You are on page 1of 65

MEASUREMENT AND MODELLING OF

ICE RINK HEAT LOADS

Mazyar Karampour

Master of Science Thesis


KTH School of Industrial Engineering and Management
Energy Technology Department EGI-2011-094MSC
Division of Applied Thermodynamics and Refrigeration
SE-100 44 STOCKHOLM
Measurement and Modelling of Ice Rinks Heat Loads

Master of Science Thesis EGI 2011/ETT:094MSC

Measurement and modelling of ice rink heat loads

Mazyar Karampour

Approved Examiner Supervisor


Date Bjrn Palm Joachim Claesson
Commissioner Contact person

Master student: Mazyar Karampour


Forskarbacken 19/1508
11415 Stockholm
Registration Number: 801012-6558
Department Energy Technology
Degree program Sustainable Energy Engineering
Examiner at EGI: Prof. Dr. Bjrn Palm
Supervisor at EGI: Dr. Joachim Claesson
Supervisor at Industry: Eng. Lic. Jrgen Rogstam

2
Measurement and Modelling of Ice Rinks Heat Loads

ABSTRACT
Ice rinks are among the most energy intensive public buildings in developed and developing
countries. According to a research on Swedish ice rinks; a typical ice rink consumes approximately
1185 MWh/year which leads to more than 300 GWh/year for the 342 Swedish indoor ice rinks. The
refrigeration system is usually the largest consumer by 43% average share of the total energy
consumption.
To decrease the refrigeration system energy demand, there are a variety of energy efficiency
techniques known and available but the key to select the best ones is finding the major heat loads on
the ice sheet and refrigeration system, which is unique for each ice rink. To fulfil this objective and
in addition to review literature, this study has two main approaches.
The first approach is to measure and evaluate the performance of the refrigeration system in two ice
rinks, called Norrtlje and lta. The estimated cooling capacity is approximately equal to the total
heat load on the ice plus the heat gains in the distribution system. This goal has been accomplished
by using a performance analyser called ClimaCheck which is based on an internal method
because it uses the compressor as an internal mass flow meter and consequently, there is no need for
an external one. The refrigerant mass flow rate is calculated by an energy balance over the
compressor. By knowing the mass flow, enthalpy of the refrigerant, etc. the cooling capacity and
COP of the system can be calculated.
While the total heat load is known by the first approach, the second approach tries to discover
different heat loads shares by analytical modelling. The measured physical and thermodynamical
parameters plus the ice rink geometrical characteristics are input to the heat transfer correlations to
estimate the heat load magnitude.
The results of the measurements show that the total energy consumption in Norrtlje is about two
third of lta. The main reasons for this less energy consumption are smarter control systems for
compressors and pumps, better ventilation distribution design and 1C-2C higher ice temperature.
Analytical modelling for a sample day has estimated that about 84% of the total heat loads is
originated from the heat loads on ice sheet while the distribution system causes the remaining 16%.
Moreover, calculations show that convection plus small portion of condensation (altogether 36%),
radiation (23%), ice resurfacing (14%) and lighting (7%) are the largest heat loads in winter while in
summer condensation is another significant heat load (10%). Comparing two six-hour periods, one
without ice resurfacing and four resurfacings in the second one, 30% more cooling demand has been
calculated for the second period. Furthermore, it has been shown that the evaporator to brine is the
contributor for 66% of the heat transfer resistances from ice to evaporator while brine to bottom ice
and bottom to top ice accounts for 27% and 7% respectively.
To conclude, a parallel performance analysis of the refrigeration system and heat loads
estimation proves to be a useful tool for adopting proper design and control for energy efficient
operation.

Key words: Ice Rink, Refrigeration, Heat Load, Power Consumption, Energy Efficiency, Modelling, Measurement

3
Measurement and Modelling of Ice Rinks Heat Loads

ACKNOWLEDGMENT

I like to express my deep appreciation and respect to Jrgen Rogstam, for his kind support, valuable
lessons and never getting tired of my endless questions.
Special thanks to my supervisor at KTH, Dr. Joachim Claesson and Kenneth Weber at ETM
Kylteknik AB for their helpful comments and discussions. Kenneth was really a generous person in
sharing the valuable experiences with me.
Thanks to Swedish Energy Agency for financing this research as part of the Stoppsladd project.
I am grateful to Jakob Mnberg (ClimaCheck), Ari Penttil (Prorink), Antoni Gosalvez (Mayekawa-
MYCOM), John Ekwall (Swedish Meteorological and Hydrological Institute), Torbjrn Thoresson
(REFCALC) and Pavel Makhnatch for their help to provide me some required data.
I should thank Matthias Dahlberg for making the company Energi & Kylanalys a pleasant and
friendly atmosphere to work.

The last thanks to my family, for their lifelong support.

4
Measurement and Modelling of Ice Rinks Heat Loads

CONTENTS
1. Introduction ............................................................................................................................................... 9
1.1 Objectives...............................................................................................................................................10
1.2 Methodology ..........................................................................................................................................10
1.3 Scope and limitations............................................................................................................................11
2. Ice rinks ....................................................................................................................................................12
2.1 Ice rink energy systems ........................................................................................................................12
2.2 Ice rink energy systems shares ............................................................................................................18
2.3 Ice rink refrigeration system ................................................................................................................19
2.3.1 Ice pad structure and piping arrangement .................................................................................21
2.4 Heat loads in ice rinks ..........................................................................................................................23
2.4.1 Convection-Condensation ...........................................................................................................23
2.4.2 Radiation .........................................................................................................................................23
2.4.3 Conduction .....................................................................................................................................23
2.5 Energy efficiency in ice rinks ..............................................................................................................25
2.5.1 Heat loads decrease .......................................................................................................................25
2.5.2 Refrigeration and distribution system performance improvement ........................................26
2.5.3 Ice/concrete slab quality enhancement......................................................................................27
3. Experimental measurements .................................................................................................................28
3.1 Ice rinks ..................................................................................................................................................28
3.1.1 Norrtlje ice rink............................................................................................................................28
3.1.2 lta ice rink ....................................................................................................................................30
3.2 Performance analyser - ClimaCheck ..................................................................................................31
3.2.1 Energy balance method ................................................................................................................32
3.2.2 ClimaCheck method modification ..............................................................................................34
3.3 Measurement results .............................................................................................................................36
3.3.1 Cooling chain temperatures .....................................................................................................36
3.3.2 Evaporation/Condensation temperatures .................................................................................37
3.3.3 Brine and coolant temperatures ..................................................................................................38
3.3.4 Air temperature and relative humidity over ice, indoor and outdoor....................................39
3.3.5 Electric power input and cooling capacity.................................................................................39

5
Measurement and Modelling of Ice Rinks Heat Loads

3.3.6 Total energy consumption ...........................................................................................................40


4. Analytical modelling ...............................................................................................................................42
4.1 Heat loads...............................................................................................................................................42
4.1.1 Radiation .........................................................................................................................................43
4.1.2 Convection .....................................................................................................................................44
4.1.3 Condensation .................................................................................................................................45
4.1.4 Lighting ...........................................................................................................................................47
4.1.5 Ground Conduction .....................................................................................................................48
4.1.6 Brine headers..................................................................................................................................48
4.1.7 Ice resurfacing ................................................................................................................................49
4.1.8 Pump work .....................................................................................................................................50
4.1.9 Skaters .............................................................................................................................................50
4.1.10 Results for heat loads shares......................................................................................................51
4.2 Heat flux method ..................................................................................................................................53
4.2.1 Results .............................................................................................................................................54
4.3 Temperature resistances-differences ..................................................................................................55
5. conclusion ................................................................................................................................................56
6. Future work / suggestions.....................................................................................................................57
6.1 Future work ......................................................................................................................................57
6.2 Suggestions .......................................................................................................................................57
7. Bibliograpgy .............................................................................................................................................58
8. appendix ...................................................................................................................................................60
8.1 Compressor heat rejection sample calculations ................................................................................60
8.2 Cooling capacity sample calculations .................................................................................................63
8.3 Norrtlje and lta ice rinks photo gallery .........................................................................................64

6
Measurement and Modelling of Ice Rinks Heat Loads

FIGURES

Figure 1: Refrigeration system energy vs. total purchased energy for ice rinks (Rogstam (c), 2011) .... 9
Figure 2: Energy systems in ice rink (Retscreen, 2005) ..............................................................................12
Figure 3: Configurations of heat rejection and heat recovery from a refrigeration system (Sawalha,
2010) ..................................................................................................................................................................13
Figure 4: A ventilation duct over the stands in an ice rink ........................................................................14
Figure 5: Dehumidification by water vapour condensation (IIHF, 2010)...............................................15
Figure 6: Dehumidification by Desiccant wheel (IIHF, 2010) ..................................................................16
Figure 7: An integrated ventilation and desiccant dehumidification system (Munters, 2011) ..............16
Figure 8: Energy systems consumption shares (Rogstam (a), 2010) ........................................................18
Figure 9: Refrigeration plant with recovery (IIHF, 2010) ..........................................................................19
Figure 10: Refrigeration components electricity consumption shares (Rogstam (b), 2010) .................20
Figure 11: Ice pad structure (How ice rink works?, 2011) .........................................................................21
Figure 12: Typical piping arrangement in a distribution network (Ingvar, 2007) ...................................22
Figure 13: Daily indoor ice rink heat loads (ASHRAE, 2010) ..................................................................24
Figure 14: Norrtlje Sportcentrum, a) Ice hockey hall, b) Bandy, c) Artificial soccer field, d) Indoor
sport hall, e) Track and field pitch, f) Pool (to be constructed)...............................................................28
Figure 15: Green soccer field in white winter thanks to condenser waste heat .............................29
Figure 16: Norrtlje ice rink spectators stand (top-left), machinery room inside (top-right),
compressors (bottom-left), and machinery room outside (bottom-right) ...............................................30
Figure 17: lta ice rink hall and spectator stand (top-left), machinery room (top-right), flooded
evaporator (bottom-left), and one of the two compressors (bottom-right)............................................31
Figure 18: ClimaCheck basic instrumentation configuration ....................................................................32
Figure 19: Energy balance over compressor ................................................................................................33
Figure 20: ClimaCheck flowchart for Norrtlje and lta ice rinks ...........................................................34
Figure 21: Relative heat rejection versus RPM and tcond (teva=-10C, superheat =7K, subcool = 5K)35
Figure 22: Average relative heat rejection versus tcond (teva=-10C, superheat =7K, subcool = 5K) ...36
Figure 23: Ice, brine and evaporating refrigerant temperature fluctuations, 15 March 2011, Norrtlje
............................................................................................................................................................................37
Figure 24: Evaporation and condensation temperatures, 15 March 2011 ...............................................38
Figure 25: Brine and coolant temperatures, 15 March 2011 .....................................................................38
Figure 26: Air temperatures and relative humidity, 15 March 2011 .........................................................39
Figure 27: Electric power and cooling capacity, 15 March 2011 ..............................................................40
Figure 28: Total refrigeration system energy usage and outdoor temperatures in March 2011 ...........41
Figure 29: Heat loads in ice rinks and their impact points ........................................................................42
Figure 30: Angle factor between two aligned parallel faces (engel, 2007) ............................................44
Figure 31: Cooling capacity versus heat loads at midnight, 15 March 2011 ...........................................46
Figure 32: Air and ice temperatures and air relative humidity, 12 July 2010, Norrtlje.........................46
Figure 33: Condensation heat transfer coefficient, 12 July 2010, Norrtlje ............................................47
Figure 34: Lighting fixtures in Norrtlje .......................................................................................................48
Figure 35: Hourly average ice temperature, 15 March 2011, Norrtlje....................................................50

7
Measurement and Modelling of Ice Rinks Heat Loads

Figure 36: Heat loads shares in the total heat load .....................................................................................52
Figure 37: Top and bottom temperature sensors embedded in the ice ...................................................53
Figure 38: Top and bottom heat transfer rate on days 14, 15 and 16 April 2011 ..................................54
Figure 39: Ice average temperature fluctuations on 14, 15 and 16 April 2011 .......................................54
Figure 40: Heat flow from ice to refrigeration plant ..................................................................................55
Figure 41: MYCOM software interface ........................................................................................................60
Figure 42: Cooling capacity calculation sample for 23:00-23:59 on March 15, 2011.............................63
Figure 43: Flooded evaporator (right) and brine pumps (left) - lta .......................................................64
Figure 44: Coolant pumps and condenser (left corner) - lta ..................................................................64
Figure 45: DX evaporator (right), desuperheater (top-left) and condenser (bottom-left) - Norrtlje 64
Figure 46: refrigeration system for outdoor bandy field - Norrtlje ........................................................64
Figure 47: heat recovery pump for ventilation - lta .................................................................................64
Figure 48: District heating system - Norrtlje .............................................................................................64
Figure 49: desiccant wheel dehumidification and ventilation heat recovery unit - lta ........................65
Figure 50: dehumidification piping (right) and heating/cooling coils (left) in ventilation ducts -
Norrtlje ............................................................................................................................................................65
Figure 51: ClimaCheck central control unit - lta ......................................................................................65
Figure 52: Instruments for over ice temperature and humidity measurements- lta ............................65
Figure 53: ventilation ducts and lighting - lta ...........................................................................................65
Figure 54: ice resurfacing machine - lta .....................................................................................................65

TABLES
Table 1: Available lamps for ice rinks (IIHF, 2010) ...................................................................................17
Table 2: Ice pad and piping dimensions (ASHRAE, 2010)(IIHF, 2010) ................................................22
Table 3: Sample temperature control (Everything Ice, 2000) ...................................................................27
Table 4: Reasons for higher energy consumption in lta ..........................................................................41
Table 5: Physical properties for brine headers for heat load calculation .................................................49
Table 6: Heat loads summary .........................................................................................................................51
Table 7: Daily heat load calculations, 15 March 2011 ................................................................................52
Table 8: Heat transfer resistances and temperature differences ...............................................................55
Table 9: Heat rejection calculation results by MYCOM software ............................................................61

8
Measurement and Modelling of Ice Rinks Heat Loads

1. INTRODUCTION
Imagination of a prosperous sustainable society without smart energy strategies seems impossible.
While the amount of world energy consumption increases nonstop, there are only two solutions to
avoid the fatal consequences: producing energy more sustainably and using the produced energy
more efficiently. While there are big efforts to use renewable energies, it seems that still there is a
long way to go and the dominating resources are still non-renewable energies. Keeping this in mind,
using this energy more efficiently is the best answer to problems following by enormous energy
consumption.
Ice rinks are among the most energy consuming public areas which roots in simultaneous cooling,
heating, ventilation and lighting demand. In small municipalities, ice rinks are the biggest energy
consumers. Average annual energy consumed in a Swedish ice rink is 1185 MWh/year which this
amount is supplied 82% by electricity and 18% by heat and the total energy consumption for
Sweden ice rinks exceeds 300 GWh/year. The refrigeration system has the biggest share with 43%.
(Rogstam (a), 2010)
The relation between the refrigeration system energy usage versus the total purchased energy
(including electricity and heat) is shown in Figure 1 for a number of ice rinks. It is expected that
refrigeration energy consumption should increase with the total consumption increase but a
considerable spread is seen. Very different operation and activities patterns and not considering the
heat recovery potential in some ice rinks would be justifications for this spread. (Rogstam (c), 2011)

1200
Refrigeration system energy usage

1000

800
(MWh/yr)

600

400

200

0
0 500 1000 1500 2000
Total purchased energy ( MWh/yr)
Figure 1: Refrigeration system energy vs. total purchased energy for ice rinks (Rogstam (c), 2011)

9
Measurement and Modelling of Ice Rinks Heat Loads

As a comparison, Qubec ice rinks average energy consumption is around 1 500 MWh/year, while
the most efficient ones consumes 800 MWh/year and the least efficient ones 2 400 MWh/year
(Nicolas, 2009). For the whole Canadian ice rinks the total electricity consumption is approximately
3 500 GWh/year. (Bellache, 2007)
In Sweden there are about 341 indoor and 140 outdoor ice rinks, sized about 1800 m2 (60 m30 m).
Furthermore, 60 outdoor bandy rinks, around 8000 m2 each, exist in Sweden. Nine indoor bandy
arenas are built during the recent years. The operating months for indoor ice rinks is 6-10 months,
with an average of 8 months. For outdoor ice rinks, the winter period which lasts 3-5 months is the
operating time. (Rogstam (a), 2010)
While the total energy consumption by indoor ice rinks is more than 300 GWh/year, the ice rink
numbers and the working periods is increasing continuously and it seems that Swedish people need
more and more ice rinks, all year round. It means that the energy consumption will increase steadily
if there are no policies adopted for better energy efficiency techniques. To find the best energy
efficiency solutions, the first step is to know various heat loads and their shares on the load to the
refrigeration system which is the largest energy consumer.

