Line Size Calculation

Operating Hydro Test


Line Op.Temp. Design Pr.
Area of application Line No Location PID No Functional Description Material Flow Size in NB 0 Pr. Pr.
Vel m/s ( C) ( Kg/cm2)
( Kg/cm2) ( Kg/cm2)
Page 1
Intake cum grease Service water to intake
115-SW-GI-50-011 1 Pipe GI Pipe GI 3.0 25 1.70 20-30 6 9 13.5
removal Chamber chamber
Intake cum grease Raw Sewage pump to grease
103-RS-DI-100-011 1 Pipe DI Pipe DI 5.0 100 0.18 20-30 2.2 3.3 4.95
removal Chamber removal Chamber
Intake cum grease
RS-DI-1500-RS-107 Raw Sewage line from Client 1 Influent pipe Raw sewage inlet pipe HDPE 6583.3 1500 1.04 20-30 0.6 0.9 1.35
removal Chamber
Intake cum grease Intake cum grease removal Motorized Penstock gate
1 Gate SS-316 2194.4 1000 sq 0.61 20-30 0.6 0.9 1.35
removal Chamber Chamber with ex spindle
Page 2 0 0
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-800-001 2 Pipe DI PIPE DI 2200.0 800 1.22 20-30 Atm+0.1 1.65 2.475
suction
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-800-003 2 Pipe DI PIPE DI 2200.0 800 1.22 20-30 Atm+0.1 1.65 2.475
suction
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-800-005 2 Pipe DI PIPE DI 2200.0 800 1.22 20-30 Atm+0.1 1.65 2.475
suction
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-800-007 2 Pipe DI PIPE DI 2200.0 800 1.22 20-30 Atm+0.1 1.65 2.475
suction
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-600-002 2 Pipe DI PIPE DI 2200.0 600 2.16 20-30 2.2 3.3 4.95
discharge
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-600-004 2 Pipe DI PIPE DI 2200.0 600 2.16 20-30 2.2 3.3 4.95
discharge
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-600-006 2 Pipe DI PIPE DI 2200.0 600 2.16 20-30 2.2 3.3 4.95
discharge
Raw Sewage pump individual
Raw Sewage Sump 103-RS-DI-600-008 2 Pipe DI PIPE DI 2200.0 600 2.16 20-30 2.2 3.3 4.95
discharge
Raw Sewage pump main
Raw Sewage Sump 103-RS-DI-1000-009 2 Pipe DI PIPE DI 6600.0 1000 2.34 20-30 2.2 3.3 4.95
discharge header
Page 3 0 0
Flushing line to mechanical
Preliminary Treatment 115-SW-GI-80-010 3 Pipe GI Pipe GI 30 80 1.66 20-30 6 9 13.5
screen
Motorized Penstock gate
Preliminary Treatment Inlet chamber STP 3 Valve SS-316 2194.4 1000 sq 0.61 20-30 0.6 0.9 1.35
with ex spindle
Page 4 0 0
Grit Chamber to Oil & grease
Preliminary Treatment 106-OG-DI-150-010 4 Influent pipe PIPE DI 30 150 0.47 20-30 0.6 0.9 1.35
pump
Grit Chamber to Oil & grease
Preliminary Treatment 106-OG-DI-150-009 4 Influent pipe PIPE DI 30 150 0.47 20-30 0.6 0.9 1.35
pump
Air line to Aerated Grit
Preliminary Treatment 120-A-SS316-80-003 4 Pipe PIPE SS-316 210 80 11.61 38 0.35 0.525 0.7875
Chamber
Air line to Aerated Grit
Preliminary Treatment 120-A-SS316-80-006 4 Pipe PIPE SS-316 210 80 11.61 38 0.35 0.525 0.7875
Chamber
Drain line from Aerated Grease
Preliminary Treatment 120-D-50-L-013 4 pipe PIPE DI 1 50 0.14 20-30 0.6 0.9 1.35
Chamber
Drain line from Aerated Grease
Preliminary Treatment 120-D-50-L-014 4 pipe PIPE DI 1 50 0.14 20-30 0.6 0.9 1.35
Chamber
Motorized Penstock gate
Preliminary Treatment Aerated Grit Chamber 4 Gate SS-316 2194.4 1000 sq 0.61 20-30 0.6 0.9 1.35
with ex spindle
Page 5 0 0
Grit and Grease removal from
Preliminary Treatment 106-L-DI-150-002 5 Influent pipe PIPE DI 3 150 0.05 20-30 0.6 0.9 1.35
Aerated Grit Chamber
Grit and Grease removal from
Preliminary Treatment 106-L-DI-150-003 5 Influent pipe PIPE DI 3 150 0.05 20-30 0.6 0.9 1.35
Aerated Grit Chamber
Grease removal from Aerated
Preliminary Treatment 106-L-DI-150-006 5 Influent pipe PIPE DI 3 150 0.05 20-30 0.6 0.9 1.35
Grease Chamber
Grease removal from Aerated
Preliminary Treatment 106-L-DI-150-008 5 Influent pipe PIPE DI 3 150 0.05 20-30 0.6 0.9 1.35
Grease Chamber
Air line to Aerated Grit
Preliminary Treatment 120-A-SS316-80-009 5 Pipe PIPE SS-316 210 80 11.61 38 0.35 0.525 0.7875
Chamber
Air line to Aerated Grit
Preliminary Treatment 120-A-SS316-80-012 5 Pipe PIPE SS-316 210 80 11.61 38 0.35 0.525 0.7875
Chamber
Drain line from Aerated Grease
Preliminary Treatment 120-D-50-L-015 5 pipe PIPE DI 1 50 0.14 20-30 0.6 0.9 1.35
Chamber
Drain line from Aerated Grease
Preliminary Treatment 120-D-50-L-016 5 pipe PIPE DI 1 50 0.14 20-30 0.6 0.9 1.35
Chamber
Drain line from Aerated Grease
Preliminary Treatment 106-OG-DI-150-011 5 pipe PIPE DI 2 150 0.03 20-30 0.6 0.9 1.35
Chamber
Motorized Penstock gate
Preliminary Treatment Aerated Grease Chamber 5 Gate SS-316 2194.4 1000 sq 0.27 20-30 0.6 0.9 1.35
with ex spindle
Page 6 0 0
Filtrate Transfer Pump to
Preliminary Treatment 139-F-DI-150-003 6 Pipe DI DI 125 150 1.97 20-30 1.5 2.25 3.375
Equalization Tank
Equalization Tank to Anarobic
Preliminary Treatment 107-SW-DI-600-001 6 Pipe DI DI 1900 600 1.87 20-30 0.7 1.05 1.575
tank
Equalization Tank to Anarobic
Preliminary Treatment 107-SW-DI-600-002 6 Pipe DI DI 1900 600 1.87 20-30 0.7 1.05 1.575
tank
Equalization Tank to Anarobic
Preliminary Treatment 107-SW-DI-600-003 6 Pipe DI DI 1900 600 1.87 20-30 0.7 1.05 1.575
tank
Motorized Penstock gate
Preliminary Treatment Equalization Tank 6 Gate SS-316 2194.4 1000 sq 0.61 20-30 0.6 0.9 1.35
with ex spindle
Page 7 0 0

