You are on page 1of 38

Cat Electronic Technician 2015A v1.

0
Configuration

27/7/2017 PM 2:27

C15 Genset (FFH02232)


Parameter Value
Equipment ID NOT PROGRAMMED
Engine Serial Number FFH02232
ECM Serial Number 00786291JL
Software Group Part Number 2948086-00
Software Group Release Date AUG06
Software Group Description C15-MEUI-ACERT-A4

EMCP 3.1
Parameter Value
ECM Part Number 3007645-00
ECM Serial Number 0188B296UA
Software Group Part Number 3041259-00
Software Group Release Date OCT2006
Software Group Description L0 6_3 Standard -- English, 2.1 Prod,
26Oct2006

Description Value TT
Automatic Start/Stop
Engine Start Fault Protection 30 sec
Activation Delay Time
Crank Duration 10 sec
Crank Cycle Rest Interval 10 sec
Engine Purge Cycle Time 0 sec
Maximum Number of Crank 5
Cycles
Cooldown Duration 5 min
Start Aid Activation Time 0 sec
Crank Alert Activation Time 0 sec
Crank Terminate RPM 400 rpm
Engine Fuel Type Configuration Diesel
Fuel Shutoff Solenoid Type Energized to Run
Configuration
Engine Type Configuration Electronic
Engine Controller J1939 Data Proprietary J1939 Support
Link Support Configuration
Engine Cooldown Speed Rated Speed
Configuration
Engine Operating State Input Hardwired Input
Configuration
Fuel Priming Feature Enable Disabled
Status
Engine Forced Idle Feature Disabled
Enable Status
AVR Desired Voltage Request
Maximum Generator Voltage 5%
Output Bias Percentage
Generator Nominal Output 415 Volts
Voltage
Battery Voltage Monitor
High Battery Voltage Warning 30.0 Volts
Event Threshold
High Battery Voltage Warning 30 sec
Event Notification Delay Time
High Battery Voltage Shutdown 32.0 Volts
Event Threshold
High Battery Voltage Shutdown 2 sec
Event Notification Delay Time
Low Battery Voltage Warning 18.0 Volts
Event Threshold
Low Battery Voltage Warning 10 sec
Event Notification Delay Time
Low Battery Charging System 25.0 Volts
Voltage Warning Event
Threshold
Low Battery Charging System 30 sec
Voltage Warning Event
Notification Delay Time
Digital Inputs
Digital Input #1 Active State Low
Configuration
Digital Input #2 Active State Low
Configuration
Digital Input #3 Active State Low
Configuration
Digital Input #4 Active State Low
Configuration
Digital Input #5 Active State Low
Configuration
Digital Input #6 Active State Low
Configuration
Digital Selectors
Digital Selector #1 Source Input #1
Configuration
Digital Selector #2 Source Input #1
Configuration
Digital Selector #3 Source Input #3
Configuration
Digital Selector #4 Source Input #7
Configuration
Digital Selector #5 Source Disabled or Not Installed
Configuration
Digital Selector #6 Source Disabled or Not Installed
Configuration
Digital Selector #7 Source Disabled or Not Installed
Configuration
Digital Selector #8 Source Disabled or Not Installed
Configuration
Digital Selector #9 Source Disabled or Not Installed
Configuration
Digital Selector #10 Source Disabled or Not Installed
Configuration
Engine Coolant Temperature Monitor
Engine Coolant Temperature Data Link
Sensor Configuration
High Engine Coolant 216 Deg F
Temperature Warning Event
Threshold
High Engine Coolant 2 sec
Temperature Warning Event
Notification Delay Time
High Engine Coolant 225 Deg F
Temperature Shutdown Event
Threshold
High Engine Coolant 10 sec
Temperature Shutdown Event
Notification Delay Time
Low Engine Coolant 70 Deg F
Temperature Warning Event
Threshold
Low Engine Coolant 2 sec
Temperature Warning Event
Notification Delay Time
Engine Coolant Temperature Map #1
Sensor Configuration Code
Engine Oil Pressure Monitor
Engine Oil Pressure Sensor Data Link
Configuration
Low Engine Oil Pressure 35 psi
Warning Event Threshold
Low Idle Low Engine Oil 15 psi
Pressure Warning Event
Threshold
Low Engine Oil Pressure 0 sec
Warning Event Notification
Delay Time
Low Engine Oil Pressure 30 psi
Shutdown Event Threshold
Low Idle Low Engine Oil 10 psi
Pressure Shutdown Event
Threshold
Low Engine Oil Pressure 0 sec
Shutdown Event Notification
Delay Time
Low Engine Oil Pressure Step 1200 rpm
Speed
Engine Oil Pressure Sensor Map #1
Configuration Code
Engine Speed Monitor
Flywheel Teeth 113
Engine Overspeed Setpoint 1770 rpm
Engine Underspeed Warning 1290 rpm
Event Threshold
Engine Underspeed Warning 2.0 sec
Event Notification Delay Time
Engine Underspeed Shutdown 1230 rpm
Event Threshold
Engine Underspeed Shutdown 2.0 sec
Event Notification Delay Time
Engine Speed Sensor Sensor
Configuration
Event Input Functions
Event Input Function #1 Custom Event
Suspect Parameter Number
Event Input Function #1 Failure Condition Exists
Mode Identifier
Event Input Function #1 Event 10 sec
Notification Delay Time
Event Input Function #1 Active High
State Configuration
Event Input Function #2 Fuel Tank Leak
Suspect Parameter Number
Event Input Function #2 Failure Condition Exists
Mode Identifier
Event Input Function #2 Event 0 sec
Notification Delay Time
Event Input Function #2 Active High
State Configuration
Event Input Function #3 Earth Fault
Suspect Parameter Number
Event Input Function #3 Failure Condition Exists
Mode Identifier
Event Input Function #3 Event 0 sec
Notification Delay Time
Event Input Function #3 Active High
State Configuration
Event Input Function #4 Fuel Level
Suspect Parameter Number
Event Input Function #4 Failure Low Warning
Mode Identifier
Event Input Function #4 Event 0 sec
Notification Delay Time
Event Input Function #4 Active High
State Configuration
Event Input Function #5 Disabled or Not Installed
Suspect Parameter Number
Event Input Function #5 Failure Disabled or Not Installed
Mode Identifier
Event Input Function #5 Event Disabled or Not Installed
Notification Delay Time
Event Input Function #5 Active Disabled or Not Installed
State Configuration
Event Input Function #6 Disabled or Not Installed
Suspect Parameter Number
Event Input Function #6 Failure Disabled or Not Installed
Mode Identifier
Event Input Function #6 Event Disabled or Not Installed
Notification Delay Time
Event Input Function #6 Active Disabled or Not Installed
State Configuration
Event Output Functions
Event Output Function #1 Engine Oil Pressure
Suspect Parameter Number
Event Output Function #1 **Disabled
Trigger Condition
Event Output Function #2 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #2 Disabled or Not Installed
Trigger Condition
Event Output Function #3 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #3 Disabled or Not Installed
Trigger Condition
Event Output Function #4 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #4 Disabled or Not Installed
Trigger Condition
Event Output Function #5 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #5 Disabled or Not Installed
Trigger Condition
Event Output Function #6 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #6 Disabled or Not Installed
Trigger Condition
Event Output Function #7 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #7 Disabled or Not Installed
