Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
I. INTRODUCTION
Since the invention of differential schemes, current
transformer (CT) saturation has been one of the main
problems for differential transformer protection. CT saturation
leads to inaccurate measurement of primary currents that may
cause relay malfunction. Saturation also increases current
measurement error that creates a false differential current. It is
impossible to predict or even estimate this error due to the
unpredictable nature of CT saturation (many factors such as
fault level, fault inception angle, system configuration, CT
remanence etc. affect level of saturation and measurement
error). This false spill current may cause spurious relay
operation under through-faults.
Over the years, relay manufacturers have used various
methods to deal with this problem. Dual bias slopes are
commonly used to restrain relays from tripping under CT
saturation. Some studies on CT saturation effects on older
style relays were done in the past [1], [2], but very few on new
digital relays [3], [4]. These studies usually focus attention on
Manuscript received 13/3/2014. Materials and equipment used for this
work were supplied by Ausgrid.
Michael Stanbury is a protection engineer with Ausgrid, Sydney, NSW,
Australia (e-mail: michael.stanbury@gmail.com).
Zarko Djekic is a senior protection engineer with Ausgrid, Sydney, NSW,
Australia (e-mail: ZDjekic@ausgrid.com.au).
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
HV CT
LV CT
Zs
HV CT
HV CT
LV CT
LV CT
Rf
In-zone
Fault
Fig. 1. Primary system model showing an in-zone fault with three parallel
transformers.
A. Relay Testing
To observe relay behavior, secondary fault current
waveforms were generated using the described primary system
and CT models. Various fault types were simulated including
3 phase, 2 phase and line to ground faults. Both in-zone and
through-faults on the low side of the transformer were
simulated. For each type of fault, several levels of CT
saturation were simulated by varying the remanence. The level
of saturation varied from no saturation to maximum possible
saturation. A total of 46 faults were injected into each of the
three relays.
The three relays chosen were modern numerical transformer
differential relays (here called Black6, Blue4 and Blue7).
They were each set for 132/11 kV, YNyn transformers. Slope
1 was set to the manufacturers recommended values. Slope 2
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
was set very low - about the same as slope 1 - to test whether
harmonic blocking would provide security during throughfaults with CT saturation. (On Black6, a low slope 2 was
achieved by setting breakpoint 2 to its maximum value of 30
per unit.)
Both the recorded and simulated secondary current
waveforms were injected into the three relays using the
Omicron CMC 356 test set. The relays were wired in series so
the same injected current flowed through each simultaneously.
Oscillographic fault records were downloaded from each relay
for analysis.
Using the fault records, relay state values were observed,
paying particular attention to the time just after saturation
begins (when it is most severe). This is the most difficult time
for the relay to distinguish in-zone and through-faults. Relay
state values for each fault were compared to the state values in
the EMTP and VBA relay models for verification.
B. Degree of Saturation
In order to accurately characterize harmonic blocking
behavior under CT saturation, it was necessary to develop a
way to quantify the level of saturation. Here we define the
degree of saturation (1) which was used to investigate relay
blocking behavior for different levels of saturation. It provides
a way to compare the results of different CT models
objectively, and to characterize the blocking behavior of
relays. The degree of saturation is defined as a value between
zero and one such that zero means no saturation, and one
means the CT outputs nothing for one full cycle.
(1)
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
Operate [pu]
Fig. 3. Operate vs restraint plot using the SSM for a 132/11 kV transformer,
protected by a Black6 relay.
1
This is true for relays with a slope 2 that passes through the origin (e.g.
Black6 and Blue4). For relays where slope 2 meets slope 1 at the breakpoint
(e.g. Blue7), slope 2 would need to be well over 100%, the break point would
need to be very low, and even then it may not be possible to prevent nuisance
trips without harmonic blocking or harmonic restraint elements being active.
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
5
Similar behavior was seen when current waveforms from
real CTs undergoing primary injections were used. Fig. 6
shows a situation very similar to Fig. 5, except that the
saturated waveform was recorded from a real CT, rather than a
simulation. The recorded secondary waveform was then
injected into the relays. The blocking behavior is very similar
to Fig. 5, verifying our CT models for this purpose. The
Black6 fault record is shown but Blue7 was similar. Blue4 was
not tested.
Fig. 6. Single phase to earth external fault with light saturation, recorded by
Black6. Secondary currents recorded during high current primary injection
test.
Fig. 5. Single phase to earth external fault with light saturation, as recorded
by Black6 (test E3). Blocked regions shaded gray.
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
7
for any differential protection scheme with harmonic blocking
enabled.
Fig. 10. Single phase to earth, in-zone fault with extremely poor CTs, as
recorded by Black6.
