You are on page 1of 36

Cable Sizing Fundamentals and

E l e c t r i c a l LV S t a n d a r d
Armada Hotel, Petaling Jaya
2 3 rd A u g u s t 2 0 1 4

Cable Sizing For Safe Power


System Based on IEC Standards
I r . H . P. L o o i ( m e k t r i c o n @ g m a i l . c o m )
B.Eng (Hons), FIEM, Jurutera Gas

Part

Cable

Sizing

SYNOPOSIS

We had an overview of the following topics in Part 1


1.

Introduction

2.

Scope

3.

General Design Procedure (design road map)

4.

Earthing system

5.

Cable types & installation method

6.

Circuit configuration

Part 2 will deal with Cable Sizing with the following:


1.

Overview

2.

Protection Device & Implication for cable sizing

3.

Simplified Method 60364-5-52

4.

Heat Flow Calculation 60297 series

23 r d August 2014

OVERVIEW TO CABLE SIZING

23 r d August 2014

OVERVIEW TO CABLE SIZING

23 r d August 2014

OVERVIEW NEHER MCGRATH AMPACITY

Cable sizing or Amps capacity calculation is basically a heat transfer problem. 1957 Neher
MacGrath equation makes the following simplification assumptions:
(a) Assumption of steady state conditions;
(b) The heat transfer media surrounding the cable system is homogeneous and the following
conditions apply:
(i) In case of cables in air, thermal transfer via convection is assumed to predominate
(direct solar radiation to be considered if relevant);
(ii) In case of cables in ground or embedded in solid media, conduction predominate;
(c) Cable diameter is assumed negligible compared to cable length, this reduces the model to
2-dimensions.
I
= Ampacity (current carrying capacity), (kA)
Tc = Conductor temperature, (C)
Ta = Ambient temperature, (C)
TD= Conductor temp rise due to dielectric loss, (C)
Rdc = Conductor dc resistance, (/foot)
Yc = Loss increment due to skin & proximity effects
Rca = Thermal resistance between conductor and
ambient (thermal feet)
23 r d August 2014

OVERVIEW 2 METHODS

Simplified 60364-5-52 Annex B to E look up tables

IEC 60287 series of equations,

23 r d August 2014

Circuit
Capacity

Cable
Ampacity

Voltage
Drop

I2 <1.45In

23 r d August 2014

IEC 60364-4-43 CIRCUIT CAPACITY

(1) IB < In < Iz


(2) I2 < 1.45 x Iz
Select
protective
devices,
In > IB
In = nominal
current rating
of protective
devices

IB decide current
rating of circuit
IB > load current
Check I2 < 1.45 Iz

Calculate cable size


based on:
Iz > In

Calculate
current
from load

I2 = current ensuring effective


Iz = current capacity of cable.
operation
within
time
prescribed
for
protective
Cables
Electrical load
device
23 r d August 2014
Protection devices

IEC 60364-4-43 CIRCUIT CAPACITY

23 r d August 2014

10 IEC 60364-5-52 ANNEX B

Current
capacity
required

Installation method
Reference methods Table B52.1
Current capacities
Tables B52.2 to B52.13
Temperature correction factor
Table B52.14 (cables in air);
B52.15 (cables in ground) and
B52.16 (cables in ducts)

Correction factor for soil


thermal resistivity
Table B52.16 for method D only
where soil resistivity is other
than 2.5 K-m/W.

Reduction factor for more than one (single or multi core) cable
per circuit.
Table B52.17 for installation method E to F
Table B52.18 for cables laid direct in ground
Table B52.19 for cables laid in duct in ground
Table B52.20 for multi core cables in free air (method E only)
Table B52.21 for single core cables in free air (method F only)
Annex E reduction factor due to harmonic currents

23 r d August 2014

11 IEC 60364-5-52 TABLE B52.16

Typical thermal resistivity of soil are included in the handbook.

