You are on page 1of 37

Al-Balqa Applied University

Power systems Protection


course

Department of Electrical Power Energy


Dr Audih Engineering
alfaoury 1
Part 6
Overcurrent Protective Relays

Dr Audih alfaoury 2
Overcurrent relays
Is the simplest and cheaper type of protection used for lines,
transformers, generators and motor.

Overcurrent relays Types:-


Based on operating time characteristics, normally defined by the
time vs. current curve (or T-I curve), there are three main types :
Instantaneous
Time-dependent ( Definite time or Inverse time)
Mixed ( Definite time + Inverse time)
1.Instantaneous Overcurrent Relays(50,50N)
These relays operate without time delay, so they are called
instantaneous units (operating time= 0.1 second).
The simplest form of these relays are the magnetic attraction
types, Solid- State, digital and numerical over-current relays .

Instantaneous Overcurrent Relays operate without time delay, ( 0.1s)

Dr Audih alfaoury 3
The pickup current or threshold is adjustable **.
Pickup Current Setting
Taps in the Relay Current Coil.
Air-Gap Adjustment.
Spring Adjustment.
Features of Electromechanical 50 Elements
Suitable for AC and DC Systems.
Operation Time Less Than 3 Cycles

**smallest detectable value of current that will be operate the relay.


Dr Audih alfaoury 4
Instantaneous Curve (50)

Operation zone
of relay

Un operation
zone due 3
cycles

Dr Audih alfaoury 5
2. Time Overcurrent Relays
Operate with a time delay.
Time delay is adjustable.
Pick up current is also adjustable.
There are five different types of time over-current relays
(depends on their time-current characteristic curves) :-
Definite time (DT) or (precise time).
Inverse-time :-
Moderately inverse
Inverse (Normal)
Very inverse
Extremely inverse
2.1 Definite-Time Overcurrent Relays (DT)
The definite-time relay operates with some delay this delay is
adjustable as well as the current threshold.

Time over-current relays operate with a time delay


Dr Audih alfaoury 6
2.2 Inverses-Time
This type of relay have an operating time depending
on the value of the current, generally with an inverse
characteristic,(increasing time decreasing current or
voice versa)
The operation time
of the relay is smaller
as the current gets
larger (small value
of time compared with
current value).
Also have two settings:
1- pick-up current and
2- curve level.
The operation time of is smaller as the current gets larger
Dr Audih alfaoury 7
In early electromechanical relays the curve is set by
means of a dial. Thus, the setting is called the time dial
setting - TDS.
The most common three
types of inverse curves
used are:

o Standard inverse (SI)

o Very inverse (VI)

o Extremely inverse (EI).

IEEE does not specify coefficients in the standard curve equation. Thus, each manufacturers curve is
similar. But different IEC curves are standardized
Dr Audih alfaoury 8
Typical Inverse-Time Overcurrent Relay Elements:
1. Induction disc over-current relay.

2. Shaded-Pole Induction 51 Element

Dr Audih alfaoury 9
Overcurrent Relay Setting
50 Elements: Pickup Setting
51 Elements Pickup setting
Time delay setting
definite time: time setting
inverse time: curve selection
Note: The Selection of an Overcurrent Relay Time Curve According
to American Standard (ANSI)

Time-over-current relays (ANSI 51 relays) have two basic settings:


1- Pickup current and
2- Time delay settings.
The process for determining the time delay setting involves:
(1) Calculation of a time delay value in definite-time over-current
elements.
(2) Selection in inverse-time over-current elements of a time -
current curve from a family of curves.
Instantaneous over current (50) elements have only one setting: the pickup current.
Dr Audih alfaoury 10
2.3 Mixed Curves Over-Current Relays
Mixed curves have all the advantages of the different types of over-
current relays. As the over current elements are built as separate
units, we may implement the over-current protection principles using:
a) a combination of instantaneous and definite-time elements .
b) a combination of instantaneous and inverse-time elements.
c) a combination of instantaneous, definite-time and inverse-time
elements.
d) a combination of definite-time and inverse-time elements(IDMT).

Dr Audih alfaoury 11
Note: This type of characteristic is mainly used in digital relays.

Dr Audih alfaoury 12
2.3.3 Mixed Curves (Inverse-Time +Definite -Time)
IDMT Characteristics
The most commonly used type of relay is the inverse
definite with minimum time lag relay (IDMT) in which
inverse characteristic plus definite time characteristic
are used. The operating time is approximately
inversely proportional to the fault current near pickup
value and become substantially constant slightly above
the pick up value
of the relay.
The characteristic
is shown in Fig.
Wattmetric and
shaded pole relays
of induction type can
be used to obtain
this characteristic.
Dr Audih alfaoury 13
Standard Time and Inverse definite minimum time
(IDMT) Relay Characteristics

In American standard the time over-current relay are


five different types of characteristic curves.
CO-6 Definite minimum,
CO-7 Moderately inverse,
CO-8 Inverse,
CO-9 Very inverse,
CO-11 Extremely inverse,
The time level settings are selected so that all relays
operate in 0.2 sec at 20 times the tap setting.

These time-current characteristics are compared in Figure in next


slides.

Dr Audih alfaoury 14
Extremely inverse
Very inverse

Inverse

Moderately inverse

Definite minimum

Dr Audih alfaoury 15
CO-8 (normal inverse).

