10.1 PIPING.
10.1.1 The pipe used in the sprinkler system (from the pump house to
the installation valves) shall be laid normally laid underground or
in masonry culverts with removable covers of incombustible
construction and shall be of any one of the following types: -
b) Centrifugally Cast (spun) iron class "A" pipes with Tyton joints
conforming to IS-1536.
1
10.1.3 Underground pipes shall be laid not less than 1M below ground
level. Where soil conditions are unsatisfactory, masonry or
equivalent supports shall be provided at regular intervals.
10.1.4 Pipes shall not be laid under buildings or plant areas or storage
areas. As far as possible, pipes shall not be laid under large open
storage, railroads and roads carrying heavy traffic.
10.1.5 Pipes shall not traverse on ground, which is not under the control
of the owner of the installation. Pipes shall also not pass through
public roadways.
10.1.6 The installation piping (from the pump house up to the installation
valve and also the installation piping with sprinklers) shall be
capable of withstanding for two hours a pressure equivalent to
150% of the maximum working pressure.
10.1.7 All boltholes in the flanges shall be drilled. Drilling of each flange
shall be in accordance with the relevant Indian or ASTM or British
standards.
10.1.9 Welded joints shall not be permitted for pipes having diameter
less than 50 mm.
2
10.2 FITTINGS.
10.2.3 Welded fittings according to the laid down welding procedure are
permitted. Welded parts shall be galvanised or suitably coated
after welding as per the requirement of the areas to be protected
by the system i.e. chemical and electrolytic corrosion.
10.2.4 Welded joints shall not be permitted for fittings of less than 50
mm diameter.
10.3.2 Pipework shall not be used to support any other loads except
where primary support is designed for the suspension of the piped
service.
10.3.6 The supports on which the pipework rests shall be secured firmly
in position.
10.3.7 The thickness of all parts of pipe supports shall not be less than 3
mm.
3
10.3.9 Pipework in corrosive areas shall be of either stainless steel or
suitably protected against corrosion.
10.3.10The distance between the pipe supports measured along the line
of connected pipes (whether the pipes run horizontally, vertically
or at angles) shall not be less than the following Table 10.
TABLE – 10
Up to 65 mm 4.0M
65 mm to 100 mm 6.0M
100 mm to 250 mm 6.5M
10.3.11DISTRIBUTION PIPES
10.3.12RANGE PIPES