toptech MultiLoad II, MultiLoad II -RCU, MultiLoad II
1-Arm, MultiLoad II - SMP, FCM Flow Control Module are trademarks of Toptech Systems, Inc.
Copyright 2000 - 2011 Toptech Systems, Inc. All Rights Reserved.

Table of Contents
CHAPTER 1
PROTOCOL SPECIFICATION ..................................................................................................... 6
1.1
DEFINITIONS ............................................................................................................................................ 6
1.2
SMITH PROTOCOL .................................................................................................................................... 7
1.3
BROOKS PROTOCOL ................................................................................................................................. 7
1.4
DANIELS PROTOCOL ................................................................................................................................. 7
1.5
MODBUS-RTU PROTOCOL ........................................................................................................................ 8
1.5.1 Read Holding Registers (fn=3) .......................................................................................................... 8
1.5.2 Write Single Registers (fn=6)............................................................................................................. 8
1.5.3 Loopback/Maintenance (fn=8) ........................................................................................................... 9
1.5.4 Preset Multiple Registers (fn=16) ...................................................................................................... 9
1.5.5 Error Responses (fn= +128) .............................................................................................................. 9
1.5.6 Modbus Register Map Summary ..................................................................................................... 10
1.5.7 Extended Services Register ............................................................................................................ 10
CHAPTER 2

MULTILOAD COMMAND RESPONSES ................................................................................... 11

CHAPTER 3

QUERY COMMAND: .................................................................................................................. 13

CHAPTER 4

FUNCTION COMMANDS: .......................................................................................................... 14

CHAPTER 5
TERMINAL COMMANDS: .......................................................................................................... 15
5.1
TERMINAL ESCAPE COMMANDS:.............................................................................................................. 15
CHAPTER 6
METER COMMANDS: ................................................................................................................ 20
6.1
AUTHORIZE PRESET (PRODUCT AND PRESET VOLUME): ........................................................................... 20
6.2
CLEAR ALARMS: ..................................................................................................................................... 20
6.3
ENABLE PRESET .................................................................................................................................... 20
6.4
END TRANSACTION................................................................................................................................. 20
6.5
BATCH COMPLETE .................................................................................................................................. 21
6.6
BATCH END:........................................................................................................................................... 21
6.7
END BATCH:........................................................................................................................................... 21
6.8
PRESET MESSAGE: ................................................................................................................................ 22
6.9
PROVING TRANSACTION MODE: .............................................................................................................. 22
6.10
REQUEST STATUS & PRESET ALARMS: .................................................................................................... 23
6.11
REQUEST SMP STATUS & PRESET ALARMS: ........................................................................................... 46
6.12
TRIP PRESET ALARMS: ........................................................................................................................... 46
6.13
REQUEST BAY ALARMS: ......................................................................................................................... 47
6.14
REQUEST COMPONENT ALARMS: ............................................................................................................ 48
6.15
REQUEST METER ALARMS: ..................................................................................................................... 49
6.16
REQUEST ADDITIVE ALARMS: .................................................................................................................. 50
6.17
START PRESET FLOW : ............................................................................................................................ 51
6.18
STOP PRESET FLOW: ............................................................................................................................. 51
CHAPTER 7
REGISTER OPERATIONS: ........................................................................................................ 52
7.1
GENERIC REGISTERS ............................................................................................................................. 53
7.1.1 Register Data Types ........................................................................................................................ 53

7.1.2 000 RCU Level Configuration Registers ...................................................................................... 59


7.1.3 100 Bay Level Configuration Registers ........................................................................................ 61
7.1.4 101 Preset Level Configuration Registers .................................................................................... 62
7.1.5 102 Meter Level Configuration Registers ..................................................................................... 65
7.1.6 103 Component Level Configuration Registers ............................................................................ 68
7.1.7 104 Additive Level Configuration Registers ................................................................................. 70
7.1.8 105 Custom Logic Definitions Registers ...................................................................................... 72
7.1.9 200 Stand Alone BOL Definition Registers .................................................................................. 76
7.1.10
800 Transaction Archive Registers .......................................................................................... 79
7.2
SPECIAL PURPOSE REGISTERS ............................................................................................................... 81
7.2.1 000 MultiLoad Firmware Version .................................................................................................. 81
7.2.2 001 Date and Time ....................................................................................................................... 81
7.2.3 003 FCM Poll Rate ....................................................................................................................... 81
7.2.4 005 Current BOL/Ticket Number .................................................................................................. 81
7.2.5 070 Ethernet Enable ..................................................................................................................... 81
7.2.6 071 IP Address ............................................................................................................................. 82
7.2.7 072 IP Mask .................................................................................................................................. 82
7.2.8 073 IP Gateway ............................................................................................................................ 82
7.2.9 074 IP Host ................................................................................................................................... 82
7.2.10
085 Modem Initialization String ................................................................................................ 82
7.2.11
091..093 Communication Port Parameters .............................................................................. 82
7.2.12
095..099 Program Mode Passwords (5) .................................................................................. 83
7.2.13
112 - Real-Time Preset Total Gross Totalizers ........................................................................... 84
7.2.14
113 - Real-Time Preset Total Net Totalizers ............................................................................... 84
7.2.15
133 FCM IO Access ................................................................................................................. 84
7.2.16
140 Current Latitude/Longitude position Registers (MultiLoad Mobile Only) ........................... 85
7.2.17
141 Current Transaction Latitude/Longitude/Site Index Registers (MultiLoad Mobile Only) ... 86
7.2.18
400 - Preset Definition Registers ................................................................................................ 86
7.2.19
401 External Preset Display Register ...................................................................................... 87
7.2.20
500 - Product Definition Registers .............................................................................................. 87
7.2.21
600 - Standalone Driver Card Database ..................................................................................... 88
7.2.22
650 GPS Site Database (MultiLoad Mobile Only) ..................................................................... 88
7.2.23
700 - Configurable Language Prompts ....................................................................................... 89
7.2.24
710 - Bay Alarm Messages ......................................................................................................... 89
7.2.25
711 - Preset Alarm Messages ..................................................................................................... 91
7.2.26
712 - Meter Alarm Messages ...................................................................................................... 92
7.2.27
713 - Component Alarm Messages ............................................................................................. 94
7.2.28
714 - Additive Alarm Messages .................................................................................................. 96
7.2.29
910 Read Event Log Message Queue ..................................................................................... 97
7.2.30
912 Read W & M Change Log Message Queue ...................................................................... 98
7.2.31
950 - Current Driver Card Number .............................................................................................. 98
7.2.32
951..954 - Current Driver Prompt Information ............................................................................. 98
7.2.33
960 Input Data .......................................................................................................................... 98
7.2.34
961 Input Data Terminating Key .............................................................................................. 99
7.2.35
962 - Current Driver Card Data ................................................................................................... 99
7.2.36
998 Bitmap Graphic Cache .................................................................................................... 101

CHAPTER 8
COMMUNICATION TRACE EXAMPLE ................................................................................... 102
8.1
STARTUP OF HOST SOFTWARE ............................................................................................................. 102
8.1.1 Update Date & Time ...................................................................................................................... 102
8.1.2 Update Product Definitions ............................................................................................................ 102
8.1.3 Update Preset Definitions .............................................................................................................. 103
8.1.4 Status Query .................................................................................................................................. 103
8.2
TRANSACTION AUTHORIZATION ............................................................................................................. 104
8.2.1 Process Driver Card In .................................................................................................................. 104
8.2.2 Authorize a Transaction on MultiLoad ........................................................................................... 105
8.2.3 Reading Totalizers ......................................................................................................................... 105
8.3
BATCH AUTHORIZATION ........................................................................................................................ 106
8.3.1 Authorize a Batch on MultiLoad ..................................................................................................... 106
8.3.2 Monitor Load During Delivery ........................................................................................................ 108
8.4
END OF BATCH PROCESSING ................................................................................................................ 108
8.4.1 Ending a Batch on MultiLoad......................................................................................................... 108
8.5
END OF TRANSACTION PROCESSING ..................................................................................................... 109
8.5.1 Ending a Transaction on MultiLoad ............................................................................................... 109
8.6
SHUTDOWN OF HOST SOFTWARE .......................................................................................................... 109
CHAPTER 9
DATA COMMUNICATION NOTES AND RECOMMENDATIONS ........................................... 110
9.1
PROTOCOL SELECTION: RS-232 VS. RS-485 ........................................................................................ 110
9.1.1 RS-232 ........................................................................................................................................... 110
9.1.2 RS-485 ........................................................................................................................................... 110
9.2
CABLE SELECTION................................................................................................................................ 110
9.3
LINE TERMINATION IN MULTI-DROPPED COMMUNICATIONS ..................................................................... 110
9.4
OPTICAL ISOLATION .............................................................................................................................. 111
9.5
SHIELD GROUNDING ............................................................................................................................. 111

Chapter 1 Protocol Specification

CHAPTER 1

PROTOCOL SPECIFICATION

The MultiLoad auto-detects four low level computer protocols for host communications.
- Smith Protocol
- Brooks Protocol
- Daniels
- Modbus-RTU Protocol
Note: All unknown or not allowed signal or code sequences are rejected and have no impact on the
software or measurement data.
Host communication can occur via multi-dropped RS-232/RS-485 serial on COM 1 or Ethernet 10/100 socket
communication on port 7734.

1.1

DEFINITIONS

The non-printing characters that form the skeleton of the Smith and Brooks protocols are standard ASCII
(American Standard Code Information Interchange):

ASCII CHARACTER

DECIMAL

HEX

BINARY

NUL

00000000

STX

00000010

ETX

00000011

SOH

00000001

PAD

127

7F

01111111

CHARACTER

DESCRIPTION

BCC

Block Check Characters. The ASCII hex representation of the binary sum of all
the data in the message from the SOH through the ETX character.

LRC

Longitudinal Redundancy Check. The LRC is an ASCII character computed as


the exclusive or (XOR) sum of all characters following the STX and including
the ETX.

CRC

Cyclic Redundancy Check.

A1..A3

A 3-character ASCII unit address of the MultiLoad. Please refer to the


MultiLoad User Guide for configuring the unit address.

D1..Dn

Data field characters.

Fn

Function field code.

Adr

A single character binary unit address of the MultiLoad.

Chapter 1 Protocol Specification

1.2

SMITH PROTOCOL

The Smith protocol is compatible with devices from Smith Meter, such as the Accuload I and Accuload II mini
computer modes of operation. Using this protocol, MultiLoad accepts data in the format:

NUL

STX

A1

A2

data

ETX

LRC

PAD

A1 and A2 are the last two digits of the unit address in the RCU configuration.

1.3

BROOKS PROTOCOL

The Brooks protocol is compatible with devices from Brooks Instruments such as their Petrocount RAU and
IMS Control units running in computer mode. Using this protocol, MultiLoad accepts data in the format:

SOH

DESTINATION
A1

1.4

A2

A3

SOURCE
S1

S2

STX

data

ETX

S3

BCC
1

BCC
2

DANIELS PROTOCOL

The Daniels protocol is compatible with devices from Daniels Flow Products. Using this protocol, MultiLoad
accepts and responds with data in the format:
Quiet
Time

ADR

FN

LEN
(2 252)

D1...DN

CRC1

CRC2

Quiet
Time

Daniels protocol messages are framed by a quiet time of three and one-half characters.

ADR is binary character of the address of the MultiLoad. Typically 0x01.

Fn is expected to be 0x41/0x42 alternating on each command. Responses will have Fn as 0x41/0x42


for normal responses and 0xc1/0xc2 for exception responses.

D1Dn is string data containing the commands listed in this manual.

Note: Modbus extention to return larger packet sizes: On messages with data packet sizes from 2 to 252
characters the Fn values of 0x41/0x42 will be returned. With messages outside this range, Fn will be the MSB
value of the data size and the Len will be LSB of the data size.
For Example:
Fn = 0x41, Len = 0x80, when data packet size = 0x0080,
Fn = 0x42, Len = 0x80, when data packet size = 0x0080,
Fn = 0x00, Len = 0xFF, when data packet size = 0x00FF ( 255),
Fn = 0x01, Len = 0x00, when data packet size = 0x0100 ( 256),
Fn = 0x01, Len = 0x01, when data packet size = 0x0101 ( 257),
Fn = 0x02, Len = 0x00, when data packet size = 0x0200 ( 512),
Fn = 0x04, Len = 0x00, when data packet size = 0x0400 (1024),
Fn = 0x08, Len = 0x00, when data packet size = 0x0800 (2048).

Chapter 1 Protocol Specification

1.5

MODBUS-RTU PROTOCOL

The Modbus-RTU protocol has been implemented to be as compatible as possible with the original published
Modicon Modbus-RTU standard.
Note: The Modbus protocol allows parameter register access only as defined by the explicit mapping in
this manual. To send the ASCII commands (R000, T`A, MAM, MRS, etc.) that are handled by the other
three protocols, the Modbus Extended Services registers must be used.
Using the modbus protocol, MultiLoad accepts data in the following format:
Quiet
Time

ADR

FN

...

CRC1

CRC2

Quiet
Time

Modbus-RTU protocol messages are framed by a quiet time of three and one-half characters.
ADR is binary character of the address of the MultiLoad. Typically 0x01.
Fn is the Modbus function. Functions implemented are as follows.
The formal specification of Modbus lists the starting Holding Register address as 40001. The Modbus
Holding Register functions (Fn 3, 6 and 16) all have an implied 4XXXX reference. Referencing Holding
Register 40001 is addressed as register 0000 in the register address field in the message for fn 3, 6, and
16.
Since Modbus addressing has been implemented in various ways over the years, to avoid confusion in
this manual, the Modbus Holding Register addresses listed are the value in the register address field in
the message. If it is necessary to know the formal Modbus Holding Register address, simply add 40001
to the register addresses listed in the manual.
1.5.1

READ HOLDING REGISTERS (FN=3)


Note: Both Modbus registers MUST be read at the same time when reading 32-bit values.

Tx:
Number
Quiet Time

ADR

FN=3

Start
Register
MSB

Start
Register
LSB

Of
Registers
MSB

Number
of
Registers
LSB

CRC1

CRC2

Quiet Time

Rx:
FN=3

Quiet
Time

1.5.2

ADR

(+128 if
error)

Byte
Count

1st
Register
MSB

1st
Register
LSB

Next
Register
MSB

Next
Register
MSB

CRC1

CRC2

Quiet
Time

WRITE SINGLE REGISTERS (FN=6)


Note: can not be used for 32-bit registers.

Tx:
Quiet Time

ADR

FN=6

ADR

(+128 if
error)

Start
Register
MSB

Start
Register
LSB

Register

Register

MSB

LSB

Start
Register
MSB

Start
Register
LSB

Register

Register

MSB

LSB

CRC1

CRC2

Quiet Time

CRC1

CRC2

Quiet Time

Rx:
FN=6
Quiet Time

Chapter 1 Protocol Specification

1.5.3

LOOPBACK/MAINTENANCE (FN=8)
Note: only loopback of command supported.

Tx:
Quiet Time

ADR

FN=8

Diagnostic
Code MSB

Diagnostic
Code LSB

Data MSB

Data LSB

CRC1

CRC2

Quiet Time

ADR

FN=8

Diagnostic
Code MSB

Diagnostic
Code LSB

Data MSB

Data LSB

CRC1

CRC2

Quiet Time

Rx:
Quiet Time

1.5.4

PRESET MULTIPLE REGISTERS (FN=16)


Note: Both Modbus registers MUST be written at the same time when writing 32-bit values.

Tx:
Number
Quiet
Time

ADR

FN=16

Start
Register
MSB

Start
Register
LSB

Of
Registers
MSB

Number
of
Registers
LSB

1st
Register
MSB

Byte
Count

1st
Register
LSB

Next
Register
MSB

Next
Register
MSB

CRC1

CRC2

Quiet
Time

Rx:
FN=16
Quiet Time

1.5.5

ADR

(+128 if
error)

Number
Start
Register
MSB

Start
Register
LSB

Of
Registers
MSB

Number
of
Registers
LSB

CRC1

CRC2

Quiet Time

ERROR RESPONSES (FN= +128)

Rx:
Quiet Time

ADR

FN+128

Error
Subcode

CRC2

CRC1

Error Subcodes are:


1 = Invalid Function Code. Indicates that the use of an invalid or unimplemented function has been
attempted.
2 = Invalid Address Field. Indicates that a read or write was made to an invalid address. Can also
indicate that a read or write to a single register of a 32-bit value has been attempted.
3 = Invalid Data Field. Indicates that an attempt to write an invalid value to a register has occured. This
error code will also be returned if an attempt is made to change a value under Weights and Measures control
without with W&M switch being in the active state.
4 = Query Processing Failure. This code is not returned.

Chapter 1 Protocol Specification

1.5.6

MODBUS REGISTER MAP SUMMARY


1 999
1000 1199
1200 1399
1400 1599
1600 1799
1800 1999
2000 2199
2200 2999
3000 3999
4000 6000
7000 7799
7800 - 7999
8000 - 8999
9000-10999

1.5.7

General, BOL Template, MIsc. Configurations.


RCU Configurations
Bay Configurations
Preset Configurations
Meter Configurations
Component Configurations
Additive Configurations
Product, Alarm, Database, Misc. Configurations
Totalizers
Preset, Meter, Component and Additive Status
Status, Authorization Control and Alarms
Transaction Archive
Preset Definitions
Extended Services Register

EXTENDED SERVICES REGISTER

Not all commands native to the MultiLoad II have corresponding mapping to Modbus registers. The Extended
Services register was implemented as a way to support sending and receiving native Multiload II commands
across the Modbus RTU interface. Any native command listed can be sent to the MultiLoad via the extended
Services Register.
Modbus Registers:
Write Holding Register=9000, Len=1, 16-Bit Integer (Command Length)
Write Holding Register=9001, Max Len=999, Characters (Command Text)
Read Holding Register=9000, Len=2, 32-Bit Integer (Reply Length)
Read Holding Register=9001, Max Len=999, Characters (Reply Text)
Perform the following operations to use of the Extended Services Register:
1. Write the Command Length into the Holding Register 9000 (max value of 999 characters).
2. Write the Command Text into the Holding Register 9001 (max length of 999).
3. Command will execute when the final character of the Command Text is written (9001+Command
Length-1).
4. Read the Reply Length from the Holding Register 9000 (max value of 999 characters).
5. Read the Reply Text from the Holding Register 9001 (max length of 999).
Steps 1 & 2 can be done with a single Modbus Function 16.
Steps 4 & 5 can be done with a single Modbus Function 3.

10

Chapter 2 MultiLoad Responses

CHAPTER 2

11

MULTILOAD COMMAND RESPONSES

<command_status> <rcu_status> <card_status> <command specific response data>


For MultiLoad to acknowledge a message two conditions must be meet. First the message must fit the
Message Framing Protocol with a valid LRC, BCC or CRC. Second, the address specified in the first two
characters of the command must match the configured MultiLoad address. Any message that satisfies both of
these requirements will be sent a response.
Modbus:
If using the Modbus protocol, the Modbus Extended Services Registers must be used to pass in
these ASCII string commands.
The first three characters of every response will contain command, RCU and card status data as defined below.
enum
{
VALID_COMMAND
= 0,
INVALID_PARAMETER
= 1,
INVALID_COMMAND
= 2
} command_status;
enum
{
IDLE
AUTH_BAY
MENU_MODE
DIAG_MODE
AUTHORIZING_LOAD
LOAD_AUTHORIZED
COMPLETING_LOAD
TRANSACTION_DONE
TRANSACTION_CANCEL
PULLING_TRANSACTION
ARCHIVING_TRANSACTION
TRANSACTION_AUTHORIZED
RCU_NOT_CONFIGURED
RCU_POWER_UP
INITIALIZING
NO_TRANSACTION
REMOTE_AUTH_PRESET1
REMOTE_AUTH_PRESET2
REMOTE_AUTH_PRESET3
REMOTE_AUTH_PRESET4
REMOTE_AUTH_PRESET5
REMOTE_AUTH_PRESET6
REMOTE_AUTH_PRESET7
REMOTE_AUTH_PRESET8

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

'0',
'4',
'9',
'%',
'A',
'B',
'C',
'D',
'E',
'P',
'R',
'T',
'?',
'!',
'I',
'N',
'a',
'b',
'c',
'd',
'e',
'f',
'g',
'h',

Chapter 2 MultiLoad Responses

REMOTE_AUTH_PRESET9
REMOTE_AUTH_PRESET10
REMOTE_AUTH_PRESET11
REMOTE_AUTH_PRESET12
REMOTE_AUTH_PRESET13
REMOTE_AUTH_PRESET14
} rcu_status;

12

=
=
=
=
=
=

'i',
'j',
'k',
'l',
'm',
'n'

Modbus:
Read Only Register=7000, Len=1, Character (rcu_status)
enum
{
CARD_NOT_INSERTED
CARD_INSERTED
} card_status;

=0,
=1

Modbus:
Read Only Register=7001, Len=1, Character (card_status)
In most cases a command will return additional information specific to the command. This information will
always follow the three status characters. For example if the following valid command to read the current
firmware version is sent:
Command
R000

=>
=>

Response
0?0000MultiLoad II v3.29.xx Jan xx 2009

With 0?0 as the three status characters and 000MultiLoad II v3.29.xx Jan xx 2009 as the command specific
response.

Chapter 3 Query Command

CHAPTER 3

13

QUERY COMMAND:

Query Command
=>
Response
Q
=>
0?0XXXX
Where:
XXXX = 4 digit hexadecimal number with bits representing the rcu_status as:
union
{
unsigned int value;
struct
{
unsigned char rcu_trans_header:1;
unsigned char proving_mode:1;
unsigned char power_up:1;
// indicated system has been powered on
unsigned char configured:1;
// indicates configuration state
unsigned char unassigned_keypress_on_load_screen:1;
unsigned char logmsg_queued:1;
// a log message is available
unsigned char unused6:1;
unsigned char unused7:1;
unsigned char wm_logmsg_queued:1;
// a w&m log message is available
unsigned char host_up:1;
// host system is up, card in will be allowed.
unsigned char input_in_progress:1;
unsigned char input_done:1;
unsigned char unused12:1;
unsigned char reserved13:1;
unsigned char wm_key:1;
// W&M key is active
unsigned char program_key:1;
// Program key is active
} flags;
} rcu_status;
This command also resets the Host Down Timer and should be issued periodically to notify MultiLoad that the
Host is still active.
Modbus:
Read Only Register=7002, Len=1, 16-Bit Integer (XXXX)

Chapter 4 Function Commands

CHAPTER 4

14

FUNCTION COMMANDS:

FREBOOT
=
Performs a software reboot of the MultiLoad RCU.
FFACTORY
=
Restores all MultiLoad registers to factory defaults.
FUPDATEAPPFLASH =
Updates the Flash with an uploaded image (req. W&M and a valid image)
Modbus:
Supported through Modbus Extended Services Registers.
FUNCONFIG
=
Clears the configured RCU status bit.
FRECONFIG
=
Sets the configured RCU status bit.
Modbus:
Write Only Register=7010, Len=1, 16-Bit Integer (any value=FUNCONFIG)
Write Only Register=7011, Len=1, 16-Bit Integer (any value=FRECONFIG)
FPOWERUP
=
Resets the power_up RCU status bit. This bit is set on power up.
Modbus:
Write Only Register=7012, Len=1, 16-Bit Integer (any value=FPOWERUP)
FHOSTUP

Sets the host_up RCU status bit. Cleared on power up or when host down
timeout expires between Q commands. Command should be issued when host
system starts communicating with MultiLoad.