23 r d August 2014

12 IEC 60364-5-52 TABLE B52.16

23 r d August 2014

13 IEC 60364-5-52 EXAMPLE


EXAMPLE
Estimate load current

0.9x25kW/(0.85x415Vx3
36A.

25kW

1
2

36A

Choose rating of circuit IB= 50A.

1
3

60A

Choose protection device In= 63A (In>IB)

1
4

25mm

1
5

200s

Size cable IZ > In; choose 4x25mm PVC; IZ 90A


Table B52-5
Check I2 < 1.45Iz 130A
Fuse 63A blow in abour 200s at 130A (I2)
MCB 63A trip in about 240s at 130A (I2)
23 r d August 2014

14 IEC 60364-5-52 EXAMPLE


Melt Time Current Data 2-125 Amperes

Example

Time in Second

gG Fuse 63A
Melt in 200s for 130A
current (over-load)

Fuse 63A
Melt at about 0.01s for 2kA
current (short circuit
current)
Current in Amperes

23 r d August 2014

15 IEC 60898 BREAKER CLASS

23 r d August 2014

16 IEC 60898 FUSES

(a) The first letter indicates the breaking range of fuse-links:


(i) g for full range breaking capacity; general purpose fuse link interrupts
all faults and is usually used for all overload and short circuit application.
(ii) a for partial range breaking capacity, usually associated with another
protective device in cascade for discrimination between different
segments of a circuit. It is usually used for short circuit protection only.
(b) The second letter indicates the utilisation category, which defines the
accuracy of the time-current characteristics,
(i)
G indicates general application;
(ii)
M indicates protection of motor;
(iii)
R indicates semiconductor protection;
(iv)
S indicates semiconductor protection;
(v)
Tr indicates for transformer protection;
(vi)
D indicates time-delay (UL 248); and
(vii)
N indicates non-time-delay (UL 248).
23 r d August 2014

17 IEC 60898 FUSES

23 r d August 2014

18 IEC 60364-5-52 VOLTAGE DROP

23 r d August 2014

19 NEUTRAL CABLE

Neutral (TN and TT systems) shall have the same cross sectional area and
not less than that of the line conductor in the following cases (refer IEC

60364-5-52 Clause 524.2).


(i)

In all cases of single-phase, 2-wire circuits.

(ii) In polyphase and single-phase 3-wire circuit, when the size of the line
conductors is less than or equal to 16mm2 copper or 25mm2
aluminium.
Note: Some national codes require that neutral cable should be the same size
as line conductor. This requirement is mandatory in Malaysia in all cases,
except between transformer and main switch board and at the discretion
of the designer who is expected to take into account issues relating to
neutral current listed below..

23 r d August 2014

20 HARMONICS, ANNEX E, 5-52


Where significant harmonic current occurs in three-phase circuits, reduction
factor for conductor sizing in accordance with Table 9 (Annex E of IEC 60364-552) shall be applied.
When harmonics exceed 33%, neutral currents may exceed the line current in
which case neutral conductors may be oversized compared to line conductors.

Third harmonic content of


phase current (%)
0 -15
15 - 33
33 - 45
> 45

Reduction factor
Size selection is based on
Size selection is based on
phase current
neutral current
1.0
0.86
0.86
1.0
23 r d August 2014

R = Ro [1 + 20 ( 20)]

X= 2 10-7 Ln [2s/d]

R = Rso [1 + 20 (sc 20)]


1= (Rs/SR) [ 1 /(1 + (Rs/X))]

23 r d August 2014

22 IEC 60287

Type of insulation
Polyvinyl chloride (PVC) (Thermo-plastics)
Cross-lined polyethylene (XLPE) and ethylene
propylene rubber (EPR) (Thermosetting)
Mineral (PVC covered or bare exposed to touch)

Temperature limit a, d
70C at the conductor
90C at the conductor b
70C at the sheath

