You are on page 1of 32

PW CABLE TRAY

LADDER, TROUGH
AND SOLID BOTTOM

STEEL
HOT-DIP
G GALVANIZED STEEL

WIDTHS (W) INCHES


6 9 12 18 24 30 36

RAIL HEIGHTS (H) INCHES


4 5 6 7
LADDER
LENGTHS (L) FEET
10 12 20 24
RAIL FLANGE (IN.)
RAIL HEIGHT (IN.)

LOAD DEPTH (IN.)

TRAY SYSTEM NUMBER AMP RATING


NEMA CLASS

CSA CLASS
CONNECTORS & FITTINGS:
SERIES
Necessary connectors and [] ][
fasteners are supplied with
all trays and fittings. Extra
connectors for field cuts
1 12C, 16A D, 3M S1 A457 100
or spares must be ordered 20A, 16B - S2 1D80 1D81 200
separately. 4 3
1 3/4 20B, 16C D, 6M S2 1D82 1D83 400
SAFE LOAD:
Allowable cable load in
20C E, 6M S2 1D69* 1D70 400
pounds per linear foot 1 12C, 16A D, 3M S1 1E72 100
uniformly distributed.
Based on tray with 5 4 20B, 16C - S2 1E45 1E46 400
standard rung on 9" 1 3/4
20C D, 6M S2 1E53* 1E54 400
centers and supported on
simple beam with safety 1 12C, 16A D, 3M S1 A639 100
factor of 1.5 per NEMA VE1.
6 5 20B, 16C E, 6M S2 1F45* 1F46 400
CONCENTRATED LOAD: 1 3/4
All ladders with solid rungs
20C E, 6M S2 1F53* 1F54 400
METALLIC STRAIGHT SECTIONS STEEL

and trays with corrugated 1 12C, 16A D, 3M S1 1772 100


bottoms will support a
200 lb. concentrated load 7 6 20B, 16C E, 6M S2 1755* 1756 400
applied at the center of 1 3/4
20C E, 6M S2 1753 1754 400
the tray in addition to the
NEMA-rated cable load *1D69, 1F45, and 1F53 corrugated bottom tray systems have a CSA load class D,6M rating.
without collapse. 1E53 and 1755 corrugated bottom tray systems do not have CSA load class ratings.

SPLICES Match above to determine the connectors you need.

SERIES1
Fitting side rails have 2" tangents (flat portion
beyond curvature) at the end of each fitting, to
accommodate splice plates with four holes.
SERIES2
Fitting side rails have 5" tangents at the end of
each fitting, to accommodate splice plates with
eight holes.
28

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

VENTED CORRUGATED SOLID CORRUGATED

SUPPORT SPAN (FT.)

6 8 10 12 14 16 18 20 22 24

SAFE LOAD DATA (LBS./FT.) / DEFLECTION (IN.) / SAFETY FACTOR 1.5


Legrand trays
439 0.31 250 0.55 160 0.86 111 1.24 78 1.61 58 2.06 marked with CSA
load class have been
439 0.20 338 0.51 216 0.79 150 1.14 110 1.55 84 2.02 67 2.56 54 3.16 44 3.74 34 4.07 tested (loading, finish
439 0.16 439 0.50 312 0.88 217 1.26 159 1.72 122 2.25 96 2.84 78 3.51 63 4.18 52 4.87 and electrical) by UL
to CSA standard 126
439 0.39 400 0.87 278 1.25 204 1.70 156 2.21 123 2.80 100 3.46 81 4.09 66 4.77 22.2 .

400 0.21 225 0.38 144 0.59 100 0.85 71 1.13 52 1.40
439 0.11 439 0.37 304 0.62 211 0.90 155 1.22 119 1.59 94 2.02 76 2.49 61 2.92 50 3.38
439 0.34 400 0.75 278 1.08 204 1.47 156 1.92 123 2.43 100 3.00 81 3.54 60 4.13
All Legrand steel
420 0.13 236 0.22 151 0.35 105 0.50 74 0.65 55 0.83
cable trays are
439 0.08 439 0.25 336 0.47 233 0.68 171 0.92 131 1.20 104 1.52 84 1.88 68 2.24 53 2.47 Classified by UL as
equipment grounding
439 0.20 439 0.50 319 0.75 235 1.02 180 1.34 142 1.69 115 2.09 93 2.48 73 2.75 conductors per NEC

METALLIC STRAIGHT SECTIONS STEEL


392.60. (UL File No.
400 0.10 225 0.18 144 0.28 100 0.40 71 0.53 52 0.66
E60796)
439 0.07 439 0.22 300 0.38 208 0.54 153 0.73 117 0.96 93 1.22 75 1.50 61 1.79 50 2.08

439 .017 439 0.42 319 0.63 235 0.86 180 1.12 142 1.42 115 1.75 93 2.11 76 2.52

STEEL STRAIGHT SECTION CATALOG NUMBERING EXAMPLE:


SYSTEM NO. PRODUCT NO.
BOTTOM TYPE 09-A457-0012-36-
VENTED NON-VENTED
06 6" Rung Spacing SC Solid Corrugated LENGTH
09 9" Rung Spacing* TRAY SYSTEM WIDTH RUNG OPTION
* Standard rung spacing 0010 10'-0"
12 12" Rung Spacing Not available for NUMBER 0012* 12'-0" 06 6" Add suffix for
18 18" Rung Spacing** This identifies the 0020 20'-0" 09 9" non-standard rung.
VC Vented Corrugated
flange out tray 0024 24'-0"
specific tray design 12 12" See page 63 for details
and is used as a * Standard for 18 18" and other rung options.
product number prefix SERIES 1 24 24"
for straight sections. Standard for 30 30"
36 36"
SERIES 2
29

For detailed material and finish descriptions, see page 6.


WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

STAINLESS
STEEL
STAINLESS STEEL
L AISI Type 304L

STAINLESS STEEL
T AISI Type 316L

WIDTHS (W) INCHES


6 9 12 18 24 30 36

RAIL HEIGHTS (H) INCHES LADDER


4 5 6 7

LENGTHS (L) FEET TRAY SYSTEM NUMBER


RAIL FLANGE

NEMA CLASS
RAIL HEIGHT

LOAD DEPTH

SERIES
10 12 20 24
(IN.)

(IN.)

(IN.)

CONNECTORS & FITTINGS:


[] [] ][ ][
Necessary connectors and 12B S1 3408 3416
fasteners are supplied with 1
12C, 16A S1 3409 3417
all trays and fittings. Extra
connectors for field cuts 4 3 20A, 16B S2 3476 3D85 3D63 3D82
or spares must be ordered 1 3/4 20B, 16C S2 3456 3D92 3D93 3D58
separately.
20C S2 3406 3445 3407 3446
SAFE LOAD: 12B S1 3504 3514
Allowable cable load in 1
pounds per linear foot 12C, 16A S1 3505 3515
5 4
uniformly distributed. 20B, 16C S2 3551 3594 3550 3582
Based on tray with 1 3/4
standard rung on 9"
20C S2 3587 3593 3592 3583
centers and supported on 12B S1 3603 3620
METALLIC STRAIGHT SECTIONS STAINLESS STEEL

simple beam with safety 1


12C, 16A S1 3604 3621
factor of 1.5 per NEMA VE1. 6 5
20B, 16C S2 3F67 3F85 3F68 3F66
CONCENTRATED LOAD: 1 3/4
20C S2 3645 3F35 3F58 3F61
All ladders with solid rungs
and trays with corrugated 12B S1 3734 3738
bottoms will support a 1
12C, 16A S1 3735 3739
200 lb. concentrated load 7 6
applied at the center of 20B, 16C S2 3701 3723 3754 3756
1 3/4
the tray in addition to the 20C S2 3714 3724 3722 3760
NEMA-rated cable load
without collapse.

SPLICES Match above to determine the connectors you need.

SERIES1
Fitting side rails have 2" tangents (flat portion
beyond curvature) at the end of each fitting, to
accommodate splice plates with four holes.
SERIES2
Fitting side rails have 5" tangents at the end of
each fitting, to accommodate splice plates with
eight holes.
30

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

SOLID BOTTOM

SUPPORT SPAN (FT.)


6 8 10 12 14 16 18 20 22 24
SAFE LOAD DATA (LBS./FT.) / DEFLECTION (IN.) / SAFETY FACTOR 1.5
300 0.30 169 0.54 108 0.85 75 1.22
400 0.32 225 0.57 144 0.90 100 1.29 71 1.71 52 2.13
556 0.31 313 0.55 200 0.86 139 1.24 102 1.69 78 2.20 62 2.79 50 3.44
564 0.24 469 0.62 300 0.97 208 1.39 153 1.89 117 2.47 93 3.13 75 3.70 86 4.60 48 5.13
564 0.54 400 0.94 278 1.36 204 1.85 156 2.41 123 3.05 100 3.77 81 4.45 63 4.96
300 0.20 169 0.35 108 0.55 75 0.79
400 0.23 225 0.41 144 0.64 100 0.93 71 1.23 52 1.53
564 0.16 469 0.42 300 0.66 208 0.95 153 1.29 117 1.69 93 2.14 75 2.64 61 3.14 48 3.51
564 0.46 400 0.80 278 1.16 204 1.57 156 2.05 123 2.60 100 3.21 81 3.79 63 4.22
300 0.11 169 0.20 108 0.31 75 0.45

METALLIC STRAIGHT SECTIONS STAINLESS STEEL


400 0.14 225 0.24 144 0.38 100 0.54 71 0.71 52 0.89
564 0.12 469 0.32 300 0.51 208 0.73 153 0.99 117 1.30 93 1.64 75 2.03 61 2.42 48 2.70
564 0.31 400 0.54 278 0.77 204 1.05 156 1.38 123 1.74 100 2.15 81 2.54 63 2.83
300 0.10 169 0.17 108 0.27 75 0.39
400 0.11 225 0.19 144 0.30 100 0.43 71 0.57 52 0.71
564 0.10 469 0.26 300 0.41 208 0.58 153 0.79 117 1.04 93 1.31 75 1.62 61 1.93 48 2.15
564 0.28 400 0.48 278 0.69 204 0.93 156 1.22 123 1.55 100 1.91 81 2.05 63 2.28

STAINLESS STEEL STRAIGHT SECTION CATALOG NUMBERING EXAMPLE:


BOTTOM TYPE 09-3620-0012-18-
VENTED
06 6" Rung Spacing
09 9" Rung Spacing* LENGTH
12 12" Rung Spacing TRAY SYSTEM 0010 10'-0" WIDTH RUNG OPTION
18 18" Rung Spacing NUMBER 0012* 12'-0" 06 6" Add suffix for
This identifies the 0020 20'-0" 09 9" non-standard rung.
NON-VENTED
specific tray design 0024 24'-0" 12 12" See page 63 for details
SF Solid Flat Bottom
and is used as a * Standard for 18 18" and other rung options.
* Standard rung spacing product number prefix SERIES 1 24 24"
Not available with
for straight sections. 30 30"
flange out tray Standard for
36 36"
SERIES 2
31

For detailed material and finish descriptions, see page 6.


WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

HORIZONTAL 90 ELBOW G L T HORIZONTAL 60 ELBOW G L T

A W

R
D S1 S2

B
S1 S2 B D
R2
90 R2
R
60

W C C

PRODUCT SERIES1 SERIES2 PRODUCT SERIES1 SERIES2


NUMBER W R2 NUMBER W R2
RADIUS (IN.) A B C D A B C D RADIUS (IN.) A B C D A B C D

6 18 20 20 34 34 23 23 40 40 6 18 185/8 133/4 32 181/2 231/8 163/8 41 233/4


9 21 23 23 37 37 26 26 43 43 9 21 211/4 163/4 345/8 20 255/8 193/8 431/2 251/4
12 24 26 26 40 40 29 29 46 46 12 24 233/4 193/4 371/8 211/2 283/8 223/8 461/4 263/4
9012 18 30 32 32 46 46 35 35 52 52 6012 18 30 29 253/4 423/8 241/2 331/2 283/8 513/8 293/4
12 12
24 36 38 38 52 52 41 41 58 58 24 36 341/8 313/4 471/2 271/2 385/8 343/8 561/2 323/4
30 42 44 44 58 58 47 47 64 64 30 42 393/8 373/4 523/4 301/2 437/8 403/8 613/4 353/4
36 48 50 50 64 64 53 53 70 70 36 48 441/2 433/4 577/8 331/2 49 463/8 667/8 383/4
6 30 32 32 58 58 35 35 64 64 6 30 29 193/4 523/4 301/2 331/2 223/8 613/4 353/4
9 33 35 35 61 61 38 38 67 67 9 33 315/8 223/4 553/8 32 361/8 253/8 643/8 371/4
12 36 38 38 64 64 41 41 70 70 12 36 341/8 253/4 577/8 331/2 383/4 283/8 67 383/4
9024 18 42 44 44 70 70 47 47 76 76 6024 18 42 393/8 313/4 631/8 361/2 437/8 343/8 721/8 413/4
24 24
24 48 50 50 76 76 53 53 82 82 24 48 441/2 373/4 681/4 391/2 491/8 403/8 773/8 443/4
30 54 56 56 82 82 59 59 88 88 30 54 493/4 433/4 731/2 421/2 541/8 463/8 825/8 473/4
36 60 62 62 88 88 65 65 94 94 36 60 547/8 493/4 785/8 451/2 593/8 523/8 873/4 503/4
6 42 44 44 82 82 47 47 88 88 6 42 393/8 253/4 731/2 421/2 437/8 283/8 821/2 473/4
9 45 47 47 85 85 50 50 91 91 9 45 42 283/4 761/8 44 461/2 313/8 851/8 491/4
12 48 50 50 88 88 53 53 94 94 12 48 441/2 313/4 785/8 451/2 491/8 343/8 873/4 503/4
9036 18 54 56 56 94 94 59 59 100 100 6036 18 54 493/4 373/4 837/8 481/2 541/4 403/8 927/8 533/4
36 36
24 60 62 62 100 100 65 65 106 106 24 60 547/8 433/4 89 511/2 591/2 463/8 981/8 563/4
30 66 68 68 106 106 71 71 112 112 30 66 601/8 493/4 941/4 541/2 643/4 523/8 1033/8 593/4
36 72 74 74 112 112 77 77 118 118 36 72 651/4 553/4 993/8 571/2 697/8 583/8 1081/2 623/4
METALLIC FITTINGS

WIDTHS (W) INCHES SPLICES Match above to determine the connectors you need.
6 9 12 18 24 30 36
SERIES1
RAIL HEIGHTS (H) INCHES Fitting side rails have 2" tangents (flat portion
4 5 6 7
beyond curvature) at the end of each fitting, to
accommodate splice plates with four holes.
RADIUS (R) INCHES SERIES2
12 24 36 Fitting side rails have 5" tangents at the end of
each fitting, to accommodate splice plates with
eight holes.
32

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

HORIZONTAL REDUCERS G L T HORIZONTAL STANDARD TEE G L T

LEFT HAND
W1

L
A
W1
STRAIGHT REDUCER
W2

W
RIGHT HAND
L LENGTH (L) W1 B
INCHES
S1 12 L
R S1 S2

W2 S2 18
W2 W

MAIN BRANCH PRODUCT NUMBER PRODUCT SERIES1 SERIES2


WIDTH (IN.) WIDTH (IN.) NUMBER W
W1 W2 STRAIGHT LEFT HAND RIGHT HAND RADIUS (IN.) A B A B

9 6 0109 0709 0809 6 34 20 40 23


6 0112 0712 0812 9 37 23 43 26
12
9 0112 0712 0812 12 40 26 46 29
6 0118 0718 0818 2012 18 46 32 52 35
12
18 9 0118 0718 0818 24 52 38 58 41
12 0118 0718 0818 30 58 44 64 47
6 0124 0724 0824 36 64 50 70 53
9 0124 0724 0824 6 58 32 64 35
24
12 0124 0724 0824 9 61 35 67 38
18 0124 0724 0824 12 64 38 70 41
6 0130 0730 0830 2024 18 70 44 76 47
24
9 0130 0730 0830 24 76 50 82 53
30 12 0130 0730 0830 30 82 56 88 59
18 0130 0730 0830 36 88 62 94 65
24 0130 0730 0830 6 82 44 88 47
6 0136 0736 0836 9 85 47 91 50
9 0136 0736 0836 12 88 50 94 53
12 0136 0736 0836 2036 18 94 56 100 59
36 36
18 0136 0736 0836 24 100 62 106 65
24 0136 0736 0836 30 106 68 112 71
30 0136 0736 0836 36 112 74 118 77

HORIZONTAL REDUCERS CATALOG NUMBERING EXAMPLE:


METALLIC FITTINGS

FITTING
SYSTEM NO. PRODUCT NO. BRANCH WIDTH

WIDTHS (W) INCHES


BOTTOM TYPE LD-6 G 2 O -0109-06
VENTED
6 9 12 18 24 30 36 LD Ladder
VC Vented Corrugated
MATERIAL
SIDE RAIL G FITTING FLANGE
RAIL HEIGHTS (H) INCHES NON-VENTED
HEIGHT SERIES DIRECTION
SC Solid Corrugated
4 5 6 7 4 4" L 1 Series 1 I Flange In
SF Solid Flat Bottom
2 Series 2 O Flange Out
Not available for flange out tray 5 5" T
RADIUS (R) INCHES 6 6"
12 24 36 7 7"
34

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

HORIZONTAL REDUCING/ G L T
EXPANDING TEES

REDUCING TEE MAIN BRANCH PRODUCT SERIES1 SERIES2 PRODUCT SERIES1 SERIES2 PRODUCT SERIES1 SERIES2
WIDTH WIDTH NUMBER NUMBER NUMBER
W1 W2 RADIUS (IN.) A B A B RADIUS (IN.) A B A B RADIUS (IN.) A B A B
9 6 34 23 40 26 58 35 64 38 82 47 88 50
6 34 26 40 29 58 38 64 41 82 50 88 53
12
9 37 26 43 29 61 38 67 41 85 50 91 53
6 34 32 40 35 58 44 64 47 82 56 88 59
18 9 37 32 43 35 61 44 67 47 85 56 91 59
12 40 32 46 35 64 44 70 47 88 56 94 59
A
6 34 38 40 41 58 50 64 53 82 62 88 65
9 37 38 43 41 61 50 67 53 85 62 91 65
24
W1 W1
12 40 38 46 41 64 50 70 53 88 62 94 65
B
18 46 38 52 41 70 50 76 53 94 62 100 65
6 2012 34 44 40 47 2024 58 56 64 59 2036 82 68 88 71
R S1 S2 12 24 36
9 37 44 43 47 61 56 67 59 85 68 91 71
W2 30 12 40 44 46 47 64 56 70 59 88 68 94 71
18 46 44 52 47 70 56 76 59 94 68 100 71
24 52 44 58 47 76 56 82 59 100 68 106 71
6 34 50 40 53 58 62 64 65 82 74 88 77
9 37 50 43 53 61 62 67 65 85 74 91 77
12 40 50 46 53 64 62 70 65 88 74 94 77
36
18 46 50 52 53 70 62 76 65 94 74 100 77
24 52 50 58 53 76 62 82 65 100 74 106 77
30 58 50 64 53 82 62 88 65 106 74 112 77

EXPANDING TEE 9 37 20 43 23 61 32 67 35 85 44 91 47
12 40 20 46 23 64 32 70 35 88 44 94 47
18 46 20 52 23 70 32 76 35 94 44 100 47
6
24 52 20 58 23 76 32 82 35 100 44 106 47
30 58 20 64 23 82 32 88 35 106 44 112 47
36 64 20 70 23 88 32 94 35 112 44 118 47
12 40 23 46 26 64 35 70 38 88 47 94 50
18 46 23 52 26 70 35 76 38 94 47 100 50
9 24 52 23 58 26 76 35 82 38 100 47 106 50
30 58 23 64 26 82 35 88 38 106 47 112 50
A
36 2012 64 23 70 26 2024 88 35 94 38 2036 112 47 118 50
12 24 36
W1 18 46 26 52 29 70 38 76 41 94 50 100 53
B
24 52 26 58 29 76 38 82 41 100 50 106 53
12
R S1 S2 30 58 26 64 29 82 38 88 41 106 50 112 53
36 64 26 70 29 88 38 94 41 112 50 118 53
W2
24 52 32 58 35 76 44 82 47 100 56 106 59
18 30 58 32 64 35 82 44 88 47 106 56 112 59
36 64 32 70 35 88 44 94 47 112 56 118 59
30 58 38 64 41 82 50 88 53 106 62 112 65
24
36 64 38 70 41 88 50 94 53 112 62 118 65
30 36 64 44 70 47 88 56 94 59 112 68 118 71

REDUCING TEE CATALOG NUMBERING EXAMPLE:


METALLIC FITTINGS

FITTING MAIN BRANCH


SYSTEM NO. PRODUCT NO. WIDTH WIDTH
BOTTOM TYPE LD-6 G 2 O -2012-2412
VENTED
LD Ladder MATERIAL
VC Vented Corrugated
SIDE RAIL G FITTING FLANGE W1 (W2)
NON-VENTED HEIGHT SERIES DIRECTION 06 6"
SC Solid Corrugated L 09 9"
4 4" 1 - SERIES 1 I Flange In
SF Solid Flat Bottom 12 12"
5 5" T O Flange Out
Not available for flange out tray 2 - SERIES 2 18 18"
6 6" 24 24"
7 7" W2 applies only to reducing 30 30"
and expanding tees. 36 36"
35

For detailed material and finish descriptions, see page 6.


WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

HORIZONTAL CROSSES G L T

STANDARD CROSS

PRODUCT SERIES 1 SERIES 2 PRODUCT SERIES 1 SERIES 2 PRODUCT SERIES 1 SERIES 2


W NUMBER NUMBER NUMBER
RADIUS (IN.) A A RADIUS (IN.) A A RADIUS (IN.) A A

6 34 40 58 64 82 88
9 37 43 61 67 85 91
12 40 46 64 70 88 94
A
W 18 1012 46 52 1024 70 76 1036 94 100
12 24 36
24 52 58 76 82 100 106
30 58 64 82 88 106 112
A W W
36 64 70 88 94 112 118

R S1 S2

REDUCING CROSS

MAIN BRANCH PROD. SERIES 1 SERIES 2 PROD. SERIES 1 SERIES 2 PROD. SERIES 1 SERIES 2
WIDTH WIDTH NUM. NUM. NUM.
W1 W2 RADIUS A B A B RADIUS A B A B RADIUS A B A B
9 6 34 37 40 43 58 61 64 67 82 85 88 91
6 34 40 40 46 58 64 64 70 82 88 88 94
12
9 37 40 43 46 61 64 67 70 85 88 91 94
6 34 46 40 52 58 70 64 76 82 94 88 100
A
18 9 37 46 43 52 61 70 67 76 85 94 91 100
12 40 46 46 52 64 70 70 76 88 94 94 100
6 34 52 40 58 58 76 64 82 82 100 88 106
B W1 W1 9 37 52 43 58 61 76 67 82 85 100 91 106
24
12 40 52 46 58 64 76 70 82 88 100 94 106
R S1 S2 18 46 52 52 58 70 76 76 82 94 100 100 106
6 1012 34 58 40 64 1024 58 82 64 88 1036 82 106 88 112
W2 12 24 36
9 37 58 43 64 61 82 67 88 85 106 91 112
30 12 40 58 46 64 64 82 70 88 88 106 94 112
18 46 58 52 64 70 82 76 88 94 106 100 112
24 52 58 58 64 76 82 82 88 100 106 106 112
6 34 64 40 70 58 88 64 94 82 112 88 118
9 37 64 43 70 61 88 67 94 85 112 91 118
12 40 64 46 70 64 88 70 94 88 112 94 118
36
18 46 64 52 70 70 88 76 94 94 112 100 118
24 52 64 58 70 76 88 82 94 100 112 106 118
30 58 64 64 70 82 88 88 94 106 112 112 118

REDUCING CROSS CATALOG NUMBERING EXAMPLE:


METALLIC FITTINGS

FITTING MAIN BRANCH


SYSTEM NO. PRODUCT NO. WIDTH WIDTH

WIDTHS (W) INCHES


BOTTOM TYPE LD-6G2I-1012- 24-06
VENTED
6 9 12 18 24 30 36 LD Ladder
VC Vented Corrugated FITTING
SERIES W1 (W2)
RAIL HEIGHTS (H) INCHES NON-VENTED SIDE RAIL FLANGE 06 6"
SC Solid Corrugated 1 - SERIES 1
4 5 6 7 HEIGHT DIRECTION 09 9"
SF Solid Flat Bottom 4 4" 2 - SERIES 2 12 12"
I Flange In
Not available for flange out tray 18 18"
5 5" MATERIAL O Flange Out
RADIUS (R) INCHES 6 6" 24 24"
G L T W2 applies only 30 30"
12 24 36 7 7"
to reducing cross 36 36"
36

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

HORIZONTAL WYE BRANCHES G L T

LEFT HAND RIGHT HAND

PRODUCT NUMBER SERIES 1 SERIES 2


W LH RH A B C A B C
RADIUS (IN.) RADIUS (IN.)
6 263/8 101/4 161/4 293/8 101/4 161/4
9 305/8 123/8 213/8 335/8 123/8 213/8
12 347/8 141/2 261/2 377/8 141/2 261/2
18 4024 4124 433/8 183/4 363/4 463/8 183/4 363/4
24 24
24 517/8 23 47 547/8 23 47
RR RR 30 603/8 271/4 571/4 633/8 271/4 571/4
BB
36 687/8 311/2 671/2 717/8 311/2 671/2
CC

W
W

AA AA

HORIZONTAL ADJUSTABLE ELBOW G L T

SERIES 1 SERIES 2
PRODUCT W
NUMBER X X

6 4 7
W 9 4 7
12 4 7
W+2 0401 18 4 7
24 4 7
X
30 4 7
36 4 7

HORIZONTAL WYE BRANCH CATALOG NUMBERING EXAMPLE:


METALLIC FITTINGS

FITTING
SYSTEM NO. PRODUCT NO.
BOTTOM TYPE LD-6G2O-4024- 24
VENTED
LD Ladder FITTING
VC Vented Corrugated SERIES WIDTH
SIDE RAIL 06 6"
NON-VENTED 1 - SERIES 1
HEIGHT 09 9"
SC Solid Corrugated
SF Solid Flat Bottom 4 4" 2 - SERIES 2 12 12"
Not available for flange out tray 5 5" MATERIAL FLANGE 18 18"
DIRECTION 24 24"
6 6" G L T
I Flange In 30 30"
7 7" 36 36"
O Flange Out
37

For detailed material and finish descriptions, see page 6.


WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

VERTICAL OUTSIDE 90 ELBOW G L T VERTICAL OUTSIDE 60 ELBOW G L T

60
90 H
H

B
B
R S1 S2
R

S1 S2 A
A

RAIL HEIGHT (IN.) > 4, 5, 6, 7 RAIL HEIGHT (IN.) > 4, 5, 6, 7


PRODUCT SERIES 1 SERIES 2 PRODUCT SERIES 1 SERIES 2
NUMBER W* NUMBER W*
RADIUS (IN.) A B A B RADIUS (IN.) A B A B

9212 ALL 14 14 17 17 6212 ALL 131/2 73/4 18 13/8


12 12
9224 ALL 26 26 29 29 6224 ALL 237/8 133/4 283/8 163/8
24 24
9236 ALL 38 38 41 41 6236 ALL 341/4 193/4 383/4 223/8
36 36

VERTICAL OUTSIDE 45 ELBOW G L T VERTICAL OUTSIDE 30 ELBOW G L T

45
30
H
H
S1 S2
S1 S2 B B

R
R

A
A

RAIL HEIGHT (IN.) > 4, 5, 6, 7 RAIL HEIGHT (IN.) > 4, 5, 6, 7


PRODUCT SERIES 1 SERIES 2 PRODUCT SERIES 1 SERIES 2
NUMBER W* NUMBER W*
RADIUS (IN.) A B A B RADIUS (IN.) A B A B

4712 ALL 12 5 171/8 71/8 3212 ALL 93/4 25/8 153/8 41/8
12 12
4724 ALL 201/2 81/2 255/8 105/8 3224 ALL 153/4 41/4 213/8 53/4
24 24
4736 ALL 287/8 12 34 141/8 3236 ALL 213/4 57/8 273/8 73/8
36 36
METALLIC FITTINGS

SPLICES Match above to determine the connectors you need.

WIDTHS (W) INCHES SERIES1


6 9 12 18 24 30 36 Fitting side rails have 2" tangents (flat portion beyond
curvature) at the end of each fitting, to accommodate
RAIL HEIGHTS (H) INCHES splice plates with four holes.
4 5 6 7 SERIES2
Fitting side rails have 5" tangents at the end of each
RADIUS (R) INCHES
fitting, to accommodate splice plates with eight
12 24 36 holes.
38

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

VERTICAL INSIDE 90 ELBOW G L T VERTICAL INSIDE 60 ELBOW G L T

R
R

90 B 60
B

H H

A A

VERTICAL INSIDE 45 ELBOW G L T VERTICAL INSIDE 30 ELBOW G L T

R
R 30
45

B H B
H

A A

RAIL HEIGHT > 4 5 6 7


PRODUCT SERIES 1 SERIES 2 SERIES 1 SERIES 2 SERIES 1 SERIES 2 SERIES 1 SERIES 2
NUMBER R W
RADIUS (IN.) A B A B A B A B A B A B A B A B
9112 12 ALL 18 18 21 21 19 19 22 22 20 20 23 23 21 21 24 24
90 9124 24 ALL 30 30 33 33 31 31 34 34 32 32 35 35 33 33 36 36
9136 36 ALL 42 42 45 45 43 43 46 46 44 44 47 47 45 45 48 48

6112 12 ALL 167/8 93/4 213/8 123/8 173/4 101/4 221/4 127/8 185/8 103/4 231/8 133/8 191/2 111/4 24 137/8
60 6124 24 ALL 271/4 153/4 313/4 183/8 281/8 161/4 323/8 187/8 29 163/4 331/2 193/8 297/8 171/4 343/8 197/8
6136 36 ALL 373/4 213/4 421/4 243/8 385/8 221/4 431/8 247/8 393/8 223/4 437/8 253/8 401/4 231/4 443/4 257/8

4612 12 ALL 143/4 61/8 197/8 81/4 151/2 61/2 205/8 85/8 161/4 63/4 213/8 87/8 167/8 7 22 91/8
45 4624 24 ALL 231/4 95/8 283/8 113/4 24 10 291/8 121/8 245/8 101/4 293/4 123/8 253/8 101/2 301/2 125/8
4636 36 ALL 313/4 131/4 367/8 151/4 321/2 131/2 375/8 155/8 331/8 133/4 381/4 157/8 337/8 14 39 161/4

3112 12 ALL 113/4 31/4 173/8 43/4 121/4 31/4 177/8 43/4 123/4 33/8 183/8 47/8 131/4 35/8 187/8 51/8
30 3124 24 ALL 173/4 43/4 233/8 61/4 181/4 47/8 237/8 63/8 183/4 5 243/8 61/2 191/4 51/4 247/8 63/4
3136 36 ALL 233/4 63/8 293/8 77/8 241/4 61/2 297/8 8 243/4 65/8 303/8 81/8 251/4 67/8 307/8 83/8
METALLIC FITTINGS

VERTICAL ELBOW CATALOG NUMBERING EXAMPLE:


FITTING SYSTEM NO. PRODUCT NO.
BOTTOM TYPE LD-6G2 I-6124- 24 WIDTH
VENTED SIDE RAIL 06 6"
LD Ladder FLANGE 09 9"
HEIGHT DIRECTION
VC Vented Corrugated 12 12"
4 4" I Flange In
NON-VENTED MATERIAL 18 18"
5 5" FITTING O Flange Out 24 24"
SC Solid Corrugated
6 6"
G L T SERIES 30 30"
SF Solid Flat Bottom
Not available for flange out tray 7 7" 1 - SERIES 1 36 36"
2 - SERIES 2
39

For detailed material and finish descriptions, see page 6.


WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

VERTICAL TEES G L T VERTICAL CROSS G L T

TEE DOWN TEE UP

H A
B R A
H
W

W
R WB W R
W
FLANGE-IN
H TRAYS FLANGE-OUT TRAYS
A
A

TEE UP fittings have rungs or bottom members


for cable support across the bottom of the fitting.
PRODUCT NUMBER SERIES 1 SERIES 2 PRODUCT SERIES 1 SERIES 2
RADIUS (IN.) NUMBER W H
W H RADIUS (IN.) A A
TEE TEE A B A B
DOWN UP 4 56 62
4 56 30 62 33 1124 5 57 63
ALL
5 57 31 63 34 24 6 58 64
2124 2224 ALL
24 24 6 58 32 64 35 7 59 65
7 59 33 65 36

VERTICAL 90 SUPPORT ELBOW G L T CABLE SUPPORT HOOK

PRODUCT SERIES 2
NUMBER W H
RADIUS A COMPLETE CATALOG NO.
4 21 5.38" DS-1841-ZN
9312 5 22
ALL
12 6 23
7 24
1.38"
4 33
Supports cables at the
top of long vertical drops 9324 5 34
ALL
where the weight of the 24 6 35
vertical cable may be 7 36
excessive. Hooks (sold
4 45
separately) attach to the
brace in the elbow; when 9336 5 46
ALL
used with cable grips 36 6 47
(supplied by others), 7 48
tension in the vertical
cable is relieved and
transferred to the elbow.
METALLIC FITTINGS

VERTICAL TEE DOWN CATALOG NUMBERING EXAMPLE:


FITTING SYSTEM NO. PRODUCT NO.
WIDTHS (W) INCHES
6 9 12 18 24 30 36
BOTTOM TYPE LD-6G2 I-2124- 24 WIDTH
VENTED SIDE RAIL 06 6"
LD Ladder FLANGE 09 9"
HEIGHT DIRECTION
RAIL HEIGHTS (H) INCHES VC Vented Corrugated 12 12"
4 4" I Flange In
NON-VENTED MATERIAL 18 18"
4 5 6 7 5 5" FITTING O Flange Out 24 24"
SC Solid Corrugated
6 6"
G L T SERIES 30 30"
SF Solid Flat Bottom
RADIUS (R) INCHES Not available for flange out tray 7 7" 1 - SERIES 1 36 36"
12 24 36 2 - SERIES 2
40

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

41

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

Covers protect and contain cables. They are highly recommended


TRAY COVERS to avoid damage to the tray contents and to protect against the
elements. Some covers can also be attached to the tray with
hinges; please contact Legrand for more information.

SOLID COVERS
FLANGE IN 13/4" FLANGE OUT
SERIES 2

[] ][
SOLID, FLAT NON-FLANGED PRODUCT NUMBER
FLAT, NON-FLANGED
M 2002 2067
L 3002 3038
T 3042 3039
SOLID, FLAT FLANGED* PRODUCT NUMBER
M 2000 2066
G 1000 1066
FLAT, FLANGED
L 3000 3036
T 3005 3029
SOLID, PEAKED 15 FLANGED PRODUCT NUMBER
M 2140 2114
G 1140 1114
L 3128 3131
PEAKED 15, FLANGED
T 3017 3040
LOUVERED, FLAT NON-FLANGED PRODUCT NUMBER
LOUVERED COVERS
M 2006 2112
L 3050 3117
T 3041 3112
LOUVERED, FLAT FLANGED* PRODUCT NUMBER
M 2007 2104
G 1007 1104
FLAT, NON-FLANGED L 3070 3003
T 3076 3113
WIDTHS (W) INCHES
6 9 12 18 24 30 36

RAIL HEIGHTS (H) INCHES


FLAT, FLANGED 4 5 6 7
* Flange is 3/8" wide.
15 is standard angle for peaked covers. Flange is 3/8" wide.
METALLIC COVERS

COVER CATALOG NUMBERING EXAMPLE:


COVER LENGTH OR
SIDE RAIL SYSTEM NO. FITTING PRODUCT NO.
Standards:
HEIGHT* 6 0 - 2 0 0 0 - 0 0 1 2 -3 6 - 0 5 - B COVER THICKNESS
40 4" Letter suffixes are G 18 Ga.
50 5" used to indicate
LENGTH FITTING
60 6" WIDTH TANGENT alternate cover M L T 20 Ga.
0006** 6'
70 7" 0010 10' 05 - SERIES 2 thicknesses. Leave
0012 12' A 18 Gage (0.048")
* Side rail height necessary for outside vertical fitting covers. blank for standard
or (5" Tangents ) B 16 Gage (0.060")
** Standard lengh for steel covers hot-dip galvanized after thickness.
fabrication per ASTMA-123 is 6'-0". 9224 C 14 Gage (0.075")

FITTING PRODUCT NO.


42

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

FLAT COVER CONNECTORS M T G* PEAKED COVER CONNECTORS M T G*

For use with indoor, outdoor, or vertical flat covers. Top and For use with indoor, outdoor, or vertical peaked covers. Top and
bottom pieces are 1" wide. Install one connector over each bottom pieces are 1" wide. Install one connector over each
cover joint and space additional connectors on 36"- 48" centers. cover joint and space additional connectors on 36"- 48" centers.

CHANNEL-STYLE CHANNEL-STYLE

APPLICATION APPLICATION

STRAP-STYLE STRAP-STYLE

APPLICATION APPLICATION

PRODUCT PRODUCT
DESCRIPTION FASTENERS DESCRIPTION FASTENERS
NUMBER NUMBER

CHANNEL 1400 ZN S6 CHANNEL 1411 ZN S6

STRAP 1423 CD S6 STRAP 1440 CD S6

METALLIC COVER CONNECTORS


COVER CONNECTOR CATALOG NUMBERING EXAMPLE:
SPLICES Match above to determine the connectors you need.
FITTING
SYSTEM NO. PRODUCT NO.

SERIES1 6A2O-1411-24-S6
Fitting side rails have 2" tangents (flat portion
beyond curvature) at the end of each fitting, to SIDE FITTING WIDTH
accommodate splice plates with four holes. RAIL SERIES
SERIES2 HEIGHT FASTENERS
MATERIAL FLANGE
Fitting side rails have 5" tangents at the end of ZN CD S6
L T G* DIRECTION
each fitting, to accommodate splice plates with
eight holes. *optional
43

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

COVER CONNECTOR CLIPS T H-BINDER COVER JOINT STRIP A

For use with indoor, horizontal covers. Flange-in clip requires Closes gaps at cover joints. Notched for the tray side rail.
tray with 1" side rail flanges. Flange-out clip works with any No fasteners required.
H-Binder
side rail flange width. SoldStrip
individually.
FLANGE-IN CLIP FLANGE-OUT CLIP

H-Binder Strip

Abutting Covers
Abutting Covers

PRODUCT
DESCRIPTION NUMBER
FLAT COVER CLIP 0925
PRODUCT FASTENER PEAKED COVER CLIP 0926
DESCRIPTION NUMBER INCLUDED
CATALOG NUMBERING EXAMPLE (EA.):
FLANGE-IN 1410 Connector System No. Width
S6 A2O - 0925 -06
FLANGE-OUT 1853 AI,
A1O and A2O are the only three
CATALOG NUMBERING EXAMPLE (EA.): Connector System No. possiblities for this part.
Material Fasteners
T - 1410 -S6

RAISED COVER CONNECTOR M T G* RAISED COVER CONNECTOR A M T

For use with all covers, indoors and outdoors. Covers are Raised cover connectors allow for ventilation of ladder tray
attached to uprightmounted C channel on the top of the installations while protecting cables from possible falling objects.
cable tray. Install 36"-48" on center. Raised cover connectors allow a gap of 1, 2, 3 or 4.
Flat or Peaked Cover with Flanges
APPLICATION
Gap
METALLIC COVER ACCESSORIES

GAP DIMENSION PRODUCT FASTENER PRODUCT FASTENER


(IN.) NUMBER OPTIONS NUMBER INCLUDED
1 1441
1432 S6
2 1442
ZN S6 CATALOG NUMBERING EXAMPLE (EA.):
3 1443 Material Fasteners
4 1444 M - 1432 -S6
CATALOG NUMBERING EXAMPLE:
Fitting System No. Width Fasteners
6T2O - 1441 - 06 - S6

RAIL HEIGHTS (H) INCHES


4 5 6 7
44

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

Cadmium-plated steel fasteners are standard for all splice plate connectors on aluminum and steel cable tray systems. All splices
are supplied in pairs. Type 316 stainless steel fasteners are standard on stainless steel systems, but are available as an option on
all aluminum and steel systems. Sufficient connector pairs with fasteners are automatically included with each shipment of straight
sections and fittings. Extras for field cuts or spares must be ordered separately. Bonding jumpers are required for all expansion
splice plates, adjustable connectors, and tray discontinuities. The symbol indicates that bonding jumpers are required.

STANDARD SPLICE G T MID-SPAN SPLICE G T

These heavy-duty splice plates


SERIES1 SERIES2 SERIES2
are designed for random location,
including mid-span. Field-drilled
holes are required in the bottom
flanges of adjoining trays.

