You are on page 1of 2

PP 00, PP 00-A

(, ; NYY, NAYY)
Standard:
SRPS N.C5.220
Nominal voltage Uo/U: 0,6/1 kV
Test voltage:
3,5 kV

CONSTRUCTION
Conductor: Wire or rope, class 2, according to JUS N.C0.015, annealed copper: type PP 00, or aluminum:
type PP 00-A
Insulation: PVC mass
Core: Two or multi cores are stranded together.
Filling: No vulcanized rubber compound layer over the core. Cables with sector-shaped conductors (designated S in the table): wrapped thermoplastic tapes.
Sheath: PVC mass layer.
Sheath color black
APPLICATION
For laying indoors, in ducts, in earth, in the open air, in urban networks and industrial plants, electric power
plants and switchgear assemblies, where one cannot expect mechanical damages.
TECHNICAL DATA
Permissable Conductor temperature:
- max operating temperature + 70C
- in short circuit (max 5 s), max 160C
Working temperature:
at laying and handling min. + 5C
Smallest bending radius:
- single core cables 15D (D - cable diameter)
- multi core cables 12 D
Standard construction data
n x q1)
mm2
1x1,5
1x2,5
1x4
1x6
1x10
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
3x1,5
3x2,5

Cu number
PP 00
kg/km
14,4
24
38
58
96
154
240
336
480
672
912
1152
1440
1778
2304
29
48
77
115
192
307
480
43
72

Al number
PP 00-A
kg/km
12
18
29
46
72
102
145
203
276
348
435
537
696
23
36
58
93
145
-

D
mm
7,0
7,5
8,0
8,5
9,5
11,0
13,0
13,5
15,5
17,5
19,0
20,5
22,5
24,5
28,0
10,5
11,5
13,0
14,5
16,5
19,0
22,0
11,0
12,0

Q kg/km
PP 00
65
82
105
125
174
252
363
475
637
850
1115
1365
1707
2056
2657
150
197
270
365
494
683
1005
171
227

PP 00-A
78
89
110
143
204
251
316
398
516
617
736
896
1131
235
277
350
467
688
-

PP 00, PP 00-A
3x4
115
35
14,0
3x6
173
52
15,0
3x10
288
87
17,0
3x16
461
139
20,5
3x25*
720
218
23,0
3x35*
1008
305
27,0
S 3x50
1440
435
25,0
S 3x70
2016
609
28,5
S 3x95
2736
827
32,5
S 3x120
3456
1044
35,5
S 3x150
4320
1305
39,5
S 3x185
5328
1610
43,5
S 3x240
6912
2088
49,0
3x25+16*
874
263
24,5
3x35+16*
1162
351
27,0
S 3x50+25
1680
507
29,0
S 3x70+35
2352
711
30,0
S 3x95+50
3216
972
34,5
S 3x120+70
4128
1247
38,0
S 3x150+70
4992
1508
41,0
S 3x185+95
6240
1888
48,5
S 3x240 +120
8064
2436
54,0
4x1,5
58
12,0
4x2,5
96
13,0
4x4
154
46
15,0
4x6
230
70
16,5
4x10
384
116
18,5
4x16
614
186
22,0
4x25*
960
290
25,5
4x35*
1344
406
28,5
S 4x50
1920
580
29,5
S 4x70
2688
812
33,0
S 4x95
3648
1102
38,5
S 4x120
4608
1392
41,5
S 4x150
5760
1740
46,0
S 4x185
7104
2148
51,0
S 4x240
9216
3480
58,0
5x1,5
72
12,5
5x2,5
120
14,0
5x4
192
58
16,5
5x6
288
88
17,5
5x10
480
145
20,5
5x16
768
233
24,0
5x25
1200
363
28,5
*
Sector shape construction per customer request possible.
1)
S in front of the wire number stands for sector shape conductors
q Conductor cross section,
n wire number
D cable diameter,
Q weight of the cable

(, ; NYY, NAYY)
307
400
570
851
1246
1686
1715
2391
3251
4037
4928
6127
7983
1278
1627
2105
2760
3794
4755
5645
7361
9492
201
270
378
483
692
1044
1542
2011
2380
3144
4381
5310
6569
8127
10560
238
323
455
582
838
1275
1925

284
306
391
530
736
930
853
1095
1438
1742
2128
2597
3363
850
1109
1019
1340
1715
2019
2433
3046
3903
298
354
456
591
909
1210
1103
1356
1883
2248
2737
3430
4404
352
421
546
729
1226

You might also like