Modbus:
Write Only Register=7013, Len=1, 16-Bit Integer (any value=FHOSTUP)
FHOSTDOWN

Clears the host_up RCU status bit. Command should be issued when host
system stops communicating with MultiLoad.

Modbus:
Write Only Register=7014, Len=1, 16-Bit Integer (any value=FHOSTDOWN)
FHOSTWAIT
=
Bypass host down timer once with alternate timeout.
Modbus:
Write Only Register=7015, Len=1, 16-Bit Integer (any value=FHOSTUP)
FPccc.
FCLEARPROD

=
=

Send ccc characters to the attached printer port (if defined).


Clear all product definitions (500 register) except for the 000-Unknown Product
definition.
Clear Access ID and PIN database.
Clears all custom logic entries.

FCLEARID
=
FCLEARCUSTOM
=
Modbus:
Supported through Modbus Extended Services Registers.

Chapter 5 Terminal Commands

CHAPTER 5

TERMINAL COMMANDS:

Ts
Where:
s = Any text string to display. Display string may contain one or more terminal escape commands.

5.1

TERMINAL ESCAPE COMMANDS:

<ESC><Terminal Escape Command and parameters >


Where Terminal Escape Commands are:
A

Authorize Transaction:
Authorize MultiLoad Transaction. Will display load screen.
Modbus:
Write Only Register=7016, Len=1, 16-Bit Integer (any value=Authorize Transaction)
Cx

Clear RCU counters


Where,
X = counter to clear, 1 = counter 1, 2 = counter 2

Setup Data Entry


Used to display a flashing cursor (Setup Data Entry Length > 1) and allow user input. Data to be
retrieved at R960, R961.

Turn on Big Font


Used to enable double size font.

Turn off Big Font


Used to return to normal size font.

Set Foreground/Background Text Colors


Where:
f = (character) 0x20 + Foreground Color Palette Index
b = (character) 0x20 + Background Color Palette Index
Pixel color palette index values defined as:
Black
= 0x00
Blue
= 0x01
Red
= 0x02
Magenta
= 0x03
Green
= 0x04
Cyan
= 0x05
Yellow
= 0x06
White
= 0x07
Custom 0
= 0x08 (Not available)

15

Chapter 5 Terminal Commands

Custom 1
= 0x09 (Not available)
Custom 2
= 0x0a (Not available)
Custom 3
= 0x0b (Not available)
Custom 4
= 0x0c (Not available)
Custom 5
= 0x0d (Not available)
Flash 1
= 0x0e
Flash 2
= 0x0f
Example: To display a green word 'Hello' code the string as follows:
T<ESC>G$Hello
$ = 0x20 + 0x04 (Green)
= 0x20 + 0x07 (White)
H

Home Cursor to Position (0,0)


Move cursor position to upper left corner of screen.

Ircle

Set Reverse Video


Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
l = (character) 0x20 + Length in Text Columns
e = 0 or 1 (0 = Set Inverse Text, 1 = Clear Inverse Text)

Erase from Cursor to End of Line


Use with after <ESC>Y first to clear an entire line. Can be used as a CR since cursor will be positioned
on next line.

Erase from Cursor to End of Screen


Use with after <ESC>H to clear entire screen.

Lxx

Setup Data Entry Length


Where:
xx = Length of Data Entry Input Required (00-25) (0 = Key Press with No Flashing Cursor)

Turn On Cursor

Turn Off Cursor

R
Reset the RCU Display
Modbus:
Write Only Register=7017, Len=1, 16-Bit Integer (any value=Reset RCU Display)
Yrc

Set Cursor Position


Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)

Clear Entire Display

16

Chapter 5 Terminal Commands

<

Unlock the Display

>

Lock the Display

Turn Character Echo On

Turn Asterisk Echo On

arcwh Draw Progress Box


Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
w = (character) 0x20 + Width in Text Columns
h = (character) 0x20 + Height in Text Rows Down
brcwhp Update Progress Box
Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
w = (character) 0x20 + Width in Text Columns
h = (character) 0x20 + Height in Text Rows Down
p = (character) 0x20 + Percent Value to Display (0 = None, 100 = Full)
crcpf

Display Animation Frame


Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
p = (character) 0x20 + Animation Picture Index
f = (character) 0x20 + Animation Frame Index
Note: Test only since Animation Picture Index and Animation Frame Index values may change between
firmware versions.

df

Display Factory Logo


Where:
f = (character) 0x20 + Factory Logo Index
Note: Test only since Factory Logo Index values may change between firmware versions.

ercwd
Draw Display Graphic
Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
w = (character) 0x20 + Width in Text Columns
d = (character) 0x20 + pixel color palette index values from left to right, top to bottom,
Note: Each text column = 16 pixels wide, each text row = 30 pixels high
Pixel color palette index values defined as:

17

Chapter 5 Terminal Commands

Black = 0x00
Blue
= 0x01
Red
= 0x02
Magenta
= 0x03
Green = 0x04
Cyan = 0x05
Yellow = 0x06
White = 0x07
Custom 0
= 0x08 (Not available)
Custom 1
= 0x09 (Not available)
Custom 2
= 0x0a (Not available)
Custom 3
= 0x0b (Not available)
Custom 4
= 0x0c (Not available)
Custom 5
= 0x0d (Not available)
Flash 1 = 0x0e
Flash 2 = 0x0f
Example: To position a small graphic starting at row 5, column 20, column width 2, code the string as
follows:
T<ESC>e%4
$$$$$$

$$$
$$$$
$$$$$$$$
$$$$$$$$$$
Note: formatted for illustration only, there are no spaces or CRs in the above command.
'%' = 0x20 + 5
'4' = 0x20 + 20
= 0x20 + 2
= 0x20 + 0x07 (White) $ = 0x20 + 0x04 (Green)
grcwhc Fill Box with a Color
Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
w = (character) 0x20 + Width in Text Columns
h = (character) 0x20 + Height in Text Columns Down
c = (character) 0x20 + color palette index value
Pixel color palette index values defined as:
Black
= 0x00
Blue
= 0x01
Red
= 0x02
Magenta
= 0x03
Green
= 0x04
Cyan
= 0x05
Yellow
= 0x06
White
= 0x07
Custom 0
= 0x08 (Not available)

18

Chapter 5 Terminal Commands

Custom 1
Custom 2
Custom 3
Custom 4
Custom 5
Flash 1
Flash 2

19

= 0x09 (Not available)


= 0x0a (Not available)
= 0x0b (Not available)
= 0x0c (Not available)
= 0x0d (Not available)
= 0x0e
= 0x0f

hrcwhaaaaaaaa Display Graphic Cache


Where:
r = (character) 0x20 + Top Text Row Position (0 = top, 15 = bottom)
c = (character) 0x20 + Left Text Column Position (0 = left, 39 = right)
w = (character) 0x20 + Width in Text Columns
h = (character) 0x20 + Height in Text Columns
aaaaaaaa = 8 character hexadecimal cache offset start value.
See R/U 998 command for more details on cache offset.

Modbus:
Supported through Modbus Extended Services Registers.

Chapter 6 Meter Commands

CHAPTER 6
6.1

20

METER COMMANDS:

AUTHORIZE PRESET (PRODUCT AND PRESET VOLUME):

MAMpppaiiivvvvvvvvvcc
Where:
ppp = The specified zero-based preset or load arm number (000-011).
a = Authorize bit, 0 = Cancel Authorization, 1 = Authorize.
iii = Product Index (500 register) for the authorized product.
vvvvvvvvv = Preset volume.
cc = Compartment number.
Note: Will only accept Authorize Preset command when in REMOTE_AUTH_PRESET state or when preset is
authorized and a batch not already authorized.
Modbus:
Write Only Register=7500+5*ppp, Len=1, 16-Bit Integer (iii)
Write Only Register=7501+5*ppp, Len=2, 32-Bit Integer (vvvvvvvvv)
Write Only Register=7503+5*ppp, Len=1, 16-Bit Integer (cc)
Write Only Register=7504+5*ppp, Len=1, 16-Bit Integer (a)
Note: Last Authorize Preset Register Used=7559

6.2

CLEAR ALARMS:

MCAppp
Where:
ppp = The specified zero-based preset or load arm number (000-011).
Modbus:
Write Only Register=7020+ppp, Len=1, 16-Bit Integer (any value)

6.3

ENABLE PRESET

MEMpppa
Where:
ppp = The specified zero-based preset or load arm number (000-011).
a = Enable Flag, 0 = Disabled, 1 = Enabled/Not Available, 2 = Available
Modbus:
Write Only Register=7032+ppp, Len=1, 16-Bit Integer (a)

6.4

END TRANSACTION

MET
When an ET command is received, a forced card out will occur.
Note: The Host will still need to send a MEB command for each preset that reaches a
PRESET_END_OF_BATCH state.
Modbus:
Write Only Register=7044, Len=1, 16-Bit Integer (any value)

Chapter 6 Meter Commands

6.5

BATCH COMPLETE

MBCppp
Where:
ppp = The specified zero-based preset or load arm number (000-011).
When a BC command is received, the preset flow will stop and the batch will be marked as complete. The
operator will not be able to restart the batch, but will be allowed to clear the batch and preset another (pending
Host authorization).
Modbus:
Write Only Register=7045+ppp, Len=1, 16-Bit Integer (any value)

6.6

BATCH END:

MBEppp
Where:
ppp = The specified zero-based preset or load arm number (000-011).
Command used to start end batch processing and to transition state to PRESET_END_OF_BATCH when flow
stops and final values are received.
Note: Typical end of batch command order is:
MSMppp (tell Multiload to stop flow)
MBCppp (tell Multiload to mark batch as complete, no further flowing on batch)
MBEppp (tell Multiload to get ready for total pickup)
wait for state==PRESET_END_OF_BATCH (ok to get totals)
MRSppp to get totals
MEBppp (ok to clear totals on Multiload)
Modbus:
Write Only Register=7057+ppp, Len=1, 16-Bit Integer (any value)

6.7

END BATCH:

MEBppp
Where:
ppp = The specified zero-based preset or load arm number (000-011).
Command is used to finish end-of-batch processing and that totals can be cleared.
Modbus:
Write Only Register=7069+ppp, Len=1, 16-Bit Integer (any value)

21

Chapter 6 Meter Commands

6.8

PRESET MESSAGE:

MPMpppssssssssssddddddddddddddddddddddddddddddddddddddd
Where:
ppp = The specified zero-based preset or load arm number (000-011).
ssssssssss = 10 Character Message.
ddddddddddddddddddddddddddddddddddddddd = 39 Character Detail Message.
Displays a message for the particular preset. A detail message will be displayed when the preset is selected.
Driver and acknowledge and clear the message by pressing CLR key.
Modbus:
Only supported through Modbus Extended Services Registers.

6.9

PROVING TRANSACTION MODE:

MPTx
When:
x = Mode Status 0 = Off, 1 = On. Default Off when transaction is authorized.
Command is used to indicate when a card in is done with a proving card and meter proving may be done during
this transaction.
Modbus:
Write Only Register=7081, Len=1, 16-Bit Integer (x)

22

Chapter 6 Meter Commands

6.10

REQUEST STATUS & PRESET ALARMS:

MRSpppxxxxyyyyzzzzaaaa => RSppp (Requested parameters as listed below).


Where:
ppp = The specified zero-based preset or load arm number (000-011).
xxxx = Optional response configuration bits #0 in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned int preset_state:1;
unsigned int preset_status_0:1;
unsigned int preset_alarms:1;
unsigned int volume_preset_whole:1;
unsigned int batch_gross_del_whole:1;
unsigned int batch_net_del_whole:1;
unsigned int batch_temp_tenths:1;
unsigned int batch_pressure_tenths:1;
unsigned int batch_gravity:1;
unsigned int gross_flow_rate:1;
unsigned int component_batch_gross_del_whole:1;
unsigned int component_batch_net_del_whole:1;
unsigned int component_batch_temp_tenths:1;
unsigned int component_batch_pressure_tenths:1;
unsigned int component_batch_gravity:1;
unsigned int additive_batch_gross_del_thous:1;
} flags;
} query_0; (default value 0x965f.)

23

Chapter 6 Meter Commands

yyyy = Optional response configuration bits #1 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned int preset_status_0:1;
unsigned int preset_status_1:1;
unsigned int preset_status_2:1;
unsigned int meter_status_0:1;
unsigned int meter_status_1:1;
unsigned int meter_status_2:1;
unsigned int component_status_0:1;
unsigned int component_status_1:1;
unsigned int component_status_2:1;
unsigned int additive_status_0:1;
unsigned int additive_status_1:1;
unsigned int additive_status_2:1;
unsigned int temp_press_in_hunds:1;
unsigned int component_current_temp_hund:1;
unsigned int component_current_pressure_hund:1;
unsigned int component_current_density_tenths:1;
} flags;
} query_1; (default value 0x0000.)

24

Chapter 6 Meter Commands

zzzz = Optional response configuration bits #2 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned int meter_batch_gross_del_whole:1; //Mass
unsigned int meter_gross_flow_rate:1; // Mass
unsigned int component_current_relative_density_tenthous:1;
unsigned int unused_3:1;
unsigned int unused_4:1;
unsigned int unused_5:1;
unsigned int unused_6:1;
unsigned int unused_7:1;
unsigned int unused_8:1;
unsigned int unused_9:1;
unsigned int unused_10:1;
unsigned int unused_11:1;
unsigned int unused_12:1;
unsigned int unused_13:1;
unsigned int unused_14:1;
unsigned int unused_15:1;
} flags;
} query_2; (default value 0x0000.)
aaaa = Optional response configuration bits #3 in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned int component_meter_gross_del_whole:1;
unsigned int component_meter_net_del_whole:1; // Mass
unsigned int component_meter_batch_temp_tenths:1;
unsigned int component_meter_batch_pressure_tenths:1;
unsigned int component_meter_batch_gravity:1;
unsigned int component_meter_current_temp_tenths:1;
unsigned int component_meter_current_pressure_tenths:1;
unsigned int component_meter_current_gravity:1;
unsigned int component_meter_current_relative_density_tenthous:1;
unsigned int unused_9:1;
unsigned int unused_10:1;
unsigned int unused_11:1;
unsigned int unused_12:1;
unsigned int unused_13:1;

25

Chapter 6 Meter Commands

unsigned int unused_14:1;


unsigned int unused_15:1;
} flags;
} query_3; (default value 0x0000.)
Defaults are compatible with previous Multiload MRS replies.
To query for preset information only use: MRSppp03ff
To query for preset pressure only use: MRSppp0080
To query for additive delivered only use: MRSppp8000
RS = Request Status Response
ppp = The specified zero-based preset or load arm number (000-011).

26

Chapter 6 Meter Commands

Query 0 and 1 Responses:


wwww= preset state in hexidecimal as:
enum
{
PRESET_IDLE
PRESET_LOW_FLOW
PRESET_HIGH_FLOW
PRESET_1ST_TRIP
PRESET_2ND_TRIP
PRESET_FINAL_TRIP
PRESET_START
PRESET_ALARM
PRESET_COMPLETE
PRESET_NOT_AUTH
PRESET_WAIT_TMS
PRESET_AUTH
PRESET_PRESET
PRESET_DISABLED
PRESET_STOP
PRESET_REMOTE_MSG
PRESET_END_OF_BATCH
PRESET_ARCHIVING
PRESET_CLEARING
PRESET_TRANS_DONE
} preset_state;

27

= 0,
= 1,
= 2,
= 3,
= 4,
= 5,
= 6,
= 7,
= 8,
= 9,
= 10,
= 11,
= 12,
= 13,
= 14,
= 15,
= 16,
= 17,
= 18,
= 19

Chapter 6 Meter Commands

xxxx= preset status #0 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char preset_enabled:1;
unsigned char preset_host_enabled:1;
unsigned char authorized:1;
unsigned char flow_active:1;
unsigned char batch_authorized:1;
unsigned char remote_msg:1;
unsigned char remote_desc:1;
unsigned char load_complete:1;
unsigned char end_batch:1;
unsigned char end_batch_done:1;
unsigned char tms_got_data:1;
unsigned char archived:1;
unsigned char batch_cleared:1;
unsigned char clearing_load:1;
unsigned char load_cleared:1;
unsigned char trans_done:1;
} flags:
} preset_status_0;

28

// preset is enabled
// preset enabled by host
// preset available for use
// flow state is not idle
// product & preset has been authorized
// remote message active
// remote descriptive message active
// no further loading on batch can be done
// MBE command processing started
// MBE command processing done
// MEB command received
// batch data has been archived into
transaction database
// batch has been cleared
// load clear has been issued
// load has been cleared
// transaction is done

Chapter 6 Meter Commands

29

yyyy= preset alarms in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char preset_fcm_com:1;

unsigned char preset_permissive:1;


unsigned char swing_arm_permissive:1;
unsigned char line_not_flushed:1;

unsigned char preset_block_valve:1;


unsigned char bay_alarm:1;
unsigned char component_alarm:1;
unsigned char additive_alarm:1;
unsigned char meter_stop:1;
unsigned char preset_overrun:1;
unsigned char excess_flow:1;
unsigned char unused11:1;
unsigned char unused12:1;
unsigned char unused13:1;
unsigned char unused14:1;
unsigned char configuration_error:1;
} flags;
} preset_alarms;

// one or more FCMs that are required for


PRESET status or signals are in com
error.
// preset permissive not active but preset is
authorized to load.
// swing arm not in bay and preset is
authorized to load.
// less than min_line_flush_vol has flowed
since a non-flush component has flowed
and batch was ended.
// block value status does not agree with
commanded valve position.
// a bay level alarm currently exists.
// a component level alarm currently exists
for this preset.
// a additive level alarm currently exists for
this preset.
// meter stop button for preset pressed
// preset delivered volume is over target
volume by overrun_alarm_vol.
// preset flow rate has exceeded
excess_flow_alarm_rate.

// preset configuration has invalid data,


check message log for details

Chapter 6 Meter Commands

qqqqqqqqq= preset quantity in whole units


ddddddddd = delivered gross quantity in whole units

30

ddddddddd = delivered net quantity in whole

units
Note: if the Use Hundredths W&M RCU parameter is enabled, the gross and net quantity value will have an implied two decimal places.

sddddd = signed batch average temp in tenths or hundredths


sddddd = signed batch average pressure in tenths or hundredths
dddddd = depending on API table selected,
batch average density in tenths OR
batch average relative density in ten thousands OR
batch average gravity in tenths
ddddd = preset gross flow rate in whole units
Modbus :
Where: p = preset (0-11)
Read Only Register=4000+p, Len=1, 16-Bit Integer (wwww)
Read Only Register=4012+p, Len=1, 16-Bit Integer (xxxx)
Read Only Register=4024+p, Len=1, 16-Bit Integer (yyyy)
Read Only Register=4036+p, Len=2, 32-Bit Integer (qqqqqqqqq)
Read Only Register=4060+p, Len=2, 32-Bit Integer (ddddddddd (gross))
Read Only Register=4084+p, Len=2, 32-Bit Integer (ddddddddd (net))
Read Only Register=4108+p, Len=2, 32-Bit Integer (sddddd (temp))
Read Only Register=4132+p, Len=2, 32-Bit Integer (sddddd (pressure))
Read Only Register=4156+p, Len=2, 32-Bit Integer (dddddd)
Read Only Register=4180+p, Len=1, 16-Bit Integer (ddddd (rate))

Chapter 6 Meter Commands

per meter(5):
ddddddddd = meter delivered gross quantity in whole units
Note: if the Use Hundredths W&M RCU parameter is enabled, the gross quantity value will have an implied two decimal places.

ddddd = meter gross flow rate in whole units


Modbus :
Where: p = preset (0-11), m = meter (0-4)
Read Only Register=4192+p*5+m, Len=2, 32-Bit Integer (ddddddddd (gross))
Read Only Register=4312+p*5+m, Len=1, 16-Bit Integer (ddddd (rate))

31

Chapter 6 Meter Commands

per component(8):
ddddddddd = delivered gross quantity in whole units
ddddddddd = delivered net quantity in whole units
Note: if the Use Hundredths W&M RCU parameter is enabled, the gross and net quantity value will have an implied two decimal places.

sddddd = signed component batch average temp in tenths or hundredths


sddddd = component batch average pressure in tenths or hundredths
dddddd = depending on API table selected,
component batch average density in tenths OR
component batch average relative density in ten thousands OR
component batch average gravity in tenths
sddddd = signed component current temp in hundredths
sddddd = signed component current pressure in hundredths
sddddd = signed component current density in tenths
sddddd = signed component current relative density in ten thousands
ddddddddd = component meter delivered gross quantity in whole units
ddddddddd = component meter delivered net quantity in whole units
sddddd = signed component meter batch average temp in tenths or hundredths
sddddd = component meter batch average pressure in tenths or hundredths
dddddd = depending on API table selected,
component meter batch average density in tenths OR
component meter batch average relative density in ten thousands OR
component meter batch average gravity in tenths
sddddd = signed component meter current temp in hundredths
sddddd = signed component meter current pressure in hundredths
sddddd = signed component meter current density in tenths
sddddd = signed component meter current relative density in ten thousands
Modbus :
Where: p = preset (0-11), c = component (0-7)
Read Only Register=4372+p*8+c, Len=2, 32-Bit Integer (ddddddddd (gross))
Read Only Register=4564+p*8+c, Len=2, 32-Bit Integer (ddddddddd (net))
Read Only Register=4756+p*8+c, Len=2, 32-Bit Integer (sddddd (component average temp))
Read Only Register=4948+p*8+c, Len=2, 32-Bit Integer (sddddd (component average pressure))
Read Only Register=5140+p*8+c, Len=2, 32-Bit Integer (dddddd (component average density/rel.
dens./gravity))
Read Only Register=5332+p*8+c, Len=2, 32-Bit Integer (sddddd (component current temp))
Read Only Register=5524+p*8+c, Len=2, 32-Bit Integer (sddddd (component current pressure))
Read Only Register=5716+p*8+c, Len=2, 32-Bit Integer (sddddd (component current density))
Read Only Register=6292+p*8+c, Len=2, 32-Bit Integer (sddddd (component current relative density))

32

Chapter 6 Meter Commands

per additive(16):
ddddddddd = delivered quantity in thousands
Modbus :
Where: p = preset (0-11), a = additive (0-11)
Read Only Register=5908+p*16+a, Len=2, 32-Bit Integer (ddddddddd (delivered quantity in thousands))

33

Chapter 6 Meter Commands

Query 1 Responses:
xxxx= preset status #0 in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char preset_enabled:1;
unsigned char preset_host_enabled:1;
unsigned char authorized:1;
unsigned char flow_active:1;
unsigned char batch_authorized:1;
unsigned char remote_msg:1;
unsigned char remote_desc:1;
unsigned char load_complete:1;
unsigned char end_batch:1;
unsigned char end_batch_done:1;
unsigned char tms_got_data:1;
unsigned char archived:1;
unsigned char batch_cleared:1;
unsigned char clearing_load:1;
unsigned char load_cleared:1;
unsigned char trans_done:1;
} flags:
} preset_status_0;

34

// preset is enabled
// preset enabled by host
// preset available for use
// flow state is not idle
// product & preset has been authorized
// remote message active
// remote descriptive message active
// no further loading on batch can be done
// MBE command processing started
// MBE command processing done
// MEB command received
// batch data has been archived into
transaction database
// batch has been cleared
// load clear has been issued
// load has been cleared
// transaction is done

Chapter 6 Meter Commands

xxxx= preset status #1 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char program_clear_errors:1;
unsigned char remote_clear_errors:1;
unsigned char driver_clear_errors:1;
unsigned char clearing_errors:1;
unsigned char flow_batch:1;
unsigned char clear_batch:1;
unsigned char clear_load:1;
unsigned char flush_stage_needed:1;
unsigned char open_blk_val:1;
unsigned char blk_val_status:1;
unsigned char close_blk_val:1;
unsigned char remote_start:1;
unsigned char swing_arm:1;
unsigned char meter_stop:1;
unsigned char alarm_out:1;
unsigned char permissive:1;
} flags:
} preset_status_1;

35

// command to clear errors


// command to clear errors
// command to clear errors
// currently clearing errors
// command to flow/not flow product
// command to clear batch
// command to clear load
// product flush stage required
// block valve open
// block valve status
// block valve close
// remote start button status
// swing arm select status
// meter stop button status
// preset alarm output status
// preset permissive input status

Chapter 6 Meter Commands

xxxx= preset status #2 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char permissive_out:1;
// preset permissive output status
unsigned char load_interrupted:1;
// has loading been interrupted
unsigned char clearing_batch:1;
// batch in process of clearing
unsigned char alt_high_flow:1;
// alt_high_flow input active
unsigned char gross_value_measured_for_trade:1; // gross value is W&M approved
unsigned char wm_clear_errors:1;
// command to clear errors
unsigned char batch_alarm:1;
// one or more preset level alarms occurred
during the batch
unsigned char unused2_7:1;
// future use
unsigned char unused2_8:1;
// future use
unsigned char unused2_9:1;
// future use
unsigned char unused2_10:1;
// future use
unsigned char unused2_11:1;
// future use
unsigned char unused2_12:1;
// future use
unsigned char unused2_13:1;
// future use
unsigned char unused2_14:1;
// future use
unsigned char unused2_15:1;
// future use
} flags:
} preset_status_2;
Modbus:
Supported through Modbus Extended Services Registers.