PRODUCT PRODUCT
NUMBER FASTENER OPTIONS NUMBER FASTENER OPTIONS

1302 CD S6 1385 CD S6
CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Connector System No. Fasteners Connector System No. Fasteners
4G1 - 1302 -CD 4G2 - 1385 -S6
This item must be specified as Series 2 in the System No.

UNIVERSAL SPLICE G T REDUCING HEIGHT SPLICE G T

These splice plates are designed to connect to existing cable tray. These splice plates are designed to connect cable tray side
rails with different heights. The connector system number
SERIES1 SERIES2 includes the larger side rail height. Choose the product
number depending on the reduced side rail height.

SERIES1 SERIES2

PRODUCT
NUMBER FASTENER OPTIONS

1335

METALLIC SPLICES & CONNECTORS


CD S6
PRODUCT
CATALOG NUMBERING EXAMPLE: SIZE FASTENER OPTIONS
NUMBER
Connector System No. Fasteners
4G1 - 1335 -CD
1386 REDUCES TO 4" HIGH TRAY

1379 REDUCES TO 5" HIGH TRAY CD S6

1355 REDUCES TO 6" HIGH TRAY


SPLICES Match above to determine the connectors you need. CATALOG NUMBERING EXAMPLE:
Connector System No. Fasteners

SERIES1 6G2 - 1386 - CD

Fitting side rails have 2" tangents (flat portion


beyond curvature) at the end of each fitting, to
accommodate splice plates with four holes.
SERIES2
Fitting side rails have 5" tangents at the end of
each fitting, to accommodate splice plates with
eight holes.
45

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

Cadmium-plated steel fasteners are standard for all splice plate connectors on aluminum and steel cable tray systems. All splices
are supplied in pairs. Type 316 stainless steel fasteners are standard on stainless steel systems, but are available as an option on
all aluminum and steel systems. Sufficient connector pairs with fasteners are automatically included with each shipment of straight
sections and fittings. Extras for field cuts or spares must be ordered separately. Bonding jumpers are required for all expansion
splice plates, adjustable connectors, and tray discontinuities. The symbol indicates that bonding jumpers are required.

EXPANSION SPLICE G T STRAIGHT REDUCER SPLICE G T

Permits thermal contraction


SERIES1 SERIES1
and expansion in a cable tray
SERIES2 installation. The length of the SERIES2
straight cable tray run and the
temperature differential govern the
number and spacing of expansion
connectors. Expansion splice plates RN
permit 2" of movement. 2

PRODUCT PRODUCT
FASTENER OPTIONS FASTENER OPTIONS
NUMBER NUMBER
1314 CD S6
1303 CD S6
CATALOG NUMBERING EXAMPLE:
CATALOG NUMBERING EXAMPLE:
Connector System No. Fasteners
Connector System No. RN Fasteners
4G2 - 1314 -CD 4G2 - 1303 -06-CD

OFFSET REDUCER SPLICE G T 90 CONNECTOR G T

SERIES1 SERIES1
SERIES2 SERIES2

AL
WI L TRA
DT
RN HS Y

PRODUCT FASTENER OPTIONS PRODUCT


METALLIC SPLICES & CONNECTORS

NUMBER FASTENER OPTIONS


NUMBER
1304 CD S6
1320 CD S6
CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Connector System No. RN Fasteners Connector System No. Fasteners
4G2 - 1304 -12 - S6 4G2 - 1320 -CD

SPLICES Match above to determine the connectors you need.


WIDTHS (W) INCHES
6 9 12 18 24 30 36 SERIES1
Fitting side rails have 2" tangents (flat portion beyond
RAIL HEIGHTS (H) INCHES curvature) at the end of each fitting, to accommodate
4 5 6 7 splice plates with four holes.
SERIES2
REDUCTION (RN) INCHES
Fitting side rails have 5" tangents at the end of each
3 6 9 12 15 18 21 24 27 30
fitting, to accommodate splice plates with eight holes.
46

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

All splices are supplied in pairs. Bonding jumpers are required for use with all adjustable splices.

FLOOR FLANGE / TRAY-TO-BOX G T HORIZONTAL ADJUSTABLE SPLICE G T


CONNECTOR

Fasteners for tray


SERIES1 SERIES1
attachment only
SERIES2 are included. Floor SERIES2 ALL
connection leg has W
9/16 diameter hole. For odd angle
bends up to 30

PRODUCT PRODUCT
FASTENER OPTIONS FASTENER OPTIONS
NUMBER NUMBER

1864 CD S6 1305 CD S6
CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Connector System No. Fasteners Connector System No. Fasteners
4G2 - 1864 -CD 4G2 - 1305 -CD
W

7/16 DIA
VERTICAL VERTICAL HANGER HOLES TRAY-TO-BOX
G T G T G T
ADJUSTABLE SPLICE SPLICE FRAME CONNECTOR

SERIES1 Maximum bend angle is +-90 SERIES1 SERIES1 Sold individually.


APPLICATION W
SERIES2 SERIES2 SERIES2
7/16 DIA
HOLES

ALL DIMENSIONS
W
A A H + 3-3/4
B

B W+4
A
PRODUCT PRODUCT PRODUCT

METALLIC SPLICES & CONNECTORS


FASTENER OPTIONS FASTENER OPTIONS FASTENER OPTIONS
NUMBER NUMBER NUMBER

1307 CD S6 0356 CD S6 0403 CD S6


CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Connector System No. Fasteners Connector System No. Fasteners Connector System No. Width Fasteners
4G2 - 1307 -CD 6G2 - 0356 -S6 4G2 - 0403 - 12 -CD

All connectors on these pages are designed to fit Series 1 and 2 systems. When ordering, however, they should be specified as Series 2.
47

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

LAMINATED ALUMINUM A
BONDING JUMPERS
PRODUCT L RATED AMPS
NUMBER (N.E.C. 250-122)
Use across all discontinuities, expansion joints, and adjustable BJ 21 " 2000
connectors to maintain electrical continuity in the cable tray CATALOG NUMBERING EXAMPLE (EA:):
system. Also use to bond the cable tray system to the building Material Fasteners
ground. Bonding jumpers are not required at standard or rigid A - BJ - 2000 - GE
splice locations. Fasteners for laminated bonding jumpers are
INSULATED COPPER C
included; fasteners for insulated jumpers must be ordered
separately. PRODUCT COPPER RATED AMPS
NUMBER CABLE SIZE (N.E.C. 250-122)
LAMINATED ALUMINUM INSULATED COPPER A806 #6 200

15"
A807 #4 300
A804 #2 500
A803 #1 600
A808 1/O 800
A809 2/O 1000
A805 3/O 1200
Laminated Aluminum: (4) 3/8" x 1" bolts per bonding jumper A810 4/O 1600
(included).
4/O WELDING
Insulated Copper: Made with flame-retardant, moisture- and A814* CABLE 2107 1800
heat-resistant, insulated copper cable. Tin plated copper lugs STRANDS
have one hole, sized for 3/8" x 3/4" bolt. Length is 15" to the
CATALOG NUMBERING EXAMPLE (EA.):
center of the lug holes. Special lengths, lugs, and cables are Material
also available. C - A806
*Length is 30" to the center of the lug holes. One-hole
tin-plated copper lugs are sized for 1/2" bolt.

SPLICE FASTENERS

Knurled Bolt: Specially designed for cable tray


connectors, the ribbed neck firmly grips the tray side COMPLETE
DESCRIPTION SIZE CATALOG NUMBER
rail to prevent screw rotation while tightening. Bolt
can also be tightened with a Phillips screwdriver. KNURLED DS-8530-01-CD CD
BOLT
3/8"-16 x 3/4"
DS-8926-01-S6 S6
Flanged Hex Nut: Free spinning lock-type nut
with a serrated face, eliminating the need for a FLANGED DS-8524-01-CD CD
HEX NUT
3/8" DIA.
washer. Nuts require a 9/16" wrench. Tighten to DS-8927-01-S6 S6
approximately 19-25 ft-lbs of torque. LOCKING DS-8575-02-CD CD
METALLIC SPLICES & CONNECTORS

HEX NUT
3/8" DIA.
DS-8576-01-S6 S6
Locking Hex Nut: For use with expansion
connectors. Deformed threads cause this nut to FLAT DS-8596-01-CD CD
WASHER
3/8" DIA.
lock on to the bolt after just a few turns, allowing DS-8600-01-S6 S6
movement of the bolt in the expansion slot without
possibility of the nut backing off. Typically identified
by a rectangular indentation on the side of the nut.

Flat Washer: For use with expansion connectors.


Install under the locking hex nut in the expansion
slots. Prevents binding in the expansion slot during
movement of the tray due to thermal expansion.

RAIL HEIGHTS (H) INCHES


4 5 6 7
48

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

STRAIGHT HORIZONTAL DIVIDER A M T G* VERTICAL FITTING DIVIDER A M T G*

For use with all straight tray. Furnished with four #10 Furnished with two #10 self-drilling screws.
self-drilling screws.

PRODUCT PRODUCT
NUMBER L FASTENER OPTIONS NUMBER R DIVIDER TYPE

0012-99 12 ZN S6 9112-99 12
CATALOG NUMBERING EXAMPLE: 9124-99 24 90 INSIDE ELBOW
Accessory System No. Fasteners 9136-99 36
4A - 0012-99 - ZN
9212-99 12
9224-99 24 90 OUTSIDE ELBOW
9236-99 36
6112-99 12
FLEXIBLE HORIZONTAL DIVIDER A M T G*
6124-99 24 60 INSIDE ELBOW
6136-99 36
For use with all horizontal fittings of any radius.
6212-99 12
Furnished with three #10 self-drilling screws.
6224-99 24 60 OUTSIDE ELBOW
6236-99 36
4612-99 12
4624-99 24 45 INSIDE ELBOW
4636-99 36
4712-99 12

PRODUCT 4724-99 24 45 OUTSIDE ELBOW


NUMBER L FASTENER OPTIONS
4736-99 36
0606-99 6' ZN S6 3112-99 12
CATALOG NUMBERING EXAMPLE: 3124-99 24 30 INSIDE ELBOW
Accessory System No. Fasteners 3136-99 36
4T - 0606-99 - S6
3212-99 12
3224-99 24 30 OUTSIDE ELBOW
3236-99 36

FASTENER OPTIONS ZN S6

CATALOG NUMBERING EXAMPLE: METALLIC ACCESSORIES


Accessory System No. Fasteners
4A - 9212-99 -ZN

49
G* = optional

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

DIVIDER HOLD DOWN CLIP M T G* 5" VINYL DIVIDER SPLICE V

Purchased separately. Supplied with carriage bolt and flanged Splices joints of abutting divider strips. Vinyl edge strip is also
hex nut. Designed for use with ladders with box-shaped rungs available in bulk lengths.
(Types BX & BHsee pages 66-67).

