You are on page 1of 48

1 2 3 4 5 6

M/s. VEE VEE CONTROLS PRIVATE LIMITED


Plot No. L-3 & 4, 9th Cross, 1st Stage,
A A
Peenya Industrial Estate,
Bangalore - 560 058
Phone: +91-80-41272030 / 2050 Email ID: crm1@veeveecontrols.com
Website: www.veeveecontrols.com engg@veeveecontrols.com

BUS BAR PROTECTION PANEL


B B

Customer: M/s. FLOVEL ENERGY PVT LTD.

Client: M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY

Consultant: -----

Project name: NAM THI 2 HPP(2X4.0MW)


C C

Manufacturer: VEE VEE CONTROLS PRIVATE LIMITED

P.O. No: 4500005745 DT:22.08.2017

Job No: VV 17-124

Drawing No.: VV 17-124 E


D D

Quantity: 01

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Title Page / Cover Sheet 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / COV
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 1 in COV Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Table of contents
PAGE
Drawing section Page Page description Revision
SL. NO.

Cover Sheet
A A
1 Title Page / Cover Sheet 03 1

Table Of Content

1 Table of Content 03 2

2 Table of Content 03 3

General Arrangement

1 03 4

2 INTERNAL ARRANGEMENT 03 5

3 LEGEND DETAILS 03 6
B B
4 REAR &FOUNDATION DETAILS 03 7

5 CONSTRUCTION DETAILS 03 8

Single Line Diagram

1 SINGLE LINE DIAGRAM 03 9

2 TRIP LOGIC 03 10

3 TRIP MATRIX 03 11

Schematic Drawing

1 DC DISTRIBUTION CIRCUIT 03 12
C C
2 AC CIRCUIT 03 13

3 BUS BAR PROT. RELAY CT INPUTS 03 14

4 BUS BAR PROT. RELAY CT INPUTS 03 15

5 BUS BAR PROT. RELAY BI INPUTS 03 16

6 BUS BAR PROT. RELAY BO OUTPUTS 03 17

7 BAY CONTROL UNIT CT&PT INPUTS 03 18

8 BUS BAR PROT. RELAY BO OUTPUTS 03 19

9 86BB-Z1 TRIPPING CIRCUIT 03 20

D
10 86BB-Z2 TRIPPING CIRCUIT 03 21 D

11 50LBB TRIPPING CIRCUIT 03 22

12 AUX. CONTROL CIRCUIT 03 23

13 AUX. CONTROL CIRCUIT 03 24

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Table of Content 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TOC
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 2 in TOC Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Table of contents
PAGE
Drawing section Page Page description Revision
SL. NO.

Schematic Drawing
A A
14 AUX. CONTROL CIRCUIT 03 25

15 AUX. CONTROL CIRCUIT 03 26

16 ANNUNCIATOR FRONT VIEW 03 27

17 ANNUNCIATOR CIRCUIT 03 28

18 52 BC OPEN & CLOSE CIRCUIT 03 29

19 52 BC OPEN & CLOSE CIRCUIT 03 30

20 89 BC-1&2 OPEN &CLOSE CIRCUIT 03 31

21 INDICATION CIRCUIT 03 32

B 22 POTENTIAL FREE CONTACTS FOR SCADA 03 33 B

23 POTENTIAL FREE CONTACTS FOR SCADA 03 34

24 POTENTIAL FREE CONTACTS FOR EVN 03 35

25 POTENTIAL FREE CONTACTS FOR EVN 03 36

Reports
Terminal Diagram

1 Terminal Diagram 03 37

2 Terminal Diagram 03 38

3 Terminal Diagram 03 39
C C
4 Terminal Diagram 03 40

5 Terminal Diagram 03 41

6 Terminal Diagram 03 42

7 Terminal Diagram 03 43

8 Terminal Diagram 03 44

9 Terminal Diagram 03 45

10 Terminal Diagram 03 46

11 Terminal Diagram 03 47

D
Reports D
Bill Of Materials

1 BILL OF MATERIAL 03 48

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Table of Content 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TOC
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 2 OF 2 in TOC Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A
2115
E-mail : contact@flovel.net Web : http://www.flovel.net
MNP X1

2000 ANN
1 2 9 10
3 4 11 12
1900 5 6 13 14
7 8 15 16

1800

1700

1600
X3 P746 X4

1500
P14DG
1400 P746

B B
PB1 PB2 PB3 PB4 PB5 EMERGENCY STOP

1300 86BB-Z2 RESET


ANN. ACCEPT ANN. RESET86BB-Z1 RESET 50LBB RESET

1200 REAR FRONT


2000

BCS1 BCS2 BCS3 HINGED FIXED


1100 DOOR

2115
DOOR
1000 X9 SS1 X11
MVAXM1

MVAX31
900
195

295
800
X6 X7 X8

700
MVAJM15

MVAJM15

MVAJM15
86BB-Z1

86BB-Z2

50LBB
600
SEM2 115KV BUS SEM1
SEM3
C C
500 SEM4 SEM5

VAA11
400 80DC

300 RTB1
X13 X14
200
15

RTB2 RTB3
EARTH BUS
25x10mm-TINNED Cu.
100

100
15mm ANTI
ANTI VIBRATION VIBRATION PAD
PAD
O
750 25
800 25
100

800

FRONT VIEW SIDE VIEW


D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMEMTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
EXTERNAL ARRANGEMENT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / GA
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 5 in GA Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

K1 K2 K3 K4 K5 K6 K7 K8

H1 H2 BZ
PB6
A SS2
FOR VVC CABLES A

WDX-1 WDX-2 K9 K10 K10A K11 K12 K13

FOR VVC CABLES


K25 K26 K27 K28 K29 86Z2X
FOR VVC CABLES

FOR VVC CABLES


FOR VVC CABLES

FOR VVC CABLES


FOR VVC CABLES
K14 K15 K16 K17 K18 K19 K20 K21
86Z1X 50LBBX
FOR VVC CABLES

F1
F2
F3
F4

F6
F7
F8
F5
FOR VVC CABLES
K22 RL6X 195X 295X RL5X RL1X K23 K24
80AC

FOR VVC CABLES

F10

F11
F9
R1 R2 R3 R4 FOR VVC CABLES

89 BC1 ES1

X17
1-4
1-14
FOR VVC CABLES

X1
B B

2000

2000
DCTB ACTB

89 BC-2ES2
1-4

X18
1-4
X3

X8
1-4

1-4
1-4 1-4
FOR VVC CABLES

FOR VVC CABLES


CTTB1-TO-CTTB6

52 BC

X22
X13

1-16
FOR FIELD CABLES

X4
1-3

1-3
FOR VVC CABLES

X13A
1-16

FOR FIELD CABLES


1-10

1-10
X11
1-4

89 BC-1
X5

X23
1-6
X2
1-4

1-10

1-10
X19 X12
X6

89 BC-2

X24
1-6
X10
1-4

X7
1-3

1-3
X17-18

1-18

89 BC1 ES1
1-4

X14

X25
X20

1-4
X9
1-10

1-10
C C
X25
1-4

89 BC-2ES2
TB1
1-17

X26
X26

1-4
1-4

SH
15

15
750 750

MOUNTING PLATE MOUNTING PLATE


SIDE VIEW (INTERNAL) SIDE VIEW (INTERNAL)
D D

NOTE:-
IG TENTATIVE(FINAL WILL BE PROVIDE WITH ASBUILT DRAWING)

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
INTERNAL ARRANGEMENT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / GA
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 2 OF 5 in GA Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

LEGEND DETAILS LEGEND DETAILS


SL No. TAG DESCRIPTION SL No. TAG DESCRIPTION
X1 MNP BUS PROTECTION PANEL 1 PB1 ANN. TEST/DC FAIL TEST(INSIDE THE PANEL)
X2 ANN ANNUNCIATOR 2 PB2 ANN.ACCEPT/DC FAIL ACCEPT
X3 P746 BUSBAR PROTECTION RELAY 3 PB3 ANN. RESET
X4 P14DG BAY CONTROL RELAY FOR BUS COUPLER 4 PB4 86BB-Z1 RESET
X5 195 TRIP COIL -1 SUPERVISION RELAY 5 PB5 86BB-Z2 RESET
X6 295 TRIP COIL -2 SUPERVISION RELAY 6 PB6 50LBB RESET
B B

X7 86BB-Z1 ZONE-1 MASTER TRIP RELAY 7 EPB EMERGENCY STOP


X8 86BB-Z2 ZONE-2 MASTER TRIP RELAY 8 BCS1 B/C CB CONTROL SWITCH
X9 50LBB LOCAL BACK UP MASTER TRIP RELAY 9 BCS2 ISOLATOR-1 SELECTOR SWITCH
X10 80DC DC SUPERVISION RELAY 10 BCS3 ISOLATOR-2 SELECTOR SWITCH
X11 RTB1 RELAY TEST TERMINAL BLOCK(P746) 11 SS1 LOCAL/REMOTE SELECTOR SWITCH
X12 RTB2 RELAY TEST TERMINAL BLOCK(P746) 12 SS2 PANEL/BCU SEELCTOR SWITCH(INSIDE THE PANEL)
X13 RTB3 RELAY TEST TERMINAL BLOCK(P746)
SEM-1 BUS COUPLER CB
SEM-2 BUS ISOLATOR -1
C SEM-3 BUS ISOLATOR -2 C

SEM-4 EARTH SWITCH-1


SEM-5 EARTH SWITCH-2

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
LEGEND DETAILS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / GA
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 3 OF 5 in GA Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A
MCSP-1

PUNCHED LOUVERS
WITH PERFORATED SHEET
FRONT
LOUVERS WITH FAN LOUVERS

800

100 600 100


∅14X 4 HOLES
B B

GLAND PLATE

GLAND PLATE
2000

300X500mm

300X500mm
2115

750
700
DRAWING
POUCH

C C

LOUVERS LOUVERS
15

REAR
100

D D
800
REAR VIEW

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
REAR &FOUNDATION DETAILS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / GA
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 4 OF 5 in GA Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

CONSTRUCTION DETAILS & GENERAL NOTES:- 5. LABELS & LEGEND DETAILS:

1. ENCLOSURE DETAILS: a) PATTERN LETTERS ENGRAVED ON BLACK


BACK GROUND
A a) ENCLOSURE DIMENSION 2115(H)x800(W)x750(D) A
b) MATERIAL ANODISED ALUMINIUM STRIPS
b) LOAD BEARING MEMBER 2.5mm, CRCA
c) NON LOAD BEARING MEMBER 2mm, CRCA 6. VOLTAGE & CURRENT DETAILS:
d) GLAND PLATE THICKNESS 3mm, CRCA a) SYSTEM VOLTAGE & FREQUENCY 115kV, 50Hz
e) BASE FRAME HEIGHT 100mm, ISMC b) CONTROL SUPPLY 220V DC
f) ANTI VIBRATION PAD 15mm THICK c) AUXILIARY SUPPLY 230V AC,50Hz
g) ENCLOSURE PROTECTION IP 54 d) PT SEC. VOLTAGE 110V AC
h) PANEL TYPE SIMPLEX, FLOOR MOUNTING e) CT SEC. CURRENT 1A
i) NEOPRENE CROSS LINKED POLY ETHYLENE 7. CABLE ENTRY DETAILS:
j) WEIGHT OF THE ENCLOSURE apprx. 500kgs.
a) CABLE ENTRY BOTTOM
2. SHADE & PAINTING DETAILS:
B 8. STANDARD REFERENCE: IEC 60439 B

a) PAINTING TYPE POWDER COATED


b) SHADE INTERIOR RAL 7035
c) SHADE EXTERIOR RAL 7035 9. 20% SPARE TERMINAL BLOCKS WILL BE PROVIDED.
d) THICKNESS 80 Microns(min.)
e) BASE FRAME BLACK
f) FINISHING TYPE STRUCTURE

3. BUS BAR DETAILS:

a) EARTH BUS BAR SIZE 25x6mm, TINNED COPPER

4. CABLE DETAILS:
C a) GRADE 1.1kV FRLS PVC INSULATED FLEXIBLE MULTISTRAND COPPER C

b) CABLES FOR CT SEC. WIRING 4Sq.mm RED,YELLOW,BLUE & BLACK FOR R,Y,B &
NEUTRAL RESPECTIVELY
c) CABLES FOR PT SEC. WIRING 2.5Sq.mm RED,YELLOW,BLUE & BLACK FOR R,Y,B &
NEUTRAL RESPECTIVELY
d) CABLES FOR AUXILIARY 2.5Sq.mm BLACK
CIRCUIT (230V AC)
e) CABLES FOR CONTROL 1.5Sq.mm GREY
CIRCUIT (220V DC)

f) POTENTIAL FREE CIRCUIT 1.5Sq.mm GREY


g) SHIELD CABLE 1Sq.mm 2 CORE SHIELDED
D D
h) ANN. CIRCUIT 1 Sq.mm WHITE
i) CABLES FOR EARTHING 2.5Sq.mm YELLOW WITH GREEN STRIP LINE
j) CABLES FOR SCADA 1.5Sq.mm ORANGE COLOUR

