You are on page 1of 3

Dimension

Calculation
Very AutoCAD
critical According
after 2020 to NFPA 82
Waste
Design
Projection

Proposed Incinerator
Minimum Temperature
Must be high temperature to ensure organic destruction. Temperature shall be
measured in conjunction with residence time requirements. Some organic compound
such as halogenated and polynuclear organics are more refractory than others and
therefore require higher minimum temperatures for destruction.

Proposed temperature = 1150oC

Minimum Retention Time


Shall be high enough to ensure that the combustion gasses have sufficient time to mix
the air available and achieve the required temperature to complete the reactions.

Proposed time = 2seconds

Primary Air Injection


The design shall ensure that there is proper primary air distribution to promote good
contact between waste being burned and incoming air.

Proposed = Multi-port injection to maximize distribution


Secondary Air Injection
Shall be used to promote mixing and allow for completion of the combustion process.

Proposed = Must allow high capacity storage for penetration and mixing.

Auxillary Burner Capacity


An auxiliary burner shall be used to pre-heat the system to its operating temperature
before any waste be charged to the incinerator. Can also be used to provide additional
heat, if necessary, to complete the combustion process in the secondary chamber.

Proposed = 100 % of primary and secondary design heat capacity.

You might also like