You are on page 1of 2

R

SERIES...
IH153ES - IR EMBER DETECTOR

fladet IH-153ES Infra Red Ember Detector with IP-67

Protection is used to detect smoldering moving embers. The

detector makes use of Infra Red sensitive photoelectric sensor

for detection of ember (as in smoldering coal). It has a spectral

filter of 3 - 14µm, which is insensitive to visible light.

The IR Ember Detector can reliably and quickly detect weak

Infra Red radiations emitted from ember due to smoldering

fragment of wood or coal. IR Ember Detector is an efficient

alternative to any flame detector which has the limitation of

low sensitivity to ember.


IH 153ES - IR EMBER DETECTOR
It can be connected to any standard conventional Fire Alarm

Control Panel or to any addressable Fire Alarm Control Panel.


ADVANTAGES:
It can also be connected to Annunciator/PLC/DCS through the í Rugged model suitable to be used in challenging

potential free ‘NO/NC’ contacts provided. In-built RED LED is environment with weather and dust proof protection.
í High Sensitivity even in mist & Fog
also provided for visual indication in case of fire/ember
í 4 Range of Sensitivity Selection Provision
detection. Normal working of the detector can be ensured by í Easy to Install and operate

flickering of GREEN LED indication. The detector also has an í High speed Response
í Free from False Alarms
in-built Air Purging provision to clean the detector eye by
í Visual Indication for Alarm/Normal condition
using instrument air. í Low Maintenance Cost

APPLICATIONS: í Stand Alone Air Purging or In-built Air Purging option

í Highly Recommended to use in coal conveyors to detect


Smoldering coal or Ember. INSTALLATION CONSIDERATION :
í Material conveyors where fire initially starts with the
ember. fladet IH-153ES shall be installed such that the
í Environment that are unsuitable for other type of detectors
view path of the detector is unobstructed. Existence of IR
to detect moving ember or ember with flame.
radiation sources like direct sunlight, hot bodies may
DETECTOR SENSITIVITY : affect the performance of the detector. For conveyor
IH153ES detect 100 sq. cm. glowing ember at application (like coal conveyor) the detector should be
o
distance of 1 to 3 metre in 90 Cone angle and Straight Line at mounted on the Conveyor Hood or Gantry structure
normal Sensitivity. The Sensitivity is also adjustable as per
looking down at the material being transported.
requirements
Filter Sensitivity 100 %

80

60

40
20

0
2.5 3 4 5 6 7 8 9 10 15 Micrometers

ANGULAR SENSITIVITY
TECHNICAL SPECIFICATION - PART NO : IH153ES
01. BRAND NA ME fladet series.. MAINTENANCE & INSPECTION:
02 . MANUFA CTURER AGNI CONTROLS, CHENNAI

03. QUIESCENT CURRENT < 40mA

04. ALARM CURRENT < 120mA


To assure maximum detector sensitivity, keep the
05. RELA Y CONTACT
RATING 5A at 30VDC, 1A at 250VAC surface of the detector (Detector eye) free from
06. CABLE ENTRY 3/4" ET/ M20 X 1.5 - 3 Nos.
07. PROTECT ION CLASS IP 67 contaminations at all time. Periodically test the
08. SENSING ELEMENT INFRA RED

09. INDICA TION


NORMAL-FLICKERING GREEN LED sensitivity of the detector using a controlled ember.
FIRE - RED LED
10. OPERATING
T EMPERATURE -20Deg.C to +60Deg,C fladet IH-153ES offers an additional provision for
11. FINISH ENCLOS URE - HAMMER TONE GRA Y
12. SUPPLY 24VDC±20%
connecting to pneumatic air purging system to clean the
13. OUTPUT 1. ONE SET OF 'NO-COM-NC' CONTA CT FOR FIRE + ONE
SET OF DUPLICATE 'NO -COM- NC' CONTA CT. surface of the detector.
2. ONE SET OF 'NO-COM-NC' CONTA CT FOR FA ULT +
ONE SET OF DUPLICA TE 'NO -COM- NC' CONTACT.
ORDERING INFO:
3. ZONE DETECTOR LINE TO CONNECT DIRECTLY
R
STANDA RD CONVENTIONL FIRE ALARM PANEL
14. MAT ERIAL CA ST ALUMINIUM LM6

15.FASTENERS SS 304 SERIES...


16. A IR PURGING 1-2 BAR
17. A PPLICATION COAL/ WOOD MA TERIA L CONVEYOR & A REAS WHERE
1) IH 153ES - IR Ember Detector
SMOLDERING FIRE IS POSSIBLE
2) IH153ES-P - IR Ember Detector with in-built air purging
18. SENSIT IVITY SELECTION 4 RANGE OF SELECTION,
1. VERY HIGH SENSITIVITY 3) Air purging Unit
2. HIGH SENSITIVITY
3. NORMA L SENSITIVIT Y (DEFAULT SETTING) 3.1) IH323 (stand alone)(Suitable to be used with IH153ES)
4. LOW SENSITIVITY
19. EMC PROTECTION IMMUNE T O EMC/EMII INTERFERENCE.
3.2) IH323 CT (stand alone with sequential timer)(Suitable to be
used with IH153ES)
3.3) IH323 DC CT (Suitable with IH153ES-P Model)
APPROVAL/ CONFIRMATION /
CERTIFICATION:
ACCESSORIES:
1. CERTIFICATE NO. ET/EMC/2014/943
2. IP Protection Certified by ETDC. 1. Swivel Mounting Base - IH-MB-01 XY - 1 No.
3. Confirming to Requirement of NFPA 72E. 2. Cable Glands - 2 Nos.
4. Confirming to Requirement of IS-2189. 3. User Manual
Packing Size : 300 (L) X 250 (B) X 165 (H) (all in mm)
Packing Weight : 3.0 Kg. Max.

Important : M/s. Agni Controls 1985-2014


29
This document is not intended to be used for installation No :1, 6th street, Dr.Subbarayan Nagar, Kodambakkam,
29 YEARS IN FIRE & SAFETY
Chennai - 600024, India
purposes. Specifications are subject to change without prior PH : +91-44-32518235
notice. FAX : +91-44-24812475
REVISED AS ON DEC 2014 Website : www.balafire.com
DOC.NO: I-MK-3.6-016, REV-01
E-mail : marketing@agnicontrols.com