Secondary Treatment 117-A-SS316-700-006 Aeration blower line to sump 7 Air pipe Pipe ( Aeration) SS-316 19800 700 14.30 96 0.75 1.125 1.6875

Secondary Treatment 101-A-SS316-250-008 Aeration blower line to sump 7 Air pipe Pipe ( Aeration) SS-316 6600 250 37.37 96 0.75 1.125 1.6875

Secondary Treatment 111-SL-DI-600-001 1st Stage Aeration Tank 7 Pipe DI Pipe DI 1875 600 1.84 20-30 1 1.5 2.25

Secondary Treatment 111-SL-DI-600-002 1st Stage Aeration Tank 7 Pipe DI Pipe DI 1875 600 1.84 20-30 1 1.5 2.25

Motorized Penstock gate


Secondary Treatment 1st Stage Aeration Tank 7 Gate SS-316 2194.4 1000 sq 0.61 20-30 0.6 0.9 1.35
with ex spindle
Page 8 0 0

Secondary Treatment 101-A-SS316-250-010 Aeration blower line to sump 8 Air pipe Pipe ( Aeration) SS-316 6600 250 37.37 96 0.75 1.125 1.6875

Secondary Treatment 111-SL-DI-600-003 1st Stage Aeration Tank 8 Pipe DI Pipe DI 1875 600 1.84 20-30 1 1.5 2.25

Secondary Treatment 111-SL-DI-600-004 1st Stage Aeration Tank 8 Pipe DI Pipe DI 1875 600 1.84 20-30 1 1.5 2.25
Motorized Penstock gate
Secondary Treatment 8 Gate SS-316 2194.4 1000 sq 0.61 20-30 0.6 0.9 1.35
with ex spindle
Page 9 0 0

Secondary Treatment 101-A-SS316-250-012 Aeration blower line to sump 9 Air pipe Pipe ( Aeration) SS-316 6600 250 37.37 96 0.75 1.125 1.6875

Secondary Treatment 111-SL-DI-600-005 1st Stage Aeration Tank 9 Pipe DI Pipe DI 1875 600 1.84 20-30 1 1.5 2.25

Secondary Treatment 111-SL-DI-600-006 1st Stage Aeration Tank 9 Pipe DI Pipe DI 1875 600 1.84 20-30 1 1.5 2.25