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
CONSTRUCTION DETAILS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / GA
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 5 OF 5 in GA Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

110kV OUTGOING FEEDER-1 110kV OUTGOING FEEDER-2

89L1-2 89L2-2

L1-CT L2-CT
P746

B B

52L1 52L2

89L1-1 89L2-1

52BC BC-CT
110KV BUS-1 110KV BUS-2

89BC-1 89BC-2
89GT1-2 89GT2-2

C C

52GT1-2 52GT2-2
P14D
GT1-CT2 GT2-CT2

GT-1 FEEDER GT-2 FEEDER

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
SINGLE LINE DIAGRAM 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SLD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 3 in SLD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

87BB-BUS SECTION -1 ZONE-1


(L1-CT,GT1-CT2,BC-CT) AND
86BB-Z1
87BB-BUS SECTION -2 ZONE-2
(L2-CT,GT2-CT2,BC-CT)

FROM 87CZ CHECK ZONE AND 86BB-Z2


B
P746 (L1-CT,L2-CT,GT1-CT2,GT2-CT2)
B

50 LBB
L1-CT,L2-CT,GT1-CT2,GT2-CT2,BC-CT
50 LBB

C 52 BC CLOSE C
AND

FROM 50,51,50N,51N
P14DG

D D

TRIP LOGIC
CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS
Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
TRIP LOGIC 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SLD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 2 OF 3 in SLD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

6.3kV
52L1 52L2 52GT1-2 52GT2-2 52BC LRMP-1 LRMP-2 INDOOR
LRMP-1 LRMP-1 TRMP-2 TRMP-2 BPP DT DT SWITCH GEAR
86L 862 86T 86T TRIP COIL-I&II ANNUNCIATOR SEND SEND PANEL-2

86BB-Z1

B B

86BB-Z2

50LBB

P746(RL-10)
50LBB LRMP-1

P746(RL-11)
50LBB LRMP-2

C P746(RL-12) C

50LBB TRMP-1

P746(RL-13)
50LBB TRMP-2

TRIP MATRIX

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
TRIP MATRIX 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SLD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 3 OF 3 in SLD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

A A
220VDC SUPPLY 220VDC SUPPLY
FROM CUSTOMER TO ADJACENT PANEL

BPP

DCTB DCTB
1 2 3 4

J1 J2
J1
J2

1 3
B F1 B
MCB 2 4
DP, 10A J3 220VDC +VE SUPPLY J3

J4 220VDC -VE SUPPLY J4

1 3 1 3 1 3 1 3
PB6 1
F2 F3 F4 F5 /16.4:D
MCB 2 4 MCB 2 4 MCB 2 4 MCB 2 4
DP, 10A DP, 10A DP, 10A DP, 10A DC FAIL 2
TEST J6A

L101 L102 K1 K2 J401 J402 J5 J6 VAA11


C C
9
80DC
10

5.1:D

8.2:A
9.1:B

5.1:A

8.2:A
9.1:B
16.2:D
16.2:D

2
1 /2.5:B
5
220VDC AUX. SUPPLY 220VDC AUX. SUPPLY 220VDC AUX. SUPPLY 220VDC AUX. SUPPLY 4
TO ANNUNCIATION TO MASTER TRIP RELAY TO P746 TO P14DG RELAY(BCU) 3 /17.2:D
CIRCUIT CIRCUIT & CONTACT MULTI.CIRCUIT (BUS BAR PROTECTION RELAY) 11
6 7 /24.5:A
14 15 /22.5:A

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
DC DISTRIBUTION CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

1 Ph, 50Hz, 1 Ph, 50Hz,


230V AC SUPPLY 230V AC SUPPLY
A FROM GMRP TO ADJACENT PANEL A

Ph Nu Ph Nu

BPP

ACTB ACTB
1 2 3 4

H1 H2 H1 H2

1 3
F6
MCB 2 4
B DP, 16A B
H3 230VAC (Ph) SUPPLY H3

H4 230VAC (Nu) SUPPLY H4

1 3 1
F7 1 3 80DC
MCB 2 4 /1.5:C 2 5
DP, 6A 1 3 F9
F8 MCB 2 4 H14
H5 H7 DP, 6A
MCB 2 4 5 H14
DP, 6A
H9 13

FAIL ACCEPT
21
PB1

REMOTE DC
1
1 80AC /16.4:C 80AC
1 /2.6:C /2.6:C 14
1 TH2 22 DC FAIL 2
H9B H10 H11 ACCEPT
TH1 2
6 H13 H13
C DLS 2 PS H8A H9A H12 H13 C
2
1 FAN
H8
x1
H6 PE
x1 BZ
A1
x2
x1
CFL 2 80AC
A2

16.3:C
16.3:C
SH
x2 x2

H4 H4
CUBICAL UTILITY SOCKET 230VAC AUX. SUPPLY BUZZER
13 14 /2.6:C
HEATER ON PANEL LAMP DC FAIL
TO ANNUNCIATION 21 22 /2.5:C
EXHAUST CIRCUIT
FAN

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
AC CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 2 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

P746
P746 BUSBAR PROTECTION RELAY LED CONFIGARATION
-CTTB1
1 1A10 LED-1 IDMT O/C LINE-1
s2 -RTB1
R D24 87BB LED-2 INST O/C LINE-1
1A11 50LBB
A s1
A
2 1
L1-CT /A(1) LED-3 IDMT O/C LINE-2
1A71 D23 50/
200/400/600/800/1A 51
s2 LED-4 INST O/C LINE-2
CORE1: CL 5P20,15VA 2 1A30
FROM LINE-1 SIDE Y
s1 1A31 D26 LED-5 IDMT O/C GT-1
4 3
D25
/B(1) LED-6 INST O/C GT-1
1A71
s2
B LED-7 IDMT O/C GT-2
s1 3 1A50 D28
1A51 LED-8 INST O/C GT-2
6 5
/C(1)
1A71 D27 LED-9 IDMT O/C B/C

LED-10 INST O/C B/C


8 7
4 1A70
LED-11 50LBB TO LINE-1

LED-12 50LBB TO LINE-2

B -RTB1 LED-13 50LBB TO GT1 B

2A11 D18
LED-14 50LBB TO GT2
-CTTB2 10 9
/A(2)
1 2A10 2A71 D17 LED-15 TRIP DOWN ZONE-1
s2
LED-16 TRIP DOWN ZONE-2
R
2A31 D20
s1 LED-17 SPARE
L2-CT 12 11
2 2A30
200/400/600/800/1A 2A71 D19
/B(2)
CORE1: CL 5P20,15VA s2
LED-18 LCD RESET
FROM LINE-2 SIDE Y
s1 D22
2A51
3 2A50
14 13
/C(2)
s2 2A71 D21
B
s1
16 15
4 2A70

C C

-RTB2

3A11 D12

-CTTB3 2 1
/A(3)
1 3A10 D11

s2
R
GT1 3A31 D14
s1
60/80/120/1A 2 4 3
3A30 /B(3)
CORE2: CL 5P20,15VA D13
FROM TRAFO (HV SIDE) s2
Y
s1 D16
3A51
3 3A50
6 5
/C(3)
s2 D15
D D
B
s1

4 3A71
3A70
8 7

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BUS BAR PROT. RELAY CT INPUTS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 3 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

P746 BUSBAR PROTECTION RELAY


-CTTB4
1 4A10

s2 -RTB2
R 4A11 F24 87BB 50LBB
A GT2 A
s1 10 9
60/80/120/1A /A(4)
4A71 F23 50/
CORE2: CL 5P20,15VA
51
FROM TRAFO HV SIDE s2
2 4A30
Y
s1 4A31 F26
12 11
/B(4)
4A71 F25
s2
B
s1 3 4A50 F28
4A51
14 13
/C(4)
4A71 F27

16 15
4 4A70

B B

-RTB3
5A11 F18

-CTTB5 2 1
/A(5)
1 5A10 5A71 F17

s2
R
5A31 F20
s1
2 4 3
5A30 /B(5)
B/C 5A71 F19
200/400/600/800/1A s2
CORE1: CL 5P20,15VA Y
s1 F22
5A51
3 5A50
6 5
/C(5)
s2 5A71 F21
B
s1
C 8 7
C
4 5A70

-CTTB6
1
6A11 F12

/A(6)
6A71 F11
CIRCUIT GRMP(P14DB)

2
6A31 F14
SPARE
TO PROTECTION

/B(6)
6A71 F13

3
6A51 F16

/C(6)
6A71 F15
D D
4

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BUS BAR PROT. RELAY CT INPUTS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 4 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

-VE
220V DC AUX. SUPPLY
A 1.4:C A

J402

J402

P746

G11

G13

G15
-M1

E11

E13

E15

G1

G3

G5

G7

G9
E1

E3

E5

E7

E9
220V DC POWER SUPPLY

IEC61850 COM.
COMMUNICATION

B B
-
+

G10

G12

G14

G16
E10

E12

E14

E16
M2

G2

G4

G6

G8
E2

E4

E6

E8

J401 J403 J404


J405 J406 J407 J408 J409 J410 J411 J412 J413 J414 J415 J416 J417 J401

-TB1 1

86BB-Z2
/10.3:B
13 13 13 13 13 13 13 13 9
86BB-Z1
13 13 13 13 /9.3:B 9
K1 K2 K3 K4 K5 K6 K7 K8 K9 K15 K19 K14
/12.1:C /12.3:C 14 /12.4:C 14 /12.5:C 14 /12.5:C 14 /13.1:B 14 /13.5:B 14 /14.2:C 14 /13.4:B 14 11
14 /12.2:C 14 /12.2:C 14 /12.3:C 14 11 2
C C

J401 J401 J401 J401 J401 J401 J401 J401 J401 J401 J401 J401 J401 J401 J401 J401
GT2 CB CLOSE
MASTER TRIP RELAY

B/C SF6 PR LOCK OUT 50LBB


GT2 ISOLATOR CLOSE

B/C CB CLOSE
GT1 ISOLATOR-2 CLOSE

89 BC-1 CLOSE

ZONE-2 MASTER TRIP RELAY


GT1 CB CLOSE

89 BC-2 CLOSE
LINE-2 ISOLATOR-1 CLOSE

SPARE
LINE-1 CB CLOSE

LINE-2 CB CLOSE
LINE ISOLATOR-1 CLOSE

BUS BAR ZONE-1

1.3:C

+VE
220V DC
D AUX. SUPPLY D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BUS BAR PROT. RELAY BI INPUTS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 5 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

IDMT/INST O/C (50/51) FOR LINE-1

IDMT/INST O/C (50/51) FOR LINE-2

IDMT/INST O/C (50/51) FOR GT1

IDMT/INST O/C (50/51) FOR GT2


TO ZONE-1 MASTER TRIP RELAY

TO ZONE-2 MASTER TRIP RELAY

TO 50LBB MASTER TRIP RELAY

50LBB TO LINE-1(86)

50LBB TO LINE-2(86)

50LBB TO GT1(86)T
P746 RELAY FAULT

(FOR DT SEND)

(FOR DT SEND)

(6.3KV SWG-2)
50LBB TO GT2
B/C CB TRIP

SPARE

SPARE

SPARE

SPARE
9.2:C 10.2:C 11.2:C 15.1:C 15.2:C 15.2:C 15.3:C
12.6:B
X2 1 X2 3 X2 5 X2 7 X2 9 X2 11 X2 13 X2 15 X2 17

B B

K1 K1 K1 7U1 7U3 7U5 7U7 7U9 K1 7U1 K1 K1 K1 K1 7U13 7U15 7U17


P746

L13

L14

L16

L17
L11
L1

L3

L5

L7

L9

K13

K14

K16

K17
K11
K1

K3

K5

K7

K9
M12
WATCH DOG

RL13

RL14
RL5

RL6

RL7

RL8

RL10

RL11

RL12

RL15

RL16
RL1

RL2

RL3

RL4

RL9
M11

L10

L12

L15

L18

K10

K12

K15

K18
L2

L4

L6

L8

K2

K4

K6

K8
C C

K11 K102 K104 7U2 7U4 7U6 7U8 7U10 K106 7U12 K42 K43 K44 K45 7U14 7U16 7U18

2 4 6 8 10 11.3:C 12 15.1:C 15.2:C 15.2:C 15.3:C 14 16 18


12.6:B 9.3:C 10.3:C

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BUS BAR PROT. RELAY BO OUTPUTS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 6 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

