You are on page 1of 44

Fan Coil Range

HYDRONIC
TERMINALS
This document can be subjected to variations. Descriptions, performance data, images and diagrams are indicative only.
For further information contact Climaveneta Comunications/Marketing Department or visit www.climaveneta.com
Fan Coil Range
HYDRONIC
TERMINALS

i-LIFE2 | 2021002/2042004 pg. 4 HWD | 6021104 pg. 30

Professional fan-coils with cabinet or Ducted type terminal 4,8-15,1 kW


built-in version powered by EC Brushless
centrifugal fan 2 - 7,5 kW

HWD HP | 00710121 pg. 34

a-LIFE2 | 1021002/1041004 pg. 12 High head ducted type terminal


16,8-29,8 kW
Fan-coil for professional applications, with
cabinet or built-in version 1,5-7,5 kW

HRD | 021151 pg. 36

Heat recuperator unit 290-4000 m3/h

a-LIFE2 HP | 3021204 pg. 20

High head fan-coil for professional


application built-in version 2,88 - 8,60 kW
a-CHD | 6062209 pg. 38

Cassette type terminal 3,2-11,5 kW

i-LIFE Slim | 102502 pg. 24

Residential fan-coil with cabinet or i-CHD | 7062209 pg. 40


concealed version, with inverter motor
and tangential fan 0,84 - 3,86 kW Cassette type terminal with continuous
variation of air flow and cooling power
4,56-10,6 kW

MHD2 | 3060 pg. 28 CONTROLLERS pg. 42


Hi-wall type terminal 2,15 - 4,63 kW The wide range of available wall-mounted
and built-in controllers allows a user-friendly
and complete regulation of all the functions,
and an easy integration in home automation
and building management systems.
4
HYDRONIC TERMINALS

i-LIFE2
2021002 / 2041004

VERSION

DFIO built-in version, front air intake, horizontal installation


DFIV built-in version, front air intake, vertical installation
DLIO built-in version, low air intake, horizontal installation
DLIV built-in version, low air intake, vertical installation.

DFMO with cabinet, front air intake, horizontal installation


DFMV with cabinet, front air intake, vertical installation
DLMO with cabinet, low air intake, horizontal installation
DLMV with cabinet, low air intake, vertical installation

FEATURES

 High efficiency EC motor. Modulating speed


centrifugal fan and air flow regulation.
 Energy consumption reduced by more than 50%
 Coils with aluminium fins and copper pipes.
 Configurations for 2 and 4 pipe Systems.
 Left-hand water connections, easy convertible into
right-hand, by simply turning the coil
 Air filter on all models.
 Automatically closing flap to cover and protect
electric controls from dripping water (in conformity

PROFESSIONAL FAN-COIL WITH CABINET OR


with directive 60335-2-40).
 Elegant cover structure that integrates the use of
BUIT-IN VERSION, POWERED BY EC high quality plastic materials, with traditional
galvanized and precoated materials.
BRUSHLESS CENTRIFUGAL FAN  Structure in galvanised steel of high thickness for
2,00-7,50 kW maximum resistance to rust.
 Auxiliary drain pan with thermal insulation for all
Horizontal versions, made of galvanized steel.
New i-LIFE2 fancoil is powered by a modulating speed centrifugal fan. This new concept of  Plastic drain pan for all Vertical versions.
fancoil operates with continuous air flow regulation assuring the best comfort and a concrete
energy savings. Thanks to the different versions, with cabinet or buit-in, low air intake or front
air intake, vertical or horizontal installation, it results very easy to find the perfect solution for
any requirement. A dedicated range of controllers allows a user friendly and complete
regulation of all the functions, and an easy integration in home automation, centralization and
Building Management Systems.

ACCESSORY
COMMANDS
 Hot water coil kit
EK PLUG-IN CONTROL /EKW WALL MOUNTED connected to i-HB Power Board that must be mounted
CONTROL on board of the unit.  Kit RS485 - interface for Building Management System
User interface for selection of functioning mode  Kit control board to manage 0-10V or 3 points
(OFF/summer/winter/AUTO), fan speed IK CONTROL WITH LCD SCREEN modulating valve unit
(Max/Med/Min/AUTO), temperature set. Control of main Interface with LCD screen with user-friendly icons.
 Main coil 2-way/3-way valve unit
and additional coil valve unit (summer/winter - 2 and 4 Control kit for universal installation: wall-mounted as well
as plug-in. Selection of functioning mode  Additional coil 2-way/3-way valve unit
pipes installation). Management of traditional ON/OFF valve
unit or modulating valve unit 0-10V or 3 points. Air and (OFF/summer/winter/AUTO), fan speed  Kit LIFE2 BOX
water temperature probe. Multifunction digital input (Max/Med/Min/AUTO), temperature set. Control iK could  Kit Gateway interface for MyHome Bticino System
configurable by user. Configuration dip switch. Modbus function manually or with weekly timer regulation
configurable by the customer. Control of main coil valve  Air intake grille kit with version cover
protocol for installation in BMS (e.g. Idrorelax system by
Climaveneta). Installation and management of Master-Slave unit (summer/winter - 2 pipes) and additional coil (winter  Straight and angular (90) plenum kits for air outlet
system up to 8 LIFE fan coil units. Easy control installation - 4 pipes). Management of traditional ON/OFF valve unit  Plenum kit with round, straight or 90 air ducts.
thanks to 2 wires connection. or modulating valve unit 0-10V or 3 points (supply 230
 Straight and angular (90) plenum kits for air inlet
VAC or 24V). Parameters configurable directly by user.
INFRARED REMOTE CONTROL Modbus protocol for installation in Building Management  Heating element kit
Set-point regulation. Easy selection of the functioning mode System (e.g. Idrorelax system by Climaveneta).  Horizontal and vertical fan coil auxiliary tray
(cooling, heating, dehumidification, ventilation), and the fan Installation and management of Master-Slave system up
speed (Max, Med, Min, AUTO). User-sfriendly compact to 8 LIFE fan coil units. Easy control installation thanks to
remote control with fine aethetics. The receiver must be 2 wires connection through HB power board.
5

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL DATA i-LIFE2

B
6
HYDRONIC TERMINALS

i-LIFE2
2021002

TECHNICAL DATA i-LIFE2


7

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL DATA i-LIFE2


8
HYDRONIC TERMINALS

i-LIFE2
2041004

TECHNICAL DATA i-LIFE2


9

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL DATA i-LIFE2


10
HYDRONIC TERMINALS

i-LIFE2
2041004

TECHNICAL DATA i-LIFE2


11

2P 4P
2 PIPES 4 PIPES CONTROLLER
12
HYDRONIC TERMINALS

a-LIFE2
1021002 / 1041004

VERSION

DLMV with cabinet, low air intake, vertical installation


DLMO with cabinet, low air intake, horizontal installation
DFMV with cabinet, front air intake, vertical installation
DFMO with cabinet, front air intake, horizontal installation

DLIV built-in version, low air intake, vertical installation.


DLIO built-in version, low air intake, horizontal installation
DFIV built-in version, front air intake, vertical installation
DFIO built-in version, front air intake, horizontal installation

FEATURES

 Centrifugal Fan with double air inlet, to ensure the


best performances with the best acoustic
emissions.
 Coils with aluminium fins and copper pipes.
FAN-COIL FOR PROFESSIONAL APPLICATIONS,  Configurations for 2 and 4 pipe Systems.

WITH CABINET OR BUILT-IN VERSION  Left-hand water connections, easy convertible into
right-hand, by simply turning the coil
1,50-7,50 kW  6-speed autotransformer;
 Air filter on all models.
The new a-LIFE2 fancoil has been specifically developed to be adapted to every ambient
thanks to its modern and minimal design which is result of the full experience and  Automatically closing flap to cover and protect
electric controls from dripping water (in conformity
Climavenetas know-how on this range of products. Centrifugal fan with 6 speed via with directive 60335-2-40).
auto-transformer. Thanks to the different versions, with cabinet or buit in, low air intake  Auxiliary drain pan with thermal insulation for all
or front air intake, vertical or horizontal installation, it results very easy to find the perfect Horizontal versions, made of galvanized steel.
solution any time.  Plastic drain pan for all Vertical versions.