Trigger Condition
Event Output Function #8 Disabled or Not Installed
Suspect Parameter Number
Event Output Function #8 Disabled or Not Installed
Trigger Condition
Event Response Configuration - Diagnostic Events
Air Filter Differential Pressure Activate Warning Condition
Sensor Diagnostic Response
Configuration
Air Filter Differential Pressure No
Sensor Diagnostic Audible Alert
Air Filter Differential Pressure No
Sensor Diagnostic Breaker #1
Trip
Air Filter Differential Pressure No
Sensor Diagnostic Breaker #2
Trip
Ambient Air Temperature Activate Warning Condition
Sensor Diagnostic Response
Configuration
Ambient Air Temperature No
Sensor Diagnostic Audible Alert
Ambient Air Temperature No
Sensor Diagnostic Breaker #1
Trip
Ambient Air Temperature No
Sensor Diagnostic Breaker #2
Trip
Engine Coolant Level Sensor Activate Warning Condition
Diagnostic Response
Configuration
Engine Coolant Level Sensor No
Diagnostic Audible Alert
Engine Coolant Level Sensor No
Diagnostic Breaker #1 Trip
Engine Coolant Level Sensor No
Diagnostic Breaker #2 Trip
Engine Coolant Temperature Activate Warning Condition
Sensor Diagnostic Response
Configuration
Engine Coolant Temperature No
Sensor Diagnostic Audible Alert
Engine Coolant Temperature No
Sensor Diagnostic Breaker #1
Trip
Engine Coolant Temperature No
Sensor Diagnostic Breaker #2
Trip
Engine Oil Level Sensor Activate Warning Condition
Diagnostic Response
Configuration
Engine Oil Level Sensor No
Diagnostic Audible Alert
Engine Oil Level Sensor No
Diagnostic Breaker #1 Trip
Engine Oil Level Sensor No
Diagnostic Breaker #2 Trip
Engine Oil Pressure Sensor Activate Warning Condition
Diagnostic Response
Configuration
Engine Oil Pressure Sensor No
Diagnostic Audible Alert
Engine Oil Pressure Sensor No
Diagnostic Breaker #1 Trip
Engine Oil Pressure Sensor No
Diagnostic Breaker #2 Trip
Engine Oil Temperature Sensor Activate Warning Condition
Diagnostic Response
Configuration
Engine Oil Temperature Sensor No
Diagnostic Audible Alert
Engine Oil Temperature Sensor No
Diagnostic Breaker #1 Trip
Engine Oil Temperature Sensor No
Diagnostic Breaker #2 Trip
Engine Speed Sensor Activate Hard Shutdown
Diagnostic Response Condition
Configuration
Engine Speed Sensor Yes
Diagnostic Audible Alert
Engine Speed Sensor No
Diagnostic Breaker #1 Trip
Engine Speed Sensor No
Diagnostic Breaker #2 Trip
Exhaust Temperature Sensor Activate Warning Condition
Diagnostic Response
Configuration
Exhaust Temperature Sensor No
Diagnostic Audible Alert
Exhaust Temperature Sensor No
Diagnostic Breaker #1 Trip
Exhaust Temperature Sensor No
Diagnostic Breaker #2 Trip
Right Exhaust Temperature Activate Warning Condition
Sensor Diagnostic Response
Configuration
Right Exhaust Temperature No
Sensor Diagnostic Audible Alert
Right Exhaust Temperature No
Sensor Diagnostic Breaker #1
Trip
Right Exhaust Temperature No
Sensor Diagnostic Breaker #2
Trip
Left Exhaust Temperature Activate Warning Condition
Sensor Diagnostic Response
Configuration
Left Exhaust Temperature No
Sensor Diagnostic Audible Alert
Left Exhaust Temperature No
Sensor Diagnostic Breaker #1
Trip
Left Exhaust Temperature No
Sensor Diagnostic Breaker #2
Trip
Fire Extinguisher Pressure Activate Warning Condition
Sensor Diagnostic Response
Configuration
Fire Extinguisher Pressure No
Sensor Audible Alert
Fire Extinguisher Pressure No
Sensor Breaker #1 Trip
Fire Extinguisher Pressure No
Sensor Breaker #2 Trip
Fuel Filter Differential Pressure Activate Warning Condition
Sensor Diagnostic Response
Configuration
Fuel Filter Differential Pressure No
Sensor Diagnostic Audible Alert
Fuel Filter Differential Pressure No
Sensor Diagnostic Breaker #1
Trip
Fuel Filter Differential Pressure No
Sensor Diagnostic Breaker #2
Trip
Fuel Level Sensor Diagnostic Activate Warning Condition
Response Configuration
Fuel Level Sensor Diagnostic No
Audible Alert
Fuel Level Sensor Diagnostic No
Breaker #1 Trip
Fuel Level Sensor Diagnostic No
Breaker #2 Trip
External Tank Fuel Level Activate Warning Condition
Sensor Diagnostic Response
Configuration
External Tank Fuel Level No
Sensor Diagnostic Audible Alert
External Tank Fuel Level No
Sensor Diagnostic Breaker #1
Trip
External Tank Fuel Level No
Sensor Diagnostic Breaker #2
Trip
Generator Bearing #1 Activate Warning Condition
Temperature Sensor Diagnostic
Response Configuration
Generator Bearing #1 No
Temperature Sensor Diagnostic
Audible Alert
Generator Bearing #1 No
Temperature Sensor Diagnostic
Breaker #1 Trip
Generator Bearing #1 No
Temperature Sensor Diagnostic
Breaker #2 Trip
Generator Output Sensing Activate Warning Condition
System Diagnostic Response
Configuration
Generator Output Sensing Yes
System Diagnostic Audible
Alert
Generator Output Sensing No
System Diagnostic Breaker #1
Trip
Generator Output Sensing No
System Diagnostic Breaker #2
Trip
Engine Oil Filter Differential Activate Warning Condition
Pressure Sensor Diagnostic
Response Config
Engine Oil Filter Differential No
Pressure Sensor Diagnostic
Audible Alert
Engine Oil Filter Differential No
Pressure Sensor Diagnostic
Breaker #1 Trip
Engine Oil Filter Differential No
Pressure Sensor Diagnostic
Breaker #2 Trip
Primary Data Link Diagnostic Activate Warning Condition
Response Configuration
Primary Data Link Diagnostic No
Audible Alert
Primary Data Link Diagnostic No
Breaker #1 Trip
Primary Data Link Diagnostic No
Breaker #2 Trip
Starting Air Pressure Sensor Activate Warning Condition
Diagnostic Response
Configuration
Starting Air Pressure Sensor No
Diagnostic Audible Alert
Starting Air Pressure Sensor No
Diagnostic Breaker #1 Trip
Starting Air Pressure Sensor No
Diagnostic Breaker #2 Trip
Battery Charger Failure Activate Warning Condition
Diagnostic Response
Configuration
Battery Charger Failure Yes
Diagnostic Audible Alert
Engine Controller Not Activate Warning Condition
Responding Diagnostic
Response Configuration
Engine Controller Not No
Responding Diagnostic Audible
Alert
Engine Controller Not No
Responding Diagnostic Breaker
#1 Trip
Engine Controller Not No
Responding Diagnostic Breaker
#2 Trip
Event Response Configuration - Engine Protection Events
Air Damper Closed Event Hard Shutdown & Active Only
Response Configuration Condition
Air Damper Closed Event Yes
Audible Alert
High Air Filter Differential Activate Warning Condition
Pressure Warning Event
Response Configuration
High Air Filter Differential Yes
Pressure Warning Event
Audible Alert
High Air Filter Differential No
Pressure Warning Event
Breaker #1 Trip
High Air Filter Differential No
Pressure Warning Event
Breaker #2 Trip
High Air Filter Differential Activate Hard Shutdown
Pressure Shutdown Event Condition
Response Configuration
High Air Filter Differential Yes
Pressure Shutdown Event
Audible Alert
High Air Filter Differential No
Pressure Shutdown Event
Breaker #1 Trip
High Air Filter Differential No
Pressure Shutdown Event
Breaker #2 Trip