P14DG NUMERICAL RELAY

-CTTB7
1 -RTB3 FUNCTION KEYS
A 6A12 6A13 21 A
10 9 F1:B/C CB CLOSE
22
IA 50 50N
F2:B/C CB OPEN
2
6A32 6A33 23
FROM CORE-2 12 11 51 51N
200/400/600/800/1A 24
IB
15VA,CL:5P20
3
6A52 6A53 25 25 P14DG
14 13 LED CONFIGARATION
IC
26
LED-1 IDMT O/C
4
6A72 6A73 27
LED-2 INST O/C
16 15
In
28 LED-3 IDMT E/F

LED-4 INST E/F


B B
LED-5 Z1/Z2 OPTD

LED-6 CHECK SYNC OK


F10 LED-7 LIVE LINE

LED-8 LIVE BUS


X10 1E11 1 2 2E21A 17

1
3 4 2E41A VA

5 6 18
1E31 2E61A
FROM BUS PT-2 2 VB
CORE:2 7 8 2E81A
F1- B/C CB CLOSE
CLASS:3P,30VA
19
4P,6A
1E51 MCB F2- B/C CB OPEN
VC
3 20
C
F3- LED RESET C

1E71
4
F11

X10 1E12 1 2 3E21A 15

5 V.CHECK
FROM BUS PT-1 16 SYN
CORE:2
CLASS:3P,30VA 1E52 3 4 3E41A IEC61850 COM.
COMMUNICATION
6 DP,6A
MCB

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BAY CONTROL UNIT CT&PT INPUTS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 7 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

AUX. SUPPLY
1.4:C 1.4:C

P14DG NUMERICAL RELAY


J5

J6 AUX.SUPPLY
13

A A
14

86BB-Z1 86BB-Z2
L1
1 3 J5A 5 7 J5A1 46
ZONE-1 MASTER TRIP
NOT OPTD. /9.3:B /10.3:B

J5 J6
K9 L2
B/C BREAKER CLOSE 44 43 J5B 48 3 K1
/12.6:B
/13.1:B
WD PROTECTION RELAY FAULT .(ANN)
5 K12
/12.6:B

J6 52

K10 L3 32 K1
32 31 J5C /14.6:B
B/C BREAKER OPEN 50
/13.2:B RL1 BACK UP O/C&E/F OPTD
30 K31
B /14.6:B B

K15 L4 36 K1
14 13 /15.5:A
BUS-1 ISOLATOR CLOSE J5D 45
/13.5:B RL2 34 K38 CHECK SYN O/P
/15.5:A

40 K1
K19 L5 /9.2:C
84 83 J5E 47 TO ZONE-1 MASTER TRIP RELAY
BUS-2 ISOLATOR CLOSE /14.2:C
RL3 38 K102
/9.3:C

44 K1
/10.2:C
TO ZONE-2 MASTER TRIP RELAY
86BB-Z1 RL4 42 K104
80BB ZONE-1 &ZONE-2 OPTD L6 /10.3:C
19 17 J5F 49

/9.3:B 31 K1
/14.5:B
86BB-Z2 TO B/C CB CLOSE MULTIPLICATION
RL5 29 K30
19 17 /14.5:B

C /10.3:B 35 K1 C
/14.4:B
TO B/C CB TRIP MULTIPLICATION
RL6 33 K27
/14.4:B

K12 39 K1
A 1 L7 /15.3:A
14 13 J5I J5G 51 LIVE LINE
B/C CLOSE CMD /13.3:B RL7 37 K36
BCS1 /15.3:A

43 K1
N
C
T

/15.4:A

J6 55
LIVE BUS
RL8 41 K37
/15.4:A
B 1 L8
J5H 53
B/C TRIP CMD BCS1
N
C
T

D IEC61850 COM. D
COMMUNICATION

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BUS BAR PROT. RELAY BO OUTPUTS 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 8 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A UPP A

K1
/1.3:C 10.1:B

K2
/1.3:C 10.1:B

B 86BB-Z1 B
MVAJM15
X3 5 REMOTE X3 6
RESET
RL1/10

K101
PB4
1 2 25
RESET K1 K101
4 7
/11.3:B 8

RL3 27 RL1-B
K102 26
P14DG K1 40 38 K102 1 RL1 K2
9
8.5:C
23
RL1 5

BUSBAR PROTECTION RELAY(P746) K1 L1 L2 K102 28


2 K2
6.2:C 6
ZONE-1
RL1-A
3
C C
K1 X3 1
FUTURE TRIP X3 2 K102
IF ANY
86BB MASTER TRIP RELAY (ZONE-1)
K1 X3 3 FUTURE TRIP X3 4 K102
IF ANY 1 3 /8.2:A
2 4 /22.1:B
5 7 /18.1:C
6 8 /22.1:B
K1 X3 7 X3 8 K102
9 11 /5.3:C
10 12 /17.2:A
FUTURE 13 15 /18.4:A
14 16 /19.3:A
K1 X3 9 X3 10 K102
17 19 /8.2:C
18 20 /15.5:A

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
86BB-Z1 TRIPPING CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 9 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

UPP

A A

K1
/9.6:B 11.1:B

K2
/9.6:B 11.1:B

86BB-Z2 MVAJM15
X3 15 REMOTE X3 16
B B
RESET
RL2/10

K103
PB5
1 2 25
RESET K1 K103
4 7
8

RL4 27 RL2-B
K104 26
P14DG K1 44 42 K104 1 RL2 K2
9
8.5:C
23
RL2 5

BUSBAR PROTECTION RELAY(P746) K1 L3 L4 K104 28


2 K2
6.2:C 6
ZONE-2
RL2-A
3

K1 X3 11
FUTURE TRIP X3 12 K104
C C
IF ANY
86BB MASTER TRIP RELAY (ZONE-2)
K1 X3 13 FUTURE TRIP X3 14 K104
IF ANY 1 3 /18.1:C
2 4 /22.1:C
5 7 /8.3:A
6 8 /22.1:C
K1 X3 17 X3 18 K104
9 11 /5.5:C
10 12 /17.2:A
FUTURE 13 15 /18.5:A
14 16 /19.3:A
K1 X3 19 X3 20 K104
17 19 /8.2:C
18 20 /15.5:A

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
86BB-Z2 TRIPPING CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 10 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

UPP
A A

K1
/10.6:B 12.1:B

K2
/10.6:B 12.1:C

B 50LBB MVAJM15 B
X3 25 REMOTE X3 26
RESET
RL3/10

K105
PB4
1 2 25
RESET K1 K105
4 7
/9.2:B 8

27 RL3-B
K106 26
1 RL3 K2
9

23
RL8 5

K1 L17 L18 K106 28


BUSBAR PROTECTION RELAY(P746) 2 K2
6.3:C 6
RL3-A
3
C C
K1 X3 21
FUTURE TRIP X3 22 K106
IF ANY
50LBB
K1 X3 23 FUTURE TRIP X3 24 K106
IF ANY 1 3 /17.2:B
2 4 /24.3:A
5 7 /22.3:A
K1 X3 27 X3 28 K106 6 8 /22.3:B
9 11 /24.3:A
10 12 /22.1:B
FUTURE
13 15 /22.3:B
K1 X3 29 X3 30 K106 14 16 /24.1:B
17 19 /22.3:B
18 20 /15.6:A

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
50LBB TRIPPING CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 11 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

B K1 K1 K1 K1 K1 K1 K1 K1 K1 B
/11.6:B 13.1:A

X1 1 X1 3 X1 5 X1 7 X1 9 X1 11 X1 13 X1 15
M11 3

FROM LINE-1CB FROM LINE-1 FROM LINE-2CB FROM LINE-2


GT1 CB CLOSE
GT1 ISOLATOR
GT2 CB CLOSE
GT2 ISOLATOR P746 WD
ISOLATOR ISOLATOR CLOSE CLOSE 6.2:C 8.5:B
M12 5
2 4 6
8 10 12 14 16

K4 K5 K6 K7 K8 K9 K10 K11 K12


K3

A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
K1 K2 K3 K4 K5 K6 K7 K8 WDX-1 WDX-2
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2

C C

/11.6:B
K2 K2 K2 K2 K2 K2 K2 K2 K2 K2
13.1:C
LINE CB-1 CLOSE BUS BAR PROTECTION
LINE ISOLATOR-1 CLOSE LINE CB-2 CLOSE LINE-2 ISOLATOR CLOSE GT1 CB CLOSE GT1 ISOLATOR CLOSE GT2 CB CLOSE GT2 ISOLATOR CLOSE RELAY FAULTY BCU RELAY FAULTY
13 14 /5.1:C 13 14 /5.2:C 13 14 /5.2:C 13 14 /5.2:C 13 14 /5.2:C 13 14 /5.3:C 13 14 /5.3:C 13 14 /5.3:C 13 14 /17.2:C 13 14 /17.2:C
43 44 /24.5:B 43 44 /24.5:B 43 44 /24.5:B 43 44 /24.5:C 43 44 /24.5:C 43 44 /24.5:D 43 44 /24.5:D 43 44 /24.5:D 43 44 /24.3:C
53 54 /22.5:B 53 54 /22.5:B 53 54 /22.5:B 53 54 /22.5:C 53 54 /22.5:C 53 54 /22.5:D 53 54 /22.5:D 53 54 /22.5:D 53 54 /22.3:C

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
AUX. CONTROL CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 12 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

K1 K1 K1 K1 K1 K1 K1 K1 K1
/12.6:B /14.1:B

X1 17 X1 19 X1 21 X1 23 X1 25 X1 27 X1 29 X1 31

B/C CB SPRING B/C CB B/C CB B/C CB SF6 PR. 89BC-1


B/C CB CLOSE B/C CB OPEN CHARGED LOCAL LOCK OUT CLOSE 89 BC-1 OPEN
REMOTE

18 20 22 34 26 28 30 32
B B

K13 K14 K15 K16 K17 K18 K19 K20

A1 A1 A1 A1 A1 A1 A1 A1 A1
K9 K10 K10A K11 K12 K13 K14 K15 K16
A2 A2 A2 A2 A2 A2 A2 A2 A2

/12.6:C
K2 K2 K2 K2 K2 K2 K2 K2 K2
/14.1:C
B/C CB CLOSE B/C CB OPEN B/C CB SPRING B/C CB B/C CB B/C CB SF6 PR. 89 BC-1 89 BC-1 OPEN
CHARGED LOCAL REMOTE LOCK OUT CLOSE
13 14 /5.4:C 21 22 /21.2:B 13 14 /23.1:A 13 14 /5.4:C 13 14 /20.1:B
13 14 /23.1:B 13 14 /8.2:C 13 14 /23.1:C 13 14 /5.5:C
C 43 44 /8.3:B 31 32 /8.3:B 43 44 /25.1:A 13 14 /8.3:B 21 22 /20.2:B C
43 44 /25.1:B 43 44 /25.1:B 43 44 /25.1:C 43 44 /25.1:C
53 54 /21.1:B 53 54 /20.1:A 43 44 /18.2:B 43 44 /25.3:A
63 64 /23.1:A 63 64 /20.2:A 53 54 /23.1:B 53 54 /17.2:B 53 54 /21.2:B 53 54 /21.3:B
73 74 /25.1:B 73 74 /20.4:A 83 84 /23.1:C 63 64 /23.3:A 83 84 /23.3:A
83 84 /20.5:A 73 74 /25.3:B

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
AUX. CONTROL CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 13 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

K1 K1 K1 K1 K1 K1 K1 K1 K1 K1 K1 K1
/13.6:A /15.1:A

X1 33 X1 35 X1 37 X1 39 X1 41 X1 43
35 5 5 31 32
89 BC-1 89 BC-2 89 BC-2 P14D P14D P14D
B MCB TRIP
SS1- LOCAL 89 BC-2 OPEN SS1-REMOTE
MCB TRIP 195 295 B
CLOSE RL6 /18.5:A /19.4:A RL5 RL1
8.5:C 33 7 7 8.5:C 29 8.5:B 30