1.1 Objectives
The objective of this study is to evaluate the heat loads in ice rinks. To obtain the best results the
following steps are intended:
a) Study literature on measurements and models on heat loads in ice rinks or similar applications.
b) Evaluation of two ice rinks with ClimaCheck instrumentation enabling monitoring the cooling
capacity/ice rink heat load.
c) Build a simulation model with an appropriate tool for simulating the ice rink heat load in order to
find the heat transfer mechanisms shares in the total heat load.

1.2 Methodology
To fulfil the objectives of the research, three main steps are decided.
The first step is to review the ice rink energy systems, the technology and different users of the input
energy to the ice rinks, heat loads in the ice rinks and furthermore, to introduce the most promising
energy efficient methods used to decrease the energy consumption in ice rinks.
The second step is the experimental part; two ice rinks will be introduced. Moreover, a measurement
system installed in these two ice rinks will be described. Finally, the results of the measurements will
be presented. The most important output of theses measurement is to find the cooling capacity and,
indirectly, total heat load which refrigeration system should compensate.

10
Measurement and Modelling of Ice Rinks Heat Loads

Trying to break the total heat load into various components will be discussed in the third step,
analytical modelling. A correlation or estimate to calculate each of the major heat loads in the ice
rinks will be presented and then the total heat loads will be compared with the provided cooling
capacity.

1.3 Scope and limitations


While the refrigeration system and heat loads of the indoor and outdoor ice rinks are to some extent
similar, this research concentrates mainly on indoor ice rinks and in particular two indoor ice rinks in
the Stockholm region. This makes the results and conclusions applicable the best for similar climate
and built environment conditions, for example Scandinavian or North American locations above
50-55 latitude.
The interactions between the heat loads, as the driving forces, the ice, as the object of cooling, and
the refrigeration system, as the responding/cooling system, is of main interest in this research. That
is why other energy systems in ice rinks including the heating and ventilation systems are not
discussed and analysed in any extend.
The limitations of the research are few unknown parameters in the measurement and modelling
process. Whenever such a parameter is encountered, it has been mentioned and the best possible
logical assumption is made.

11
Measurement and Modelling of Ice Rinks Heat Loads

2. ICE RINKS
2.1 Ice rink energy systems
Ice rink energy system is comprised of several energy systems, indicated in Figure 2, because there
are various demands in the ice rinks. What makes the ice rinks unique in comparison with other
public buildings is the wide range of demands. For example, there is a permanent need for cooling
and heating to provide temperatures ranging from -4C (ice) to around +60C (Domestic Hot
Water) in the ice rinks, simultaneously and in a stable condition. There is a second difficulty as well;
there are very few internal partitions to separate these energy systems targets.
The energy systems that every ice rink should have are: refrigeration, heating, ventilation,
dehumidification and lighting. The first three ones require distribution systems as well which are
powered by pumps and fans for mass and energy transfer.

Figure 2: Energy systems in ice rink (Retscreen, 2005)

Refrigeration system is the most important energy system as it makes the ice and keeps it from melting.
Considering the huge ice mass, for a typical ice rink the cooling capacity should be around 300-350
kW (IIHF, 2010). The most conventional refrigeration system used is electricity powered vapour
compression indirect system. This system is explained more in section 2.3.

12
Measurement and Modelling of Ice Rinks Heat Loads

Heating system provides the required heat for space heating, ventilation, domestic hot water (DMW),
ice resurfacing water, floor heating, snow melting, and subsoil heating. The heating system can be
fed by fossil fuels, electricity or district heating but the most energy efficient, cost effective and
environmentally friendly method is to use the heat rejected by the refrigeration system through the
condenser and desuperheater (if available). The amount of heat pumped by the refrigeration system
can cover a great share of the heating demand, sometimes even 100% of the need (ASHRAE, 2010).
Using this integrated method is smart as the refrigeration system is used both in the evaporator side
and the condenser side; hence it is not only a refrigeration system but also a heat pump. There are
various ways available to exploit this waste heat. Some examples have been shown in Figure 3.

Figure 3: Configurations of heat rejection and heat recovery from a refrigeration system (Sawalha, 2010)

The middle layout is a refrigeration system without heat recovery and the refrigerant heat is rejected
to atmosphere. It is called floating condensing as the condensation pressure follows the ambient
temperature. In this case, all of the heating demands should be covered by a separate heating system
including district heating, heat pump, etc.
Top-left layout is a heat recovery system by a desuperheater. This system is suitable when the
discharge temperature is relatively high. Refrigeration systems that use NH3 or CO2 can use this
desuperheater heat recovery. The regulating valve after the condenser/gas cooler can adjust the
discharge pressure and, consequently, the desuperheater heating capacity.
Top-right and bottom-left figures are two heat pump cascade solutions. In the bottom-left layout
heat is recovered from the condenser and delivered to a heat pump as the low grade heat. Then the
heat pump upgrades it to higher temperatures for HVAC demands. This allows the refrigeration
system to have lower discharge pressures. This system is called heat pump cascade. Top-right

13
Measurement and Modelling of Ice Rinks Heat Loads

solution (heat pump cascade for subcooling) is similar to the heat pump cascade but the heat is
recovered in a subcooler after the condenser. This increases the efficiency of the refrigeration
system.
The bottom-right system is a fixed-head pressure heat recovery system. In this solution the discharge
pressure is adjusted according to the HVAC system demand. There is a coolant which transfers the
heat from the condenser to the HVAC system. (Sawalha, 2010)

Ventilation system delivers the fresh air to the inhabitants and provides the standard air change rate to
avoid pollutant, smell, fog and biological disease sources concentration. During the design of the
ventilation system, it can be divided into two zones; the ice rink and public areas. In the ice rink,
spectators stand and emissions from ice resurfacing machine (if it is not an electric one) are to be
considered. Moreover, direct air blown to the ice surface should be avoided. For public areas, air
change required in the closed spaces including restaurant, offices, locker rooms for players, coaches,
referees and linesmen, drying rooms, medical rooms and toilets/showers should be considered
(IIHF, 2010).

Figure 4: A ventilation duct over the stands in an ice rink

14
Measurement and Modelling of Ice Rinks Heat Loads

Dehumidification system keeps the relative humidity of the indoor air up to a standard level. Too humid
indoor air causes the corrosion of the metal and rotting of the wooden structures. Moreover, fungi
and mould growth is more probable in a humid atmosphere. Another problem with too much water
vapour content in the air is the fog created over the ice that makes it hard to play or control the
movements. The last problem is the heat load on the ice due to condensation.
To dehumidify the air, two primary solutions are available. The first one is to cool the humid air
below its dew point. This leads to condensation of part of the air water content. For cooling the air,
part of the cold brine can be used. Figure 5 illustrates this dehumidification process.
Dehumidification by condensation can be integrated with ventilation or refrigeration system.

Figure 5: Dehumidification by water vapour condensation (IIHF, 2010)

The second method is to use water absorbing materials like silica gel. The most well-known
equipment which uses this technique is called desiccant wheel. Desiccant wheel is the major
component in a desiccant humidification system. It is a slow rotating wheel containing some
absorbent chemicals (normally silica gel). When moist air passes one portion of the wheel, the
moisture is absorbed. While it is rotating, in other portion of the wheel a drying air is blown to the
wet absorbent to dry and regenerate it. In this system, the desiccant wheel plays a role of a
moisture transporter; takes the moisture away from the supply air to the ice rink and transports it
to the exhaust air. A simple desiccant dehumidification is shown in Figure 6.

15
Measurement and Modelling of Ice Rinks Heat Loads

Figure 6: Dehumidification by Desiccant wheel (IIHF, 2010)

Desiccant dehumidification system can be integrated with an air handling unit of ventilation system.
Figure 7 indicates an example of such a system. The return air from the ice rink (pink stream) is
divided into two streams: one to be exhausted to the atmosphere and a portion is mixed with the
fresh make-up air. The heat from the return exhaust air is recovered in an energy recovery wheel to
preheat the make-up air.
Then, a mixture of return and make-up air passes the desiccant wheel in the middle of the unit. The
desiccant wheel removes some portions of moisture from this air. The desiccant wheel is reactivated
(regenerated) by a hot air stream in the upper part of the wheel to be used as a moisture absorbent
again in the lower part. The supply air after the desiccant wheel can be heated or cooled by
heating/cooling coils. However, in ice rinks cooling coils are not used most of the year. The air
enters the ice rink as the supply air from left side of the unit.

Figure 7: An integrated ventilation and desiccant dehumidification system (Munters, 2011)

16
Measurement and Modelling of Ice Rinks Heat Loads

Lighting is an energy system that provides a clear and pleasant indoor environment for the skaters
and spectators as well. Different activities in an ice rink require different light intensities. Lighting
intensity is normally measured in units of lumen (lux) or foot candle (FC). Each foot candle is equal
to 10.76 lux. In general, figure or recreational skating requires10-15 foot-candles and curling 10-50
FC while ice hockey needs 80-150 foot candles. As a consequence, a method to decrease the energy
consumption by the lighting system is to control the lighting intensity. (DOE, 1980)(Everything Ice,
2000)
Another method to have an efficient and smart lighting system is to select energy-efficient lamps
and lighting fixtures. Lamps can be categorized to incandescent and burst illuminates according to
their operational principle. Generally, incandescent lamps are only suitable for general lighting,
except for halogen lamps. Incandescent lamps consume relatively high electricity compared to the
produced visible light. They have short life time but good controllability. Burst lamps, in contrast,
have high efficiencies and long lifetime but poor controllability. Generally, Burst lights are more
suitable for rink lighting (IIHF, 2010). Table 1 shows some of the more well-known lamps available
for ice rinks.
Luminous-efficacy of a lighting source is defined as the ratio of emitted visible light, in lux, to the
total consumed electricity, in W. This parameter shows how much energy efficient the lighting
device is. The luminous-efficacy for some incandescent lamps are 15-20% while some burst lamps
including metal halide and florescent lamps can have 80-90% efficacy (Luminous, 2011). This means
that, for example a 13 W compact florescent lamp can provides the same lighting of 800 lumens as a
60 W incandescent lamp (Everything Ice, 2000).
Table 1: Available lamps for ice rinks (IIHF, 2010)

Type Applicability Power range Life Note

Compact Good energy


General lighting 5-55 W 8 000-12 000 h
fluorescent lamps efficiency

Standard General lighting Good energy


30-80 W 20 000 h
fluorescent lamps Rink lighting efficiency

Good for rink


Metal halide lamps Rink lighting 35-2000 W 6 000 - 20 000 h
lighting

High pressure Poor colour


Rink lighting 50-400 W 14 000 24 000 h
sodium lamps rendering

Long life, expensive


Induction lamps Rink lighting 55-165 W 60 000 h
(so far)

Excellent colour
Halogen lamps Special lighting 20-2000 W 2 000 4 000 h
rendering, good
dimming capabilities

17
Measurement and Modelling of Ice Rinks Heat Loads

2.2 Ice rink energy systems shares


Through a statistical study of more than one hundred ice rinks in Sweden it is revealed that the
refrigeration system has the largest share in total energy consumption, 43% (in average) as indicated
in Figure 8. (Rogstam (a), 2010) Heating with 26% share is the second biggest energy consumer. In
Sweden the main sources of heating are district heating and/or electricity plus the heat recovered
from the refrigeration systems high pressure side and the heat recovered from exhaust air in
ventilation system. Lighting, ventilation system fans and dehumidification system are the next largest
energy consumers.

