You are on page 1of 48

Hexa Series

Conzerv EM64xxH and EasyLogic™ PM1130H


Launch Training

Roopa Jalakantan & Shreesha Pandith


Power Solutions Marketing India

Confidential Property of Schneider Electric


Power Monitoring offer positioning

Cost Performance Partner End User IM400


IM10/20
Network Performance IM9

Asset Performance ION8800

ION8650
CM4000T
ION7x50
PM8000
EM6400NG PM2000 /
PM5000
Hexa

Basic Metering Advanced Metering Utility Metering Insulation


Monitoring
High Volume, Standard Product Configured to order Utility Segment Insulation Monitoring
Playbook #1 Critical Power Grid PQ & Revenue Metering IT Systems,
Playbook #3 Playbook #3 Playbook #3

Gateways & Energy Servers


Confidential Property of Schneider Electric
Com’X Link150 Power Solutions 2
Power Monitoring Hardware

Advanced power quality analyzers/ high accuracy COM’X 510


revenue, transient detection, ABT application, Energy Management & Dashboard in a box, Data
embedded web pages, Modbus mastering, GPS time logger via cloud, Remote data push over hosted
sync, SOE, Expandable IO, IEC PQ Compliance platform, Connect isolated sites via GPRS/ WIFI,
Onboard DI/AI
Advanced

ION7X50 ION8650 CM4XXX


Patented Disturbance detection,
Intermediate PQ , on board memory,
alarms, waveform capture, sags & swells,
smart demand controller. EGX 300
Intermediate Integrated gateway server, Any Modbus
EM 72XX serial device to Ethernet gateway, Local
PM 8000 PM5560
Data logging and visualization.
Harmonics Monitoring,
Predictive Demand monitoring,
Multitariff, WAGES integration
Basic
EM6400NG PM2XXX PM53XX/51XX iEM3000

Hexa LINK 150


Energy and Power Modbus to Ethernet
Monitoring, VAF- protocol convertion,
PF Entry dual ethernet

EM 6436 EM 6433 EM 6438/36Dual EM 6459 EM1XXX DM 6XXX DM3XXX/DM1XXX

BCPM VIGILOHM
Rack monitoring - Solid/Spilt Insulation monitoring
core, Maximize uptime Devices, Fault detection/ locators
Confidential Property of Schneider Electric |
Strategic Intent for “Hexa Series”

Ageing Platform [>15 years]

Simplification of offers –
Existing 38 references

Confidential Property of Schneider Electric | Page 4


Why Hexa?

Confidential Property of Schneider Electric | Page 5


High Sampling Rate 1 2 3 4 5 6

32 Samples /
Cycle

Overview
•Existing Series of EM64xx series sampling rate was 20 Samples / Cycle i.e 1000 records per sec
•Existing Series of Hexa has been upgraded to 32 Samples / Cycle i.e 1600 per sec
•Critical for precision electrical Monitoring – Most of the Local Competition don’t the sampling rate

ConfidentialProperty
Confidential PropertyofofSchneider
SchneiderElectric
Electric 6
Onsite Calibration 1 2 3 4 5 6

Verification

Calibration
LED

Overview
Capture LED pulse through Optical adapter from RSS meter to determine the % error
LED pulse weight (meter constant) configurable from 1 to 9999000 pulse/ k_h (Wh or VAh or VARh)

ConfidentialProperty
Confidential PropertyofofSchneider
SchneiderElectric
Electric 7
Dual Sourcing Upgraded 1 2 3 4 5 6

Dual Source +
THD% + Relay

Overview
Relay can be operated based on the set limits assigned for V L-L, V L-N, Amps, Hz, PF, Instantaneous power (W, VA,
VAR), demand parameter (W, VA, VAR)
Can be configured for 4 alarms at a time

ConfidentialProperty
Confidential PropertyofofSchneider
SchneiderElectric
Electric 8
Check what matters the 1 2 3 4 5 6

Most

Configurable
Favorite Page

Overview
Number and type of parameters can be chosen and arranged in Favourite page according to the user’s requirement

ConfidentialProperty
Confidential PropertyofofSchneider
SchneiderElectric
Electric 9
Compact Size 1 2 3 4 5 6

Reduced Depth –
49mm*

Overview
The depth of the existing range of meters was 82mm
The depth of the new range of meters is 49mm except for PM1130H [52mm]

ConfidentialProperty
Confidential PropertyofofSchneider
SchneiderElectric
Electric 10
Green Premium Product 1 2 3 4 5 6

RoHS / ReACH/
EOL / PEP

Overview
Over 75 % of Schneider Electric products have been awarded the Green Premium ecolabel .