34 36 38 40 42 44

K21 K22 K23 K24 K25 K26 K27 K28 K29 K30 K31

A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
K17 K18 K19 K20 K21 K22 RL6X 195X 295X RL5X RL1X
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2 A2

/13.6:C
K2 K2 K2 K2 K2 K2 K2 K2 K2 K2 K2 K2
/15.1:B
89 BC-1 LOCAL 89 BC-2 89 BC-2 OPEN REMOTE 89 BC-2 B/C CB TRIP TRIP COIL-1 HEALTHY TRIP COIL-2 HEALTHY CLOSING BACK UP O/C&E/F
MCB TRIP CLOSE MCB TRIP MULTIPLICATION MULTIPLICATION MULTIPLICATION
C C
13 14 /5.4:C 13 14 /23.3:C 13 14 /18.1:A 13 14 /18.1:A 13 14 /18.1:B 13 14 /17.2:B
13 14 /23.3:D 13 14 /18.4:A
13 14 /23.3:B 13 14 /20.1:C 43 44 /18.2:B 13 14 /20.2:B 43 44 /24.3:D
21 22 /20.5:B 43 44 /19.2:B 21 22 /22.3:B 21 22 /22.3:C
43 44 /25.3:B 23 24 /20.2:C 23 24 /20.3:B 43 44 /25.3:D
53 54 /21.3:B 43 44 /25.3:C 31 32 /24.3:B 31 32 /24.3:C 53 54 /22.3:D
23 24 /20.4:C 63 64 /23.3:C 53 54 /20.4:B 33 34 /20.4:B 43 44 /25.1:D 43 44 /25.1:D
23 24 /20.5:C 73 74 /25.3:D 63 64 /21.4:B 43 44 /20.5:B 53 54 /23.1:C 53 54 /23.1:D
83 84 /8.3:B

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
AUX. CONTROL CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 14 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

K1 K1 K1 K1 K1 K1 K1 K1 K1 K1
/14.6:B 15.1:C

A A
X1 45 X1 47
39 43 36 18 18 18
1 COMMON P14D P14D P14D
CLOSE 89BC-1E CLOSE 89BC-2E 86BB-Z1 86BB-Z2 50LBB
SS2 RL7 RL8 RL2
PANEL
PANEL/BCU
8.5:C 37 8.5:D 41 34 /9.3:B 20 /10.3:B 20 /11.3:B 20
SEL. SWITCH 8.5:B
BCU 46 48
A1 B1
K32 K33 K34 K35 K36 K37 K38 K39 K40 K41

A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
K23 K24 K25 K26 K27 K28 K29 86Z1X 86Z2X 50LBBX
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2

B B
/14.6:C
K2 K2 K2 K2 K2 K2 K2 K2 K2 K2 K2
15.1:D
CHECK OK 86BB ZONE-1 86BB ZONE-2 50LBB
PANEL BCU CLOSE 89BC-1E CLOSE 89BC-2E LIVE LINE LIVE BUS

13 14 /18.1:B 13 14 /23.5:A 13 14 /23.5:C 13 14 /18.2:B 13 14 /18.2:B 13 14 /18.3:C 13 14 /24.1:A 13 14 /24.1:A 13 14 /24.3:B


13 14 /18.1:B
43 44 /19.2:A 21 22 /21.4:B 21 22 /21.5:B 21 22 /18.2:C 21 22 /18.2:C 21 22 /24.1:B 21 22 /24.1:C 43 44 /24.3:B
43 44 /19.2:A
53 54 /18.3:A 21 22 /20.2:A 21 22 /20.4:A 43 44 /18.3:B 43 44 /18.3:C 31 32 /24.1:B 31 32 /24.1:C
53 54 /18.4:A 43 44 /22.1:A 43 44 /22.1:B
31 32 /18.2:C 31 32 /18.2:C
31 32 /25.5:A 31 32 /25.5:B
43 44 /21.4:B 43 44 /21.5:B
61 62 /23.5:A 61 62 /23.5:C
83 84 /25.5:A 83 84 /25.5:B

/15.6:A
K1 K1 K1 K1 K1
21.1:A

K3 K5 K7 K9
P746 P746 P746 P746
C C
RL10 RL11 RL12 RL13
6.4:C K4 6.4:C K6 6.4:C K8 6.4:C K10

K42 K43 K44 K45

A1 A1 A1 A1
R1 R2 R3 R4
A2 A2 A2 A2

K2 K2 K2 K2 K2
/15.6:B 21.1:C

50LBB TO LINE-1(86) 50LBB TO LINE-2(86) 50LBB TO GT1(86)T 50LBB TO GT2


D (FOR DT SEND) (FOR DT SEND) (6.3KV SWG-2) D
83 84 /25.5:C 83 84 /25.5:C 83 84 /25.5:D 83 84 /25.5:D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
AUX. CONTROL CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 15 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

BPP

ANNUNCIATOR

W1 W2 W3 W4
A A

ZONE-1 PROTECTION ZONE-2 PROTECTION


BACKUP O/C&E/F OPTD SPARE
OPTD OPTD

TRIP TRIP TRIP TRIP


W5 W6 W7 W8

50LBB INITIATION B/C CB SPARE


SPARE
SF6 PR. LOCK OUT

TRIP TRIP TRIP TRIP


W9 W10 W11 W12

B/C CB TRIP COIL-1 B/C CB TRIP COIL-2 BUSBAR PROTECTION


UNHEALTHY UNHEALTHY RELAY FAULT BACK UP RELAY FAULT
B B

ALARM ALARM ALARM ALARM


W13 W14 W15 W16

SPARE SPARE SPARE DC FAIL

ALARM ALARM ALARM ALARM

AUX. SUPPLY

+VE -VE C TA C NTA L N E TEST ACK RST COM RS+ RS-

C C

2RS+ 2RS-

H10 H11 L105 L106 L107 L108


SH2
X4
1
L103 L104 X5 1 X5 2 X5 3
3 ANN. ACCEPT
FROM SCADA X4 3
3 3
PB1
2 ANN. RESET RS485 COM PORT
2.4:C 2.5:C 4 FROM SCADA
/2.6:C PB2
x1 x1 4
PB6 4 4
H1 H2 /1.5:C
x2 x2
L101 L102 230VAC AUX.
L102 SUPPLY
HOOTER FOR HOOTER FOR
TRIP ALARM NON TRIP ALARM

D /1.2:C D
220VDC
AUX.
/1.2:C
SUPPLY

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
ANNUNCIATOR FRONT VIEW 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 16 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

BPP

ANNUNCIATOR 8 WINDOW

A A
L109
C

86BB-Z1
10 12 L110
W1 ZONE-1 PROTECTION OPTD TRIP
/9.3:B

86BB-Z2
10 12 L111 ZONE-2 PROTECTION OPTD
W2 TRIP
/10.3:B

RL1X
13 14 L112
W3 BACK UP O/C &E/FOPTD TRIP
/14.6:C

X6 1 2 L113
W4 SPARE TRIP

50LBB
B
1 3 L114 B
W5
50LBB INITIATION TRIP
/11.3:B

K14
53 54 L115
W6 B/C CB SF6 PR. LOCK OUT TRIP
/13.4:B

X6 3 4 L116 SPARE
W7 TRIP

X6 5 6 L117
W8 SPARE TRIP

195
1 3 L118
W9 B/C CB TRIP COIL-1 UNHEALTHY ALARM
/18.5:A

295
1 3 L119
W10 B/C CB TRIP COIL-2 UNHEALTHY ALARM
C /19.4:A C

WDX-1
13 14 L120
W11 BUSBAR PROTECTION RELAY FAULT ALARM
/12.6:C

WDX-2
13 14 L121
W12 BACK UP PROTECTION RELAY FAULT ALARM
/12.6:C

X6 7 8 L122
W13 SPARE ALARM

X6 9 10 L123
W14 SPARE ALARM

X6 11 12 L124
W15 SPARE ALARM

D D
80DC
11 3 L125
W16 DC FAIL ALARM

/1.5:C

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
ANNUNCIATOR CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 17 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

1K6

1K6
195
A A
X7 MVAX31
13 13 5
1K8 1K8 1K8 1K8 1K8 1K8
195X 295X
/14.5:C 14/14.5:C 14 53
6
K24 X7 X7
27
/15.2:B 13 13 12 14
BCU 54 21
86BB-Z1 86BB-Z2 13
1K8A
1K5 53 /9.3:B /10.3:B A B RLA RLB
1K6A 13 X7 15 15
K23 9 13 15 22
BCS1 2 /15.1:B RL6X 14
REMOTE
PANEL 54
1K4 /14.4:C 14 TRIP
C 43 10 1K11 1K11 1K11 1K11
N 13 K19 1K12C 1K9
X7 1K10 C
T 3 /14.2:C
B RL5X 44
SS1
REMOTE 28
/14.5:C 14 L
CLOSE BCS1 2
1K35 1K6B
1K5 4 C R
13 13
K23 K24 43 N 1 3 /17.2:C
/15.1:B /15.2:B
B 14 14 1K3A K15 T 5 7 /14.5:B B
PANEL 1K3B BCU B
/13.5:B 44
1K6C 1K9
L 13 13 43
SS1
R K27 K28 K27
/15.3:B 14 /15.4:B 14 /15.3:B 44
1K3 LIVE LINE LIVE BUS LIVE LINE
1K6D 1K6E 1K6F
1 21 21 43
86BB-Z2 K28 K27 K28
/10.3:B 3 /15.4:B 22 /15.3:B 22 /15.4:B 44
DEAD BUS DEAD LINE LIVE BUS
1K6G
1K2
13
5
K29
86BB-Z1 /15.5:B 14
/9.3:B 7 CHECK OK.

1K1 1K8 1K11 1K12 1K13


C 1K7 C
31
X7 K25
2
/15.2:B
X7 8
X7 11 16 17
32
1K7B
1 31
K26
/15.3:B
32
X7 7

TO CLOSING POST CLOSE PRE


(+Ve) COIL (+Ve) (-Ve)
TO TRIP COIL-1 CLOSE

CB TRIP COIL-1 SUPERVISION RELAY


D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
52 BC OPEN & CLOSE CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 18 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A
295 A
MVAX31
2K1 2K1 2K1 2K1 2K1 2K1 2K1 2K1

43
K24 X9 X9
27
/15.2:B 14 14 3 5
BCU 44 21
86BB-Z1 86BB-Z2 13
2K10 /9.3:B RLA
43
X9 /10.3:B A B RLB
43 16 16
K23 7 4 6 22
/15.1:B RL6X 14
REMOTE
PANEL 44
/14.4:C 44 TRIP
8 2K4 2K4 2K4 2K4
2K8 2K9
2K7
C
28
2
L
SS1
C R
BCS1 N 1 3 /17.2:C
B 5 7 /14.5:B B
B
T
2K8
2K4 2K4

2K1 2K4 2K5 2K6


C C

X9 1
X9 2 X9 9 X9 10

POST CLOSE PRE


(-Ve)
(+Ve) TO TRIP COIL-1 CLOSE

D CB TRIP COIL-2 SUPERVISION RELAY D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
52 BC OPEN & CLOSE CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 19 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A A
3K4A 5K4A

53 63 73 21 83
K10 21 K10 K10 K26 K10
/13.2:B 54 /13.2:B 64 /13.2:B 74 /15.3:B 22 /13.2:B 84
K25
/15.2:B 22

3K4 4K4 5K4 6K4

13 21
53 21
K16 3K5 K16 4K5 5K5
/13.5:B /13.5:B K20 K20
14 22
/14.3:C 54 /14.3:C 22
6K5

X8 X8 X8
3 7 11
B B

4 8 12

3K3 4K3
5K3 6K3

13 23 33 43

K21 K21 K21 K21


/14.3:C /14.3:C 24 /14.3:C 34 /14.3:C 44
14
B B B B
T T 4K2 T 5K2 T 6K2
3K2
BCS2 N BCS2 N BCS3 N BCS3 N
4K5A 5K5A
C X8 3K5A C X8 C X8 C X8
2 6 10 14
2 2 2 2
REMOTE REMOTE REMOTE REMOTE
3K1A 4K1A 5K1A 6K1A
13 1 23 5 23 9 23 13

K18 K18 K18 K18


/14.2:C /14.2:C 24 /14.2:C 24 /14.2:C 24
14

5K1 6K1

3K1 4K1
C C

X13 1 X13 2 X13 3 X13 4 X13 5 X13 6 X13 7 X13 8

89 BC-1 89 BC-1 89 BC-2 89 BC-2


CLOSEING CKT OPENING CKT CLOSEING CKT OPENING CKT

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
89 BC-1&2 OPEN &CLOSE CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 20 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