1%

5%
6%
Refrigeration
9%
Heating
43% Lighting
Ventilation Fans
10%
Dehumidification
Miscellaneous
Misc. Pumps

26%

Figure 8: Energy systems consumption shares (Rogstam (a), 2010)

There are several other researches confirmed that refrigeration system is the biggest energy
consumer in majority of world ice rinks. In a research by CANMET, the research organization of
Natural Resources Canada, refrigeration consumption is estimated to be 50% of the total energy
consumption, by electricity or heat (AAQ, 2003). In a research by International Ice Hockey
federation, refrigeration plant consumes 57% of the electricity input to a prototype ice rink in
Munich, Germany (IIHF, 2010). A research published in ASHRAE journal estimates that while in an
inefficient arena (1950 MWh/year consumption) refrigeration share is only 23%, in an efficient
arena with heat recovery systems (840 MWh/year) refrigeration consumes about 42% of the total.
(Nicholas, 2009)

18
Measurement and Modelling of Ice Rinks Heat Loads

2.3 Ice rink refrigeration system


The refrigeration system is known as the heart of the ice rink because it is the guard to keep the ice in
its most desired form.
A refrigeration system for the ice rink is direct, indirect, or a combination of them called partly
indirect. In the direct system the refrigerant is pumped below the ice pad and the whole refrigerant
distribution pipes serves as a large evaporator. This method is less used as there is a need for huge
amount of refrigerant charge. R-22 and ammonia are the most used refrigerants for the direct
systems but R-22 is banned now in many countries due to its global warming potential and ammonia
has a charge limit according to its hazards and cannot be used in large systems including ice rink
direct systems.
Indirect system is the most conventional layout for ice rink refrigeration system. In this system a
primary refrigerant cools a secondary refrigerant, known as brine, and then the distribution system
circulates this secondary refrigerant below the ice pad and returns it back to evaporator. In Sweden,
more than 97% of the ice rinks are indirect or partly indirect. (Makhnatch, 2010)
Partly indirect are systems that either evaporator or condenser is connected to the source or sink by
a secondary fluid for heat exchange. In partly indirect systems some portion of the cooling is
provided by a direct system as well. (Melinder, 2009)
A drawing of a typical ice rink with indirect system is demonstrated in Figure 9. As mentioned,
refrigeration unit cools the brine in evaporator and the brine is sent to the embedded cooling pipes
below the ice pad. The refrigeration system typically consists of a vapour compression cycle driven
by electricity as the primary cycle. About 85% of the Sweden ice rinks use Ammonia as the
refrigerant while the remaining use R404A, R134a or other HFC refrigerants. (Makhnatch, 2010)

Figure 9: Refrigeration plant with recovery (IIHF, 2010)

19
Measurement and Modelling of Ice Rinks Heat Loads

In the secondary loop there are one or more pumps that circulate the brine. Calcium Chloride
(CaCl2) and Frezium are the most conventional brines in Sweden. In some ice rinks a small portion
of the brine flow can be used in dehumidification units, as indicated in Figure 9.
Compressors for ice rinks are traditionally reciprocating compressors while screw compressors are
the other choices. Generally, more than one compressor is used for ice rinks and among the several
compressors one of them can be selected to be ample capacity to adjust cooling production in
harmony with fluctuating heat loads. In the ice making period or heavy activities on ice during high
activity hours, the second compressor will be engaged to assist the first one.
The rejected heat from condenser can be recovered to supply a number of heat demands in an ice
rink including ventilation unit, floor heating, hot water storage (which is used for domestic hot water
and/or ice resurfacing water) and ground frost protection. There are some other heat demands
which are not shown in the sketch; for example, part of the heat can be used to melt the snow,
produced during ice resurfacing, or a portion can be used for a nearby swimming pool.
75% to 100% of the space and water heating requirements can be supplied by smart heat recovery
(ASHRAE, 2010). The excess unexploited heat is removed in outdoor cooling coils which are
installed on ice rink roof, generally. The most conventional cooling units are dry air coolers and the
most used coolants in Sweden are Glycol, Ethylene Glycol and Propylene Glycol (Makhnatch,
2010).
Looking at the power consumption in refrigeration system as shown in Figure 10, it has been
revealed that compressors account for 80% of the total electricity consumption while brine pumps,
coolant pumps and dry cooler fans consume 10%, 5% and 5% respectively. (Rogstam (b), 2010)

5%
5%

10%
Compressors
Brine Pumps
Coolant Pumps
Dry Cooler Fans

80%

Figure 10: Refrigeration components electricity consumption shares (Rogstam (b), 2010)

20
Measurement and Modelling of Ice Rinks Heat Loads

2.3.1 Ice pad structure and piping arrangement


Ice pad structure consists of a number of layers and each layer is designed in response to a
requirement. As indicated in Figure 11, the topmost layer is ice. The most conventional structure for
the second layer is concrete while in some ice rinks sand or asphalt is used as well. The distribution
system of brine pipes is embedded in this chilled concrete slab. The level of concrete and pipes
should be completely flat to have a well-distributed cooling and uniform ice thickness.

Figure 11: Ice pad structure (How ice rink works?, 2011)

Below the cold concrete layer there is an insulation pad to decrease the conduction heat gains from
the ground. The next layer is heated concrete. It holds the weight of the top layers and it is heated
to eliminate or minimize the hazards of ground heaving. Ground heaving which is contributed by
soil freezing can lead to collapse of the whole ice pad structure. One of the most conventional
methods to keep the concrete layer warm is to run warm water in a pipe system, similar to the brine
pipes. The condenser heat recovery system can be the water heating source.
All the layers are laid on a layer of sand and gravel. A ground water drain collects any water to avoid
the water to be absorbed by the top layers. For the concrete and insulation layers being as dry as
possible is a requirement.
Figure 12 shows a typical piping arrangement for an ice rink. There are two brine pipe headers
which one of them is the brine supply header and the other one is return header or collector. As it is
shown, the brine distribution pipes are branched from the headers and have a U shape. This simple
U shape is called two-pass arrangement but a four-pass arrangement is applied in some ice rinks as
well. Four-pass layout has a W shape. Four-pass systems are claimed to be more energy efficient and
decrease the energy consumption. (AAQ, 2003)
As it can be seen in the figure, the brine header size is decreased gradually when the flow decreases
as well. The reason is to have a uniform flow, and as a consequence, heat transfer distribution.
Another method for uniform flow distribution is to use some small orifices in the inlet of the small
brine distribution pipes. In this arrangement the brine header sizes remain constant.

21
Measurement and Modelling of Ice Rinks Heat Loads

Figure 12: Typical piping arrangement in a distribution network (Ingvar, 2007)

Dimensions of the ice pad structure and header and distribution pipes are indicated in Table 2. It
can be seen the concrete thickness is 150 mm and the brine distribution pipes are located such that
pipes top point is 25- 50 mm lower than ice bottom surface. Smaller the distance, less heat transfer
resistance occurs. Furthermore, less concrete thickness leads to less load on the refrigeration system
and there are some tries to decrease the 150 mm thickness to 125 mm.
Header pipes are 6-8 inches (150-200 mm) typically and made of steel or Polyvinyl Chloride (PVC).
Small brine distribution pipes are 25-32 mm and can be steel or polyethylene plastic pipes. There are
some new materials including copper tubes which demonstrate a good heat transfer and flexibility
properties (Shahzad, 2006). The distribution pipes are fixed in 100 mm spacing with some supports
or spacers.
Table 2: Ice pad and piping dimensions (ASHRAE, 2010)(IIHF, 2010)

parameter size
Ice thickness 25-30 mm
Concrete thickness 150 mm
Insulation thickness 100 mm
Brine headers diameter 150-200 mm
Brine distribution pipes diameter 25-32 mm
Pipes spacing 75-125 mm (100 mm typically)
Top pipe bottom ice distance 25-50 mm

22
Measurement and Modelling of Ice Rinks Heat Loads

2.4 Heat loads in ice rinks


Heat loads in ice rinks can be categorized into three dominating heat transfer mechanisms:
Convection - Condensation
Radiation
Conduction

Brief explanations of these will be given here but the detailed mathematical correlations used for
calculations are discussed in chapter four, analytical modelling.

2.4.1 Convection-Condensation
In convection heat transfer of air to the ice, air temperature, ice surface temperature and air velocity
are important parameters. Higher temperature gradient between air and ice surface and higher air
velocity lead to higher convective heat transfer, hence lower air velocity over ice and closer air and
ice temperature are factors to decrease this heat load.
Furthermore, water vapour in the humid air rejects its heat to the ice and condenses on the surface.
This phenomenon is more serious in the ice rinks which are in operation during a humid summer
climate. Dehumidification of the supply ventilation air is necessary to avoid condensation and keep
the relative humidity low. Condensation could be a source of bad ice surface quality which brings
the ice resurfacing requirement, hence has an indirect negative impact as well.

2.4.2 Radiation
Two major sources of radiation are ceiling radiation and lighting. In several ice arenas radiation is
reported having the largest share in heat loads on the ice (ASHRAE, 2010). The radiation from
ceiling to ice could be estimated by the Boltzmann correlation which will be used later.
One of the most important factors in ceiling radiation is emissivity index which is normally 0.85-0.95
for conventional materials used for roof ceiling construction. It is possible to do some coverings as
aluminium foils or aluminium based clothes and paints which can reduce the ceiling radiation
considerably, sometimes to 10%.
Lighting is the second source of radiation to the ice as up to 60% of the light can be converted to
heat and absorbed by ice (ASHRAE, 2010). A smart way to reduce this heat load is to control the
light intensity according to the demand. In other words, it is not necessary to have lighting with full
intensity all the working hours of the ice rink. When only few children play on the ice the lighting
should be less intense in comparison with a professional match with hundreds of spectators.

2.4.3 Conduction
Main contributors to conduction are ice resurfacing, brine pump work, brine headers, ground
conduction and skaters.
Ice resurfacing is a requirement to maintain the ice surface in a good condition. To fulfil this, ice
resurfacing machine shaves the ice surface and then pours down a layer of hot water on the ice. The

23
Measurement and Modelling of Ice Rinks Heat Loads

normal volume of water is 400-700 litres and the resurfacing water temperature is 30-80. The lower
the water temperature, less heat load on the ice sheet would be dropped. (ASHRAE, 2010)
Pump work causes an increase in the enthalpy of the secondary refrigerant passing the pump. Typical
power consumption for these pumps is 15 kW. This 15 kW can be considered as a 15 kW heater in
the brine circuit and that is why it should be tried to use variable speed pump to decrease this power
consumption during unnecessary occasions including night shut down period.
Headers are located along the length or the width of the ice rink. As they are colder than their
environment, they should be insulated or covered with ice to decrease the heat gains (cooling losses)
as much as possible.
Ground conduction is a source of constant heat load on the system. The ground is separated by about
10cm insulation from the cold concrete but still there is some heat flux as the ground is heated to
avoid the soil freezing.
Skaters activities on the ice transfers heat through the ice surface but this is the only heat load that ice
rink owners like to be as high as possible.

To exemplify the heat loads shares, in Figure 13 there is a comparison of the shares of heat loads for
two ice rinks in Canada and US, during three seasons. It can be seen that radiation, convection,
pump work and ice resurfacing are the largest heat loads. Condensation has a significant effect
during summer (humid season) but it is not considerable during winter (dry season).

100,00%
90,00%
skaters
80,00%
headers
Heatloadshares(%)

70,00%
pumpwork
60,00%
groundconduction
50,00%
40,00% iceresurfacing

30,00% condensation
20,00% lighting
10,00% radiation
0,00% convection
Edmonton,Winter Pittsburgh,Summer Pittsburgh,Spring
(95.4W/m2) (135.5W/m2) (114.3W/m2)

Figure 13: Daily indoor ice rink heat loads (ASHRAE, 2010)

24
Measurement and Modelling of Ice Rinks Heat Loads

2.5 Energy efficiency in ice rinks


There are several methods to use the input energy in ice rinks more efficiently but all of them can be
categorized in one of the three classifications below:
Heat loads decrease
Refrigeration and distribution system performance improvement
Ice/concrete slab quality enhancement

It should be noted that in energy efficiency applications instead of only focusing on the refrigeration
system, it is better to study the whole building in an integrated approach. For example, maybe a
method decreases the refrigeration system efficiency a little but in general, helps the waste heat
recovery systems to supply the heat demands better.

2.5.1 Heat loads decrease


1. Low-e ceiling. Ceiling radiation is one of the largest heat loads in the ice rinks. The conventional
materials for ceiling (wood, steel, etc.) have an emissivity index 0.85-0.95. The low-e ceiling concept
referred to ceilings covered/painted with low-e aluminium based paints or suspended aluminium
based clothes over the ceiling trusses. These low radiating ceilings have emissivity indexes in the
ranges 0.05-0.2. By using low-e ceilings the radiation load can be decreased to 50% or less
(Retscreen, 2003). It has an indirect impact as well which increases the light reflections and as a
consequence less lighting is required in these arenas. The effect of less lighting is discussed in the
lighting section.
2. Dehumidification. Humidity control is a way towards thermal comfort in all public areas but in ice
rinks it has other significant effect as well. Water vapour in humid air over the ice rejects its heat to
ice to condense on the surface. As a consequence, the humidity should be controlled and normally it
is kept up to 50%-55%. Desiccant wheels are one of the most efficient dehumidification systems
which fulfil the heat recovery from exhaust air and humidity regulation simultaneously.
3. Lighting. Less lighting has two impacts on the energy consumption, direct and indirect. The direct
impact is less electricity consumption of the lamps. The indirect impact is according to the less heat
transferred by radiation to the ice which decreases the refrigeration system electricity consumption.
One way to decrease the lighting is to use more efficient lamps, for example using T5 or T8
fluorescent lamps instead of the metal halide lamps. Furthermore, the lighting intensity is not
required to be max during the whole day and it can be adjusted according to the activity on the ice.
4. Resurfacing water. Ice resurfacing water quality, volume and temperature have significant effects on
the heat loads. More purified/treated water makes a better ice with higher thermal conductivity.
Moreover, less resurfacing water temperature and volume decreases the load. In Sweden 30C-40C
is the normal temperature range (Makhnatch, 2010) while in North America 55C-80C is the case
for many ice rinks.
5. Header pipes. Header pipes lying in the trenches should be insulated or frozen with an ice layer on
them to reduce the cooling losses. Parts of the header pipes which are outside the trenches should as
well be insulated. Other way to decrease the losses is to increase the brine temperature in pipes and

25
Measurement and Modelling of Ice Rinks Heat Loads

then there is less temperature gradient between brine pipe headers and surrounding air. (Refer to
section 2.5.3 and Table 3)
6. Air convection and air tightness. Temperature and velocity of the air moving above the ice surface has
a great influence on the convection heat transfer. To control these parameters, direct air flows from
ventilation diffusers should be avoided. At night, the ventilation system can be turned off or reduced
down or the temperature of the supplied air during the less-crowded hours can be lowered.
Pollution controllers is another way to adjust the ventilation demand as the big space inside the ice
rinks buildings has too many leaks that sometimes ventilation looks unnecessary.
Air tightness is to stop the uncontrolled movement of air into and out of a building which is not for
a specific and planned purpose. Air tightness is another important factor to keep the building
interior atmosphere isolated from outdoor conditions as in warm and humid seasons it can increase
the convection and condensation heat loads severely.
7. Stands heating. To select the heating method for the spectators, its side effects as a heat load on the
ice should be considered. One of the best solutions is infrared heater over the stands as it provides
spot heating. If it is not possible and the ventilation system is used simultaneously for heating, it
should be considered that the air should not be blown to the ice directly.