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
saturation. This occurs on lowest transformer tap (lowest ratio
of VHV/VLV). If large enough CTs are used, the unrestrained
element may be able to detect even medium current in-zone
faults (e.g. low side faults without back-feed), allowing very
fast tripping. To determine whether the existing CTs are large
enough, our VBA code can be used. It produces graphs like
Fig. 3 which allow the engineer to visually choose an
unrestrained pickup that maximizes sensitivity without
compromising security during CT saturation. In cases where
CTs are poor, there is a much smaller gap between the in-zone
and external faults on the restraint-operate plane so it will not
be possible to put the horizontal unrestrained line between
them for all transformer taps. Even if the unrestrained pickup
cannot see the majority of low side in-zone faults, setting it in
this way allows it to see many of them. This provides some
redundancy in case the protection engineer sets the restrained
differential incorrectly. A reduced unrestrained pickup may
produce faster tripping for faults during energization when the
restrained element is blocked by large second harmonic
content from inrush currents. Inrush can last for a long period
(seconds) and prevent the relay from tripping even for
maximum faults on the low side of the transformer.
D. Checking the Performance of Existing CTs
The previous sections explained the effect of CT saturation
on modern relay algorithms, and can be used to improve
protection settings with the existing CTs. However, this
method should only be used where the existing CTs have a
certain minimum performance level. This section will describe
how to check whether existing CTs are good enough for the
harmonic blocking method presented here to function as
intended.
Harmonic blocking or harmonic restraint must be enabled to
prevent nuisance trips due to inrush. Simulations and tests
presented here have shown that harmonic blocking is also
activated during CT saturation. If slope 2 is lowered and
harmonic blocking is relied upon to provide security, then
harmonic blocking becomes a constraint on the minimum
performance of differential CTs. In order for this to work
effectively, CTs must not saturate so heavily that blocking is
deactivated during through-faults (see far right of Fig. 14), and
they must not saturate so quickly that they block the restrained
element for in-zone faults before the relay issues a trip
command. It is difficult to directly relate these requirements to
a particular CT specification but the following two rules of
thumb were found to work for our primary system and the
three relays tested:
1) The minimum time to saturation should be longer than
the time for the DC offset to decay to 80% of its
maximum level. This helps to ensure that CTs do not
saturate too heavily.
2) The minimum time to saturation for the highest inzone fault (with the maximum number of transformers
in parallel), must be longer than the time that the relay
needs to trip.
The time to saturation in the above points should be
8
calculated for the worst case. This means the fault has
maximum expected X/R, maximum DC offset and worst case
remanence in the same direction as the DC offset. For our
primary system with a maximum X/R of 50, two cycles of
unsaturated time was found to provide excellent sensitivity
and security, even when slope 2 was set the same as slope 1.
Note that if the existing CTs do not meet the two rules of
thumb above, it is likely that they will perform very poorly in
all transformer differential schemes, not just the method
presented here.
E. Cross Blocking
Many relays provide the option that when one phase blocks
due to harmonics, the other phases are blocked also. This cross
blocking behavior can provide greater security during inrush
and through-faults with CT saturation, however it could create
a great risk during in-zone faults. If the differential CTs have
very poor performance (i.e. if they do not adhere to the two
rules of thumb in section D), it is possible that a CT on one
phase could saturate very quickly and all three restrained
elements are blocked before the relay trips. All restrained
differential elements remain blocked until the last CT comes
out of saturation. On the other hand, if independent blocking is
used, the other two phases can still trip even if the first phase
CT saturates and blocks very quickly. For this reason cross
blocking should not be used where CT performance is poor
(e.g. if time to saturation is less than half a cycle).
VI. CONCLUSION
Traditional wisdom has dictated that a high slope 2 provides
security during through-faults with saturation. This work has
shown that, when enabled, it is actually harmonic blocking
which is providing security and the high slope 2 probably does
not contribute at all because the relay is blocked whenever
saturation occurs. In addition, the high slope 2 may be
reducing sensitivity to some in-zone faults. Slope 2 will only
provide security during saturation if it is set correctly but there
is very little guidance in relay manuals for how to set slope 2
and the break point. The nonlinear nature of CT saturation
makes setting slope 2 and the break point a very challenging
problem, whereas setting harmonic blocking is trivial because
standard settings can be used.
Results have been presented which demonstrate how
modern transformer differential relays behave when CT
saturation occurs by injecting 46 simulated faults into three
relays. A model has been presented which accurately predicts
the blocking and restraint behavior of these relays during
saturation. The results suggest that a high slope 2 may not be
necessary to provide security during through-faults with CT
saturation if harmonic blocking is enabled. This allows slope 2
to be lowered significantly, leading to greater sensitivity for
some internal, turn-to-turn faults. We have introduced the
novel suggestion that many utilities may be unknowingly
relying on harmonic blocking for security whilst thinking that
a high slope 2 was effectively set. These settings would have
suboptimal sensitivity due to the unnecessarily high slope 2. It
is suggested that many utilities could safely lower slope 2 if
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
they are using harmonic blocking because these results apply
very generally.