A A

K1
/15.3:C

53 21 53 53 53 63 21 43 21 43

K9 K10 K15 K16 K19 K20 K25 K25 K26 K26


/13.1:B /13.2:B /13.5:B /13.5:B 54 /14.2:C /14.3:C /15.2:B 22 /15.2:B 44 /15.3:B 22 /15.3:B 44
54 22 54 54 64

K48 K49 K50 K51 K52 K53 K54 K55


K46 K47
B B
S1 S2 S3 S4 S5

1 2
1 2 1 2 1 2 1 2

C C C C C

C C

K2
/15.3:D

BC CB 89 CB-1 89 CB-2 EARTH SWITCH-1 EARTH SWITCH-2

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
INDICATION CIRCUIT 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 21 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

SCADA

U1 X11 1 U15 X12 1 1U1 X13A 1


A A

TO TRIP LINE PANEL-1 80DC


86Z1X 50LBB 110V DC SUPPLY HEALTHY
/15.5:B
MASTER TRIP RELAY /11.3:B 86L(LRMP) /1.5:C

(86BB) NO CONTACT ZONE-1 5 7 X12 2


14 15 1U2 X13A 2
43 44 U2 X11 2 U16

U17 X12 3
U3 X11 3

TO TRIP LINE PANEL-2


50LBB 86L(LRMP) 1U3 X13A 3
86Z2X MASTER TRIP RELAY
/11.3:B
/15.5:B
(86BB) NO CONTACT ZONE-2 6 8 U18 X12 4
43 44 X11 4 K1
U4 /12.1:C LINE CB-1 CLOSE
U19 X12 5
53 54 1U4 X13A 4

U5 X11 5
50LBB TO TRIP 86GT (TRMP) -1
/11.3:B
50LBB 1U5 X13A 5
/11.3:B
MASTER TRIP RELAY 13 15 U20 X12 6
(86BB) NO CONTACT
10 12 U6 X11 6
K2 LINE ISOLATOR-1 CLOSE
U21 X12 7 /12.2:C
B B
86BB-Z1 53 54 X13A 6
1U6
2 4 U7 X11 7
50LBB
/9.3:B /11.3:B TO TRIP 86GT (TRMP) -2
MASTER TRIP RELAY 17 19 U22 X12 8
1U7 X13A 7
(86BB) NC CONTACT ZONE-1
195X
U8 X11 8
LINE CB-2 CLOSE
21 22 U23 X12 9
K3
/12.2:C
86BB-Z1 /14.5:C
6 8 U9 X11 9
53 54 1U8 X13A 8
TC-I FAULTY
/9.3:B
MASTER TRIP RELAY U24 X12 10
(86BB) NC CONTACT ZONE-1 X13A 9
295X 1U9
U10 X11 10 21 22 U25 X12 11

/14.5:C K4 LINE-2 ISOLATOR CLOSE


86BB-Z2 /12.3:C
2 4 U11 X11 11 53 54 X13A 10
TC-II FAULTY 1U10
/10.3:B
MASTER TRIP RELAY U26 X12 12

(86BB) NC CONTACT ZONE-2


C 1U11 X13A 11 C
U12 X11 12

U27 X12 13
GT-1 CB CLOSE
86BB-Z2 K5
/12.3:C
6 8 U13 X11 13
WDX-2 53 54 1U12 X13A 12
/10.3:B /12.6:C BCU RELAY FAULTY
MASTER TRIP RELAY
(86BB) NC CONTACT ZONE-2 53 54 U28 X12 14

U14 X11 14 1U13 X13A 13


U29 X12 15
GT-1 ISOLATOR CLOSE
K6
RL1X /12.4:C
/14.6:C BACK UP O/C&E/F
53 54 1U14 X13A 14
53 54 U30 X12 16

1U15 X13A 15

K7
/12.5:C GT-2 CB CLOSE
53 54 1U16 X13A 16
D D

1U17 X13A 17

K8 GT-2 ISOLATOR CLOSE


/12.5:C
53 54 1U18 X13A 18

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
POTENTIAL FREE CONTACTS FOR SCADA 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 22 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

2U1 X14 1
3U1 X15 1

5U1 X17 1
K10A
/13.2:B 52BC OPEN K16
/13.5:B 89 BC-1 OPEN
A 13 14 X14 2 K25 A
2U2 83 84 X15 2 /15.2:B 89 BC-1 ES-1 CLOSE
3U2
13 14 5U2 X17 2

2U3 X14 3
3U3 X15 3

5U3 X17 3
K9 52 BC CLOSE
/13.1:B K15 89BC-1 CLOSE
/13.5:B 89 BC-1 ES-1 OPEN
63 64 2U4 X14 4
63 64 3U4 X15 4 K25
61 62 5U4 X17 4

/15.2:B
2U5 X14 5
3U5 X15 5

52 BC SPRING CHARGED
K11 89BC-1 MCB TRIP
/13.3:B K17
/14.1:C
13 14 2U6 X14 6
13 14 3U6 X15 6

2U7 X14 7
B B

K12 52 BC LOCAL
/13.3:B
53 54 2U8 X14 8

2U9 X14 9

K13 52 BC REMOTE
/13.4:B
13 14 2U10 X14 10

6U1 X18 1
4U1 X16 1
2U11 X14 11

SF6 LOCK OUT K26


K20 /15.3:B 89 BC-2 ES-2 CLOSE
K14 /14.3:C 89 BC-2 OPEN
/13.4:B 13 14 X18 2
6U2
13 14 4U2 X16 2
83 84 2U12 X14 12
C C

2U13 X14 13 6U3 X18 3


4U3 X16 3

TRIP COIL-I 89 BC-2 ES-2 OPEN


195X K19 89BC-2 CLOSE
/14.5:C HEALTHY /14.2:C
K26
53 54 2U14 X14 14
61 62 6U4 X18 4
63 64 4U4 X16 4
/15.3:B

2U15 X14 15
4U5 X16 5

TRIP COIL-II
295X HEALTHY 89BC-2 MCB TRIP
/14.5:C
K22
/14.4:C
53 54 2U16 X14 16 13 14 4U6 X16 6

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
POTENTIAL FREE CONTACTS FOR SCADA 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 23 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

EVN

U1A X19 1 U15A X20 1 1U1A X21 1

TO TRIP LINE PANEL-1 80DC


A 86Z1X 50LBB 110V DC SUPPLY HEALTHY A
/15.5:B
MASTER TRIP RELAY /11.3:B 86L(LRMP) /1.5:C

(86BB) NO CONTACT ZONE-1 2 4 X20 2


6 7 1U2A X21 2
13 14 U2A X19 2 U16A

U17A X20 3
U3A X19 3

TO TRIP LINE PANEL-2


50LBB 86L(LRMP) 1U3A X21 3
86Z2X MASTER TRIP RELAY
/11.3:B
/15.5:B
(86BB) NO CONTACT ZONE-2 9 11 U18A X20 4
13 14 X19 4 K1
U4A /12.1:C LINE CB-1 CLOSE
U19A X20 5
43 44 1U4A X21 4

U5A X19 5
50LBBX TO TRIP 86GT (TRMP) -1
/15.6:B
50LBB 1U5A X21 5
/11.3:B
MASTER TRIP RELAY 43 44 U20A X20 6
(86BB) NO CONTACT
14 16 U6A X19 6
K2 LINE ISOLATOR-1 CLOSE
U21A X20 7 /12.2:C
86Z1X 43 44 X21 6
1U6A
21 22 U7A X19 7
B 50LBBX B
/15.5:B /15.6:B TO TRIP 86GT (TRMP) -2
MASTER TRIP RELAY 13 14 U22A X20 8
1U7A X21 7
(86BB) NC CONTACT ZONE-1
195X
U8A X19 8
LINE CB-2 CLOSE
31 32 U23A X20 9
K3
/12.2:C
86Z1X /14.5:C
31 32 U9A X19 9
43 44 1U8A X21 8
TC-I FAULTY
/15.5:B
MASTER TRIP RELAY U24A X20 10
(86BB) NC CONTACT ZONE-1 X21 9
295X 1U9A
U10A X19 10 31 32 U25A X20 11

/14.5:C K4 LINE-2 ISOLATOR CLOSE


86Z2X /12.3:C
21 22 U11A X19 11 43 44 X21 10
TC-II FAULTY 1U10A
/15.5:B
MASTER TRIP RELAY U26A X20 12

(86BB) NC CONTACT ZONE-2


1U11A X21 11
U12A X19 12

C U27A X20 13
GT-1 CB CLOSE C
86Z2X K5
/12.3:C
31 32 U13A X19 13
WDX-2 43 44 1U12A X21 12
/15.5:B /12.6:C BCU RELAY FAULTY
MASTER TRIP RELAY
(86BB) NC CONTACT ZONE-2 43 44 U28A X20 14

U14A X19 14 1U13A X21 13


U29A X20 15
GT-1 ISOLATOR CLOSE
K6
RL1X /12.4:C
/14.6:C BACK UP O/C&E/F
43 44 1U14A X21 14
43 44 U30A X20 16

1U15A X21 15

K7
/12.5:C GT-2 CB CLOSE
43 44 1U16A X21 16

D D
1U17A X21 17

K8 GT-2 ISOLATOR CLOSE


/12.5:C
43 44 1U18A X21 18

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
POTENTIAL FREE CONTACTS FOR EVN 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 24 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

5U1A X25 1

K25
/15.2:B 89 BC-1 ES-1 CLOSE
83 84 5U2A X25 2

A 2U1A X22 1 A
3U1A X23 1

5U3A X25 3
K10A
/13.2:B 52BC OPEN K16
/13.5:B 89 BC-1 OPEN
43 44 X22 2 89 BC-1 ES-1 OPEN
2U2A 43 44 3U2A X23 2
K25
31 32 5U4A X25 4

/15.2:B
2U3A X22 3
3U3A X23 3

K9 52 BC CLOSE
/13.1:B K15 89BC-1 CLOSE
/13.5:B
73 74 2U4A X22 4
73 74 3U4A X23 4
6U1A X26 1

2U5A X22 5 K26


3U5A X23 5 /15.3:B 89 BC-2 ES-2 OPEN
52 BC SPRING CHARGED 83 84 6U2A X26 2
K11 89BC-1 MCB TRIP
/13.3:B K17
/14.1:C
B 43 44 2U6A X22 6 B
43 44 3U6A X23 6
6U3A X26 3

X22 7 89 BC-2 ES-2 CLOSE


2U7A
K26
31 32 6U4A X26 4
K12 52 BC LOCAL
/13.3:B /15.3:B
43 44 2U8A X22 8

2U9A X22 9
5U1 X27 1

K13 52 BC REMOTE
/13.4:B
R1
/15.1:D
43 44 2U10A X22 10 83 84 5U2 X27 2

4U1A X24 1
2U11A X22 11
5U3 X27 3
C C
SF6 LOCK OUT K20
K14 /14.3:C 89 BC-2 OPEN R2
/13.4:B /15.2:D
43 44 4U2A X24 2
43 44 2U12A X22 12 83 84 5U4 X27 4

2U13A X22 13
4U3A X24 3
5U5 X27 5

195X K19 89BC-2 CLOSE


/14.5:C TRIP COIL-I HEALTHY /14.2:C R3
43 44 X22 14 /15.2:D
2U14A 73 74 4U4A X24 4
83 84 5U6 X27 6

2U15A X22 15
4U5A X24 5
5U7 X27 7

295X TRIP COIL-II HEALTHY 89BC-2 MCB TRIP


/14.5:C
K22
/14.4:C R4
43 44 X22 16 /15.3:D
2U16A 43 44 4U6A X24 6

D
83 84 5U8 X27 8
D

5U9 X27 9

R5

83 84 5U10 X27 10

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
POTENTIAL FREE CONTACTS FOR EVN 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / SCH
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 25 OF 25 in SCH Total pages: 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-ACTB -CTTB3
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
H1 GT1 60/80/120/1A CORE5: CL 5P20,15VA FROM 3A10
1 1Ph, 50Hz, 230VAC SUPPLY FROM GMRP (Ph) -F6:1 1 -RTB2:2
TRAFO (HV SIDE)
H2 GT1 60/80/120/1A CORE5: CL 5P20,15VA FROM 3A30
2 1Ph, 50Hz, 230VAC SUPPLY FROM GMRP (Nu) -F6:3 2 -RTB2:4
TRAFO (HV SIDE)
1Ph, 50Hz, 230VAC SUPPLY TO ADJACENT PANEL H1 GT1 60/80/120/1A CORE5: CL 5P20,15VA FROM 3A50
3 -F6:1 3 -RTB2:6
(Ph) TRAFO (HV SIDE)
1Ph, 50Hz, 230VAC SUPPLY TO ADJACENT PANEL H2 GT1 60/80/120/1A CORE5: CL 5P20,15VA FROM 3A70
4 -F6:3 4 -RTB2:8
(Nu) TRAFO (HV SIDE)
H14
5 REMOTE DC FAIL ACCEPT -PB1:1
H13
6 REMOTE DC FAIL ACCEPT -80AC:A1