2.5.2 Refrigeration and distribution system performance improvement


1. Waste heat recovery. The refrigerant after the compressor is cooled in desuperheater and condenser.
This heat can be recovered for heating demands. In this point of view, refrigeration system can be
considered as a heat pump which the heat loads on the ice plays the role of the low level heat
sources and the heat pump (refrigeration system) upgrades the heat level to distribute it in the
required location and applications. According to the temperature degradation from desuperheater
inlet to condenser outlet, the heat can be used for various applications including DHW, floor
heating water, resurfacing water, snow melting, swimming pool heating, subfloor (soil) heating
water, ventilation and space heating.
2. Brine pump. A full speed brine pumps working 24 hours a day can account for 15% (Retscreen,
2003) of the total electricity consumption in the refrigeration systems. Furthermore, this consumed
electricity by brine pumps is converted as heat to the brine and therefore, it has direct and indirect
negative effects on energy consumption. To decrease the consumption, variable speed pumps are
one of the best solutions. They can be controlled by brine temperatures.
3. Brine pipe passes. The brine pipes are generally two pass configuration (as shown in Figure 12) but
four pass configurations have been installed in several ice rinks over the world and no problem has
been reported. Four pass layouts require less pumping power. (AAQ, 2003)
4. Compressor demand control. Similar to brine pumps, constant-speed compressors are not enough
energy efficient as the amount of cooling required should be controlled by ice or brine temperature.
At night or low-activity day hours it is not wise to have all the compressors on with full speed. For
controlling the provided cooling capacity, electric motors equipped with frequency converters are
used. In addition, using more than one compressor is a way to adjust the refrigeration with cooling
demand. During the rush hours, the auxiliary compressor(s) can run in parallel with the first
compressor.

26
Measurement and Modelling of Ice Rinks Heat Loads

2.5.3 Ice/concrete slab quality enhancement


1. Ice temperature and thickness. Considering the huge mass of ice (more than 40 ton for a typical 1800
m2, 25 mm ice sheet) each degree colder ice requires a significant amount of cooling. Therefore, any
effort to keep the ice thickness as thin as possible or the ice temperature as high as possible will help
using energy more efficiently. The recommended ice thickness is 25 mm. Recommended ice
temperature varies according to the sport/activity. For hockey -6.5C to -5.5C, figure skating -4C
to -3C and recreational skating -3C to -2C is satisfactory (ASHRAE, 2010). Overcooling the ice
compared to these recommended values means energy waste and the ice rink owner should pay for
it unnecessarily. During the night, when there is less heat load, these temperatures can be raised.
Table 3 is a sample for ice temperature control. During midnight or early in the morning the ice
temperature can be kept 2-3C higher than the high load periods. It should be mentioned that the
ice temperature can be manipulated by brine temperature adjustments and setting the control system
for a schedule similar to Table 3, as an example.

Table 3: Sample temperature control (Everything Ice, 2000)

Typical Daily Brine Cycle


Period Brine Temperature Rink Function
0.00-6:00 -4C Night setback
6:00-8:00 -4C Ice maintenance
8:00-16:00 -6C Low load
16:00-18:00 -7C Figure skating
18:00-24:00 -8C Hockey

2. Concrete thickness and thermal conductivity. While the main object of cooling is ice, the heat transfer
medium from ice to brine is concrete and less heat transfer resistance through concrete will cause
less required cooling capacity. Concrete thickness in Swedish ice rinks is, typically, 150 mm which
25-50 mm is the distance from brine pipes top to the concrete surface (ice bottom). In parallel to
concrete thickness, concrete thermal conductivity is very important. Better concrete quality leads to
better heat transfer and less resistances.

27
Measurement and Modelling of Ice Rinks Heat Loads

3. EXPERIMENTAL MEASUREMENTS
As the second step of this research, the performance of two refrigeration plants in two ice rinks is to
be evaluated. To fulfil this objective, first, the ice rinks and their refrigeration systems are described
in brief. Then, ClimaCheck, as a tool and method to analyse the performance of the refrigeration
system is discussed and some modifications for more accurate calculations are suggested and
applied. Finally, the results of the measurements (including power consumption and important
temperatures) and estimated cooling capacity for some sample time periods are shown and
discussed.

3.1 Ice rinks


Two ice rinks which are studied in this research are situated in Norrtlje and lta. Ice rink in
Norrtlje belongs to the Norrtlje Sportcentrum which is located about one hour north-east of
Stockholm. lta ice rink is located in the Nacka district, Stockholm.

3.1.1 Norrtlje ice rink


Norrtlje sport Centrum is comprised of two ice rinks, one indoor for hockey and figure skating and
another one outdoor for bandy. Through this report only the indoor ice rink is considered and
studied and for the outdoor rink another research project is in process. Moreover, there are an
artificial soccer field, an indoor sport hall, a track and field pitch and a pool to be constructed - in
the sport facility. (Figure 14)

Figure 14: Norrtlje Sportcentrum, a) Ice hockey hall, b) Bandy, c) Artificial soccer field, d) Indoor sport hall,
e) Track and field pitch, f) Pool (to be constructed)

28
Measurement and Modelling of Ice Rinks Heat Loads

Among the neighbour sport fields, the artificial grass field is of particular interest as it uses part of
the waste heat from the refrigeration system condenser to prevent freezing, even during the harsh
winter climate (Figure 15). The heating piping system is similar to an ice rink but here the pitch is
heated by the underground pipes containing ammonia 15% - water which is heated by condenser. In
other words, the refrigeration system acts as a heat pump to keep the soccer field from freezing.

Figure 15: Green soccer field in white winter thanks to condenser waste heat

Norrtlje ice rink is about 1800 m2 (60 m30 m) and its spectator capacity is 700-800 people, as
shown in Figure 16 top-left. It is open all year round except for mid-April to mid-June. The
refrigeration system is indirect with ammonia as refrigerant, calcium chloride 21% - water as
secondary refrigerant and the coolant is ethylene glycol 35% - water.
The refrigeration system is bought and shipped prefabricated from Finland. It is located outside the
ice rink building as the inside old machinery room became useless after a price increase in district
cooling water (Figure 16 bottom-right). Two MYCOM reciprocating compressors with nominal
total cooling capacity of 300 kW and nominal 55 kW motor capacity are the driving forces of the
refrigeration system. The evaporator is direct expansion and VAHTERUS shell and plate heat
exchanger. The condenser and desuperheater are from the same manufacturer. There are two 15 kW
brine pumps but only one is in operation during the measurements period of this research project.
All the involved electrical motors mentioned are equipped with frequency converters.
The humidity of the ice rink is controlled by a dehumidification system using a part of the cold brine
to decrease the humidity ratio of the incoming air, mainly in the humid months. The heat rejected
from the desuperheater is used to supply part of the heat required for space heating, ventilation, hot
water and ice resurfacing water.

29
Measurement and Modelling of Ice Rinks Heat Loads

Figure 16: Norrtlje ice rink spectators stand (top-left), machinery room inside (top-right), compressors
(bottom-left), and machinery room outside (bottom-right)

3.1.2 lta ice rink


The lta ice rink is similar to Norrtlje ice rink comparing the size, spectator capacity and length of
the season. The refrigeration system is indirect with ammonia as refrigerant, calcium chloride 24% -
water as secondary refrigerant and the coolant is propylene glycol 40% - water.
Two GRAM reciprocating compressors with total nominal cooling capacity of 400 kW and 90 kW
nominal motor capacity are the driving forces of the refrigeration plant in lta ice rink, which are
shown in Figure 17. These compressors were built in 1976 and brought from another ice rink, after
being used a couple of years. It seems that they are over-sized for the required cooling capacity that
might be a source of inefficiency. The evaporator is a flooded type plate heat exchanger (Figure 17
bottom-left). The condenser is an ALFA LAVAL plate heat exchanger and the desuperheater is a
shell and tube heat exchanger. In lta two nominal 15 kW brine pumps and two 11 kW coolant
pumps run and none of the machineries are controlled by frequency converters.
To control the humidity in lta one desiccant wheel is installed in the hall.

30
Measurement and Modelling of Ice Rinks Heat Loads

Figure 17: lta ice rink hall and spectator stand (top-left), machinery room (top-right), flooded evaporator
(bottom-left), and one of the two compressors (bottom-right)

3.2 Performance analyser - ClimaCheck


ClimaCheck is a tool to analyse the performance of refrigeration, air conditioning or heat pump
systems. The motivation to use this tool is that from January 2009, an EU regulation requires that all
air conditioning systems above 12 kW are to be performance inspected.
The basic flowchart of ClimaCheck can be seen in Figure 18. For a simple basic refrigeration cycle,
seven temperature sensors, two pressure sensors and one electrical power meter are used to
determine the performance of the system from a thermodynamic point of view. The data which are
measured are refrigerant temperatures and pressures before and after the compressor(s), air/water
temperatures in and out from evaporator/condenser and refrigerant temperature before the
expansion valve. Furthermore, compressor electrical voltage and amperage are measured to know
the electrical power input to the refrigeration system.

31
Measurement and Modelling of Ice Rinks Heat Loads

Figure 18: ClimaCheck basic instrumentation configuration

The ClimaCheck instrument can be a portable field kit or permanent fixed installation. Both of them
can be connected to the internet to be monitored anywhere and the logged data can be processed
through the ClimaCheck software to obtain the required calculated results.

3.2.1 Energy balance method


To analyse the performance of the ice rinks refrigeration system an internal method is used. This
method is referred to as the ClimaCheck method. In the internal method the compressor is used
as a mass flow meter and therefore there is no need installing an external mass flow meter. The
refrigerant mass flow rate is calculated by an energy balance over the compressor (Berglf, 2010). By
measuring the pressure and temperature before and after the compressor and the electricity input to
the compressor it is possible to calculate the mass flow rate according to Figure 19:

.
1
. .

Where
: Refrigerant mass flow rate
: Electric motor efficiency
: Electric power to the compressor motors

: Heat loss from compressor body and/or compressor cooling by oil/water

. : Enthalpy after compressor

. : Enthalpy before compressor

32
Measurement and Modelling of Ice Rinks Heat Loads

Figure 19: Energy balance over compressor

The enthalpy after the evaporator is known with two temperature and pressure sensors. The
enthalpy before the evaporator is equal to the enthalpy before the expansion valve and this can be
known by measuring the temperature before the expansion valve and the known high pressure. By
knowing the refrigerant mass flow rate and the enthalpies before and after the evaporator, the
cooling capacity can be calculated.
The COP of the system can be estimated as the cooling capacity and electrical power are known.
The heating capacity of the condenser and desuperheater are similarly possible to estimate as the
refrigerant mass flow rate and temperatures in and out from condenser and desuperheater are
measured.
In addition to the measured data, two parameters are important for an accurate calculation; the
electrical motor efficiency and the heat rejection from the compressor body.
The precise electric efficiency is not easy to know since type and power of motor, motor age and
motor full/part load will influence this. In addition, the frequency converter efficiency should be
considered as well.
For the Norrtlje compressors it is mentioned in their manual that the motor efficiency is 90% in
standard conditions. The frequency converters efficiency normally ranges 97-99% and for the
calculations here the worst case (97%) is considered. It means that in general the total electrical
efficiency of the frequency converter and electric motor is 87.3% (=0.900.97). In lta, there is no
frequency converter and the compressor efficiency is not mentioned anywhere but according to a
paper from US department of energy (motor challenge, 2010) typical compressor efficiency with this
capacity ranges 90-92% where the worst case is chosen. It is worth mentioning that lta
compressors are very old and running most of the time part load that can influence the compressor
efficiency significantly but in the calculations 90% is considered as the compressor motor efficiency.
To estimate the heat losses from the compressor body 7% of the input power is suggested by
ClimaCheck (Berglf, 2010). Moreover, the amount of compressor cooling by oil and/or water
should, if possible, be measured in the field or the compressor design-software can be used to find
the amount of energy losses.
For lta, the compressors cylinder heads are cooled by water and the supply and return
temperatures are measured. The water mass flow rate is estimated to be 0.1 kg/s and therefore, the
amount of compressor cooling is calculated. In Norrtlje, this heat rejection by compressor body

33
Measurement and Modelling of Ice Rinks Heat Loads

was unknown and assumed to be constantly 4 kW by ClimaCheck but it does not seem to give an
accurate estimation of the cooling capacity. As a consequence, it was decided to use MYCOM
compressors software for better estimates. The modification to ClimaCheck calculation is described
in the next part.

Figure 20: ClimaCheck flowchart for Norrtlje and lta ice rinks

In Norrtlje and lta ice rinks, to monitor the heat loads on the ice sheet, the ice temperature, air
temperature and humidity close to ice surface, indoor and outdoor temperatures are measured as
well. Figure 20 indicates a flowchart of the measurement configuration.

3.2.2 ClimaCheck method modification


7% heat rejection assumption is good for hermetic and semi hermetic compressors but for the open
compressors the amount of energy loss to input power ratio is more than this 7%. Normally, the
open reciprocating compressors are cooled by oil or water. In lta, as explained before, the mass
flow rate and temperatures of the cooling water are measured and therefore the amount of energy
losses by compressor and its cylinder heads can be calculated by:

% 2

In Norrtlje, the compressor software is used to find the amount of oil and jacket heat rejection.
Figure 21 shows the ratio of heat rejected to absorbed power versus condensing temperature for
several compressor speeds (a sample calculation is shown in appendix, section 8.1). Heat rejection is
the sum of oil and jacket heat rejection. The absorbed power means the shaft power and is equal to
the electrical power multiplied by electrical efficiency. This graph is selected among four graphs
drawn for four conditions: -10C or -12C evaporation temperature and zero degree

34
Measurement and Modelling of Ice Rinks Heat Loads

subcooling/superheating or 5K subcooling and 7K superheating. After studying many conditions it


seems that the below conditions (-10C evaporation, 5K subcooling and 7K superheating) is the
most frequent one.

