You are on page 1of 6

Double Circuit Transmission Line Fault Distance Location using

Artificial Neural Network

Anamika Jain and A.S.Thoke R. N. Patel


Department of Electrical Engineering Department of Electrical and Electronics Engineering
National Institute of Technology S. S. College of Engg. and Technology
Raipur, India Bhilai, India
anamika_jugnu@yahoo.com, asthoke@yahoo.co.in ramnpatel@gmail.com

AbstractDistance relays used for protection of transmission over reach due to DC offset current. Also these schemes
lines have problems of under-reach, over-reach and mal- require remote end information if the transmission line is
operation due to high impedance faults. Further the problem is fed from sources at both the ends. These are required to
compounded when the distance relays are used for protection minimize the errors due to the remote end infeed and load
of double circuit transmission lines due to effect of zero
flow variations. Travelling wave schemes have problems
sequence mutual coupling. Different types of faults on a
protected transmission line should be located correctly. This with faults close to the bus and faults with close-to-zero
paper presents a single neural network for fault distance fault inception angle.
location for all the ten types of faults (3 LG, 3 LLG, 3 LL, 1 One of the new tools recently introduced into power
LLL) in both the circuits of a double circuit transmission line system protection is Artificial Neural Networks (ANN).
fed from sources at both the end. This technique uses only one ANN is powerful in pattern recognition, classification and
end data and accurate fault distance location is achieved after generalization. Neural Networks are useful for power system
one cycle from the inception of fault. The proposed Artificial applications because they can be trained with off-line data.
Neural Network (ANN) based Fault Distance Locator uses ANNs possess excellent features such as noise immunity,
fundamental components of three phase current signals of both
robustness and fault tolerance. Therefore, the decision made
the circuits & three phase voltage signals to learn the hidden
relationship in the input patterns. An improved performance is by an ANN-based relay will not be seriously affected by
obtained once the neural network is trained suitably, thus variations in system parameters. Consequently, various
performing correctly when faced with different system ANN-based algorithms have been investigated and
parameters and conditions i.e. varying fault type, fault implemented in power systems in recent years [6]. Faulty
location, fault resistance, fault inception angle, presence of phase selection and distance location using neural network
mutual coupling and remote source infeed. for single circuit transmission lines has been reported in [7].
Fault classification for double-circuit lines using self-
Keywords- Artificial Neural Network; Double circuit fault organization mapping feature neural network is presented in
distance location; Mutual coupling; Transmission line; High
[8], however it does not locate the faults. The work presented
impedance fault
in [9] deals with the compensation of fault resistance using
ANN for determination of location of fault. A single line to
I. INTRODUCTION ground fault location method employing wavelet fuzzy
Fault location estimation is a desirable feature in any neural network in the distribution lines of an industrial
protective relaying scheme for transmission lines. By system is proposed in [10], other types of fault have not been
accurately locating a fault, the amount of time spent by line considered. An adaptive distance protection of double circuit
repair crews in searching for the fault can be kept at a line using zero sequence thevenin equivalent impedance and
minimum. Locating the fault on the transmission line compensation factor for mutual coupling is presented in [11].
accelerates line restoration & maintains system stability. Back propagation method based on Levenberg-Marquardt
Different types of algorithms for finding fault location on optimisation technique is used to locate the faults in [12]. In
EHV/UHV transmission lines have been developed and a companion paper [13], fault distance location for single
proposed over the years. These algorithms may be broadly line to ground faults on double circuit transmission lines
classified as (i) those computing power frequency current using neural network has been reported.
and voltage phasors to find impedance and hence fault This paper presents an application of artificial neural
location [1, 2], (ii) those using differential equations of line network for fault distance location in a double end fed
and estimating line parameters [3] and (iii) those based on double circuit transmission line for all the ten types of shunt
the traveling wave which uses one terminal data or two faults using only one terminal data considering the effects of
terminal data [4]-[5]. Most of the reactance-based schemes mutual coupling, remote source infeed, varying fault type,
suffer from under reach due to high impedance fault and fault location, fault resistance and fault inception angle. The