-CTTB4
B B

Target 1 Wiring Function text Wiring Target 2


-CTTB1 GT2 60/80/120/1A CORE1: CL 5P20,15VA FROM 4A10
1 -RTB2:10
TRAFO HV SIDE
GT2 60/80/120/1A CORE1: CL 5P20,15VA FROM 4A30
Target 1 Wiring Function text Wiring Target 2 2 -RTB2:12
TRAFO HV SIDE
L1-CT 800/1A CORE1: CL 5P20,20VA FROM 1A10 GT2 60/80/120/1A CORE1: CL 5P20,15VA FROM 4A50
1 -RTB1:2 3 -RTB2:14
LINE-1 SIDE TRAFO HV SIDE
L1-CT 800/1A CORE1: CL 5P20,20VA FROM 1A30 GT2 60/80/120/1A CORE1: CL 5P20,15VA FROM 4A70
2 -RTB1:4 4 -RTB2:16
LINE-1 SIDE TRAFO HV SIDE
L1-CT 800/1A CORE1: CL 5P20,20VA FROM 1A50
3 -RTB1:6
LINE-1 SIDE
L1-CT 800/1A CORE1: CL 5P20,20VA FROM 1A70
4 -RTB1:8
LINE-1 SIDE

C
-CTTB5 C

Target 1 Wiring Function text Wiring Target 2


-CTTB2 5A10
1 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -RTB3:2
5A30
Target 1 Wiring Function text Wiring Target 2 2 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -RTB3:4
L2-CT 800/1A CORE1: CL 5P20,20VA FROM 2A10 6A31
1 -RTB1:10 2 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F14
LINE-2 SIDE
L2-CT 800/1A CORE1: CL 5P20,20VA FROM 2A30 5A50
2 -RTB1:12 3 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -RTB3:6
LINE-2 SIDE
L2-CT 800/1A CORE1: CL 5P20,20VA FROM 2A50 6A51
3 -RTB1:14 3 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F16
LINE-2 SIDE
L2-CT 800/1A CORE1: CL 5P20,20VA FROM 2A70 5A70
4 -RTB1:16 4 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -RTB3:8
LINE-2 SIDE
6A71;6A71;6A71
4 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F11;-X032:F13;-X
D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-CTTB6 -TB1
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
6A11 J401
1 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F12 2 SPARE -F4:2
6A31
2 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F14
6A51
3 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F16
6A71;6A71;6A71
4 B/C 200/400/600/800/1A CORE1: CL 5P20,15VA -X032:F11;-X032:F13;-X032:F15 -X1
Target 1 Wiring Function text Wiring Target 2
K1
1 FROM LINE-1CB -F3:2
-CTTB7 K3
B 2 FROM LINE-1CB -K1:A1 B

K1
Target 1 Wiring Function text Wiring Target 2 3 FROM LINE-1 ISOLATOR
6A12 K4
1 200/400/600/800/1A 15VA,CL:5P20 -RTB3:10 4 FROM LINE-1 ISOLATOR -K2:A1
6A32 K1
2 200/400/600/800/1A 15VA,CL:5P20 -RTB3:12 5 FROM LINE-2CB
6A52 K5
3 200/400/600/800/1A 15VA,CL:5P20 -RTB3:14 6 FROM LINE-2CB -K3:A1
6A72 K1
4 200/400/600/800/1A 15VA,CL:5P20 -RTB3:16 7 FROM LINE-2 ISOLATOR
K6
8 FROM LINE-2 ISOLATOR -K4:A1
K1
9 GT1 CB CLOSE
K7
C
-DCTB 10 GT1 CB CLOSE -K5:A1
C
K1
11 GT1 ISOLATOR CLOSE
Target 1 Wiring Function text Wiring Target 2 K8
12 GT1 ISOLATOR CLOSE -K6:A1
J1
1 220V DC SUPPLY FROM CUSTOMER (+VE) -F1:1
K1
13 GT2 CB CLOSE
J2
2 220V DC SUPPLY FROM CUSTOMER (-VE) -F1:3
K9
14 GT2 CB CLOSE -K7:A1
J1
3 220V DC SUPPLY TO ADJACENT PANEL (+VE) -F1:1
K1
15 GT2 ISOLATOR CLOSE -P746:M12
J2
4 220V DC SUPPLY TO ADJACENT PANEL (-VE) -F1:3
K10
16 GT2 ISOLATOR CLOSE -K8:A1
K1
17 B/C CB CLOSE -P14DG-X032
K13
18 B/C CB CLOSE -K9:A1
D
-TB1 K1 D
19 B/C CB OPEN
K14
Target 1 Wiring Function text Wiring Target 2 20 B/C CB OPEN -K10:A1
J417 K1
1 SPARE -X_3:G14 21 B/C CB SPRING CHARGED

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 2 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X1 -X1
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
K15 K35
22 B/C CB SPRING CHARGED -K11:A1 48 OPEN 89BC-2E -K26:A1
K1
23 B/C CB LOCAL
B/C CB LOCAL K1
24
K1
25 B/C CB REMOTE -X2
K17
26 B/C CB REMOTE -K13:A1
K1 Target 1 Wiring Function text Wiring Target 2
27 B/C CB SF6 PR.LOCK OUT
7U1
1 IDMT/INST O/C (50/51) FOR LINE-1 -P746:L5
K18
28 B/C CB SF6 PR.LOCK OUT -K14:A1
7U2
B 2 IDMT/INST O/C (50/51) FOR LINE-1 -P746:L6 B
K1
29 89BC-1 CLOSE
7U3
3 IDMT/INST O/C (50/51) FOR LINE-2 -P746:L7
K19
30 89BC-1 CLOSE -K15:A1
7U4
4 IDMT/INST O/C (50/51) FOR LINE-2 -P746:L8
K1
31 89BC-1 OPEN
7U5
5 IDMT/INST O/C (50/51) FOR GT -P746:L9
K20
32 89 BC-1 OPEN -K16:A1
7U6
6 IDMT/INST O/C (50/51) FOR GT -P746:L10
K1
33 89 BC-1 MCB TRIP
7U7
7 IDMT/INST O/C (50/51) FOR GT -P746:L11
K16
34 B/C CB LOCAL -K12:A1
7U8
8 SPARE -P746:L12
K21
34 89 BC-1 MCB TRIP -K17:A1
7U9
9 B/C CB TRIP -P746:L14
K1
35 89 BC-1 REMOTE
7U10
10 B/C CB TRIP -P746:L15
C
K22 C
36 89 BC-1 REMOTE -K18:A1
7U1
11 SPARE -P746:K1
K1
37 89BC-2 CLOSE
7U12
12 SPARE K2
K23
38 89BC-2 CLOSE -K19:A1
7U13
13 SPARE -P746:K11
K1
39 89 BC-2 OPEN
7U14
14 SPARE K12
K24
40 89 BC-2 OPEN -K20:A1
7U15
15 SPARE -P746:K14
K1
41 89 BC-2 REMOTE
7U16
16 SPARE K15
K25
42 89 BC-2 REMOTE -K21:A1
7U17
17 SPARE -P746:K17
K1
43 89 BC-2 MCB TRIP -P14DG-X032
7U18
18 SPARE K18
K26
44 89 BC-2 MCB TRIP -K22:A1
D D
K31
45 OPEN 89BC-1E -P14DG-X032
K34
46 OPEN 89BC-1E -K25:A1
K1
47 OPEN 89BC-2E -P14DG-X032

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 3 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X3 -X3
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K1 K106
1 -F3:2 28 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -27
ANY
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K102 K1
2 -27 29 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -F3:2
ANY
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K1 K106
3 -F3:2 30 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -27
ANY
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K102
4 -27
ANY
REMOTE RESET 86BBZ-1 MASTER TRIP RELAY K1
5 -F3:2;-PB4:1
FROM SCADA
REMOTE RESET 86BBZ-1 MASTER TRIP RELAY K101;K101
6
FROM SCADA
-PB4:2;-25 -X4
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K1
7 -F3:2
ANY
B Target 1 Wiring Function text Wiring Target 2 B
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K102
8 -27
ANY L106
1 ANN. ACCEPT FROM SCADA ACK
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K1
9 -F3:2
ANY L108
2 ANN. ACCEPT FROM SCADA COM
86BBZ-1 MASTER TRIP RELAY -FUTURE TRIP IF K102
10 -27
ANY L107
3 ANN. RESET FROM SCADA RST
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K1
11 -F3:2
ANY L108
4 ANN. RESET FROM SCADA COM
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K104
12 -27
ANY
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K1
13 -F3:2
ANY
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K104
14 -27
ANY
REMOTE RESET 86BBZ-2 MASTER TRIP RELAY K1 -X5
15 -F3:2;-PB5:1
FROM SCADA
C REMOTE RESET 86BBZ-2 MASTER TRIP RELAY K103;K103 C
16 -PB5:2;-25 Target 1 Wiring Function text Wiring Target 2
FROM SCADA
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K1 ANNUNCIATOR RS485 COMMUNICATION 2RS+
17 -F3:2 1 RS+
ANY PORT-RS+
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K104 ANNUNCIATOR RS485 COMMUNICATION 2RS-
18 -27 2 RS-
ANY PORT-RS-
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K1 SH2
19 -F3:2 3 SHIELD
ANY
86BBZ-2 MASTER TRIP RELAY -FUTURE TRIP IF K104
20 -27
ANY
K1
21 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -F3:2
K106
22 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -27 -X6
K1
23 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -F3:2
K106 Target 1 Wiring Function text Wiring Target 2
24 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -27
D L109 D
1 ANNUNCIATOR SPARE C
REMOTE RESET 50LBB MASTER TRIP RELAY K1
25 -F3:2;-PB4:1
FROM SCADA L113
2 ANNUNCIATOR SPARE -X6:W4
REMOTE RESET 50LBB MASTER TRIP RELAY K105;K105
26 -PB4:2;-25
FROM SCADA L109
3 ANNUNCIATOR SPARE C
K1
27 50LBB MASTER TRIP RELAY -FUTURE TRIP IF ANY -F3:2

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 4 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X6 -X7
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
L116 1K8;1K8;1K8
4 ANNUNCIATOR SPARE -X6:W7 14 FUTURE TRIP -X7:12;-195-B:13;-195-
L109 1K11;1K11
5 ANNUNCIATOR SPARE C 15 FUTURE TRIP -X7:13;-195-A:22
L117 52-TG CB TRIP COIL-1 SUPERVISION RELAY PRE 1K12
6 ANNUNCIATOR SPARE -X6:W8 16 -195-B:14
CLOSE
L109 1K13
7 ANNUNCIATOR SPARE C 17 52-TG CB TRIP COIL-1 SUPERVISION RELAY(-Ve) -195-C:28
L122
8 ANNUNCIATOR SPARE -X6:W13
L109
9 ANNUNCIATOR SPARE C
L123
10 ANNUNCIATOR SPARE -X6:W14 -X8
B B
L109
11 ANNUNCIATOR SPARE C
L124 Target 1 Wiring Function text Wiring Target 2
12 ANNUNCIATOR SPARE -X6:W15
3K1
1 89 BC-1 CLOSING FUTURE I/L
3K2
2 89 BC-1 CLOSING FUTURE I/L -K21:14
3K5
3 89 BC-1 CLOSING FUTURE I/L -K25:22
-X7 3K5A
4 89 BC-1 CLOSING FUTURE I/L
4K1
Target 1 Wiring Function text Wiring Target 2 5 89 BC-1 CLOSING FUTURE I/L
4K2
1 52 BC I/C 6 89 BC-1 CLOSING FUTURE I/L -K21:14
1K1 4K5
2 52 BC I/C -86BB-Z1:7 7 89 BC-1 OPENING FUTURE I/L -K10:63
C C
1K4 4K5A
3 52 BC REMOTE CLOSE FROM SCADA -RL5X:13 8 89 BC-1 OPENING FUTURE I/L
1K3A 5K1
4 52 BC REMOTE CLOSE FROM SCADA 9 89 BC-1 CLOSING FUTURE I/L
1K6 5K2
5 52 BC I/C -195X:13 10 89 BC-1 CLOSING FUTURE I/L -K21:14
1K6A 5K5
6 52 BC I/C -K19:43 11 89 BC-2 CLOSING FUTURE I/L -K26:22
52-TG CB TRIP COIL-1 SUPERVISION RELAY POST 1K7 5K5A
7 -K26:32 12 89 BC-2 CLOSING FUTURE I/L
CLOSE
1K8 6K1
8 52-TG CB TRIP COIL-1(+VE) -K23:53 13 89 BC-1 CLOSING FUTURE I/L
1K8;1K8 6K2
9 52 BC CB REMOTE TRIP -K24:53;-86BB-Z1:13 14 89 BC-1 CLOSING FUTURE I/L -K21:14
1K10
10 52 BC CB REMOTE TRIP
D 52-TG CB TRIP COIL-1 SUPERVISION RELAY POST 1K11;1K11;1K11 D
11 -86BB-Z1:15;-86BB-Z2:15
CLOSE
1K8;1K8
12 FUTURE TRIP -86BB-Z2:13;-X7:14
1K11;1K11
13 FUTURE TRIP -86BB-Z2:15;-X7:15