25,00
(Heat rejection/Absored Power) %

20,00
RPM=900
RPM=1000
15,00 RPM=1100
RPM=1200
RPM=1300
10,00 RPM=1400
RPM=1500
RPM=1600
5,00
RPM=1700
RPM=1800
0,00
0 10 20 30 40 50
Condensing Temperature (C)

Figure 21: Relative heat rejection versus RPM and tcond (teva=-10C, superheat =7K, subcool = 5K)

To have a correlation for compressor loss, average heat rejection over absorbed power ratio is
drawn for various condensing temperatures as shown in Figure 22. As the Norrtlje compressors are
cooled better with the cooling media, it is assumed that only 5% of the energy is lost from the
compressor body. Therefore, the amount of compressor loss for Norrtlje can be estimated by:

. .
% 3

35
Measurement and Modelling of Ice Rinks Heat Loads

25,00

(Heat rejection/Absored Power)


20,00

15,00
y = 0,2046x + 12,215
%
10,00

5,00

0,00
0 10 20 30 40 50
Condensing temperature (C)

Figure 22: Average relative heat rejection versus tcond (teva=-10C, superheat =7K, subcool = 5K)

3.3 Measurement results


The measurements have been done concentrating on the refrigeration system, the ice and its
surrounding climatic conditions in order to analyse the performance of the refrigeration system in
response to fluctuating heat loads, and in a further step, to find the major and minor heat loads.
In both ice rinks, a majority of the ClimaCheck instruments are installed in the machinery room and
in places which have been explained before. Furthermore, to record the ice temperature, two
temperature sensors have been embedded in the top and bottom of Norrtlje ice, but in lta there is
only one ice temperature sensor. Moreover, some air temperature and relative humidity sensors
record the data in three locations, a few centimetres above the ice, some meters above the ice (ice
hall indoor conditions) and ice rink outdoor.
As a great amount of data have been recorded every minute in each ice rink, there are vast amounts
of logged data available and in following parts just samples of the most important ones have been
shown and analysed. There is much more stability in the Norrtlje performance, hence majority of
the graphs, to be discussed, belongs to Norrtlje.

3.3.1 Cooling chain temperatures


The cooling chain temperatures show how the provided cooling is transmitted and distributed from
evaporator to ice (in reality the direction of the energy flow is vice versa, from ice to evaporator). As
an example, Figure 23 shows temperatures of the evaporation, brine in and out from evaporator and
ice top/bottom for the day 15 March 2011 for Norrtlje ice rink. These profiles can help to check
whether the system works properly and stable or not. The observation from this figure is that the
refrigeration system seems to work in stable conditions as the evaporation temperature is stable.
When one compressor is in operation, the evaporator temperature is around -10.4C and when the
parallel second compressor starts, it decreases to below -11C.

36
Measurement and Modelling of Ice Rinks Heat Loads

Another parameter to examine is the brine in and out temperature difference. It is kept constant to
around 1.5-2C thanks to the variable speed brine pump which regulates the brine mass flow rate.
Moreover, it can be seen that the number of compressors working is governed by brine return
temperature (brine in) with a set point of -4C 0.5C.
Furthermore, ice top and bottom temperatures are also shown in Figure 23. The two temperatures
are measured with PT1000 sensors embedded in the ice. The bottom sensor is put on the concrete
surface before the ice build-up started and the second is placed approximately 15 mm up in the ice,
which is in fact about 10 mm from the actual surface. It can be seen clearly that ice resurfacing with
warm water takes place six times; once early in the morning before 7:00 start, once in the midday
and four times in the evening during the intensive activity hours.
Finally, this graph gives the opportunity to check the the temperature waste from the source,
evaporator, to the user, ice. It can be seen that the highest temperature increase occurs during the
heat transfer between the evaporator and brine. It might be as a result of a too small heat transfer
area and/or the requirement for superheat in the evaporator..

1
Temperature (C)

5 BRINEIN
7
BRINEOUT
9
ICEBOTTOM
11
ICETOP
13
EVAPORATOR
15
00:00:00
00:52:00
01:44:00
02:36:00
03:28:00
04:20:00
05:12:00
06:04:00
06:56:00
07:48:00
08:40:00
09:32:00
10:26:00
11:18:00
12:10:00
13:03:00
13:55:00
14:47:00
15:40:00
16:32:00
17:24:00
18:16:00
19:08:00
20:01:00
20:53:00
21:45:00
22:37:00
23:29:00

Figure 23: Ice, brine and evaporating refrigerant temperature fluctuations, 15 March 2011, Norrtlje

3.3.2 Evaporation/Condensation temperatures


Figure 24 shows the evaporation and condensation temperatures for the same day. It can be seen
that at the start and end of the day two compressors run. During the rest of the day one compressor
is enough to compensate for heat loads. It seems that two compressors are necessary during the first
hour of midnight because the effects of the heat loads from last night are still remained on the ice.
The reason for two compressors running during the last three-four hours is the heat loads of rush
evening hours. There were some more activities on the ice and there are four ice resurfacings (Figure
23). As a consequence, the second compressor starts to work in parallel. It can be seen that there is a
time lag between the ice resurfacing heat loads start (around 18:00) and the second compressor
being on (around 20:00); the ice acts as a thermal storage body.

37
Measurement and Modelling of Ice Rinks Heat Loads

00:00:00
00:50:00
01:40:00
02:30:00
03:20:00
04:10:00
05:00:00
05:50:00
06:40:00
07:30:00
08:20:00
09:10:00
10:02:00
10:52:00
11:42:00
12:32:00
13:23:00
14:13:00
15:03:00
15:54:00
16:44:00
17:34:00
18:24:00
19:14:00
20:05:00
20:55:00
21:45:00
22:35:00
23:25:00
25,0
20,0
15,0
Temperature (C)

10,0
5,0 One
Two
0,0 compressor
compressors
-5,0
-10,0
-15,0
-20,0

Evaporation temperature Condensation temperature

Figure 24: Evaporation and condensation temperatures, 15 March 2011

3.3.3 Brine and coolant temperatures


The temperatures of the brine and coolant have been indicated in Figure 25. Brine in and out
temperature difference is kept constant 1.5-2C, due to brine pump variable speed operation. The
temperature difference of the coolant in and out is around 10C when one compressor runs and
during the two compressors operation simultaneously, the coolant out temperature rises about 5C.

25

20
Temperature (C)

15

10 BRINEIN

5 BRINEOUT
COOLANTIN
0
COOLANTOUT
5

10
00:00:00
00:52:00
01:44:00
02:36:00
03:28:00
04:20:00
05:12:00
06:04:00
06:56:00
07:48:00
08:40:00
09:32:00
10:26:00
11:18:00
12:10:00
13:03:00
13:55:00
14:47:00
15:40:00
16:32:00
17:24:00
18:16:00
19:08:00
20:01:00
20:53:00
21:45:00
22:37:00
23:29:00

Figure 25: Brine and coolant temperatures, 15 March 2011

38
Measurement and Modelling of Ice Rinks Heat Loads

3.3.4 Air temperature and relative humidity over ice, indoor and outdoor
The results of the air temperature and relative humidity measurements in three locations (over ice, in
the ice rink and outdoor) have been shown in Figure 26.
It can be seen that the relative humidity in the ice rink is kept lower than 45-50%, thanks to the
dehumidification system. The relative humidity close to the ice surface is higher, 50-60%, because
the air temperature (light blue line) is colder in comparison to ice hall temperature (red line).
It is worth mentioning that this graph is for 15 March 2011, a relatively cold and dry day. In
describing the calculations for condensation, a humid warm summer day is chosen to demonstrate
the significance of relative humidity impact on the condensation heat load.
Looking at the three temperatures shown in Figure 26, stable indoor conditions can be compared
with outdoor temperature fluctuations of more than 10C. It is a sign for stable energy systems
(heating, ventilation, cooling) operation and good insulation.

30 70

25 60

Relative humidity %
20 50
Temperature (C)

rhishall
15 40
rhoverice
10 30 tempishall
5 20 outdoortemp
tempoverice
0 10

5 0
00:44:00
01:42:00
02:40:00
03:38:00
04:36:00
05:34:00
06:32:00
07:30:00
08:28:00
09:26:00
10:24:00
11:22:00
12:20:00
13:18:00
14:16:00
15:14:00
16:14:00
17:13:00
18:11:00
19:09:00
20:07:00
21:05:00
22:03:00
23:01:00
23:59:00

Figure 26: Air temperatures and relative humidity, 15 March 2011

3.3.5 Electric power input and cooling capacity


Measuring the electricity input to the refrigeration system is one of the most important logged data
as it is the main requirement to be able having an energy balance over the compressor to calculate
the refrigerant mass flow rate. To find this power, voltage and amperage of the electricity is
measured.
In Figure 27, the electricity consumption is shown for the same sample day. For this day one
compressor starts to consume about 19 kW and in next hours it increases the consumption to 23
kW softly, due to frequency converter operation. During the two compressors parallel running, the
total consumption is around 38 kW. It means that the compressors never run with their full speed in
this day according to the control system functions. However, it has been observed that in warm
39
Measurement and Modelling of Ice Rinks Heat Loads

summer days or for the ice making periods, the consumed electricity by the compressors is more
than 70-80 kW.

300

Power -Cooling Capacity (kW)


250

200

150

100

50

0
00:46:00
01:49:00
02:52:00
03:55:00
04:58:00
06:01:00
07:04:00
08:07:00
09:10:00
10:15:00
11:18:00
12:21:00
13:25:00
14:28:00
15:32:00
16:35:00
17:38:00
18:41:00
19:45:00
20:48:00
21:51:00
22:54:00
23:59:00
Q cooling (kW) Electric Power (kW)

Figure 27: Electric power and cooling capacity, 15 March 2011

When the input power has been measured, the ClimaCheck method makes it possible to calculate
the system cooling capacity and COP. On 15 March 2011, COP by one compressor is 5.5-6 but by
two compressors COP is around 5. This come from more difference between evaporation and
condensation temperatures during the peak loads (Figure 24). The refrigeration system has to
provide colder refrigerant, rejects the heat with higher temperature and the pressure ratio over
compressors increase, as well.

3.3.6 Total energy consumption


The total electricity consumption of the refrigeration systems and the outdoor temperatures of the
two rinks for March 2011 are shown in Figure 28. The total energy consumption is the sum of the
compressor electricity consumption and the auxiliary equipment including brine and coolant pumps
and dry cooler fans.
The energy consumption is clearly higher in lta despite the same outdoor temperatures. The main
reason for higher daily consumption in lta (1550 kWh/day average) in comparison with Norrtlje
(920 kWh/day average) is the auxiliary pumps and fans. The compressors in lta are not capacity
controlled and they are switched on-off several times per day but the brine and coolant pumps are
running continuously with full rated powers of 15 kW and 11 kW respectively, even when the
compressors are off. On the other side, in Norrtlje, these pumps change their speed according to
the cooling load.

40
Measurement and Modelling of Ice Rinks Heat Loads

The second reason for the higher electricity consumption may be related to the ice temperature.
While the average ice temperature in Norrtlje is -4C to -3C, it is -6C to -5C in lta. A lower ice
temperature increases the energy consumption in two ways. First, lower ice temperature requires
more cooling and hence, more electricity consumption. Secondly, colder ice increases the amount of
absorbed heat through radiation-convection-condensation.
1800
29
Energy consumption (kWh/day)

1600 26

Outdoor Temperature (C)


1400 23
20
1200
17
1000 14
800 11
600 8
5
400
2
200 -1
0 -4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

ltaconsumption(kWh/day) Norrtljeconsumption(kWh/day) ltatemp. Norrtljetemp.

Figure 28: Total refrigeration system energy usage and outdoor temperatures in March 2011

The last reason for higher energy consumption in lta is related to the ventilation ducts
configuration. In Norrtlje there is one ventilation duct header over the spectators stand, while in
lta there are two ventilation headers; one over the stands and another one in the middle of the ice
rink and over the ice sheet (refer to Figure 53). This may cause more air movements over the ice,
with higher temperature and more velocity in comparison to Norrtlje. That is why convection is
one of the major heat loads in lta.
Table 4 summarizes the main reasons for more energy consumption in lta.
Table 4: Reasons for higher energy consumption in lta

lta (1550 kWh/day) Norrtlje(920 kWh/day)

Capacity controlled by brine


Compressors On Off periodically
temperature
Brine & Coolant pumps Without frequency converter With frequency converter
2 Main distribution ducts, 1 Main distribution duct over the
Ventilation
one over ice/one over stands stands

Ice temperature -6C to -5C -4C to -3C

41
Measurement and Modelling of Ice Rinks Heat Loads

4. ANALYTICAL MODELLING
In the experimental measurement part it is described how the cooling capacity can be estimated by
ClimaCheck method and the explained modifications. This cooling capacity is an indication of the
total heat loads on the ice sheet plus the heat gains of the provided cooling in its way from
evaporator to ice.
In the analytical modelling part, the objective is to understand what the various heat loads are and
how they can be calculated/estimated. In other words, the total heat load is broken down to find
the magnitude and share of each heat load. This step helps any technician or ice rink owner to
discover what the main sources of heat loads in the rink are.
Furthermore, another method is introduced to guess the amount of heat loads on ice, just by
knowing and using the ice top and bottom temperatures. It is not as precise as the ClimaCheck
method, but is a simple useful gauge to present the magnitude of the heat loads.
Finally, the heat transfer from ice to the evaporator is evaluated according to the temperature
resistances. The objective is to discover where the biggest resistances against the heat flow are.

4.1 Heat loads


In part 2.4 heat loads are classified according to their type of heat transfer mechanisms. In another
point of view, these loads can be categorised into two groups according to their location of impacts:
those which directly impact the ice, trying to melt it down and those heat gains that have impacts
along the refrigerant-brine-concrete-ice path and increase the required cooling capacity.
Figure 29 demonstrates these two groups of heat loads. Convection, condensation, radiation,
lighting, ice resurfacing and skaters activities are heat loads for ice, directly and for the refrigeration
system, indirectly. The ground conduction, brine headers heat gain and brine pumps work belong to
the second group which can be called distribution system losses.
.

Figure 29: Heat loads in ice rinks and their impact points

42
Measurement and Modelling of Ice Rinks Heat Loads

In the following sections the correlations and methods of estimating each heat load is introduced
and a result sample for each calculation is presented and discussed. Then, for a whole day heat loads
share is calculated to find the major and minor heat loads.

4.1.1 Radiation
Radiation is one of the most significant heat loads in ice rinks as two large surfaces of cold ice and
relatively warm ceiling face each other. To calculate the radiation the Stefan-Boltzmann equation can
be applied:

Where is the Stefan-Boltzmann constant and equals to 5.6710-8 W/(m2K4) and ci is gray body
configuration factor for radiation from ceiling to ice surface and can be calculated by:

is the emissivity factor and for normal ceiling constructions and ice structure ranges from 0.8 to
0.95. Fci is the angle factor and depends on the geometric properties of the ceiling surface, ice
surface and the ice rink height. The geometry inputs are the following, ice sheet 6030 m, ceiling
height and surface 9 m and 2200 m2 respectively. Graphs like what is shown in Figure 30 are used to
avoid the complex correlation for calculating this angle factor.
An example of a radiation calculation for one of the ice rinks is shown in Figure 31 as a sum of
radiation, convection and condensation heat loads. This will be discussed after convection and
condensation explanations.
It should be mentioned that for ceiling temperature, as there was no installed temperature logger in
the height, an average value of indoor and outdoor temperature is considered. As explained in
future work chapter, measuring the ceiling temperature with infrared cameras is going to be done
which can make the radiation calculations more accurate.

