You are on page 1of 5

Los Delfines - Restaurant Delphos

HVAC Load Analysis


for

Hotel Los Delfines


Lima
Lima

Prepared By:

Pier De La Cruz
Generafrio S.a.c.
Lima
Lima

jueves, 9 de Junio de 2016


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Los Delfines - Restaurant Delphos
Hell Page 2

Building Summary Loads


Building peaks in March at 2pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 4,652 0 0.00 0 151,862 151,862 54.50
Wall 3,702 0 0.00 0 22,567 22,567 8.10
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 70 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 174,430 174,430 62.60
Lighting 1,657 0 0.00 0 6,219 6,219 2.23
Equipment 6,065 0 0.00 0 22,763 22,763 8.17
People 80 0 0.00 19,360 22,000 41,360 14.84
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 0 0 0.00 0 0 0 0.00
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 12,144 12,144 4.36
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 14,497 14,497 5.20
Return Duct 0 0 0.00 0 7,248 7,248 2.60
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 19,360 259,302 278,661 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 0 0 0 0.00
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 19,360 225,412 244,772 87.84
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 33,889 33,889 12.16
Building Totals 0 0.00 19,360 259,302 278,661 100.00

Check Figures
Total Building Supply Air (based on a 17 TD): 13,199 CFM
Total Building Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 829 Sq.ft
Supply Air Per Unit Area: 15.9308 CFM/Sq.ft
Area Per Cooling Capacity: 35.6786 Sq.ft/Ton
Cooling Capacity Per Area: 0.0280 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 23.22 Tons

C:\Users\Generafrio 1\Desktop\Calculo carga termica - Restaurant.CHV jueves, 9 de Junio de 2016, 10:39 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Los Delfines - Restaurant Delphos
Hell Page 3

Air Handler #1 - UE-01 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Restaurant 829 0 225,412 19,360 None None
2pm March 80 0 13,199 0 0 0
21,740 0.00 15.93 0 0 0
Runout duct size: 6 in. dia, Diffusers: 106, CFM/runout: 125, Velocity: 634.2 ft/min, Pressure drop: 0.256 in.wg./100ft
Zone Peak Totals: 829 0 225,412 19,360
Total Zones: 1 80 0 13,199 0 0 0
Unique Zones: 1 21,740 0.00 15.93 0 0 0
Main trunk duct size: 48 in. h x 48in. w, Velocity: 895.0 ft/min, Pressure drop: 0.022 in.wg./100ft

C:\Users\Generafrio 1\Desktop\Calculo carga termica - Restaurant.CHV jueves, 9 de Junio de 2016, 10:39 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Los Delfines - Restaurant Delphos
Hell Page 4

Air Handler #1 - UE-01 - Total Load Summary


Air Handler Description: UE-01 Constant Volume - Proportion
Supply Air Fan: Blow-Thru with program estimated horsepower of 4.79 HP
Fan Input: 65% motor and fan efficiency with 1.5 in. water across the fan
Sensible Heat Ratio: 0.93 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 2pm in March.
Outdoor Conditions: 87 DB, 76 WB, 116.46 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.998 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 225,412 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 14,497 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 239,909 Btuh
Cooling Supply Air: 239,909 / (.998 X 1.1 X 17) = 13,199 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 7,248 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 12,144 Btuh
Total sensible gain on return side of coil: 19,392 Btuh
Total sensible gain on air handling system: 259,302 Btuh
Zone space latent gain: 19,360 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 19,360 Btuh
Total system sensible and latent gain: 278,661 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17 TD): 13,199 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 829 Sq.ft
Supply Air Per Unit Area: 15.9308 CFM/Sq.ft
Area Per Cooling Capacity: 35.6786 Sq.ft/Ton
Cooling Capacity Per Area: 0.0280 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 23.22 Tons

C:\Users\Generafrio 1\Desktop\Calculo carga termica - Restaurant.CHV jueves, 9 de Junio de 2016, 10:39 a. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Los Delfines - Restaurant Delphos
Hell Page 5

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Restaurant peaks (sensible) in March at 2pm, Air Handler 1 (UE-01), Group 0, 77.0 x 10.8,
Construction Type: 11 (Medium)
Roof-1-1-No.Clg-L 4,652 0.50 42.4 0.700 138,057 11.900 55,353
Wall-1-E-C-M 1,162 0.83 24.7 0.350 10,061 5.950 6,916
Wall-2-W-C-M 1,162 0.83 13.1 0.350 5,334 5.950 6,916
Wall-3-N-C-M 689 0.83 13.1 0.350 3,161 5.950 4,098
Wall-4-S-C-M 689 0.83 8.1 0.350 1,960 5.950 4,098
Lights-Prof=1 1,657 1.000 5,654
Equipment-Prof=1 6,065 1.000 20,694 0
People-Prof=1 80.0 1.000 20,000 17,600
Floor slab 70 8.500 595
Sub-total 204,920 17,600 0
Safety factors: +10% +10% +10%
--------- --------- ---------
Total w/ safety factors: 225,412 19,360 0

C:\Users\Generafrio 1\Desktop\Calculo carga termica - Restaurant.CHV jueves, 9 de Junio de 2016, 10:39 a. m.