Motorized Penstock gate


Secondary Treatment 9 Gate SS-316 2194.4 1000 sq 0.27 20-30 0.6 0.9 1.35
with ex spindle
Page 10 0 0
Motorized Penstock gate
Secondary Treatment DD Clarifier 10 Gate SS-316 458.3 600 sq 0.35 20-30 0.6 0.9 1.35
with ex spindle
Individual outlet line from DD
Secondary Treatment 112-SL-DI-350-002 10 Pipe DI DI 458.3 350 1.32 20-30 0.6 0.9 1.35
Clarifier
Individual outlet line from DD
Secondary Treatment 112-SL-DI-350-003 10 Pipe DI DI 458.3 350 1.32 20-30 0.6 0.9 1.35
Clarifier
Common Outlet line from DD
Secondary Treatment 112-SL-DI-800-001 10 Pipe DI DI 1833.33 800 1.01 20-30 0.6 0.9 1.35
Clarifier
Page 11 0 0
Motorized Penstock gate
Secondary Treatment DD Clarifier 11 Gate SS-316 458.3 600 sq 0.35 20-30 0.6 0.9 1.35
with ex spindle
Individual outlet line from DD
Secondary Treatment 112-SL-DI-350-004 11 Pipe DI DI 458.3 350 1.32 20-30 0.6 0.9 1.35
Clarifier
Individual outlet line from DD
Secondary Treatment 112-SL-DI-350-005 11 Pipe DI DI 458.3 350 1.32 20-30 0.6 0.9 1.35
Clarifier
Page 12 0 0
Motorized Penstock gate
Secondary Treatment DD Clarifier 12 Gate SS-316 458.3 600 sq 0.35 20-30 0.6 0.9 1.35
with ex spindle
Individual outlet line from DD
Secondary Treatment 112-SL-DI-350-006 12 Pipe DI DI 458.3 350 1.32 20-30 0.6 0.9 1.35
Clarifier
Individual outlet line from DD
Secondary Treatment 112-SL-DI-350-006 12 Pipe DI DI 458.3 350 1.32 20-30 0.6 0.9 1.35
Clarifier
outlet header line from DD
Secondary Treatment 112-SL-DI-350-006 12 Pipe DI DI 916.7 800 0.51 20-30 0.6 0.9 1.35
Clarifier
Page 13 0 0
Motorized Penstock gate
Tertiary Treatment Disc Filter 13 Gate SS-316 1833.3 1000 sq 0.51 20-30 0.6 0.9 1.35
with ex spindle
Motorized Penstock gate
Tertiary Treatment UV Infection 13 Gate SS-316 1833.3 1000 sq 0.51 20-30 0.6 0.9 1.35
with ex spindle
Backwash Pump individual
Tertiary Treatment 113-FW-DI-150-001 13 Pipe DI Pipe DI 50 150 0.79 20-30 Atm+0.1 1.65 2.475
suction line
Backwash Pump individual
Tertiary Treatment 113-FW-DI-150-002 13 Pipe DI Pipe DI 50 150 0.79 20-30 Atm+0.1 1.65 2.475
suction line
Backwash Pump individual
Tertiary Treatment 113-FW-DI-150-003 13 Pipe DI Pipe DI 50 150 0.79 20-30 Atm+0.1 1.65 2.475
suction line
Backwash Pump individual
Tertiary Treatment 113-FW-DI-150-004 13 Pipe DI Pipe DI 50 150 0.79 20-30 Atm+0.1 1.65 2.475
suction line
Backwash Pump individual
Tertiary Treatment 113-FW-DI-150-005 13 Pipe DI Pipe DI 50 100 1.77 20-30 2.5 3.75 5.625
discharge line
Backwash Pump individual
Tertiary Treatment 113-FW-DI-150-006 13 Pipe DI Pipe DI 50 100 1.77 20-30 2.5 3.75 5.625
discharge line
Backwash Pump discharge line
Tertiary Treatment 113-FW-DI-150-007 13 Pipe DI Pipe DI 50 100 1.77 20-30 2.5 3.75 5.625
to fltrate sump
Page 14 0 0
Flushing Pump outet line 80 NB
Tertiary Treatment 115-SW-DI-80-001 14 Pipe DI Pipe DI 30 80 1.66 20-30 6 9 13.5
(DI Pipe)
Flushing Pump outet line 80 NB
Tertiary Treatment 115-SW-DI-80-002 14 Pipe DI Pipe DI 30 80 1.66 20-30 6 9 13.5
(DI Pipe)
Flushing Pump outet header
Tertiary Treatment 115-SW-GI-80-003 14 Pipe GI Pipe GI 30 80 1.66 20-30 6 9 13.5
line
Flushing Pump outet to Plant
Tertiary Treatment 115-SW-GI-25-008 14 Pipe GI Pipe GI 2 25 1.13 20-30 6 9 13.5
Cleaning
Flushing Pump outet to Dosing
Tertiary Treatment 115-SW-GI-50-007 14 Pipe GI Pipe GI 2 50 0.28 20-30 6 9 13.5
Area
Flushing Pump outet to Belt
Tertiary Treatment 115-SW-GI-80-006 14 Pipe GI Pipe GI 20 80 1.11 20-30 6 9 13.5
filter press pump
Flushing Pump outet to wash
Tertiary Treatment 115-SW-GI-80-005 14 Pipe GI Pipe GI 20 80 1.11 20-30 6 9 13.5
water pump GBT
Flushing Pump outet to
Tertiary Treatment 115-SW-GI-80-004 14 Pipe GI Pipe GI 2 80 0.11 20-30 6 9 13.5
Anerobic sludge digestor
Tertiary Treatment 115-SW-GI-25-009 Service water for DD clarifier 14 Pipe GI Pipe GI 5 25 2.83 20-30 6 9 13.5

Tertiary Treatment 115-SW-GI-25-010 Service water for Fine screen 14 Pipe GI Pipe GI 30 25 16.99 20-30 6 9 13.5