36

Chapter 6 Meter Commands

per meter(6):
xxxx= meter status #0 in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char program_clear_errors:1;
unsigned char remote_clear_errors:1;
unsigned char driver_clear_errors:1;
unsigned char clearing_errors:1;
unsigned char clear_totals:1;
unsigned char start_flow:1;
unsigned char stop_flow:1; ;
unsigned char high_flow:1;
unsigned char upstream_valve:1;
unsigned char downstream_valve:1;
unsigned char alarm_out:1;
unsigned char authorized:1;
unsigned char permissive:1;
unsigned char permissive_out:1;
unsigned char wm_clear_errors:1;
unsigned char unused0_15:1;
} flags:
} meter_status_0;

37

// command to clear errors


// command to clear errors
// command to clear errors
// currently clearing errors
// commanded to clear totals
// commanded to start flow
// commanded to stop flow
// forcing flow into high flow
// upstream valve status
// downstream valve status
// meter alarm output status
// meter authorized output status
// meter permissive input status
// meter permissive output status
// command to clear errors
// future use

Chapter 6 Meter Commands

xxxx= meter status #1 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char unused1_0:1;
unsigned char unused1_1:1;
unsigned char unused1_2:1;
unsigned char unused1_3:1;
unsigned char unused1_4:1;
unsigned char unused1_5:1;
unsigned char unused1_6:1;
unsigned char unused1_7:1;
unsigned char unused1_8:1;
unsigned char unused1_9:1;
unsigned char unused1_10:1;
unsigned char unused1_11:1;
unsigned char unused1_12:1;
unsigned char unused1_13:1;
unsigned char unused1_14:1;
unsigned char unused1_15:1;
} flags:
} meter_status_1;

38

// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use

Chapter 6 Meter Commands

xxxx= meter status #2 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char unused2_0:1;
unsigned char unused2_1:1;
unsigned char unused2_2:1;
unsigned char unused2_3:1;
unsigned char unused2_4:1;
unsigned char unused2_5:1;
unsigned char unused2_6:1;
unsigned char unused2_7:1;
unsigned char unused2_8:1;
unsigned char unused2_9:1;
unsigned char unused2_10:1;
unsigned char unused2_11:1;
unsigned char unused2_12:1;
unsigned char unused2_13:1;
unsigned char unused2_14:1;
unsigned char unused2_15:1;
} flags:
} meter_status_2;
Modbus:
Supported through Modbus Extended Services Registers.

39

// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use

Chapter 6 Meter Commands

per component(8):
xxxx= component status #0 in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char program_clear_errors:1;
unsigned char remote_clear_errors:1;
unsigned char driver_clear_errors:1;
unsigned char clearing_errors:1;
unsigned char clear_batch:1;
unsigned char remote_start_button:1;
unsigned char pump_run:1;
unsigned char pump_kill:1;
unsigned char pump_status:1;
unsigned char open_blk_val:1;
unsigned char blk_val_status:1;
unsigned char close_blk_val:1;
unsigned char alarm_out:1;
unsigned char authorized:1;
unsigned char permissive:1;
unsigned char permissive_out:1;
} flags:
} component_status_0;

40

// command to clear errors


// command to clear errors
// command to clear errors
// currently clearing errors
// commanded to clear batch
// remote start button input status
// pump run output status
// pump kill output status
// pump status input status
// open block valve output status
// block valve status input status
// close block valve output status
// alarm out output status
// authorized output status
// component permissive input status
// component permissive output status

Chapter 6 Meter Commands

xxxx= component status #1 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char blend_ready:1;
// component blend ready
unsigned char blend_complete:1;
// component blend complete
unsigned char flush_ready:1;
// component flush ready
unsigned char flush_complete:1;
// component flush complete
unsigned char sequential_delivery:1;
// component to be sequentially delivered
unsigned char clearing_batch:1;
// component batch in process of clearing
unsigned char gross_value_measured_for_trade:1; // gross value is W&M approved
unsigned char wm_clear_errors:1;
// command to clear errors
unsigned char unused1_8:1;
// future use
unsigned char unused1_9:1;
// future use
unsigned char unused1_10:1;
// future use
unsigned char unused1_11:1;
// future use
unsigned char unused1_12:1;
// future use
unsigned char unused1_13:1;
// future use
unsigned char unused1_14:1;
// future use
unsigned char unused1_15:1;
// future use
} flags:
} component_status_1;

41

Chapter 6 Meter Commands

xxxx= component status #2 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char unused2_0:1;
unsigned char unused2_1:1;
unsigned char unused2_2:1;
unsigned char unused2_3:1;
unsigned char unused2_4:1;
unsigned char unused2_5:1;
unsigned char unused2_6:1;
unsigned char unused2_7:1;
unsigned char unused2_8:1;
unsigned char unused2_9:1;
unsigned char unused2_10:1;
unsigned char unused2_11:1;
unsigned char unused2_12:1;
unsigned char unused2_13:1;
unsigned char unused2_14:1;
unsigned char unused2_15:1;
} flags:
} component_status_2;
Modbus:
Supported through Modbus Extended Services Registers.

42

// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use

Chapter 6 Meter Commands

per additive(16):
xxxx= additive status #0 in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char program_clear_errors:1;
unsigned char remote_clear_errors:1;
unsigned char driver_clear_errors:1;
unsigned char clearing_errors:1;
unsigned char clear_batch:1;
unsigned char test_button:1;
unsigned char pump_run:1;
unsigned char pump_kill:1;
unsigned char pump_status:1;
unsigned char open_blk_val:1;
unsigned char blk_val_status:1;
unsigned char close_blk_val:1;
unsigned char flush_pump_run:1;
unsigned char alarm_out:1;
unsigned char authorized:1;
unsigned char permissive:1;
} flags:
} additive_status_0;

43

// command to clear errors


// command to clear errors
// command to clear errors
// commanded to clear errors
// commanded to clear batch
// test inject button input status
// pump run output status
// pump kill output status
// pump status input status
// open block valve output status
// block valve status input status
// close block valve output status
// flush pump run output status
// alarm out output status
// authorized output status
// additive permissive input status

Chapter 6 Meter Commands

xxxx= additive status #1 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char permissive_out:1;
unsigned char feedback_status:1;
unsigned char wm_clear_errors:1;
unsigned char unused1_3:1;
unsigned char unused1_4:1;
unsigned char unused1_5:1;
unsigned char unused1_6:1;
unsigned char unused1_7:1;
unsigned char unused1_8:1;
unsigned char unused1_9:1;
unsigned char unused1_10:1;
unsigned char unused1_11:1;
unsigned char unused1_12:1;
unsigned char unused1_13:1;
unsigned char unused1_14:1;
unsigned char unused1_15:1;
} flags:
} additive_status_1;

44

// permissive out output status


// additive feedback input status
// command to clear errors
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use

Chapter 6 Meter Commands

xxxx= additive status #2 in hexadecimal as:


union
{
unsigned int value;
struct
{
unsigned char unused2_0:1;
unsigned char unused2_1:1;
unsigned char unused2_2:1;
unsigned char unused2_3:1;
unsigned char unused2_4:1;
unsigned char unused2_5:1;
unsigned char unused2_6:1;
unsigned char unused2_7:1;
unsigned char unused2_8:1;
unsigned char unused2_9:1;
unsigned char unused2_10:1;
unsigned char unused2_11:1;
unsigned char unused2_12:1;
unsigned char unused2_13:1;
unsigned char unused2_14:1;
unsigned char unused2_15:1;
} flags:
} additive_status_2;
Modbus:
Supported through Modbus Extended Services Registers.

45

// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use
// future use

Chapter 6 Meter Commands

6.11

REQUEST SMP STATUS & PRESET ALARMS:

MSSpppxxxxyyyyzzzz => SSppp (Requested parameters as listed above).


The MSS command for the MultiLoad II SMP, is identical to the MRS command but only returns 1 component
instead of 8, 1 meter instead of 4, and 2 additives instead of 16 additives in the response.

6.12

TRIP PRESET ALARMS:

MTPApppyyyy => TPAppp


Where:
ppp = The specified zero-based preset or load arm number (000-011).
yyyy= preset alarms in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char preset_fcm_com:1;
// one or more FCMs that are required for
PRESET status or signals are in com
error.
unsigned char preset_permissive:1;
// preset permissive not active but preset is
authorized to load.
unsigned char swing_arm_permissive:1;
// swing arm not in bay and preset is
authorized to load.
unsigned char line_not_flushed:1;
// less than min_line_flush_vol has flowed
since a non-flush component has flowed
and batch was ended.
unsigned char preset_block_valve:1;
// block value status does not agree with
commanded valve position.
unsigned char bay_alarm:1;
// a bay level alarm currently exists.
unsigned char component_alarm:1;
// a component level alarm currently exists
for this preset.
unsigned char additive_alarm:1;
// a additive level alarm currently exists for
this preset.
unsigned char meter_stop:1;
// meter stop button for preset pressed
unsigned char preset_overrun:1;
// preset delivered volume is over target
volume by overrun_alarm_vol.
unsigned char excess_flow:1;
// preset flow rate has exceeded
excess_flow_alarm_rate.
unsigned char unused11:1;
unsigned char unused12:1;
unsigned char unused13:1;
unsigned char unused14:1;
unsigned char configuration_error:1;
// preset configuration has invalid data,
check message log for details
} flags;
} preset_alarms;

46

Chapter 6 Meter Commands

47

Modbus:
Write Only Register=7082+ppp, Len=1, 16-Bit Integer (yyyy)

6.13

REQUEST BAY ALARMS:

MRBA => RBAxxxx


Where:
xxxx = bay alarms in hexadecimal as:
union
{
struct
{
unsigned char bay_fcm_com:1;
unsigned char bay_permissive0:1;

unsigned char bay_permissive1:1;

unsigned char bay_permissive2:1;

unsigned char bay_permissive3:1;

unsigned char bay_permissive4:1;

unsigned char bay_permissive5:1;

unsigned char bay_permissive6:1;

unsigned char bay_permissive7:1;

unsigned char all_stop:1;


unsigned char bay_pcm_com:1;
unsigned char printer_error:1;
unsigned char unused12:1;
unsigned char unused13:1;
unsigned char unused14:1;
unsigned char fcm_trace:1;
} flags;
unsigned int value;
} bay_alarms;
Modbus:

// one or more FCMs that are required for BAY


status or signals are in com error.
// user definable preset permissive 0 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 1 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 2 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 3 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 4 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 5 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 6 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// user definable preset permissive 7 not active
but bay is authorized to load. Error message
can be renamed to indicate permissive.
// all stop button pressed
// one or more FCMs that are required for BAY
status or signals are in comm error.
// one or more printers are in error.

Chapter 6 Meter Commands

Read Only Register=7094, Len=1, 16-Bit Integer (xxxx)

6.14

REQUEST COMPONENT ALARMS:

MRCAppp => RCApppxxxx


Where:
ppp = The specified zero-based preset or load arm number (000-011).
per component(8):
xxxx = component alarms in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char component_fcm_com:1;
// one or more FCMs that are
required for COMPONENT status
or signals are in comm error.
unsigned char component_permissive:1;
// component permissive not active
but component is authorized to
load.
unsigned char component_block_valve:1;
// block value status does not
agree with commanded valve
position.
unsigned char component_unauth_flow:1;
//
greater
than
unauth_flow_alarm_vol has been
metered when component was not
authorized for flow.
unsigned char component_pump_status:1;
// pump status does not agree with
commanded pump state.
unsigned char meter_alarm:1;
// a meter level alarm currently
exists for this component.
unsigned char component_over_blend_tol:1;
// blend precent has been over by
blend_chk_alarm_pct
for
blend_chk_alarm_time seconds.
unsigned char component_under_blend_tol:1; // blend precent has been under by
blend_chk_alarm_pct
for
blend_chk_alarm_time seconds.
unsigned char component_api_table:1;
// API VCF table error
unsigned char unused9:1;
unsigned char unused10:1;
unsigned char unused11:1;
unsigned char unused12:1;
unsigned char unused13:1;
unsigned char unused14:1;
unsigned char unused15:1;
} flags;
} component_alarm;
Modbus:
Where: p = preset (0-11), c = component (0-7)

48

Chapter 6 Meter Commands

Read Only Register=7095+8*p+c, Len=1, 16-Bit Integer (xxxx)


Note: Last Component Alarm Register Used=7190

6.15

REQUEST METER ALARMS:

MRMAppp => RMApppxxxx


Where:
ppp = The specified zero-based preset or load arm number (000-011).
per meter(5):
xxxx = meter alarms in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char meter_fcm_com:1;
// one or more FCMs that are required for
METER status or signals are in comm
error.
unsigned char meter_permissive:1;
// meter permissive not active but meter is
authorized to load.
unsigned char fcm_invalid_config:1;
// FCM reporting an error with loaded
configuration. (Meter factors likely source
of this type of error.)
unsigned char fcm_wdt_reset:1;
// FCM stopped flow due to lack of
communication from RCU.
unsigned char fcm_com_timeout:1;
// FCM com timed out due to a lack of
communication from RCU.
unsigned char valve_fault:1;
// greater than value_fault_alarm_vol has
been metered since flow was stopped.
unsigned char low_flow:1;
// flow rate was below low_flow_alarm_rate
for low_flow_alarm_time seconds while
attempting to flow.
unsigned char excess_flow:1;
//
flow
rate
was
above
excess_flow_alarm_rate.
unsigned char quad_encoding:1;
// max_quad_errors were received.
unsigned char density_error:1;
// density signal not valid or density <
alarm_low_density
or
density
>
alarm_high_density.
unsigned char temp_error:1;
// temp signal not valid or temp <
alarm_low_temp
or
temp
>
alarm_high_temp.
unsigned char valve_control:1;
// not able to slow for stop flow rate for
valve_control_alarm_time.
unsigned char meter_creep:1;
// greater than meter_creep_alarm_vol has
been metered since flow was stopped.
unsigned char pressure_error:1;
// pressure signal not valid or pressure <
alarm_low_pressure
or
pressure
>
alarm_high_pressure.
unsigned char quad_encoding_a:1; // max_quad_errors were received on channel
A.

49

Chapter 6 Meter Commands

unsigned char quad_encoding_b:1; // max_quad_errors were received on channel


B.
} flags;
} meter_alarms;
Modbus:
Where: p = preset (0-11), m = meter (0-4)
Read Only Register=7191+5*p+m, Len=1, 16-Bit Integer (xxxx)
Note: Last Meter Alarm Register Used=7250

6.16

REQUEST ADDITIVE ALARMS:

MRAAppp => RAApppxxxx


Where:
ppp = The specified zero-based preset or load arm number (000-011).
per additive(16):
xxxx = additive alarms in hexadecimal as:
union
{
unsigned int value;
struct
{
unsigned char additive_fcm_com:1;
// one or more FCMs that are required for
ADDITIVE status or signals are in comm
error.
unsigned char additive_permissive:1;
// additive permissive not active but
additive is authorized to load.
unsigned char additive_under_add:1;
// recipe additive needed is under actual
additive
delivered
by
under_adtv_alarm_injects.
unsigned char additive_over_add:1;
// recipe additive needed is over actual
additive
delivered
by
over_adtv_alarm_injects.
unsigned char additive_valve_fault:1;
// greater than value_fault_alarm_vol has
been metered since flow was stopped.
unsigned char additive_pump_status:1; // pump status does not agree with
commanded pump state.
unsigned char additive_injection:1;
// piston switch or pulser did not indicate
an injection took place.
unsigned char additive_unauth_flow:1; // greater than unauth_flow_alarm_vol has
been metered when additive was not
authorized for flow.
unsigned char additive_line_not_flushed:1; // min_line_flush_volume of product has
not flushed since last inject was completed
and batch was ended.
unsigned char additive_meter_creep:1; // greater than meter_creep_alarm_vol has
been metered since flow was stopped.
unsigned char additive_block_valve:1; // block valve status does not agree with
commanded valve position.
unsigned char unused11:1;

50

Chapter 6 Meter Commands

unsigned char unused12:1;


unsigned char unused13:1;
unsigned char unused14:1;
unsigned char unused15:1;
} flags;
} additive_alarms;
Modbus:
Where: p = preset (0-11), a = additive (0-15)
Read Only Register=7251+16*p+a, Len=1, 16-Bit Integer (xxxx)
Note: Last Additive Alarm Register Used=7442

6.17

START PRESET FLOW:

MMSppp
Where:
ppp = The specified zero-based preset or load arm number (000-011).
Starts flow for the particular preset. A message is placed into the Message Log when this command is
executed.
Modbus:
Write Only Register=7443+ppp, Len=1, 16-Bit Integer (any value)

6.18

STOP PRESET FLOW:

MSMpppssssssssssddddddddddddddddddddddddddddddddddddddd
Where:
ppp = The specified zero-based preset or load arm number (000-011).
ssssssssss = 10 Character Optional Message.
ddddddddddddddddddddddddddddddddddddddd = 39 Character Optional Detail Message.
Stops flow and displays a message for the particular preset. A detail message will be displayed when the preset
is selected. Driver and acknowledge and clear the message by pressing CLR key.
Modbus:
Write Only Register=7455+ppp, Len=1, 16-Bit Integer (any value)
Stop Preset Message only supported through Modbus Extended Services Register.

51

Chapter 7 Register Operations

CHAPTER 7

52

REGISTER OPERATIONS:

Read Register Command


R<register/sub-registers>
R004
R104021000001
R999

=>
=>
=>
=>
=>

Response
<status><register/sub-registers><register value(s)>
0?00004000000001
0?0104021000001000000020
1?0999 (invalid register!)

Update Register Command


U<register/sub-registers><register value(s)> =>
U004000000001
U104021000001000000020
U999000000001

=>

Response
<status><register/sub-registers>
=>
0?0004
=>
0?0104021000001
=>
1?0999 (invalid register or value!)

MultiLoad contains literally hundreds of registers that configure everything from message toggling delay to meter
factors. All of these registers are accessed using the same two commands.
To read the value of a register the command is R followed by the register and sub register numbers. The
response will be the register and sub register numbers, followed by the register value. The value may be up to
9 decimal digits.
To update the value of a register the command is U followed by the register and sub register numbers and the
value to be stored.
While almost all registers can be read or updated, a few have only read access. Many others have protection
that prevents updates while a transaction is in process, host system is up, or when Weights & Measures security
is in effect.

Chapter 7 Register Operations

7.1

GENERIC REGISTERS

7.1.1

REGISTER DATA TYPES

53

All registers are read and updated as positive integers even when values expressed are non positive or
fractional. In some cases a several values are concatenated bit-wise to form the register value.
unsigned int Unsigned integer value.
Numeric Value
Register Value
12345
12345
unsigned div10 Unsigned numeric value with 1 decimal place.
Numeric Value
Register Value
1234.5
12345
unsigned div100 Unsigned numeric value with 2 decimal places.
Numeric Value
Register Value
123.45
12345
unsigned div1000 Unsigned numeric value with 3 decimal places.
Numeric Value
Register Value
12.345
12345
unsigned div10000 Unsigned numeric value with 4 decimal places.
Numeric Value
Register Value
1.2345
12345
percent Unsigned percent value with 2 decimal places.
Numeric Value
Register Value
123.45%
12345
percent div 10000 Unsigned percent value with 4 decimal places.
Numeric Value
Register Value
1.2345%
12345
signed int Signed integer value.
Numeric Value
+12345
+0
+1
+32767
-32768
-1

Register Value
12345
0
1
32767
32768
65535

signed div10 Signed numeric value with 1 decimal place.


Numeric Value
Register Value

Chapter 7 Register Operations

+1234.5
+0.0
+0.1
+3276.7
-3276.8
-0.1

54

12345
0
1
32767
32768
65535

signed div100 Signed numeric value with 2 decimal places.