ConfidentialProperty
Confidential PropertyofofSchneider
SchneiderElectric
Electric 11
Substitution Plan
38 DIFFERENT REFERENCES CURTAIL DOWN TO 12 REFERENCES

Confidential Property of Schneider Electric | Page 12


Substitution 38 CR’s 11 CR’s

30002000 EM6433 0.5 RS


30002031 EM6433 1.0 30002278 EM6436dual 0.5 RS
30002016 EM6433 1.0 RS EM6433H Cl 1.0 RS-485 30002306 EM6436dual 1.0
30002926 EM6433 1A0.2 RS EM6433H Cl 0.5 RS-485 30002277 EM6436dual 1.0 RS PM1130H Cl 0.5 RS-485
30002336 EM6433 1A0.5S RS 30002438 EM6436dual DM 0.5 RS 5 com ref to 1 ref
30002436 EM6433 5A 0.5S RS 7 com ref to 2 ref 30002351 EM6436dual DM 1.0 RS
30002927 EM6433 5A0.2 RS
30002269 EM6438 0.5 RS EM6438H Cl 1.0 RS-485
30002893 EM6430 Cl1.0
30002026 EM6438 1.0 RS EM6438H Cl 0.5 RS-485
30002892 EM6430 Cl1.0 RS485
30002437 EM6438DM 0.5 RS 4 com ref to 2 ref
30002201 EM6436 0.5
30002305 EM6438DM 1.0 RS
30002015 EM6436 0.5 RS
30002220 EM6459 0.5
30002295 EM6436RPM 1.0
30002221 EM6459 0.5 RS
30001994 EM6436 1.0 EM6436H Cl 1.0 30002008 EM6459 1.0 EM6459H Cl 1.0
30001999 EM6436 1.0 RS EM6436H Cl 1.0 RS-485 30001804 EM6459 1.0 RS EM6459H Cl 1.0 RS-485
30002930 EM6436 1A0.2 EM6436H Cl 0.5 RS-485 30002934 EM6459 1A 0.2 RS EM6459H Cl 0.5 RS-485
30002931 EM6436 1A0.2 RS 30002935 EM6459 1A0.2
30002203 EM6436 1A0.5S RS 14 com ref to 3 ref 30002936 EM6459 5A 0.2 8 com ref to 3 ref
30002932 EM6436 5A0.2 30002224 EM6459 5A0.5S
30002933 EM6436 5A0.2 RS
30002205 EM6436 5A0.5S RS
30002204 EM6436 Cl0.5S, Iin:5A
PRODUCT FEATURES

Confidential Property of Schneider Electric | Page 14


Easylogic PM1130H – Multisource Restricted MFM

● Key features

● Class Accuracy 0.5


● VAF + PF+ Power & Energy [ Any One] + Demand [ Anyone]
● Sampling Rate of 32 Samples/Cycle
● Multi sourcing [EB / DG]
● THD % for Voltage & Current
● Relay Contact for Multi set limits [ Any 4 points at a time]
● Configurable Favorite Page
● Calibration and Communication LED
● Analog Load Bar
● Data Integrity : Communication Disable on the front panel of the Meter
● Application : Any kind of Industry – Tenant Billing
Confidential Property of Schneider Electric ● Communication Variant only – SE COM DATA MODULE 15
Conzerv EM6438H – Dual Source Meter

● Key features

● Class Accuracy 1.0 / 0.5


● PF+ Power [Anyone] + Energy [ Any One]
● Dual Source Energy
● Sampling Rate of 32 Samples/Cycle
● Calibration and Communication LED
● Analog Load Bar
● Data Integrity : Communication Disable on the front panel of the Meter
● Application : Any kind of Industry – Tenant Billing
● Communication Variant only – SE COM DATA MODULE