Tertiary Treatment 115-SW-GI-25-011 Service water for coarse screen 14 Pipe GI Pipe GI 5 25 2.83 20-30 6 9 13.5
Page 15
Reuse water Quality Pump
Tertiary Treatment 116-FW-DI-80-003 15 Pipe DI Pipe DI 21 80 1.16 20-30 3 4.5 6.75
discharge
Tertiary Treatment 116-FW-HDPE_1500-004 Effluent to Conacao Bay 15 Pipe HDPE Pipe HDPE 3666.67 1500 0.58 20-30 0.6 0.9 1.35
Page 16
Aeration Bower individual
Secondary Treatment 117-A-SS316-400-001 16 Pipe SS316 S316 6600 400 14.60 96 0.75 1.125 1.6875
discharge line
Aeration Bower individual
Secondary Treatment 117-A-SS316-400-002 16 Pipe SS316 S316 6600 400 14.60 96 0.75 1.125 1.6875
discharge line
Aeration Bower individual
Secondary Treatment 117-A-SS316-400-003 16 Pipe SS316 S316 6600 400 14.60 96 0.75 1.125 1.6875
discharge line
Aeration Bower individual
Secondary Treatment 117-A-SS316-400-004 16 Pipe SS316 S316 6600 400 14.60 96 0.75 1.125 1.6875
discharge line
Aeration Bower individual
Secondary Treatment 117-A-SS316-400-005 16 Pipe SS316 S316 6600 400 14.60 96 0.75 1.125 1.6875
discharge line
Aeration Bower common
Secondary Treatment 117-A-SS316-400-006 16 Pipe SS316 S316 19800 700 14.30 96 0.75 1.125 1.6875
discharge line
Aeration Bower common
Secondary Treatment 117-A-SS316-80-013 discharge line to Air sludge 16 Pipe SS316 S316 150 80 8.29 96 0.75 1.125 1.6875
holding tank
Page 17
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-001 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line A/B Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-002 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line A/B Blower
Air blower header discharge
Preliminary Treatment 120-A-SS316-80-003 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line A/B Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-004 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line C/D Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-005 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line C/D Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-006 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line C/D Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-007 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line E/F Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-008 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line E/F Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-009 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line E/F Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-010 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line G/H Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-011 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line G/H Blower
Air blower individual discharge
Preliminary Treatment 120-A-SS316-80-012 17 Pipe SS316 S316 210 80 11.61 38 0.35 0.525 0.7875
line G/H Blower
Page 18
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-450-002 18 Pipe DI pipe DI 900 450 1.57 20-30 0.7 1.05 1.575
discharge line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-450-004 18 Pipe DI pipe DI 900 450 1.57 20-30 0.7 1.05 1.575
discharge line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-450-006 18 Pipe DI pipe DI 900 450 1.57 20-30 0.7 1.05 1.575
discharge line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-450-008 18 Pipe DI pipe DI 900 450 1.57 20-30 0.7 1.05 1.575
discharge line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-450-010 18 Pipe DI pipe DI 900 450 1.57 20-30 0.7 1.05 1.575
discharge line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-600-001 18 Pipe DI pipe DI 900 600 0.88 20-30 0.7 1.05 1.575
suction line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-600-003 18 Pipe DI pipe DI 900 600 0.88 20-30 0.7 1.05 1.575
suction line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-600-005 18 Pipe DI pipe DI 900 600 0.88 20-30 0.7 1.05 1.575
suction line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-600-007 18 Pipe DI pipe DI 900 600 0.88 20-30 0.7 1.05 1.575
suction line
RAS / WAS Pump individual
Tertiary Treatment 114-SL-DI-600-009 18 Pipe DI pipe DI 900 600 0.88 20-30 0.7 1.05 1.575
suction line
WAS Sludge to Sludge Handling
Tertiary Treatment 114-SL-DI-250-012 18 Pipe DI pipe DI 300 250 1.70 20-30 0.7 1.05 1.575
Tank
WAS Sludge to Thickened
Tertiary Treatment 114-SL-DI-100-013 18 Pipe DI pipe DI 100 150 1.57 20-30 0.7 1.05 1.575
Sludge Sump
Tertiary Treatment 114-SL-DI-400-014 RAS Sludge to Anaerobic tank 18 Pipe DI pipe DI 900 400 1.99 20-30 0.7 1.05 1.575

Tertiary Treatment 114-SL-DI-400-015 RAS Sludge to Anaerobic tank 18 Pipe DI pipe DI 900 400 1.99 20-30 0.7 1.05 1.575