COMMANDS

PS PLUG-IN/PSW WALL MOUNTED input configurable by user. Configuration dip switch. Modbus
Fan speed slider, mode slider (OFF/summer/winter). ON/OFF protocol for installation in BMS (e.g. Idrorelax system by
valve unit control (summer/winter for 2 pipes installation), Climaveneta). Installation and management of Master-Slave
ON/OFF second valve unit control (winter for 4 pipes system up to 8 LIFE fan coil units. Easy control installation
installation). Remote water temperature probe. thanks to 2 wires connection.
ACCESSORY
MT PLUG-IN/MTW WALL MOUNTED IK CONTROL WITH LCD SCREEN
Fan speed slider, mode slider (OFF/summer/winter). Thermostat Interface with LCD screen with user-friendly icons. Control kit  Hot water coil kit
with set point regulation. ON/OFF valve unit control for universal installation: wall-mounted as well as plug-in.  Kit Bus Adapter for BMS
(summer/winter for 2 pipes installation), ON/OFF second valve Selection of functioning mode (OFF/summer/winter/AUTO),
unit control (winter for 4 pipes installation). Room temperature fan speed (Max/Med/Min/AUTO), temperature set.  Kit RS485 - interface for Building Management System
probe. Remote water temperature probe. Control iK could function manually or with weekly timer  Kit Gateway interface for MyHome Bticino System
AT PLUG-IN/ATW WALL MOUNTED regulation configurable by the customer. Control of main coil
 Interface SPB Kit
Mode button (OFF/summer/winter/AUTO), fan speed button valve unit (summer/winter - 2 pipes) and additional coil
(Max/Med/Min/AUTO). Thermostat with set point regulation. (winter - 4 pipes). Management of traditional ON/OFF valve  Kit control board to manage 0-10V or 3 points
ON/OFF valve unit control (summer/winter for 2 and 4 pipes unit or modulating valve unit 0-10V or 3 points (supply 230 modulating valve unit
installation). Control of traditional or PWM modulating valve VAC or 24V). Parameters configurable directly by user.  Main and additional coil valve unit ON/OFF, PWM,
units. Room temperature probe and water temperature probe. Modbus protocol for installation in Building Management 0-10V, 3 points 2-way or 3-way
Digital input configurable as: window contact, economy, heating System (e.g. Idrorelax system by Climaveneta).
or cooling remote changeover, periodic ventilation. Installation and management of Master-Slave system up to 8  Kit LIFE2 BOX
Configuration dip switch. TTL serial port with Modbus protocol LIFE fan coil units. Easy control installation thanks to 2 wires  Plenum kit with round, straight or 90 air ducts.
for installation in BMS. connection through HB power board
 Air intake grille kit with version cover
EK PLUG-IN CONTROL /EKW WALL MOUNTED CONTROL INFRARED REMOTE CONTROL  Horizontal and vertical fan coil auxiliary tray
User interface for selection of functioning mode Set-point regulation. Easy selection of the functioning mode
(OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), (cooling, heating, dehumidification, ventilation), and the fan  Electric heaters
temperature set. Control of main and additional coil valve unit speed (Max, Med, Min, AUTO). User-sfriendly compact
(summer/winter - 2 and 4 pipes installation). Management of remote control with fine aethetics. The receiver must be
traditional ON/OFF valve unit or modulating valve unit 0-10V or connected to i-HB Power Board that must be mounted on
3 points . Air and water temperature probe. Multifunction digital board of the unit.
13

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL DATA a-LIFE2

B
14
HYDRONIC TERMINALS

a-LIFE2
1021002

TECHNICAL DATA a-LIFE2


15

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL DATA a-LIFE2


16
HYDRONIC TERMINALS

a-LIFE2
1041004

TECHNICAL DATA a-LIFE2


17

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL DATA a-LIFE2


18
HYDRONIC TERMINALS

a-LIFE2
1041004

TECHNICAL DATA a-LIFE2


19

2P 4P
2 PIPES 4 PIPES CONTROLLER

LIFE2 BOX

UNIT DESCRIPTION MODEL A

LIFE2 BOX is a wall-mounted accessory that allows users to prepare the fan coil water and LIFE2 BOX 102/104-202/204
electrical connections in advance. The fan coil is fitted inside the structure when the work LIFE2 BOX 302-304/402-404
has been completed, thus simplifying the operations to be performed on site. LIFE2 BOX 502-504/602-604

 The kit consists of a galvanised sheet metal structure, front closing panel and frame with
manually adjustable flap. The kit is available in version painted RAL 9003 and also
NEUTRAL version (raw metal sheet).
 LIFE2 BOX can house i-LIFE2 fan- coils, DLIV/DLIO version: low air inlet, vertical outlet.
It is available for sizes 100/200, 300/400, 500/600.
20
HYDRONIC TERMINALS

a-LIFE2 HP
3021204

VERSION

DFIO built-in version, front air intake,


horizontal installation
DFIV built-in version, front air intake,
vertical installation
DLIO built-in version, low air intake,
horizontal installation
DLIV built-in version, low air intake,
vertical installation.

FEATURES

 High pressure centrifugal fan unit for ducted


system.
 Multi speed directly coupled electric motor.
 Configurations for 2 and 4 pipe Systems.
 Structure in hot galvanised steel for maximum
resistance to rust.
 Left-hand water connections, easy convertible
into right-hand, by simply turning the coil.
 Air filter on all models.
 Auxiliary drain pan with thermal insulation for all
HIGH HEAD FAN-COIL FOR PROFESSIONAL Horizontal versions, made of galvanized steel.
 Plastic drain pan for all Vertical versions.
APPLICATION BUILT-IN VERSION
2,88 - 8,60 kW

a-LIFE2 HP are professional high-head fan coils by Climaveneta.


The enhanced motor and the built-in version make these units ideal for ducted
systems in tertiary and commercial sectors.

B
COMMANDS

ATW WALL MOUNTED input configurable by user. Configuration dip


Mode button (OFF/summer/winter/AUTO), fan speed button switch.Modbus protocol for installation in BMS (e.g. H
(Max/Med/Min/AUTO). Thermostat with set point regulation. Idrorelax system by Climaveneta). Installation and A
ON/OFF valve unit control (summer/winter for 2 and 4 management of Master-Slave system up to 8 LIFE2 fan
pipes installation). Control of traditional or PWM modulating coil units. Easy control installation thanks to 2 wires ACCESSORY
valve units. Room temperature probe and water connection.
temperature probe. Digital input configurable as: window  Hot water coil kit
contact, economy, heating or cooling remote changeover, IK CONTROL WITH LCD SCREEN
periodic ventilation. Configuration dip switch. TTL serial port Interface with LCD screen with user-friendly icons.  Main coil 2-way/3-way valve unit
with Modbus protocol for installation in BMS. Control kit for universal installation: wall-mounted as well  Main and additional coil valve unit ON/OFF, PWM,
as plug-in. Selection of functioning mode 0-10 V, 3 points 2-way or 3-way
MTW WALL MOUNTED (OFF/summer/winter/AUTO), fan speed
Fan speed slider, mode slider (OFF/summer/winter). (Max/Med/Min/AUTO), temperature set.  Kit control board to manage 0-10V or 3 points
Thermostat with set point regulation. ON/OFF valve unit Control iK could function manually or with weekly timer modulating valve unit
control (summer/winter for 2 pipes installation), ON/OFF regulation configurable by the customer.  Kit RS485 - interface for Building Management
second valve unit control (winter for 4 pipes installation). Control of main coil valve unit (summer/winter - 2 pipes) System
Room temperature probe. Remote water temperature and additional coil (winter - 4 pipes). Management of
probe. traditional ON/OFF valve unit or modulating valve unit 0-  Kit Bus Adapter for BMS
10V or 3 points (supply 230 VAC or 24V). Parameters  Kit Gateway interface for MyHome Bticino System
PSW WALL MOUNTED configurable directly by user. Modbus protocol for
Fan speed slider, mode slider (OFF/summer/winter). installation in Building Management System (e.g. Idrorelax  Interface SPB Kit
ON/OFF valve unit control (summer/winter for 2 pipes system by Climaveneta). Installation and management of  Heating element kit
installation), ON/OFF second valve unit control (winter for 4 Master-Slave system up to 8 LIFE2 fan coil units. Easy
pipes installation). Remote water temperature probe. control installation thanks to 2 wires connection through  Condensate drain pump
HB power board  Horizontal and vertical fan coil auxiliary tray
REMOTE CONTROL EKW
User interface for selection of functioning mode INFRARED REMOTE CONTROL  Hose kit
(OFF/summer/winter/AUTO), fan speed Set-point regulation. Easy selection of the functioning mode  Straight and angular (90) plenum kits for air inlet
(Max/Med/Min/AUTO), temperature set. Control of main (cooling, heating, dehumidification, ventilation), and the fan
and additional coil valve unit (summer/winter - 2 and 4 speed (Max, Med, Min, AUTO).
 Plenum kit with round, straight or 90 air ducts.
pipes installation). Management of traditional ON/OFF User-sfriendly compact remote control with fine aethetics.
valve unit or modulating valve unit 0-10V or 3 points. The receiver must be connected to i-HB Power Board that
Air and water temperature probe. Multifunction digital must be mounted on board of the unit.
21

