Professional Documents
Culture Documents
III) is based on the load current control and only needs load
current measurements in addition to the measurements required
in Method I. The fourth control method (Method IV) studied is
a combination of Methods II and III. Hence, it needs both the
supply voltage magnitude and the load current measurements.
Methods I and II are suitable for drives where current sensors
are not otherwise used. Methods I and III are suitable for
applications where the magnitude measurements of supply
voltages are not applied.
All the methods are easy to implement and do not require
complicated computing. In addition, the simulation and mea- Fig. 2. Input phase current space-vectors of the IMC line bridge: (a) i >0
surement results will show that the methods produce line cur- and (b) i < 0. (c) Synthesis of the input current reference vector.
rents with remarkably lower distortion than full-bridge diode
rectifiers. The results will also show that Methods I and III
cannot compensate the effects of the supply voltage harmonics
as effectively as Methods II and IV because in those methods
ideal supply voltages are assumed.
A. Space-Vector Modulation
The indirect space-vector modulation used for MC has been
presented in [4] and is directly suitable for IMC as presented
in [7]. It is based on the space-vectors of input voltages and
currents and output voltages, , , , respectively Fig. 3. (a) Output phase voltage space-vectors of the IMC load bridge. (b) Syn-
thesis of the output voltage reference vector.
(1)
(3)
where . (5)
In (2) , , and are the switching functions of the
IMC line bridge and is their space-vector. The allowed The line bridge is always modulated to produce maximum dc
switching states producing the input current space-vectors are link voltage so that [4], [7]
presented in Fig. 2. Reference vector is synthesized as a
time average of adjacent vectors and , whose duty cycles (6)
are and , respectively, as presented in Fig. 2(c).
In (3) , , and are the switching functions of Thus, the average link voltage on one modulation period is
the IMC load bridge and is their space-vector. The allowed
switching states producing output voltage space-vectors are pre- (7)
sented in Fig. 3(a). Reference vector is synthesized as a
time average of adjacent vectors and , whose duty cycles The calculation of the duty cycles is based on the modulation
are and , respectively, as presented in Fig. 3(b). index , which is equal to the modulation index of conventional
When the line bridge is assumed to be ideal the instant active voltage source inverter:
powers of line and dc link are equal. By substituting (2) into the
power equation it is possible to define the instant dc link voltage
(8)
[7]
(4) where in linear modulation [4], [7]. Substituting (7)
JUSSILA AND TUUSA: COMPARISON OF SIMPLE CONTROL STRATEGIES 141
(9)
When the separate duty cycles of the line and load bridges, ,
and , , respectively, are combined the result is four ac-
tive duty cycles [4], [7], so that the output voltages desired are
produced directly from the three-phase input voltages
(10a)
(10b)
(10c)
(10d) Fig. 4. Block diagram of the IMC control methods.
(13)
142 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
C. Method III
(15) In the third control method of the IMC (Method III) a load
current feedback loop is added to the open-loop control system
where again it is assumed that 1. of Method I as presented in Fig. 4. The supply voltages are not
Also in this case the supply voltages , , and are measured, thus the calculation of the modulation index is based
measured instead of capacitor voltages as presented in Fig. 4. on the assumption of ideal sinusoidal mains. The synchroniza-
To filter modulation frequency components the first order tion of the line current reference vector is also defined with PLL
digital low-pass filter with the cut-off frequency of 3.18 kHz as in Method I.
was used in the software implementation. The reason for the The current references are given in two-axis form in
arrangement is that when the zero crossings are detected from stationary coordinates and . The measured load
the supply voltage it is easier to measure the voltage magnitudes currents are and , which are used to define the actual
from the same point than arrange another voltage measurement two-axis currents and . Both current controllers are iden-
setup. Naturally, the phase differences between the higher order tical discrete time antiwindup PI-controllers [7]. The PI-con-
voltage harmonics of the supply and capacitor voltages are trollers are used because they can be considered to be the basic
more remarkable and better results for load magnitudes could current control strategy when current control is an inner loop of
be obtained if the capacitor voltages were used [13]. cascade closed-loop control system in electric drives.