Confidential Property of Schneider Electric 16


Conzerv EM6436H – Load Manager

● Key features

● Class Accuracy 1.0 / 0.5


● VAF + PF+ Power [Anyone] + Energy [ Any One]
● Sampling Rate of 32 Samples/Cycle
● Configurable Favorite Page
● Calibration and Communication LED
● Analog Load Bar
● Data Integrity : Communication Disable on the front panel of the Meter
● Application : Any kind of Industry – Tenant Billing
● Communication + Non Com Variant - SE COM DATA MODULE

Confidential Property of Schneider Electric 17


Conzerv EM6433H – Energy Meter

● Key features

● Class Accuracy 1.0 / 0.5


● Amps+ PF+ Power [Anyone] + Energy [ Any One]
● Sampling Rate of 32 Samples/Cycle
● Calibration and Communication LED
● Analog Load Bar
● Data Integrity : Communication Disable on the front panel of the Meter
● Application : Any kind of Industry – Tenant Billing
● Communication Variant only – SE COM DATA MODULE

Confidential Property of Schneider Electric 18


Conzerv EM6459H – VAF Meter

● Key features

● Class Accuracy 1.0 / 0.5


● VAF + PF
● Sampling Rate of 32 Samples/Cycle
● Communication LED
● Data Integrity : Communication Disable on the front panel of the Meter
● Application : Any kind of Industry – Tenant Billing
● Communication + Non Com Variant - SE COM DATA MODULE

Confidential Property of Schneider Electric 19


7.1. Product feature set matrix
Parameters EM6459H EM6436H EM6433H EM6438H PM1130H
Old model ref EM6459 EM6436 EM6433 EM6438 EM6436 Dual
EM6430, EM6436RPM
Communication Non Com(NC)/ RS-485 Non Com(NC)/ RS-485 RS-485 RS-485 RS-485
Class of accuracy 1.0 (NC/ RS-485), 1.0 (NC/ RS-485), 1.0 (RS-485) 1.0 (RS-485), 0.5 (RS-485)
0.5 (RS-485) 0.5 (RS-485) 0.5 (RS-485) 0.5 (RS-485)
VAF √ √ √
PF √ √ √ √ √
W, VA, VAR One Power One Power One Power One Power
Wh, VAh, VARh One Energy One Energy One Energy One Energy
OnHr, RunHr,Int OnHrs, Int OnHr/ RunHr/ Int OnHr/ RunHr/ Int OnHr/ RunHr/ Int OnHr/ RunHr/ Int
Demand √ (one Pwr)
THD%, V & I, ph √
V & A % Un Bal √ √ √ (Amps) √
% Load √ √ √ √
Ph Angle/ RPM √ √ RPM √ RPM
Alarm/ Relay √ (4 para)
Common Features
Energy Accuracy as per IEC
Analog Load Bar
62053-21/22

Life Time Counter – Meter On , Configurable Password – 0000


Power Interruption to 9999

Green Premium EcoMark-


Universal Operating range
RoHS, ReaCH, EP, EoL

Confidential Property of Schneider Electric | Page 21


Key Differentiating Features
Suppression Current - 5 mA to 13 Different Wiring
99 mA Configuration

Relay Output – Demand Configurable Password – 0000


Control to 9999

Retro Fit Block Protection / Tamper Cover

Confidential Property of Schneider Electric | Page 22


7.3. EM6459H, VAF PF meters

Applications

Conzerv range, EM64xxH series


EM6459H METSEEM6459HCL10NC EM6459H NC CL 1.0

EM6459H METSEEM6459HCL10RS EM6459H RS CL 1.0

EM6459H METSEEM6459HCL05RS EM6459H RS CL 0.5


7.3. Feature comparison
EM6459 vs EM6459H
Features EM6459 EM6459H
Life time counter Meter ON Hrs, power outage Meter ON Hrs, power outage

Display type 8 segment large 14mm LED, Alpha numeric 8 segment large 14.2 mm LED, Alpha numeric

Analog load bar 12 LED’s on front panel 12 LED’s on front panel

IP Degree of protection IP51 front & IP 30 rear IP51 front & IP30 rear, upgrade to IP54 front
with optional gasket
Suppression current Not available Selectable from 5 mA to 99 mA