43
Measurement and Modelling of Ice Rinks Heat Loads

Figure 30: Angle factor between two aligned parallel faces (engel, 2007)

4.1.2 Convection
The temperature of the air moving above the ice is a few degrees higher than zero and the ice
temperature is few degrees lower than zero. This temperature difference is the driving force for
convection. The amount of convection heat load can be calculated by equation (6):

c is the convective heat transfer coefficient. It can be calculated by an experimental equation


(ASHRAE, 2010) which uses the air velocity over ice to take into consideration both natural and
forced convection:

. .

The heat transfer coefficient is assumed to be 5 W/m2K as a reasonable assumption with air
velocity 0.4-0.5 m/s over ice (DOE, 1980).

44
Measurement and Modelling of Ice Rinks Heat Loads

4.1.3 Condensation
The driving force for water vapour condensation is the difference between the partial pressure of
water vapour (in the air close to ice surface) and the saturation pressure of water at ice top surface
temperature.
The general condensation heat transfer equation is similar to convection and the difference is in the
condensation heat transfer coefficient instead of the convective one. Condensation, which in some
books known as diffusion, can be estimated by equation (8)

d is the diffusion (condensation) heat transfer coefficient and be calculated by equation (9)
(Granryd, 2005):

is air relative humidity. P1 and P2 are water vapour saturation pressures in air and on ice top
surface can be calculated by equations (11) and (12):

.
.
.

It should be mentioned that equation (11) is appropriate for temperatures higher than zero while
equation (12) is suitable for temperatures lower than zero.
By knowing the correlations to calculate radiation, convection and condensation heat loads, a time
period is chosen to examine these estimations. In order to eliminate the effects of lighting, ice
resurfacing and skaters activities, the first six hours of March 15 midnight is selected. It has been
tried to check these calculations with the cooling capacity minus ground and pump heat gains. The
results for the calculations shown in Figure 31 indicate a good match. It is indicated that average net
cooling capacity is 98.5 kW while the average heat loads on the ice is 92.5 kW. The slight 6 kW
difference is due to brine headers heat loads which will be discussed later.

45
Measurement and Modelling of Ice Rinks Heat Loads

Q cooling (kW) ground-pump gains eleminated


heat loads (kW)radiation-convection-condensation
110
105
Cooling-heat loads (kW)

100
95
90
85
80
75
70
00:00:00
00:12:00
00:24:00
00:36:00
00:48:00
01:00:00
01:12:00
01:24:00
01:36:00
01:48:00
02:00:00
02:12:00
02:24:00
02:36:00
02:48:00
03:00:00
03:12:00
03:24:00
03:36:00
03:48:00
04:00:00
04:12:00
04:24:00
04:36:00
04:48:00
05:00:00
05:12:00
05:24:00
05:36:00
05:48:00
06:00:00
Figure 31: Cooling capacity versus heat loads at midnight, 15 March 2011

The chosen day was a cold dry day and as a consequence, condensation has a share of less than 2%.
For this six-hour period, convection accounts for about 56% and radiation 42% of the total heat
load.
To study the condensation load and its effect better, the warmest day of the humid summer 2010 is
studied below. As shown in Figure 32, on this day relative humidity above the ice and in the ice rink
is 60-70%. It can be compared with Figure 26 to realize the difference.

20 80
70
15
60
Relative humidity %
Temperature (C)

10 50
temp ice top
40 temp ice hall
5 30 temp over ice
rh ice hall
20
0 rh over ice
10
-5 0
00:00:00
01:15:00
02:30:00
03:45:00
05:00:00
06:16:00
07:31:00
08:46:00
10:02:00
11:16:00
12:32:00
13:47:00
15:03:00
16:19:00
18:02:00
19:17:00
20:32:00
21:47:00
23:03:00

Figure 32: Air and ice temperatures and air relative humidity, 12 July 2010, Norrtlje

46
Measurement and Modelling of Ice Rinks Heat Loads

On March 15, 2011 the condensation heat transfer coefficient is very smaller than the convective
heat transfer coefficient but on July 12, 2010 it is shown in Figure 33 that while c is equal to 5

W/m2.k, average d is 1.1-1.4 W/m2.k. In other words, for this humid day condensation heat load is
about 25-30% of the convection heat load. This leads to a share of 10% in total heat load for
condensation.

2
Heat transfer Coefficient (W/m2.K)

1,8
1,6
1,4
1,2
1
0,8 _d
0,6
0,4
0,2
0
00:00:00
01:19:00
02:38:00
03:57:00
05:17:00
06:36:00
07:55:00
09:14:00
10:34:00
11:52:00
13:12:00
14:32:00
15:51:00
17:38:00
18:58:00
20:17:00
21:36:00
22:56:00
Figure 33: Condensation heat transfer coefficient, 12 July 2010, Norrtlje

4.1.4 Lighting
Each lighting fixture in Norrtlje is composed of three lamps each consumes 48 watts electricity.
There are 6 rows of lighting rails and each rail contains 38 lighting fixtures, then the total lighting
electricity consumption should be 32.8 kW approximately. According to ASHRAE up to 60% of
this input energy can be converted to the radiated heat but as fluorescent lamps are among the
energy efficient lighting devices, 40% is assumed as the ratio of radiated heat from lamps to the ice,
which is 13.1 kW.

47
Measurement and Modelling of Ice Rinks Heat Loads

Figure 34: Lighting fixtures in Norrtlje

4.1.5 Ground Conduction


To calculate the amount of heat conduction from ground to the concrete, which increases the
amount of required cooling capacity, it is assumed that the concrete temperature is -5C as the brine
in and out average are -4C and -6C, respectively. Ground temperature is kept +5C by soil heating
pipes, and then there is 10C temperature difference between the ground and the concrete. The
distance between these two heat transfer sheets is filled with 10cm concrete (brine pipe top to
concrete bottom) and 10cm thick polystyrene insulation. Thermal conductivity for the concrete is
1.7 W/mK and polystyrene is 0.04 W/mK (Makhnatch, 2010 and FAO, 2003). These parameters
lead to 7 kW conduction heat gains from ground.

4.1.6 Brine headers


Supply and return brine headers are located along the 30 m width of the ice rink. These two 150
mm pipes are in a trench and they are covered with 2 cm thick ice as a heat transfer resistance. The
distance between the trench and the evaporator, inside the machinery room is 10m and the pipes
have 2 cm Armaflex insulation, 0.033 W/mK thermal conductivity. These data can be used to
calculate the amount of heat gain by the brine pipe headers. Whether the resistance to heat transfer
is the pipe wall, the 2-cm ice ring around pipe or the insulation, the conduction heat transfer is equal
to:

Using equation (13) and the parameters summarized in Table 5 leads to 6.7 kW heat load on the
refrigeration plant due to brine headers heat gains.

48
Measurement and Modelling of Ice Rinks Heat Loads

Table 5: Physical properties for brine headers for heat load calculation

Thermal conductivity
Size (mm) Temperature (C)
(W/m.K)
Pipe Di = 77
Pipe = 43 Brine = -5
60m pipe-ice Pipe Do = 84
Ice = 2.25 Ice surface = -3
Ice thickness = 20
Pipe Di = 77
Pipe = 43 Brine = -5
20m pipe-insulation Pipe Do = 84
Insulation = 0.033 Ambient = 10
Insulation thickness = 20

4.1.7 Ice resurfacing


Ice resurfacing adds a significant amount of heat to the ice. The amount of resurfacing heat can be
estimated by equation (14): (ASHRAE, 2010).

Qresurfacing 1000 Vf . tf t i

Where Vf is the flood water volume (m3), tf and ti are the water and ice temperatures (C). Flooded
water is typically 0.4 to 0.7 m3. In Norrtlje flood water volume and temperature are 600 litres and
35C, respectively. Ice temperature is considered to be -1.5C according to Figure 23. These input
data result in about 81 kWh heat addition to ice for each ice resurfacing.
To study the significance of ice resurfacing heat load an exercise has been done. On March 15, two
six-hour period has been chosen, 12:00-18:00 when there is no ice resurfacing and 18:00-24:00 when
there are four ice resurfacings. The produced cooling capacity for the first six hours is 701 kWh
while for the second six-hour period it is 912 kWh. It means that there is a need for 30% more
cooling in the second period because there are several ice resurfacings.
It was mentioned before that each ice resurfacing heat addition is 81 kWh. It means that four ice
resurfacings have 324 kWh total load. From this 324 kWh, 211 kWh (=912-701) is compensated by
the refrigeration system and the remaining is stored in ice body, which later and during the next
midnight will be transferred to the refrigeration system as well. This heat absorption causes an
increase in ice temperature during the evening and has been shown in Figure 35. It is discussed
before that when the ice becomes warmer and there is a risk for melting, the second compressor
starts to work in parallel with the first one. Furthermore, during the less crowded hours of midday
ice is in rest and the temperature decreases slightly.

49
Measurement and Modelling of Ice Rinks Heat Loads

-0,5

-1
Temperature (C)

hourly
-1,5 avergaeice
temperature
-2

-2,5 two
-3
compressors

-3,5

Figure 35: Hourly average ice temperature, 15 March 2011, Norrtlje

4.1.8 Pump work


The brine pump nominal power in Norrtlje is 15 kW and the speed is controlled by a frequency
converter. When the compressors are off, this pump is jogging with a low frequency. This is
necessary because the system control is based on the brine return temperature. When one
compressor works, this pump operates at 40Hz and consumes about half of the nominal capacity,
7.5 kW. During the peak load conditions the brine pump frequency is 50Hz and the electricity
consumption is close to nominal capacity, 15 kW. As a consequence, the heat load from the brine
pump has a step function with three values; near zero, 7.5 kW and 15 kW according to the cooling
capacity demand.

4.1.9 Skaters
Skaters heat load is very hard to estimate precisely as there should be detailed information of
activities, their duration and type (heavy, light, etc...) and even if this information is available still
there is no scientific methods introduced to calculate the heat load, for example by skates friction on
the ice or skaters body radiation. ASHRAE suggests assuming 4% of the total heat loads regarding
to skaters activities on the ice.

50
Measurement and Modelling of Ice Rinks Heat Loads

4.1.10 Results for heat loads shares


In the previous nine sections it has been described how to calculate, estimate or for a few cases have
a logical good guess for each heat load in the ice rinks.
Table 6 shows a summary for six heat loads other than radiation, convection and condensation. The
other three ones do not have a relatively constant value as these six ones have, during their period of
impacts. By period of impact it is meant that for example lighting is a heat load during the
working hours of the ice rink, around 18 hours a day.
Table 6: Heat loads summary

Heat source Heat Gain (kW/kWh) Notes/assumptions

Lighting 13 kW Heat/emitted light = 40%

+5C ground and -5C concrete, 10 cm polystyrene,


Ground 7 kW
10 cm concrete
7.5 kW (1 Compressor) 40Hz
Brine pump
15 kW (2 Compressors) 50Hz

Ice resurfacing 81 kWh per resurfacing 35C resurfacing water, 600 litres flood water

Brine header 20m insulated pipe headers


6.7 kW
pipes 60m frozen pipe headers

Skaters 4% of total heat load -

In order to find the share and weight of the heat loads in total heat load on the ice sheet and
refrigeration system, daily heat loads estimation has been fulfilled for 15 March 2011 in Norrtlje ice
rink and the results are demonstrated in Table 7 and Figure 36. Average radiation heat load is 33 kW
and daily average convection-condensation is 51.5 kW. These heat loads applied during the whole 24
hours. Lighting is applied from 6:00 in the morning to 24:00, and then the 13 kW load is not applied
on the ice during six hours of midnight. Brine header and ground conduction have their loads all the
day. Brine pump average heat load is calculated to be 9 kW as in some hours it runs by 7.5 kW
power and the remaining with 15 kW. Furthermore, there are six ice resurfacings. All the above heat
loads account for 96% of the total daily heat load and the remaining 4% is skaters heat load.
As it is shown in the table, the total heat load is equal to 3 430 kWh. The refrigeration system should
compensate this heat load. To examine this, the average cooling capacity is calculated to be 142 kW
as in many hours the cooling capacity is 120-130 kW and in few hours it is 180-190 kW (refer to
Figure 27) and then the total daily cooling is 3 408 kWh which shows a good match with the heat
loads sum.

51
Measurement and Modelling of Ice Rinks Heat Loads

Table 7: Daily heat load calculations, 15 March 2011

heat load kW kWh


radiation 33 792
lighting 13 234
convection - condensation 51.5 1236
ice resurfacing 81 kWh/res. 486
header pipe 6.7 160.8
brine pump 9 (Avg.) 216
ground 7 168
skaters 4% of total 137.2

total daily heat load 3430

total daily cooling capacity 142 (Avg.) 3408

Heat loads shares are indicated in Figure 36. Convection, radiation, ice resurfacing and lighting are
the four biggest heat loads in this ice rink while condensation (less than 3% of convection) and
skaters are the smallest ones. Conduction heat gains of the distribution system ground, header pipe
and brine pipe - have almost equal shares. This figure demonstrates that about 84% of the total heat
loads are the loads on the ice and 16% are the losses in the distribution system. It should be
reminded that condensation has a bigger share in summer, as discussed before.
ground skaters
brine pump 5% 4%
6%

header pipe
5% radiation
23%

ice resurfacing lighting


14% 7%

convection
+condensation
36%

Figure 36: Heat loads shares in the total heat load

52
Measurement and Modelling of Ice Rinks Heat Loads

4.2 Heat flux method


Top and bottom ice temperature fluctuations can be used to estimate the amount of heat load on ice
sheet and the amount of heat transferred to the cold concrete slab. To measure these, two
temperature sensors are installed in the ice as indicated below. From Fourier-Biot, the general
transient conduction equation, the ice sheet case can be simplified to one dimensional transient
conduction (diffusion equation), as the thickness of the ice is only 0.1-0.2% of the ice length and
width and hence equation (15) governs the heat transfer process in ice:

T represents the ice temperature, t for time; z is the ice thickness axis and is the thermal diffusivity
of ice which equals to k/Cp of the ice (thermal conductivity over the density and specific heat
capacity which are considered 2.25 W/mK, 912 kg/m3 and 2087 J/kgK respectively).
The temperature profile is T=Az2+Bz+C which A, B and C would be known by boundary
conditions and temperature as a function of time. If the z axis starts from the top ice and goes
downward to ice bottom, it is possible to say z=0 for ice top and z=depth difference between two
sensors for ice bottom (15mm in Norrtlje). Then C is equal to ice top temperature at z=0. A
can be known by using equation (15) and twice differentiating the temperature profile equation.
When A and C are known, B can be calculated by using ice bottom temperature.
To conclude, as the temperature fluctuations over time and place are measured and known, heat flux
to the top and bottom surface of the ice can be achieved by equation (16) and then by multiplying to
ice surface area (1800 m2) heat transfer rate can be calculated:

top ice temp. sensor

Ice

bottom ice temp. sensor

Figure 37: Top and bottom temperature sensors embedded in the ice

53
Measurement and Modelling of Ice Rinks Heat Loads

4.2.1 Results
The results of the calculation by this method are shown in Figure 38 for the days 14-16 April 2011.
The reason for selecting these three days is that at 20:30 on 15 April the refrigeration system was
switched off and at 6:30 of the third day the compressor was switched on again. The effect of this
switch off-on is seen as the lowest heat transfer rate.