Tertiary Treatment 114-SL-DI-400-016 RAS Sludge to Anaerobic tank 18 Pipe DI pipe DI 900 400 1.99 20-30 0.7 1.05 1.575
RAS / WAS Pump common
Tertiary Treatment 114-SL-DI-800-011 18 Pipe DI pipe DI 2700 800 1.49 20-30 0.7 1.05 1.575
discharge header
Page 19 0 0
Gravity Belt Thickener Feed
Tertiary Treatment 115-SL-DI-200-001 19 Pipe DI pipe DI 150 200 1.33 20-30 1.5 2.25 3.375
Pump individual discharge
Gravity Belt Thickener Feed
Tertiary Treatment 115-SL-DI-200-002 19 Pipe DI pipe DI 150 200 1.33 20-30 1.5 2.25 3.375
Pump individual discharge
Gravity Belt Thickener Feed
Tertiary Treatment 115-SL-DI-200-003 19 Pipe DI pipe DI 150 200 1.33 20-30 1.5 2.25 3.375
Pump individual discharge
Gravity Belt Thickener Feed
Tertiary Treatment 115-SL-DI-200-004 Pump discharge 19 Pipe DI pipe DI 150 200 1.33 20-30 1.5 2.25 3.375
interconnecting line
Gravity Belt Thickener Feed
Tertiary Treatment 115-SL-DI-200-005 Pump discharge 19 Pipe DI pipe DI 150 200 1.33 20-30 1.5 2.25 3.375
interconnecting line
Page 20 0 0
Service water line for Gravity
Tertiary Treatment 115-SW-GI-80-005 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
Belt Thickning Unit
Wash water pump individual
Tertiary Treatment 116-SW-GI-50-001 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
suction
Wash water pump individual
Tertiary Treatment 116-SW-GI-50-003 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
suction
Wash water pump individual
Tertiary Treatment 116-SW-GI-50-002 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
discharge
Wash water pump individual
Tertiary Treatment 116-SW-GI-50-004 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
discharge
Wash water pump line to
Tertiary Treatment 116-SW-GI-50-005 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
Gravity Belt thickening unit
Wash water pump line to
Tertiary Treatment 116-SW-GI-50-006 20 Pipe DI Pipe DI 6 50 0.85 20-30 6 9 13.5
Gravity Belt thickening unit
Wash water pump line to
Tertiary Treatment 116-SW-GI-50-007 20 Pipe DI Pipe DI 6 50 0.85 20-30 0.6 0.9 1.35
Gravity Belt thickening unit
Gravity Belt Thickening Unit to
Tertiary Treatment 116-SL-DI-200-018 20 Pipe DI Pipe DI 25 200 0.22 20-30 0.6 0.9 1.35
thickened sludge sump
Gravity Belt Thickening Unit to
Tertiary Treatment 116-SL-DI-200-019 20 Pipe DI Pipe DI 25 200 0.22 20-30 0.6 0.9 1.35
thickened sludge sump
Gravity Belt Thickening Unit to
Tertiary Treatment 116-SL-DI-200-020 20 Pipe DI Pipe DI 25 200 0.22 20-30 0.6 0.9 1.35
thickened sludge sump
Gravity Belt Thickening Unit to
Tertiary Treatment 116-SL-DI-300-021 thickened sludge sump 20 Pipe DI Pipe DI 50 300 0.20 20-30 0.6 0.9 1.35
common header
Compressed air ine individual
Tertiary Treatment 116-CS-DI-25-008 20 Pipe CS Pipe CS 5 25 2.83 40 6 9 13.5
discharge
Compressed air ine individual
Tertiary Treatment 116-CS-DI-25-009 20 Pipe CS Pipe CS 5 25 2.83 40 6 9 13.5
discharge
Compressed air ine discharge
Tertiary Treatment 116-CS-DI-25-010 20 Pipe CS Pipe CS 5 25 2.83 40 6 9 13.5
header
Compressed air ine to Gravity
Tertiary Treatment 116-CS-DI-25-011 20 Pipe CS Pipe CS 5 25 2.83 40 6 9 13.5
Belt Thickning Unit
Compressed air ine to Gravity
Tertiary Treatment 116-CS-DI-25-012 20 Pipe CS Pipe CS 5 25 2.83 40 6 9 13.5
Belt Thickning Unit
Compressed air ine to Gravity
Tertiary Treatment 116-CS-DI-25-013 20 Pipe CS Pipe CS 5 25 2.83 40 6 9 13.5
Belt Thickning Unit
Gravity Belt Thickning Unit to
Tertiary Treatment 116-CS-DI-25-014 20 Pipe DI Pipe DI 125 150 1.97 20-30 0.6 0.9 1.35
filtrate Sump
Gravity Belt Thickning Unit to
Tertiary Treatment 116-CS-DI-25-015 20 Pipe DI Pipe DI 125 150 1.97 20-30 0.6 0.9 1.35
filtrate Sump
Gravity Belt Thickning Unit to
Tertiary Treatment 116-CS-DI-25-016 20 Pipe DI Pipe DI 125 150 1.97 20-30 0.6 0.9 1.35
filtrate Sump
Gravity Belt Thickener header
Tertiary Treatment 116-CS-DI-25-016 20 Pipe DI Pipe DI 250 200 2.21 20-30 0.6 0.9 1.35
line
Page 21
Sludge Treatment and Digester Feed Pump individual
118-SL-DI-200-001 21 Pipe DI Pipe DI 50 200 0.44 20-30 0.6 0.9 1.35
Disposal suction Line
Sludge Treatment and Digester Feed Pump individual
118-SL-DI-200-003 21 Pipe DI Pipe DI 50 200 0.44 20-30 0.6 0.9 1.35
Disposal suction Line
Sludge Treatment and Digester Feed Pump individual
118-SL-DI-200-002 21 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal discharge Line
Sludge Treatment and Digester Feed Pump individual
118-SL-DI-200-004 21 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal discharge Line
Sludge Treatment and Digester Feed Pump discharge
118-SL-DI-200-005 21 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal line to Sludge Ejector 1

Sludge Treatment and Digester Feed Pump discharge


118-SL-DI-200-006 21 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal line to Sludge Ejector 2
Page 22
Sludge Treatment and Service water supply manifold
22 Pipe CS Pipe CS 50 150 0.79 20-30 6 9 13.5
Disposal to HE
Sludge Treatment and
118-SL-DI-150-007 Digested feed pump to HE 22 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal
Sludge Treatment and
118-SL-DI-150-008 Digested feed pump to HE 22 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal
Sludge Treatment and HE to anaerobic sludge
118-SL-DI-150-001 22 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal digeaster 1
Sludge Treatment and HE to anaerobic sludge
118-SL-DI-150-002 22 Pipe DI Pipe DI 50 150 0.79 20-30 1.2 1.8 2.7
Disposal digeaster 2
Sludge Treatment and Sludge recirculation pump to
118-SL-DI-150-011 22 Pipe DI Pipe DI 100 150 1.57 20-30 1 1.5 2.25
Disposal HE
Sludge Treatment and Sludge recirculation pump to
118-SL-DI-150-005 22 Pipe DI Pipe DI 100 150 1.57 20-30 1 1.5 2.25
Disposal HE
Sludge Treatment and HE to Service water balancing
120-PW-DI-150-002 22 Pipe DI Pipe DI 100 150 1.57 20-30 1 1.5 2.25
Disposal manifold
Page 23
Sludge Treatment and Sludge recirculation pump
122-SL-DI-150-003 23 Pipe DI Pipe DI 50 150 0.79 20-30 Atm+0.1 1.65
Disposal suction
Sludge Treatment and Sludge recirculation pump
122-SL-DI-150-004 23 Pipe DI Pipe DI 50 150 0.79 20-30 Atm+0.1 1.65
Disposal suction
Sludge Treatment and Sludge recirculation pump
122-SL-DI-150-005 23 Pipe DI Pipe DI 100 150 1.57 20-30 1 1.5 2.25
Disposal discharge
Sludge Treatment and Sludge recirculation pump
122-SL-DI-150-011 23 Pipe DI Pipe DI 100 150 1.57 20-30 1 1.5 2.25
Disposal discharge
Sludge Treatment and Anaerobic sludge digester to
122-SL-DI-150-006 23 Pipe DI Pipe DI 50 250 0.28 20-30 1 1.5 2.25
Disposal digested sludge holding tank