Numeric Value
Register Value
+123.45
12345
+0.00
0
+0.01
1
+327.67
32767
-327.68
32768
-0.01
65535
signed div1000 Signed numeric value with 3 decimal places.
Numeric Value
Register Value
+12.345
12345
+0.000
0
+0.001
1
+32.767
32767
-32.768
32768
-0.001
65535
signed div10000 Signed numeric value with 4 decimal places.
Numeric Value
Register Value
+1.2345
12345
+0.0000
0
+0.0001
1
+3.2767
32767
-3.2768
32768
-0.0001
65535
disable enable Enumerated disable and enable values.
enum{ //
Enumerated Value
Register Value
DISABLED
= 0,
ENABLED
=1
};
measure Enumerated measure values.
enum{ //
Enumerated Value
Register Value
GALLONS
= 0,
LITRES
= 1,
CUBIC_METERS
= 2,
TONNES
= 3,

Chapter 7 Register Operations

KILOGRAMS
GRAMS
POUNDS
BARRELS
NO_MEASURE
LITERS
DECALITERS

55

= 4,
= 5,
= 6,
= 7,
= 8,
= 9,
= 10,

};
api table name Enumerated api table name values.
enum{ //
Enumerated Value
Register Value
NONE
= 0,
TABLE_6A
= '1',
TABLE_6B
= '2',
TABLE_6C
= 'F',
TABLE_6D
= 'U',
TABLE_7
= 'M',
TABLE_8
= 'H',
TABLE_23E
= 'a',
TABLE_24A
= '3',
TABLE_24B
= '4',
TABLE_24E
= 'S',
TABLE_26
= 'B',
TABLE_34
= '7',
TABLE_53A
= 'Q'
TABLE_53B
= 'R'
TABLE_53D
= 'Y'
TABLE_54
= 'A',
TABLE_54A
= '5',
TABLE_54B
= '6',
TABLE_54BE
= 'P',
TABLE_54C
= '8',
TABLE_54D
= 'X',
TABLE_59E
= 'b',
TABLE_60A
= 'C',
TABLE_60B
= 'D',
TABLE_60D
= 'E',
TABLE_60o
= 'c',
TABLE_901A
= 'd',
TABLE_TEC
= '9',
TABLE_TEC_ETH
= 'G',
TABLE_I
= 'I',
TABLE_J
= 'J',
TABLE_K
= 'K',
TABLE_L
= 'L',
TABLE_O
= 'O',

Chapter 7 Register Operations

TABLE_1122
TABLE_1122M

56

= 'T',
= 'W',

};
Note: Register value is still an integer value not an ascii char. For example, to specify TABLE_54, the ascii
value of A or 65 would be the register value, not the characterA.

fcm address FCM addressing parameters.


This type is a bit-wise concatenation of four different FCM addressing parameters that is expressed as a single
register value.
struct fcm_address_type
{
unsigned char port_number:3;
// FCM port range 0-7
unsigned char fcm_number:5;
// FCM number range 0-31
unsigned char invert:1;
// Normal signal = 0, Invert signal = 1
// For pulse outputs, single pulse = 0, dual pulse = 1
unsigned char enabled:1;
// Disabled = 0, Enabled = 1
unsigned char ext_port:3;
// ext_port(3) << 3 + port_number(3) => Port range 0-39
unsigned char unused:3;
};
Note: Register value is still an integer value not a binary structure.
For example, to specify port_number 4, fcm_number 1, normal signal, enabled, (0000,0,1,0,00001,100) the
numeric value of the bit-wise concatenation of these four different FCM addressing parameters would be
0x020C = 524.
For example, to specify port_number 11, fcm_number 3, normal signal, enabled, (0000,1,1,0,00011,011) the
numeric value of the bit-wise concatenation of these four different FCM addressing parameters would be
0x061B = 1563.
language Enumerated language values.
enum{ //
Enumerated Value
Register Value
LANGUAGE_ENGLISH = 0,
LANGUAGE_SPANISH = 1,
LANGUAGE_PORTUGUESE = 2,
LANGUAGE_FRENCH = 3,
LANGUAGE_MANDARIN
= 4,
};
alarm count reset mode Enumerated alarm count reset mode values.
enum{ //
Enumerated Value
Register Value
AUTH_TRANS
= 0,
CLEAR_PROMOTED = 1,
TIME_2_MIN
= 2,
TIME_5_MIN
= 3,
TIME_15_MIN
= 4,
TIME_30_MIN
= 5,
TIME_60_MIN
= 6,
TIME_3_HOURS
= 7,

Chapter 7 Register Operations

TIME_6_HOURS
TIME_12_HOURS
TIME_24_HOURS
};

57

= 8,
= 9,
= 10,

Chapter 7 Register Operations

meter type Enumerated meter type values.


enum{ //
Enumerated Value
METER_TYPE_VOLUME_PULSE_INPUT
METER_TYPE_MASS_PULSE_INPUT
METER_TYPE_VOLUME_ANALOG_INPUT
};

58

Register Value
= 0,
= 1,
=2

totalizer Totalizer selection parameter.


This type is a bit-wise concatenation of four totalizer selection parameters that is expressed as a single register
value.
struct totalizer_selection_type
{
unsigned int preset_selected:1;
unsigned int meter_selected:1;
unsigned int component_selected:1;
unsigned int additive_selected:1;
unsigned int unused0:4;
unsigned int unused1:8;
unsigned int unused2:8;
unsigned int unused3:8;
};
Note: Register value is still an integer value not a binary structure.
For example, to specify preset_selected and component_selected, (0101) the numeric value of the bit-wise
concatenation of these four different totalizer selection parameters would be 0x0005 = 3.

Chapter 7 Register Operations

7.1.2
Prefix

59

000 RCU LEVEL CONFIGURATION REGISTERS


Register Description

R/U

004

Reload ROM Lang File

R/U

008

R/U

Date Type

Min

Max

Default

Value

Value

Value

Modbus
Protection

Register
Len=2

disable/enable

Enabled

General

1008

Driver Language

language

English

General

1016

009

Program Mode Language

language

English

General

1018

R/U

010

Card Reader

disable/enable

Enabled

General

1020

R/U

011

Prox Card Pull Secs

unsigned int

General

1022

R/U

012

Remote Processing

disable/enable

Enabled

General

1024

R/U

013

Message Swap Delay

unsigned int

60

General

1026

R/U

014

Message Hold Delay

unsigned int

60

10

General

1028

R/U

015

Max GPS Site Distance


(MultiLoad Mobile Only)

unsigned int

10000

200

General

R/U

016

Auto Authorize

disable/enable

Disabled

General

1032

R/U

017

MM/DD/YY Date

disable/enable

Enabled

W&M

1034

R/U

018

Default to Alt Lang

disable/enable

Disabled

General

1036

R/U

019

Load Date From End

disable/enable

Enabled

General

1038

R/U

020

Measure Used

measures

Gallons

W&M

1040

R/U

021

Print Blend Details

unsigned int

General

1042

R/U

022

Compartment Entry

disable/enable

Disabled

General

1044

R/U

023

Config Timeout Mins

unsigned int

20

General

1046

R/U

024

Print Totalizers

None

General

1048

R/U

025

unused

R/U

026

Large Prompts

disable/enable

Disabled

General

1052

R/U

027

Confirm Flow Starts

disable/enable

Disabled

General

1054

R/U

028

Display Adtv as CCs

disable/enable

Disabled

General

1056

R/U

029

Display Hundredths

disable/enable

Disabled

General

1058

R/U

030

Use Hundredths

disable/enable

Disabled

W&M

1060

R/U

031

unused

R/U

032

Print Ticket

disable/enable

Disabled

General

1064

R/U

033

Form Feed After Tckt

disable/enable

Enabled

General

1066

R/U

034

Print Ticket on PCM

disable/enable

Disabled

General

1068

R/U

035

Ticket PCM

unsigned int

32

General

1070

R/U

036

Meter Arch Timeout

unsigned int

120

30

General

1072

R/U

037

InactivityTimeout

unsigned int

60

35

General

1074

R/U

038

Print Msg Log on PCM

Disabled

General

1076

R/U

039

Message Log PCM#

unsigned int

General

1078

R/U

040

No Prox Pull If Flow

disable/enable

Disabled

General

1080

R/U

041

Host Down Timeout

unsigned int

30

General

1082

30

1030

99

totalizers

1050

1062

disable/enable
0

30

32

999

Chapter 7 Register Operations

Prefix

Register Description

60

Date Type

unsigned int

Modbus

Min

Max

Default

Value

Value

Value

60

999

999

General

1084

Disabled

General

1086

General

1088

Disabled

General

1090

Protection

Register
Len=2

R/U

042

Host Wait Timeout

R/U

043

Prt Alibi Log on PCM

R/U

044

Alibi Log PCM#

R/U

045

Swing Arm Secondary

disable/enable

R/U

046

Screen Saver Timeout

unsigned int

65535

600

General

1092

R/U

047

Screen Saver Bright

percent

10000

5000

General

1094

R/U

048

Min Time Change Secs

unsigned int

65535

60

W&M

1096

R/U

049

Display Load Volume

disable/enable

Disabled

General

1098

R/U

050

FCM Trace

disable/enable

Disabled

General

1100

R/U

051

Measure On Load Scrn

disable/enable

Disabled

W&M

1102

R/U

052

Status Scrn Lockout

disable/enable

Enabled

General

1104

R/U

053

Load Screen Timeout

unsigned int

65535

60

General

1106

R/U

054

Preset Slct Timeout

unsigned int

65535

General

1108

R/U

055

Pixel Test

disable/enable

Disabled

General

1110

R/U

056

Meter Proving Mode

disable/enable

Disabled

General

1112

R/U

057

Trace Preset Number

unsigned int

General

1114

R/U

058

unused

R/U

059

Trace Recipe

R/U

060

Trace Adtv Number

unsigned int

R/U

061

Trace FCM Number

unsigned int

R/U

062

Trace FCM Assignment

R/U

063

R/U

disable/enable
unsigned int

12

1116
disable/enable

Disabled

General

1118

16

General

1120

33

32

General

1122

disable/enable

Disabled

General

1124

Trace Meter Flows

disable/enable

Disabled

General

1126

064

Trace Adtv Volume

disable/enable

Disabled

General

1128

R/U

065

unused

1130

R/U

066

unused

1132

R/U

067

unused

1134

R/U

068

W&M Key FCM#

fcm address

Disabled

W&M

1136

R/U

069

Program Key FCM#

fcm address

Disabled

W&M

1138

R/U

090

RCU Address

unsigned int

General

1180

999

Chapter 7 Register Operations

7.1.3

61

100 BAY LEVEL CONFIGURATION REGISTERS


Modbus
Min

Max

Default

Register

Date Type

Value

Value

Value

Protection

Len=2

Access

Register

Description

R/U

100000

Number Bay Presets

unsigned int

12

General

1200

R/U

100001

Number of FCMs

unsigned int

32

General

1202

R/U

100002

Number of PCMs

unsigned int

32

General

1204

R/U

100003

Temps in F

disable/enable

Disabled

W&M

1206

R/U

100004

Canada API Limits

disable/enable

Disabled

W&M

1208

R/U

100005

unused

R/U

100006

Bay Number

unsigned int

9999

General

1212

R/U

100007

Number External Presets

unsigned int

12

General

1214

R/U

100008

unused

1216

R/U

100009

unused

1218

R/U

100080

unused

1360

R/U

100081

Output Pulse FCM#

Fcm address

R/U

100082

Output Pulse Factor

unsigned div 1000

R/U

100083

unused

1366

R/U

100084

unused

1368

R/U

100085

unused

1370

R/U

100086

unused

1372

R/U

100087

unused

1374

R/U

100088

unused

1376

R/U

100089

Alarm Out FCM#

Fcm address

Disabled

General

1378

R/U

100090

Authorized FCM#

Fcm address

Disabled

General

1380

R/U

100091

Permiss 0 FCM#

Fcm address

Disabled

General

1382

R/U

100092

Permiss 1 FCM#

Fcm address

Disabled

General

1384

R/U

100093

Permiss 2 FCM#

Fcm address

Disabled

General

1386

R/U

100094

Permiss 3 FCM#

Fcm address

Disabled

General

1388

R/U

100095

Permiss 4 FCM#

Fcm address

Disabled

General

1390

R/U

100096

Permiss 5 FCM#

Fcm address

Disabled

General

1392

R/U

100097

Permiss 6 FCM#

Fcm address

Disabled

General

1394

R/U

100098

Permiss 7 FCM#

Fcm address

Disabled

General

1396

R/U

100099

Permiss Out FCM#

Fcm address

Disabled

General

1398

1210

0.001

50.000

Disabled

General

1362

10.000

W&M

1364

Chapter 7 Register Operations

7.1.4

62

101 PRESET LEVEL CONFIGURATION REGISTERS

Note: ppp = The specified zero-based preset or load arm number (000-011).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
Modbus
Description

Min

Max

Default

Register

Date Type

Value

Value

Value

Protection

Len=2

Prefix

Register

R/U

101000ppp

Number of Meters

unsigned int

General

1400

R/U

101001ppp

Number of Components

unsigned int

General

1402

R/U

101002ppp

Number of Additives

unsigned int

16

General

1404

R/U

101003ppp

Sequential Blending

disable/enable

Disabled

General

1406

R/U

101004ppp

Ratio Blending

disable/enable

Disabled

General

1408

R/U

101005ppp

W&M Controlled

disable/enable

Disabled

W&M

1410

R/U

101006ppp

Proving Flow Rate

unsigned int

9999

600

General

1412

R/U

101007ppp

Excess Flw Alrm Rate

unsigned int

9999

1100

General

1414

R/U

101008ppp

Overrun Alarm Vol

unsigned int

65535

General

1416

R/U

101009ppp

Low Flow Start Vol

unsigned int

65535

50

General

1418

R/U

101010ppp

Low Flow Restart Vol

unsigned int

65535

15

General

1420

R/U

101011ppp

Low Flow Rate

unsigned int

9999

150

General

1422

R/U

101012ppp

High Flow Rate

unsigned int

9999

600

General

1424

R/U

101013ppp

Proving Low Flow Vol

unsigned int

65535

50

General

1426

R/U

101014ppp

Line Flush Vol

unsigned int

65535

General

1428

R/U

101015ppp

Line Flush Min Vol

unsigned int

65535

General

1430

R/U

101016ppp

Line Flush Comp#

unsigned int

General

1432

R/U

101017ppp

Take L.F. from Match

disable/enable

Enabled

General

1434

R/U

101018ppp

Take L.F. from First

disable/enable

Disabled

General

1436

R/U

101019ppp

Take L.F. from Last

disable/enable

Disabled

General

1438

R/U

101020ppp

unused

R/U

101021ppp

Alt. High Flow Rate

unsigned int

9999

600

General

1442

R/U

101022ppp

Stop Start Delay

unsigned int

65535

General

1444

R/U

101023ppp

Blnd Chk Start Vol

unsigned int

65535

60

Conditional

1446

R/U

101024ppp

Blnd Chk Restart Vol

unsigned int

65535

10

Conditional

1448

R/U

101025ppp

Blnd Chk Alarm %

percent

0.10%

100.00%

5.00%

Conditional

1450

R/U

101026ppp

Blnd Chk Alarm Vol

unsigned int

65535

25

Conditional

1452

R/U

101027ppp

Blnd Chk Alarm Time

unsigned int

65535

10

Conditional

1454

R/U

101028ppp

unused

R/U

101029ppp

Blnd On Lead Comp

R/U

101030ppp

Blnd Adj Start Vol

unsigned int

R/U

101031ppp

Blnd Adj Restart Vol

unsigned int

R/U

101032ppp

Blnd Adj Dev %

percent

1440

1456
disable/enable

Disabled

General

1458

65535

60

General

1460

65535

10

General

1462

0.00%

100.00%

1.00%

General

1464

Chapter 7 Register Operations

63

Modbus
Description

Min

Max

Default

Register

Date Type

Value

Value

Value

Protection

Len=2

Prefix

Register

R/U

101033ppp

Blnd Adj Dev Vol

unsigned int

65535

General

1466

R/U

101034ppp

Blnd Adj Time

unsigned int

65535

General

1468

R/U

101035ppp

unused

R/U

101036ppp

Min Preset Volume

unsigned long int

999999

100

General

1472

R/U

101037ppp

Default Preset Volume

unsigned long int

999999

General

1474

R/U

101038ppp

Max Preset Volume

unsigned long int

999999

10000

General

1476

R/U

101039ppp

Auto Batch Authorize

disable/enable

Disabled

General

1478

R/U

101040ppp

Deliver In Net

disable/enable

Disabled

W&M

1480

R/U

101041ppp

BlkValve Open Delay

unsigned int

65535

General

1482

R/U

101042ppp

B.V. Open Alrm Time

unsigned int

65535

10

General

1484

R/U

101043ppp

B.V. Close Alrm Time

unsigned int

65535

10

General

1486

R/U

101044ppp

unused

1488

R/U

101045ppp

unused

1490

R/U

101046ppp

Output Pulse FCM#

Fcm address

R/U

101047ppp

Output Pulse Factor

unsigned div 1000

R/U

101048ppp

Output Pulse Net

R/U

101049ppp

Alt High Flow Start Delay

unsigned int

R/U

101050ppp

Alt High Flow Stop Delay

unsigned int

R/U

101051ppp

Permissive Alarm Time

unsigned int

R/U

101080ppp

unused

1560

R/U

101081ppp

unused

1562

R/U

101082ppp

unused

1564

R/U

101083ppp

unused

1566

R/U

101084ppp

unused

1568

R/U

101085ppp

unused

1570

R/U

101086ppp

Remote Clear FCM#

fcm address

Disabled

General

1572

R/U

101087ppp

Alt. H.F. Rate FCM#

fcm address

Disabled

General

1574

R/U

101088ppp

Close Blk Val FCM#

fcm address

Disabled

General

1576

R/U

101089ppp

Blk Val Status FCM#

fcm address

Disabled

General

1578

R/U

101090ppp

Open Blk Val FCM#

fcm address

Disabled

General

1580

R/U

101091ppp

Flow Active FCM#

fcm address

Disabled

General

1582

R/U

101092ppp

Batch Authorizd FCM#

fcm address

Disabled

General

1584

R/U

101093ppp

Remote Start FCM#

fcm address

Disabled

General

1586

R/U

101094ppp

Swing Arm FCM#

fcm address

Disabled

General

1588

R/U

101095ppp

Meter Stop FCM#

fcm address

Disabled

General

1590

R/U

101096ppp

Alarm Out FCM#

fcm address

Disabled

General

1592

R/U

101097ppp

Authorized FCM#

fcm address

Disabled

General

1594

1470

Disabled

General

1492

10.000

W&M

1494

Disabled

W&M

1496

999

General

1498

999

General

1500

999

General

1502

0.001

50.000

disable/enable

Chapter 7 Register Operations

64

Modbus
Description

Date Type

Min

Max

Default

Register

Value

Value

Value

Protection

Len=2

Prefix

Register

R/U

101098ppp

Permiss FCM#

fcm address

Disabled

General

1596

R/U

101099ppp

Permiss Out FCM#

fcm address

Disabled

General

1598

Chapter 7 Register Operations

7.1.5

65

102 METER LEVEL CONFIGURATION REGISTERS

Note:

ppp = The specified zero-based preset or load arm number (000-011).


mmm = The specified zero-based meter number (000-005).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
The Modbus Meter Index Register sets the mmm index, Read/Write Register=998, Len=1, 16-Bit Integer
Modbus
Min

Max

Default

Date Type

Value

Value

Value

R / U 102000pppmmm Flow Control Module#

unsigned int

31

General

1600

R / U 102001pppmmm Side-Stream on Mtr#

unsigned int

General

1602

Disabled

General

1604

Prefix

Register

Description

R / U 102002pppmmm Side Stream on Any Meter

disable/enable

Register
Protection Len=2

R / U 102003pppmmm unused
R / U 102004pppmmm Meter Address
R / U 102005pppmmm Meter Type

1606
unsigned int

255

meter type

W&M

1608

Volume Pulse

W&M

1610

R / U 102006pppmmm Max Quad Errors

unsigned int

65535

10

W&M

1612

R / U 102007pppmmm Reset Quad Errors

unsigned int

1000

65535

10000

W&M

1614

R / U 102008pppmmm Low Flow Alarm Rate

unsigned int

65535

10

General

1616

R / U 102009pppmmm Low Flow Alarm Time

unsigned div1000

0.000

999.999

10.000

General

1618

R / U 102010pppmmm Excess Flw Alrm Rate

unsigned int

9999

800

General

1620

R / U 102011pppmmm Minimum Flow Rate

unsigned int

9999

50

General

1622

R / U 102012pppmmm Maximum Flow Rate

unsigned int

9999

650

General

1624

R / U 102013pppmmm Low Flow DB Rate

unsigned int

9999

40

General

1626

R / U 102014pppmmm High Flow DB Rate

unsigned int

9999

40

General

1628

R / U 102015pppmmm 1st Stage DB Rate

unsigned int

9999

40

General

1630

R / U 102016pppmmm 2nd Stage DB Rate

unsigned int

9999

40

General

1632

R / U 102017pppmmm Valve Cntl Alrm Time

unsigned div1000

0.000

65.535

10.000

General

1634

R / U 102018pppmmm Valve Fault Alrm Vol

unsigned int

65535

30

General

1636

R / U 102019pppmmm Creep Reset Time

unsigned int

65535

General

1638

R / U 102020pppmmm Ratio Adj P. Factor

unsigned div100

0.00

655.35

10.00

General

1640

R / U 102021pppmmm Ratio Adj D. Factor

unsigned div100

0.00

655.35

0.30

General

1642

unsigned int

65535

15

General

1644

R / U 102023pppmmm Flow Scan Time

unsigned div1000

0.100

1.000

0.100

General

1646

R / U 102024pppmmm Valve Dwell Time

unsigned div1000

0.010

65.535

1.000

General

1648

R / U 102025pppmmm Valve Dwell StepRate

unsigned int

9999

General

1650

R / U 102026pppmmm Valve Dwell StepTime

unsigned div1000

0.000

5.000

0.000

General

1652

R / U 102027pppmmm Adaptive Valve Control

disable/enable

Disabled

General

1654

R / U 102028pppmmm Analog Valve Control

disable/enable

Disabled

General

1656

R / U 102029pppmmm 4-20mA Increase Step

Unsigned div 1000

4.000

0.080

General

1658

R / U 102030pppmmm 4-20mA Decrease Step

Unsigned div 1000

4.000

0.800

General

1660

R / U 102022pppmmm Meter Creep Alrm Vol

Chapter 7 Register Operations

66

Modbus
Prefix

Register

Description

Date Type

Min

Max

Default

Value

Value

Value

Register
Protection Len=2

R / U 102031pppmmm unused

1662

R / U 102032pppmmm unused

1664

R / U 102033pppmmm unused

1666

R / U 102034pppmmm Analog Meter Flow Rate @ 4mA

unsigned int

9999

W&M

1668

R / U 102035pppmmm Analog Meter Flow Rate @ 20mA

unsigned int

9999

600

W&M

1670

R / U 102036pppmmm Analog Meter Flow Rate Offset

signed div1000

-9.999

9.999

W&M

1672

R / U 102037pppmmm Analog Meter Flow Rate Cutoff

unsigned int

9999

W&M

1674

R / U 102038pppmmm unused
R / U 102039pppmmm Density Sensor
R / U 102040pppmmm Density Sensor FCM#

1676
disable/enable
unsigned int

31

Disabled

W&M

1678

W&M

1680

R / U 102041pppmmm unused

1682

R / U 102042pppmmm Default Density

unsigned div10

9999.9

General

1684

R / U 102043pppmmm Alarm Low Density

unsigned div10

9999.9

General

1686

R / U 102044pppmmm Alarm High Density

unsigned div10

9999.9

12000

General

1688

R / U 102045pppmmm Density Alarm Time

unsigned int

60

General

1690

R / U 102046pppmmm Density @ 4mA

unsigned div10

4000.0

W&M

1692

R / U 102047pppmmm Density @ 20mA

unsigned div10

4000.0

12000

W&M

1694

signed div10

-300

300

W&M

1696

R / U 102048pppmmm Density Offset


R / U 102049pppmmm unused
R / U 102050pppmmm Pressure Sensor
R / U 102051pppmmm Pressure Sensor FCM#

