Line harmonic currents created by adjustable frequency control

Nonlinear loads
Nonlinear loads like adjustable frequency controls create line harmonics when connected to the AC power distribution
system. These harmonic currents are a result of non-sinusoidal current, which is a characteristic of all adjustable
frequency controls using diodes or silicon controlled rectifiers (SCRs) on the input.

Line harmonic currents created by adjustable frequency control (on photo: 400V real-time passive harmonic filter;
via enspecpower.com)

The control’s input current is composed of the fundamental sinusoidal current (50 or 60 Hz) and currents at frequencies
higher than the fundamental frequency. These harmonic currents do not aid in the transmission of power to the connected
load, but contribute to the volt-ampere losses in the power distribution system.

Some of the negative effects of AC line harmonics if not properly addressed are:

1. Possible interference with communication equipment.


2. Possible overheating of transformers and other branch circuit equipment.
3. Possible increased heating in motors connected across-the-line due to copper and iron losses.
4. Possible resonance with power factor capacitors.

The AC input line harmonic current magnitudes may vary with control designs. The power distribution system impedance
at the installation and the control’s input design determines the actual magnitude of line harmonic currents. Because of
these variables, it is difficult to suggest general guidelines to predict the magnitude of the line harmonic currents. When
the actual harmonic current values are required, the control manufacturer should be consulted.

http://electrical-engineering-portal.com/line-harmonic-currents-adjustable-frequency-control-created 1/4
1/30/2018 Line harmonic currents created by adjustable frequency control | EEP

When AC line harmonic currents exist in a power distribution system, the


harmonic currents may be amplified through frequency resonance of power factor
correction capacitors with transformer inductance to cause equipment failures.

A point of common coupling (PCC) is the


interconnection between two utility customers
(photo credit: ecmweb.com)

Harmonic distortion levels as stated in IEEE 519 are intended to be applied at the Point of Common Coupling
(PCC) between the utility system and multiple users. Harmonic distortion levels can be measured or predicted
through modeling techniques of the power distribution system and the total connected adjustable speed drive
system.

The harmonic voltage and current distortion values at the PCC may be reduced through several abatement
methods that include:

1. Design Techniques

Power system design – decreasing the drive system load, as a percentage of the total power distribution network load
will improve harmonic voltage distortion conditions.

DC Link choke/inductor – an inherent design feature within some controls, provides a minimum level of harmonic
reduction by changing the rate of rise of the input current.

2. Line Impedance

AC line reactor – based upon the percent of line impedance, provides a lower amplitude of harmonic currents by slowing
down the rate of rise of input current pulses, similar to DC link choke.

Drive Isolation Transformer – provides similar performance to an AC line reactor with the additional power quality
benefit of being able to adjust the voltage magnitude.

3. Multi-pulse methods/converter design topologies

Phase multiplication – involves the use of a phase-shifting transformer for feeding multi-pulse control inputs. By properly
shifting the phase relationship to various 6-pulse controls, the net effect in the power system is to create a 12-pulse
circuit with cancellation of the 5th and 7th characteristic harmonics. However, this method is most effective when the
motor loads are of equal size and load.

12-pulse rectifier – a control that utilizes a dual 6-pulse rectifier network with a phase shifting transformer for proper
commutation of the dual bridges. Similar to phase multiplication, the net effect is cancellation of the 5th, 7th, 17th, and
19th characteristic harmonics.

http://electrical-engineering-portal.com/line-harmonic-currents-adjustable-frequency-control-created 2/4
1/30/2018 Line harmonic currents created by adjustable frequency control | EEP

Inverter output AC line reactor

18-pulse rectifier – a control that utilizes three 6-pulse rectifier networks with phase shifting transformers for proper
commutation. This results in an improved waveform, cancellation of lower order 5th, 7th, 11th, 13th, 23rd, 25th, 29th, and
31st characteristic harmonics.

Active rectifier input – a control that incorporates gate controlled power semi-conductors in the input rectifier stage to
shape the input current waveform, to a sinusoidal current waveform symmetrical to the voltage.

This method of harmonic abatement is the most complex. A microprocessor controller is required for gate
control of the input power semi-conductors.

4. Harmonic Filters

Shunt filters – passive filters that are properly designed and for the 5th, 7th, and 13th harmonics can effectively reduce
the harmonic currents in a power distribution system. Each filter consists of a series LC circuit, tuned to resonate at a
specific harmonic frequency acting as a low impedance path shunting the source of harmonics.

400V real-time passive harmonic filter (photo credit:


enspecpower.com)

http://electrical-engineering-portal.com/line-harmonic-currents-adjustable-frequency-control-created 3/4
1/30/2018 Line harmonic currents created by adjustable frequency control | EEP

Specific site application considerations apply since the filter cannot distinguish between the harmonics from the control
equipment, other external power system harmonics, or additional installed control equipment.

Series filters – these filters consist of a parallel LC circuit tuned to resonate a specific frequency, similar to a shunt filter.
The series reactor acts to de-tune other power distribution system harmonics from being trapped by the passive filter.

Harmonic injection – adaptive compensators are designed to constantly monitor the AC line input current to the control
by injecting a current equal in frequency/magnitude and 180° out phase to the distorted current. This action will cause
cancellation of the line harmonic currents.

Active filters – designed primarily for multiple non-linear harmonic loads, monitoring dynamic load conditions and
switching necessary VAR compensation.

Harmonics: What are they, why do I care, how do I solve?

Harmonics: What are they, why do I care, how do I solve?

Reference: NEMA Standards Publication – Application Guide For AC Adjustable Speed Drive Systems

About Author

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high
power busbar trunking (<6300A) in power substations, commercial buildings and industry fascilities. Professional in
AutoCAD programming. Present on Google+

http://electrical-engineering-portal.com/line-harmonic-currents-adjustable-frequency-control-created 4/4

You might also like