Top Heat Transfer Rate (kW) Bottom Heat Transfer Rate (kW)
140
Heat transfer rate (kW)

120
100
80
60
40
20
0
10-11
12-13
14-15
16-17
18-19
20-21
22-23

10-11
12-13
14-15
16-17
18-19
20-21
22-23

10-11
12-13
14-15
16-17
18-19
20-21
22-23
0-1
2-3
4-5
6-7
8-9

0-1
2-3
4-5
6-7
8-9

0-1
2-3
4-5
6-7
8-9
Figure 38: Top and bottom heat transfer rate on days 14, 15 and 16 April 2011

The difference between the top and bottom heat flow rate may show the ice temperature rise or
decrease. For instance, during the compressor-off period, as the brine becomes warmer, less heat is
transferred to the concrete slab and the absorbed heat causes the ice temperature to rise.
Furthermore, the steep decrease in heat gain during the compressor-off period seems to indicate the
significant effect of ice temperature on radiation and convection heat gains. In other words, colder
ice absorbs more heat and vice versa.

0,00
Temperature (C)

1,00 Shut down


period
2,00
3,00
4,00
01
34
67

1213
1516
1819
2122
01
34
67

1213
1516
1819
2122
01
34
67

1213
1516
1819
2122
910

910

910

Figure 39: Ice average temperature fluctuations on 14, 15 and 16 April 2011

54
Measurement and Modelling of Ice Rinks Heat Loads

4.3 Temperature resistances-differences


Some other calculations can be done to analyse the performance of refrigeration and distribution
system. The objective of these calculations is to find the places which are the main resistances to the
heat transfer from the ice to the refrigeration system.
As it was mentioned before, Figure 40 demonstrates the heat flow from the heat loads above the ice
to the refrigeration system. In this energy flow, concrete and brine plays a medium role and as
indicated ground, header and pump heat loads are added to the above ice loads through this path.

Figure 40: Heat flow from ice to refrigeration plant

Three temperature differences are considered to be calculated; evaporator-brine, average brine in


and out temperatures- bottom ice and bottom-top ice temperature difference. Table 8 summarizes
the results for March 15, 2011 in the Norrtlje ice rink. As it is shown the major heat transfer
resistance is in the heat transfer from brine to evaporator. The reason may be related to the
difference in the mechanism of the heat transfer and the actual surfaces used for the heat transfer. In
the evaporator convection occurs while for the two other situations conduction is the prevailing heat
transfer mechanism. The solution to have less temperature resistance might be a heat exchanger with
more heat transfer area and to not be dependent on evaporator superheat control.

Table 8: Heat transfer resistances and temperature differences

Average resistance (K/kW) average T (K)


evaporator-brine 0.0400 5.63 (LMTD)
Avg. brine-bottom ice 0.0168 1.97
bottom-top ice 0.0041 0.47

It should be mentioned that for calculating the first temperature difference, log mean temperature
difference is used as in evaporator the two-phase refrigerant temperature is almost constant while
the brine temperature decreases. Looking at the resistances and differences, it can be concluded that
two third of the total resistance resulted from the evaporator-brines while other shares are 27% and
7%.

55
Measurement and Modelling of Ice Rinks Heat Loads

5. CONCLUSION
Methods to analyse the refrigeration system performance have been studied by using the
ClimaCheck instrumentation plus the compressor heat rejection calculation. Furthermore, ice and
indoor hall conditions are studied to understand the driving factors for the heat loads. The results of
the measurements show that the total energy consumption in Norrtlje is about two third of lta.
The main reasons for this less energy consumption are smarter control for compressors and pumps,
better ventilation distribution design and 1C-2C higher ice temperature.
Methods to estimate the heat loads and their shares in the ice rinks total heat load are introduced.
These estimates are useful to select the proper energy efficiency measures. Analytical modelling for a
sample day has estimated that about 84% of the total heat loads is originated from the heat loads on
ice sheet while the distribution system causes the remaining 16%. Moreover, calculations show that
convection plus small portion of condensation (altogether 36%), radiation (23%), ice resurfacing
(14%) and lighting (7%) are the largest heat loads in winter while in summer condensation is another
significant heat load (10%). Comparing two six-hour periods, one without ice resurfacing and four
resurfacings in the second one, 30% more cooling demand has been calculated for the second
period.
A heat flux method to calculate the heat transfer in the ice is introduced. It has been shown that
with the help of two temperature sensors embedded in ice, it is possible to have an estimation of the
heat loads on the ice. Moreover, the effect of ice temperature on the heat absorbing process is
discussed.
Finding the heat transfer resistances, it has been shown that evaporator to brine contributes with
66% of the heat transfer resistances from ice to evaporator while brine to bottom ice and bottom to
top ice accounts for 27% and 7% respectively.
To conclude, a parallel performance analysis of the refrigeration system and heat loads
estimation proves to be a useful tool for adopting proper design and control for energy efficient
operation.

56
Measurement and Modelling of Ice Rinks Heat Loads

6. FUTURE WORK / SUGGESTIONS


6.1 Future work
This thesis was part of a greater study for energy efficiency in ice rinks. There are some more
researches which are in process or will be started in future including:
A paper has been presented in 23rd IIR International Congress of Refrigeration titled:
Experimental cooling load analysis of ice rinks. Another paper can be prepared to reflect
the latest results.
Energy Usage Prediction model comparing Indoor vs. Outdoor Ice Rinks
Indoor ice rink more detailed temperature measurements including the ceiling temperature
and ice surface by IR camera
Research on ice physical properties and its impacts on the total heat load

6.2 Suggestions
There are some ideas that may worth thinking:
In lta ice rink a low-e ceiling is installed during summer 2011. It can be a valuable study to
compare the energy consumptions before and after the installation and it can show the
significant effect of this technique (or its weakness).
As radiation and convection are the two big heat loads in ice rinks, it seems that more
detailed calculations and modelling is required. For example for radiation, a better knowledge
of ceiling temperature and its value is necessary. Furthermore, the ceiling shape by
ASHRAE (and in this study) is assumed to be flat while in reality, many ceilings are curved
and a broader study is required on this topic. For convection, the heat transfer coefficient is
taken from a paper of 1970s and it seems that better correlations should be derived by new
researches.
Ice rinks are mostly used in northern countries with cold winters including North American,
Russia and Scandinavian countries. There could be some systems to use the very cold
outdoor air, for example during midnights, to help the refrigeration system works with a
lower capacity.
Covering the ice during nights can lower the radiation and convection, probably to a great
extent. The advantages and disadvantages of such a system can be studied.
Body heat losses of open compressors and the input electricity losses are sources of
uncertainty in cooling capacity calculations and they are not easy to obtain. More research
and accuracy is necessary for ClimaCheck evaluation of refrigeration systems with open
compressors.

57
Measurement and Modelling of Ice Rinks Heat Loads

7. BIBLIOGRAPGY
AAQ, 2003, Technical Fact Sheets on the Impacts of New Energy Efficiency Technologies
and Measures in Ice Rinks, The Association des Arenas du Qubec
ASHRAE. 2010, ASHRAE Refrigeration Handbook, chapter 44:ice rinks, ANSI/ASHRAE
standard
Bellache et al. 2007, Calculation of refrigeration loads by convection, radiation and
condensation in ice rinks using a transient 3D zonal model
Berglf K. 2010, Optimization through performance inspections, Proc. Stockholm
Conference, IIF/IIR.
engel, Yunus.A et al. 2007, Fundamentals of Thermal-Fluid Sciences, Chapter 22:
Radiation heat transfer, McGraw-Hill
DOE. 1980, energy conservation in ice skating rinks, prepared by B.K.Dietrich and
T.J.MacAvoy, U.S. Department of energy, Washington, D.C.
Everything Ice, 2000, Recreation Facilities Design Manual, publish authorized by Manitoba
Hydro, Canada
FAO, 2003, The use of ice on small fishing vessels, food and agriculture organization of the
united nations, Rome, 2003, available at
http://www.fao.org/docrep/006/Y5013E/y5013e00.htm#Contents
Granryd E. 2005, Refrigerating Engineering, Part II, Chapter 15: Processes in moist air,
frosting and defrosting, KTH, Department of Energy Technology
How ice rink works?, 2011, available at
http://entertainment.howstuffworks.com/ice-rink2.htm
IIHF, 2010. Technical guidelines of an ice rink, international ice hockey federation guide
book, chapter 3
Ingvar, 2007, Ice skating rink-movable, available at
http://www.ingvar.is/Plants/IceSkatingRink/IceSkatingRink.html
Luminous. 2011, Wikipedia: Luminous Efficacy available at:
http://en.wikipedia.org/wiki/Luminous_efficacy
Makhnatch P. 2010, Technology and Energy Inventory of Ice Rinks, Master thesis, KTH
Melinder . 2009, Handbook on indirect refrigeration and heat pump systems, Effsys2
program, KTH
Motor challenge, 2010, determining electric motor load and efficiency, US department of
Energy
Munters, 2011, Munters DryCoolTM Dehumidification Systems, Engineering Catalogue
available at:
http://webdh.munters.com/webdh/BrochureUploads/Engineering%20Catalog-
%20DDS.pdf
Nicolas L. 2009, Improving efficiency in ice hockey arenas, ASHRAE Journal June 2009
Retscreen, 2005, Energy Efficiency Project Analysis for Supermarkets and Arenas,
presentation for Clean energy project analysis course, Canada

58
Measurement and Modelling of Ice Rinks Heat Loads

Rogstam J. (a) 2010, Energy usage statistics and saving potential in ice rinks, Proc. Stockholm
Conference, IIF/IIR.
Rogstam J. (b) 2010, Ice rinks using carbon dioxide as secondary refrigerant, Proc. Stockholm
Conference, IIF/IIR.
Rogstam J. (c)/Karampour M. 2011, Experimental cooling load analysis of ice rinks, The
23rd IIR International Congress of Refrigeration, Prague
Sawalha S. and Chen Y. 2010, Investigations of Heat Recovery in Different Refrigeration
System Solutions in Supermarkets, Effsys2 Project final report, KTH
Shahzad K. 2006, an ice rink refrigeration system based on CO2 as secondary fluid in copper
tubes, Master Thesis, IUC/KTH.

59
Measurement and Modelling of Ice Rinks Heat Loads

8. APPENDIX
To bring a clearer vision of some important calculations, in sections 8.1 and 8.2 two sample
calculations are shown. The method to estimate the percentage of heat rejected from compressor
body in comparison to the shaft power is described in section 8.1. Furthermore, in section 8.2 the
calculation to find the cooling capacity is shown for one hour, as a sample.
The last section shows some figures of the two ice rinks including their refrigeration, heating,
ventilation and dehumidification systems.

8.1 Compressor heat rejection sample calculations


The heat that is rejected from the compressor is estimated by using MYCOM software. It is a
compressor selection and analysis software. The interface, as shown in Figure 41, includes the
refrigerant type, thermodynamics of the cycle, compressor specifications and calculation results. The
compressors used in Norrtlje are K series with 8 cylinders.
Various RPMs and condensing temperatures have been studied (refer to section 3.2.2) to find a
general correlation for the heat rejection.

Figure 41: MYCOM software interface

60
Measurement and Modelling of Ice Rinks Heat Loads

Table 9: Heat rejection calculation results by MYCOM software

teva = -10C, superheat = 7K, subcool = 5K


tcond (C)
10 15 20 25 30 35 40
Cooling Capacity kW 109.9 104.5 99 93.3 87.5 81.5 75.3
Absorbed Power kW 12.4 14.6 16.6 18.5 20.3 21.8 23.2
RPM=900

Oil Heat Rejection kW 0.58 0.58 0.58 0.58 0.58 0.58 0.58
Jacket Heat Rejection kW 1.58 2.13 2.69 3.24 3.79 4.33 4.88
Total heat Rejection kW 2.16 2.71 3.27 3.82 4.37 4.91 5.46
(Tot. Heat/abs. Power)% 17.42 18.56 19.70 20.65 21.53 22.52 23.53
Cooling Capacity kW 122.1 116.2 110.2 103.9 97.5 91 84.2
Absorbed Power kW 14 16.4 18.7 20.8 22.7 24.5 26
RPM=1000

Oil Heat Rejection kW 0.58 0.58 0.58 0.58 0.58 0.58 0.74
Jacket Heat Rejection kW 1.79 2.35 2.9 3.46 4.02 4.57 5.13
Total heat Rejection kW 2.37 2.93 3.48 4.04 4.6 5.15 5.87
(Tot. Heat/abs. Power)% 16.93 17.87 18.61 19.42 20.26 21.02 22.58
Cooling Capacity kW 134.2 127.8 121.3 114.5 107.6 100.5 93.2
Absorbed Power kW 15.7 18.4 20.8 23.2 25.3 27.2 28.9
RPM=1100

Oil Heat Rejection kW 0.58 0.58 0.58 0.58 0.58 0.69 0.91
Jacket Heat Rejection kW 1.97 2.54 3.1 3.67 4.24 4.8 5.37
Total heat Rejection kW 2.55 3.12 3.68 4.25 4.82 5.49 6.28
(Tot. Heat/abs. Power)% 16.24 16.96 17.69 18.32 19.05 20.18 21.73
Cooling Capacity kW 146.1 139.3 132.3 125.1 117.6 110 102.2
Absorbed Power kW 17.5 20.3 23 25.5 27.9 30 31.8
RPM=1200

Oil Heat Rejection kW 0.58 0.58 0.58 0.58 0.64 0.86 1.09
Jacket Heat Rejection kW 2.13 2.71 3.29 3.87 4.44 5.02 5.6
Total heat Rejection kW 2.71 3.29 3.87 4.45 5.08 5.88 6.69
(Tot. Heat/abs. Power)% 15.49 16.21 16.83 17.45 18.21 19.60 21.04
Cooling Capacity kW 158 150.7 143.2 135.5 127.6 119.5 111.1
Absorbed Power kW 19.3 22.3 25.2 27.9 30.5 32.7 34.7
RPM=1300