Sludge Treatment and Anaerobic sludge digester to


122-SL-DI-150-012 23 Pipe DI Pipe DI 50 250 0.28 20-30 1 1.5 2.25
Disposal digested sludge holding tank
Page 24
Sludge Treatment and
124-BG-CS-200-001 Ceramic filter to Flare 24 Pipe CS Pipe CS 150 200 1.33 35-40 0.25 0.375 0.5625
Disposal
Sludge Treatment and
124-BG-200-002 To Biogas scrubber system 24 Pipe CS Pipe CS 150 150 2.36 35-40 0.25 0.375 0.5625
Disposal
Sludge Treatment and Sludge digester to biogas
122-BG-CS-200-003 24 Pipe CS Pipe CS 150 200 1.33 35-40 0.25 0.375 0.5625
Disposal scrubber system
Sludge Treatment and Ceramic filter to Biogas engine
125-BG-CS-200-001 24 Pipe CS Pipe CS 150 150 2.36 35-40 0.25 0.375 0.5625
Disposal by Biogas blower
Page 25
Sludge Treatment and
Biogas Scrubber System 25 Pipe CS Pipe CS 100 150 1.57 60 1 1.5 2.25
Disposal
Sludge Treatment and
131-BG-CS-150-001 To biogas engine pump 25 Pipe CS Pipe CS 100 150 1.57 60 1 1.5 2.25
Disposal
Sludge Treatment and
131-BG-SS316-150-003 Biogas engine pump discharge 25 Pipe SS Pipe SS-316 100 150 1.57 60 1 1.5 2.25
Disposal
Sludge Treatment and
131-BG-CS-150-002 To biogas engine pump 25 Pipe CS Pipe CS 100 150 1.57 60 1 1.5 2.25
Disposal
Sludge Treatment and
131-BG-SS316-150-004 Biogas engine pump discharge 25 Pipe SS Pipe SS-316 100 150 1.57 60 1 1.5 2.25
Disposal
Sludge Treatment and
131-BG-SS316-150-001 To Biogas balancing manifold 25 Pipe SS Pipe SS-316 100 150 1.57 60 1 1.5 2.25
Disposal
Sludge Treatment and
131-BG-SS316-150-002 To Biogas balancing manifold 25 Pipe SS Pipe SS-316 100 150 1.57 60 1 1.5 2.25
Disposal
Page 26
Sludge Treatment and
135-DS-DI-150-001 Belt filter press suction line 26 Pipe DI Pipe DI 25 150 0.39 20-30 Atm+0.1 1.65
Disposal
Sludge Treatment and
135-DS-DI-150-003 Belt filter press suction line 26 Pipe DI Pipe DI 25 150 0.39 20-30 Atm+0.1 1.65
Disposal
Sludge Treatment and
135-DS-DI-150-005 Belt filter press suction line 26 Pipe DI Pipe DI 25 150 0.39 20-30 Atm+0.1 1.65
Disposal
Sludge Treatment and
135-DS-DI-150-001 Belt filter press discharge line 26 Pipe DI Pipe DI 25 100 0.88 20-30 1.5 2.25 3.375
Disposal
Sludge Treatment and
135-DS-DI-150-003 Belt filter press discharge line 26 Pipe DI Pipe DI 25 100 0.88 20-30 1.5 2.25 3.375
Disposal
Sludge Treatment and
135-DS-DI-150-005 Belt filter press discharge line 26 Pipe DI Pipe DI 25 100 0.88 20-30 1.5 2.25 3.375
Disposal
Sludge Treatment and
135-DS-DI-150-007 Belt filter press discharge line 26 Pipe DI Pipe DI 25 100 0.88 20-30 1.5 2.25 3.375
Disposal
Sludge Treatment and
135-DS-DI-150-008 Belt filter press discharge line 26 Pipe DI Pipe DI 25 100 0.88 20-30 1.5 2.25 3.375
Disposal
Sludge Treatment and
135-DS-DI-150-002 Belt filter press discharge line 26 Pipe DI Pipe DI 25 100 0.88 20-30 1.5 2.25 3.375
Disposal
Page 27
Sludge Treatment and Wash water pump discharge
137-SW-DI-50-003 27 Pipe DI pipe DI 20 50 2.83 20-30 7 10.5 15.75
Disposal line
Sludge Treatment and Wash water pump discharge
137-SW-DI-50-004 27 Pipe DI pipe DI 20 50 2.83 20-30 7 10.5 15.75
Disposal line
Sludge Treatment and Wash water pump discharge
137-SW-DI-50-005 27 Pipe DI pipe DI 20 50 2.83 20-30 7 10.5 15.75
Disposal line
Sludge Treatment and Wash water pump discharge
137-SW-DI-50-006 27 Pipe DI pipe DI 20 50 2.83 20-30 7 10.5 15.75
Disposal line
Sludge Treatment and Wash water pump discharge
137-SW-DI-50-007 27 Pipe DI pipe DI 20 50 2.83 20-30 7 10.5 15.75
Disposal line
Sludge Treatment and
137-SW-DI-60-001 Wash water pump suction line 27 Pipe DI pipe DI 20 65 1.68 20-30 Atm+0.1 1.65
Disposal
Sludge Treatment and
137-SW-DI-60-002 Wash water pump suction line 27 Pipe DI pipe DI 20 65 1.68 20-30 Atm+0.1 1.65
Disposal
Sludge Treatment and
137-SW-DI-200-004 Belt filter press to Filtrate sump 27 Pipe DI Pipe DI 20 200 0.18 20-30 0.6 0.9 1.35
Disposal
Sludge Treatment and Compressed air line to Belt
138-CA-DI-25-002 27 Pipe DI Pipe DI 6.3 25 3.57 20-30 6 9 13.5
Disposal Filter Press
Sludge Treatment and Compressed air line to Belt
138-CA-DI-25-001 27 Pipe DI Pipe DI 6.3 25 3.57 20-30 6 9 13.5
Disposal Filter Press
Sludge Treatment and Compressed air line to Belt
138-CA-DI-25-003 27 Pipe DI Pipe DI 6.3 25 3.57 20-30 6 9 13.5
Disposal Filter Press
Sludge Treatment and Compressed air line to Belt
138-CA-DI-25-004 27 Pipe DI Pipe DI 6.3 25 3.57 20-30 6 9 13.5
Disposal Filter Press
Sludge Treatment and Compressed air line to Belt
138-CA-DI-25-005 27 Pipe DI Pipe DI 6.3 25 3.57 20-30 6 9 13.5
Disposal Filter Press
Page 28
Sludge Treatment and Filtrate Transfer Pump
139-F-DI-150-001 28 Pipe DI Pipe DI 125 150 1.97 20-30 1.5 2.25 3.375
Disposal individual discharge