978-1-4244-5612-3/09/$26.00 2009
c IEEE 13
algorithm employs the fundamental components of three coupling between the two circuits. We can see that DC offset
phase voltages and the six phase currents of the two parallel current is also present in the phase current signals. Due to
lines at one end only. The performance of the proposed this the conventional relays detect the healthy phases also to
scheme has been investigated by a number of offline tests. be faulty and may thus mal-operate. This is not desirable,
The simulation results show that all the ten type of faults only the faulted circuit should be disconnected while power
can be correctly located after one cycle from the inception continues to flow through the healthy circuit with reduced
of fault. The algorithm is immune to effects of mutual power transfer. Further, when high fault resistance is
coupling, remote source infeed, variation in fault type, fault involved in ground faults at far end of the line, the
conventional distance relays under-reach, and over-reach due
location, fault resistance and fault inception angle. The
to the effect of weakly damped DC offset current and/or
technique does not require communication link to retrieve
remote end source infeed to fault branch.
the remote end data and nor zero sequence current Preprocessing is useful method that significantly reduces
compensation for healthy phases. Such comprehensive work the size of the neural network and improves the performance
has not been reported earlier for fault distance location of and speed of training process. Three phase voltage and six
double circuit line. current input signals were sampled at a sampling frequency
of 1 kHz and further processed by simple 2nd-order low-pass
II. POWER SYSTEM NETWORK SIMULATION
Butterworth filter with cut-off frequency of 400 Hz.
The system studied is composed of 220KV double circuit Subsequently, one full cycle Discrete Fourier transform is
transmission line 100 km in length, connected to sources at used to calculate the fundamental components of voltages
each end; its single line diagram is shown in Fig. 1 [13]. and currents. The input signals were normalized in order to
Short circuit capacity of the equivalent thevenin sources on make the ANN input level (1) [14].
two sides of the line is considered to be 1.25 GVA., Xs/Rs
ratio of source is 10. The transmission line is simulated using III. ANN BASED FAULT DISTANCE LOCATOR
distributed parameter line model using MATALB 7.01 The basic procedure used to implement a neural network
software as shown in Fig. 2. Double circuit transmission line in the fault distance location algorithm in double circuit
parameters are shown in Table I. transmission line is described below.
A. Selecting the right architecture
One factor in determining the right size and structure for
the network is the number of inputs and outputs that it must
have. The lower the number of inputs, the smaller the
network can be. However, sufficient input data to
characterize the problem must be ensured. Only the
magnitudes recorded at one end of the line are used. The
Figure 1. Single line diagram of power system under study. inputs to distance relays are mainly the voltages and
currents. Hence the network inputs chosen here are the
magnitudes of the fundamental components (50 Hz) of three
TABLE I. DOUBLE CIRCUIT LINE PARAMETERS phase voltages and six currents measured at the relay
Positive sequence resistance R1, /KM 0.01809 location. As the basic task of fault location is to determine
Zero sequence resistance R0, /KM 0.2188 the distance to the fault, the distance to the fault, in km with
Zero sequence mutual resistance R0m, /KM 0.20052 regard to the total length of the line, should be the only
Positive sequence inductance L1, H/KM 0.00092974 output provided by the fault location network. Thus the
Zero sequence inductance L0, H/KM 0.0032829
input X and the output Y for the fault location network are:
Zero sequence mutual inductance L0m, H/KM 0.0020802
Positive sequence capacitance C1, F/KM 1.2571e-008
Zero sequence capacitance C0, F/KM 7.8555e-009 X = [Va ,Vb ,Vc , I a1 , I b1 , I c1 , I a 2 , I b 2 , I c 2 ]
(1)
Zero sequence mutual capacitance C0m, F/KM -2.0444e-009
Y = Lf[ ] (2)
For example a double phase to ground fault A1B1N- The major issue in the design of ANN architecture is to
double phase to ground fault occurs at 10 KM from end S on ensure that when choosing the number of hidden layers and
circuit 1 of the configuration shown in Fig.1 at 60 ms with
number of neurons in the hidden layers, its attribute for
0 (zero) fault resistance and i=0 (zero degree) fault
generalization is well maintained. In this respect, since there
inception angle and s= 45, pre-fault power flow angle. The
three phase voltage and current waveforms is shown in Fig. is no parametric/theoretic guidance available, the design has
3. As expected, a current is also induced in the A2 & B2- to be based on a heuristic approach [15].
phases of healthy circuit 2 due to zero sequence mutual

14 2009 World Congress on Nature & Biologically Inspired Computing (NaBIC 2009)
Figure 2. Power system model simulated in MATLAB 7.5 Simulink software.
3 Phase Phase Voltage (Volts)

5
x 10
2
Ref.
1 Va
Vb
0 Vc
-1

-2
0 20 40 60 80 100 120 140 150
Faulty ckt-1 (Amp.)

Ref.
Phase Currents of

5000
Ia1
Ib1
0 Ic1

-5000
0 20 40 60 80 100 120 140 150
of Healthy ckt-2 (Amp.)