Low Air Filter Differential Activate Warning Condition
Pressure Warning Event
Response Configuration
Low Air Filter Differential Yes
Pressure Warning Event
Audible Alert
Low Air Filter Differential No
Pressure Warning Event
Breaker #1 Trip
Low Air Filter Differential No
Pressure Warning Event
Breaker #2 Trip
Low Air Filter Differential Yes
Pressure Warning Event Fault
Protection Timer
Low Air Filter Differential Activate Hard Shutdown
Pressure Shutdown Event Condition
Response Configuration
Low Air Filter Differential Yes
Pressure Shutdown Event
Audible Alert
Low Air Filter Differential No
Pressure Shutdown Event
Breaker #1 Trip
Low Air Filter Differential No
Pressure Shutdown Event
Breaker #2 Trip
Low Air Filter Differential Yes
Pressure Shutdown Event Fault
Protection Timer
Emergency Stop Activated Activate Hard Shutdown
Event Response Configuration Condition
Emergency Stop Activated Yes
Event Audible Alert
Emergency Stop Activated No
Event Breaker #1 Trip
Emergency Stop Activated No
Event Breaker #2 Trip
High Engine Coolant Level Activate Warning Condition
Warning Event Response
Configuration
High Engine Coolant Level Yes
Warning Event Audible Alert
High Engine Coolant Level No
Warning Event Breaker #1 Trip
High Engine Coolant Level No
Warning Event Breaker #2 Trip
High Engine Coolant Level Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Engine Coolant Level Yes
Shutdown Event Audible Alert
High Engine Coolant Level No
Shutdown Event Breaker #1
Trip
High Engine Coolant Level No
Shutdown Event Breaker #2
Trip
Low Engine Coolant Level Activate Warning Condition
Warning Event Response
Configuration
Low Engine Coolant Level Yes
Warning Event Audible Alert
Low Engine Coolant Level No
Warning Event Breaker #1 Trip
Low Engine Coolant Level No
Warning Event Breaker #2 Trip
Low Engine Coolant Level Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Low Engine Coolant Level Yes
Shutdown Event Audible Alert
Low Engine Coolant Level No
Shutdown Event Breaker #1
Trip
Low Engine Coolant Level No
Shutdown Event Breaker #2
Trip
High Engine Coolant Activate Warning Condition
Temperature Warning Event
Response Configuration
High Engine Coolant Yes
Temperature Warning Event
Audible Alert
High Engine Coolant No
Temperature Warning Event
Breaker #1 Trip
High Engine Coolant No
Temperature Warning Event
Breaker #2 Trip
High Engine Coolant Yes
Temperature Warning Event
Fault Protection Timer
High Engine Coolant Activate Hard Shutdown
Temperature Shutdown Event Condition
Response Configuration
High Engine Coolant Yes
Temperature Shutdown Event
Audible Alert
High Engine Coolant No
Temperature Shutdown Event
Breaker #1 Trip
High Engine Coolant No
Temperature Shutdown Event
Breaker #2 Trip
High Engine Coolant Yes
Temperature Shutdown Event
Fault Protection Timer
Low Engine Coolant Activate Warning Condition
Temperature Warning Event
Response Configuration
Low Engine Coolant Yes
Temperature Warning Event
Audible Alert
Low Engine Coolant No
Temperature Warning Event
Breaker #1 Trip
Low Engine Coolant No
Temperature Warning Event
Breaker #2 Trip
Low Engine Coolant No
Temperature Warning Event
Fault Protection Timer
Engine Failure To Start Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Engine Failure To Start Yes
Shutdown Event Audible Alert
Engine Failure To Start No
Shutdown Event Breaker #1
Trip
Engine Failure To Start No
Shutdown Event Breaker #2
Trip
High Engine Oil Level Warning Activate Warning Condition
Event Response Configuration
High Engine Oil Level Warning Yes
Event Audible Alert
High Engine Oil Level Warning No
Event Breaker #1 Trip
High Engine Oil Level Warning No
Event Breaker #2 Trip
High Engine Oil Level Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Engine Oil Level Yes
Shutdown Event Audible Alert
High Engine Oil Level No
Shutdown Event Breaker #1
Trip
High Engine Oil Level No
Shutdown Event Breaker #2
Trip
Low Engine Oil Level Warning Activate Warning Condition
Event Response Configuration
Low Engine Oil Level Warning Yes
Event Audible Alert
Low Engine Oil Level Warning No
Event Breaker #1 Trip
Low Engine Oil Level Warning No
Event Breaker #2 Trip
Low Engine Oil Level Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Low Engine Oil Level Shutdown Yes
Event Audible Alert
Low Engine Oil Level Shutdown No
Event Breaker #1 Trip
Low Engine Oil Level Shutdown No
Event Breaker #2 Trip
Low Engine Oil Pressure Activate Warning Condition
Warning Event Response
Configuration
Low Engine Oil Pressure Yes
Warning Event Audible Alert
Low Engine Oil Pressure No
Warning Event Breaker #1 Trip
Low Engine Oil Pressure No
Warning Event Breaker #2 Trip
Low Engine Oil Pressure Yes
Warning Event Fault Protection
Timer
Low Engine Oil Pressure Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Low Engine Oil Pressure Yes
Shutdown Event Audible Alert
Low Engine Oil Pressure No
Shutdown Event Breaker #1
Trip
Low Engine Oil Pressure No
Shutdown Event Breaker #2
Trip
Low Engine Oil Pressure Yes
Shutdown Event Fault
Protection Timer
High Engine Oil Temperature Activate Warning Condition
Warning Event Response
Configuration
High Engine Oil Temperature Yes
Warning Event Audible Alert
High Engine Oil Temperature No
Warning Event Breaker #1 Trip
High Engine Oil Temperature No
Warning Event Breaker #2 Trip
High Engine Oil Temperature No
Warning Event Fault Protection
Timer
High Engine Oil Temperature Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Engine Oil Temperature Yes
Shutdown Event Audible Alert
High Engine Oil Temperature No
Shutdown Event Breaker #1
Trip
High Engine Oil Temperature No
Shutdown Event Breaker #2
Trip
High Engine Oil Temperature No
Shutdown Event Fault
Protection Timer
Low Engine Oil Temperature Activate Warning Condition
Warning Event Response
Configuration
Low Engine Oil Temperature Yes
Warning Event Audible Alert
Low Engine Oil Temperature No
Warning Event Breaker #1 Trip
Low Engine Oil Temperature No
Warning Event Breaker #2 Trip
Low Engine Oil Temperature Yes
Warning Event Fault Protection
Timer
Low Engine Oil Temperature Disable Condition
Shutdown Event Response
Configuration
Low Engine Oil Temperature No
Shutdown Event Audible Alert
Low Engine Oil Temperature No
Shutdown Event Breaker #1
Trip
Low Engine Oil Temperature No
Shutdown Event Breaker #2
Trip
Low Engine Oil Temperature No
Shutdown Event Fault
Protection Timer
Unexpected Engine Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Unexpected Engine Shutdown Yes
Event Audible Alert
Unexpected Engine Shutdown No
Event Breaker #1 Trip
Unexpected Engine Shutdown No
Event Breaker #2 Trip
Engine Overspeed Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Engine Overspeed Shutdown Yes
Event Audible Alert
Engine Overspeed Shutdown No
Event Breaker #1 Trip
Engine Overspeed Shutdown No
Event Breaker #2 Trip
Engine Underspeed Warning Activate Warning Condition
Event Response Configuration
Engine Underspeed Warning Yes