1698
disable/enable
unsigned int

31

Disabled

W&M

1700

W&M

1702

R / U 102052pppmmm unused

1704

R / U 102053pppmmm Default Pressure

unsigned int

9999

9999

W&M

1706

R / U 102054pppmmm Alarm Low Pressure

unsigned int

9999

100

General

1708

R / U 102055pppmmm Alarm High Pressure

unsigned int

9999

450

General

1710

R / U 102056pppmmm Pressure Alarm Time

unsigned int

60

General

1712

R / U 102057pppmmm Pressure @ 4mA

unsigned int

9999

W&M

1714

R / U 102058pppmmm Pressure @ 20mA

unsigned int

9999

650

W&M

1716

R / U 102059pppmmm Pressure Offset

signed div100

-3.00

3.00

0.00

W&M

1718

R / U 102060pppmmm Relative Density Sensor

disable/enable

Disabled

W&M

1678

W&M

1680

R / U 102061pppmmm Relative Density Sensor FCM#

unsigned int

31

R / U 102062pppmmm unused

1682

R / U 102063pppmmm Default Relative Density

unsigned div10000

0.0000

2.0000

0.0000

General

1684

R / U 102064pppmmm Alarm Low Relative Density

unsigned div10000

0.0000

2.0000

0.0000

General

1686

R / U 102065pppmmm Alarm High Relative Density

unsigned div10000

0.0000

2.0000

1.2000

General

1688

R / U 102066pppmmm Relative Density Alarm Time

unsigned int

60

0.0000

General

1690

unsigned div10000

0.0000

4.0000

0.0000

W&M

1692

R / U 102067pppmmm Relative Density @ 4mA

Chapter 7 Register Operations

67

Modbus
Min

Max

Default

Date Type

Value

Value

Value

unsigned div10000

0.0000

4.0000

1.2000

W&M

1694

signed div10000

-0.0300

0.0300

0.0000

W&M

1696

R / U 102070pppmmm 2% MF Limit Ref

unsigned div10000

0.0000

6.5535

0.0000

W&M

1740

R / U 102071pppmmm Adjacent MF Dev Limt

unsigned div10000

0.0000

0.1000

0.0000

W&M

1742

unsigned div100

0.00

5.00

3.00

W&M

1744

Prefix

Register

Description

R / U 102068pppmmm Relative Density @ 20mA


R / U 102069pppmmm Relative Density Offset

R / U 102072pppmmm Temp Offset Limit

Register
Protection Len=2

R / U 102073pppmmm unused

1746

R / U 102074pppmmm unused

1748

R / U 102080pppmmm unused

1760

R / U 102081pppmmm Alarm Out FCM#

fcm address

Disabled

General

1762

R / U 102082pppmmm Authorized FCM#

fcm address

Disabled

General

1764

R / U 102083pppmmm Permiss FCM#

fcm address

Disabled

General

1766

R / U 102084pppmmm Permiss Out FCM#

fcm address

Disabled

General

1768

R / U 102085pppmmm Meter K-Factor

unsigned int

50

W&M

1770

Disabled

W&M

1772

R / U 102086pppmmm Quad Check Enable

65535

disable/enable

R / U 102087pppmmm unused
R / U 102088pppmmm Temperature Offset

1774
signed div100

-5.00

5.00

0.00

W&M

1776

R / U 102089pppmmm Temperatr Alarm Time

unsigned int

60

General

1778

R / U 102090pppmmm Temp Sensor FCM#

unsigned int

31

W&M

1780

R / U 102091pppmmm Temperature Sensor

disable/enable

Enabled

W&M

1782

R / U 102092pppmmm Default Temperature

signed div10

-999.9

999.9

999.9

W&M

1784

R / U 102093pppmmm Alarm Low Temp

signed div10

-999.9

999.9

-999.9

General

1786

R / U 102094pppmmm Alarm High Temp

signed div10

-999.9

999.9

999.9

General

1788

R / U 102095pppmmm Temp Module Type

unsigned int

19

W&M

1790

R / U 102096pppmmm Temperature @ 4mA

signed div10

-999.9

999.9

-50.0

W&M

1792

R / U 102097pppmmm Temperature @ 20mA

signed div10

-999.9

999.9

350.0

W&M

1794

R / U 102098pppmmm unused

1796

R / U 102099pppmmm unused

1798

Chapter 7 Register Operations

7.1.6

68

103 COMPONENT LEVEL CONFIGURATION REGISTERS

Note:

ppp = The specified zero-based preset or load arm number (000-011).


ccc = The specified zero-based component number (000-007).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
The Modbus Component Index Register sets the ccc index, Read/Write Register=997, Len=1, 16-Bit Integer
Modbus
Register
Prefix

Register

Description

Date Type

Min Value Max Value Default Value Protection

Len=2

R / U 103000pppccc Meter#

unsigned int

General

1800

R / U 103001pppccc High Flow Rate

unsigned int

9999

600

General

1802

R / U 103002pppccc 1st Stage Trip Vol

unsigned int

65535

70

General

1804

R / U 103003pppccc 1st Stage Flow Rate

unsigned int

9999

225

General

1806

R / U 103004pppccc 2nd Stage Trip Vol

unsigned int

65535

20

General

1808

R / U 103005pppccc 2nd Stage Flow Rate

unsigned int

9999

150

General

1810

R / U 103006pppccc Final Trip Vol

unsigned div100

0.00

655.35

1.15

General

1812

R / U 103007pppccc Final Trip Max Time

unsigned div1000

0.000

65.535

5.000

General

1814

R / U 103008pppccc Final Trip Vol Lock

disable/enable

Disabled

General

1816

10

General

1818

R / U 103009pppccc Unauth Flow Alrm Vol

unsigned int

65535

R / U 103010pppccc unused
R / U 103011pppccc W&M Recipe Percentage

1820
unsigned div 100

0.00

100.00

0.00

W&M

R / U 103012pppccc unused

1822
1824

R / U 103013pppccc BlkValve Open Rate

unsigned int

9999

General

1826

R / U 103014pppccc BlkValve Open Delay

unsigned int

65535

General

1828

R / U 103015pppccc B.V. Open Alrm Time

unsigned int

65535

10

General

1830

R / U 103016pppccc B.V. Close Alrm Time

unsigned int

65535

10

General

1832

R / U 103017pppccc Pump Start Delay

unsigned int

65535

General

1834

R / U 103018pppccc Pump Stop Delay

unsigned int

65535

30

General

1836

R / U 103019pppccc Pump Start Alrm Time

unsigned int

65535

General

1838

R / U 103020pppccc Flow Start Delay

unsigned int

65535

General

1840

R / U 103021pppccc unused
R / U 103022pppccc Unauth Reset Time

1842
unsigned int

65535

General

R / U 103023pppccc unused

1844
1846

R / U 103024pppccc Fallback Rate

unsigned int

350

General

1848

R / U 103025pppccc Fallback Time

unsigned int

65535

General

1850

R / U 103026pppccc Fallback Retry Time

unsigned int

65535

General

1852

R / U 103027pppccc Fallback Retry Vol

unsigned int

65535

General

1854

R / U 103039pppccc API CTL Table Name

CTL table name

None

W&M

1878

R / U 103040pppccc API CPL Table Name

CPL table name

None

W&M

1880

disable/enable

Disabled

W&M

1882

R / U 103041pppccc API Extrapolated Range

Chapter 7 Register Operations

69

Modbus
Register
Prefix

Register

Description

Date Type

Min Value Max Value Default Value Protection

R / U 103042pppccc unused
R / U 103043pppccc API Gravity
R / U 103044pppccc Default Relative Density

Len=2
1884

signed div10

-100.0

1100.0

0.0

W&M

1886

unsigned div10000 0.0000

2.0000

0.0000

W&M

1888

R / U 103045pppccc Default Density

unsigned div10

9999.9

W&M

1890

R / U 103046pppccc Expansion Coef.

unsigned div10

2000.0

W&M

1892

R / U 103047pppccc Hydrometer Used

disable/enable

Disabled

W&M

1894

R / U 103048pppccc unused

1896

R / U 103049pppccc unused

1898

R / U 103070pppccc unused

1940

R / U 103071pppccc unused

1942

R / U 103072pppccc unused

1944

R / U 103073pppccc unused

1946

R / U 103074pppccc Close Blk Val FCM#

fcm address

Disabled

General

1948

R / U 103075pppccc Blk Val Status FCM

fcm address

Disabled

General

1950

R / U 103076pppccc Open Blk Val FCM#

fcm address

Disabled

General

1952

R / U 103077pppccc unused

1954

R / U 103078pppccc Pump Run FCM#

fcm address

Disabled

General

1956

R / U 103079pppccc Pump Kill FCM#

fcm address

Disabled

General

1958

R / U 103080pppccc Pump Status FCM#

fcm address

Disabled

General

1960

R / U 103081pppccc Alarm Out FCM#

fcm address

Disabled

General

1962

R / U 103082pppccc Authorized FCM#

fcm address

Disabled

General

1964

R / U 103083pppccc Permiss FCM#

fcm address

Disabled

General

1966

R / U 103084pppccc Permiss Out FCM#

fcm address

Disabled

General

1968

1.2000

1.0000

W&M

1970

9999

150

W&M

1972

1.2000

1.0000

W&M

1974

9999

200

W&M

1976

1.2000

1.0000

W&M

1978

9999

400

W&M

1980

1.2000

1.0000

W&M

1982

R / U 103085pppccc Meter Factor #1


R / U 103086pppccc Meter Factor #1 Rate
R / U 103087pppccc Meter Factor #2
R / U 103088pppccc Meter Factor #2 Rate
R / U 103089pppccc Meter Factor #3
R / U 103090pppccc Meter Factor #3 Rate
R / U 103091pppccc Meter Factor #4

unsigned div10000 0.8000


unsigned int

unsigned div10000 0.8000


unsigned int

unsigned div10000 0.8000


unsigned int

unsigned div10000 0.8000

R / U 103092pppccc Meter Factor #4 Rate

unsigned int

9999

800

W&M

1984

R / U 103093pppccc # Meter Factors Used

unsigned int

W&M

1986

R / U 103094pppccc unused

1988

Chapter 7 Register Operations

7.1.7

70

104 ADDITIVE LEVEL CONFIGURATION REGISTERS

Note:

ppp = The specified zero-based preset or load arm number (000-011).


aaa = The specified zero-based additive number (000-0015).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
The Modbus Additive Index Register sets the aaa index, Read/Write Register=999, Len=1, 16-Bit Integer
Modbus
Register
Prefix

Register

Description

Date Type

Min Value Max Value Default Value Protection

disable/enable

Len=2

R/U

104000pppaaa Additive Enable

Disabled

General

2000

R/U

104001pppaaa Flow Control Module#

unsigned int

31

General

2002

R/U

104002pppaaa FCM Port#

unsigned int

General

2004

R/U

104003pppaaa W&M Controlled

disable/enable

Disabled

W&M

2006

R/U

104004pppaaa Upstream Block Valve

disable/enable

Disabled

General

2008

R/U

104005pppaaa unused

R/U

104006pppaaa Piston Injector Used

disable/enable

Disabled

General

2012

R/U

104007pppaaa Pulser Input Used

disable/enable

Enabled

General

2014

R/U

104008pppaaa Piston Input Used

disable/enable

Disabled

General

2016

R/U

104009pppaaa Pstn Inp Norm Low

disable/enable

Disabled

General

2018

R/U

104010pppaaa unused

2020

R/U

104011pppaaa unused

2022

R/U

104019pppaaa Solenoid Shut Pulses

unsigned int

255

General

2038

R/U

104020pppaaa Shutoff Vol From End

unsigned int

65535

General

2040

R/U

104021pppaaa LastInj Vol From End

unsigned int

65535

20

General

2042

R/U

104022pppaaa Line Flush Min Vol

unsigned int

65535

General

2044

R/U

104023pppaaa Assigned Component

unsigned int

General

2046

R/U

104024pppaaa W&M Recipe Percentage

percent div 10000

0.0000%

6.5535%

0.0000%

W&M

2048

R/U

104025pppaaa unused

2050

R/U

104026pppaaa unused

2052

R/U

104027pppaaa Additive Vol/Inject

unsigned div10000

0.0000

6.5535

0.0200

Conditional

2054

R/U

104028pppaaa Vol/Inject Cal Factr

unsigned div10000

0.0001

6.5535

1.0000

Conditional

2056

R/U

104029pppaaa unused

2058

R/U

104030pppaaa unused

2060

R/U

104031pppaaa Additive Mtr K-Factr

unsigned int

65535

2600

Conditional

2062

R/U

104032pppaaa Additive Mtr Factor

unsigned div10000

0.0001

6.5535

1.0000

Conditional

2064

R/U

104033pppaaa Max Pstn Missed Inj

unsigned int

65535

Conditional

2066

R/U

104034pppaaa MaxSolenoid Inj Time

unsigned div1000

0.100

10.000

4.000

Conditional

2068

R/U

104035pppaaa Under Add Alrm # Inj

unsigned int

65535

Conditional

2070

R/U

104036pppaaa Over Add Alrm # Inj

unsigned int

65535

Conditional

2072

R/U

104037pppaaa Check Add Tol Time

unsigned int

65535

10

Conditional

2074

R/U

104038pppaaa Unauth Flow Alrm Vol

unsigned int

65535

100

General

2076

2010

Chapter 7 Register Operations

71

Modbus
Register
Prefix

Register

Description

Date Type

Min Value Max Value Default Value Protection

Len=2

R/U

104039pppaaa Valve Fault Alrm Vol

unsigned int

65535

300

General

2078

R/U

104040pppaaa Over Inject Vol

unsigned int

65535

Conditional

2080

R/U

104041pppaaa Creep Reset Time

unsigned int

65535

General

2082

R/U

104042pppaaa Unauth Reset Time

unsigned int

65535

General

2084

R/U

104043pppaaa Max Pistn Throw Time

unsigned div1000

0.100

10.000

1.800

General

2086

R/U

104044pppaaa Pump Start Alrm Time

unsigned int

65535

General

2088

R/U

104045pppaaa Meter Creep Alrm Vol

unsigned int

65535

150

General

2090

R/U

104046pppaaa Remote Calibration

Enabled

General

2092

R/U

104047pppaaa B.V. Open Alrm Time

unsigned int

65535

10

General

2094

R/U

104048pppaaa B.V. Close Alrm Time

unsigned int

65535

10

General

2096

R/U

104049pppaaa Pump Stop Delay

unsigned int

65535

General

2098

R/U

104050pppaaa Flush Pump Run Time

unsigned int

65535

30

General

2100

R/U

104051pppaaa Meter Flushed

disable/enable

Disabled

General

2102

R/U

104052pppaaa Solenoid Flushed

disable/enable

Disabled

General

2104

R/U

104053pppaaa unused

R/U

104054pppaaa W&M Alarm Promo Count

unsigned int

65535

W&M

R/U

104055pppaaa W&M Alarm Reset Mode

alarm count
reset mode

10

W&M

R/U

104085pppaaa unused

2170

R/U

104086pppaaa unused

2172

R/U

104087pppaaa unused

2174

R/U

104088pppaaa Flush Pump Run FCM#

fcm address

Disabled

General

2176

R/U

104089pppaaa Close Blk Val FCM#

fcm address

Disabled

General

2178

R/U

104090pppaaa Blk Val Status FCM#

fcm address

Disabled

General

2180

R/U

104091pppaaa Open Blk Val FCM#

fcm address

Disabled

General

2182

R/U

104092pppaaa Test Button FCM#

fcm address

Disabled

General

2184

R/U

104093pppaaa Pump Run FCM#

fcm address

Disabled

General

2186

R/U

104094pppaaa Pump Kill FCM#

fcm address

Disabled

General

2188

R/U

104095pppaaa Pump Status FCM#

fcm address

Disabled

General

2190

R/U

104096pppaaa Alarm Out FCM#

fcm address

Disabled

General

2192

R/U

104097pppaaa Authorized FCM#

fcm address

Disabled

General

2194

R/U

104098pppaaa Permiss FCM#

fcm address

Disabled

General

2196

R/U

104099pppaaa Permiss Out FCM#

fcm address

Disabled

General

2198

disable/enable

2106
2108
2110

Chapter 7 Register Operations

7.1.8

Note:

105 CUSTOM LOGIC DEFINITIONS REGISTERS


R105iiiii
=>
0?0105iiiiittttt
U105105iiiiittttt
=>
0?0105
Where:
iiiii = The specified zero-based custom logic index (0000-1023).
For Modbus, the Modbus Custom Logic Index Register sets the iiii index.
Modbus: Read/Write Register=296, Len=1, 16-Bit Integer (iiiii)
ttttt = Custom Logic Type as:
enum custom_logic_type
{
// misc types
UNUSED = 0,
FCM_INPUT_PORT = 1,
FCM_OUTPUT_PORT = 2,
// run time values
RCU_RT = 10,
BAY_RT = 11,
PRESET_RT = 12,
COMPONENT_RT = 13,
METER_RT = 14,
ADDITIVE_RT = 15,
// boolean operations and comparitors
ALWAYS_FALSE = 100,
ALWAYS_TRUE = 101,
ASSIGN = 102,
NOT = 103,
AND = 104,
NAND = 105,
OR = 106,
NOR = 107,
EOR = 108,
// analog operations
ADD = 120,
SUBTRACT = 121,
MULTIPLY = 122,
DIVIDE = 123,
SET_VALUE = 124,
// analog comparitors
EQUAL = 140,
LESS_THAN = 141,
GREATER_THAN = 142,
LESS_THAN_OR_EQUAL = 143,
GREATER_THAN_OR_EQUAL = 144,
} type;

72

Chapter 7 Register Operations

Modbus: Read/Write Register=297, Len=1, 16-Bit Integer (ttttt)


= Type Specific Commands
If type -= UNUSED, (No Further Parameters)
If type -= FCM_INPUT, fffffppppp
Where:
fffff FCM Number (0-32)
ppppp FCM Port (0-7)
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (fffff)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
If type -= FCM_OUTPUT, fffffpppppxxxxx
Where:
fffff FCM Number (0-32)
ppppp FCM Port (0-7)
xxxxx = Custom logic index (0000-1023).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (fffff)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
Modbus: Read/Write Register=300, Len=1, 16-Bit Integer (xxxxx)
If type -= RCU_RT, rrrrr
Where:
rrrrr Bay Real Time Parameter Type as
custom_logic_rcu_real_time_prompt[] =
{
{"Proving Mode"},
// 00000
{"W&M Key"}, // 00001
{"Program Key"},
// 00002
{"Card Inserted"},
// 00003
};
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (rrrrr)
If type -= BAY_RT, rrrrrppppp
Where:
rrrrr Bay Real Time Parameter Type as
custom_logic_bay_real_time_prompt[] =
{
{"Clearing Errors"},
// 00000
{"Diag Mode"}, // 00001
{"All Stop"},
// 00002
{"Alarm Out"}, // 00003
{"Authorized"}, // 00004
{"Permissive Out"},
// 00005
{"Permissive 0"},
// 00006

73

Chapter 7 Register Operations

74

{"Permissive 1"},
{"Permissive 2"},
{"Permissive 3"},
{"Permissive 4"},
{"Permissive 5"},
{"Permissive 6"},
{"Permissive 7"},

// 00007
// 00008
// 00009
// 00010
// 00011
// 00012
// 00013

};
ppppp Zero-based preset number (00000-00011).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (rrrrr)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
If type -= PRESET_RT, rrrrrppppp
Where:
rrrrr Preset Real Time Parameter Type as
custom_logic_preset_real_time_prompt[] =
{
{"Authorized"}, // 00000
{"Flow Active"}, // 00001
{"BatchAuthorized"},
// 00002
{"Load Complete"},
// 00003
{"Clearing Errors"},
// 00004
{"Clearing Load"},
// 00005
{"Open Blk Valve"},
// 00006
{"Blk Val Status"},
// 00007
{"Close Blk Valve"},
// 00008
{"Remote Start"},
// 00009
{"Swing Arm"}, // 00010
{"Meter Stop"}, // 00011
{"Alarm Out"}, // 00012
{"Permissive"}, // 00013
{"Permissive Out"},
// 00014
};
ppppp Zero-based preset number (00000-00011).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (rrrrr)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
If type -= COMPONENT_RT, rrrrrppppplllll
Where:
rrrrr Component Real Time Parameter Type as
custom_logic_component_real_time_prompt[] =
{
{"Clearing Errors"},
// 00000
{"Clear Batch"}, // 00001
{"Rem Start Buttn"},
// 00002
{"Pump Run"}, // 00003

Chapter 7 Register Operations

75

{"Pump Kill"}, // 00004


{"Pump Status"},
// 00005
{"Open Blk Valve"},
// 00006
{"Blk Val Status"},
// 00007
{"Close Blk Valve"},
// 00008
{"Alarm Out"}, // 00009
{"Authorized"}, // 00010
{"Permissive"}, // 00011
{"Permissive Out"},
// 00012
};
ppppp Zero-based preset number (00000-00011).
lllll = Zero based component number (00000-00007).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (rrrrr)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
Modbus: Read/Write Register=300, Len=1, 16-Bit Integer (lllll)
If type -= METER_RT, rrrrrppppplllll
Where:
rrrrr Meter Real Time Parameter Type as
custom_logic_meter_real_time_prompt[] =
{
{"Clearing Errors"},
// 00000
{"Clear Totals"}, // 00001
{"Alarm Out"}, // 00002
{"Authorized"}, // 00003
{"Permissive"}, // 00004
{"Permissive Out"},
// 00005
{"SidStrm On Mtr"},
// 00006
};
ppppp Zero-based preset number (00000-00011).
lllll = Zero based meter number (00000-00003).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (rrrrr)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
Modbus: Read/Write Register=300, Len=1, 16-Bit Integer (lllll)
If type -= ADDITIVE_RT, rrrrrppppplllll
Where:
rrrrr Additive Real Time Parameter Type as
custom_logic_additive_real_time_prompt[]
{
(Clearing Errors),
// 00000
(Clear Batch"}, // 00001
(Test Button"}, // 00002
("Pump Run"}, // 00003
{"Pump Kill"}, // 00004
{"Pump Status"},
// 00005

Chapter 7 Register Operations

76

{"Open Blk Valve"},


// 00006
{"Blk Val Status"},
// 00007
{"Flush Pump Run"},
// 00008
{"Close Blk Valve"},
// 00009
{"Alarm Out"}, // 00010
{"Authorized"}, // 00011
{"Permissive"}, // 00012
{"Permissive Out"},
// 00013
};
ppppp Zero-based preset number (00000-00011).
lllll = Zero based additive number (00000-00015).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (rrrrr)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (ppppp)
Modbus: Read/Write Register=300, Len=1, 16-Bit Integer (lllll)
If type -= ALWAYS_FALSE or ALWAYS_FALSE, (No Further Parameters)
If type -= ASSIGN or NOT, xxxxx
Where:
xxxxx = Custom logic index (0000-1023).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (xxxxx)
If type -= any other valid type, xxxxxyyyyy
Where:
xxxxx = Custom logic index (0000-1023).
yyyyy = Custom logic index (0000-1023).
Modbus: Read/Write Register=298, Len=1, 16-Bit Integer (xxxxx)
Modbus: Read/Write Register=299, Len=1, 16-Bit Integer (yyyyy)
7.1.9

