Technical Particulars For Drinking Water Coolers

For RC Period (01-04-2016 To 31-03-2017)


Generated on: May 28, 2017 11:11 PM NIC

Schedule 1 Self Contained Drinking Water Cooler with (Non CFC Refrigerant)Energy
Unit : NOS. Efficient Compressor

Cooling Type Storage Rate of Max. Energy


Capacity Capacity Consumption Watts
Ltrs/Hr. Ltrs.

1 40 Storage 40 575
2 40 Storage 80 575
3 60 Storage 120 775
4 150 Storage 150 1550

NOTES TO TENDERERS:-
1. The tenderers are required to give the complete technical details of the water
coolers as per QUESTIONNIARE attached. They should also enclose the technical
literature/catalogue for all the models highlighting the salient technical features (in
triplicate).

Page 1 of 6
Detailed Specification

Schedule 1 Self Contained Drinking Water Cooler with (Non CFC Refrigerant)Energy Efficient
Compressor
Specification:-
"ISI marked" Self-contained Drinking Water Cooler with 'Eco' friendly(non-
CFC refrigerant ) energy efficient compressor conforming to IS:1475(Part
1):2001(Reaffirmed 2007).

Page 2 of 6
Questionnaire

Schedule Self Contained Drinking Water Cooler with (Non CFC Refrigerant)Energy
Efficient Compressor

1 Model of the unit :


2 Overall dimensions of the unit :
3 Dimensions of tank(Inside); WxDxH mm :
4 Dimensions of Pedastal WxDxH mm :
5 Dimnsions of S.S. front panel below the water outlets (mm) :
6 Material of Padestal i.e. S.S./Nylon based conforms to which specn:
7 Water supply pressure and size of water inlet (Kg/cm ,mm) :
8 No of Faucets/Taps provided :
9 Details of drains provided & material :
10 Make & model of Compressor :
11 Type of compressor :
12 Starting method of compressor :
13 Capacity of compressor (K.cal/hr):
14 Max. output of compressor motor (Kw) :
15 Rated current , speed, & voltage of compressor (Amps, rpm, volts) :
16 Max. full load current of compressor :
17 Warranty of compressor (In years) :
18 Refrigerant used :
19 Class of insulation of compressor motor :
20 Pull down time for storage type water coolers as per Clause 7.8.2.1 :--
a. Ambient temp (Deg.C)
b. Initial water temp.(Deg.C)
c. Final water temp.(Deg.C)
d. Pull down time (Min)
e. Voltage(Volts)
f. Current(Amps)
g. Power consumption(watts)
21 a. Max. input of Fan motor (Amps/watts) :
b.Type of fan motor should confirm to IS:996/2009 :

22 Power factor of condensor fan motor :


23 Particulars of Condenser Coil :--
a. Face area(Sq.mtr):
b. Tube material, OD, & wall thickness(mm):
c. Number of rows :
d. Number of holes per row(Nos):
e. Fin material & thickness(mm):
f. No. of fins per cm(Nos)
24 Particulars of Insulating material :--

Page 3 of 6
a. Thickness (mm) :
b. Material with trade name, if any. :
25 Mention `Makes` of following items :--
a. Electric Motor :
b. Capacitor :
c. Condenser / Evaporator :
d. Thermostat with details of differential and its range:

Drawing/Proforma/Annexure Attached [Click on following to view/print]