1500
Ref.
1000
Phase Currents

Ia2
500 Ib2
0 Ic2
-500
-1000
-1500
0 20 40 60 80 100 120 140 150
Time in ms

Figure 3. Three phase voltages & currents during double phase to ground fault on ckt-1 at 10 KM from SS-1 end at 60 ms, Rf=0, i=0 and s= 45.

The ANN architecture, including the number of inputs to functions, the tansig function was chosen as transfer function
the network and the number of neurons in hidden layers, is for the hidden layer, and pure linear function purelin in the
determined empirically by experimenting with various output layer.
network configurations. Through a series of trial and error,
and modifications of the ANN architecture, the best
IW{1,1} LW{2,1}
performance is achieved by using a three layer neural
network with 9 inputs and 1 output as shown in Fig. 4. The
number of neurons for the hidden layer is 40. The final b{1} b{2}
determination of the neural network requires the relevant
transfer functions in the layers to be established. After 9 Inputs 40 Neurons 1 Output
analysing the various possible combinations of transfer Figure 4. Structure of ANN based fault distance locator.
functions normally used, such as logsig, tansig and linear

2009 World Congress on Nature & Biologically Inspired Computing (NaBIC 2009) 15
B. Learning rule selection
The back-propagation learning rule is used in perhaps
8090% of practical applications. Improvement techniques
can be used to make back-propagation more reliable and
faster. The back-propagation learning rule can be used to
adjust the weights and biases of networks to minimize the
sum-squared error of the network. This is done by
continually changing the values of the network weights and
biases in the direction of steepest descent with respect to
error. The simple back-propagation method is slow because
it requires small learning rates for stable learning,
improvement techniques such as momentum and adaptive
learning rate or an alternative method to gradient descent,
LevenbergMarquardt optimisation, can be used. Various Figure 5. Training of ANN based fault distance locator for all the ten
techniques were applied to the different network types of faults in both the circuits of transmission line.
architectures, and it was concluded that the most suitable
epochs to 4.66127e-04 in around half an hour time as shown
training method for the architecture selected was based on
the LevenbergMarquardt (Trainlm) optimization technique. in Fig. 5. Once the network is trained sufficiently and
suitably with large training data sets, the network gives the
C. Training process correct output after one cycle from the inception of fault.
To train the network, a suitable number of representative
examples of the relevant phenomenon must be selected so
that the network can learn the fundamental characteristics of IV. TEST RESULT OF ANN BASED FAULT DISTANCE
the problem and, once training is completed, provide correct LOCATOR
outputs in new situations not used during training. To obtain Once training was completed, ANN based Fault distance
enough examples to train the network, a software package locator was then extensively tested using independent data
MATLAB 7.01 is used. Using SIMULINK &
sets consisting of fault scenarios never used previously in
SIMPOWERSYSTEM toolbox of MATLAB all the ten
types of fault at different fault locations between 0-100% of training. For different faults of the validation/test data set,
line length and fault inception angles 0 & 90 have been fault type, fault location, fault resistance and fault inception
simulated as shown below in Table II. The total number of angle were changed to investigate the effects of these factors
ground faults simulated are 12x10x2x3 = 720 & 8x10x2 = on the performance of the proposed algorithm. The network
160 thus total fault cases are 880 and from each fault cases was tested and performance was validated by presenting all
ten numbers of post fault samples have been extracted to the ten types of fault cases with varying fault locations
form the training data set for neural network. Thus the total (Lf=0-90KM), fault resistances (Rf=0-100) and fault
number of patterns generated for training are 8800 patterns. inception angles (i=0-360). As shown in table III all the
TABLE II. TRAINING PATTERNS GENERATION
faults cases are correctly located. Fig. 6-9 shows the output
of the fault distance locator for different types of faults. It is
Parameter Set value clear from these figures that all the faults were correctly
LG: A1N, A2N, B1N, B2N, C1N, C2N
LL: A1B1, A2B2, B1C1, B2C2, A1C1, located after one cycle time from the inception of fault.
Fault type
A2C2 Table III shows some of the test results of ANN based
LLG: A1B1N, A2B2N, B1C1N, fault locator under different fault conditions. It can be seen
B2C2N, A1C1N, A2C2N
LLL: A1B1C1, A2B2C2 that all results are correct with reasonable accuracy. At
various locations different types of faults were tested to find
Fault location (Lf in KM) 1, 10, 20, 30, 80 and 90 km
out the maximum deviation of the estimated distance Lf
Fault inception angle (i) 0 & 90 measured from the relay location, from the actual fault
location La. Then the resulted estimated error e is
Fault resistance (Rf) 0, 50 & 100
expressed as a percentage of total line length L as:
Pre-fault power flow angle
45
(s)
L f La
e= 100%
The ANN based fault distance locator was trained using L (3)
LevenbergMarquardt training algorithm using neural
network toolbox of Matlab. This learning strategy converges In all the fault cases, the results have shown that the errors
quickly and the mean squared error (mse) decreases in 300 in locating the fault are less than -7% to +1.97%.