Heart beat LED Not available Available

Password Default 0000 Selectable from 0000 to 9999

RPM Available Available

Confidential Property of Schneider Electric 24


7.3. Feature comparison
EM6459 vs EM6459H
Features EM6459 EM6459H
Accuracy Class: 1.0/ 0.5 Class: 1.0/ 0.5

Sampling rate 20 32

UI/ HMI navigation LED panel, 5 panel buttons LED panel, 4 panel buttons

Power Factor True PF True PF (accurate due to high sampling rate)

Current range 100mA to 6A (Inom:5A or 1A) 10mA to 6A (Inom:5A or 1A)

Form factor (H*W*D) 96*96*80mm 96*96*49mm

Protection cover Available Available

Control Power 44-277V DC, AC 50/60Hz 44-277V DC, AC 50/60Hz

Voltage range 80 to 480V L-L AC 50/60Hz 80 to 480V L-L AC 50/60Hz CAT III

Communication 2-wire RS-485 & Non-com type (legacy com 2-wire RS-485 (SE common data module +
data module) legacy com data module)
Confidential Property of Schneider Electric 25
7.3. Parameters/ diag pages

Parameters measured No of para Diagnostic information


Voltage, L-L & L-N, Avg & per-ph 8 All LED test
Current, Avg & per-phase 4 Sl Number
Hz 1 Model reference
Power Factor 4 OS number
Ampere Deg (btw V to A, per-ph) 3 RS number
% Load, per-phase 3 Error code
Amps & Volts , % un-balance, 3 ph 2 Communication status (DM6200H)
RPM 1
Meter ID
Neutral current, derived 1 Baud rate
Parity
Ground current, derived 1
Meter ON Hrs 1
Power Outage 1
Total number of parameters 29
7.4. EM6433H Energy meters

Applications

Conzerv range, EM6433H


Model ref Logistics/ Commercial ref Short description
EM6433H METSEEM6433HCL10RS EM6433H RS CL 1.0
EM6433H METSEEM6433HCL05RS EM6433H RS CL 0.5
7.4. Feature comparison
EM6433 vs EM6433H
Features EM6433 EM6433H
Energy accuracy Class: 1.0/ 0.5 Class: 1.0/ 0.5 (0.5 for i4i) tested as per IEC
62053-21/ 22 for energy test clause
Sampling rate 20 32

UI/ HMI navigation LED panel, 5 panel buttons LED panel, 4 panel buttons

Current range 100mA to 6A (Inom:5A or 1A) 10mA to 6A (Inom:5A or 1A), additional error
b/w 10mA to 150mA
Form factor (H*W*D) 96*96*80mm 96*96*493mm

Protection cover Available Available

Control Power 44-277V DC, AC 50/60Hz 44-277V DC, AC 50/60Hz

Communication 2-wire RS-485 & Non-com type (legacy com 2-wire RS-485 (SE common data module +
data module) legacy com data module)
IP Degree of protection IP51 front & IP 30 rear IP51 front & IP30 rear, upgrade to IP54 front
Confidential Property of Schneider Electric with optional gasket 28
7.4. Feature comparison
EM6433 vs EM6433H
Features EM6433 EM6433H
Power parameter Any one (W or VA or VAR, selected through Any one (W or VA or VAR, selected through
set-up) set-up)
Energy parameter Any one (Wh or VAh or VARh, depending on Any one (Wh or VAh or VARh, depending on
selected power parameter, unidirectional) selected power parameter, unidirectional)
Energy resolution 4+4 5+3 digits, takes longer time to overflow

Life time counter Load Run Hrs, Meter ON Hrs, power outage Load Run Hrs, Meter ON Hrs, power outage

Display type 8 segment large 14.2 mm LED, Alpha numeric 8 segment large 14.2 mm LED, Alpha numeric

Analog load bar 12 LED’s on front panel 12 LED’s on front panel

Suppression current Not available Selectable from 5 mA to 99 mA

Pulse LED & Heart beat LED Not available Available

Password Default 0000 Selectable from 0000 to 9999


Confidential Property of Schneider Electric 29
7.4. Parameters/ diag pages

Parameters measured No of para Diagnostic information


Current, Avg & per-phase 4 All LED test
% Load, per-phase 3 Sl Number
Amps, % un-balance among 3 ph 1 Model reference
Load Run Hrs 1 OS number
Neutral current, derived 1 RS number
Ground current, derived 1 Error code
Meter ON Hrs 1 Communication status (DM6200H)
Power Outage 1
Meter ID
Total number of parameters 13 Baud rate
Parity
7.5. EM6436H Load manager