Event Audible Alert
Engine Underspeed Warning No
Event Breaker #1 Trip
Engine Underspeed Warning No
Event Breaker #2 Trip
Engine Underspeed Warning Yes
Event Fault Protection Timer
Engine Underspeed Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Engine Underspeed Shutdown Yes
Event Audible Alert
Engine Underspeed Shutdown No
Event Breaker #1 Trip
Engine Underspeed Shutdown No
Event Breaker #2 Trip
Engine Underspeed Shutdown Yes
Event Fault Protection Timer
High Exhaust Temperature Activate Warning Condition
Warning Event Response
Configuration
High Exhaust Temperature Yes
Warning Event Audible Alert
High Exhaust Temperature No
Warning Event Breaker #1 Trip
High Exhaust Temperature No
Warning Event Breaker #2 Trip
High Exhaust Temperature No
Warning Event Fault Protection
Timer
High Exhaust Temperature Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Exhaust Temperature Yes
Shutdown Event Audible Alert
High Exhaust Temperature No
Shutdown Event Breaker #1
Trip
High Exhaust Temperature No
Shutdown Event Breaker #2
Trip
High Exhaust Temperature No
Shutdown Event Fault
Protection Timer
Low Exhaust Temperature Activate Warning Condition
Warning Event Response
Configuration
Low Exhaust Temperature Yes
Warning Event Audible Alert
Low Exhaust Temperature No
Warning Event Breaker #1 Trip
Low Exhaust Temperature No
Warning Event Breaker #2 Trip
Low Exhaust Temperature Yes
Warning Event Fault Protection
Timer
Low Exhaust Temperature Disable Condition
Shutdown Event Response
Configuration
Low Exhaust Temperature No
Shutdown Event Audible Alert
Low Exhaust Temperature No
Shutdown Event Breaker #1
Trip
Low Exhaust Temperature No
Shutdown Event Breaker #2
Trip
Low Exhaust Temperature Yes
Shutdown Event Fault
Protection Timer
High Right Exhaust Activate Warning Condition
Temperature Warning Event
Response Configuration
High Right Exhaust Yes
Temperature Warning Event
Audible Alert
High Right Exhaust No
Temperature Warning Event
Breaker #1 Trip
High Right Exhaust No
Temperature Warning Event
Breaker #2 Trip
High Right Exhaust No
Temperature Warning Event
Fault Protection Timer
High Right Exhaust Activate Hard Shutdown
Temperature Shutdown Event Condition
Response Configuration
High Right Exhaust Yes
Temperature Shutdown Event
Audible Alert
High Right Exhaust No
Temperature Shutdown Event
Breaker #1 Trip
High Right Exhaust No
Temperature Shutdown Event
Breaker #2 Trip
High Right Exhaust No
Temperature Shutdown Event
Fault Protection Timer
Low Right Exhaust Activate Warning Condition
Temperature Warning Event
Response Configuration
Low Right Exhaust Yes
Temperature Warning Event
Audible Alert
Low Right Exhaust No
Temperature Warning Event
Breaker #1 Trip
Low Right Exhaust No
Temperature Warning Event
Breaker #2 Trip
Low Right Exhaust Yes
Temperature Warning Event
Fault Protection Timer
Low Right Exhaust Disable Condition
Temperature Shutdown Event
Response Configuration
Low Right Exhaust No
Temperature Shutdown Event
Audible Alert
Low Right Exhaust No
Temperature Shutdown Event
Breaker #1 Trip
Low Right Exhaust No
Temperature Shutdown Event
Breaker #2 Trip
Low Right Exhaust No
Temperature Shutdown Event
Fault Protection Timer
High Left Exhaust Temperature Activate Warning Condition
Warning Event Response
Configuration
High Left Exhaust Temperature Yes
Warning Event Audible Alert
High Left Exhaust Temperature No
Warning Event Breaker #1 Trip
High Left Exhaust Temperature No
Warning Event Breaker #2 Trip
High Left Exhaust Temperature No
Warning Event Fault Protection
Timer
High Left Exhaust Temperature Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Left Exhaust Temperature Yes
Shutdown Event Audible Alert
High Left Exhaust Temperature No
Shutdown Event Breaker #1
Trip
High Left Exhaust Temperature No
Shutdown Event Breaker #2
Trip
High Left Exhaust Temperature No
Shutdown Event Fault
Protection Timer
Low Left Exhaust Temperature Activate Warning Condition
Warning Event Response
Configuration
Low Left Exhaust Temperature Yes
Warning Event Audible Alert
Low Left Exhaust Temperature No
Warning Event Breaker #1 Trip
Low Left Exhaust Temperature No
Warning Event Breaker #2 Trip
Low Left Exhaust Temperature Yes
Warning Event Fault Protection
Timer
Low Left Exhaust Temperature Disable Condition
Shutdown Event Response
Configuration
Low Left Exhaust Temperature No
Shutdown Event Audible Alert
Low Left Exhaust Temperature No
Shutdown Event Breaker #1
Trip
Low Left Exhaust Temperature No
Shutdown Event Breaker #2
Trip
Low Left Exhaust Temperature No
Shutdown Event Fault
Protection Timer
High Fuel Filter Differential Activate Warning Condition
Pressure Warning Event
Response Configuration
High Fuel Filter Differential Yes
Pressure Warning Event
Audible Alert
High Fuel Filter Differential No
Pressure Warning Event
Breaker #1 Trip
High Fuel Filter Differential No
Pressure Warning Event
Breaker #2 Trip
High Fuel Filter Differential Activate Hard Shutdown
Pressure Shutdown Event Condition
Response Config
High Fuel Filter Differential Yes
Pressure Shutdown Event
Audible Alert
High Fuel Filter Differential No
Pressure Shutdown Event
Breaker #1 Trip
High Fuel Filter Differential No
Pressure Shutdown Event
Breaker #2 Trip
Low Fuel Filter Differential Activate Warning Condition
Pressure Warning Event
Response Configuration
Low Fuel Filter Differential Yes
Pressure Warning Event
Audible Alert
Low Fuel Filter Differential No
Pressure Warning Event
Breaker #1 Trip
Low Fuel Filter Differential No
Pressure Warning Event
Breaker #2 Trip
Low Fuel Filter Differential Yes
Pressure Warning Event Fault
Protection Timer
Low Fuel Filter Differential Activate Hard Shutdown
Pressure Shutdown Event Condition
Response Configuration
Low Fuel Filter Differential Yes
Pressure Shutdown Event
Audible Alert
Low Fuel Filter Differential No
Pressure Shutdown Event
Breaker #1 Trip
Low Fuel Filter Differential No
Pressure Shutdown Event
Breaker #2 Trip
Low Fuel Filter Differential Yes
Pressure Shutdown Event Fault
Protection Timer
High Fuel Level Warning Event Activate Warning Condition
Response Configuration
High Fuel Level Warning Event Yes
Audible Alert
High Fuel Level Warning Event No
Breaker #1 Trip
High Fuel Level Warning Event No
Breaker #2 Trip
High Fuel Level Shutdown Activate Hard Shutdown
Event Response Configuration Condition
High Fuel Level Shutdown Yes
Event Audible Alert
High Fuel Level Shutdown No
Event Breaker #1 Trip
High Fuel Level Shutdown No
Event Breaker #2 Trip
Low Fuel Level Warning Event Activate Warning Condition
Response Configuration
Low Fuel Level Warning Event Yes
Audible Alert
Low Fuel Level Warning Event No
Breaker #1 Trip
Low Fuel Level Warning Event No
Breaker #2 Trip
Low Fuel Level Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Low Fuel Level Shutdown Yes
Event Audible Alert
Low Fuel Level Shutdown No
Event Breaker #1 Trip
Low Fuel Level Shutdown No