PRODUCT PRODUCT
FASTENER OPTIONS
NUMBER
5" NUMBER
1852 ZN S6 0930
CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Material Fasteners Material
M - 1852 - ZN V - 0930

DIVIDER SPLICE SELF-DRILLING SCREW

Sold in bags of 25. Provided with all dividers, but extras


can be ordered separately.

COMPLETE CAT. NO. COMPLETE CATALOG NO. SIZE


A COTJ-AL DS-8930-01-ZN ZN #10 X 3/4"
M COTJ-PG DS-8930-01-S6 S6 #10 X 3/4"
T COTJ-316
METALLIC ACCESSORIES

50

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

BLIND END PLATE M T G* CABLE DROPOUT A M T G*

Seals off the open end of a cable tray. Attaches to the tray using Provides a smooth, rounded surface for cables dropping out
standard 3/8" dia. connector fasteners. of the bottom of the cable tray.

PRODUCT PRODUCT NUMBER R


FASTENER OPTIONS
NUMBER
0253 3/4
0402 CD S6
0254 5
CATALOG NUMBERING EXAMPLE:
FASTENER ZN S6
Height/Material Width Fasteners
OPTIONS
4T - 0402 - 12 - CD
CATALOG NUMBERING EXAMPLE:
Material -Flange Width Fasteners
AI-0253-06 -S6

TRAY WIDTH (NOMINAL) 6 9 12 18 24 30 36

DROPOUT WIDTH (FLG IN) 2 1/4 51/4 81/4 141/4 201/4 261/4 321/4 IN

DROPOUT WIDTH (FLG OUT) 51/4 81/4 113/4 173/4 233/4 293/4 353/4

WALL PENETRATION SLEEVE M G T OUTDOOR CONVERSION FOR G T


WALL PENETRATION

Provides a rigid support for cable tray at wall penetrations. Makes ladder tray wall penetrations weather resistant to
Overall length of the sleeve is 20". Will fit walls up to 8" thick. minimize water intrusions. Removable cover/shield fastens
Bonding jumpers are not required for use with wall sleeves. to tray and wall penetration sleeve for the utmost in weather
Two pairs of splice plates and fasteners are included for tray protection.
attachment. Fits Standard Hot-Dip
Galvanized or Stainless
SERIES1 SERIES1
"0424" or "0440" wall
SERIES2 SERIES2 penetrations (see page 58.)
Sized to fit flange-in or
PRODUCT
FASTENER OPTIONS flange-out trays
NUMBER
PRODUCT
0424 CD S6 FASTENER OPTIONS
NUMBER
CATALOG NUMBERING EXAMPLE:
Connector System No Width Fasteners 0434 CD S6
4T2 - 0424 -12- S6 CATALOG NUMBERING EXAMPLE:
Connector System No Width Fasteners
4G2 - 0434 -06- CD
METALLIC ACCESSORIES

The wall penetration sleeve and outdoor conversion kit are designed to fit Series 1 and 2 systems.
When ordering, however, they should be specified as Series 2.

51
G* = optional

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

HOLD DOWN/EXPANSION CLAMP A Z T Z-HOLD DOWN/EXPANSION GUIDE M T G*

Works as an expansion guide and flips over for use as a hold down Wraps around the tray side rail for use with all solid bottom
clamp for use with all ladder trays. Sold individually. trays. Can also be used with any flange-in tray system.
Expansion guide is slightly taller to permit longitudinal tray
movement caused by thermal expansion. Sold individually.

PRODUCT FASTENER
NUMBER OPTIONS PRODUCT NUMBER FASTENER
OPTIONS
1893-01* ZN S6 Z-HOLD DOWN EXPANSION

1893-02 NONE 1866-01* 1867-01 ZN S6

1893-03 ZN S6 1866-02 1867-02 None

CATALOG NUMBERING EXAMPLE: 1866-03 1867-03 ZN S6


Material Fasteners
CATALOG NUMBERING EXAMPLE:
A - 1893-01 -ZN
Accessory System No. Fasteners
* Includes 3/8"x 1" hex bolt, 3/8" 4M - 1866-01 -ZN
flanged nut. * Includes " x " carriage bolt, " flanged nut.
Includes 3/8" x 1" hex bolt, 3/8"
Includes " x 1" screw, " spring nut.
spring nut.

HEAVY-DUTY HOLD DOWN BRACKETS A G T WIRE MESH-TO-LADDER CLAMP Z T

Designed for use with all trays. 3/8" diameter hardware This unique clamp allows wire mesh cable tray to be attached
for tray attachment only is included. Holes for structure to the side rails of any ladder tray and a pre-installed setscrew
attachment are sized for 1/2" diameter fasteners. Ideal for secures the junction for a permanent installation.
vertical tray support. Sold in pairs.

PRODUCT FASTENER OPTIONS PRODUCT FASTENER OPTIONS


NUMBER NUMBER
A845 CD S6 WMC 2LA CD S6
CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Material Fasteners Material Fasteners
T - A845 -S6 T - WMC 2LA -S6
METALLIC ACCESSORIES

SPLICES Match above to determine the connectors you need.

SERIES1
Fitting side rails have 2" tangents (flat portion
beyond curvature) at the end of each fitting, to
WIDTHS (W) INCHES accommodate splice plates with four holes.

6 9 12 18 24 30 36 SERIES2
Fitting side rails have 5" tangents at the end of
RAIL HEIGHTS (H) INCHES each fitting, to accommodate splice plates with
4 5 6 7 eight holes.
52

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

I-BEAM HOLD DOWN CLAMP/ Z T SINGLE OVERHEAD HANGER CLAMP M


EXPANSION GUIDE

Hold Down Clamp firmly attaches the cable tray to the flange Attaches to the tray bottom flange and supports the cable tray
of an I-beam type support. directly from a threaded rod without the need for an additional
Expansion Guide attaches the clamp to the flange of an support member. Threaded rod purchased separately.
I-beam type support, allowing movement of the tray side rail
due to thermal contraction and expansion.
SERIES1

PRODUCT NUMBER FASTENER


OPTIONS PRODUCT ROD FASTENERS
HOLD DOWN EXPANSION NUMBER DIA. INCLUDED
A802-01* A802-02 CD S6 1899-01 1/2"
ZN S6
CATALOG NUMBERING EXAMPLE:
1899-02 3 /8"
Accessory System No. Fasteners
CATALOG NUMBERING EXAMPLE:
Z - A802-01 -S6
Material Fasteners
*Includes (2) " x 5/8" screws and
M - 1899-01 -S6
(1) " x 1 "screw.
Includes (1) " x 1"screw.

No drilling is required for either installation.

HANGER BRACKETS M T G* NYLON ISOLATION PAD N

SINGLE: Supports a single tray side rail Made of extruded black nylon. Can be installed between the
from a " threaded rod. For use with cable tray and support member to provide electrical isolation
all flange-out ladder tray systems. of the tray system. Can also be used to facilitate cable tray
Safe load = 300 lbs. per bracket. movement caused by thermal contraction and expansion.
No fasteners required.

PRODUCT NUMBER DIMENSIONS


8945 1/8" X 3" X 6"
DOUBLE: Supports two tray side rails CATALOG NUMBERING EXAMPLE:
that are installed side-by-side from a Material
N - 8945
single " threaded rod. For use with
all flange-out ladder tray systems.
Safe load = 300 lbs. per bracket.

FASTENER
PRODUCT NUMBER OPTIONS METALLIC ACCESSORIES
SINGLE A836 NONE
DOUBLE A837* ZN S6
CATALOG NUMBERING EXAMPLE:
Accessory System No. Fasteners
4M2- A837 - ZN
*Includes " x 5" hex head bolt and "
flanged nut.

53
G* = optional

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

FLANGE OUT
SINGLE HANGER CHANNEL A M G T TRAY PRODUCT NUMBER FLANGE IN
WIDTH
HANGER KIT L (W+4) L (W+10)
Made from 12-gage strut. Hangers have 9/16" diameter holes 13/16" from each
end to accept 1/2" threaded rod. Kit includes fasteners. When used with Z-type 6 10 16
hold-down clamps, select hanger with flange out dimensions. 9 13 19
SINGLE HANGER 12 16 22
CHANNEL KIT*
15/8" 18 0373 0393 22 28
24 28 34
15/8" L 30 34 40
36 40 46
L
FASTENERS INCLUDED WITH KIT ONLY* ZN S6
CATALOG NUMBERING EXAMPLE:
Material Length Fasteners
13
/16" M- 0393-10 - S6*
13
/16" DIA.

FLANGE OUT
DOUBLE HANGER CHANNEL A M G T TRAY PRODUCT NUMBER FLANGE IN
WIDTH
HANGER KIT L (W+4) L (W+10)
Made from 12-gage struts welded back-to-back. Hangers have 9/16" dia.
holes 13/16" from each end to accept 1/2" threaded rod. When used with Z-type 6 10 16
hold-down clamps, select hanger with flange out dimensions. 9 13 19
DOUBLE HANGER 12 16 22
15/8" CHANNEL KIT*
18 0371 0394 22 28
24 28 34
31/4"
L 30 34 40
36 40 46
FASTENERS INCLUDED WITH KIT ONLY* ZN S6
L

CATALOG NUMBERING EXAMPLE:


Material Length Fasteners
13
/16" 9
/16" DIA.
M- 0394-16 - S6*

FLANGE OUT
CENTER HANGER CHANNEL M G T TRAY PRODUCT NUMBER FLANGE IN
WIDTH
HANGER KIT L (W+2) L (W+6)
Mounts with one 1/2" threaded rod to allow cable installation from both sides. Cable
should be loaded evenly on both sides of the center support to remain level. 12-gage 6 8 12
strut accepts channel nuts for hold down clamps with no drilling required. Not 9 11 15
recommended for trays over 24" wide. When used with Z-type hold-down clamps, 12 0369 0395 14 18
METALLIC ACCESSORIES

select hanger with flange out dimensions. 18 20 24


CENTER HANGER 24 26 30
15/8" CHANNEL KIT*
FASTENERS INCLUDED WITH KIT ONLY* ZN S6
CATALOG NUMBERING EXAMPLE:
Material Length Fasteners
15/8"
M- 0395-10 - S6*

L L

54 *Kits include hardware for ladder trays. Contact Legrand for other design options.