16 2009 World Congress on Nature & Biologically Inspired Computing (NaBIC 2009)
TABLE III. TEST RESULTS OF ANN BASED FAULT LOCATOR
Fault Fault
Fault Calculated
Fault Inception Location Error
Resistance Output
type angle La e (%)
Rf () Lf (KM)
i () (KM)
A1N 45 80 67 64.470 -2.53
A2N 90 90 77 76.447 -0.553
B1N 225 90 88 87.024 -0.976
B2N 270 80 89 88.624 -0.376
C1N 360 95 95 92.405 -2.595
C2N 180 70 38 35.449 -2.551
Figure 6. Test result for B1-N fault at 89Km source S end with A1B1 135 - 5 4.435 -0.565
Rf=80, i=270 (75ms fault inception time) & s=45. A2B2 0 - 15 15.066 0.066
B1C1 360 - 33 33.181 0.181
B2C2 135 - 90 89.490 -0.51
C1A1 90 - 22 22.144 0.144
C2A2 315 - 64 64.545 0.545
A1B1N 135 30 85 82.955 -2.045
A2B2N 45 60 57 56.459 -0.541
B1C1N 0 10 35 34.606 -0.394
B2C2N 270 80 89 88.632 -0.368
C1A1N 315 0 4 5.3833 1.3833
C1A1N 225 30 58 50.838 -7.162
C2A2N 90 40 24 20.105 -3.895
C2A2N 360 95 63 62.551 -0.449
A2B2C2 180 - 15 12.418 -2.582
Figure 7. Test result for A1C1 fault at 22Km from source S end at A2B2C2 360 - 85 86.973 1.973
i=90 (65ms fault inception time) & s=45.
V. COMPARISON WITH THE EXISTANG SCHEMES
The salient features of some of the existing ANN based
fault location schemes and the proposed scheme are
presented in Table IV. The proposed scheme has several
advantages : a single ANN for all the ten types of faults in
both the circuits, wider range of fault resistance and fault
inception angle, remote source infeed and mutual coupling
effects considered. Accuracy of the algorithm is good in
most of the fault cases as shown in Table III except in one
case wherein it is 7%. Response time is 1 cycle comparable
to the conventional distance relay.
Figure 8. Test result for A1B1N fault at 57KM from source S end at VI. CONCLUSIONS
Rf=60 , i=45 (62.5 ms fault inception time) & s=45.
An accurate neural network based algorithm for fault
distance location on double circuit transmission line fed
from sources at both ends is presented covering all 20 types
of faults in both the circuits. The algorithm employs the
fundamental components of three line voltages and the six
line currents of the two parallel lines at one end only. The
algorithm determines fault distance location after one cycle
from the inception of fault. The algorithm effectively
eliminates the effect of varying fault type, fault location,
fault resistance, fault inception angle, mutual coupling and
remote source infeed. The performance of the proposed
scheme has been investigated by a number of offline tests.
Figure 9. Test result for A2B2C2 fault at 85KM from source S end at
i=360 (80ms fault inception time) & s=45. The complexity of all the ten types of faults in both the

2009 World Congress on Nature & Biologically Inspired Computing (NaBIC 2009) 17
circuit of line, fault locations (0-90%), fault inception angles The technique does not require communication link to
(0-360) and fault resistances (0-100) are considered. The retrieve the remote end data and nor zero sequence current
simulation results show that all the ten types of faults can be compensation for healthy phases.
correctly located after one cycle from the inception of fault.

TABLE IV. COMPARISION OF NEURAL NETWORK BASED FAULT LOCATION SCHEMES

Schemes Fault locator Line Fault resistance Fault Inception Other Factors Response time
suggested by inputs configuration Rf range () angle i () considered and Accuracy

Other types of Response time not


Single circuit line faults and wide indicated and
R.N. Mahanty and Samples of 3-
for LG & LL 0-200 0-90 variation in error is 6%.
P.B. Gupta [16] phase V and I
faults only inception angle
not onsidered.

Other types of Response time not


Samples of 50Hz
faults and indicated and
A.J. Mazon et al compoents of 3- Double circuit line
0-20 - variation in error is 0.19%
[12] phase V and I of for LG faults only
inception angle
each circuits
not onsidered.