Event Breaker #2 Trip
External Tank High Fuel Level Activate Warning Condition
Warning Event Response
Configuration
External Tank High Fuel Level Yes
Warning Event Audible Alert
External Tank High Fuel Level No
Warning Event Breaker #1 Trip
External Tank High Fuel Level No
Warning Event Breaker #2 Trip
External Tank High Fuel Level Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
External Tank High Fuel Level Yes
Shutdown Event Audible Alert
External Tank High Fuel Level No
Shutdown Event Breaker #1
Trip
External Tank High Fuel Level No
Shutdown Event Breaker #2
Trip
External Tank Low Fuel Level Activate Warning Condition
Warning Event Response
Configuration
External Tank Low Fuel Level Yes
Warning Event Audible Alert
External Tank Low Fuel Level No
Warning Event Breaker #1 Trip
External Tank Low Fuel Level No
Warning Event Breaker #2 Trip
External Tank Low Fuel Level Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
External Tank Low Fuel Level Yes
Shutdown Event Audible Alert
External Tank Low Fuel Level No
Shutdown Event Breaker #1
Trip
External Tank Low Fuel Level No
Shutdown Event Breaker #2
Trip
Fuel Leak Event Response Activate Warning Condition
Configuration
Fuel Leak Event Audible Alert Yes
Fuel Leak Event Breaker #1 No
Trip
Fuel Leak Event Breaker #2 No
Trip
High Engine Oil Filter Activate Warning Condition
Differential Pressure Warning
Event Response Config
High Engine Oil Filter Yes
Differential Pressure Warning
Event Audible Alert
High Engine Oil Filter No
Differential Pressure Warning
Event Breaker #1 Trip
High Engine Oil Filter No
Differential Pressure Warning
Event Breaker #2 Trip
High Engine Oil Filter Activate Hard Shutdown
Differential Pressure Shutdown Condition
Event Response Config
High Engine Oil Filter Yes
Differential Pressure Shutdown
Event Audible Alert
High Engine Oil Filter No
Differential Pressure Shutdown
Event Breaker #1 Trip
High Engine Oil Filter No
Differential Pressure Shutdown
Event Breaker #2 Trip
Low Engine Oil Filter Activate Warning Condition
Differential Pressure Warning
Event Response Config
Low Engine Oil Filter Yes
Differential Pressure Warning
Event Audible Alert
Low Engine Oil Filter No
Differential Pressure Warning
Event Breaker #1 Trip
Low Engine Oil Filter No
Differential Pressure Warning
Event Breaker #2 Trip
Low Engine Oil Filter Yes
Differential Pressure Warning
Fault Protection Timer
Low Engine Oil Filter Activate Hard Shutdown
Differential Pressure Shutdown Condition
Event Response Config
Low Engine Oil Filter Yes
Differential Pressure Shutdown
Event Audible Alert
Low Engine Oil Filter No
Differential Pressure Shutdown
Event Breaker #1 Trip
Low Engine Oil Filter No
Differential Pressure Shutdown
Event Breaker #2 Trip
Low Engine Oil Filter Yes
Differential Pressure Shutdown
Fault Protection Timer
High Starting Air Pressure Activate Warning Condition
Warning Event Response
Configuration
High Starting Air Pressure Yes
Warning Event Audible Alert
High Starting Air Pressure No
Warning Event Breaker #1 Trip
High Starting Air Pressure No
Warning Event Breaker #2 Trip
High Starting Air Pressure Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Starting Air Pressure Yes
Shutdown Event Audible Alert
High Starting Air Pressure No
Shutdown Event Breaker #1
Trip
High Starting Air Pressure No
Shutdown Event Breaker #2
Trip
Low Starting Air Pressure Activate Warning Condition
Warning Event Response
Configuration
Low Starting Air Pressure Yes
Warning Event Audible Alert
Low Starting Air Pressure No
Warning Event Breaker #1 Trip
Low Starting Air Pressure No
Warning Event Breaker #2 Trip
Low Starting Air Pressure Yes
Warning Event Fault Protection
Timer
Low Starting Air Pressure Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Low Starting Air Pressure Yes
Shutdown Event Audible Alert
Low Starting Air Pressure No
Shutdown Event Breaker #1
Trip
Low Starting Air Pressure No
Shutdown Event Breaker #2
Trip
Low Starting Air Pressure Yes
Shutdown Event Fault
Protection Timer
High Gas Pressure Warning Activate Warning Condition
Event Response Configuration
High Gas Pressure Warning Yes
Event Audible Alert
High Gas Pressure Warning No
Event Breaker #1 Trip
High Gas Pressure Warning No
Event Breaker #2 Trip
High Gas Pressure Shutdown Activate Hard Shutdown
Event Response Configuration Condition
High Gas Pressure Shutdown Yes
Event Audible Alert
High Gas Pressure Shutdown No
Event Breaker #1 Trip
High Gas Pressure Shutdown No
Event Breaker #2 Trip
Low Gas Pressure Warning Activate Warning Condition
Event Response Configuration
Low Gas Pressure Warning Yes
Event Audible Alert
Low Gas Pressure Warning No
Event Breaker #1 Trip
Low Gas Pressure Warning No
Event Breaker #2 Trip
Low Gas Pressure Shutdown Activate Hard Shutdown
Event Response Configuration Condition
Low Gas Pressure Shutdown Yes
Event Audible Alert
Low Gas Pressure Shutdown No
Event Breaker #1 Trip
Low Gas Pressure Shutdown No
Event Breaker #2 Trip
Engine Intake Manifold Charge Activate Hard Shutdown
Combustion Event Response Condition
Configuration
Engine Intake Manifold Charge Yes
Combustion Event Audible Alert
Engine Intake Manifold Charge No
Combustion Event Loss of
Utility
Engine Intake Manifold Charge No
Combustion Event Breaker #1
Trip
Engine Intake Manifold Charge No
Combustion Event Breaker #2
Trip
Engine Intake Manifold Charge No
Combustion Event Fault
Protection Timer
Event Response Configuration - Generator Protection Events
High Generator Bearing #1 Activate Warning Condition
Temperature Warning Event
Response Configuration
High Generator Bearing #1 Yes
Temperature Warning Event
Audible Alert
High Generator Bearing #1 No
Temperature Warning Event
Breaker #1 Trip
High Generator Bearing #1 No
Temperature Warning Event
Breaker #2 Trip
High Generator Bearing #1 No
Temperature Warning Event
Fault Protection Timer
High Generator Bearing #1 Activate Hard Shutdown
Temperature Shutdown Event Condition
Response Configuration
High Generator Bearing #1 Yes
Temperature Shutdown Event
Audible Alert
High Generator Bearing #1 No
Temperature Shutdown Event
Breaker #1 Trip
High Generator Bearing #1 No
Temperature Shutdown Event
Breaker #2 Trip
High Generator Bearing #1 No
Temperature Shutdown Event
Fault Protection Timer
Low Generator Bearing #1 Activate Warning Condition
Temperature Warning Event
Response Configuration
Low Generator Bearing #1 Yes
Temperature Warning Event
Audible Alert
Low Generator Bearing #1 No
Temperature Warning Event
Breaker #1 Trip
Low Generator Bearing #1 No
Temperature Warning Event
Breaker #2 Trip
Low Generator Bearing #1 Yes
Temperature Warning Event
Fault Protection Timer
Low Generator Bearing #1 Disable Condition
Temperature Shutdown Event
Response Configuration
Low Generator Bearing #1 No
Temperature Shutdown Event
Audible Alert
Low Generator Bearing #1 No
Temperature Shutdown Event
Breaker #1 Trip
Low Generator Bearing #1 No