Applications

Conzerv range, EM6436H


Model ref Logistics/ Commercial ref Short description
EM6436H METSEEM6436HCL10NC EM6436H NC CL 1.0
EM6436H METSEEM6436HCL10RS EM6436H RS CL 1.0
EM6436H METSEEM6436HCL05RS EM6436H RS CL 0.5
7.5. Feature comparison
EM6436 vs EM6436H
Features EM6436 EM6436H
Energy accuracy Class: 1.0/ 0.5 Class: 1.0/ 0.5, tested as per IEC 62053-21/
22 for energy test clause
Sampling rate 20 32

UI/ HMI navigation LED panel, 5 panel buttons LED panel, 4 panel buttons

Power Factor True PF True PF (accurate due to high sampling rate)

Current range 100mA to 6A (Inom:5A or 1A) 10mA to 6A (Inom:5A or 1A), additional error
b/w 10mA to 150mA
Form factor (H*W*D) 96*96*80mm 96*96*49mm

Protection cover Available Available

Control Power 44-277V DC, AC 50/60Hz 44-277V DC, AC 50/60Hz

Voltage range 80 to 480V L-L AC 50/60Hz 80 to 480V L-L AC 50/60Hz CAT III

Communication 2-wire RS-485 & Non-com type (legacy com 2-wire RS-485 (SE common data module +
Confidential Property of Schneider Electric data module) legacy com data module) 32

RPM Not available Available


7.5. Feature comparison
EM6436 vs EM6436H
Features EM6436 EM6436H
Power parameters Any one (W or VA or VAR, selected through Any one (W or VA or VAR, selected through
set-up) set-up)
Energy parameter Any one (Wh or VAh or VARh, depending on Any one (Wh or VAh or VARh, depending on
selected power parameter, unidirectional) selected power parameter, unidirectional)
Energy resolution 4+4 5+3 digits, takes longer time to overflow

Life time counter Load Run Hrs, Meter ON Hrs, power outage Load Run Hrs, Meter ON Hrs, power outage

Display type 8 segment large 14mm LED, Alpha numeric 8 segment large 14.2 mm LED, Alpha numeric

Analog load bar 12 LED’s on front panel 12 LED’s on front panel

Suppression current Not available Selectable from 5 mA to 99 mA

Favorite page Not available Users can pick and place the parameters in
one page
Pulse LED & Heart beat LED Not available Available

Password Default 0000 Selectable from 0000 to 9999

IP degree of protection
Confidential Property of Schneider Electric
IP51 front & IP 30 rear IP51 front & IP30 rear, upgrade to IP54 front 33
with optional gasket
7.5. Parameters/ diag pages

Parameters measured No of para Parameters measured/ displayed No of para


Voltage, L-L & L-N, Avg & per-ph 8 Power, Total & per-phase (W, VA, VAR) 4
(one power vector at a time)
Current, Avg & per-phase 4
Energy (Wh, VAh,VARh) (one energy) 1
Hz 1
Power Factor 4 Load Run Hrs 1

Ampere Deg (btw V to A, per-ph) 3 Old register (Wh, Run Hrs) 2

% Load, per-phase 3 Total number of parameters 8

Amps & Volts, % un-balance, 3 ph 2


RPM 1 Diagnostic information
Neutral current, derived 1 All LED test, Sl number, Model reference,
Ground current, derived 1 OS & RS number, Error code,
Communication status, Meter ID, Baud
Meter ON Hrs 1 rate, Parity
Power Outage 1
Total number of parameters 30
7.6. EM6438H Dual source meter

Applications Dual source/ Multi-source/ ON Load-Off Load/ Run-


Idle load condition

Conzerv range, EM6438H


Model ref Logistics/ Commercial ref Short description
EM6438H METSEEM6438HCL10RS EM6438H RS CL 1.0
EM6438H METSEEM6438HCL05RS EM6438H RS CL 0.5
7.6. EM6438H Features explained