2P 4P
2 PIPES 4 PIPES DUCT CONTROLLER

TECHNICAL DATA a-LIFE HP


a-LIFE2 HP / DFIV - DLIV 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202
ELECTRICAL DATA
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 127 127 115 115 196 196 225 225 285 285
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m3/h 561 623 705 783 1004 1116 1390 1544 1740 1933
Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60
Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32
Max water flow (1) m3/h 0,496 0,565 0,644 0,713 0,795 0,895 1,067 1,240 1,386 1,481
Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9
Total capacity in heating mode (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4
Water flow in heating (2) m3/h 0,496 0,563 0,642 0,711 0,794 0,895 1,065 1,237 1,383 1,478
Pressure drop in heating (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8
Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59
Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68
MED SPEED
Air flow m3/h 500 555 525 583 767 852 1078 1198 1547 1719
Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10
Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03
Max water flow (1) m3/h 0,398 0,465 0,523 0,556 0,615 0,773 0,981 1,076 1,291 1,394
Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0
Total capacity in heating mode (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8
Water flow in heating (2) m3/h 0,398 0,464 0,522 0,555 0,614 0,772 0,980 1,074 1,289 1,393
Pressure drop in heating (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0
Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57
Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66
MIN SPEED
Air flow m3/h 392 435 464 516 584 649 923 1026 1381 1534
Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40
Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25
Max water flow (1) m3/h 0,358 0,380 0,393 0,503 0,554 0,603 0,832 0,930 1,188 1,274
Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7
Total capacity in heating mode (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82
Water flow in heating (2) m3/h 0,358 0,380 0,391 0,502 0,553 0,602 0,831 0,927 1,186 1,272
Pressure drop in heating (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7
Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54
Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63
SIZE AND WEIGHT
A (5) mm 650 650 850 850 1050 1050 1250 1250 1450 1450
B (5) mm 215 215 215 215 215 215 215 215 215 215
H (5) mm 450 450 450 450 450 450 450 450 450 450
Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34

a-LIFE2 HP / DFIO - DLIO 0302 0402 0502 0602 0702 0802 0902 1002 1102 1202
ELECTRICAL DATA
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 127 127 115 115 196 196 225 225 285 285
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m3/h 561 623 705 783 1004 1116 1390 1544 1740 1933
Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60
Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32
Max water flow (1) m3/h 0,496 0,565 0,644 0,713 0,795 0,895 1,067 1,240 1,386 1,481
Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9
Total capacity in heating mode (2) kW 3,83 4,35 4,96 5,49 6,13 6,91 8,22 9,55 10,7 11,4
Water flow in heating (2) m3/h 0,496 0,563 0,642 0,711 0,794 0,895 1,065 1,237 1,383 1,478
Pressure drop in heating (2) kPa 26,7 31,9 10,4 12,9 16,8 19,6 29,4 37,9 14,1 15,8
Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59
Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68
MED SPEED
Air flow m3/h 500 555 525 583 767 852 1078 1198 1547 1719
Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10
Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03
Max water flow (1) m3/h 0,398 0,465 0,523 0,556 0,615 0,773 0,981 1,076 1,291 1,394
Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0
Total capacity in heating mode (2) kW 3,07 3,58 4,03 4,28 4,74 5,96 7,57 8,29 9,95 10,8
Water flow in heating (2) m3/h 0,398 0,464 0,522 0,555 0,614 0,772 0,980 1,074 1,289 1,393
Pressure drop in heating (2) kPa 17,5 22,1 7,0 8,0 10,3 14,9 25,2 29,2 12,2 14,0
Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57
Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66
MIN SPEED
Air flow m3/h 392 435 464 516 584 649 923 1026 1381 1534
Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40
Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25
Max water flow (1) m3/h 0,358 0,380 0,393 0,503 0,554 0,603 0,832 0,930 1,188 1,274
Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7
Total capacity in heating mode (2) kW 2,76 2,94 3,02 3,88 4,27 4,65 6,41 7,16 9,15 9,82
Water flow in heating (2) m3/h 0,358 0,380 0,391 0,502 0,553 0,602 0,831 0,927 1,186 1,272
Pressure drop in heating (2) kPa 14,3 15,1 4,0 6,6 8,5 9,3 18,6 22,3 10,3 11,7
Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54
Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63
SIZE AND WEIGHT
A (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545
B (5) mm 215 215 215 215 215 215 215 215 215 215
H (5) mm 450 450 450 450 450 450 450 450 450 450
Operating weight (5) kg 14 15 20 21 24 25 28 29 31 34

Notes:
1 Room temperature 27C d.b./19C w.b.; Chilled water (in/out) 7/12C
2 Room temperature 20C d.b.; Hot water (in/out) 50/* C (with identical flow note1)
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
22
HYDRONIC TERMINALS

a-LIFE2 HP
3021204

TECHNICAL DATA a-LIFE HP


a-LIFE2 HP / DFIV - DLIV 0304 0404 0504 0604 0704 0804 0904 1004 1104 1204
ELECTRICAL DATA
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 127 127 115 115 196 196 225 225 285 285
4 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m3/h 561 623 705 783 1004 1116 1390 1544 1740 1933
Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60
Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32
Max water flow (1) m3/h 0,496 0,565 0,644 0,713 0,795 0,895 1,067 1,240 1,386 1,481
Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9
Total capacity in heating mode (2) kW 2,34 2,66 3,29 3,64 3,71 4,18 4,96 5,76 6,44 6,88
Water flow in heating (2) m3/h 0,205 0,233 0,288 0,319 0,325 0,366 0,435 0,505 0,565 0,603
Pressure drop in heating (2) kPa 13,6 17,3 26,3 31,7 11,1 13,9 15,4 20,4 17,9 20,1
Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59
Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68
MED SPEED
Air flow m3/h 500 555 525 583 767 852 1078 1198 1547 1719
Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10
Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03
Max water flow (1) m3/h 0,398 0,465 0,523 0,556 0,615 0,773 0,981 1,076 1,291 1,394
Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0
Total capacity in heating mode (2) kW 1,88 2,19 2,67 2,84 2,87 3,61 4,56 5,00 6,00 6,48
Water flow in heating (2) m3/h 0,165 0,192 0,234 0,249 0,252 0,316 0,400 0,438 0,526 0,568
Pressure drop in heating (2) kPa 9,0 12,0 17,8 20,0 6,8 10,5 13,1 15,6 15,7 18,1
Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57
Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66
MIN SPEED
Air flow m3/h 392 435 464 516 584 649 923 1026 1381 1534
Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40
Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25
Max water flow (1) m3/h 0,358 0,380 0,393 0,503 0,554 0,603 0,832 0,930 1,188 1,274
Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7
Total capacity in heating mode (2) kW 1,69 1,79 2,00 2,75 2,59 2,81 3,86 4,32 5,52 5,92
Water flow in heating (2) m3/h 0,148 0,157 0,175 0,225 0,227 0,246 0,338 0,379 0,484 0,519
Pressure drop in heating (2) kPa 7,3 8,2 10,4 16,6 5,6 6,5 9,6 11,9 13,5 15,4
Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54
Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63
SIZE AND WEIGHT
A (5) mm 650 650 850 850 1050 1050 1250 1250 1450 1450
B (5) mm 215 215 215 215 215 215 215 215 215 215
H (5) mm 450 450 450 450 450 450 450 450 450 450
Operating weight (5) kg 15 16 21 22 25 26 29 31 32 35
Notes:
1 Room temperature 27C d.b./19C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 70/60C
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
23