Sludge Treatment and Filtrate Transfer Pump
139-F-DI-150-002 28 Pipe DI Pipe DI 125 150 1.97 20-30 1.5 2.25 3.375
Disposal individual discharge
Page 29
Chemical Dosing Pipe -
Chemical Dosing 141-C-uPVC-40-004 PACL dosing unit -Suction line 29 Pipe ( For PACL ) PVC 2 50 0.28 20-30 Atm+0.1 1.65
suction line
Chemical Dosing Pipe -
Chemical Dosing 141-C-uPVC-40-005 PACL dosing unit-discharge line 29 Pipe ( For PACL) PVC 2 40 0.44 20-30 3 4.5 6.75
discharge line
PACL loading/unloading unit - Chemical Dosing Pipe -
Chemical Dosing 141-C-uPVC-40-004 29 Pipe ( For PACL ) PVC 2 65 0.17 20-30 Atm+0.1 1.65
Suction line suction line
PACL loading/unloading unit - Chemical Dosing Pipe -
Chemical Dosing 141-C-uPVC-40-005 29 Pipe ( For PACL) PVC 2 50 0.28 20-30 1.5 2.25 3.375
discharge line discharge line
Page 30
ALKALI DOSING UNIT -Suction Chemical Dosing Pipe -
Chemical Dosing 143-C-uPVC-50-004 30 Pipe ( For ALKALI ) PVC 1 50 0.14 20-30 Atm+0.1 1.65
line suction line
ALKALI DOSING UNIT-discharge Chemical Dosing Pipe -
Chemical Dosing 143-C-uPVC-50-005 30 Pipe ( For ALKALI) PVC 1 40 0.22 20-30 3 4.5 6.75
line discharge line
ALKALI DOSING UNIT-
Chemical Dosing Pipe -
Chemical Dosing 142-C-uPVC-65-001 loading/unloading unit -Suction 30 Pipe ( For ALKALI ) PVC 1 50 0.14 20-30 Atm+0.1 1.65
suction line
line
ALKALI DOSING UNIT-
Chemical Dosing Pipe -
Chemical Dosing 142-C-uPVC-65-003 loading/unloading unit - 30 Pipe ( For ALKALI) PVC 1 40 0.22 20-30 1.5 2.25 3.375
discharge line
discharge line
Page 31
SODIUM ACCESATE DOSING- Chemical Dosing Pipe - Pipe ( For SODIUM
Chemical Dosing 145-C-uPVC-40-004 31 PVC 2 50 0.28 20-30 Atm+0.1 1.65
Suction line suction line ACCESATE )
SODIUM ACCESATE DOSING- Chemical Dosing Pipe - Pipe ( For SODIUM
Chemical Dosing 145-C-uPVC-40-005 31 PVC 2 40 0.44 20-30 3 4.5 6.75
discharge line discharge line ACCESATE )
SODIUM ACCESATE
Chemical Dosing Pipe - Pipe ( For SODIUM
Chemical Dosing 144-C-uPVC-65-003 loading/unloading unit -Suction 31 PVC 2 50 0.28 20-30 Atm+0.1 1.65
suction line ACCESATE )
line
SODIUM ACCESATE DOSING
Chemical Dosing Pipe - Pipe ( For SODIUM
Chemical Dosing 144-C-uPVC-50-003 loading/unloading unit - 31 PVC 2 40 0.44 20-30 1.5 2.25 3.375
discharge line ACCESATE )
discharge line
Page 32
Chemical Dosing Pipe -
Chemical Dosing 146-uPVC-40-007 DWPE Dosing Unit 32 Pipe ( For DWPE ) PVC 0.4 40 0.09 20-30 Atm+0.1 1.65
suction line
Chemical Dosing Pipe -
Chemical Dosing 146-uPVC-40-009 DWPE Dosing Unit 32 Pipe ( For DWPE ) PVC 0.4 40 0.09 20-30 Atm+0.1 1.65
suction line
Chemical Dosing Pipe -
Chemical Dosing 146-uPVC-40-011 DWPE Dosing Unit 32 Pipe ( For DWPE ) PVC 0.4 40 0.09 20-30 Atm+0.1 1.65
suction line
Chemical Dosing Pipe -
Chemical Dosing 146-uPVC-40-008 DWPE Dosing Unit 32 Pipe ( For DWPE ) PVC 0.4 40 0.09 20-30 5 7.5 11.25
discharge line
Chemical Dosing Pipe -
Chemical Dosing 146-uPVC-40-010 DWPE Dosing Unit 32 Pipe ( For DWPE ) PVC 0.4 40 0.09 20-30 5 7.5 11.25
discharge line
Chemical Dosing Pipe -
Chemical Dosing 146-uPVC-40-012 DWPE Dosing Unit 32 Pipe ( For DWPE ) PVC 0.4 40 0.09 20-30 5 7.5 11.25
discharge line
Page 33
Chemical Dosing Pipe -
Chemical Dosing 147-uPVC-40-007 DWPE Dosing Unit 33 Pipe ( For DWPE ) PVC 0.7 40 0.15 20-30 Atm+0.1 1.65 2.475
suction line
Chemical Dosing Pipe -
Chemical Dosing 147-uPVC-40-009 DWPE Dosing Unit 33 Pipe ( For DWPE ) PVC 0.7 40 0.15 20-30 Atm+0.1 1.65 2.475
suction line
Chemical Dosing Pipe -
Chemical Dosing 147-uPVC-40-011 DWPE Dosing Unit 33 Pipe ( For DWPE ) PVC 0.7 40 0.15 20-30 Atm+0.1 1.65 2.475
suction line
Chemical Dosing Pipe -
Chemical Dosing 147-uPVC-40-008 DWPE Dosing Unit 33 Pipe ( For DWPE ) PVC 0.7 40 0.15 20-30 5 7.5 11.25
discharge line
Chemical Dosing Pipe -
Chemical Dosing 147-uPVC-40-010 DWPE Dosing Unit 33 Pipe ( For DWPE ) PVC 0.7 40 0.15 20-30 5 7.5 11.25
discharge line
Chemical Dosing Pipe -
Chemical Dosing 147-uPVC-40-012 DWPE Dosing Unit 33 Pipe ( For DWPE ) PVC 0.7 40 0.15 20-30 5 7.5 11.25
discharge line
Page 34
Chemical Dosing Pipe -
Chemical Dosing 151-OF-uPVC-40-007 Chlorine Dosing Unit 34 Pipe ( For CHLORINE ) PVC 0.1 40 0.02 20-30 Atm+0.1 1.65 2.475
suction line
Chemical Dosing Pipe -
Chemical Dosing 151-OF-uPVC-40-009 Chlorine Dosing Unit 34 Pipe ( For CHLORINE ) PVC 0.1 40 0.02 20-30 Atm+0.1 1.65 2.475
suction line
Chemical Dosing Pipe -
Chemical Dosing 151-OF-uPVC-40-008 Chlorine Dosing Unit 34 Pipe ( For CHLORINE ) PVC 0.1 40 0.02 20-30 1.5 2.25 3.375
discharge line
Chemical Dosing Pipe -
Chemical Dosing 151-OF-uPVC-40-010 Chlorine Dosing Unit 34 Pipe ( For CHLORINE ) PVC 0.1 40 0.02 20-30 1.5 2.25 3.375
discharge line
Page 35 and 36