Mineral (bare not exposed to touch and not in contact 105C at the sheath b, c
with combustible material)
Table 12 Temperature limit of cables (Table B52.1 of 60364-5-52)

23 VOLTAGE STANDARD

IEC 60287 Electric cables Calculation of the current rating


Part 1 Current rating equations (100 % load factor) and calculation of
losses:
Section 1: General;
Section 2: Sheath eddy current loss factors for two circuits in flat
formation;
Section 3: Current sharing between parallel single-core cables and calculation of circulating current losses;
Part 2 Thermal resistance:
Section 1: Calculation of thermal resistance;
Section 2: A method for calculating reduction factors for groups of cables
in free air, protected from solar radiation
Part 3 Sections on operating conditions:
Section 1: Reference operating conditions and selection of cable type;
Section 2: Economic optimization of power cable size;
Section 3: Cables crossing external heat sources
23 r d August 2014

23 r d August 2014

25 EXAMPLE 1
Circuit 1 Lighting 8 nos 80W each
Circuit 2 2x13A socket outlet in radial circuit
Circuit 3 1x15A water heater
Circuit 4 1x15A, air cool split unit air conditioning
Circuit 5 4x13A socket outlet in ring circuit
Circuit 6 6x13A socket outlet in ring circuit
Example 1, domestic wiring diagram with typical circuits

23 r d August 2014

26 EXAMPLE 1
Circuit 1 Lighting 8 nos 80W each
Circuit 2 2x13A socket outlet in radial circuit
Circuit 3 1x15A water heater
Circuit 4 1x15A, air cool split unit air conditioning
Circuit 5 4x13A socket outlet in ring circuit
Circuit 6 6x13A socket outlet in ring circuit
Example 1, domestic wiring diagram with typical circuits

23 r d August 2014

No

27 EXAMPLE 1
Fuse rating

Conductor Comments
(mm)
1.5 mm Lighting circuit (8 nos x 80W). Clause 524,
Table 52.2 of 60364-5-52 requires minimum
cable size at 1.5mm.
2.5 mm 2x13A socket outlet in radial circuit (2x300W)

6 Amps

15 Amps

20 Amps

4 mm

15 Amps

2.5 mm

1x15A socket outlet for water


(2,000W)
1x15A socket outlet for (1x750W)

30 Amps

2.5 mm

4x13A socket outlet in ring circuit (4x300W)

30 Amps

4 mm

6x13A socket outlet in ring circuit (6x300W)

60 Amps

25 mm

heater

Main feeder cables to consumer unit (total


load = 6,690W (38A).
Table 13A; Example 1, schedule of circuits
23 r d August 2014

28 EXAMPLE 1

Load Estimate

Table 13A
(previous slide)

Select Earthing
System

Determine
Installation
Method

Select & Size


Wiring / Cables

TN-S

PVC single core


in conduit;
method A1

IEC60364-5-52,
method A1; Table
B52.2

23 r d August 2014

Check:

29 EXAMPLE 1
Cct
No

Load/ current(3)
IB (A)

1
2

8x80W ~ 3.3A
2x300W ~ 3.3A

3
4

2000W ~ 9.7A
750W ~ 3.8A

IB < IN < IZ

MCB (type B)
Cable
Nom.
Effective Size mm Iz (A) (2)
rating IN
trip I2 (1)
6A
9A
1.5
14.5
15A
22.5A
2.5
19.5
20A
15A

30A
22.5A

4
2.5

26
19.5

I2 < 1.45 x IZ

Comments
230V single phase
Lighting circuit
Socket outlet
radial
circuit
Water heater
15A outlet with air
conditioning unit
Ring circuit subject to
national conditions.
Main power intake

5
4x300W ~ 6.5A
30A
45A
2.5
2x19.5
6
6x300W ~ 9.8A
30A
45A
4
2x26
7
6,690W ~ 36A
60A
90A
25
80
(1) Assume effective trip current to be 1.5 x IN.
(2) Cable installation assumes PVC insulated cables, 2 single core in conduit embedded in walls.
Current capacity referenced from IEC 60364, table B52.2, installation method A1.
(3) Load estimate are presented here without consideration of diversity as an illustration only.
The subject of load diversity can be a detail subject which may require national statistics on
23 r d August 2014
average usage of electrical appliances.