2P 4P
2 PIPES 4 PIPES DUCT CONTROLLER

TECHNICAL DATA a-LIFE HP


a-LIFE2 HP / DFIO - DLIO 0304 0404 0504 0604 0704 0804 0904 1004 1104 1204
ELECTRICAL DATA
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 127 127 115 115 196 196 225 225 285 285
4 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m3/h 561 623 705 783 1004 1116 1390 1544 1740 1933
Total capacity in cooling mode (1) kW 2,88 3,28 3,74 4,14 4,62 5,20 6,20 7,20 8,05 8,60
Sensible capacity in cooling mode (1) kW 2,39 2,77 3,15 3,53 3,91 4,44 5,14 5,91 6,99 7,32
Max water flow (1) m3/h 0,496 0,565 0,644 0,713 0,795 0,895 1,067 1,240 1,386 1,481
Mad pressure drop (1) kPa 31,5 31,9 12,2 15,2 19,5 22,4 33,5 43,1 14,2 15,9
Total capacity in heating mode (2) kW 2,34 2,66 3,29 3,64 3,71 4,18 4,96 5,76 6,44 6,88
Water flow in heating (2) m3/h 0,205 0,233 0,288 0,319 0,325 0,366 0,435 0,505 0,565 0,603
Pressure drop in heating (2) kPa 13,6 17,3 26,3 31,7 11,1 13,9 15,4 20,4 17,9 20,1
Noise Pressure (3) dB(A) 52 56 47 51 52 55 54 59 57 59
Noise Power (4) dB(A) 61 65 56 60 61 64 63 68 66 68
MED SPEED
Air flow m3/h 500 555 525 583 767 852 1078 1198 1547 1719
Total capacity in cooling mode (1) kW 2,31 2,70 3,04 3,23 3,57 4,49 5,70 6,25 7,50 8,10
Sensible capacity in cooling mode (1) kW 1,90 2,24 2,48 2,66 2,84 3,74 4,67 5,15 6,46 7,03
Max water flow (1) m3/h 0,398 0,465 0,523 0,556 0,615 0,773 0,981 1,076 1,291 1,394
Mad pressure drop (1) kPa 20,2 21,6 8,0 9,2 11,6 16,7 28,3 32,5 12,3 14,0
Total capacity in heating mode (2) kW 1,88 2,19 2,67 2,84 2,87 3,61 4,56 5,00 6,00 6,48
Water flow in heating (2) m3/h 0,165 0,192 0,234 0,249 0,252 0,316 0,400 0,438 0,526 0,568
Pressure drop in heating (2) kPa 9,0 12,0 17,8 20,0 6,8 10,5 13,1 15,6 15,7 18,1
Noise Pressure (3) dB(A) 45 52 41 44 41 49 51 54 55 57
Noise Power (4) dB(A) 54 61 50 53 50 58 60 63 64 66
MIN SPEED
Air flow m3/h 392 435 464 516 584 649 923 1026 1381 1534
Total capacity in cooling mode (1) kW 2,08 2,21 2,28 2,92 3,22 3,50 4,83 5,40 6,90 7,40
Sensible capacity in cooling mode (1) kW 1,69 1,82 1,84 2,37 2,49 2,78 3,88 4,42 5,83 6,25
Max water flow (1) m3/h 0,358 0,380 0,393 0,503 0,554 0,603 0,832 0,930 1,188 1,274
Mad pressure drop (1) kPa 16,3 14,5 4,5 7,5 9,4 10,1 20,4 24,3 10,4 11,7
Total capacity in heating mode (2) kW 1,69 1,79 2,00 2,75 2,59 2,81 3,86 4,32 5,52 5,92
Water flow in heating (2) m3/h 0,148 0,157 0,175 0,225 0,227 0,246 0,338 0,379 0,484 0,519
Pressure drop in heating (2) kPa 7,3 8,2 10,4 16,6 5,6 6,5 9,6 11,9 13,5 15,4
Noise Pressure (3) dB(A) 42 45 34 41 38 41 47 51 54 54
Noise Power (4) dB(A) 51 54 43 50 47 50 56 60 63 63
SIZE AND WEIGHT
A (5) mm 745 745 945 945 1145 1145 1345 1345 1545 1545
B (5) mm 215 215 215 215 215 215 215 215 215 215
H (5) mm 450 450 450 450 450 450 450 450 450 450
Operating weight (5) kg 15 16 21 22 25 27 29 31 32 36
Notes:
1 Room temperature 27C d.b./19C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 70/60C
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
24
HYDRONIC TERMINALS

i-LIFE Slim
102502

VERSION

DLIU built-in version for universal installation.


DLMV with cabinet for vertical installation
DLMO with cabinet for horizontal installation
DLRV Radiant Version with cabinet for vertical
installation.

FEATURES

 DC motor with inverter technology with continuous


speed regulation, to ensure the best performance
with a very low noise level.
 Elegant design and reduced depth of only 13 cm,
for installation in a residential installation.
 Tangential fan with asymetric blades that ensures
the continuous modulation of the air flow for a
better comfort and real energy savings.
 Coil with large frontal area that allows to reach
high air flow with very low pressure drop.
 Honeycomb polypropylene air filter which can be
regenerated by washing or blowing.
 Elegant cover structure that integrates the use of
RESIDENTIAL FAN-COILS WITH CABINET OR high quality plastic materials, with traditional
galvanized and precoated materials.
CONCEALED VERSION, WITH INVERTER MOTOR  Elegant cover structure that integrates the use of
E TANGENTIAL FAN. high quality plastic materials, with traditional
galvanized and epoxy powder coated materials.
0,84 - 3,86 kW  Configuration for 2 pipes systems. (upon request
also for 4 pipes systems).

i-LIFE SLIM is the new fan coil Climaveneta, with inverter technology for heating, cooling and
dehumidifying. Its elegant design with only 13 cm depth makes i-LIFE Slim the perfect solution for
residential applications. The fan coil is also available with i-LIFE R-SLIM inverter version with radiant
panel. The brushless motor allows a perfect adaptation to thermal load, without any temperature
fluctuations. Tangential fans operate through continuous air flow modulation, with no speed steps or
relay switching as traditional fan coil units. High efficiency is guaranteed in any HVAC installation
setup, in combination with any low temperature heat generator.

COMMANDS
A
IKS iHBS controller has a touch button and a LED for the
ON BOARD CONTROLLER visualization of the devices operation. All the parameters B
On-board control for unit with cabinet complete with touch are set up from iKSW.
keypad with 8 touch key, LCD display with white light ACCESSORY
ATS
symbols. Modulating fan speed with PID logic, temperature
CONTROLLER WITH 4 SPEED REGULATION
regulation, winter/summer mode, automatic mode for the
Controller for units with cabinet. Interface with 4 keys for  Drain Pan for horizontal installation
speed regulation, night mode for a silent operation.
the temperature selection, winter/summer mode, 4 speed  Main coil 2-way/3-way valve unit
Minimum water probe and solenoid management.
regulation, display for room temperature vizualization.
REMOTE CONTROL IKSW Minimum water temperature probe and solenoid valve  Fitting for air intake in built-in installation
Remote controller for built-in and with cabinet units management.  Telescopic air flow duct and 90 duct for false
complete with touch keypad with 8 touch keys, LCD ceiling and build in installation
HBS CONTROL
display with white light symbols.  Alluminium air flow vent for wall mounting
POWERBOARD CARD
Modulating fan speed with PID logic, temperature
Simple on board controler for built-in units or with cabinet  Alluminium Air intake grid
regulation, winter/summer mode, automatic mode for the
units, to be coupled with ATW Climaveneta remote control
speed regulation, night mode for a silent operation.  UVC air sterilisation device
or other remote controlers which manage the regulation of
Minimum water probe and solenoid valve management.
the fixed fan speeds. HBS has a touch button and a LED  Casing for build in version - i-LIFE Slim Box
A maximum of 31 fancoils can be connected to the iKSW
for the visualization of the device's operation. All the  Casing cover panel with frame and front panel grid
controller for open space rooms.
parameters are set up from the remote controler.
IHBS  Eurokonus adapter
ON BOARD SEMPLIFIED CONTROL  Pair of decorative and structural feet
Simple on board controller for buit - in and with cabinet
units, to be coupled with remote controller iKSW.
25

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL
NFT / U DATA i-LIFE Slim
26
HYDRONIC TERMINALS

i-LIFE Slim
102502

TECHNICAL
NFT / U DATA i-LIFE Slim
27

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL
NFT / U DATA i-LIFE Slim
28
HYDRONIC TERMINALS

MHD2
3060

VERSION

- Base Version

FEATURES

 Fan coil in ABS with high mechanical


characteristics and resistance to ageing;
 Adjustable air flow direction;
 Arrangement for right-left condensate drain pipe;
 Management of all functions by remote control
 Removable panel;

HIGH - WALL TYPE TERMINAL


2,15 - 4,63 kW

MHD2 belongs to hi-wall fan-coils of Climaveneta. The compactness


of this model and its exclusive elegance soften the visual impact and
H
make it ideal for residential and small tertiary installations.