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

WALL BRACKET G T SINGLE STRUT BRACKET G T

Recommended for use with flange-in cable trays. Made with 1 5/8" x 1 5/8" x 12 gage steel struts.

2"

L
13
/16" L

11/2" 3 /8"
1
4 /4"3

PRODUCT DESIGN LOAD -


/16 DIA. L
9
NUMBER UNIFORM (LBS.)
/8" x 1" SLOTS
3

ON 2" CENTERS 7 1000


PRODUCT DESIGN LOAD -
L H 10 720
NUMBER UNIFORM (LBS.) 1 5/8"

7 6 13 550
2" 10 6 2" 0215 16 450
0353 13 6 900 19 380
L 13
/16" L
7
/8" 22 320
19 7
3 1/8" 4 3/4" 25 290
2 3/4" H 25 7 11/2"
CATALOG NUMBERING EXAMPLE: CATALOG NUMBERING EXAMPLE:
Material Length 9
/16 DIA. Material Length
9
/16" DIA.
3
/8"Gx -1"0SLOTS
353-13 G-0215-13
ON 2" CENTERS

1 5/8"

DOUBLE STRUT BRACKET G T HEAVY-DUTY STRUT BRACKET G T

Made with 1 5/8" x 1 5/8" x 12 gage steel struts. Made with 1 5/8" x 1 5/8" x 12 gage steel struts.

2"

L L
13
/16"

3 1/8"
PRODUCT DESIGN LOAD - PRODUCT DESIGN LOAD -
L L H
NUMBER HUNIFORM (LBS.) NUMBER UNIFORM (LBS.)
7 3000 13 10 1600
10 2400 19 15 1200
1 5/8"
3 1/4" 13 13
/ "1850
16 25 18 900
STIFFENER BAR ON
31" LONG AND GREATER
16 9
/ " 1500
16 DIA. 0392 31 22 750
19 1250 37 25 675
0216
2" 22 1100 2" 43 29 580
25 960 49 32 500
13
/16" L 13
/16" L
CATALOG NUMBERING EXAMPLE:
31 770
3 /8"
1 Material Length
4 3/8" 6" 37 650 G-0392-13
METALLIC ACCESSORIES
43 560 H
9
/16" DIA. CATALOG NUMBERING EXAMPLE:
Material Length
T-0216-13
1 5/8"
13
/16"
3 1/4" STIFFENER BAR ON
31" LONG AND GREATER
9
/16" DIA.

55

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

CABLE CLAMP T GROUND WIRE ATTACHMENT CLAMP Z T

For use with all ladder cable PRODUCT NUMBER CABLE SIZE Holds one or two bare copper or aluminum ground wires against
trays with box-shaped rungs. the cable tray side rail using included 3/8 diameter fasteners.
1916-06 3/4"
This clamp does not bond the ground wire to the tray.
1916-07 7/8"
TRAY 11/4
1916-08 1"
SIDE TRAY
PROD. NO. CONDUCTOR SIZE
11/4
1916-09 11RAIL
/8" SIDE
RAIL 1873-02 #2, #1 AND 1/0
1916-10 1 /4"
1 1873-03 #6 TO #4
1916-11 13/8" 1873-04 2/0, 3/0 AND 4/0
1916-12 11/2" FASTENER OPTIONS CD S6
1916-13 15/8" CATALOG NUMBERING EXAMPLE:
Material Fasteners
1916-14 13/4"
Z - 1873-02 - S6
1916-15 17/8"
1916-16 2"
1916-17 21/8" CONDUIT BRACKET CLAMP Z T
1916-18 21/4"
1916-19 23/8"
Attaches conduit to the cable tray side rail.
1916-20 21/2"
1916-21 25/8" PROD. NO. CONDUIT DIA. EMT DIA.
1916-22 23/4" 0228-05 3/8"-" "
1916-23 27/8" 0228-06 " "
1916-24 3" 0228-10 1" 1"
1916-25 31/8" 0228-11 1" 1"
1916-26 31/4" 0228-12 1" 1"
1916-27 33/8" APPLICATION 0228-20 2" 2"
1916-28 31/2" 0228-25 2" 2"
1916-29 35/8" 0228-30 3" 3"
1916-30 33/4" 0228-40 4" 4"
1916-31 37/8" FASTENER OPTIONS ZN S4
1916-32 4" CATALOG NUMBERING EXAMPLE:
Material Fasteners
FASTENERS INCLUDED S6
T - 0228-05 - S4
CATALOG NUMBERING EXAMPLE:
Material Fasteners
T - 1916-06 -S6
CONDUIT PLATE CLAMP A M

CABLE TRAY GROUNDING CLAMP A


Attaches conduit to PRODUCT NUMBER EMT DIA.
the ladder tray rungs. 0226-05 1/2"

Provides an excellent ground for copper or aluminum ground wires 0226-06 3/4"
METALLIC ACCESSORIES

to the cable tray. A 1/4 hex wrench is used to tighten both tray and 0226-10 1"
conductor set screws. Clamps are tin-plated, extruded aluminum. 0226-11 11/4"
Conductor Range: #6AWG to 250 MCM. 0226-12 11/2"
0226-20 2"
PRODUCT FASTENERS
NUMBER
0226-25* 21/2"
INCLUDED
RUNG SPACING INCHES 0226-30* 3"
A840-01 ZN
9" PLATE 6 9 0226-40* 4"
CATALOG NUMBERING EXAMPLE:
Material Fasteners 18" PLATE 12 18 FASTENERS INCLUDED CD
A - A840-01 -ZN CATALOG NUMBERING EXAMPLE:
*Can also be used with
Rung Spacing Material Fasteners
medium-wall (IMC) and
thick-wall (rigid) conduit. 09 - M - 0226-11 - CD
56

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

CLAMP BRACKET M T INSTALLATION FASTENERS

Permits attachment of clamps or other components to the cable COMPLETE CATALOG NUMBER
tray side rail. Conduit clamps are purchased separately. DESCRIPTION SIZE
ZN S6

PRODUCT FASTENER "-20 x 6' DS-0254-06-ZN DS-0254-06-S6


11/2 NUMBER OPTIONS THREADED
ROD
3/8"-16 x 12' DS-0255-12-ZN DS-0255-12-S6
1818 ZN S6 "-13 x 12' DS-0256-12-ZN DS-0256-12-S6
2
CATALOG NUMBERING EXAMPLE:
ROD "-20 DS-0237-02-ZN DS-0237-02-S6
Material Fasteners
T - 1818 -S6 COUPLING 3/8"-16 DS-0237-04-ZN DS-0237-04-S6
11/2 NUT "-13 DS-0237-05-ZN DS-0237-05-S6
"-20 DS-0102-03-ZN DS-0102-03-S6
CHANNEL NUT
W/ SPRING
3/8"-16 DS-0102-05-ZN DS-0102-05-S6
MAPLE CABLE BLOCKS "-13 DS-0102-07-ZN DS-0102-07-S6
"-20 DS-0103-03-ZN DS-0103-03-S6
Paraffin impregnated and furnished with 1/4" dia. fasteners. CHANNEL NUT
W/O SPRING
3/8"-16 DS-0103-05-ZN DS-0103-05-S6
Contact Legrand with quantities, cable dimensions, cable "-13 DS-0103-07-ZN DS-0103-07-S6
spacing, and cable tray system information. Can be custom
designed for a wide variety of applications. "-20 DS-8585-01-ZN DS-8586-01-S6
HEX NUT 3/8"-16 DS-8575-01-ZN DS-8554-01-S6
"-13 DS-8570-01-ZN DS-8574-01-S6
"-20 DS-8845-01-ZN DS-8929-01-S6
PRODUCT NUMBER FASTENERS INCLUDED FLANGED
HEX NUT
3/8"-16 DS-8524-01-ZN DS-8927-01-S6
0950 AS SPECIFIED "-13 DS-8644-01-ZN DS-8932-01-S6
SQUARE 1"w/ "HOLE DS-0113-01-ZN DS-0113-01-S6
CHANNEL 1"w/ 3/8"HOLE DS-0113-02-ZN DS-0113-02-S6
WASHER 1"w/ "HOLE DS-0113-03-ZN DS-0113-03-S6
" DS-8598-01-ZN DS-8674-01-S6
SLIP-ON LOCK NUT ZN S4 FLAT, ROUND
WASHER
3/8" DS-8596-01-ZN DS-8600-01-S6
" DS-8595-01-ZN DS-8657-01-S6
Allows the user to slip the nut onto a rod, without actually "-20 x " DS-8502-01-ZN DS-8720-01-S6
threading it. Ideal for when nuts must be added to a rod, but HEX HEAD
BOLT
3/8"-16 x 1" DS-8520-05-ZN DS-8694-05-S6
cannot be threaded due to previously-installed equipment.
"-13 x 1' DS-8515-15-ZN DS-8533-02-S6
PRODUCT NUMBER SIZE SLOTTED, "-20 x 3/4" DS-8540-02-ZN DS-8543-01-S6
SON 1/4 1/4"-20 ROUND-HEAD 3/8"-16 x 3/4" DS-8535-01-ZN DS-8542-02-S6
SCREW "-13 x 1'" DS-8678-04-ZN DS-8548-01-S6
SON 3/8 3/8"-16

SON 1/2 1/2"-13 FOR " ROD DS-0221-01-ZN* DS-0221-01-S6*


BEAM
CATALOG NUMBERING EXAMPLE:
CLAMP
FOR 3/8" ROD DS-0221-04-ZN DS-0221-04-S6
Fasteners
SON 3/8-ZN FOR " ROD DS-0221-06-ZN DS-0221-06-S6
Safe Load: *750 lbs.; 1100 lbs.; 1600 lbs. METALLIC FASTENERS
PLASTIC SAFETY SIGN

Sign measures 8"x12".