Temperature Shutdown Event
Breaker #2 Trip
Low Generator Bearing #1 No
Temperature Shutdown Event
Fault Protection Timer
Earth Fault Event Response Activate Hard Shutdown
Configuration Condition
Earth Fault Event Audible Alert Yes
Earth Fault Event Breaker #1 No
Trip
Earth Fault Event Breaker #2 No
Trip
Generator Winding #1 High Activate Warning Condition
Temperature Warning Event
Response Configuration
Generator Winding #1 High Yes
Temperature Warning Event
Audible Alert
Generator Winding #1 High No
Temperature Warning Event
Breaker #1 Trip
Generator Winding #1 High No
Temperature Warning Event
Breaker #2 Trip
Generator Winding #1 High No
Temperature Warning Event
Fault Protection Timer
Generator Winding #2 High Activate Warning Condition
Temperature Warning Event
Response Configuration
Generator Winding #2 High Yes
Temperature Warning Event
Audible Alert
Generator Winding #2 High No
Temperature Warning Event
Breaker #1 Trip
Generator Winding #2 High No
Temperature Warning Event
Breaker #2 Trip
Generator Winding #2 High No
Temperature Warning Event
Fault Protection Timer
Generator Winding #3 High Activate Warning Condition
Temperature Warning Event
Response Configuration
Generator Winding #3 High Yes
Temperature Warning Event
Audible Alert
Generator Winding #3 High No
Temperature Warning Event
Breaker #1 Trip
Generator Winding #3 High No
Temperature Warning Event
Breaker #2 Trip
Generator Winding #3 High No
Temperature Warning Event
Fault Protection Timer
Generator Winding #1 High Activate Hard Shutdown
Temperature Shutdown Event Condition
Response Configuration
Generator Winding #1 High Yes
Temperature Shutdown Event
Audible Alert
Generator Winding #1 High No
Temperature Shutdown Event
Breaker #1 Trip
Generator Winding #1 High No
Temperature Shutdown Event
Breaker #2 Trip
Generator Winding #1 High No
Temperature Shutdown Event
Fault Protection Timer
Generator Winding #2 High Data Invalid
Temperature Shutdown Event
Response Configuration
Generator Winding #2 High Yes
Temperature Shutdown Event
Audible Alert
Generator Winding #2 High No
Temperature Shutdown Event
Breaker #1 Trip
Generator Winding #2 High No
Temperature Shutdown Event
Breaker #2 Trip
Generator Winding #2 High No
Temperature Shutdown Event
Fault Protection Timer
Generator Winding #3 High Activate Hard Shutdown
Temperature Shutdown Event Condition
Response Configuration
Generator Winding #3 High Yes
Temperature Shutdown Event
Audible Alert
Generator Winding #3 High No
Temperature Shutdown Event
Breaker #1 Trip
Generator Winding #3 High No
Temperature Shutdown Event
Breaker #2 Trip
Generator Winding #3 High No
Temperature Shutdown Event
Fault Protection Timer
Event Response Configuration - Other System Events
High Ambient Air Temperature Activate Warning Condition
Warning Event Response
Configuration
High Ambient Air Temperature Yes
Warning Event Audible Alert
High Ambient Air Temperature No
Warning Event Breaker #1 Trip
High Ambient Air Temperature No
Warning Event Breaker #2 Trip
High Ambient Air Temperature No
Warning Event Fault Protection
Timer
High Ambient Air Temperature Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Ambient Air Temperature Yes
Shutdown Event Audible Alert
High Ambient Air Temperature No
Shutdown Event Breaker #1
Trip
High Ambient Air Temperature No
Shutdown Event Breaker #2
Trip
High Ambient Air Temperature No
Shutdown Event Fault
Protection Timer
Low Ambient Air Temperature Activate Warning Condition
Warning Event Response
Configuration
Low Ambient Air Temperature Yes
Warning Event Audible Alert
Low Ambient Air Temperature No
Warning Event Breaker #1 Trip
Low Ambient Air Temperature No
Warning Event Breaker #2 Trip
Low Ambient Air Temperature Disable Condition
Shutdown Event Response
Configuration
Low Ambient Air Temperature No
Shutdown Event Audible Alert
Low Ambient Air Temperature No
Shutdown Event Breaker #1
Trip
Low Ambient Air Temperature No
Shutdown Event Breaker #2
Trip
Automatic Transfer Switch In Active Only Condition
Normal Position Event
Response Configuration
Automatic Transfer Switch In No
Normal Position Event Audible
Alert
Automatic Transfer Switch In Active Only Condition
Emergency Position Event
Response Config
Automatic Transfer Switch In No
Emergency Position Event
Audible Alert
High Battery Voltage Warning Activate Warning Condition
Event Response Configuration
High Battery Voltage Warning Yes
Event Audible Alert
High Battery Voltage Warning No
Event Breaker #1 Trip
High Battery Voltage Warning No
Event Breaker #2 Trip
High Battery Voltage Shutdown Activate Soft Shutdown
Event Response Configuration Condition
High Battery Voltage Shutdown Yes
Event Audible Alert
High Battery Voltage Shutdown No
Event Breaker #1 Trip
High Battery Voltage Shutdown No
Event Breaker #2 Trip
Low Battery Voltage Warning Activate Warning Condition
Event Response Configuration
Low Battery Voltage Warning Yes
Event Audible Alert
Low Battery Voltage Warning No
Event Breaker #1 Trip
Low Battery Voltage Warning No
Event Breaker #2 Trip
Low Battery Voltage Warning No
Event Fault Protection Timer
Low Battery Charging System Disable Condition
Voltage Warning Event
Response Configuration
Low Battery Charging System No
Voltage Warning Event Audible
Alert
Low Battery Charging System No
Voltage Warning Event Breaker
#1 Trip
Low Battery Charging System No
Voltage Warning Event Breaker
#2 Trip
Low Battery Charging System No
Voltage Warning Event Fault
Protection Timer
Engine In Cooldown Event Active Only Condition
Response Configuration
Engine In Cooldown Event No
Audible Alert
Engine Speed-Generator Activate Warning Condition
Output Freq Mismatch Warning
Event Response Config
Engine Speed-Generator Yes
Output Freq Mismatch Warning
Event Audible Alert
Engine Speed-Generator No
Output Freq Mismatch Warning
Event Breaker #1 Trip
Engine Speed-Generator No
Output Freq Mismatch Warning
Event Breaker #2 Trip
High Fire Extinguisher Pressure Activate Warning Condition
Warning Event Response
Configuration
High Fire Extinguisher Pressure Yes
Warning Event Audible Alert
High Fire Extinguisher Pressure No
Warning Event Breaker #1 Trip
High Fire Extinguisher Pressure No
Warning Event Breaker #2 Trip
High Fire Extinguisher Pressure Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
High Fire Extinguisher Pressure Yes
Shutdown Event Audible Alert
High Fire Extinguisher Pressure No
Shutdown Event Breaker #1
Trip
High Fire Extinguisher Pressure No
Shutdown Event Breaker #2
Trip
Low Fire Extinguisher Pressure Activate Warning Condition
Warning Event Response
Configuration
Low Fire Extinguisher Pressure Yes
Warning Event Audible Alert
Low Fire Extinguisher Pressure No
Warning Event Breaker #1 Trip
Low Fire Extinguisher Pressure No
Warning Event Breaker #2 Trip
Low Fire Extinguisher Pressure No
Warning Event Fault Protection
Timer
Low Fire Extinguisher Pressure Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Low Fire Extinguisher Pressure Yes