A B

COMMANDS ACCESSORY

INFRARED REMOTE CONTROL  Frame kit


Set-point regulation. Easy selection of the functioning  Solenoid valve 2 ways 1/2"
mode (cooling, heating, dehumidification, ventilation),
and the fan speed (Max, Med, Min, AUTO).  Solenoid valve kit 3 ways, 4 fits 1/2" with frame
User-sfriendly compact remote control with fine  Condensate drain pump
aethetics.
The receiver must be connected to i-HB Power Board
that must be mounted on board of the unit.
29

2P
2 PIPES WALL CONTROLLER

TECHNICAL
NFT / U DATA MHD
MHD2 30 40 50 60
ELE CTRICAL DATA
Power suppl y V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50
Max absorbed power W 24 28 40 50
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m/h 436 632 780 920
Total capacity in cooling mode (1) kW 2,15 2,67 4,00 4,63
Sensible capacit y in cooling mode (1) kW 1,82 2,13 3,02 3,91
Max water flow (1) m/h 0,37 0,46 0,69 0,80
Mad pressure drop (1) kPa 8,9 15,0 38,5 49,9
Total capacity in heating mode (2) kW 2,48 3,20 4,20 5,07
Water flow in heating (2) m/h 0,37 0,46 0,69 0,79
Pressure drop in heating (2) kPa 9,0 14,9 38,5 49,7
Noise Pressure (3) dB(A) 34 41 44 49
Noise Power (4) dB(A) 45 52 55 60
MED SPEED
Air flow m/h 376 522 691 810
Total capacity in cooling mode (1) kW 1,85 2,00 3,00 3,86
Sensible capacit y in cooling mode (1) kW 1,60 1,62 2,57 3,26
Max water flow (1) m/h 0,32 0,34 0,52 0,66
Mad pressure drop (1) kPa 7,6 10,3 25,7 37,9
Total capacity in heating mode (2) kW 2,18 2,40 3,64 4,25
Water flow in heating (2) m/h 0,32 0,34 0,52 0,67
Pressure drop in heating (2) kPa 7,7 10,2 26,0 38,1
Noise Pressure (3) dB(A) 31 31 41 45
Noise Power (4) dB(A) 42 42 52 56
MIN SPEED
Air flow m/h 334 403 570 697
Total capacity in cooling mode (1) kW 1,65 1,78 2,67 3,36
Sensible capacit y in cooling mode (1) kW 1,42 1,45 2,13 2,83
Max water flow (1) m/h 0,28 0,31 0,46 0,58
Mad pressure drop (1) kPa 6,8 8,8 21,9 30,7
Total capacity in heating mode (2) kW 1,91 2,13 3,21 3,67
Water flow in heating (2) m/h 0,28 0,30 0,46 0,58
Pressure drop in heating (2) kPa 6,8 8,7 21,8 31,1
Noise Pressure (3) dB(A) 27 28 37 42
Noise Power (4) dB(A) 38 39 48 53
SIZE AND WEI GHT
A (5) mm 845 845 920 920
B (5) mm 180 180 200 200
H (5) mm 270 270 298 298
Operating weight (5) kg 10 10 13 13
Notes:
1 Room temperature 27C d.b./19C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 50/* C (identical flow rate note 1)
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
30
HYDRONIC TERMINALS

HWD
6021104

VERSION

- base version

FEATURES

 Unit coils guarantee high efficiency thermal


exchange with low pressure drop. Finned unit coils
are made of copper tubes and high exchange
surface area aluminium fins. Coils are always
tested for leaks with dried air at 14 bar;
 The electrical power and control switchboard
includes electronic air flow regulator and terminal
blocks for connection to power supply and remote
control;
 Internal insulation in closed cell expanded
polyethylene with suitable thick to limit heat loss
and noise emission;
 The fan units, with high available working
pressures, are fitted with balanced impellers to
guarantee maximum acoustic comfort.
DUCTED TYPE TERMINAL  Structure and base plate in hot-dip galvanised
4,8 - 15,1 kW steel for maximum resistance to rust;
 Extra modules available as accessories to the
standard unit;

HWD are Climaveneta ducted hydronic terminal units. The fan units at  Remote control to manage main unit functions to
provide a total enviroment comfort. Full Auto
available working pressures, through internal insulation, ensure excellent function;
acoustic comfort levels. The compactness and ease of installation make
 Arrangement for electronic control of two on/off
HWD a suitable hydronic terminal unit for any type of setting. valve unit in the water circuit;

COMMANDS

NSW WALL MOUNTED ATW WALL MOUNTED


Fan speed slider, mode slider (OFF/summer/winter). Mode button (OFF/summer/winter/AUTO), fan speed
ON/OFF valve unit control (summer/winter for 2 pipes button (Max/Med/Min/AUTO). Thermostat with set point H
installation), ON/OFF second valve unit control (winter regulation. ON/OFF valve unit control (summer/winter
for 4 pipes installation). Setting for minimum for 2 and 4 pipes installation). Control of traditional or
temperature thermostat. PWM modulating valve units. Room temperature probe
and water temperature probe. Digital input configurable
B
PSW WALL MOUNTED as: window contact, economy, heating or cooling A
Fan speed slider, mode slider (OFF/summer/winter). remote changeover, periodic ventilation. Configuration
ON/OFF valve unit control (summer/winter for 2 pipes dip switch. TTL serial port with Modbus protocol for
installation), ON/OFF second valve unit control (winter installation in BMS.
for 4 pipes installation). Remote water temperature
probe. PCE WALL-MOUNTED
Off/summer/winter/auto selector switch. Room ACCESSORY
MTW WALL MOUNTED temperature control. Room temperature sensor.
Fan speed slider, mode slider (OFF/summer/winter). Coil temperature sensor. Three speed air flow control +  Interface SPB Kit
Thermostat with set point regulation. ON/OFF valve unit Auto. Automatic summer/winter switching. Automatic  Hot water coil kit
control (summer/winter for 2 pipes installation), ON/OFF ON/OFF valve control.  Heating element module
second valve unit control (winter for 4 pipes
installation). Room temperature probe. Remote water  Delivery and intake plenum
temperature probe.  Delivery plenum for round ducts
 Two way intake plenum with air lock
 Condensate drain pump
31

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL
HWD DATA HWD
HWD 0602 0703 0803 0904 1003 1104
ELECTRICAL DATA
Power supply V/ph/Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Max absorbed power W 370 370 440 440 900 900
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow 1300 1300 1600 1600 2200 2500
Total capacity in cooling mode (1) kW 4,80 6,20 8,00 9,70 11,5 15,1
Sensible capacity in cooling mode (1) kW 3,00 4,00 5,20 6,50 7,40 10,2
Max water flow (1) 0,826 1,066 1,376 1,668 1,978 2,597
Mad pressure drop (1) kPa 12,0 8,0 14,0 35,0 24,0 23,0
Total capacity in heating mode (2) kW 6,61 8,48 11,8 12,1 16,7 18,7
Water flow in heating (2) 0,826 1,066 1,376 1,668 1,978 2,597
Pressure drop in heating (2) kPa 9,0 7,0 14,0 22,8 21,0 20,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 68 68 72 72 78 80
MED SPEED
Air flow 1171 1171 1357 1357 1985 2243
Total capacity in cooling mode (1) kW 4,50 5,70 7,20 8,50 10,7 13,9
Sensible capacity in cooling mode (1) kW 2,80 3,70 4,60 5,90 6,90 9,70
Max water flow (1) 0,774 0,980 1,238 1,462 1,840 2,391
Mad pressure drop (1) kPa 11,0 7,0 11,0 27,0 22,0 21,0
Total capacity in heating mode (2) kW 6,19 7,88 9,34 10,6 13,7 16,8
Water flow in heating (2) 0,774 0,980 1,238 1,462 1,840 2,391
Pressure drop in heating (2) kPa 8,0 6,0 12,0 24,9 19,0 13,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 65 65 69 69 76 77
MIN SPEED
Air flow 1021 1021 1057 1057 1585 1771
Total capacity in cooling mode (1) kW 4,10 5,20 6,00 7,00 9,10 11,7
Sensible capacity in cooling mode (1) kW 2,60 3,40 3,90 4,80 6,00 8,00
Max water flow (1) 0,705 0,894 1,032 1,204 1,565 2,012
Mad pressure drop (1) kPa 9,0 6,0 9,0 21,6 17,0 15,0
Total capacity in heating mode (2) kW 5,65 7,80 7,75 9,00 13,5 14,5
Water flow in heating (2) 0,705 0,894 1,032 1,204 1,565 2,012
Pressure drop in heating (2) kPa 8,0 5,0 7,0 18,7 9,0 13,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 62 62 63 63 70 72
SIZE AND WEIGHT
A (5) mm 900 900 1050 1050 1250 1250
B (5) mm 695 695 695 695 750 750
H (5) mm 295 295 295 295 315 315
Operating weight (5) kg 41 43 50 52 63 63
Notes:
1 Room temperature 27C d.b./19C w.b.; Chilled water (in/out) 7/12C
2 Room temperature 20C d.b.; Hot water (in/out) 50/* C (with identical flow note1)
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
32
HYDRONIC TERMINALS