The angle of the input current reference vector is defined ex- The tuning of the controllers is based on the time constant
actly same as in Method I, i.e., with zero crossing detection of of the load on such a bandwidth that the frequency components
and PLL with 1. The measured voltage magni- reflected from the supply can be damped. The time constant of
tudes are used only in the calculation of the modulation index as the simulated load presented in Section IV is 0.33 ms, which is
presented in (15). Thus, the system is similar to those presented also the value of the integration time of the controller. To attain
and analyzed in [9], [11], [17], and [18]. the requirement of high bandwidth the gain of the controller was
With supply voltage feedforward the stability of the matrix set to 50. Thus, the theoretical bandwidth of the closed-loop cur-
converter system is an essential question [13], [17][19]. The rent control is 800 Hz, which in many practical drives can be too
JUSSILA AND TUUSA: COMPARISON OF SIMPLE CONTROL STRATEGIES 143
Fig. 6. Supply phase voltages in simulations: (a) waveforms, (b) spectrum, and (c) locus.
TABLE I
DISTORTED SUPPLY VOLTAGE
included is the 11th order. The relative magnitudes of harmonics
are the maximum allowed voltage harmonics allowed in the
standard [20] and their phase angles are similar to the phase
angles of the harmonics in industrial mains distorted by three-
phase diode rectifiers with capacitive loads. A total harmonic
distortion (THD) of the supply voltage is about 8.5%, which is
0.5% unit over the limit of 8% defined in [20].
high but now needed to damp the frequency components caused B. Simulation Model
by the distorted supply voltage. Thus, the capability of Method Simulations were performed with a combination of Simplorer
III depends on the controller tuning, which cannot necessarily and Matlab Simulink softwares. In the simulations -connected
always be done with the adequate bandwidth. As Method II, RL load with resistors of 30 and inductors of 10 mH was used
Method III should also produce more distorted supply currents that gives the load power of 3.9 kVA when the voltage ratio is the
than Method I. maximum 0.866. The modulation frequency was 5 kHz and the
modulator model was updated twice in one modulation period
D. Method IV [16].
The fourth IMC control method (Method IV) is a combination The prototype and type filter used was originally de-
of Methods II and III, as presented in Fig. 4. Thus it contains signed for 5-kVA rated power [16]. Thus, the supply filter design
both the supply voltage and load current measurements. Method was made supposing ideal sinusoidal supply conditions and its
IV should prevent the reflection of supply harmonics to the load main point was to fulfill the EMC requirements [21]. Desired
most effectively among the methods presented here. It should THDs of the supply current and filter capacitor voltage were
also produce the most distorted line currents. 4% and 5% when the frequency components up to 500 kHz
were taken into account. The resonance frequency was set to
IV. SIMULATIONS 1049 Hz. In the 5-kVA converter it means 2.3-mH (2.3%) in-
ductors and 10- F (10%) capacitors in -connection [21]. In
A. Distorted Supply Voltage the simulations, the damping and dc resistances of the real in-
In the typical low voltage industrial network presented in ductors were modelled connecting resistances of 88 in par-
Fig. 5 the impedance consists mostly of impedance caused allel and 55 m in series with each ideal inductance of 2.3 mH.
by distribution transformer and medium and high voltage net- The impedance of the power supply used in the measurements
works. Compared to the impedances , , of consisted of 0.03- resistor and 0.1-mH inductance in series
low voltage network are usually negligible, i.e., and these values were also used in the simulations to model the
, , , and . When power supply impedance.
the high frequency EMC in low voltage network is considered
the filtering caused by is not necessarily adequate C. Simulation Results
to provide safe operation of load in common case. Thus, As an ideal starting point to the other cases the simulation
or type filters of an IMC drive cannot be reduced to pure results with ideal sinusoidal supply voltages are presented in
type filter even though the would sometimes offer ade- Fig. 7 when Method I is applied. The voltage transfer ratio is 0.8
quate impedance for filtering, i.e., the point of common coupling 260 V 325 V and the load frequency is 40 Hz. As can be
(PCC) of the IMC is not generally in the supply side of the seen, the method, containing only the discrete-time space-vector
but inside the industrial network. Thus, in this study type modulator, produces slight distortion to currents and load volt-
line filter is applied. ages even with sinusoidal supply voltage because of inaccu-
The components of distorted supply voltage used are pre- racies produced by sampling, averaging of space-vector refer-
sented in Table I. Its relative phase voltage waveforms, spec- ences and discrete calculation. The spectra are presented with
trum, and locus are presented in Fig. 6. The highest harmonic the frequency resolution of 10 Hz up to 1 kHz.