Dr Audih alfaoury 16
CO-7 (moderate inverse).

Dr Audih alfaoury 17
Typical time curves for standard British Standard (BS142) and
IEC Standard over-current relay (normal inverse).
Time Multiples Setting TMS= 0.1-1

Dr Audih alfaoury 18
Typical IEC standard over-current relay(normal inverse).TMS=1.

Dr Audih alfaoury 19
Curve Equation

The typical time curves for CO-8 American over-current


relay(normal inverse) characteristics can be approximated by the
following equation.

Dr Audih alfaoury 20
The typical time curves for IEC standard overcurrent
relay(normal inverse) characteristics can be approximated by
the following equation.

Where :
TMS = Time multiplier setting
CTR = Current transformer ratio
PS = Plug setting
IF = Fault primary current

Dr Audih alfaoury 21
(PS) and (TMS) in Over-current Relays
The working principle of an inverse time over-current
relay is shown in figure below.
Plug Setting (PS). The current feeds a coil is controlled with
multiple taps
Time dial setting: Is the time that allows the adjustment
between contacts and the operating time

. The generated magnetic field


makes the disc rotate with a
speed proportional to the
current
The braking magnet lessens
the rotating speed and acts as
an opposing force to the
rotation. Varying the
magnetization, different
tripping curves can be
achieved.
Dr Audih alfaoury 22
Example:
Calculate the plug setting and time multiplier setting for an IDMTL
relay on the following network so that it will trip in 2.4 s .
(see Figure 1).The relay characteristic is shown in Figure 2.The C.T.
setting is 100/5 A and the fault current is 1000 A.

Figure 1

Dr Audih alfaoury 23
Dr Audih alfaoury 24
Answer:
Fault current = 1000 A
CT ratio = 100/5 A
The current into relay under fault conditions,
IF 5
I op ( relay ) 1000 50A
CTR 100
Choose plug setting100% this is 5 A Therefore, current into relay as
a multiple of plug setting during fault is 50 / 5 = 10
We require the relay to operate after 2.4 s as soon as this much
current starts flowing in the circuit. Referring to characteristic curves
below, read time multiplier setting where 10 times plug setting
current and 2.4 s cross, which is about 0.8. Accordingly,
The relay settings is: PS=5 A (100%) and TMS=0.8.
Alternatively, if the current plug setting is chosen as 125% (6.25
A), the fault current through the relay will be 50/6.25 = 8 A. The
graph shows that eight times plug setting to operate in 2.4 s, the time
multiplier should be about 0.7.
This technique is fine and give exactly required of the TM curve.
Dr Audih alfaoury 25
If the desired setting falls between the curves, and not easy to
estimate the intermediate setting accurately as the scales of the
graph are log/log. Then the following procedure is recommended.
From the scale below go to the multiple of plug setting current and
read the second value corresponding to the 1.0 time multiplier
curve. Then divide the desired time setting by this figure. This will
give the exact time multiplier setting:
Example if the second value at 10 times = 3 then for ( at 8 times it
is about 3.33 or 3.4) Desired setting = 2.4.
8
Desired setting 2.4
3.4

3.4

Dr Audih alfaoury 26
***Note the PS is given as 200% and we need to find the PSM
Dr Audih alfaoury 27
Example 2:
Determine the time of operation of a relay of rating 5A, 2.2 sec
IDMTL and having a relay setting of 125%, TMS=0.6. It is
connected to a supply circuit through a C.T 400/5 ratio. The fault
current is 4000A.
Solution:
The operating current of the relay: 51.25=6.25A
Ip=IF=4000 A

From the curve, the operating time for PSM=8 is 3.2 sec (TMS=1)
( This means that the current in secondary CT in case of fault and if we set the PSM
to 8 then the relay will operate at 6.25 A and 3.2 second )

If we select TMS=0.6 then the operation time is


0.6(TMS )
3.2 1.92sec.
1.0(TMS )
Dr Audih alfaoury 28
or From log to log curve (for
TMS=0.6)

1.92 sec

Or from Figure scale figure (for TMS=1)

Dr Audih alfaoury 29
Example 3:
If the rated current (pick up current) of a relay is 3A, and the time
dial setting(TDS) is 1.
(a) How long(time) does it take the relay to trip if the supply C.T is
rated at 400:5 A and the fault current is 480A? The type of the
OC relay is CO-8.
(b) Solve using the standard curve equation and compare the
results.

Solution:

Dr Audih alfaoury 30
b) Alternative method using curve
equation

CO-8 Characteristics

Note:
TDS(time dial setting)=TD(time delay)

Dr Audih alfaoury 31
Example 4:
For the relay R1 in the system shown determine the current tap
setting CTD. If the maximum three-phase fault current is 2400A and
the TDS=2.0.
Find the operating time if the relay type is CO-8 (inverse type).

Dr Audih alfaoury 32
Solution:
Load current at the busbar1

Since the current tap setting (CTS) of CO-8 relay available are
4,5,6,7,8,10 and 12A
Hence we choose CTS=4 (this is relay operation current in case of
fault)
Fault current If=2400 A

Dr Audih alfaoury 33
Dr Audih alfaoury 34
Dr Audih alfaoury 35
Dr Audih alfaoury 36
Dr Audih alfaoury 37

You might also like