HWD
6021104

TECHNICAL
HWD DATA HWD
HWD 602 703 803 904 1003 1104
ELECTRICAL DATA
Power supply V/ph/Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Max absorbed power W 370 370 440 440 900 900
4 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow 1300 1300 1600 1600 2200 2500
Total capacity in cooling mode (1) kW 4,80 6,20 8,00 9,70 11,5 15,1
Sensible capacity in cooling mode (1) kW 3,00 4,00 5,20 6,50 7,40 10,2
Max water flow (1) 0,826 1,066 1,376 1,668 1,978 2,597
Mad pressure drop (1) kPa 12,0 8,0 14,0 35,5 24,0 23,0
Total capacity in heating mode (2) kW 9,10 9,10 11,8 11,8 16,7 18,0
Water flow in heating (2) 0,783 0,783 1,015 1,015 1,436 1,548
Pressure drop in heating (2) kPa 9,0 9,0 14,0 34,1 13,0 15,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 68 68 72 72 78 80
MED SPEED
Air flow 1171 1171 1357 1357 1985 2243
Total capacity in cooling mode (1) kW 4,50 5,70 7,20 8,50 10,7 13,9
Sensible capacity in cooling mode (1) kW 2,80 3,70 4,60 5,90 6,90 9,70
Max water flow (1) 0,774 0,980 1,238 1,462 1,840 2,391
Mad pressure drop (1) kPa 11,0 7,0 11,0 27,3 22,0 21,0
Total capacity in heating mode (2) kW 8,60 8,60 10,6 10,6 15,6 16,8
Water flow in heating (2) 0,740 0,740 0,912 0,912 1,342 1,445
Pressure drop in heating (2) kPa 8,0 8,0 12,0 29,2 11,0 13,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 65 65 69 69 76 77
MIN SPEED
Air flow 1021 1021 1057 1057 1585 1771
Total capacity in cooling mode (1) kW 4,10 5,20 6,00 7,00 9,10 11,7
Sensible capacity in cooling mode (1) kW 2,60 3,40 3,90 4,80 6,00 8,00
Max water flow (1) 0,705 0,894 1,032 1,204 1,565 2,012
Mad pressure drop (1) kPa 9,0 6,0 9,0 21,8 17,0 15,0
Total capacity in heating mode (2) kW 7,80 7,80 9,00 9,00 13,5 14,5
Water flow in heating (2) 0,671 0,671 0,774 0,774 1,161 1,247
Pressure drop in heating (2) kPa 7,0 7,0 9,0 21,9 9,0 10,0
Noise Pressure (3) dB(A)
Noise Power (4) dB(A) 62 62 63 63 70 72
SIZE AND WEIGHT
A (5) mm 900 900 1050 1050 1250 1250
B (5) mm 695 695 695 695 750 750
H (5) mm 295 295 295 295 315 315
Operating weight (5) kg 41 43 50 52 63 63
Notes:
1 Room temperature 27C d.b./19C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 70/60C
3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
33

2P 4P
2 PIPES 4 PIPES CONTROLLER
34
HYDRONIC TERMINALS

HWD HP
00710121

VERSION

- base version

FEATURES

 Unit coils guarantee high efficiency thermal


exchange with low pressure drop. Finned unit coils
are made of copper tubes and high exchange
surface area aluminium fins. Coils are always
tested for leaks with dried air at 30 bar;
 The electrical power and control switchboard
includes electronic air flow regulator and terminal
blocks for connection to power supply and remote
control;
 Internal insulation in closed cell expanded
polyethylene with suitable thick to limit heat loss
and noise emission;
 Structure in galvanised steel of high thickness for
HIGH HEAD DUCTED TYPE TERMINAL maximum resistance to rust;
 Extra modules available as accessories to the
16,8 - 29,8 kW standard unit;

HWD HP belongs to ducted type fan-coils high head of Climaveneta.


The possibility of vertical or horizontal installation, airflow adjustment and attractive
external panelling guarantees an ease installation and make the unit adaptable to
any type of surroundings.

COMMANDS

NSW WALL MOUNTED ATW WALL MOUNTED


Fan speed slider, mode slider (OFF/summer/winter). Mode button (OFF/summer/winter/AUTO), fan speed
ON/OFF valve unit control (summer/winter for 2 pipes button (Max/Med/Min/AUTO). Thermostat with set point H
installation), ON/OFF second valve unit control (winter for regulation. ON/OFF valve unit control (summer/winter for
4 pipes installation). Setting for minimum temperature 2 and 4 pipes installation). Control of traditional or PWM
thermostat. modulating valve units. Room temperature probe and B
A
water temperature probe. Digital input configurable as:
PSW WALL MOUNTED window contact, economy, heating or cooling remote
Fan speed slider, mode slider (OFF/summer/winter). changeover, periodic ventilation.
ON/OFF valve unit control (summer/winter for 2 pipes Configuration dip switch. TTL serial port with Modbus
installation), ON/OFF second valve unit control (winter for protocol for installation in BMS.
4 pipes installation). Remote water temperature probe.
PCE WALL-MOUNTED ACCESSORY
MTW WALL MOUNTED Off/summer/winter/auto selector switch. Room
Fan speed slider, mode slider (OFF/summer/winter). temperature control. Room temperature sensor. Coil  Interface SPB Kit
Thermostat with set point regulation. ON/OFF valve unit temperature sensor. Three speed air flow control + Auto.  Hot water coil kit
control (summer/winter for 2 pipes installation), ON/OFF Automatic summer/winter switching. Automatic ON/OFF
second valve unit control (winter for 4 pipes installation). valve control.  Delivery and intake plenum
Room temperature probe. Remote water temperature  Intake grill
probe.  Two way intake plenum with air lock
 Ceiling brackets
 Auxiliary condensate collecting tray
35

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL
HWD DATA HWD HP
HWD HP 071 091 101 121
ELECTRICAL DATA
Power supply V/ph/Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
Max absorbed power W 1 1 2 2
2 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m/h 3200 3200 4400 5000
Total capacity in cooling mode (1) kW 16,8 20,1 23,4 29,8
Sensible capacity in cooling mode (1) kW 12,3 14,4 17,3 21,7
Max water flow (1) m/h 2,890 3,440 4,020 5,100
Mad pressure drop (1) kPa 24,0 22,0 14,0 11,9
Total capacity in heating mode (2) kW 16,3 19,6 23,0 29,8
Water flow in heating (2) m/h 2,890 3,440 4,020 5,100
Pressure drop in heating (2) kPa 21,1 19,3 12,3 10,5
Noise Pressure (3) dB(A) 60 60 66 69
Noise Power (4) dB(A)
SIZE AND WEIGHT
A (5) mm 1300 1300 1500 1500
B (5) mm 1119 1119 1349 1349
H (5) mm 510 510 625 625
Operating weight (5) kg 121 124 145 149
Notes:
1 Room temperature 27C d.b./19.5 C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 45/40C
3 Sound pressure at 1 (m.) from fan front
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.