200 STAND ALONE BOL DEFINITION REGISTERS


R200 => 0?0200aabbccddeeff
U200aabbccddeeff => 0?0200
Where:
aabb = BOL Line and Position Number for the BOL Number
ccdd = BOL Line and Position Number for the Card Number
eeff = BOL Line and Position Number for the Company
Modbus:
Read/Write Register=350, Len=1, 16-Bit Integer (aa)
Read/Write Register=351, Len=1, 16-Bit Integer (bb)
Read/Write Register=352, Len=1, 16-Bit Integer (cc)
Read/Write Register=353, Len=1, 16-Bit Integer (dd)
Read/Write Register=354, Len=1, 16-Bit Integer (ee)
Read/Write Register=355, Len=1, 16-Bit Integer (ff)
R201 => 0?0201aabbccddeeffgghh

Chapter 7 Register Operations

U201aabbccddeeffgghh => 0?0201


Where:
aabb = BOL Line and Position Number for the Load Date
ccdd = BOL Line and Position Number for the Load Start Time
eeff = BOL Line and Position Number for the Load End Time
gghh = BOL Line and Position Number for the Corrected To
Modbus:
Read/Write Register=356, Len=1, 16-Bit Integer (aa)
Read/Write Register=357, Len=1, 16-Bit Integer (bb)
Read/Write Register=358, Len=1, 16-Bit Integer (cc)
Read/Write Register=359, Len=1, 16-Bit Integer (dd)
Read/Write Register=360, Len=1, 16-Bit Integer (ee)
Read/Write Register=361, Len=1, 16-Bit Integer (ff)
Read/Write Register=362, Len=1, 16-Bit Integer (gg)
Read/Write Register=363, Len=1, 16-Bit Integer (hh)
R202 => 0?0202aabbccddeeff
U202aabbccddeeff => 0?0202
Where:
aabb = BOL Line and Position Number for the Hazard Message
Modbus:
Read/Write Register=364, Len=1, 16-Bit Integer (aa)
Read/Write Register=365, Len=1, 16-Bit Integer (bb)
R203 => 0?0203aabbccddeeffgghhiijjkk
U203aabbccddeeffgghhiijjkk => 0?0203
Where:
aa = BOL Line Number to Start Product Totals
bb = BOL Position Number for the Product Code
cc = BOL Position Number for the Product Description
dd = BOL Position Number for the Product Gross Volume
ee = BOL Position Number for the Product Net Volume
ff = BOL Position Number for the Product Average Temp
gg = BOL Position Number for the Product Preset Number
hh = BOL Position Number for the Product Gravity/Density
ii = BOL Position Number for the Product Pressure
jj = BOL Position Number for the Product Alarm
kk = BOL Position Number for the Compartment Number (optional)
Modbus:
Read/Write Register=366, Len=1, 16-Bit Integer (aa)
Read/Write Register=367, Len=1, 16-Bit Integer (bb)
Read/Write Register=368, Len=1, 16-Bit Integer (cc)
Read/Write Register=369, Len=1, 16-Bit Integer (dd)
Read/Write Register=370, Len=1, 16-Bit Integer (ee)
Read/Write Register=371, Len=1, 16-Bit Integer (ff)
Read/Write Register=372, Len=1, 16-Bit Integer (gg)

77

Chapter 7 Register Operations

Read/Write Register=373, Len=1, 16-Bit Integer (hh)


Read/Write Register=374, Len=1, 16-Bit Integer (ii)
Read/Write Register=375, Len=1, 16-Bit Integer (jj)
R204 => 0?0204aabbccdd
U204aabbccdd => 0?0204
Where:
aabb = BOL Line and Position Number for the Total Product Gross Volume
ccdd = BOL Line and Position Number for the Total Product Net Volume
Modbus:
Read/Write Register=376, Len=1, 16-Bit Integer (aa)
Read/Write Register=377, Len=1, 16-Bit Integer (bb)
Read/Write Register=378, Len=1, 16-Bit Integer (cc)
Read/Write Register=379, Len=1, 16-Bit Integer (dd)

Note:

R300iiill => 0?0300iiill


U300iiill => 0?0300iiill
Where:
iii = BOL Literal Line Index (0-29)
For Modbus, the Modbus Custom Logic Index Register sets the iii index.
Modbus: Read/Write Register=417, Len=1, 16-Bit Integer (iii)
ll = BOL Line Number
= Literal String (Max 80 Characters)
Modbus:
Read/Write Register=418, Len=1, 16-Bit Integer (ll)
Read/Write Register=419, Len=80, Characters ()
Note: Last Register Used=498
R410iil => 0?0410iilaabbcc
U410iilaabbcc => 0?0410iil
Where:
ii = Prompt Index (0-3)
l = Language Index (0-5)
aa = Input Length (0-19)
bbcc = BOL Line and Position Number
= Prompt String (Max 20 Characters)
Modbus:
l = Language Index (0-1)
Read/Write Register=550+23*(2*ii+l), Len=1, 16-Bit Integer (aa)
Read/Write Register=551+23*(2*ii+l), Len=1, 16-Bit Integer (bb)
Read/Write Register=552+23*(2*ii+l), Len=1, 16-Bit Integer (cc)
Read/Write Register=553+23*(2*ii+l), Len=20, Characters ()
Note: Last Prompt Register Used=733
R420iii => 0?0420iii

78

Chapter 7 Register Operations

U420iii => 0?0420iii


Where:
iii = Hazard Index (0-4)
= Hazard String (Max 40 Characters)
Modbus:
Read/Write Register=734+40*iii, Len=40, Characters ()
Note: Last Register Used=833
7.1.10 800 TRANSACTION ARCHIVE REGISTERS
R005 =>
0?0BBBBB
Where:
BBBBB = BOL Transaction Number of Current or Last Transaction completed.
Modbus: Read Only Register=48, Len=1, 16-Bit Integer

Note:

Note:

R800BBBBII => 0?0800BBBBII


(or)
R800BBBBIIII => 0?0800BBBBIIII
Where:
BBBB = BOL Transaction Number
For Modbus, the Modbus Transaction Number Index Register sets the BBBB index.
Modbus: Read/Write Register=7800, Len=1, 16-Bit Integer (BBBB)
II (or) IIII = BOL Detail Line Index
For Modbus, the Modbus Transaction Detail Index Register sets the IIII index.
Modbus: Read/Write Register=7801, Len=1, 16-Bit Integer (IIII)
= Type Specific Parameters
if BOL Detail Line Index = 00,
IIBBBBnnnn(10)oosssspppptttteeaaaa(25)bbbb(25)cccc(25)dddd(25)
(or)
IIIIBBBBnnnn(10)oosssspppptttteeaaaa(25)bbbb(25)cccc(25)dddd(25)
II (or) IIII = BOL Detail Line Index
BBBB = BOL Transaction Number
nnnn = Card Number (10 Characters)
oo = Company Number
ssss = Load Start Time
pppp = Load Stop Time
tttt = Load Date
ee = Number of Details in Transaction
aaaa = Driver Prompt #1 Value (25 Characters)
bbbb = Driver Prompt #2 Value (25 Characters)
cccc = Driver Prompt #3 Value (25 Characters)
dddd = Driver Prompt #4 Value (25 Characters)
Modbus:
Read/Write Register=7810, Len=2, 32-Bit Integer (nnnn)

79

Chapter 7 Register Operations

Read/Write Register=7812, Len=1, 16-Bit Integer (oo)


Read/Write Register=7813, Len=1, 16-Bit Integer (ssss)
Read/Write Register=7814, Len=1, 16-Bit Integer (pppp)
Read/Write Register=7815, Len=1, 16-Bit Integer (tttt)
Read/Write Register=7816, Len=1, 16-Bit Integer (ee)
Read/Write Register=7817, Len=25, Characters (aaaa)
Read/Write Register=7842, Len=25, Characters (bbbb)
Read/Write Register=7867, Len=25, Characters (cccc)
Read/Write Register=7892, Len=25, Characters (dddd)
if BOL Detail Line Index > 00,
IIBBBBppptthhhccccccgggggggggnnnnnnnnnttttddddmmrrrr
(or)
IIIIBBBBppptthhhccccccgggggggggnnnnnnnnnttttddddmmrrrr
II (or) IIII = BOL Detail Line Index
BBBB = BOL Transaction Number
ppp = Preset Number
tt = Detail Type,
1 Saleable Product,
2 Component,
3 Additive,
4 Meter,
5 Preset Totalizer,
6 Meter Totalizer,
7 Component Totalizer,
8 Additive Totalizer
hhh = Legacy Header Index (not used)
cccccc = Product Code
ggggggggg = Gross Volume
nnnnnnnnn = Net Volume
Note: if the Use Hundredths W&M RCU parameter is enabled, the gross and net quantity value will have an implied two decimal places.

tttt = Average Temp


dddd = Gravity or Density
mm = Compartment
rrrr = Average Pressure
Modbus:
Read/Write Register=7810, Len=1, 16-Bit Integer (ppp)
Read/Write Register=7811, Len=1, 16-Bit Integer (tt)
Read/Write Register=7812, Len=6, Characters (cccccc)
Read/Write Register=7818, Len=2, 32-Bit Integer (ggggggggg)
Read/Write Register=7820, Len=2, 32-Bit Integer (nnnnnnnnn)
Read/Write Register=7822, Len=1, 16-Bit Integer (tttt)
Read/Write Register=7823, Len=1, 16-Bit Integer (dddd)
Read/Write Register=7824, Len=1, 16-Bit Integer (mm)
Read/Write Register=7825, Len=1, 16-Bit Integer (rrrr)

80

Chapter 7 Register Operations

7.2

SPECIAL PURPOSE REGISTERS

7.2.1

000 MULTILOAD FIRMWARE VERSION


R000 =>
0?0sssssssssssssssssss
Where:
sssssssssssssssssss = Firmware Identification
000MultiLoad II
v3.31.xx Jan
000MultiLoad II
v4.31.xx Jan
000MultiLoad 1Arm v3.31.xx Jan
000MultiLoad 1Arm v4.31.xx Jan
000MultiLoad Mobl v3.31.xx Jan
000MultiLoad Mobl v4.31.xx Jan
000MultiLoad SMP v3.31.xx Jan
000MultiLoad SMP v4.31.xx Jan

81

xx
xx
xx
xx
xx
xx
xx
xx

2011
2011
2011 (discontinued)
2011 (discontinued)
2011
2011
2011
2011

Modbus: Read Only Register=000, Len=35, Characters (sssssssssssssssssss)


7.2.2

001 DATE AND TIME


R001 =>
0?0001YYMMDDHHMMSS
U001YYMMDDHHMMSS
=>
0?0
Where:
YY = Year (00-99).
MM = Month (01-12)
DD = Day (01-32)
HH = Hours (00-23)
MM = Minutes (00-59)
SS = Seconds (00-59)
Note: Update will only occur if new time is different from current time by number of seconds specified by
R014 (Min Time Change Secs).
Modbus: Read/Write Register=035, Len=12, Characters (YYMMDDHHMMSS)

7.2.3

003 FCM POLL RATE


R003 =>
0?0DD
Where:
DD = Average number of FCMs polled per second.
Modbus: Read Only Register=047, Len=1, 16-Bit Integer

7.2.4

005 CURRENT BOL/TICKET NUMBER


R005 =>
0?0DDDDD
Where:
DDDDD = Current BOL/Ticket Number.
Modbus: Read Only Register=048, Len=1, 16-Bit Integer

7.2.5

070 ETHERNET ENABLE


R070

=>

0?0070DDDDDDDDD

Chapter 7 Register Operations

U070DDDDDDDDD
=>
0?0
Where:
DDDDDDDDD = (000000000 = Disabled), (000000001 = Enabled)
Modbus: Read/Write Register=049, Len=1, 16-Bit Integer
7.2.6

071 IP ADDRESS
R071 =>
0?0071DDD.DDD.DDD.DDD
U071DDD.DDD.DDD.DDD
=>
0?0
Where:
DDD.DDD.DDD.DDD = IP Address
Modbus: Read/Write Register=050, Len=2, 32-Bit Integer (4 8-bit numbers)

7.2.7

072 IP MASK
R072 =>
0?0072DDD.DDD.DDD.DDD
U072DDD.DDD.DDD.DDD
=>
0?0
Where:
DDD.DDD.DDD.DDD = IP Mask
Modbus: Read/Write Register=052, Len=2, 32-Bit Integer (4 8-bit numbers)

7.2.8

073 IP GATEWAY
R073 =>
0?0073DDD.DDD.DDD.DDD
U073DDD.DDD.DDD.DDD
=>
0?0
Where:
DDD.DDD.DDD.DDD = IP Gateway
Modbus: Read/Write Register=054, Len=2, 32-Bit Integer (4 8-bit numbers)

7.2.9

074 IP HOST
R074 =>
0?0074DDD.DDD.DDD.DDD
U074DDD.DDD.DDD.DDD
=>
0?0
Where:
DDD.DDD.DDD.DDD = IP Host
Modbus: Read/Write Register=056, Len=2, 32-Bit Integer (4 8-bit numbers)

7.2.10 085 MODEM INITIALIZATION STRING


R085 =>
0?0085SSS...
U085SSS
=>
0?0
Where:
SSS = ASCII Modem Initialization String (Default "AT&F0&B1&C1&D0S0=1")
Modbus: Read/Write Register=058, Len=40, Characters (SSS), Null Terminated
7.2.11 091..093 COMMUNICATION PORT PARAMETERS
R09p =>
0?009pSDPTAC
U09pSDPTAC =>
0?0

82

Chapter 7 Register Operations

Where:
p = Communication Port (1-3)
S = Communication Speed
0 = 300 BAUD
1 = 1200 BAUD
2 = 2400 BAUD
3 = 4800 BAUD
4 = 9600 BAUD
5 = 19.2K BAUD
6 = 38.4K BAUD
7 = 57.6K BAUD
8 = 115K BAUD
9 = 230K BAUD
D = Data Bits
0 = 7 Data Bits
1 = 8 Data Bits
P = Parity
0 = None
1 = Odd
2 = Even
T = Stop Bits
1 = 1 Stop Bit
2 = 2 Stop Bits
A = Port Assignment
0 = Not in Use
1 = Host
2 = FCMs
3 = Printer
4 = Event Log Printer
5 = Ethernet Pass Thru
6 = Alibi Log
7 = GPS (MultiLoad Mobile Only)
C = Connection Type
0 = Single/Master
1 = Multi-dropped Slave
2 = 2-Wire RS485
Modbus:
p=0, Read/Write Register=243, Len=6, Characters (SDPTAC)
p=1, Read/Write Register=249, Len=6, Characters (SDPTAC)
p=2, Read/Write Register=255, Len=6, Characters (SDPTAC)
7.2.12 095..099 PROGRAM MODE PASSWORDS (5)
R095 =>
0?0095SSSSSSS
U095SSSSSSS =>
0?0
Where:

83

Chapter 7 Register Operations

SSSSSSS = ASCII Password String (Default 00000)


Modbus:
Read/Write Register=261, Len=7, Characters (SSSSSSS), Null Terminated
Read/Write Register=268, Len=7, Characters (SSSSSSS), Null Terminated
Read/Write Register=275, Len=7, Characters (SSSSSSS), Null Terminated
Read/Write Register=282, Len=7, Characters (SSSSSSS), Null Terminated
Read/Write Register=289, Len=7, Characters (SSSSSSS), Null Terminated
7.2.13 112 - REAL-TIME PRESET TOTAL GROSS TOTALIZERS
R112ppp
=>
0?0112pppPPPPPPPPPMMMMMMMMMCCCCCCCCCAAAAAAAAA
Where:
ppp = The specified zero-based preset or load arm number (000-011).
PPPPPPPPP = Preset Total Gross Totalizer
MMMMMMMMM = Meter Total Gross Totalizers (at least 4 meters, 9 digits per totalizer.)
CCCCCCCCC = Component Total Gross Totalizers (8 components, 9 digits per totalizer.)
Note: if the Use Hundredths W&M RCU parameter is enabled, the preset, meter and component gross quantity values will have an implied
two decimal places.

AAAAAAAAA = Additive Total Gross Totalizers in Thousands, (16 additives, 9 digits per
totalizer.)
Modbus:
Where: p = preset (0-11), m = meter (0-4), c = component (0-7), a=additive (0-15)
Read Only Registers=3000+2*p, Len=2, 32-Bit Integer (PPPPPPPPP)
Read Only Registers=3024+2*(5*p+m), Len=2, 32-Bit Integer (MMMMMMMMM)
Read Only Registers=3144+2*(8*p+c), Len=2, 32-Bit Integer (CCCCCCCCC)
Read Only Registers=3336+2*(16*p+a), Len=2, 32-Bit Integer (AAAAAAAAA)
Note: Last Gross Totalizer register used=3719
7.2.14 113 - REAL-TIME PRESET TOTAL NET TOTALIZERS
R113ppp
=>
0?0113pppPPPPPPPPPCCCCCCCCC
Where:
ppp = The specified zero-based preset or load arm number (000-011).
PPPPPPPPP = Preset Total Net Totalizer
CCCCCCCCC = Component Total Net Totalizers (8 components, 9 digits per totalizer.)
Note: if the Use Hundredths W&M RCU parameter is enabled, the preset and component net quantity values will have an implied two
decimal places.

Modbus:
Where: p = preset (0-11), c = component (0-7)
Read Only Registers=3720+2*p, Len=2, 32-Bit Integer (PPPPPPPPP)
Read Only Registers=3744+2*(8*p+c), Len=2, 32-Bit Integer (CCCCCCCCC)
Note: Last Net Totalizer register used=3935
7.2.15 133 FCM IO ACCESS
R133fffppp
=>
0?0133fffpppc
Where:
fff = FCM number (000-031).
ppp = FCM port number (0-35)

84

Chapter 7 Register Operations

c = FCM com, 0 FCM COM ok, 1 FCM COM error.


= Type Specific Replies
if FCM port number is 0..7, d
Where:
d=
State of Digital Port (0 Off, 1 On)
if FCM port number is 8, fffff
Where:
ffff =
Raw frequency/digital value from Opto 22 Analog Module
if FCM port number is 9, sfffff
Where:
sttttt = Temp in Hundreds from Opto 22 RTD Analog Module
(no offset added)
if FCM port number is 10, sttttt
Where:
sttttt = Temp in Hundreds from Toptech RTD Module, FCM II
or I/O Board (no offset added)
Note: All Temps in C or F depending on Register R100003 ("Temps in F").
if FCM port number is 20..35, d (this is used to access I/O board ports and FCM II
expander ports > 7)
Where:
d = State of Digital Port (s-20) (0 Off, 1 On)
Modbus:
Supported through Modbus Extended Services Registers.
U133fffpppd =>
0?0133fff
Where:
fff = FCM number (000-031).
ppp = FCM port number (0-35)
d = Set new state of digital port (0 Off, 1 On)
Note: States commanded with R133 are ORd with any other functionality already assigned to the port)
7.2.16 140 CURRENT LATITUDE/LONGITUDE POSITION REGISTERS (MULTILOAD MOBILE ONLY)
R140 => 0?0140+lllllllll+ooooooooo
Where:
+lllllllll = Current Latitude Position.
+ooooooooo = Current Longitude Position.
Note: Latitude format (S 90 to N 90) is:
if Latitude >= 0 then "N" else "S"
integer_degrees = abs(Latitude) / 60000
float_minutes = (abs(Latitude) % 60000) / 1000
Note: Longitude format (180 E to 180 W) is:
if Longitude >= 0 then "E" else "W"
integer_degrees = abs(Longitude) / 60000
float_minutes = (abs(Longitude) % 60000) / 1000
Note: Latitude & Longitude = 999999999 when no valid data available.

85

Chapter 7 Register Operations

Modbus:
Read Only Registers=310, Len=2, 32-Bit Signed Integer (+lllllllll)
Read Only Registers=312, Len=2, 32-Bit Signed Integer (+ooooooooo)
7.2.17 141 CURRENT TRANSACTION LATITUDE/LONGITUDE/SITE INDEX REGISTERS (MULTILOAD MOBILE ONLY)
R141 => 0?0141+lllllllll+ooooooooosssssssss
Where:
+lllllllll = Current Transaction Latitude Position.
+ooooooooo = Current Transaction Longitude Position.
sssssssss = Current Transaction Site Index (GPS Site Database).
Note: Updated on transaction authorization (T<esc>A).
Note: Latitude format (S 90 to N 90) is:
if Latitude >= 0 then "N" else "S"
integer_degrees = abs(Latitude) / 60000
float_minutes = (abs(Latitude) % 60000) / 1000
Note: Longitude format (180 E to 180 W) is:
if Longitude >= 0 then "E" else "W"
integer_degrees = abs(Longitude) / 60000
float_minutes = (abs(Longitude) % 60000) / 1000
Note: Site Index = +999999999 when no site match exists.
Modbus:
Read Only Registers=314, Len=2, 32-Bit Signed Integer (+lllllllll)
Read Only Registers=316, Len=2, 32-Bit Signed Integer (+ooooooooo)
Read Only Registers=318, Len=2, 32-Bit Unsigned Integer (sssssssss)
7.2.18 400 - PRESET DEFINITION REGISTERS
R400ppp
=>
0?0400pppNNNNNNNNNNCCCAAAPPPRRR
U400pppNNNNNNNNNNCCCAAAPPP =>
0?0
Where:
ppp = The specified zero-based preset or load arm number (000-011).
NNNNNNNNNN = 10 Character Preset Name
CCC = Component Product Index (500 register) for each component (8 component indices, 3
digits per index.)
AAA = Additive Product Index (500 register) for each additive (16 additive indices, 3 digits per
index.)
RRR = Standalone Authorized Product Index (500 register) (33 product indices, 3 digits per
index.)
Modbus:
Where: p = preset (0-11), c = component (0-7), a = additive (0-15)
Read/Write Registers=8000+67*p, Len=10, Characters (NNNNNNNNNN), Null Terminated
Read/Write Registers=8010+67*p+c, Len=1, 16-Bit Integer (CCC)
Read/Write Registers=8018+67*p+a, Len=1, 16-Bit Integer (AAA)
Read/Write Registers=8034+67*p+r, Len=1, 16-Bit Integer (RRR)
Note: Last Preset Definition register used=8805

86

Chapter 7 Register Operations

7.2.19 401 EXTERNAL PRESET DISPLAY REGISTER


R401ppp
=>
0?0400pppllllllllllPPPPPPPPPVVVVVVVVVssssssssss
U401pppllllllllllPPPPPPPPPVVVVVVVVVssssssssss
=>
0?0
Where:
ppp = external preset number, number must follow last multiload preset # defined.
llllllllll = 10 character product string.
PPPPPPPPP = 9 character preset volume (note only digits will be displayed).
VVVVVVVVV = 9 character delivered volume (note only digits will be displayed).
ssssssssss = 10 character status string.
This interface will allow a host to display other preset volumes, seperate from ML values on the load
screen. These values will be maintained in a different color to clearly estiblish them as not legal
relevant and that they should not be used for trade.
A new bay parameter "Number External Presets" is used to specify how many external presets should
be displayed.
External Preset Load Screen Data will be updated when this command is received.
When an external preset is selected, the state will go to a 'a'-'h' matching the preset number.
MAMppp - can be sent by the host to return to the load screen when done driving the screen.
Modbus:
Supported through Modbus Extended Services Registers.
7.2.20 500 - PRODUCT DEFINITION REGISTERS

Note:

R500iii =>
0?0500iiiHCCCCCCLLLLLLLLLLLLLLLLLLLLLLLLLDDDDDDDDDDCCCPPPPPAAAPPPPP
U500iiiHCCCCCCLLLLLLLLLLLLLLLLLLLLLLLLLDDDDDDDDDDCCCPPPPPAAAPPPPP
=>
0?0
Where:
iii = The specified zero based product index (000-099).
For Modbus, the Modbus Product Definition Index Register sets the iii index.
Modbus: Read/Write Register=2200, Len=1, 16-Bit Integer (iii)
H = Hazzard Index (stand alone use only).
CCCCCC = 6 Character Product Code.
LLLLLLLLLLLLLLLLLLLLLLLLL = 25 Character Long Product Description.
DDDDDDDDDD = 10 Character Product Description.
CCCPPPPP = Component Product Definition Index (CCC) & Component Percent with an
implied two decimal places (i.e. 01234 => 012.34%) (8 component CCCPPPPP pairs).
AAAPPPPP = Additive Product Definition Index (AAA) & Additive Percent with an implied four
decimal places (i.e. 12345 => 1.2345%) (up to 12 additive AAAPPPPP pairs). Note: Max
Additive Percentage is 6.5535%.
Modbus:
Where: c = component (0-7), a = additive (0-11)
Read/Write Register=2201, Len=1, 16-Bit Integer (H)
Read/Write Register=2202, Len=6, Characters (CCCCCC)
Read/Write Register=2208, Len=25, Characters (LLLLLLLLLLLLLLLLLLLLLLLLL)
Read/Write Register=2233, Len=10, Characters (DDDDDDDDDD)
Read/Write Register=2243+2*c, Len=1, 16-Bit Integer (CCC)
Read/Write Register=2244+2*c, Len=1, 16-Bit Integer (PPPPP)

87

Chapter 7 Register Operations

Read/Write Register=2259+2*a, Len=1, 16-Bit Integer (AAA)


Read/Write Register=2260+2*a, Len=1, 16-Bit Integer (PPPPP)
Note: Last Product Definition register used=2271 (only 6 additives)
7.2.21 600 - STANDALONE DRIVER CARD DATABASE

Note:

R600iii =>
0?0600iiiccccccccppppmmlbbbbbbbbbbbbbbbb
U600iiiccccccccppppmmlbbbbbbbbbbbbbbbb
=>
0?0
Where:
iii = Card database index (1 300)
For Modbus, the Modbus Card Database Index Register sets the iii index.
Modbus: Read/Write Register=2300, Len=1, 16-Bit Integer (iii)
cccccccc = Card Number
pppp = PIN Number
mm = Company Id (unused)
l = Language Index (0 or 1)
bbbbbbbbbbbbbbbb = Preset lockouts as 16 bit binary number
(For example 0000000000000011 = preset 1 & 2 locked out for driver)
Modbus:
Read/Write Register=2301, Len=2, 32-Bit Integer (cccccccc)
Read/Write Register=2303, Len=1, 16-Bit Integer (pppp)
Read/Write Register=2304, Len=1, 16-Bit Integer (mm)
Read/Write Register=2305, Len=1, 16-Bit Integer (l)
Read/Write Register=2306, Len=1, 16-Bit Integer (bbbbbbbbbbbbbbbb)

7.2.22 650 GPS SITE DATABASE (MULTILOAD MOBILE ONLY)

Note:

R650iiiiiiiii
=> 0?0650iiiiiiiiinnnnnnnnnnnnnnn+lllllllll+ooooooooo
U650iiiiiiiiinnnnnnnnnnnnnnn+lllllllll+ooooooooo
=>
0?00?0650iiiiiiiiinnnnnnnnnnnnnnn+lllllllll+ooooooooo
Where:
iiiiiiiii = Site Index (000000000-000003999)
For Modbus, the Modbus GPS Site Database Index Register sets the iiiiiiiii index.
Modbus: Read/Write Register=2350, Len=1, 16-Bit Integer (iiiiiiiii)
nnnnnnnnnnnnnnn = Site Name (15 Characters Padded)
+lllllllll = Site Latitude Position.
+ooooooooo = Site Longitude Position.
Note: An Update to index 0 will clear the entire list.
Note: Latitude format (S 90 to N 90) is:
if Latitude >= 0 then "N" else "S"
integer_degrees = abs(Latitude) / 60000
float_minutes = (abs(Latitude) % 60000) / 1000
Note: Longitude format (180 E to 180 W) is:
if Longitude >= 0 then "E" else "W"
integer_degrees = abs(Longitude) / 60000

88

Chapter 7 Register Operations

float_minutes = (abs(Longitude) % 60000) / 1000


Modbus:
Read/Write Register=2351, Len=15, Characters (nnnnnnnnnnnnnnn)
Read/Write Register=2366, Len=2, 32-Bit Signed Integer (+lllllllll)
Read/Write Register=2368, Len=2, 32-Bit Signed Integer (+ooooooooo)
7.2.23 700 - CONFIGURABLE LANGUAGE PROMPTS

Note:

Note:

R700iil =>
0?0700iilsss
U700iilsss =>
0?0
Where:
ii = Prompt Index with defaults as:
00 = "Insert driver card..."
01 = "For Access"
02 = "Invalid Driver..."
03 = "Remove Card..."
04 = "Please Wait..."
07 = "Press 'A' key to Begin..."
19 = "A=Next B=Prev C=Abort D=Pick"
20= "System Unavailable"
28 = "PRE PRODUCT
SET DEL STATUS "
35 = "" // Alternate Load Screen Footer
For Modbus, the Modbus Language Prompt Index Register sets the ii index.
Modbus: Read/Write Register=2400, Len=1, 16-Bit Integer (ii)
l = Language Index (0 or 1)
For Modbus, the Modbus Language Prompt Language Index Register sets the l index.
Modbus: Read/Write Register=2401, Len=1, 16-Bit Integer (l)
sss = Prompt string (40 ASCII characters or 20 UTF-8 characters, 3-bytes each)
Note: if prompt string empty, null, built in prompt will be used based on language setting.
Note: only the prompts listed above can be changed.
Modbus:
Read/Write Register=2402, Len=60, Characters (sss)

7.2.24 710 - BAY ALARM MESSAGES


R710iii =>
0?0710iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
U710iiilllllssssssssssssssssssssssssssssss =>
0?0
U710iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
=>
0?0
Where:
iii = Alarm Index with defaults as:
struct alarm_def factory_bay_alarm[16] =
{
{"*BAY FCM" , AUTO_CLEAR}, // 710000
{"*GROUND ", AUTO_CLEAR}, // 710001
{"*VRU
", AUTO_CLEAR}, // 710002
{"*OVERFILL ", AUTO_CLEAR}, // 710003

89

Chapter 7 Register Operations

90

{"*ESD PERM ", AUTO_CLEAR}, // 710004


{"*BAY PERM4", AUTO_CLEAR}, // 710005
{"*BAY PERM5", AUTO_CLEAR}, // 710006
{"*BAY PERM6", AUTO_CLEAR}, // 710007
{"*BAY PERM7", AUTO_CLEAR}, // 710008
{"*ALL STOP" , AUTO_CLEAR}, // 710009
{"*BAY PCM ", AUTO_CLEAR}, // 710010
{"*PRNTR ERR", AUTO_CLEAR}, // 710011
{"*GPS ERROR", AUTO_CLEAR}, // 710012
{"*BALARM 13", DRIVER_CLEAR}, // 710013
{"*BALARM 14", DRIVER_CLEAR}, // 710014
{"*FCM TRACE", DRIVER_CLEAR}// 710015
Note:

(MultiLoad Mobile Only)

};
For Modbus, the Modbus Bay Alarm Index Register sets the iii index.
Modbus: Read/Write Register=2500, Len=1, 16-Bit Integer (iii)
lll = Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}alarm_level;
ssssssssssssssssssssssssssssss = Alarm Message (prefix with an *)
Note: Up to 30 UTF-8 bytes to represent a max of 10 characters.
ccccc = Promotion Count (00000=no promotion)
ppppp = Promoted Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}promoted_alarm_level;
rrrrr = Reset Mode as:
enum
{
AUTH_TRANS = 0,
CLEAR_PROMOTED = 1,
TIME_2_MIN = 2,
TIME_5_MIN = 3,
TIME_15_MIN = 4,
TIME_30_MIN = 5,

Chapter 7 Register Operations

91

TIME_60_MIN = 6,
TIME_3_HOURS = 7,
TIME_6_HOURS = 8,
TIME_12_HOURS = 9,
TIME_24_HOURS = 10,
}alarm_count_reset_mode;
Note: only permissive names can be changed, iii=1..8
Modbus:
Read/Write Register=2501, Len=1, 16-Bit Integer (lllll)
Read/Write Register=2502, Len=15, Characters (sssssssssssssss)
Note: Up to 15 UTF-8 bytes to represent a max of 10 characters.
Read/Write Register=2517, Len=1, 16-Bit Integer (ccccc)
Read/Write Register=2518, Len=1, 16-Bit Integer (ppppp)
Read/Write Register=2519, Len=1, 16-Bit Integer (rrrrr)
7.2.25 711 - PRESET ALARM MESSAGES

Note:

R711iii =>
0?0711iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
U711iiilllllssssssssssssssssssssssssssssss =>
0?0
U711iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
=>
Where:
iii = Alarm Index with defaults as:
struct alarm_def factory_preset_alarm[16] =
{
{"*PRE FCM" , AUTO_CLEAR}, // 711000
{"*PRE PERM" , AUTO_CLEAR}, // 711001
{"*SWING ARM", AUTO_CLEAR}, // 711002
{"*NO LNFLSH", DRIVER_CLEAR}, // 711003
{"*PALARM 04", DRIVER_CLEAR}, // 711004
{"*BAY ALARM", AUTO_CLEAR}, // 711005
{"*COMP ALRM", AUTO_CLEAR}, // 711006
{"*ADD ALARM", AUTO_CLEAR}, // 711007
{"*MTR STOP" , AUTO_CLEAR}, // 711008
{"*OVERRUN" , REMOTE_CLEAR}, // 711009
{"*EXCESS FL", REMOTE_CLEAR}, // 711010
{"*PALARM 11", DRIVER_CLEAR}, // 711011
{"*PALARM 12", DRIVER_CLEAR}, // 711012
{"*PALARM 13", DRIVER_CLEAR}, // 711013
{"*PALARM 14", DRIVER_CLEAR}, // 711014
{"*INVCONFIG", AUTO_CLEAR} // 711015
};
For Modbus, the Modbus Preset Alarm Index Register sets the iii index.
Modbus: Read/Write Register=2520, Len=1, 16-Bit Integer (iii)
lll = Alarm Level as:
enum

0?0

Chapter 7 Register Operations

{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}alarm_level;
ssssssssssssssssssssssssssssss = Alarm Message (prefix with an *)
Note: Up to 30 UTF-8 bytes to represent a max of 10 characters.
ccccc = Promotion Count (00000=no promotion)
ppppp = Promoted Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}promoted_alarm_level;
rrrrr = Reset Mode as:
enum
{
AUTH_TRANS = 0,
CLEAR_PROMOTED = 1,
TIME_2_MIN = 2,
TIME_5_MIN = 3,
TIME_15_MIN = 4,
TIME_30_MIN = 5,
TIME_60_MIN = 6,
TIME_3_HOURS = 7,
TIME_6_HOURS = 8,
TIME_12_HOURS = 9,
TIME_24_HOURS = 10,
}alarm_count_reset_mode;
Note: only permissive names can be changed, iii=1.
Modbus:
Read/Write Register=2521, Len=1, 16-Bit Integer (lllll)
Read/Write Register=2522, Len=15, Characters (sssssssssssssss)
Note: Up to 15 UTF-8 bytes to represent a max of 10 characters.
Read/Write Register=2537, Len=1, 16-Bit Integer (ccccc)
Read/Write Register=2538, Len=1, 16-Bit Integer (ppppp)
Read/Write Register=2539, Len=1, 16-Bit Integer (rrrrr)
7.2.26 712 - METER ALARM MESSAGES
R712iii =>

0?0712iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr

92

Chapter 7 Register Operations

Note:

U712iiilllllssssssssssssssssssssssssssssss =>
0?0
U712iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
Where:
iii = Alarm Index with defaults as:
struct alarm_def factory_meter_alarm[16] =
{
{"*MTR FCM" , AUTO_CLEAR}, // 712000
{"*MTR PERM" , AUTO_CLEAR}, // 712001
{"*FCM CONF" , REMOTE_CLEAR}, // 712002
{"*FCM WDT" , REMOTE_CLEAR}, // 712003
{"*FCM TMOUT", REMOTE_CLEAR}, // 712004
{"*VALVE FLT", PROGRAM_CLEAR}, // 712005
{"*LOW FLOW" , DRIVER_CLEAR}, // 712006
{"*EXCESS FL", REMOTE_CLEAR}, // 712007
{"*QUAD ENC" , REMOTE_CLEAR}, // 712008
{"*FCM PERM" , DRIVER_CLEAR}, // 712009
{"*RTD ERROR", REMOTE_CLEAR}, // 712010
{"*VALVE CTL", REMOTE_CLEAR}, // 712011
{"*MTR CREEP", REMOTE_CLEAR}, // 712012
{"*PRES ALRM", REMOTE_CLEAR}, // 712013
{"*QUAD CH A", REMOTE_CLEAR}, // 712014
{"*QUAD CH B", REMOTE_CLEAR} // 712015
};
For Modbus, the Modbus Meter Alarm Index Register sets the iii index.
Modbus: Read/Write Register=2540, Len=1, 16-Bit Integer (iii)
lll = Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}alarm_level;
ssssssssssssssssssssssssssssss = Alarm Message (prefix with an *)
Note: Up to 30 UTF-8 bytes to represent a max of 10 characters.
ccccc = Promotion Count (00000=no promotion)
ppppp = Promoted Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4

93

=>

0?0

Chapter 7 Register Operations

94

}promoted_alarm_level;
rrrrr = Reset Mode as:
enum
{
AUTH_TRANS = 0,
CLEAR_PROMOTED = 1,
TIME_2_MIN = 2,
TIME_5_MIN = 3,
TIME_15_MIN = 4,
TIME_30_MIN = 5,
TIME_60_MIN = 6,
TIME_3_HOURS = 7,
TIME_6_HOURS = 8,
TIME_12_HOURS = 9,
TIME_24_HOURS = 10,
}alarm_count_reset_mode;
Note: only permissive names can be changed, iii=1.
Modbus:
Read/Write Register=2541, Len=1, 16-Bit Integer (lllll)
Read/Write Register=2542, Len=15, Characters (sssssssssssssss)
Note: Up to 15 UTF-8 bytes to represent a max of 10 characters.
Read/Write Register=2557, Len=1, 16-Bit Integer (ccccc)
Read/Write Register=2558, Len=1, 16-Bit Integer (ppppp)
Read/Write Register=2559, Len=1, 16-Bit Integer (rrrrr)
7.2.27 713 - COMPONENT ALARM MESSAGES
R713iii =>
0?0713iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
U713iiilllllssssssssssssssssssssssssssssss =>
0?0
U713iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
=>
Where:
iii = Alarm Index with defaults as:
struct alarm_def factory_component_alarm[16] =
{
{"*COMP FCM" , AUTO_CLEAR}, // 713000
{"*COMP PERM", AUTO_CLEAR}, // 713001
{"*BLK VALVE", AUTO_CLEAR}, // 713002
{"*UNAUTH FL", REMOTE_CLEAR}, // 713003
{"*PUMP STAT", DRIVER_CLEAR}, // 713004
{"*MTR ALARM", AUTO_CLEAR}, // 713005
{"*OVR BLEND", DRIVER_CLEAR}, // 713006
{"*UND BLEND", DRIVER_CLEAR}, // 713007
{"*API TABLE", DRIVER_CLEAR}, // 713008
{"*DENSITY ", REMOTE_CLEAR}, // 713009
{"*CALARM 10", DRIVER_CLEAR}, // 713010
{"*CALARM 11", DRIVER_CLEAR}, // 713011

0?0

Chapter 7 Register Operations

95

{"*CALARM 12", DRIVER_CLEAR}, // 713012


{"*CALARM 13", DRIVER_CLEAR}, // 713013
{"*CALARM 14", DRIVER_CLEAR}, // 713014
{"*CALARM 15", DRIVER_CLEAR} // 713015
Note:

};
For Modbus, the Modbus Component Alarm Index Register sets the iii index.
Modbus: Read/Write Register=2560, Len=1, 16-Bit Integer (iii)
lll = Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}alarm_level;
ssssssssssssssssssssssssssssss = Alarm Message (prefix with an *)
Note: Up to 30 UTF-8 bytes to represent a max of 10 characters.
ccccc = Promotion Count (00000=no promotion)
ppppp = Promoted Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}promoted_alarm_level;
rrrrr = Reset Mode as:
enum
{
AUTH_TRANS = 0,
CLEAR_PROMOTED = 1,
TIME_2_MIN = 2,
TIME_5_MIN = 3,
TIME_15_MIN = 4,
TIME_30_MIN = 5,
TIME_60_MIN = 6,
TIME_3_HOURS = 7,
TIME_6_HOURS = 8,
TIME_12_HOURS = 9,
TIME_24_HOURS = 10,
}alarm_count_reset_mode;
Note: only permissive names can be changed, iii=1.
Modbus:

Chapter 7 Register Operations

96

Read/Write Register=2561, Len=1, 16-Bit Integer (lllll)


Read/Write Register=2562, Len=15, Characters (sssssssssssssss)
Note: Up to 15 UTF-8 bytes to represent a max of 10 characters.
Read/Write Register=2577, Len=1, 16-Bit Integer (ccccc)
Read/Write Register=2578, Len=1, 16-Bit Integer (ppppp)
Read/Write Register=2579, Len=1, 16-Bit Integer (rrrrr)
7.2.28 714 - ADDITIVE ALARM MESSAGES

Note:

R714iii =>
0?0710iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
U714iiilllllssssssssssssssssssssssssssssss =>
0?0
U714iiilllllsssssssssssssssssssssssssssssscccccppppprrrrr
=>
Where:
iii = Alarm Index with defaults as:
struct alarm_def factory_additive_alarm[16] =
{
{"*ADTV FCM" , AUTO_CLEAR}, // 714000
{"*ADTV PREM", AUTO_CLEAR}, // 714001
{"*UND ADTV" , REMOTE_CLEAR}, // 714002
{"*OVR ADTV" , REMOTE_CLEAR}, // 714003
{"*VALVE FLT", PROGRAM_CLEAR}, // 714004
{"*PUMP STAT", DRIVER_CLEAR}, // 714005
{"*INJCT FLT", DRIVER_CLEAR}, // 714006
{"*UNAUTH FL", REMOTE_CLEAR}, // 714007
{"*NO LNFLSH", DRIVER_CLEAR}, // 714008
{"*MTR CREEP", REMOTE_CLEAR}, // 714009
{"*BLK VALVE", AUTO_CLEAR}, // 714010
{"*AALARM 11", DRIVER_CLEAR}, // 714011
{"*AALARM 12", DRIVER_CLEAR}, // 714012
{"*AALARM 13", DRIVER_CLEAR}, // 714013
{"*AALARM 14", DRIVER_CLEAR}, // 714014
{"*AALARM 15", DRIVER_CLEAR} // 714015
};
For Modbus, the Modbus Additive Alarm Index Register sets the iii index.
Modbus: Read/Write Register=2580, Len=1, 16-Bit Integer (iii)
lll = Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}alarm_level;
ssssssssssssssssssssssssssssss = Alarm Message (prefix with an *)

0?0

Chapter 7 Register Operations

Note: Up to 30 UTF-8 bytes to represent a max of 10 characters.


ccccc = Promotion Count (00000=no promotion)
ppppp = Promoted Alarm Level as:
enum
{
AUTO_CLEAR = 0,
DRIVER_CLEAR = 1,
REMOTE_CLEAR = 2,
PROGRAM_CLEAR = 3,
WM_CLEAR = 4
}promoted_alarm_level;
rrrrr = Reset Mode as:
enum
{
AUTH_TRANS = 0,
CLEAR_PROMOTED = 1,
TIME_2_MIN = 2,
TIME_5_MIN = 3,
TIME_15_MIN = 4,
TIME_30_MIN = 5,
TIME_60_MIN = 6,
TIME_3_HOURS = 7,
TIME_6_HOURS = 8,
TIME_12_HOURS = 9,
TIME_24_HOURS = 10,
}alarm_count_reset_mode;
Note: only permissive names can be changed, iii=1.
Modbus:
Read/Write Register=2581, Len=1, 16-Bit Integer (lllll)
Read/Write Register=2582, Len=15, Characters (sssssssssssssss)
Note: Up to 15 UTF-8 bytes to represent a max of 10 characters.
Read/Write Register=2597, Len=1, 16-Bit Integer (ccccc)
Read/Write Register=2598, Len=1, 16-Bit Integer (ppppp)
Read/Write Register=2599, Len=1, 16-Bit Integer (rrrrr)
7.2.29 910 READ EVENT LOG MESSAGE QUEUE
R910 =>
0?0910 OR 0?0910ccyymmddhhmmss.
Where: (when a message is pending, see logmsg_queued bit on Q command)
cc = Number of messages remaining in the queue (00-99)
yymmdd = Year, Month, and Day of log message
hhmmss = Hour, Minute, and Second of log message
. = Text of log message (max length 80 characters)
Modbus:
Read Only Register=2600, Len=2, 32-Bit Integer (cc)
Read Only Register=2602, Len=2, 32-Bit Integer (yymmdd)

97

Chapter 7 Register Operations

Read Only Register=2604, Len=2, 32-Bit Integer (hhmmss)


Read Only Register=2606, Len=80, Characters (ssssssssss)
Note: Last Event Log Message Queue register used=2685
7.2.30 912 READ W & M CHANGE LOG MESSAGE QUEUE
R912 =>
0?0912 OR 0?0912tttccccyymmddhhmm.
Where: (when a message is pending, see wm_logmsg_queued bit on Q command)
ttt = TMS W&M change type (proprietary, do not use)
10 = Temp Offset Change
12 = Transmitter Resolution Change
0 = All Others Changes
cccc = Number of messages remaining in the queue (0000-0999)
yymmdd = Year, Month, and Day of log message
hhmm = Hour and Minute of log message
. = Text of log message
Modbus:
Supported through Modbus Extended Services Registers.
7.2.31 950 - CURRENT DRIVER CARD NUMBER
In Remote Processing mode, to be populated by host and will be stored with transaction.
In Stand Alone Processing mode, will be populated with user supplied data.
R950 =>
0?0950sss
U950sss
=>
0?0
Where:
sss = Driver card number.
Modbus:
Read/Write Register=2700, Len=25, Characters (sss)
7.2.32 951..954 - CURRENT DRIVER PROMPT INFORMATION
(Stockholder, Customer, Account, Consignee)
In Remote Processing mode, to be populated by host and will be stored with transaction.
In Stand Alone Processing mode, will be populated with user supplied data.
R951 =>
0?0951sss
U951sss
=>
0?0
Where:
sss = Driver Prompt Data for Stored BOL
Modbus:
Read/Write Register=2725, Len=25, Characters (951-sss)
Read/Write Register=2750, Len=25, Characters (952-sss)
Read/Write Register=2775, Len=25, Characters (953-sss)
Read/Write Register=2800, Len=25, Characters (954-sss)
7.2.33 960 INPUT DATA
R960

=>

0?0960sss

98

Chapter 7 Register Operations

Where:
sss = Input data string from the Terminal Escape Code `E.
Modbus:
Read Only Register=2851, Len=25, Characters (sss)
7.2.34 961 INPUT DATA TERMINATING KEY
R961 =>
0?0961c
Where:
C = Terminating Key from the Terminal Escape Code `E
A = Next
B = Prev
C = Abort/Exit
D = Enter
E = CLR
Modbus:
Read Only Register=2850, Len=1, Character (c)
7.2.35 962 - CURRENT DRIVER CARD DATA
R962 =>
0?0962sss
Where:
sss = Driver card data string.
For HID 26-bit Prox Cards,
0=yy=0000000=xxxxxxxx=01 Card number that was read from the card.
Where:
yy is the facility number (00-99)
xxxxxxxx is the card number (00000000-00065535).
For HID 26-bit Corporate 1000 Formatted Prox Cards,
0=yyyy=00000=xxxxxxxx=01 Card number that was read from the card.
Where:
yyyy is the company number (0000-4095)
xxxxxxxx is the card number (00000000-01048575).
For HID 37-bit H10320 formatted Prox cards,
0=yy=0000000=xxxxxxxx=01 Card number that was read from the card.
Where:
yy is the facility number (Always 00).
xxxxxxxx is the card number (00000000-99999999).
For TWIC cards,
1111,2222,333333,4,5,6666666666788889 TWIC Card FASC-N that was read from the card.
Where,
1111 = Agency Code
2222 = System Code
333333 = Credential Number

99

Chapter 7 Register Operations

4 = Credential Series
5 = Individual Credential Issue
6666666666 = Person Identifier (Used as Card Number in Access ID Database)
7 = Organizational Category
8888 = Organizational Identifier
9 = Person/Organization Association
Modbus:
Read Only Register=2900, Len=80, Characters (sss)

100

Chapter 7 Register Operations

7.2.36 998 BITMAP GRAPHIC CACHE


R998aaaaaaaa =>
0?0998aaaaaaaad
Where:
aaaaaaaa = 8 character hexadecimal cache offset start value.
Cache size = 16MB, Cache offset values = 0x00000000 - 0x00ffffff
Two pixels per cache byte.
Note: Graphics Cache is in volatile memory. On power cycle, entire Graphics Cache will be
populated with 0s (spaces) for pixel data. Use R998 command to verify cache has not been cleared.
Note: Graphics Cache memory is also used for temporary storage of uploaded firmware images
before writing into flash memory. Do not use the R998, W998 or T<esc>h (Display Graphic Cache)
commands while uploading or flashing new firmware.
d = 64 (characters) 0x20 + pixel color palette index values,
See T<esc>e (Draw Display Graphic) command for more details on pixel data.
W998aaaaaaaad
=>
998
Where:
aaaaaaaa = 8 character hexadecimal cache offset start value.
See R998 command for more details on cache offset.
d = even number of (characters) 0x20 + pixel color palette index values,
See T<esc>e (Draw Display Graphic) command for more details on pixel data.
Modbus:
Supported through Modbus Extended Services Registers.