INSPECTION REPORT FORMAT

Page 4 of 6
General Technical requirement For TE :
i)Firm shall have BIS License conforming to IS:1475(Part-1)2001(Reaffirmed 2007).
ii)The water Coolers shall be suitable for operation on 230 V +/-10 %,50 Hz,single
phase A.C.supply.
iii) The tenderers shall declare specn. details of non-CFC compressor.
iv) Tank shall be fabricated from S.S Sheet of 0.8mm minimum thickness as per AISI 304
and shall be made by electrically seam welded lap joints or alternatively from 0.6mm
minimum thickness Stainles steel sheet with PUF insulation. However tank fabricated by
double seam jointing is also acceptable if the same is reinforced and sealed by lead-
free solder material. Use of lead soldering material for sealing the joints of water
tank is not permitted. Water tank cover and lid bottom shall be made of 1.25mm
aluminimum sheet duly anodised/eppoxy painted/high impact polystyrene (HIP) of 1.5mm
thickness.Positive locking of the lid is to be provided (lock with two keys). A drain
plug at the bottom of the storage tank to be provided to draw out water while
cleaning.
v) The cabinet of the water cooler shall be made of Stainless Steel sheet (Grade 304)
of 0.8mm minimum. The front panel below the water outlets in the storage type water
coolers shall be made of stainless steel of 0.8mm minimum. The drain pan for storage
type water coolers shall be made of stainless steel sheet of 0.6mm minimum upto size
40 ltrs/hr and beyond 40 ltrs/hr of 0.8mm minimum thickness. The bottom pedestal shall
be made of 2.50mm minimum thick stainless steel sheet or Nylon based material.
Pedestal shall have a minimum ground clearance of 100mm for ease of cleaning.Pedestal
shall be strong enough to withstand weight with storage tank full and shall be
reinforced to prevent askewing. The body shall be held securely with the pedestal with
stainless steel nuts and bolts.The drain size should be 25mm or above. In case water
outlets are provided on three sides then all the three lower panels should be made of
aluminium sheet or stainless steel sheet.
vi) If any mild steel components used in the manufacture of the drinking wtaer cooler
shall be individually degreased, pickled, scrubbed and rinsed to remove grease, rust,
scale or/any other foreign elements. Immediately after pickling the M.S. parts shall
be given phosphating treatment. The components alongwith the front panels shall then
be given a primer coat with a finish coat of stove enamel paint. The finish shall be
smooth and uniform with hard tough film of the enamel adhering to the surface. The
finish shall be free from all the visible defects and shall not chip when tapped
lightly with a dull pointed instrument. Alternative method of corrosion protection
like plastic powder coating, electrostatic painting shall be permitted.
vii) Refrigeration coils to be fully soldered to the outside of the tank for good
thermal contact and not merely tack welded.
viii) The tenderers are required to furnish wattage/litre for the model as actually
obtained in their product at rated conditions.
ix) There shall not be any gap between water tank cover (mask) and water tank to
prevent rodent/inspect/dust entry.
x) Condensor fan motor shall be capacitor start and capacitor run(CSR) or permanently
split capacitor(PSC)or alternatively permanently lubricated motor may be provided.
xi) Water tank overflow should be adequately covered with strainer such as wire
meshetc. to avoid rodent/insect/dust entry.
xii) The power factor of water cooler shall not be less than 0.85 at capacity rating
test conditions.
xiii) The thermostat shall conform to IS:11338-1985 (Reaffirmed 1999), During
inspection performance of thermostat shall also be checked at minimum and maximum
positions.

SAMPLING:
No of samples for acceptance test shall be 10% of the offered lot capacity wise
subject to minimum of 1 number.

Pre- despatch inspection of stores against the R/C shall be reported as per Inspection

Page 5 of 6
Report proforma No.MECH-201. A copy of this proforma is enclosed with the hard copy of
T.E. The suppliers down loading the tender from Web site shall obtain the copy of this
Form from DS(ME)DGS&D N.Delhi.

TP Prepared By TP Scrutenised By

Name Ranjana Bhatti V K Verma


Desig AD(QA) DIRECTOR (QA)
Date 09-11-2015 21-12-2015
TP Approved By
TP Recommended By

Name V K Verma
Desig DIRECTOR (QA) DDG(QA)
Date 19-02-2016 14-03-2016

Forwarded to(Purchase Dte.): Mechanical Engineering

With Ref. To(Pur. Wing No.): DWC/ME-3/RC-12010000/03 dated 28/10/2015


QA/MECH/201
QA Wing Ref. No.

Page 6 of 6