Besides improving sensitivity, utilities could simplify their
protection setting calculations by relying on harmonic
blocking rather than slope 2 for security. Rather than
performing complex calculations for slope 2 and the break
points, standard values could be used along with a standard
setting for harmonic blocking (typically ~15%). Such
standardization can reduce human error and save time by
allowing standard test shots to be used by technicians. Our
testing indicates that in many cases, slope 2 does not provide
adequate security on its own and harmonic blocking is
required to deal with CT saturation. In some instances where
poor performance CTs are installed, it may not even be
possible to provide adequate security using slope
characteristics alone. Harmonic blocking or harmonic restraint
can be used to achieve this.
Although this research focused on harmonic blocking,
harmonic restraint was also investigated and showed similar
behavior. The harmonic restraint element significantly
contributes to security during external faults with
asymmetrical CT saturation. Harmonic restraint also allows a
significant reduction in slope 2 settings, allowing improved
sensitivity. It seems that the harmonic restraint element may
also delay a trip for internal faults if CTs do not adhere to the
two rules of thumb in Discussion section D. Harmonic
restraint could be an area of further research to verify these
preliminary findings.
Two rules of thumb have been presented which help to
decide whether existing CTs perform well enough to rely on
harmonic blocking for security. This blocking effect has not
been traditionally used to specify CTs but since underspecified
CTs could potentially saturate and block a relay during an inzone fault, this should be a primary consideration for utilities
when specifying a transformer differential CT.
For some relays like Blue4, a high slope 2 does not
necessarily reduce sensitivity because it adaptively changes
between slope 1 and 2 depending whether it has determined
that the fault is inside or out of the zone of protection.
However, even for this relay it seems that slope 2 could be set
quite low because harmonic blocking alone is highly effective
at providing security during through-fault.
In an informal survey we found that very few protection
engineers were aware that asymmetrical CT saturation
activates harmonic blocking in transformer differential relays.
This is unsurprising, given that there is very little reference to
this behavior in relay manuals or the literature. This could be a
missed opportunity to increase sensitivity by lowering slope 2.
Furthermore, it could be potentially dangerous if CTs are
specified incorrectly and early blocking occurs during in-zone
faults. It is hoped that this paper and subsequent research will
convey this important message to the wider protection
community.
9
REFERENCES
[1]
APPENDIX
A. CT Model Details
This section presents the two CT models used to produce
the simulated saturated waveforms. The Simple Step Model
(SSM) [7] acts as an ideal CT until the flux density reaches the
saturation flux level. At this point, the secondary current
instantly drops to zero. A chopped waveform is produced. An
equivalent circuit is shown in Fig. 11.
&
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
(2)
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
open, /0& < < +/0&
,
closed,
+/0& 89: "; > 0
*
( = closed, /0& 89: "; < 0 (3)
+ open, + 89: " 0
/0&
;
*
) open, /0& 89: "; 0
10
Secondary current waveforms were recorded and used to
verify CT models. More detailed verification of EMTP CT
models has been conducted previously [11]. The two CT
models (SSM and EMTP) were also compared to each other.
B. Relay Model Verification
To ensure that our relay model was accurate, we compared
the outputs of the models to the fault records downloaded
from the relays. Fault waveforms were simulated from light to
extreme saturation and injected into the three relays. The fault
waveforms were downloaded to observe the behavior of
harmonic blocking. The predictions of the SSM and relay
models were compared to the downloaded fault records. Note
that the injections into the relays were produced by a different
CT model (nonlinear reactor model) and a different
implementation (EMTP) to the predictor implementation
(SSM and VBA).
Fig. 14 shows how the relays measure the level of second
harmonic in the spill which is used to decide whether to block.
The solid line shows the predictions of the SSM and the data
points are individual through-faults as measured by the three
relays (Black6, Blue4 and Blue7). The dashed line at 15%
shows a typical harmonic blocking relay setting. Values above
the dashed line activate harmonic blocking. Different degrees
of saturation were generated by varying the arc resistance Rf.
Lower arc resistance produces more significant CT saturation
primarily due to the higher X/R ratio of the fault. This plot is
for the worst case of extreme transformer tap. On central taps
the curve is skewed even further to the left so the relay blocks
for even lower degrees of saturation. There is good agreement
between the SSM and all relay fault records. The only
functionally important aspect is whether the relay blocks
(above the dashed line) or not (below the dashed line).
Peak 2nd Harmonic / Fundamental [%]
0.2
0.4
0.6
Degree of Saturation
Blue4
487E
Relay Setting
0.8
1
T60
Black6
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TPWRD.2014.2372794, IEEE Transactions on Power Delivery
TPWRD-00281-2014
11
0.8
0.6
0.4
0.2
0
0.5
1.5
Restraint [pu]
Blue4
Simple Step Model
SEL-487E
Operate [pu]
1.5
1
0.5
0
0.5
1.5
Restraint [pu]
Simple Step Model
2.5
Blue7
SEL-787
Fig. 16. Operate vs restraint for Blue4 (circles) and Blue7 (diamonds).
2.5
Black6
GE T60
0885-8977 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.