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 5 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X9 -X11
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
52-TG CB TRIP COIL-1 SUPERVISION RELAY POST 2K1 MASTER TRIP RELAY (86BB) NO CONTACT U3
1 -K23:43 3 -86Z2X:43
CLOSE(+ve) ZONE-2
52-TG CB TRIP COIL-1 SUPERVISION RELAY POST 2K4;2K4;2K4 MASTER TRIP RELAY (86BB) NO CONTACT U4
2 -86BB-Z1:16;-86BB-Z2:16 4 -86Z2X:44
CLOSE ZONE-2
2K1;2K1 U5
3 FUTURE TRIP -86BB-Z2:14;-X9:5 5 MASTER TRIP RELAY (86BB) NO CONTACT -50LBB:10
2K4;2K4 U6
4 FUTURE TRIP -86BB-Z2:16;-X9:6 6 MASTER TRIP RELAY (86BB) NO CONTACT -50LBB:12
2K1;2K1;2K1 MASTER TRIP RELAY (86BB) NC CONTACT U7
5 FUTURE TRIP -X9:3;-295-B:13;-295-A:21 7 -86BB-Z1:4
ZONE-1
2K4;2K4 MASTER TRIP RELAY (86BB) NC CONTACT U8
6 FUTURE TRIP -X9:4;-295-A:22 8 -86BB-Z1:2
ZONE-1
2K1;2K1 MASTER TRIP RELAY (86BB) NC CONTACT U9
7 REMOTE TRIP -K24:43;-86BB-Z1:14 9 -86BB-Z1:8
ZONE-1
B B
2K9 MASTER TRIP RELAY (86BB) NC CONTACT U10
8 REMOTE TRIP 10 -86BB-Z1:6
ZONE-1
52-TG CB TRIP COIL-1 SUPERVISION RELAY PRE 2K5 MASTER TRIP RELAY (86BB) NC CONTACT U11
9 -295-B:14 11 -86BB-Z2:4
CLOSE ZONE-2
2K6 MASTER TRIP RELAY (86BB) NC CONTACT U12
10 52-TG CB TRIP COIL-1 SUPERVISION RELAY(-Ve) -295-C:28 12 -86BB-Z2:2
ZONE-2
MASTER TRIP RELAY (86BB) NC CONTACT U13
13 -86BB-Z2:8
ZONE-2
MASTER TRIP RELAY (86BB) NC CONTACT U14
14 -86BB-Z2:6
ZONE-2

-X10
Target 1 Wiring Function text Wiring Target 2
1E11 1E11 -X12
-F10:1 1 FROM BUS PT-2 CORE:2 CL:3P,30VA
C C
1E31 1E31
-F10:3 2 FROM BUS PT-2 CORE:2 CL:3P,30VA Target 1 Wiring Function text Wiring Target 2
1E51 1E51 U15
-F10:5 3 FROM BUS PT-2 CORE:2 CL:3P,30VA 1 TO TRIP LINE PANEL-1 86L(LRMP) -50LBB:5
1E71 1E71 U16
-F10:7 4 FROM BUS PT-2 CORE:2 CL:3P,30VA 2 TO TRIP LINE PANEL-1 86L(LRMP) -50LBB:7
1E12 1E12 U17
-F11:1 5 FROM BUS PT-1 CORE:2 CL:3P,30VA 3 TO TRIP LINE PANEL-2 86L(LRMP) -50LBB:6
1E52 1E52 U18
-F11:3 6 FROM BUS PT-1 CORE:2 CL:3P,30VA 4 TO TRIP LINE PANEL-2 86L(LRMP) -50LBB:8
U19
5 TO TRIP 86GT (TRMP) -1 -50LBB:13
U20
6 TO TRIP 86GT (TRMP) -1 -50LBB:15
U21
-X11 7 TO TRIP 86GT (TRMP) -2 -50LBB:17
D U22 D
8 TO TRIP 86GT (TRMP) -2 -50LBB:19
Target 1 Wiring Function text Wiring Target 2 U23
9 TC-I FAULTY -195X:22
MASTER TRIP RELAY (86BB) NO CONTACT U1
1 -86Z1X:43
ZONE-1 TO SCADA U24
10 TC-I FAULTY -195X:21
MASTER TRIP RELAY (86BB) NO CONTACT U2
2 -86Z1X:44
ZONE-1

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 6 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X12 -X13A
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
U25 1U17
11 TC-II FAULTY -295X:22 17 GT-2 ISOLATOR CLOSE -K8:53
U26 1U18
12 TC-II FAULTY -295X:21 18 GT-2 ISOLATOR CLOSE -K8:54
U27
13 BCU RELAY FAULTY TO SCADA -WDX-2:53
U28
14 BCU RELAY FAULTY TO SCADA -WDX-2:54
U29
15 BACK UP O/C TO SCADA -RL1X:53 -X14
U30
16 BACK UP O/C TO SCADA -RL1X:54
Target 1 Wiring Function text Wiring Target 2
2U1
B 1 52BC OPEN -K10A:13 B

2U2
2 52BC OPEN -K10A:14
-X13A 2U3
3 52 BC CLOSE -K9:63
2U4
Target 1 Wiring Function text Wiring Target 2 4 52 BC CLOSE -K9:64
1U1 2U5
1 110V DC SUPPLY UNHEALTHY F/B TO SCADA -80DC:14 5 52 BC SPRING CHARGED -K11:13
1U2 2U6
2 110V DC SUPPLY UNHEALTHY F/B TO SCADA -80DC:15 6 52 BC SPRING CHARGED -K11:14
1U3 2U7
3 LINE CB-1 CLOSE -K1:53 7 52 BC LOCAL -K12:53
1U4 2U8
4 LINE CB-1 CLOSE -K1:54 8 52 BC LOCAL -K12:54
1U5 2U9
5 LINE ISOLATOR-1 CLOSE -K2:53 9 52 BC REMOTE -K13:13
C C
1U6 2U10
6 LINE ISOLATOR-1 CLOSE -K2:54 10 52 BC REMOTE -K13:14
1U7 2U11
7 LINE CB-2 CLOSE -K3:53 11 SF6 LOCK OUT -K14:83
1U8 2U12
8 LINE CB-2 CLOSE -K3:54 12 SF6 LOCK OUT -K14:84
1U9 2U13
9 LINE-2 ISOLATOR CLOSE -K4:53 13 TRIP COIL-I HEALTHY -195X:53
1U10 2U14
10 LINE-2 ISOLATOR CLOSE -K4:54 14 TRIP COIL-I HEALTHY -195X:54
1U11 2U15
11 GT-1 CB CLOSE -K5:53 15 TRIP COIL-II HEALTHY -295X:53
1U12 2U16
12 GT-1 CB CLOSE -K5:54 16 TRIP COIL-II HEALTHY -295X:54
1U13
13 GT-1 ISOLATOR CLOSE -K6:53
D 1U14 D
14 GT-1 ISOLATOR CLOSE -K6:54
1U15
15 GT-2 CB CLOSE -K7:53
1U16
16 GT-2 CB CLOSE -K7:54

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 7 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X15 -X18
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
3U1 6U1
1 89 BC-1 OPEN -K16:83 1 89 BC-2 ES-2 OPEN -K26:13
3U2 6U2
2 89 BC-1 OPEN -K16:84 2 89 BC-2 ES-2 OPEN -K26:14
3U3 6U3
3 89BC-1 CLOSE -K15:63 3 89 BC-2 ES-2 CLOSE -K26:61
3U4 6U4
4 89BC-1 CLOSE -K15:64 4 89 BC-2 ES-2 CLOSE -K26:62
3U5
5 89BC-1 MCB TRIP -K17:13
3U6
6 89BC-1 MCB TRIP -K17:14

-X19
B B

Target 1 Wiring Function text Wiring Target 2


-X16 MASTER TRIP RELAY (86BB) NO CONTACT U1A
1 -86Z1X:13
ZONE-1
MASTER TRIP RELAY (86BB) NO CONTACT U2A
Target 1 Wiring Function text Wiring Target 2 2 -86Z1X:14
ZONE-1
4U1 MASTER TRIP RELAY (86BB) NO CONTACT U3A
1 89 BC-2 OPEN -K20:13 3 -86Z2X:13
ZONE-2
4U2 MASTER TRIP RELAY (86BB) NO CONTACT U4A
2 89 BC-2 OPEN -K20:14 4 -86Z2X:14
ZONE-2
4U3 U5A
3 89BC-2 CLOSE -K19:63 5 MASTER TRIP RELAY (86BB) NO CONTACT -50LBB:14
4U4 U6A
4 89BC-2 CLOSE -K19:64 6 MASTER TRIP RELAY (86BB) NO CONTACT -50LBB:16
4U5 MASTER TRIP RELAY (86BB) NC CONTACT U7A
5 89BC-2 MCB TRIP -K22:13 7 -86Z1X:22
C
ZONE-1 C
4U6 MASTER TRIP RELAY (86BB) NC CONTACT U8A
6 89BC-2 MCB TRIP -K22:14 8 -86Z1X:21
ZONE-1
MASTER TRIP RELAY (86BB) NC CONTACT U9A
9 -86Z1X:32
ZONE-1
MASTER TRIP RELAY (86BB) NC CONTACT U10A
10 -86Z1X:31
ZONE-1
MASTER TRIP RELAY (86BB) NC CONTACT U11A
-X17 11
ZONE-2
-86Z2X:22
MASTER TRIP RELAY (86BB) NC CONTACT U12A
12 -86Z2X:21
ZONE-2
Target 1 Wiring Function text Wiring Target 2 MASTER TRIP RELAY (86BB) NC CONTACT U13A
13 -86Z2X:32
5U1 ZONE-2
1 89 BC-1 ES-1 OPEN -K25:13
MASTER TRIP RELAY (86BB) NC CONTACT U14A
14 -86Z2X:31
5U2 ZONE-2
2 89 BC-1 ES-1 OPEN -K25:14
5U3
3 89 BC-1 ES-1 CLOSE -K25:61
D D
5U4
4 89 BC-1 ES-1 CLOSE -K25:62