 Any one power vector can be selected through set up


mode for measurement and display
• W or VA or VAR of Source 1 or 2 (instantaneous)
• Wh or VAh or VARh of Source 1 + Source 2 (dual registers
for energy parameters)
 Digital input: 2 pin smart sensor, 18 to 60V DC or 80 to
300V AC. Presence of voltage state across sensor
triggers the activation of alternate source register in
the meter
 Dual energy registers:- Can be used for – alternate
source or multi-tariff or load vs Idle running
conditions
7.6. Feature comparison
EM6438 vs EM6438H
Features EM6438 EM6438H
Energy accuracy Class: 1.0/ 0.5 Class: 1.0/ 0.5 (0.5 for i4i) tested as per IEC
62053-21/ 22 for energy test clause
Sampling rate 20 32

UI/ HMI navigation LED panel, 5 panel buttons LED panel, 4 panel buttons

Current range 100mA to 6A (Inom:5A or 1A) 10mA to 6A (Inom:5A or 1A)

Sealing provision NA Available

Form factor (H*W*D) 96*96*80mm 96*96*49mm

Sealing provision Not available Available

Control Power 44-277V DC, AC 50/60Hz 44-277V DC, AC 50/60Hz

Voltage range 80 to 480V L-L AC 50/60Hz 80 to 480V L-L AC 50/60Hz CAT III

Communication 2-wire RS-485 & Non-com type 2-wire RS-485 (SE common data module)

IP Degree of protection IP51 front & IP 30 rear IP51 front & IP30 rear, upgrade to IP54 front
Confidential Property of Schneider Electric
with optional gasket 37
7.6. Feature comparison
EM6438 vs EM6438H
Features EM6438 EM6438H
Power parameters Any one (W or VA or VAR, selected through Any one (W or VA or VAR, selected through
set-up) set-up)
Energy parameter Any one (Wh or VAh or VARh, depending on Any one (Wh or VAh or VARh, depending on
selected power parameter, unidirectional) selected power parameter, unidirectional)
Energy resolution 4+4 5+3 digits, takes longer time to overflow
Life time counter Load Run Hrs, Meter ON Hrs, power outage Load Run Hrs, Meter ON Hrs, power outage
Display type 8 segment large 14mm LED, Alpha numeric 8 segment large 14.2 mm LED, Alpha numeric
Analog load bar 12 LED’s on front panel 12 LED’s on front panel
Suppression current Not available Selectable from 5 mA to 99 mA
Pulse LED & Heart beat LED Not available Available
Password Default 0000 Selectable from 0000 to 9999
RPM Available Available

Confidential Property of Schneider Electric 38


7.6. Parameters/ diag pages

Parameters measured No of para Diagnostic information


Power, Total & per-phase (W, VA, 4 All LED test, Sl number, Model reference,
VAR) (one power vector at a time) OS & RS number, Error code,
Communication status, Meter ID, Baud
Source 1 & 2 Energy and total (Wh, 3
rate, Parity
VAh,VARh)
Load Run Hrs (Source 1 & 2 and 3
total)
Old register (Source 1 & 2:- Wh, 6
Run Hrs and total)
Power Factor 4
Meter ON Hrs 1
Power Outage 1
Total number of parameters 22
7.7. PM1130 Dual source meter with relay

Applications Dual source/ Multi-source/ ON Load-


Off Load/ Run-Idle load condition

EasyLogic range, PM1130H


Model ref Logistics/ Commercial ref Short description
PM1130H METSEPM1130HCL05RS PM1130H RS CL 0.5
7.7. PM1130H Features explained