Oil Heat Rejection kW 0.58 0.58 0.58 0.58 0.81 1.04 1.28
Jacket Heat Rejection kW 2.27 2.86 3.45 4.05 4.64 5.23 5.82
Total heat Rejection kW 2.85 3.44 4.03 4.63 5.45 6.27 7.1
(Tot. Heat/abs. Power)% 14.77 15.43 15.99 16.59 17.87 19.17 20.46
Cooling Capacity kW 169.7 162 154 145.9 137.5 128.9 120.1
Absorbed Power kW 21.1 24.4 27.5 30.4 33.1 35.5 37.7
RPM=1400

Oil Heat Rejection kW 0.58 0.58 0.58 0.74 0.99 1.23 1.48
Jacket Heat Rejection kW 2.38 3 3.61 4.22 4.83 5.44 6.05
Total heat Rejection kW 2.96 3.58 4.19 4.96 5.82 6.67 7.53
(Tot. Heat/abs. Power)% 14.03 14.67 15.24 16.32 17.58 18.79 19.97

61
Measurement and Modelling of Ice Rinks Heat Loads

Cooling Capacity kW 181.1 173.1 164.7 156.1 147.3 138.2 129


Absorbed Power kW 22.9 26.4 29.8 32.9 35.7 38.4 40.7
RPM=1500

Oil Heat Rejection kW 0.58 0.58 0.65 0.92 1.17 1.43 1.69
Jacket Heat Rejection kW 2.48 3.11 3.75 4.38 5.01 5.64 6.27
Total heat Rejection kW 3.06 3.69 4.4 5.3 6.18 7.07 7.96
(Tot. Heat/abs. Power)% 13.36 13.98 14.77 16.11 17.31 18.41 19.56
Cooling Capacity kW 192.4 183.9 175.2 166.2 156.9 147.4 137.8
Absorbed Power kW 24.8 28.6 32.1 35.4 38.4 41.2 43.7
RPM=1600

Oil Heat Rejection kW 0.58 0.58 0.82 1.1 1.37 1.65 1.92
Jacket Heat Rejection kW 2.56 3.22 3.87 4.53 5.18 5.84 6.49
Total heat Rejection kW 3.14 3.8 4.69 5.63 6.55 7.49 8.41
(Tot. Heat/abs. Power)% 12.7 13.3 14.6 15.9 17.1 18.2 19.2
Cooling Capacity kW 203.4 194.6 185.5 176.1 166.4 156.5 146.5
Absorbed Power kW 26.8 30.7 34.4 37.9 41.1 44.1 46.7
RPM=1700

Oil Heat Rejection kW 0.58 0.71 1 1.29 1.58 1.87 2.15


Jacket Heat Rejection kW 2.62 3.3 3.99 4.67 5.35 6.03 6.71
Total heat Rejection kW 3.2 4.01 4.99 5.96 6.93 7.9 8.86
(Tot. Heat/abs. Power)% 11.94 13.06 14.51 15.73 16.86 17.91 18.97
Cooling Capacity kW 214.2 205 195.5 185.8 175.8 165.5 155
Absorbed Power kW 28.8 32.9 36.8 40.5 43.9 47 49.8
RPM=1800

Oil Heat Rejection kW 0.58 0.88 1.19 1.49 1.79 2.1 2.4
Jacket Heat Rejection kW 2.66 3.38 4.09 4.8 5.51 6.23 6.93
Total heat Rejection kW 3.24 4.26 5.28 6.29 7.3 8.33 9.33
(Tot. Heat/abs. Power)% 11.25 12.95 14.35 15.53 16.63 17.72 18.73

62
Measurement and Modelling of Ice Rinks Heat Loads

8.2 Cooling capacity sample calculations


Figure 42 shows the cooling capacity calculation for the last hour of March 15, 2011.

Electric Enthalpy Enthalpy Enthalpy


ref comp ref exp in ref comp Hp Lp t_cond Q_rejection m_dot Q_cooling
Day time Power ExpVal in Comp in Comp out
in (C) (C) out (C) (KPa_a) (KPa_a) (C) (kW) (kg/s) (kW)
(kW) (kJ/kg) (kJ/kg) (kJ/kg)
2011-03-15 23:59:00 -3,9 8,4 79,6 886 273,3 37,7 21,03 239,25 1467,72 1637,06 7,08 0,1525 187,39
2011-03-15 23:58:00 -3,9 8,4 79,5 886,3 273,2 37,8 21,04 239,25 1467,73 1636,80 7,10 0,1532 188,19
2011-03-15 23:57:00 -3,9 8,4 79,5 886 273 38,1 21,03 239,25 1467,75 1636,81 7,16 0,1544 189,70
2011-03-15 23:56:00 -3,9 8,4 79,4 886,6 273,2 38 21,05 239,25 1467,73 1636,54 7,14 0,1542 189,47
2011-03-15 23:55:00 -3,9 8,4 79,4 886,6 273,1 38,2 21,05 239,25 1467,74 1636,54 7,18 0,1550 190,48
2011-03-15 23:54:00 -3,9 8,3 79,4 886 273 37,7 21,03 238,78 1467,75 1636,56 7,08 0,1530 188,05
2011-03-15 23:53:00 -3,9 8,3 79,4 885,7 273 37,8 21,02 238,78 1467,75 1636,57 7,10 0,1534 188,54
2011-03-15 23:52:00 -3,9 8,4 79,4 886 273 37,7 21,03 239,25 1467,75 1636,56 7,08 0,1530 187,98
2011-03-15 23:51:00 -3,8 8,4 79,4 885,7 273 37,5 21,02 239,25 1468,00 1636,57 7,04 0,1524 187,29
2011-03-15 23:50:00 -3,8 8,4 79,4 886,8 273,1 37,9 21,06 239,25 1467,99 1636,53 7,12 0,1541 189,30
2011-03-15 23:49:00 -3,8 8,4 79,5 887,1 273,2 37,7 21,07 239,25 1467,98 1636,77 7,08 0,1530 188,02
2011-03-15 23:48:00 -3,8 8,4 79,5 888,2 273,4 37,6 21,11 239,25 1467,96 1636,72 7,07 0,1526 187,52
2011-03-15 23:47:00 -3,8 8,4 79,5 887,4 273,7 37,6 21,08 239,25 1467,93 1636,75 7,07 0,1526 187,46
2011-03-15 23:46:00 -3,8 8,4 79,5 887,1 273,5 37,9 21,07 239,25 1467,95 1636,77 7,12 0,1538 188,98
2011-03-15 23:45:00 -3,8 8,4 79,6 886,6 273,4 38,1 21,05 239,25 1467,96 1637,03 7,16 0,1544 189,70
2011-03-15 23:44:00 -3,8 8,4 79,6 886,3 273,4 38 21,04 239,25 1467,96 1637,04 7,14 0,1540 189,19
2011-03-15 23:43:00 -3,7 8,4 79,6 886,3 273,6 37,7 21,04 239,25 1468,18 1637,04 7,08 0,1530 187,98
2011-03-15 23:42:00 -3,7 8,4 79,8 886,3 273,4 38 21,04 239,25 1468,20 1637,54 7,14 0,1537 188,95
2011-03-15 23:41:00 -3,7 8,4 79,9 886 273,5 37,9 21,03 239,25 1468,19 1637,80 7,12 0,1531 188,16
2011-03-15 23:39:00 -3,7 8,4 79,9 886 273,1 37,8 21,03 239,25 1468,23 1637,80 7,10 0,1527 187,71
2011-03-15 23:38:00 -3,7 8,4 79,9 886,6 273,3 38,2 21,05 239,25 1468,21 1637,77 7,18 0,1543 189,69
2011-03-15 23:36:00 -3,7 8,4 79,8 886,8 273,6 37,7 21,06 239,25 1468,18 1637,52 7,08 0,1525 187,45
2011-03-15 23:35:00 -3,8 8,5 79,8 887,4 273,5 37,7 21,08 239,72 1467,95 1637,50 7,09 0,1523 187,09
2011-03-15 23:34:00 -3,8 8,5 79,8 888,2 274 37,9 21,11 239,72 1467,90 1637,47 7,12 0,1531 188,04
2011-03-15 23:33:00 -3,8 8,5 79,8 888,2 273,4 37,8 21,11 239,72 1467,96 1637,47 7,11 0,1528 187,62
2011-03-15 23:32:00 -3,8 8,5 79,8 888,5 273,8 37,9 21,12 239,72 1467,92 1637,46 7,13 0,1531 188,08
2011-03-15 23:31:00 -3,8 8,5 79,8 888,8 273,7 38,1 21,13 239,72 1467,93 1637,44 7,16 0,1540 189,09
2011-03-15 23:30:00 -3,8 8,5 79,8 889,3 273,6 37,7 21,14 239,72 1467,94 1637,42 7,09 0,1524 187,13
2011-03-15 23:29:00 -3,8 8,5 79,7 889,3 273,9 37,8 21,14 239,72 1467,91 1637,18 7,11 0,1530 187,86
2011-03-15 23:28:00 -3,8 8,5 79,7 889,3 273,6 38,3 21,14 239,72 1467,94 1637,18 7,20 0,1550 190,38
2011-03-15 23:27:00 -3,8 8,6 79,7 890,1 274 37,8 21,17 240,18 1467,90 1637,15 7,11 0,1530 187,80
2011-03-15 23:26:00 -3,8 8,5 79,7 891 274 37,9 21,20 239,72 1467,90 1637,11 7,13 0,1534 188,39
2011-03-15 23:25:00 -3,8 8,5 79,7 890,1 273,8 38 21,17 239,72 1467,92 1637,15 7,15 0,1538 188,89
2011-03-15 23:24:00 -3,8 8,6 79,7 890,4 273,8 37,9 21,18 240,18 1467,92 1637,14 7,13 0,1534 188,33
2011-03-15 23:23:00 -3,8 8,6 79,8 890,4 274,1 38,1 21,18 240,18 1467,89 1637,38 7,17 0,1540 189,01
2011-03-15 23:22:00 -3,7 8,7 79,8 891,5 273,9 37,8 21,22 240,65 1468,15 1637,34 7,11 0,1530 187,81
2011-03-15 23:21:00 -3,7 8,7 79,9 892,1 274,1 37,8 21,24 240,65 1468,13 1637,57 7,12 0,1528 187,52
2011-03-15 23:20:00 -3,7 8,7 79,9 892,3 274,4 38,1 21,25 240,65 1468,10 1637,56 7,17 0,1540 188,98
2011-03-15 23:19:00 -3,7 8,7 79,9 893,4 274,5 38,2 21,29 240,65 1468,10 1637,52 7,19 0,1544 189,49
2011-03-15 23:18:00 -3,7 8,8 80 894,3 274,5 38,2 21,32 241,12 1468,10 1637,73 7,20 0,1542 189,17
2011-03-15 23:17:00 -3,7 8,8 80 894,8 274,9 38 21,34 241,12 1468,06 1637,71 7,16 0,1533 188,14
2011-03-15 23:16:00 -3,7 8,7 80 894,3 274,6 38,2 21,32 240,65 1468,09 1637,73 7,20 0,1542 189,22
2011-03-15 23:15:00 -3,7 8,6 80 893,4 274,6 38,3 21,29 240,19 1468,09 1637,76 7,21 0,1545 189,77
2011-03-15 23:14:00 -3,7 8,6 80,1 889,9 274,4 37,8 21,17 240,18 1468,10 1638,14 7,11 0,1523 186,96
2011-03-15 23:13:00 -3,7 8,6 80,2 890,4 274,1 38 21,18 240,18 1468,13 1638,37 7,15 0,1529 187,72
2011-03-15 23:12:00 -3,6 8,6 80,1 890,4 274,1 38,3 21,18 240,18 1468,38 1638,13 7,21 0,1545 189,79
2011-03-15 23:11:00 -3,7 8,6 80,1 891 274,5 38 21,20 240,18 1468,10 1638,10 7,15 0,1531 187,96
2011-03-15 23:10:00 -3,7 8,6 80,1 890,7 274,6 38,2 21,19 240,18 1468,09 1638,11 7,19 0,1539 188,93
2011-03-15 23:09:00 -3,7 8,6 80,1 891 274,1 37,6 21,20 240,18 1468,13 1638,10 7,07 0,1515 186,03
2011-03-15 23:08:00 -3,7 8,6 80,1 890,4 274,1 37,6 21,18 240,18 1468,13 1638,13 7,07 0,1515 186,02
2011-03-15 23:07:00 -3,7 8,6 80,1 891,8 274,4 38,3 21,23 240,19 1468,10 1638,07 7,21 0,1543 189,48
2011-03-15 23:06:00 -3,7 8,6 80 891,2 274,1 38,3 21,21 240,18 1468,13 1637,85 7,21 0,1545 189,78
2011-03-15 23:05:00 -3,7 8,6 80 891,5 274,5 38,1 21,22 240,19 1468,10 1637,84 7,17 0,1537 188,74
2011-03-15 23:04:00 -3,7 8,6 80 891,8 274,3 38,3 21,23 240,19 1468,11 1637,82 7,21 0,1545 189,77
2011-03-15 23:03:00 -3,7 8,6 80 891,8 274,3 37,9 21,23 240,19 1468,11 1637,82 7,13 0,1529 187,79
2011-03-15 23:02:00 -3,7 8,7 79,9 892,3 274,4 37,7 21,25 240,65 1468,10 1637,56 7,10 0,1523 187,00
2011-03-15 23:01:00 -3,7 8,7 79,8 893,2 274,6 37,8 21,28 240,65 1468,09 1637,28 7,12 0,1530 187,76
2011-03-15 23:00:00 -3,7 8,7 79,8 894,3 274,6 37,9 21,32 240,65 1468,09 1637,23 7,14 0,1534 188,29
Figure 42: Cooling capacity calculation sample for 23:00-23:59 on March 15, 2011

63
Measurement and Modelling of Ice Rinks Heat Loads

8.3 Norrtlje and lta ice rinks photo gallery

Figure 43: Flooded evaporator (right) and brine pumps Figure 44: Coolant pumps and condenser (left corner) -
(left) - lta lta

Figure 45: DX evaporator (right), desuperheater (top-left) Figure 46: refrigeration system for outdoor bandy field -
and condenser (bottom-left) - Norrtlje Norrtlje

Figure 47: heat recovery pump for ventilation - lta Figure 48: District heating system - Norrtlje

64
Measurement and Modelling of Ice Rinks Heat Loads

Figure 49: desiccant wheel dehumidification and Figure 50: dehumidification piping (right) and
ventilation heat recovery unit - lta heating/cooling coils (left) in ventilation ducts - Norrtlje

Figure 52: Instruments for over ice temperature and


Figure 51: ClimaCheck central control unit - lta
humidity measurements- lta

Figure 53: ventilation ducts and lighting - lta Figure 54: ice resurfacing machine - lta

65

You might also like