Shutdown Event Audible Alert
Low Fire Extinguisher Pressure No
Shutdown Event Breaker #1
Trip
Low Fire Extinguisher Pressure No
Shutdown Event Breaker #2
Trip
Low Fire Extinguisher Pressure No
Shutdown Event Fault
Protection Timer
Generator Control Not in Activate Warning Condition
Automatic Warning Event
Response Configuration
Generator Control Not in Yes
Automatic Warning Event
Audible Alert
Generator Breaker Locked Out Warning & Active Only
Warning Event Response Condition
Configuration
Generator Breaker Locked Out Yes
Warning Event Audible Alert
Generator Breaker Locked Out No
Warning Event Breaker #1 Trip
Generator Breaker Locked Out No
Warning Event Breaker #2 Trip
Utility Breaker Locked Out Disable Condition
Warning Event Response
Configuration
Utility Breaker Locked Out No
Warning Event Audible Alert
Utility Breaker Locked Out No
Warning Event Breaker #1 Trip
Utility Breaker Locked Out No
Warning Event Breaker #2 Trip
Earth Leakage Event Response Activate Hard Shutdown
Configuration Condition
Earth Leakage Event Audible Yes
Alert
Earth Leakage Event Breaker No
#1 Trip
Earth Leakage Event Breaker No
#2 Trip
Event Response Configuration - Custom Events
Custom Event #1 High Warning Activate Warning Condition
Event Response Configuration
Custom Event #1 High Warning Yes
Event Audible Alert
Custom Event #1 High Warning No
Event Breaker #1 Trip
Custom Event #1 High Warning No
Event Breaker #2 Trip
Custom Event #1 High Warning No
Event Fault Protection Timer
Custom Event #1 High Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #1 High Yes
Shutdown Event Audible Alert
Custom Event #1 High No
Shutdown Event Breaker #1
Trip
Custom Event #1 High No
Shutdown Event Breaker #2
Trip
Custom Event #1 High No
Shutdown Event Fault
Protection Timer
Custom Event #1 Low Warning Activate Warning Condition
Event Response Configuration
Custom Event #1 Low Warning Yes
Event Audible Alert
Custom Event #1 Low Warning No
Event Breaker #1 Trip
Custom Event #1 Low Warning No
Event Breaker #2 Trip
Custom Event #1 Low Warning No
Event Fault Protection Timer
Custom Event #1 Low Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #1 Low Yes
Shutdown Event Audible Alert
Custom Event #1 Low No
Shutdown Event Breaker #1
Trip
Custom Event #1 Low No
Shutdown Event Breaker #2
Trip
Custom Event #1 Low No
Shutdown Event Fault
Protection Timer
Custom Event #1 Condition Active Only Condition
Exists Event Response
Configuration
Custom Event #1 Condition No
Exists Event Audible Alert
Custom Event #1 Condition No
Exists Event Loss of Utility
Custom Event #1 Condition No
Exists Event Breaker #1 Trip
Custom Event #1 Condition No
Exists Event Breaker #2 Trip
Custom Event #1 Condition No
Exists Event Fault Protection
Timer
Custom Event #2 High Warning Activate Warning Condition
Event Response Configuration
Custom Event #2 High Warning Yes
Event Audible Alert
Custom Event #2 High Warning No
Event Breaker #1 Trip
Custom Event #2 High Warning No
Event Breaker #2 Trip
Custom Event #2 High Warning No
Event Fault Protection Timer
Custom Event #2 High Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #2 High Yes
Shutdown Audible Alert
Custom Event #2 High No
Shutdown Breaker #1 Trip
Custom Event #2 High No
Shutdown Breaker #2 Trip
Custom Event #2 High No
Shutdown Fault Protection
Timer
Custom Event #2 Low Warning Activate Warning Condition
Event Response Configuration
Custom Event #2 Low Warning Yes
Audible Alert
Custom Event #2 Low Warning No
Breaker #1 Trip
Custom Event #2 Low Warning No
Breaker #2 Trip
Custom Event #2 Low Warning No
Fault Protection Timer
Custom Event #2 Low Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #2 Low Yes
Shutdown Event Audible Alert
Custom Event #2 Low No
Shutdown Event Breaker #1
Trip
Custom Event #2 Low No
Shutdown Event Breaker #2
Trip
Custom Event #2 Low No
Shutdown Event Fault
Protection Timer
Custom Event #2 Condition Active Only Condition
Exists Event Response
Configuration
Custom Event #2 Condition No
Exists Event Audible Alert
Custom Event #2 Condition No
Exists Event Loss of Utility
Custom Event #2 Condition No
Exists Event Breaker #1 Trip
Custom Event #2 Condition No
Exists Event Breaker #2 Trip
Custom Event #2 Condition No
Exists Event Fault Protection
Timer
Custom Event #3 High Warning Activate Warning Condition
Event Response Configuration
Custom Event #3 High Warning Yes
Event Audible Alert
Custom Event #3 High Warning No
Event Breaker #1 Trip
Custom Event #3 High Warning No
Event Breaker #2 Trip
Custom Event #3 High Warning No
Event Fault Protection Timer
Custom Event #3 High Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #3 High Yes
Shutdown Event Audible Alert
Custom Event #3 High No
Shutdown Event Breaker #1
Trip
Custom Event #3 High No
Shutdown Event Breaker #2
Trip
Custom Event #3 High No
Shutdown Event Fault
Protection Timer
Custom Event #3 Low Warning Activate Warning Condition
Event Response Configuration
Custom Event #3 Low Warning Yes
Event Audible Alert
Custom Event #3 Low Warning No
Event Breaker #1 Trip
Custom Event #3 Low Warning No
Event Breaker #2 Trip
Custom Event #3 Low Warning No
Event Fault Protection Timer
Custom Event #3 Low Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #3 Low Yes
Shutdown Event Audible Alert
Custom Event #3 Low No
Shutdown Event Breaker #1
Trip
Custom Event #3 Low No
Shutdown Event Breaker #2
Trip
Custom Event #3 Low No
Shutdown Event Fault
Protection Timer
Custom Event #3 Condition Active Only Condition
Exists Event Response
Configuration
Custom Event #3 Condition No
Exists Event Audible Alert
Custom Event #3 Condition No
Exists Event Loss of Utility
Custom Event #3 Condition No
Exists Event Breaker #1 Trip
Custom Event #3 Condition No
Exists Event Breaker #2 Trip
Custom Event #3 Condition No
Exists Event Fault Protection
Timer
Custom Event #4 High Warning Activate Warning Condition
Event Response Configuration
Custom Event #4 High Warning Yes
Event Audible Alert
Custom Event #4 High Warning No
Event Breaker #1 Trip
Custom Event #4 High Warning No
Event Breaker #2 Trip
Custom Event #4 High Warning No
Event Fault Protection Timer
Custom Event #4 High Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #4 High Yes
Shutdown Event Audible Alert
Custom Event #4 High No
Shutdown Event Breaker #1
Trip
Custom Event #4 High No
Shutdown Event Breaker #2
Trip
Custom Event #4 High No
Shutdown Event Fault
Protection Timer
Custom Event #4 Low Warning Activate Warning Condition
Event Response Configuration
Custom Event #4 Low Warning Yes
Event Audible Alert
Custom Event #4 Low Warning No
Event Breaker #1 Trip
Custom Event #4 Low Warning No
Event Breaker #2 Trip
Custom Event #4 Low Warning No
Event Fault Protection Timer
Custom Event #4 Low Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #4 Low Yes
Shutdown Event Audible Alert
Custom Event #4 Low No