144 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
TABLE II
SIMULATION RESULTS
Comparing the results of the control methods presented it can Fig. 14. Measured waveforms and spectra (f = 10 Hz) of Method I with
sinusoidal supply voltage when f = 40 Hz: (a) supply voltage u and current
be observed that the supply voltage feedforward of Method II i , (b) spectrum of i , (c) waveform of load current i , and (d) spectrum of i .
can reduce the load current distortion considerably but not to-
tally. The first reason is that the magnitude of is used instead
of capacitor voltages. As an example Method IV ( 40 Hz) To attain the same current with the same voltage transfer ratio
was simulated using the capacitor voltage measurements when as in the simulations the -connected load consisted of
the THDs for , , and were 21.5%, 5.3%, and 3.2%, 27- resistors and 10-mH inductors that gives the load power
respectively, so that the effect of voltage measurement point is of 3.9 kVA with the voltage ratio of 0.866. filter parameters
not very remarkable in this case. The second reason is that cur- were 2.3 mH and 10 F as in the simulations.
rent is not modulated along the instantaneous supply voltage The control system was implemented by microcontroller
vector, which would be required to attain exactly constant output (Motorola MPC555), which defines the switching states and
power as presented in Section III-B. However, that would prob- their durations after every 100 s, i.e., it updates the modulator
ably cause stability problems as presented in [13], [17], and [19]. twice in the modulation period [16]. All control methods were
The current control of Method III cannot alone reduce the dis- implemented with the microcontroller. The required currents
tortion as well as Method II. To achieve sufficient compensation and voltages were measured using the ten bits A/D converters
with current control it has to be combined to the supply voltage of the microcontroller. The current filters and controllers of
feedforward as in Method IV. Open-loop control of Method I Methods III and IV had the same parameters as in the simula-
produces the most sinusoidal supply current but on the other tions.
hand its load current is highly distorted. As presented in Fig. 13, the size of the prototype is not
minimized but the aim has been to build a prototype easy to
V. MEASUREMENTS modify and test different control systems. The microcontroller
and driver boards are the general boards of the institute. In
A. IMC System addition, supply filter inductor and both line and load bridges
The IMC prototype is described in [16]. Its nominal load have higher current ratings than required by the system.
power is 5 kVA and modulation frequency is 5 kHz. Its block
diagram is presented in Fig. 12 and the prototype is shown in B. Measurement Results
Fig. 13. In the measurements, the distorted supply voltage with Measurement results of Method I with ideal sinusoidal
the amplitude of the fundamental component of 325 V was not supply voltage are presented in Fig. 14 and in Table III, where
available thus 305 V was used instead. Its locus and the relative all THDs are calculated up to 2 kHz. The amplitude of the
magnitudes of the harmonic components are the same as in the sinusoidal supply voltage was 305 V. Method I was also
simulations presented in Fig. 6 and in Table I. tested with distorted supply voltage. Measurement results are
146 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007
TABLE III
MEASUREMENT RESULTS
Fig. 19. Loci of currents with Method I, when f = 40 Hz: (a) simulated and
Fig. 21. Loci of currents with Method IV, when f = 40 Hz: (a) simulated and
(b) measured line currents; (c) simulated and (d) measured load currents.
(b) measured line currents; (c) simulated and (d) measured load currents.
VI. CONCLUSION
First, the conduction of harmonics through an MC was ana-
lyzed using space-vector presentation. After that, four control
methods of the IMC were presented and compared in simula-
tions and measurements. The methods required neither compli-
cated computing nor complex measurements.
It was observed that the open-loop control method of the
IMC without information of supply voltage magnitude or load
current produced most distorted load currents. The current
Fig. 20. Loci of currents with Method II, when f = 40 Hz: (a) simulated and feedback control could not alone compensate the effects of
(b) measured line currents; (c) simulated and (d) measured load currents. supply voltage harmonics on the load current sufficiently when
the supply voltage was assumed to be ideal. In addition, the cur-
rent controllers cannot necessarily be tuned in all drives so that
Method II does not contain current control. The differences be- adequate bandwidth is achieved. The sufficient compensation
tween simulation and measurement results are caused by the was achieved only with the methods where the measured supply
non-idealities of the realization. The accuracy of the voltage voltages were used in the calculation of modulation index. In
measurement in the prototype is worse than assumed in the sim- all cases, the compensation increased line current distortion.
ulations therefore Methods II and IV are not as effective in the The analysis presented is valid for both DMC and IMC. Thus,
measurements as in the simulations even though the difference the control methods presented as well as their comparison are
is quite small. In addition, stray inductances, delays, non-ideal also applicable to DMC.
148 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 22, NO. 1, JANUARY 2007