1. MEASUREMENT CHECK:
3φ -Current injected in all phases & measurements checked.
CHANNEL
CH. NO INJECTED MEASURED COMMENTS
RATING
1 1A 1A 2998 A Bay-410 R _Phase Current
2 1A 1A 3000 A Bay-410 Y _Phase Current
3 1A 1A 2999 A Bay-410 B _Phase Current
2. DIFFERENTIAL PROTECTION:
a)Differential Relay Stability testing(Bay-410 and Bay-411):
Bay-1 Bay-2 ID
Diff. Current in
Curent in pri(A) Current in pri(A) pri(A)
Bay-410-I1 3000 (ø = 0º) Bay-411-I1 3000 (ø = 180º) IDL1 0.262
Bay-410-I2 3000 (ø = 240º) Bay-411-I2 3000 (ø = 60º) IDL2 0.394
Bay-410-I3 3000 (ø = 120º) Bay-411-I3 3000 (ø = 300º) IDL3 0.203
b)Differential Pickup:
i) BAY-410 (Secondary):
BAY-410
Setting:
=>In sec=0.2A
Checklist
Binary Inputs Checked as per relay assignment OK
Binary Outputs Checked as per relay assignment OK
LED Indicators Checked as per relay assignment OK
Earthing Checked as per scheme assignment OK
Inspect for physical damage/defects Checked-OK
Remarks:
Relay found healthy and fit for service.