101

Chapter 8 Communication Trace Example

CHAPTER 8

COMMUNICATION TRACE EXAMPLE

The following is an example of a typical communication session with MultiLoad starting with host system
startup, driver card in, transaction authorization, batch authorization, end of batch processing, and host system
shutdown.
Upon startup it is recommended that the host system verify as many parameters as practical to avoid
problems during loading due to mis-configuration. If any parameters are different then expected the
discrepancy should be logged and startup should be aborted. Recommended parameters to check are:
Firmware Version
Configured bit is set.
Remote Processing is enabled.
Number of configured presets.
Number of meters, components and additives for all presets.

8.1

STARTUP OF HOST SOFTWARE

8.1.1

UPDATE DATE & TIME

Sent:(U001010515153200) Received: (000)


Modbus:
Fn=0x16, Write (YYMMDDHHMMSS) to Registers 35 46
8.1.2

UPDATE PRODUCT DEFINITIONS

Start with a clear database and upload base product and additive definitions into indexes 020-099
Sent:(FCLEARPROD) Received: (000)
Sent:(U5000200001100Regular Unlead
RUL
02010000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000210001300Premium Unlead
PUL
02110000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000220000600Chevron Additive
CHEVADD
02210000000000000000000000000000000000000000000000000000000000000210000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000230000700Shell Additive
SHEADD
02310000000000000000000000000000000000000000000000000000000000000220000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000240000800Generic Additive
GENADD
02410000000000000000000000000000000000000000000000000000000000000230000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000250000300Base Kerosene
KERO
02510000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000260001400Base Low Sulfur Diesel BASLSD
02610000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)

102

Chapter 8 Communication Trace Example

Sent:(U5000270000900Red Dye
REDDYE
02710000000000000000000000000000000000000000000000000000000000000260000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000280000500Winter Additive
WINADD
02810000000000000000000000000000000000000000000000000000000000000270000000000000000000000
00000000000000000000000) Received: (000)
Modbus:
For each recipe:
Fn=0x06, Write Recipe Index to Register 2200
Fn=0x16, Write Recipe Data to Registers 2201 2267
(both writes can be done at the same time with one Fn=0x16 command)
8.1.3

UPDATE PRESET DEFINITIONS

Sent:(U400000BLENDER
02002100000000000000000002202302400000000000000000000000000000000000000002002102202302400
0000000000000000000000000000000000000000000000000000000000000000000000000000000000)
Received: (000)
Sent:(U400001BLENDER
02002100000000000000000002202300000000000000000000000000000000000000000002002102202300000
0000000000000000000000000000000000000000000000000000000000000000000000000000000000)
Received: (000)
Sent:(U400002LSD
02000000000000000000000002200000000000000000000000000000000000000000000002002200000000000
0000000000000000000000000000000000000000000000000000000000000000000000000000000000)
Received: (000)
Sent:(U400003HSD
02500000000000000000000000000000000000000000000000000000000000000000000002500000000000000
0000000000000000000000000000000000000000000000000000000000000000000000000000000000)
Received: (000)
Sent:(U400004KEROSENE
02600000000000000000000002700000000000000000000000000000000000000000000002602702800000000
0000000000000000000000000000000000000000000000000000000000000000000000000000000000)
Received: (000)
Modbus:
Fn=0x16, Write Preset Data to Registers 8000 8066
Fn=0x16, Write Preset Data to Registers 8067 8133
Fn=0x16, Write Preset Data to Registers 8134 8200
Fn=0x16, Write Preset Data to Registers 8201 8267
Fn=0x16, Write Preset Data to Registers 8268 8334

8.1.4

STATUS QUERY

Periodically query the status of MultiLoad by issuing the following command.


This command also provides indication to MultiLoad that the host is still up.
Sent:(Q) Received: (0000038)
From the Q response, when needed send the following commands:
power_up bit is set
Modbus:
Fn=0x03, Read Register 7000

103

Chapter 8 Communication Trace Example

Sent:(FPOWERUP) Received:(000)
logmsg_queued bit is set
Modbus:
Fn=0x06, Write 0 to Register 7012
Sent:(R910) Received: (00091000010515153200REGAINED COMMUNICATION WITH HOST.)
host_up bit is clear
Modbus:
Fn=0x03, Read Registers 2600 ... 2685
Sent:(FHOSTUP) Received: (000)
Modbus:
Fn=0x06, Write 0 to Register 7013

8.2

TRANSACTION AUTHORIZATION

8.2.1

PROCESS DRIVER CARD IN

Reset terminal screen.


Sent:(T_R) Received: (000)
Modbus:
Fn=0x06, Write 0 to Register 7017
Wait for card in by watching the CARD_STATUS character
Sent:(Q) Received: (000C218)
Sent:(Q) Received: (000C218)
...(some time later)...
Sent:(Q) Received: (041C218)
Modbus:
Fn=0x03, Read Register 7001 -> 0
Fn=0x03, Read Register 7001 -> 0
...(some time later)...
Fn=0x03, Read Register 7001 -> 1
Get the card number
Sent:(R962) Received: (0419620=01=0000000=00004504=01)
Modbus:
Fn=0x03, Read Registers 2900 2979
Prompt for Driver PIN
Sent:(T_H_K_>Enter Pin: _!_L04_E) Received: (041)
Modbus:
Use Extended Services Register
Wait for driver input_done bit to be set
Sent:(Q) Received: (041C618)

104

Chapter 8 Communication Trace Example

...(some time later)...


Sent:(Q) Received: (041CA18)
Modbus:
Fn=0x03, Read Register 7002 -> (0xC61A)
...(some time later)...
Fn=0x03, Read Register 7002 -> (0xCA1A)
Get driver input and terminating key
Sent:(R960) Received: (0419601111)
Sent:(R961) Received: (041961D)
Modbus:
Fn=0x03, Read Registers 2850 ... 2875
8.2.2

AUTHORIZE A TRANSACTION ON MULTILOAD

Authorize transaction on Multiload

Sent:(T_A) Received: (0T1)


Modbus:
Fn=0x06, Write 0 to Register 7016
Enable available presets
Sent:(MEM0002) Received: (0T1)
Sent:(MEM0012) Received: (0T1)
Sent:(MEM0022) Received: (0T1)
Modbus:
Fn=0x06, Write 2 to Register 7032
Fn=0x06, Write 2 to Register 7033
Fn=0x06, Write 2 to Register 7034
Upload the driver number and any other additional information to be included with stored BOL in Multiload
Sent:(U95000004504) Received: (0T1)
Sent:(U9510001234) Received: (0T1)
Sent:(U952
) Received: (0T1)
Sent:(U953
) Received: (0T1)
Sent:(U954
) Received: (0T1)
Modbus:
Fn=0x16, Write data to Registers 2700 2724
Fn=0x16, Write data to Registers 2725 2749
Fn=0x16, Write data to Registers 2750 2774
Fn=0x16, Write data to Registers 2775 2799
Fn=0x16, Write data to Registers 2800 2824
8.2.3

READING TOTALIZERS

Sent:(R112000) Received:
(0001120000000010000000010000000000000000000000000000000000010000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000

105

Chapter 8 Communication Trace Example

00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
0000)
Sent:(R112001) Received:
(0001120010000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
0000)
Sent:(R112002) Received:
(0001120020000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
0000)
Sent:(R112003) Received:
(0001120030000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
0000)
Sent:(R112004) Received:
(0001120040000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
0000)
Modbus:
Fn=0x03, Read Registers 3000 3006 (Preset Gross Totalizers)
Fn=0x03, Read Registers 3144 3191 (Component Gross Totalizers)
Fn=0x03, Read Registers 3336 3432 (Additive Gross Totalizers)
Etc

8.3

BATCH AUTHORIZATION

8.3.1

AUTHORIZE A BATCH ON MULTILOAD

Checking status found a preset authorization request for a preset.


Sent:(Q) Received: (0a1CA1A)
Modbus:
Fn=0x03, Read Register 7000 -> a
Prompt driver for batch information.
Display available product names
Sent:(T_H_K_Y! 1. Regular Unlead_Y 2. Premium Unlead) Received: (0a1)
Modbus:
Use Extended Services Register
Prompt for product name
Sent:(T_H_>Enter Preset #01 Product Code: _@ _L02_E) Received: (0a1)
Modbus:
Use Extended Services Register
Wait for driver input done

106

Chapter 8 Communication Trace Example

Sent:(Q) Received: (0a1C61A)


...(some time later)...
Sent:(Q) Received: (0a1CA1A)
Modbus:
Fn=0x03, Read Register 7002 -> (0xC61A)
...(some time later)...
Fn=0x03, Read Register 7002 -> (0xCA1A)
Get driver input and terminating key
Sent:(R960) Received: (0a19601 )
Sent:(R961) Received: (0a1961D)
Modbus:
Fn=0x03, Read Registers 2850 ... 2875
Prompt for preset quantity
Sent:(T_H_K_>Enter Preset #01 Qty: _@_L06_E) Received: (0a1)
Modbus:
Use Extended Services Register
Wait for driver input done
Sent:(Q) Received: (0a1C61A)
...(some time later)...
Sent:(Q) Received: (0a1CA1A)
Modbus:
Fn=0x03, Read Register 7002 -> (0xC61A)
...(some time later)...
Fn=0x03, Read Register 7002 -> (0xCA1A)
Get driver input and terminating key
Sent:(R960) Received: (0a19601000 )
Sent:(R961) Received: (0a1961D)
Modbus:
Fn=0x03, Read Registers 2850 ... 2875
Upload selected recipe definitions into index in range of 001-019 (recommend using preset number as index).
Sent:(U5000010001100Regular Unlead
RUL
02010000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (0a1)
Modbus:
Fn=0x06, Write Index 1 to Register 2200
Fn=0x16, Write Recipe Data to Registers 2201 2267
Authorize preset for batch indicating volume and recipe definition index.
Sent:(MAM000100100000100000) Received: (0T1)
Modbus:
Fn=0x16, Write Authorization Data (1, 0, 1000, 1, 1) to Registers 7500 7504

107

Chapter 8 Communication Trace Example

Status no longer request for remote authoriziation


Sent:(Q) Received: (0T1CA3A)
Modbus:
Fn=0x03, Read Register 7000 -> T
8.3.2

MONITOR LOAD DURING DELIVERY

Sent:(MRS000) Received:
(0T1RS0000001001F0000000001000000000015+0022400113000000015+00224000000000+0000000000000
0+00000000000000+00000000000000+00000000000000+00000000000000+00000000000000+000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
000000000000000000000000000000000000000000000000)
Sent:(MRS001) Received:
(0T1RS001000000070000000000000000000000+0000000000000000000+00000000000000+0000000000000
0+00000000000000+00000000000000+00000000000000+00000000000000+00000000000000+000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
000000000000000000000000000000000000000000000000)
Sent:(MRS002) Received:
(0T1RS002000000070000000000000000000000+0000000000000000000+00000000000000+0000000000000
0+00000000000000+00000000000000+00000000000000+00000000000000+00000000000000+000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
000000000000000000000000000000000000000000000000)
Sent:(MRS003) Received:
(0T1RS003000900030000000000000000000000+0000000000000000000+00000000000000+0000000000000
0+00000000000000+00000000000000+00000000000000+00000000000000+00000000000000+000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
000000000000000000000000000000000000000000000000)
Sent:(MRS004) Received:
(0T1RS004000900030000000000000000000000+0000000000000000000+00000000000000+0000000000000
0+00000000000000+00000000000000+00000000000000+00000000000000+00000000000000+000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
000000000000000000000000000000000000000000000000)
Modbus:
Fn=0x03, Read Registers 4060 4067 (Preset Gross Volumes)
Fn=0x03, Read Registers 4084 4091 (Preset Net Volumes)
Etc

8.4

END OF BATCH PROCESSING

8.4.1

ENDING A BATCH ON MULTILOAD

End Batch request can come from MultiLoad (Driver Clears Batch or Card Pull) or from the Host with a MBE
command.
Wait until preset state is PRESET_END_OF_BATCH and pick up totals (with MRS) and/or totalizers.
Sent:(MRS000) Received:
(0T1RS000001107970000000001000000001000+0022400000000001000+00224000000000+0000000000000
0+00000000000000+00000000000000+00000000000000+00000000000000+00000000000000+000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000
000000000000000000000000000000000000000000000000)
Modbus:
Fn=0x03, Read Registers 4060 4067 (Preset Gross Volumes)

108

Chapter 8 Communication Trace Example

Fn=0x03, Read Registers 4084 4091 (Preset Net Volumes)


Etc
Send end batch command to allow MultiLoad to clear batch totals.
Sent:(MEB000) Received: (0T1)
Modbus:
Fn=0x06, Write Register 7069
When preset state returns to PRESET_IDLE, prompting for next batch can begin again.

8.5

END OF TRANSACTION PROCESSING

8.5.1

ENDING A TRANSACTION ON MULTILOAD

A transaction can be ended by MultiLoad (Driver pulls card) or from the Host with a MET command
End of transaction processing started when RCU state changes to COMPLETING_LOAD.
Sent:(Q) Received: (0C0C23B)
Modbus:
Fn=0x03, Read Register 7000
And uncleared batched will be set to end batch waiting for the host to acknowledge with a MEB command to
clear totals.
When all presets have been cleared, RCU status will go to TRANSACTION_DONE.
Sent:(Q) Received: (0D0C238)
Modbus:
Fn=0x03, Read Register 7000
Reset display to reset RCU status back to idle.
Sent:(T_R) Received: (000)
Modbus:
Fn=0x06, Write 0 to Register 7017

8.6

SHUTDOWN OF HOST SOFTWARE

Sent:(FHOSTDOWN) Received: (000)


Modbus:
Fn=0x03, Write 0 to Register 7014

109

Chapter 9 Data Communication Notes and Recommendations

CHAPTER 9

DATA COMMUNICATION NOTES AND RECOMMENDATIONS

This topic provides some basic communications concepts, as well as Toptech's recommendations for achieving
optimum performance.

9.1

PROTOCOL SELECTION: RS-232 VS. RS-485

9.1.1

RS-232

RS-232 communications protocol was designed for point-to-point (i.e., computer to a single device)
communications for short distances. The actual specification for RS-232 distance is limited to 50 feet. In
practice, however, RS-232 communications can be successful at distances over 1000 feet. We generally try to
limit distances to 500-600 feet. RS-232 requires a minimum of 3 wires: Transmit, Receive and Signal ground
wires. More wires are required for hardware handshaking. RS-232 can work on straight, non twisted-pair wiring.
If existing wiring that is not twisted-pair must be used, then RS-232 protocol should be used.
9.1.2

RS-485

RS-485 communications protocol was designed for multi-point (i.e., computer to multiple devices, also called
multi-dropped) communications and can support distances over 5,000 feet. RS-485 requires 4 wires (2 twistedpair) for normal full-duplex communications. With special hardware, 2-wire half-duplex RS-485 can be
accomplished. RS-485 utilizes a transmit pair of wires (TDA and TDB) and a receive pair of wires (RDA and
RDB). A ground wire is not recommended normally, although some devices may have a terminal block for an
RS-485 ground. Most multi-dropped devices require RS-485 communications. When installing new wiring, RS485 twisted-pair wiring is preferred.

9.2

CABLE SELECTION

The speed and distance of communications is mostly affected by the capacitance and resistance of the wiring.
Copper wiring is generally low resistance, so this is not normally the limiting factor. Capacitance, however, can
vary greatly from one type of wire to another. In general, the larger the wire, the higher the capacitance. Wiring
size of 20 to 24 gauge is typically best for data communications. Capacitance of 16pf or less is preferred. With
16pf cable, 9600 baud communications can operate over 1000 feet for RS-232, and over 5000 feet for RS-485.
Doubling the capacitance will generally halve the baud rate or the distance.
Data communications cable should always be shielded. Individual wires or pairs do not need shielding, but an
overall shield should always be used. Whenever possible, always run data communications cable in conduit
and protected from moisture. Moisture can invade most cable coatings and disrupt data communications
integrity. For exposed routing or direct burial, Teflon coatings are recommended. Armored cable is also
available for running over-head without conduit.
RS-232 communications will work over almost any type of wiring, although speed and distance may be limited
by some wiring. Straight (individual) wires or twisted-pair wiring can be used. RS-485 communications requires
twisted-pair wiring with an impedance of 100 ohms.
For new installations, if you select wiring suitable for RS-485 wiring, it will always work for RS-232. This will
provide the ability to change from one communications protocol to another without replacing the wiring.

9.3

LINE TERMINATION IN MULTI-DROPPED COMMUNICATIONS

Toptech Systems has specialized hardware that will support multi-dropping of devices on a single RS-232
communication line. This is accomplished by tri-stating or disconnecting the transmitter of a device when it is
not transmitting on the communications line. This is similar to the RS-485 multi-dropping method. Due to the
tri-stating of the transmitters, the transmit circuit is 'floating' when no device is transmitting. This can sometimes
cause problems for the computer's receiver circuit, usually framing errors or break conditions.

110

Chapter 9 Data Communication Notes and Recommendations

To keep these problems under control, multi-dropped lines need line termination resistors installed. This can be
installed on the receiver of the line driver for the line. For RS-232 communications, a 500 to 1000 ohm resistor
is placed between the receive (RD) and signal ground (SG) wires of the line driver for the line. For RS-485
communications, a 220 to 270 ohm resistor is placed between the receive pair (RDA and RDB) wires of the line
driver for the line. Termination resistors actually weaken the driver's ability to transmit; therefore, when longer
lines are used or many devices are multi-dropped, the higher resistor values must be used. Unfortunately, the
proper value must sometimes be determined by experimentation. For RS-232, the resistor value must be large
enough to allow the transmitter to drive the voltage levels to at least +3VDC and -3VDC. For RS-485, the
resistor value must be large enough to allow the transmitter to produce a .25 VDC difference in the transmit pair,
but not large enough to disrupt the balance of the line. Too low of a resistor value will typically cause a short on
the data communications line and inhibit communications.
Please note that in RS-485 communications specifications, you will find that 100 ohm termination resistors are
recommended. This is a different type of line termination than what we are discussing here. The 100 ohm
termination is specifically for line balancing and is typically not required for baud rates less then 38,000 baud.
This is well above most PC data communications capabilities.

9.4

OPTICAL ISOLATION

Due to the major power fluctuations that may occur in an industrial environment and the effect of lightning
storms in an area with lots of piping, we recommend that any data communications line connecting devices
powered from different AC circuits be protected with optical isolation devices. The RS-232 to RS-485
converters that Toptech supplies provide this isolation. We also provide an RS-232 optical isolation device for
RS-232 lines. Similar devices are available from Black Box Corporation and Burr-Brown. One isolation device
must be installed on each data communications line. This is different from line drivers or short-haul modems
that require a device on each end.
Please note that any line termination used must be installed on the field side of the optical isolator. Also, optical
isolators are directional, which means that one side is for the computer (DCE) and the other side is for the field
equipment (DTE). They will not transmit data if installed backwards!

9.5

SHIELD GROUNDING

Due to all of the electrical noise generated by an industrial environment, all data communications cable must be
properly shielded. If not properly shielded, communications may work for a while, but you will most probably
experience intermittent communications errors and outages. Most data communications cable comes with good
shielding built in, but if not properly installed, the shielding will be ineffective. Proper installation requires that
the shield be attached to earth ground on ONE END ONLY, typically at the junction box on the computer end,
and MUST BE CONTINUOUS through all junction boxes out to the field equipment. In addition, the shield
should be taped back at each field device and should NEVER be connected to a field device. Unfortunately,
several of the field device manufacturers have terminal blocks labeled for attachment of the shield, and many of
their installation drawings indicate that the shield should be attached to the field devices. Under no
circumstances should the shield ever be attached to a field device!
When connecting through a junction box, care must be taken that the shields be treated just like any other wire.
The shield must remain continuous across the junction box. Don't tie multiple shields together. Route each
shield across the junction box, making sure that it does not short to the box or any other point. Inside of a
junction box, wires are typically unshielded. If a junction box is installed in an electrically noisy area, near
motors, etc., the junction box must be able to provide shielding. Also, AC wiring should not be run into a
junction box that has unshielded data communications wiring. Especially, AC circuits with loads that are
switching off and on or that have a high current flow must be avoided. These will introduce noise into the data
communications lines inside of the junction box.

111