HWD HP 0071 0091 0101 0121


ELECTRICAL DATA
Power supply V/ph/Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz
Max absorbed power W 1 1 2 2
4 PIPES SYSTEM CONFIGURATION
MAX SPEED
Air flow m/h 3200 3200 4400 5000
Total capacity in cooling mode (1) kW 16,8 20,1 23,4 29,8
Sensible capacity in cooling mode (1) kW 12,3 14,4 17,3 21,7
Max water flow (1) m/h 2,890 3,440 4,020 5,100
Mad pressure drop (1) kPa 24,0 22,0 14,0 11,9
Total capacity in heating mode (2) kW 25,0 25,0 36,0 39,0
Water flow in heating (2) m/h 2,200 2,200 3,200 3,400
Pressure drop in heating (2) kPa 13,0 13,0 19,0 22,0
Noise Pressure (3) dB(A) 60 60 66 69
Noise Power (4) dB(A)
SIZE AND WEIGHT
A (5) mm 1300 1300 1500 1500
B (5) mm 1119 1119 1349 1349
H (5) mm 510 510 625 625
Operating weight (5) kg 121 124 145 149
Notes:
1 Room temperature 27C d.b./19.5 C w.b., Chilled water (in/out) 7/12C
2 Room temperature 20C d.b., hot water (in/out) 70/60C
3 Sound pressure at 1 (m.) from fan front
4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.
5 Unit in standard configuration/execution, without optional accessories.
36
HYDRONIC TERMINALS

HRD
021151

VERSION

- base version

FEATURES

 Removable aluzink plate side panels;


 Panels insulated and soundproofed with
polyethylene/polyester with average thickness of
10 mm (mod. HRD 0021-0051) and 20 mm for the
other models;
 High efficiency aluminium plate static type heat
recovery units, with airflow separated by special
seals;
HEAT RECUPERATOR UNIT  UE3 efficiency air filters, which may be easily
removed from any side of the unit (bottom, side,
290-4000 m /h 3
top) for periodic cleaning;
 Fan casings on vibration-isolation mountings;
 Double inlet centrifugal fans for fresh air intake and
HRD heat recuperator units for residential and commercial application allow maximum room used air extraction, which may be removed from
comfort and energy saving. In modern systems is becoming necessary to create forced any side of the unit for periodic maintenance;
ventilation, which involves air conditioned expelling; thereby consuming more energy and  Multi speed directly coupled electric motor;
consequenting increasing costs. HRD heat recuperators have obviated such as problems  A terminal block with a relay board is fitted on the
using an aluminium static recovery unit that saves more than 50% energy, otherwise be lost unit to aid electrical connections and fan control;
with expelled stale air. HRD can be integrated in traditional systems with fan coils, chillers  Stainless steel condensate collecting tray, with
and radiators and may operate both in summer and winter. These units are recommended for condensate drain directed downwards;
suspended ceiling installation and may be suitably ducted to allow the fresh air intake and
distribution.

COMMANDS

NSW WALL MOUNTED ATW WALL MOUNTED H


Fan speed slider, mode slider (OFF/summer/winter). Mode button (OFF/summer/winter/AUTO), fan speed
ON/OFF valve unit control (summer/winter for 2 pipes button (Max/Med/Min/AUTO). Thermostat with set point
installation), ON/OFF second valve unit control (winter regulation. ON/OFF valve unit control (summer/winter A B
for 4 pipes installation). Setting for minimum for 2 and 4 pipes installation). Control of traditional or
temperature thermostat. PWM modulating valve units. Room temperature probe
and water temperature probe. Digital input configurable
MTW WALL MOUNTED as: window contact, economy, heating or cooling
Fan speed slider, mode slider (OFF/summer/winter). remote changeover, periodic ventilation. Configuration
Thermostat with set point regulation. ON/OFF valve unit dip switch. TTL serial port with Modbus protocol for ACCESSORY
control (summer/winter for 2 pipes installation), ON/OFF installation in BMS.
second valve unit control (winter for 4 pipes  Interface SPB Kit
installation). Room temperature probe. Remote water PCE WALL-MOUNTED
 Hot water coil kit
temperature probe. Off/summer/winter/auto selector switch. Room
temperature control. Room temperature sensor. Coil  Cool water coil kit
temperature sensor. Three speed air flow control +  Heating element kit
Auto. Automatic summer/winter switching. Automatic
ON/OFF valve control.
37

PLATE CONTROLLER

TECHNICAL
HWD DATA HRD
HRD 021 031 051 071 091 101 121 151
ELECTRICAL DATA
Power supply V/ph/Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 230V~50Hz 400V-3N~50Hz
Max absorbed power W 90 130 294 700 700 700 1100 1500
PERFORMANCE
MAX SPEED
Air flow m/h 290 550 1000 1400 1900 2500 3200 4000
Available static pressure Pa 60 65 90 140 120 110 170 170
Noise Pressure (1) dB(A) 53 54 54 60 58 58 61 62
Efficency (2) % 52,3 54,6 53,4 52,1 51,8 57,6 56,0 55,6
Recovery heat exchanger capacity (2) kW 1,34 2,57 4,60 6,20 8,40 12,30 15,30 19,40
Renewal air temperature (2) C 8,10 8,70 8,30 8,00 7,90 9,40 9,00 8,90
SIZE AND WEIGHT
A (3) mm 990 990 1150 1350 1450 1700 1700 1700
B (3) mm 750 750 860 900 900 1230 1230 1230
H (3) mm 270 270 385 410 470 490 530 630
Operating weight (3) kg 39 41 68 91 99 140 155 179
Notes:
1 Sound pressure at 1 (m.) from fan front
2 Size valued in the following Hypothesis: T inlet external air 5 C; T ambient 20 C ; nominal air capacity
3 Unit in standard configuration/execution, without optional accessories.
38
HYDRONIC TERMINALS

a-CHD
0606 - 2209

VERSION

U-2T electromechanical version for


2-pipe system
U-4T electromechanical version for
4-pipe system

FEATURES

 Frame in galvanised steel insulated with


self-extinguishing closed-cell polyethylene blanket
of suitable thickness, to limit heat loss and noise to
a minimum.
 Airflow grille in ABS built in the cassette.
 Supplied in 1 cartonbox 5-speed electric motor
inclusive of thermal switch.
 Fan Low-rev radial-blade fan to maximise acoustic
comfort.
 Coil with corrugated aluminium fins and copper
pipes, tested with dried air at 14 bar.
 Switchboard with power and control terminal block
with screw terminals
 Set-up for fresh air intake.
 Set-up for duct air distribution.
 Condensate auxiliary tray standard supplied;

CASSETTE TYPE TERMINAL


3,20-11,5 kW

New a-CHD cassette of Climaveneta, with 5 speeds AC motor, is available in two


version: for two pipe installation (unit with single coil) and for four pipe installation
(unit with double coil). Wide range of sizes and easy installation make them suitable
H
for all types of installations.

B
A

COMMANDS ACCESSORY

MTW WALL MOUNTED ATW WALL MOUNTED  Main coil 2-way/3-way valve unit
Fan speed slider, mode slider (OFF/summer/winter). Mode button (OFF/summer/winter/AUTO), fan speed  Additional coil 2-way/3-way valve unit
Thermostat with set point regulation. ON/OFF valve unit button (Max/Med/Min/AUTO). Thermostat with set
control (summer/winter for 2 pipes point regulation. ON/OFF valve unit control  Fresh Air renewal connection
installation), ON/OFF second valve unit control (winter (summer/winter for 2 and 4 pipes installation).  Duct Connection Flange
for 4 pipes installation). Room temperature probe.  Kit Bus Adapter for BMS
Remote water temperature probe. Control of traditional or PWM modulating valve units.
Room temperature probe and water temperature  Kit Gateway interface for MyHome Bticino System
INFRARED REMOTE CONTROL probe. Digital input configurable as: window contact,
Set-point regulation.Easy selection of the functioning economy, heating or cooling remote changeover,
mode (cooling, heating, dehumidification, ventilation), periodic ventilation. Configuration dip switch.
and the fan speed (Max, Med, Min, AUTO). TTL serial port with Modbus protocol for installation
User-sfriendly compact remote control with fine in BMS.
aethetics. The receiver must be connected to i-HB
Power Board that must be mounted on board of the
unit.
39

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL
HWD DATA a-CHD
40
HYDRONIC TERMINALS

i-CHD
706-2209

VERSION

U-2T electromechanical version for


2-pipe system
U-4T Version for 4 pipe installations,
can be realized with the cassette
i- CHD 2-pipe, via the valve
mounting 4FOR2.