Odor Control PIPE 29000 1000 10.26 20-30 0.0175 0.02625 0.039375
Odor gas transmission pipe FRP
Deodorisation fan main header
Odor Control 148-O-GRP-800-001 PIPE 6.63 20-30 0.0175 0.02625 0.039375
line Odor gas transmission pipe FRP 12000 800
From Raw sewage pumping
Odor Control 105-O-GRP-600-010 PIPE 5.90 20-30 0.0175 0.02625 0.039375
station Odor gas transmission pipe FRP 6000 600
Odor Control 105-O-GRP-350-004 From Equalisation Tank PIPE 7.74 20-30 0.0175 0.02625 0.039375
Odor gas transmission pipe FRP 3500 400
Odor Control 102-O-GRP-350-001 From Mechanical coarse screen Odor gas transmission pipe PIPE FRP 2000 350 5.78 20-30 0.0175 0.02625 0.039375
From Garavity belt thickening
Odor Control 102-O-GRP-100-022 Odor gas transmission pipe PIPE FRP 1500 300 5.90 20-30 0.0175 0.02625 0.039375
unit
Odor Control 102-O-GRP-200-010 Thickend sludge sump Odor gas transmission pipe PIPE FRP 800 200 7.08 20-30 0.0175 0.02625 0.039375
Odor Control 102-O-GRP-150-003 Mechanical find screen PIPE 6.29 20-30 0.0175 0.02625 0.039375
Odor gas transmission pipe FRP 400 150
Deodorisation fan discharge
Odor Control 148-O-GRP-800-002 PIPE 5.53 20-30 0.0175 0.02625 0.039375
line Odor gas transmission pipe FRP 10000 800
Odor Control 148-O-GRP-500-002 Deodorisation fan suction line PIPE 56.62 20-30 0.0175 0.02625 0.039375
Odor gas transmission pipe FRP 40000 500