Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案
Directory Page 目录页
NEPC Ghorasal #3 Unit Re-powering Project Site Management Department Electric Automation Branch 电自专业公司
Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案
第 3 页 共 10 页
NEPC Ghorasal #3 Unit Re-powering Project Site Management Department Electric Automation Branch 电自专业公司
insulation breakdown occurs inside the tested transformer, there are two things that
will happen:
在交流耐压试验过程中,若仪表指示不抖动,被试变压器无放电声音,说明被试变压器能经
受试验电压而无异常。当被试变压器内绝缘击穿时,会出现两种情况:
●The current indicated will rise suddenly and the tested transformer will make
electric discharge sound; besides, the protective ball gap may have electric
discharge, which shows the internal breakdown of the tested transformer.
电流指示突然上升,且被试变压器发出放电响声,同时保护球系有可能放电,说明被试变压
器内部击穿。
●The amperemeter decreases suddenly, which also shows the breakdown of the tested
transformer.
电流表突然下降,也表明被试变压器击穿。
5.1.2 Judgment based on the sound of electric discharge or breakdown
由放电或击穿的声音判断
●Electric discharge due to oil gap breakdown: If the tested transformer has internal
electric discharge in the voltage boosting process and makes a sound like a metal
object bumping the oil tank, it generally shows the inertial breakdown of oil gap
and sudden change of amperemeter indication due to insufficient oil gap distance or
electric field distortion. When repeating the test, the discharge voltage will not
fall dramatically as the dielectric strength of oil gap is recovered. If the discharge
voltage is lower than that at the first time, it shows the solid insulation breakdown.
油间隙击穿放电:若在加压过程中被试变压器内部放电,发出很像金属撞击油箱的声音,一
般是由于油间隙距离不够或电场畸变,而导致油间隙惯性击穿,电流表指示突变。当重复试
验时,由于油隙抗电强度恢复,其放电电压不会明显下降。若放电电电压比第一次低,则是
固体绝缘击穿。
●Electric discharge of gas gap in oil: During the test, if the electric discharge
sound at the second time is lower than that at the first time, the instrument indicator
has no great swing and the electric discharge disappears when repeating the test,
such phenomenon is usually caused by electric discharge of gas gap in oil. In the
case of partial breakdown of gas gap, the sound is slightly intermittent and the
amperemeter indication also will not change significantly. The breakdown caused by
bubbles in oil, either penetrating or partial, may disappear during the repeated test.
This is resulted from bubble escape after disruptive discharge.
油中气体间隙放电:试验时,若第二次出现的放电声比第一次的声音小,仪表指示摆动不大,
Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案
第 5 页 共 10 页
NEPC Ghorasal #3 Unit Re-powering Project Site Management Department Electric Automation Branch 电自专业公司
再重复试验时放电又消失,这种现象常是油中气体间隙放电所致。当气隙局部击穿时声音轻
微断续,电流表指示也不会明显变动。油中气泡所引起的击穿,无论是贯穿性还是局部性的,
在重复试验时均可能消失。这是由于击穿放电后,气泡逸出所致。
●Electric discharge of metal pieces with floating potential: In the voltage boosting
process, there is electric discharge sound like bean frying inside the tested
transformer and the amperemeter indication is very unstable, which might be the
electric discharge to ground of metal pieces with floating potential (for example,
the iron core and earthing clamp are not connected together with a sheet metal during
manufacturing, and electric discharge will occur when the voltage between them
reaches a certain level).
悬浮电位的金属件放电:在加压过程中,被试变压器内部如像有炒豆般的放电声,而电流表
指示又很不稳定,这可能是带有悬浮电位的金属件对地放电(如在制造过程中铁芯和接地的
夹件未用金属片连接,当两者之间达到一定的电压时,便会发生放电)。
●Solid insulation creepage: If there is giggling electric discharge sound or clunk
and the amperemeter indication increases sharply, this is caused by internal solid
insulation creepage or coil end-to-yoke creepage. When repeating the test, the
discharge voltage will decline significantly.
固体绝缘爬电:若出现哧哧的放电声,或是沉闷的响声,电流表指示突增,这是由于内部固
体绝缘爬电,或线圈端部对铁轭爬电。再重复试验时,放电电压就明显下降。
●Electric discharge of external test circuit: In the case of insulation breakdown
of external test circuit, there will be obvious sound and discharge sparks, which
can be easily observed. During the test, there is slight corona in air or the porcelain
surface has slight electric discharge, which is normal.
外部试验回路放电:当外部试验回路绝缘击穿时,将发生明显的响声和放电火花,这是容易
观察到的。在试验时,空气中有轻微电晕或瓷件表面有很轻的放电,仍属正常现象。
6 Technical Measures for the Partial Discharge Test 局部放电试验技术措施
6.1 Long-duration induced withstand voltage and partial discharge measurement test
长时感应耐压带局部放电测量试验
In this test, the maximum working voltage at transformer HV side Um=253kV
在本次试验中,变压器高压侧最高工作电压 Um=253kV
KV KV
KV
Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案
第 6 页 共 10 页
NEPC Ghorasal #3 Unit Re-powering Project Site Management Department Electric Automation Branch 电自专业公司
图 2 长时感应耐压带局放测量接线图(C 相试验)
图 3 感应施加电压的时间顺序图
(1) Switch on the power under the voltage not higher than U2/3; increase the voltage
to 1.1Um/√3 and keep it for 5 minutes.
