Disconnecting means
Overload protection
Time delay of 1 or 2
seconds before breaker trips
Specifications
Feature
FDMP
HFDMP
JGMPS
JGMPH
LGMPS
LGMPH
Interruption rating
at 240V
Interruption rating
at 480V
Interruption rating
at 600V
Icu/Ics at 240V
Icu/Ics at 415V
100% rated
FLA range (A)
Motor class protection
Phase unbalance protection
(current)active for phase
current >0.5 FLA setting
Phase loss protection
(current)active for phase
current >0.5 FLA setting
Thermal memory protection
High load indicator
Pre-detection relays
Internal accessories
65 kA
100 kA
85 kA
100 kA
85 kA
100 kA
35 kA
65 kA
35 kA
65 kA
50 kA
65 kA
18 kA
25 kA
18 kA
25 kA
25 kA
35 kA
65 kA/33 kA
35 kA/18 kA
No
40205
5, 10, 15, 20
100 kA/50 kA
65 kA/33 kA
No
40205
5, 10, 15, 20
Min. phase
0.25 max. phase
for 1 second
Yes
Factory installed
Aux, alarm,
shunt trip, UVR
Min. phase
0.25 max. phase
for 1 second
Yes
Factory installed
Aux, alarm,
shunt trip, UVR
85 kA/85 kA
40 kA/40 kA
Yes
20250
10, 15, 20, 30
25% delta
phase-to-phase
for 5 seconds
Min. phase
0.25 max. phase
for 1 second
Yes
LED
Yes
Field installed
Aux, alarm, pre-detection
relay, shunt trip, UVR
100 kA/100 kA
70 kA/53 kA
Yes
20250
10, 15, 20, 30
25% delta
phase-to-phase
for 5 seconds
Min. phase
0.25 max. phase
for 1 second
Yes
LED
Yes
Field installed
Aux, alarm, pre-detection
relay, shunt trip, UVR
85 kA/85 kA
50 kA/50 kA
Yes
100630
10, 15, 20, 30
25% delta
phase-to-phase
for 5 seconds
Min. phase
0.25 max. phase
for 1 second
Yes
LED
Yes
Field installed
Aux, alarm, pre-detection
relay, shunt trip, UVR
100 kA/100 kA
70 kA/70 kA
Yes
100630
10, 15, 20, 30
25% delta
phase-to-phase
for 5 seconds
Min. phase
0.25 max. phase
for 1 second
Yes
LED
Yes
Field installed
Aux, alarm, pre-detection
relay, shunt trip, UVR
Continuous Amperes
35 kA Without Phase
Unbalance, Class 10
Motor Protection Only
35 kA With Phase
Unbalance and Adjustable
Motor Class Protection
65 kA Without Phase
Unbalance, Class 10
Motor Protection Only
65 kA With Phase
Unbalance and Adjustable
Motor Class Protection
80
100
160
205
FDMP3080L
FDMP3100L
FDMP3160L
FDMP3205L
FDMP3080JL
FDMP3100JL
FDMP3160JL
FDMP3205JL
HFDMP3080L
HFDMP3100L
HFDMP3160L
HFDMP3205L
HFDMP3080JL
HFDMP3100JL
HFDMP3160JL
HFDMP3205JL
Continuous Amperes
(100% Rated)
35 kAIC
65 kAIC
Continuous Amperes
(100% Rated)
35 kAIC
65 kAIC
50
100
160
250
JGMPS050G
JGMPS100G
JGMPS160G
JGMPS250G
JGMPH050G
JGMPH100G
JGMPH160G
JGMPH250G
250
400
600
630
LGMPS250G
LGMPS400G
LGMPS600G
LGMPS630G
LGMPH250G
LGMPH400G
LGMPH600G
LGMPH630G
A 630 amperes is not a UL listed rating. 600 amperes is the maximum UL or CSA rating
for LG breaker.
NNote: For pre-trip alarm option, order Style Number 5721B31G02 separately.