COMPLETE CATALOG NUMBER


P-0949-01

57

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH
AND SOLID BOTTOM

20" Fabricated cable tray fire stop sleeves from Legrand, combined
Loose collar slides

FIRE WALL PENETRATION SLEEVE M G T with Hilti over


Firestop products, are an economical alternative
sleeve after it
is placed in the wall
to the high cost of fabricating protective fire wall and floor
penetration sleeves in the field.
This firestop system provides a rigid support for cable tray
Fixed collar is in a UL classified system approved for fire wall and floor
welded to sleeve
penetrations. After
Cable trays are attached to both the sleeve is placed in the wall or floor,
theends
splice
of the sleeve using standard
loose collar slides over it. Hardware for the tray connection
plate connectors

only is included. Hardware required to mount sleeves to the


wall or floor is not included.
7/16" diameter holes
W*+6"
The Hilti forFire Block is a compressible fire stop brick, well-suited
3/8" hardware
(not included)
for installations where frequent cable changes may be required.
PRODUCT FASTENER Blocks are easily cut to fit any space, and can be removed and
H*+6"
NUMBER OPTIONS reinstalled when cable configurations change. When exposed to
fire, the blocks expand to lock the seal in place.
0440 CD S6
W*=Nominal Tray Width
Each cable tray firestop sleeve includes:
H*=Tray Side Rail Height
One penetration sleeve with flanges
SIDE VIEW
Hilti Fire Blocks
One Hilti Firestop Putty Stick
20"
Loose collar slides
over sleeve after it Hardware for cable tray connection to the wall sleeve:
is placed in the wall Hilti Fire Blocks

Wall Assembly - Metallic and fiberglass cable trays with two side rails.
(Gypsum Wall Shown)
Cables The Firestop kit includes two pairs of splice plates with
AdjustableCollar
Hilti Fire Blocks nuts &Fixed
bolts;
Collar
316 stainless steel is recommended for use
Penetration Sleeve
with fiberglass systems.
Cables Floor Assembly
Fixed collar is
welded to sleeve NUMBER OF HILTI FIRE BLOCKS INCLUDED WITH EACH SLEEVE
Cable trays are attached to both
ends of the sleeve using standard
splice plate connectors SLEEVE
Masonry Anchors
SIDE RAIL HEIGHT (IN.)
Adjustable Collar (Not Included)
Fixed Collar
Wall Anchors
(Not Included)
WIDTH 4 5 6 7
END VIEW 6
Penetration Sleeve
2 2 3 3
W*+6" 7/16" diameter holes 9 3 3 4 4
for 3/8" hardware
(not included)
12 3 4 5 6
18 5 6 7 8
H*+6"
24 6 8 9 11
30 8 10 12 14
36 9 12 14 16
W*=Nominal Tray Width
H*=Tray Side Rail Height

OUTDOOR CONVERSION FOR WALL PENETRATION (0434)


See page 51.

UL classified for use with:


2-hr concrete or block walls
METALLIC FIRESTOP SYSTEMS

Hilti Fire Blocks


2-hr concrete floors
all Assembly
ypsum Wall Shown) 1-hr gypsum walls
Cables 2-hr gypsum walls
djustableCollar
Fixed Collar
Penetration Sleeve

Floor Assembly

Masonry Anchors
Adjustable Collar (Not Included)
l Anchors
t Included)

Penetration Sleeve

58

WWW.LEGRAND.US/CABLOFIL
PW CABLE TRAY
LADDER, TROUGH W*=Nominal Tray Width
W*=Nominal
H*=Tray Side Rail HeightTray Width
AND SOLID BOTTOM H*=Tray Side Rail Height

Floor Firestop Sleeve Example Floor Firestop Sleeve Example


0440 product used as a floor sleeve per UL assembly 0440 product used as a floor sleeve per UL assembly
W-L-3226 and C-AJ-3232 F-A-3022
Hilti Fire Blocks
Hilti Fire Blocks
Wall Assembly
WallShown)
(Gypsum Wall Assembly
(Gypsum Wall Shown)
Cables
AdjustableCollar Cables
Hilti Fire Blocks AdjustableCollar
Hilti Fire Blocks Fixed Collar
Penetration Sleeve Fixed Collar
Penetration Sleeve

Cables Floor Assembly


Cables Floor Assembly

Masonry Anchors
Adjustable Collar Masonry Anchors
(Not Included)
Wall Anchors Adjustable Collar (Not Included)
Fixed Collar Wall Anchors
(Not Included)
Fixed Collar (Not Included)
Penetration Sleeve
Penetration Sleeve

WALL/FLOOR SLEEVE DESCRIPTION TECHNICAL DATA


Designed for single runs of cable tray, having a height and Construction.............Arc Welded
width to match the tray system specified. One end of the 20 inch
Sleeve
sleeve has a flange attached 6 inches from the end, while the
Dimensions...............20" x Tray Width x Tray Height
flange for the other end is floating and is free to slide directly
against the face of the wall as needed. The 20 inch length of the Flange
Dimensions...............(Tray Width + 6") x (Tray Height + 6")
sleeve will accommodate a wall thickness of up to 8 inches. A
wall thickness of 8 inches will result in the sleeve protruding 6 UL Classification.......Qualifies for use as an equipment grounding
inches from each side of the wall. Both ends of the sleeve are conductor per N.E.C. 392.7. Cross-sectional area
and amperage ratings are based on the cable tray
punched with holes for attaching cable tray splice plates or
system attached to the sleeve.
hardware needed for the tray system specified.

INSTALLATION HILTI FIRE BLOCKS INSTALLATION


The opening in the wall should be within 1 inch of the nominal Walls: Hilti Fire Blocks shall be installed with 5" dimension
height and width of the cable tray. The flanges of the sleeve projecting through and centered within wall assembly.
have 7/16" diameter mounting holes for attachment to the wall Floors: Hilti Fire Blocks shall be installed with 5" dimension
using 3/8" diameter hardware. Hardware for wall attachment is projecting through opening, flush with the top surface of
not included. After the sleeve is mounted in the wall or floor, sleeve or recessed within sleeve at any level above the top
the cable trays on either side of the sleeve can be connected surface of floor.
using the hardware supplied with the sleeve. When the trays
Fire blocks fill the annular space between the cables and the
are in place, the cables should be pulled through the wall and
sleeve. Fire Blocks may be cut to match the profile of cables
sleeve as needed. After all of the cables are installed in the
or to fit opening. Any voids should be filled with 0618 Firestop
tray, install the Fire Blocks as described. Any voids between
Putty Stick.
cables should be filled with the Firestop Putty Stick.

METALLIC FIRESTOP SYSTEMS

WALL PENETRATION SLEEVE CATALOG NUMBERING EXAMPLE:


CONNECTOR SYSTEM NO. PRODUCT NO.
6 M 2 - 0 4 4 0 - 3 6 - CD FASTENER
OPTIONS
SIDE RAIL
HEIGHT WIDTH CD
4 4" 06 6" S6
FITTING SERIES 09 9"
5 5" This item must 12 12"
6 6"
MATERIAL be specified as 18 18"
7 7" M G L T SERIES 2
24 24"
30 30"
36 36"
59

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL


PW CABLE TRAY
LADDER, TROUGH W*=Nominal Tray Width
W*=Nominal
H*=Tray Side Rail HeightTray Width
AND SOLID BOTTOM H*=Tray Side Rail Height

Floor Firestop Sleeve Example Floor Firestop Sleeve Example


0440 product used as a floor sleeve per UL assembly 0440 product used as a floor sleeve per UL assembly
W-L-3226 and C-AJ-3232 F-A-3022
Hilti Fire Blocks
Hilti Fire Blocks
Wall Assembly
WallShown)
(Gypsum Wall Assembly
(Gypsum Wall Shown)
Cables
AdjustableCollar Cables
Hilti Fire Blocks AdjustableCollar
Hilti Fire Blocks Fixed Collar
Penetration Sleeve Fixed Collar
Penetration Sleeve

Cables Floor Assembly


Cables Floor Assembly

Masonry Anchors
Adjustable Collar Masonry Anchors
(Not Included)
Wall Anchors Adjustable Collar (Not Included)
Fixed Collar Wall Anchors
(Not Included)
Fixed Collar (Not Included)
Penetration Sleeve
Penetration Sleeve

WALL/FLOOR SLEEVE DESCRIPTION TECHNICAL DATA


Designed for single runs of cable tray, having a height and Construction.............Arc Welded
width to match the tray system specified. One end of the 20 inch
Sleeve
sleeve has a flange attached 6 inches from the end, while the
Dimensions...............20" x Tray Width x Tray Height
flange for the other end is floating and is free to slide directly
against the face of the wall as needed. The 20 inch length of the Flange
Dimensions...............(Tray Width + 6") x (Tray Height + 6")
sleeve will accommodate a wall thickness of up to 8 inches. A
wall thickness of 8 inches will result in the sleeve protruding 6 UL Classification.......Qualifies for use as an equipment grounding
inches from each side of the wall. Both ends of the sleeve are conductor per N.E.C. 392.7. Cross-sectional area
and amperage ratings are based on the cable tray
punched with holes for attaching cable tray splice plates or
system attached to the sleeve.
hardware needed for the tray system specified.

INSTALLATION HILTI FIRE BLOCKS INSTALLATION


The opening in the wall should be within 1 inch of the nominal Walls: Hilti Fire Blocks shall be installed with 5" dimension
height and width of the cable tray. The flanges of the sleeve projecting through and centered within wall assembly.
have 7/16" diameter mounting holes for attachment to the wall Floors: Hilti Fire Blocks shall be installed with 5" dimension
using 3/8" diameter hardware. Hardware for wall attachment is projecting through opening, flush with the top surface of
not included. After the sleeve is mounted in the wall or floor, sleeve or recessed within sleeve at any level above the top
the cable trays on either side of the sleeve can be connected surface of floor.
using the hardware supplied with the sleeve. When the trays
Fire blocks fill the annular space between the cables and the
are in place, the cables should be pulled through the wall and
sleeve. Fire Blocks may be cut to match the profile of cables
sleeve as needed. After all of the cables are installed in the
or to fit opening. Any voids should be filled with 0618 Firestop
tray, install the Fire Blocks as described. Any voids between
Putty Stick.
cables should be filled with the Firestop Putty Stick.

METALLIC FIRESTOP SYSTEMS

WALL PENETRATION SLEEVE CATALOG NUMBERING EXAMPLE:


CONNECTOR SYSTEM NO. PRODUCT NO.
6 M 2 - 0 4 4 0 - 3 6 - CD FASTENER
OPTIONS
SIDE RAIL
HEIGHT WIDTH CD
4 4" 06 6" S6
FITTING SERIES 09 9"
5 5" This item must 12 12"
6 6"
MATERIAL be specified as 18 18"
7 7" M G L T SERIES 2
24 24"
30 30"
36 36"
59

For detailed material and finish descriptions, see page 6. WWW.LEGRAND.US/CABLOFIL