FEATURES

 High efficiency EC motor. Modulating speed centrifugal


fan and air flow regulation.
 Energy consumption reduced by more than 50%
 Unit coils guarantee high efficiency thermal exchange
with low pressure drop. Finned unit coils are made of
copper tubes and high exchange surface area
aluminium fins. Coils are always tested for leaks with
dried air at 14 bar;
CASSETTE TYPE TERMINAL WITH  Frame in galvanised steel insulated with
CONTINUOUS VARIATION OF self-extinguishing closed-cell polyethylene blanket
of suitable thickness, to limit heat loss and noise to
AIR FLOW AND COOLING POWER a minimum.
4,56-10,6 kW  Airflow grille in ABS built in the cassette, supplied in 1
cartonbox.
 Electrical power and control switchboard, complete
with electronic air flow regulator and terminal board
i-CHD is the new cassette of Climaveneta, with high efficency EC motor and for connection to network and available remote
Centrifugal fans that operates through a continuous air flow modulation, with controls;
low energy consumtion and perfect comfort. i-CHD is supplyed on 2 pipes  Availability to have fresh air intake, distribute air flow
version. For the 4 Pipes installations we reccomend the 2 Pipes i-CHD in four directions and also in different room place
cassette with 4For2 kit valves. thanks to air diffuser present on the unit;
 Condensate auxiliary tray standard supplied;

COMMANDS

MTW WALL MOUNTED IK CONTROL WITH LCD SCREEN


Fan speed slider, mode slider (OFF/summer/winter). Interface with LCD screen with user-friendly icons. Control
Thermostat with set point regulation. ON/OFF valve unit kit for universal installation: wall-mounted as well as plug-
control (summer/winter for 2 pipes installation), ON/OFF in. Selection of functioning mode
second valve unit control (winter for 4 pipes installation). (OFF/summer/winter/AUTO), fan speed
Room temperature probe. Remote water temperature probe. (Max/Med/Min/AUTO), temperature set. Control iK could H
function manually or with weekly timer regulation
ATW WALL MOUNTED configurable by the customer. Control of main coil valve
Mode button (OFF/summer/winter/AUTO), fan speed button unit (summer/winter - 2 pipes) and additional coil (winter -
(Max/Med/Min/AUTO). Thermostat with set point regulation. 4 pipes). Management of traditional ON/OFF valve unit or
ON/OFF valve unit control (summer/winter for 2 and 4 pipes modulating valve unit 0-10V or 3 points (supply 230 VAC B
installation). Control of traditional or PWM modulating valve or 24V). Parameters configurable directly by user. Modbus A
units. Room temperature probe and water temperature probe. protocol for installation in Building Management System
Digital input configurable as: window contact, economy, (e.g. Idrorelax system by Climaveneta). Installation and
heating or cooling remote changeover, periodic ventilation. management of Master-Slave system up to 8 LIFE fan coil
Configuration dip switch. TTL serial port with Modbus protocol units. Easy control installation thanks to 2 wires connection
for installation in BMS. through HB power board.
ACCESSORY

EK PLUG-IN CONTROL INFRARED REMOTE CONTROL  Main coil 2-way/3-way valve unit
EKW WALL MOUNTED CONTROL Set-point regulation. Easy selection of the functioning  Kit valves 4For2
User interface for selection of functioning mode mode (cooling, heating, dehumidification, ventilation), and
(OFF/summer/winter/AUTO), fan speed (Max/Med/Min/AUTO), the fan speed (Max, Med, Min, AUTO).  Fresh Air renewal connection
temperature set. Control of main User-sfriendly compact remote control with fine aethetics.  Duct Connection Flange
and additional coil valve unit (summer/winter - 2 and 4 pipes The receiver must be connected to i-HB Power Board that
 i-HB Power box
installation). Management of traditional ON/OFF valve unit or must be mounted on board of the unit.
modulating valve unit 0-10V or 3 points. Air and water  Kit RS485 - interface for Building Management
temperature probe. Multifunction digital input configurable by System
user. Configuration dip switch. Modbus protocol for installation
in BMS (e.g. Idrorelax system by Climaveneta). Installation and
management of Master-Slave system up to 8 LIFE fan coil
units. Easy control installation thanks to 2 wires connection.
41

2P 4P
2 PIPES 4 PIPES CONTROLLER

TECHNICAL
HWD DATA i-CHD
42
HYDRONIC TERMINALS

CONTROLLERS
THE WIDE RANGE OF AVAILABLE Infrared Remote Control

WALL-MOUNTED AND BUILT-IN Set-point regulation.


Easy selection of the functioning
CONTROLLERS, ALLOWS A USER- mode (cooling, heating,
dehumidification, ventilation),
FRIENDLY AND COMPLETE and the fan speed (Max, Med,

REGULATION OF ALL THE FUNCTIONS,


Min, AUTO). User-sfriendly
compact remote control with fine

AND AN EASY INTEGRATION WITH aethetics. The receiver must be


connected to i-HB Power Board
HOME AUTOMATION, CENTRALIZATION, that must be mounted on board
of the unit.
BUILDING MANAGEMENT SYSTEMS.

NS plug-in AT plug-in
NSW wall mounted ATW wall mounted

Fan speed slider, mode slider, Room thermostat, manual-


minimum temperature and automatic regulation of
thermostat and command of fan, manualand automatic
on/off valves mode change-over, room-
and minimum temperature
probes and command of
on/off valves.
Multifunction digital contact.
Configuration dip switch.

PS plug-in MT plug-in
PSW wall mounted MTW wall mounted

Fan speed slider, mode Room thermostat, fan


slider, minimum speed slider, mode slider,
temperature probe and room- and minimum
regulation of on/off valves temperature probes and
regulation of on/off valves

EK plug-in iK universal
EKW wall mounted
Electronic control with LCD
Room thermostat, manualand display, room thermostat,
automatic regulation of fan, manual and automatic
manual- and automatic regulation of fan, manual- and
mode, change-over, roomand automatic mode change-over,
minimum temperature room and minimum
probes, regulation of electric temperature probes, regulation
heater, valves (on/off or of electric heater, valves (on/off
modulating), serial or modulating), 0-10 V output
connection for mini-network for the regulation of the energy-
and integration into BMSor saving brushless fan motor,
Idrorelax systems serial connection for mini-
network and integration into
BMS or Idrorelax systems

Notes
Refer to the dedicated product's pages for more information about compatibility between the controllers and the single fan coil.
The iK, EK, EKW controllers installed with a-LIFE and a-LIFE HP have to be combined with the 'HB LIFE' power board (cod. 7349051500).
43

MULTIPLE CONNECTION HYDRONIC TERMINALS


MODEL SIZE NS-NSW (1) PS-PSW (1) MT-MTW (1) AT-ATW (1) SPB (2) SPB (3) Input *
a-LIFE2 10 - 8 8 3 15 9 0,2
20 - 8 8 3 15 9 0,2
30 - 6 6 2 15 9 0,3
40 - 6 6 2 15 5 0,3
50 - 6 6 2 15 4 0,3
60 - 6 6 2 15 4 0,3
70 - 3 3 1 15 3 0,6
80 - 3 3 1 15 2 0,6
90 - 3 3 1 15 2 0,73
100 - 3 3 1 15 2 0,73
i-LIFE2 20 - - - - - - 0.5
40 - - - - - - 0.5
60 - - - - - - 0.6
80 - - - - - - 0.6
100 - - - - - - 0.6
a-LIFE2 HP 30 - 5 5 2 15 3 0,42
40 - 5 5 2 15 3 0,42
50 - 5 5 2 15 2 0,49
60 - 5 5 2 15 2 0,49
70 - 2 2 1 15 2 0,85
80 - 2 2 1 15 2 0,85
90 - 2 2 1 15 2 1
100 - 3 3 1 15 2 1
110 - 1 1 0 15 2 1,3
120 - 1 1 0 15 2 1,3
a-CHD 606 - - 20 15 - - 0,22
706 - - 20 15 - - 0,37
1108 - - 20 15 - - 0,64
2209 - - 20 15 - - 1,35
i-CHD 706 - - 20 15 - - 0,34
1108 - - 20 15 - - 0,76
2209 - - 20 15 - - 1,74
HWD 602 1 0 0 - 15 1 1,3
703 1 0 0 - 15 1 1,3
803 1 0 0 - 15 1 1,55
904 1 0 0 - 15 1 1,55
1003 0 0 0 - 0 0 3,5
1104 0 0 0 - 0 0 3,5
HWD HP 71 0 0 0 - 0 0 2,9
91 0 0 0 - 0 0 2,9
101 0 0 0 - 0 0 7,9
121 0 0 0 - 0 0 9,5

For further information about connections to the units, please refer to the technical instructions of each controller.

Notes
(1) Maximum number of units of the same model that can be connected to a single controller
(2) Maximum number of units of different models and sizes that can be connected to a single controller (installing a SPB kit in each unit)
(3) Maximum number of units of the same size and model that can be connected to a controller (installing a single SPB kit)
(*) Current consumption of each unit in (A)
HYDRONIC TERMINALS_07-2014_ENG_00

You might also like