 Any one power vector can be selected through set up


mode for measurement and display
• W or VA or VAR of Source 1 or 2 (instantaneous)
• Wh or VAh or VARh of Source 1 + Source 2 (dual registers
for energy parameters)
 Dual energy registers:- Can be used for – alternate
source or multi-tariff or load vs Idle running
conditions
 Digital input: 2 pin smart sensor, 18 to 60V DC or 80 to
300V AC. Presence of voltage state across sensor
triggers the activation of alternate source register in
the meter
 Relay output: Form A relay, 2A max w/ 24V DC or 300V
L-N AC. Can be configured for 4 alarms from V L-N,
V L-L, A, PF, F, VA, W, VAR, Demand -W/ VA/ VAR
parameters
7.7. Feature comparison
EM6436 dual vs PM1130H
Features EM6436 Dual PM1130H
Energy accuracy Class: 1.0/ 0.5 Class: 0.5 tested as per IEC 62053- 22 for
energy test clause
Sampling rate 20 32
UI/ HMI navigation LED panel, 5 panel buttons LED panel, 4 panel buttons
Harmonics NA THD% for V & I, per-ph, more accurate due to
high sampling rate
Power Factor True PF True PF (accurate due to high sampling rate)
Current range 100mA to 6A (Inom:5A or 1A) 10mA to 6A (Inom:5A or 1A), additional error
b/w 10mA to 150mA
Mechanical Relay NA Max 4 parameters from the combo of 14 para
Sealing provision NA Available
Form factor (H*W*D) 96*96*80mm 96*96*52mm
Control Power 44-277V DC, AC 50/60Hz 44-277V DC, AC 50/60Hz
Voltage range 80 to 480V L-L AC 50/60Hz 80 to 480V L-L AC 50/60Hz CAT III
Communication
Confidential Property of Schneider Electric 2-wire RS-485 & Non-com type (legacy com 2-wire RS-485 (SE common data module + 42
data module) legacy com data module)
7.7. Feature comparison
EM6436 dual vs PM1130H
Features EM6436 Dual PM1130H
Power parameters Any one (W or VA or VAR, selected through Any one (W or VA or VAR, selected through
set-up) set-up)
Energy parameter Any one (Wh or VAh or VARh, depending on Any one (Wh or VAh or VARh, depending on
selected power parameter, unidirectional) selected power parameter, unidirectional)
Energy resolution 4+4 5+3 digits, takes longer time to overflow
Life time counter Load Run Hrs, Meter ON Hrs, power outage Load Run Hrs, Meter ON Hrs, power outage
Demand parameters W, VA or VAR (any one) W, VA, VAR (any one), accurate
Display type 8 segment large 14.2 mm LED, Alpha numeric 8 segment large 14.2 mm LED, Alpha numeric
Analog load bar 12 LED’s on front panel 12 LED’s on front panel
Suppression current Not available Selectable from 5 mA to 99 mA
Favorite page Not available Users can pick and place the parameters in
one page
Pulse LED & Heart beat LED Not available Available
Password Default 0000 Selectable from 0000 to 9999
Confidential Property of Schneider Electric 43
RPM Available Available
7.7. Parameters/ diag pages

Parameters measured No of para Parameters measured/ displayed No of para


Voltage, L-L & L-N, Avg & per-ph 8 Power, Total & per-phase (W, VA, VAR) 4
Current, Avg & per-phase 4 Source 1 & 2 Energy and total (Wh, 3
VAh,VARh)
Hz 1
Demand (Last, Rising, Time remaining, 5
Power Factor 4
Max DM, MD occurrence)
Ampere Deg (btw V to A, per-ph) 3
Load Run Hrs (Source 1 & 2 and total) 3
% Load, per-phase 3
V THD%, A THD%, per-phase 6
Amps & Volts, % un-balance, 3 ph 2
Relay status 1
RPM 1
Old register (Source 1 & 2:- Wh, Run 6
Neutral current, derived 1 Hrs and total)
Ground current, derived 1 Total number of parameters 28
Meter ON Hrs 1 Diagnostic information
Power Outage 1 All LED test, Sl number, Model reference, OS & RS number,
Total number of parameters 30 Error code, Communication status, Meter ID, Baud rate, Parity
What’s new in PM2230????

Confidential Property of Schneider Electric | Page 45


Winning Specifications for PM2230.

Multi Sourcing (EB / DG)

12am Snapshot – 04 parameters

Variable Rate Counters : KgCO2

Calibration and COM LED

Onboard Memory , COM Disable

Confidential Property of Schneider Electric | Page 46


Now PM2230 can be used for Multi Sourcing(EB/DG)
GenSet

AC-DC Converter

• Voltage Signal (continuous) from GenSet (battery)


DC V:18.5 • GenSet ON Status: 18.5V to 36V: Tariff register #2
to 36V
(GenSet)
DI-1 • GenSet OFF Status: 0V to 4V: Tariff register #1
(Utility)

Battery Digital Tariff #


Volts Input

Loads
status
Utility OFF (0-4V) 0 #1
GenSet ON (18.5-36V) 1 #2

Utility Source
Schneider Electric - Division - Name – Date 47

You might also like