Bhavesh R. Bhalja Mutual coupling, Not indicated


p, q and Double circuit line
& R.P. 0-200 - remote source
resistance for LG faults only
Maheshwari [17] infeed.

Double circuit line Mutual coupling, 1 cycle time from


Samples of 50Hz
for all 10 types of remote source inception of faults
compoents of 3-
Proposed scheme faults in both the 0-100 0-360 infeed and all 10 and % error is -
phase V and I of
circuits (total 20 types of faults in 7% to +1.97%.
each circuits
types of fault) both the ckts.

REFERENCES
[10] Fan Chunju, K.K. Li, W.L. Chan, Yu Weiyong and Zhang Zhaoning,
[1] M.S. Sachdev, R. Agarwal, A technique for estimating transmission
Application of wavelet fuzzy neural network in locating single line
line fault locations from digital impedance relay measurement, IEEE
to ground fault (SLG) in distribution lines, International Journal of
Transactions on Power Delivery, vol. 3 No.1, January 1988, pp-121-
Electrical Power & Energy Systems, vol. 29, Issue 6, July 2007, pp.
129.
497-50.
[2] A.J. Mazon, et al, New method of fault location on double-circuit
[11] A.G. Jongepier and L. Van Der Sluis, Adaptive distance protection
two-terminal transmission lines, Electric Power Systems Research
of double circuit lines using artificial neural networks, IEEE
Journal, Vol. 35 (3), pp. 213219, 1995.
Transactions on Power Delivery, vol. 12, No.1, January 1997, pp. 97-
[3] M. Garca-Gracia ,W. Osal and M.P. Comech, Line protection based
105.
on the differential equation algorithm using mutual coupling,
[12] A.J. Mazon, et al, A new approach to fault location in two-terminal
Electric Power Systems Research Journal, vol. 77, Issues 5-6, April
transmission lines using artificial neural networks, Electric Power
2007, pp. 566-573.
Systems Research Journal, vol. 56, 2000, pp. 261266.
[4] David W.P.Thomas, Ricardo J.O. Carvalho and Elisete T. Pereira,
[13] Anamika Jain, A.S. Thoke, and R. N. Patel, Double circuit
Fault location in distribution systems based on traveling waves, in
transmission line fault location using artificial neural network,
Proc. 2003 IEEE PowerTech Conf., vol. 2, pp. 1-5.
CSVTU Journal, Bhillai, C.G. India, vol. 2, No.1, Jan09, pp. 40-45.
[5] D.W.P. Thomas, C. Christopoulos, Y. Tang, P. Gale and J. Stokoe,
[14] Anamika Jain, A. S. Thoke, and R. N. Patel, Classification of single
Single ended traveling wave fault location scheme based on wavelet
line to ground faults on double circuit transmission line using ANN,
analysis, in Proc. 2004 IEE International conf. on Development in
International Journal of Computer and Electrical Engineering
Power System Protection, vol.1, pp. 196-199.
(IJCEE), vol. 1, No. 2, June 2009, pp. 199-205.
[6] R. Aggarwal and Y. Song, Artificial neural networks in power
[15] S.Haykin, Neural Networks, IEEE Press, 1994.
systems. III. Examples of applications in power systems, Power Eng.
[16] R.N. Mahanty and P.B.D. Gupta, Application of RBF neural network
J., vol. 12, No. 6, 1998, pp. 279287.
to fault classification and location in transmission lines, IEE Proc-
[7] Anamika Jain, V.S. Kale and A.S. Thoke, Application of artificial
Gen. Trans. Distr., vol. 151, No. 2, 2004, pp. 201212.
neural networks to transmission line faulty phase selection and fault
[17] Bhavesh R. Bhalja and R.P. Maheswari, High resistance faults on
distance location, Proceedings of the IASTED International
two terminal parallel transmission line: Analysis, simulation studies,
conference Energy and Power System, Chiang Mai, Thailand, Mar.
and an adaptive distance relaying scheme, IEEE Trans. PWRD, vol.
29-31, 2006, paper No. 526-803, pp. 262-267.
22, No.2, April-2007, pp. 801-812.
[8] R.K. Aggarwal, Q.Y. Xuan, A.T. Johns, R.W. Dunn, Fault
classification for double-circuits using self-organization mapping
neural network, Proc. 32nd Universities Power Engineering Conf., 1
September 1997.
[9] S.A. Khaparde, N. Warke and S.H. Agarwal, An adaptive approach
in distance protection using an artificial neural network, Electric
Power Systems Research, vol. 37, Issue 1, April 1996, pp. 39-46.

18 2009 World Congress on Nature & Biologically Inspired Computing (NaBIC 2009)

You might also like