You are on page 1of 2

Perhitungan Grounding Instalasi

65 V 65 V 65
Rt = = = =3,01
Trip Current K MCB x I n 2,5 x 8,64

0,5 x V sistem 0,5 x 220


Rg = = =5,09
Trip Current 2,5 x 8,64

V sistem 220
I g= = =27,16 A
Rtanah + R g 3,01+5,09

t
a= I g2 x = 27,162 x
k
30
5,3=64,62 mm2

r=
a

=
64,62
3,14
=4,54 mm=4,54 x 103 m

4 xl 100 4x7
R=
2xxl
ln
r (1 = )
2 x 3,14 x 7
ln
(
4,54 x 103 )
1 =2,27 x 7,73=17,55

1 1 1 1 R 1 17 ,55
Rp
=k +
R R ( ) ; maka, -- R p= ( )
k 2
=
5,3 (2 )
=1,6

Elektroda Batang

Keterangan :

Rt
= R tanah ( )

K MCB = konstanta MCB -- 2,5


In
= arus nominal MCB ( A )
Rg
= R gangguan ( )
Ig
= arus gangguan ( A )
a = luas penampang elektroda ( mm )
t = waktu gangguan ( detik ) -- 30 detik
k = konstanta -- 5,3
r = jari-jari elektroda ( m )
R = resistansi satu elektroda ( )