Shutdown Event Breaker #1
Trip
Custom Event #4 Low No
Shutdown Event Breaker #2
Trip
Custom Event #4 Low No
Shutdown Event Fault
Protection Timer
Custom Event #4 Condition Active Only Condition
Exists Event Response
Configuration
Custom Event #4 Condition No
Exists Event Audible Alert
Custom Event #4 Condition No
Exists Event Loss of Utility
Custom Event #4 Condition No
Exists Event Breaker #1 Trip
Custom Event #4 Condition No
Exists Event Breaker #2 Trip
Custom Event #4 Condition No
Exists Event Fault Protection
Timer
Custom Event #5 High Warning Activate Warning Condition
Event Response Configuration
Custom Event #5 High Warning Yes
Event Audible Alert
Custom Event #5 High Warning No
Event Breaker #1 Trip
Custom Event #5 High Warning No
Event Breaker #2 Trip
Custom Event #5 High Warning No
Event Fault Protection Timer
Custom Event #5 High Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #5 High Yes
Shutdown Event Audible Alert
Custom Event #5 High No
Shutdown Event Breaker #1
Trip
Custom Event #5 High No
Shutdown Event Breaker #2
Trip
Custom Event #5 High No
Shutdown Event Fault
Protection Timer
Custom Event #5 Low Warning Activate Warning Condition
Event Response Configuration
Custom Event #5 Low Warning Yes
Event Audible Alert
Custom Event #5 Low Warning No
Event Breaker #1 Trip
Custom Event #5 Low Warning No
Event Breaker #2 Trip
Custom Event #5 Low Warning No
Event Fault Protection Timer
Custom Event #5 Low Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #5 Low Yes
Shutdown Event Audible Alert
Custom Event #5 Low No
Shutdown Event Breaker #1
Trip
Custom Event #5 Low No
Shutdown Event Breaker #2
Trip
Custom Event #5 Low No
Shutdown Event Fault
Protection Timer
Custom Event #5 Condition Active Only Condition
Exists Event Response
Configuration
Custom Event #5 Condition No
Exists Event Audible Alert
Custom Event #5 Condition No
Exists Event Loss of Utility
Custom Event #5 Condition No
Exists Event Breaker #1 Trip
Custom Event #5 Condition No
Exists Event Breaker #2 Trip
Custom Event #5 Condition No
Exists Event Fault Protection
Timer
Custom Event #6 High Warning Activate Warning Condition
Event Response Configuration
Custom Event #6 High Warning Yes
Event Audible Alert
Custom Event #6 High Warning No
Event Breaker #1 Trip
Custom Event #6 High Warning No
Event Breaker #2 Trip
Custom Event #6 High Warning No
Event Fault Protection Timer
Custom Event #6 High Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #6 High Yes
Shutdown Event Audible Alert
Custom Event #6 High No
Shutdown Event Breaker #1
Trip
Custom Event #6 High No
Shutdown Event Breaker #2
Trip
Custom Event #6 High No
Shutdown Event Fault
Protection Timer
Custom Event #6 Low Warning Activate Warning Condition
Event Response Configuration
Custom Event #6 Low Warning Yes
Event Audible Alert
Custom Event #6 Low Warning No
Event Breaker #1 Trip
Custom Event #6 Low Warning No
Event Breaker #2 Trip
Custom Event #6 Low Warning No
Event Fault Protection Timer
Custom Event #6 Low Activate Hard Shutdown
Shutdown Event Response Condition
Configuration
Custom Event #6 Low Yes
Shutdown Event Audible Alert
Custom Event #6 Low No
Shutdown Event Breaker #1
Trip
Custom Event #6 Low No
Shutdown Event Breaker #2
Trip
Custom Event #6 Low No
Shutdown Event Fault
Protection Timer
Custom Event #6 Condition Active Only Condition
Exists Event Response
Configuration
Custom Event #6 Condition No
Exists Event Audible Alert
Custom Event #6 Condition No
Exists Event Loss of Utility
Custom Event #6 Condition No
Exists Event Breaker #1 Trip
Custom Event #6 Condition No
Exists Event Breaker #2 Trip
Custom Event #6 Condition No
Exists Event Fault Protection
Timer
Event System
Event Warning Condition Enabled
Response Auto Reset Enable
Status
Event Audible Alert Response Enabled
Auto Reset Enable Status
Event Loss Of Utility Response Enabled
Auto Reset Enable Status
Event Breaker #1 Trip Enabled
Response Auto Reset Enable
Status
Event Breaker #2 Trip Enabled
Response Auto Reset Enable
Status
Generator AC Monitor
Generator Connection Wye (or Star) Connection
Configuration
Generator Potential 1 Volts
Transformer Primary Winding
Rating
Generator Potential 1 Volts
Transformer Secondary
Winding Rating
Generator Current Transformer 800 Amps
Primary Winding Rating
Generator Current Transformer 5 Amps
Secondary Winding Rating
Number of Generator Poles 4 Poles
Generator Rated Frequency 50 Hz
Generator Rated Voltage 415 Volts
Generator Rated Power 328 kW
Generator Rated Apparent 430 kVA
Power
Governor Desired Engine Speed Request
Maximum Engine Speed Bias 400 rpm
Generator Nominal Output 50.0 Hz
Frequency
Electronic Control Module Reduced Power Mode
Electronic Control Module Disabled
Reduced Power Mode Enable
Status
Electronic Control Module 30 min
Reduced Power Mode Delay
Time
Relay Outputs
Relay Output #1 Active State High
Configuration
Relay Output #2 Active State High
Configuration
Relay Output #3 Active State High
Configuration
Relay Output #4 Active State High
Configuration
Relay Output #5 Active State High
Configuration
Relay Output #6 Active State High
Configuration
Programmable Trip Point Function
Programmable Trip Point Disabled or Not Installed
Function #1 Trigger Condition
Programmable Trip Point -1 %
Function #1 Percentage
Threshold
Programmable Trip Point Disabled or Not Installed
Function #1 Hysteresis
Percentage
Programmable Trip Point Disabled or Not Installed
Function #1 Trip Activation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #1 Trip Deactivation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #2 Trigger Condition
Programmable Trip Point -1 %
Function #2 Percentage
Threshold
Programmable Trip Point Disabled or Not Installed
Function #2 Hysteresis
Percentage
Programmable Trip Point Disabled or Not Installed
Function #2 Trip Activation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #2 Trip Deactivation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #3 Trigger Condition
Programmable Trip Point -1 %
Function #3 Percentage
Threshold
Programmable Trip Point Disabled or Not Installed
Function #3 Hysteresis
Percentage
Programmable Trip Point Disabled or Not Installed
Function #3 Trip Activation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #3 Trip Deactivation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #4 Trigger Condition
Programmable Trip Point -1 %
Function #4 Percentage
Threshold
Programmable Trip Point Disabled or Not Installed
Function #4 Hysteresis
Percentage
Programmable Trip Point Disabled or Not Installed
Function #4 Trip Activation
Delay Time
Programmable Trip Point Disabled or Not Installed
Function #4 Trip Deactivation
Delay Time
Configuration Data
Engine Serial Number Not Programmed
Display Preferences
Display Pressure Units kPa
Configuration
Display Temperature Units Degrees Centigrade (Celsius)
Configuration
Display Volume Units liters
Configuration

You might also like