23 r d August 2014

Case

(a)
(b)

(a)
(b)
(b)

(a)
(b)

(b)

Installation
Configuration(1); XLPE cable31

Conductor
Current capacity
Group
(1) (mm)2 L
Esize
XAMPLE
ARGE
of
cablesCABLES
rating factor
(2) (3)

Multi core cable (B52.12, column 3, method E)


3 x 4 core, 1 cable
3x300mm / 4 3x621A = 1,853A
diameter apart
core
3 x 4 core, 1 cable
2x240mm / 4 3x538A = 1,614A
diameter apart
core
Single core cables in trefoil (B52.12, column 5, method F)
Trefoil, 2 circuit @ 2 cable 7x400mm / 1 2x823A = 1,646A
diameter apart on 1 ladder
core (5)
Trefoil, 3 circuit touching
11x240mm / 1 3x607A = 1,821A
core (5)
Trefoil, 3 circuit @ 2 cable 11x240mm / 1 3x607A = 1,821A
diameter apart on 1 ladder
core (5)
Single core cables in flat formation (B52.12, column 6 or 7,
method F or G)
Cable touching (method 7x400mm / 1 2x868A = 1,736A
F), 2 circuits, 1 ladder.
core (5)
1 cable diameter apart, 7x300mm / 1 2x902A = 1,804A
(method G), 2 circuits, 1
core (5)
ladder.
1 cable diameter apart, 7x240mm / 1 2x781A = 1,562A
(method G), 2 circuits, 1
core (5)
ladder.

Corrected
current
capacity

B52.20
1

1,853A

1,614A

B52.21
1

1,646A

0.82 (4)

1,493A

1)

1,821A

B52.21
0.97

1,684A

0.97

1,750A

0.97

1,515A
23 r d August
2014

32 EXAMPLE 2 LARGE CABLES


Notes:
(1) Installation configuration and conductor sizes are based on table B52.12 for
XLPE insulated copper cables.
(2) Group rating factor where only 1 cable ladder is used is referenced from table
B52.17 row 5. Finer graduation in group factor can be obtained from tables
B52.20 (for multi core cables and B52.21 (for single core cables).
(3) In all cases, we assume only one cable ladder used.
(4) Group rating for case 2(b). Table B52.21 for single core cables on ladder in
trefoil only considers case of cable-circuits laid 2 De apart. To consider case of
cable touching, table B52.17 is referred for reduction factor.
(5) For single core cables, we assume neutrals to be sizes. The odd cable is
therefore used as neutral e.g. 11 core means 3x1 core for each line conductor
and 2x1 core for neutral. In some national jurisdiction, size neutral may not
be allowed.
(6) Ambient temperature is assumed to be at 30C, for temperature correction
factor at 1 (from table B52.14).
23 r d August 2014
Table 14A; Example 2, schedule of cable sizes and configurations

33 EXAMPLE 2 LARGE CABLES

23 r d August 2014

34 EXAMPLE 2 LARGE CABLES

23 r d August 2014

35 EXAMPLE 2 LARGE CABLES

23 r d August 2014

Cable Sizing Fundamentals and


E l e c t r i c a l LV S t a n d a r d
Armada Hotel, Petaling Jaya
2 3 rd A u g u s t 2 0 1 4

Cable Sizing For Safe Power System Based


o n
I E C
S t a n d a r d s
I r . H . P. L o o i ( m e k t r i c o n @ g m a i l . c o m )
B.Eng (Hons), FIEM, Jurutera Gas

Part

Cable

Sizing

T h a n k Yo u f o r y o u r A t t e n t i o n !

You might also like