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 8 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X20 -X21
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
U15A 1U7A
1 TO TRIP LINE PANEL-1 86L(LRMP) -50LBB:2 7 LINE CB-2 CLOSE -K3:43
U16A 1U8A
2 TO TRIP LINE PANEL-1 86L(LRMP) -50LBB:4 8 LINE CB-2 CLOSE -K3:44
U17A 1U9A
3 TO TRIP LINE PANEL-2 86L(LRMP) -50LBB:9 9 LINE-2 ISOLATOR CLOSE -K4:43
U18A 1U10A
4 TO TRIP LINE PANEL-2 86L(LRMP) -50LBB:11 10 LINE-2 ISOLATOR CLOSE -K4:44
U19A 1U11A
5 TO TRIP 86GT (TRMP) -1 -50LBBX:43 11 GT-1 CB CLOSE -K5:43
U20A 1U12A
6 TO TRIP 86GT (TRMP) -1 -50LBBX:44 12 GT-1 CB CLOSE -K5:44
U21A 1U13A
7 TO TRIP 86GT (TRMP) -2 -50LBBX:13 13 GT-1 ISOLATOR CLOSE -K6:43
B B
U22A 1U14A
8 TO TRIP 86GT (TRMP) -2 -50LBBX:14 14 GT-1 ISOLATOR CLOSE -K6:44
U23A 1U15A
9 TC-I FAULTY -195X:32 15 GT-2 CB CLOSE -K7:43
U24A 1U16A
10 TC-I FAULTY -195X:31 16 GT-2 CB CLOSE -K7:44
U25A 1U17A
11 TC-II FAULTY -295X:32 17 GT-2 ISOLATOR CLOSE -K8:43
U26A 1U18A
12 TC-II FAULTY -295X:31 18 GT-2 ISOLATOR CLOSE -K8:44
U27A
13 BCU RELAY FAULTY TO SCADA -WDX-2:43
U28A
14 BCU RELAY FAULTY TO SCADA -WDX-2:44
U29A
15 BACK UP O/C TO SCADA -RL1X:43 -X22
C
U30A C
16 BACK UP O/C TO SCADA -RL1X:44
Target 1 Wiring Function text Wiring Target 2
2U1A
1 52BC OPEN -K10A:43
2U2A
2 52BC OPEN -K10A:44
-X21 2U3A
3 52 BC CLOSE -K9:73
2U4A
Target 1 Wiring Function text Wiring Target 2 4 52 BC CLOSE -K9:74
1U1A 2U5A
1 110V DC SUPPLY UNHEALTHY F/B TO SCADA -80DC:6 5 52 BC SPRING CHARGED -K11:43
1U2A 2U6A
2 110V DC SUPPLY UNHEALTHY F/B TO SCADA -80DC:7 6 52 BC SPRING CHARGED -K11:44
1U3A 2U7A
3 LINE CB-1 CLOSE -K1:43 7 52 BC LOCAL -K12:43
D 1U4A 2U8A D
4 LINE CB-1 CLOSE -K1:44 8 52 BC LOCAL -K12:44
1U5A 2U9A
5 LINE ISOLATOR-1 CLOSE -K2:43 9 52 BC REMOTE -K13:43
1U6A 2U10A
6 LINE ISOLATOR-1 CLOSE -K2:44 10 52 BC REMOTE -K13:44

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 9 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X22 -X24
A A

Target 1 Wiring Function text Wiring Target 2 Target 1 Wiring Function text Wiring Target 2
2U11A 4U6A
11 SF6 LOCK OUT -K14:43 6 89BC-2 MCB TRIP -K22:44
2U12A
12 SF6 LOCK OUT -K14:44
2U13A
13 TRIP COIL-I HEALTHY -195X:43
2U14A
14 TRIP COIL-I HEALTHY -195X:44 -X25
2U15A
15 TRIP COIL-II HEALTHY -295X:43
2U16A Target 1 Wiring Function text Wiring Target 2
16 TRIP COIL-II HEALTHY -295X:44
5U1A
1 89 BC-1 ES-1 OPEN -K25:83
5U2A
B 2 89 BC-1 ES-1 OPEN -K25:84 B

5U3A
3 89 BC-1 ES-1 CLOSE -K25:31
-X23 5U4A
4 89 BC-1 ES-1 CLOSE -K25:32

Target 1 Wiring Function text Wiring Target 2


3U1A
1 89 BC-1 OPEN -K16:43
3U2A
2 89 BC-1 OPEN -K16:44 -X26
3U3A
3 89BC-1 CLOSE -K15:73
3U4A Target 1 Wiring Function text Wiring Target 2
4 89BC-1 CLOSE -K15:74
6U1A
1 89 BC-2 ES-2 OPEN -K26:83
3U5A
5 89BC-1 MCB TRIP -K17:43
C
6U2A C
2 89 BC-2 ES-2 OPEN -K26:84
3U6A
6 89BC-1 MCB TRIP -K17:44
6U3A
3 89 BC-2 ES-2 CLOSE -K26:31
6U4A
4 89 BC-2 ES-2 CLOSE -K26:32

-X24
Target 1 Wiring Function text Wiring Target 2 -X27
4U1A
1 89 BC-2 OPEN -K20:43
4U2A Target 1 Wiring Function text Wiring Target 2
2 89 BC-2 OPEN -K20:44
5U1
1 89 BC-2 ES-2 OPEN -R1:83
4U3A
3 89BC-2 CLOSE -K19:73
D 5U2 D
2 89 BC-2 ES-2 OPEN -R1:84
4U4A
4 89BC-2 CLOSE -K19:74
5U3
3 89 BC-2 ES-2 OPEN -R2:83
4U5A
5 89BC-2 MCB TRIP -K22:43
5U4
4 89 BC-2 ES-2 OPEN -R2:84

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 10 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

Terminal diagram

-X27
A A

Target 1 Wiring Function text Wiring Target 2


5U5
5 89 BC-2 ES-2 OPEN -R3:83
5U6
6 89 BC-2 ES-2 OPEN -R3:84
5U7
7 89 BC-2 ES-2 OPEN -R4:83
5U8
8 89 BC-2 ES-2 OPEN -R4:84
5U9
9 89 BC-2 ES-2 OPEN -R5:83
5U10
10 89 BC-2 ES-2 OPEN -R5:84

B B

C C

D D

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
Terminal Diagram 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / TD
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 11 OF 11 in TD Total pages: OF 48
1 2 3 4 5 6
1 2 3 4 5 6

TABLE-1:
BOM FOR BPP PANEL QTY: 1 No.
SL. NO. DESIGNATION DESCRIPTION QTY MAKE SL. NO. DESIGNATION DESCRIPTION QUANTITY MAKE

1 NO ADDON BLOCK:
K1-K29,RL6X,RL5X,
MLD SERIES ANNUNCIATOR AUX. CONTACTOR K1-K8, K12,K23,K24
RL1X
WITH RS485 PORT WDX-1&2,K10A, RATING : 220V DC WDX2,195X,295X,RL1X ABB
11 40 NOS
No. OF WAYS : 16 WAYS 195X,295X 4NO ADDON BLOCK:
CONTACTS : 2NO+2NC K9,K10,K15,K19
1 FOR TRIP : RED ,86Z1X,86Z2X,50LBB
A ANN. FOR NON-TRIP : AMBER 2NO+2NC ADDON BLOCK: A
1 NO. SECO K14,K16,K20,K25,K26
DC VOLT. RATING : 220V DC
STANDBY SUPPLY : 230V AC 12 DOOR LIMIT SWITCH
DLS 1 NO. SIEMENS
RATING : 230V AC, 6A
NOTE:- PARITY,BAUDRATE & ID SHALL
BE SITE SELECTABLE CUBICLE HEATER
13 SH 1 NO. GIRISH
Bz BUZZER FOR DC FAIL , 230V AC RATING : 240V AC, 150W
2 1 NO. ALAN
RELAY TERMINAL BLOCK ,WITH TEST PLUG FOR RTB LEDLAMP,ONE FEET FITTING
14 CFL 1 NO. HAVELLS
TYPE : 3Ph, 4W, 3Ele 230VAC, 5W
3 RTB1-3 03 NO DEEPL
OPEN LINK TYPE
15 FAN
FAN 4", 230VAC, EXHAUST FAN REXNORD
SUITABLE FOR REAR CON. 1 No.

MASTER TRIP RELAY THERMOSTAT


16 TH1,TH2 02 No's GIRISH
4 TYPE : MVAJM15 RATING : 30-85°, 230V AC
86BB-Z1 02 NO ALSTOM
VOLT. RATING : 220V DC
86BB-Z2 17 DISCONNECTING TYPE
CONTACTS : 6NO+4NC TERMINALS AS REQD. PHOENIX
STUD TYPE
(WITH ELECTRICAL RESET TYPE)
MINIATURE CIRCUIT BREAKER
MASTER TRIP RELAY F1 RATING : DP, 16A, 220V DC 1 NO.
B 5 50LBB TYPE : MVAJM15 F2-F5 RATING : DP, 6A, 220V DC 5 NOS. B
01 NO ALSTOM 18 ABB
VOLT. RATING : 220V DC F6 RATING : DP, 16A, 230V AC 1 NO.
CONTACTS : 10NO F7-F9 RATING : DP, 6A, 230V AC 3 No's
(WITH ELECTRICAL RESET TYPE) F10 RATING : 4P, 6A, 230V AC 1 No's
F11 RATING : DP, 6A, 110V AC 1 No's
VOLTAGE : 220V DC
6 H1,H2 TYPE : ELECTRONIC TYPE, DUAL TONE 2NOS. PUSH BUTTONS
ALAN
SIZE : 96 Sq.mm SIZE : 22.5mm DIA
PB6 ANN. TEST/DC FAIL TEST (1NO+1NC)-YELLOW 1 NO.
PB1 ANN. ACCEPT/DC FAIL ACCEPT (2NO)-BLACK 1 NO.
AUX. CONTACTOR
PB2 ANN. RESET (1NO)-BLUE 1 NO.
7 80AC RATING : 230V AC, 9A 1 NO. 19 TEKNIC
ABB PB3,PB4,PB5 86BB RESET-BLUE 3 NO.
CONTACTS : 2NO+2NC
EPB EMG STOP 1 NO.

BCU
DC SUPERVISION RELAY
TYPE : P14DG
8 80DC TYPE :VAA11
VOLT. RATING : 110V AC 1 NO.
1 NO. 20 P14DG
RATING : 220V DC ALSTOM
CONTACTS :8 INPUT,8 OUTPUT
CONTACTS : 2NO+2C/O ALSTOME
COMMUNICATION :IEC61850
SIZE : 1/4N V
C RATED CURRENT : 1A C
AUX SUPPLY : 220V DC
BUSABR .DIFFERENTIAL RELAY

TYPE : P746(80TE)
9 P746 RATED CURRENT : 1A LOCAL/REMOTE SELECTOR SWITCH
MOUNTING : FLUSH 01 NO ALSTOM 21 SS1 1 NO. SWITRON
4 POLE,4 WAY WITHOUT OFF,75x75 SQ.MM,
INPUT : 24 INPUT 16A, 220V DC SUPPLY,LOCKBLE TYPE
OUTPUT : 24 OUTPUT
RATING : 220V DC PANEL/BCU SEELCTOR SWITCH
COMMUNICATION : IEC61850 22 SS2 1 POLE,2 WAY WITHOUT OFF 22.5MM DIA 1 NO. TEKNIC
16A, 220V DC SUPPLY
TNC BREAKER CONTROL SWITCH FOR SEMAPHORE INDICATOR,LED TYPE
PISTOL GRIP HANDLE RATING : 220V DC 1 NO.
23 SEM1 SIZE : 48 mm DIA, DEEPL(DAV)
TYPE : TNC SEM2-5 SIZE : 36 mm DIA, 4 NO.
BCS1-3 3NO. SWITRON
10 SIZE : 75x75mm.
RATING : 220V DC, 32A POWER SOCKET ANCHOR ROMA
24 PS 1 NO.
CONTROL CONTACT : 3C +3T 230VAC, 5/15A, ROUND & FLAT PIN UNIVERSAL TYPE

TRIP CIRCUIT SUPERVISION RELAY


25 195,295
D TYPE : MVAXM31 D
2 NO.'S ALSTOM
VOLT. RATING : 220VDC
CONTACTS : 1NO+2NC
CASE SIZE :4

PLUG IN RELAYS
26 R1-R4 4C/O,220VDC,7A WITH BASE
4 NO.'S FINDER

CUSTOMER : M/s. FLOVEL ENERGY PVT LTD. SCALE : NTS


Appd By : Manjunath.R
Description:
R03 ASBUILT DRAWING HB MR MR 13.01.2018 PROJECT NAME : NAM THI 2 HPP(2X4.0MW)
JOB No : VV 17-124 REV.No.
R02 AS PER CUSTOMER COMMENTS SN MR MR 08.12.2017 Chkd By : Manjunath.R CLIENT NAME : M/s. SONG DA 7.02 HYDROELECTRIC JOINT STOCK COMPANY
BILL OF MATERIAL 03
R01 AS PER CUSTOMER COMMENTS SN MR MR 05.12.2017 EQUIPMENT : BUS BAR PROTECTION PANEL DRG SUB No. : VV 17-124 E / BOM
Drawn By : Soumya
Rev Revision comment Prep Chkd Appd Date DATE : 18.10.2017 Sheet : 1 OF 1 in BOM Total pages: 48
1 2 3 4 5 6

You might also like