在不大于 U2/3 的电压下接通电源,电压上升到 1.1Um/√3,保持 5 min;
(2) Increase the voltage to U2 and keep it for 5 minutes.
电压上升到 U2,保持 5 min
(3) Increase the voltage to U1 and keep it for 24 seconds.
电压上升到 U1,保持 24sec;
Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案
第 8 页 共 10 页
NEPC Ghorasal #3 Unit Re-powering Project Site Management Department Electric Automation Branch 电自专业公司
(4) Uninterruptedly decrease the voltage to U2 immediately after the test and keep
it for at least 30 minutes, and measure the partial discharge quantity in this process.
试验后立刻不间断地将电压降到 U2,并至少保持 30min,过程中测量局部放电量。
(5) After the measurement, decrease the voltage to 1.1Um/√3 and keep it for 5 minutes.
Read the discharge quantity in this process, and then decrease the voltage to zero
quickly.
测量完成后,降低电压至 1.1Um/√3,保持 5 min。读取过程中的放电量,然后将电压迅速降
为零。
7 Safety Measures 安全措施
7.1 In order to ensure the safety of personnel and equipment, the relevant
requirements of DL 5009.1-2014 “Code of Work Safety for Power Works Construction
(Thermal Power Plant)” shall be strictly observed.
为保证人身和设备安全,应严格遵守《电力建设安全工作规程(火力发电厂部分)》DL
5009.1-2014 中有关规定。
7.2 During the AC Voltage Withstand, it is required to set up fences around test
equipment and arrange special personnel for monitoring, so as to guarantee personal
and equipment safety and prevent irrelevant persons from entering. During the test,
good communication shall be maintained between the test personnel and watch man. No
watch man may leave the job site without the consent of the test personnel. The person
responsible for raising voltage shall pay attention to the situation around the site
at any time. Once the voltmeter indicates a great swing of voltage, and the current
meter indicates a sharp increase of current, where there is smell or smoke or insulator
burning sound and abnormal phenomena such as noise appears, it’s required to
immediately reduce the voltage, disconnect the power and stop the test. The device
under test shall be discharged of electricity before it’s examined to for
troubleshooting and continuing the test.
进行交流耐压试验时,为保证人身安全和设备安全,要求必须在试验设备周围设围栏,并有
专人监护,防止无关人员误入。试验时试验人员与看守人员通讯要畅通,没有试验人员的命
令看守人员不得离开岗位。负责升压的人要随时注意周围的情况,一旦发现电压表指示摆动
很大,电流表指示急剧增加、绝缘烧焦气味或冒烟或发生响声等异常现象时,应立即降低电
压,断开电源停止试验,对被试设备进行放电后再对设备进行检查,查明原因并排除后方可
继续试验。
7.3 Before the voltage withstand test, conduct the short-circuit earthing of CT
secondary winding for the ascending flanged base of transformer. The earthing of
Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案
第 9 页 共 10 页
NEPC Ghorasal #3 Unit Re-powering Project Site Management Department Electric Automation Branch 电自专业公司
transformer core and shell as well as the earthing copper bar connection have been
done.
耐压试验前,将变压器升高座的电流互感器二次绕组应短路接地。变压器铁芯、外壳的接地
及接地连线铜牌已完成。
7.4 Arrange special personnel responsible for site safety and monitoring energized
equipment, which should be set with safety shields and hung with “Danger! High
Voltage” signs. Test equipment also should be set with safety shields. Test personnel
entering the site must wear helmets, and must fasten the safety belt when working
at heights. Persons other than test personnel should not enter the test site, which
should be monitored by specially-assigned personnel.
设专人负责现场安全,负责监视带电设备,带电设备要设置安全遮栏,并挂“止步,高压危
险”标示牌,试验设备也应设置安全遮栏。试验人员进入现场必须戴安全帽,高空作业必须
挂安全带。非试验人员不得进入试验场地,并有专人监护。
7.5 Before the test, check test equipment, ensure all components and protection
functions are normal, and take rainproofing and sun-resisting measures for test
apparatus and equipment.
试验前检查试验设备,确保各部件正常,各项保护功能正常,做好试验仪器设备的防雨、防
晒的措施。
7.6 During the test, related equipment around the tested transformer should be earthed
reliably.
试验时,被试变压器周围有关设备应可靠接地。
7.7 Do not get close to HV equipment immediately after the test. Operation is allowed
only after hanging the earthing wire and ensuring the residual electric charge is
discharged safely.
试验结束后,不要马上靠近或接近高压设备,待悬挂接地线后,确保残余电荷释放安全后,
方可进行工作。
7.8 The site should be arranged with specially-assigned persons responsible for fire
protection work, and also with sufficient qualified fire-fighting equipment.
现场要派人专门负责消防工作,并备有足够的合格消防器材。
Method Statement Of Main Transformer AC Voltage Withstand Test And Partial Discharge Test 主变交流耐压和局部放电试验方案